PVB Outdoor Vacuum Circuit Breaker Guide
PVB Outdoor Vacuum Circuit Breaker Guide
PRODUCT BROCHURE
                                 —
                                 Contents
—
Introduction
      Overview                                                knowledge and modular manufacturing techinique   Product characteristic                                   • Compact design provides easy installation
      PVB outdoor vacuum circuit breaker (hereinafter         allow PVB outdoor circuit breaker to meet any    PVB is perfect synthesis of ABB's affirmed               • 10,000 full load operation
      referred to PVB) is pole mounted switch equipment       need and schedule.PVB outdoor vacuum circuit     technology in designing and constructing vacuum          • Parts and components are recyclable
      of ABB vacuum circuit breaker series, Rated             breakers can meet various protections            interrupter and HCEP with highly molded research         • No oil or gas insulation=environmentally
      voltage is 12 kV, applied to the overhead lines.        requirements under the situation with power      and manufacturing technology, and also is                  friendly product
                                                              electricity, including making and breaking       combination of advanced EL operating mechanism.          • Plastic parts are manufactured according to
      ABB's PVB is one of the most flexible devices for       short-circuit current. PVB has a very good                                                                  standard ISO 11469 to ensure product was
      smart grid application, and also provides maximum       performance on frequent operation occasions,     Both the vacuum interrupter and poles                      easily separated at the end of its life time
      functionality and mounting flexibility suitable for     and PVB can fully meet the requirements of       encapsulated in HCEP insulation material are
      a variety of applications. This is especially true of   automatic reclosing with high reliability and    manufactured by German CalorEmag Company                 Flexible configuration
      our feeder automation product, where years of           electrical service lifetime.                     which is famous as manufacturer of ABB vacuum            PVB has different flexible configurations according
                                                                                                               interrupter.                                             to customer different requirements, such as
                                                                                                                                                                        configuration with visible break.
                                                                                                               Breaking short-circuit current in the vacuum PVB
                                                                                                               does not require an interrupting and insulating          Main additional features of PVB integrated
                                                                                                               medium. In fact, the interrupter does not contain        disconnector product are:
                                                                                                               ignitable material.                                      • Outside visible isolated gap
                                                                                                                                                                        • 3 phase mechanical operation disconnector,
                                                                                                               In any case, on separation of the contacts,an              reliable mechanical interlocking with the PVB
                                                                                                               electric arc is generated made up exclusively of           circuit breaker
                                                                                                               molten and vaporized contact material. The electric      • Disconnector with excellent performance and
                                                                                                               arc supported by the external energy only remains          high technical ratings
                                                                                                               until the current is cancelled by passing through
                                                                                                               natural zero. At that instant, the rapid reduction       Standards
                                                                                                               in the load density carried and the fast condensation    • IEC 60694-2002 Common specifications for
                                                                                                               of the metallic vapour lead to extremely rapid             high-voltage switchgear and controlgear
                                                                                                               recovery of the dielectric properties. The vacuum          standards
                                                                                                               interrupter therefore recovers the insulating capacity   • IEC 62271-100 High-voltage switchgear and
                                                                                                               which withstand the transient recovery voltage,            controlgear - Part 100: High-voltage
                                                                                                               definitively the arc is extinguished.                      alternating-current circuit-breakers
                                                                                                                                                                        • GB/T 11022 Common specifications for
                                                                                                               Since high dielectric strength can be reached in           high-voltage switchgear and controlgear
                                                                                                               vacuum, even with minimum distances, interruption          standards
                                                                                                               of the circuit is also guaranteed when separation        • GB 1984 High-voltage alternating-current
                                                                                                               of the contacts takes place a few milliseconds             circuit-breakers
                                                                                                               before passage of the current through natural zero.      • GB/T 311.1 Insulation coordination for high voltage
                                                                                                                                                                          transmission and distribution equipment
                                                                                                               The special geometry of the contacts and the             • DL/T 402 Specification of high-voltage
                                                                                                               material used, together with the limited duration          alternating-current circuit-breakers
                                                                                                               and low voltage of the arc guarantee minimum             • DL/T 403 HV vacuum circuit-breaker for rated
                                                                                                               contact wear and long life. Furthermore, the vacuum        voltage 12 kV to 40.5 kV
                                                                                                               prevents their oxidation and contamination.              • DL/T 593 Common specifications for high-voltage
                                                                                                                                                                          switchgear and controlgear standards
                                                                                                               Features                                                 • DL/T 813 Specification for 12 kV H. V.
                                                                                                               • Vacuum interruption technique                            alternating current automatic circuit recloser
                                                                                                               • Modular design for easy service ability in the field   • GB 1985 High-voltage alternating-current
                                                                                                               • The contacts in vacuum protect against                   disconnectors and earthing switches
                                                                                                                 oxidation and contamination                            • IEC 62271-102 High-voltage switchgear and
                                                                                                               • Suitable for different climatic conditions               controlgear - Part 102: Alternating-current
                                                                                                               • Low operating force                                      disconnectors and earthing switches
                                                                                                               • Spring operation mechanism equipped with
                                                                                                                 mechanical anti-pump device supplied as
                                                                                                                 standard
6     PVB outdoor vacuum circuit breaker                                                                  Technical parameters                                                                                                7
—                                                                    —
Introduction                                                         Technical parameters
                                                                      Circuit breaker
      Seismic intensity                                   9 Degree                      Short time withstand current                                                                     kA        20
      High limit:                                                                       Withstand duration                                                                               s         4
                                                                                        Peak withstand current (peak)                                                                    kA        50
      horizontal acceleration                                                           Ice covering                                                                                     mm        10
      Simulated earthquake waves                          0.50 g                        Circuit breaker level                                                                                      C2-E2-M2*
      Sine resonate waves                                 0.30 g                        Rated operating sequence                                                                                   O-0.3 s-CO-180 s (15 s)-CO**
                                                                                        Mechanical mechanism type                                                                                  Spring mechanism
                                                                                        Dimension                                                                                        mm        1028x856x512 (HXWXD)
      Special condition
      Application in special condition, please contact                                  Weight                                                                                           kg        110 (Incl. CT)
      and consult with manufacturer in advance.                                         Pollution level                                                                                            IV
                                                                                        Ingress degree                                                                                             IPX6
      Generally, the following special condition can be
                                                                                        Mechanical endurance (number of close-open operations)                                           n         10,000
      considered by manufacturer:
      • Installation altitude exceeds 1000 m                                            Power frequency withstand voltage, 50/60 sec/1 min          To earth and between phases          kV        48
      • External insulation can be decreased                                                                                                        Across the isolating distance        kV        54.5
      • Choose the products which can be used in                                        Lightning impulse withstand voltage                         To earth and between phases          kV        85
        altiplano area
                                                                      Disconnector
                                                                                                                                                    Across the isolating distance        kV        96
      • Installed in higher ambient temperature
                                                                                        Short time withstand current                                                                     kA        20
      • Decrease continuous operating current PVB
                                                                                        Withstand duration                                                                               s         4
                                                                                        Peak withstand current (peak)                                                                    kA        50
                                                                                        Ice breaking                                                                                     mm        10
                                                                                        Dimension                                                                                        mm        1093x1015x542 (HXWXD)***
                                                                                        Pollution level                                                                                            IV
                                                                                        Mechanical endurance                                                                             CO        3000
                                                                     * According to the definition of standard: GB 1984-2003                 demonstrated by specific type tests(circuit-breaker with
                                                                       High-voltage alternating-current circuit-breakers, C2-E2-M2           extended mechanical endurance, mechanically type tested for
                                                                       circuit breaker means:                                                10,000 operations).
                                                                         Circuit-Breaker Class C2: Circuit-breaker with very low         NOTE: A combination of the different classes of circuit-breakers
                                                                         probability of restrike during capacitive current breaking as         with regard to electrical endurance, mechanical
                                                                         demonstrated by specific type test.                                   endurance and the restrike probability during capacitive
                                                                                                                                               current breaking is possible. For the designation of
                                                                         Circuit-Breaker Class E2: Circuit-breaker designed so as not          these circuit-breakers the notation of the different
                                                                         to require maintenance of the interrupting parts of the               classes are combined following an alphabetical order, for
                                                                         main circuit during its expected operation life, and only             example C1-M2.
                                                                         minimal maintenance of its other parts(circuit-breaker
                                                                         with extended electrical endurance).                            ** Motor operating PVB with smart controllers can carry out 4-5
                                                                                                                                            reclosing sequences.
                                                                         Circuit-Breaker Class M2: Frequently operated                   *** The dimension is the overall dimension with CB.
                                                                         circuit-breaker for special service requirements and            **** Rated current 1250 A is only for the circuit-breakers.
                                                                         designed so as to require only limited maintenance as
8     PVB outdoor vacuum circuit breaker                                                                         Structure and functions                                                                                                                      9
—
Structure and functions
      PVB structure                                         Following contact separation, single melting         An electromagnetic force is self-generated and                                                                         1 Stem/terminal
      The poles of PVB are capsulated by insulated          points form on the surface of the cathode,           this acts tangentially, causing rapid arc rotation                                                                     2 Twist protection
      material which is Hydrophobic Cycloaliphatic          producing metal vapours which support the arc.       around the contact axis.                                                                                               3 Bellows
      Epoxy (HCEP) and the poles are installed                                                                                                                                                                                          4 Interrupter housing
      vertically on the mechanism tank (see rightside       The diffuse vacuum arc is characterised by           This means the arc is forced to rotate and to                                                                          5 Shield
      picture). Poles casted by HCEP canminimize            expansion over the contact surface and by an         involve a wider surface than that of a fixed                                                                           6 Ceramic insulator
      partial discharge and mechanicaldamage. When          even distribution of the thermal stress.             contracted arc.                                                                                                        7 Shield
      PVB is closed, current path of the main circuit is:                                                                                                                                                                               8 Contacts
      upper teminal→static contact in the vacuum            At the rated current of the vacuum interrupter,      Apart from minimising thermal stress on the                                                                            9 Terminal
      interrupter→dynamic contact in the vacuum             the electric arc is always of the diffuse type.      contacts, all this makes contact erosion negligible                                                                    10 Interrupter housing
      interrupter→lowerterminal→external circuit.           Contact erosion is negligible, and the number of     and, above all, allows the interruption process
                                                            current interruptions very high.                     even with very high short-circuits.
      Interruption principle of ABB interrupters
      Vacuum Interrupter                                    As the interrupted current value increases           ABB vacuum interrupters are zero-current
      ABB has been developing and manufacturing             (above the rated value), the electric arc tends to   interrupters and are free of any re-striking.
      vacuum interrupters since the early 1980 s.           be transformed from the diffuse into the
      Worldwide, more than two million ABB vacuum           contracted type, due to the Hall effect.             Rapid reduction in the current charge and rapid
      interrupters are in service. ABB's vacuum                                                                  condensation of the metal vapours simultaneously
      interrupter facility uses the latest technologies     Starting at the anode, the arc contracts and as      with the zero-current, means maximum dielectric
      in high quality mass production to produce the        the current rises further it tends to become         strength can be restored between the interrupter
      next generation of vacuum interrupters. This          sharply defined.                                     contacts within microseconds.
      new generation vacuum interrupter is robust for
      universal application.                                Near the area involved there is an increase in
                                                            temperature with consequent thermal stress on
      Advantages                                            the contact. To prevent overheating and erosion
      • Maximum reliability                                 of the contacts, the arc is kept rotating. With
      • Superior contact wear                               arc rotation it becomes similar to a moving
      • Long life: 10,000 full load operations              conductor which the current passes through.
      • Minimal maintenance
      • Environmentally friendly                            The spiral geometry of ABB vacuum interrupter
                                                            contacts
      In a vacuum interrupter, separation of                The special geometry of the spiral contacts
      current-carrying contacts initiates the vacuum        generates a radial magnetic field in all areas of
      arc and this is maintained until the current zero     the arc column, concentrated over the contact
      and can be influenced by magnetic fields.             circumferences.                                         Diffuse arc.                        Contraction         Contraction over
                                                                                                                                                         over anode.          anode and
                                                                                                                                                                               cathode.
      Diffuse or contracted vacuum arcs
                                                                                                                      Schematic diagram of the transition from a diffuse
                                                                                                                      arc to a contracted arc in a vacuum interrupter.
Terminal
                                                                                                                                                      Short-circuit
                                                                                               CT                                                     current
                                                                                                                          Current, Voltage
                                                                                               Terminal
                                                                                                                                                                           Arc voltage
                                     Main circuit                                              Pole                                          System voltage
                                     Terminal                                                                                                                               Short-circuit current
                                                                                                                                                                            interruption
                                                                                                                                                              Contact                               Time
                                                                                                                                                              separation
                                                                                               Open and
                                     Operation handle                                                                                                                              Recovery voltage
                                                                                               Close Handle                                                                        (system frequency)
                                                                                                                                                                               Transient recovery
                                                                                               Charging Rod                                                                    (TRV) (high frequency)      Radial magnetic field contact arrangement with a
                                                                                               Tank                                                                                                        rotating vacuum arc.
                                     Mounting bracket                                                            Development of current and voltage trends
                                                                                                                 during a single phase vacuum interruption process.
10    PVB outdoor vacuum circuit breaker                                                                              Structure and functions                                                                               11
—
Structure and functions
      Solid-encapsulated pole                                     Characteristic of insulating material               Operating mechanism                                   Manual operating PVB
      PVB's pole assemblies are constructed of UV                 HCEP is light, and anti-aging, so it can meet the   PVB uses EL-mechanical operation, and the             Spring operating mechanism of PVB can be
      resistant HCEP encapsulating material and are               requirements of using in outdoor severe             optional secondary accessories can be installed       charged manually via charging rod simply and
      design to provide a rated 10,000 full load                  environment and enhance anti-corrosion during       easily and quickly, and EL mechanical operation       reliably. After the spring operating mechanism
      operations without maintenance. Meanwhile                   high-pollution environment of equipment.            is spring operated mechanism.                         being charged, PVB can be closed via operation
      HECP can supply protection for vacuum                                                                                                                                 handle, if PVB is closed, PVB can be opened by
      interrupter to decrease the effect of dust and                                                                  EL-mechanical operating mechanism                     operation handle without charging the spring
      humidity, and main contacts will enduringly be                                                                  The mechanical operating mechanism of PVB             operating mechanism again!
      encapsulated in vacuum condition through arc                                                                    circuit-breaker is of simple concept and use,
      extinguished chamber which constitutes                                                                          and can be customized with a wide range of            Protection functions of manual operating PVB
      vacuum interrupter unit.                                                                                        easily and rapidly installed accessories.             Protection elements of manual operating PVB
                                                                                                                                                                            are CT, MFC protection control device and
                                                                                                                      This simplicity translates into greater reliability   overcurrent release. When the overhead lines
                                                                                                                      of circuit breaker. The EL operating mechanism        have overloaded current or fault current, CT will
                                                                                                                      is of the stored energy type with the                 sense the current and secondary current of CT
                                                                                                                      anti-pumping device mounted as standard to            will increase accordingly, thus the current into
                                                                                                                      prevent incorrect operations.                         the MFC protection control will over the setting
                                                                                                                                                                            value to drive the overcurrent release to trip.
                                                                                                                      Position of open or closed, and charging status
                                                                                                                      are visible from the indication windows which
                                                                                                                      are at the bottom of PVB tank (please find the
                                                                                                                      dimension of the windows in detail shown
                                                                                                                      below).
—
Structure and functions
Auxiliary switch
                                                                                                                        Parameters                        Values
                                                                                                                        Rated voltage Un                  DC220 V
                                                                                                                        Rated frequency                   50 Hz
                                                                                                                        Rated current                     3A
Auxiliary switch
—
Structure and functions
      To fulfill more complicated protection functions     Indicator lights                                   Front mounted RS-232 port                            Metering
      settings, SCADA, and DA functions, PCD control       • Continual self-checking with status indication   • Independent from rear mounted RS-232 port          • Meters current and voltage (with PT voltage
      unit and feeder relay REF 615 can be configured      • Pickup and lockout indication                    • Easy download and upload of data on-site             input supplied) to ± 1% accuracies
      in control cabinet.                                                                                       using WinPCD                                       • Measures kW and kVAR, power factor, demand
                                                           Front panel pushbuttons                                                                                   Watts and VARs, and frequency to ± 2% accuracy
      Motor operating PVB with Intelligent                 • Up to six protection groups available            Separate open and close pushbuttons                  • User-selectable load profile data sampling 5,
      Protection Functions--PCD Control Device             • Front panel button to set Alt 1 settings         • Separate indicator light for easier viewing          15, 30, 60 minute time internal which will
      An intelligent control device has functions of       • Ground blocked, remote blocked, and reclose      • ANSI or IEC coloring for individual practices        contain 13.3, 40, 80 or 160 days of information
      protection, monitoring, and controlling.               blocked pushbuttons                                                                                   • All data can be downloaded on-site or
                                                           • Sensitive earth fault (SEF) available for        Control cabinet                                        remotely through communications interface
      Local human-machine interface                          ungrounded or Delta CT applications              • Stainless steel cabinet, NEMA 3R with drip         • Includes assignable phases for easy phase
      • Enlarged LCD (1"x5") with large characters         • PROG 1 battery test load feature preprogrammed     shied                                                selection and selectable power flow
        (two lines of 20 characters)                       • User programmable LEDs for alarms, additional    • Battery provides full operational capability for
      • Simple menu-driven programming using large           targets, etc                                       to 48 hours (15-27 kV) /24 hours (38 kV)           Protective functions
        six- button keypad                                 • Counters button for easy access to number of     • Ample space for mounting communications            • Phase time overcurrent protection (51P)
      • Backlit display indicates metering values, fault     operations and overcurrent trip information        equipment                                          • Phase instantaneous overcurrent protection
        information and location                                                                              • Three-point latching with padlockable handle         (50P-1)
      • Temperature compensated                            Hot line tagging feature                           • Vented design                                      • Two definite time overcurrent settings (50P-2,
      • Battery test function included                     • On faceplate for simpler and safer operation                                                            50P-3)
                                                           • Can be mapped for multiple applications          Communication & I/O ports                            • Ground overcurrent protection (51N)
                                                                                                              • Isolated RS-232 and RS-485 ports                   • Ground instantaneous overcurrent protection
                                                                                                              • ST fiber optic ports                                 (50N-1)
                                                                                                              • Modbus ASCII and RTU, and DNP 3.0TM                • Two definite time ground overcurrent settings
                                                                                                                protocols included with all units                    (50N-2, 50N-3)
                                                                                                              • DNP 3.0TM is compliant to Level 2                  • Negative sequence overcurrent protection (46)
                                                                                                              • IEC 60870-5-101                                    • Two independent steps for load shed,
                                                                                                              • Programmable I/O ports: 6 inputs, 4 outputs          restoration, and over-frequency (81S, 81R, 81O)
                                                                                                                available with UPS                                 • Undervoltage and overvoltage control and
                                                                                                              • Programmable I/O ports: 10 inputs, 7 outputs         alarm (27/59)
                                                                                                                available with PS                                  • Phase and ground directional overcurrent
                                                                                                                                                                     protection (67P, 67N)
                                                                                                              Oscillographic data                                  • Sensitive Earth Fault protection with directional
                                                                                                              • Storage capacity of 64 cycles of monitored           features (optional)
                                                                                                                waveform data at 32 samples per cycle              • Up to four reclose cycles (define a recloser cycle
                                                                                                              • All data can be downloaded on-site or                79-1→79-5) close four times / trip five Adaptive
                                                                                                                remotely through communication interfaces            reclosing shots: each reclose sequence allows
                                                                                                                                                                     independent programming of protective
                                                                                                              Fault recording                                        functions
                                                                                                              • Records last 128 operations of:                    • Available with up to 38 recloser curves, nine ANSI
                                                                                                              • Phase and ground fault amperes                       curves, four IEC curves and three user
                                                                                                              • Phase and ground voltage                           • Programmable curves
                                                                                                              • Isolates the faulted section
                                                                                                              • Reclose time- Distance to fault
                                                                                                              • Estimated fault resistance
                                                                                                              • Time stamp
                                                                                                              • Stores 1024 operation records
16    PVB outdoor vacuum circuit breaker                                                                                             Structure and functions                                                                            17
—
Structure and functions
      Motor operating PVB with Intelligent               • The REF615 is the one of most powerful,         Standard configuration functionality                     Overcurrent and directional earth-   Overcurrent and non- directional
      protection functions--REF615 relay                   advanced and simplest protection relay,                                                                           fault protection                  earth-fault protection
      REF 615 is a member of ABB's Relion® family and      perfectly offering time and instantaneous
      a part of its 615 protection and control product     overcurrent, negative sequence overcurrent,                                                               Std. conf. A        Std. conf. B     Std. conf. C        Std. conf. D
      series. The 615 series IEDs are characterized by     and voltage metering and protection.The relay   Protection
      their compactness and withdrawable design.           also features optional high impedance fault     Three-phase non-directional overcurrent, low-set stage        ●                    ●                ●                  ●
      Engineered from ground up, the 615 series has        (HIZ) and ungrounded distribution systems,      Three-phase non-directional overcurrent,                      ●                    ●                ●                  ●
      been designed to unleash the full protection of      and the replay incorporates a flexible
                                                                                                           high-set stage, instance 1
      the IEC 61850 standard for communication and         three-phase multi-shot auto-reclose function
      interoperatability of substation automation          for automatic restoration in temporary faults   Three-phase non-directional overcurrent,                      ●                    ●                ●                  ●
      devices.                                             on overhead lines                               high-set stage, instance 2
                                                         • I/O extension model, has maximum 17 BI/O, 13    Three-phase non-directional overcurrent,                      ●                    ●                ●                  ●
      The REF615 provides main protection for overhead     SI/O
                                                                                                           instantaneous stage
      lines, cable feeders, and busbar systems of        • Drawout design
      distribution substations. It can be applied for    • Six setting groups                              Directional earth-fault, low-set stage, instance 1            ●                    ●                ●                  ●
      protection and control of grounded and             • High-speed (<1 ms) output                       Directional earth-fault, low-set stage, instance 2            ●                    ●                ●                  ●
      un-grounded distribution systems. Flexible         • Fault recording: higher sample frequency,       Directional earth-fault, high-set stage                       ●                    ●                ●                  ●
      order coding allows for choosing current-only or     larger storage capacity can record 12           Non-directional earth-fault, high-set stage                   ●                    ●                ●                  ●
      current-and-voltage configurations to best fit       analogue signals and 64 digital signals
                                                                                                           (cross country earth-fault)
      your application needs.                            • HMI: Large, and easy to read LCD screen
                                                         • Environmentally friendly design with RoHS       Transient/intermittent earth-fault                            ●                    ●                ●                  ●
                                                           compliance                                      Non-directional earth-fault, low-set stage                     -                   -                ●                  ●
                                                                                                           Non-directional earth-fault, high-set stage                    -                   -                ●                  ●
                                                                                                           Non-directional earth-fault,                                   -                   -                ●                  ●
                                                                                                           instantaneous stage                                            -                   -                ●                  ●
                                                                                                           Non-directional sensitive earth-fault
                                                                                                           Negative-sequence overcurrent, instance 1                     ●                    ●                ●                  ●
                                                                                                           Negative-sequence overcurrent, instance 2                     ●                    ●                ●                  ●
                                                                                                           Phase discontinuity                                           ●                    ●                ●                  ●
                                                                                                           Thermal overload                                              ●                    ●                ●                  ●
                                                                                                           Circuit breaker failure protection                            ●                    ●                ●                  ●
                                                                                                           Three-phase inrush current detection                          ●                    ●                ●                  ●
                                                                                                           Arc protection with three sensors                             ○                    ○                ○                  ○
                                                                                                           Control
                                                                                                           Circuit breaker control with basic interlocking 1)            ●                    ●                ●                  ●
                                                                                                           Circuit breaker control with extended interlocking 2)          -                   ●                -                   -
                                                                                                           Auto-reclosing of one circuit breaker                         ○                    ○                ○                  ○
                                                                                                           Supervision and monitoring                                     -                   ●                -                  ●
                                                                                                           Circuit breaker condition monitoring                          ●                    ●                ●                  ●
                                                                                                           Trip-circuit supervision of two trip circuits                 ●                    ●                ●                  ●
                                                                                                           Measurement
                                                                                                           Transient disturbance recorder                                ●                    ●                ●                  ●
                                                                                                           Three-phase current measurement                               ●                    ●                ●                  ●
                                                                                                           Current sequence components                                   ●                    ●                ●                  ●
                                                                                                           Residual current measurement                                  ●                    ●                ●                  ●
                                                                                                           Residual voltage measurement                                  ●                    ●                -                   -
                                                                                                           ● = Included, ○ = Optional at the time of the order
18     PVB outdoor vacuum circuit breaker                                                                                                                                                          Electrical circuit diagram                                                        19
—
Electrical circuit diagram
Manual operating PVB Motor operating PVB with simple control cabinet
                                                                                                                                                                                                                                                                                A
                                                                                                                                                                                                                                                TR1
                                                                                                                                                                                                                                TR2
MO3
                                                                                                                                                                                                                                                                                B
                                                                                                                                                                                       TR1
                                                                                                                                                       TR2
                                                                                                                                                                                                                                                                                C
                                                                                                                                                                                             MO3
                                                                                                                                               5
                                                                                                                                                                                                                                                                                BV
                                                                                                                                                                                                                                                                           W2
                                                                                                                                                                                                                                                            4
                                                                                                                                                                                                                                                                3
                                                                                                                                                                                                                                                                    2
                                                                                                                                                                                                                                                                    1
                                                                                                                                                                                 8
                                                                                                                                                   9
       Rectifier Bridge
                          Rectifier Bridge
                                             MFC Protection Control Device
                                                                             Overcurrent Release
                                                                                                   Current Transformer
                                                                                                                         Current Transformer
                                                                                                                                                                                                                                                                    L1N
                                                                                                                                                                                                                                                                          L1L
                                                                                                                                                                 6
                                                                                                                                                                            :
                                                                                                                                                                     BC-C
                                                                                                                                                                                BC-A
                                                                                                                                                             4
—
Electrical circuit diagram
       Motor operating PVB with smart control cabinet (PCD)   Motor operating PVB with smart control cabinet (REF 615)
22    PVB outdoor vacuum circuit breaker                                                     Overall dimension and mounting modes                                    23
—
Overall dimension and mounting modes
280 280
280 280
                                                                                                                                                                   1098
                                                        1028
775 D
400 244
720 40
                                                                                                                                                           C
                                                        4-M12/Installing holes
                                                  145
                                                  43
                                                                                                                           C                         D
                                                                                             Type A CT                     800                       800
                                                                                             Type B CT                     855                       855
         Charging indicator                 Open and close indicator
                                                                                             Note:
                                                                                             Type A CT includes CT ratio: 400/5, 630/5, 630-400/5;
                                                                                             Type B CT includes CT ratio: 200/5, 400-200/5.
24    PVB outdoor vacuum circuit breaker                                                                           Overall dimension and mounting modes                                          25
—
Overall dimension and mounting modes
                                                                                                                   Mounting mode 5:
                                                                                                                   Single pole side installation (i n c l u d e s:
                                                                                                                   clamp and bracket, pole diameter:
                                                                                                                   180 mm-250 mm)
722 2- 17
                                                                                                                                                                              22
                                                                                                                                                                                         6-17x35
                                                                                                                                                                     125
                                                                                                                                                                     79 100
                                                                                                                                                                                         4- 14
      *Mounting mode 3:
                                                                         *Mounting mode 4:
      Double pole rectangular bracket (side)
                                                                         Tower installation                        Mounting mode 6:
                                                                                                                   Single pole triangular bracket installation                     723
                                                                                                                   (includes: Clamp and Bracket, pole
      * For mounting mode 2/mounting mode 3/mounting mode                                                          diameter: 180 mm-250 mm)
        4, only rectangular bracket is supplied, if further support is
        needed, contact us.
26                           PVB outdoor vacuum circuit breaker                                                                                                                           Circuit-breaker selection and ordering                                                             27
—
Circuit-breaker selection and ordering
                                                                                                     12          : 12 m
                                                                                                                                                                Rated voltage: 12 kV                                                         12
                                                                                                     xx          : Customer specify (<15 m)                     Rated current: 630 A/1250 A                                               06/12
                                                                                                                                                                Rated short-circuit breaking current: 20 kA                                 20
                                                                                                                 : None
                                                                                                                                                                Carbon steel HV cabinet (default)
                                                                     Control cabinet:                BCU-A       : Simple control cabinet
                                                                                                                                                                Stainless steel HV cabinet                                                              S
                                                                                                     BCU-B       : Intelligent control cabinet (With PCD)
                                                                                                     BCU-C       : Intelligent control cabinet (With REF 615)   Manual operating mechanism                                                                  H
                                                                                                                                                                Motor operating mechanism                                                                   M
                                                                     Disconnector                    D           : Integrated with disconector                  CT ratio: 630/5                                                                                 60
                                                                                                                 : Without disconnector (default)               Ratio: 400/5                                                                                    40
                                                                                                                                                                Ratio: 200/5                                                                                    20
                                                                                                                                                                Ratio: 630-400/5                                                                                64
                                                                     Control voltage:                A1          : AC110 V                                      Ratio: 400-200/5                                                                                42
                                                                                                     A2          : AC220 V                                      Ratio: 1250/5                                                                                   55
                                                                                                                                                                                                                                                                O
                                                                                                     D1          : DC110 V                                      Other CT ratio, please comment requirement:
                                                                                                     D2          : DC220 V                                      Control   voltage: AC110 V                                                                             A1
                                                                                                     D3          : DC24 V                                       Control   voltage: AC220 V                                                                             A2
                                                                                                                                                                Control   voltage: DC110 V                                                                             D1
                                                                                                     D4          : DC48 V
                                                                                                                                                                Control   voltage: DC220 V                                                                             D2
                                                                     CT ratio:                       60          : 630/5 A                                      Control   voltage: DC24 V                                                                              D3
                                                                                                                                                                Control   voltage: DC48 V                                                                              D4
                                                                                                     40          : 400/5 A
                                                                                                     20          : 200/5 A                                      Without disconnector (default)
                                                                                                     64          : 630-400/5 A                                  Integrated with disconector                                                                                 D
                                                                                                     42          : 400-200/5 A
                                                                                                     55          : 1250/5 A                                     No control dabinet
                                                                                                     O           : Others                                       Simple control cabinet                                                                                          BCU-A
                                                                                                                                                                Intelligent control cabinet (With PCD)                                                                          BCU-B
                                                                     Operating mechanism:            H           : Manual
                                                                                                                                                                Intelligent control cabinet (With REF 615)                                                                      BCU-C
                                                                                                     M           : Motor
                                                                     HV cabinet                                  : Carbon Steel (Default)                       Control   cable   length: 6 m                                                                                           06
                                                                                                     S           : Stainless Steet                              Control   cable   length: 9 m                                                                                           09
                                                                                                                                                                Control   cable   length: 12 m                                                                                          12
                                                                                                                                                                Control   cable   length: (<15 m)                                                                                       xx
                                                                     12.06.20: *                     Rated voltage                    : 12 kV
                                                                                                     Rated current                    : 630 A                   2 CT parameters:      □ Phase A, C
                                                                                                     Rated breaking current           : 20 kA                                         □ Phase A, B, C (Remark: Standard PVB with 2 pcs CT respectively on phase A and C)
                                                                                                                                                                3 Mounting modes (mounting bracket suitable for pole whose diameter is 180 mm~250 mm)
                                                                     PVB:                            Outdoor vacuum circuit breaker                               □ Mounting mode 1 □ Mounting mode 2 □ Mounting mode 3 □ Mounting mode 4 □Mounting mode 5
                                                                                                                                                                  □ Mounting mode 6 □ Others (Require detail drawings from customer side):
*: 12.06.20 is for rated current 630 A, if the rated current is 1250 A, the selection is 12.12.20                                                               4 PT Control cable:   □6m       □9m       □ 12 m    □ m customer specify (<15 m)
                                                                                                                                                                5 Transformer (JDZW-1010 kV/0.1 kV/0.22 kV):
Type number description                                                                      HV cabinet: carbon steel                                                                 □ None □ 1 PC         □ 2 PCS □ 3 PCS
E.G: PVB/12.06.20-M40-A1/BCU-A-06                                                            Operating mechanism: motor                                         6 Configurated with MFC protection control device □ YES     □ NO
Description:                                                                                 CT tatio: 400/5 A
PVB: outdoor pole mounted vacuum circuit breaker                                             Control voltage: AC110 V
                                                                                             Disconnector: without disconnector                                 Ordering company:
Rated voltage: 12 kV
Rated current: 630 A                                                                         Control cabinet: simple control cabinet                            Manufacturer_ABB Xiamen Electrical Controlgear Co.,Ltd.               Signature:
Short-circuit breaking current: 20 kA                                                        Control cable length: 6 m                                                                                                                Signature:
                                                                                                                                                                                                                                      Year: Month: Day:
—
ABB Xiamen Switchgear Co., Ltd.
No. 885, FangShanXiEr Road, Xiang’an District,
Xiamen, Fujian, 361101
Tel: 0592 602 6033
Fax: 0592 603 0505
www.abb.com
9AKK105713A0059_EN_REV C 022021