PRODUCT BROCHURE

PVB outdoor vacuum circuit breaker

• Global proven reputation


• Accountable solution for safety and
reliability
• Wide range offering, easy business
and convenient installation


2 PVB outdoor vacuum circuit breaker Contents 3


Contents

04-06 Introduction 22-25 Overall dimension and mounting modes


04 Overview 22-23 Dimension
05 Product characteristic 24 Mounting modes
05 Standard 25 Mounting modes and rectangular bracket
06 Application condition
26-27 Circuit-breaker selection and ordering
07 Technical parameters 26 Selection
07 PVB technical parameters 27 Ordering requirements

08-17 Structure and functions


08 PVB structure
08-09 Interruption principle of ABB interrupter
10 Solid-encapsulated pole
11 Operating mechanism
11 Protection functions of manual operating
PVB
12-13 Motor operating PVB with simple
protection functions
14-15 Motor operating PVB with intelligent
protection functions--PCD Control Device
16-17 Motor operating PVB with intelligent
protection functions-- REF615 relay

18 Electrical circuit diagram


18 Manual operating PVB
19 Motor operating PVB with simple control
cabinet
20 Motor operating PVB with smart control
cabinet (PCD)
21 Motor operating PVB with smart control
cabinet (REF615)
4 PVB outdoor vacuum circuit breaker Introduction 5


Introduction

Overview knowledge and modular manufacturing techinique Product characteristic • Compact design provides easy installation
PVB outdoor vacuum circuit breaker (hereinafter allow PVB outdoor circuit breaker to meet any PVB is perfect synthesis of ABB's affirmed • 10,000 full load operation
referred to PVB) is pole mounted switch equipment need and schedule.PVB outdoor vacuum circuit technology in designing and constructing vacuum • Parts and components are recyclable
of ABB vacuum circuit breaker series, Rated breakers can meet various protections interrupter and HCEP with highly molded research • No oil or gas insulation=environmentally
voltage is 12 kV, applied to the overhead lines. requirements under the situation with power and manufacturing technology, and also is friendly product
electricity, including making and breaking combination of advanced EL operating mechanism. • Plastic parts are manufactured according to
ABB's PVB is one of the most flexible devices for short-circuit current. PVB has a very good standard ISO 11469 to ensure product was
smart grid application, and also provides maximum performance on frequent operation occasions, Both the vacuum interrupter and poles easily separated at the end of its life time
functionality and mounting flexibility suitable for and PVB can fully meet the requirements of encapsulated in HCEP insulation material are
a variety of applications. This is especially true of automatic reclosing with high reliability and manufactured by German CalorEmag Company Flexible configuration
our feeder automation product, where years of electrical service lifetime. which is famous as manufacturer of ABB vacuum PVB has different flexible configurations according
interrupter. to customer different requirements, such as
configuration with visible break.
Breaking short-circuit current in the vacuum PVB
does not require an interrupting and insulating Main additional features of PVB integrated
medium. In fact, the interrupter does not contain disconnector product are:
ignitable material. • Outside visible isolated gap
• 3 phase mechanical operation disconnector,
In any case, on separation of the contacts,an reliable mechanical interlocking with the PVB
electric arc is generated made up exclusively of circuit breaker
molten and vaporized contact material. The electric • Disconnector with excellent performance and
arc supported by the external energy only remains high technical ratings
until the current is cancelled by passing through
natural zero. At that instant, the rapid reduction Standards
in the load density carried and the fast condensation • IEC 60694-2002 Common specifications for
of the metallic vapour lead to extremely rapid high-voltage switchgear and controlgear
recovery of the dielectric properties. The vacuum standards
interrupter therefore recovers the insulating capacity • IEC 62271-100 High-voltage switchgear and
which withstand the transient recovery voltage, controlgear - Part 100: High-voltage
definitively the arc is extinguished. alternating-current circuit-breakers
• GB/T 11022 Common specifications for
Since high dielectric strength can be reached in high-voltage switchgear and controlgear
vacuum, even with minimum distances, interruption standards
of the circuit is also guaranteed when separation • GB 1984 High-voltage alternating-current
of the contacts takes place a few milliseconds circuit-breakers
before passage of the current through natural zero. • GB/T 311.1 Insulation coordination for high voltage
transmission and distribution equipment
The special geometry of the contacts and the • DL/T 402 Specification of high-voltage
material used, together with the limited duration alternating-current circuit-breakers
and low voltage of the arc guarantee minimum • DL/T 403 HV vacuum circuit-breaker for rated
contact wear and long life. Furthermore, the vacuum voltage 12 kV to 40.5 kV
prevents their oxidation and contamination. • DL/T 593 Common specifications for high-voltage
switchgear and controlgear standards
Features • DL/T 813 Specification for 12 kV H. V.
• Vacuum interruption technique alternating current automatic circuit recloser
• Modular design for easy service ability in the field • GB 1985 High-voltage alternating-current
• The contacts in vacuum protect against disconnectors and earthing switches
oxidation and contamination • IEC 62271-102 High-voltage switchgear and
• Suitable for different climatic conditions controlgear - Part 102: Alternating-current
• Low operating force disconnectors and earthing switches
• Spring operation mechanism equipped with
mechanical anti-pump device supplied as
standard
6 PVB outdoor vacuum circuit breaker Technical parameters 7

— —
Introduction Technical parameters

Application condition PVB technical parameters


General condition
Parameters Unit Values
Ambient temperature Rated voltage Un kV 12
High limit +40°c +40°c Rated current In A 630/1250****
Average temperature limit in 24 hours +35°c +35°c Rated frequency Hz 50/60
Low limit -40°c* -40°c* Power frequency withstand voltage, 50/60 sec/1 min To earth and between phases Dry kV 42
* motor operation is -25°c
Wet kV 34
Across the isolating distance Dry kV 48
Installation altitude Lightning impulse withstand voltage To earth and between phases kV 75
High limit 1000 m* 1000m*
Across the isolating distance kV 85
* special design can reach to 2000 m Short-circuit breaking current/Operations kA/n 20 kA/30
Short-circuit making current (peak) kA 50

Circuit breaker
Seismic intensity 9 Degree Short time withstand current kA 20
High limit: Withstand duration s 4
Peak withstand current (peak) kA 50
horizontal acceleration Ice covering mm 10
Simulated earthquake waves 0.50 g Circuit breaker level C2-E2-M2*
Sine resonate waves 0.30 g Rated operating sequence O-0.3 s-CO-180 s (15 s)-CO**
Mechanical mechanism type Spring mechanism
Dimension mm 1028x856x512 (HXWXD)
Special condition
Application in special condition, please contact Weight kg 110 (Incl. CT)
and consult with manufacturer in advance. Pollution level IV
Ingress degree IPX6
Generally, the following special condition can be
Mechanical endurance (number of close-open operations) n 10,000
considered by manufacturer:
• Installation altitude exceeds 1000 m Power frequency withstand voltage, 50/60 sec/1 min To earth and between phases kV 48
• External insulation can be decreased Across the isolating distance kV 54.5
• Choose the products which can be used in Lightning impulse withstand voltage To earth and between phases kV 85
altiplano area

Disconnector
Across the isolating distance kV 96
• Installed in higher ambient temperature
Short time withstand current kA 20
• Decrease continuous operating current PVB
Withstand duration s 4
Peak withstand current (peak) kA 50
Ice breaking mm 10
Dimension mm 1093x1015x542 (HXWXD)***
Pollution level IV
Mechanical endurance CO 3000

* According to the definition of standard: GB 1984-2003 demonstrated by specific type tests(circuit-breaker with
High-voltage alternating-current circuit-breakers, C2-E2-M2 extended mechanical endurance, mechanically type tested for
circuit breaker means: 10,000 operations).

Circuit-Breaker Class C2: Circuit-breaker with very low NOTE: A combination of the different classes of circuit-breakers
probability of restrike during capacitive current breaking as with regard to electrical endurance, mechanical
demonstrated by specific type test. endurance and the restrike probability during capacitive
current breaking is possible. For the designation of
Circuit-Breaker Class E2: Circuit-breaker designed so as not these circuit-breakers the notation of the different
to require maintenance of the interrupting parts of the classes are combined following an alphabetical order, for
main circuit during its expected operation life, and only example C1-M2.
minimal maintenance of its other parts(circuit-breaker
with extended electrical endurance). ** Motor operating PVB with smart controllers can carry out 4-5
reclosing sequences.
Circuit-Breaker Class M2: Frequently operated *** The dimension is the overall dimension with CB.
circuit-breaker for special service requirements and **** Rated current 1250 A is only for the circuit-breakers.
designed so as to require only limited maintenance as
8 PVB outdoor vacuum circuit breaker Structure and functions 9


Structure and functions

PVB structure Following contact separation, single melting An electromagnetic force is self-generated and 1 Stem/terminal
The poles of PVB are capsulated by insulated points form on the surface of the cathode, this acts tangentially, causing rapid arc rotation 2 Twist protection
material which is Hydrophobic Cycloaliphatic producing metal vapours which support the arc. around the contact axis. 3 Bellows
Epoxy (HCEP) and the poles are installed 4 Interrupter housing
vertically on the mechanism tank (see rightside The diffuse vacuum arc is characterised by This means the arc is forced to rotate and to 5 Shield
picture). Poles casted by HCEP canminimize expansion over the contact surface and by an involve a wider surface than that of a fixed 6 Ceramic insulator
partial discharge and mechanicaldamage. When even distribution of the thermal stress. contracted arc. 7 Shield
PVB is closed, current path of the main circuit is: 8 Contacts
upper teminal→static contact in the vacuum At the rated current of the vacuum interrupter, Apart from minimising thermal stress on the 9 Terminal
interrupter→dynamic contact in the vacuum the electric arc is always of the diffuse type. contacts, all this makes contact erosion negligible 10 Interrupter housing
interrupter→lowerterminal→external circuit. Contact erosion is negligible, and the number of and, above all, allows the interruption process
current interruptions very high. even with very high short-circuits.
Interruption principle of ABB interrupters
Vacuum Interrupter As the interrupted current value increases ABB vacuum interrupters are zero-current
ABB has been developing and manufacturing (above the rated value), the electric arc tends to interrupters and are free of any re-striking.
vacuum interrupters since the early 1980 s. be transformed from the diffuse into the
Worldwide, more than two million ABB vacuum contracted type, due to the Hall effect. Rapid reduction in the current charge and rapid
interrupters are in service. ABB's vacuum condensation of the metal vapours simultaneously
interrupter facility uses the latest technologies Starting at the anode, the arc contracts and as with the zero-current, means maximum dielectric
in high quality mass production to produce the the current rises further it tends to become strength can be restored between the interrupter
next generation of vacuum interrupters. This sharply defined. contacts within microseconds.
new generation vacuum interrupter is robust for
universal application. Near the area involved there is an increase in
temperature with consequent thermal stress on
Advantages the contact. To prevent overheating and erosion
• Maximum reliability of the contacts, the arc is kept rotating. With
• Superior contact wear arc rotation it becomes similar to a moving
• Long life: 10,000 full load operations conductor which the current passes through.
• Minimal maintenance
• Environmentally friendly The spiral geometry of ABB vacuum interrupter
contacts
In a vacuum interrupter, separation of The special geometry of the spiral contacts
current-carrying contacts initiates the vacuum generates a radial magnetic field in all areas of
arc and this is maintained until the current zero the arc column, concentrated over the contact
and can be influenced by magnetic fields. circumferences. Diffuse arc. Contraction Contraction over
over anode. anode and
cathode.
Diffuse or contracted vacuum arcs
Schematic diagram of the transition from a diffuse
arc to a contracted arc in a vacuum interrupter.

Terminal

Short-circuit
CT current

Current, Voltage
Terminal
Arc voltage
Main circuit Pole System voltage
Terminal Short-circuit current
interruption

Contact Time
separation
Open and
Operation handle Recovery voltage
Close Handle (system frequency)

Transient recovery
Charging Rod (TRV) (high frequency) Radial magnetic field contact arrangement with a
Tank rotating vacuum arc.
Mounting bracket Development of current and voltage trends
during a single phase vacuum interruption process.
10 PVB outdoor vacuum circuit breaker Structure and functions 11


Structure and functions

Solid-encapsulated pole Characteristic of insulating material Operating mechanism Manual operating PVB
PVB's pole assemblies are constructed of UV HCEP is light, and anti-aging, so it can meet the PVB uses EL-mechanical operation, and the Spring operating mechanism of PVB can be
resistant HCEP encapsulating material and are requirements of using in outdoor severe optional secondary accessories can be installed charged manually via charging rod simply and
design to provide a rated 10,000 full load environment and enhance anti-corrosion during easily and quickly, and EL mechanical operation reliably. After the spring operating mechanism
operations without maintenance. Meanwhile high-pollution environment of equipment. is spring operated mechanism. being charged, PVB can be closed via operation
HECP can supply protection for vacuum handle, if PVB is closed, PVB can be opened by
interrupter to decrease the effect of dust and EL-mechanical operating mechanism operation handle without charging the spring
humidity, and main contacts will enduringly be The mechanical operating mechanism of PVB operating mechanism again!
encapsulated in vacuum condition through arc circuit-breaker is of simple concept and use,
extinguished chamber which constitutes and can be customized with a wide range of Protection functions of manual operating PVB
vacuum interrupter unit. easily and rapidly installed accessories. Protection elements of manual operating PVB
are CT, MFC protection control device and
This simplicity translates into greater reliability overcurrent release. When the overhead lines
of circuit breaker. The EL operating mechanism have overloaded current or fault current, CT will
is of the stored energy type with the sense the current and secondary current of CT
anti-pumping device mounted as standard to will increase accordingly, thus the current into
prevent incorrect operations. the MFC protection control will over the setting
value to drive the overcurrent release to trip.
Position of open or closed, and charging status
are visible from the indication windows which
are at the bottom of PVB tank (please find the
dimension of the windows in detail shown
below).

Advantages of HCEP over CEP


• Improved performance and heavily polluted areas
• Improved weatherability and outdoor aging
• Increased life expectancy
• Enhanced reliability

Why we need Hydrophobicity?


• Improved waters beading and runoff
• Lower leakage currents- Less discharge activity
• Lower flash over probability
• Battery reliability
• Improved life expectancy
Comparison of CEP and HCEP after 1000 hours salt-fog test
12 PVB outdoor vacuum circuit breaker Structure and functions 13


Structure and functions

Current transformer Motor operator


This carries out automatic charging of the
Rated ratio Accuracy Insulation level (rated voltage / PFW / BIL) Pollution level circuit-breaker operating mechanism closing
630/5 5P10 12/42/75 kV Ⅳ springs. After circuit-breaker closing, the geared
400/5 5P10 12/42/75 kV Ⅳ motor immediately recharges the closing springs.
In the case of a power cut or during maintenance
200/5 5P10 12/42/75 kV Ⅳ
work, the closing springs can be charged manually
630, 400/5 5P10 12/42/75 kV Ⅳ in any case(by means of the special crank handle
400, 200/5 5P10 12/42/75 kV Ⅳ incorporated in the operating mechanism).

MFC protection control device Overcurrent release Parameters Values


• Cold load time for Inrush current, time delay • Rated current: 5 A, DC Rated voltage Un DC 24,48, 110, 220 V
setting has four options: 0, 200 ms, 400 ms, • Insulation level: E AC (50, 60 Hz) 110, 220 V
600 ms • Power frequent withstand voltage: 2000 V/1 min
Operating limits 85~110% Un
• Time overcurrent, its delay time can be set
from 40 ms to 3 s with 16 options Power on inrush (Ps) DC: 500 W; AC=500 VA
• Multiplier of rated current (CT secondary value) Rated power (Pn) DC: 200 W; AC=200 VA
Motor operator
for instantaneous overcurrent protection can Inrush duration 0.2 s
be set: 2, 3, 4, and 5 Charging time 4~7 s
• Time delay for Instantaneous overcurrent can
Insulation voltage 2500 V 50 Hz (1 min)
be set: 0, 40 ms, 80 ms, and 120 ms
• Power loss of MFC is less than 0.5 W at normal
work condition Opening and closing release
• Ambient temperature: -40°c~+85°c This allows remote control of the PVB. The release
Over current release can operate both in direct and alternating current.
• Protection function is achieved through phase
A and phase C, which controlled by two This release is suitable for both instantaneous and
independent CPU permanent service. In the case of instantaneous
service, the minimum current impulse time must
Motor operating PVB with simple protection be 100 ms.
functions
In order to operate the circuit breaker safely and Parameters Values
use less effort, meanwhile ready for DA, manual Rated voltage Un DC 24, 48, 110, 220 V
PVB can be upgradedto motor operating AC (50, 60 Hz) 110, 220 V
mechanism PVB by adding motor operator and
Operating limits 65~120% Un
control cabinet which is installed below the Pole
to fulfill protection function. Power on inrush (Ps) DC: 200 W; AC: 200 VA
Rated power (Pn) DC: 5 W; AC: 5 VA
(Note: One (1) potential transformer at least is Inrush duration 100 ms Opening and closing release
needed to supply power for control cabinet). Closing time 35~80 ms
Opening time 45~80 ms
MFC protection control device
Insulation voltage 2500 V 50 Hz (1 min)

Auxiliary switch

Parameters Values
Rated voltage Un DC220 V
Rated frequency 50 Hz
Rated current 3A

Auxiliary switch

Simple control cabinet


14 PVB outdoor vacuum circuit breaker Structure and functions 15


Structure and functions

To fulfill more complicated protection functions Indicator lights Front mounted RS-232 port Metering
settings, SCADA, and DA functions, PCD control • Continual self-checking with status indication • Independent from rear mounted RS-232 port • Meters current and voltage (with PT voltage
unit and feeder relay REF 615 can be configured • Pickup and lockout indication • Easy download and upload of data on-site input supplied) to ± 1% accuracies
in control cabinet. using WinPCD • Measures kW and kVAR, power factor, demand
Front panel pushbuttons Watts and VARs, and frequency to ± 2% accuracy
Motor operating PVB with Intelligent • Up to six protection groups available Separate open and close pushbuttons • User-selectable load profile data sampling 5,
Protection Functions--PCD Control Device • Front panel button to set Alt 1 settings • Separate indicator light for easier viewing 15, 30, 60 minute time internal which will
An intelligent control device has functions of • Ground blocked, remote blocked, and reclose • ANSI or IEC coloring for individual practices contain 13.3, 40, 80 or 160 days of information
protection, monitoring, and controlling. blocked pushbuttons • All data can be downloaded on-site or
• Sensitive earth fault (SEF) available for Control cabinet remotely through communications interface
Local human-machine interface ungrounded or Delta CT applications • Stainless steel cabinet, NEMA 3R with drip • Includes assignable phases for easy phase
• Enlarged LCD (1"x5") with large characters • PROG 1 battery test load feature preprogrammed shied selection and selectable power flow
(two lines of 20 characters) • User programmable LEDs for alarms, additional • Battery provides full operational capability for
• Simple menu-driven programming using large targets, etc to 48 hours (15-27 kV) /24 hours (38 kV) Protective functions
six- button keypad • Counters button for easy access to number of • Ample space for mounting communications • Phase time overcurrent protection (51P)
• Backlit display indicates metering values, fault operations and overcurrent trip information equipment • Phase instantaneous overcurrent protection
information and location • Three-point latching with padlockable handle (50P-1)
• Temperature compensated Hot line tagging feature • Vented design • Two definite time overcurrent settings (50P-2,
• Battery test function included • On faceplate for simpler and safer operation 50P-3)
• Can be mapped for multiple applications Communication & I/O ports • Ground overcurrent protection (51N)
• Isolated RS-232 and RS-485 ports • Ground instantaneous overcurrent protection
• ST fiber optic ports (50N-1)
• Modbus ASCII and RTU, and DNP 3.0TM • Two definite time ground overcurrent settings
protocols included with all units (50N-2, 50N-3)
• DNP 3.0TM is compliant to Level 2 • Negative sequence overcurrent protection (46)
• IEC 60870-5-101 • Two independent steps for load shed,
• Programmable I/O ports: 6 inputs, 4 outputs restoration, and over-frequency (81S, 81R, 81O)
available with UPS • Undervoltage and overvoltage control and
• Programmable I/O ports: 10 inputs, 7 outputs alarm (27/59)
available with PS • Phase and ground directional overcurrent
protection (67P, 67N)
Oscillographic data • Sensitive Earth Fault protection with directional
• Storage capacity of 64 cycles of monitored features (optional)
waveform data at 32 samples per cycle • Up to four reclose cycles (define a recloser cycle
• All data can be downloaded on-site or 79-1→79-5) close four times / trip five Adaptive
remotely through communication interfaces reclosing shots: each reclose sequence allows
independent programming of protective
Fault recording functions
• Records last 128 operations of: • Available with up to 38 recloser curves, nine ANSI
• Phase and ground fault amperes curves, four IEC curves and three user
• Phase and ground voltage • Programmable curves
• Isolates the faulted section
• Reclose time- Distance to fault
• Estimated fault resistance
• Time stamp
• Stores 1024 operation records
16 PVB outdoor vacuum circuit breaker Structure and functions 17


Structure and functions

Motor operating PVB with Intelligent • The REF615 is the one of most powerful, Standard configuration functionality Overcurrent and directional earth- Overcurrent and non- directional
protection functions--REF615 relay advanced and simplest protection relay, fault protection earth-fault protection
REF 615 is a member of ABB's Relion® family and perfectly offering time and instantaneous
a part of its 615 protection and control product overcurrent, negative sequence overcurrent, Std. conf. A Std. conf. B Std. conf. C Std. conf. D
series. The 615 series IEDs are characterized by and voltage metering and protection.The relay Protection
their compactness and withdrawable design. also features optional high impedance fault Three-phase non-directional overcurrent, low-set stage ● ● ● ●
Engineered from ground up, the 615 series has (HIZ) and ungrounded distribution systems, Three-phase non-directional overcurrent, ● ● ● ●
been designed to unleash the full protection of and the replay incorporates a flexible
high-set stage, instance 1
the IEC 61850 standard for communication and three-phase multi-shot auto-reclose function
interoperatability of substation automation for automatic restoration in temporary faults Three-phase non-directional overcurrent, ● ● ● ●
devices. on overhead lines high-set stage, instance 2
• I/O extension model, has maximum 17 BI/O, 13 Three-phase non-directional overcurrent, ● ● ● ●
The REF615 provides main protection for overhead SI/O
instantaneous stage
lines, cable feeders, and busbar systems of • Drawout design
distribution substations. It can be applied for • Six setting groups Directional earth-fault, low-set stage, instance 1 ● ● ● ●
protection and control of grounded and • High-speed (<1 ms) output Directional earth-fault, low-set stage, instance 2 ● ● ● ●
un-grounded distribution systems. Flexible • Fault recording: higher sample frequency, Directional earth-fault, high-set stage ● ● ● ●
order coding allows for choosing current-only or larger storage capacity can record 12 Non-directional earth-fault, high-set stage ● ● ● ●
current-and-voltage configurations to best fit analogue signals and 64 digital signals
(cross country earth-fault)
your application needs. • HMI: Large, and easy to read LCD screen
• Environmentally friendly design with RoHS Transient/intermittent earth-fault ● ● ● ●
compliance Non-directional earth-fault, low-set stage - - ● ●
Non-directional earth-fault, high-set stage - - ● ●
Non-directional earth-fault, - - ● ●
instantaneous stage - - ● ●
Non-directional sensitive earth-fault
Negative-sequence overcurrent, instance 1 ● ● ● ●
Negative-sequence overcurrent, instance 2 ● ● ● ●
Phase discontinuity ● ● ● ●
Thermal overload ● ● ● ●
Circuit breaker failure protection ● ● ● ●
Three-phase inrush current detection ● ● ● ●
Arc protection with three sensors ○ ○ ○ ○
Control
Circuit breaker control with basic interlocking 1) ● ● ● ●
Circuit breaker control with extended interlocking 2) - ● - -
Auto-reclosing of one circuit breaker ○ ○ ○ ○
Supervision and monitoring - ● - ●
Circuit breaker condition monitoring ● ● ● ●
Trip-circuit supervision of two trip circuits ● ● ● ●
Measurement
Transient disturbance recorder ● ● ● ●
Three-phase current measurement ● ● ● ●
Current sequence components ● ● ● ●
Residual current measurement ● ● ● ●
Residual voltage measurement ● ● - -
● = Included, ○ = Optional at the time of the order
18 PVB outdoor vacuum circuit breaker Electrical circuit diagram 19


Electrical circuit diagram

Manual operating PVB Motor operating PVB with simple control cabinet

A
TR1
TR2

MO3

B
TR1
TR2

C
MO3
5

BV
W2
4
3
2
1
8
9
Rectifier Bridge
Rectifier Bridge
MFC Protection Control Device
Overcurrent Release
Current Transformer
Current Transformer

L1N
L1L
6


BC-C

BC-A
4

The status of circuit breaker for all electrical control


circuit diagram of the catalogue is: the circuit breaker
is in open position; control circuit has no electricity;
charging spring is uncharged.
20 PVB outdoor vacuum circuit breaker Electrical circuit diagram 21


Electrical circuit diagram

Motor operating PVB with smart control cabinet (PCD) Motor operating PVB with smart control cabinet (REF 615)
22 PVB outdoor vacuum circuit breaker Overall dimension and mounting modes 23


Overall dimension and mounting modes

Dimension--PVB without disconnector Dimension--PVB with disconnector

856 512 995

280 280

280 280

1098
1028

775 D

400 244

720 40

C
4-M12/Installing holes
145
43

C D
Type A CT 800 800
Type B CT 855 855
Charging indicator Open and close indicator
Note:
Type A CT includes CT ratio: 400/5, 630/5, 630-400/5;
Type B CT includes CT ratio: 200/5, 400-200/5.
24 PVB outdoor vacuum circuit breaker Overall dimension and mounting modes 25


Overall dimension and mounting modes

Mounting modes Mounting modes and rectangular bracket

Mounting mode 1: *Mounting mode 2:


Single pole rectangular bracket Double pole rectangular bracket (Front)

Mounting mode 5:
Single pole side installation (i n c l u d e s:
clamp and bracket, pole diameter:
180 mm-250 mm)

722 2- 17

22
6-17x35

125
79 100
4- 14
*Mounting mode 3:
*Mounting mode 4:
Double pole rectangular bracket (side)
Tower installation Mounting mode 6:
Single pole triangular bracket installation 723
(includes: Clamp and Bracket, pole
* For mounting mode 2/mounting mode 3/mounting mode diameter: 180 mm-250 mm)
4, only rectangular bracket is supplied, if further support is
needed, contact us.
26 PVB outdoor vacuum circuit breaker Circuit-breaker selection and ordering 27


Circuit-breaker selection and ordering

Selection Ordering requirements

PVB/ □ - □□□- □ / □ / □ □ PVB/ 12.06.20 - H 64 - A1 / D / BCU-A - 06


06 :6m
Control cable length: 09 :9m Outdoor pole mounted circuit breaker

12 : 12 m
Rated voltage: 12 kV 12
xx : Customer specify (<15 m) Rated current: 630 A/1250 A 06/12
Rated short-circuit breaking current: 20 kA 20
: None
Carbon steel HV cabinet (default)
Control cabinet: BCU-A : Simple control cabinet
Stainless steel HV cabinet S
BCU-B : Intelligent control cabinet (With PCD)
BCU-C : Intelligent control cabinet (With REF 615) Manual operating mechanism H
Motor operating mechanism M
Disconnector D : Integrated with disconector CT ratio: 630/5 60
: Without disconnector (default) Ratio: 400/5 40
Ratio: 200/5 20
Ratio: 630-400/5 64
Control voltage: A1 : AC110 V Ratio: 400-200/5 42
A2 : AC220 V Ratio: 1250/5 55
O
D1 : DC110 V Other CT ratio, please comment requirement:
D2 : DC220 V Control voltage: AC110 V A1
D3 : DC24 V Control voltage: AC220 V A2
Control voltage: DC110 V D1
D4 : DC48 V
Control voltage: DC220 V D2
CT ratio: 60 : 630/5 A Control voltage: DC24 V D3
Control voltage: DC48 V D4
40 : 400/5 A
20 : 200/5 A Without disconnector (default)
64 : 630-400/5 A Integrated with disconector D
42 : 400-200/5 A
55 : 1250/5 A No control dabinet
O : Others Simple control cabinet BCU-A
Intelligent control cabinet (With PCD) BCU-B
Operating mechanism: H : Manual
Intelligent control cabinet (With REF 615) BCU-C
M : Motor
HV cabinet : Carbon Steel (Default) Control cable length: 6 m 06
S : Stainless Steet Control cable length: 9 m 09
Control cable length: 12 m 12
Control cable length: (<15 m) xx
12.06.20: * Rated voltage : 12 kV
Rated current : 630 A 2 CT parameters: □ Phase A, C
Rated breaking current : 20 kA □ Phase A, B, C (Remark: Standard PVB with 2 pcs CT respectively on phase A and C)
3 Mounting modes (mounting bracket suitable for pole whose diameter is 180 mm~250 mm)
PVB: Outdoor vacuum circuit breaker □ Mounting mode 1 □ Mounting mode 2 □ Mounting mode 3 □ Mounting mode 4 □Mounting mode 5
□ Mounting mode 6 □ Others (Require detail drawings from customer side):
*: 12.06.20 is for rated current 630 A, if the rated current is 1250 A, the selection is 12.12.20 4 PT Control cable: □6m □9m □ 12 m □ m customer specify (<15 m)
5 Transformer (JDZW-1010 kV/0.1 kV/0.22 kV):
Type number description HV cabinet: carbon steel □ None □ 1 PC □ 2 PCS □ 3 PCS
E.G: PVB/12.06.20-M40-A1/BCU-A-06 Operating mechanism: motor 6 Configurated with MFC protection control device □ YES □ NO
Description: CT tatio: 400/5 A
PVB: outdoor pole mounted vacuum circuit breaker Control voltage: AC110 V
Disconnector: without disconnector Ordering company:
Rated voltage: 12 kV
Rated current: 630 A Control cabinet: simple control cabinet Manufacturer_ABB Xiamen Electrical Controlgear Co.,Ltd. Signature:
Short-circuit breaking current: 20 kA Control cable length: 6 m Signature:
Year: Month: Day:

ABB Xiamen Switchgear Co., Ltd.
No. 885, FangShanXiEr Road, Xiang’an District,
Xiamen, Fujian, 361101