Model: HYXE-S01H
6. Model: HYXE-S01H
6.1 Safety summary
● Read this manual carefully prior to use of this product. and important considerations relating to safety, which
● Considerations stated in this section are given under must be complied with!
“ warning”. ● Keep this manual properly after reading for reference
Warning contains improper operations which may at any time in future.
cause serious consequence,
Installation - electrical works
● Please entrust your dealer or professional expert with installation.
Improper installation may cause leakage, electric shock, fire or fall of unit.
warning ● Electrical installation must be subject to proper qualification and certification, and must be carried
out by any qualified service provider.
Insufficient capacity of power supply or improper construction may cause electric shock or fire.
136
Model: HYXE-S01H
6.2 Features
Features
Mode Cool/Heat/Auto/Fan/Dry
Timer 24-hour Size: 120mm×70mm
Max. connectable indoor units:16
Error code / Parameter check/Auto test run/
Maintenance
Indoor&Outdoor PCB checking/Self diagnostic function LCD display
Touch button
Louver Louver setting//Mute
Fan speed 6
Temperature control ●
Air filter cleaning reminding ●
6.3 Installation
6.3.1 Installation Site Selection
Cable section 0.3 mm2 ≥ 0.75 mm2
Cable length 30 m 500 m
6.3.2 Component List
Name Appearance Quantity
Wired Remote Control 1
Screw
2
(M4×25mm)
Operation Manual 1
Installation manual 1
137
Model: HYXE-S01H
6.3.3 Description of the parts
To proceed with below instructions, all the displays are listed. It is different from actual running.
A Operation
① Mode Button ⑤ Start/Stop
② Temperature Down ⑥ Temperature Up
③ Fan ⑦ Louver
④ Timer ⑧ Quiet
B Screen
⑨ Blowing/Cooling/Dehumidification
Auto-heating mode
⑩ Key locking indication 21 System address code
11 Filter indication 22 System address specified on site
12 Defrosting indication 23 Service code
13 Centralized control indication
14 Spot inspection indication
15 rial operation indication
16 Blast direction indication
17 Mute indication
18 Blast volume indication
19 Timer status indication
20 Temperature/humidity indication
Considerations
● Touch key on remote controller gently with finger, and ● Press TIMER and MODE button for 3 seconds to
do not press keys with excessive force. switch between Celsius and Fahrenheit(OC or OF).
138
Model: HYXE-S01H
6.3.4 Dimension data
6.3.5 Installation space
Where the remote control is mounted
vertically with other remote controls,
the vertical mounting distance between
two adjacent remote controls shall be
approx. 50mm.
139
Model: HYXE-S01H
6.3.6 Installation procedure
[Installation instructions]
□ 1) Detach the main unit from the bottom plate by inserting a flat-head screwdriver into the two gaps
at lower side of remote control to unscrew it. Improper operations may cause damage to clasp
beside the gaps and fail assembly of the main unit, so be sure to take much care when detaching
it.
□ 2) Fix bottom plate and handle wires.
A. Lay wire along the groove made in the wall.
Fix with two screws provided in accessories.
Wire is threaded through the mounting hole
in lower enclosure and connected to the
terminal on board of main unit.
B. Lead wire out from the top or side of remote controller for installation.
(1) Made a lead-out port with pliers at the right or top side of remote
controller.
(2) Fix the bottom of the enclosure with screws provided.
(3) Connect and lay wire along the wiring channel provided in remote
controller.
140
Model: HYXE-S01H
6.4 Electrical wiring
Up to16 indoor units can be connected
Remote control indoor unit
1.25-3X
50 100
* Be sure to use wire of 0.3~0.75mm2 (in length not larger than 30m). In case of length larger than 30m, use
stranded wire of 1P -0. 75mm2 (in length not larger than 500m).
* Any interim cable between remote control and indoor unit must be laid at least 30cm away from power cable.
* In case of spacing less than 30cm, lay the interim cable in cable tray fabricated of metal earthed in D pattern,
or otherwise the equipment may fail due to interference to the power supply.
* In case that the remote control is used to control more than one indoor unit, set addresses of coolant system
Caution and indoor units properly, especially when it is used to control indoor units in more than one coolant system,
or otherwise signal transmit may fail.
* For instructions on wiring between remote control and indoor unit and setting of address of indoor units, refer
to the installation manual for indoor unit.
* In case of any gap between cable and thread-in hole of remote control, bind it with ethylene-based tape, to
keep out insects and avoid any failure caused thereby.
* Do not use it along with timer.
141
Model: HYXE-S01H
6.5 Checking procedure
★ [T.RUN] is displayed on the screen
★ Number of indoor units connected is displayed on the screen.
□1) Power On. set
Only one indoor unit can be connected
Start power supply to all indoor
In case that number of indoor units connected is indicated
Caution incorrectly, related unit may be in poor contact, or search for
It is normal when only part of LED indicators on address fails due to interference. You can switch off the power
screen turn on in the short time after power supply supply, perform the following inspection and ensure proper
is started. connection. (Do not handle mains switch frequently in a short
time (10 seconds)).
(1) The power supply to indoor unit is not switched on or power
□2) Please wait for about 3 minutes during address supply cable is in poor contact.
search. (The waiting duration may be 5 minutes (2) Cable between indoor units or to remote control is in poor
depending on specific model) contact.
(3) Rotary switch or DIP switch is set incorrectly.
Attention
□3) Start trial run When it is the case as shown at the left side, the
set equipment may be searching for address. You can exit
from trial operation and then retry.
□4) Exit from trial operation
(1) Not operation (2) In operation
Press and hold MODE + ▼ Start/Stop
Press MODE + ▼ and hold them for 3 for three seconds to exit Press this switch.
seconds to start trial operation.
142
Model: HYXE-S01H
6.6 Operation instruction
Basic
Operations
Cooling/heating/dehumidifying/auto/blasting
Heating function is available only in products furnished with heater.
Connect power supply.
For protection of compressor, power supply need be connected
prior to operation.
Preparation
Do not disconnect power supply during operation.
Press MODE to select an operation mode.
Mode
selection
● Auto operation mode requires additional settings. For more details consult your dealer.
● When a product with full refresh air heater is connected, only blasting mode is indicated. For more details consult your
dealer.
● Depending on the AC air duct connected, dehumidifying or auto-dehumidifying may be indicated on wire controller. For
more details consult your dealer.
● When DC air duct is connected, three dehumidifying modes may be indicated on wire controller: standard dehumidify
, dry dehumidifying , and strong dehumidifying . For more details consult your dealer.
143
Model: HYXE-S01H
Temperature Setting
Each press on 『 』 temperature rises by 1 ℃ .
Each press on 『 』 temperature falls by 1 ℃
Humidity Setting
● When connecting AC auto dehumidifier
Each press on 『 』, humidity rises by 1%.
(Available only in auto-dehumidifying mode on indoor unit with
automatic dehumidifying function)
3
Each press on 『 』, humidity falls by 1%.
● When dc air duct is connected, three dehumidifying modes may be indicated on wired controller: standard dehumidifying
, dry dehumidifying , and strong dehumidifying . For more details consult your dealer.
Fan Speed Setting
Press FAN to set fan speed.
Each press on FAN, the fan speed change in the following
sequence:
can only be exchanged when connect with the
unit having 6 levels fan speed.
● In dehumidifying mode, the default fan speed is low-speed which cannot be changed. Airflow can be changed only on
indoor unit with quick dehumidifying function.
144
Model: HYXE-S01H
Louver Setting
Considerations
● Louver will not be indicated for indoor unit without air deflector.
● Louver setting in indoor unit with four-way airflow.
Press to start operation.
Press LOU. to select louver.
Louver icon will keep flashing.
1
Each press , the stop position of louver changes in the following
sequence.
2
Each press , the stop position of louver changes in the following
sequence.
● Louver angle varies depending on different models of indoor unit. For more details refer to related operation manual.
● When louver keeps swinging, blade position as indicated on screen may be different from actual blade position,
When louver direction is fixed, please set louver based on the indication on screen.
● Upon pressing on the key, sometimes blades of louver may not stop immediately.
Quiet Setting
Considerations
● In indoor unit without mute function, mute mode will not be indicated. Mute function may be invalid
where some fan speeds are unavailable.
In operation status, press QUIET to set it to mute, and is
displayed in screen.
● When mute function is activated via wired controller, current fan speed will be displayed and cannot be regulated.
● When air conditioner is powered off, mute function will be deactivated.
● When operation mode is changed, mute function will be deactivated.
145
Model: HYXE-S01H
Timer Setting
Function & Action
● Air conditioner will be started from standby when the time set on timer has elapsed.
● Air conditioner will be shut down from operation when the time set on timer has elapsed.
When air conditioner is standby and scheduled start-up has not
been set, press TIMER to set schedule start-up, and icon
keeps flashing.
Timer
ON
Press . to increase time by 0.5 or 1 hour.
Press to decrease time by 0.5 or 1 hour.
Timer
ON
When air conditioner is standby and scheduled shutdown has
not been set, press TIMER to set schedule shutdown, and icon
keeps flashing.
Timer
OFF
Press to increase time by 0.5 or 1 hour.
Press to decrease time by 0.5 or 1 hour.
Timer
OFF
● Timing range is 0.5~24 hours. Upon completion, press TIMER to exit from current setting.
● Timing range is 0~10 hours, at a step of 0.5 hour.
● Timing range is 10-24 hours, at a step of 1 hour.
146
Model: HYXE-S01H
Operation Setting
Press key.
Operation indicator turns on and the Indoor unit starts up.
Running
Press key again.
Operation indicator turns off and the indoor unit stops.
Shut
down
● When heating operation stops, indoor unit will keep on blasting for about 2 minutes.
147
Model: HYXE-S01H
Other LCD Display
Status indication
● is activated.
When remote controller is disabled on centralized control, the
Centralized remote controller is unavailable for start-up, temperature/fan
speed/louver setting.
control
● is displayed when filter screen requires
cleaning.
Filter After cleaning the filter and hold FAN for 3 seconds to
clear the icon.
(1) Set
temperature
● is displayed
indication area
Where check mode is available, press and hold MODE
displays spot
Check + FAN for three seconds, 7-segment temperature icon
inspection item
area will display the last alarm code, or ”00" if no alarm
(2) Timer
has been given; press MODE to move to MODE 1.
indication area
displays specific
value of spot
Other Screen Indication
# T.RUN indication Prior to trial
Press and hold MODE for three seconds to start trial operation
operation setting, and T.RUN is activated on screen. setting, time
Test 7-segment temperature setting code indicates number for scheduled
run of indoor units connected to wired controller. Keep start-up will be
operation mode, fan speed and operation status prior to indicated as set.
trial operation setting.
148
Model: HYXE-S01H
6.7 Alarm indication
● Operation indicator keeps flashing.
Abnormal
● Indoor unit address, system and alarm code are indicated on screen.
● All indications will be cleared.
● In case of shutdown due to power failure, the equipment will not resume operation
Power off automatically even when power is resumed. In such case please restart the equipment.
● In case of instantaneous power failure for 2 seconds, the equipment will resume
operation automatically.
● All indications will be cleared and the equipment may stop operation due to protection
Disturb of microprocessor in response to interference. In such case please restart the
equipment.
149
Model: HYXE-S01H
6.8 Check mode
Check Menu
Display statuses of air conditioner.
(1) Set temperature
● Check mode
indication area
Where check mode is available, press and hold displays spot
MODE + FAN for three seconds, 7-segment inspection item, and
temperature indication area will display the last the initial display is
alarm code, or "00" if no alarm has been given; bl.
short press MODE to move to spot inspection (2) Timer indication
mode 1, and select items by using area displays
[▼] [▲]. specific value of
spot inspection item. Press and hold MODE and
The initial display FAN for three second.
is set temperature
value.
150