0% found this document useful (0 votes)
201 views63 pages

Rs 485 Df1 Allen Bradley

Solid state equipment has operational characteristics differing from those of electromechanical devices. The examples and diagrams in this manual are included solely for illustrative purposes. No patent liability is assumed by the Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.

Uploaded by

kellychio24
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
201 views63 pages

Rs 485 Df1 Allen Bradley

Solid state equipment has operational characteristics differing from those of electromechanical devices. The examples and diagrams in this manual are included solely for illustrative purposes. No patent liability is assumed by the Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.

Uploaded by

kellychio24
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 63

RS-485 DF1 Adapter

20-COMM-S FRN 1.xxx

User Manual

Important User Information


Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited. Throughout this manual we use notes to make you aware of safety considerations. ATTENTION: Identies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.

Attentions help you: identify a hazard avoid the hazard recognize the consequences

Important: Identies information that is especially important for successful application and understanding of the product. Shock Hazard labels may be located on or inside the drive to alert people that dangerous voltage may be present.

Summary of Changes
This is the rst release of the RS-485 DF1 FRN 1.xxx.

Notes:

Table of Contents
Preface About This Manual
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1 Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . . P-2 Rockwell Automation Support. . . . . . . . . . . . . . . . . . . . . . . . P-2

Chapter 1

Getting Started
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-2 1-3 1-3 1-4 1-5 1-6

Chapter 2

Installing the Adapter


Preparing for an Installation. . . . . . . . . . . . . . . . . . . . . . . . . . Commissioning the Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Adapter to the Network. . . . . . . . . . . . . . . . . Connecting the Adapter to the Drive . . . . . . . . . . . . . . . . . . . Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2-1 2-3 2-4 2-6

Chapter 3

Conguring the Adapter


Conguration Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using DriveExplorer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using the PowerFlex HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the Data Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the CRC/BCC Selection . . . . . . . . . . . . . . . . . . . . . . Setting a Fault Action. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Resetting the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Viewing the Adapter Conguration . . . . . . . . . . . . . . . . . . . . 3-1 3-2 3-3 3-4 3-4 3-5 3-5 3-7 3-8

Chapter 4 Chapter 5

Using DriveExplorer on the RS-485 Network


Drive Explorer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1

Troubleshooting
Locating the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . PORT Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MOD Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Net A Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Net B Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Module Diagnostic Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . Module Diagnostic Items (continued) . . . . . . . . . . . . . . . . . . Viewing and Clearing Events. . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5-2 5-3 5-3 5-4 5-5 5-6 5-7

ii

Table of Contents

Appendix A

Specications
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2

Appendix B

Adapter Parameters
About Parameter Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . B-1 Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

Appendix C Glossary Index

Logic Command/Status Words


PowerFlex 70 and PowerFlex 700 Drives . . . . . . . . . . . . . . . C-1

Preface

About This Manual


Topic Related Documentation Conventions Used in this Manual Rockwell Automation Support Page P-1 P-2 P-2

Related Documentation
For: DF1 Protocol DriveExplorer Refer to: DF1 Protocol and Command Set Reference manual DriveExplorer Getting Results Manual Online help (installed with the software) DriveTools 2000 http://www.ab.com/drives/drivetools_2000 Online help (installed with the software) PowerFlex HIM HIM Quick Reference PowerFlex 70 Drive PowerFlex 70 User Manual PowerFlex 70 Reference Manual PowerFlex 700 Drive PowerFlex 700 User Manual PowerFlex 700 Reference Manual RSLinx Getting Results with RSLinx Online help (installed with the software) Publication 1770-6.5.16 9306-GR001

20HIM-QR001 20A-UM001 20A-RM001 20B-UM001 20B-RM001 9399-WAB32GR

Documentation can be obtained online at http://www.ab.com/manuals

P-2

About This Manual

Conventions Used in this Manual


The following conventions are used throughout this manual: Parameter names are shown in the following format Parameter xxx - [*]. The xxx represents the parameter number. The * represents the parameter name. For example Parameter 01 - [DPI Port]. Menu commands are shown in bold type face and follow the format Menu > Command. For example, if you read Select File > Open, you should click the File menu and then click the Open command. The rmware release is displayed as FRN X.xxx. The FRN signies Firmware Release Number. The X is the major release number. The xxx is the minor update number.

Rockwell Automation Support


Rockwell Automation offers support services worldwide, with over 75 sales/support ofces, over 500 authorized distributors, and over 250 authorized systems integrators located through the United States alone. In addition, Rockwell Automation representatives are in every major country in the world.

Local Product Support


Contact your local Rockwell Automation representative for sales and order support, product technical training, warranty support, and support service agreements.

Technical Product Assistance


If you need to contact Rockwell Automation for technical assistance, please review the information in Chapter 5, Troubleshooting rst. If you still have problems, then call your local Rockwell Automation representative

U.S. Allen-Bradley Drives Technical Support:


E-mail: [email protected] Tel: (1) 262.512.8176 Fax: (1) 262.512.2222 Online: http://www.ab.com/support/abdrives

Chapter 1

Getting Started
The RS-485 DF1 (20-COMM-S) is an embedded communication option for any one drive in the PowerFlex 7-Class family. It can also be used with other Allen-Bradley products implementing DPI, a functional enhancement to SCANport.
Topic Components Features Compatible Products Required Equipment Page 1-1 1-2 1-3 1-3 Topic Safety Precautions Quick Start Modes of Operation Page 1-4 1-5 1-6

Components
Figure 1.1 Components of the Adapter


# Part Status Indicators Description Four LEDs that indicate the status of the connected drive, adapter, and network. Refer to Chapter 4, Using DriveExplorer on the RS-485 Network. DPI A 20-pin, single-row shrouded male header. An Internal Interface Connector cable is connected to this connector and a connector on the drive. RS-485 DF1 A 6-pin connector to which a 6-pin linear plug can be connected. Connector Node Switches for setting the node address. Address Switches Data Rate Switch for setting the RS-485 DF1 data rate at which the adapter Switch communicates.

1-2

Getting Started

Features
The RS-485 DF1 adapter features the following: The adapter is mounted in and receives power from the PowerFlex drive. Captive screws are used to secure and ground the adapter to the drive. Switches let you set a node address and network data rate before applying power to the PowerFlex drive. Alternatively, you can disable the switches and use parameters to congure these features. A number of conguration tools can be used to congure the adapter and connected drive. The tools include the PowerFlex HIM on the drive, or drive-conguration software such as DriveExplorer (version 2.02 or higher) or DriveTools 2000 (version 1.01 or higher). Status indicators report the status of the drive communications, adapter, and network. They are visible both when the cover is opened and when it is closed. Allows DriveExplorer (version 2.02 or higher) to connect to a PowerFlex drive with a 1203-SSS, and route out over RS-485 to other PowerFlex drives. Allows an RS-485 DF1 Master device to access the PowerFlex drive: Logic Command/Reference Logic Status Feedback Datalinks A-D Explicit message support

User dened fault actions determine how the adapter and PowerFlex drive respond to communication disruptions on the network.

Getting Started

1-3

Compatible Products
DPI is a second generation peripheral communication interface (see Glossary). The RS-485 DF1 adapter is compatible with Allen-Bradley PowerFlex drives and other products that support DPI. DPI is a functional enhancement to SCANport. At the time of publication, compatible products include: PowerFlex 70 drives PowerFlex 700 drives PowerFlex 7000 drives

Required Equipment
Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes: One RS-485 DF1 adapter A 2.54 cm (1 in.) and a 15.24 cm (6 in.) Internal Interface cable (only one cable is needed to connect the adapter to the drive) One six-pin linear RS-485 DF1 plug (connected to the RS-485 DF1 connector on the adapter) One grounding wrist strap This manual

User-Supplied Equipment
To install and congure the RS-485 DF1 adapter, you must supply: A small athead or Phillips screwdriver RS-485 cable (Belden 3106A or equivalent recommended) Conguration tool, such as: PowerFlex HIM DriveExplorer (version 2.02 or higher) or DriveTools 2000 (version 1.01 or higher) - 1203-SSS AnaCANda (version 3.001 or higher)

1-4

Getting Started

Safety Precautions
Please read the following safety precautions carefully
.

ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the associated machinery should plan or implement the installation, start-up, conguration, and subsequent maintenance of the product using a RS-485 DF1 adapter. Failure to comply may result in injury and/or equipment damage. ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove all power from the PowerFlex drive, and then verify power has been removed before installing or removing a RS-485 DF1 adapter. ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must not be directly connected together via 1202-C* cables. Unpredictable behavior due to timing and other internal procedures can result if two or more devices are connected in this manner. ATTENTION: Risk of injury or equipment damage exists. If the RS-485 DF1 adapter is transmitting control I/O to the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting an adapter. ATTENTION: Risk of injury or equipment damage exists. Parameter 10 - [Comm Flt Action] lets you determine the action of the adapter and connected PowerFlex drive if communications are disrupted. By default, this parameter faults the PowerFlex drive. You can set this parameter so that the PowerFlex drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage. ATTENTION: Risk of injury or equipment damage exists. When a system is congured for the rst time, there may be unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing.

! ! ! !

Getting Started

1-5

Quick Start
This section is designed to help experienced users congure or set up the RS-485 DF1 adapter. If you are unsure how to complete a step, refer to the referenced chapter.
Step 1 Review the safety precautions for the adapter. 2 3 Verify that the PowerFlex drive is properly installed. Commission the adapter. Set a unique node address and the appropriate data rate using the switches on the adapter. If desired, you can disable the switches and use parameter settings instead. Install the adapter. Verify that the PowerFlex drive is not powered. Then, connect the adapter to the network using a RS-485 cable and to the drive using the Internal Interface cable. Use the captive screws to secure and ground the adapter to the drive. Apply power to the adapter. The adapter receives power from the drive and network. Apply power to the network and to the drive. The status indicators should be green. If there is a problem, refer to Chapter 4, Using DriveExplorer on the RS-485 Network. Congure the adapter for your application. Set the parameters for the following features as required by your application: I/O conguration. Fault actions. Apply power to the RS-485 DF1 master. Verify that the master and network are installed and functioning in accordance with RS-485 DF1 standards. Refer to Throughout This Manual Drive User Manual Chapter 2, Installing the Adapter Chapter 2, Installing the Adapter Chapter 2, Installing the Adapter Chapter 3, Conguring the Adapter

1-6

Getting Started

Modes of Operation
The adapter uses four status indicators to report its operating status. They can be viewed on the adapter or through the drive cover. See Figure 1.2.
Figure 1.2 Status Indicators (location on drive may vary)

PWR

STS

PORT MOD NET A NET B

Status Indicator PORT

Status(1) Green Flashing Green

Description Normal Operation. The adapter is properly connected and is communicating with the drive. The adapter is in the process of establishing a connection to the drive. This status indicator will turn solid green or red. Normal Operation. The adapter is operational and is transferring I/O data. Normal Operation. The adapter is operational, but is not transferring I/O data. Normal Operation. The adapter is properly connected and communicating on the network. The adapter is properly connected, but is not communicating with any devices on the network. Module receiving data.

MOD

Green Flashing Green Green Flashing Green Flashing Green

NET A

(1)

NET B

If all status indicators are off, the adapter is not receiving power. Refer to Chapter 2, Installing the Adapter, for instructions on installing the adapter. If any other conditions occur, refer to Chapter 4, Using DriveExplorer on the RS-485 Network.

Chapter 2

Installing the Adapter


Chapter 2 provides instructions for installing the adapter on a PowerFlex drive.
Topic Preparing for an Installation Commissioning the Adapter Connecting the Adapter to the Network Connecting the Adapter to the Drive Applying Power Page 2-1 2-1 2-3 2-4 2-6

Preparing for an Installation


Before installing the RS-485 DF1 adapter: Verify that you have all required equipment. Refer to Chapter 1, Getting Started.

Commissioning the Adapter


To commission the adapter, you must set a unique node address, the data rate used by the network and the error checking method. (Refer to the Glossary for details). Important: New settings are recognized only when power is applied to the adapter or the adapter is reset. If you change a setting, cycle power or perform a reset. ATTENTION: Risk of equipment damage exists. The RS-485 DF1 adapter contains ESD (Electrostatic Discharge) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage, Publication 8000-4.5.2.

2-2

Installing the Adapter 1. Set the node address switches.


Figure 2.1 Setting the Node Address
2 1 0 9 8 7 6 3 4 5 1 0 9 8 7 6 2 3 4 5

Tens Digit

Ones Digit

Setting 0 99

Description Node address used by the adapter if switches are enabled. The default switch setting is 1. Important: If the Data Rate switch is set to PGM (Program), the adapter will use the setting of Parameter 03 - [DF1 Addr Cfg] for the node address. The default parameter setting is 1. Refer to Chapter 3, Conguring the Adapter.

2. Set the Data Rate switch.


Figure 2.2 Setting the Data Rate

9600 19.2K 4800 38.4K 2400 1200 PGM

Setting 1200 2400 4800 9600 19.2K 38.4K PGM

Description The adapter is set to the respective data rate.

The adapter uses the setting of Parameter 05 - [DF1 Rate Cfg] for the data rate. 9600 is the default parameter setting. Refer to Chapter 3, Conguring the Adapter.

Installing the Adapter

2-3

Connecting the Adapter to the Network


ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing an adapter. 1. Remove power from the drive. 2. Use static control precautions. 3. Connect an RS-485 cable to the network, and route it through the bottom of the PowerFlex drive. 4. Connect a 6-pin linear plug to the RS-485 cable.
Figure 2.3 Example Network Connections Node 1
O M SH IE G LD N D R A M R A M TE TE

Node 2
O M SH IE G LD N D R A M TE

Node "n"
O M SH IE G LD N D

Terminal GND SHIELD COM B A TERM

Signal CHASSIS GND(1) SHIELD COMMON Signal B Signal A TERMINATION(2)

Function Shield GND termination Shield RC termination Signal Common Tx Rx DTx Rx D+ Signal RC termination

(1) The shield must be grounded at a single point on the network (jumper terminals SHIELD and GND). (2) Jumper Terminals TERM and A on the adapters at end of the RS-485 network. This enables a built in RC termination network on the adapter.

5. Connect the cable to the adapter.

2-4

Installing the Adapter

Connecting the Adapter to the Drive


1. Remove power from the drive. 2. Use static control precautions. 3. Connect the Internal Interface cable to the DPI port on the drive and then to DPI connector on the adapter.
Figure 2.4 DPI Ports and Internal Interface Cables

RS-485 DF1 Adapter

PowerFlex 70 Drive

PowerFlex 700 Drive 0 - 1 Frame # Description 15.24 cm (6 in.) Internal Interface cable DPI connector #

PowerFlex 700 Drive 2 Frame & Larger Description RS-485 connector 2.54 cm (1 in.) Internal Interface cable

Installing the Adapter 4. On a PowerFlex 70, fold the Internal Interface cable behind the adapter and mount the adapter on the drive using the four captive screws. On a PowerFlex 700, just mount the adapter on the drive using the four captive screws to secure and ground it to the drive.

2-5

Important: All screws must be tightened since the adapter is grounded through a screw. Recommended torque is 0.9 N-m (8.0 lb.-in.)
Figure 2.5 Mounting the Adapter

Drive Adapter
Internal Interface cable folded behind the adapter and in front of drive. PowerFlex 70 Drive Adapter mounts in drive.

PowerFlex 700 Drive (0 - 1 Frames) Adapter mounts on door.

PowerFlex 700 Drive (2 Frame & Larger) Adapter mounts in drive.

2-6

Installing the Adapter

Applying Power
ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify that parameter settings and switch settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive. 1. Close the door or reinstall the cover on the drive. The status indicators can be viewed on the front of the drive after power has been applied. 2. Ensure that the adapter will have a unique address on the network and is set at the correct data rate. If a new data rate or address is needed, reset its switches (Refer to Commissioning the Adapter in this chapter.) 3. Apply power to the PowerFlex drive. The adapter receives its power from the connected drive. When you apply power to the product for the rst time, the status indicators should be green after an initialization. If there is a problem, refer to Chapter 4, Using DriveExplorer on the RS-485 Network. 4. If the data rate switch is set to PGM, use a conguration tool to set the data rate and node address parameters in the adapter (Chapter 3, Conguring the Adapter). 5. Verify that the master and network are installed and functioning in accordance with RS-485 DF1 standards.

Chapter 3

Conguring the Adapter


Chapter 3 provides instructions and information for setting the parameters in the adapter.
Topic Conguration Tools Using the PowerFlex HIM Setting the Node Address Setting the Data Rate Page 3-1 3-3 3-4 3-4 Topic Setting a Fault Action Resetting the Adapter Viewing the Adapter Conguration Page 3-5 3-7 3-8

For a list of parameters, refer to Appendix B, Adapter Parameters. For denitions of terms in this chapter, refer to the Glossary.

Conguration Tools
The RS-485 DF1 adapter stores parameters and other information in its own non-volatile memory. You must, therefore, access the adapter to view and edit its parameters. The following tools can be used to access the adapter parameters:
Tool DriveExplorer Software (version 2.02 or higher) DriveExecutive Software (version 1.01 or higher) PowerFlex HIM Refer To: DriveExplorer Getting Results Manual, Publication 9306-5.3, or the online help DriveTools 2000 Online Help page 3-3

3-2

Conguring the Adapter

Using DriveExplorer
With DriveExplorer software, you can edit parameters in both the 1203-SSS serial converter and the connected product. On PowerFlex 70 and PowerFlex 700 drives (or other DPI products), you can also edit parameters in any of the attached peripherals, such as the 20-COMM-S. DriveExplorer Lite is shipped with the 1203-SSS serial converter. It is a free, limited-feature version of DriveExplorer.

DriveExplorer Lite Quick Start


This section is designed to help users start using DriveExplorer Lite. If you are unsure how to complete a step, refer to the online help (select Help > Help Topics) or the DriveExplorer Getting Results Manual, Publication 9306-5.2, which is included on the CD.
Step 1 Select Explore > Congure Communication. Select the communications port and baud rate that you are using. Select either checksum and accept the default time for the time-out. 2 Select Explore > Connect > Local. A node eventually appears under Devices. 3 In the left pane, click the + signs to expand the tree. Click the product or serial converter to display parameters in the right pane. Double-click a parameter to edit it. Figure 3.1 DriveExplorer

Conguring the Adapter

3-3

Using the PowerFlex HIM


If your drive has either an LED or LCD HIM (Human Interface Module), access parameters in the adapter as shown below. It is recommended that you read through the steps for your HIM before performing the sequence. For additional HIM information, refer to your PowerFlex Drive User Manual or the HIM Quick Reference card.

Using an LED HIM


Step 1. Press the ALT and then Sel (Device) to display the Device Screen. 2. Press the Up Arrow or Down Arrow to scroll to the 20-COMM-S adapter. Letters represent les in the drive, and numbers represent ports. The adapter is usually connected to port 5. Press the Enter key to enter your selection. A parameter database is constructed, and then the rst parameter is displayed. Edit the parameters using the same techniques that you use to edit drive parameters. Key(s)
Device
ALT Sel

Example Screens

OR

3.

4.

Using an LCD HIM


Step Key(s) 1. In the main menu, press the Up OR Arrow or Down Arrow to scroll to Device Select. 2. 3. Press Enter to enter your selection. Press the Up Arrow or Down Arrow to scroll to the 20-COMM-S adapter. Press Enter to select the 20-COMM-S adapter. The main menu for the adapter is displayed. Edit the parameters using the same techniques that you use to edit drive parameters. OR Example Screens F-> Stopped Auto 0.00 Hz Main Menu: Diagnostics Parameter Device Select

4.

5.

Port 5 Device 20-COMM-S Main Menu: Diagnostics Parameter Device Select

3-4

Conguring the Adapter

Setting the Node Address


If the adapter Data Rate switch is set to PGM, the value of Parameter 03 - [DF1 Addr Cfg] determines the node address. 1. Set the value of Parameter 03 - [DF1 Addr Cfg] to a unique node address.
Figure 3.2 RS-485 DF1 Node Address Screen on an LCD HIM Port 5 Device 20-COMM-S Parameter #: 3 DF1 Addr Cfg 1 0 <> 99 Default = 1

2. Reset the adapter. Refer to the Resetting the Adapter section in this chapter.

Setting the Data Rate


If the adapter Data Rate switch is set to PGM, the value of Parameter 05 - [DF1 Rate Cfg] determines the RS-485 DF1 data rate. Your application may require a different setting. 1. Set the value of Parameter 05 - [DF1 Rate Cfg] to the data rate at which your network is operating.
Figure 3.3 RS-485 DF1 Data Rate Screen on an LCD HIM Port 5 Device 20-COMM-S Parameter #: 5 DF1 Rate Cfg 3 9600 bps Value 0 1 2 3 4 5 Baud Rate 1200 bps 2400 bps 4800 bps 9600 bps (default) 19.2 kbps 38.4 kbps

2. Reset the adapter. Refer to the Resetting the Adapter section in this chapter.

Conguring the Adapter

3-5

Setting the CRC/BCC Selection


Two types of error checking methods are used with the DF1 protocol, Cyclic Redundancy Check (CRC) and (BCC). 1. Set the value of Parameter 24 - [CRC/BCC] to the method used by the network.
Figure 3.4 RS-485 DF1 CRC/BCC Screen on a LCD HIM Port 5 Device 20-COMM-S Parameter #: 24 CRC/BCC Cfg 0 BCC Value Selection 0 BCC (default) 1 CRC

Setting a Fault Action


By default, when communications are disrupted (for example, a cable is disconnected) or the scanner is idle, the drive responds by faulting if it is using I/O from the network. You can congure a different response to communication disruptions using Parameter 10 - [Comm Flt Action]. ATTENTION: Risk of injury or equipment damage exists. Parameter 10 - [Comm Flt Action] lets you determine the action of the adapter and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set the parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage.

3-6

Conguring the Adapter

To change the fault action


Set the values of Parameters 10 - [Comm Flt Action] to the desired responses:
Value 0 1 2 3 4 Action Fault (default) Stop Zero Data Hold Last Send Flt Cfg Description The drive is faulted and stopped. (Default) The drive is stopped, but not faulted. The drive is sent 0 for output data after a communications disruption. This does not command a stop. The drive continues in its present state after a communications disruption. The drive is sent the data that you set in the fault conguration parameters (Parameters 14 - [Flt Cfg Logic] through 23 - [Flt Cfg D2 In]).

Figure 3.5 Fault Action Screens on an LCD HIM Port 5 Device 20-COMM-S Parameter #: 10 Comm Flt Action 0 Fault

Changes to this parameter takes effect immediately. A reset is not required.

To set the fault conguration parameters


If you set Parameter 10 - [Comm Flt Action] to the send Flt Cfg, the values in the following parameters are sent to the drive after a communications fault occurs. You must set these parameters to values required by your application.
Parameter 14 15 16 23 Name Flt Cfg Logic Flt Cfg Ref Flt Cfg x1 In or Flt Cfg x2 In Description A 16-bit value sent to the drive for Logic Command. A 32-bit value (0 4294967295) sent to the drive as a Reference or Datalink. Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most signicant word of the value must be set to zero (0) or a fault will occur.

Changes to these parameters take effect immediately. A reset is not required.

Conguring the Adapter

3-7

Resetting the Adapter


Changes to switch settings on some adapter parameters require that you reset the adapter before the new settings take effect. You can reset the adapter by cycling power to the drive or by using the following parameter: Set the Parameter 09 - [Reset Module] to Reset Module:

ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting a connected adapter.
Figure 3.6 Reset Screen on an LCD HIM Port 5 Device 20-COMM-S Parameter #: 9 Reset Module 1 Reset Module Value 0 1 2 Description Ready (Default) Reset Module Set Defaults

When you enter 1 = Reset Module, the adapter will be immediately reset. When you enter 2 = Set Defaults, the adapter will set all adapter parameters to their factory-default settings. A reset is still required for some parameter changes to take effect. The value of this parameter will be restored to 0 = Ready after the adapter is reset.

3-8

Conguring the Adapter

Viewing the Adapter Conguration


The following parameters provide information about how the adapter is congured. You can view these parameters at any time.
Number 01 02 04 Name DPI Port DPI Data Rate DF1 Addr Act Description The port on the drive to which the adapter is connected. Usually, it is on Port 5. The data rate used by DPI in the drive. It is set in the drive, and the adapter detects it. The node address used by the adapter. This will be one of the following values: The address set by the Node Address switches. The value of Parameter 03 - [DF1 Addr Cfg] if the switches have been disabled. In order for either of the above to take effect, the adapter has to be reset or power cycled. The data rate used by the adapter. This will be one of the following values: The data rate set by the Data Rate switch. The value of Parameter 05 - [DF1 Rate Cfg] if the switches have been disabled. In order for either of the above to take effect, the adapter has to be reset or power cycled. The size of the Reference/Feedback (16 bits or 32 bits). It is set in the drive and the adapter automatically uses the correct size. The size of the Datalinks (16 bits or 32 bits). It is set in the drive and the adapter automatically uses the correct size. Source from which the adapter node address and data rate are taken. This will be either switches on the adapter or parameters in EEPROM. It is determined by the settings of the switches on the adapter. The I/O used by the adapter. This value is the same as Parameter 13 - [DPI I/O Cong] unless the parameter was changed and the adapter was not reset. Bit Denitions Bit 7 6 5 4 3 2 1 0 0 = Cmd/Ref Default x x x 0 0 0 0 1 1 = Datalink A 2 = Datalink B 3 = Datalink C 4 = Datalink D 5 = Not Used 6 = Not Used 7 = Not Used Actual Checksum or CRC selection. Determines if the adapter ignores messages with duplicate TNS IDs. Normally set to Enable (default). Set to Disable if using a ProSoft 3150-DFM module or any device which does not increment the TNS ID.

06

DF1 Rate Act

07 08 11

Ref/Fdbk Size Datalink Size Active Cfg

13

DPI I/O Act

25 26

CRC/BCC Act Dup Msg Detect

Chapter 4

Using DriveExplorer on the RS-485 Network


Chapter 4 provides instructions for conguring DriveExplorer (version 2.02 or higher) to access PowerFlex drives on the RS-485 network (Figure 4.1).
Figure 4.1 Example RS-485 DF1 Network

Drive Explorer
Select Explore > Connect > Network (Figure 4.2).
Figure 4.2

Select Single to connect to a single node on the network. Select Multiple to connect to multiple nodes and enter the node range (Figure 4.3). Ofine or Online text will be displayed next to the number to show if the particular node is present on the network. In this example, two nodes with DFI addresses of 1 and 2 will be accessed. Click Connect.

4-2

Using DriveExplorer on the RS-485 Network


Figure 4.3

DriveExplorer will perform a search within the range of the selected nodes and list them (Figure 4.4).
Figure 4.4

Click on each node to have DriveExplorer perform a device read (Figure 4.5). A + will appear to the left of the node upon completion.
Figure 4.5

Using DriveExplorer on the RS-485 Network

4-3

Click on the + for each node to expand the information (Figure 4.6).
Figure 4.6

Click on the desired item to access its parameters (Figure 4.7).


Figure 4.7

4-4

Using DriveExplorer on the RS-485 Network

Notes:

Chapter 5

Troubleshooting
Chapter 5 contains troubleshooting information.
Topic Locating the Status Indicators PORT Status Indicator MOD Status Indicator Page 5-1 5-2 5-3 Topic Net A Status Indicator Module Diagnostic Items Viewing and Clearing Events Page 5-3 5-5 5-7

Locating the Status Indicators


The RS-485 DF1 adapter has four status indicators. They can be viewed on the adapter or through the drive cover. See Figure 5.1.
Figure 5.1 Status Indicators (location on drive may vary)


PORT MOD NET A NET B

PWR

STS

Number

Status Indicator PORT MOD NET A NET B

Description DPI Connection Status Adapter Status DF1 Status DF1 Trafc

Page 5-2 5-3 5-3 5-4

5-2

Troubleshooting

PORT Status Indicator


Status Off Cause The adapter is not powered or is not connected properly to the drive. Flashing The adapter is not receiving a Red ping message from the drive. Solid The drive has refused an Red I/O connection from the adapter. Another DPI peripheral is using the same DPI port as the adapter. Corrective Action Securely connect the adapter to the drive using the ribbon cable. Apply power to the drive. Verify that cables are securely connected. Cycle power to the drive. Important: Cycle power to the product after making any of the following corrections. Verify that all DPI cables are securely connected and not damaged. Replace cables if necessary. Verify that the DPI Host supports Datalinks. Congure the adapter to use a Datalink that is not already being used by another peripheral. Connect the adapter to a product that supports Allen-Bradley DPI communications (for example, PowerFlex drives). No Action. This status indicator will turn solid red. Verify Parameter 12 - [DPI I/O Cong] settings. Normal behavior if no DPI I/O is enabled. No Action.

Orange

The adapter is connected to a product that does not support Allen-Bradley DPI communications. Flashing The adapter is establishing an Green I/O connection to the drive or Parameter 12 - [DPI I/O Cong] is congured for all I/O disabled. Solid The adapter is properly Green connected and is communicating with the drive.

Troubleshooting

5-3

MOD Status Indicator


Status Off Cause The adapter is not powered. Corrective Action Securely connect the adapter to the drive using the ribbon cable. Apply power to the drive. Clear faults in the adapter. Cycle power to the drive. If cycling power does not correct the problem, the parameter settings may have been corrupted. Reset defaults and recongure the module. If resetting defaults does not correct the problem, ash the adapter with the latest rmware release. Cycle power to the drive. Replace the adapter. Place the scanner in RUN mode. Program the controller to recognize and transmit I/O to the adapter. Congure the adapter for the program in the controller. Normal behavior if no DPI I/O is enabled. No action.

Flashing The adapter has failed the Red rmware test.

Solid Red Flashing Green

The adapter has failed the hardware test. The adapter is operational, but is not transferring I/O data.

Solid Green

The adapter is operational and transferring I/O data.

Net A Status Indicator


Status Off Cause Corrective Actions The adapter is not powered Securely connect the adapter to the drive or adapter is not connected using the Internal Interface cable. properly to the network. Correctly connect the RS-485 cable to the DF1 plug. Apply power to the drive. Flashing The adapter is properly Place the controller in RUN mode, or apply Green connected, but is not power to the peer device that will send I/O. communicating with any Program a controller or peer device to devices on the network. recognize and transmit I/O to the adapter. Congure the adapter for the program in the controller or the I/O from the peer device. Solid The adapter is properly No action required. Green connected and communicating on the network. Flashing A network connection has Place the scanner in RUN mode, or apply Red timed out. power to the peer device that will send I/O. Check the amount of trafc on the network.

5-4

Troubleshooting

Net B Status Indicator


Status Off Cause The adapter is not receiving data over the network. Corrective Actions Place the controller in RUN mode, or apply power to the peer device that will send I/O. Program a controller or peer device to recognize and transmit I/O to the adapter. Congure the adapter for the program in the controller or the I/O from the peer device. No action required.

Flashing The adapter is receiving Green data over the network.

Troubleshooting

5-5

Module Diagnostic Items


The following diagnostic items can be accessed using DriveExplorer (version 2.01 or higher), DriveExecutive (version 1.01 or higher) or PowerFlex LCD HIM (version 2.001 or higher).
No. Name 1 Common Logic Cmd 2 Prod Logic Cmd 3 4 5 6 7 Reference Common Logic Sts Product Logic Status Feedback Datalink A1 In Description Current value of the Common Logic Command being transmitted to the Host by this peripheral. Current value of the Product Specic Logic Command being transmitted to the Host by this peripheral. Current value of the Product Specic Reference being transmitted to the Host by this peripheral. Current value of the Common Logic Status being received from the Host by this peripheral. Current value of the Product Specic Logic Status being received from the Host by this peripheral. Current value of the Product Specic Feedback being received from the Host by this peripheral. Current value of Datalink A1 In being transmitted to the Host by this peripheral (if not using Datalink A1, this parameter should have a value of zero). Current value of Datalink A2 In being transmitted to the Host by this peripheral (if not using Datalink A2, this parameter should have a value of zero). Current value of Datalink B1 In being transmitted to the Host by this peripheral (if not using Datalink B1, this parameter should have a value of zero). Current value of Datalink B2 In being transmitted to the Host by this peripheral (if not using Datalink B2, this parameter should have a value of zero). Current value of Datalink C1 In being transmitted to the Host by this peripheral (if not using Datalink C1, this parameter should have a value of zero). Current value of Datalink C2 In being transmitted to the Host by this peripheral (if not using Datalink C2, this parameter should have a value of zero). Current value of Datalink D1 In being transmitted to the Host by this peripheral (if not using Datalink D1, this parameter should have a value of zero). Current value of Datalink D2 In being transmitted to the Host by this peripheral (if not using Datalink D2, this parameter should have a value of zero). Current value of Datalink A1 being received from the Host by this peripheral. Current value of Datalink A2 being received from the Host by this peripheral. Current value of Datalink B1 being received from the Host by this peripheral. Current value of Datalink B2 being received from the Host by this peripheral. Current value of Datalink C1 being received from the Host by this peripheral. Current value of Datalink C2 being received from the Host by this peripheral. Current value of Datalink D1 being received from the Host by this peripheral.

Datalink A2 In

Datalink B1 In

10

Datalink B2 In

11

Datalink C1 In

12

Datalink C2 In

13

Datalink D1 In

14

Datalink D2 In

15 16 17 18 19 20 21

Datalink A1 Out Datalink A2 Out Datalink B1 Out Datalink B2 Out Datalink C1 Out Datalink C2 Out Datalink D1 Out

5-6

Troubleshooting

Module Diagnostic Items (continued)


22 23 24 25 26 27 28 29 30 31 32 33 Datalink D2 Out Field Flash Cnt DPI Rx Errors DPI Tx Errors Clear DF1 Counts DF1 Packets Sent DF1 Packets Rcvd Undelivered Msgs ENQs Received NAK Bad Packet NAK No Memory Duplicate Msgs Current value of Datalink D2 being received from the Host by this peripheral. Current value of the Field Flash Counter. Current value of the DPI CAN Receive Error Counter register. Current value of the DPI CAN Transmit Error Counter Register. Ready = No Action Enable = Clears all DF1 Counter Parameters Reports the number of DF1 packets sent by the Peripheral. Reports the number of DF1 packets received by the Peripheral. Reports the number of DF1 packets that were sent by the Peripheral, but not acknowledged. Reports the number of ENQ requests received by the Peripheral. Reports the number of responses received (BCC or CRC calculated by Peripheral did not match that in the packet). Report the number of requests received by the Peripheral that could not be processed due to insufcient memory available to buffer the incoming packet. Reports the number of duplicate messages received the Peripheral. A duplicate message is detected when the SRC, TNS and CMD elds of two consecutive messages are identical. I/O Communication timeout value (secs) before Pr.10 [Comm Flt Action] is taken. The value of the Data Rate SW on the adapter. The value of the Node Address SW on the adapter.

34 35 36

PCCC I/O Timeout Data Rate SW Node Address SW

Troubleshooting

5-7

Viewing and Clearing Events


The adapter maintains an event queue that reports the history of its actions. You can view the event queue using an LCD PowerFlex HIM, DriveExplorer (2.01 or higher) software, or DriveExecutive (1.01 or higher) software.

To view and clear events


Step Keys Viewing Events 1. Access parameters in the adapter. Refer to Using the PowerFlex HIM in Chapter 3. 2. 3. 4. Press the Up Arrow or Down Arrow to scroll to Diagnostics. Press Enter to display the Diagnostics menu in the adapter. Repeat steps 2 and 3 to enter the Events option and then View Event Queue option. Press the Up Arrow or Down Arrow to scroll through the events. The most recent event is Event 1. OR OR Event Q: 1 Ping Time Flt E3 Example Screen Main Menu: Diagnostics Parameter Device Select

5.

Clearing Events 1. Access parameters in the Adapter. Refer to Using the PowerFlex HIM in Chapter 3. 2. 3. 4. Press the Up Arrow or Down Arrow to scroll to Diagnostics. Press Enter to display the Diagnostics menu in the adapter. Repeat steps 2 and 3 to enter the Events option and then the Clr Event option or Clear Event Queue option. A message will pop up to conrm that you want to clear the message or queue. Press Enter to clear all events out of the event queue. All event queue entries will then display No Event. Dgn: Events View Event Queue Clear Event Clear Event Queue OR

5.

5-8

Troubleshooting

Events
Many events in the Event queue occur under normal operation. If you encounter unexpected communications problems, the events may help you or Allen-Bradley personnel may troubleshoot the problem. The following events may appear in the event queue:
Code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Event Description No Event Empty event queue entry. DPI Bus Off Flt A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise. Ping Time Flt A ping message was not received on DPI within the specied time. Port ID Flt The adapter is not connected to a correct port on a DPI product. Port Change The DPI port changed. Flt Host Sent The DPI product issued this because it was reset. Reset EEPROM Sum The EEPROM in the adapter is corrupt. Flt Online @ The adapter and DPI product are communicating at 125 kbps. 125 kbps Online @ The adapter and DPI product are communicating at 500 kbps. 500 kbps Bad Host Flt The adapter was connected to an incompatible product. Dup. Port Flt Another peripheral with the same port number is already in use. Type 0 Login The adapter has logged in for type 0 control. Type 0 Time The adapter has not received a type 0 status message within Flt the specied time. DL Login The adapter has logged into a Datalink. DL Reject Flt The Host rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral. DL Time Flt The adapter has not received a Datalink message within the specied time. Control The adapter has sent a Soft Control Disable command to the Disabled DPI product. Control The adapter has sent a Soft Control Enable command to the Enabled DPI product. PCCC IO Time The adapter has not received a PCCC control message within Flt the specied time-out interval. Normal The adapter successfully started up. Startup Message A Client-Server message sent by the peripheral was not Timeout completed.

Troubleshooting

5-9

Events (continued)
Code 22 23 24 25 26 27 Event DPI Fault Msg DPI Fault Clear Flt Cfg Error Description The DPI Host has faulted. The DPI Host transitions from a faulted to a non-faulted state.

At least one of the Fault Conguration parameters contains a value greater than 65535 and the DPI product expects a 16-bit value. DF1 NAK NAK received. Manual Reset The module was reset by the user. Language The language text memory segment is corrupt. CRC Bad

5-10

Troubleshooting

Notes:

Appendix A

Specications
This chapter presents the specications for the adapter.
Topic Communications Electrical Mechanical Page A-1 A-1 A-1 Topic Page Environmental A-2 Regulatory Compliance A-2

Communications
Network Protocol Data Rates Drive Protocol Data Rates DF1 1200, 2400, 4800, 9600, 19.2K, 38.4K, PGM The PGM (Program) setting on the switch is used to set the data rate using the adapter parameter. DPI 125K or 500K

Electrical
Consumption Drive 150 mA at 5 Vdc supplied through the drive

Mechanical
Dimensions Height Length Width Weight 16 mm (0.625 inches) 86 mm (3.34 inches) 81 mm (3.16 inches) 60g (2 oz.)

A-2

Specications

Environmental
Temperature Operating Storage Relative Humidity Atmosphere -10 to 50C (14 to 149F) -40 to +85C (-40 to 185F) -5 to 95% non-condensing Important: Adapter must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the adapter is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.

Regulatory Compliance
UL CE 508C and CUL EN61800-3

Appendix B

Adapter Parameters
Appendix B provides information about the RS-485 DF1 adapter parameters.
Topic Page About Parameter Numbers B-1 Parameter List B-1

About Parameter Numbers


The parameters in the adapter are numbered consecutively. However, depending on which conguration tool you use, they may have different numbers.
Conguration Tool DriveExplorer DriveExecutive HIM Numbering Scheme The adapter parameters begin with parameter 1. For example, Parameter 01 - [DPI Port] is parameter 1 as indicated by this manual.

Parameter List
Parameter No. Name and Description 01 [DPI Port] Port to which the adapter is connected. This will usually be port 5. 02 Details Default: Minimum: Maximum: Type: [DPI Data Rate] Default: Data rate used by the drive. This data rate is set in Values: the drive, and the adapter detects it. Type: [DF1 Addr Cfg] Default: Node address if the Data Rate switch is set to Minimum: PGM (Program). Maximum: Type: Reset Required: [DF1 Addr Actual] Default: DF1 node address actually used by the adapter. Minimum: Maximum: Type:

03

04

0 0 7 Read Only 0 = 125 kbps 0 = 125 kbps 1 = 500 kbps Read Only 1 0 254 Read/Write Yes 1 0 254 Read Only

B-2

Adapter Parameters

Parameter No. Name and Description 05 [DF1 Rate Cfg] DF1 data rate if the data rate switch is set to PGM (Program).

Details Default: Values:

06

[DF1 Rate Actual] DF1 data rate actually used by the adapter.

Type: Reset Required: Default: Values:

07

[Ref/Fdbk Size] Size of the Reference/Feedback (determined by drive).

Type: Default: Value:

08

Type: [Datalink Size] Default: Size of each Datalink word (determined by drive). Values: [Reset Module] No action if set to Ready. Resets the adapter if set to Reset Module. Restores the adapter to its factory default settings if set to Set Defaults. This parameter is a command. It will be reset to 0 = Ready after the command has been performed. Type: Default: Values Type: Reset Required:

09

3 = 9600 bps 0 = 1200 bps 1 = 2400 bps 2 = 4800 bps 3 = 9600 bps 4 = 19.2 kbps 5 = 38.4 kbps Read/Write Yes 3 = 9600 bps 0 = 1200 bps 1 = 2400 bps 2 = 4800 bps 3 = 9600 bps 4 = 19.2 kbps 5 = 38.4 kbps Read Only 0 = 16-bit 0 = 16-bit 1 = 32-bit Read Only 0 = 16-bit 0 = 16-bit 1 = 32-bit Read Only 0 = Ready 0 = Ready 1 = Reset Module 2 = Set Defaults Read/Write No

!
10

ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting I/O that controls the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting a connected adapter. 0 = Fault 0 = Fault 1 = Stop 2 = Zero Data 3 = Hold Last 4 = Send Flt Cfg Read/Write No

Default: [Comm Flt Action] Values: Action that the adapter and drive take if the adapter detects that RS-485 DF1 communications have been disrupted. This setting is effective only if I/O that controls the drive is transmitted through the adapter. Type: Reset Required:

ATTENTION: Risk of injury or equipment damage exists. Parameter 10 - [Comm Flt Action] lets you determine the action of the adapter and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage.

Adapter Parameters
Parameter No. Name and Description 11 [Active Cfg] Source from which the adapter node address and data rate are taken. This will either be switches on the adapter or parameters in EEPROM. It is determined by the settings of the switches on the adapter. 12 [DPI I/O Cong] I/O that is transferred through the adapter.

B-3

Details Default: Values: Type: Default: Bit Values: Type: Reset Required: Bit Denitions 0 = Cmd/Ref 1 = Datalink A 2 = Datalink B 3 = Datalink C 4 = Datalink D 5 = Not Used 6 = Not Used 7 = Not Used Default: Bit Values:

0 = Switches 0 = Switches 1 = EEPROM Read Only xxx0 0001 0 = I/O disabled 1 = I/O enabled Read/Write Yes

Bit 7 6 5 4 3 2 1 0 Default x x x 0 0 0 0 1

13

14

15

[DPI I/O Active] xxx0 0001 I/O that the adapter is actively transmitting. The 0 = I/O disabled value of this parameter will usually be equal to the 1 = I/O enabled value of Parameter 12 - DPI I/O Cong. Type: Read Only Bit Denitions Bit 7 6 5 4 3 2 1 0 0 = Cmd/Ref Default x x x 0 0 0 0 1 1 = Datalink A 2 = Datalink B 3 = Datalink C 4 = Datalink D 5 = Not Used 6 = Not Used 7 = Not Used [Flt Cfg Logic] Default: 0000 0000 0000 0000 Sets the Logic Command data that is sent to the Minimum: 0000 0000 0000 0000 drive if the following is true: Maximum: 1111 1111 1111 1111 Parameter 10 - [Comm Flt Action] is set to Type: Read/Write Send Flt Cfg and communications are Reset Required: No disrupted. The bit denitions will depend on the product to which the adapter is connected. [Flt Cfg Ref] Default: 0 Sets the Reference data that is sent to the drive if Minimum: 0 the following is true: Maximum: 4294967295 Parameter 10 - [Comm Flt Action] is set to Type: Read/Write Send Flt Cfg and communications are Reset Required: No disrupted. Important: If the drive uses a 16-bit Reference, the most signicant word of this value must be set to zero (0) or a fault will occur.

B-4

Adapter Parameters

Parameter No. Name and Description 16 [Flt Cfg A1] 17 [Flt Cfg A2] 18 [Flt Cfg B1] 19 [Flt Cfg B2] 20 [Flt Cfg C1] 21 [Flt Cfg C2] 22 [Flt Cfg D1] 23 [Flt Cfg D2] Sets the data that is sent to the Datalink in the drive if the following is true: Parameter 10 - [Comm Flt Action] is set to Send Flt Cfg and communications are disrupted.

Details Default: Default: Default: Default: Default: Default: Default: Default: Minimum: Maximum: Type: Reset Required:

0 0 0 0 0 0 0 0 0 4294967295 Read/Write No

24

Important: If the drive uses 16-bit Datalinks, the most signicant word of this value must be set to zero (0) or a fault will occur. Default: 0 = BCC [CRC/BCC Cfg] Bit Values: 0 = BCC Techniques for error detection in data 1 = CRC communications. Must match the technique used Read/Write by the software or controller communicating with Type: Reset Required: Yes the adapter. [CRC/BCC Act] Actual checksum or CRC selection. [Dup Msg Detect] Determines if the adapter ignores duplicate messages. Normally set to Enable (default). Set to Disable if using a ProSoft 3150-DFM module or any device which does not increment the TNS ID. Default: Bit Values: Type: Default: Bit Values: Type: Reset Required: 0 = BCC 0 = BCC 1 = CRC Read Only 1 = Enable 0 = Disable 1 = Enable Read/Write No

25

26

Appendix C

Logic Command/Status Words


Appendix C provides the denitions of the Logic Command/Logic Status words that are used for some products that can be connected to the RS-485 DF1 adapter. If you do not see the Logic Command/Logic Status for the product that you are using, refer to your products documentation.

PowerFlex 70 and PowerFlex 700 Drives


Logic Command Word
Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description x Stop 0 = Not Stop 1 = Stop x Start* 0 = Not Start 1 = Start x Jog 0 = Not Jog 1 = Jog x Clear 0 = Not Clear Faults Faults 1 = Clear Faults x x Direction 00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control x Local 0 = No Local Control Control 1 = Local Control x MOP 0 = Not Increment Increment 1 = Increment x x Accel Rate 00 = No Command 01 = Accel Rate 1 Command 10 = Accel Rate 2 Command 11 = Hold Accel Rate x x Decel Rate 00 = No Command 01 = Decel Rate 1 Command 10 = Decel Rate 2 Command 11 = Hold Decel Rate x x x Reference 000 = No Command Select 001 = Ref. 1 (Ref A Select) 010 = Ref. 2 (Ref B Select) 011 = Ref. 3 (Preset 3) 100 = Ref. 4 (Preset 4) 101 = Ref. 5 (Preset 5) 110 = Ref. 6 (Preset 6) 111 = Ref. 7 (Preset 7) x MOP 0 = Not Decrement Decrement 1 = Decrement * A 0 = Not Stop condition (logic 0) must rst be present before a 1 = Start condition will start the drive.

C-2

Logic Command/Status Words

PowerFlex 70 and PowerFlex 700 Drives


Logic Status Word
Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status x Ready x x x x x x x x x x x Description 0 = Not Ready 1 = Ready Active 0 = Not Active 1 = Active Command 0 = Reverse Direction 1 = Forward Actual 0 = Reverse Direction 1 = Forward Accel 0 = Not Accelerating 1 = Accelerating Decel 0 = Not Decelerating 1 = Decelerating Alarm 0 = No Alarm 1 = Alarm Fault 0 = No Fault 1 = Fault At Speed 0 = Not At Reference 1 = At Reference Local 000 = Port 0 (TB) Control 001 = Port 1 010 = Port 2 011 = Port 3 100 = Port 4 101 = Port 5 110 = Port 6 111 = No Local Reference 0000 = Ref A Auto 0001 = Ref B Auto 0010 = Preset 2 Auto 0011 = Preset 3 Auto 0100 = Preset 4 Auto 0101 = Preset 5 Auto 0110 = Preset 6 Auto 0111 = Preset 7 Auto 1000 = Term Blk Manual 1001 = DPI 1 Manual 1010 = DPI 2 Manual 1011 = DPI 3 Manual 1100 = DPI 4 Manual 1101 = DPI 5 Manual 1110 = DPI 6 Manual 1111 = Jog Ref

Glossary
A
Adapter Devices such as drives, controllers, and computers usually require an adapter to provide a communication interface between them and a network such as RS-485 DF1. An adapter reads data on the network and transmits it to the connected device. It also reads data in the device and transmits it to the network. The 20-COMM-S adapter is an adapter that connects, PowerFlex drives to a RS-485 DF1 network. Adapters are sometimes also called cards, embedded communication options, gateways, modules, and peripherals.

Block Check Character (BCC) A technique for error detection in data communications. A character is added to a transmission block, which is compared with a second BCC computed by the receiver to determine if the transmission is error free. Controller A controller, also called programmable logic controller, is a solid-state control system that has a user-programmable memory for storage of instructions to implement specic functions such as I/O control, logic, timing, counting, report generation, communication, arithmetic, and data le manipulation. A controller consists of a central processor, input/ output interface, and memory. See also Scanner. Cyclic Redundancy Check (CRC) A commonly used technique for error detection in data communications. A polynomial algorith is performed on the data, and the resultant checksum is appended at the end of the frame. The receiving device performs a similar algorithm.

Data Rate The data rate is the speed at which data is transferred on the RS-485 DF1 network. Each device on a RS-485 DF1 network must be set for the same data rate. You can set the RS-485 DF1 adapter to 1200, 2400, 4800, 9600, 19.2K, or 38.4 kbps.

Glossary-2 Datalinks A Datalink is a type of pointer used by some PowerFlex drives to transfer data to and from the controller. Datalinks allow specied parameter value(s) to be accessed or changed without using explicit messages. When enabled, each Datalink consumes either four bytes or eight bytes in both the input and output image table of the controller. The drive determines the size of Datalinks. DF1 An Allen-Bradley datalink layer protocol that combines features of subcategories D1 (data transparency) and F1 (2-way simultaneous transmission with embedded responses) of ANSI x3.28 specication. DPI DPI is a second generation peripheral communication interface used by various Allen-Bradley drives and power products. It is a functional enhancement to SCANport. DPI Peripheral A device that provides an interface between DPI and a network or user. Peripheral devices are also referred to as adapters and modules. The serial converter and PowerFlex HIM are examples of DPI peripherals. DPI Product A device that uses the DPI communications interface to communicate with one or more peripheral devices. For example, a motor drive such as a PowerFlex drive is a DPI product. In this manual, a DPI product is also referred to as product or Host. DriveExplorer Software DriveExplorer software is a tool for monitoring and conguring Allen-Bradley products and adapters. It can be run on computers running Microsoft Windows 95, Windows 98, Windows NT (version 4.0 or higher), Windows CE (version 2.0 or higher), Windows ME, Windows 2000, and Windows XP operating systems. DriveExplorer (version 2.02 or higher) can be used to congure this adapter and PowerFlex drives. Information about DriveExplorer software and a free lite version can be accessed at http://www.ab.com/drives/driveexplorer.

Glossary-3 DriveExecutive Software DriveExecutive is part of the DriveTools2000 software suite designed for Microsoft Windows 95, Windows 98, Windows NT (4.0 or higher), Windows ME, Windows 2000, and Windows XP operating systems. This software suite provides a family of tools that you can use to program, monitor, control, troubleshoot, and maintain Allen Bradley products. DriveTools 2000 (version 1.01 or higher) can be used with PowerFlex drives. Information about DriveTools can be accessed at http:// www.ab.com/drives. DriveTools A software suite designed for Microsoft Windows 95, Windows 98, and Windows NT (4.0 or higher) operating systems. To fully utilize DSI products, use DriveTools 2000 version 1.01 or higher. This software suite provides a family of tools that you can use to program, monitor, control, troubleshoot, and maintain Allen-Bradley products. Information about DriveTools can be accessed at http://www.ab.com/drives.

Fault Action A fault action determines how the adapter and connected product act when a communications fault (for example, a cable is disconnected) occurs or when the scanner is switched out of run mode. The former uses a communications fault action, and the latter uses an idle fault action. Fault Conguration When communications are disrupted (for example, a cable is disconnected), the adapter and PowerFlex drive can respond with a user-dened fault conguration. The user sets the data that is sent to the drive in the fault conguration parameters (Parameters 14 - [Flt Cfg Logic] through 23 - [Flt Cfg D2]). When a fault action parameter is set to use the fault conguration and a fault occurs, the data from these parameters is sent as the Command Logic, Reference, and/or Datalink(s). Flash Update The process of updating rmware in the adapter. The adapter can be ash updated using the Xmodem protocol and a 1203-SSS Serial Converter (version 3.001 or higher).

HIM (Human Interface Module) A device that can be used to congure and control a PowerFlex drive. New HIMs (20-HIM-x) can be used to congure connected peripherals.

Glossary-4 Hold Last When communications are disrupted (for example, a cable is disconnected), the adapter and PowerFlex drive can respond by holding last. Hold last results in the drive receiving the last data received via the RS-485 DF1 connection before the disruption. If the drive was running and using the Reference from the adapter, it will continue to run at the same Reference.

I/O Data I/O data, sometimes called implicit messages or input/output, transmit time-critical data such as a Logic Command and Reference. The terms input and output are dened from the scanners point of view. Output is transmitted by the scanner and consumed by the adapter. Input is transmitted by the adapter and consumed by the scanner. Logic Command/Logic Status The Logic Command is used to control the PowerFlex drive (e.g., start, stop, direction). It consists of one 16-bit word of input to the adapter from the network. The denitions of the bits in this word depend on the drive. The Logic Status is used to monitor the PowerFlex drive (for example, operating state, motor direction). It consists of one 16-bit word of output from the adapter to the network. The denitions of the bits in this word depend on the drive.

Node Address A RS-485 DF1 network can have as many as 255 devices connected to it. Each device on the network must have a unique node address from 0 and 254. Non-Volatile Storage (NVS) NVS is the permanent memory of a device. Devices such as the adapter and drive store parameters and other information in NVS so that they are not lost when the device loses power. NVS is sometimes called EEPROM.

Programmable Controller Communications Command (PCCC) PCCC is the protocol used by some controllers to communicate with devices on a network. Some software products (i.e., DriveExplorer and DriveTools 2000), also use PCCC to communicate.

Glossary-5 Ping A ping is a message that is sent by a DPI product to its peripheral devices. They use the ping to gather data about the product, including whether it can receive messages and whether they can log in for control. PowerFlex 7-Class Drives The Allen-Bradley PowerFlex 7-Class family of drives include the PowerFlex 70 and PowerFlex 700. These drives can be used for applications ranging from 0.37 kW (0.5 HP) to 3,000 kW (4,000 HP). All PowerFlex 7-Class drives implement DPI, allowing them to use the 20-COMM-S RS-485 DF1 adapter. Programmable Controller A solid-state control system that has a user-programmable memory for storage of instructions to implement specic functions such as I/O control, logic, timing, counting, report generation, communication, arithmetic, and data le manipulation. A controller consists of central processor, input/output interface, and memory. A controller is designed as an industrial control system.

Reference/Feedback The Reference is used to send a Reference (for example, speed, frequency, torque) to the product. It consists of one word of input to the adapter from the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive. Feedback is used to monitor the speed of a product. It consists of one word of output from the adapter to the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive.

Scanner A scanner is a separate module (of a multi-module controller) or a built-in component (of a single-module controller) that provides communication with adapters connected to a network. See also Controller. Status Indicators Status indicators are LEDs that are used to report the status of the adapter, network, and drive. They are on the adapter and can be viewed on the front cover of the drive when the drive is powered.

Glossary-6

Type 0/Type 1/Type 2 Control When transmitting I/O, the adapter can use different types of messages for control. The Type 0, Type 1, Type 2 control events help Allen-Bradley personnel identify the type of messages that an adapter is using. Transaction Number (TNS) A 2-byte eld in a DF1 message packet that is used in combination with the SRC (source node of the message) and CMD (command code) bytes to uniquely identify every message packet. The TNS is typically incremented each time a new DF1 message is sent. The reply message will contain the same TNS value.

Zero Data When communications are disrupted (for example, a cable is disconnected), the adapter and drive can respond with zero data. Zero data results in the drive receiving zero as values for command data. If the drive was running and using the Reference from the adapter, it will stay running, but at zero Reference.

Index
Numerics
10-pin linear plug, 2-3 5-pin linear plug, 2-3 commissioning the adapter, 2-1 communications module, refer to adapter compatible products, 1-3 components, 1-1 conguration tools, 3-1 connecting the adapter to the network, 2-3 controller denition, G-1 CRC, B-4 Cyclic, G-1 denition, G-1

A
adapter applying power, 2-6 commissioning, 2-1 compatible products, 1-3 components, 1-1 denition, G-1 features, 1-2 grounding, 2-5 illustration, 1-1 installing, 2-1 mounting, 2-5 parameters, B-1 to B-4 resetting, 3-7 specications, A-1 tools to congure, 3-1 viewing the active conguration, 3-8 applying power to the adapter, 2-6 attentions, 1-4

D
data exchange Cyclic, G-1 data rate denition, G-1 setting with a parameter, 3-4, 3-5 setting with the switch, 2-2 Datalink Size parameter, B-2 datalinks denition, G-2 DeviceNet 10-pin linear plug, 2-3 5-pin linear plug, 2-3 cables, 2-3 connector on adapter, 1-1 denition, G-2 specication, G-2 DeviceNet adapter, refer to adapter DF1, G-2 dimensions, A-1 DN Active Cfg parameter, B-3 DN Addr Actual parameter, B-1 DN Addr Cfg parameter, B-1

B
baud rate, refer to data rate bit denitions for logic command/ status word, C-1

C
cables DeviceNet, 2-3 DPI Internal Interface, 2-4 catalog number, 1-1 Comm Flt Action parameter, B-2

Index-2 DN Rate Actual parameter, B-2 DN Rate Cfg parameter, B-2 DPI connector on adapter, 1-1 data rate, 3-8 denition, G-2 Internal Interface cable, 2-4 peripheral, G-2 products, G-2 DPI Data Rate parameter, B-1 DPI I/O Active parameter, B-3 DPI I/O Cong parameter, B-3 DPI Port parameter, B-1 DriveExplorer, 3-1, 3-2 accessing parameters with, 3-1 denition, G-2 free lite version, G-2 supported feature, 1-2 using, 3-2 drives, see PowerFlex drives drives, see SCANport or DPI products DriveTools accessing parameters with, 3-1 denition, G-3 supported feature, 1-2

F
fault action conguring an adapter, 3-5 denition, G-3 fault conguration conguring an adapter for, 3-5 denition, G-3 faulted node recovery denition, G-3 supported feature, 1-2 faults, refer to events features, 1-2 rmware release, P-2 ash update, G-3 Flt Cfg A1 - D2 parameters, B-4 Flt Cfg Logic parameter, B-3 Flt Cfg Ref parameter, B-3

G
grounding the adapter, 2-5

H
heartbeat rate denition, G-3 HIM (Human Interface Module) accessing parameters with, 3-1 denition, G-3 LCD model, 3-3 LED model, 3-3 hold last conguring an adapter for, 3-5 denition, G-4

E
EEPROM, refer to Non-Volatile Storage (NVS) equipment required, 1-3 Events, 5-9 events clearing, 5-7 list of, 5-8 viewing, 5-7

I
I/O denition, G-4

Index-3 installation applying power to the adapter, 2-6 commissioning the adapter, 2-1 connecting to the drive, 2-4 connecting to the network, 2-3 preparing for, 2-1 Internal Interface cable, 2-4 Internal Interface cables connecting to a drive, 2-4 connecting to an adapter, 2-4 illustration, 2-4 NET B status indicator locating, 4-1, 5-1 not used, 4-1, 5-1 node address denition, G-4 setting with a parameter, 3-4 Non-Volatile Storage (NVS) denition, G-4 in adapter, 3-1

O
objects denition, G-4 ODVA, A-1, G-2 On, 2-5 operating status, 1-6

L
LCD HIM, 3-3 LED HIM, 3-3 LEDs, refer to status indicators logic command/status bit denitions, C-1 denition, G-4

P
parameters accessing, 3-1 active conguration, 3-8 convention, P-2 list of, B-1 to B-4 numbers, B-1 PCCC denition, G-4 supported feature, 1-2 ping, G-5 plug, 2-3 PORT status indicator locating, 4-1, 5-1 troubleshooting with, 5-2, 5-3 power consumption, A-1 PowerFlex drives, G-5 70/700 logic command/status, C-1 compatible with adapter, 1-3 HIM, 3-3 installing adapter on, 2-4 preparing for an installation, 2-1

M
MAC ID, refer to node address manual conventions, P-2 related documentation, P-1 web site, P-1 mechanical dimensions, A-1 MOD status indicator locating, 4-1, 5-1 modes of operation, 1-6 Module, 5-6 mounting the adapter, 2-5

N
NET A status indicator locating, 4-1, 5-1

Index-4 processor, refer to controller producer/consumer network, G-5 products, see SCANport or DPI products Programmable, G-5 programmable logic controller, refer to controller switches locating, 1-1

T
technical support, P-2 tools required, 1-3 Transaction, G-6 Troubleshooting, 5-1 Type, G-5

Q
quick start, 1-5

R
Ref/Fdbk Size parameter, B-2 reference/feedback denition, G-5 regulatory compliance, A-1 related documentation, P-1 Reset, 3-7 Reset Module parameter, B-2 resetting an adapter, 3-7 ribbon cable, refer to Internal Interface cable RS, 3-4 RSLinx, P-2

U
update, see ash update Using, 3-3, 4-1

W
web site for manuals, P-1 web sites, G-3 wiring, refer to cables

Z
zero data conguring an adapter for, 3-5 denition, G-6

S
safety precautions, 1-4 scanner denition, G-5 Set, 2-2 specications adapter, A-1 DeviceNet, G-2 status indicators denition, G-5 identifying, 1-6 locating, 4-1, 5-1

Allen-Bradley, ControlFLASH, DPI, DriveExplorer, DriveTools32, DriveExecutive, DriveTools 2000, PLC-5, PowerFlex, SCANport, and SLC are trademarks of Rockwell Automation. The DF1 Protocol is an Allen-Bradley proprietary interface, originally designed to provide a communications link to a variety of AB products. RSLinx and RSLogix are trademarks of Rockwell Software. Windows, Windows CE, Windows NT, Windows ME, Windows 2000, Windows XP, and Microsoft are either registered trademarks or trademarks of Microsoft Corporation.

Publication 20COMM-UM005A-EN-P May 2002

Copyright 2002 Rockwell Automation, Inc. All rights reserved. Printed USA

P/N 307359-P01
.

You might also like