B-T-G Operation
B-T-G Operation
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 1 of 28
BOILER TURBINE / GENERATOR AUXILIARY
1. Check that:
1) Power supplies to all electrical auxiliaries are available from the starting transformer and DEG is also available.
2) Instrument air compressor system is in service and instrument air supply pressure to all instruments and controls which use air are normal.
3) All supervisory instruments are in operation satisfactory.
4) Main and auxiliary cooling water system are operating.
Water treatment system, chlorination plant, ferrous sulfate system and chemical injection system are in service.
5) Lubricating oil for auxiliary equipment is adequate.
6) Fuel tanks are filled up to normal level.
7) All soot blowers are retracted from furnace.
8) Drum level television is available and drum level indicators are normal.
9) All access doors and inspection holes are closed tightly.
2. Check and prepare boiler systems of air, 2. Check and confirm turbine and generator 2. Check and confirm auxiliaries.
fuel gas, water, steam, fuel, etc. for start system.
up. 1) CW. Pump is in service
(See boiler instruction book). 2.1. Check the oil level (MAV01CL03, - P01) in (PAC10/11AP001).
the main 2) Check that water boxes are full and
oil tank, and test the oil level alarm then close the vents.
(MAV01CL01 – S01) and (MAV01CL02 –
S01). The normal oil level is 600 mm
below the upper plate of the main oil tank.
The alarm level is 100 mm from the
normal level.
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 2 of 28
BOILER TURBINE / GENERATOR AUXILIARY
2-1 Water system (start – up BFP & boiler 2-2 Generator 3) Check condensate system from
filling) (Refer to flow diagram No. KUO- demineralized
150-399 & 332). water head tank to the condenser and on
through
1). Confirm that the following main are closed. 1). Stator winding cooling water system is in the system to the deaerator, including related
service. instruments, instruments air, and control
a. Continues blow valves (HAN31AAO1/02). power
b. Drum water level reducing valve a. Cooling water pump A or B is operating as follows:
(HAN30AA02/03). (MKF12AP001 or MKF12AP002).
c. Soot blower steam and auxiliary steam b. Pump discharge pressure (6-9 bar. g) a. Check that the level in the demineralized
supply valves (HCB20AA01, (MKF12CP04 – P01). water head tank is adequate and make up
LBC41AA01/05). c. Generator inlet cooling water (1.8 bar. g) water supply system are ready for operation.
d. Valves on auxiliary steam line (MKF17CP07 – P01). b. Check that condenser hot well level is
(LBG21AA04). d. Stator cooling water conductivity (less than normal for start – up. Usually above normal
e. N2 gas injection valve. 0.5/cm) (MKF17CQ001, MKF22Q001). running level.
f. Drain valves of down – comer and feed e. Generator inlet cooling water flow c. Check that condensate pumps are ready for
water line (9HAN23AA02, (Approximately 740 1/min) service.
HAN21/22AA01, HAN10AA01/02). (MKF17CF01 – P01). d. Check that condensate line to deaerator is
g. Bypass valve of super heater and re-heater f. Deionizer water flow (Approximately set for normal operation through all heat
line. 1.15/1/min) (MKF20CF01 – P01). exchanger with bypasses closed where
g. Generator inlet cooling water temperature provided, line and equipment fall, all line
2). Confirm that the following main valves are less than 46 C (MKF17CT01 – P01). vents and drains are closed, control valves
open. h. Storage tank water level is normal normal with instrument air available and
(MKF19B3001). ready for operation.
a. Boiler feed water stop valves i. Stand – by side pump (COS) is “AUTO” e. Check deaerator for normal water level,
(LAB70AA02). position (MKF12AP001 or MKF12AP002). controls and alarms for proper operation.
b. Main steam boiler stop valve j. Cooling water for cooling water cooler is f. Check that LP heater bypass valves are
(LBA10AA13). available (MKF10BC001, MKF20BC001). closed.
c. Air vent valves (HAO1AA25/26, k. Stator cooling water temperature controller
HAH01AA01/03, HAH23AA01/02, is in service. 4) Check that auxiliary steam control to
LBA10AA01/02, HAJ01AA01/02). deaerator is in service and deaerator is
d. Drain valve for super heater, main steam 2). Shaft sealing oil system is in service. pegged and vent to atmosphere is open.
pipe including hot and cold reheat pipe
(HAN55AA01/02, HAN65AA01/02, a. Seal oil vacuum pump is operating
HAN75AA01/02, HAN85AA01/02, (MKW20AP001).
LBA21AA05/02, LBA22AA05,
JAJ01AA04/05/06/07).
e. Instrument intake valves.
f. Sampling and chemical injection valve.
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 3 of 28
BOILER TURBINE / GENERATOR AUXILIARY
3). Super heater and re heater temperature b. Vacuum of vacuum tank (MKW10CP01 – 5). Check the feed water system from the
control valves are closed. P01). Deaerator to the steam generator, noting
(LAE41/42AA501, Approximately 74 – 76 cmHg. that all lines and equipment are filled, that
LAE11/12AA501, LAF60AA501). c. Vacuum tank oil level is normal water line vents and drains are closed tight,
4). Feed water flow control valves are closed (MKW20BB001). instrument are in service, instrument air
(LAB62/63AA02). d. Main seal oil pump is operating and control power are available and
5). Water filling of boiler: (MKW12AP001). normal.
e. Seal oil pump discharge pressure 7.3 bar. g
a. Open a boiler water filling valve (MKW12CP02 – P01). a. Check that the boiler feed pump are ready
(LAB61AA03). And fill the boiler with f. Seal oil pressure at turbine end collector for start - up as follows.
demineralized water until the boiler water ring end. (See B.F.Pump instruction book).
reaches normal drum water level - 100mm. Generator H2 pressure + 0.34 bar. g Oil level normal
b. Close the boiler water filling valve. (MKW13CP01 – P – 1, MKW14CP01 – Pump inlet valves: OPEN
P01). Pump discharge valves : CLOSED
2-2 Draft system (start – up of fans) g. Seal oil differential pressure approximately. Sealing water supply and returns valves:
(Refer to flow diagram No. KUO – 150 – 0.34 bar. g (MKW10CP – P01). OPEN Minimum flow recirculation line set
409). h. Emergency seal oil pump (COS) is for automatic operation. All instruments,
“AUTO” position (MKW31AP001). controls, instrument air and control power
1). confirm that the manual dumpers position are i. Emergency seal oil vacuum pump (COS) is in normal service.
workable condition. “AUTO” position (MKW10AP002). b. Check feed water system from the BFP to
2). Start one of flame detector fan (ANO1). the outlet of HP No. 06 heater.
3). Put the following items selector station on 3). Hydrogen control system. Note that:
AUTO. All HP heaters full of water on water side
a. Generator hydrogen pressure 3.0 – 3.1barg by checking vents and that all water side
a. Group control A/H (1) and (2). (MKG23CP05 – P011). vents and drains are CLOSED TIGHT. HP
b. FDF (1) and (2) controller. heaters bypass three way valve is set in
c. Group control FDF (1) and (2). 3. Open drains valves as follows: “heater in service” position.
d. FDF inlet main controller. 1). Main stop valve above and below seat 6). Check high pressure and low pressure
e. GRF (1) and (2) controller. drain valves. heater drainage system noting heater
f. Group control GRF (1) and (2). (MAL10AA001, MAL20AA001, levels, proper setting of drain valves,
g. GRF main controller. MAL11AA001, MAL21AA001, instrument air supply, etc.
h. Group control combustion air supply. MAL10AA002, MAL20AA002, 7). Check that all heater vent valves in the
MAL11AA002, MAL21AA002). vent line where orifice.
4). Push ON “group control combustion air 2). Reheat stop valve above and below seat
supply button” with draft equipments with drain
start step by step automatically. valves. (MAL30AA002, MAL40AA002,
MAL32AA002, MAL42AA002).
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 4 of 28
BOILER TURBINE / GENERATOR AUXILIARY
a. STEP 1: FG A/H (1) and (2) ON 3). Intercept valve below seat drain valves. Plates are used are fully opened.
(HLD1/2AC01) A/H inlet gas and outlet air (MAL50AA002, MAL60AA002). 8) Check that all bled steam stop valves are
Damper open (BLA41/42AB01, closed.
HNA11/12AB01) A/H bypass damper dose 4. Check that drain trap valves are set as 9) Start boiler feed pump as follows:
(HLA33/34AB01) follows: (Refer to B. F. Pump instruction book)
b. STEP 2: All air register open. Inlet and outlet valve: OPEN See part A, item 13.a.
c. STEP 3 &4: FG FDH (1) and (2) on FDF Bypass valve: CLOSED
inlet Vane & outlet damper close a. Check that water level in deaerator storage
(HLB01/02Ab01, HLA11/12AB02 1) No. 1 bled stem drain trap tank is normal.
FDF on HLB1/2AN01). FDF controller 2) No. 2 // // // // b. Start BFP (LAC10/20, 30AP002)
auto. 3) No. 3 // // // // c. Check operation of BFP minimum flow
d. STEP 5: FG GRF on 4) Cold reheat steam line drain trap circulation control valve.
GRF inlet and outlet damper close. 5) Steam jet air ejector steam drain trap (Lab11/21/31AA002)
(HNF21/22AB01, HNF11/12AB01) d. Open discharge valve and
GRF on GLB1/2AN01) 5. Check that condenser vacuum breaker is (LAB10/20/30AA003) required, HP feed
GRF controller auto OPEN. (MAG01AA001). water system and boiler.
GRF outlet damper open and GRF
sealing damper close (HNF21/22AB01, 10) Check the evacuation system.
HLA16AB01/02)
e. Air flow is increased up more than 50% a. Vacuum pump air suction valves are closed
f. STEP 6: Wait for furnace purge 5min b. Steam jet air, ejector.
g. STEP 7: Purge timer over Steam supply valve: closed (LAG30AA002)
h. Air flow is decreased to 15% Air vent valve : closed (MAJ01AA206)
i. STEP 8: Air register close
j. STEP 9: Ignition release ON
2.3 Igniter & diesel oil firing system
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 5 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 6 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 7 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 8 of 28
BOILER TURBINE / GENERATOR AUXILIARY
5) When drum pressure reaches 2 to 3 1. Check to see that the vapour extractor is
bar a, close boiler vent valve fully. running.
(HA01AA25/26, HAH01AA01/03, (Confirm that the vapour extractor start
HAH23AA01/03, LBA10AA01/02) light goes on at *CCR)
2. Oil purifier in service
6) Adjust super heater and main steam
drain valves up to 20% 1) Push the oil separator vent fan
(HAN55AA01/02, HAN65AA01/02, (MAV90AN001) Confirm that the oil
HAN75AA01/02, Han85AA01/02, separator start light goes on
LBA21AA02/05, LBA22AA05) 2) Open the oil separator inlet valve
7) Control PH at economizer outlet at 4.1 (HAV90AA002) and the oil
to 9.4 by injecting hydrazine or separator outlet valve
ammonia in to deaerator down comer (MAV92AA002)
or CP outlet. 3) Push the oil circulating pump
8) Increase the firing rate if necessary (HAV91AA001) start button
Check tail pressure between the
cartridge filter inlet and outlet is less
than 1.5 bar a.
3. Turbine oil system in service.
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 9 of 28
BOILER TURBINE / GENERATOR AUXILIARY
9) After drum pressure reaches about 5 3) Confirm that the jacking oil pump
bars, super heater and main steam inlet valve (MAV80AA0010 open.
drain valves can be closed.
HP turbine bypass valve open by 4) Push the jacking oil pump
manual and keep the reheat pressure 5 (MAV80Ap001) start button at CCR.
bar a (LBC11/12AA501). 5) Confirm that the jacking oil pump
10) Confirm that the HP Turbine spray start light goes on at CCR.
valves are open and control steam 6) Check to see that the oil level is
temperature at 195 C (LAE60AA01, normal as indicated by the float level
LAE60AA502, LAE61/62AA501). gauge, with the pump running and
11) Start to send steam to auxiliary steam the system filled with oil.
header. 7) Check to see that the bearing oil
Open auxiliary steam stop valve pressure is normal at 1.72 bars (g).
(LBC41AA01) and steam control 8) Check to see that the operating oil
valve (LBG10AA501/502) gradually. pressure is normal at 13.7 bars (g).
12) Put the steam conversion system in 9) Check the oil flow at each bearing
service (Refer to flow diagram No. sight discharge.
KU1 – 249 – 684) 10) The oil to the bearings must not be
less than 27 C or more than 40 C for
turning gear operation.
11) Push the turning gear motor
(MAK10) start button at CCR.
12) Confirm that the turning gear motor
start light goes on at CCR.
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 10 of 28
BOILER TURBINE / GENERATOR AUXILIARY
13) Put the heavy fuel oil system in 13) Push the turning gear engage start
service (Refer to flow diagram No. button at CCR.
KUO – 153 – 547, KUO – 156 – 320, 14) Confirm that the turning gear engage
KUI – 273 – 474) light goes on at CCR.
a. Heavy fuel oil tank level is normal. 4. gland seal system in service
b. Confirm that the following main
valves are open: 1) Check the following conditions:
o All burner inlet valves (HHF70 –
81AA01) a. Auxiliary steam stop valve
o Instrument intake valves (LBG40AA002) is fully open.
c. Confirm that the drain, vent and b. Primary super heater outlet steam
bypass valves are close. stop valve (LBG50AA002) is fully
d. Check the auxiliary steam system: open.
o Atomizing steam line c. Isolating valves of SSR water pot are
o Oil heating steam line fully open (LBW30AA005, 06).
o Steam trace line d. Auxiliary steam bypass valve of SSR
e. Put steam trace line in service is fully closed (LBG40AA003).
f. Start fuel oil pump: e. Primary super heater outlet steam
o Check oil temperature is normal bypass valve (LBG50AA003) is fully
closed.
o Put fuel oil control valve at 0%
f. Mixing steam inlet valve
o Start heavy fuel oil supply pump
(LBW01AA001/002) of gland
(EGD41AP01) exhauster fan is cracked open (15 –
o Start heavy fuel oil boiler pump 20%).
(HHF11AP01) g. Condensate system is in service.
c. Warming up of recirculation line.
o Open fuel flow control valve 2) Push open – button of the steam feed
gradually and carry out the to SSR drain valves
arming up of fuel oil by opening (LBG50AA004/005)
of recirculation valve 3) Confirm that the full – open lights of
o Put in service fuel oil heater the steam feed to SSR drain valves to
(HHF41/51/61BC01) on.
d. Make atomizing steam alive. 4) Push start – button of the gland
o Open atomizing steam supply condenser exhauster fan
valve gradually (LBJ01AN001/002) at CCR
o Confirm that atomizing steam 5) Confirm that start – light of the gland
pressure is controlled at 10.5 bar condenser exhauster fan goes on.
a. (HHM10AP01)
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 11 of 28
BOILER TURBINE / GENERATOR AUXILIARY
14) Put steam air heater in service (Refer 6) Check to see that the SSR steam feed
to flow diagram No. KUO – 150 – valve (LBG50AA002) and the SSR
312) auxiliary steam feed valve
(LBG40AA002) is automatically
a. Confirm that all valve positions on open.
system are normal.
b. Open the heating steam stop valve 7) After the SSR Steam feed valve
(LBG 32AA05) and heating steam open, check to see that the steam feed
intake valve (LBS32AA502) to SSR drain valves
gradually. (LBG50AA004/055) are
c. Start one of SAH drain pumps after automatically closed.
high level of drain tank ANN comes 8) Confirm that the gland steam
on (LNC10/11AP01) pressure and the gland condenser
d. Put SAH drain pump selector station shell vacuum are normal.
on auto.
Confirm that SAH drain level is *Use SSR steam bypass valve (LBG40/50AA003) 1. Vacuum up
controlled normally. if necessary, to get normal steam seal header
e. Waste the drain to the drain flush pressure and boiler pressure goes up, adjust the 1) Start the vacuum pump
tank. bypass valve as needed. 2) When the vacuum is near normal,
f. Drain quality becomes good, recover one of vacuum pumps stop.
the drain to the deaerator. 5. When the condenser vacuum reaches to
g. After the average temperature of A/H 0.07 bar. g LP bypass stop valves are open
cold end reaches to 130 C, close A/H and LP bypass valve control mode is put
bypass air and gas damper. onto auto position.
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 12 of 28
BOILER TURBINE / GENERATOR AUXILIARY
18) Start warming of soot blower line and 6. Start turbine pre – warming
then operate A/H soot blower
(HLB20AA01/03). If HP turbine after first stage metal is below
19) Light on heavy oil burner (HH79 – 150 C, HP turbine pre – warming is required
81/AV01) one by one, and adjust the
fuel oil flow control valve to maintain 1) Prior to start HP turbine pre –
oil pressure. warming, check to see that:
20) Cut off diesel oil burner (HA70, a. All turbine drain valves are fully
72/EA100) one by one. open
21) After completing of oil burner change b. The turbine is on turning
from diesel oil to heavy oil, confirm c. The gland steam supply system is in
the following items. service
a. Heavy oil flow is adjusted 10 – d. The condenser vacuum is built up
12m /hour e. 8bar (a) reheat pressure is
b. Air flow is adjusted at 25% established.
c. Combustion condition in the furnace f. The ventilator valves
d. Heavy oil pressure and temperature is (MAA07AA001, MAA08AA001)
normal are fully closed
e. Average temperature of A/H cold end g. The emergency blow down valve
is controlled at 130 C (MAA06AA001) is fully open
f. Feed water temperature is heated up h. The emergency trip valve is tripped
to 110 C. position
i. The turbine control valves are fully
open
j. The drain trap valves of cold reheat
are fully open
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 13 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 14 of 28
BOILER TURBINE / GENERATOR AUXILIARY
o CV & ICBV
o ICV (MAB30AA001,
MAB40AA001)
6) Note.
a. CHECK TO SEE THAT THE BACK –
UP OVERSPEED TRIP IS ITS
NORMAL SETTING POSITION.
b. SET THE INITIAL PRESSURE AND
VACUUM UNLOADER OUT – OF –
ACTION WITH A LOW STEAM
PRESSURE START UP.
c. CHECK THE SUPERVISORY
INSTRUMENT to see that the turbine
rotor is straight.
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 15 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 16 of 28
BOILER TURBINE / GENERATOR AUXILIARY
TURBINE ROLLING
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 17 of 28
BOILER TURBINE / GENERATOR AUXILIARY
6. Excitation
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 18 of 28
BOILER TURBINE / GENERATOR AUXILIARY
SYNCHRONIZATION
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 19 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 20 of 28
BOILER TURBINE / GENERATOR AUXILIARY REMARKS
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 21 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 22 of 28
BOILER TURBINE / GENERATOR AUXILIARY
For normal shutdown of short duration the load should be reduced gradually, to avoid excessive rate of change of turbine metal temperature, thus reducing
distortion of hot parts, including valves, shells and rotors. The exact procedure should be modified to give the expected optimum conditions of temperatures and
pressures to be expected at the time of the restarting of the unit. (See turbine instruction book “Operating Instructions”
Prior to the unit shutdown, it is very important to 1. Take vacuum unloading and initial pressure 1. When the total auxiliary power being used
carry out one cycle operation of all soot blowers. unloading device. is within the rating of the starting
1. Load down. 2. Reduce load transformer, transfer auxiliary power to the
starting transformer.
1) Steam temperature control is change o Temperature differentials between 2. As load is reduced, check drainage of all
to manual operation at 40 – 60% load. inner and outer surface should be feed water heaters.
2) At around 40% load, stop one of minimized and held below that 3. One of BFP stop at 40% load.
boiler feed water pump. recommended by “Allowable 4. One of main condensate pump and
3) If necessary cutting out the burners in Differences”. Careful boiler operation condensate booster pump at 40% load.
accordance with the load, take into is required for temperature control.
consideration of cutting out the burner o Watch metal temperature, differential
when the fuel oil pressure reaches to expansion, steam pressure and
minimum one. temperature, exhaust hood
4) During load operation, control main temperature, etc., to be sure safe limits
and reheat steam temperatures to meet are not exceeded.
the turbine requirements. o In the event extended operation at light
5) Load down further to around 25% loads (below transfer point) is not
load and stop GRF. planned and the unit is to be tripped
6) Load down to around 15% loads from out promptly upon reduction of load, it
25% load. Change the boiler master to is permissible to SHUT THE
manual and HP turbine bypass valve TURBINE DOWN as a procedure
are changes to pressure control. simplification.
In case of boiler forced cooling after
shut down the unit, reduce the main Proceed as follows:
steam pressure by changing of set
point of HP turbine bypass valve up to 1) Gradually reduce load to
50 bars. approximately 15% rated.
7) During 15% load operation, level only 2) When the unit load reaches about
two burners. At that time it is better to 15% rated, note that the water sprays
leave two burners to get uniform to the turbine exhaust hoods are put
absorption heat. in service.
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 23 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 24 of 28
BOILER TURBINE / GENERATOR AUXILIARY
AUXILIARY STOP
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 25 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 26 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 27 of 28
BOILER TURBINE / GENERATOR AUXILIARY
_________________________________________________________________________________________________________________________________________________________________________________________
/conversion/tmp/activity_task_scratch/749598701.doc Rehabilitate by: Farooq Sharif & Zafar Ali Sabir Page 28 of 28