You are on page 1/ 207

optical networks ltd

ltd

Project: Confidentiality Level


KCRC Light Rail Contract No. DB-2010 For internal use only (and within project)
Light Rail Telecommunication -
SCADA System

Submittal Title: Division


SCADA RTU / Marshalling Boxes Point Schedule Transportation Systems

Document No.: Issuing Department


DB2010-DES-DDSCAD-50013-R03 Signaling and Control Systems
Mass Transit

Released (Authorised), Division, Tel., Signature: Location and Date:

Peter Idle, Siemens Ltd., SLHK, TS2, 2460-5550 Hong Kong, 5 July 2004

Released, Division, Tel., Signature: Location and Date:

Ian M. Hampton, Siemens Ltd., SLHK TS2, 2460-5510 Hong Kong, 5 July 2004

Checked (Reviewed), Division, Tel., Signature: Location and Date:

Eric Choi, Siemens Ltd., SLHK, TS2, 2460-5529 Hong Kong, 5 July 2004

Prepared, Division, Tel., Signature: Location and Date:

Donna So, Siemens Ltd., SLHK, TS2, 2460-5525 Hong Kong, 5 July 2004

KCRC Light Rail Contract No. DB-2010 SLHK TS Document No.:


Light Rail Telecommunication – SCADA System DB2010-DES-DDSCAD-50013-R03

Document Title : Version: F


SCADA RTU / Marshalling Boxes Point Schedule Date: 13 April 2004
Copyright (C) Siemens Ltd. 2002 All Rights Reserved

Unrestricted
optical networks ltd

ltd

SCADA RTU / Project:


KCRC LIGHT RAIL
Contract No. DB-2010
MARSHALLING BOXES Light Rail Telecommunication -
SCADA System
POINT SCHEDULE
Sheet No. Rev. Title NOTES:
001 F COVER
1 The I/O schedule and terminations are formulated in accordance with the following information:
[Information for the entries with "?" in this schedule should be supplied by CC-230/KCRC.]
002 F CONTENTS
1.1 As-fitted “SCADA Termination Tables for Rectifier Stations RS1 to RS13, dated June 1996” enclosed in Atkins’ letter ref.: WR1CRN2001-028402
(CRE/DB2010/0298) dated 13 December 2001. [Construction of point schedule for RS01 to RS13]
003 F REVISION
1.2 Updated I/O Tables which was attached in the KCRC's e-mail ref.: DB2010/SC/0112/018 dated 20 December 2001. [Construction of point schedule for
RS01 to RS13]

1.3 Draft schedule I/O points for the traction power equipment provided by CC-230 Contractor during the SCADA Interface Meeting on 10 January.
[Construction of point schedule for RS14 to RS16]

1.4 “Traction Power SCADA Interface for R14, R15 & R16” enclosed in Atkins’ letter ref.: WR1CRN2002-0035297 (CRE/DB2010/0427) dated 20 February
2002. [Construction of point schedule for RS14 to RS16]

1.5 Information supplemented by the Appendix U of PS. [Construction of point schedule for RS01 to RS16]
1.6 Reasonably practical suggestions for Transducer Output Ranges, Actual Ranges of Engineering values, Alarm Limits, Alarm Priority, etc. as they were
not specified in the PS. [Construction of point schedule for RS01 to RS16]
Remark: Please refer to "CONTENTS" for the description of each Sheet Number.
1.7 “SCADA Interface for All Rectiifer Stations (Submission No.: CC0230/CSF-ID/P/000548/A)” enclosed in Atkins’ letter ref.: WR1CRN2002-0077641
(CRE/DB2010/0553) dated 16 April 2002. [Additional information for the construction of point schedule for RS14 to RS16]

1.8 Additional information for the missing terminations in marshalling boxes for RS01 to RS13 "SCADA Point Schedule Extraction" attached in KCRC's e-
mail ref.: DB2010/SC/0204/004 dated 8 April 2002. [Additional information for the construction of point schedule for RS01 to RS13]

1.9 Description of digital inputs states detailed in 6 pages of "DigitalStatus_Alarm Name.pdf" ('Digital Input Processing Conventions' extracted from the
LN2068 Database Configuration Manual) which was conveyed in KCRC's e-mail ref.: DB2010/SC/0204/019 dated 19 April 2002. [Additional
information for the construction of point schedule for RS01 to RS16]

1.10 Rev. C has been updated to account for revised RTU termination interface details resulting from a necessary change identified during the detailed
design works (reallocation of single-bit and double-bit assigments). The additional information provides correlation between the RTU Cabinet
terminations and the Marshalling Cabinet terminations. All other information such as I/O quantity, descriptions, etc. have not changed.

1.11 Rev. D has been updated to account for revised RTU termination interface details resulting from a necessary change identified during Migration, PAT
and SAT in which KCRC Engineer’s Instruction No. DB2010/030 is also included.

2 Additional traction power equipment to be installed within the rectifier stations RS8, RS10, RS13 and RS14 have been accounted for.

3 48-core control cables will be used between Marshalling Boxes and RTU Cabinets for Digital Inputs and Control Outputs. 72-core control cables will be
used for those of Analogue Inputs.

4 Terminal blocks are reserved for "COMMON" for Digital Inputs and Control Outputs. Terminal blocks for the "COMMON'" of Digital Inputs (odd numbers
of terminal blocks) and Control Outputs are not shown in the Point Schedule.

5 Spare cables should be terminated at terminal blocks of RTU Cabinets and Marshalling Boxes if available.

6 Double deck terminal blocks with disconnectible function are proposed for interface of Analogue Inputs and Control Outputs. Modular terminal blocks
with pluggable optocouplers are proposed for interface of Digital Inputs.

E 13-Feb-2004 Approved by Title Sheet No.


D (Used by CC230) Peter Idle
COVER 001
C 04-Jun-2002
B 30-Apr-2002 Drawn by Donna So DOC. No.
A 28-Jan-2002 Checked by Eric Choi DB2010-DES-DDSCAD-50013-R03

Unrestricted
DB2010-DES-DDSCAD-50013-R03
Rev Date Designed by Kevin Chau

Unrestricted
LIGHT RAIL TELECOMMUNICATION - SCADA SYSTEM
SCADA RTU POINT SCHEDULE

REV. SHEET NO. DATE CONTENTS DRAWN CHECKED APPROVED REV. SHEET NO. DATE CONTENTS DRAWN CHECKED APPROVED

A [RS01] - 1 to 4 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu


A [RS02] - 1 to 5 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS03] - 1 to 4 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS04] - 1 to 5 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS05] - 1 to 4 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS06] - 1 to 5 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS07] - 1 to 4 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS08] - 1 to 5 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS09] - 1 to 5 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS10] - 1 to 4 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS11] - 1 to 4 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS12] - 1 to 5 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS13] - 1 to 5 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS14] - 1 to 8 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS15] - 1 to 6 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu
A [RS16] - 1 to 6 INITIAL RELEASE Gordon Tsui Jeco Chan Simon Chiu

E 13-Feb-2004 Approved by Title Sheet No.


D (Used by CC230) Peter Idle
REVISION 003
C 04-Jun-2002
B 30-Apr-2002 Drawn by Donna So DOC. No.
A 28-Jan-2002 Checked by Eric Choi DB2010-DES-DDSCAD-50013-R03
Rev Date Designed by Kevin Chau

Unrestricted
LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2023/03/23
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
IO address Front IO address Front (+ve) (-ve)
No. connector No. connector
Pin No. Pin No.

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R01 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R01 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 363 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R01 RING MAIN H03 SOLKOR TRIP S005-6 - 364 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R01 RING MAIN H03 PILOT WIRE ALARM S005-7 - 350 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R01 RING MAIN H03 OVERLOAD ALARM S005-8 - 365 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 - SPARE S005-9 - - - - - - - - - - - - - - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R01 RING MAIN H04 CONTROL SELECTOR SWITCH S005-12 - 175 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R01 RING MAIN H04 O/C EARTH FAULT TRIP S005-13 - 369 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R01 RING MAIN H04 SOLKOR TRIP S005-14 - 371 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R01 RING MAIN H04 PILOT WIRE ALARM S005-15 - 372 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 OVERLOAD ALARM S005-16 - 370 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 - SPARE S005-17 - - - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 - SPARE S005-18 - - - - - - - - - - - - - - - - - - - - - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 - SPARE S005-19 - - - - - - - - - - - - - - - - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R01 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-22 - 6 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R01 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-23 - 207 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R01 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-24 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R01 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-25 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R01 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-26 - 210 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R01 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-27 - 211 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R01 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-28 - 212 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R01 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-29 - 213 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R01 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-30 - 214 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R01 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-31 - 215 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R01 RECTIFIER 1 FRAME EARTH TRIP S005-32 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R01 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-33 - 217 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R01 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-34 - 218 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R01 RECTIFIER 1 DIODE OVER TEMP ALARM S005-35 - 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R01 RECTIFIER 1 DIODE OVER TEMP TRIP S005-36 - 220 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R01 RECTIFIER 1 REVERSE CURRENT TRIP S005-37 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R01 RECTIFIER 1 SURGE ARRESTOR TRIP S005-38 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R01 RECTIFIER 1 FILTER CIRCUIT ALARM S005-39 - 223 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R01 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-40 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 - SPARE S005-41 - - - - - - - - - - - - - - - - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R01 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S005-44 - 58 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 - SPARE S005-45 - - - - - - - - - - - - - - - - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R01 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S005-48 - 10 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R01 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-2 - 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R01 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-3 - 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R01 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-4 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R01 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-5 - 228 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R01 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-6 - 229 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R01 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-7 - 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R01 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-8 - 231 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R01 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-9 - 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R01 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-10 - 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R01 RECTIFIER 2 FRAME EARTH TRIP S006-11 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R01 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-12 - 235 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R01 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-13 - 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R01 RECTIFIER 2 DIODE OVER TEMP ALARM S006-14 - 237 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R01 RECTIFIER 2 DIODE OVER TEMP TRIP S006-15 - 238 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R01 RECTIFIER 2 REVERSE CURRENT TRIP S006-16 - 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R01 RECTIFIER 2 SURGE ARRESTOR TRIP S006-17 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R01 RECTIFIER 2 FILTER CIRCUIT ALARM S006-18 - 241 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R01 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-19 - 242 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 - SPARE S006-20 - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R01 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-23 - 64 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 - SPARE S006-24 - - - - - - - - - - - - - - - - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R01 AUXILIARY TRANSFORMER 11KV SWITCH H5 S006-25 - 2 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 - SPARE S006-26 - 1 - - - - - - - - - - - - - - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R01 AUXILIARY TRANSFORMER 11KV SW H5 FUSE BLOWN TRIP S006-27 - 243 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R01 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-28 - 244 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 - SPARE S006-29 - 253 - - - - - - - - - - - - - - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R01 750V DCCB TRIP CCT SUPERVISION ALARM S006-30 - 373 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 5 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2023/03/23
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
IO address Front IO address Front (+ve) (-ve)
No. connector No. connector
Pin No. Pin No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R01 TRACK FEEDER D27 CONTROL SELECTOR SWITCH S006-33 - 28 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R01 TRACK FEEDER D27 INSTANT OVERCURRENT S006-34 - 245 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R01 TRACK FEEDER D27 RATE OF RISE TRIP S006-35 - 246 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R01 TRACK FEEDER D27 LINE TESTING S006-36 - 29 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R01 TRACK FEEDER D27 LINE IMPEDANCE LOW S006-37 - 247 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 SPARE S006-38 - - - - - - - - - - - - - - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R01 TRACK FEEDER D28 CONTROL SELECTOR SWITCH S006-41 - 36 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R01 TRACK FEEDER D28 INSTANT OVERCURRENT S006-42 - 248 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S09 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R01 TRACK FEEDER D28 RATE OF RISE TRIP S006-43 - 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R01 TRACK FEEDER D28 LINE TESTING S006-44 - 37 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R01 TRACK FEEDER D28 LINE IMPEDANCE LOW S006-45 - 250 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R01 TRACK FEEDER D11 CONTROL SELECTOR SWITCH S007-2 - 44 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R01 TRACK FEEDER D11 INSTANT OVERCURRENT S007-3 - 251 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R01 TRACK FEEDER D11 RATE OF RISE TRIP S007-4 - 357 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R01 TRACK FEEDER D11 LINE TESTING S007-5 - 45 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R01 TRACK FEEDER D11 LINE IMPEDANCE LOW S007-6 - 358 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R01 TRACK FEEDER D12 CONTROL SELECTOR SWITCH S007-10 - 52 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R01 TRACK FEEDER D12 INSTANT OVERCURRENT S007-11 - 359 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R01 TRACK FEEDER D12 RATE OF RISE TRIP S007-12 - 360 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R01 TRACK FEEDER D12 LINE TESTING S007-13 - 53 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R01 TRACK FEEDER D12 LINE IMPEDANCE LOW S007-14 - 361 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S09 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R01 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-18 - 362 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R01 AC/DC SYSTEM MAINS FAILED ALARM S007-19 - 198 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R01 AC/DC SYSTEM 380V FEEDER MCB S007-20 - 199 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - - - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R01 AC/DC SYSTEM AC EARTH FAULT TRIP S007-21 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R01 AC/DC SYSTEM BATTERY CHARGER S007-22 - 201 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R01 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-23 - 352 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R01 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-24 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R01 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-25 - 203 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R01 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-26 - 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R01 AC/DC SYSTEM 110V DC COMMON FEEDER S007-27 - 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R01 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-28 - 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R01 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-29 - 391 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R01 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-30 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R01 COMMON EQUIPMENT INTRUDER ALARM S007-31 - 393 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R01 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 - SPARE S007-33 - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R01 RING MAIN H03 VCB S005-2 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R01 RING MAIN H03 VCB S005-3 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R01 RING MAIN H04 VCB S005-10 - 173 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R01 RING MAIN H04 VCB S005-11 - 174 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R01 RECTIFIER FEEDER H01 VCB S005-20 - 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R01 RECTIFIER FEEDER H01 VCB S005-21 - 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R01 RECTIFIER FEEDER D1 DCCB S005-42 - 59 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R01 RECTIFIER FEEDER D1 DCCB S005-43 - 60 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R01 RECTIFIER FEEDER H02 VCB S005-46 - 7 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R01 RECTIFIER FEEDER H02 VCB S005-47 - 8 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R01 RECTIFIER FEEDER D2 DCCB S006-21 - 65 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R01 RECTIFIER FEEDER D2 DCCB S006-22 - 66 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R01 TRACK FEEDER D27 DCCB S006-31 - 23 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R01 TRACK FEEDER D27 DCCB S006-32 - 24 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R01 TRACK FEEDER D28 DCCB S006-39 - 31 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R01 TRACK FEEDER D28 DCCB S006-40 - 32 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R01 TRACK FEEDER D11 DCCB S006-47 - 39 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R01 TRACK FEEDER D11 DCCB S006-48 - 40 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R01 TRACK FEEDER D12 DCCB S007-8 - 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R01 TRACK FEEDER D12 DCCB S007-9 - 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R01 DC COMMON EQUIPMENT D07 CONTACTOR S007-16 - 55 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R01 DC COMMON EQUIPMENT D07 CONTACTOR S007-17 - 56 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R01 DUMMY CB VCB POSITION internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R01 DUMMY CB VCB POSITION internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
I20.0 1 R0S06 - SPARE S006-33 - - - - - - - - - - - NO 0 - - - - - - - - -
I20.1 2 R0S06 - SPARE S006-34 - - - - - - - - - - - NO 0 - - - - - - - - -
I20.2 3 R0S06 - SPARE S006-35 - - - - - - - - - - - NO 0 - - - - - - - - -
I20.3 4 R0S06 - SPARE S006-36 - - - - - - - - - - - NO 0 - - - - - - - - -
I20.4 5 R0S06 - SPARE S006-37 - - - - - - - - - - - NO 0 - - - - - - - - -
I20.5 6 R0S06 - SPARE S006-38 - - - - - - - - - - - - - - - - - - - - - -
I20.6 7 R0S06 - SPARE S006-41 - - - - - - - - - - - NO 0 - - - - - - - - -
I20.7 8 R0S06 - SPARE S006-42 - - - - - - - - - - - NO 0 - - - - - - - - -
- 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
- 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
I21.0 11 R0S06 - SPARE S006-43 - - - - - - - - - - - NO 0 - - - - - - - - -
I21.1 12 R0S06 - SPARE S006-44 - - - - - - - - - - - NO 0 - - - - - - - - -
I21.2 13 R0S06 - SPARE S006-45 - - - - - - - - - - - NO 0 - - - - - - - - -
I21.3 14 R0S06 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - - -
I21.4 15 R0S06 - SPARE S007-2 - - - - - - - - - - - NO 0 - - - - - - - - -
I21.5 16 R0S06 - SPARE S007-3 - - - - - - - - - - - NO 0 - - - - - - - - -
I21.6 17 R0S06 - SPARE S007-4 - - - - - - - - - - - NO 0 - - - - - - - - -
I21.7 18 R0S06 - SPARE S007-5 - - - - - - - - - - - NO 0 - - - - - - - - -
1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 6 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2023/03/23
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
IO address Front IO address Front (+ve) (-ve)
No. connector No. connector
Pin No. Pin No.

I22.0 21 R0S06 - SPARE S007-6 - - - - - - - - - - - NO 0 - - - - - - - - -


I22.1 22 R0S06 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - - -
I22.2 23 R0S06 - SPARE S007-10 - - - - - - - - - - - NO 0 - - - - - - - - -
I22.3 24 R0S06 - SPARE S007-11 - - - - - - - - - - - NO 0 - - - - - - - - -
I22.4 25 R0S06 - SPARE S007-12 - - - - - - - - - - - NO 0 - - - - - - - - -
I22.5 26 R0S06 - SPARE S007-13 - - - - - - - - - - - NO 0 - - - - - - - - -
I22.6 27 R0S06 - SPARE S007-14 - - - - - - - - - - - NO 0 - - - - - - - - -
I22.7 28 R0S06 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - - -
- 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
- 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
I23.0 31 R0S06 - SPARE S007-18 - - - - - - - - - - - NO 0 - - - - - - - - -
I23.1 32 R0S06 - SPARE S007-19 - - - - - - - - - - - NO 0 - - - - - - - - -
I23.2 33 R0S06 - SPARE S007-20 - - - - - - - - - - - NO 0 - - - - - - - - -
I23.3 34 R0S06 - SPARE S007-21 - - - - - - - - - - - NO 0 - - - - - - - - -
I23.4 35 R0S06 - SPARE S007-22 - - - - - - - - - - - NO 0 - - - - - - - - -
I23.5 36 R0S06 - SPARE S007-23 - - - - - - - - - - - NO 0 - - - - - - - - -
I23.6 37 R0S06 - SPARE S007-24 - - - - - - - - - - - NO 0 - - - - - - - - -
I23.7 38 R0S06 - SPARE S007-25 - - - - - - - - - - - NO 0 - - - - - - - - -
2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 7 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2023/03/23
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
IO address Front IO address Front (+ve) (-ve)
No. connector No. connector
Pin No. Pin No.

ZS1 ZS1 1 R0S12 - - R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S12 - - R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S12 IW.256 1 R1S04 R01 TRACK FEEDER D27 DC CURRENT S009-1 - 334 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-1 (-) IW.256 5 R0S12 IW.256 21 R1S04 - - S009-2 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850
TB2-2 (+) IW.258 6 R0S12 IW.258 2 R1S04 R01 RECTIFIER FEEDER H01 CURRENT S009-3 - 335 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-2 (-) IW.258 7 R0S12 IW.258 22 R1S04 - - S009-4 - - 418 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-3 (+) IW.260 8 R0S12 IW.260 3 R1S04 R01 RECTIFIER UNIT 1 DC CURRENT S009-5 - 339 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-3 (-) IW.260 9 R0S12 IW.260 23 R1S04 - - S009-6 - - 422 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-4 (+) IW.262 10 R0S12 IW.262 4 R1S04 R01 RECTIFIER UNIT 1 DC VOLTAGE S009-7 - 340 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-4 (-) IW.262 11 R0S12 IW.262 24 R1S04 - - S009-8 - - 423 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931
TB2-5 (+) IW.264 15 R0S12 IW.264 5 R1S04 R01 TRACK FEEDER D28 DC CURRENT S009-9 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-5 (-) IW.264 16 R0S12 IW.264 25 R1S04 - - S009-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850
TB2-6 (+) IW.266 17 R0S12 IW.266 6 R1S04 R01 RECTIFIER FEEDER H02 CURRENT S009-11 - 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-6 (-) IW.266 18 R0S12 IW.266 26 R1S04 - - S009-12 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-7 (+) IW.268 19 R0S12 IW.268 7 R1S04 R01 RECTIFIER UNIT 2 DC CURRENT S009-13 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-7 (-) IW.268 20 R0S12 IW.268 27 R1S04 - - S009-14 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-8 (+) IW.270 21 R0S12 IW.270 8 R1S04 R01 RECTIFIER UNIT 2 DC VOLTAGE S009-15 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-8 (-) IW.270 22 R0S12 IW.270 28 R1S04 - - S009-16 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931
TB2-9 (+) IW.272 26 R0S12 IW.272 9 R1S04 R01 TRACK FEEDER D11 DC CURRENT S009-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-9 (-) IW.272 27 R0S12 IW.272 29 R1S04 - - S009-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850
TB2-10 (+) IW.274 28 R0S12 IW.274 10 R1S04 R01 RING MAIN H03 CURRENT S009-19 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-10 (-) IW.274 29 R0S12 IW.274 30 R1S04 - - S009-20 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-11 (+) IW.276 30 R0S12 IW.276 11 R1S04 R01 RING MAIN H04 CURRENT S009-21 - 354 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-11 (-) IW.276 31 R0S12 IW.276 31 R1S04 - - S009-22 - - 437 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-12 (+) IW.278 32 R0S12 IW.278 12 R1S04 R01 AC BUSBAR VOLTAGE S009-23 - 349 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00%
TB2-12 (-) IW.278 33 R0S12 IW.278 32 R1S04 - - S009-24 - - 432 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.95 10.395 11.495 11.78
TB2-13 (+) IW.280 37 R0S12 IW.280 13 R1S04 R01 TRACK FEEDER D12 DC CURRENT S009-25 - 347 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-13 (-) IW.280 38 R0S12 IW.280 33 R1S04 - - S009-26 - - 430 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850
TB2-14 (+) IW.282 39 R0S12 IW.282 14 R1S04 R01 DC BUSBAR DC VOLTAGE S009-27 - 348 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00%
TB2-14 (-) IW.282 40 R0S12 IW.282 34 R1S04 - - S009-28 - - 431 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.25 556.5 902.5 931
TB2-15 (+) IW.284 41 R0S12 IW.284 15 R1S04 R01 NEGATIVE DC BUSBAR DC RETURN CURRENT S009-29 - 343 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00%
TB2-15 (-) IW.284 42 R0S12 IW.284 35 R1S04 - - S009-30 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800
TB2-16 (+) IW.286 43 R0S12 IW.286 16 R1S04 - SPARE S009-31 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S12 IW.286 36 R1S04 - - S009-32 - - - - - - - - - to - - to - - - - - - - - - - - - -
S110-RD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
S112-BL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-A - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
IW.288 1 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.288 21 R1S05 - - - - - - - - - - - - to -
IW.290 2 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.290 22 R1S05 - - - - - - - - - - - - to -
IW.292 3 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.292 23 R1S05 - - - - - - - - - - - - to -
IW.294 4 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.294 24 R1S05 - - - - - - - - - - - - to -
IW.296 5 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.296 25 R1S05 - - - - - - - - - - - - to -
IW.298 6 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.298 26 R1S05 - - - - - - - - - - - - to -
IW.300 7 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.300 27 R1S05 - - - - - - - - - - - - to -
IW.302 8 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.302 28 R1S05 - - - - - - - - - - - - to -
IW.304 9 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.304 29 R1S05 - - - - - - - - - - - - to -
IW.306 10 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.306 30 R1S05 - - - - - - - - - - - - to -
IW.308 11 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.308 31 R1S05 - - - - - - - - - - - - to -
IW.310 12 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.310 32 R1S05 - - - - - - - - - - - - to -
IW.312 13 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.312 33 R1S05 - - - - - - - - - - - - to -
IW.314 14 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.314 34 R1S05 - - - - - - - - - - - - to -
IW.316 15 R1S05 - SPARE - - - - AI - - - - - 0 to +20
IW.316 35 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - -
IW.318 16 R1S05 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - -
IW.318 36 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - -
ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S11 Q4.0 2 R1S02 R01 RING MAIN H03 VCB OPEN S008-2 - 16 - CO - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S11 Q4.1 3 R1S02 R01 RING MAIN H03 VCB CLOSE S008-3 - 15 - CO - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S11 Q4.2 6 R1S02 R01 RING MAIN H04 VCB OPEN S008-4 - 176 - CO - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S11 Q4.3 7 R1S02 R01 RING MAIN H04 VCB CLOSE S008-5 - 177 - CO - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S11 Q4.4 12 R1S02 R01 RECTIFIER FEEDER H01 VCB OPEN S008-6 - 82 - CO - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S11 Q4.5 13 R1S02 R01 RECTIFIER FEEDER H01 VCB CLOSE S008-7 - 81 - CO - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S11 Q4.6 16 R1S02 R01 RECTIFIER FEEDER D1 DCCB OPEN S008-8 - 17 - CO - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S11 Q4.7 17 R1S02 R01 RECTIFIER FEEDER D1 DCCB CLOSE S008-9 - 18 - CO - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-09 Q5.0 15 R0S11 Q5.0 22 R1S02 R01 RECTIFIER FEEDER H02 VCB OPEN S008-10 - 84 - CO - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S11 Q5.1 23 R1S02 R01 RECTIFIER FEEDER H02 VCB CLOSE S008-11 - 83 - CO - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S11 Q5.2 26 R1S02 R01 RECTIFIER FEEDER D2 DCCB OPEN S008-12 - 19 - CO - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S11 Q5.3 27 R1S02 R01 RECTIFIER FEEDER D2 DCCB CLOSE S008-13 - 20 - CO - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S11 Q5.4 32 R1S02 R01 TRACK FEEDER D27 DCCB OPEN S008-14 - 25 - CO - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S11 Q5.5 33 R1S02 R01 TRACK FEEDER D27 DCCB CLOSE S008-15 - 26 - CO - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S11 Q5.6 36 R1S02 R01 TRACK FEEDER D28 DCCB OPEN S008-16 - 33 - CO - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S11 Q5.7 37 R1S02 R01 TRACK FEEDER D28 DCCB CLOSE S008-17 - 34 - CO - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-17 Q6.0 26 R0S11 Q6.0 2 R1S03 R01 TRACK FEEDER D11 DCCB OPEN S008-18 - 41 - CO - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S11 Q6.1 3 R1S03 R01 TRACK FEEDER D11 DCCB CLOSE S008-19 - 42 - CO - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S11 Q6.2 6 R1S03 R01 TRACK FEEDER D12 DCCB OPEN S008-20 - 49 - CO - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S11 Q6.3 7 R1S03 R01 TRACK FEEDER D12 DCCB CLOSE S008-21 - 50 - CO - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S11 Q6.4 12 R1S03 R01 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S008-22 - 61 - CO - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S11 Q6.5 13 R1S03 - SPARE S008-23 - - - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S11 Q6.6 16 R1S03 R01 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S11 Q6.7 17 R1S03 R01 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-25 Q7.0 37 R0S11 Q7.0 22 R1S03 - SPARE S008-26 - - - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S11 Q7.1 23 R1S03 - SPARE S008-27 - - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S11 Q7.2 26 R1S03 - SPARE S008-28 - - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S11 Q7.3 27 R1S03 - SPARE S008-29 - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 8 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2023/03/23
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
IO address Front IO address Front (+ve) (-ve)
No. connector No. connector
Pin No. Pin No.

RL-29 Q7.4 41 R0S11 Q7.4 32 R1S03 - SPARE S008-30 - - - - - - - - - - - - - - - - - - - - - -


RL-30 Q7.5 42 R0S11 Q7.5 33 R1S03 - SPARE S008-31 - - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S11 Q7.6 36 R1S03 - SPARE S008-32 - - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S11 Q7.7 37 R1S03 - SPARE S008-33 - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S11 UC- - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S11 UC- - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S11 UC+ 31 - - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S11 UC+ 35 - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 9 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
- - - -
NC NC - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
- - - -
NC NC - -
- - - -
NC C - -
NC C - -
- - - -
NC C - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 10 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
- - - -
- - - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 11 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 12 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
C NC NC C
-8.143 -6.786 7.200 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 7.200 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 7.200 8.143
C NC NC C
- - 7.125 9.025
C NC NC C
- - 7.125 9.025
C NC NC C
0.760 8.316 9.196 9.424
C NC NC C
-8.143 -6.786 7.200 8.143
C NC NC C
3.943 5.565 9.025 9.310
C NC NC C
- - 6.333 7.238
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 13 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS01 [RS01] 14 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R02 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 14 - SB R/L LOCAL REMOTE -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R02 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 363 - SB OPER RESET OPERATED -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R02 RING MAIN H03 SOLKOR TRIP S005-6 - 364 - SB OPER RESET OPERATED -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R02 RING MAIN H03 PILOT WIRE ALARM S005-7 - 368 - SB OPNL NORMAL OPERATED -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R02 RING MAIN H03 OVERLOAD ALARM S005-8 - 365 - SB OPNL NORMAL OPERATED -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 R02 ROLLING SHUTTER - S005-9 - ? - SB OPNL NORMAL OPERATED -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R02 RING MAIN H04 CONTROL SELECTOR SWITCH S005-12 - 20 - SB R/L LOCAL REMOTE -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R02 RING MAIN H04 O/C EARTH FAULT TRIP S005-13 - 354 - SB OPER RESET OPERATED -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R02 RING MAIN H04 SOLKOR TRIP S005-14 - 355 - SB OPER RESET OPERATED -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R02 RING MAIN H04 PILOT WIRE ALARM S005-15 - - SB OPNL NORMAL OPERATED -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R02 RING MAIN H04 OVERLOAD ALARM S005-16 - 356 - SB OPNL NORMAL OPERATED -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 050 SECTION BREAKER S13 CONTROL SELECTOR SWITCH S005-17 - 180 - SB R/L LOCAL REMOTE -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 050 SECTION BREAKER S14 CONTROL SELECTOR SWITCH S005-18 - 190 - SB R/L LOCAL REMOTE -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 - SPARE S005-19 - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R02 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-22 - 6 - SB R/L LOCAL REMOTE -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R02 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-23 - 207 - SB OPER RESET OPERATED -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R02 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-24 - 208 - SB OPER RESET OPERATED -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R02 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-25 - 209 - SB OPER RESET OPERATED -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R02 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-26 - 210 - SB OPNL NORMAL OPERATED -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R02 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-27 - 211 - SB OPER RESET OPERATED -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R02 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-28 - 212 - SB OPNL NORMAL OPERATED -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R02 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-29 - 213 - SB OPER RESET OPERATED -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R02 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-30 - 214 - SB OPNL NORMAL OPERATED -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R02 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-31 - 215 - SB OPER RESET OPERATED -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R02 RECTIFIER 1 FRAME EARTH TRIP S005-32 - 216 - SB OPER RESET OPERATED -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R02 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-33 - 217 - SB OPNL NORMAL OPERATED -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R02 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-34 - 218 - SB OPER RESET OPERATED -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R02 RECTIFIER 1 DIODE OVER TEMP ALARM S005-35 - 219 - SB OPNL NORMAL OPERATED -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R02 RECTIFIER 1 DIODE OVER TEMP TRIP S005-36 - 220 - SB OPER RESET OPERATED -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R02 RECTIFIER 1 REVERSE CURRENT TRIP S005-37 - 221 - SB OPER RESET OPERATED -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R02 RECTIFIER 1 SURGE ARRESTOR TRIP S005-38 - 222 - SB OPER RESET OPERATED -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R02 RECTIFIER 1 FILTER CIRCUIT ALARM S005-39 - 223 - SB OPNL NORMAL OPERATED -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R02 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-40 - 224 - SB OPNL NORMAL OPERATED -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 - SPARE S005-41 - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R02 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S005-44 - 23 - SB R/L LOCAL REMOTE -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 - SPARE S005-45 - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R02 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S005-48 - 10 - SB R/L LOCAL REMOTE -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R02 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-2 - 225 - SB OPER RESET OPERATED -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R02 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-3 - 226 - SB OPER RESET OPERATED -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R02 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-4 - 227 - SB OPER RESET OPERATED -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R02 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-5 - 228 - SB OPNL NORMAL OPERATED -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R02 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-6 - 229 - SB OPER RESET OPERATED -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R02 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-7 - 230 - SB OPNL NORMAL OPERATED -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R02 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-8 - 231 - SB OPER RESET OPERATED -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R02 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-9 - 232 - SB OPNL NORMAL OPERATED -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R02 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-10 - 233 - SB OPER RESET OPERATED -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R02 RECTIFIER 2 FRAME EARTH TRIP S006-11 - 234 - SB OPER RESET OPERATED -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R02 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-12 - 235 - SB OPNL NORMAL OPERATED -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 15 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -


DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R02 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-13 - 236 - SB OPER RESET OPERATED -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R02 RECTIFIER 2 DIODE OVER TEMP ALARM S006-14 - 237 - SB OPNL NORMAL OPERATED -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R02 RECTIFIER 2 DIODE OVER TEMP TRIP S006-15 - 238 - SB OPER RESET OPERATED -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R02 RECTIFIER 2 REVERSE CURRENT TRIP S006-16 - 239 - SB OPER RESET OPERATED -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R02 RECTIFIER 2 SURGE ARRESTOR TRIP S006-17 - 240 - SB OPER RESET OPERATED -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R02 RECTIFIER 2 FILTER CIRCUIT ALARM S006-18 - 241 - SB OPNL NORMAL OPERATED -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R02 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-19 - 242 - SB OPNL NORMAL OPERATED -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 - SPARE S006-20 - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R02 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-23 - 54 - SB R/L LOCAL REMOTE -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 - SPARE S006-24 - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R02 AUXILIARY TRANSFORMER 11KV SWITCH H5 S006-25 - 2 - SB OPEN OPEN CLOSED -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 - SPARE S006-26 - 1 - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R02 AUXILIARY TRANSFORMER 11KV SW H5 FUSE BLOWN TRIP S006-27 - 243 - SB OPER RESET OPERATED -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R02 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-28 - 244 - SB OPNL NORMAL OPERATED -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 - SPARE S006-29 - 367 - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R02 750V DCCB TRIP CCT SUPERVISION ALARM S006-30 - 371 - SB OPNL NORMAL OPERATED -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 16 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R02 TRACK FEEDER D12 CONTROL SELECTOR SWITCH S006-33 - 57 - SB R/L LOCAL REMOTE -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R02 TRACK FEEDER D12 INSTANT OVERCURRENT S006-34 - 359 - SB O/C RESET OVERCURRENT -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R02 TRACK FEEDER D12 RATE OF RISE TRIP S006-35 - 360 - SB OPER RESET OPERATED -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R02 TRACK FEEDER D12 LINE TESTING S006-36 - 30 - SB PROG COMPLETED IN PROGRESS -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R02 TRACK FEEDER D12 LINE IMPEDANCE LOW S006-37 - 361 - SB OPNL NORMAL OPERATED -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S006-38 - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R02 TRACK FEEDER D11 CONTROL SELECTOR SWITCH S006-41 - 58 - SB R/L LOCAL REMOTE -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R02 TRACK FEEDER D11 INSTANT OVERCURRENT S006-42 - 248 - SB O/C RESET OVERCURRENT -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R02 TRACK FEEDER D11 RATE OF RISE TRIP S006-43 - 249 - SB OPER RESET OPERATED -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R02 TRACK FEEDER D11 LINE TESTING S006-44 - 59 - SB PROG COMPLETED IN PROGRESS -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R02 TRACK FEEDER D11 LINE IMPEDANCE LOW S006-45 - 250 - SB OPNL NORMAL OPERATED -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S006-46 - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R02 TRACK FEEDER D14 CONTROL SELECTOR SWITCH S007-2 - 60 - SB R/L LOCAL REMOTE -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R02 TRACK FEEDER D14 INSTANT OVERCURRENT S007-3 - 251 - SB O/C RESET OVERCURRENT -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R02 TRACK FEEDER D14 RATE OF RISE TRIP S007-4 - 357 - SB OPER RESET OPERATED -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R02 TRACK FEEDER D14 LINE TESTING S007-5 - 42 - SB PROG COMPLETED IN PROGRESS -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R02 TRACK FEEDER D14 LINE IMPEDANCE LOW S007-6 - 358 - SB OPNL NORMAL OPERATED -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-7 - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R02 TRACK FEEDER D13 CONTROL SELECTOR SWITCH S007-10 - 61 - SB R/L LOCAL REMOTE -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R02 TRACK FEEDER D13 INSTANT OVERCURRENT S007-11 - 245 - SB O/C RESET OVERCURRENT -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R02 TRACK FEEDER D13 RATE OF RISE TRIP S007-12 - 246 - SB OPER RESET OPERATED -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R02 TRACK FEEDER D13 LINE TESTING S007-13 - 62 - SB PROG COMPLETED IN PROGRESS -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R02 TRACK FEEDER D13 LINE IMPEDANCE LOW S007-14 - 247 - SB OPNL NORMAL OPERATED -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 - SPARE S007-15 - - - - - - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R02 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-18 - 362 - SB OPER RESET OPERATED -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R02 AC/DC SYSTEM MAINS FAILED ALARM S007-19 - 198 - SB OPNL NORMAL OPERATED -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R02 AC/DC SYSTEM 380V FEEDER MCB S007-20 - 199 - SB MCB NORMAL OPEN -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R02 AC/DC SYSTEM AC EARTH FAULT TRIP S007-21 - 200 - SB OPER RESET OPERATED -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R02 AC/DC SYSTEM BATTERY CHARGER S007-22 - 201 - SB B/C NORMAL ISOLATED -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R02 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-23 - 366 - SB OPNL NORMAL OPERATED -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R02 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-24 - 202 - SB OPNL NORMAL OPERATED -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R02 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-25 - 203 - SB FLTN NORMAL FAULT -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R02 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-26 - 204 - SB FLTN NORMAL FAULT -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R02 AC/DC SYSTEM 110V DC COMMON FEEDER S007-27 - 205 - SB FLTN NORMAL FAULT -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R02 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-28 - 206 - SB OPNL NORMAL OPERATED -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R02 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-29 - 391 - SB OPNL NORMAL OPERATED -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R02 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-30 - 392 - SB OPER RESET OPERATED -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R02 COMMON EQUIPMENT INTRUDER ALARM S007-31 - 393 - SB OPNL NORMAL OPERATED -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 050 SECTION BREAKER S13 OVERCURRENT TRIP S007-32 - 183 - SB OPER RESET OPERATED -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 050 SECTION BREAKER S13 LOW VOLTAGE TRIP S007-33 - 184 - SB T/V RESET OPERATED -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 050 SECTION BREAKER S14 OVERCURRENT TRIP S007-34 - 193 - SB OPER RESET OPERATED -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 050 SECTION BREAKER S14 LOW VOLTAGE TRIP S007-35 - 194 - SB T/V RESET OPERATED -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 - SPARE S007-40 - 40 - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R02 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 - SPARE S007-42 - 42 - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 - SPARE S007-43 - 43 - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 - SPARE S007-44 - 44 - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 - SPARE S007-45 - 45 - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 17 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -


DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R02 RING MAIN H03 VCB OPENED S005-2 - 11 - DB CB1 DISCONNECT OPEN -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R02 RING MAIN H03 VCB CLOSED S005-3 - 12 - DB CB1 - - CLOSED
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R02 RING MAIN H04 VCB OPENED S005-10 - 17 - DB CB1 DISCONNECT OPEN -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R02 RING MAIN H04 VCB CLOSED S005-11 - 18 - DB CB1 - - CLOSED
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R02 RECTIFIER FEEDER H01 VCB OPENED S005-20 - 3 - DB CB1 DISCONNECT OPEN -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R02 RECTIFIER FEEDER H01 VCB CLOSED S005-21 - 4 - DB CB1 - - CLOSED
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R02 RECTIFIER FEEDER D1 DCCB OPENED S005-42 - 24 - DB CB1 DISCONNECT OPEN -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R02 RECTIFIER FEEDER D1 DCCB CLOSED S005-43 - 25 - DB CB1 - - CLOSED
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R02 RECTIFIER FEEDER H02 VCB OPENED S005-46 - 7 - DB CB1 DISCONNECT OPEN -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R02 RECTIFIER FEEDER H02 VCB CLOSED S005-47 - 8 - DB CB1 - - CLOSED
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R02 RECTIFIER FEEDER D2 DCCB OPENED S006-21 - 55 - DB CB1 DISCONNECT OPEN -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R02 RECTIFIER FEEDER D2 DCCB CLOSED S006-22 - 56 - DB CB1 - - CLOSED
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R02 TRACK FEEDER D12 DCCB OPENED S006-31 - 26 - DB CB1 DISCONNECT OPEN -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R02 TRACK FEEDER D12 DCCB CLOSED S006-32 - 27 - DB CB1 - - CLOSED
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R02 TRACK FEEDER D11 DCCB OPENED S006-39 - 32 - DB CB1 DISCONNECT OPEN -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R02 TRACK FEEDER D11 DCCB CLOSED S006-40 - 33 - DB CB1 - - CLOSED
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 18 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -


ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R0S06 R02 TRACK FEEDER D14 DCCB OPENED S006-47 - 38 - DB CB1 DISCONNECT OPEN -
DI-260 I20.1 5 R0S11 I20.1 2 R0S06 R02 TRACK FEEDER D14 DCCB CLOSED S006-48 - 39 - DB CB1 - - CLOSED
DI-262 I20.2 6 R0S11 I20.2 3 R0S06 R02 TRACK FEEDER D13 DCCB OPENED S007-8 - 44 - DB CB1 DISCONNECT OPEN -
DI-264 I20.3 7 R0S11 I20.3 4 R0S06 R02 TRACK FEEDER D13 DCCB CLOSED S007-9 - 45 - DB CB1 - - CLOSED
DI-266 I20.4 8 R0S11 I20.4 5 R0S06 R02 DC COMMON EQUIPMENT D07 CONTACTOR S007-16 - 50 - DB CB1 DISCONNECT OPEN -
DI-268 I20.5 9 R0S11 I20.5 6 R0S06 R02 DC COMMON EQUIPMENT D07 CONTACTOR S007-17 - 51 - DB CB1 - - CLOSED
DI-270 I20.6 10 R0S11 I20.6 7 R0S06 050 SECTION BREAKER S13 DCCB OPENED S007-36 - 181 - DB CB1 DISCONNECT OPEN -
DI-272 I20.7 11 R0S11 I20.7 8 R0S06 050 SECTION BREAKER S13 DCCB CLOSED S007-37 - 182 - DB CB1 - - CLOSED
UM0 UM0 12 R0S11 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R0S06 050 SECTION BREAKER S14 DCCB OPENED S007-38 - 191 - DB CB1 DISCONNECT OPEN -
DI-276 I21.1 16 R0S11 I21.1 12 R0S06 050 SECTION BREAKER S14 DCCB CLOSED S007-39 - 192 - DB CB1 - - CLOSED
DI-278 I21.2 17 R0S11 I21.2 13 R0S06 R02 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN -
DI-280 I21.3 18 R0S11 I21.3 14 R0S06 R02 DUMMY CB VCB CLOSED internal wiring - 4 - DB CB1 - - CLOSED
DI-282 I21.4 19 R0S11 I21.4 15 R0S06 - SPARE S007-46 - 46 - - - - -
DI-284 I21.5 20 R0S11 I21.5 16 R0S06 - SPARE S007-47 - 47 - - - - -
DI-286 I21.6 21 R0S11 I21.6 17 R0S06 - SPARE S007-48 - 48 - - - - -
DI-288 I21.7 22 R0S11 I21.7 18 R0S06 - SPARE S008-2 - 2 - - - - -
UM1 UM1 23 R0S11 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW1 UW1 24 R0S11 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R0S06 - SPARE S008-5 - - - - - - -
DI-292 I22.1 27 R0S11 I22.1 22 R0S06 - SPARE S008-6 - - - - - - -
DI-294 I22.2 28 R0S11 I22.2 23 R0S06 - SPARE S008-7 - - - - - - -
DI-296 I22.3 29 R0S11 I22.3 24 R0S06 - SPARE S008-8 - - - - - - -
DI-298 I22.4 30 R0S11 I22.4 25 R0S06 - SPARE S008-9 - - - - - - -
DI-300 I22.5 31 R0S11 I22.5 26 R0S06 - SPARE S008-10 - - - - - - -
DI-302 I22.6 32 R0S11 I22.6 27 R0S06 - SPARE S008-11 - - - - - - -
DI-304 I22.7 33 R0S11 I22.7 28 R0S06 - SPARE S008-12 - - - - - - -
UM2 UM2 34 R0S11 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R0S06 - SPARE S008-13 - - - - - - -
DI-308 I23.1 38 R0S11 I23.1 32 R0S06 - SPARE S008-14 - - - - - - -
DI-310 I23.2 39 R0S11 I23.2 33 R0S06 - SPARE S008-15 - - - - - - -
DI-312 I23.3 40 R0S11 I23.3 34 R0S06 - SPARE S008-16 - - - - - - -
DI-314 I23.4 41 R0S11 I23.4 35 R0S06 - SPARE S008-17 - - - - - - -
DI-316 I23.5 42 R0S11 I23.5 36 R0S06 - SPARE S008-18 - - - - - - -
DI-318 I23.6 43 R0S11 I23.6 37 R0S06 - SPARE S008-19 - - - - - - -
DI-320 I23.7 44 R0S11 I23.7 38 R0S06 - SPARE S008-20 - - - - - - -
UM3 UM3 45 R0S11 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - -
UW3 UW3 46 R0S11 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 19 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -


ZS2 ZS2 2 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
TB2-1 (+) IW.256 4 R0S13 IW.256 1 R1S05 R02 TRACK FEEDER D12 DC CURRENT S012-1 - 344 - AI - - - -
TB2-1 (-) IW.256 5 R0S13 IW.256 21 R1S05 - - S012-2 - - 427 - - - -
TB2-2 (+) IW.258 6 R0S13 IW.258 2 R1S05 R02 RECTIFIER FEEDER H01 CURRENT S012-3 - 335 - AI - - - -
TB2-2 (-) IW.258 7 R0S13 IW.258 22 R1S05 - - S012-4 - - 418 - - - -
TB2-3 (+) IW.260 8 R0S13 IW.260 3 R1S05 R02 RECTIFIER UNIT 1 DC CURRENT S012-5 - 339 - AI - - - -
TB2-3 (-) IW.260 9 R0S13 IW.260 23 R1S05 - - S012-6 - - 422 - - - -
TB2-4 (+) IW.262 10 R0S13 IW.262 4 R1S05 R02 RECTIFIER UNIT 1 DC VOLTAGE S012-7 - 340 - AI - - - -
TB2-4 (-) IW.262 11 R0S13 IW.262 24 R1S05 - - S012-8 - - 423 - - - -
TB2-5 (+) IW.264 15 R0S13 IW.264 5 R1S05 R02 TRACK FEEDER D11 DC CURRENT S012-9 - 345 - AI - - - -
TB2-5 (-) IW.264 16 R0S13 IW.264 25 R1S05 - - S012-10 - - 428 - - - -
TB2-6 (+) IW.266 17 R0S13 IW.266 6 R1S05 R02 RECTIFIER FEEDER H02 CURRENT S012-11 - 336 - AI - - - -
TB2-6 (-) IW.266 18 R0S13 IW.266 26 R1S05 - - S012-12 - - 419 - - - -
TB2-7 (+) IW.268 19 R0S13 IW.268 7 R1S05 R02 RECTIFIER UNIT 2 DC CURRENT S012-13 - 341 - AI - - - -
TB2-7 (-) IW.268 20 R0S13 IW.268 27 R1S05 - - S012-14 - - 424 - - - -
TB2-8 (+) IW.270 21 R0S13 IW.270 8 R1S05 R02 RECTIFIER UNIT 2 DC VOLTAGE S012-15 - 342 - AI - - - -
TB2-8 (-) IW.270 22 R0S13 IW.270 28 R1S05 - - S012-16 - - 425 - - - -
TB2-9 (+) IW.272 26 R0S13 IW.272 9 R1S05 R02 TRACK FEEDER D14 DC CURRENT S012-17 - 346 - AI - - - -
TB2-9 (-) IW.272 27 R0S13 IW.272 29 R1S05 - - S012-18 - - 429 - - - -
TB2-10 (+) IW.274 28 R0S13 IW.274 10 R1S05 R02 RING MAIN H03 CURRENT S012-19 - 337 - AI - - - -
TB2-10 (-) IW.274 29 R0S13 IW.274 30 R1S05 - - S012-20 - - 420 - - - -
TB2-11 (+) IW.276 30 R0S13 IW.276 11 R1S05 R02 RING MAIN H04 CURRENT S012-21 - 338 - AI - - - -
TB2-11 (-) IW.276 31 R0S13 IW.276 31 R1S05 - - S012-22 - - 421 - - - -
TB2-12 (+) IW.278 32 R0S13 IW.278 12 R1S05 R02 AC BUSBAR VOLTAGE S012-23 - 349 - AI - - - -
TB2-12 (-) IW.278 33 R0S13 IW.278 32 R1S05 - - S012-24 - - 432 - - - -
TB2-13 (+) IW.280 37 R0S13 IW.280 13 R1S05 R02 TRACK FEEDER D13 DC CURRENT S012-25 - 347 - AI - - - -
TB2-13 (-) IW.280 38 R0S13 IW.280 33 R1S05 - - S012-26 - - 430 - - - -
TB2-14 (+) IW.282 39 R0S13 IW.282 14 R1S05 R02 DC BUSBAR DC VOLTAGE S012-27 - 348 - AI - - - -
TB2-14 (-) IW.282 40 R0S13 IW.282 34 R1S05 - - S012-28 - - 431 - - - -
TB2-15 (+) IW.284 41 R0S13 IW.284 15 R1S05 R02 NEGATIVE BUSBAR DC RETURN CURRENT S012-29 - 343 - AI - - - -
TB2-15 (-) IW.284 42 R0S13 IW.284 35 R1S05 - - S012-30 - - 426 - - - -
TB2-16 (+) IW.286 43 R0S13 IW.286 16 R1S05 - SPARE S012-31 - - - - - - -
TB2-16 (-) IW.286 44 R0S13 IW.286 36 R1S05 - - S012-32 - - - - - - -
ZS1 ZS1 1 - - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
ZS2 ZS2 2 - - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
IW 288 1 R1S06 - SPARE - - - - AI - - - -
IW 288 21 R1S06 - SPARE - - - - - - - -
IW 290 2 R1S06 - SPARE - - - - AI - - - -
IW 290 22 R1S06 - SPARE - - - - - - - -
IW 292 3 R1S06 - SPARE - - - - AI - - - -
IW 292 23 R1S06 - SPARE - - - - - - - -
IW 294 4 R1S06 - SPARE - - - - AI - - - -
IW 294 24 R1S06 - SPARE - - - - - - - -
IW 296 5 R1S06 - SPARE - - - - AI - - - -
IW 296 25 R1S06 - SPARE - - - - - - - -
IW 298 6 R1S06 - SPARE - - - - AI - - - -
IW 298 26 R1S06 - SPARE - - - - - - - -
IW 300 7 R1S06 - SPARE - - - - AI - - - -
IW 300 27 R1S06 - SPARE - - - - - - - -
IW 302 8 R1S06 - SPARE - - - - AI - - - -
IW 302 28 R1S06 - SPARE - - - - - - - -
IW 304 9 R1S06 - SPARE - - - - AI - - - -
IW 304 29 R1S06 - SPARE - - - - - - - -
IW 306 10 R1S06 - SPARE - - - - AI - - - -
IW 306 30 R1S06 - SPARE - - - - - - - -
IW 308 11 R1S06 - SPARE - - - - AI - - - -
IW 308 31 R1S06 - SPARE - - - - - - - -
IW 310 12 R1S06 - SPARE - - - - AI - - - -
IW 310 32 R1S06 - SPARE - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 20 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

IW 312 13 R1S06 - SPARE - - - - AI - - - -


IW 312 33 R1S06 - SPARE - - - - - - - -
IW 314 14 R1S06 - SPARE - - - - AI - - - -
IW 314 34 R1S06 - SPARE - - - - - - - -
IW 316 15 R1S06 - SPARE - - - - AI - - - -
IW 316 35 R1S06 - SPARE - - - - - - - -
IW 318 16 R1S06 - SPARE - - - - - - - -
IW 318 36 R1S06 - SPARE - - - - - - - -
S110-RD - - - - - - S012- - - - - - - - -
S110-BK - - - - - - S012- - - - - - - - -
S112-BL - - - - - - S012- - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 21 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only)
Modules) RTU Modules)

Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10)
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - - - - - S009-1 - - - - - - - -
ZS1 ZS1 1 R0S12 ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
ZS2 ZS2 2 R0S12 ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - -
RL-01 Q4.0 4 R0S12 Q4.0 2 R1S02 R02 RING MAIN H03 VCB OPEN S009-2 - 16 - CO - - - -
RL-02 Q4.1 5 R0S12 Q4.1 3 R1S02 R02 RING MAIN H03 VCB CLOSE S009-3 - 15 - CO - - - -
RL-03 Q4.2 6 R0S12 Q4.2 6 R1S02 R02 RING MAIN H04 VCB OPEN S009-4 - 22 - CO - - - -
RL-04 Q4.3 7 R0S12 Q4.3 7 R1S02 R02 RING MAIN H04 VCB CLOSE S009-5 - 21 - CO - - - -
RL-05 Q4.4 8 R0S12 Q4.4 12 R1S02 R02 RECTIFIER FEEDER H01 VCB OPEN S009-6 - 64 - CO - - - -
RL-06 Q4.5 9 R0S12 Q4.5 13 R1S02 R02 RECTIFIER FEEDER H01 VCB CLOSE S009-7 - 63 - CO - - - -
RL-07 Q4.6 10 R0S12 Q4.6 16 R1S02 R02 RECTIFIER FEEDER D1 DCCB OPEN S009-8 - 77 - CO - - - -
RL-08 Q4.7 11 R0S12 Q4.7 17 R1S02 R02 RECTIFIER FEEDER D1 DCCB CLOSE S009-9 - 78 - CO - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-09 Q5.0 15 R0S12 Q5.0 22 R1S02 R02 RECTIFIER FEEDER H02 VCB OPEN S009-10 - 66 - CO - - - -
RL-10 Q5.1 16 R0S12 Q5.1 23 R1S02 R02 RECTIFIER FEEDER H02 VCB CLOSE S009-11 - 65 - CO - - - -
RL-11 Q5.2 17 R0S12 Q5.2 26 R1S02 R02 RECTIFIER FEEDER D2 DCCB OPEN S009-12 - 75 - CO - - - -
RL-12 Q5.3 18 R0S12 Q5.3 27 R1S02 R02 RECTIFIER FEEDER D2 DCCB CLOSE S009-13 - 76 - CO - - - -
RL-13 Q5.4 19 R0S12 Q5.4 32 R1S02 R02 TRACK FEEDER D12 DCCB OPEN S009-14 - 28 - CO - - - -
RL-14 Q5.5 20 R0S12 Q5.5 33 R1S02 R02 TRACK FEEDER D12 DCCB CLOSE S009-15 - 29 - CO - - - -
RL-15 Q5.6 21 R0S12 Q5.6 36 R1S02 R02 TRACK FEEDER D11 DCCB OPEN S009-16 - 34 - CO - - - -
RL-16 Q5.7 22 R0S12 Q5.7 37 R1S02 R02 TRACK FEEDER D11 DCCB CLOSE S009-17 - 35 - CO - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-17 Q6.0 26 R0S12 Q6.0 2 R1S03 R02 TRACK FEEDER D14 DCCB OPEN S009-18 - 40 - CO - - - -
RL-18 Q6.1 27 R0S12 Q6.1 3 R1S03 R02 TRACK FEEDER D14 DCCB CLOSE S009-19 - 41 - CO - - - -
RL-19 Q6.2 28 R0S12 Q6.2 6 R1S03 R02 TRACK FEEDER D13 DCCB OPEN S009-20 - 46 - CO - - - -
RL-20 Q6.3 29 R0S12 Q6.3 7 R1S03 R02 TRACK FEEDER D13 DCCB CLOSE S009-21 - 47 - CO - - - -
RL-21 Q6.4 30 R0S12 Q6.4 12 R1S03 R02 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S009-22 - 68 - CO - - - -
RL-22 Q6.5 31 R0S12 Q6.5 13 R1S03 - SPARE S009-23 - - - - - - - -
RL-23 Q6.6 32 R0S12 Q6.6 16 R1S03 R02 050 SECTION BREAKER S13 DCCB OPEN S009-24 - 185 - CO - - - -
RL-24 Q6.7 33 R0S12 Q6.7 17 R1S03 R02 050 SECTION BREAKER S13 DCCB CLOSE S009-25 - 186 - CO - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-25 Q7.0 37 R0S12 Q7.0 22 R1S03 R02 050 SECTION BREAKER S14 DCCB OPEN S009-26 - 195 - CO - - - -
RL-26 Q7.1 38 R0S12 Q7.1 23 R1S03 R02 050 SECTION BREAKER S14 DCCB CLOSE S009-27 - 196 - CO - - - -
RL-27 Q7.2 39 R0S12 Q7.2 26 R1S03 R02 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - -
RL-28 Q7.3 40 R0S12 Q7.3 27 R1S03 R02 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - -
RL-29 Q7.4 41 R0S12 Q7.4 32 R1S03 - SPARE S049 - RC5-7 - - - - -
RL-30 Q7.5 42 R0S12 Q7.5 33 R1S03 - SPARE S009-31 - - - - - - -
RL-31 Q7.6 43 R0S12 Q7.6 36 R1S03 - SPARE S009-32 - - - - - - -
RL-32 Q7.7 44 R0S12 Q7.7 37 R1S03 - SPARE S009-33 - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S12 UC- - R1S03 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - -
FR1 FR1 35 R0S12 UC- - R1S03 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - -
UE0 UE0 45 R0S12 UC+ 31 R1S03 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - -
UE1 UE1 46 R0S12 UC+ 35 R1S03 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 22 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 23 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - - - -
- - - - YES 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 24 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC NC - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 25 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- - - - - - - - - - - - - - - - - - -
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 26 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - YES 0 - - - - - - - - - C NC - -
ERROR - - - YES 0 - - - - - - - - - - - NC C
- - - - NO 0 - - - - - - - - - C NC - -
ERROR - - - NO 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 27 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC NC C
- - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143 -6.786 7.200 8.143
- 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - - 6.333 7.521
- 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - - 4.524 5.429
- 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 - - 9.025 9.310
- -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
- 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - - 6.333 7.521
- 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - - 4.524 5.429
- 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 - - 9.025 9.310
- -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC NC C
- - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143 -6.786 7.200 8.143
- 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 7.500 9.500 - - 285 361 - - 7.125 9.025
- 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 7.500 9.500 - - 285 361 - - 7.125 9.025
- 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.5 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - 0.800 7.920 9.680 10.000 1.05 10.395 11.495 11.875 0.840 8.316 9.196 9.500
- -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC NC C
- - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143 -6.786 7.200 8.143
- 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - 4.150 5.300 9.500 9.800 435.75 556.5 902.5 931 4.358 5.565 9.025 9.310
- 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - 6.667 7.619 - - 3325 3800 - - 6.333 7.238
- - to - - to - - - - - - - - - - - - - - - - -
- - to - - to - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- -20 to +20 -7000 to 7000 A dc - - 0.01 -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.5 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 28 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - to - - - - - - - - - - - - - - - - -
- - to - - to - - - - - - - - - - - - - - - - -
- - to - - to - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 29 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(DB only) Range (mA) Values Of-State Value
Time
Delay
(11) to to Units (sec) LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
LL L H HH

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS02 [RS02] 30 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R03 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R03 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 365 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R03 RING MAIN H03 SOLKOR TRIP S005-6 - 354 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R03 RING MAIN H03 PILOT WIRE ALARM S005-7 - 356 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R03 RING MAIN H03 OVERLOAD ALARM S005-8 - 355 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 - SPARE S005-9 - - - - - - - - - - - - - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R03 RING MAIN H04 CONTROL SELECTOR SWITCH S005-12 - 175 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R03 RING MAIN H04 O/C EARTH FAULT TRIP S005-13 - 366 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R03 RING MAIN H04 SOLKOR TRIP S005-14 - 367 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R03 RING MAIN H04 PILOT WIRE ALARM S005-15 - 368 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R03 RING MAIN H04 OVERLOAD ALARM S005-16 - 369 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 - SPARE S005-17 - - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 - SPARE S005-18 - - - - - - - - - - - - - - - - - - - - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 - SPARE S005-19 - - - - - - - - - - - - - - - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R03 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-22 - 6 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R03 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-23 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R03 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-24 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R03 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-25 - 210 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R03 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-26 - 211 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R03 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-27 - 212 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R03 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-28 - 213 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R03 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-29 - 214 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R03 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-30 - 215 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R03 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-31 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R03 RECTIFIER 1 FRAME EARTH TRIP S005-32 - 217 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R03 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-33 - 218 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R03 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-34 - 219 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R03 RECTIFIER 1 DIODE OVER TEMP ALARM S005-35 - 220 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R03 RECTIFIER 1 DIODE OVER TEMP TRIP S005-36 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R03 RECTIFIER 1 REVERSE CURRENT TRIP S005-37 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R03 RECTIFIER 1 SURGE ARRESTOR TRIP S005-38 - 223 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R03 RECTIFIER 1 FILTER CIRCUIT ALARM S005-39 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R03 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-40 - 225 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 - SPARE S005-41 - - - - - - - - - - - - - - - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R03 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S005-44 - 58 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 - SPARE S005-45 - - - - - - - - - - - - - - - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R03 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S005-48 - 10 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R03 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-2 - 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R03 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-3 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R03 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-4 - 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R03 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-5 - 229 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R03 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-6 - 230 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R03 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-7 - 231 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R03 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-8 - 232 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R03 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-9 - 233 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R03 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-10 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R03 RECTIFIER 2 FRAME EARTH TRIP S006-11 - 235 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R03 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-12 - 236 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R03 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-13 - 237 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R03 RECTIFIER 2 DIODE OVER TEMP ALARM S006-14 - 238 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R03 RECTIFIER 2 DIODE OVER TEMP TRIP S006-15 - 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R03 RECTIFIER 2 REVERSE CURRENT TRIP S006-16 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R03 RECTIFIER 2 SURGE ARRESTOR TRIP S006-17 - 241 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R03 RECTIFIER 2 FILTER CIRCUIT ALARM S006-18 - 242 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R03 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-19 - 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 - SPARE S006-20 - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R03 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-23 - 64 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 - SPARE S006-24 - - - - - - - - - - - - - - - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R03 AUXILIARY TRANSFORMER 11KV SWITCH H5 S006-25 - 2 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 - SPARE S006-26 - 1 - - - - - - - - - - - - - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R03 AUXILIARY TRANSFORMER 11KV SW H5 FUSE BLOWN TRIP S006-27 - 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R03 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-28 - 245 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 - SPARE S006-29 - 363 - - - - - - - - - - - - - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R03 750V DCCB TRIP CCT SUPERVISION ALARM S006-30 - 371 - SB - ALARM NORMAL - - - - - NO 0 - - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 31 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R03 TRACK FEEDER D27 CONTROL SELECTOR SWITCH S006-33 - 65 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R03 TRACK FEEDER D27 INSTANT OVERCURRENT S006-34 - 360 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R03 TRACK FEEDER D27 RATE OF RISE TRIP S006-35 - 361 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R03 TRACK FEEDER D27 LINE TESTING S006-36 - 27 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R03 TRACK FEEDER D27 LINE IMPEDANCE LOW S006-37 - 362 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S006-38 - - - - - - - - - - - - - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R03 TRACK FEEDER D28 CONTROL SELECTOR SWITCH S006-41 - 66 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R03 TRACK FEEDER D28 INSTANT OVERCURRENT S006-42 - 249 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R03 TRACK FEEDER D28 RATE OF RISE TRIP S006-43 - 250 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R03 TRACK FEEDER D28 LINE TESTING S006-44 - 33 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R03 TRACK FEEDER D28 LINE IMPEDANCE LOW S006-45 - 251 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R03 TRACK FEEDER D13 CONTROL SELECTOR SWITCH S007-2 - 67 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R03 TRACK FEEDER D13 INSTANT OVERCURRENT S007-3 - 357 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R03 TRACK FEEDER D13 RATE OF RISE TRIP S007-4 - 358 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R03 TRACK FEEDER D13 LINE TESTING S007-5 - 39 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R03 TRACK FEEDER D13 LINE IMPEDANCE LOW S007-6 - 359 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R03 TRACK FEEDER D14 CONTROL SELECTOR SWITCH S007-10 - 68 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R03 TRACK FEEDER D14 INSTANT OVERCURRENT S007-11 - 246 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R03 TRACK FEEDER D14 RATE OF RISE TRIP S007-12 - 247 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R03 TRACK FEEDER D14 LINE TESTING S007-13 - 46 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R03 TRACK FEEDER D14 LINE IMPEDANCE LOW S007-14 - 248 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R03 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-18 - 364 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -

DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R03 AC/DC SYSTEM MAINS FAILED ALARM S007-19 - 198 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R03 AC/DC SYSTEM 380V FEEDER MCB S007-20 - 199 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R03 AC/DC SYSTEM AC EARTH FAULT TRIP S007-21 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R03 AC/DC SYSTEM BATTERY CHARGER S007-22 - 201 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R03 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-23 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R03 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-24 - 203 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R03 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-25 - 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R03 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-26 - 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R03 AC/DC SYSTEM 110V DC COMMON FEEDER S007-27 - 206 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R03 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-28 - 207 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R03 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-29 - 391 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R03 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-30 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R03 COMMON EQUIPMENT INTRUDER ALARM S007-31 - 393 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R03 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 - SPARE S007-33 - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R03 RING MAIN H03 VCB OPENED S005-2 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R03 RING MAIN H03 VCB CLOSED S005-3 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R03 RING MAIN H04 VCB OPENED S005-10 - 173 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R03 RING MAIN H04 VCB CLOSED S005-11 - 174 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R03 RECTIFIER FEEDER H01 VCB OPENED S005-20 - 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R03 RECTIFIER FEEDER H01 VCB CLOSED S005-21 - 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R03 RECTIFIER FEEDER D1 DCCB OPENED S005-42 - 52 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R03 RECTIFIER FEEDER D1 DCCB CLOSED S005-43 - 53 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R03 RECTIFIER FEEDER H02 VCB OPENED S005-46 - 7 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R03 RECTIFIER FEEDER H02 VCB CLOSED S005-47 - 8 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R03 RECTIFIER FEEDER D2 DCCB OPENED S006-21 - 55 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R03 RECTIFIER FEEDER D2 DCCB CLOSED S006-22 - 56 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R03 TRACK FEEDER D27 DCCB OPENED S006-31 - 23 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R03 TRACK FEEDER D27 DCCB CLOSED S006-32 - 24 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R03 TRACK FEEDER D28 DCCB OPENED S006-39 - 29 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R03 TRACK FEEDER D28 DCCB CLOSED S006-40 - 30 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R03 TRACK FEEDER D13 DCCB OPENED S006-47 - 35 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R03 TRACK FEEDER D13 DCCB CLOSED S006-48 - 36 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R03 TRACK FEEDER D14 DCCB OPENED S007-8 - 41 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R03 TRACK FEEDER D14 DCCB CLOSED S007-9 - 42 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R03 DC COMMON EQUIPMENT D07 DCCB Earth Switch Open S007-16 - 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - -

DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R03 DC COMMON EQUIPMENT D07 DCCB Earth Switch Close S007-17 - 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - -

DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R03 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R03 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
I20.0 1 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I20.1 2 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I20.2 3 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I20.3 4 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I20.4 5 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I20.5 6 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I20.6 7 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I20.7 8 R0S06 - SPARE - - - - - - - - - - - - - - - - - - - - - -
- 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I21.0 11 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I21.1 12 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I21.2 13 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I21.3 14 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I21.4 15 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I21.5 16 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 32 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

I21.6 17 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -


I21.7 18 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I22.0 21 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I22.1 22 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I22.2 23 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I22.3 24 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I22.4 25 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I22.5 26 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I22.6 27 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I22.7 28 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
- 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I23.0 31 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I23.1 32 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I23.2 33 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I23.3 34 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I23.4 35 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I23.5 36 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I23.6 37 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
I23.7 38 R0S06 - SPARE - - - - - - - - - - - - NO 0 - - - - - - - -
2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - -
2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 33 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S12 IW.256 1 R1S04 R03 TRACK FEEDER D27 DC CURRENT S009-1 - 344 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00%
TB2-1 (-) IW.256 5 R0S12 IW.256 21 R1S04 - - S009-2 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520
TB2-2 (+) IW.258 6 R0S12 IW.258 2 R1S04 R03 RECTIFIER FEEDER H01 CURRENT S009-3 - 335 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00%
TB2-2 (-) IW.258 7 R0S12 IW.258 22 R1S04 - - S009-4 - - 418 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76
TB2-3 (+) IW.260 8 R0S12 IW.260 3 R1S04 R03 RECTIFIER UNIT 1 DC CURRENT S009-5 - 339 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00%
TB2-3 (-) IW.260 9 R0S12 IW.260 23 R1S04 - - S009-6 - - 422 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375
TB2-4 (+) IW.262 10 R0S12 IW.262 4 R1S04 R03 RECTIFIER UNIT 1 DC VOLTAGE S009-7 - 340 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00%
TB2-4 (-) IW.262 11 R0S12 IW.262 24 R1S04 - - S009-8 - - 423 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5
TB2-5 (+) IW.264 15 R0S12 IW.264 5 R1S04 R03 TRACK FEEDER D28 DC CURRENT S009-9 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00%
TB2-5 (-) IW.264 16 R0S12 IW.264 25 R1S04 - - S009-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520
TB2-6 (+) IW.266 17 R0S12 IW.266 6 R1S04 R03 RECTIFIER FEEDER H02 CURRENT S009-11 - 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00%
TB2-6 (-) IW.266 18 R0S12 IW.266 26 R1S04 - - S009-12 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76
TB2-7 (+) IW.268 19 R0S12 IW.268 7 R1S04 R03 RECTIFIER UNIT 2 DC CURRENT S009-13 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00%
TB2-7 (-) IW.268 20 R0S12 IW.268 27 R1S04 - - S009-14 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375
TB2-8 (+) IW.270 21 R0S12 IW.270 8 R1S04 R03 RECTIFIER UNIT 2 DC VOLTAGE S009-15 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00%
TB2-8 (-) IW.270 22 R0S12 IW.270 28 R1S04 - - S009-16 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5
TB2-9 (+) IW.272 26 R0S12 IW.272 9 R1S04 R03 TRACK FEEDER D13 DC CURRENT S009-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00%
TB2-9 (-) IW.272 27 R0S12 IW.272 29 R1S04 - - S009-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375
TB2-10 (+) IW.274 28 R0S12 IW.274 10 R1S04 R03 RING MAIN H03 CURRENT S009-19 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00%
TB2-10 (-) IW.274 29 R0S12 IW.274 30 R1S04 - - S009-20 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285
TB2-11 (+) IW.276 30 R0S12 IW.276 11 R1S04 R03 RING MAIN H04 CURRENT S009-21 - 350 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00%
TB2-11 (-) IW.276 31 R0S12 IW.276 31 R1S04 - - S009-22 - - 433 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285
TB2-12 (+) IW.278 32 R0S12 IW.278 12 R1S04 R03 AC BUSBAR VOLTAGE S009-23 - 349 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00%
TB2-12 (-) IW.278 33 R0S12 IW.278 32 R1S04 - - S009-24 - - 432 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 1.05 10.395 11.495
TB2-13 (+) IW.280 37 R0S12 IW.280 13 R1S04 R03 TRACK FEEDER D14 DC CURRENT S009-25 - 347 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00%
TB2-13 (-) IW.280 38 R0S12 IW.280 33 R1S04 - - S009-26 - - 430 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520
TB2-14 (+) IW.282 39 R0S12 IW.282 14 R1S04 R03 DC BUSBAR DC VOLTAGE S009-27 - 348 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00%
TB2-14 (-) IW.282 40 R0S12 IW.282 34 R1S04 - - S009-28 - - 431 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 435.75 556.5 902.5
TB2-15 (+) IW.284 41 R0S12 IW.284 15 R1S04 R03 NEGATIVE DC BUSBAR DC RETURN CURRENT S009-29 - 343 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00%
TB2-15 (-) IW.284 42 R0S12 IW.284 35 R1S04 - - S009-30 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325
TB2-16 (+) IW.286 43 R0S12 IW.286 16 R1S04 - SPARE S009-31 - - - - - - - - - to - - to - - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S12 IW.286 36 R1S04 - - S009-32 - - - - - - - - - to - - to - - - - - - - - - - - -
S110-RD - - R0S12 - - - - - S009-70 - 405 - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S12 - - - - - S009-71 - - 488 - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S12 - - - - - S009-72 - - 488 - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 34 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - R0S12 - - - - - S008-1 - - - - - - - - - - - - - - - - - - - - - -


IW.288 1 R1S05 - SPARE - - - - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00%
IW.288 21 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.290 2 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00%
IW.290 22 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.292 3 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00%
IW.292 23 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.294 4 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00%
IW.294 24 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.296 5 R1S05 - SPARE - - - - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00%
IW.296 25 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.298 6 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00%
IW.298 26 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.300 7 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00%
IW.300 27 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.302 8 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00%
IW.302 28 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.304 9 R1S05 - SPARE - - - - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00%
IW.304 29 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.306 10 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00%
IW.306 30 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.308 11 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00%
IW.308 31 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.310 12 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00%
IW.310 32 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.312 13 R1S05 - SPARE - - - - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2500 3000 5.00% 5.00% 5.00%
IW.312 33 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.314 14 R1S05 - SPARE - - - - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00%
IW.314 34 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.316 15 R1S05 - SPARE - - - - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00%
IW.316 35 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.318 16 R1S05 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - -
IW.318 36 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - -
ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S11 Q4.0 2 R1S02 R03 RING MAIN H03 VCB OPEN S008-2 - 15 - CO - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S11 Q4.1 3 R1S02 R03 RING MAIN H03 VCB CLOSE S008-3 - 16 - CO - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S11 Q4.2 6 R1S02 R03 RING MAIN H04 VCB OPEN S008-4 - 176 - CO - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S11 Q4.3 7 R1S02 R03 RING MAIN H04 VCB CLOSE S008-5 - 177 - CO - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S11 Q4.4 12 R1S02 R03 RECTIFIER FEEDER H01 VCB OPEN S008-6 - 70 - CO - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S11 Q4.5 13 R1S02 R03 RECTIFIER FEEDER H01 VCB CLOSE S008-7 - 69 - CO - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S11 Q4.6 16 R1S02 R03 RECTIFIER FEEDER D1 DCCB OPEN S008-8 - 17 - CO - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S11 Q4.7 17 R1S02 R03 RECTIFIER FEEDER D1 DCCB CLOSE S008-9 - 18 - CO - - - - - - - - - - - - - - - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-09 Q5.0 15 R0S11 Q5.0 22 R1S02 R03 RECTIFIER FEEDER H02 VCB OPEN S008-10 - 72 - CO - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S11 Q5.1 23 R1S02 R03 RECTIFIER FEEDER H02 VCB CLOSE S008-11 - 71 - CO - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S11 Q5.2 26 R1S02 R03 RECTIFIER FEEDER D2 DCCB OPEN S008-12 - 19 - CO - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S11 Q5.3 27 R1S02 R03 RECTIFIER FEEDER D2 DCCB CLOSE S008-13 - 20 - CO - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S11 Q5.4 32 R1S02 R03 TRACK FEEDER D27 DCCB OPEN S008-14 - 25 - CO - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S11 Q5.5 33 R1S02 R03 TRACK FEEDER D27 DCCB CLOSE S008-15 - 26 - CO - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S11 Q5.6 36 R1S02 R03 TRACK FEEDER D28 DCCB OPEN S008-16 - 31 - CO - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S11 Q5.7 37 R1S02 R03 TRACK FEEDER D28 DCCB CLOSE S008-17 - 32 - CO - - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-17 Q6.0 26 R0S11 Q6.0 2 R1S03 R03 TRACK FEEDER D13 DCCB OPEN S008-18 - 37 - CO - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S11 Q6.1 3 R1S03 R03 TRACK FEEDER D13 DCCB CLOSE S008-19 - 38 - CO - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S11 Q6.2 6 R1S03 R03 TRACK FEEDER D14 DCCB OPEN S008-20 - 43 - CO - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S11 Q6.3 7 R1S03 R03 TRACK FEEDER D14 DCCB CLOSE S008-21 - 44 - CO - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S11 Q6.4 12 R1S03 R03 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S008-22 - 50 - CO - - - - - - - - - - - - - - - - - -

RL-22 Q6.5 31 R0S11 Q6.5 13 R1S03 - SPARE S008-23 - - - - - - - - - - - - - - - - - - - - - -


RL-23 Q6.6 32 R0S11 Q6.6 16 R1S03 R03 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S11 Q6.7 17 R1S03 R03 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - -
L+ 19 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-25 Q7.0 37 R0S11 Q7.0 22 R1S03 - SPARE S008-26 - - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S11 Q7.1 23 R1S03 - SPARE S008-27 - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S11 Q7.2 26 R1S03 - SPARE S008-28 - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S11 Q7.3 27 R1S03 - SPARE S008-29 - - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S11 Q7.4 32 R1S03 - SPARE S008-30 - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S11 Q7.5 33 R1S03 - SPARE S008-31 - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S11 Q7.6 36 R1S03 - SPARE S008-32 - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S11 Q7.7 37 R1S03 - SPARE S008-33 - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S11 UC- - R1S03 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S11 UC- - R1S03 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S11 UC+ 31 R1S03 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S11 UC+ 35 R1S03 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 35 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - -
- - - - -
- NC NC - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- NC NC - -
- NC C - -
- - - - -
- - - - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- - - - -
- NC NC - -
- NC C - -
- - - - -
- - - - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- - - - -
- - - - -
- NC C - -
- - - - -
- NC NC - -
- - - - -
- NC NC - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- - - - -
- NC NC - -
- - - - -
- NC NC - -
- - - - -
- NC C - -
- NC C - -
- - - - -
- C NC - -
- - - - -
- - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 36 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - -
- - - - -
- NC NC - -
- NC C - -
- NC C - -
- NC NC - -
- NC C - -
- - - - -
- NC NC - -
- NC C - -
- - - - -
- - - - -
- NC C - -
- NC NC - -
- NC C - -
- - - - -
- NC NC - -
- NC C - -
- NC C - -
- NC NC - -
- - - - -
- - - - -
- NC C - -
- - - - -
- NC NC - -
- NC C - -
- NC C - -
- NC NC - -
- NC C - -
- - - - -
- - - - -
- - - - -
- NC C - -

- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- - - - -
- - - - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- - - - -
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- - - - -
- - - - -
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- - - - -
- - - - -
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -

- - - NC C

- C NC - -
- - - NC C
- - - - -
- - - - -
- - - - -
- - - - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- NC C - -
- - - - -
- - - - -
- - - - -
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C

Unrestricted 749775924.xlsx/RS03 [RS03] 37 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- C NC - -
- - - NC C
- - - - -
- - - - -
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- - - - -
- - - - -
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C
- C NC - -
- - - NC C

Unrestricted 749775924.xlsx/RS03 [RS03] 38 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - -
- - - - -
5.00% C NC NC C
2850 -8.143 -6.786 7.200 8.143
5.00% C NC NC C
90.25 - - 6.333 7.521
5.00% C NC NC C
2850 - - 4.524 5.429
5.00% C NC NC C
931 - - 9.025 9.310
5.00% C NC NC C
2850 -8.143 -6.786 7.200 8.143
5.00% C NC NC C
90.25 - - 6.333 7.521
5.00% C NC NC C
2850 - - 4.524 5.429
5.00% C NC NC C
931 - - 9.025 9.310
5.00% C NC NC C
2850 -8.143 -6.786 6.786 8.143
5.00% C NC NC C
361 - - 7.125 9.025
5.00% C NC NC C
361 - - 7.125 9.025
5.00% C NC NC C
11.78 0.840 8.316 9.196 9.424
5.00% C NC NC C
2850 -8.143 -6.786 7.200 8.143
5.00% C NC NC C
931 4.358 5.565 9.025 9.310
5.00% C NC NC C
3800 - - 6.333 7.238
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 39 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
5.00% C NC NC C
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -

- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -

- - - - -
- - - - -
- - - - -
- - - - -
- - - - -

- - - - -
- - - - -
- - - - -

- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -

- - - - -
- - - - -
- - - - -
- - - - -

Unrestricted 749775924.xlsx/RS03 [RS03] 40 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R04 MAIN INCOMER H04 CONTROL SELECTOR SWITCH S005-4 Y1 32 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R04 MAIN INCOMER H04 O/C EARTH FAULT TRIP S005-5 Y1 251 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R04 MAIN INCOMER H04 REVERSE POWER TRIP S005-6 Y1 250 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R04 MAIN INCOMER H04 INTERTRIP S005-7 Y1 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R04 RING MAIN H01 CONTROL SELECTOR SWITCH S005-10 Y1 5 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 R04 RING MAIN H01 O/C EARTH FAULT TRIP S005-11 Y1 245 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R04 RING MAIN H01 SOLKOR TRIP S005-12 Y1 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R04 RING MAIN H01 OVERLOAD ALARM S005-13 Y1 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 - SPARE S005-14 Y1 - - - - - - - - - - - - - - - - - - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 - SPARE S005-15 Y1 - - - - - - - - - - - - - - - - - - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R04 RING MAIN H03 CONTROL SELECTOR SWITCH S005-18 Y1 20 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 R04 RING MAIN H03 O/C EARTH FAULT TRIP S005-19 Y1 242 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 R04 RING MAIN H03 SOLKOR TRIP S005-20 Y1 241 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 R04 RING MAIN H03 OVERLOAD ALARM S005-21 Y1 240 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 - SPARE S005-22 Y1 - - - - - - - - - - - - - - - - - - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 - SPARE S005-23 Y1 - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R04 RING MAIN H06 CONTROL SELECTOR SWITCH S005-26 Y1 37 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R04 RING MAIN H06 O/C EARTH FAULT TRIP S005-27 Y1 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R04 RING MAIN H06 SOLKOR TRIP S005-28 Y1 235 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R04 RING MAIN H06 OVERLOAD ALARM S005-29 Y1 234 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 - SPARE S005-30 Y1 - - - - - - - - - - - - - - - - - - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 - SPARE S005-31 Y1 - - - - - - - - - - - - - - - - - - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R04 INTERCONNECT H07 CONTROL SELECTOR SWITCH S005-34 Y1 69 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R04 INTERCONNECT H07 O/C EARTH FAULT TRIP S005-35 Y1 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R04 INTERCONNECT H07 SOLKOR TRIP S005-36 Y1 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R04 INTERCONNECT H07 OVERLOAD ALARM S005-37 Y1 225 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 - SPARE S005-38 Y1 - - - - - - - - - - - - - - - - - - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 - SPARE S005-39 Y1 - - - - - - - - - - - - - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R04 RING MAIN H08 CONTROL SELECTOR SWITCH S005-42 Y1 171 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R04 RING MAIN H08 O/C EARTH FAULT TRIP S005-43 Y1 230 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R04 RING MAIN H08 SOLKOR TRIP S005-44 Y1 229 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R04 RING MAIN H08 OVERLOAD ALARM S005-45 Y1 228 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 - SPARE S005-46 Y1 - - - - - - - - - - - - - - - - - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 - SPARE S005-47 Y1 - - - - - - - - - - - - - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R04 RING MAIN H09 CONTROL SELECTOR SWITCH S006-3 Y1 180 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R04 RING MAIN H09 O/C EARTH FAULT TRIP S006-4 Y1 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R04 RING MAIN H09 SOLKOR TRIP S006-5 Y1 232 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R04 RING MAIN H09 OVERLOAD ALARM S006-6 Y1 231 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 - SPARE S006-7 Y1 - - - - - - - - - - - - - - - - - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 - SPARE S006-8 Y1 - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R04 STANDBY 11KV H11 CONTROL SELECTOR SWITCH S006-11 Y1 200 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R04 STANDBY 11KV H11 O/C EARTH FAULT TRIP S006-12 Y1 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R04 STANDBY 11KV H11 LOCKOUT ALARM S006-13 Y1 238 - SB FLT RESET FAULT - - - - - NO 0 - - - - - - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R04 STANDBY 11KV H11 OVERLOAD ALARM S006-14 Y1 237 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 - SPARE S006-15 Y1 - - - - - - - - - - - - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 - SPARE S006-16 Y1 - - - - - - - - - - - - - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R04 BUS SECTION H05 CONTROL SELECTOR SWITCH S006-19 Y1 49 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R04 BUS SECTION H05 O/C EARTH FAULT TRIP S006-20 Y1 248 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 - SPARE S006-21 Y1 - - - - - - - - - - - - - - - - - - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R04 AUTO CHANGEOVER PANEL INHIBIT ALARM S006-22 Y1 211 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R04 AUTO CHANGEOVER PANEL ENABLE SELECTOR SWITCH S006-23 Y1 217 - SB ACO OFF (Disable) ON (Enable) - - - - - NO 0 - - - - - - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R04 AUTO CHANGEOVER PANEL STATUS S006-24 Y1 218 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R04 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S006-27 Y1 12 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R04 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-28 Y1 84 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R04 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-29 Y1 83 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R04 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S006-30 Y1 82 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R04 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S010-2 Y 251 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R04 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S006-31 Y1 81 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R04 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S010-3 Y 250 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R04 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S010-4 Y 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R04 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S010-5 Y 248 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R04 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S010-6 Y 247 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R04 RECTIFIER 1 FRAME EARTH TRIP S010-7 Y 246 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R04 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S010-8 Y 245 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 41 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R04 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S010-9 Y 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R04 RECTIFIER 1 DIODE OVER TEMP ALARM S010-10 Y 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R04 RECTIFIER 1 DIODE OVER TEMP TRIP S010-11 Y 242 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R04 RECTIFIER 1 REVERSE CURRENT TRIP S010-12 Y 241 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R04 RECTIFIER 1 SURGE ARRESTOR TRIP S006-32 Y1 80 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 R04 RECTIFIER 1 FILTER CIRCUIT ALARM S010-13 Y 240 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R04 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S010-14 Y 239 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 - SPARE S010-15 Y - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R04 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S010-18 Y 1 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 - SPARE S010-19 Y - - - - - - - - - - - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R04 RECTIFIER FEEDER H10 CONTROL SELECTOR SWITCH S006-35 Y1 189 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 R04 RECTIFIER FEEDER H10 O/C EARTH FAULT TRIP S006-36 Y1 79 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R04 RECTIFIER FEEDER H10 OVERLOAD TRIP S006-37 Y1 78 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R04 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-38 Y1 77 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R04 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S010-20 Y 238 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R04 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-39 Y1 76 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R04 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S010-21 Y 237 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 R04 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S010-22 Y 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R04 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S010-23 Y 235 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R04 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S010-24 Y 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R04 RECTIFIER 2 FRAME EARTH TRIP S010-25 Y 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R04 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S010-26 Y 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R04 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S010-27 Y 231 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R04 RECTIFIER 2 DIODE OVER TEMP ALARM S010-28 Y 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R04 RECTIFIER 2 DIODE OVER TEMP TRIP S010-29 Y 229 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R04 RECTIFIER 2 REVERSE CURRENT TRIP S010-30 Y 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R04 RECTIFIER 2 SURGE ARRESTOR TRIP S006-40 Y1 75 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R04 RECTIFIER 2 FILTER CIRCUIT ALARM S010-31 Y 227 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R04 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S010-32 Y 226 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 - SPARE S010-33 Y - - - - - - - - - - - - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R04 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S010-36 Y 4 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 - SPARE S010-37 Y - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R04 AUXILIARY TRANSFORMER 11KV SWITCH H12 S006-41 Y1 193 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R04 MAIN INCOMER H04 AC ENERGY (PULSE) S006-42 Y1 340 423 PI - - - - - - - - - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R04 AUXILIARY TRANSFORMER 11KV SW H12 FUSE BLOWN TRIP S006-43 Y1 74 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R04 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-44 Y1 73 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R04 TRACK FEEDER D13 CONTROL SELECTOR SWITCH S010-40 Y 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R04 TRACK FEEDER D13 INSTANT OVERCURRENT S010-41 Y 224 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R04 TRACK FEEDER D13 RATE OF RISE TRIP S010-42 Y 223 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 R04 TRACK FEEDER D13 LINE TESTING S010-43 Y 10 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R04 TRACK FEEDER D13 LINE IMPEDANCE LOW S010-44 Y 222 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 - SPARE S010-45 Y - - - - - - - - - - - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R04 TRACK FEEDER D14 CONTROL SELECTOR SWITCH S010-48 Y 23 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R04 TRACK FEEDER D14 INSTANT OVERCURRENT S011-2 Y 221 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R04 TRACK FEEDER D14 RATE OF RISE TRIP S011-3 Y 220 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R04 TRACK FEEDER D14 LINE TESTING S011-4 Y 19 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R04 TRACK FEEDER D14 LINE IMPEDANCE LOW S011-5 Y 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R04 RING MAIN H13 OVERLOAD ALARM S014-8 Y1 367 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R04 TRACK FEEDER D15 CONTROL SELECTOR SWITCH S011-9 Y 32 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R04 TRACK FEEDER D15 INSTANT OVERCURRENT S011-10 Y 218 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R04 TRACK FEEDER D15 RATE OF RISE TRIP S011-11 Y 217 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R04 TRACK FEEDER D15 LINE TESTING S011-12 Y 28 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R04 TRACK FEEDER D15 LINE IMPEDANCE LOW S011-13 Y 216 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 TUM LR/WR INTERCHANGE OVPD POWER SUPPLY FAIL s014-13 Y1 56 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R04 TRACK FEEDER D16 CONTROL SELECTOR SWITCH S011-17 Y 41 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R04 TRACK FEEDER D16 INSTANT OVERCURRENT S011-18 Y 215 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R04 TRACK FEEDER D16 RATE OF RISE TRIP S011-19 Y 214 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R04 TRACK FEEDER D16 LINE TESTING S011-20 Y 37 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R04 TRACK FEEDER D16 LINE IMPEDANCE LOW S011-21 Y 213 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 TUM LR/WR INTERCHANGE OVPD OPERATING S014-12 Y1 59 - SB OPNL NORMAL OPERATED - - - - - - - - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R04 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S011-25 Y 212 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R04 AC/DC SYSTEM MAINS FAILED ALARM S011-26 Y 211 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R04 AC/DC SYSTEM 380V FEEDER MCB S011-27 Y 210 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R04 AC/DC SYSTEM AC EARTH FAULT TRIP S011-28 Y 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 42 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R0S06 R04 AC/DC SYSTEM BATTERY CHARGER S011-29 Y 208 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - -
DI-260 I20.1 5 R0S11 I20.1 2 R0S06 R04 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S011-30 Y 207 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-262 I20.2 6 R0S11 I20.2 3 R0S06 R04 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S011-31 Y 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-264 I20.3 7 R0S11 I20.3 4 R0S06 R04 AC/DC SYSTEM 11KV CONTROL VOLTAGE S011-32 Y 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - -
DI-266 I20.4 8 R0S11 I20.4 5 R0S06 R04 AC/DC SYSTEM 750V CONTROL VOLTAGE S011-33 Y 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - -
DI-268 I20.5 9 R0S11 I20.5 6 R0S06 R04 AC/DC SYSTEM 110V DC COMMON FEEDER S011-34 Y 203 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - -
DI-270 I20.6 10 R0S11 I20.6 7 R0S06 R04 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S011-35 Y 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-272 I20.7 11 R0S11 I20.7 8 R0S06 R04 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S006-45 Y1 358 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM0 UM0 12 R0S11 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R0S06 R04 COMMON EQUIPMENT FIRE PROTECTION ALARM S006-46 Y1 359 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-276 I21.1 16 R0S11 I21.1 12 R0S06 R04 COMMON EQUIPMENT INTRUDER ALARM S006-47 Y1 360 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-278 I21.2 17 R0S11 I21.2 13 R0S06 R04 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-280 I21.3 18 R0S11 I21.3 14 R0S06 R04 750V DCCB TRIP CCT SUPERVISION ALARM S011-37 Y 200 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-282 I21.4 19 R0S11 I21.4 15 R0S06 R04 RING MAIN H13 CONTROL SELECTOR SWITCH S014-4 Y1 363 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-284 I21.5 20 R0S11 I21.5 16 R0S06 R04 RING MAIN H13 O/C EARTH FAULT TRIP S014-5 Y1 369 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-286 I21.6 21 R0S11 I21.6 17 R0S06 R04 RING MAIN H13 SOLKOR TRIP S014-6 Y1 368 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-288 I21.7 22 R0S11 I21.7 18 R0S06 R04 RING MAIN H13 PILOT WIRE ALARM S014-7 Y1 371 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM1 UM1 23 R0S11 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S11 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R0S06 TUM LR/WR INTERCHANGE OVPD CONTACTOR OPEN s014-15 Y1 54 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-292 I22.1 27 R0S11 I22.1 22 R0S06 TUM LR/WR INTERCHANGE OVPD CONTACTOR CLOSE S014-9 Y1 55 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-294 I22.2 28 R0S11 I22.2 23 R0S06 TUM LR/WR INTERCHANGE OVPD MAINTENANCE ISOLATOR OPEN S014-10 Y1 57 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-296 I22.3 29 R0S11 I22.3 24 R0S06 TUM LR/WR INTERCHANGE OVPD MAINTENANCE ISOLATOR CLOSE S014-11 Y1 58 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-298 I22.4 30 R0S11 I22.4 25 R0S06 - SPARE ? ? ? - DB - - - - - - - - - - - - - -
DI-300 I22.5 31 R0S11 I22.5 26 R0S06 - SPARE ? ? ? - DB - - - - - - - - - - - - - - - - -
DI-302 I22.6 32 R0S11 I22.6 27 R0S06 - SPARE S014-14 Y1 ? DB - - - - - - - - - - - - - - - -
DI-304 I22.7 33 R0S11 I22.7 28 R0S06 - SPARE ? ? ? - DB - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S11 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R0S06 R04 MAIN INCOMER H04 VCB S005-2 Y1 30 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-308 I23.1 38 R0S11 I23.1 32 R0S06 R04 MAIN INCOMER H04 VCB S005-3 Y1 31 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-310 I23.2 39 R0S11 I23.2 33 R0S06 R04 RING MAIN H01 VCB S005-8 Y1 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-312 I23.3 40 R0S11 I23.3 34 R0S06 R04 RING MAIN H01 VCB S005-9 Y1 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-314 I23.4 41 R0S11 I23.4 35 R0S06 R04 RING MAIN H03 VCB S005-16 Y1 18 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-316 I23.5 42 R0S11 I23.5 36 R0S06 R04 RING MAIN H03 VCB S005-17 Y1 19 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-318 I23.6 43 R0S11 I23.6 37 R0S06 R04 RING MAIN H06 VCB S005-24 Y1 35 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-320 I23.7 44 R0S11 I23.7 38 R0S06 R04 RING MAIN H06 VCB S005-25 Y1 36 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
UM3 UM3 45 R0S11 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S11 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-322 I24.0 4 R0S12 I24.0 1 R0S07 R04 INTERCONNECT H07 VCB S005-32 Y1 67 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-324 I24.1 5 R0S12 I24.1 2 R0S07 R04 INTERCONNECT H07 VCB S005-33 Y1 68 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-326 I24.2 6 R0S12 I24.2 3 R0S07 R04 RING MAIN H08 VCB S005-40 Y1 169 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-328 I24.3 7 R0S12 I24.3 4 R0S07 R04 RING MAIN H08 VCB S005-41 Y1 170 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-330 I24.4 8 R0S12 I24.4 5 R0S07 R04 RING MAIN H09 VCB S005-48 Y1 178 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-332 I24.5 9 R0S12 I24.5 6 R0S07 R04 RING MAIN H09 VCB S006-2 Y1 179 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-334 I24.6 10 R0S12 I24.6 7 R0S07 R04 STANDBY 11KV H11 VCB S006-9 Y1 198 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-336 I24.7 11 R0S12 I24.7 8 R0S07 R04 STANDBY 11KV H11 VCB S006-10 Y1 199 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
UM0 UM0 12 R0S12 - 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S12 - 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-338 I25.0 15 R0S12 I25.0 11 R0S07 R04 BUS SECTION H05 VCB S006-17 Y1 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-340 I25.1 16 R0S12 I25.1 12 R0S07 R04 BUS SECTION H05 VCB S006-18 Y1 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-342 I25.2 17 R0S12 I25.2 13 R0S07 R04 RECTIFIER FEEDER H02 VCB S006-25 Y1 10 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-344 I25.3 18 R0S12 I25.3 14 R0S07 R04 RECTIFIER FEEDER H02 VCB S006-26 Y1 11 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-346 I25.4 19 R0S12 I25.4 15 R0S07 R04 RECTIFIER FEEDER D1 DCCB S010-16 Y 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-348 I25.5 20 R0S12 I25.5 16 R0S07 R04 RECTIFIER FEEDER D1 DCCB S010-17 Y 2 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-350 I25.6 21 R0S12 I25.6 17 R0S07 R04 RECTIFIER FEEDER H10 VCB S006-33 Y1 187 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-352 I25.7 22 R0S12 I25.7 18 R0S07 R04 RECTIFIER FEEDER H10 VCB S006-34 Y1 188 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
UM1 UM1 23 R0S12 1L+ 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S12 1M 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-354 I26.0 26 R0S12 I26.0 21 R0S07 R04 RECTIFIER FEEDER D2 DCCB S010-34 Y 6 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-356 I26.1 27 R0S12 I26.1 22 R0S07 R04 RECTIFIER FEEDER D2 DCCB S010-35 Y 5 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-358 I26.2 28 R0S12 I26.2 23 R0S07 R04 TRACK FEEDER D13 DCCB S010-38 Y 8 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-360 I26.3 29 R0S12 I26.3 24 R0S07 R04 TRACK FEEDER D13 DCCB S010-39 Y 9 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-362 I26.4 30 R0S12 I26.4 25 R0S07 R04 TRACK FEEDER D14 DCCB S010-46 Y 17 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-364 I26.5 31 R0S12 I26.5 26 R0S07 R04 TRACK FEEDER D14 DCCB S010-47 Y 18 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-366 I26.6 32 R0S12 I26.6 27 R0S07 R04 TRACK FEEDER D15 DCCB S011-7 Y 26 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-368 I26.7 33 R0S12 I26.7 28 R0S07 R04 TRACK FEEDER D15 DCCB S011-8 Y 27 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
UM2 UM2 34 R0S12 - 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S12 - 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-370 I27.0 37 R0S12 I27.0 31 R0S07 R04 TRACK FEEDER D16 DCCB S011-15 Y 35 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-372 I27.1 38 R0S12 I27.1 32 R0S07 R04 TRACK FEEDER D16 DCCB S011-16 Y 36 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-374 I27.2 39 R0S12 I27.2 33 R0S07 R04 DC COMMON EQUIPMENT D07 CONTACTOR S011-23 Y 45 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-376 I27.3 40 R0S12 I27.3 34 R0S07 R04 DC COMMON EQUIPMENT D07 CONTACTOR S011-24 Y 44 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-378 I27.4 41 R0S12 I27.4 35 R0S07 R04 RING MAIN H13 VCB S014-2 Y1 361 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-380 I27.5 42 R0S12 I27.5 36 R0S07 R04 RING MAIN H13 VCB S014-3 Y1 362 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-382 I27.6 43 R0S12 I27.6 37 R0S07 R04 DUMMY CB VCB POSITION internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - -
DI-384 I27.7 44 R0S12 I27.7 38 R0S07 R04 DUMMY CB VCB POSITION internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - -
UM3 UM3 45 R0S12 2L+ 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S12 2M 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
I28.0 1 R0S08 - SPARE S006-33 - - - - - - - - - - - NO 0 - - - - - - -
I28.1 2 R0S08 - SPARE S006-34 - - - - - - - - - - - NO 0 - - - - - - -
I28.2 3 R0S08 - SPARE S006-35 - - - - - - - - - - - NO 0 - - - - - - -
I28.3 4 R0S08 - SPARE S006-36 - - - - - - - - - - - NO 0 - - - - - - -
I28.4 5 R0S08 - SPARE S006-37 - - - - - - - - - - - NO 0 - - - - - - -
I28.5 6 R0S08 - SPARE S006-38 - - - - - - - - - - - - - - - - - - - -
I28.6 7 R0S08 - SPARE S006-41 - - - - - - - - - - - NO 0 - - - - - - -
I28.7 8 R0S08 - SPARE S006-42 - - - - - - - - - - - NO 0 - - - - - - -
- 19 R0S08 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
- 20 R0S08 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
I29.0 11 R0S08 - SPARE S006-43 - - - - - - - - - - - NO 0 - - - - - - -
I29.1 12 R0S08 - SPARE S006-44 - - - - - - - - - - - NO 0 - - - - - - -
I29.2 13 R0S08 - SPARE S006-45 - - - - - - - - - - - NO 0 - - - - - - -
I29.3 14 R0S08 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - -
I29.4 15 R0S08 - SPARE S007-2 - - - - - - - - - - - NO 0 - - - - - - -
I29.5 16 R0S08 - SPARE S007-3 - - - - - - - - - - - NO 0 - - - - - - -
I29.6 17 R0S08 - SPARE S007-4 - - - - - - - - - - - NO 0 - - - - - - -
I29.7 18 R0S08 - SPARE S007-5 - - - - - - - - - - - NO 0 - - - - - - -
1L+ 19 R0S08 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
1M 20 R0S08 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
I30.0 21 R0S08 - SPARE S007-6 - - - - - - - - - - - NO 0 - - - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 43 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

I30.1 22 R0S08 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - -


I30.2 23 R0S08 - SPARE S007-10 - - - - - - - - - - - NO 0 - - - - - - -
I30.3 24 R0S08 - SPARE S007-11 - - - - - - - - - - - NO 0 - - - - - - -
I30.4 25 R0S08 - SPARE S007-12 - - - - - - - - - - - NO 0 - - - - - - -
I30.5 26 R0S08 - SPARE S007-13 - - - - - - - - - - - NO 0 - - - - - - -
I30.6 27 R0S08 - SPARE S007-14 - - - - - - - - - - - NO 0 - - - - - - -
I30.7 28 R0S08 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - -
- 39 R0S08 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
- 40 R0S08 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
I31.0 31 R0S08 - SPARE S007-18 - - - - - - - - - - - NO 0 - - - - - - -
I31.1 32 R0S08 - SPARE S007-19 - - - - - - - - - - - NO 0 - - - - - - -
I31.2 33 R0S08 - SPARE S007-20 - - - - - - - - - - - NO 0 - - - - - - -
I31.3 34 R0S08 - SPARE S007-21 - - - - - - - - - - - NO 0 - - - - - - -
I31.4 35 R0S08 - SPARE S007-22 - - - - - - - - - - - NO 0 - - - - - - -
I31.5 36 R0S08 - SPARE S007-23 - - - - - - - - - - - NO 0 - - - - - - -
I31.6 37 R0S08 - SPARE S007-24 - - - - - - - - - - - NO 0 - - - - - - -
I31.7 38 R0S08 - SPARE S007-25 - - - - - - - - - - - NO 0 - - - - - - -
2L+ 39 R0S08 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
2M 40 R0S08 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 44 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S15 IW.256 1 R1S06 R04 MAIN INCOMER H04 POWER FACTOR S013-1 Y1 341 - AI - - - - - -10 to +10
cos(60deg) to
lagging cos(60deg) leading - - - 1.0% 0.7 0.8 0.65 0.75 5.00% 5.00%
TB2-1 (-) IW.256 5 R0S15 IW.256 21 R1S06 - - S008-2 - - 424 - - - - - - to - - to - - - - - 49.458 41.410 8.243 6.902 42.69278389 32.85988038

TB2-2 (+) IW.258 6 R0S15 IW.258 2 R1S06 R04 MAIN INCOMER H04 CURRENT S008-3 Y1 338 - AI - - - - - 0 to +10 0 to 2000 A ac - - 1.0% - - 1500 1800 5.00% 5.00%
TB2-2 (-) IW.258 7 R0S15 IW.258 22 R1S06 - - S008-4 - - 421 - - - - - - to - - to - - - - - - - 7.500 9.000 - -
TB2-3 (+) IW.260 8 R0S15 IW.260 3 R1S06 R04 MAIN INCOMER H04 VOLTAGE S008-5 Y1 339 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00%
TB2-3 (-) IW.260 9 R0S15 IW.260 23 R1S06 - - S008-6 - - 422 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 1.050 10.395
TB2-4 (+) IW.262 10 R0S15 IW.262 4 R1S06 R04 MAIN INCOMER H04 POWER S008-7 Y1 340 - AI - - - - - 0 to +10 0 to 50 MW - - 1.0% - - - - 5.00% 5.00%
TB2-4 (-) IW.262 11 R0S15 IW.262 24 R1S06 - - S008-8 - - 423 - - - - - - to - - to - - - - - - - - - - -
TB2-5 (+) IW.264 15 R0S15 IW.264 5 R1S06 R04 TRACK FEEDER D13 DC CURRENT S013-1 Y 340 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00%
TB2-5 (-) IW.264 16 R0S15 IW.264 25 R1S06 - - S013-2 - - 423 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375
TB2-6 (+) IW.266 17 R0S15 IW.266 6 R1S06 R04 RING MAIN H01 CURRENT S008-9 Y1 335 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-6 (-) IW.266 18 R0S15 IW.266 26 R1S06 - - S008-10 - - 418 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-7 (+) IW.268 19 R0S15 IW.268 7 R1S06 R04 RING MAIN H03 CURRENT S008-11 Y1 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-7 (-) IW.268 20 R0S15 IW.268 27 R1S06 - - S008-12 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-8 (+) IW.270 21 R0S15 IW.270 8 R1S06 R04 RING MAIN H06 CURRENT S008-13 Y1 345 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-8 (-) IW.270 22 R0S15 IW.270 28 R1S06 - - S008-14 - - 428 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-9 (+) IW.272 26 R0S15 IW.272 9 R1S06 R04 TRACK FEEDER D14 DC CURRENT S013-3 Y 341 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00%
TB2-9 (-) IW.272 27 R0S15 IW.272 29 R1S06 - - S013-4 - - 424 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375
TB2-10 (+) IW.274 28 R0S15 IW.274 10 R1S06 R04 INTERCONNECT H07 CURRENT S008-15 Y1 346 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-10 (-) IW.274 29 R0S15 IW.274 30 R1S06 - - S008-16 - - 429 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-11 (+) IW.276 30 R0S15 IW.276 11 R1S06 R04 RING MAIN H08 CURRENT S008-17 Y1 347 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-11 (-) IW.276 31 R0S15 IW.276 31 R1S06 - - S008-18 - - 430 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-12 (+) IW.278 32 R0S15 IW.278 12 R1S06 R04 RING MAIN H09 CURRENT S008-19 Y1 348 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-12 (-) IW.278 33 R0S15 IW.278 32 R1S06 - - S008-20 - - 431 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-13 (+) IW.280 37 R0S15 IW.280 13 R1S06 R04 TRACK FEEDER D15 DC CURRENT S013-5 Y 342 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00%
TB2-13 (-) IW.280 38 R0S15 IW.280 33 R1S06 - - S013-6 - - 425 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375
TB2-14 (+) IW.282 39 R0S15 IW.282 14 R1S06 R04 AC BUSBAR CURRENT S008-21 Y1 342 - AI - - - - - 0 to +10 0 to 2000 A ac - - 1.0% - - 1500 1800 5.00% 5.00%
TB2-14 (-) IW.282 40 R0S15 IW.282 34 R1S06 - - S008-22 - - 425 - - - - - - to - - to - - - - - - - 7.500 9.000 - -
TB2-15 (+) IW.284 41 R0S15 IW.284 15 R1S06 R04 AC BUSBAR LHS VOLTAGE S008-23 Y1 343 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00%
TB2-15 (-) IW.284 42 R0S15 IW.284 35 R1S06 - - S008-24 - - 426 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 1.050 10.395
TB2-16 (+) IW.286 43 R0S15 IW.286 16 R1S06 R04 AC BUSBAR RHS VOLTAGE S008-25 Y1 344 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 0.05 0.05
TB2-16 (-) IW.286 44 R0S15 IW.286 36 R1S06 - - S008-26 - - 427 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 1.05 10.395
ZS1 ZS1 1 R0S16 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S16 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
TB2-17 (+) IW.288 4 R0S16 IW.288 1 R1S07 R04 TRACK FEEDER D16 DC CURRENT S013-7 Y 343 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00%
TB2-17 (+) IW.288 5 R0S16 IW.288 21 R1S07 - - S013-8 - - 426 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375
TB2-18 (+) IW.290 6 R0S16 IW.290 2 R1S07 R04 RECTIFIER FEEDER H02 CURRENT S008-27 Y1 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00%
TB2-18 (-) IW.290 7 R0S16 IW.290 22 R1S07 - - S008-28 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - -
TB2-19 (+) IW.292 8 R0S16 IW.292 3 R1S07 R04 RECTIFIER UNIT 1 DC CURRENT S013-9 Y 335 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00%
TB2-19 (-) IW.292 9 R0S16 IW.292 23 R1S07 - - S013-10 - - 418 - - - - - - to - - to - - - - - - - 4.762 5.714 - -
TB2-20 (+) IW.294 10 R0S16 IW.294 4 R1S07 R04 RECTIFIER UNIT 1 DC VOLTAGE S013-11 Y 336 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00%
TB2-20 (-) IW.294 11 R0S16 IW.294 24 R1S07 - - S013-12 - - 419 - - - - - - to - - to - - - - - - - 9.500 9.800 - -
TB2-21 (+) IW.296 15 R0S16 IW.296 5 R1S07 - SPARE S013-13 Y - - - - - - - - to - - to - - - - - - - - - - -
TB2-21 (-) IW.296 16 R0S16 IW.296 25 R1S07 - - S013-14 - - - - - - - - - to - - to - - - - - - - - - - -
TB2-22 (+) IW.298 17 R0S16 IW.298 6 R1S07 R04 RECTIFIER FEEDER H10 CURRENT S008-29 Y1 349 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00%
TB2-22 (-) IW.298 18 R0S16 IW.298 26 R1S07 - - S008-30 - - 432 - - - - - - to - - to - - - - - - - 6.667 7.917 - -
TB2-23 (+) IW.300 19 R0S16 IW.300 7 R1S07 R04 RECTIFIER UNIT 2 DC CURRENT S013-15 Y 337 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00%
TB2-23 (-) IW.300 20 R0S16 IW.300 27 R1S07 - - S013-16 - - 420 - - - - - - to - - to - - - - - - - 4.762 5.714 - -
TB2-24 (+) IW.302 21 R0S16 IW.302 8 R1S07 R04 RECTIFIER UNIT 2 DC VOLTAGE S013-17 Y 338 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00%
TB2-24 (-) IW.302 22 R0S16 IW.302 28 R1S07 - - S013-18 - - 421 - - - - - - to - - to - - - - - - - 9.500 9.800 - -
TB2-25 (+) IW.304 26 R0S16 IW.304 9 R1S07 - SPARE S013-19 Y - - - - - - - - to - - to - - - - - - - - - - -
TB2-25 (-) IW.304 27 R0S16 IW.304 29 R1S07 - - S013-20 - - - - - - - - - to - - to - - - - - - - - - - -
TB2-26 (+) IW.306 28 R0S16 IW.306 10 R1S07 R04 DC BUSBAR DC VOLTAGE S013-21 Y 344 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00%
TB2-26 (-) IW.306 29 R0S16 IW.306 30 R1S07 - - S013-22 - - 427 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 435.750 556.500
TB2-27 (+) IW.308 30 R0S16 IW.308 11 R1S07 R04 NEGATIVE DC BUSBAR DC RETURN CURRENT S013-23 Y 339 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00%
TB2-27 (-) IW.308 31 R0S16 IW.308 31 R1S07 - - S013-24 - - 422 - - - - - - to - - to - - - - - - - 6.667 7.619 - -
TB2-28 (+) IW.310 32 R0S16 IW.310 12 R1S07 R04 STANDBY 11KV H11 CURRENT S008-31 Y1 350 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-28 (-) IW.310 33 R0S16 IW.310 32 R1S07 - - S008-32 - - 433 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-29 (+) IW.312 37 R0S16 IW.312 13 R1S07 - SPARE S013-27 Y - - - - - - - - to - - to - - - - - - - - - - -
TB2-29 (-) IW.312 38 R0S16 IW.312 33 R1S07 - - S013-28 - - - - - - - - - to - - to - - - - - - - - - - -
TB2-30 (+) IW.314 39 R0S16 IW.314 14 R1S07 R04 RING MAIN H13 CURRENT S013-29 Y 351 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-30 (-) IW.314 40 R0S16 IW.314 34 R1S07 - - S013-30 - - 434 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-31 (+) IW.316 41 R0S16 IW.316 15 R1S07 - SPARE S013-31 Y - - - - - - - - to - - to - - - - - - - - - - -
TB2-31 (-) IW.316 42 R0S16 IW.316 35 R1S07 - - S013-32 - - - - - - - - - to - - to - - - - - - - - - - -
TB2-32 (+) IW.318 43 R0S16 IW.318 16 R1S07 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - -
TB2-32 (-) IW.318 44 R0S16 IW.318 36 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - -
- - - - - - - - - - - - -
- - - - IW.320 1 R1S08 - SPARE - - - - AI - - - - - -20 to +20
- - - - IW.320 21 R1S08 - - - - - - - - - - - - to -
- - - - IW.322 2 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.322 22 R1S08 - - - - - - - - - - - - to -
- - - - IW.324 3 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.324 23 R1S08 - - - - - - - - - - - - to -
- - - - IW.326 4 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.326 24 R1S08 - - - - - - - - - - - - to -
- - - - IW.328 5 R1S08 - SPARE - - - - AI - - - - - -20 to +20
- - - - IW.328 25 R1S08 - - - - - - - - - - - - to -
- - - - IW.330 6 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.330 26 R1S08 - - - - - - - - - - - - to -
- - - - IW.332 7 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.332 27 R1S08 - - - - - - - - - - - - to -
- - - - IW.334 8 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.334 28 R1S08 - - - - - - - - - - - - to -
- - - - IW.336 9 R1S08 - SPARE - - - - AI - - - - - -20 to +20
- - - - IW.336 29 R1S08 - - - - - - - - - - - - to -
- - - - IW.338 10 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.338 30 R1S08 - - - - - - - - - - - - to -
- - - - IW.340 11 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.340 31 R1S08 - - - - - - - - - - - - to -
- - - - IW.342 12 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.342 32 R1S08 - - - - - - - - - - - - to -
- - - - IW.344 13 R1S08 - SPARE - - - - AI - - - - - -20 to +20
- - - - IW.344 33 R1S08 - - - - - - - - - - - - to -
- - - - IW.346 14 R1S08 - SPARE - - - - AI - - - - - 0 to +10
- - - - IW.346 34 R1S08 - - - - - - - - - - - - to -
- - - - IW.348 15 R1S08 - SPARE - - - - AI - - - - - 0 to +20
- - - - IW.348 35 R1S08 - - - - - - - - - - - - to - - to - - - - - - - - - - -
- - - - IW.350 16 R1S08 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - -
- - - - IW.350 36 R1S08 - - - - - - - - - - - - to - - to - - - - - - - - - - -
S110-RD - - - - - - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - - - - - - - - - - - - - - - - - - - - - - - - - -
S110-RD - - - - - +110V - S008-68 Y1 405 - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 45 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

S110-BK - - - - - +110V RTN - S008-69 Y1 - 488 - - - - - - - - - - - - - - - - - -


S112-BL - - - - - +12V RTN - S008-70 Y1 - 488 - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 46 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
(Internal Wiring at Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - - - - LOCAL/REMOTE - S007-1 Y1 - - - - - - - - - - - - - - - - - - - -


ZS1 ZS1 1 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S13 Q4.0 2 R1S02 R04 MAIN INCOMER H04 VCB OPEN S007-2 Y1 34 - CO - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S13 Q4.1 3 R1S02 R04 MAIN INCOMER H04 VCB CLOSE S007-3 Y1 33 - CO - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S13 Q4.2 6 R1S02 R04 RING MAIN H01 VCB OPEN S007-4 Y1 7 - CO - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S13 Q4.3 7 R1S02 R04 RING MAIN H01 VCB CLOSE S007-5 Y1 6 - CO - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S13 Q4.4 12 R1S02 R04 RING MAIN H03 VCB OPEN S007-6 Y1 22 - CO - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S13 Q4.5 13 R1S02 R04 RING MAIN H03 VCB CLOSE S007-7 Y1 21 - CO - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S13 Q4.6 16 R1S02 R04 RING MAIN H06 VCB OPEN S007-8 Y1 39 - CO - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S13 Q4.7 17 R1S02 R04 RING MAIN H06 VCB CLOSE S007-9 Y1 38 - CO - - - - - - - - - - - - - - - - -
L+ 1 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-09 Q5.0 15 R0S13 Q5.0 22 R1S02 R04 INTERCONNECT H07 VCB OPEN S007-10 Y1 71 - CO - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S13 Q5.1 23 R1S02 R04 INTERCONNECT H07 VCB CLOSE S007-11 Y1 70 - CO - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S13 Q5.2 26 R1S02 R04 RING MAIN H08 VCB OPEN S007-12 Y1 173 - CO - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S13 Q5.3 27 R1S02 R04 RING MAIN H08 VCB CLOSE S007-13 Y1 172 - CO - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S13 Q5.4 32 R1S02 R04 RING MAIN H09 VCB OPEN S007-14 Y1 182 - CO - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S13 Q5.5 33 R1S02 R04 RING MAIN H09 VCB CLOSE S007-15 Y1 181 - CO - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S13 Q5.6 36 R1S02 R04 BUS SECTION H05 VCB OPEN S007-16 Y1 50 - CO - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S13 Q5.7 37 R1S02 R04 BUS SECTION H05 VCB CLOSE S007-17 Y1 51 - CO - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-17 Q6.0 26 R0S13 Q6.0 2 R1S03 R04 RECTIFIER FEEDER H02 VCB OPEN S007-18 Y1 14 - CO - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S13 Q6.1 3 R1S03 R04 RECTIFIER FEEDER H02 VCB CLOSE S007-19 Y1 13 - CO - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S13 Q6.2 6 R1S03 R04 RECTIFIER FEEDER D1 DCCB OPEN S012-2 Y 396 - CO - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S13 Q6.3 7 R1S03 R04 RECTIFIER FEEDER D1 DCCB CLOSE S012-3 Y 395 - CO - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S13 Q6.4 12 R1S03 R04 RECTIFIER FEEDER H10 VCB OPEN S007-20 Y1 190 - CO - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S13 Q6.5 13 R1S03 R04 RECTIFIER FEEDER H10 VCB CLOSE S007-21 Y1 191 - CO - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S13 Q6.6 16 R1S03 R04 RECTIFIER FEEDER D2 DCCB OPEN S012-4 Y 398 - CO - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S13 Q6.7 17 R1S03 R04 RECTIFIER FEEDER D2 DCCB CLOSE S012-5 Y 397 - CO - - - - - - - - - - - - - - - - -
L+ 19 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-25 Q7.0 37 R0S13 Q7.0 22 R1S03 R04 TRACK FEEDER D13 DCCB OPEN S012-6 Y 15 - CO - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S13 Q7.1 23 R1S03 R04 TRACK FEEDER D13 DCCB CLOSE S012-7 Y 16 - CO - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S13 Q7.2 26 R1S03 R04 TRACK FEEDER D14 DCCB OPEN S012-8 Y 24 - CO - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S13 Q7.3 27 R1S03 R04 TRACK FEEDER D14 DCCB CLOSE S012-9 Y 25 - CO - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S13 Q7.4 32 R1S03 R04 TRACK FEEDER D15 DCCB OPEN S012-10 Y 33 - CO - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S13 Q7.5 33 R1S03 R04 TRACK FEEDER D15 DCCB CLOSE S012-11 Y 34 - CO - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S13 Q7.6 36 R1S03 R04 TRACK FEEDER D16 DCCB OPEN S012-12 Y 42 - CO - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S13 Q7.7 37 R1S03 R04 TRACK FEEDER D16 DCCB CLOSE S012-13 Y 43 - CO - - - - - - - - - - - - - - - - -
L+ 39 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S13 FR0 - R1S03 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S13 FR1 - R1S03 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S13 UE0 31 R1S03 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S13 UE1 35 R1S03 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
RL-33 Q8.0 4 R0S14 Q8.0 2 R1S04 R04 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S012-14 Y 56 - CO - - - - - - - - - - - - - - - - -
RL-34 Q8.1 5 R0S14 Q8.1 3 R1S04 - SPARE S012-15 Y - - - - - - - - - - - - - - - - - - - -
RL-35 Q8.2 6 R0S14 Q8.2 6 R1S04 - SPARE S012-16 Y - - - - - - - - - - - - - - - - - - -
RL-36 Q8.3 7 R0S14 Q8.3 7 R1S04 - SPARE S012-17 Y - - - - - - - - - - - - - - - - - - -
RL-37 Q8.4 8 R0S14 Q8.4 12 R1S04 - SPARE S012-18 Y - - - - - - - - - - - - - - - - - - -
RL-38 Q8.5 9 R0S14 Q8.5 13 R1S04 - SPARE S012-19 Y - - - - - - - - - - - - - - - - - - -
RL-39 Q8.6 10 R0S14 Q8.6 16 R1S04 - SPARE S012-20 Y - - - - - - - - - - - - - - - - - - -
RL-40 Q8.7 11 R0S14 Q8.7 17 R1S04 - SPARE S012-21 Y - - - - - - - - - - - - - - - - - - -
L+ 19 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-41 Q9.0 15 R0S14 Q9.0 22 R1S04 R04 BUS SECTION H05 LHS UNDER VOLTAGE RESET S012-22 Y1 52 - CO - - - - - - - - - - - - - - - - -
RL-42 Q9.1 16 R0S14 Q9.1 23 R1S04 - SPARE S012-23 Y1 - - - - - - - - - - - - - - - - - - -
RL-43 Q9.2 17 R0S14 Q9.2 26 R1S04 R04 BUS SECTION H05 RHS UNDER VOLTAGE RESET S012-24 Y1 53 - CO - - - - - - - - - - - - - - - - -
RL-44 Q9.3 18 R0S14 Q9.3 27 R1S04 - SPARE S012-25 Y1 - - - - - - - - - - - - - - - - - - -
RL-45 Q9.4 19 R0S14 Q9.4 32 R1S04 R04 AUTO CHANGEOVER PANEL CONTROL (ACO CONTROL OFF) S012-26 Y1 220 - CO - - - - - - - - - - - - - - - - -
RL-46 Q9.5 20 R0S14 Q9.5 33 R1S04 R04 AUTO CHANGEOVER PANEL ENABLE (ACO CONTROL ON) S007-27 Y1 219 - CO - - - - - - - - - - - - - - - - -
RL-47 Q9.6 21 R0S14 Q9.6 36 R1S04 - SPARE S007-28 Y1 - - - - - - - - - - - - - - - - - - - -
RL-48 Q9.7 22 R0S14 Q9.7 37 R1S04 - SPARE S007-29 Y1 - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-49 Q10.0 26 R0S14 Q10.0 2 R1S05 R04 STANDBY 11KV H11 VCB OPEN S007-30 Y1 202 - CO - - - - - - - - - - - - - - - - -
RL-50 Q10.1 27 R0S14 Q10.1 3 R1S05 R04 STANDBY 11KV H11 VCB CLOSE S007-31 Y1 201 - CO - - - - - - - - - - - - - - - - -
RL-51 Q10.2 28 R0S14 Q10.2 6 R1S05 R04 RING MAIN H13 VCB OPEN S007-32 Y1 364 - CO - - - - - - - - - - - - - - - - -
RL-52 Q10.3 29 R0S14 Q10.3 7 R1S05 R04 RING MAIN H13 VCB CLOSE S007-33 Y1 365 - CO - - - - - - - - - - - - - - - - -
RL-53 Q10.4 30 R0S14 Q10.4 12 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-54 Q10.5 31 R0S14 Q10.5 13 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-55 Q10.6 32 R0S14 Q10.6 16 R1S05 R04 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - -
RL-56 Q10.7 33 R0S14 Q10.7 17 R1S05 R04 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - -
L+ 19 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-57 Q11.0 37 R0S14 Q11.0 22 R1S05 R04 AUTO CHANGEOVER PANEL ACO RESET INHIBIT CONTROL S007-38 Y1 213 - CO - - - - - - - - - - - - - - - - -
RL-58 Q11.1 38 R0S14 Q11.1 23 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-59 Q11.2 39 R0S14 Q11.2 26 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-60 Q11.3 40 R0S14 Q11.3 27 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-61 Q11.4 41 R0S14 Q11.4 32 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-62 Q11.5 42 R0S14 Q11.5 33 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-63 Q11.6 43 R0S14 Q11.6 36 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
RL-64 Q11.7 44 R0S14 Q11.7 37 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S14 FR0 - R1S05 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S14 FR1 - R1S05 - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S14 UE0 31 R1S05 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S14 UE1 35 R1S05 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 47 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 48 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - NC NC - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - - - - -
- - - - - -
- - NC C - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 49 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - - - - -
- - - - - -
- - NC C - -

Unrestricted 749775924.xlsx/RS04 [RS04] 50 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 51 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
0.75 0.85 - -
7.115 5.477
5.00% 5.00% C NC NC C
1425 1710 - - 7.125 8.550
5.00% 5.00% C NC NC C
11.495 11.78 0.840 8.316 9.196 9.424
5.00% 5.00% C NC NC C
- - - - - -
10.00% 5.00% C NC NC C
2520 2850 -8.143 -6.786 7.200 8.143
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
10.00% 5.00% C NC NC C
2520 2850 -8.143 -6.786 7.200 8.143
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
10.00% 5.00% C NC NC C
2520 2850 -8.143 -6.786 7.200 8.143
5.00% 5.00% C NC NC C
1425 1710 - - 7.125 8.550
5.00% 5.00% C NC NC C
11.495 11.78 0.840 8.316 9.196 9.424
0.05 0.05 C NC NC C
11.495 11.78 0.840 8.316 9.196 9.424
- - - - - -
- - - - - -
10.00% 5.00% C NC NC C
2520 2850 -8.143 -6.786 7.200 8.143
5.00% 5.00% C NC NC C
76 90.25 - - 6.333 7.521
5.00% 5.00% C NC NC C
2375 2850 - - 4.524 5.429
5.00% 5.00% C NC NC C
902.500 931.000 - - 9.025 9.310
- - - - - -
- - - - - -
5.00% 5.00% C NC NC C
76 90.25 - - 6.333 7.521
5.00% 5.00% C NC NC C
2375 2850 - - 4.524 5.429
5.00% 5.00% C NC NC C
902.5 931 - - 9.025 9.310
- - - - - -
- - - - - -
5.00% 5.00% C NC NC C
902.5 931 4.358 5.565 9.025 9.310
5.00% 5.00% C NC NC C
3325 3800 - - 6.333 7.238
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
- - - - - -
- - - - - -
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
- - - - - -
- - - - - -
- - - - - -
- - - - - -

C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 52 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 53 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS04 [RS04] 54 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R05 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R05 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 366 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R05 RING MAIN H03 SOLKOR TRIP S005-6 - 367 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 - SPARE S005-7 - - - - - - - - - - - - - - - - - - - - - - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R05 RING MAIN H03 OVERLOAD ALARM S005-8 - 368 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 R05 ROLLING SHUTTER S005-9 - 395 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R05 RING MAIN H04 CONTROL SELECTOR SWITCH S005-12 - 20 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R05 RING MAIN H04 O/C EARTH FAULT TRIP S005-13 - 365 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R05 RING MAIN H04 SOLKOR TRIP S005-14 - 354 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R05 RING MAIN H04 PILOT WIRE ALARM S005-15 - 356 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R05 RING MAIN H04 OVERLOAD ALARM S005-16 - 355 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 - SPARE S005-17 - - - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 - SPARE S005-18 - - - - - - - - - - - - - - - - - - - - - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 - SPARE S005-19 - - - - - - - - - - - - - - - - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R05 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-22 - 6 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R05 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-23 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R05 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-24 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R05 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-25 - 210 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R05 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-26 - 211 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R05 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-27 - 212 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R05 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-28 - 213 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R05 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-29 - 214 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R05 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-30 - 215 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R05 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-31 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R05 RECTIFIER 1 FRAME EARTH TRIP S005-32 - 217 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R05 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-33 - 218 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R05 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-34 - 219 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R05 RECTIFIER 1 DIODE OVER TEMP ALARM S005-35 - 220 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R05 RECTIFIER 1 DIODE OVER TEMP TRIP S005-36 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R05 RECTIFIER 1 REVERSE CURRENT TRIP S005-37 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R05 RECTIFIER 1 SURGE ARRESTOR TRIP S005-38 - 223 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R05 RECTIFIER 1 FILTER CIRCUIT ALARM S005-39 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R05 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-40 - 225 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 - SPARE S005-41 - - - - - - - - - - - - - - - - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R05 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S005-44 - 58 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 - SPARE S005-45 - - - - - - - - - - - - - - - - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R05 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S005-48 - 10 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R05 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-2 - 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R05 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-3 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R05 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-4 - 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R05 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-5 - 229 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R05 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-6 - 230 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R05 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-7 - 231 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R05 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-8 - 232 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R05 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-9 - 233 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R05 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-10 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R05 RECTIFIER 2 FRAME EARTH TRIP S006-11 - 235 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R05 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-12 - 236 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R05 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-13 - 237 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R05 RECTIFIER 2 DIODE OVER TEMP ALARM S006-14 - 238 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R05 RECTIFIER 2 DIODE OVER TEMP TRIP S006-15 - 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R05 RECTIFIER 2 REVERSE CURRENT TRIP S006-16 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R05 RECTIFIER 2 SURGE ARRESTOR TRIP S006-17 - 241 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R05 RECTIFIER 2 FILTER CIRCUIT ALARM S006-18 - 242 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R05 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-19 - 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 - SPARE S006-20 - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R05 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-23 - 64 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 - SPARE S006-24 - - - - - - - - - - - - - - - - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R05 AUXILIARY TRANSFORMER 11KV SWITCH H5 S006-25 - 2 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 - SPARE S006-26 - 1 - - - - - - - - - - - - - - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R05 AUXILIARY TRANSFORMER 11KV SW H5 FUSE BLOWN TRIP S006-27 - 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R05 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-28 - 245 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 - SPARE S006-29 - 263 - - - - - - - - - - - - - - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R05 750V DCCB TRIP CCT SUPERVISION ALARM S006-30 - 371 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R05 TRACK FEEDER D13 CONTROL SELECTOR SWITCH S006-33 - 28 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R05 TRACK FEEDER D13 INSTANT OVERCURRENT S006-34 - 360 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R05 TRACK FEEDER D13 RATE OF RISE TRIP S006-35 - 361 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R05 TRACK FEEDER D13 LINE TESTING S006-36 - 29 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R05 TRACK FEEDER D13 LINE IMPEDANCE LOW S006-37 - 362 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S006-38 - - - - - - - - - - - - - - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R05 TRACK FEEDER D14 CONTROL SELECTOR SWITCH S006-41 - 36 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R05 TRACK FEEDER D14 INSTANT OVERCURRENT S006-42 - 249 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R05 TRACK FEEDER D14 RATE OF RISE TRIP S006-43 - 250 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R05 TRACK FEEDER D14 LINE TESTING S006-44 - 38 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R05 TRACK FEEDER D14 LINE IMPEDANCE LOW S006-45 - 251 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R05 TRACK FEEDER D15 CONTROL SELECTOR SWITCH S007-2 - 44 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R05 TRACK FEEDER D15 INSTANT OVERCURRENT S007-3 - 357 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R05 TRACK FEEDER D15 RATE OF RISE TRIP S007-4 - 358 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R05 TRACK FEEDER D15 LINE TESTING S007-5 - 45 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R05 TRACK FEEDER D15 LINE IMPEDANCE LOW S007-6 - 359 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 55 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - - -


DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R05 TRACK FEEDER D16 CONTROL SELECTOR SWITCH S007-10 - 52 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R05 TRACK FEEDER D16 INSTANT OVERCURRENT S007-11 - 246 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R05 TRACK FEEDER D16 RATE OF RISE TRIP S007-12 - 247 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R05 TRACK FEEDER D16 LINE TESTING S007-13 - 53 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R05 TRACK FEEDER D16 LINE IMPEDANCE LOW S007-14 - 248 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 56 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -


UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R05 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-18 - 364 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R05 AC/DC SYSTEM MAINS FAILED ALARM S007-19 - 198 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R05 AC/DC SYSTEM 380V FEEDER MCB S007-20 - 199 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - - - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R05 AC/DC SYSTEM AC EARTH FAULT TRIP S007-21 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R05 AC/DC SYSTEM BATTERY CHARGER S007-22 - 201 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R05 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-23 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R05 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-24 - 203 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R05 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-25 - 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R05 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-26 - 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R05 AC/DC SYSTEM 110V DC COMMON FEEDER S007-27 - 206 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R05 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-28 - 207 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R05 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-29 - 391 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R05 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-30 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R05 COMMON EQUIPMENT INTRUDER ALARM S007-31 - 393 476 SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R05 COMMON EQUIPMENT W371 INTRUDER ALARM S007-32 - ? - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 R05 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R05 RING MAIN H03 VCB OPENED S005-2 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R05 RING MAIN H03 VCB CLOSED S005-3 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R05 RING MAIN H04 VCB OPENED S005-10 - 17 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R05 RING MAIN H04 VCB CLOSED S005-11 - 18 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R05 RECTIFIER FEEDER H01 VCB OPENED S005-20 - 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R05 RECTIFIER FEEDER H01 VCB CLOSED S005-21 - 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R05 RECTIFIER FEEDER D1 DCCB OPENED S005-42 - 59 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R05 RECTIFIER FEEDER D1 DCCB CLOSED S005-43 - 60 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R05 RECTIFIER FEEDER H02 VCB OPENED S005-46 - 7 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R05 RECTIFIER FEEDER H02 VCB CLOSED S005-47 - 8 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R05 RECTIFIER FEEDER D2 DCCB OPENED S006-21 - 65 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R05 RECTIFIER FEEDER D2 DCCB CLOSED S006-22 - 66 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R05 TRACK FEEDER D13 DCCB OPENED S006-31 - 23 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R05 TRACK FEEDER D13 DCCB CLOSED S006-32 - 24 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R05 TRACK FEEDER D14 DCCB OPENED S006-39 - 31 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R05 TRACK FEEDER D14 DCCB CLOSED S006-40 - 32 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R05 TRACK FEEDER D15 DCCB OPENED S006-47 - 39 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R05 TRACK FEEDER D15 DCCB CLOSED S006-48 - 40 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R05 TRACK FEEDER D16 DCCB OPENED S007-8 - 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R05 TRACK FEEDER D16 DCCB CLOSED S007-9 - 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R05 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S007-16 - 56 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R05 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S007-17 - 55 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R05 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R05 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - I20.0 1 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I20.1 2 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I20.2 3 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I20.3 4 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I20.4 5 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I20.5 6 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I20.6 7 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I20.7 8 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- - - - - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
- - - - I21.0 11 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I21.1 12 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I21.2 13 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I21.3 14 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I21.4 15 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I21.5 16 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I21.6 17 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I21.7 18 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- - - - 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
- - - - I22.0 21 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I22.1 22 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I22.2 23 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I22.3 24 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I22.4 25 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I22.5 26 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I22.6 27 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I22.7 28 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - - 39 R0S06 +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- - - - - 40 R0S06 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
- - - - I23.0 31 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I23.1 32 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I23.2 33 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I23.3 34 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I23.4 35 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I23.5 36 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I23.6 37 R0S06 - SPARE internal wiring - - - - - - - - - - - - 0 - - - - - - - - -
- - - - I23.7 38 R0S06 - SPARE internal wiring - - - - - - - - - - - - 0 - - - - - - - - -
- - - - 2L+ 39 R0S06 +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - 2M 40 R0S06 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 57 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S12 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S12 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S12 IW.256 1 R1S04 R05 TRACK FEEDER D13 DC CURRENT S009-1 - 344 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-1 (-) IW.256 5 R0S12 IW.256 21 R1S04 - - S009-2 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850
TB2-2 (+) IW.258 6 R0S12 IW.258 2 R1S04 R05 RECTIFIER FEEDER H01 CURRENT S009-3 - 335 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-2 (-) IW.258 7 R0S12 IW.258 22 R1S04 - - S009-4 - - 418 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-3 (+) IW.260 8 R0S12 IW.260 3 R1S04 R05 RECTIFIER UNIT 1 DC CURRENT S009-5 - 339 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-3 (-) IW.260 9 R0S12 IW.260 23 R1S04 - - S009-6 - - 422 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-4 (+) IW.262 10 R0S12 IW.262 4 R1S04 R05 RECTIFIER UNIT 1 DC VOLTAGE S009-7 - 340 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-4 (-) IW.262 11 R0S12 IW.262 24 R1S04 - - S009-8 - - 423 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.500 931.000
TB2-5 (+) IW.264 15 R0S12 IW.264 5 R1S04 R05 TRACK FEEDER D14 DC CURRENT S009-9 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-5 (-) IW.264 16 R0S12 IW.264 25 R1S04 - - S009-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850
TB2-6 (+) IW.266 17 R0S12 IW.266 6 R1S04 R05 RECTIFIER FEEDER H02 CURRENT S009-11 - 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-6 (-) IW.266 18 R0S12 IW.266 26 R1S04 - - S009-12 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-7 (+) IW.268 19 R0S12 IW.268 7 R1S04 R05 RECTIFIER UNIT 2 DC CURRENT S009-13 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-7 (-) IW.268 20 R0S12 IW.268 27 R1S04 - - S009-14 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-8 (+) IW.270 21 R0S12 IW.270 8 R1S04 R05 RECTIFIER UNIT 2 DC VOLTAGE S009-15 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-8 (-) IW.270 22 R0S12 IW.270 28 R1S04 - - S009-16 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931
TB2-9 (+) IW.272 26 R0S12 IW.272 9 R1S04 R05 TRACK FEEDER D15 DC CURRENT S009-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-9 (-) IW.272 27 R0S12 IW.272 29 R1S04 - - S009-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850
TB2-10 (+) IW.274 28 R0S12 IW.274 10 R1S04 R05 RING MAIN H03 CURRENT S009-19 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-10 (-) IW.274 29 R0S12 IW.274 30 R1S04 - - S009-20 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-11 (+) IW.276 30 R0S12 IW.276 11 R1S04 R05 RING MAIN H04 CURRENT S009-21 - 338 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-11 (-) IW.276 31 R0S12 IW.276 31 R1S04 - - S009-22 - - 421 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-12 (+) IW.278 32 R0S12 IW.278 12 R1S04 R05 AC BUSBAR VOLTAGE S009-23 - 349 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00%
TB2-12 (-) IW.278 33 R0S12 IW.278 32 R1S04 - - S009-24 - - 432 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 1.050 10.395 11.495 11.78
TB2-13 (+) IW.280 37 R0S12 IW.280 13 R1S04 R05 TRACK FEEDER D16 DC CURRENT S009-25 - 347 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2800 3000 5.00% 5.00% 10.00% 5.00%
TB2-13 (-) IW.280 38 R0S12 IW.280 33 R1S04 - - S009-26 - - 430 - - - - - - to - - to - - - - - -8.571 7.143 8.000 8.571 -2850 2625 2520 2850
TB2-14 (+) IW.282 39 R0S12 IW.282 14 R1S04 R05 DC BUSBAR DC VOLTAGE S009-27 - 348 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00%
TB2-14 (-) IW.282 40 R0S12 IW.282 34 R1S04 - - S009-28 - - 431 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 435.750 556.500 902.5 931
TB2-15 (+) IW.284 41 R0S12 IW.284 15 R1S04 R05 NEGATIVE DC BUSBAR DC RETURN CURRENT S009-29 - 343 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00%
TB2-15 (-) IW.284 42 R0S12 IW.284 35 R1S04 - - S009-30 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800
TB2-16 (+) IW.286 43 R0S12 IW.286 16 R1S04 - SPARE S009-31 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S12 IW.286 36 R1S04 - - S009-32 - - - - - - - - - to - - to - - - - - - - - - - - - -
S110-RD - - R0S12 - - - - - S009-70 - 405 - - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S12 - - - - - S009-71 - - 488 - - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S12 - - - - - S009-72 - - 488 - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 58 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - R0S12 - - - - - S008-1 - - - - - - - - - - - - - - - - - - - - - - -


IW.288 1 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.288 21 R1S05 - - - - - - - - - - - - to -
IW.290 2 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.290 22 R1S05 - - - - - - - - - - - - to -
IW.292 3 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.292 23 R1S05 - - - - - - - - - - - - to -
IW.294 4 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.294 24 R1S05 - - - - - - - - - - - - to -
IW.296 5 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.296 25 R1S05 - - - - - - - - - - - - to -
IW.298 6 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.298 26 R1S05 - - - - - - - - - - - - to -
IW.300 7 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.300 27 R1S05 - - - - - - - - - - - - to -
IW.302 8 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.302 28 R1S05 - - - - - - - - - - - - to -
IW.304 9 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.304 29 R1S05 - - - - - - - - - - - - to -
IW.306 10 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.306 30 R1S05 - - - - - - - - - - - - to -
IW.308 11 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.308 31 R1S05 - - - - - - - - - - - - to -
IW.310 12 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.310 32 R1S05 - - - - - - - - - - - - to -
IW.312 13 R1S05 - SPARE - - - - AI - - - - - -20 to +20
IW.312 33 R1S05 - - - - - - - - - - - - to -
IW.314 14 R1S05 - SPARE - - - - AI - - - - - 0 to +10
IW.314 34 R1S05 - - - - - - - - - - - - to -
IW.316 15 R1S05 - SPARE - - - - AI - - - - - 0 to +20
IW.316 35 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - -
IW.318 16 R1S05 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - -
IW.318 36 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - -
ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S11 Q4.0 2 R1S02 R05 RING MAIN H03 VCB OPEN S008-2 - 16 - CO - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S11 Q4.1 3 R1S02 R05 RING MAIN H03 VCB CLOSE S008-3 - 15 - CO - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S11 Q4.2 6 R1S02 R05 RING MAIN H04 VCB OPEN S008-4 - 22 - CO - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S11 Q4.3 7 R1S02 R05 RING MAIN H04 VCB CLOSE S008-5 - 21 - CO - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S11 Q4.4 12 R1S02 R05 RECTIFIER FEEDER H01 VCB OPEN S008-6 - 80 - CO - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S11 Q4.5 13 R1S02 R05 RECTIFIER FEEDER H01 VCB CLOSE S008-7 - 81 - CO - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S11 Q4.6 16 R1S02 R05 RECTIFIER FEEDER D1 DCCB OPEN S008-8 - 73 - CO - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S11 Q4.7 17 R1S02 R05 RECTIFIER FEEDER D1 DCCB CLOSE S008-9 - 74 - CO - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-09 Q5.0 15 R0S11 Q5.0 22 R1S02 R05 RECTIFIER FEEDER H02 VCB OPEN S008-10 - 82 - CO - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S11 Q5.1 23 R1S02 R05 RECTIFIER FEEDER H02 VCB CLOSE S008-11 - 83 - CO - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S11 Q5.2 26 R1S02 R05 RECTIFIER FEEDER D2 DCCB OPEN S008-12 - 75 - CO - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S11 Q5.3 27 R1S02 R05 RECTIFIER FEEDER D2 DCCB CLOSE S008-13 - 76 - CO - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S11 Q5.4 32 R1S02 R05 TRACK FEEDER D13 DCCB OPEN S008-14 - 25 - CO - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S11 Q5.5 33 R1S02 R05 TRACK FEEDER D13 DCCB CLOSE S008-15 - 26 - CO - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S11 Q5.6 36 R1S02 R05 TRACK FEEDER D14 DCCB OPEN S008-16 - 33 - CO - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S11 Q5.7 37 R1S02 R05 TRACK FEEDER D14 DCCB CLOSE S008-17 - 34 - CO - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-17 Q6.0 26 R0S11 Q6.0 2 R1S03 R05 TRACK FEEDER D15 DCCB OPEN S008-18 - 41 - CO - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S11 Q6.1 3 R1S03 R05 TRACK FEEDER D15 DCCB CLOSE S008-19 - 42 - CO - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S11 Q6.2 6 R1S03 R05 TRACK FEEDER D16 DCCB OPEN S008-20 - 49 - CO - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S11 Q6.3 7 R1S03 R05 TRACK FEEDER D16 DCCB CLOSE S008-21 - 50 - CO - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S11 Q6.4 12 R1S03 R05 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S008-22 - 61 - CO - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S11 Q6.5 13 R1S03 S008-23 - - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S11 Q6.6 16 R1S03 R05 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S11 Q6.7 17 R1S03 R05 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-25 Q7.0 37 R0S11 Q7.0 22 R1S03 - SPARE S008-26 - - - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S11 Q7.1 23 R1S03 - SPARE S008-27 - - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S11 Q7.2 26 R1S03 - SPARE S008-28 - - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S11 Q7.3 27 R1S03 - SPARE S008-29 - - - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S11 Q7.4 32 R1S03 - SPARE S008-30 - - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S11 Q7.5 33 R1S03 - SPARE S008-31 - - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S11 Q7.6 36 R1S03 - SPARE S008-32 - - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S11 Q7.7 37 R1S03 - SPARE S008-33 - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S11 FR0 - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S11 FR1 - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S11 UE0 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S11 UE1 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 59 Printed on: 04/30/2024


Alarm Priority

Alm 0 Alm 1 Alm 2 Alm 3


or LL or L or H or HH

- - - -
- - - -
NC NC - -
NC C - -
NC C - -
- - - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
- - - -
NC NC - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
- - - -
NC NC - -
- - - -
NC C - -
NC C - -
- - - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
- - - -
- - - -
NC C - -

Unrestricted 749775924.xlsx/RS05 [RS05] 60 Printed on: 04/30/2024


Alarm Priority

Alm 0 Alm 1 Alm 2 Alm 3


or LL or L or H or HH

- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 61 Printed on: 04/30/2024


Alarm Priority

Alm 0 Alm 1 Alm 2 Alm 3


or LL or L or H or HH

- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 62 Printed on: 04/30/2024


Alarm Priority

Alm 0 Alm 1 Alm 2 Alm 3


or LL or L or H or HH

- - - -
- - - -
C NC NC C
-8.143 -6.786 7.200 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 7.200 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 7.200 8.143
C NC NC C
- - 7.125 9.025
C NC NC C
- - 7.125 9.025
C NC NC C
0.840 8.316 9.196 9.424
C NC NC C
-8.143 7.500 7.200 8.143
C NC NC C
4.358 5.565 9.025 9.310
C NC NC C
- - 6.333 7.238
- - - -
- - - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 63 Printed on: 04/30/2024


Alarm Priority

Alm 0 Alm 1 Alm 2 Alm 3


or LL or L or H or HH

- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS05 [RS05] 64 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R06 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R06 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 365 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R06 RING MAIN H03 SOLKOR TRIP S005-6 - 354 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R06 RING MAIN H03 PILOT WIRE ALARM S005-7 - 356 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R06 RING MAIN H03 OVERLOAD ALARM S005-8 - 355 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 R02 ROLLING SHUTTER - S005-9 - 395 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R06 RING MAIN H04 CONTROL SELECTOR SWITCH S005-12 - 20 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R06 RING MAIN H04 O/C EARTH FAULT TRIP S005-13 - 366 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R06 RING MAIN H04 SOLKOR TRIP S005-14 - 367 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R06 RING MAIN H04 PILOT WIRE ALARM S005-15 - 369 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R06 RING MAIN H04 OVERLOAD ALARM S005-16 - 368 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 - SPARE S005-17 - - - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 R06 RING MAIN H05 CONTROL SELECTOR SWITCH S005-20 - 177 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 R06 RING MAIN H05 O/C EARTH FAULT TRIP S005-21 - 371 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R06 RING MAIN H05 SOLKOR TRIP S005-22 - 372 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R06 RING MAIN H05 PILOT WIRE ALARM S005-23 - 374 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R06 RING MAIN H05 OVERLOAD ALARM S005-24 - 373 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R06 110 SECTION BREAKER S15 CONTROL SELECTOR SWITCH S005-25 - 180 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R06 110 SECTION BREAKER S16 CONTROL SELECTOR SWITCH S005-26 - 190 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 - SPARE S005-27 - - - - - - - - - - - - - - - - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R06 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-30 - 6 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R06 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-31 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R06 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-32 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R06 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-33 - 210 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R06 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-34 - 211 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R06 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-35 - 212 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R06 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-36 - 213 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R06 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-37 - 214 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R06 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-38 - 215 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R06 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-39 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R06 RECTIFIER 1 FRAME EARTH TRIP S005-40 - 217 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R06 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-41 - 218 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R06 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-42 - 219 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R06 RECTIFIER 1 DIODE OVER TEMP ALARM S005-43 - 220 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R06 RECTIFIER 1 DIODE OVER TEMP TRIP S005-44 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R06 RECTIFIER 1 REVERSE CURRENT TRIP S005-45 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R06 RECTIFIER 1 SURGE ARRESTOR TRIP S005-46 - 223 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R06 RECTIFIER 1 FILTER CIRCUIT ALARM S005-47 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R06 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-48 - 225 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 - SPARE S006-2 - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R06 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S006-5 - 58 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 - SPARE S006-6 - - - - - - - - - - - - - - - - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R06 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S006-9 - 10 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R06 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-10 - 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R06 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-11 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R06 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-12 - 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R06 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-13 - 229 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R06 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-14 - 230 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R06 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-15 - 231 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R06 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-16 - 232 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R06 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-17 - 233 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R06 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-18 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R06 RECTIFIER 2 FRAME EARTH TRIP S006-19 - 235 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R06 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-20 - 236 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R06 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-21 - 237 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R06 RECTIFIER 2 DIODE OVER TEMP ALARM S006-22 - 238 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R06 RECTIFIER 2 DIODE OVER TEMP TRIP S006-23 - 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R06 RECTIFIER 2 REVERSE CURRENT TRIP S006-24 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R06 RECTIFIER 2 SURGE ARRESTOR TRIP S006-25 - 241 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R06 RECTIFIER 2 FILTER CIRCUIT ALARM S006-26 - 242 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R06 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-27 - 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 LT1 OVPD POWER SUPPLY FAIL s006-28 - 386 - SB OPNL NORMAL OPERATED - - - - - - - - - - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R06 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-31 - 64 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 LT1 OVPD OPERATING s006-32 - 389 - SB OPNL NORMAL OPERATED - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 65 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R06 AUXILIARY TRANSFORMER 11KV SWITCH H6 S006-33 - 2 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 LT1 OVPD (SPARE) POWER SUPPLY FAIL S006-34 - - - SB OPNL NORMAL OPERATED - - - - - - - - - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R06 AUXILIARY TRANSFORMER 11KV SW H6 FUSE BLOWN TRIP S006-35 - 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R06 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-36 - 245 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 LT1 OVPD (SPARE) OPERATING s006-37 - - - SB OPNL NORMAL OPERATED - - - - - - - - - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 R06 750V DCCB TRIP CCT SUPERVISION ALARM S006-38 - 370 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R06 TRACK FEEDER D15 CONTROL SELECTOR SWITCH S006-41 - 66 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R06 TRACK FEEDER D15 INSTANT OVERCURRENT S006-42 - 360 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R06 TRACK FEEDER D15 RATE OF RISE TRIP S006-43 - 361 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R06 TRACK FEEDER D15 LINE TESTING S006-44 - 27 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R06 TRACK FEEDER D15 LINE IMPEDANCE LOW S006-45 - 362 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 SIH LR/WR INTERCHANGE OVPD POWER SUPPLY FAIL s006-46 - 399 - SB OPNL NORMAL OPERATED - - - - - - - - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R06 TRACK FEEDER D16 CONTROL SELECTOR SWITCH S007-2 - 68 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R06 TRACK FEEDER D16 INSTANT OVERCURRENT S007-3 - 249 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R06 TRACK FEEDER D16 RATE OF RISE TRIP S007-4 - 250 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R06 TRACK FEEDER D16 LINE TESTING S007-5 - 33 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R06 TRACK FEEDER D16 LINE IMPEDANCE LOW S007-6 - 251 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 SIH LR/WR INTERCHANGE OVPD OPERATING s007-7 - 402 - SB OPNL NORMAL OPERATED - - - - - - - - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R06 TRACK FEEDER D17 CONTROL SELECTOR SWITCH S007-10 - 70 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R06 TRACK FEEDER D17 INSTANT OVERCURRENT S007-11 - 357 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R06 TRACK FEEDER D17 RATE OF RISE TRIP S007-12 - 358 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R06 TRACK FEEDER D17 LINE TESTING S007-13 - 39 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R06 TRACK FEEDER D17 LINE IMPEDANCE LOW S007-14 - 359 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R06 TRACK FEEDER D18 CONTROL SELECTOR SWITCH S007-18 - 72 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R06 TRACK FEEDER D18 INSTANT OVERCURRENT S007-19 - 246 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R06 TRACK FEEDER D18 RATE OF RISE TRIP S007-20 - 247 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R06 TRACK FEEDER D18 LINE TESTING S007-21 - 46 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R06 TRACK FEEDER D18 LINE IMPEDANCE LOW S007-22 - 248 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R06 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R06 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-26 - 364 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R06 AC/DC SYSTEM MAINS FAILED ALARM S007-27 - 198 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R06 AC/DC SYSTEM 380V FEEDER MCB S007-28 - 199 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R06 AC/DC SYSTEM AC EARTH FAULT TRIP S007-29 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R06 AC/DC SYSTEM BATTERY CHARGER S007-30 - 201 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R06 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-31 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R06 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-32 - 203 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R06 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-33 - 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R06 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-34 - 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 R06 AC/DC SYSTEM 110V DC COMMON FEEDER S007-35 - 206 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R06 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-36 - 207 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R06 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-37 - 391 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R06 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-38 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R06 COMMON EQUIPMENT INTRUDER ALARM S007-39 - 393 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R06 110 SECTION BREAKER S15 OVERCURRENT TRIP S007-40 - 183 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R06 110 SECTION BREAKER S15 LOW VOLTAGE TRIP S007-41 - 184 - SB T/V RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R06 110 SECTION BREAKER S16 OVERCURRENT TRIP S007-42 - 193 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R06 110 SECTION BREAKER S16 LOW VOLTAGE TRIP S007-43 - 194 - SB T/V RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 LT1 OVPD CONTACTOR OPEN s007-48 - 384 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 LT1 OVPD CONTACTOR CLOSE S008-2 - 385 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 LT1 OVPD MAINTENANCE ISOLATOR OPEN S008-5 - 387 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 LT1 OVPD MAINTENANCE ISOLATOR CLOSE S008-6 - 388 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 LT1 OVPD (SPARE) CONTACTOR OPEN S008-7 - - - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 LT1 OVPD (SPARE) CONTACTOR CLOSE S008-8 - - - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 LT1 OVPD (SPARE) MAINTENANCE ISOLATOR OPEN S008-9 - - - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 LT1 OVPD (SPARE) MAINTENANCE ISOLATOR CLOSE S008-10 - - - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 SIH LR/WR INTERCHANGE OVPD CONTACTOR OPEN s008-16 - 397 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 SIH LR/WR INTERCHANGE OVPD CONTACTOR OPEN s008-15 - 398 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 SIH LR/WR INTERCHANGE OVPD MAINTENANCE ISOLATOR OPEN S008-13 - 400 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 SIH LR/WR INTERCHANGE OVPD MAINTENANCE ISOLATOR CLOSE S008-14 - 401 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 SPARE s008-11 - - - DB - - - - - - - - - - - - - - - - - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 SPARE s007-23 - - - DB - - - - - - - - - - - - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 SPARE S008-17 - - - DB - - - - - - - - - - - - - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 SPARE S008-18 - - - DB - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 66 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R0S06 R06 RING MAIN H03 VCB OPENED S005-2 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-260 I20.1 5 R0S11 I20.1 2 R0S06 R06 RING MAIN H03 VCB CLOSED S005-3 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-262 I20.2 6 R0S11 I20.2 3 R0S06 R06 RING MAIN H04 VCB OPENED S005-10 - 17 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-264 I20.3 7 R0S11 I20.3 4 R0S06 R06 RING MAIN H04 VCB CLOSED S005-11 - 18 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-266 I20.4 8 R0S11 I20.4 5 R0S06 R06 RING MAIN H05 VCB OPENED S005-18 - 175 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-268 I20.5 9 R0S11 I20.5 6 R0S06 R06 RING MAIN H05 VCB CLOSED S005-19 - 176 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-270 I20.6 10 R0S11 I20.6 7 R0S06 R06 RECTIFIER FEEDER H01 VCB OPENED S005-28 - 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-272 I20.7 11 R0S11 I20.7 8 R0S06 R06 RECTIFIER FEEDER H01 VCB CLOSED S005-29 - 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM0 UM0 12 R0S11 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R0S06 R06 RECTIFIER FEEDER D1 DCCB OPENED S006-3 - 52 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-276 I21.1 16 R0S11 I21.1 12 R0S06 R06 RECTIFIER FEEDER D1 DCCB CLOSED S006-4 - 53 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-278 I21.2 17 R0S11 I21.2 13 R0S06 R06 RECTIFIER FEEDER H02 VCB OPENED S006-7 - 7 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-280 I21.3 18 R0S11 I21.3 14 R0S06 R06 RECTIFIER FEEDER H02 VCB CLOSED S006-8 - 8 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-282 I21.4 19 R0S11 I21.4 15 R0S06 R06 RECTIFIER FEEDER D2 DCCB OPENED S006-29 - 55 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-284 I21.5 20 R0S11 I21.5 16 R0S06 R06 RECTIFIER FEEDER D2 DCCB CLOSED S006-30 - 56 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-286 I21.6 21 R0S11 I21.6 17 R0S06 R06 TRACK FEEDER D15 DCCB OPENED S006-39 - 23 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-288 I21.7 22 R0S11 I21.7 18 R0S06 R06 TRACK FEEDER D15 DCCB CLOSED S006-40 - 24 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM1 UM1 23 R0S11 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S11 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R0S06 R06 TRACK FEEDER D16 DCCB OPENED S006-47 - 29 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-292 I22.1 27 R0S11 I22.1 22 R0S06 R06 TRACK FEEDER D16 DCCB CLOSED S006-48 - 30 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-294 I22.2 28 R0S11 I22.2 23 R0S06 R06 TRACK FEEDER D17 DCCB OPENED S007-8 - 35 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-296 I22.3 29 R0S11 I22.3 24 R0S06 R06 TRACK FEEDER D17 DCCB CLOSED S007-9 - 36 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-298 I22.4 30 R0S11 I22.4 25 R0S06 R06 TRACK FEEDER D18 DCCB OPENED S007-16 - 41 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-300 I22.5 31 R0S11 I22.5 26 R0S06 R06 TRACK FEEDER D18 DCCB CLOSED S007-17 - 42 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-302 I22.6 32 R0S11 I22.6 27 R0S06 R06 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S007-24 - 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-304 I22.7 33 R0S11 I22.7 28 R0S06 R06 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S007-25 - 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM2 UM2 34 R0S11 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R0S06 R06 110 SECTION BREAKER S15 DC CB OPENED S007-44 - 181 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-308 I23.1 38 R0S11 I23.1 32 R0S06 R06 110 SECTION BREAKER S15 DC CB CLOSED S007-45 - 182 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-310 I23.2 39 R0S11 I23.2 33 R0S06 R06 110 SECTION BREAKER S16 DC CB OPENED S007-46 - 191 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-312 I23.3 40 R0S11 I23.3 34 R0S06 R06 110 SECTION BREAKER S16 DC CB CLOSED S007-47 - 192 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-314 I23.4 41 R0S11 I23.4 35 R0S06 R06 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - -
DI-316 I23.5 42 R0S11 I23.5 36 R0S06 R06 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - -
DI-318 I23.6 43 R0S11 I23.6 37 R0S06 - SPARE S008-19 - - - - - - - - - - - - - - - - - - - - - -
DI-320 I23.7 44 R0S11 I23.7 38 R0S06 - SPARE S008-20 - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S11 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S11 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
- - - I24.0 1 R0S07 - SPARE S006-33 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I24.1 2 R0S07 - SPARE S006-34 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I24.2 3 R0S07 - SPARE S006-35 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I24.3 4 R0S07 - SPARE S006-36 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I24.4 5 R0S07 - SPARE S006-37 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I24.5 6 R0S07 - SPARE S006-38 - - - - - - - - - - - - - - - - - - - - - -
- - - I24.6 7 R0S07 - SPARE S006-41 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I24.7 8 R0S07 - SPARE S006-42 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - - 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
- - - I25.0 11 R0S07 - SPARE S006-43 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I25.1 12 R0S07 - SPARE S006-44 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I25.2 13 R0S07 - SPARE S006-45 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I25.3 14 R0S07 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - - -
- - - I25.4 15 R0S07 - SPARE S007-2 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I25.5 16 R0S07 - SPARE S007-3 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I25.6 17 R0S07 - SPARE S007-4 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I25.7 18 R0S07 - SPARE S007-5 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - 1L+ 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
- - - 1M 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
- - - I26.0 21 R0S07 - SPARE S007-6 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I26.1 22 R0S07 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - - -
- - - I26.2 23 R0S07 - SPARE S007-10 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I26.3 24 R0S07 - SPARE S007-11 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I26.4 25 R0S07 - SPARE S007-12 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I26.5 26 R0S07 - SPARE S007-13 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I26.6 27 R0S07 - SPARE S007-14 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I26.7 28 R0S07 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - - -
- - - - 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
- - - I27.0 31 R0S07 - SPARE S007-18 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I27.1 32 R0S07 - SPARE S007-19 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I27.2 33 R0S07 - SPARE S007-20 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I27.3 34 R0S07 - SPARE S007-21 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I27.4 35 R0S07 - SPARE S007-22 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I27.5 36 R0S07 - SPARE S007-23 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I27.6 37 R0S07 - SPARE S007-24 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - I27.7 38 R0S07 - SPARE S007-25 - - - - - - - - - - - NO 0 - - - - - - - - -
- - - 2L+ 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
- - - 2M 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 67 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S13 - - R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S13 - - R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S13 IW.256 1 R1S04 R06 TRACK FEEDER D15 DC CURRENT S009-1 - 344 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-1 (-) IW.256 5 R0S13 IW.256 21 R1S04 - - S009-2 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850
TB2-2 (+) IW.258 6 R0S13 IW.258 2 R1S04 R06 RECTIFIER FEEDER H01 CURRENT S009-3 - 335 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-2 (-) IW.258 7 R0S13 IW.258 22 R1S04 - - S009-4 - - 418 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-3 (+) IW.260 8 R0S13 IW.260 3 R1S04 R06 RECTIFIER UNIT 1 DC CURRENT S009-5 - 339 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-3 (-) IW.260 9 R0S13 IW.260 23 R1S04 - - S009-6 - - 422 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-4 (+) IW.262 10 R0S13 IW.262 4 R1S04 R06 RECTIFIER UNIT 1 DC VOLTAGE S009-7 - 340 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-4 (-) IW.262 11 R0S13 IW.262 24 R1S04 - - S009-8 - - 423 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.500 931.000
TB2-5 (+) IW.264 15 R0S13 IW.264 5 R1S04 R06 TRACK FEEDER D16 DC CURRENT S009-9 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-5 (-) IW.264 16 R0S13 IW.264 25 R1S04 - - S009-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850
TB2-6 (+) IW.266 17 R0S13 IW.266 6 R1S04 R06 RECTIFIER FEEDER H02 CURRENT S009-11 - 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-6 (-) IW.266 18 R0S13 IW.266 26 R1S04 - - S009-12 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-7 (+) IW.268 19 R0S13 IW.268 7 R1S04 R06 RECTIFIER UNIT 2 DC CURRENT S009-13 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-7 (-) IW.268 20 R0S13 IW.268 27 R1S04 - - S009-14 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-8 (+) IW.270 21 R0S13 IW.270 8 R1S04 R06 RECTIFIER UNIT 2 DC VOLTAGE S009-15 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-8 (-) IW.270 22 R0S13 IW.270 28 R1S04 - - S009-16 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931
TB2-9 (+) IW.272 26 R0S13 IW.272 9 R1S04 R06 TRACK FEEDER D17 DC CURRENT S009-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-9 (-) IW.272 27 R0S13 IW.272 29 R1S04 - - S009-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850
TB2-10 (+) IW.274 28 R0S13 IW.274 10 R1S04 R06 RING MAIN H03 CURRENT S009-19 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-10 (-) IW.274 29 R0S13 IW.274 30 R1S04 - - S009-20 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-11 (+) IW.276 30 R0S13 IW.276 11 R1S04 R06 RING MAIN H04 CURRENT S009-21 - 338 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-11 (-) IW.276 31 R0S13 IW.276 31 R1S04 - - S009-22 - - 421 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-12 (+) IW.278 32 R0S13 IW.278 12 R1S04 R06 AC BUSBAR VOLTAGE S009-23 - 349 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00%
TB2-12 (-) IW.278 33 R0S13 IW.278 32 R1S04 - - S009-24 - - 432 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.950 10.395 11.495 11.78
TB2-13 (+) IW.280 37 R0S13 IW.280 13 R1S04 R06 TRACK FEEDER D18 DC CURRENT S009-25 - 347 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-13 (-) IW.280 38 R0S13 IW.280 33 R1S04 - - S009-26 - - 430 - - - - - - to - - to - - - - - -8.571 7.143 7.143 8.571 -2850 2625 2375 2850
TB2-14 (+) IW.282 39 R0S13 IW.282 14 R1S04 R06 DC BUSBAR DC VOLTAGE S009-27 - 348 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00%
TB2-14 (-) IW.282 40 R0S13 IW.282 34 R1S04 - - S009-28 - - 431 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500 902.5 931
TB2-15 (+) IW.284 41 R0S13 IW.284 15 R1S04 R06 NEGATIVE BUSBAR DC RETURN CURRENT S009-29 - 343 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00%
TB2-15 (-) IW.284 42 R0S13 IW.284 35 R1S04 - - S009-30 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800
TB2-16 (+) IW.286 43 R0S13 IW.286 16 R1S04 R06 RING MAIN H05 CURRENT S009-31 - 350 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 0.05 0.05 0.05 0.05
TB2-16 (-) IW.286 44 R0S13 IW.286 36 R1S04 - - S009-32 - - 433 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
S110-RD - - R0S13 - - R1S04 - - S009-70 - 405 - - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S13 - - R1S04 - - S009-71 - - 488 - - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S13 - - R1S04 - - S009-72 - - 488 - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 68 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - R0S13 - - R1S04 - - S012-1 - - - - - - - - - - - - - - - - - - - - - - -


- - - - - R1S05 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - R1S05 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
- - - IW.288 1 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.288 21 R1S05 - - - - - - - - - - - - to -
- - - IW.290 2 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.290 22 R1S05 - - - - - - - - - - - - to -
- - - IW.292 3 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.292 23 R1S05 - - - - - - - - - - - - to -
- - - IW.294 4 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.294 24 R1S05 - - - - - - - - - - - - to -
- - - IW.296 5 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.296 25 R1S05 - - - - - - - - - - - - to -
- - - IW.298 6 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.298 26 R1S05 - - - - - - - - - - - - to -
- - - IW.300 7 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.300 27 R1S05 - - - - - - - - - - - - to -
- - - IW.302 8 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.302 28 R1S05 - - - - - - - - - - - - to -
- - - IW.304 9 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.304 29 R1S05 - - - - - - - - - - - - to -
- - - IW.306 10 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.306 30 R1S05 - - - - - - - - - - - - to -
- - - IW.308 11 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.308 31 R1S05 - - - - - - - - - - - - to -
- - - IW.310 12 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.310 32 R1S05 - - - - - - - - - - - - to -
- - - IW.312 13 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.312 33 R1S05 - - - - - - - - - - - - to -
- - - IW.314 14 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.314 34 R1S05 - - - - - - - - - - - - to -
- - - IW.316 15 R1S05 - SPARE - - - - AI - - - - - 0 to +20
- - - IW.316 35 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - -
- - - IW.318 16 R1S05 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - -
- - - IW.318 36 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - -
ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S12 Q4.0 2 R1S02 R06 RING MAIN H03 VCB OPEN S012-2 - 16 - CO - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S12 Q4.1 3 R1S02 R06 RING MAIN H03 VCB CLOSE S012-3 - 15 - CO - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S12 Q4.2 6 R1S02 R06 RING MAIN H04 VCB OPEN S012-4 - 22 - CO - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S12 Q4.3 7 R1S02 R06 RING MAIN H04 VCB CLOSE S012-5 - 21 - CO - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S12 Q4.4 12 R1S02 R06 RECTIFIER FEEDER H01 VCB OPEN S012-6 - 80 - CO - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S12 Q4.5 13 R1S02 R06 RECTIFIER FEEDER H01 VCB CLOSE S012-7 - 81 - CO - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S12 Q4.6 16 R1S02 R06 RECTIFIER FEEDER D1 DCCB OPEN S012-8 - 73 - CO - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S12 Q4.7 17 R1S02 R06 RECTIFIER FEEDER D1 DCCB CLOSE S012-9 - 74 - CO - - - - - - - - - - - - - - - - - - -
- - - L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
- - - M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-09 Q5.0 15 R0S12 Q5.0 22 R1S02 R06 RECTIFIER FEEDER H02 VCB OPEN S012-10 - 82 - CO - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S12 Q5.1 23 R1S02 R06 RECTIFIER FEEDER H02 VCB CLOSE S012-11 - 83 - CO - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S12 Q5.2 26 R1S02 R06 RECTIFIER FEEDER D2 DCCB OPEN S012-12 - 75 - CO - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S12 Q5.3 27 R1S02 R06 RECTIFIER FEEDER D2 DCCB CLOSE S012-13 - 76 - CO - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S12 Q5.4 32 R1S02 R06 TRACK FEEDER D15 DCCB OPEN S012-14 - 25 - CO - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S12 Q5.5 33 R1S02 R06 TRACK FEEDER D15 DCCB CLOSE S012-15 - 26 - CO - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S12 Q5.6 36 R1S02 R06 TRACK FEEDER D16 DCCB OPEN S012-16 - 31 - CO - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S12 Q5.7 37 R1S02 R06 TRACK FEEDER D16 DCCB CLOSE S012-17 - 32 - CO - - - - - - - - - - - - - - - - - - -
- - - L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
- - - M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-17 Q6.0 26 R0S12 Q6.0 2 R1S03 R06 TRACK FEEDER D17 DCCB OPEN S012-18 - 37 - CO - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S12 Q6.1 3 R1S03 R06 TRACK FEEDER D17 DCCB CLOSE S012-19 - 38 - CO - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S12 Q6.2 6 R1S03 R06 TRACK FEEDER D18 DCCB OPEN S012-20 - 43 - CO - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S12 Q6.3 7 R1S03 R06 TRACK FEEDER D18 DCCB CLOSE S012-21 - 44 - CO - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S12 Q6.4 12 R1S03 R06 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S012-22 - 51 - CO - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S12 Q6.5 13 R1S03 - SPARE S012-23 - - - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S12 Q6.6 16 R1S03 - SPARE S012-24 - - - - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S12 Q6.7 17 R1S03 - SPARE S012-25 - - - - - - - - - - - - - - - - - - - - - -
- - - L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
- - - M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-25 Q7.0 37 R0S12 Q7.0 22 R1S03 R06 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S12 Q7.1 23 R1S03 R06 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S12 Q7.2 26 R1S03 R06 RING MAIN H05 VCB OPEN S012-28 - 179 - CO - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S12 Q7.3 27 R1S03 R06 RING MAIN H05 VCB CLOSE S012-29 - 178 - CO - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S12 Q7.4 32 R1S03 R06 110 SECTION BREAKER S15 DCCB OPEN S012-30 - 185 - CO - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S12 Q7.5 33 R1S03 R06 110 SECTION BREAKER S15 DCCB CLOSE S012-31 - 186 - CO - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S12 Q7.6 36 R1S03 R06 110 SECTION BREAKER S16 DCCB OPEN S012-32 - 195 - CO - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S12 Q7.7 37 R1S03 R06 110 SECTION BREAKER S16 DCCB CLOSE S012-33 - 196 - CO - - - - - - - - - - - - - - - - - - -
- - - L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
- - - M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S12 - - ENABLE CONTACT AND COMMON RETURN LINE ON THE - - - - - - - - - - - - - - - - - - - - - - - -
32 CO
FR1 FR1 35 R0S12 - - ENABLE CONTACT AND COMMON RETURN LINE ON THE - - - - - - - - - - - - - - - - - - - - - - - -
32 CO
UE0 UE0 45 R0S12 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S12 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 69 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC NC - -
NC NC - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
NC NC - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 70 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
NC NC - -
- - - -
NC C - -
NC C - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
- - - -
- - - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
NC NC - -
NC C - -
- - - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 71 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
- - - -
- - - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 72 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
C NC NC C
-8.143 -6.786 6.786 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 6.786 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 6.786 8.143
C NC NC C
- - 7.125 9.025
C NC NC C
- - 7.125 9.025
C NC NC C
0.760 8.316 9.196 9.424
C NC NC C
-8.143 7.500 6.786 8.143
C NC NC C
3.943 5.565 9.025 9.310
C NC NC C
- - 6.333 7.238
C NC NC C
- - 7.125 9.025
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 73 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -

- - - -

- - - -
- - - -

Unrestricted 749775924.xlsx/RS06 [RS06] 74 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S07 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R07 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R07 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 363 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R07 RING MAIN H03 SOLKOR TRIP S005-6 - 364 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R07 RING MAIN H03 PILOT WIRE ALARM S005-7 - 350 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R07 RING MAIN H03 OVERLOAD ALARM S005-8 - 365 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 R07 ROLLING SHUTTER S005-9 - 395 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R07 RING MAIN H04 CONTROL SELECTOR SWITCH S005-12 - 20 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R07 RING MAIN H04 O/C EARTH FAULT TRIP S005-13 - 354 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R07 RING MAIN H04 SOLKOR TRIP S005-14 - 355 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R07 RING MAIN H04 PILOT WIRE ALARM S005-15 - 351 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R07 RING MAIN H04 OVERLOAD ALARM S005-16 - 356 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 - SPARE S005-17 - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 - SPARE S005-18 - - - - - - - - - - - - - - - - - - - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 - SPARE S005-19 - - - - - - - - - - - - - - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R07 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-22 - 6 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R07 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-23 - 207 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R07 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-24 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R07 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-25 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R07 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-26 - 210 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R07 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-27 - 211 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R07 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-28 - 212 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R07 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-29 - 213 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R07 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-30 - 214 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R07 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-31 - 215 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R07 RECTIFIER 1 FRAME EARTH TRIP S005-32 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R07 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-33 - 217 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R07 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-34 - 218 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R07 RECTIFIER 1 DIODE OVER TEMP ALARM S005-35 - 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R07 RECTIFIER 1 DIODE OVER TEMP TRIP S005-36 - 220 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R07 RECTIFIER 1 REVERSE CURRENT TRIP S005-37 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R07 RECTIFIER 1 SURGE ARRESTOR TRIP S005-38 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R07 RECTIFIER 1 FILTER CIRCUIT ALARM S005-39 - 223 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R07 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-40 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 - SPARE S005-41 - - - - - - - - - - - - - - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R07 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S005-44 - 58 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 - SPARE S005-45 - - - - - - - - - - - - - - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R07 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S005-48 - 10 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R07 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-2 - 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R07 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-3 - 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R07 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-4 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R07 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-5 - 228 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R07 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-6 - 229 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R07 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-7 - 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R07 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-8 - 231 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R07 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-9 - 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R07 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-10 - 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R07 RECTIFIER 2 FRAME EARTH TRIP S006-11 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R07 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-12 - 235 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R07 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-13 - 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R07 RECTIFIER 2 DIODE OVER TEMP ALARM S006-14 - 237 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R07 RECTIFIER 2 DIODE OVER TEMP TRIP S006-15 - 238 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R07 RECTIFIER 2 REVERSE CURRENT TRIP S006-16 - 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R07 RECTIFIER 2 SURGE ARRESTOR TRIP S006-17 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R07 RECTIFIER 2 FILTER CIRCUIT ALARM S006-18 - 241 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R07 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-19 - 242 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 - SPARE S006-20 - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R07 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-23 - 64 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 - SPARE S006-24 - - - - - - - - - - - - - - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R07 AUXILIARY TRANSFORMER 11KV SWITCH H5 S006-25 - 2 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 - SPARE S006-26 - 1 - - - - - - - - - - - - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R07 AUXILIARY TRANSFORMER 11KV SW H5 FUSE BLOWN TRIP S006-27 - 243 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R07 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-28 - 244 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 - SPARE S006-29 - 353 - - - - - - - - - - - - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R07 750V DCCB TRIP CCT SUPERVISION ALARM S006-30 - 371 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 75 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R07 TRACK FEEDER D17 CONTROL SELECTOR SWITCH S006-33 - 28 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R07 TRACK FEEDER D17 INSTANT OVERCURRENT S006-34 - 245 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R07 TRACK FEEDER D17 RATE OF RISE TRIP S006-35 - 246 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R07 TRACK FEEDER D17 LINE TESTING S006-36 - 29 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R07 TRACK FEEDER D17 LINE IMPEDANCE LOW S006-37 - 247 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S006-38 - - - - - - - - - - - - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R07 TRACK FEEDER D18 CONTROL SELECTOR SWITCH S006-41 - 36 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R07 TRACK FEEDER D18 INSTANT OVERCURRENT S006-42 - 248 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R07 TRACK FEEDER D18 RATE OF RISE TRIP S006-43 - 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R07 TRACK FEEDER D18 LINE TESTING S006-44 - 38 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R07 TRACK FEEDER D18 LINE IMPEDANCE LOW S006-45 - 250 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R07 TRACK FEEDER D19 CONTROL SELECTOR SWITCH S007-2 - 44 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R07 TRACK FEEDER D19 INSTANT OVERCURRENT S007-3 - 251 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R07 TRACK FEEDER D19 RATE OF RISE TRIP S007-4 - 357 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R07 TRACK FEEDER D19 LINE TESTING S007-5 - 45 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R07 TRACK FEEDER D19 LINE IMPEDANCE LOW S007-6 - 358 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R07 TRACK FEEDER D20 CONTROL SELECTOR SWITCH S007-10 - 52 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R07 TRACK FEEDER D20 INSTANT OVERCURRENT S007-11 - 359 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R07 TRACK FEEDER D20 RATE OF RISE TRIP S007-12 - 360 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R07 TRACK FEEDER D20 LINE TESTING S007-13 - 53 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R07 TRACK FEEDER D20 LINE IMPEDANCE LOW S007-14 - 361 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R07 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-18 - 362 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R07 AC/DC SYSTEM MAINS FAILED ALARM S007-19 - 198 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R07 AC/DC SYSTEM 380V FEEDER MCB S007-20 - 199 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R07 AC/DC SYSTEM AC EARTH FAULT TRIP S007-21 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R07 AC/DC SYSTEM BATTERY CHARGER S007-22 - 201 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R07 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-23 - 352 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R07 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-24 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R07 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-25 - 203 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R07 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-26 - 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R07 AC/DC SYSTEM 110V DC COMMON FEEDER S007-27 - 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R07 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-28 - 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R07 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-29 - 391 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R07 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-30 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R07 COMMON EQUIPMENT INTRUDER ALARM S007-31 - 393 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R07 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 - SPARE S007-33 - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R07 RING MAIN H03 VCB OPENED S005-2 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R07 RING MAIN H03 VCB CLOSED S005-3 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R07 RING MAIN H04 VCB OPENED S005-10 - 17 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R07 RING MAIN H04 VCB CLOSED S005-11 - 18 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R07 RECTIFIER FEEDER H01 VCB OPENED S005-20 - 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R07 RECTIFIER FEEDER H01 VCB CLOSED S005-21 - 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R07 RECTIFIER FEEDER D1 DCCB OPENED S005-42 - 59 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R07 RECTIFIER FEEDER D1 DCCB CLOSED S005-43 - 60 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R07 RECTIFIER FEEDER H02 VCB OPENED S005-46 - 7 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R07 RECTIFIER FEEDER H02 VCB CLOSED S005-47 - 8 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R07 RECTIFIER FEEDER D2 DCCB OPENED S006-21 - 65 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R07 RECTIFIER FEEDER D2 DCCB CLOSED S006-22 - 66 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R07 TRACK FEEDER D17 DCCB OPENED S006-31 - 23 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R07 TRACK FEEDER D17 DCCB CLOSED S006-32 - 24 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R07 TRACK FEEDER D18 DCCB OPENED S006-39 - 31 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R07 TRACK FEEDER D18 DCCB CLOSED S006-40 - 32 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R07 TRACK FEEDER D19 DCCB OPENED S006-47 - 39 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R07 TRACK FEEDER D19 DCCB CLOSED S006-48 - 40 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R07 TRACK FEEDER D20 DCCB OPENED S007-8 - 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R07 TRACK FEEDER D20 DCCB CLOSED S007-9 - 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R07 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S007-16 - 55 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R07 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S007-17 - 56 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R07 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R07 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -
I20.0 1 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I20.1 2 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I20.2 3 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I20.3 4 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I20.4 5 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I20.5 6 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I20.6 7 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I20.7 8 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
- 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - -
- 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - -
I21.0 11 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I21.1 12 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I21.2 13 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I21.3 14 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I21.4 15 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I21.5 16 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I21.6 17 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I21.7 18 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - -
1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - -
I22.0 21 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I22.1 22 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I22.2 23 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 76 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

I22.3 24 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -


I22.4 25 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I22.5 26 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I22.6 27 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I22.7 28 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
- 39 R0S06 +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - -
- 40 R0S06 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - -
I23.0 31 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I23.1 32 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I23.2 33 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I23.3 34 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I23.4 35 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I23.5 36 R0S06 - SPARE - - - - - - - - - - - - 0 - - - - - - -
I23.6 37 R0S06 - SPARE internal wiring - - - - - - - - - - - - 0 - - - - - - -
I23.7 38 R0S06 - SPARE internal wiring - - - - - - - - - - - - 0 - - - - - - -
2L+ 39 R0S06 +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - -
2M 40 R0S06 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 77 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S12 IW.256 1 R1S04 R07 TRACK FEEDER D17 DC CURRENT S009-1 - 344 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00%
TB2-1 (-) IW.256 5 R0S12 IW.256 21 R1S04 - - S009-2 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375
TB2-2 (+) IW.258 6 R0S12 IW.258 2 R1S04 R07 RECTIFIER FEEDER H01 CURRENT S009-3 - 335 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00%
TB2-2 (-) IW.258 7 R0S12 IW.258 22 R1S04 - - S009-4 - - 418 - - - - - - to - - to - - - - - - - 6.667 7.917 - -
TB2-3 (+) IW.260 8 R0S12 IW.260 3 R1S04 R07 RECTIFIER UNIT 1 DC CURRENT S009-5 - 339 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00%
TB2-3 (-) IW.260 9 R0S12 IW.260 23 R1S04 - - S009-6 - - 422 - - - - - - to - - to - - - - - - - 4.762 5.714 - -
TB2-4 (+) IW.262 10 R0S12 IW.262 4 R1S04 R07 RECTIFIER UNIT 1 DC VOLTAGE S009-7 - 340 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00%
TB2-4 (-) IW.262 11 R0S12 IW.262 24 R1S04 - - S009-8 - - 423 - - - - - - to - - to - - - - - - - 9.500 9.800 - -
TB2-5 (+) IW.264 15 R0S12 IW.264 5 R1S04 R07 TRACK FEEDER D18 DC CURRENT S009-9 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00%
TB2-5 (-) IW.264 16 R0S12 IW.264 25 R1S04 - - S009-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375
TB2-6 (+) IW.266 17 R0S12 IW.266 6 R1S04 R07 RECTIFIER FEEDER H02 CURRENT S009-11 - 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00%
TB2-6 (-) IW.266 18 R0S12 IW.266 26 R1S04 - - S009-12 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - -
TB2-7 (+) IW.268 19 R0S12 IW.268 7 R1S04 R07 RECTIFIER UNIT 2 DC CURRENT S009-13 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00%
TB2-7 (-) IW.268 20 R0S12 IW.268 27 R1S04 - - S009-14 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - -
TB2-8 (+) IW.270 21 R0S12 IW.270 8 R1S04 R07 RECTIFIER UNIT 2 DC VOLTAGE S009-15 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00%
TB2-8 (-) IW.270 22 R0S12 IW.270 28 R1S04 - - S009-16 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - -
TB2-9 (+) IW.272 26 R0S12 IW.272 9 R1S04 R07 TRACK FEEDER D19 DC CURRENT S009-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00%
TB2-9 (-) IW.272 27 R0S12 IW.272 29 R1S04 - - S009-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375
TB2-10 (+) IW.274 28 R0S12 IW.274 10 R1S04 R07 RING MAIN H03 CURRENT S009-19 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-10 (-) IW.274 29 R0S12 IW.274 30 R1S04 - - S009-20 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-11 (+) IW.276 30 R0S12 IW.276 11 R1S04 R07 RING MAIN H04 CURRENT S009-21 - 338 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00%
TB2-11 (-) IW.276 31 R0S12 IW.276 31 R1S04 - - S009-22 - - 421 - - - - - - to - - to - - - - - - - 7.500 9.500 - -
TB2-12 (+) IW.278 32 R0S12 IW.278 12 R1S04 R07 AC BUSBAR VOLTAGE S009-23 - 349 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00%
TB2-12 (-) IW.278 33 R0S12 IW.278 32 R1S04 - - S009-24 - - 432 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.950 10.395
TB2-13 (+) IW.280 37 R0S12 IW.280 13 R1S04 R07 TRACK FEEDER D20 DC CURRENT S009-25 - 347 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2500 3000 5.00% 5.00%
TB2-13 (-) IW.280 38 R0S12 IW.280 33 R1S04 - - S009-26 - - 430 - - - - - - to - - to - - - - - -8.571 7.143 7.143 8.571 -2850 2625
TB2-14 (+) IW.282 39 R0S12 IW.282 14 R1S04 R07 DC BUSBAR DC VOLTAGE S009-27 - 348 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00%
TB2-14 (-) IW.282 40 R0S12 IW.282 34 R1S04 - - S009-28 - - 431 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500
TB2-15 (+) IW.284 41 R0S12 IW.284 15 R1S04 R07 NEGATIVE DC BUSBAR DC RETURN CURRENT S009-29 - 343 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00%
TB2-15 (-) IW.284 42 R0S12 IW.284 35 R1S04 - - S009-30 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - -
TB2-16 (+) IW.286 43 R0S12 IW.286 16 R1S04 - SPARE S009-31 - - - - - - - - - to - - to - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S12 IW.286 36 R1S04 - - S009-32 - - - - - - - - - to - - to - - '- '- - - - - - - -
S110-RD - - R0S12 - - - - - S009-70 - 405 - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S12 - - - - - S009-71 - - 488 - - - - - - - - - - - - - - - - - -
S112-BL - - R0S12 - - - - - S009-72 - - 488 - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 78 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - R0S12 - - - - - S008-1 - - - - - - - - - - - - - - - - - - - - -


- - - IW.288 1 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.288 21 R1S05 - - - - - - - - - - - - to -
- - - IW.290 2 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.290 22 R1S05 - - - - - - - - - - - - to -
- - - IW.292 3 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.292 23 R1S05 - - - - - - - - - - - - to -
- - - IW.294 4 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.294 24 R1S05 - - - - - - - - - - - - to -
- - - IW.296 5 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.296 25 R1S05 - - - - - - - - - - - - to -
- - - IW.298 6 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.298 26 R1S05 - - - - - - - - - - - - to -
- - - IW.300 7 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.300 27 R1S05 - - - - - - - - - - - - to -
- - - IW.302 8 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.302 28 R1S05 - - - - - - - - - - - - to -
- - - IW.304 9 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.304 29 R1S05 - - - - - - - - - - - - to -
- - - IW.306 10 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.306 30 R1S05 - - - - - - - - - - - - to -
- - - IW.308 11 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.308 31 R1S05 - - - - - - - - - - - - to -
- - - IW.310 12 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.310 32 R1S05 - - - - - - - - - - - - to -
- - - IW.312 13 R1S05 - SPARE - - - - AI - - - - - -20 to +20
- - - IW.312 33 R1S05 - - - - - - - - - - - - to -
- - - IW.314 14 R1S05 - SPARE - - - - AI - - - - - 0 to +10
- - - IW.314 34 R1S05 - - - - - - - - - - - - to -
- - - IW.316 15 R1S05 - SPARE - - - - AI - - - - - 0 to +20
- - - IW.316 35 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - -
- - - IW.318 16 R1S05 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - -
- - - IW.318 36 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - -
ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S11 Q4.0 2 R1S02 R07 RING MAIN H03 VCB OPEN S008-2 - 16 - CO - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S11 Q4.1 3 R1S02 R07 RING MAIN H03 VCB CLOSE S008-3 - 15 - CO - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S11 Q4.2 6 R1S02 R07 RING MAIN H04 VCB OPEN S008-4 - 21 - CO - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S11 Q4.3 7 R1S02 R07 RING MAIN H04 VCB CLOSE S008-5 - 22 - CO - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S11 Q4.4 12 R1S02 R07 RECTIFIER FEEDER H01 VCB OPEN S008-6 - 77 - CO - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S11 Q4.5 13 R1S02 R07 RECTIFIER FEEDER H01 VCB CLOSE S008-7 - 78 - CO - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S11 Q4.6 16 R1S02 R07 RECTIFIER FEEDER D1 DCCB OPEN S008-8 - 73 - CO - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S11 Q4.7 17 R1S02 R07 RECTIFIER FEEDER D1 DCCB CLOSE S008-9 - 74 - CO - - - - - - - - - - - - - - - - -
L+ 19
M 20
RL-09 Q5.0 15 R0S11 Q5.0 22 R1S02 R07 RECTIFIER FEEDER H02 VCB OPEN S008-10 - 79 - CO - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S11 Q5.1 23 R1S02 R07 RECTIFIER FEEDER H02 VCB CLOSE S008-11 - 80 - CO - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S11 Q5.2 26 R1S02 R07 RECTIFIER FEEDER D2 DCCB OPEN S008-12 - 75 - CO - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S11 Q5.3 27 R1S02 R07 RECTIFIER FEEDER D2 DCCB CLOSE S008-13 - 76 - CO - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S11 Q5.4 32 R1S02 R07 TRACK FEEDER D17 DCCB OPEN S008-14 - 25 - CO - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S11 Q5.5 33 R1S02 R07 TRACK FEEDER D17 DCCB CLOSE S008-15 - 26 - CO - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S11 Q5.6 36 R1S02 R07 TRACK FEEDER D18 DCCB OPEN S008-16 - 33 - CO - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S11 Q5.7 37 R1S02 R07 TRACK FEEDER D18 DCCB CLOSE S008-17 - 34 - CO - - - - - - - - - - - - - - - - -
L+ 39
M 40
RL-17 Q6.0 26 R0S11 Q6.0 2 R1S03 R07 TRACK FEEDER D19 DCCB OPEN S008-18 - 41 - CO - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S11 Q6.1 3 R1S03 R07 TRACK FEEDER D19 DCCB CLOSE S008-19 - 42 - CO - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S11 Q6.2 6 R1S03 R07 TRACK FEEDER D20 DCCB OPEN S008-20 - 49 - CO - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S11 Q6.3 7 R1S03 R07 TRACK FEEDER D20 DCCB CLOSE S008-21 - 50 - CO - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S11 Q6.4 12 R1S03 R07 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S008-22 - 61 - CO - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S11 Q6.5 13 R1S03 - SPARE S008-23 - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S11 Q6.6 16 R1S03 R07 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S11 Q6.7 17 R1S03 R07 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - -
L+ 19
M 20
RL-25 Q7.0 37 R0S11 Q7.0 22 R1S03 - SPARE S008-26 - 69 - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S11 Q7.1 23 R1S03 - SPARE S008-27 - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S11 Q7.2 26 R1S03 - SPARE S008-28 - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S11 Q7.3 27 R1S03 - SPARE S008-29 - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S11 Q7.4 32 R1S03 - SPARE S008-30 - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S11 Q7.5 33 R1S03 - SPARE S008-31 - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S11 Q7.6 36 R1S03 - SPARE S008-32 - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S11 Q7.7 37 R1S03 - SPARE S008-33 - - - - - - - - - - - - - - - - - - - -
L+ 39
M 40
FR0 FR0 34 R0S11 FR0 - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S11 FR1 - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S11 UE0 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S11 UE1 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 79 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC C - -
- - - - - -
- - NC NC - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - NC NC - -
- - - - - -
- - NC NC - -
- - - - - -
- - NC C - -
- - NC C - -
- - - - - -
- - NC C - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 80 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - - - - -
- - - - - -
- - NC C - -
- - - - - -
- - NC NC - -
- - NC C - -
- - NC C - -
- - NC NC - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - NC C - -
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -

Unrestricted 749775924.xlsx/RS07 [RS07] 81 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - C NC - -
- - - - NC C
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 82 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
- - - - - -
5.00% 5.00% C NC NC C
2375 2850 -8.143 -6.786 6.786 8.143
5.00% 5.00% C NC NC C
76 90.25 - - 6.333 7.521
5.00% 5.00% C NC NC C
2375 2850 - - 4.524 5.429
5.00% 5.00% C NC NC C
902.500 931.000 - - 9.025 9.310
5.00% 5.00% C NC NC C
2375 2850 -8.143 -6.786 6.786 8.143
5.00% 5.00% C NC NC C
76 90.25 - - 6.333 7.521
5.00% 5.00% C NC NC C
2375 2850 - - 4.524 5.429
5.00% 5.00% C NC NC C
902.5 931 - - 9.025 9.310
5.00% 5.00% C NC NC C
2375 2850 -8.143 -6.786 6.786 8.143
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
5.00% 5.00% C NC NC C
285 361 - - 7.125 9.025
5.00% 5.00% C NC NC C
11.495 11.78 0.760 8.316 9.196 9.424
5.00% 5.00% C NC NC C
2375 2850 -8.143 7.500 6.786 8.143
5.00% 5.00% C NC NC C
902.5 931 3.943 5.565 9.025 9.310
5.00% 5.00% C NC NC C
3325 3800 - - 6.333 7.238
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 83 Printed on: 04/30/2024


Deadband of Alarm Limit Alarm Priority

H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - -
C NC NC C
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -

- - - - - -
- - - - - -
- - - - - -
- - - - - -

Unrestricted 749775924.xlsx/RS07 [RS07] 84 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S07 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R08 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R08 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 363 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R08 RING MAIN H03 SOLKOR TRIP S005-6 - 364 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R08 RING MAIN H03 PILOT WIRE ALARM S005-7 - 350 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R08 RING MAIN H03 OVERLOAD ALARM S005-8 - 365 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 - SPARE S005-9 - - - - - - - - - - - - - - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R08 RING MAIN H04 CONTROL SELECTOR SWITCH S005-12 - 20 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R08 RING MAIN H04 O/C EARTH FAULT TRIP S005-13 - 354 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R08 RING MAIN H04 SOLKOR TRIP S005-14 - 355 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R08 RING MAIN H04 PILOT WIRE ALARM S005-15 - 351 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R08 RING MAIN H04 OVERLOAD ALARM S005-16 - 356 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 - SPARE S005-17 - - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 R08 RING MAIN H05 CONTROL SELECTOR SWITCH S005-20 new 5 6 SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 R08 RING MAIN H05 O/C EARTH FAULT TRIP S005-21 new 13 14 SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R08 RING MAIN H05 SOLKOR TRIP S005-22 new 15 16 SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R08 RING MAIN H05 PILOT WIRE ALARM S005-23 new 11 12 SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R08 RING MAIN H05 OVERLOAD ALARM S005-24 new 17 18 SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R08 RING MAIN H05 TRIP CCT SUPERVISION ALARM S005-25 - ? - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 - SPARE S005-26 - - - - - - - - - - - - - - - - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R08 INITIAL FLOOD WARNING - S005-27 - 399 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R08 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-30 - 6 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R08 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-31 - 207 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R08 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-32 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R08 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-33 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R08 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-34 - 210 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R08 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-35 - 211 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R08 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-36 - 212 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R08 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-37 - 213 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R08 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-38 - 214 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R08 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-39 - 215 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R08 RECTIFIER 1 FRAME EARTH TRIP S005-40 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R08 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-41 - 217 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R08 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-42 - 218 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R08 RECTIFIER 1 DIODE OVER TEMP ALARM S005-43 - 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R08 RECTIFIER 1 DIODE OVER TEMP TRIP S005-44 - 220 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R08 RECTIFIER 1 REVERSE CURRENT TRIP S005-45 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R08 RECTIFIER 1 SURGE ARRESTOR TRIP S005-46 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R08 RECTIFIER 1 FILTER CIRCUIT ALARM S005-47 - 223 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R08 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-48 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 - SPARE S006-2 - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R08 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S006-5 - 58 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 - SPARE S006-6 - - - - - - - - - - - - - - - - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R08 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S006-9 - 10 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R08 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-10 - 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R08 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-11 - 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R08 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-12 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R08 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-13 - 228 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R08 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-14 - 229 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R08 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-15 - 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R08 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-16 - 231 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R08 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-17 - 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R08 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-18 - 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R08 RECTIFIER 2 FRAME EARTH TRIP S006-19 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R08 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-20 - 235 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R08 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-21 - 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R08 RECTIFIER 2 DIODE OVER TEMP ALARM S006-22 - 237 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R08 RECTIFIER 2 DIODE OVER TEMP TRIP S006-23 - 238 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R08 RECTIFIER 2 REVERSE CURRENT TRIP S006-24 - 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R08 RECTIFIER 2 SURGE ARRESTOR TRIP S006-25 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R08 RECTIFIER 2 FILTER CIRCUIT ALARM S006-26 - 241 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R08 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-27 - 242 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 - SPARE S006-28 - - - - - - - - - - - - - - - - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R08 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-31 - 64 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 - SPARE S006-32 - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 85 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R08 AUXILIARY TRANSFORMER 11KV SWITCH H6 S006-33 - 2 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 - SPARE S006-34 - 1 - - - - - - - - - - - - - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R08 AUXILIARY TRANSFORMER 11KV SW H6 FUSE BLOWN TRIP S006-35 - 243 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R08 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-36 - 244 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 - SPARE S006-37 - - - - - - - - - - - - - - - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 R08 CRITICAL FLOOD WARNING - S006-38 - 400 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R08 TRACK FEEDER D19 CONTROL SELECTOR SWITCH S006-41 - 28 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R08 TRACK FEEDER D19 INSTANT OVERCURRENT S006-42 - 359 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R08 TRACK FEEDER D19 RATE OF RISE TRIP S006-43 - 360 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R08 TRACK FEEDER D19 LINE TESTING S006-44 - 29 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R08 TRACK FEEDER D19 LINE IMPEDANCE LOW S006-45 - 361 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R08 TRACK FEEDER D20 CONTROL SELECTOR SWITCH S007-2 - 36 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R08 TRACK FEEDER D20 INSTANT OVERCURRENT S007-3 - 248 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R08 TRACK FEEDER D20 RATE OF RISE TRIP S007-4 - 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R08 TRACK FEEDER D20 LINE TESTING S007-5 - 38 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R08 TRACK FEEDER D20 LINE IMPEDANCE LOW S007-6 - 250 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R08 TRACK FEEDER D21 CONTROL SELECTOR SWITCH S007-10 - 44 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R08 TRACK FEEDER D21 INSTANT OVERCURRENT S007-11 - 251 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R08 TRACK FEEDER D21 RATE OF RISE TRIP S007-12 - 357 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R08 TRACK FEEDER D21 LINE TESTING S007-13 - 45 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R08 TRACK FEEDER D21 LINE IMPEDANCE LOW S007-14 - 358 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R08 TRACK FEEDER D22 CONTROL SELECTOR SWITCH S007-18 - 52 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R08 TRACK FEEDER D22 INSTANT OVERCURRENT S007-19 - 245 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R08 TRACK FEEDER D22 RATE OF RISE TRIP S007-20 - 246 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R08 TRACK FEEDER D22 LINE TESTING S007-21 - 53 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R08 TRACK FEEDER D22 LINE IMPEDANCE LOW S007-22 - 247 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 - SPARE S007-23 - - - - - - - - - - - - - - - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R08 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-26 - 362 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R08 AC/DC SYSTEM MAINS FAILED ALARM S007-27 - 198 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R08 AC/DC SYSTEM 380V FEEDER MCB S007-28 - 199 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R08 AC/DC SYSTEM AC EARTH FAULT TRIP S007-29 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R08 AC/DC SYSTEM BATTERY CHARGER S007-30 - 201 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R08 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-31 - 352 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R08 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-32 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R08 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-33 - 203 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R08 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-34 - 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 R08 AC/DC SYSTEM 110V DC COMMON FEEDER S007-35 - 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R08 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-36 - 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R08 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-37 - 391 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R08 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-38 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R08 COMMON EQUIPMENT INTRUDER ALARM S007-39 - 393 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R08 TRACK FEEDER D32 CONTROL SELECTOR SWITCH S007-42 - 177 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R08 TRACK FEEDER D32 INSTANT OVERCURRENT S007-43 - 371 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R08 TRACK FEEDER D32 RATE OF RISE TRIP S007-44 - 372 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 - SPARE S007-45 - - - - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R08 TRACK FEEDER D32 LINE TESTING S007-46 - 178 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R08 TRACK FEEDER D32 LINE IMPEDANCE LOW S007-47 - 373 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R08 TRACK FEEDER D32 TRIP CCT SUPERVISION ALARM S007-48 - 374 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R08 TRACK FEEDER D32 LINE TEST CONTROL SELECTOR SWITCH S008-2 - 385 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R08 TRACK FEEDER D32 TRANSFER TRIP S008-5 - 179 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 - SPARE S008-6 - - - - - - - - - - - - - - - - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R08 TRACK FEEDER D31 CONTROL SELECTOR SWITCH S008-9 - 188 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R08 TRACK FEEDER D31 INSTANT OVERCURRENT S008-10 - 375 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R08 TRACK FEEDER D31 RATE OF RISE TRIP S008-11 - 376 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 - SPARE S008-12 - - - - - - - - - - - - - - - - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R08 TRACK FEEDER D31 LINE TESTING S008-13 - 189 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R08 TRACK FEEDER D31 LINE IMPEDANCE LOW S008-14 - 377 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R08 750V DCCB TRIP CCT SUPERVISION ALARM S008-15 - 378 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R08 TRACK FEEDER D31 LINE TEST CONTROL SELECTOR SWITCH S008-16 - 387 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R08 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 - SPARE S008-18 - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 86 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R0S06 R08 RING MAIN H03 VCB OPENED S005-2 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-260 I20.1 5 R0S11 I20.1 2 R0S06 R08 RING MAIN H03 VCB CLOSED S005-3 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-262 I20.2 6 R0S11 I20.2 3 R0S06 R08 RING MAIN H04 VCB OPENED S005-10 - 17 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-264 I20.3 7 R0S11 I20.3 4 R0S06 R08 RING MAIN H04 VCB CLOSED S005-11 - 18 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-266 I20.4 8 R0S11 I20.4 5 R0S06 R08 RING MAIN H05 VCB OPENED S005-18 new 1 2 DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-268 I20.5 9 R0S11 I20.5 6 R0S06 R08 RING MAIN H05 VCB CLOSED S005-19 new 3 4 DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-270 I20.6 10 R0S11 I20.6 7 R0S06 R08 RECTIFIER FEEDER H01 VCB OPENED S005-28 - 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-272 I20.7 11 R0S11 I20.7 8 R0S06 R08 RECTIFIER FEEDER H01 VCB CLOSED S005-29 - 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM0 UM0 12 R0S11 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R0S06 R08 RECTIFIER FEEDER D1 DCCB OPENED S006-3 - 59 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-276 I21.1 16 R0S11 I21.1 12 R0S06 R08 RECTIFIER FEEDER D1 DCCB CLOSED S006-4 - 60 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-278 I21.2 17 R0S11 I21.2 13 R0S06 R08 RECTIFIER FEEDER H02 VCB OPENED S006-7 - 7 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-280 I21.3 18 R0S11 I21.3 14 R0S06 R08 RECTIFIER FEEDER H02 VCB CLOSED S006-8 - 8 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-282 I21.4 19 R0S11 I21.4 15 R0S06 R08 RECTIFIER FEEDER D2 DCCB OPENED S006-29 - 65 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-284 I21.5 20 R0S11 I21.5 16 R0S06 R08 RECTIFIER FEEDER D2 DCCB CLOSED S006-30 - 66 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-286 I21.6 21 R0S11 I21.6 17 R0S06 R08 TRACK FEEDER D19 DCCB OPENED S006-39 - 23 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-288 I21.7 22 R0S11 I21.7 18 R0S06 R08 TRACK FEEDER D19 DCCB CLOSED S006-40 - 24 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM1 UM1 23 R0S11 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S11 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R0S06 R08 TRACK FEEDER D20 DCCB OPENED S006-47 - 31 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-292 I22.1 27 R0S11 I22.1 22 R0S06 R08 TRACK FEEDER D20 DCCB CLOSED S006-48 - 32 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-294 I22.2 28 R0S11 I22.2 23 R0S06 R08 TRACK FEEDER D21 DCCB OPENED S007-8 - 39 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-296 I22.3 29 R0S11 I22.3 24 R0S06 R08 TRACK FEEDER D21 DCCB CLOSED S007-9 - 40 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-298 I22.4 30 R0S11 I22.4 25 R0S06 R08 TRACK FEEDER D22 DCCB OPENED S007-16 - 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-300 I22.5 31 R0S11 I22.5 26 R0S06 R08 TRACK FEEDER D22 DCCB CLOSED S007-17 - 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-302 I22.6 32 R0S11 I22.6 27 R0S06 R08 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S007-24 - 56 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-304 I22.7 33 R0S11 I22.7 28 R0S06 R08 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S007-25 - 55 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
UM2 UM2 34 R0S11 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R0S06 R08 TRACK FEEDER D32 DCCB OPENED S007-40 - 172 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-308 I23.1 38 R0S11 I23.1 32 R0S06 R08 TRACK FEEDER D32 DCCB CLOSED S007-41 - 173 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-310 I23.2 39 R0S11 I23.2 33 R0S06 R08 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - -
DI-312 I23.3 40 R0S11 I23.3 34 R0S06 R08 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - -
DI-314 I23.4 41 R0S11 I23.4 35 R0S06 R08 TRACK FEEDER D31 DCCB OPENED S008-7 - 182 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - -
DI-316 I23.5 42 R0S11 I23.5 36 R0S06 R08 TRACK FEEDER D31 DCCB CLOSED S008-8 - 183 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - -
DI-318 I23.6 43 R0S11 I23.6 37 R0S06 - SPARE S008-19 - - - - - - - - - - - - - - - - - - - - - -
DI-320 I23.7 44 R0S11 I23.7 38 R0S06 - SPARE S008-20 - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S11 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S11 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
I24.0 1 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I24.1 2 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I24.2 3 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I24.3 4 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I24.4 5 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I24.5 6 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I24.6 7 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I24.7 8 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I25.0 11 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I25.1 12 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I25.2 13 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I25.3 14 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I25.4 15 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I25.5 16 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I25.6 17 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I25.7 18 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
1L+ 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
1M 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I26.0 21 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I26.1 22 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I26.2 23 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I26.3 24 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I26.4 25 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I26.5 26 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I26.6 27 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I26.7 28 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
- 39 R0S07 +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- 40 R0S07 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I27.0 31 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I27.1 32 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I27.2 33 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I27.3 34 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I27.4 35 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I27.5 36 R0S07 - SPARE - - - - - - - - - - - - 0 - - - - - - - - -
I27.6 37 R0S07 - SPARE internal wiring - - - - - - - - - - - - 0 - - - - - - - - -
I27.7 38 R0S07 - SPARE internal wiring - - - - - - - - - - - - 0 - - - - - - - - -
2L+ 39 R0S07 +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - -
2M 40 R0S07 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 87 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S14 IW.256 1 R1S06 R08 TRACK FEEDER D19 DC CURRENT S010-1 - 344 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-1 (-) IW.256 5 R0S14 IW.256 21 R1S06 - - S010-2 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850
TB2-2 (+) IW.258 6 R0S14 IW.258 2 R1S06 R08 RECTIFIER FEEDER H01 CURRENT S010-3 - 335 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-2 (-) IW.258 7 R0S14 IW.258 22 R1S06 - - S010-4 - - 418 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-3 (+) IW.260 8 R0S14 IW.260 3 R1S06 R08 RECTIFIER UNIT 1 DC CURRENT S010-5 - 339 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-3 (-) IW.260 9 R0S14 IW.260 23 R1S06 - - S010-6 - - 422 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-4 (+) IW.262 10 R0S14 IW.262 4 R1S06 R08 RECTIFIER UNIT 1 DC VOLTAGE S010-7 - 340 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-4 (-) IW.262 11 R0S14 IW.262 24 R1S06 - - S010-8 - - 423 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.500 931.000
TB2-5 (+) IW.264 15 R0S14 IW.264 5 R1S06 R08 TRACK FEEDER D20 DC CURRENT S010-9 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-5 (-) IW.264 16 R0S14 IW.264 25 R1S06 - - S010-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 8.010 8.571 -2850 -2375 2375 2850
TB2-6 (+) IW.266 17 R0S14 IW.266 6 R1S06 R08 RECTIFIER FEEDER H02 CURRENT S010-11 - 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00%
TB2-6 (-) IW.266 18 R0S14 IW.266 26 R1S06 - - S010-12 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25
TB2-7 (+) IW.268 19 R0S14 IW.268 7 R1S06 R08 RECTIFIER UNIT 2 DC CURRENT S010-13 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00%
TB2-7 (-) IW.268 20 R0S14 IW.268 27 R1S06 - - S010-14 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850
TB2-8 (+) IW.270 21 R0S14 IW.270 8 R1S06 R08 RECTIFIER UNIT 2 DC VOLTAGE S010-15 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00%
TB2-8 (-) IW.270 22 R0S14 IW.270 28 R1S06 - - S010-16 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931
TB2-9 (+) IW.272 26 R0S14 IW.272 9 R1S06 R08 TRACK FEEDER D21 DC CURRENT S010-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 5.00% 5.00%
TB2-9 (-) IW.272 27 R0S14 IW.272 29 R1S06 - - S010-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 8.010 8.571 -2850 -2375 2660 2850
TB2-10 (+) IW.274 28 R0S14 IW.274 10 R1S06 R08 RING MAIN H03 CURRENT S010-19 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-10 (-) IW.274 29 R0S14 IW.274 30 R1S06 - - S010-20 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-11 (+) IW.276 30 R0S14 IW.276 11 R1S06 R08 RING MAIN H04 CURRENT S010-21 - 338 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00%
TB2-11 (-) IW.276 31 R0S14 IW.276 31 R1S06 - - S010-22 - - 421 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
TB2-12 (+) IW.278 32 R0S14 IW.278 12 R1S06 R08 AC BUSBAR VOLTAGE S010-23 - 349 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00%
TB2-12 (-) IW.278 33 R0S14 IW.278 32 R1S06 - - S010-24 - - 432 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.950 10.395 11.495 11.78
TB2-13 (+) IW.280 37 R0S14 IW.280 13 R1S06 R08 TRACK FEEDER D22 DC CURRENT S010-25 - 347 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2800 3000 5.00% 5.00% 5.00% 5.00%
TB2-13 (-) IW.280 38 R0S14 IW.280 33 R1S06 - - S010-26 - - 430 - - - - - - to - - to - - - - - -8.571 7.143 8.010 8.571 -2850 2625 2660 2850
TB2-14 (+) IW.282 39 R0S14 IW.282 14 R1S06 R08 DC BUSBAR DC VOLTAGE S010-27 - 348 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00%
TB2-14 (-) IW.282 40 R0S14 IW.282 34 R1S06 - - S010-28 - - 431 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500 902.5 931
TB2-15 (+) IW.284 41 R0S14 IW.284 15 R1S06 R08 NEGATIVE DC BUSBAR DC RETURN CURRENT S010-29 - 343 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00%
TB2-15 (-) IW.284 42 R0S14 IW.284 35 R1S06 - - S010-30 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800
TB2-16 (+) IW.286 43 R0S14 IW.286 16 R1S06 R08 RING MAIN H05 CURRENT (FUTURE) S010-31 new 35 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 0.05 0.05 0.05 0.05
TB2-16 (-) IW.286 44 R0S14 IW.286 36 R1S06 - - S010-32 new - 36 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361
ZS1 ZS1 1 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
TB2-17 (+) IW.288 4 R0S15 IW.288 1 R1S07 R08 TRACK FEEDER D32 DC CURRENT S010-33 - 366 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2800 3000 5.00% 5.00% 5.00% 5.00%
TB2-17 (+) IW.288 5 R0S15 IW.288 21 R1S07 - - S010-34 - - 449 - - - - - - to - - to - - - - - -8.571 7.143 8.010 8.571 -2850 2625 2660 2850
TB2-18 (+) IW.290 6 R0S15 IW.290 2 R1S07 - SPARE S010-35 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-18 (-) IW.290 7 R0S15 IW.290 22 R1S07 - - S010-36 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-19 (+) IW.292 8 R0S15 IW.292 3 R1S07 - SPARE S010-37 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-19 (-) IW.292 9 R0S15 IW.292 23 R1S07 - - S010-38 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-20 (+) IW.294 10 R0S15 IW.294 4 R1S07 - SPARE S010-39 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-20 (-) IW.294 11 R0S15 IW.294 24 R1S07 - - S010-40 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-21 (+) IW.296 15 R0S15 IW.296 5 R1S07 R08 TRACK FEEDER D31 DC CURRENT S010-41 - 367 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2500 2800 3000 5.00% 5.00% 5.00% 5.00%
TB2-21 (-) IW.296 16 R0S15 IW.296 25 R1S07 - - S010-42 - - 450 - - - - - - to - - to - - - - - -8.571 7.143 8.010 8.571 -2850 2625 2660 2850
TB2-22 (+) IW.298 17 R0S15 IW.298 6 R1S07 - SPARE S010-43 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-22 (-) IW.298 18 R0S15 IW.298 26 R1S07 - - S010-44 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-23 (+) IW.300 19 R0S15 IW.300 7 R1S07 - SPARE S010-45 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-23 (-) IW.300 20 R0S15 IW.300 27 R1S07 - - S010-46 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-24 (+) IW.302 21 R0S15 IW.302 8 R1S07 - SPARE S010-47 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-24 (-) IW.302 22 R0S15 IW.302 28 R1S07 - - S010-48 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-25 (+) IW.304 26 R0S15 IW.304 9 R1S07 - SPARE S010-49 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-25 (-) IW.304 27 R0S15 IW.304 29 R1S07 - - S010-50 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-26 (+) IW.306 28 R0S15 IW.306 10 R1S07 - SPARE S010-51 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-26 (-) IW.306 29 R0S15 IW.306 30 R1S07 - - S010-52 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-27 (+) IW.308 30 R0S15 IW.308 11 R1S07 - SPARE S010-53 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-27 (-) IW.308 31 R0S15 IW.308 31 R1S07 - - S010-54 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-28 (+) IW.310 32 R0S15 IW.310 12 R1S07 - SPARE S010-55 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-28 (-) IW.310 33 R0S15 IW.310 32 R1S07 - - S010-56 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-29 (+) IW.312 37 R0S15 IW.312 13 R1S07 - SPARE S010-57 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-29 (-) IW.312 38 R0S15 IW.312 33 R1S07 - - S010-58 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-30 (+) IW.314 39 R0S15 IW.314 14 R1S07 - SPARE S010-59 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-30 (-) IW.314 40 R0S15 IW.314 34 R1S07 - - S010-60 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-31 (+) IW.316 41 R0S15 IW.316 15 R1S07 - SPARE S010-61 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-31 (-) IW.316 42 R0S15 IW.316 35 R1S07 - - S010-62 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-32 (+) IW.318 43 R0S15 IW.318 16 R1S07 - SPARE S010-63 - - - - - - - - - to - - to - - - - - - - - - - - - -
TB2-32 (-) IW.318 44 R0S15 IW.318 36 R1S07 - - S010-64 - - - - - - - - - to - - to - - - - - - - - - - - - -
S110-RD - - R0S15 - - - - - S010-70 - 405 - - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S15 - - - - - S010-71 - - 488 - - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S15 - - - - - S010-72 - - 488 - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 88 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Line 1) Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit
Wiring at RTU Module (Internal Wiring at Module Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Delay
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units (sec) LL L H HH LL L H HH
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - R0S15 - - - - - S009-1 - - - - - - - - - - - - - - - - - - - - - - -


ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S12 Q4.0 2 R1S02 R08 RING MAIN H03 VCB OPEN S009-2 - 15 - CO - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S12 Q4.1 3 R1S02 R08 RING MAIN H03 VCB CLOSE S009-3 - 16 - CO - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S12 Q4.2 6 R1S02 R08 RING MAIN H04 VCB OPEN S009-4 - 21 - CO - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S12 Q4.3 7 R1S02 R08 RING MAIN H04 VCB CLOSE S009-5 - 22 - CO - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S12 Q4.4 12 R1S02 R08 RECTIFIER FEEDER H01 VCB OPEN S009-6 - 77 - CO - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S12 Q4.5 13 R1S02 R08 RECTIFIER FEEDER H01 VCB CLOSE S009-7 - 78 - CO - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S12 Q4.6 16 R1S02 R08 RECTIFIER FEEDER D1 DCCB OPEN S009-8 - 73 - CO - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S12 Q4.7 17 R1S02 R08 RECTIFIER FEEDER D1 DCCB CLOSE S009-9 - 74 - CO - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-09 Q5.0 15 R0S12 Q5.0 22 R1S02 R08 RECTIFIER FEEDER H02 VCB OPEN S009-10 - 79 - CO - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S12 Q5.1 23 R1S02 R08 RECTIFIER FEEDER H02 VCB CLOSE S009-11 - 80 - CO - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S12 Q5.2 26 R1S02 R08 RECTIFIER FEEDER D2 DCCB OPEN S009-12 - 75 - CO - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S12 Q5.3 27 R1S02 R08 RECTIFIER FEEDER D2 DCCB CLOSE S009-13 - 76 - CO - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S12 Q5.4 32 R1S02 R08 TRACK FEEDER D19 DCCB OPEN S009-14 - 25 - CO - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S12 Q5.5 33 R1S02 R08 TRACK FEEDER D19 DCCB CLOSE S009-15 - 26 - CO - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S12 Q5.6 36 R1S02 R08 TRACK FEEDER D20 DCCB OPEN S009-16 - 33 - CO - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S12 Q5.7 37 R1S02 R08 TRACK FEEDER D20 DCCB CLOSE S009-17 - 34 - CO - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-17 Q6.0 26 R0S12 Q6.0 2 R1S03 R08 TRACK FEEDER D21 DCCB OPEN S009-18 - 41 - CO - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S12 Q6.1 3 R1S03 R08 TRACK FEEDER D21 DCCB CLOSE S009-19 - 42 - CO - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S12 Q6.2 6 R1S03 R08 TRACK FEEDER D22 DCCB OPEN S009-20 - 49 - CO - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S12 Q6.3 7 R1S03 R08 TRACK FEEDER D22 DCCB CLOSE S009-21 - 50 - CO - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S12 Q6.4 12 R1S03 R08 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S009-22 - 61 - CO - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S12 Q6.5 13 R1S03 - SPARE S009-23 - - - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S12 Q6.6 16 R1S03 - SPARE S009-24 - - - - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S12 Q6.7 17 R1S03 - SPARE S009-25 - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-25 Q7.0 37 R0S12 Q7.0 22 R1S03 - SPARE S009-26 - 69 - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S12 Q7.1 23 R1S03 - SPARE S009-27 - - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S12 Q7.2 26 R1S03 R08 RING MAIN H05 (FUTURE) VCB OPEN S009-28 new 7 8 CO - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S12 Q7.3 27 R1S03 R08 RING MAIN H05 (FUTURE) VCB CLOSE S009-29 new 9 10 CO - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S12 Q7.4 32 R1S03 - SPARE S009-30 - - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S12 Q7.5 33 R1S03 - SPARE S009-31 - - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S12 Q7.6 36 R1S03 R08 TRACK FEEDER D32 DCCB OPEN S009-32 - 174 - CO - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S12 Q7.7 37 R1S03 R08 TRACK FEEDER D32 DCCB CLOSE S009-33 - 175 - CO - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S12 - - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S12 - - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S13 - - - - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S13 - - - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - -
RL-33 Q8.0 4 R0S13 Q8.0 2 R1S04 R08 TRACK FEEDER D31 LINE TEST CONTROL ON S009-34 - 382 - CO - - - - - - - - - - - - - - - - - - -
RL-34 Q8.1 5 R0S13 Q8.1 3 R1S04 R08 TRACK FEEDER D31 LINE TEST CONTROL OFF S009-35 - 383 - CO - - - - - - - - - - - - - - - - - - -
RL-35 Q8.2 6 R0S13 Q8.2 6 R1S04 R08 TRACK FEEDER D31 DCCB OPEN S009-36 - 185 - CO - - - - - - - - - - - - - - - - - - -
RL-36 Q8.3 7 R0S13 Q8.3 7 R1S04 R08 TRACK FEEDER D31 DCCB CLOSE S009-37 - 186 - CO - - - - - - - - - - - - - - - - - - -
RL-37 Q8.4 8 R0S13 Q8.4 12 R1S04 R08 TRACK FEEDER D32 LINE TEST CONTROL ON S009-38 - 380 - CO - - - - - - - - - - - - - - - - - - -
RL-38 Q8.5 9 R0S13 Q8.5 13 R1S04 R08 TRACK FEEDER D32 LINE TEST CONTROL OFF S009-39 - 381 - CO - - - - - - - - - - - - - - - - - - -
RL-39 Q8.6 10 R0S13 Q8.6 16 R1S04 R08 TRACK FEEDER D21 LINE TEST CONTROL ON S009-40 - ? - CO - - - - - - - - - - - - - - - - - - -
RL-40 Q8.7 11 R0S13 Q8.7 17 R1S04 R08 TRACK FEEDER D21 LINE TEST CONTROL OFF S009-41 - ? - CO - - - - - - - - - - - - - - - - - - -
L+ 19 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-41 Q9.0 15 R0S13 Q9.0 22 R1S04 R08 TRACK FEEDER D22 LINE TEST CONTROL ON S009-42 - ? - CO - - - - - - - - - - - - - - - - - - -
RL-42 Q9.1 16 R0S13 Q9.1 23 R1S04 R08 TRACK FEEDER D22 LINE TEST CONTROL OFF S009-43 - ? - CO - - - - - - - - - - - - - - - - - - -
RL-43 Q9.2 17 R0S13 Q9.2 26 R1S04 - SPARE S009-44 - - - - - - - - - - - - - - - - - - - - - -
RL-44 Q9.3 18 R0S13 Q9.3 27 R1S04 - SPARE S009-45 - - - - - - - - - - - - - - - - - - - - - -
RL-45 Q9.4 19 R0S13 Q9.4 32 R1S04 - SPARE S009-46 - - - - - - - - - - - - - - - - - - - - - -
RL-46 Q9.5 20 R0S13 Q9.5 33 R1S04 - SPARE S009-47 - - - - - - - - - - - - - - - - - - - - - -
RL-47 Q9.6 21 R0S13 Q9.6 36 R1S04 - SPARE S009-48 - - - - - - - - - - - - - - - - - - - - - -
RL-48 Q9.7 22 R0S13 Q9.7 37 R1S04 R08 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
L+ 39 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-49 Q10.0 26 R0S13 Q10.0 36 R1S05 R08 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - -
RL-50 Q10.1 27 R0S13 Q10.1 37 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-51 Q10.2 28 R0S13 Q10.2 39 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-52 Q10.3 29 R0S13 Q10.3 40 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-53 Q10.4 30 R0S13 Q10.4 2 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-54 Q10.5 31 R0S13 Q10.5 3 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-55 Q10.6 32 R0S13 Q10.6 6 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-56 Q10.7 33 R0S13 Q10.7 7 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 20 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL)
RL-57 Q11.0 37 R0S13 Q11.0 12 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-58 Q11.1 38 R0S13 Q11.1 13 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-59 Q11.2 39 R0S13 Q11.2 16 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-60 Q11.3 40 R0S13 Q11.3 17 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-61 Q11.4 41 R0S13 Q11.4 19 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-62 Q11.5 42 R0S13 Q11.5 20 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-63 Q11.6 43 R0S13 Q11.6 22 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
RL-64 Q11.7 44 R0S13 Q11.7 23 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE)
M 40 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL)
FR0 FR0 34 R0S13 - - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
FR1 FR1 35 R0S13 - - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE 32 CO - - - - - - - - - - - - - - - - - - - - - - - -
UE0 UE0 45 R0S13 - - - - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S13 - - - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 89 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
- - - -
NC C - -
NC NC - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
- - - -
NC NC - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
NC NC - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 90 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
NC NC - -
- - - -
NC C - -
NC C - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
- - - -
- - - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC NC - -
NC C - -
NC C - -
- - - -
- - - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
NC NC - -
NC C - -
- - - -
- - - -
NC C - -
- - - -
NC NC - -
NC C - -
NC C - -
NC NC - -
NC C - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 91 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
- - - -
- - - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
NC C - -
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
C NC - -
- - NC C
- - - -
- - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 92 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
C NC NC C
-8.143 -6.786 6.786 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 6.900 8.143
C NC NC C
- - 6.333 7.521
C NC NC C
- - 4.524 5.429
C NC NC C
- - 9.025 9.310
C NC NC C
-8.143 -6.786 7.190 8.143
C NC NC C
- - 7.125 9.025
C NC NC C
- - 7.125 9.025
C NC NC C
0.850 8.316 9.196 9.424
C NC NC C
-8.143 6.770 7.100 8.143
C NC NC C
4.380 5.565 9.025 9.310
C NC NC C
- - 6.333 7.238
C NC NC C
- - 7.125 9.025
- - - -
- - - -
C NC NC C
-8.143 -6.770 7.100 8.143
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
C NC NC C
-8.143 -6.770 7.100 8.143
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 93 Printed on: 04/30/2024


Alarm Priority

Alm 0 or Alm 1 or Alm 2 or Alm 3 or


LL L H HH

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -

- - - -
- - - -
- - - -
- - - -

Unrestricted 749775924.xlsx/RS08 [RS08] 94 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. Delay
(+ve) (-ve) LL L
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S7 I4.0 1 R0S02 R09 MAIN INCOMER H05 CONTROL SELECTOR SWITCH S010-4 Y1 32 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-4 I4.1 5 R0S7 I4.1 2 R0S02 R09 MAIN INCOMER H05 O/C EARTH FAULT TRIP S010-5 Y1 251 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-6 I4.2 6 R0S7 I4.2 3 R0S02 R09 MAIN INCOMER H05 REVERSE POWER TRIP S010-6 Y1 250 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-8 I4.3 7 R0S7 I4.3 4 R0S02 R09 MAIN INCOMER H05 INTERTRIP S010-7 Y1 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-10 I4.4 8 R0S7 I4.4 5 R0S02 R09 RING MAIN H01 CONTROL SELECTOR SWITCH S010-10 Y1 5 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-12 I4.5 9 R0S7 I4.5 6 R0S02 R09 RING MAIN H01 O/C EARTH FAULT TRIP S010-11 Y1 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-14 I4.6 10 R0S7 I4.6 7 R0S02 R09 RING MAIN H01 SOLKOR TRIP S010-12 Y1 235 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-16 I4.7 11 R0S7 I4.7 8 R0S02 R09 RING MAIN H01 OVERLOAD ALARM S010-13 Y1 234 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S7 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S7 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S7 I5.0 11 R0S02 R09 RING MAIN H01 PILOT WIRE ALARM S010-14 Y1 ? - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-20 I5.1 16 R0S7 I5.1 12 R0S02 - SPARE S010-15 Y1 - - - - - - - - - - - - - - - - - - - - - - -
DI-22 I5.2 17 R0S7 I5.2 13 R0S02 R09 RING MAIN H02 CONTROL SELECTOR SWITCH S010-18 Y1 20 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-24 I5.3 18 R0S7 I5.3 14 R0S02 R09 RING MAIN H02 O/C EARTH FAULT TRIP S010-19 Y1 245 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-26 I5.4 19 R0S7 I5.4 15 R0S02 R09 RING MAIN H02 SOLKOR TRIP S010-20 Y1 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-28 I5.5 20 R0S7 I5.5 16 R0S02 R09 RING MAIN H02 OVERLOAD ALARM S010-21 Y1 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-30 I5.6 21 R0S7 I5.6 17 R0S02 R09 RING MAIN H02 PILOT WIRE ALARM S010-22 Y1 ? - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-32 I5.7 22 R0S7 I5.7 18 R0S02 - SPARE S010-23 Y1 - - - - - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S7 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S7 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S7 I6.0 21 R0S02 R09 INTERCONNECT H03 CONTROL SELECTOR SWITCH S010-26 Y1 37 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-36 I6.1 27 R0S7 I6.1 22 R0S02 R09 INTERCONNECT H03 O/C EARTH FAULT TRIP S010-27 Y1 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-38 I6.2 28 R0S7 I6.2 23 R0S02 R09 INTERCONNECT H03 SOLKOR TRIP S010-28 Y1 232 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-40 I6.3 29 R0S7 I6.3 24 R0S02 R09 INTERCONNECT H03 OVERLOAD ALARM S010-29 Y1 231 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-42 I6.4 30 R0S7 I6.4 25 R0S02 R09 INTERCONNECT H03 PILOT WIRE ALARM S010-30 Y1 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-44 I6.5 31 R0S7 I6.5 26 R0S02 - SPARE S010-31 Y1 - - - - - - - - - - - - - - - - - - - - - - -
DI-46 I6.6 32 R0S7 I6.6 27 R0S02 R09 RING MAIN H07 CONTROL SELECTOR SWITCH S010-34 Y1 69 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-48 I6.7 33 R0S7 I6.7 28 R0S02 R09 RING MAIN H07 O/C EARTH FAULT TRIP S010-35 Y1 242 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S7 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S7 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S7 I7.0 31 R0S02 R09 RING MAIN H07 SOLKOR TRIP S010-36 Y1 241 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-52 I7.1 38 R0S7 I7.1 32 R0S02 R09 RING MAIN H07 OVERLOAD ALARM S010-37 Y1 240 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-54 I7.2 39 R0S7 I7.2 33 R0S02 R09 RING MAIN H07 PILOT WIRE ALARM S010-38 Y1 ? - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-56 I7.3 40 R0S7 I7.3 34 R0S02 R09 AUTO CHANGEOVER PANEL INHIBIT ALARM S010-39 Y1 201 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-58 I7.4 41 R0S7 I7.4 35 R0S02 R09 BUS SECTION H06 CONTROL SELECTOR SWITCH S010-42 Y1 49 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-60 I7.5 42 R0S7 I7.5 36 R0S02 R09 BUS SECTION H06 O/C EARTH FAULT TRIP S010-43 Y1 248 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-62 I7.6 43 R0S7 I7.6 37 R0S02 R09 RING MAIN H08 CONTROL SELECTOR SWITCH S010-48 Y1 183 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-64 I7.7 44 R0S7 I7.7 38 R0S02 R09 RING MAIN H08 O/C EARTH FAULT TRIP S011-2 Y1 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S7 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S7 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R09 RING MAIN H08 SOLKOR TRIP S011-3 Y1 238 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R09 RING MAIN H08 OVERLOAD ALARM S011-4 Y1 237 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R09 RING MAIN H08 PILOT WIRE ALARM S011-5 Y1 ? - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R09 RING MAIN H08 TRIP CCT SUPERVISION ALARM S011-6 Y1 ? - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R09 AUTO CHANGEOVER PANEL ENABLE SELECTOR SWITCH S011-7 Y1 217 - SB ACO OFF (Disable) ON (Enable) - - - - - NO 0 - - - - - - - - - NC NC
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R09 AUTO CHANGEOVER PANEL STATUS S011-8 Y1 218 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R09 RECTIFIER FEEDER H04 CONTROL SELECTOR SWITCH S011-11 Y1 12 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R09 RECTIFIER FEEDER H04 O/C EARTH FAULT TRIP S011-12 Y1 229 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R09 RECTIFIER FEEDER H04 OVERLOAD TRIP S011-13 Y1 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R09 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S011-14 Y1 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R09 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-2 Y 214 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R09 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S011-15 Y1 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R09 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-3 Y 213 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R09 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-4 Y 212 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R09 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-5 Y 211 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R09 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-6 Y 210 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R09 RECTIFIER 1 FRAME EARTH TRIP S005-7 Y 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R09 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-8 Y 208 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R09 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-9 Y 207 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R09 RECTIFIER 1 DIODE OVER TEMP ALARM S005-10 Y 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R09 RECTIFIER 1 DIODE OVER TEMP TRIP S005-11 Y 205 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R09 RECTIFIER 1 REVERSE CURRENT TRIP S005-12 Y 204 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R09 RECTIFIER 1 SURGE ARRESTOR TRIP S011-16 Y1 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R09 RECTIFIER 1 FILTER CIRCUIT ALARM S005-13 Y 203 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R09 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-14 Y 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 - SPARE S005-15 Y - - - - - - - - - - - - - - - - - - - - - - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R09 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S005-18 Y 2 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 - SPARE S005-19 Y - - - - - - - - - - - - - - - - - - - - - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R09 RECTIFIER FEEDER H09 CONTROL SELECTOR SWITCH S011-19 Y1 189 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R09 RECTIFIER FEEDER H09 O/C EARTH FAULT TRIP S011-20 Y1 84 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R09 RECTIFIER FEEDER H09 OVERLOAD TRIP S011-21 Y1 83 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R09 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S011-22 Y1 82 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R09 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S005-20 Y 251 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R09 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S011-23 Y1 81 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R09 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S005-21 Y 250 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R09 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S005-22 Y 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R09 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S005-23 Y 248 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 R09 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S005-24 Y 247 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R09 RECTIFIER 2 FRAME EARTH TRIP S005-25 Y 246 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R09 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S005-26 Y 245 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R09 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S005-27 Y 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R09 RECTIFIER 2 DIODE OVER TEMP ALARM S005-28 Y 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R09 RECTIFIER 2 DIODE OVER TEMP TRIP S005-29 Y 242 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 R09 RECTIFIER 2 REVERSE CURRENT TRIP S005-30 Y 241 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C

Unrestricted 749775924.xlsx/RS09 [RS09] 95 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. Delay
(+ve) (-ve) LL L
No. No. (sec)

DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R09 RECTIFIER 2 SURGE ARRESTOR TRIP S011-24 Y1 80 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R09 RECTIFIER 2 FILTER CIRCUIT ALARM S005-31 Y 240 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R09 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S005-32 Y 239 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 - SPARE S005-33 Y - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS09 [RS09] 96 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. Delay
(+ve) (-ve) LL L
No. No. (sec)

UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -


UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R09 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S005-36 Y 7 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S005-37 Y - - - - - - - - - - - - - - - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R09 AUXILIARY TRANSFORMER 11KV SWITCH H10 S011-25 Y1 192 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - - NC NC
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 - SPARE S011-26 Y1 193 - - - - - - - - - - - - - - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R09 AUXILIARY TRANSFORMER 11KV SW H10 FUSE BLOWN TRIP S011-27 Y1 79 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R09 AUXILIARY TRANSFORMER TEMP HIGH ALARM S011-28 Y1 78 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R09 TRACK FEEDER D21 CONTROL SELECTOR SWITCH S005-40 Y 14 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R09 TRACK FEEDER D21 INSTANT OVERCURRENT S005-41 Y 228 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R09 TRACK FEEDER D21 RATE OF RISE TRIP S005-42 Y 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R09 TRACK FEEDER D21 LINE TESTING S005-43 Y 10 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R09 TRACK FEEDER D21 LINE IMPEDANCE LOW S005-44 Y 226 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 - SPARE S005-45 Y - - - - - - - - - - - - - - - - - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R09 TRACK FEEDER D22 CONTROL SELECTOR SWITCH S005-48 Y 23 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R09 TRACK FEEDER D22 INSTANT OVERCURRENT S006-2 Y 234 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R09 TRACK FEEDER D22 RATE OF RISE TRIP S006-3 Y 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R09 TRACK FEEDER D22 LINE TESTING S006-4 Y 19 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R09 TRACK FEEDER D22 LINE IMPEDANCE LOW S006-5 Y 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 - SPARE S006-6 Y - - - - - - - - - - - - - - - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R09 TRACK FEEDER D23 CONTROL SELECTOR SWITCH S006-9 Y 32 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R09 TRACK FEEDER D23 INSTANT OVERCURRENT S006-10 Y 231 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R09 TRACK FEEDER D23 RATE OF RISE TRIP S006-11 Y 230 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R09 TRACK FEEDER D23 LINE TESTING S006-12 Y 28 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R09 TRACK FEEDER D23 LINE IMPEDANCE LOW S006-13 Y 229 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 - SPARE S006-14 Y - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R09 TRACK FEEDER D24 CONTROL SELECTOR SWITCH S006-17 Y 41 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R09 TRACK FEEDER D24 INSTANT OVERCURRENT S006-18 Y 237 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R09 TRACK FEEDER D24 RATE OF RISE TRIP S006-19 Y 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R09 TRACK FEEDER D24 LINE TESTING S006-20 Y 37 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R09 TRACK FEEDER D24 LINE IMPEDANCE LOW S006-21 Y 235 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R09 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring Y - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R09 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S006-25 Y 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R09 AC/DC SYSTEM MAINS FAILED ALARM S006-26 Y 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R09 AC/DC SYSTEM 380V FEEDER MCB S006-27 Y 223 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - - - - NC C
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R09 AC/DC SYSTEM AC EARTH FAULT TRIP S006-28 Y 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R09 AC/DC SYSTEM BATTERY CHARGER S006-29 Y 221 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - - - NC C
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R09 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S006-30 Y 220 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R09 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S006-31 Y 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R09 AC/DC SYSTEM 11KV CONTROL VOLTAGE S006-32 Y 218 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R09 AC/DC SYSTEM 750V CONTROL VOLTAGE S006-33 Y 217 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R09 AC/DC SYSTEM 110V DC COMMON FEEDER S006-34 Y 216 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R09 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S006-35 Y 215 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R09 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S011-45 Y1 358 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R09 COMMON EQUIPMENT FIRE PROTECTION ALARM S011-46 Y1 359 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R09 COMMON EQUIPMENT INTRUDER ALARM S011-47 Y1 360 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R09 750V DCCB TRIP CCT SUPERVISION ALARM S006-37 Y 200 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R09 MAIN INCOMER H05 AC ENERGY (PULSE) S011-32 Y1 24 108 PI - - - - - - - kWh NO - - - - - - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 - SPARE S006-14 Y - - - - - - - - - - - - - - - - - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 - SPARE S006-14 Y - - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS09 [RS09] 97 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. Delay
(+ve) (-ve) LL L
No. No. (sec)

ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R0S06 R09 MAIN INCOMER H05 VCB OPENED S010-2 Y1 30 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-260 I20.1 5 R0S11 I20.1 2 R0S06 R09 MAIN INCOMER H05 VCB CLOSED S010-3 Y1 31 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-262 I20.2 6 R0S11 I20.2 3 R0S06 R09 RING MAIN H01 VCB OPENED S010-8 Y1 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-264 I20.3 7 R0S11 I20.3 4 R0S06 R09 RING MAIN H01 VCB CLOSED S010-9 Y1 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-266 I20.4 8 R0S11 I20.4 5 R0S06 R09 RING MAIN H02 VCB OPENED S010-16 Y1 18 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-268 I20.5 9 R0S11 I20.5 6 R0S06 R09 RING MAIN H02 VCB CLOSED S010-17 Y1 19 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-270 I20.6 10 R0S11 I20.6 7 R0S06 R09 INTERCONNECT H03 VCB OPENED S010-24 Y1 35 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-272 I20.7 11 R0S11 I20.7 8 R0S06 R09 INTERCONNECT H03 VCB CLOSED S010-25 Y1 36 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM0 UM0 12 R0S11 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R0S06 R09 RING MAIN H07 VCB OPENED S010-32 Y1 67 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-276 I21.1 16 R0S11 I21.1 12 R0S06 R09 RING MAIN H07 VCB CLOSED S010-33 Y1 68 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-278 I21.2 17 R0S11 I21.2 13 R0S06 R09 BUS SECTION H06 VCB OPENED S010-40 Y1 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-280 I21.3 18 R0S11 I21.3 14 R0S06 R09 BUS SECTION H06 VCB CLOSED S010-41 Y1 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-282 I21.4 19 R0S11 I21.4 15 R0S06 R09 DUMMY CB VCB OPENED internal wiring Y1 - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - - C NC
DI-284 I21.5 20 R0S11 I21.5 16 R0S06 R09 DUMMY CB VCB CLOSED internal wiring Y1 - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - - - -
DI-286 I21.6 21 R0S11 I21.6 17 R0S06 R09 RING MAIN H08 VCB OPENED S010-46 Y1 181 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-288 I21.7 22 R0S11 I21.7 18 R0S06 R09 RING MAIN H08 VCB CLOSED S010-47 Y1 182 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM1 UM1 23 R0S11 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S11 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R0S06 R09 RECTIFIER FEEDER H04 VCB OPENED S011-9 Y1 10 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-292 I22.1 27 R0S11 I22.1 22 R0S06 R09 RECTIFIER FEEDER H04 VCB CLOSED S011-10 Y1 11 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-294 I22.2 28 R0S11 I22.2 23 R0S06 R09 RECTIFIER FEEDER D1 DCCB OPENED S005-16 Y 4 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-296 I22.3 29 R0S11 I22.3 24 R0S06 R09 RECTIFIER FEEDER D1 DCCB CLOSED S005-17 Y 3 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-298 I22.4 30 R0S11 I22.4 25 R0S06 R09 RECTIFIER FEEDER H09 VCB OPENED S011-17 Y1 187 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-300 I22.5 31 R0S11 I22.5 26 R0S06 R09 RECTIFIER FEEDER H09 VCB CLOSED S011-18 Y1 188 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-302 I22.6 32 R0S11 I22.6 27 R0S06 R09 RECTIFIER FEEDER D2 DCCB OPENED S005-34 Y 6 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-304 I22.7 33 R0S11 I22.7 28 R0S06 R09 RECTIFIER FEEDER D2 DCCB CLOSED S005-35 Y 5 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM2 UM2 34 R0S11 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R0S06 R09 TRACK FEEDER D21 DCCB OPENED S005-38 Y 8 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-308 I23.1 38 R0S11 I23.1 32 R0S06 R09 TRACK FEEDER D21 DCCB CLOSED S005-39 Y 9 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-310 I23.2 39 R0S11 I23.2 33 R0S06 R09 TRACK FEEDER D22 DCCB OPENED S005-46 Y 17 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-312 I23.3 40 R0S11 I23.3 34 R0S06 R09 TRACK FEEDER D22 DCCB CLOSED S005-47 Y 18 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-314 I23.4 41 R0S11 I23.4 35 R0S06 R09 TRACK FEEDER D23 DCCB OPENED S006-7 Y 26 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-316 I23.5 42 R0S11 I23.5 36 R0S06 R09 TRACK FEEDER D23 DCCB CLOSED S006-8 Y 27 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-318 I23.6 43 R0S11 I23.6 37 R0S06 R09 TRACK FEEDER D24 DCCB OPENED S006-15 Y 35 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-320 I23.7 44 R0S11 I23.7 38 R0S06 R09 TRACK FEEDER D24 DCCB CLOSED S006-16 Y 36 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM3 UM3 45 R0S11 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S11 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-322 I24.0 4 R0S12 I24.0 1 R0S07 R09 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S006-23 Y 45 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-324 I24.1 5 R0S12 I24.1 2 R0S07 R09 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S006-24 Y 44 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-326 I24.2 6 R0S12 I24.2 3 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-328 I24.3 7 R0S12 I24.3 4 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-330 I24.4 8 R0S12 I24.4 5 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-332 I24.5 9 R0S12 I24.5 6 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-334 I24.6 10 R0S12 I24.6 7 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-336 I24.7 11 R0S12 I24.7 8 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S12 - 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S12 - 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-338 I25.0 15 R0S12 I25.0 11 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-340 I25.1 16 R0S12 I25.1 12 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-342 I25.2 17 R0S12 I25.2 13 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-344 I25.3 18 R0S12 I25.3 14 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-346 I25.4 19 R0S12 I25.4 15 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-348 I25.5 20 R0S12 I25.5 16 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-350 I25.6 21 R0S12 I25.6 17 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-352 I25.7 22 R0S12 I25.7 18 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S12 1L+ 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S12 1M 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-354 I26.0 26 R0S12 I26.0 21 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-356 I26.1 27 R0S12 I26.1 22 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-358 I26.2 28 R0S12 I26.2 23 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-360 I26.3 29 R0S12 I26.3 24 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-362 I26.4 30 R0S12 I26.4 25 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-364 I26.5 31 R0S12 I26.5 26 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-366 I26.6 32 R0S12 I26.6 27 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-368 I26.7 33 R0S12 I26.7 28 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S12 - 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S12 - 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-370 I27.0 37 R0S12 I27.0 31 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-372 I27.1 38 R0S12 I27.1 32 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-374 I27.2 39 R0S12 I27.2 33 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-376 I27.3 40 R0S12 I27.3 34 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-378 I27.4 41 R0S12 I27.4 35 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-380 I27.5 42 R0S12 I27.5 36 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-382 I27.6 43 R0S12 I27.6 37 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-384 I27.7 44 R0S12 I27.7 38 R0S07 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S12 2L+ 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S12 2M 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS09 [RS09] 98 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. Delay
(+ve) (-ve) LL L
No. No. (sec)

ZS1 ZS1 1 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S15 IW.256 1 R1S06 R09 MAIN INCOMER H05 POWER FACTOR S013-1 Y1 341 - AI - - - - - -10 to +10 cos(60d to cos(60d - - - 1.0% 0.7 0.8 0.65 0.75 5.00% 5.00% 0.75 0.85
eg) eg)
TB2-1 (-) IW.256 5 R0S15 IW.256 21 R1S06 - - S013-2 Y1 - 424 - - - - - - to - -
lagging to -
leading - - - - 49.458 41.410 8.243 6.902 42.69278389 32.85988038 7.115 5.477
TB2-2 (+) IW.258 6 R0S15 IW.258 2 R1S06 R09 MAIN INCOMER H05 CURRENT S013-3 Y1 338 - AI - - - - - 0 to +10 0 to 2000 A ac - - 1.0% - - 1500 1800 5.00% 5.00% 5.00% 5.00% C NC
TB2-2 (-) IW.258 7 R0S15 IW.258 22 R1S06 - - S013-4 Y1 - 421 - - - - - - to - - to - - - - - - - 7.500 9.000 - - 1425 1710 - -
TB2-3 (+) IW.260 8 R0S15 IW.260 3 R1S06 R09 MAIN INCOMER H05 VOLTAGE S013-5 Y1 339 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC
TB2-3 (-) IW.260 9 R0S15 IW.260 23 R1S06 - - S013-6 Y1 - 422 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.950 10.395 11.495 11.78 0.840 8.316
TB2-4 (+) IW.262 10 R0S15 IW.262 4 R1S06 R09 MAIN INCOMER H05 POWER S013-7 Y1 340 - AI - - - - - 0 to +10 0 to 50 MW - - 1.0% - - - - 5.00% 5.00% 5.00% 5.00% C NC
TB2-4 (-) IW.262 11 R0S15 IW.262 24 R1S06 - - S013-8 Y1 - 423 - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-5 (+) IW.264 15 R0S15 IW.264 5 R1S06 R09 TRACK FEEDER D21 DC CURRENT S008-1 Y 340 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2800 2800 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-5 (-) IW.264 16 R0S15 IW.264 25 R1S06 - - S008-2 Y - 423 - - - - - - to - - to - - - - - -8.571 -8.000 8.000 8.571 -2850 -2660 2660 2850 -8.143 6.780
TB2-6 (+) IW.266 17 R0S15 IW.266 6 R1S06 R09 RING MAIN H02 CURRENT S013-9 Y1 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-6 (-) IW.266 18 R0S15 IW.266 26 R1S06 - - S013-10 Y1 - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-7 (+) IW.268 19 R0S15 IW.268 7 R1S06 R09 INTERCONNECT H03 CURRENT S013-11 Y1 345 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-7 (-) IW.268 20 R0S15 IW.268 27 R1S06 - - S013-12 Y1 - 428 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-8 (+) IW.270 21 R0S15 IW.270 8 R1S06 R09 RING MAIN H07 CURRENT S013-13 Y1 346 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-8 (-) IW.270 22 R0S15 IW.270 28 R1S06 - - S013-14 Y1 - 429 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-9 (+) IW.272 26 R0S15 IW.272 9 R1S06 R09 TRACK FEEDER D22 DC CURRENT S008-3 Y 341 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 2800 2800 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-9 (-) IW.272 27 R0S15 IW.272 29 R1S06 - - S008-4 Y - 424 - - - - - - to - - to - - - - - -8.571 8.000 8.000 8.571 -2850 2940 2660 2850 -8.143 6.780
TB2-10 (+) IW.274 28 R0S15 IW.274 10 R1S06 R09 RING MAIN H01 CURRENT S013-15 Y1 335 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-10 (-) IW.274 29 R0S15 IW.274 30 R1S06 - - S013-16 Y1 - 418 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-11 (+) IW.276 30 R0S15 IW.276 11 R1S06 R09 RING MAIN H08 CURRENT S013-27 Y1 350 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-11 (-) IW.276 31 R0S15 IW.276 31 R1S06 - - S013-28 Y1 - 433 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-12 (+) IW.278 32 R0S15 IW.278 12 R1S06 R09 DC BUSBAR DC VOLTAGE S008-5 Y 344 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-12 (-) IW.278 33 R0S15 IW.278 32 R1S06 - - S008-6 Y - 427 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500 902.5 931 4.400 5.565
TB2-13 (+) IW.280 37 R0S15 IW.280 13 R1S06 R09 TRACK FEEDER D23 DC CURRENT S008-9 Y 342 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-13 (-) IW.280 38 R0S15 IW.280 33 R1S06 - - S008-10 Y - 425 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2660 2850 -8.143 -6.786
TB2-14 (+) IW.282 39 R0S15 IW.282 14 R1S06 R09 AC BUSBAR CURRENT S013-17 Y1 342 - AI - - - - - 0 to +10 0 to 2000 A ac - - 1.0% - - - - 5.00% 5.00% 5.00% 5.00% C NC
TB2-14 (-) IW.282 40 R0S15 IW.282 34 R1S06 - - S013-18 Y1 - 425 - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-15 (+) IW.284 41 R0S15 IW.284 15 R1S06 R09 AC BUSBAR LHS VOLTAGE S013-19 Y1 343 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC
TB2-15 (-) IW.284 42 R0S15 IW.284 35 R1S06 - - S013-20 Y1 - 426 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.950 10.395 11.495 11.78 0.840 8.316
TB2-16 (+) IW.286 43 R0S15 IW.286 16 R1S06 R09 AC BUSBAR RHS VOLTAGE S013-21 Y1 344 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 0.05 0.05 0.05 0.05 C NC
TB2-16 (-) IW.286 44 R0S15 IW.286 36 R1S06 - - S013-22 Y1 - 427 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.95 10.395 11.495 11.78 0.840 8.316
ZS1 ZS1 1 R0S16 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S16 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
TB2-17 (+) IW.288 4 R0S16 IW.288 1 R1S07 R09 TRACK FEEDER D24 DC CURRENT S008-11 Y 343 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-17 (+) IW.288 5 R0S16 IW.288 21 R1S07 - - S008-12 Y - 426 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2660 2850 -8.143 -6.786
TB2-18 (+) IW.290 6 R0S16 IW.290 2 R1S07 R09 RECTIFIER FEEDER H04 CURRENT S013-23 Y1 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC
TB2-18 (-) IW.290 7 R0S16 IW.290 22 R1S07 - - S013-24 Y1 - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - -
TB2-19 (+) IW.292 8 R0S16 IW.292 3 R1S07 R09 RECTIFIER UNIT 1 DC CURRENT S008-13 Y 335 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-19 (-) IW.292 9 R0S16 IW.292 23 R1S07 - - S008-14 Y - 418 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - -
TB2-20 (+) IW.294 10 R0S16 IW.294 4 R1S07 R09 RECTIFIER UNIT 1 DC VOLTAGE S008-15 Y 336 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-20 (-) IW.294 11 R0S16 IW.294 24 R1S07 - - S008-16 Y - 419 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.500 931.000 - -
TB2-21 (+) IW.296 15 R0S16 IW.296 5 R1S07 - SPARE - Y - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-21 (-) IW.296 16 R0S16 IW.296 25 R1S07 - - - Y - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-22 (+) IW.298 17 R0S16 IW.298 6 R1S07 R09 RECTIFIER FEEDER H09 CURRENT S013-25 Y1 349 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC
TB2-22 (-) IW.298 18 R0S16 IW.298 26 R1S07 - - S013-26 Y1 - 432 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - -
TB2-23 (+) IW.300 19 R0S16 IW.300 7 R1S07 R09 RECTIFIER UNIT 2 DC CURRENT S008-17 Y 337 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-23 (-) IW.300 20 R0S16 IW.300 27 R1S07 - - S008-18 Y - 420 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - -
TB2-24 (+) IW.302 21 R0S16 IW.302 8 R1S07 R09 RECTIFIER UNIT 2 DC VOLTAGE S008-19 Y 338 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-24 (-) IW.302 22 R0S16 IW.302 28 R1S07 - - S008-20 Y - 421 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 - -
TB2-25 (+) IW.304 26 R0S16 IW.304 9 R1S07 - SPARE - Y - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-25 (-) IW.304 27 R0S16 IW.304 29 R1S07 - - - Y - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-26 (+) IW.306 28 R0S16 IW.306 10 R1S07 R09 NEGATIVE DC BUSBAR DC RETURN CURRENT S008-21 Y 339 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC
TB2-26 (-) IW.306 29 R0S16 IW.306 30 R1S07 - - S008-22 Y - 422 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800 - -
TB2-27 (+) IW.308 30 R0S16 IW.308 11 R1S07 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-27 (-) IW.308 31 R0S16 IW.308 31 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-28 (+) IW.310 32 R0S16 IW.310 12 R1S07 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-28 (-) IW.310 33 R0S16 IW.310 32 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-29 (+) IW.312 37 R0S16 IW.312 13 R1S07 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-29 (-) IW.312 38 R0S16 IW.312 33 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-30 (+) IW.314 39 R0S16 IW.314 14 R1S07 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-30 (-) IW.314 40 R0S16 IW.314 34 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-31 (+) IW.316 41 R0S16 IW.316 15 R1S07 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-31 (-) IW.316 42 R0S16 IW.316 35 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-32 (+) IW.318 43 R0S16 IW.318 16 R1S07 - SPARE - - - - - - - - - - to - - to - - - -
TB2-32 (-) IW.318 44 R0S16 IW.318 36 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
S110-RD - - R0S16 - - - - - S013-68 Y1 405 - - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S16 - - - - - S013-69 Y1 - 488 - - - - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S16 - - - - - S013-70 Y1 - 488 - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS09 [RS09] 99 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. Delay
(+ve) (-ve) LL L
No. No. (sec)

RL-A - - R0S16 - - - - - S012-1 Y1 - - - - - - - - - - - - - - - - - - - - - - - -


ZS1 ZS1 1 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S13 Q4.0 2 R1S02 R09 MAIN INCOMER H05 VCB OPEN S012-2 Y1 34 - CO - - - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S13 Q4.1 3 R1S02 R09 MAIN INCOMER H05 VCB CLOSE S012-3 Y1 33 - CO - - - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S13 Q4.2 6 R1S02 R09 RING MAIN H01 VCB OPEN S012-4 Y1 7 - CO - - - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S13 Q4.3 7 R1S02 R09 RING MAIN H01 VCB CLOSE S012-5 Y1 6 - CO - - - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S13 Q4.4 12 R1S02 R09 RING MAIN H02 VCB OPEN S012-6 Y1 22 - CO - - - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S13 Q4.5 13 R1S02 R09 RING MAIN H02 VCB CLOSE S012-7 Y1 21 - CO - - - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S13 Q4.6 16 R1S02 R09 INTERCONNECT H03 VCB OPEN S012-8 Y1 39 - CO - - - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S13 Q4.7 17 R1S02 R09 INTERCONNECT H03 VCB CLOSE S012-9 Y1 38 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02
LM 20 R1S02
RL-09 Q5.0 15 R0S13 Q5.0 22 R1S02 R09 RING MAIN H07 VCB OPEN S012-10 Y1 71 - CO - - - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S13 Q5.1 23 R1S02 R09 RING MAIN H07 VCB CLOSE S012-11 Y1 70 - CO - - - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S13 Q5.2 26 R1S02 R09 BUS SECTION H06 VCB OPEN S012-12 Y1 50 - CO - - - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S13 Q5.3 27 R1S02 R09 BUS SECTION H06 VCB CLOSE S012-13 Y1 51 - CO - - - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S13 Q5.4 32 R1S02 R09 RING MAIN H08 VCB OPEN S012-14 Y1 185 - CO - - - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S13 Q5.5 33 R1S02 R09 RING MAIN H08 VCB CLOSE S012-15 Y1 184 - CO - - - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S13 Q5.6 36 R1S02 R09 RECTIFIER FEEDER H04 VCB OPEN S012-16 Y1 14 - CO - - - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S13 Q5.7 37 R1S02 R09 RECTIFIER FEEDER H04 VCB CLOSE S012-17 Y1 13 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02
LM 40 R1S02
RL-17 Q6.0 26 R0S13 Q6.0 2 R1S03 R09 RECTIFIER FEEDER D1 DCCB OPEN S007-2 Y 396 - CO - - - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S13 Q6.1 3 R1S03 R09 RECTIFIER FEEDER D1 DCCB CLOSE S007-3 Y 395 - CO - - - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S13 Q6.2 6 R1S03 R09 RECTIFIER FEEDER H09 VCB OPEN S012-18 Y1 190 - CO - - - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S13 Q6.3 7 R1S03 R09 RECTIFIER FEEDER H09 VCB CLOSE S012-19 Y1 191 - CO - - - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S13 Q6.4 12 R1S03 R09 RECTIFIER FEEDER D2 DCCB OPEN S007-4 Y 398 - CO - - - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S13 Q6.5 13 R1S03 R09 RECTIFIER FEEDER D2 DCCB CLOSE S007-5 Y 397 - CO - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S13 Q6.6 16 R1S03 R09 TRACK FEEDER D21 DCCB OPEN S007-6 Y 15 - CO - - - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S13 Q6.7 17 R1S03 R09 TRACK FEEDER D21 DCCB CLOSE S007-7 Y 16 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S03
LM 20 R1S03
RL-25 Q7.0 37 R0S13 Q7.0 22 R1S03 R09 TRACK FEEDER D22 DCCB OPEN S007-8 Y 24 - CO - - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S13 Q7.1 23 R1S03 R09 TRACK FEEDER D22 DCCB CLOSE S007-9 Y 25 - CO - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S13 Q7.2 26 R1S03 R09 TRACK FEEDER D23 DCCB OPEN S007-10 Y 33 - CO - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S13 Q7.3 27 R1S03 R09 TRACK FEEDER D23 DCCB CLOSE S007-11 Y 34 - CO - - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S13 Q7.4 32 R1S03 R09 TRACK FEEDER D24 DCCB OPEN S007-12 Y 42 - CO - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S13 Q7.5 33 R1S03 R09 TRACK FEEDER D24 DCCB CLOSE S007-13 Y 43 - CO - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S13 Q7.6 36 R1S03 R09 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S007-14 Y 56 - CO - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S13 Q7.7 37 R1S03 - SPARE S007-15 Y - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S03
LM 40 R1S03
FR0 FR0 34 R0S13 - - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ONAND
THECOMMON
32 CO
FR1 FR1 35 R0S13 - - - - ENABLE CONTACT RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 R0S13 - - - - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S13 - - - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-33 Q8.0 4 R0S14 Q8.0 2 R1S04 - SPARE S007-16 Y - - - - - - - - - - - - - - - - - - - - - - -
RL-34 Q8.1 5 R0S14 Q8.1 3 R1S04 - SPARE S007-17 Y - - - - - - - - - - - - - - - - - - - - - - -
RL-35 Q8.2 6 R0S14 Q8.2 6 R1S04 - SPARE S007-18 Y - - - - - - - - - - - - - - - - - - - - - - -
RL-36 Q8.3 7 R0S14 Q8.3 7 R1S04 - SPARE S007-19 Y - - - - - - - - - - - - - - - - - - - - - - -
RL-37 Q8.4 8 R0S14 Q8.4 12 R1S04 - SPARE S012-20 Y1 - - - - - - - - - - - - - - - - - - - - - - -
RL-38 Q8.5 9 R0S14 Q8.5 13 R1S04 R09 AUTO CHANGEOVER PANEL ACO RESET INHIBIT CONTROL S012-21 Y1 203 - CO - - - - - - - - - - - - - - - - - - - - -
RL-39 Q8.6 10 R0S14 Q8.6 16 R1S04 R09 AUTO CHANGEOVER PANEL CONTROL (ACO CONTROL OFF) S012-22 Y1 220 - CO - - - - - - - - - - - - - - - - - - - - -
RL-40 Q8.7 11 R0S14 Q8.7 17 R1S04 R09 AUTO CHANGEOVER PANEL ENABLE (ACO CONTROL ON) S012-23 Y1 219 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S04
LM 20 R1S04
RL-41 Q9.0 15 R0S14 Q9.0 22 R1S04 R09 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - -
RL-42 Q9.1 16 R0S14 Q9.1 23 R1S04 R09 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - -
RL-43 Q9.2 17 R0S14 Q9.2 26 R1S04 - BIT) SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-44 Q9.3 18 R0S14 Q9.3 27 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-45 Q9.4 19 R0S14 Q9.4 32 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-46 Q9.5 20 R0S14 Q9.5 33 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-47 Q9.6 21 R0S14 Q9.6 36 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-48 Q9.7 22 R0S14 Q9.7 37 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S04
LM 40 R1S04
RL-49 Q10.0 26 R0S14 Q10.0 2 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-50 Q10.1 27 R0S14 Q10.1 3 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-51 Q10.2 28 R0S14 Q10.2 6 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-52 Q10.3 29 R0S14 Q10.3 7 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-53 Q10.4 30 R0S14 Q10.4 12 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-54 Q10.5 31 R0S14 Q10.5 13 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-55 Q10.6 32 R0S14 Q10.6 16 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-56 Q10.7 33 R0S14 Q10.7 17 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S05
LM 20 R1S05
RL-57 Q11.0 37 R0S14 Q11.0 22 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-58 Q11.1 38 R0S14 Q11.1 23 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-59 Q11.2 39 R0S14 Q11.2 26 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-60 Q11.3 40 R0S14 Q11.3 27 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-61 Q11.4 41 R0S14 Q11.4 32 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-62 Q11.5 42 R0S14 Q11.5 33 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-63 Q11.6 43 R0S14 Q11.6 36 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-64 Q11.7 44 R0S14 Q11.7 37 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S05
LM 40 R1S05
FR0 FR0 34 R0S14 - - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
FR1 FR1 35 R0S14 - - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 R0S14 - - - - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S14 - - - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS09 [RS09] 100 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS09 [RS09] 101 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS09 [RS09] 102 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS09 [RS09] 103 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
- -
- -
NC C
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS09 [RS09] 104 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
#VALUE! #VALUE!
NC C
7.125 8.550
NC C
9.196 9.424
NC C
- -
NC C
7.150 8.143
NC C
7.125 9.025
NC C
7.125 9.025
NC C
7.125 9.025
NC C
7.150 8.143
NC C
7.125 9.025
NC C
7.125 9.025
NC C
9.025 9.310
NC C
7.150 8.143
NC C
- -
NC C
9.196 9.424
NC C
9.196 9.424
- -
- -
NC C
7.150 8.143
NC C
6.333 7.521
NC C
4.524 5.429
NC C
9.025 9.310
- -
- -
NC C
6.333 7.521
NC C
4.524 5.429
NC C
9.025 9.310
- -
- -
NC C
6.333 7.238
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS09 [RS09] 105 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS09 [RS09] 106 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Prio
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL
No. No. (sec)

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R10 RING MAIN H03 CONTROL SELECTOR SWITCH S005-4 - 13 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R10 RING MAIN H03 O/C EARTH FAULT TRIP S005-5 - 363 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R10 RING MAIN H03 SOLKOR TRIP S005-6 - 364 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R10 RING MAIN H03 PILOT WIRE ALARM S005-7 - 350 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R10 RING MAIN H03 OVERLOAD ALARM S005-8 - 365 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 - SPARE S005-9 - - - - - - - - - - - - - - - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R10 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-12 - 6 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R10 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-13 - 207 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R10 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-14 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R10 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-15 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R10 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-16 - 210 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 R10 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-17 - 211 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 R10 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-18 - 212 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 R10 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-19 - 213 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R10 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-20 - 214 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R10 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-21 - 215 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R10 RECTIFIER 1 FRAME EARTH TRIP S005-22 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R10 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-23 - 217 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R10 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-24 - 218 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R10 RECTIFIER 1 DIODE OVER TEMP ALARM S005-25 - 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R10 RECTIFIER 1 DIODE OVER TEMP TRIP S005-26 - 220 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R10 RECTIFIER 1 REVERSE CURRENT TRIP S005-27 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R10 RECTIFIER 1 SURGE ARRESTOR TRIP S005-28 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R10 RECTIFIER 1 FILTER CIRCUIT ALARM S005-29 - 223 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R10 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-30 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 - SPARE S005-31 - - - - - - - - - - - - - - - - - - - - - - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R10 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S005-34 - 58 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 - SPARE S005-35 - - - - - - - - - - - - - - - - - - - - - - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R10 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S005-38 - 10 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R10 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S005-39 - 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R10 RECTIFIER FEEDER H02 OVERLOAD TRIP S005-40 - 226 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R10 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S005-41 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R10 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S005-42 - 228 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R10 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S005-43 - 229 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R10 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S005-44 - 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R10 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S005-45 - 231 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R10 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S005-46 - 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R10 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S005-47 - 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R10 RECTIFIER 2 FRAME EARTH TRIP S005-48 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R10 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-2 - 235 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R10 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-3 - 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R10 RECTIFIER 2 DIODE OVER TEMP ALARM S006-4 - 237 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R10 RECTIFIER 2 DIODE OVER TEMP TRIP S006-5 - 238 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R10 RECTIFIER 2 REVERSE CURRENT TRIP S006-6 - 239 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R10 RECTIFIER 2 SURGE ARRESTOR TRIP S006-7 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R10 RECTIFIER 2 FILTER CIRCUIT ALARM S006-8 - 241 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R10 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-9 - 242 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 - SPARE S006-10 - - - - - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R10 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-13 - 64 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 - SPARE S006-14 - - - - - - - - - - - - - - - - - - - - - - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R10 AUXILIARY TRANSFORMER 11KV SWITCH H4 S006-15 - 2 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - - NC
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 - SPARE S006-16 - 1 - - - - - - - - - - - - - - - - - - - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R10 AUXILIARY TRANSFORMER 11KV SW H4 FUSE BLOWN TRIP S006-17 - 243 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R10 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-18 - 244 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 - SPARE S006-19 - 353 - - - - - - - - - - - - - - - - - - - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R10 750V DCCB TRIP CCT SUPERVISION ALARM S006-20 - 371 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R10 TRACK FEEDER D23 CONTROL SELECTOR SWITCH S006-23 - 28 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R10 TRACK FEEDER D23 INSTANT OVERCURRENT S006-24 - 359 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R10 TRACK FEEDER D23 RATE OF RISE TRIP S006-25 - 360 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R10 TRACK FEEDER D23 LINE TESTING S006-26 - 29 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R10 TRACK FEEDER D23 LINE IMPEDANCE LOW S006-27 - 361 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 - SPARE S006-28 - - - - - - - - - - - - - - - - - - - - - - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R10 TRACK FEEDER D24 CONTROL SELECTOR SWITCH S006-31 - 36 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R10 TRACK FEEDER D24 INSTANT OVERCURRENT S006-32 - 248 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS10 [RS10] 107 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Prio
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL
No. No. (sec)

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R10 TRACK FEEDER D24 RATE OF RISE TRIP S006-33 - 249 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R10 TRACK FEEDER D24 LINE TESTING S006-34 - 37 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R10 TRACK FEEDER D24 LINE IMPEDANCE LOW S006-35 - 250 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 - SPARE S006-36 - - - - - - - - - - - - - - - - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R10 TRACK FEEDER D25 CONTROL SELECTOR SWITCH S006-39 - 44 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 R10 TRACK FEEDER D25 INSTANT OVERCURRENT S006-40 - 251 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R10 TRACK FEEDER D25 RATE OF RISE TRIP S006-41 - 357 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R10 TRACK FEEDER D25 LINE TESTING S006-42 - 45 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R10 TRACK FEEDER D25 LINE IMPEDANCE LOW S006-43 - 358 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 - SPARE S006-44 - - - - - - - - - - - - - - - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R10 TRACK FEEDER D26 CONTROL SELECTOR SWITCH S006-47 - 52 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 R10 TRACK FEEDER D26 INSTANT OVERCURRENT S006-48 - 245 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R10 TRACK FEEDER D26 RATE OF RISE TRIP S007-2 - 246 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R10 TRACK FEEDER D26 LINE TESTING S007-3 - 53 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R10 TRACK FEEDER D26 LINE IMPEDANCE LOW S007-4 - 247 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 - SPARE S007-5 - - - - - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R10 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-8 - 362 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 R10 AC/DC SYSTEM MAINS FAILED ALARM S007-9 - 198 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R10 AC/DC SYSTEM 380V FEEDER MCB S007-10 - 199 - SB MCB NORMAL OPEN - - - - - NO 0 - - - - - - - - - NC
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R10 AC/DC SYSTEM AC EARTH FAULT TRIP S007-11 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R10 AC/DC SYSTEM BATTERY CHARGER S007-12 - 201 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - - - NC
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R10 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S007-13 - 352 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R10 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S007-14 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R10 AC/DC SYSTEM 11KV CONTROL VOLTAGE S007-15 - 203 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R10 AC/DC SYSTEM 750V CONTROL VOLTAGE S007-16 - 204 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R10 AC/DC SYSTEM 110V DC COMMON FEEDER S007-17 - 205 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R10 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S007-18 - 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R10 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S007-19 - 391 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R10 COMMON EQUIPMENT FIRE PROTECTION ALARM S007-20 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R10 COMMON EQUIPMENT INTRUDER ALARM S007-21 - 393 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R10 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 - SPARE S007-23 - - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R10 RING MAIN H05 CONTROL SELECTOR SWITCH S005-20 new 5 6 SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R10 RING MAIN H05 O/C EARTH FAULT TRIP S005-21 new 13 14 SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R10 RING MAIN H05 SOLKOR TRIP S005-22 new 15 16 SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R10 RING MAIN H05 PILOT WIRE ALARM S005-23 new 11 12 SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R10 RING MAIN H05 OVERLOAD ALARM S005-24 new 17 18 SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 - SPARE S007-31 - - - - - - - - - - - - - - - - - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 - SPARE S007-32 - - - - - - - - - - - - - - - - - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 - SPARE S007-33 - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R10 RING MAIN H03 VCB OPENED S005-2 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R10 RING MAIN H03 VCB CLOSED S005-3 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R10 RECTIFIER FEEDER H01 VCB OPENED S005-10 - 3 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R10 RECTIFIER FEEDER H01 VCB CLOSED S005-11 - 4 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R10 RECTIFIER FEEDER D1 DCCB OPENED S005-32 - 59 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R10 RECTIFIER FEEDER D1 DCCB CLOSED S005-33 - 60 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R10 RECTIFIER FEEDER H02 VCB OPENED S005-36 - 7 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R10 RECTIFIER FEEDER H02 VCB CLOSED S005-37 - 8 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R10 RECTIFIER FEEDER D2 DCCB OPENED S006-11 - 65 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R10 RECTIFIER FEEDER D2 DCCB CLOSED S006-12 - 66 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R10 TRACK FEEDER D23 DCCB OPENED S006-21 - 23 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R10 TRACK FEEDER D23 DCCB CLOSED S006-22 - 24 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R10 TRACK FEEDER D24 DCCB OPENED S006-29 - 31 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R10 TRACK FEEDER D24 DCCB CLOSED S006-30 - 32 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R10 TRACK FEEDER D25 DCCB OPENED S006-37 - 39 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R10 TRACK FEEDER D25 DCCB CLOSED S006-38 - 40 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R10 TRACK FEEDER D26 DCCB OPENED S006-45 - 47 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R10 TRACK FEEDER D26 DCCB CLOSED S006-46 - 48 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R10 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S007-6 - 56 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R10 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S007-7 - 55 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R10 RING MAIN H05 VCB OPENED S005-18 new 1 2 DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R10 RING MAIN H05 VCB CLOSED S005-19 new 3 4 DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R10 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - - C
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R10 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS10 [RS10] 108 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Prio
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL
No. No. (sec)

ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S12 IW.256 1 R1S04 R10 TRACK FEEDER D23 DC CURRENT S009-1 - 344 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C
TB2-1 (-) IW.256 5 R0S12 IW.256 21 R1S04 - - S009-2 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143
TB2-2 (+) IW.258 6 R0S12 IW.258 2 R1S04 R10 RING MAIN H03 CURRENT S009-3 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C
TB2-2 (-) IW.258 7 R0S12 IW.258 22 R1S04 - - S009-4 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 -
TB2-3 (+) IW.260 8 R0S12 IW.260 3 R1S04 R10 AC BUSBAR VOLTAGE S009-5 - 349 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C
TB2-3 (-) IW.260 9 R0S12 IW.260 23 R1S04 - - S009-6 - - 432 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.950 10.395 11.495 11.78 0.760
TB2-4 (+) IW.262 10 R0S12 IW.262 4 R1S04 R10 DC BUSBAR DC VOLTAGE S009-7 - 348 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C
TB2-4 (-) IW.262 11 R0S12 IW.262 24 R1S04 - - S009-8 - - 431 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500 902.500 931.000 3.943
TB2-5 (+) IW.264 15 R0S12 IW.264 5 R1S04 R10 TRACK FEEDER D24 DC CURRENT S009-9 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C
TB2-5 (-) IW.264 16 R0S12 IW.264 25 R1S04 - - S009-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143
TB2-6 (+) IW.266 17 R0S12 IW.266 6 R1S04 R10 RECTIFIER FEEDER H01 CURRENT S009-11 - 335 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C
TB2-6 (-) IW.266 18 R0S12 IW.266 26 R1S04 - - S009-12 - - 418 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 -
TB2-7 (+) IW.268 19 R0S12 IW.268 7 R1S04 R10 RECTIFIER UNIT 1 DC CURRENT S009-13 - 339 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C
TB2-7 (-) IW.268 20 R0S12 IW.268 27 R1S04 - - S009-14 - - 422 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 -
TB2-8 (+) IW.270 21 R0S12 IW.270 8 R1S04 R10 RECTIFIER UNIT 1 DC VOLTAGE S009-15 - 340 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C
TB2-8 (-) IW.270 22 R0S12 IW.270 28 R1S04 - - S009-16 - - 423 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 -
TB2-9 (+) IW.272 26 R0S12 IW.272 9 R1S04 R10 TRACK FEEDER D25 DC CURRENT S009-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C
TB2-9 (-) IW.272 27 R0S12 IW.272 29 R1S04 - - S009-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143
TB2-10 (+) IW.274 28 R0S12 IW.274 10 R1S04 R10 RECTIFIER FEEDER H02 CURRENT S009-19 - 336 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C
TB2-10 (-) IW.274 29 R0S12 IW.274 30 R1S04 - - S009-20 - - 419 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 -
TB2-11 (+) IW.276 30 R0S12 IW.276 11 R1S04 R10 RECTIFIER UNIT 2 DC CURRENT S009-21 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C
TB2-11 (-) IW.276 31 R0S12 IW.276 31 R1S04 - - S009-22 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 -
TB2-12 (+) IW.278 32 R0S12 IW.278 12 R1S04 R10 RECTIFIER UNIT 2 DC VOLTAGE S009-23 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C
TB2-12 (-) IW.278 33 R0S12 IW.278 32 R1S04 - - S009-24 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 -
TB2-13 (+) IW.280 37 R0S12 IW.280 13 R1S04 R10 TRACK FEEDER D26 DC CURRENT S009-25 - 347 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C
TB2-13 (-) IW.280 38 R0S12 IW.280 33 R1S04 - - S009-26 - - 430 - - - - - - to - - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143
TB2-14 (+) IW.282 39 R0S12 IW.282 14 R1S04 R10 NEGATIVE DC BUSBAR DC RETURN CURRENT S009-27 - 343 - AI - - - - - 0 to +20 0 to 10500 V dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C
TB2-14 (-) IW.282 40 R0S12 IW.282 34 R1S04 - - S009-28 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800 -
TB2-15 (+) IW.284 41 R0S12 IW.284 15 R1S04 R10 RING MAIN H05 CURRENT S010-31 new 25 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C
TB2-15 (-) IW.284 42 R0S12 IW.284 35 R1S04 - - S010-32 new - 26 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 -
TB2-16 (+) IW.286 43 R0S12 IW.286 16 R1S04 - SPARE S009-31 - - - - - - - - - to - - to - - - - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S12 IW.286 36 R1S04 - - S009-32 - - - - - - - - - to - - to - - - - - - - - - - - - - -
S110-RD - - R0S12 - - - - - S009-70 - 405 - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S12 - - - - - S009-71 - - 488 - - - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S12 - - - - - S009-72 - - 488 - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS10 [RS10] 109 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Prio
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL
No. No. (sec)

RL-A - - R0S12 - - - - - S008-1 - - - - - - - - - - - - - - - - - - - - - - - -


- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
IW.288 1 R1S05 - SPARE - - - - AI - - - - - -20 to +20 C
IW.288 21 R1S05 - - - - - - - - - - - - to - -
IW.290 2 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.290 22 R1S05 - - - - - - - - - - - - to - -
IW.292 3 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.292 23 R1S05 - - - - - - - - - - - - to - -
IW.294 4 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.294 24 R1S05 - - - - - - - - - - - - to - -
IW.296 5 R1S05 - SPARE - - - - AI - - - - - -20 to +20 C
IW.296 25 R1S05 - - - - - - - - - - - - to - -
IW.298 6 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.298 26 R1S05 - - - - - - - - - - - - to - -
IW.300 7 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.300 27 R1S05 - - - - - - - - - - - - to - -
IW.302 8 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.302 28 R1S05 - - - - - - - - - - - - to - -
IW.304 9 R1S05 - SPARE - - - - AI - - - - - -20 to +20 C
IW.304 29 R1S05 - - - - - - - - - - - - to - -
IW.306 10 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.306 30 R1S05 - - - - - - - - - - - - to - -
IW.308 11 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.308 31 R1S05 - - - - - - - - - - - - to - -
IW.310 12 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.310 32 R1S05 - - - - - - - - - - - - to - -
IW.312 13 R1S05 - SPARE - - - - AI - - - - - -20 to +20 C
IW.312 33 R1S05 - - - - - - - - - - - - to - -
IW.314 14 R1S05 - SPARE - - - - AI - - - - - 0 to +10 C
IW.314 34 R1S05 - - - - - - - - - - - - to - -
IW.316 15 R1S05 - SPARE - - - - AI - - - - - 0 to +20 C
IW.316 35 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - -
IW.318 16 R1S05 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - - -
IW.318 36 R1S05 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S11 Q4.0 2 R1S02 R10 RING MAIN H03 VCB OPEN S008-2 - 16 - CO - - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S11 Q4.1 3 R1S02 R10 RING MAIN H03 VCB CLOSE S008-3 - 15 - CO - - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S11 Q4.2 6 R1S02 R10 RECTIFIER FEEDER H01 VCB OPEN S008-4 - 22 - CO - - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S11 Q4.3 7 R1S02 R10 RECTIFIER FEEDER H01 VCB CLOSE S008-5 - 21 - CO - - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S11 Q4.4 12 R1S02 R10 RECTIFIER FEEDER D1 DCCB OPEN S008-6 - 17 - CO - - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S11 Q4.5 13 R1S02 R10 RECTIFIER FEEDER D1 DCCB CLOSE S008-7 - 18 - CO - - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S11 Q4.6 16 R1S02 R10 RECTIFIER FEEDER H02 VCB OPEN S008-8 - 68 - CO - - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S11 Q4.7 17 R1S02 R10 RECTIFIER FEEDER H02 VCB CLOSE S008-9 - 67 - CO - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02
M 20 R1S02
RL-09 Q5.0 15 R0S11 Q5.0 22 R1S02 R10 RECTIFIER FEEDER D2 DCCB OPEN S008-10 - 19 - CO - - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S11 Q5.1 23 R1S02 R10 RECTIFIER FEEDER D2 DCCB CLOSE S008-11 - 20 - CO - - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S11 Q5.2 26 R1S02 R10 TRACK FEEDER D23 DCCB OPEN S008-12 - 25 - CO - - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S11 Q5.3 27 R1S02 R10 TRACK FEEDER D23 DCCB CLOSE S008-13 - 26 - CO - - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S11 Q5.4 32 R1S02 R10 TRACK FEEDER D24 DCCB OPEN S008-14 - 33 - CO - - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S11 Q5.5 33 R1S02 R10 TRACK FEEDER D24 DCCB CLOSE S008-15 - 34 - CO - - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S11 Q5.6 36 R1S02 R10 TRACK FEEDER D25 DCCB OPEN S008-16 - 41 - CO - - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S11 Q5.7 37 R1S02 R10 TRACK FEEDER D25 DCCB CLOSE S008-17 - 42 - CO - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02
M 40 R1S02
RL-17 Q6.0 26 R0S11 Q6.0 2 R1S03 R10 TRACK FEEDER D26 DCCB OPEN S008-18 - 49 - CO - - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S11 Q6.1 3 R1S03 R10 TRACK FEEDER D26 DCCB CLOSE S008-19 - 50 - CO - - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S11 Q6.2 6 R1S03 R10 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S008-20 - 61 - CO - - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S11 Q6.3 7 R1S03 - SPARE S008-21 - - - - - - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S11 Q6.4 12 R1S03 R10 RING MAIN H05 VCB OPEN S009-28 new 7 8 CO - - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S11 Q6.5 13 R1S03 R10 RING MAIN H05 VCB CLOSE S009-29 new 9 10 CO - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S11 Q6.6 16 R1S03 - SPARE S008-24 - 69 - - - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S11 Q6.7 17 R1S03 R10 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT internal wiring - - - CO - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S03 BIT)
M 20 R1S03
RL-25 Q7.0 37 R0S11 Q7.0 22 R1S03 R10 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT internal wiring - - - CO - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S11 Q7.1 23 R1S03 - BIT) SPARE S008-27 - - - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S11 Q7.2 26 R1S03 - SPARE S008-28 - - - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S11 Q7.3 27 R1S03 - SPARE S008-29 - - - - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S11 Q7.4 32 R1S03 SECTION BREAKER STATUS & SPARE S008-30 - - - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S11 Q7.5 33 R1S03 CONTROL REFER
- TO RS12 SPARE S008-31 - - - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S11 Q7.6 36 R1S03 - SPARE S008-32 - - - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S11 Q7.7 37 R1S03 - SPARE S008-33 - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S03
LM 40 R1S03
FR0 FR0 34 R0S11 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - -
ONAND
THECOMMON
32 CO
FR1 FR1 35 R0S11 FR1 - - - ENABLE CONTACT RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 R0S11 UE0 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S11 UE1 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS10 [RS10] 110 Printed on: 04/30/2024


Alarm Priority

Alm 1 or Alm 2 or Alm 3 or


L H HH

- - -
- - -
NC - -
C - -
C - -
C - -
C - -
- - -
NC - -
C - -
- - -
- - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
- - -
- - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
- - -
- - -
C - -
- - -
NC - -
- - -
NC - -
C - -
C - -
C - -
- - -
- - -
- - -
- - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
- - -
- - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
- - -
- - -
- - -
NC - -
- - -
NC - -
- - -
C - -
C - -
- - -
C - -
- - -
- - -
NC - -
C - -
C - -
NC - -
C - -
- - -
NC - -
C - -
- - -
- - -

Unrestricted 749775924.xlsx/RS10 [RS10] 111 Printed on: 04/30/2024


Alarm Priority

Alm 1 or Alm 2 or Alm 3 or


L H HH

- - -
- - -
C - -
NC - -
C - -
- - -
NC - -
C - -
C - -
NC - -
- - -
- - -
C - -
- - -
NC - -
C - -
C - -
NC - -
C - -
- - -
- - -
- - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
- - -
- - -
C - -
C - -
C - -
C - -
C - -
C - -
C - -
- - -
- - -
- - -
- - -
- - -
NC - -
C - -
C - -
C - -
C - -
- - -
- - -
- - -
- - -
- - -
NC - -
- NC C
NC - -
- NC C
NC - -
- NC C
NC - -
- NC C
- - -
- - -
NC - -
- NC C
NC - -
- NC C
NC - -
- NC C
NC - -
- NC C
- - -
- - -
NC - -
- NC C
NC - -
- NC C
NC - -
- NC C
NC - -
- NC C
- - -
- - -

Unrestricted 749775924.xlsx/RS10 [RS10] 112 Printed on: 04/30/2024


Alarm Priority

Alm 1 or Alm 2 or Alm 3 or


L H HH

- - -
- - -
NC NC C
-6.786 7.200 8.143
NC NC C
- 7.125 9.025
NC NC C
8.316 9.196 9.424
NC NC C
5.565 9.025 9.310
NC NC C
-6.786 7.200 8.143
NC NC C
- 6.333 7.521
NC NC C
- 4.524 5.429
NC NC C
- 9.025 9.310
NC NC C
-6.786 7.200 8.143
NC NC C
- 6.333 7.521
NC NC C
- 4.524 5.429
NC NC C
- 9.025 9.310
NC NC C
-6.786 7.200 8.143
NC NC C
- 6.333 7.238
NC NC C
- 7.125 9.025
- - -
- - -
- - -
- - -
- - -

Unrestricted 749775924.xlsx/RS10 [RS10] 113 Printed on: 04/30/2024


Alarm Priority

Alm 1 or Alm 2 or Alm 3 or


L H HH

- - -
- - -
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
NC NC C
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -

- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -

- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -

- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -

- - -
- - -
- - -
- - -

Unrestricted 749775924.xlsx/RS10 [RS10] 114 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


S7-400 RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(Internal Wiring at Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Delay LL L H HH LL L H HH Alm 0 Alm 1 Alm 2 Alm 3
Terminal Pin No. Terminal Pin No. (+ve) (-ve) (sec) or LL or L or H or HH
No. No.

ZS1 ZS1 1 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S07 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R11 RING MAIN H01 CONTROL SELECTOR SWITCH S005-04 - 3 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R11 RING MAIN H01 O/C EARTH FAULT TRIP S005-05 - 199 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R11 RING MAIN H01 SOLKOR TRIP S005-06 - 198 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R11 RING MAIN H01 PILOT WIRE ALARM S005-07 - 196 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 R11 RING MAIN H01 OVERLOAD ALARM S005-08 - 197 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 - SPARE S005-09 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R11 RING MAIN H02 CONTROL SELECTOR SWITCH S005-12 - 8 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R11 RING MAIN H02 O/C EARTH FAULT TRIP S005-13 - 195 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R11 RING MAIN H02 SOLKOR TRIP S005-14 - 194 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R11 RING MAIN H02 PILOT WIRE ALARM S005-15 - 192 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R11 RING MAIN H02 OVERLOAD ALARM S005-16 - 193 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 - SPARE S005-17 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 R11 RING MAIN H03 CONTROL SELECTOR SWITCH S005-20 - 13 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 R11 RING MAIN H03 O/C EARTH FAULT TRIP S005-21 - 191 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R11 RING MAIN H03 SOLKOR TRIP S005-22 - 190 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 - SPARE S005-23 - - - - - - - - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R11 RING MAIN H03 OVERLOAD ALARM S005-24 - 189 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 - SPARE S005-25 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 - SPARE S005-26 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 - SPARE S005-27 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R11 RECTIFIER FEEDER H04 CONTROL SELECTOR SWITCH S005-30 - 28 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R11 RECTIFIER FEEDER H04 O/C EARTH FAULT TRIP S005-31 - 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R11 RECTIFIER FEEDER H04 OVERLOAD TRIP S005-32 - 235 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R11 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-33 - 234 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R11 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-34 - 233 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R11 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S005-35 - 232 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R11 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-36 - 231 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R11 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-37 - 230 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R11 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-38 - 229 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R11 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-39 - 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R11 RECTIFIER 1 FRAME EARTH TRIP S005-40 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R11 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-41 - 226 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R11 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-42 - 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R11 RECTIFIER 1 DIODE OVER TEMP ALARM S005-43 - 224 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R11 RECTIFIER 1 DIODE OVER TEMP TRIP S005-44 - 223 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R11 RECTIFIER 1 REVERSE CURRENT TRIP S005-45 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R11 RECTIFIER 1 SURGE ARRESTOR TRIP S005-46 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R11 RECTIFIER 1 FILTER CIRCUIT ALARM S005-47 - 220 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R11 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-48 - 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 - SPARE S006-02 - - - - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R11 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S006-05 - 63 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 - SPARE S006-06 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R11 TRACK FEEDER D91 CONTROL SELECTOR SWITCH S006-09 - 80 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R11 TRACK FEEDER D91 INSTANT OVERCURRENT S006-10 - 218 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R11 TRACK FEEDER D91 RATE OF RISE TRIP S006-11 - 217 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R11 TRACK FEEDER D91 LINE TESTING S006-12 - 60 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R11 TRACK FEEDER D91 LINE IMPEDANCE LOW S006-13 - 202 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 - SPARE S006-14 - - - - - - - - - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 2M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R11 TRACK FEEDER D92 CONTROL SELECTOR SWITCH S006-17 - 73 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R11 TRACK FEEDER D92 INSTANT OVERCURRENT S006-18 - 207 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R11 TRACK FEEDER D92 RATE OF RISE TRIP S006-19 - 206 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R11 TRACK FEEDER D92 LINE TESTING S006-20 - 61 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R11 TRACK FEEDER D92 LINE IMPEDANCE LOW S006-21 - 205 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 - SPARE S006-22 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R11 TRACK FEEDER D93 CONTROL SELECTOR SWITCH S006-25 - 66 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R11 TRACK FEEDER D93 INSTANT OVERCURRENT S006-26 - 204 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R11 TRACK FEEDER D93 RATE OF RISE TRIP S006-27 - 203 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R11 TRACK FEEDER D93 LINE TESTING S006-28 - 62 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R11 AC/DC SYSTEM MAINS FAILED ALARM S006-29 - 186 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R11 DC COMMON EQUIPMENT D05 FRAME EARTH TRIP S006-30 - 201 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R11 DC COMMON EQUIPMENT D05 EMERGENCY TRIP S006-31 - 200 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R11 AC/DC SYSTEM BATTERY CHARGER S006-32 - 251 - SB B/C NORMAL ISOLATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R11 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S006-33 - 185 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R11 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S006-34 - 250 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS11 [RS11] 115 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


S7-400 RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(Internal Wiring at Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Delay LL L H HH LL L H HH Alm 0 Alm 1 Alm 2 Alm 3
Terminal Pin No. Terminal Pin No. (+ve) (-ve) (sec) or LL or L or H or HH
No. No.

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R11 AC/DC SYSTEM 11KV CONTROL VOLTAGE S006-35 - 249 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R11 AC/DC SYSTEM 750V CONTROL VOLTAGE S006-36 - 248 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R11 AC/DC SYSTEM 110V DC COMMON FEEDER S006-37 - 247 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R11 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S006-38 - 246 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 - SPARE S006-39 - 391 - - - - - - - - - - - - - - - - - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S006-40 - 392 - - - - - - - - - - - - - - - - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R11 COMMON EQUIPMENT INTRUDER ALARM S006-41 - 393 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R11 750V DCCB TRIP CCT SUPERVISION ALARM S006-42 - 402 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R11 WORKSHOP FEEDER H05 CONTROL SELECTOR SWITCH S006-45 - 18 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R11 WORKSHOP FEEDER H05 EARTH FAULT TRIP S006-46 - 245 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R11 WORKSHOP TRANSFORMER 1 SUDDEN PRESSURE TRIP S006-47 - 244 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 R11 WORKSHOP TRANSFORMER 1 PRESSURE RELIEF ALARM S006-48 - 243 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R11 WORKSHOP TRANSFORMER 1 LIQUID LEVEL LOW TRIP S007-02 - 242 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R11 WORKSHOP TRANSFORMER 1 WINDING TEMP HIGH ALARM S007-03 - 241 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R11 WORKSHOP TRANSFORMER 1 WINDING TEMP HIGH TRIP S007-04 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R11 WORKSHOP TRANSFORMER 1 LIQUID TEMP HIGH ALARM S007-05 - 239 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R11 WORKSHOP TRANSFORMER 1 LIQUID TEMP HIGH TRIP S007-06 - 238 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 R11 WORKSHOP TRANSFORMER 1 RESTRICT E/F TRIP S007-07 - 237 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 - SPARE S007-08 - 394 - - - - - - - - - - - - - - - - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 - SPARE S007-09 - 395 - - - - - - - - - - - - - - - - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R11 WORKSHOP FEEDER H06 CONTROL SELECTOR SWITCH S007-12 - 23 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R11 WORKSHOP FEEDER H06 EARTH FAULT TRIP S007-13 - 216 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R11 WORKSHOP TRANSFORMER 2 SUDDEN PRESSURE TRIP S007-14 - 215 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R11 WORKSHOP TRANSFORMER 2 PRESSURE RELIEF ALARM S007-15 - 214 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R11 WORKSHOP TRANSFORMER 2 LIQUID LEVEL LOW TRIP S007-16 - 213 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R11 WORKSHOP TRANSFORMER 2 WINDING TEMP HIGH ALARM S007-17 - 212 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R11 WORKSHOP TRANSFORMER 2 WINDING TEMP HIGH TRIP S007-18 - 211 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R11 WORKSHOP TRANSFORMER 2 LIQUID TEMP HIGH ALARM S007-19 - 210 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R11 WORKSHOP TRANSFORMER 2 LIQUID TEMP HIGH TRIP S007-20 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R11 WORKSHOP TRANSFORMER 2 RESTRICT E/F TRIP S007-21 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 - SPARE S007-22 - 480 - - - - - - - - - - - - - - - - - - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 - SPARE S007-23 - 481 - - - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R11 AC/DC SYSTEM LV DISTRIBUTION BOARD COMMON S007-24 - 483 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 - SPARE S007-26 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 - SPARE S007-27 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 - SPARE S007-28 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 - SPARE S007-29 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 - SPARE S007-30 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 - SPARE S007-31 - - - - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R11 RING MAIN H01 VCB OPENED S005-02 - 1 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 R11 RING MAIN H01 VCB CLOSED S005-03 - 2 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R11 RING MAIN H02 VCB OPENED S005-10 - 6 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 R11 RING MAIN H02 VCB CLOSED S005-11 - 7 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R11 RING MAIN H03 VCB OPENED S005-18 - 11 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R11 RING MAIN H03 VCB CLOSED S005-19 - 12 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R11 RECTIFIER FEEDER H04 VCB OPENED S005-28 - 26 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R11 RECTIFIER FEEDER H04 VCB CLOSED S005-29 - 27 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R11 RECTIFIER FEEDER D1 DCCB OPENED S006-03 - 65 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R11 RECTIFIER FEEDER D1 DCCB CLOSED S006-04 - 64 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R11 TRACK FEEDER D91 DCCB OPENED S006-07 - 84 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R11 TRACK FEEDER D91 DCCB CLOSED S006-08 - 83 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R11 TRACK FEEDER D92 DCCB OPENED S006-15 - 77 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R11 TRACK FEEDER D92 DCCB CLOSED S006-16 - 76 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R11 TRACK FEEDER D93 DCCB OPENED S006-23 - 70 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R11 TRACK FEEDER D93 DCCB CLOSED S006-24 - 69 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R11 WORKSHOP FEEDER H05 VCB OPENED S006-43 - 16 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R11 WORKSHOP FEEDER H05 VCB CLOSED S006-44 - 17 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 R11 WORKSHOP FEEDER H06 VCB OPENED S007-10 - 21 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R11 WORKSHOP FEEDER H06 VCB CLOSED S007-11 - 22 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - - NC C
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R11 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - - C NC - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R11 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - - - - NC C
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 - SPARE S007-32 - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 - SPARE S007-33 - - - - - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS11 [RS11] 116 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


S7-400 RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(Internal Wiring at Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Delay LL L H HH LL L H HH Alm 0 Alm 1 Alm 2 Alm 3
Terminal Pin No. Terminal Pin No. (+ve) (-ve) (sec) or LL or L or H or HH
No. No.

ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S12 IW.256 1 R1S04 R11 TRACK FEEDER D91 DC CURRENT S009-01 - 344 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-1 (-) IW.256 5 R0S12 IW.256 21 R1S04 - - S009-02 - - 427 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
TB2-2 (+) IW.258 6 R0S12 IW.258 2 R1S04 R11 RING MAIN H01 CURRENT S009-03 - 335 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-2 (-) IW.258 7 R0S12 IW.258 22 R1S04 - - S009-04 - - 418 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - - 7.125 9.025
TB2-3 (+) IW.260 8 R0S12 IW.260 3 R1S04 R11 RING MAIN H02 CURRENT S009-05 - 336 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-3 (-) IW.260 9 R0S12 IW.260 23 R1S04 - - S009-06 - - 419 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - - 7.125 9.025
TB2-4 (+) IW.262 10 R0S12 IW.262 4 R1S04 R11 RING MAIN H03 CURRENT S009-07 - 337 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-4 (-) IW.262 11 R0S12 IW.262 24 R1S04 - - S009-08 - - 420 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285.000 361.000 - - 7.125 9.025
TB2-5 (+) IW.264 15 R0S12 IW.264 5 R1S04 R11 TRACK FEEDER D92 DC CURRENT S009-09 - 345 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-5 (-) IW.264 16 R0S12 IW.264 25 R1S04 - - S009-10 - - 428 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
TB2-6 (+) IW.266 17 R0S12 IW.266 6 R1S04 R11 RECTIFIER FEEDER H04 CURRENT S009-11 - 338 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-6 (-) IW.266 18 R0S12 IW.266 26 R1S04 - - S009-12 - - 421 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - - 6.333 7.521
TB2-7 (+) IW.268 19 R0S12 IW.268 7 R1S04 R11 RECTIFIER UNIT 1 DC CURRENT S009-13 - 341 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-7 (-) IW.268 20 R0S12 IW.268 27 R1S04 - - S009-14 - - 424 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - - 4.524 5.429
TB2-8 (+) IW.270 21 R0S12 IW.270 8 R1S04 R11 RECTIFIER UNIT 1 DC VOLTAGE S009-15 - 342 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-8 (-) IW.270 22 R0S12 IW.270 28 R1S04 - - S009-16 - - 425 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 - - 9.025 9.310
TB2-9 (+) IW.272 26 R0S12 IW.272 9 R1S04 R11 TRACK FEEDER D93 DC CURRENT S009-17 - 346 - AI - - - - - -20 to +20 -7000 to 7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-9 (-) IW.272 27 R0S12 IW.272 29 R1S04 - - S009-18 - - 429 - - - - - - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
TB2-10 (+) IW.274 28 R0S12 IW.274 10 R1S04 R11 AC BUSBAR VOLTAGE S009-19 - 348 - AI - - - - - 0 to +10 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-10 (-) IW.274 29 R0S12 IW.274 30 R1S04 - - S009-20 - - 431 - - - - - - to - - to - - - - - 0.800 7.920 9.680 9.920 0.950 10.395 11.495 11.78 0.760 8.316 9.196 9.424
TB2-11 (+) IW.276 30 R0S12 IW.276 11 R1S04 R11 DC BUSBAR DC VOLTAGE S009-21 - 347 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-11 (-) IW.276 31 R0S12 IW.276 31 R1S04 - - S009-22 - - 430 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500 902.5 931 3.943 5.565 9.025 9.310
TB2-12 (+) IW.278 32 R0S12 IW.278 12 R1S04 R11 NEGATIVE DC BUSBAR DC RETURN CURRENT S009-23 - 343 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-12 (-) IW.278 33 R0S12 IW.278 32 R1S04 - - S009-24 - - 426 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800 - - 6.333 7.238
TB2-13 (+) IW.280 37 R0S12 IW.280 13 R1S04 - SPARE S009-25 - - - - - - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-13 (-) IW.280 38 R0S12 IW.280 33 R1S04 - - S009-26 - - - - - - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-14 (+) IW.282 39 R0S12 IW.282 14 R1S04 R11 WORKSHOP FEEDER H05 CURRENT S009-27 - 339 - AI - - - - - 0 to +10 0 to 100 A ac - - 1.0% 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-14 (-) IW.282 40 R0S12 IW.282 34 R1S04 - - S009-28 - - 422 - - - - - - to - - to - - - - - 0.000 0.000 8.000 9.500 0.000 0.000 76 90.25 0.000 0.000 7.600 9.025
TB2-15 (+) IW.284 41 R0S12 IW.284 15 R1S04 R11 WORKSHOP FEEDER H06 CURRENT S009-29 - 340 - AI - - - - - 0 to +10 0 to 100 A ac - - 1.0% 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-15 (-) IW.284 42 R0S12 IW.284 35 R1S04 - - S009-30 - - 423 - - - - - - to - - to - - - - - 0.000 0.000 8.000 9.500 0.000 0.000 76 90.25 0.000 0.000 7.600 9.025
TB2-16 (+) IW.286 43 R0S12 IW.286 16 R1S04 - SPARE S009-31 - - - - - - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S12 IW.286 36 R1S04 - - S009-32 - - - - - - - - - to - - to - - - - - - - - - - - - - - - - -
S110-RD - - R0S12 - - - - - S009-70 - 405 - - - - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S12 - - - - - S009-71 - - 488 - - - - - - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S12 - - - - - S009-72 - - 488 - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS11 [RS11] 117 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


S7-400 RTU S7-400 RTU S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
(Internal Wiring at Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
RTU Modules) RTU Modules) Time
Terminal No. Modules Modules Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Delay LL L H HH LL L H HH Alm 0 Alm 1 Alm 2 Alm 3
Terminal Pin No. Terminal Pin No. (+ve) (-ve) (sec) or LL or L or H or HH
No. No.

RL-A - - R0S12 - - - - - S008-01 - - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S11 Q4.0 2 R1S02 R11 RING MAIN H01 VCB OPEN S008-02 - 5 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S11 Q4.1 3 R1S02 R11 RING MAIN H01 VCB CLOSE S008-03 - 4 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S11 Q4.2 6 R1S02 R11 RING MAIN H02 VCB OPEN S008-04 - 10 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S11 Q4.3 7 R1S02 R11 RING MAIN H02 VCB CLOSE S008-05 - 9 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S11 Q4.4 12 R1S02 R11 RING MAIN H03 VCB OPEN S008-06 - 15 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S11 Q4.5 13 R1S02 R11 RING MAIN H03 VCB CLOSE S008-07 - 14 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S11 Q4.6 16 R1S02 R11 RECTIFIER FEEDER H04 VCB OPEN S008-08 - 30 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S11 Q4.7 17 R1S02 R11 RECTIFIER FEEDER H04 VCB CLOSE S008-09 - 29 - CO - - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02
LM 20 R1S02
RL-09 Q5.0 15 R0S11 Q5.0 22 R1S02 R11 RECTIFIER FEEDER D1 DCCB OPEN S008-10 - 386 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S11 Q5.1 23 R1S02 R11 RECTIFIER FEEDER D1 DCCB CLOSE S008-11 - 387 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S11 Q5.2 26 R1S02 R11 TRACK FEEDER D91 DCCB OPEN S008-12 - 79 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S11 Q5.3 27 R1S02 R11 TRACK FEEDER D91 DCCB CLOSE S008-13 - 78 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S11 Q5.4 32 R1S02 R11 TRACK FEEDER D92 DCCB OPEN S008-14 - 72 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S11 Q5.5 33 R1S02 R11 TRACK FEEDER D92 DCCB CLOSE S008-15 - 71 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S11 Q5.6 36 R1S02 - SPARE S008-16 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S11 Q5.7 37 R1S02 - SPARE S008-17 - - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02
LM 40 R1S02
RL-17 Q6.0 26 R0S11 Q6.0 2 R1S03 - SPARE S008-18 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S11 Q6.1 3 R1S03 - SPARE S008-19 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S11 Q6.2 6 R1S03 R11 WORKSHOP FEEDER H05 VCB OPEN S008-20 - 20 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S11 Q6.3 7 R1S03 R11 WORKSHOP FEEDER H05 VCB CLOSE S008-21 - 19 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S11 Q6.4 12 R1S03 R11 WORKSHOP FEEDER H06 VCB OPEN S008-22 - 24 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S11 Q6.5 13 R1S03 R11 WORKSHOP FEEDER H06 VCB CLOSE S008-23 - 25 - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S11 Q6.6 16 R1S03 R11 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S11 Q6.7 17 R1S03 R11 DUMMY CB BIT)
VCB OPEN/CLOSE (LEAST SIGINIFICANT internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S03 BIT)
LM 20 R1S03
RL-25 Q7.0 37 R0S11 Q7.0 22 R1S03 - SPARE S008-26 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S11 Q7.1 23 R1S03 - SPARE S008-27 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S11 Q7.2 26 R1S03 - SPARE S008-28 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S11 Q7.3 27 R1S03 - SPARE S008-29 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S11 Q7.4 32 R1S03 - SPARE S008-30 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S11 Q7.5 33 R1S03 - SPARE S008-31 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S11 Q7.6 36 R1S03 - SPARE S008-32 - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S11 Q7.7 37 R1S03 - SPARE S008-33 - - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S03
LM 40 R1S03
FR0 FR0 34 R0S11 FR0 - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
FR1 FR1 35 R0S11 FR1 - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 R0S11 UE0 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S11 UE1 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS11 [RS11] 118 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S7 I4.0 1 R0S02 R12 RING MAIN H04 CONTROL SELECTOR SWITCH S005-4 - 16 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-4 I4.1 5 R0S7 I4.1 2 R0S02 R12 RING MAIN H04 O/C EARTH FAULT TRIP S005-5 - 178 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-6 I4.2 6 R0S7 I4.2 3 R0S02 R12 RING MAIN H04 SOLKOR TRIP S005-6 - 181 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-8 I4.3 7 R0S7 I4.3 4 R0S02 R12 RING MAIN H04 OVERLOAD ALARM S005-7 - 179 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-10 I4.4 8 R0S7 I4.4 5 R0S02 R12 RING MAIN H04 PILOT WIRE ALARM S005-8 - 180 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-12 I4.5 9 R0S7 I4.5 6 R0S02 R12 RING MAIN H04 NO VOLT RELAY S005-9 - 182 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-14 I4.6 10 R0S7 I4.6 7 R0S02 R12 ROLLING SHUTTER - S005-10 - 379 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-16 I4.7 11 R0S7 I4.7 8 R0S02 - SPARE S005-11 - - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S7 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S7 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S7 I5.0 11 R0S02 - SPARE S005-12 - - - - - - - - - - - - - - - - - - - - - - - -
DI-20 I5.1 16 R0S7 I5.1 12 R0S02 R12 RING MAIN H04 TRIP CCT SUPERVISION ALARM S005-13 - 185 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-22 I5.2 17 R0S7 I5.2 13 R0S02 - SPARE S005-14 - - - - - - - - - - - - - - - - - - - - - - - -
DI-24 I5.3 18 R0S7 I5.3 14 R0S02 - SPARE S005-15 - - - - - - - - - - - - - - - - - - - - - - - -
DI-26 I5.4 19 R0S7 I5.4 15 R0S02 R12 RING MAIN H03 CONTROL SELECTOR SWITCH S005-18 - 12 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-28 I5.5 20 R0S7 I5.5 16 R0S02 R12 RING MAIN H03 O/C EARTH FAULT TRIP S005-19 - 170 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-30 I5.6 21 R0S7 I5.6 17 R0S02 R12 RING MAIN H03 SOLKOR TRIP S005-20 - 173 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-32 I5.7 22 R0S7 I5.7 18 R0S02 R12 RING MAIN H03 OVERLOAD ALARM S005-21 - 171 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S7 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S7 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S7 I6.0 21 R0S02 - SPARE S005-22 - - - - - - - - - - - - - - - - - - - - - - - -
DI-36 I6.1 27 R0S7 I6.1 22 R0S02 R12 RING MAIN H03 NO VOLT RELAY S005-23 - 174 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-38 I6.2 28 R0S7 I6.2 23 R0S02 - SPARE S005-24 - - - - - - - - - - - - - - - - - - - - - - - -
DI-40 I6.3 29 R0S7 I6.3 24 R0S02 - SPARE S005-25 - - - - - - - - - - - - - - - - - - - - - - - -
DI-42 I6.4 30 R0S7 I6.4 25 R0S02 - SPARE S005-26 - - - - - - - - - - - - - - - - - - - - - - - -
DI-44 I6.5 31 R0S7 I6.5 26 R0S02 R12 RING MAIN H03 TRIP CCT SUPERVISION ALARM S005-27 - 176 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-46 I6.6 32 R0S7 I6.6 27 R0S02 R12 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-30 - 4 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-48 I6.7 33 R0S7 I6.7 28 R0S02 R12 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-31 - 201 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S7 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S7 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S7 I7.0 31 R0S02 R12 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-32 - 202 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-52 I7.1 38 R0S7 I7.1 32 R0S02 R12 RECT 1 TRANSFORMER PRESSURE RELIEF TRIP S005-33 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-54 I7.2 39 R0S7 I7.2 33 R0S02 R12 RECT 1 TRANSFORMER GAS/LIQUID LEVEL TRIP S005-34 - 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-56 I7.3 40 R0S7 I7.3 34 R0S02 R12 RECT 1 TRANSFORMER LIQUID LEVEL ALARM S005-35 - 229 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-58 I7.4 41 R0S7 I7.4 35 R0S02 R12 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-36 - 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-60 I7.5 42 R0S7 I7.5 36 R0S02 R12 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-37 - 231 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-62 I7.6 43 R0S7 I7.6 37 R0S02 R12 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-38 - 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-64 I7.7 44 R0S7 I7.7 38 R0S02 R12 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-39 - 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S7 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S7 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R12 RECTIFIER 1 FRAME EARTH TRIP S005-40 - 212 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R12 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-41 - 207 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R12 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-42 - 211 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R12 RECTIFIER 1 DIODE OVER TEMP ALARM S005-43 - 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R12 RECTIFIER 1 DIODE OVER TEMP TRIP S005-44 - 210 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R12 RECTIFIER 1 REVERSE CURRENT TRIP S005-45 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R12 RECTIFIER 1 SURGE ARRESTOR TRIP S005-46 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R12 RECTIFIER 1 FILTER CIRCUIT ALARM S005-47 - 205 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R12 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S005-48 - 204 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R12 RECTIFIER FEEDER D1 TRIP CCT SUPERVISION ALARM S006-2 - 195 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R12 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S006-5 - 29 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R12 RECTIFIER FEEDER H01 TRIP CCT SUPERVISION ALARM S006-6 - 203 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 - SPARE S006-7 - - - - - - - - - - - - - - - - - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 - SPARE S006-8 - - - - - - - - - - - - - - - - - - - - - - - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R12 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S006-11 - 8 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R12 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-12 - 214 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R12 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-13 - 215 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R12 RECT 2 TRANSFORMER PRESSURE RELIEF TRIP S006-14 - 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R12 RECT 2 TRANSFORMER GAS/LIQUID LEVEL TRIP S006-15 - 237 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R12 RECT 2 TRANSFORMER LIQUID LEVEL ALARM S006-16 - 238 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R12 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-17 - 239 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R12 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-18 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R12 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-19 - 241 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R12 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-20 - 242 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R12 RECTIFIER 2 FRAME EARTH TRIP S006-21 - 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R12 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-22 - 220 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R12 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-23 - 224 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R12 RECTIFIER 2 DIODE OVER TEMP ALARM S006-24 - 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R12 RECTIFIER 2 DIODE OVER TEMP TRIP S006-25 - 223 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R12 RECTIFIER 2 REVERSE CURRENT TRIP S006-26 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R12 RECTIFIER 2 SURGE ARRESTOR TRIP S006-27 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R12 RECTIFIER 2 FILTER CIRCUIT ALARM S006-28 - 218 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS12 [RS12] 119 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R12 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-29 - 217 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R12 RECTIFIER FEEDER D2 TRIP CCT SUPERVISION ALARM S006-30 - 197 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R12 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-33 - 33 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R12 RECTIFIER FEEDER H02 TRIP CCT SUPERVISION ALARM S006-34 - 216 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R12 AUXILIARY TRANSFORMER 11KV SWITCH H5 S006-35 - 17 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - - NC NC
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S006-36 - 18 - - - - - - - - - - - - - - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R12 AUXILIARY TRANSFORMER 11KV SW H5 FUSE BLOWN TRIP S006-37 - 74 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R12 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-38 - 335 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 - SPARE S006-39 - - - - - - - - - - - - - - - - - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R12 11KV BUSBAR UNDERVOLTAGE ALARM S006-40 - 172 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R12 TRACK FEEDER D13 CONTROL SELECTOR SWITCH S006-45 - 44 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R12 TRACK FEEDER D13 RATE OF RISE TRIP S006-47 - 338 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R12 TRACK FEEDER D13 INSTANT OVERCURRENT S006-48 - 337 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R12 TRACK FEEDER D13 LINE TESTING S007-2 - 45 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R12 TRACK FEEDER D13 LINE IMPEDANCE LOW S007-3 - 339 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R12 TRACK FEEDER D13 TRIP CCT SUPERVISION ALARM S007-4 - 340 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-5 - - - - - - - - - - - - - - - - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 - SPARE S007-6 - - - - - - - - - - - - - - - - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R12 TRACK FEEDER D14 CONTROL SELECTOR SWITCH S007-10 - 53 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 - SPARE S007-11 - - - - - - - - - - - - - - - - - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R12 TRACK FEEDER D14 RATE OF RISE TRIP S007-12 - 342 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R12 TRACK FEEDER D14 INSTANT OVERCURRENT S007-13 - 341 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R12 TRACK FEEDER D14 LINE TESTING S007-14 - 54 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R12 TRACK FEEDER D14 LINE IMPEDANCE LOW S007-15 - 343 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R12 TRACK FEEDER D14 TRIP CCT SUPERVISION ALARM S007-16 - 344 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 - SPARE S007-17 - - - - - - - - - - - - - - - - - - - - - - - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 - SPARE S007-18 - - - - - - - - - - - - - - - - - - - - - - - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 - SPARE S007-19 - - - - - - - - - - - - - - - - - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R12 TRACK FEEDER D13 TRANSFER TRIP S007-20 - 46 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 - SPARE S007-21 - - - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 R12 TRACK FEEDER D15 CONTROL SELECTOR SWITCH S007-24 - 61 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 - SPARE S007-25 - - - - - - - - - - - - - - - - - - - - - - - -
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 R12 TRACK FEEDER D15 RATE OF RISE TRIP S007-26 - 346 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R12 TRACK FEEDER D15 INSTANT OVERCURRENT S007-27 - 345 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R12 TRACK FEEDER D15 LINE TESTING S007-28 - 62 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R12 TRACK FEEDER D15 LINE IMPEDANCE LOW S007-29 - 347 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R12 TRACK FEEDER D15 TRIP CCT SUPERVISION ALARM S007-30 - 348 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 - SPARE S007-31 - - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 - SPARE S007-32 - - - - - - - - - - - - - - - - - - - - - - - -
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 - SPARE S007-33 - - - - - - - - - - - - - - - - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R12 TRACK FEEDER D16 CONTROL SELECTOR SWITCH S007-36 - 69 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 - SPARE S007-37 - - - - - - - - - - - - - - - - - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R12 TRACK FEEDER D16 RATE OF RISE TRIP S007-38 - 350 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R12 TRACK FEEDER D16 INSTANT OVERCURRENT S007-39 - 349 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R12 TRACK FEEDER D16 LINE TESTING S007-40 - 70 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R12 TRACK FEEDER D16 LINE IMPEDANCE LOW S007-41 - 351 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R12 TRACK FEEDER D16 TRIP CCT SUPERVISION ALARM S007-42 - 352 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 - SPARE S007-43 - - - - - - - - - - - - - - - - - - - - - - - -
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 - SPARE S007-44 - 84 - - - - - - - - - - - - - - - - - - - - - -
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 R12 TRACK FEEDER D15 TRANSFER TRIP S007-45 - 71 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R12 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S007-48 - 194 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R12 DC COMMON EQUIPMENT D07 CONTROL SELECTOR SWITCH S008-2 - 82 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 R12 DC COMMON EQUIPMENT D07 EARTH SW OVERRIDE S008-3 - 83 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 R12 DC COMMON EQUIPMENT D07 NEGATIVE VOLTS HIGH ALARM S008-4 - 354 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R12 AC/DC SYSTEM MAINS FAILED ALARM S008-5 - 186 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R12 AC/DC SYSTEM MAINS LOW VOLTAGE ALARM S008-6 - 187 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 - SPARE S008-7 - - - - - - - - - - - - - - - - - - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R12 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S008-8 - 188 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 - SPARE S008-9 - - - - - - - - - - - - - - - - - - - - - - - -
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 R12 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S008-10 - 189 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R12 AC/DC SYSTEM 11KV CONTROL VOLTAGE S008-11 - 191 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R12 AC/DC SYSTEM 750V CONTROL VOLTAGE S008-12 - 192 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS12 [RS12] 120 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R0S06 R12 AC/DC SYSTEM 110V DC COMMON FEEDER S008-13 - 193 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
DI-260 I20.1 5 R0S11 I20.1 2 R0S06 R12 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S008-14 - 190 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-262 I20.2 6 R0S11 I20.2 3 R0S06 R12 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S008-15 - 378 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-264 I20.3 7 R0S11 I20.3 4 R0S06 R12 COMMON EQUIPMENT FIRE PROTECTION ALARM S008-16 - 376 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-266 I20.4 8 R0S11 I20.4 5 R0S06 R12 COMMON EQUIPMENT INTRUDER ALARM S008-17 - 377 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-268 I20.5 9 R0S11 I20.5 6 R0S06 R12 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-270 I20.6 10 R0S11 I20.6 7 R0S06 R10/R12 295 SECTION BREAKER S13 CONTROL SELECTOR SWITCH S008-21 - 414 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-272 I20.7 11 R0S11 I20.7 8 R0S06 R10/R12 295 SECTION BREAKER S13 OVERCURRENT TRIP S008-22 - 404 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S11 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R0S06 R10/R12 295 SECTION BREAKER S13 LOW VOLTAGE TRIP S008-23 - 407 - SB T/V RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-276 I21.1 16 R0S11 I21.1 12 R0S06 - SPARE S008-24 - - - - - - - - - - - - - - - - - - - - - - - -
DI-278 I21.2 17 R0S11 I21.2 13 R0S06 R10/R12 295 SECTION BREAKER S14 CONTROL SELECTOR SWITCH S008-27 - 415 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-280 I21.3 18 R0S11 I21.3 14 R0S06 R10/R12 295 SECTION BREAKER S14 OVERCURRENT TRIP S008-28 - 410 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-282 I21.4 19 R0S11 I21.4 15 R0S06 R10/R12 295 SECTION BREAKER S14 LOW VOLTAGE TRIP S008-29 - 413 - SB T/V RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-284 I21.5 20 R0S11 I21.5 16 R0S06 - SPARE S008-30 - - - - - - - - - - - - - - - - - - - - - - - -
DI-286 I21.6 21 R0S11 I21.6 17 R0S06 R10/R12 090 SECTION BREAKER S15 CONTROL SELECTOR SWITCH S008-33 - 416 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-288 I21.7 22 R0S11 I21.7 18 R0S06 R10/R12 090 SECTION BREAKER S15 OVERCURRENT TRIP S008-34 - 392 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S11 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S11 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R0S06 R10/R12 090 SECTION BREAKER S15 LOW VOLTAGE TRIP S008-35 - 395 - SB T/V RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-292 I22.1 27 R0S11 I22.1 22 R0S06 - SPARE S008-36 - - - - - - - - - - - - - - - - - - - - - - - -
DI-294 I22.2 28 R0S11 I22.2 23 R0S06 R10/R12 090 SECTION BREAKER S16 CONTROL SELECTOR SWITCH S008-39 - 417 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-296 I22.3 29 R0S11 I22.3 24 R0S06 R10/R12 090 SECTION BREAKER S16 OVERCURRENT TRIP S008-40 - 398 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-298 I22.4 30 R0S11 I22.4 25 R0S06 R10/R12 090 SECTION BREAKER S16 LOW VOLTAGE TRIP S008-41 - 401 - SB T/V RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-300 I22.5 31 R0S11 I22.5 26 R0S06 - SPARE S008-42 - - - - - - - - - - - - - - - - - - - - - - - -
DI-302 I22.6 32 R0S11 I22.6 27 R0S06 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-304 I22.7 33 R0S11 I22.7 28 R0S06 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S11 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R0S06 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
DI-308 I23.1 38 R0S11 I23.1 32 R0S06 R12 TRACK FEEDER D13 LINE TEST CONTROL SELECTOR SWITCH S009-6 - 383 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-310 I23.2 39 R0S11 I23.2 33 R0S06 - SPARE S009-7 - - - - - - - - - - - - - - - - - - - - - - - -
DI-312 I23.3 40 R0S11 I23.3 34 R0S06 R12 TRACK FEEDER D14 LINE TEST CONTROL SELECTOR SWITCH S009-8 - 385 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-314 I23.4 41 R0S11 I23.4 35 R0S06 - SPARE S009-9 - - - - - - - - - - - - - - - - - - - - - - - -
DI-316 I23.5 42 R0S11 I23.5 36 R0S06 R12 TRACK FEEDER D15 LINE TEST CONTROL SELECTOR SWITCH S009-10 - 387 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-318 I23.6 43 R0S11 I23.6 37 R0S06 - SPARE S009-11 - - - - - - - - - - - - - - - - - - - - - - - -
DI-320 I23.7 44 R0S11 I23.7 38 R0S06 R12 TRACK FEEDER D16 LINE TEST CONTROL SELECTOR SWITCH S009-12 - 389 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
UM3 UM3 45 R0S11 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S11 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-322 I24.0 4 R0S12 I24.0 1 R0S07 R12 RING MAIN H04 VCB OPENED S005-2 - 13 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-324 I24.1 5 R0S12 I24.1 2 R0S07 R12 RING MAIN H04 VCB CLOSED S005-3 - 14 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-326 I24.2 6 R0S12 I24.2 3 R0S07 R12 RING MAIN H03 VCB OPENED S005-16 - 9 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-328 I24.3 7 R0S12 I24.3 4 R0S07 R12 RING MAIN H03 VCB CLOSED S005-17 - 10 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-330 I24.4 8 R0S12 I24.4 5 R0S07 R12 RECTIFIER FEEDER H01 VCB OPENED S005-28 - 1 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-332 I24.5 9 R0S12 I24.5 6 R0S07 R12 RECTIFIER FEEDER H01 VCB CLOSED S005-29 - 2 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-334 I24.6 10 R0S12 I24.6 7 R0S07 R12 RECTIFIER FEEDER D1 DCCB OPENED S006-3 - 27 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-336 I24.7 11 R0S12 I24.7 8 R0S07 R12 RECTIFIER FEEDER D1 DCCB CLOSED S006-4 - 28 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM0 UM0 12 R0S12 - 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S12 - 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-338 I25.0 15 R0S12 I25.0 11 R0S07 R12 RECTIFIER FEEDER H02 VCB OPENED S006-9 - 5 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-340 I25.1 16 R0S12 I25.1 12 R0S07 R12 RECTIFIER FEEDER H02 VCB CLOSED S006-10 - 6 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-342 I25.2 17 R0S12 I25.2 13 R0S07 R12 RECTIFIER FEEDER D2 DCCB OPENED S006-31 - 31 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-344 I25.3 18 R0S12 I25.3 14 R0S07 R12 RECTIFIER FEEDER D2 DCCB CLOSED S006-32 - 32 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-346 I25.4 19 R0S12 I25.4 15 R0S07 R12 DUMMY CB VCB OPENED internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - - C NC
DI-348 I25.5 20 R0S12 I25.5 16 R0S07 R12 DUMMY CB VCB CLOSED internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - - - -
DI-350 I25.6 21 R0S12 I25.6 17 R0S07 R12 TRACK FEEDER D13 DCCB OPENED S006-43 - 39 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-352 I25.7 22 R0S12 I25.7 18 R0S07 R12 TRACK FEEDER D13 DCCB CLOSED S006-44 - 40 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM1 UM1 23 R0S12 1L+ 19 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S12 1M 20 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-354 I26.0 26 R0S12 I26.0 21 R0S07 R12 TRACK FEEDER D14 DCCB OPENED S007-8 - 48 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-356 I26.1 27 R0S12 I26.1 22 R0S07 R12 TRACK FEEDER D14 DCCB CLOSED S007-9 - 49 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-358 I26.2 28 R0S12 I26.2 23 R0S07 R12 TRACK FEEDER D15 DCCB OPENED S007-22 - 56 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-360 I26.3 29 R0S12 I26.3 24 R0S07 R12 TRACK FEEDER D15 DCCB CLOSED S007-23 - 57 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-362 I26.4 30 R0S12 I26.4 25 R0S07 R12 TRACK FEEDER D16 DCCB OPENED S007-34 - 64 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-364 I26.5 31 R0S12 I26.5 26 R0S07 R12 TRACK FEEDER D16 DCCB CLOSED S007-35 - 65 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-366 I26.6 32 R0S12 I26.6 27 R0S07 R12 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S007-46 - 80 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-368 I26.7 33 R0S12 I26.7 28 R0S07 R12 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S007-47 - 79 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM2 UM2 34 R0S12 - 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S12 - 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-370 I27.0 37 R0S12 I27.0 31 R0S07 R10/R12 295 SECTION BREAKER S13 DCCB OPENED S008-19 - 405 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-372 I27.1 38 R0S12 I27.1 32 R0S07 R10/R12 295 SECTION BREAKER S13 DCCB CLOSED S008-20 - 406 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-374 I27.2 39 R0S12 I27.2 33 R0S07 R10/R12 295 SECTION BREAKER S14 DCCB OPENED S008-25 - 411 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-376 I27.3 40 R0S12 I27.3 34 R0S07 R10/R12 295 SECTION BREAKER S14 DCCB CLOSED S008-26 - 412 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-378 I27.4 41 R0S12 I27.4 35 R0S07 R10/R12 090 SECTION BREAKER S15 DCCB OPENED S008-31 - 393 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-380 I27.5 42 R0S12 I27.5 36 R0S07 R10/R12 090 SECTION BREAKER S15 DCCB CLOSED S008-32 - 394 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-382 I27.6 43 R0S12 I27.6 37 R0S07 R10/R12 090 SECTION BREAKER S16 DCCB OPENED S008-37 - 399 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-384 I27.7 44 R0S12 I27.7 38 R0S07 R10/R12 090 SECTION BREAKER S16 DCCB CLOSED S008-38 - 400 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM3 UM3 45 R0S12 2L+ 39 R0S07 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S12 2M 40 R0S07 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS12 [RS12] 121 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S15 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S15 IW.256 1 R1S06 R12 TRACK FEEDER D13 DC CURRENT S011-1 - 369 - AI - - - - - 0 to +15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-1 (-) IW.256 5 R0S15 IW.256 21 R1S06 - - S011-2 - - 452 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-2 (+) IW.258 6 R0S15 IW.258 2 R1S06 R12 RING MAIN H04 CURRENT S011-3 - 363 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-2 (-) IW.258 7 R0S15 IW.258 22 R1S06 - - S011-4 - - 446 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-3 (+) IW.260 8 R0S15 IW.260 3 R1S06 R12 RING MAIN H03 CURRENT S011-5 - 362 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-3 (-) IW.260 9 R0S15 IW.260 23 R1S06 - - S011-6 - - 445 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-4 (+) IW.262 10 R0S15 IW.262 4 R1S06 R12 RECTIFIER FEEDER H01 CURRENT S011-7 - 360 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC
TB2-4 (-) IW.262 11 R0S15 IW.262 24 R1S06 - - S011-8 - - 443 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76.000 90.250 - -
TB2-5 (+) IW.264 15 R0S15 IW.264 5 R1S06 R12 TRACK FEEDER D14 DC CURRENT S011-9 - 370 AI - - - - - 0 to +15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-5 (-) IW.264 16 R0S15 IW.264 25 R1S06 - - S011-10 - - 453 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-6 (+) IW.266 17 R0S15 IW.266 6 R1S06 R12 RECTIFIER 1 DC CURRENT S011-11 - 365 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-6 (-) IW.266 18 R0S15 IW.266 26 R1S06 - - S011-12 - - 448 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - -
TB2-7 (+) IW.268 19 R0S15 IW.268 7 R1S06 R12 RECTIFIER 1 DC VOLTAGE S011-13 - 366 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-7 (-) IW.268 20 R0S15 IW.268 27 R1S06 - - S011-14 - - 449 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 - -
TB2-8 (+) IW.270 21 R0S15 IW.270 8 R1S06 R12 RECTIFIER FEEDER H02 CURRENT S011-15 - 361 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC
TB2-8 (-) IW.270 22 R0S15 IW.270 28 R1S06 - - S011-16 - - 444 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - -
TB2-9 (+) IW.272 26 R0S15 IW.272 9 R1S06 R12 TRACK FEEDER D15 DC CURRENT S011-17 - 371 - AI - - - - - 0 to +15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-9 (-) IW.272 27 R0S15 IW.272 29 R1S06 - - S011-18 - - 454 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-10 (+) IW.274 28 R0S15 IW.274 10 R1S06 R12 RECTIFIER 2 DC CURRENT S011-19 - 367 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-10 (-) IW.274 29 R0S15 IW.274 30 R1S06 - - S011-20 - - 450 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - -
TB2-11 (+) IW.276 30 R0S15 IW.276 11 R1S06 R12 RECTIFIER 2 DC VOLTAGE S011-21 - 368 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-11 (-) IW.276 31 R0S15 IW.276 31 R1S06 - - S011-22 - - 451 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 - -
TB2-12 (+) IW.278 32 R0S15 IW.278 12 R1S06 R12 AC BUSBAR VOLTAGE S011-23 - 364 - AI - - - - - 0 to +11.4 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC
TB2-12 (-) IW.278 33 R0S15 IW.278 32 R1S06 - - S011-24 - - 447 - - - - - - to - - to - - - - - 0.912 9.029 11.035 11.309 0.950 10.395 11.495 11.78 0.866 9.480
TB2-13 (+) IW.280 37 R0S15 IW.280 13 R1S06 R12 TRACK FEEDER D16 DC CURRENT S011-25 - 372 - AI - - - - - 0 to +15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-13 (-) IW.280 38 R0S15 IW.280 33 R1S06 - - S011-26 - - 455 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-14 (+) IW.282 39 R0S15 IW.282 14 R1S06 R12 DC BUSBAR DC VOLTAGE S011-27 - 373 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-14 (-) IW.282 40 R0S15 IW.282 34 R1S06 - - S011-28 - - 456 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500 902.5 931 3.943 5.565
TB2-15 (+) IW.284 41 R0S15 IW.284 15 R1S06 R12 NEGATIVE DC BUSBAR DC RETURN CURRENT S011-29 - 374 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC
TB2-15 (-) IW.284 42 R0S15 IW.284 35 R1S06 - - S011-30 - - 457 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800 - -
TB2-16 (+) IW.286 43 R0S15 IW.286 16 R1S06 - SPARE S011-31 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S15 IW.286 36 R1S06 - - S011-32 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
S110-RD - - - - 0 - - - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - - - 0 - - - - - - - - - - - - - - - - - - - - - - - -
S112-BL - - - - 0 - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS12 [RS12] 122 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

RL-A - - - - 0 - - - - - - - - - - - - - - - - - - - - - - - - - - - -
0 R1S07 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
0 R1S07 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
IW.288 1 R1S07 - SPARE S010-33 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.288 21 R1S07 - - S010-34 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.290 2 R1S07 - SPARE S010-35 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.290 22 R1S07 - - S010-36 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.292 3 R1S07 - SPARE S010-37 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.292 23 R1S07 - - S010-38 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.294 4 R1S07 - SPARE S010-39 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.294 24 R1S07 - - S010-40 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.296 5 R1S07 - SPARE S010-41 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.296 25 R1S07 - - S010-42 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.298 6 R1S07 - SPARE S010-43 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.298 26 R1S07 - - S010-44 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.300 7 R1S07 - SPARE S010-45 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.300 27 R1S07 - - S010-46 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.302 8 R1S07 - SPARE S010-47 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.302 28 R1S07 - - S010-48 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.304 9 R1S07 - SPARE S010-49 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.304 29 R1S07 - - S010-50 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.306 10 R1S07 - SPARE S010-51 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.306 30 R1S07 - - S010-52 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.308 11 R1S07 - SPARE S010-53 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.308 31 R1S07 - - S010-54 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.310 12 R1S07 - SPARE S010-55 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.310 32 R1S07 - - S010-56 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.312 13 R1S07 - SPARE S010-57 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.312 33 R1S07 - - S010-58 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.314 14 R1S07 - SPARE S010-59 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.314 34 R1S07 - - S010-60 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.316 15 R1S07 - SPARE S010-61 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.316 35 R1S07 - - S010-62 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.318 16 R1S07 - SPARE S010-63 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.318 36 R1S07 - - S010-64 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S13 Q4.0 2 R1S02 R12 RING MAIN H04 VCB OPEN S010-3 - 25 - CO - - - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S13 Q4.1 3 R1S02 R12 RING MAIN H04 VCB CLOSE S010-4 - 26 - CO - - - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S13 Q4.2 6 R1S02 R12 RING MAIN H03 VCB OPEN S010-1 - 23 - CO - - - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S13 Q4.3 7 R1S02 R12 RING MAIN H03 VCB CLOSE S010-2 - 24 - CO - - - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S13 Q4.4 12 R1S02 R12 RECTIFIER FEEDER H01 VCB OPEN S010-5 - 19 - CO - - - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S13 Q4.5 13 R1S02 R12 RECTIFIER FEEDER H01 VCB CLOSE S010-6 - 20 - CO - - - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S13 Q4.6 16 R1S02 R12 RECTIFIER FEEDER D1 DCCB OPEN S010-7 - 35 - CO - - - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S13 Q4.7 17 R1S02 R12 RECTIFIER FEEDER D1 DCCB CLOSE S010-8 - 36 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02
M 20 R1S02
RL-09 Q5.0 15 R0S13 Q5.0 22 R1S02 R12 RECTIFIER FEEDER H02 VCB OPEN S010-9 - 21 - CO - - - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S13 Q5.1 23 R1S02 R12 RECTIFIER FEEDER H02 VCB CLOSE S010-10 - 22 - CO - - - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S13 Q5.2 26 R1S02 R12 RECTIFIER FEEDER D2 DCCB OPEN S010-11 - 37 - CO - - - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S13 Q5.3 27 R1S02 R12 RECTIFIER FEEDER D2 DCCB CLOSE S010-12 - 38 - CO - - - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S13 Q5.4 32 R1S02 R12 TRACK FEEDER D13 DCCB OPEN S010-13 - 41 - CO - - - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S13 Q5.5 33 R1S02 R12 TRACK FEEDER D13 DCCB CLOSE S010-14 - 42 - CO - - - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S13 Q5.6 36 R1S02 R12 TRACK FEEDER D13 LINE TEST CONTROL ON S010-17 - 245 - CO - - - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S13 Q5.7 37 R1S02 R12 TRACK FEEDER D13 LINE TEST CONTROL OFF S010-15 - 244 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02
M 40 R1S02
RL-17 Q6.0 26 R0S13 Q6.0 2 R1S03 R12 TRACK FEEDER D14 DCCB OPEN S010-18 - 50 - CO - - - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S13 Q6.1 3 R1S03 R12 TRACK FEEDER D14 DCCB CLOSE S010-19 - 51 - CO - - - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S13 Q6.2 6 R1S03 R12 TRACK FEEDER D14 LINE TEST CONTROL ON S010-22 - 247 - CO - - - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S13 Q6.3 7 R1S03 R12 TRACK FEEDER D14 LINE TEST CONTROL OFF S010-20 - 246 - CO - - - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S13 Q6.4 12 R1S03 R12 TRACK FEEDER D15 DCCB OPEN S010-23 - 58 - CO - - - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S13 Q6.5 13 R1S03 R12 TRACK FEEDER D15 DCCB CLOSE S010-24 - 59 - CO - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S13 Q6.6 16 R1S03 R12 TRACK FEEDER D15 LINE TEST CONTROL ON S010-26 - 249 - CO - - - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S13 Q6.7 17 R1S03 R12 TRACK FEEDER D15 LINE TEST CONTROL OFF S010-25 - 248 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19
M 20
RL-25 Q7.0 37 R0S13 Q7.0 22 R1S03 R12 TRACK FEEDER D16 DCCB OPEN S010-28 - 66 - CO - - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S13 Q7.1 23 R1S03 R12 TRACK FEEDER D16 DCCB CLOSE S010-29 - 67 - CO - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S13 Q7.2 26 R1S03 R12 TRACK FEEDER D16 LINE TEST CONTROL ON S010-32 - 251 - CO - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S13 Q7.3 27 R1S03 R12 TRACK FEEDER D16 LINE TEST CONTROL OFF S010-30 - 250 - CO - - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S13 Q7.4 32 R1S03 R12 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S010-33 - 75 - CO - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S13 Q7.5 33 R1S03 R12 DC COMMON EQUIPMENT D07 CONTACTOR CLOSE S010-34 - 76 - CO - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S13 Q7.6 36 R1S03 R12 DC COMMON EQUIPMENT D07 EARTH SW OVERRIDE ON S010-35 - 77 - CO - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S13 Q7.7 37 R1S03 R12 DC COMMON EQUIPMENT D07 EARTH SW OVERRIDE OFF S010-36 - ? - CO - - - - - - - - - - - - - - - - - - - - -
L+ 39
LM 40
FR0 FR0 34 R0S13 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE - - - - - - - - - - - - - - - - - - - - - - - - - -
32 CO
FR1 FR1 35 R0S13 FR1 - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE - - - - - - - - - - - - - - - - - - - - - - - - - -
32 CO
UE0 UE0 45 R0S14 UE0 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S14 UE1 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-33 Q8.0 4 R0S14 Q8.0 2 R1S04 - SPARE S010-37 - - - - - - - - - - - - - - - - - - - - - - - -
RL-34 Q8.1 5 R0S14 Q8.1 3 R1S04 - SPARE S010-38 - - - - - - - - - - - - - - - - - - - - - - - -
RL-35 Q8.2 6 R0S14 Q8.2 6 R1S04 R10/R12 295 SECTION BREAKER S13 DCCB OPEN S010-39 - 402 - CO - - - - - - - - - - - - - - - - - - - - -
RL-36 Q8.3 7 R0S14 Q8.3 7 R1S04 R10/R12 295 SECTION BREAKER S13 DCCB CLOSE S010-40 - 403 - CO - - - - - - - - - - - - - - - - - - - - -
RL-37 Q8.4 8 R0S14 Q8.4 12 R1S04 R10/R12 295 SECTION BREAKER S14 DCCB OPEN S010-41 - 408 - CO - - - - - - - - - - - - - - - - - - - - -
RL-38 Q8.5 9 R0S14 Q8.5 13 R1S04 R10/R12 295 SECTION BREAKER S14 DCCB CLOSE S010-42 - 409 - CO - - - - - - - - - - - - - - - - - - - - -
RL-39 Q8.6 10 R0S14 Q8.6 16 R1S04 R10/R12 090 SECTION BREAKER S15 DCCB OPEN S010-43 - 390 - CO - - - - - - - - - - - - - - - - - - - - -
RL-40 Q8.7 11 R0S14 Q8.7 17 R1S04 R10/R12 090 SECTION BREAKER S15 DCCB CLOSE S010-44 - 391 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S04
M 20 R1S04
RL-41 Q9.0 15 R0S14 Q9.0 22 R1S04 R10/R12 090 SECTION BREAKER S16 DCCB OPEN S010-45 - 396 - CO - - - - - - - - - - - - - - - - - - - - -
RL-42 Q9.1 16 R0S14 Q9.1 23 R1S04 R10/R12 090 SECTION BREAKER S16 DCCB CLOSE S010-46 - 397 - CO - - - - - - - - - - - - - - - - - - - - -
RL-43 Q9.2 17 R0S14 Q9.2 26 R1S04 - SPARE S010-47 - - - - - - - - - - - - - - - - - - - - - - - -
RL-44 Q9.3 18 R0S14 Q9.3 27 R1S04 - SPARE S010-48 - - - - - - - - - - - - - - - - - - - - - - - -
RL-45 Q9.4 19 R0S14 Q9.4 32 R1S04 R12 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - -
RL-46 Q9.5 20 R0S14 Q9.5 33 R1S04 R12 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - -
RL-47 Q9.6 21 R0S14 Q9.6 36 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS12 [RS12] 123 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

RL-48 Q9.7 22 R0S14 Q9.7 37 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -


L+ 39 R1S04
M 40 R1S04
RL-49 Q10.0 26 R0S14 Q10.0 2 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-50 Q10.1 27 R0S14 Q10.1 3 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-51 Q10.2 28 R0S14 Q10.2 6 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-52 Q10.3 29 R0S14 Q10.3 7 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-53 Q10.4 30 R0S14 Q10.4 12 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-54 Q10.5 31 R0S14 Q10.5 13 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-55 Q10.6 32 R0S14 Q10.6 16 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-56 Q10.7 33 R0S14 Q10.7 17 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S05
M 20 R1S05
RL-57 Q11.0 37 R0S14 Q11.0 22 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-58 Q11.1 38 R0S14 Q11.1 23 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-59 Q11.2 39 R0S14 Q11.2 26 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-60 Q11.3 40 R0S14 Q11.3 27 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-61 Q11.4 41 R0S14 Q11.4 32 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-62 Q11.5 42 R0S14 Q11.5 33 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-63 Q11.6 43 R0S14 Q11.6 36 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-64 Q11.7 44 R0S14 Q11.7 37 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S05
M 40 R1S05
FR0 FR0 34 R0S14 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE - - - - - - - - - - - - - - - - - - - - - - - - - -
32 CO
FR1 FR1 35 R0S14 FR1 - - - ENABLE CONTACT AND COMMON RETURN LINE ON THE - - - - - - - - - - - - - - - - - - - - - - - - - -
32 CO
UE0 UE0 45 R0S14 UE0 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S14 UE1 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS12 [RS12] 124 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS12 [RS12] 125 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS12 [RS12] 126 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -

Unrestricted 749775924.xlsx/RS12 [RS12] 127 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
NC C
8.600 9.071
NC C
7.125 9.025
NC C
7.125 9.025
NC C
6.333 7.521
NC C
8.600 9.071
NC C
4.524 5.429
NC C
9.025 9.310
NC C
6.333 7.521
NC C
8.600 9.071
NC C
4.524 5.429
NC C
9.025 9.310
NC C
10.483 10.743
NC C
8.600 9.071
NC C
9.025 9.310
NC C
6.333 7.238
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS12 [RS12] 128 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS12 [RS12] 129 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS12 [RS12] 130 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S7 I4.0 1 R0S02 R13 RING MAIN H03 CONTROL SELECTOR SWITCH S005-3 - 12 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-4 I4.1 5 R0S7 I4.1 2 R0S02 R13 RING MAIN H03 O/C EARTH FAULT TRIP S005-4 - 170 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-6 I4.2 6 R0S7 I4.2 3 R0S02 R13 RING MAIN H03 SOLKOR TRIP S005-5 - 173 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-8 I4.3 7 R0S7 I4.3 4 R0S02 - SPARE S005-6 - - - - - - - - - - - - - - - - - - - - - - - -
DI-10 I4.4 8 R0S7 I4.4 5 R0S02 R13 RING MAIN H03 OVERLOAD ALARM S005-7 - 171 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-12 I4.5 9 R0S7 I4.5 6 R0S02 R13 RING MAIN H03 NO VOLT RELAY S005-8 - 174 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-14 I4.6 10 R0S7 I4.6 7 R0S02 R13 RING MAIN H03 TRIP CCT SUPERVISION ALARM S005-9 - 176 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-16 I4.7 11 R0S7 I4.7 8 R0S02 - SPARE S005-10 - - - - - - - - - - - - - - - - - - - - - - - -
UM0 UM0 12 R0S7 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S7 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S7 I5.0 11 R0S02 - SPARE S005-11 - - - - - - - - - - - - - - - - - - - - - - - -
DI-20 I5.1 16 R0S7 I5.1 12 R0S02 - SPARE S005-12 - - - - - - - - - - - - - - - - - - - - - - - -
DI-22 I5.2 17 R0S7 I5.2 13 R0S02 - SPARE S005-13 - - - - - - - - - - - - - - - - - - - - - - - -
DI-24 I5.3 18 R0S7 I5.3 14 R0S02 R13 RING MAIN H04 CONTROL SELECTOR SWITCH S005-16 - 16 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-26 I5.4 19 R0S7 I5.4 15 R0S02 R13 RING MAIN H04 O/C EARTH FAULT TRIP S005-17 - 178 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-28 I5.5 20 R0S7 I5.5 16 R0S02 R13 RING MAIN H04 SOLKOR TRIP S005-18 - 181 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-30 I5.6 21 R0S7 I5.6 17 R0S02 R13 RING MAIN H04 PILOT WIRE ALARM S005-19 - 180 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-32 I5.7 22 R0S7 I5.7 18 R0S02 R13 RING MAIN H04 OVERLOAD ALARM S005-20 - 179 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S7 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S7 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S7 I6.0 21 R0S02 R13 RING MAIN H04 NO VOLT RELAY S005-21 - 182 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-36 I6.1 27 R0S7 I6.1 22 R0S02 R13 RING MAIN H04 TRIP CCT SUPERVISION ALARM S005-22 - 185 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-38 I6.2 28 R0S7 I6.2 23 R0S02 - SPARE S005-23 - - - - - - - - - - - - - - - - - - - - - - - -
DI-40 I6.3 29 R0S7 I6.3 24 R0S02 - SPARE S005-24 - - - - - - - - - - - - - - - - - - - - - - - -
DI-42 I6.4 30 R0S7 I6.4 25 R0S02 - SPARE S005-25 - - - - - - - - - - - - - - - - - - - - - - - -
DI-44 I6.5 31 R0S7 I6.5 26 R0S02 R13 RECTIFIER FEEDER H01 TRIP CCT SUPERVISION ALARM S005-26 - 203 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-46 I6.6 32 R0S7 I6.6 27 R0S02 R13 RECTIFIER FEEDER H01 CONTROL SELECTOR SWITCH S005-29 - 4 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-48 I6.7 33 R0S7 I6.7 28 R0S02 R13 RECTIFIER FEEDER H01 O/C EARTH FAULT TRIP S005-30 - 201 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S7 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S7 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S7 I7.0 31 R0S02 R13 RECTIFIER FEEDER H01 OVERLOAD TRIP S005-31 - 202 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-52 I7.1 38 R0S7 I7.1 32 R0S02 R13 RECT 1 TRANSFORMER PRESSURE RELIEF TRIP S005-32 - 227 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-54 I7.2 39 R0S7 I7.2 33 R0S02 R13 RECT 1 TRANSFORMER GAS/LIQUID LEVEL TRIP S005-33 - 228 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-56 I7.3 40 R0S7 I7.3 34 R0S02 R13 RECT 1 TRANSFORMER LIQUID LEVEL ALARM S005-34 - 229 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-58 I7.4 41 R0S7 I7.4 35 R0S02 R13 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S005-35 - 230 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-60 I7.5 42 R0S7 I7.5 36 R0S02 R13 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S005-36 - 231 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-62 I7.6 43 R0S7 I7.6 37 R0S02 R13 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S005-37 - 232 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-64 I7.7 44 R0S7 I7.7 38 R0S02 R13 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S005-38 - 233 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S7 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S7 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R13 RECTIFIER 1 FRAME EARTH TRIP S005-39 - 212 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R13 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S005-40 - 207 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R13 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S005-41 - 211 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R13 RECTIFIER 1 DIODE OVER TEMP ALARM S005-42 - 206 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R13 RECTIFIER 1 DIODE OVER TEMP TRIP S006-1 - 210 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R13 RECTIFIER 1 REVERSE CURRENT TRIP S006-2 - 208 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R13 RECTIFIER 1 SURGE ARRESTOR TRIP S006-3 - 209 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R13 RECTIFIER 1 FILTER CIRCUIT ALARM S006-4 - 205 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R13 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S006-5 - 204 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 - SPARE S006-6 - - - - - - - - - - - - - - - - - - - - - - - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R13 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S006-9 - 29 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R13 RECTIFIER FEEDER D1 TRIP CCT SUPERVISION ALARM S006-10 - 195 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 - SPARE S006-11 - - - - - - - - - - - - - - - - - - - - - - - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R13 RECTIFIER FEEDER H02 TRIP CCT SUPERVISION ALARM S006-12 - 216 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R13 RECTIFIER FEEDER H02 CONTROL SELECTOR SWITCH S006-15 - 8 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R13 RECTIFIER FEEDER H02 O/C EARTH FAULT TRIP S006-16 - 214 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R13 RECTIFIER FEEDER H02 OVERLOAD TRIP S006-17 - 215 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R13 RECT 2 TRANSFORMER PRESSURE RELIEF TRIP S006-18 - 236 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R13 RECT 2 TRANSFORMER GAS/LIQUID LEVEL TRIP S006-19 - 237 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R13 RECT 2 TRANSFORMER LIQUID LEVEL ALARM S006-20 - 238 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R13 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-21 - 239 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R13 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-22 - 240 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R13 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-23 - 241 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R13 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-24 - 242 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R13 RECTIFIER 2 FRAME EARTH TRIP S006-25 - 225 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R13 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-26 - 220 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R13 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S006-27 - 224 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R13 RECTIFIER 2 DIODE OVER TEMP ALARM S006-28 - 219 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R13 RECTIFIER 2 DIODE OVER TEMP TRIP S006-29 - 223 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R13 RECTIFIER 2 REVERSE CURRENT TRIP S006-30 - 221 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R13 RECTIFIER 2 SURGE ARRESTOR TRIP S006-31 - 222 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R13 RECTIFIER 2 FILTER CIRCUIT ALARM S006-32 - 218 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS13 [RS13] 131 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R13 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S006-33 - 217 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 - SPARE S006-34 - - - - - - - - - - - - - - - - - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R13 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S006-37 - 33 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R13 RECTIFIER FEEDER D2 TRIP CCT SUPERVISION ALARM S006-38 - 197 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R13 AUXILIARY TRANSFORMER 11KV SWITCH H5 S006-39 - 18 - SB OPEN OPEN CLOSED - - - - - YES 0 - - - - - - - - - NC NC
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S006-40 - 17 - - - - - - - - - - - - - - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R13 AUXILIARY TRANSFORMER 11KV SW H5 FUSE BLOWN TRIP S006-41 - 74 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R13 AUXILIARY TRANSFORMER TEMP HIGH ALARM S006-42 - 335 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R13 11KV BUSBAR UNDERVOLTAGE ALARM S007-3 - 172 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 - SPARE S007-4 - - - - - - - - - - - - - - - - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 - SPARE S007-5 - - - - - - - - - - - - - - - - - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 R13 TRACK FEEDER D31 CONTROL SELECTOR SWITCH S007-8 - 44 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 - SPARE S007-9 - - - - - - - - - - - - - - - - - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R13 TRACK FEEDER D31 INSTANT OVERCURRENT S007-10 - 337 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R13 TRACK FEEDER D31 RATE OF RISE TRIP S007-11 - 338 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R13 TRACK FEEDER D31 LINE TESTING S007-12 - 45 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R13 TRACK FEEDER D31 LINE IMPEDANCE LOW S007-13 - 339 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 R13 TRACK FEEDER D31 TRIP CCT SUPERVISION ALARM S007-14 - 340 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R13 TRACK FEEDER D31 LINE TEST CONTROL SELECTOR SWITCH S007-15 - 394 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 - SPARE S007-16 - 395 - - - - - - - - - - - - - - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R13 TRACK FEEDER D31 TRANSFER TRIP S007-17 - 46 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R13 TRACK FEEDER D32 CONTROL SELECTOR SWITCH S007-20 - 53 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 - SPARE S007-21 - - - - - - - - - - - - - - - - - - - - - - - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R13 TRACK FEEDER D32 INSTANT OVERCURRENT S007-22 - 341 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R13 TRACK FEEDER D32 RATE OF RISE TRIP S007-23 - 342 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R13 TRACK FEEDER D32 LINE TESTING S007-24 - 54 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R13 TRACK FEEDER D32 LINE IMPEDANCE LOW S007-25 - 343 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R13 TRACK FEEDER D32 TRIP CCT SUPERVISION ALARM S007-26 - 344 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R13 TRACK FEEDER D32 LINE TEST CONTROL SELECTOR SWITCH S007-27 - 396 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 - SPARE S007-28 - 397 - - - - - - - - - - - - - - - - - - - - - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 - SPARE S007-29 - - - - - - - - - - - - - - - - - - - - - - - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 - SPARE S007-30 - - - - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R0S05 - SPARE S007-31 - - - - - - - - - - - - - - - - - - - - - - - -
DI-196 I16.1 5 R0S10 I16.1 2 R0S05 R13 TRACK FEEDER D33 CONTROL SELECTOR SWITCH S007-34 - 61 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-198 I16.2 6 R0S10 I16.2 3 R0S05 - SPARE S007-35 - - - - - - - - - - - - - - - - - - - - - - - -
DI-200 I16.3 7 R0S10 I16.3 4 R0S05 R13 TRACK FEEDER D33 INSTANT OVERCURRENT S007-36 - 345 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-202 I16.4 8 R0S10 I16.4 5 R0S05 R13 TRACK FEEDER D33 RATE OF RISE TRIP S007-37 - 346 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-204 I16.5 9 R0S10 I16.5 6 R0S05 R13 TRACK FEEDER D33 LINE TESTING S007-38 - 62 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
DI-206 I16.6 10 R0S10 I16.6 7 R0S05 R13 TRACK FEEDER D33 LINE IMPEDANCE LOW S007-39 - 347 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-208 I16.7 11 R0S10 I16.7 8 R0S05 R13 TRACK FEEDER D33 TRIP CCT SUPERVISION ALARM S007-40 - 348 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S10 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R0S05 R13 TRACK FEEDER D33 LINE TEST CONTROL SELECTOR SWITCH S007-41 - 398 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-212 I17.1 16 R0S10 I17.1 12 R0S05 - SPARE S007-42 - 399 - - - - - - - - - - - - - - - - - - - - - -
DI-214 I17.2 17 R0S10 I17.2 13 R0S05 R13 TRACK FEEDER D33 TRANSFER TRIP S008-1 - 71 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-216 I17.3 18 R0S10 I17.3 14 R0S05 - SPARE S008-2 - - - - - - - - - - - - - - - - - - - - - - - -
DI-218 I17.4 19 R0S10 I17.4 15 R0S05 R13 TRACK FEEDER D34 CONTROL SELECTOR SWITCH S008-5 - 69 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-220 I17.5 20 R0S10 I17.5 16 R0S05 R13 TRACK FEEDER D34 INSTANT OVERCURRENT S008-6 - 349 - SB O/C RESET OVERCURRENT - - - - - NO 0 - - - - - - - - - NC C
DI-222 I17.6 21 R0S10 I17.6 17 R0S05 R13 TRACK FEEDER D34 RATE OF RISE TRIP S008-7 - 350 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-224 I17.7 22 R0S10 I17.7 18 R0S05 R13 TRACK FEEDER D34 LINE TESTING S008-8 - 70 - SB PROG COMPLETED IN PROGRESS - - - - - NO 0 - - - - - - - - - NC NC
UM1 UM1 23 R0S10 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R0S05 R13 TRACK FEEDER D34 LINE IMPEDANCE LOW S008-9 - 351 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-228 I18.1 27 R0S10 I18.1 22 R0S05 R13 TRACK FEEDER D34 TRIP CCT SUPERVISION ALARM S008-10 - 352 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-230 I18.2 28 R0S10 I18.2 23 R0S05 R13 TRACK FEEDER D34 LINE TEST CONTROL SELECTOR SWITCH S008-11 - 400 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-232 I18.3 29 R0S10 I18.3 24 R0S05 - SPARE S008-12 - 401 - - - - - - - - - - - - - - - - - - - - - -
DI-234 I18.4 30 R0S10 I18.4 25 R0S05 R13 DC COMMON EQUIPMENT D07 EARTH SW OVERRIDE S008-15 - 83 - SB ONOF OFF ON - - - - - NO 0 - - - - - - - - - NC NC
DI-236 I18.5 31 R0S10 I18.5 26 R0S05 R13 DC COMMON EQUIPMENT D07 FRAME EARTH TRIP S008-16 - 194 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-238 I18.6 32 R0S10 I18.6 27 R0S05 - SPARE S008-17 - 84 - - - - - - - - - - - - - - - - - - - - - -
DI-240 I18.7 33 R0S10 I18.7 28 R0S05 - SPARE S008-18 - 353 - - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S10 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R0S05 R13 DC COMMON EQUIPMENT D07 CONTROL SELECTOR SWITCH S008-19 - 82 - SB R/L LOCAL REMOTE - - - - - NO 0 - - - - - - - - - NC NC
DI-244 I19.1 38 R0S10 I19.1 32 R0S05 R13 DC COMMON EQUIPMENT D07 NEGATIVE VOLTS HIGH ALARM S008-20 - 354 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-246 I19.2 39 R0S10 I19.2 33 R0S05 - SPARE S008-21 - 355 - - - - - - - - - - - - - - - - - - - - - -
DI-248 I19.3 40 R0S10 I19.3 34 R0S05 R13 AC/DC SYSTEM MAINS FAILED ALARM S008-22 - 186 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-250 I19.4 41 R0S10 I19.4 35 R0S05 R13 AC/DC SYSTEM MAINS LOW VOLT ALARM S008-23 - 187 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-252 I19.5 42 R0S10 I19.5 36 R0S05 - SPARE S008-24 - - - - - - - - - - - - - - - - - - - - - - - -
DI-254 I19.6 43 R0S10 I19.6 37 R0S05 R13 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S008-25 - 188 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-256 I19.7 44 R0S10 I19.7 38 R0S05 R13 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM internal wiring - - - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM3 UM3 45 R0S10 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS13 [RS13] 132 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R0S06 R13 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S008-27 - 189 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-260 I20.1 5 R0S11 I20.1 2 R0S06 R13 AC/DC SYSTEM 11KV CONTROL VOLTAGE S008-28 - 191 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
DI-262 I20.2 6 R0S11 I20.2 3 R0S06 R13 AC/DC SYSTEM 750V CONTROL VOLTAGE S008-29 - 192 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
DI-264 I20.3 7 R0S11 I20.3 4 R0S06 R13 AC/DC SYSTEM 110V DC COMMON FEEDER S008-30 - 193 - SB FLTN NORMAL FAULT - - - - - NO 0 - - - - - - - - - NC C
DI-266 I20.4 8 R0S11 I20.4 5 R0S06 R13 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S008-31 - 190 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-268 I20.5 9 R0S11 I20.5 6 R0S06 R13 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S008-32 - 379 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-270 I20.6 10 R0S11 I20.6 7 R0S06 R13 COMMON EQUIPMENT FIRE PROTECTION ALARM S008-33 - 380 - SB OPER RESET OPERATED - - - - - NO 0 - - - - - - - - - NC C
DI-272 I20.7 11 R0S11 I20.7 8 R0S06 R13 COMMON EQUIPMENT INTRUDER ALARM S008-34 - 381 - SB OPNL NORMAL OPERATED - - - - - NO 0 - - - - - - - - - NC C
UM0 UM0 12 R0S11 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R0S06 R13 RING MAIN H03 VCB OPENED S005-1 - 9 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-276 I21.1 16 R0S11 I21.1 12 R0S06 R13 RING MAIN H03 VCB CLOSED S005-2 - 10 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-278 I21.2 17 R0S11 I21.2 13 R0S06 R13 RING MAIN H04 VCB OPENED S005-14 - 13 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-280 I21.3 18 R0S11 I21.3 14 R0S06 R13 RING MAIN H04 VCB CLOSED S005-15 - 14 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-282 I21.4 19 R0S11 I21.4 15 R0S06 R13 RECTIFIER FEEDER H01 VCB OPENED S005-27 - 1 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-284 I21.5 20 R0S11 I21.5 16 R0S06 R13 RECTIFIER FEEDER H01 VCB CLOSED S005-28 - 2 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-286 I21.6 21 R0S11 I21.6 17 R0S06 R13 RECTIFIER FEEDER D1 DCCB OPENED S006-7 - 27 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-288 I21.7 22 R0S11 I21.7 18 R0S06 R13 RECTIFIER FEEDER D1 DCCB CLOSED S006-8 - 28 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM1 UM1 23 R0S11 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S11 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R0S06 R13 RECTIFIER FEEDER H02 VCB OPENED S006-13 - 5 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-292 I22.1 27 R0S11 I22.1 22 R0S06 R13 RECTIFIER FEEDER H02 VCB CLOSED S006-14 - 6 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-294 I22.2 28 R0S11 I22.2 23 R0S06 R13 RECTIFIER FEEDER D2 DCCB OPENED S006-35 - 31 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-296 I22.3 29 R0S11 I22.3 24 R0S06 R13 RECTIFIER FEEDER D2 DCCB CLOSED S006-36 - 32 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-298 I22.4 30 R0S11 I22.4 25 R0S06 R13 DUMMY CB VCB POSITION internal wiring - - - DB CB1 DISCONNECT OPEN - - - - - NO 0 - - - - - - - - - C NC
DI-300 I22.5 31 R0S11 I22.5 26 R0S06 R13 DUMMY CB VCB POSITION internal wiring - - - DB CB1 - - CLOSED ERROR - - - NO 0 - - - - - - - - - - -
DI-302 I22.6 32 R0S11 I22.6 27 R0S06 R13 TRACK FEEDER D31 DCCB OPENED S007-6 - 39 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-304 I22.7 33 R0S11 I22.7 28 R0S06 R13 TRACK FEEDER D31 DCCB CLOSED S007-7 - 40 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM2 UM2 34 R0S11 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R0S06 R13 TRACK FEEDER D32 DCCB OPENED S007-18 - 48 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-308 I23.1 38 R0S11 I23.1 32 R0S06 R13 TRACK FEEDER D32 DCCB CLOSED S007-19 - 49 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-310 I23.2 39 R0S11 I23.2 33 R0S06 R13 TRACK FEEDER D33 DCCB OPENED S007-32 - 56 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-312 I23.3 40 R0S11 I23.3 34 R0S06 R13 TRACK FEEDER D33 DCCB CLOSED S007-33 - 57 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-314 I23.4 41 R0S11 I23.4 35 R0S06 R13 TRACK FEEDER D34 DCCB OPENED S008-3 - 64 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-316 I23.5 42 R0S11 I23.5 36 R0S06 R13 TRACK FEEDER D34 DCCB CLOSED S008-4 - 65 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
DI-318 I23.6 43 R0S11 I23.6 37 R0S06 R13 DC COMMON EQUIPMENT D07 CONTACTOR OPENED S008-13 - 80 - DB CB1 DISCONNECT OPEN - - - - - YES 0 - - - - - - - - - C NC
DI-320 I23.7 44 R0S11 I23.7 38 R0S06 R13 DC COMMON EQUIPMENT D07 CONTACTOR CLOSED S008-14 - 79 - DB CB1 - - CLOSED ERROR - - - YES 0 - - - - - - - - - - -
UM3 UM3 45 R0S11 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 R0S11 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS13 [RS13] 133 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

ZS1 ZS1 1 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R0S14 IW.256 1 R1S06 R13 TRACK FEEDER D31 DC CURRENT S090-02 - 369 - AI - - - - - 0 to 15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-1 (-) IW.256 5 R0S14 IW.256 21 R1S06 - - S090-01 - - 452 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-2 (+) IW.258 6 R0S14 IW.258 2 R1S06 R13 RECTIFIER FEEDER H01 CURRENT S090-04 - 360 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC
TB2-2 (-) IW.258 7 R0S14 IW.258 22 R1S06 - - S090-03 - - 443 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - -
TB2-3 (+) IW.260 8 R0S14 IW.260 3 R1S06 R13 RECTIFIER 1 DC CURRENT S090-06 - 365 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-3 (-) IW.260 9 R0S14 IW.260 23 R1S06 - - S090-05 - - 448 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - -
TB2-4 (+) IW.262 10 R0S14 IW.262 4 R1S06 R13 RECTIFIER 1 DC VOLTAGE S090-08 - 366 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-4 (-) IW.262 11 R0S14 IW.262 24 R1S06 - - S090-07 - - 449 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.500 931.000 - -
TB2-5 (+) IW.264 15 R0S14 IW.264 5 R1S06 R13 TRACK FEEDER D32 DC CURRENT S090-10 - 370 - AI - - - - - 0 to 15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-5 (-) IW.264 16 R0S14 IW.264 25 R1S06 - - S090-09 - - 453 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-6 (+) IW.266 17 R0S14 IW.266 6 R1S06 R13 RECTIFIER FEEDER H02 CURRENT S090-12 - 361 - AI - - - - - 0 to +10 0 to 120 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC
TB2-6 (-) IW.266 18 R0S14 IW.266 26 R1S06 - - S090-11 - - 444 - - - - - - to - - to - - - - - - - 6.667 7.917 - - 76 90.25 - -
TB2-7 (+) IW.268 19 R0S14 IW.268 7 R1S06 R13 RECTIFIER 2 DC CURRENT S090-14 - 367 - AI - - - - - 0 to +10 0 to 5250 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC
TB2-7 (-) IW.268 20 R0S14 IW.268 27 R1S06 - - S090-13 - - 450 - - - - - - to - - to - - - - - - - 4.762 5.714 - - 2375 2850 - -
TB2-8 (+) IW.270 21 R0S14 IW.270 8 R1S06 R13 RECTIFIER 2 DC VOLTAGE S090-16 - 368 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-8 (-) IW.270 22 R0S14 IW.270 28 R1S06 - - S090-15 - - 451 - - - - - - to - - to - - - - - - - 9.500 9.800 - - 902.5 931 - -
TB2-9 (+) IW.272 26 R0S14 IW.272 9 R1S06 R13 TRACK FEEDER D33 DC CURRENT S090-18 - 371 - AI - - - - - 0 to 15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-9 (-) IW.272 27 R0S14 IW.272 29 R1S06 - - S090-17 - - 454 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-10 (+) IW.274 28 R0S14 IW.274 10 R1S06 R13 RING MAIN H03 CURRENT S090-20 - 362 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-10 (-) IW.274 29 R0S14 IW.274 30 R1S06 - - S090-19 - - 445 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-11 (+) IW.276 30 R0S14 IW.276 11 R1S06 R13 RING MAIN H04 CURRENT S090-22 - 363 - AI - - - - - 0 to +10 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC
TB2-11 (-) IW.276 31 R0S14 IW.276 31 R1S06 - - S090-21 - - 446 - - - - - - to - - to - - - - - - - 7.500 9.500 - - 285 361 - -
TB2-12 (+) IW.278 32 R0S14 IW.278 12 R1S06 R13 AC BUSBAR VOLTAGE S090-24 - 364 - AI - - - - - 0 to 11.4 0 to 12.5 kV ac - - 1.0% 1 9.9 12.1 12.5 5.00% 5.00% 5.00% 5.00% C NC
TB2-12 (-) IW.278 33 R0S14 IW.278 32 R1S06 - - S090-23 - - 447 - - - - - - to - - to - - - - - 0.912 9.029 11.035 11.400 0.950 10.395 11.495 11.875 0.866 9.480
TB2-13 (+) IW.280 37 R0S14 IW.280 13 R1S06 R13 TRACK FEEDER D34 DC CURRENT S090-26 - 372 - AI - - - - - 0 to 15 -3500 to 7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC
TB2-13 (-) IW.280 38 R0S14 IW.280 33 R1S06 - - S090-25 - - 455 - - - - - - to - - to - - - - - 0.714 1.429 9.000 9.286 -2850 -2375 2520 2850 0.929 1.607
TB2-14 (+) IW.282 39 R0S14 IW.282 14 R1S06 R13 DC BUSBAR DC VOLTAGE S090-28 - 373 - AI - - - - - 0 to +10 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC
TB2-14 (-) IW.282 40 R0S14 IW.282 34 R1S06 - - S090-27 - - 456 - - - - - - to - - to - - - - - 4.150 5.300 9.500 9.800 394.250 556.500 902.5 931 3.943 5.565
TB2-15 (+) IW.284 41 R0S14 IW.284 15 R1S06 R13 NEGATIVE DC BUSBAR DC RETURN CURRENT S090-30 - 374 - AI - - - - - 0 to +20 0 to 10500 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC
TB2-15 (-) IW.284 42 R0S14 IW.284 35 R1S06 - - S090-29 - - 457 - - - - - - to - - to - - - - - - - 6.667 7.619 - - 3325 3800 - -
TB2-16 (+) IW.286 43 R0S14 IW.286 16 R1S06 - SPARE S090-32 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
TB2-16 (-) IW.286 44 R0S14 IW.286 36 R1S06 - - S090-31 - - - - - - - - - to - - to - - - - - - - - - - - - - - -
S110-RD - - R0S14 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - R0S14 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
S112-BL - - R0S14 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS13 [RS13] 134 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

RL-A - - R0S14 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
IW.288 1 R1S07 - SPARE - - - - AI - - - - - -20 to +20 C NC
IW.288 21 R1S07 - - - - - - - - - - - - to - - -
IW.290 2 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.290 22 R1S07 - - - - - - - - - - - - to - - -
IW.292 3 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.292 23 R1S07 - - - - - - - - - - - - to - - -
IW.294 4 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.294 24 R1S07 - - - - - - - - - - - - to - - -
IW.296 5 R1S07 - SPARE - - - - AI - - - - - -20 to +20 C NC
IW.296 25 R1S07 - - - - - - - - - - - - to - - -
IW.298 6 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.298 26 R1S07 - - - - - - - - - - - - to - - -
IW.300 7 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.300 27 R1S07 - - - - - - - - - - - - to - - -
IW.302 8 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.302 28 R1S07 - - - - - - - - - - - - to - - -
IW.304 9 R1S07 - SPARE - - - - AI - - - - - -20 to +20 C NC
IW.304 29 R1S07 - - - - - - - - - - - - to - - -
IW.306 10 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.306 30 R1S07 - - - - - - - - - - - - to - - -
IW.308 11 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.308 31 R1S07 - - - - - - - - - - - - to - - -
IW.310 12 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.310 32 R1S07 - - - - - - - - - - - - to - - -
IW.312 13 R1S07 - SPARE - - - - AI - - - - - -20 to +20 C NC
IW.312 33 R1S07 - - - - - - - - - - - - to - - -
IW.314 14 R1S07 - SPARE - - - - AI - - - - - 0 to +10 C NC
IW.314 34 R1S07 - - - - - - - - - - - - to - - -
IW.316 15 R1S07 - SPARE - - - - AI - - - - - 0 to +20 C NC
IW.316 35 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.318 16 R1S07 - SPARE - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
IW.318 36 R1S07 - - - - - - - - - - - - to - - to - - - - - - - - - - - - - - -
- R1S07 - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- R1S07 - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R0S12 Q4.0 2 R1S02 R13 RING MAIN H03 VCB OPEN S010-1 - 23 107 CO - - - - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R0S12 Q4.1 3 R1S02 R13 RING MAIN H03 VCB CLOSE S010-2 - 24 107 CO - - - - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R0S12 Q4.2 6 R1S02 R13 RING MAIN H04 VCB OPEN S010-3 - 25 - CO - - - - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R0S12 Q4.3 7 R1S02 R13 RING MAIN H04 VCB CLOSE S010-4 - 26 - CO - - - - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R0S12 Q4.4 12 R1S02 R13 RECTIFIER FEEDER H01 VCB OPEN S010-5 - 19 - CO - - - - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R0S12 Q4.5 13 R1S02 R13 RECTIFIER FEEDER H01 VCB CLOSE S010-6 - 20 - CO - - - - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R0S12 Q4.6 16 R1S02 R13 RECTIFIER FEEDER D1 DCCB OPEN S010-7 - 35 - CO - - - - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R0S12 Q4.7 17 R1S02 R13 RECTIFIER FEEDER D1 DCCB CLOSE S010-8 - 36 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S02
M 20 R1S02
RL-09 Q5.0 15 R0S12 Q5.0 22 R1S02 R13 RECTIFIER FEEDER H02 VCB OPEN S010-9 - 21 - CO - - - - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R0S12 Q5.1 23 R1S02 R13 RECTIFIER FEEDER H02 VCB CLOSE S010-10 - 22 - CO - - - - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R0S12 Q5.2 26 R1S02 R13 RECTIFIER FEEDER D2 DCCB OPEN S010-11 - 37 - CO - - - - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R0S12 Q5.3 27 R1S02 R13 RECTIFIER FEEDER D2 DCCB CLOSE S010-12 - 38 - CO - - - - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R0S12 Q5.4 32 R1S02 R13 TRACK FEEDER D31 DCCB OPEN S010-13 - 41 - CO - - - - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R0S12 Q5.5 33 R1S02 R13 TRACK FEEDER D31 DCCB CLOSE S010-14 - 42 - CO - - - - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R0S12 Q5.6 36 R1S02 R13 TRACK FEEDER D31 LINE TEST CONTROL ON S010-16 - 385 - CO - - - - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R0S12 Q5.7 37 R1S02 R13 TRACK FEEDER D31 LINE TEST CONTROL OFF S010-15 - 386 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S02
M 40 R1S02
RL-17 Q6.0 26 R0S12 Q6.0 2 R1S03 R13 TRACK FEEDER D32 DCCB OPEN S010-17 - 50 - CO - - - - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R0S12 Q6.1 3 R1S03 R13 TRACK FEEDER D32 DCCB CLOSE S010-18 - 51 - CO - - - - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R0S12 Q6.2 6 R1S03 R13 TRACK FEEDER D32 LINE TEST CONTROL ON S010-20 - 387 - CO - - - - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R0S12 Q6.3 7 R1S03 R13 TRACK FEEDER D32 LINE TEST CONTROL OFF S010-19 - 388 - CO - - - - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R0S12 Q6.4 12 R1S03 R13 TRACK FEEDER D33 DCCB OPEN S010-21 - 58 - CO - - - - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R0S12 Q6.5 13 R1S03 R13 TRACK FEEDER D33 DCCB CLOSE S010-22 - 59 - CO - - - - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R0S12 Q6.6 16 R1S03 R13 TRACK FEEDER D33 LINE TEST CONTROL ON S010-24 - 389 - CO - - - - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R0S12 Q6.7 17 R1S03 R13 TRACK FEEDER D33 LINE TEST CONTROL OFF S010-23 - 390 - CO - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S03
M 20 R1S03
RL-25 Q7.0 37 R0S12 Q7.0 22 R1S03 R13 TRACK FEEDER D34 DCCB OPEN S010-25 - 66 - CO - - - - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R0S12 Q7.1 23 R1S03 R13 TRACK FEEDER D34 DCCB CLOSE S010-26 - 67 - CO - - - - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R0S12 Q7.2 26 R1S03 R13 TRACK FEEDER D34 LINE TEST CONTROL ON S010-28 - 391 - CO - - - - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R0S12 Q7.3 27 R1S03 R13 TRACK FEEDER D34 LINE TEST CONTROL OFF S010-27 - 392 - CO - - - - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R0S12 Q7.4 32 R1S03 R13 DC COMMON EQUIPMENT D07 CONTACTOR OPEN S010-29 - 75 - CO - - - - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R0S12 Q7.5 33 R1S03 R13 DC COMMON EQUIPMENT D07 CONTACTOR CLOSE S010-30 - 76 - CO - - - - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R0S12 Q7.6 36 R1S03 R13 DC COMMON EQUIPMENT D07 EARTH SW OVERRIDE ON S010-31 - 77 - CO - - - - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R0S12 Q7.7 37 R1S03 R13 DC COMMON EQUIPMENT D07 EARTH SW OVERRIDE OFF S010-32 - ? - CO - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S03
M 40 R1S03
FR0 FR0 34 R0S12 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ONAND
THECOMMON
32 CO
FR1 FR1 35 R0S12 FR1 - - - ENABLE CONTACT RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 UE0 31 R1S03 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 UE1 35 R1S03 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 R0S13 ZS1 R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 R0S13 ZS2 R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - -
RL-33 Q8.0 4 R0S13 Q8.0 2 R1S04 R13 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT BIT) internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - -
RL-34 Q8.1 5 R0S13 Q8.1 3 R1S04 R13 DUMMY CB VCB OPEN/CLOSE (LEAST SIGINIFICANT internal wiring - - - CO - - - - - - - - - - - - - - - - - - - - -
RL-35 Q8.2 6 R0S13 Q8.2 6 R1S04 - BIT) SPARE S010-35 - - - - - - - - - - - - - - - - - - - - - - - -
RL-36 Q8.3 7 R0S13 Q8.3 7 R1S04 - SPARE S010-36 - - - - - - - - - - - - - - - - - - - - - - - -
RL-37 Q8.4 8 R0S13 Q8.4 12 R1S04 - SPARE S010-37 - - - - - - - - - - - - - - - - - - - - - - - -
RL-38 Q8.5 9 R0S13 Q8.5 13 R1S04 - SPARE S010-38 - - - - - - - - - - - - - - - - - - - - - - - -
RL-39 Q8.6 10 R0S13 Q8.6 16 R1S04 - SPARE S010-39 - - - - - - - - - - - - - - - - - - - - - - - -
RL-40 Q8.7 11 R0S13 Q8.7 17 R1S04 - SPARE S010-40 - - - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S04
M 20 R1S04
RL-41 Q9.0 15 R0S13 Q9.0 22 R1S04 - SPARE S010-41 - - - - - - - - - - - - - - - - - - - - - - - -
RL-42 Q9.1 16 R0S13 Q9.1 23 R1S04 - SPARE S010-42 - - - - - - - - - - - - - - - - - - - - - - - -
RL-43 Q9.2 17 R0S13 Q9.2 26 R1S04 - SPARE S010-43 - - - - - - - - - - - - - - - - - - - - - - - -
RL-44 Q9.3 18 R0S13 Q9.3 27 R1S04 - SPARE S010-44 - - - - - - - - - - - - - - - - - - - - - - - -
RL-45 Q9.4 19 R0S13 Q9.4 32 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS13 [RS13] 135 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module (Description Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA) Values Of-State Value
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or
Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L
No. No. (sec)

RL-46 Q9.5 20 R0S13 Q9.5 33 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -


RL-47 Q9.6 21 R0S13 Q9.6 36 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-48 Q9.7 22 R0S13 Q9.7 37 R1S04 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S04
M 40 R1S04
RL-49 Q10.0 26 R0S13 Q10.0 2 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-50 Q10.1 27 R0S13 Q10.1 3 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-51 Q10.2 28 R0S13 Q10.2 6 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-52 Q10.3 29 R0S13 Q10.3 7 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-53 Q10.4 30 R0S13 Q10.4 12 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-54 Q10.5 31 R0S13 Q10.5 13 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-55 Q10.6 32 R0S13 Q10.6 16 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-56 Q10.7 33 R0S13 Q10.7 17 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 19 R1S05
M 20 R1S05
RL-57 Q11.0 37 R0S13 Q11.0 22 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-58 Q11.1 38 R0S13 Q11.1 23 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-59 Q11.2 39 R0S13 Q11.2 26 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-60 Q11.3 40 R0S13 Q11.3 27 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-61 Q11.4 41 R0S13 Q11.4 32 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-62 Q11.5 42 R0S13 Q11.5 33 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-63 Q11.6 43 R0S13 Q11.6 36 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
RL-64 Q11.7 44 R0S13 Q11.7 37 R1S05 - SPARE - - - - - - - - - - - - - - - - - - - - - - - - -
L+ 39 R1S05
M 40 R1S05
FR0 FR0 34 R0S13 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ONAND
THECOMMON
32 CO
FR1 FR1 35 R0S13 FR1 - - - ENABLE CONTACT RETURN LINE - - - - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 R0S13 UE0 31 - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 R0S13 UE1 35 - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS13 [RS13] 136 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS13 [RS13] 137 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS13 [RS13] 138 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -

Unrestricted 749775924.xlsx/RS13 [RS13] 139 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
NC C
8.600 9.071
NC C
6.333 7.521
NC C
4.524 5.429
NC C
9.025 9.310
NC C
8.600 9.071
NC C
6.333 7.521
NC C
4.524 5.429
NC C
9.025 9.310
NC C
8.600 9.071
NC C
7.125 9.025
NC C
7.125 9.025
NC C
10.483 10.830
NC C
8.600 9.071
NC C
9.025 9.310
NC C
6.333 7.238
- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS13 [RS13] 140 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
NC C
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS13 [RS13] 141 Printed on: 04/30/2024


Alarm Priority

Alm 2 or Alm 3 or
H HH

- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -
- -
- -
- -
- -

- -
- -
- -
- -

Unrestricted 749775924.xlsx/RS13 [RS13] 142 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-2 I4.0 4 R0S07 I4.0 1 R0S02 R14 MAIN INCOMER H05 (R14VB01) CONTROL SELECTOR SWITCH S005-3 - 1004 1005 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-4 I4.1 5 R0S07 I4.1 2 R0S02 R14 MAIN INCOMER H05 (R14VB01) O/C EARTH FAULT TRIP S005-4 - 1006 1007 SB - - - NO 0 - - - - - - - - - NC C - -
DI-6 I4.2 6 R0S07 I4.2 3 R0S02 R14 MAIN INCOMER H05 (R14VB01) REVERSE POWER TRIP S005-5 - 1006 1008 SB - - - NO 0 - - - - - - - - - NC C - -
DI-8 I4.3 7 R0S07 I4.3 4 R0S02 R14 MAIN INCOMER H05 (R14VB01) INTERTRIP S005-6 - 1006 1009 SB - - - NO 0 - - - - - - - - - NC C - -
DI-10 I4.4 8 R0S07 I4.4 5 R0S02 - SPARE S005-7 - - - - - - - - - - - - - - - - - - - - -
DI-12 I4.5 9 R0S07 I4.5 6 R0S02 - SPARE - - - - - - kWh NO - - - - - - - - - - - - - -
DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R14 RING MAIN H01 (R14VB20) (FUTURE) CONTROL SELECTOR SWITCH S005-13 - 1017 1018 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R14 RING MAIN H01 (R14VB20) (FUTURE) O/C EARTH FAULT TRIP S005-14 - 1019 1020 SB - - - NO 0 - - - - - - - - - NC C - -
UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R14 RING MAIN H01 (R14VB20) (FUTURE) SOLKOR TRIP S005-15 - 1019 1021 SB - - - NO 0 - - - - - - - - - NC C - -
DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R14 RING MAIN H01 (R14VB20) (FUTURE) OVERLOAD ALARM S005-16 - 1019 1022 SB - - - NO 0 - - - - - - - - - NC C - -
DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R14 MAIN INCOMER H05 (R14VB01) TRIP CIRCUIT SUPERVISION S005-8 - 1010 1011 SB - - - NO 0 - - - - - - - - - NC C - -
DI-24 I5.3 18 R0S07 I5.3 14 R0S02 R14 RING MAIN H01 (R14VB20) (FUTURE) TRIP CCT SUPERVISION ALARM S005-18 - 1023 1024 SB - - - NO 0 - - - - - - - - - NC C - -
DI-26 I5.4 19 R0S07 I5.4 15 R0S02 R14 RING MAIN H03 (R14VB21) (TO R16) CONTROL SELECTOR SWITCH S005-23 - 1032 1033 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-28 I5.5 20 R0S07 I5.5 16 R0S02 R14 RING MAIN H03 (R14VB21) (TO R16) O/C EARTH FAULT TRIP S005-24 - 1034 1035 SB - - - NO 0 - - - - - - - - - NC C - -
DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R14 RING MAIN H03 (R14VB21) (TO R16) SOLKOR TRIP S005-25 - 1034 1036 SB - - - NO 0 - - - - - - - - - NC C - -
DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R14 RING MAIN H03 (R14VB21) (TO R16) OVERLOAD ALARM S005-26 - 1034 1037 SB - - - NO 0 - - - - - - - - - NC C - -
UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R14 RING MAIN H03 (R14VB21) (TO R16) PILOT WIRE ALARM S005-27 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R14 RING MAIN H03 (R14VB21) (TO R16) TRIP CCT SUPERVISION ALARM S005-28 - 1038 1039 SB - - - NO 0 - - - - - - - - - NC C - -
DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R14 RING MAIN H08 (R14VB22) (TO R15) CONTROL SELECTOR SWITCH S005-33 - 1047 1048 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R14 RING MAIN H08 (R14VB22) (TO R15) O/C EARTH FAULT TRIP S005-34 - 1049 1050 SB - - - NO 0 - - - - - - - - - NC C - -
DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R14 RING MAIN H08 (R14VB22) (TO R15) SOLKOR TRIP S005-35 - 1049 1051 SB - - - NO 0 - - - - - - - - - NC C - -
DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R14 RING MAIN H08 (R14VB22) (TO R15) OVERLOAD ALARM S005-36 - 1049 1052 SB - - - NO 0 - - - - - - - - - NC C - -
DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R14 RING MAIN H08 (R14VB22) (TO R15) PILOT WIRE ALARM S005-37 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R14 RING MAIN H08 (R14VB22) (TO R15) TRIP CCT SUPERVISION ALARM S005-38 - 1053 1054 SB - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R14 RING MAIN H10 (R14VB23) (TO R08) CONTROL SELECTOR SWITCH S006-3 - 1062 1063 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R14 RING MAIN H10 (R14VB23) (TO R08) O/C EARTH FAULT TRIP S006-4 - 1064 1065 SB - - - NO 0 - - - - - - - - - NC C - -
DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R14 RING MAIN H10 (R14VB23) (TO R08) SOLKOR TRIP S006-5 - 1064 1066 SB - - - NO 0 - - - - - - - - - NC C - -
DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R14 RING MAIN H10 (R14VB23) (TO R08) OVERLOAD ALARM S006-6 - 1064 1067 SB - - - NO 0 - - - - - - - - - NC C - -
DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R14 RING MAIN H10 (R14VB23) (TO R08) PILOT WIRE ALARM S006-7 - 1064 1068 SB - - - NO 0 - - - - - - - - - NC C - -
DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R14 RING MAIN H10 (R14VB23) (TO R08) TRIP CCT SUPERVISION ALARM S006-8 - 1069 1070 SB - - - NO 0 - - - - - - - - - NC C - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R14 RING MAIN H12 (R14VB24) (FUTURE) CONTROL SELECTOR SWITCH S006-13 - 1078 1079 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R14 RING MAIN H12 (R14VB24) (FUTURE) O/C EARTH FAULT TRIP S006-14 - 1080 1081 SB - - - NO 0 - - - - - - - - - NC C - -
UM3 UM3 45 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R14 RING MAIN H12 (R14VB24) (FUTURE) SOLKOR TRIP S006-15 - 1080 1082 SB - - - NO 0 - - - - - - - - - NC C - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R14 RING MAIN H12 (R14VB24) (FUTURE) OVERLOAD ALARM S006-16 - 1080 1083 SB - - - NO 0 - - - - - - - - - NC C - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R14 RING MAIN H12 (R14VB24) (FUTURE) PILOT WIRE ALARM S006-17 - 1080 1084 SB - - - NO 0 - - - - - - - - - NC C - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R14 RING MAIN H12 (R14VB24) (FUTURE) TRIP CCT SUPERVISION ALARM S006-18 - 1085 1086 SB - - - NO 0 - - - - - - - - - NC C - -
DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R14 RING MAIN H07 (R14VB02) (FUTURE) CONTROL SELECTOR SWITCH S006-23 - 1093 1094 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R14 RING MAIN H07 (R14VB02) (FUTURE) O/C EARTH FAULT TRIP S006-24 - 1095 1096 SB - - - NO 0 - - - - - - - - - NC C - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R14 RING MAIN H07 (R14VB02) (FUTURE) REVERSE POWER TRIP S006-25 - 1095 1097 SB - - - NO 0 - - - - - - - - - NC C - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R14 RING MAIN H07 (R14VB02) (FUTURE) INTERTRIP S006-26 - 1095 1098 SB - - - NO 0 - - - - - - - - - NC C - -
UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R14 AUTO CHANGEOVER PANEL INHIBIT ALARM S006-28 - 4109 4110 SB - - - NO 0 - - - - - - - - - NC C - -
DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R14 RING MAIN H07 (R14VB02) (FUTURE) TRIP CCT SUPERVISION ALARM S006-27 - 1099 1100 SB - - - NO 0 - - - - - - - - - NC C - -
DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R14 BUS SECTION H06 (R14VB11) CONTROL SELECTOR SWITCH S006-33 - 2004 2005 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R14 BUS SECTION H06 (R14VB11) O/C EARTH FAULT TRIP S006-34 - 2006 2007 SB - - - NO 0 - - - - - - - - - NC C - -
DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R14 AC BUSBAR (R14VB70) LHS UNDERVOLTAGE ALARM S006-35 - 2008 2009 SB - - - NO 0 - - - - - - - - - NC C - -
DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R14 AC BUSBAR (R14VB71) RHS UNDERVOLTAGE ALARM S006-36 - 2010 2011 SB - - - NO 0 - - - - - - - - - NC C - -
DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R14 AUTO CHANGEOVER PANEL ENABLE SELECTOR SWITCH S006-37 - 1105 1106 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R14 AUTO CHANGEOVER PANEL STATUS S006-38 - 1107 1108 SB - - - NO 0 - - - - - - - - - NC C - -
UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R14 RECTIFIER FEEDER H02 (R14VB50) CONTROL SELECTOR SWITCH S007-3 - 2019 2020 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R14 RECTIFIER FEEDER H02 (R14VB50) O/C EARTH FAULT TRIP S007-4 - 2021 2022 SB - - - NO 0 - - - - - - - - - NC C - -
DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R14 RECTIFIER FEEDER H02 (R14VB50) OVERLOAD TRIP S007-5 - 2021 2023 SB - - - NO 0 - - - - - - - - - NC C - -
DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R14 RECTIFIER FEEDER H02 (R14VB50) TRIP CCT SUPERVISION ALARM S007-6 - 2031 2032 SB - - - NO 0 - - - - - - - - - NC C - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R14 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S007-7 - 2021 2024 SB - - - NO 0 - - - - - - - - - NC C - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R14 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S007-8 - 2021 2025 SB - - - NO 0 - - - - - - - - - NC C - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R14 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S007-11 - 2021 2026 SB - - - NO 0 - - - - - - - - - NC C - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R14 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S007-12 - 2021 2027 SB - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R14 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S007-13 - 2021 2028 SB - - - NO 0 - - - - - - - - - NC C - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R14 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S007-14 - 2021 2029 SB - - - NO 0 - - - - - - - - - NC C - -
DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R14 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S007-15 - 2021 2030 SB - - - NO 0 - - - - - - - - - NC C - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R14 RECTIFIER 1 FRAME EARTH ALARM S007-16 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R14 RECTIFIER 1 FRAME EARTH TRIP S007-17 - 2033 2034 SB - - - NO 0 - - - - - - - - - NC C - -
DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R14 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S007-18 - 2035 2036 SB - - - NO 0 - - - - - - - - - NC C - -
DI-126 I11.6 43 R0S08 I11.6 37 R0S03 R14 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S007-21 - 2037 2038 SB - - - NO 0 - - - - - - - - - NC C - -
DI-128 I11.7 44 R0S08 I11.7 38 R0S03 R14 RECTIFIER 1 DIODE OVER TEMP ALARM S007-22 - 2039 2040 SB - - - NO 0 - - - - - - - - - NC C - -
UM3 UM3 45 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS14 [RS14] 143 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 R14 RECTIFIER 1 DIODE OVER TEMP TRIP S007-23 - 2041 2042 SB - - - NO 0 - - - - - - - - - NC C - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 R14 RECTIFIER 1 REVERSE CURRENT TRIP S007-24 - 2043 2044 SB - - - NO 0 - - - - - - - - - NC C - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 R14 RECTIFIER FEEDER D1 REVERSE CURRENT TRIP S013-6 - 3043 3044 SB - - - NO 0 - - - - - - - - - NC C - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 R14 RECTIFIER 1 SURGE ARRESTOR TRIP S007-26 - 2045 2046 SB - - - NO 0 - - - - - - - - - NC C - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 R14 RECTIFIER 1 FILTER CIRCUIT ALARM S007-27 - 2047 2048 SB - - - NO 0 - - - - - - - - - NC C - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 R14 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S007-28 - 2049 2050 SB - - - NO 0 - - - - - - - - - NC C - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 R14 RECTIFIER FEEDER H04 (R14VB51) CONTROL SELECTOR SWITCH S007-33 - 2056 2057 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 R14 RECTIFIER FEEDER H04 (R14VB51) O/C EARTH FAULT TRIP S007-34 - 2058 2059 SB - - - NO 0 - - - - - - - - - NC C - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 R14 RECTIFIER FEEDER H04 (R14VB51) OVERLOAD TRIP S007-35 - 2058 2060 SB - - - NO 0 - - - - - - - - - NC C - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 R14 RECTIFIER FEEDER H04 (R14VB51) TRIP CCT SUPERVISION ALARM S007-36 - 2070 2069 SB - - - NO 0 - - - - - - - - - NC C - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 R14 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S007-37 - 2058 2061 SB - - - NO 0 - - - - - - - - - NC C - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 R14 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S007-38 - 2058 2062 SB - - - NO 0 - - - - - - - - - NC C - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 R14 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S008-1 - 2058 2063 SB - - - NO 0 - - - - - - - - - NC C - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 R14 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S008-2 - 2058 2064 SB - - - NO 0 - - - - - - - - - NC C - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 R14 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S008-3 - 2058 2065 SB - - - NO 0 - - - - - - - - - NC C - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 R14 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S008-4 - 2058 2066 SB - - - NO 0 - - - - - - - - - NC C - -
UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 R14 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S008-5 - 2058 2067 SB - - - NO 0 - - - - - - - - - NC C - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 R14 RECTIFIER 2 FRAME EARTH ALARM S008-6 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 R14 RECTIFIER 2 FRAME EARTH TRIP S008-7 - 2070 2071 SB - - - NO 0 - - - - - - - - - NC C - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 R14 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S008-8 - 2072 2073 SB - - - NO 0 - - - - - - - - - NC C - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 R14 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S008-11 - 2074 2075 SB - - - NO 0 - - - - - - - - - NC C - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 R14 RECTIFIER 2 DIODE OVER TEMP ALARM S008-12 - 2076 2077 SB - - - NO 0 - - - - - - - - - NC C - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R14 RECTIFIER 2 DIODE OVER TEMP TRIP S008-13 - 2078 2079 SB - - - NO 0 - - - - - - - - - NC C - -
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R14 RECTIFIER 2 REVERSE CURRENT TRIP S008-14 - 2080 2081 SB - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R14 RECTIFIER FEEDER D2 REVERSE CURRENT TRIP S008-15 - 3052 3053 SB - - - NO 0 - - - - - - - - - NC C - -
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R14 RECTIFIER 2 SURGE ARRESTOR TRIP S008-16 - 2082 2083 SB - - - NO 0 - - - - - - - - - NC C - -
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R14 RECTIFIER 2 FILTER CIRCUIT ALARM S008-17 - 2084 2085 SB - - - NO 0 - - - - - - - - - NC C - -
DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R14 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S008-18 - 2086 2087 SB - - - NO 0 - - - - - - - - - NC C - -
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R14 RECTIFIER FEEDER H09 (R14VB52) CONTROL SELECTOR SWITCH S008-23 - 3004 3005 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R14 RECTIFIER FEEDER H09 (R14VB52) O/C EARTH FAULT TRIP S008-24 - 3006 3007 SB - - - NO 0 - - - - - - - - - NC C - -
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R14 RECTIFIER FEEDER H09 (R14VB52) OVERLOAD TRIP S008-25 - 3006 3008 SB - - - NO 0 - - - - - - - - - NC C - -
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R14 RECTIFIER FEEDER H09 (R14VB52) TRIP CCT SUPERVISION ALARM S008-26 - 3016 3017 SB - - - NO 0 - - - - - - - - - NC C - -
UM3 UM3 45 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R1S02 R14 RECT 3 TRANSFORMER SUDDEN PRESSURE TRIP S008-27 - 3006 3009 SB - - - NO 0 - - - - - - - - - NC C - -
DI-196 I16.1 5 R0S10 I16.1 2 R1S02 R14 RECT 3 TRANSFORMER PRESSURE RELIEF ALARM S008-28 - 3006 3010 SB - - - NO 0 - - - - - - - - - NC C - -
DI-198 I16.2 6 R0S10 I16.2 3 R1S02 R14 RECT 3 TRANSFORMER LIQUID LEVEL LOW TRIP S008-31 - 3006 3011 SB - - - NO 0 - - - - - - - - - NC C - -
DI-200 I16.3 7 R0S10 I16.3 4 R1S02 R14 RECT 3 TRANSFORMER WINDING TEMP HIGH ALARM S008-32 - 3006 3012 SB - - - NO 0 - - - - - - - - - NC C - -
DI-202 I16.4 8 R0S10 I16.4 5 R1S02 R14 RECT 3 TRANSFORMER WINDING TEMP HIGH TRIP S008-33 - 3006 3013 SB - - - NO 0 - - - - - - - - - NC C - -
DI-204 I16.5 9 R0S10 I16.5 6 R1S02 R14 RECT 3 TRANSFORMER LIQUID TEMP HIGH ALARM S008-34 - 3006 3014 SB - - - NO 0 - - - - - - - - - NC C - -
DI-206 I16.6 10 R0S10 I16.6 7 R1S02 R14 RECT 3 TRANSFORMER LIQUID TEMP HIGH TRIP S008-35 - 3006 3015 SB - - - NO 0 - - - - - - - - - NC C - -
DI-208 I16.7 11 R0S10 I16.7 8 R1S02 R14 RECTIFIER 3 FRAME EARTH ALARM S008-36 - - - SB - - - NO 0 - - - - - - - - - NC C - -
UM0 UM0 12 R0S10 - 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S10 - 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R1S02 R14 RECTIFIER 3 FRAME EARTH TRIP S008-37 - 3018 3019 SB - - - NO 0 - - - - - - - - - NC C - -
DI-212 I17.1 16 R0S10 I17.1 12 R1S02 R14 RECTIFIER 3 DIODE DEFECT ALARM-SINGLE S008-38 - 3020 3021 SB - - - NO 0 - - - - - - - - - NC C - -
DI-214 I17.2 17 R0S10 I17.2 13 R1S02 R14 RECTIFIER 3 DIODE DEFECT TRIP-MULTI S009-1 - 3022 3023 SB - - - NO 0 - - - - - - - - - NC C - -
DI-216 I17.3 18 R0S10 I17.3 14 R1S02 R14 RECTIFIER 3 DIODE OVER TEMP ALARM S009-2 - 3024 3025 SB - - - NO 0 - - - - - - - - - NC C - -
DI-218 I17.4 19 R0S10 I17.4 15 R1S02 R14 RECTIFIER 3 DIODE OVER TEMP TRIP S009-3 - 3026 3027 SB - - - NO 0 - - - - - - - - - NC C - -
DI-220 I17.5 20 R0S10 I17.5 16 R1S02 R14 RECTIFIER 3 REVERSE CURRENT TRIP S009-4 - 3028 3029 SB - - - NO 0 - - - - - - - - - NC C - -
DI-222 I17.6 21 R0S10 I17.6 17 R1S02 R14 RECTIFIER FEEDER D3 REVERSE CURRENT TRIP S013-8 - 3061 3062 SB - - - NO 0 - - - - - - - - - NC C - -
DI-224 I17.7 22 R0S10 I17.7 18 R1S02 R14 RECTIFIER 3 SURGE ARRESTOR TRIP S009-6 - 3030 3031 SB - - - NO 0 - - - - - - - - - NC C - -
UM1 UM1 23 R0S10 1L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S10 1M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R1S02 R14 RECTIFIER 3 FILTER CIRCUIT ALARM S009-7 - 3032 3033 SB - - - NO 0 - - - - - - - - - NC C - -
DI-228 I18.1 27 R0S10 I18.1 22 R1S02 R14 RECTIFIER 3 AUXILIARY SUPPLY FAILURE ALARM S009-8 - 3034 3035 SB - - - NO 0 - - - - - - - - - NC C - -
DI-230 I18.2 28 R0S10 I18.2 23 R1S02 R14 AUXILIARY TRANSFORMER H11 CONTROL SELECTOR SWITCH S009-13 - 2095 2096 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-232 I18.3 29 R0S10 I18.3 24 R1S02 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 O/C EARTH FAULT TRIP S009-14 - 2097 2098 SB - - - NO 0 - - - - - - - - - NC C - -
DI-234 I18.4 30 R0S10 I18.4 25 R1S02 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 PRESSURE GAUGE TRIP S009-16 - 2097 2099 SB - - - NO 0 - - - - - - - - - NC C - -
DI-236 I18.5 31 R0S10 I18.5 26 R1S02 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 TRIP CIRCUIT SUPERVISION S009-15 - 2104 2105 SB - - - NO 0 - - - - - - - - - NC C - -
DI-238 I18.6 32 R0S10 I18.6 27 R1S02 (R14VB60)
R14 11KV PANEL CONTROL CIRCUIT SUPERVISION S009-18 - 2097 2101 SB - - - NO 0 - - - - - - - - - NC C - -
DI-240 I18.7 33 R0S10 I18.7 28 R1S02 R14 AUXILIARY TRANSFORMER H11 LIQUID LEVEL LOW TRIP S009-17 - 2097 2100 SB - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S10 - 39 R1S02 (R14VB60) - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S10 - 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R1S02 R14 AUXILIARY TRANSFORMER H11 WINDING TEMP HIGH ALARM S009-21 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-244 I19.1 38 R0S10 I19.1 32 R1S02 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 WINDING TEMP HIGH TRIP S009-22 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-246 I19.2 39 R0S10 I19.2 33 R1S02 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 LIQUID TEMP HIGH ALARM S009-23 - 2097 2102 SB - - - NO 0 - - - - - - - - - NC C - -
DI-248 I19.3 40 R0S10 I19.3 34 R1S02 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 LIQUID TEMP HIGH TRIP S009-24 - 2097 2103 SB - - - NO 0 - - - - - - - - - NC C - -
DI-250 I19.4 41 R0S10 I19.4 35 R1S02 (R14VB60)
R14 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S009-27 - 3041 3042 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-252 I19.5 42 R0S10 I19.5 36 R1S02 R14 RECTIFIER FEEDER D1 TRIP CCT SUPERVISION ALARM S009-28 - 3045 3046 SB - - - NO 0 - - - - - - - - - NC C - -
DI-254 I19.6 43 R0S10 I19.6 37 R1S02 R14 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S009-33 - 3050 3051 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-256 I19.7 44 R0S10 I19.7 38 R1S02 R14 RECTIFIER FEEDER D2 TRIP CCT SUPERVISION ALARM S009-34 - 3054 3055 SB - - - NO 0 - - - - - - - - - NC C - -
UM3 UM3 45 2L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R1S03 R14 RECTIFIER FEEDER D3 CONTROL SELECTOR SWITCH S009-37 - 3059 3060 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-260 I20.1 5 R0S11 I20.1 2 R1S03 R14 RECTIFIER FEEDER D3 TRIP CCT SUPERVISION ALARM S009-38 - 3063 3064 SB - - - NO 0 - - - - - - - - - NC C - -
DI-262 I20.2 6 R0S11 I20.2 3 R1S03 R14 TRACK FEEDER D31 CONTROL SELECTOR SWITCH S010-3 - 3068 3069 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-264 I20.3 7 R0S11 I20.3 4 R1S03 R14 TRACK FEEDER D31 INSTANT OVERCURRENT S010-4 - 3070 3071 SB - - - NO 0 - - - - - - - - - NC C - -
DI-266 I20.4 8 R0S11 I20.4 5 R1S03 R14 TRACK FEEDER D31 TIME DELAY OVERCURRENT ALARM S010-5 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-268 I20.5 9 R0S11 I20.5 6 R1S03 R14 TRACK FEEDER D31 RATE OF RISE TRIP S010-6 - 3072 3073 SB - - - NO 0 - - - - - - - - - NC C - -
DI-270 I20.6 10 R0S11 I20.6 7 R1S03 R14 TRACK FEEDER D31 UNDERVOLTAGE TRIP S010-7 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-272 I20.7 11 R0S11 I20.7 8 R1S03 R14 TRACK FEEDER D31 LINE TESTING S010-8 - 3074 3075 SB - - - NO 0 - - - - - - - - - NC NC - -
UM0 UM0 12 R0S11 - 19 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R1S03 R14 TRACK FEEDER D31 LINE IMPEDANCE LOW S010-11 - 3076 3077 SB - - - NO 0 - - - - - - - - - NC C - -
DI-276 I21.1 16 R0S11 I21.1 12 R1S03 R14 TRACK FEEDER D31 TRIP CCT SUPERVISION ALARM S010-12 - 3078 3079 SB - - - NO 0 - - - - - - - - - NC C - -
DI-278 I21.2 17 R0S11 I21.2 13 R1S03 R14 TRACK FEEDER D31 TRANSFER TRIP S010-13 - 4090 4091 SB - - - NO 0 - - - - - - - - - NC C - -
DI-280 I21.3 18 R0S11 I21.3 14 R1S03 R14 TRACK FEEDER D31 LINE TEST CONTROL SELECTOR SWITCH S010-14 - 3111 3112 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-282 I21.4 19 R0S11 I21.4 15 R1S03 R14 TRACK FEEDER D32 CONTROL SELECTOR SWITCH S010-17 - 3083 3084 SB - - - NO 0 - - - - - - - - - NC NC - -

Unrestricted 749775924.xlsx/RS14 [RS14] 144 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

DI-284 I21.5 20 R0S11 I21.5 16 R1S03 R14 TRACK FEEDER D32 INSTANT OVERCURRENT S010-18 - 3085 3086 SB - - - NO 0 - - - - - - - - - NC C - -
DI-286 I21.6 21 R0S11 I21.6 17 R1S03 R14 TRACK FEEDER D32 TIME DELAY OVERCURRENT ALARM S010-21 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-288 I21.7 22 R0S11 I21.7 18 R1S03 R14 TRACK FEEDER D32 RATE OF RISE TRIP S010-22 - 3087 3088 SB - - - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS14 [RS14] 145 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

UM1 UM1 23 R0S11 1L+ 19 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -


UW1 UW1 24 R0S11 1M 20 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 21 R1S03 R14 TRACK FEEDER D32 UNDERVOLTAGE TRIP S010-23 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-292 I22.1 27 R0S11 I22.1 22 R1S03 R14 TRACK FEEDER D32 LINE TESTING S010-24 - 3089 3090 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-294 I22.2 28 R0S11 I22.2 23 R1S03 R14 TRACK FEEDER D32 LINE IMPEDANCE LOW S010-25 - 3091 3092 SB - - - NO 0 - - - - - - - - - NC C - -
DI-296 I22.3 29 R0S11 I22.3 24 R1S03 R14 TRACK FEEDER D32 TRIP CCT SUPERVISION ALARM S010-26 - 3093 3094 SB - - - NO 0 - - - - - - - - - NC C - -
DI-298 I22.4 30 R0S11 I22.4 25 R1S03 R14 TRACK FEEDER D32 TRANSFER TRIP S010-27 - 4092 4093 SB - - - NO 0 - - - - - - - - - NC C - -
DI-300 I22.5 31 R0S11 I22.5 26 R1S03 R14 TRACK FEEDER D32 LINE TEST CONTROL SELECTOR SWITCH S010-28 - 3115 3116 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-302 I22.6 32 R0S11 I22.6 27 R1S03 R14 TRACK FEEDER D37 CONTROL SELECTOR SWITCH S010-33 - 3098 3099 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-304 I22.7 33 R0S11 I22.7 28 R1S03 R14 TRACK FEEDER D37 INSTANT OVERCURRENT S010-34 - 3100 3101 SB - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S11 - 39 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S11 - 40 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R1S03 R14 TRACK FEEDER D37 TIME DELAY OVERCURRENT ALARM S010-35 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-308 I23.1 38 R0S11 I23.1 32 R1S03 R14 TRACK FEEDER D37 RATE OF RISE TRIP S010-36 - 3102 3103 SB - - - NO 0 - - - - - - - - - NC C - -
DI-310 I23.2 39 R0S11 I23.2 33 R1S03 R14 TRACK FEEDER D37 UNDERVOLTAGE TRIP S010-37 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-312 I23.3 40 R0S11 I23.3 34 R1S03 R14 TRACK FEEDER D37 LINE TESTING S010-38 - 3104 3105 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-314 I23.4 41 R0S11 I23.4 35 R1S03 R14 TRACK FEEDER D37 LINE IMPEDANCE LOW S011-1 - 3106 3107 SB - - - NO 0 - - - - - - - - - NC C - -
DI-316 I23.5 42 R0S11 I23.5 36 R1S03 R14 TRACK FEEDER D37 TRIP CCT SUPERVISION ALARM S011-2 - 3108 3109 SB - - - NO 0 - - - - - - - - - NC C - -
DI-318 I23.6 43 R0S11 I23.6 37 R1S03 R14 TRACK FEEDER D37 TRANSFER TRIP S011-3 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-320 I23.7 44 R0S11 I23.7 38 R1S03 R14 TRACK FEEDER D37 LINE TEST CONTROL SELECTOR S011-4 - 3119 3120 SB - - - NO 0 - - - - - - - - - NC NC - -
UM3 UM3 45 2L+ 39 R1S03 - SWITCH
+24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-322 I24.0 4 R0S12 I24.0 1 R1S04 R14 TRACK FEEDER D38 CONTROL SELECTOR SWITCH S011-7 - 4004 4005 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-324 I24.1 5 R0S12 I24.1 2 R1S04 R14 TRACK FEEDER D38 INSTANT OVERCURRENT S011-8 - 4006 4007 SB - - - NO 0 - - - - - - - - - NC C - -
DI-326 I24.2 6 R0S12 I24.2 3 R1S04 R14 TRACK FEEDER D38 TIME DELAY OVERCURRENT ALARM S011-11 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-328 I24.3 7 R0S12 I24.3 4 R1S04 R14 TRACK FEEDER D38 RATE OF RISE TRIP S011-12 - 4008 4009 SB - - - NO 0 - - - - - - - - - NC C - -
DI-330 I24.4 8 R0S12 I24.4 5 R1S04 R14 TRACK FEEDER D38 UNDERVOLTAGE TRIP S011-13 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-332 I24.5 9 R0S12 I24.5 6 R1S04 R14 TRACK FEEDER D38 LINE TESTING S011-14 - 4010 4011 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-334 I24.6 10 R0S12 I24.6 7 R1S04 R14 TRACK FEEDER D38 LINE IMPEDANCE LOW S011-15 - 4012 4013 SB - - - NO 0 - - - - - - - - - NC C - -
DI-336 I24.7 11 R0S12 I24.7 8 R1S04 R14 TRACK FEEDER D38 TRIP CCT SUPERVISION ALARM S011-16 - 4014 4015 SB - - - NO 0 - - - - - - - - - NC C - -
UM0 UM0 12 R0S12 - 19 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S12 - 20 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-338 I25.0 15 R0S12 I25.0 11 R1S04 R14 TRACK FEEDER D38 TRANSFER TRIP S011-17 - 4094 4095 SB - - - NO 0 - - - - - - - - - NC C - -
DI-340 I25.1 16 R0S12 I25.1 12 R1S04 R14 TRACK FEEDER D38 LINE TEST CONTROL SELECTOR SWITCH S011-18 - 4115 4116 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-342 I25.2 17 R0S12 I25.2 13 R1S04 R14 DC COMMON EQUIPMENT D07 (OVPD) CONTACTOR CONTROL SELECTOR SWITCH S011-23 - 4099 4100 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-344 I25.3 18 R0S12 I25.3 14 R1S04 R14 DC COMMON EQUIPMENT D07 (OVPD) OVERVOLTAGE ALARM S011-24 - 4101 4102 SB - - - NO 0 - - - - - - - - - NC C - -
DI-346 I25.4 19 R0S12 I25.4 15 R1S04 R14 AC/DC SYSTEM MAINS FAILED ALARM s011-25 - 4031 4032 SB - - - NO 0 - - - - - - - - - NC C - -
DI-348 I25.5 20 R0S12 I25.5 16 R1S04 - SPARE s011-26 - - - - - - - - - - - - - - - - - - - - -
DI-350 I25.6 21 R0S12 I25.6 17 R1S04 R14 AC/DC SYSTEM 110V HIGH VOLTAGE ALARM S011-27 - 4047 4048 SB - - - NO 0 - - - - - - - - - NC C - -
DI-352 I25.7 22 R0S12 I25.7 18 R1S04 R14 AC/DC SYSTEM CHARGER FAILURE S011-28 - 4045 4046 SB - - - NO 0 - - - - - - - - - NC C - -
UM1 UM1 23 R0S12 1L+ 19 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S12 1M 20 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-354 I26.0 26 R0S12 I26.0 21 R1S04 R14 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S011-31 - 4033 4034 SB - - - NO 0 - - - - - - - - - NC C - -
DI-356 I26.1 27 R0S12 I26.1 22 R1S04 R14 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S011-32 - 4035 4036 SB - - - NO 0 - - - - - - - - - NC C - -
DI-358 I26.2 28 R0S12 I26.2 23 R1S04 R14 AC/DC SYSTEM 11KV CONTROL VOLTAGE S011-33 - 4037 4038 SB - - - NO 0 - - - - - - - - - C/ NC NC/ C - -
DI-360 I26.3 29 R0S12 I26.3 24 R1S04 R14 AC/DC SYSTEM 750V CONTROL VOLTAGE S011-34 - 4039 4040 SB - - - NO 0 - - - - - - - - - C/ NC NC/ C - -
DI-362 I26.4 30 R0S12 I26.4 25 R1S04 R14 AC/DC SYSTEM 110V DC COMMON FEEDER S011-35 - 4041 4042 SB - - - NO 0 - - - - - - - - - NC C - -
DI-364 I26.5 31 R0S12 I26.5 26 R1S04 R14 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S011-36 - 4043 4044 SB - - - NO 0 - - - - - - - - - NC C - -
DI-366 I26.6 32 R0S12 I26.6 27 R1S04 R14 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT S011-37 - 5001 5002 SB - - - NO 0 - - - - - - - - - NC C - -
DI-368 I26.7 33 R0S12 I26.7 28 R1S04 R14 COMMON EQUIPMENT ALARM
FIRE PROTECTION ALARM S011-38 - 5003 5004 SB - - - NO 0 - - - - - - - - - NC C - -
UM2 UM2 34 R0S12 - 39 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S12 - 40 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-370 I27.0 37 R0S12 I27.0 31 R1S04 R14 COMMON EQUIPMENT INTRUDER ALARM S012-1 - 5005 5006 SB - - - NO 0 - - - - - - - - - NC C - -
DI-372 I27.1 38 R0S12 I27.1 32 R1S04 R14 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM S012-2 - 5007 5008 SB - - - NO 0 - - - - - - - - - NC C - -
DI-374 I27.2 39 R0S12 I27.2 33 R1S04 R14 MVAC SYSTEM FAULT ALARM S012-3 - 5009 5010 SB - - - NO 0 - - - - - - - - - NC C - -
DI-376 I27.3 40 R0S12 I27.3 34 R1S04 R14 ROOMS OVER TEMPERATURE ALARM S012-4 - 5011 5012 SB - - - NO 0 - - - - - - - - - NC C - -
DI-378 I27.4 41 R0S12 I27.4 35 R1S04 R14 VOLTAGE STABILIZER FAULT ALARM S012-5 - 5013 5014 SB - - - NO 0 - - - - - - - - - NC C - -
DI-380 I27.5 42 R0S12 I27.5 36 R1S04 - SPARE S012-6 - - - - - - - - - - - - - - - - - - - - -
DI-382 I27.6 43 R0S12 I27.6 37 R1S04 R14 MVAC MOTORISED DAMPER NO.1 POSITION S012-7 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-384 I27.7 44 R0S12 I27.7 38 R1S04 - SPARE S012-8 - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 2L+ 39 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-386 I28.0 4 R0S13 I28.0 1 R1S05 R14 MVAC MOTORISED DAMPER NO.2 POSITION S012-11 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-388 I28.1 5 R0S13 I28.1 2 R1S05 - SPARE s011-27 - - - - - - - - - - - - - - - - - - - - -
DI-390 I28.2 6 R0S13 I28.2 3 R1S05 R14 MVAC MOTORISED DAMPER NO.3 POSITION S012-13 - - - SB - - - NO 0 - - - - - - - - - NC C - -
DI-392 I28.3 7 R0S13 I28.3 4 R1S05 - SPARE S012-14 - - - - - - - - - - - - - - - - - - - - -
DI-394 I28.4 8 R0S13 I28.4 5 R1S05 R14 MVAC VENTILATION FAN NO.1 FLOW SWITCH S012-15 - 5027 5028 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-396 I28.5 9 R0S13 I28.5 6 R1S05 R14 MVAC VENTILATION FAN NO.1 FAULT ALARM S012-16 - 5029 5030 SB - - - NO 0 - - - - - - - - - NC C - -
DI-398 I28.6 10 R0S13 I28.6 7 R1S05 R14 MVAC VENTILATION FAN NO.1 EMERGENCY STOP S012-17 - 5031 5032 SB - - - NO 0 - - - - - - - - - NC C - -
DI-400 I28.7 11 R0S13 I28.7 8 R1S05 R14 MVAC VENTILATION FAN NO.1 CONTROL SELECTOR SWITCH S012-18 - 5033 5034 SB - - - NO 0 - - - - - - - - - NC NC - -
UM0 UM0 12 R0S13 - 19 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S13 - 20 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-402 I29.0 15 R0S13 I29.0 11 R1S05 S012-21 - - - - - 0 - - - - - - - - - - - - -
DI-404 I29.1 16 R0S13 I29.1 12 R1S05 s011-26 - - - - - 0 - - - - - - - - - - -
DI-406 I29.2 17 R0S13 I29.2 13 R1S05 TSW LR/WR INTERCHANGE OVPD POWER SUPPLY FAIL S012-23 - 4026 4027 SB - - - NO 0 - - - - - - - - - NC C - -
DI-408 I29.3 18 R0S13 I29.3 14 R1S05 s012-24 - - - - 0 - - - - - - - - - - - - -
DI-410 I29.4 19 R0S13 I29.4 15 R1S05 s012-25 - - - - 0 - - - - - - - - - - -
DI-412 I29.5 20 R0S13 I29.5 16 R1S05 TSW LR/WR INTERCHANGE OVPD OPERATING S012-26 - 4028 4029 SB - - - NO 0 - - - - - - - - - NC C - -
DI-414 I29.6 21 R0S13 I29.6 17 R1S05 R14 MVAC VENTILATION FAN NO.3 EMERGENCY STOP S012-27 - 5047 5048 SB - - - NO 0 - - - - - - - - - NC C - -
DI-416 I29.7 22 R0S13 I29.7 18 R1S05 R14 MVAC VENTILATION FAN NO.3 CONTROL SELECTOR SWITCH S012-28 - 5049 5050 SB - - - NO 0 - - - - - - - - - NC NC - -
UM1 UM1 23 R0S13 1L+ 19 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S13 1M 20 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-418 I30.0 26 R0S13 I30.0 21 R1S05 R14 MVAC VENTILATION FAN NO.4 FLOW SWITCH S012-31 - 5051 5052 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-420 I30.1 27 R0S13 I30.1 22 R1S05 R14 MVAC VENTILATION FAN NO.4 FAULT ALARM S012-32 - 5053 5054 SB - - - NO 0 - - - - - - - - - NC C - -
DI-422 I30.2 28 R0S13 I30.2 23 R1S05 R14 MVAC VENTILATION FAN NO.4 EMERGENCY STOP S012-33 - 5055 5056 SB - - - NO 0 - - - - - - - - - NC C - -
DI-424 I30.3 29 R0S13 I30.3 24 R1S05 R14 MVAC VENTILATION FAN NO.4 CONTROL SELECTOR SWITCH S012-34 - 5057 5058 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-426 I30.4 30 R0S13 I30.4 25 R1S05 R14 MVAC VENTILATION FAN NO.4 FLOW SWITCH S012-35 - 5059 5060 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-428 I30.5 31 R0S13 I30.5 26 R1S05 R14 MVAC VENTILATION FAN NO.5 FAULT ALARM S012-36 - 5061 5062 SB - - - NO 0 - - - - - - - - - NC C - -
DI-430 I30.6 32 R0S13 I30.6 27 R1S05 R14 MVAC VENTILATION FAN NO.5 EMERGENCY STOP S012-37 - 5063 5064 SB - - - NO 0 - - - - - - - - - NC C - -
DI-432 I30.7 33 R0S13 I30.7 28 R1S05 R14 MVAC VENTILATION FAN NO.5 CONTROL SELECTOR SWITCH S012-38 - 5065 5066 SB - - - NO 0 - - - - - - - - - NC NC - -
UM2 UM2 34 R0S13 - 39 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S13 - 40 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-434 I31.0 37 R0S13 I31.0 31 R1S05 R14 MVAC VENTILATION FAN NO.6 FLOW SWITCH S013-1 - 5067 5068 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-436 I31.1 38 R0S13 I31.1 32 R1S05 R14 MVAC VENTILATION FAN NO.6 FAULT ALARM S013-2 - 5069 5070 SB - - - NO 0 - - - - - - - - - NC C - -
DI-438 I31.2 39 R0S13 I31.2 33 R1S05 R14 MVAC VENTILATION FAN NO.6 EMERGENCY STOP S013-3 - 5071 5072 SB - - - NO 0 - - - - - - - - - NC C - -
DI-440 I31.3 40 R0S13 I31.3 34 R1S05 R14 MVAC VENTILATION FAN NO.6 CONTROL SELECTOR SWITCH S013-4 - 5073 5074 SB - - - NO 0 - - - - - - - - - NC NC - -
DI-442 I31.4 41 R0S13 I31.4 35 R1S05 R14 380V NETWORK PROTECTION RELAYS COMMON ALARM S013-5 - 5015 5016 SB - - - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS14 [RS14] 146 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

DI-444 I31.5 42 R0S13 I31.5 36 R1S05 - SPARE S007-25 - - - - - - - - - - - - - - - - - - - - -


DI-446 I31.6 43 R0S13 I31.6 37 R1S05 - SPARE S008-15 - - - - - - - - - - - - - - - - - - - - -
DI-448 I31.7 44 R0S13 I31.7 38 R1S05 - SPARE S009-5 - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 2L+ 39 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS14 [RS14] 147 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
DI-450 I32.0 4 R0S14 I32.0 1 R0S05 R14 MAIN INCOMER H05 (R14VB01) VCB OPENED S005-1 - 1001 1002 DB - - - YES 0 - - - - - - - - - C NC - -
DI-452 I32.1 5 R0S14 I32.1 2 R0S05 R14 MAIN INCOMER H05 (R14VB01) VCB CLOSED S005-2 - 1001 1003 DB - - - YES 0 - - - - - - - - - - - NC C
DI-454 I32.2 6 R0S14 I32.2 3 R0S05 R14 RING MAIN H01 (R14VB20) (FUTURE) VCB OPENED S005-11 - 1014 1015 DB - - - YES 0 - - - - - - - - - C NC - -
DI-456 I32.3 7 R0S14 I32.3 4 R0S05 R14 RING MAIN H01 (R14VB20) (FUTURE) VCB CLOSED S005-12 - 1014 1016 DB - - - YES 0 - - - - - - - - - - - NC C
DI-458 I32.4 8 R0S14 I32.4 5 R0S05 R14 RING MAIN H03 (R14VB21) (TO R16) VCB OPENED S005-21 - 1029 1030 DB - - - YES 0 - - - - - - - - - C NC - -
DI-460 I32.5 9 R0S14 I32.5 6 R0S05 R14 RING MAIN H03 (R14VB21) (TO R16) VCB CLOSED S005-22 - 1029 1031 DB - - - YES 0 - - - - - - - - - - - NC C
DI-462 I32.6 10 R0S14 I32.6 7 R0S05 R14 RING MAIN H08 (R14VB22) (TO R15) VCB OPENED S005-31 - 1044 1045 DB - - - YES 0 - - - - - - - - - C NC - -
DI-464 I32.7 11 R0S14 I32.7 8 R0S05 R14 RING MAIN H08 (R14VB22) (TO R15) VCB CLOSED S005-32 - 1044 1046 DB - - - YES 0 - - - - - - - - - - - NC C
UM0 UM0 12 R0S14 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S14 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-466 I33.0 15 R0S14 I33.0 11 R0S05 R14 RING MAIN H10 (R14VB23) (TO R08) VCB OPENED S006-1 - 1059 1060 DB - - - YES 0 - - - - - - - - - C NC - -
DI-468 I33.1 16 R0S14 I33.1 12 R0S05 R14 RING MAIN H10 (R14VB23) (TO R08) VCB CLOSED S006-2 - 1059 1061 DB - - - YES 0 - - - - - - - - - - - NC C
DI-470 I33.2 17 R0S14 I33.2 13 R0S05 R14 RING MAIN H12 (R14VB24) (FUTURE) VCB OPENED S006-11 - 1075 1076 DB - - - YES 0 - - - - - - - - - C NC - -
DI-472 I33.3 18 R0S14 I33.3 14 R0S05 R14 RING MAIN H12 (R14VB24) (FUTURE) VCB CLOSED S006-12 - 1075 1077 DB - - - YES 0 - - - - - - - - - - - NC C
DI-474 I33.4 19 R0S14 I33.4 15 R0S05 R14 RING MAIN H07 (R14VB02) (FUTURE) VCB OPENED S006-21 - 1090 1091 DB - - - YES 0 - - - - - - - - - C NC - -
DI-476 I33.5 20 R0S14 I33.5 16 R0S05 R14 RING MAIN H07 (R14VB02) (FUTURE) VCB CLOSED S006-22 - 1090 1092 DB - - - YES 0 - - - - - - - - - - - NC C
DI-478 I33.6 21 R0S14 I33.6 17 R0S05 R14 BUS SECTION H06 (R14VB11) VCB OPENED S006-31 - 2001 2002 DB - - - YES 0 - - - - - - - - - C NC - -
DI-480 I33.7 22 R0S14 I33.7 18 R0S05 R14 BUS SECTION H06 (R14VB11) VCB CLOSED S006-32 - 2001 2003 DB - - - YES 0 - - - - - - - - - - - NC C
UM1 UM1 23 R0S14 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S14 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-482 I34.0 26 R0S14 I34.0 21 R0S05 R14 RECTIFIER FEEDER H02 (R14VB50) VCB OPENED S007-1 - 2016 2017 DB - - - YES 0 - - - - - - - - - C NC - -
DI-484 I34.1 27 R0S14 I34.1 22 R0S05 R14 RECTIFIER FEEDER H02 (R14VB50) VCB CLOSED S007-2 - 2016 2018 DB - - - YES 0 - - - - - - - - - - - NC C
DI-486 I34.2 28 R0S14 I34.2 23 R0S05 R14 RECTIFIER FEEDER H04 (R14VB51) VCB OPENED S007-31 - 2053 2054 DB - - - YES 0 - - - - - - - - - C NC - -
DI-488 I34.3 29 R0S14 I34.3 24 R0S05 R14 RECTIFIER FEEDER H04 (R14VB51) VCB CLOSED S007-32 - 2053 2055 DB - - - YES 0 - - - - - - - - - - - NC C
DI-490 I34.4 30 R0S14 I34.4 25 R0S05 R14 RECTIFIER FEEDER H09 (R14VB52) VCB OPENED S008-21 - 3001 3002 DB - - - YES 0 - - - - - - - - - C NC - -
DI-492 I34.5 31 R0S14 I34.5 26 R0S05 R14 RECTIFIER FEEDER H09 (R14VB52) VCB CLOSED S008-22 - 3001 3003 DB - - - YES 0 - - - - - - - - - - - NC C
DI-494 I34.6 32 R0S14 I34.6 27 R0S05 R14 AUXILIARY TRANSFORMER H11 VCB OPENED S009-11 - 2092 2093 DB - - - YES 0 - - - - - - - - - C NC - -
DI-496 I34.7 33 R0S14 I34.7 28 R0S05 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 VCB CLOSED S009-12 - 2092 2094 DB - - - YES 0 - - - - - - - - - - - NC C
UM2 UM2 34 R0S14 - 39 R0S05 (R14VB60) - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S14 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-498 I35.0 37 R0S14 I35.0 31 R0S05 R14 RECTIFIER FEEDER D1 DCCB OPENED S009-25 - 3038 3039 DB - - - YES 0 - - - - - - - - - C NC - -
DI-500 I35.1 38 R0S14 I35.1 32 R0S05 R14 RECTIFIER FEEDER D1 DCCB CLOSED S009-26 - 3038 3040 DB - - - YES 0 - - - - - - - - - - - NC C
DI-502 I35.2 39 R0S14 I35.2 33 R0S05 R14 RECTIFIER FEEDER D2 DCCB OPENED S009-31 - 3047 3048 DB - - - YES 0 - - - - - - - - - C NC - -
DI-504 I35.3 40 R0S14 I35.3 34 R0S05 R14 RECTIFIER FEEDER D2 DCCB CLOSED S009-32 - 3047 3049 DB - - - YES 0 - - - - - - - - - - - NC C
DI-506 I35.4 41 R0S14 I35.4 35 R0S05 R14 RECTIFIER FEEDER D3 DCCB OPENED S009-35 - 3056 3057 DB - - - YES 0 - - - - - - - - - C NC - -
DI-508 I35.5 42 R0S14 I35.5 36 R0S05 R14 RECTIFIER FEEDER D3 DCCB CLOSED S009-36 - 3056 3058 DB - - - YES 0 - - - - - - - - - - - NC C
DI-510 I35.6 43 R0S14 I35.6 37 R0S05 R14 TRACK FEEDER D31 DCCB OPENED S010-1 - 3065 3066 DB - - - YES 0 - - - - - - - - - C NC - -
DI-512 I35.7 44 R0S14 I35.7 38 R0S05 R14 TRACK FEEDER D31 DCCB CLOSED S010-2 - 3065 3067 DB - - - YES 0 - - - - - - - - - - - NC C
UM3 UM3 45 2L+ 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - 90 - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - 90 - - - - - - - - - - - - - - - - - - -
DI-514 I36.0 4 R0S15 I36.0 1 R0S06 R14 TRACK FEEDER D32 DCCB OPENED S010-15 - 3080 3081 DB - - - YES 0 - - - - - - - - - C NC - -
DI-516 I36.1 5 R0S15 I36.1 2 R0S06 R14 TRACK FEEDER D32 DCCB CLOSED S010-16 - 3080 3082 DB - - - YES 0 - - - - - - - - - - - NC C
DI-518 I36.2 6 R0S15 I36.2 3 R0S06 R14 TRACK FEEDER D37 DCCB OPENED S010-31 - 3095 3096 DB - - - YES 0 - - - - - - - - - C NC - -
DI-520 I36.3 7 R0S15 I36.3 4 R0S06 R14 TRACK FEEDER D37 DCCB CLOSED S010-32 - 3095 3097 DB - - - YES 0 - - - - - - - - - - - NC C
DI-522 I36.4 8 R0S15 I36.4 5 R0S06 R14 TRACK FEEDER D38 DCCB OPENED S011-5 - 4001 4002 DB - - - YES 0 - - - - - - - - - C NC - -
DI-524 I36.5 9 R0S15 I36.5 6 R0S06 R14 TRACK FEEDER D38 DCCB CLOSED S011-6 - 4001 4003 DB - - - YES 0 - - - - - - - - - - - NC C
DI-526 I36.6 10 R0S15 I36.6 7 R0S06 R14 DC COMMON EQUIPMENT D07 (OVPD) CONTACTOR OPENED S011-22 - 4096 4098 DB - - - YES 0 - - - - - - - - - C NC - -
DI-528 I36.7 11 R0S15 I36.7 8 R0S06 R14 DC COMMON EQUIPMENT D07 (OVPD) CONTACTOR CLSOED S011-21 - 4096 4097 DB - - - YES 0 - - - - - - - - - - - NC C
UM0 UM0 12 R0S15 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW0 UW0 13 R0S15 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-530 I37.0 15 R0S15 I37.0 11 R0S06 R14 DUMMY CB VCB OPENED internal - - - DB - - - NO 0 - - - - - - - - - C NC - -
DI-532 I37.1 16 R0S15 I37.1 12 R0S06 R14 DUMMY CB VCB CLOSED wiring
internal - - - DB - - - NO 0 - - - - - - - - - - - NC C
DI-534 I37.2 17 R0S15 I37.2 13 R0S06 TSW LR/WR INTERCHANGE OVPD CONTACTOR OPEN wiring
s011-26 - 4020 4022 DB - - - YES 0 - - - - - - - - - C NC - -
DI-536 I37.3 18 R0S15 I37.3 14 R0S06 TSW LR/WR INTERCHANGE OVPD CONTACTOR CLOSE s012-22 - 4020 4021 DB - - - YES 0 - - - - - - - - - - - NC C
DI-538 I37.4 19 R0S15 I37.4 15 R0S06 TSW LR/WR INTERCHANGE OVPD MAINTENANCE ISOLATOR OPEN s012-12 - 4023 4025 DB - - - YES 0 - - - - - - - - - C NC - -
DI-540 I37.5 20 R0S15 I37.5 16 R0S06 TSW LR/WR INTERCHANGE OVPD MAINTENANCE ISOLATOR CLOSE s011-25 - 4023 4024 DB - - - YES 0 - - - - - - - - - - - NC C
DI-542 I37.6 21 R0S15 I37.6 17 R0S06 - SPARE S013-17 - - - DB - - - - - - - - - - - - - - - - - -
DI-544 I37.7 22 R0S15 I37.7 18 R0S06 - SPARE S013-18 - - - DB - - - - - - - - - - - - - - - - - -
UM1 UM1 23 R0S15 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW1 UW1 24 R0S15 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-546 I38.0 26 R0S15 I38.0 21 R0S06 - SPARE S013-21 - - - - - - - - - - - - - - - - - - - - -
DI-548 I38.1 27 R0S15 I38.1 22 R0S06 - SPARE S013-22 - - - - - - - - - - - - - - - - - - - - -
DI-550 I38.2 28 R0S15 I38.2 23 R0S06 - SPARE S013-23 - - - - - - - - - - - - - - - - - - - - -
DI-552 I38.3 29 R0S15 I38.3 24 R0S06 - SPARE S013-24 - - - - - - - - - - - - - - - - - - - - -
DI-554 I38.4 30 R0S15 I38.4 25 R0S06 - SPARE S013-25 - - - - - - - - - - - - - - - - - - - - -
DI-556 I38.5 31 R0S15 I38.5 26 R0S06 - SPARE S013-26 - - - - - - - - - - - - - - - - - - - - -
DI-558 I38.6 32 R0S15 I38.6 27 R0S06 - SPARE S013-27 - - - - - - - - - - - - - - - - - - - - -
DI-560 I38.7 33 R0S15 I38.7 28 R0S06 - SPARE S013-28 - - - - - - - - - - - - - - - - - - - - -
UM2 UM2 34 R0S15 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW2 UW2 35 R0S15 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
DI-562 I39.0 37 R0S15 I39.0 31 R0S06 - SPARE S013-31 - - - - - - - - - - - - - - - - - - - - -
DI-564 I39.1 38 R0S15 I39.1 32 R0S06 - SPARE S013-32 - - - - - - - - - - - - - - - - - - - - -
DI-566 I39.2 39 R0S15 I39.2 33 R0S06 - SPARE S013-33 - - - - - - - - - - - - - - - - - - - - -
DI-568 I39.3 40 R0S15 I39.3 34 R0S06 - SPARE S013-34 - - - - - - - - - - - - - - - - - - - - -
DI-570 I39.4 41 R0S15 I39.4 35 R0S06 - SPARE S013-35 - - - - - - - - - - - - - - - - - - - - -
DI-572 I39.5 42 R0S15 I39.5 36 R0S06 - SPARE S013-36 - - - - - - - - - - - - - - - - - - - - -
DI-574 I39.6 43 R0S15 I39.6 37 R0S06 - SPARE S013-37 - - - - - - - - - - - - - - - - - - - - -
DI-576 I39.7 44 R0S15 I39.7 38 R0S06 - SPARE S013-38 - - - - - - - - - - - - - - - - - - - - -
UM3 UM3 45 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
UW3 UW3 46 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
I40.0 1 R1S06 - SPARE S006-33 - - - - - - NO 0 - - - - - - - - - NC NC - -
I40.1 2 R1S06 - SPARE S006-34 - - - - - - NO 0 - - - - - - - - - NC C - -
I40.2 3 R1S06 - SPARE S006-35 - - - - - - NO 0 - - - - - - - - - NC C - -
I40.3 4 R1S06 - SPARE S006-36 - - - - - - NO 0 - - - - - - - - - NC NC - -
I40.4 5 R1S06 - SPARE S006-37 - - - - - - NO 0 - - - - - - - - - NC C - -
I40.5 6 R1S06 - SPARE S006-38 - - - - - - - - - - - - - - - - - - - - -
I40.6 7 R1S06 - SPARE S006-41 - - - - - - NO 0 - - - - - - - - - NC NC - -
I40.7 8 R1S06 - SPARE S006-42 - - - - - - NO 0 - - - - - - - - - NC C - -
- 19 R1S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- 20 R1S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I41.0 11 R1S06 - SPARE S006-43 - - - - - - NO 0 - - - - - - - - - NC C - -
I41.1 12 R1S06 - SPARE S006-44 - - - - - - NO 0 - - - - - - - - - NC NC - -
I41.2 13 R1S06 - SPARE S006-45 - - - - - - NO 0 - - - - - - - - - NC C - -
I41.3 14 R1S06 - SPARE S006-46 - - - - - - - - - - - - - - - - - - - - -
I41.4 15 R1S06 - SPARE S007-2 - - - - - - NO 0 - - - - - - - - - NC NC - -

Unrestricted 749775924.xlsx/RS14 [RS14] 148 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

I41.5 16 R1S06 - SPARE S007-3 - - - - - - NO 0 - - - - - - - - - NC C - -


I41.6 17 R1S06 - SPARE S007-4 - - - - - - NO 0 - - - - - - - - - NC C - -
I41.7 18 R1S06 - SPARE S007-5 - - - - - - NO 0 - - - - - - - - - NC NC - -
1L+ 19 R1S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
1M 20 R1S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I42.0 21 R1S06 - SPARE S007-6 - - - - - - NO 0 - - - - - - - - - NC C - -
I42.1 22 R1S06 - SPARE S007-7 - - - - - - - - - - - - - - - - - - - - -
I42.2 23 R1S06 - SPARE S007-10 - - - - - - NO 0 - - - - - - - - - NC NC - -
I42.3 24 R1S06 - SPARE S007-11 - - - - - - NO 0 - - - - - - - - - NC C - -
I42.4 25 R1S06 - SPARE S007-12 - - - - - - NO 0 - - - - - - - - - NC C - -
I42.5 26 R1S06 - SPARE S007-13 - - - - - - NO 0 - - - - - - - - - NC NC - -
I42.6 27 R1S06 - SPARE S007-14 - - - - - - NO 0 - - - - - - - - - NC C - -
I42.7 28 R1S06 - SPARE S007-15 - - - - - - - - - - - - - - - - - - - - -
- 39 R1S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
- 40 R1S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -
I43.0 31 R1S06 - SPARE S007-18 - - - - - - NO 0 - - - - - - - - - NC C - -
I43.1 32 R1S06 - SPARE S007-19 - - - - - - NO 0 - - - - - - - - - NC C - -
I43.2 33 R1S06 - SPARE S007-20 - - - - - - NO 0 - - - - - - - - - NC C - -
I43.3 34 R1S06 - SPARE S007-21 - - - - - - NO 0 - - - - - - - - - NC C - -
I43.4 35 R1S06 - SPARE S007-22 - - - - - - NO 0 - - - - - - - - - NC C - -
I43.5 36 R1S06 - SPARE S007-23 - - - - - - NO 0 - - - - - - - - - NC C - -
I43.6 37 R1S06 - SPARE S007-24 - - - - - - NO 0 - - - - - - - - - NC C - -
I43.7 38 R1S06 - SPARE S007-25 - - - - - - NO 0 - - - - - - - - - NC C - -
2L+ 39 R1S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - - - - - - - - - - - - - -
2M 40 R1S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS14 [RS14] 149 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R1S03 IW.256 1 R3S02 R14 MAIN INCOMER H05 (R14VB01) PHASE ANGLE S014-1 - 6007 - AI 4 to 20 +0.5 to -0.5 P.F. - - 1.0% - - -0.8 -0.7 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-1 (-) IW.256 5 R1S03 IW.256 21 R3S02 - - S014-2 - - 6008 - to - - to - - - - - #VALUE! 24.800 23.200 #VALUE! #VALUE! -0.76 -0.665 #VALUE! #VALUE! 24.160 22.640
TB2-2 (+) IW.258 6 R1S03 IW.258 2 R3S02 R14 MAIN INCOMER H05 (R14VB01) CURRENT S014-3 - 6003 - AI 4 to 20 0 to 2000 A ac - - 1.0% - - 1500 1800 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-2 (-) IW.258 7 R1S03 IW.258 22 R3S02 - - S014-4 - - 6004 - to - - to - - - - - - - 16.000 18.400 - - 1425 1710 - - 15.400 17.680
TB2-3 (+) IW.260 8 R1S03 IW.260 3 R3S02 R14 MAIN INCOMER H05 (R14VB01) VOLTAGE S014-5 - 6009 - AI 4 to 20 0 to 15 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-3 (-) IW.260 9 R1S03 IW.260 23 R3S02 - - S014-6 - - 6010 - to - - to - - - - - 5.067 14.560 16.907 17.227 0.950 10.395 11.495 11.78 5.013 15.088 16.261 16.565
TB2-4 (+) IW.262 10 R1S03 IW.262 4 R3S02 R14 MAIN INCOMER H05 (R14VB01) POWER S014-7 - 6005 - AI 4 to 20 0 to 40 MW - - 1.0% - - - - 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-4 (-) IW.262 11 R1S03 IW.262 24 R3S02 - - S014-8 - - 6006 - to - - to - - - - - - - - - - - - - - - - -
TB2-5 (+) IW.264 15 R1S03 IW.264 5 R3S02 R14 MAIN INCOMER H05 (R14VB01) CHECK POWER S014-9 - - - AI to to MW - - 1.0% 1 2 6 7 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-5 (-) IW.264 16 R1S03 IW.264 25 R3S02 - - S014-10 - - - - to - - to - - - - - - - - - 0.95 2.1 5.7 6.65 - - - -
TB2-6 (+) IW.266 17 R1S03 IW.266 6 R3S02 R14 RING MAIN H01 (R14VB20) (FUTURE) CURRENT (FUTURE) S014-11 - 6021 - AI 4 to 20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-6 (-) IW.266 18 R1S03 IW.266 26 R3S02 - - S014-12 - - 6022 - to - - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
TB2-7 (+) IW.268 19 R1S03 IW.268 7 R3S02 R14 RING MAIN H03 (R14VB21) (TO R16) CURRENT (TO R16) S014-13 - 6023 - AI 4 to 20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-7 (-) IW.268 20 R1S03 IW.268 27 R3S02 - - S014-14 - - 6024 - to - - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
TB2-8 (+) IW.270 21 R1S03 IW.270 8 R3S02 R14 RING MAIN H08 (R14VB22) (TO R15) CURRENT (TO R15) S014-15 - 6025 - AI 4 to 20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-8 (-) IW.270 22 R1S03 IW.270 28 R3S02 - - S014-16 - - 6026 - to - - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
TB2-9 (+) IW.272 26 R1S03 IW.272 9 R3S02 R14 RING MAIN H12 (R14VB24) (FUTURE) CURRENT (FUTURE) S014-19 - 6029 - AI 4 to 20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-9 (-) IW.272 27 R1S03 IW.272 29 R3S02 - - S014-20 - - 6030 - to - - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
TB2-10 (+) IW.274 28 R1S03 IW.274 10 R3S02 R14 RING MAIN H10 (R14VB23) (TO R08) CURRENT (TO+J185 R08) S014-17 - 6027 - AI 4 to 20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-10 (-) IW.274 29 R1S03 IW.274 30 R3S02 - - S014-18 - - 6028 - to - - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
TB2-11 (+) IW.276 30 R1S03 IW.276 11 R3S02 R14 AUXILIARY TRANSFORMER H11 CURRENT S014-21 - 6039 - AI 4 to 20 0 to 100 A ac - - 1.0% - - 42 50 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-11 (-) IW.276 31 R1S03 IW.276 31 R3S02 (R14VB60) - - S014-22 - - 6040 - to - - to - - - - - - - 10.720 12.000 - - 39.9 47.5 - - 10.384 11.600
TB2-12 (+) IW.278 32 R1S03 IW.278 12 R3S02 R14 RECTIFIER FEEDER H02 (R14VB50) CURRENT S014-23 - 6031 - AI 4 to 20 0 to 200 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-12 (-) IW.278 33 R1S03 IW.278 32 R3S02 - - S014-24 - - 6032 - to - - to - - - - - - - 10.400 11.600 - - 76 90.25 - - 10.080 11.220
TB2-13 (+) IW.280 37 R1S03 IW.280 13 R3S02 R14 RECTIFIER FEEDER H04 (R14VB51) CURRENT S014-25 - 6033 - AI 4 to 20 0 to 200 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-13 (-) IW.280 38 R1S03 IW.280 33 R3S02 - - S014-26 - - 6034 - to - - to - - - - - - - 10.400 11.600 - - 76 90.25 - - 10.080 11.220
TB2-14 (+) IW.282 39 R1S03 IW.282 14 R3S02 R14 RECTIFIER FEEDER H09 (R14VB52) CURRENT S014-27 - 6035 - AI 4 to 20 0 to 200 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-14 (-) IW.282 40 R1S03 IW.282 34 R3S02 - - S014-28 - - 6036 - to - - to - - - - - - - 10.400 11.600 - - 76 90.25 - - 10.080 11.220
TB2-15 (+) IW.284 41 R1S03 IW.284 15 R3S02 R14 AC BUSBAR H06 (R14VB11) CURRENT S014-29 - 6037 - AI 4 to 20 0 to 2000 A ac - - 1.0% - - - - 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-15 (-) IW.284 42 R1S03 IW.284 35 R3S02 - - S014-30 - - 6038 - to - - to - - - - - - - - - - - - - - - - -
TB2-16 (+) IW.286 43 R1S03 IW.286 16 R3S02 R14 AC BUSBAR (R14VB70) LHS VOLTAGE S014-31 - 6011 - AI 4 to 20 0 to 15 kV ac - - 1.0% 1 9.9 12.1 12.4 0.05 0.05 0.05 0.05 C NC NC C
TB2-16 (-) IW.286 44 R1S03 IW.286 36 R3S02 - - S014-32 - - 6012 - to - - to - - - - - 5.067 14.560 16.907 17.227 0.95 10.395 11.495 11.78 5.013 15.088 16.261 16.565
ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
TB2-17 (+) IW.288 4 R1S04 IW.288 1 R3S03 R14 AC BUSBAR (R14VB71) RHS VOLTAGE S014-33 - 6013 - AI 4 to +20 0 to 15 kV ac - - 1.0% 1 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-17 (+) IW.288 5 R1S04 IW.288 21 R3S03 - - S014-34 - - 6014 - to - - to - - - - - 5.067 14.560 16.907 17.227 0.95 10.395 11.495 11.78 5.013 15.088 16.261 16.565
TB2-18 (+) IW.290 6 R1S04 IW.290 2 R3S03 R14 TRACK FEEDER D31 DC CURRENT S014-35 - 6041 - AI -20 to +20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-18 (-) IW.290 7 R1S04 IW.290 22 R3S03 - - S014-36 - - 6042 - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375 2850 -8.143 -6.786 6.786 8.143
TB2-19 (+) IW.292 8 R1S04 IW.292 3 R3S03 R14 TRACK FEEDER D32 DC CURRENT S014-37 - 6043 - AI -20 to +20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-19 (-) IW.292 9 R1S04 IW.292 23 R3S03 - - S014-38 - - 6044 - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375 2850 -8.143 -6.786 6.786 8.143
TB2-20 (+) IW.294 10 R1S04 IW.294 4 R3S03 R14 TRACK FEEDER D37 DC CURRENT S014-39 - 6045 - AI -20 to +20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-20 (-) IW.294 11 R1S04 IW.294 24 R3S03 - - S014-40 - - 6046 - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375.000 2850.000 -8.143 -6.786 6.786 8.143
TB2-21 (+) IW.296 15 R1S04 IW.296 5 R3S03 R14 TRACK FEEDER D38 DC CURRENT S014-41 - 6047 - AI -20 to +20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-21 (-) IW.296 16 R1S04 IW.296 25 R3S03 - - S014-42 - - 6048 - to - - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
TB2-22 (+) IW.298 17 R1S04 IW.298 6 R3S03 R14 RECTIFIER 1 DC CURRENT S014-43 - 6053 - AI 4 to 20 0 to 5000 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-22 (-) IW.298 18 R1S04 IW.298 26 R3S03 - - S014-44 - - 6054 - to - - to - - - - - - - 12.000 13.600 - - 2375 2850 - - 11.600 13.120
TB2-23 (+) IW.300 19 R1S04 IW.300 7 R3S03 R14 RECTIFIER 1 DC VOLTAGE S014-45 - 6055 - AI 4 to 20 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-23 (-) IW.300 20 R1S04 IW.300 27 R3S03 - - S014-46 - - 6056 - to - - to - - - - - - - 19.200 19.680 - - 902.5 931 - - 18.440 18.896
TB2-24 (+) IW.302 21 R1S04 IW.302 8 R3S03 R14 RECTIFIER 2 DC CURRENT S014-47 - 6057 - AI 4 to 20 0 to 5000 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-24 (-) IW.302 22 R1S04 IW.302 28 R3S03 - - S014-48 - - 6058 - to - - to - - - - - - - 12.000 13.600 - - 2375 2850 - - 11.600 13.120
TB2-25 (+) IW.304 26 R1S04 IW.304 9 R3S03 R14 RECTIFIER 2 DC VOLTAGE S014-49 - 6059 - AI 4 to 20 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-25 (-) IW.304 27 R1S04 IW.304 29 R3S03 - - S014-50 - - 6060 - to - - to - - - - - - - 19.200 19.680 - - 902.5 931 - - 18.440 18.896
TB2-26 (+) IW.306 28 R1S04 IW.306 10 R3S03 R14 RECTIFIER 3 DC CURRENT S014-51 - 6061 - AI 4 to 20 0 to 5000 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-26 (-) IW.306 29 R1S04 IW.306 30 R3S03 - - S014-52 - - 6062 - to - - to - - - - - - - 12.000 13.600 - - 2375 2850 - - 11.600 13.120
TB2-27 (+) IW.308 30 R1S04 IW.308 11 R3S03 R14 RECTIFIER 3 DC VOLTAGE S014-53 - 6063 - AI 4 to 20 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-27 (-) IW.308 31 R1S04 IW.308 31 R3S03 - - S014-54 - - 6064 - to - - to - - - - - - - 19.200 19.680 - - 902.5 931 - - 18.440 18.896
TB2-28 (+) IW.310 32 R1S04 IW.310 12 R3S03 R14 DC BUSBAR DC VOLTAGE S014-55 - 6065 - AI 4 to 20 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-28 (-) IW.310 33 R1S04 IW.310 32 R3S03 - - S014-56 - - 6066 - to - - to - - - - - 10.640 12.480 19.200 19.680 394.250 556.500 902.5 931 10.308 12.904 18.440 18.896
TB2-29 (+) IW.312 37 R1S04 IW.312 13 R3S03 R14 NEGATIVE BUSBAR DC RETURN CURRENT S014-57 - 6069 - AI 4 to 20 0 to 6000 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-29 (-) IW.312 38 R1S04 IW.312 33 R3S03 - - S014-58 - - 6070 - to - - to - - - - - - - 13.333 14.667 - - 3325 3800 - - 12.867 14.133
TB2-30 (+) IW.314 39 R1S04 IW.314 14 R3S03 - SPARE S014-59 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-30 (-) IW.314 40 R1S04 IW.314 34 R3S03 - - S014-60 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-31 (+) IW.316 41 R1S04 IW.316 15 R3S03 R14 MVAC SYSTEM INDOOR TEMP 1 S014-61 - 6075 - AI 0 to 20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-31 (-) IW.316 42 R1S04 IW.316 35 R3S03 - - S014-62 - - 6076 - to - - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.6 30.4 3.800 6.300 10.640 12.160
TB2-32 (+) IW.318 43 R1S04 IW.318 16 R3S03 R14 MVAC SYSTEM INDOOR TEMP 2 S014-63 - 6077 - AI 0 to 20 0 to 50 deg - - 1.0% 10 15 28 32 0.05 0.05 0.05 0.05 C NC NC C
TB2-32 (-) IW.318 44 R1S04 IW.318 36 R3S03 - - S014-64 - - 6078 - to - - to - - - - - 4.000 6.000 11.200 12.800 9.5 15.75 26.6 30.4 3.800 6.300 10.640 12.160

Unrestricted 749775924.xlsx/RS14 [RS14] 150 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - - - - - -
TB2-33 (+) IW.320 4 R1S05 IW.320 1 R3S04 R14 MVAC SYSTEM INDOOR TEMP 3 S015-1 - 6079 - AI 0 to 20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-33 (-) IW.320 5 R1S05 IW.320 21 R3S04 - - S015-2 - 6080 - to - - to - - - - - 4.000 6.000 11.200 12.800 9.5 15.75 26.6 30.4 3.800 6.300 10.640 12.160
TB2-34 (+) IW.322 6 R1S05 IW.322 2 R3S04 R14 MVAC SYSTEM INDOOR TEMP 4 S015-3 - 6081 - AI 0 to 20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-34 (-) IW.322 7 R1S05 IW.322 22 R3S04 - - S015-4 - 6082 - to - - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.6 30.4 3.800 6.300 10.640 12.160
TB2-35 (+) IW.324 8 R1S05 IW.324 3 R3S04 R14 MVAC SYSTEM INDOOR TEMP 5 S015-5 - 6083 - AI 0 to 20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-35 (-) IW.324 9 R1S05 IW.324 23 R3S04 - - S015-6 - - 6084 - to - - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.6 30.4 3.800 6.300 10.640 12.160
TB2-36 (+) IW.326 10 R1S05 IW.326 4 R3S04 R14 MVAC SYSTEM INDOOR TEMP 6 S015-7 - 6085 - AI 0 to 20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-36 (-) IW.326 11 R1S05 IW.326 24 R3S04 - - S015-8 - - 6086 - to - - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.600 30.400 3.800 6.300 10.640 12.160
TB2-37 (+) IW.328 15 R1S05 IW.328 5 R3S04 R14 380V NETWORK LB01 MAIN ACB (1200A) CURRENT S015-9 - 6087 - AI 4 to 20 0 to 1200 A ac - - 1.0% - - 1080 1200 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-37 (-) IW.328 16 R1S05 IW.328 25 R3S04 - - S015-10 - 6088 - to - - to - - - - - - - 18.400 20.000 - - 1026 1140 - - 17.680 19.200
TB2-38 (+) IW.330 17 R1S05 IW.330 6 R3S04 R14 380V NETWORK LB01 MAIN ACB (1200A) VOLTAGE S015-11 - 6089 - AI 4 to 20 0 to 220 V ac - - 1.0% 198 209 - - 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-38 (-) IW.330 18 R1S05 IW.330 26 R3S04 - - S015-12 - 6090 - to - - to - - - - - 18.400 19.200 #VALUE! #VALUE! 188.100 219.450 #VALUE! #VALUE! 17.680 19.960 #VALUE! #VALUE!
TB2-39 (+) IW.332 19 R1S05 IW.332 7 R3S04 R14 380V NETWORK LB23 - TO S430 125A MCCB NO.1 CURRENT S015-13 - 6091 - AI 4 to 20 0 to 125 A ac - - 1.0% - - 113 125 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-39 (-) IW.332 20 R1S05 IW.332 27 R3S04 - - S015-14 - 6092 - to - - to - - - - - - - 18.464 20.000 - - 107.35 118.75 - - 17.741 19.200
TB2-40 (+) IW.334 21 R1S05 IW.334 8 R3S04 R14 380V NETWORK LB24 - TO S430 125A MCCB NO.2 CURRENT S015-15 - 6093 - AI 4 to 20 0 to 125 A ac - - 1.0% - - 113 125 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-40 (-) IW.334 22 R1S05 IW.334 28 R3S04 - - S015-16 - - 6094 - to - - to - - - - - - - 18.464 20.000 - - 107.35 118.75 - - 17.741 19.200
TB2-41 (+) IW.336 26 R1S05 IW.336 9 R3S04 R14 380V NETWORK LB 21 - TO S435, 500A MCCB NO.1 CURRENT S015-17 - 6095 - AI 4 to 20 0 to 500 A ac - - 1.0% - - 450 500 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-41 (-) IW.336 27 R1S05 IW.336 29 R3S04 S450, S455 & S500 - - S015-18 - - 6096 - to - - to - - - - - - - 18.400 20.000 - - 427.5 475 - - 17.680 19.200
TB2-42 (+) IW.338 28 R1S05 IW.338 10 R3S04 R14 380V NETWORK LB12 300A MCCB NO.2 CURRENT S015-19 - 6097 - AI 4 to 20 0 to 300 A ac - - 1.0% - - 270 300 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-42 (-) IW.338 29 R1S05 IW.338 30 R3S04 - - S015-20 - 6098 - to - - to - - - - - - - 18.400 20.000 - - 256.5 285 - - 17.680 19.200
TB2-43 (+) IW.340 30 R1S05 IW.340 11 R3S04 R14 380V NETWORK LB40 - TO CLP STANDBY SOURCE TO CLP SUBSTATION S015-21 - 6099 - AI 4 to 20 0 to 500 A ac - - 1.0% - - 450 500 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-43 (-) IW.340 31 R1S05 IW.340 31 R3S04 SUBSTATION S3 - S3 (500A) CURRENT - S015-22 - - 6100 - to - - to - - - - - - - 18.400 20.000 - - 427.5 475 - - 17.680 19.200
TB2-44 (+) IW.342 32 R1S05 IW.342 12 R3S04 R14 380V NETWORK LB12 STANDBY SOURCE VOLTAGE S015-23 - 6101 - AI 4 to 20 0 to 220 V ac - - 1.0% 198 209 - - 5.00% 5.00% 5.00% 5.00% C NC NC C
TB2-44 (-) IW.342 33 R1S05 IW.342 32 R3S04 - - S015-24 - - 6102 - to - - to - - - - - 18.400 19.200 #VALUE! #VALUE! 188.100 219.450 #VALUE! #VALUE! 17.680 19.960 #VALUE! #VALUE!
TB2-45 (+) IW.344 37 R1S05 IW.344 13 R3S04 - SPARE S015-25 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-45 (-) IW.344 38 R1S05 IW.344 33 R3S04 - - S015-26 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-46 (+) IW.346 39 R1S05 IW.346 14 R3S04 - SPARE S015-27 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-46 (-) IW.346 40 R1S05 IW.346 34 R3S04 - - S015-28 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-47 (+) IW.348 41 R1S05 IW.348 15 R3S04 - SPARE S015-29 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-47 (-) IW.348 42 R1S05 IW.348 35 R3S04 - - S015-30 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-48 (+) IW.350 43 R1S05 IW.350 16 R3S04 - SPARE S015-31 - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-48 (-) IW.350 44 R1S05 IW.350 36 R3S04 - - S015-32 - - - - to - - to - - - - - - - - - - - - - - - - -
ZS1 = - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 = - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
TB2-1 (+) IW.352 1 R3S05 - SPARE - - - - AI -20 to +20 C NC NC C
TB2-1 (-) IW.352 21 R3S05 - - - - - - - to - - - - -
TB2-2 (+) IW.354 2 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-2 (-) IW.354 22 R3S05 - - - - - - - to - - - - -
TB2-3 (+) IW.356 3 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-3 (-) IW.356 23 R3S05 - - - - - - - to - - - - -
TB2-4 (+) IW.358 4 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-4 (-) IW.358 24 R3S05 - - - - - - - to - - - - -
TB2-5 (+) IW.360 5 R3S05 - SPARE - - - - AI -20 to +20 C NC NC C
TB2-5 (-) IW.360 25 R3S05 - - - - - - - to - - - - -
TB2-6 (+) IW.362 6 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-6 (-) IW.362 26 R3S05 - - - - - - - to - - - - -
TB2-7 (+) IW.364 7 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-7 (-) IW.364 27 R3S05 - - - - - - - to - - - - -
TB2-8 (+) IW.366 8 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-8 (-) IW.366 28 R3S05 - - - - - - - to - - - - -
TB2-9 (+) IW.368 9 R3S05 - SPARE - - - - AI -20 to +20 C NC NC C
TB2-9 (-) IW.368 29 R3S05 - - - - - - - to - - - - -
TB2-10 (+) IW.370 10 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-10 (-) IW.370 30 R3S05 - - - - - - - to - - - - -
TB2-11 (+) IW.372 11 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-11 (-) IW.372 31 R3S05 - - - - - - - to - - - - -
TB2-12 (+) IW.374 12 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-12 (-) IW.374 32 R3S05 - - - - - - - to - - - - -
TB2-13 (+) IW.376 13 R3S05 - SPARE - - - - AI -20 to +20 C NC NC C
TB2-13 (-) IW.376 33 R3S05 - - - - - - - to - - - - -
TB2-14 (+) IW.378 14 R3S05 - SPARE - - - - AI 0 to +10 C NC NC C
TB2-14 (-) IW.378 34 R3S05 - - - - - - - to - - - - -
TB2-15 (+) IW.380 15 R3S05 - SPARE - - - - AI 0 to +20 C NC NC C
TB2-15 (-) IW.380 35 R3S05 - - - - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-16 (+) IW.382 16 R3S05 - SPARE - - - - - to - - to - - - - - - - - - - - - - - - - -
TB2-16 (-) IW.382 36 R3S05 - - - - - - - to - - to - - - - - - - - - - - - - - - - -
S110-RD - - - - - - - - - - - - - - - - - - - - - - - - - - - -
S110-BK - - - - - - - - - - - - - - - - - - - - - - - - - - - -
S112-BL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS14 [RS14] 151 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

RL-A - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
RL-01 Q4.0 4 R1S01 Q4.0 2 R2S02 R14 MAIN INCOMER H05 (R14VB01) VCB OPEN S016-1 - 4049 4050 CO - - - - - - - - - - - - - - - - - -
RL-02 Q4.1 5 R1S01 Q4.1 3 R2S02 R14 MAIN INCOMER H05 (R14VB01) VCB CLOSE S016-2 - 4049 4051 CO - - - - - - - - - - - - - - - - - -
RL-03 Q4.2 6 R1S01 Q4.2 6 R2S02 R14 BUS SECTION H06 (R14VB11) VCB OPEN S016-3 - 4053 4054 CO - - - - - - - - - - - - - - - - - -
RL-04 Q4.3 7 R1S01 Q4.3 7 R2S02 R14 BUS SECTION H06 (R14VB11) VCB CLOSE S016-4 - 4053 4055 CO - - - - - - - - - - - - - - - - - -
RL-05 Q4.4 8 R1S01 Q4.4 12 R2S02 R14 BUS SECTION H06 (R14VB11) LHS UNDER VOLTAGE RESET S016-5 - - - CO - - - - - - - - - - - - - - - - - -
RL-06 Q4.5 9 R1S01 Q4.5 13 R2S02 R14 AUTO CHANGEOVER PANEL INHIBIT CONTROL S016-6 - 4111 4112 CO - - - - - - - - - - - - - - - - - -
RL-07 Q4.6 10 R1S01 Q4.6 16 R2S02 R14 AUTO CHANGEOVER PANEL AUTO CHANGEOVER CONTROL S016-7 - 4056 4057 CO - - - - - - - - - - - - - - - - - -
RL-08 Q4.7 11 R1S01 Q4.7 17 R2S02 R14 AUTO CHANGEOVER PANEL AUTO CHANGEOVER ENABLE S016-8 - 4058 4059 CO - - - - - - - - - - - - - - - - - -
L+ 19 R2S02
M 20 R2S02
RL-09 Q5.0 15 R1S01 Q5.0 22 R2S02 R14 RING MAIN H01 (R14VB20) (FUTURE) VCB OPEN S016-9 - 4060 4061 CO - - - - - - - - - - - - - - - - - -
RL-10 Q5.1 16 R1S01 Q5.1 23 R2S02 R14 RING MAIN H01 (R14VB20) (FUTURE) VCB CLOSE S016-10 - 4060 4062 CO - - - - - - - - - - - - - - - - - -
RL-11 Q5.2 17 R1S01 Q5.2 26 R2S02 R14 RING MAIN H03 (R14VB21) (TO R16) VCB OPEN S016-11 - 4063 4064 CO - - - - - - - - - - - - - - - - - -
RL-12 Q5.3 18 R1S01 Q5.3 27 R2S02 R14 RING MAIN H03 (R14VB21) (TO R16) VCB CLOSE S016-12 - 4063 4065 CO - - - - - - - - - - - - - - - - - -
RL-13 Q5.4 19 R1S01 Q5.4 32 R2S02 R14 RING MAIN H08 (R14VB22) (TO R15) VCB OPEN S016-13 - 4066 4067 CO - - - - - - - - - - - - - - - - - -
RL-14 Q5.5 20 R1S01 Q5.5 33 R2S02 R14 RING MAIN H08 (R14VB22) (TO R15) VCB CLOSE S016-14 - 4066 4068 CO - - - - - - - - - - - - - - - - - -
RL-15 Q5.6 21 R1S01 Q5.6 36 R2S02 R14 RING MAIN H10 (R14VB23) (TO R08) VCB OPEN S016-15 - 4069 4070 CO - - - - - - - - - - - - - - - - - -
RL-16 Q5.7 22 R1S01 Q5.7 37 R2S02 R14 RING MAIN H10 (R14VB23) (TO R08) VCB CLOSE S016-16 - 4069 4071 CO - - - - - - - - - - - - - - - - - -
L+ 39 R2S02
M 40 R2S02
RL-17 Q6.0 26 R1S01 Q6.0 2 R2S03 R14 RING MAIN H12 (R14VB24) (FUTURE) VCB OPEN S016-17 - 4072 4073 CO - - - - - - - - - - - - - - - - - -
RL-18 Q6.1 27 R1S01 Q6.1 3 R2S03 R14 RING MAIN H12 (R14VB24) (FUTURE) VCB CLOSE S016-18 - 4072 4074 CO - - - - - - - - - - - - - - - - - -
RL-19 Q6.2 28 R1S01 Q6.2 6 R2S03 R14 RING MAIN H07 (R14VB02) (FUTURE) VCB OPEN S016-19 - 4075 4076 CO - - - - - - - - - - - - - - - - - -
RL-20 Q6.3 29 R1S01 Q6.3 7 R2S03 R14 RING MAIN H07 (R14VB02) (FUTURE) VCB CLOSE S016-20 - 4075 4077 CO - - - - - - - - - - - - - - - - - -
RL-21 Q6.4 30 R1S01 Q6.4 12 R2S03 R14 RECTIFIER FEEDER H02 (R14VB50) VCB OPEN S016-21 - 4078 4079 CO - - - - - - - - - - - - - - - - - -
RL-22 Q6.5 31 R1S01 Q6.5 13 R2S03 R14 RECTIFIER FEEDER H02 (R14VB50) VCB CLOSE S016-22 - 4078 4080 CO - - - - - - - - - - - - - - - - - -
RL-23 Q6.6 32 R1S01 Q6.6 16 R2S03 R14 RECTIFIER FEEDER H04 (R14VB51) VCB OPEN S016-23 - 4081 4082 CO - - - - - - - - - - - - - - - - - -
RL-24 Q6.7 33 R1S01 Q6.7 17 R2S03 R14 RECTIFIER FEEDER H04 (R14VB51) VCB CLOSE S016-24 - 4081 4083 CO - - - - - - - - - - - - - - - - - -
L+ 19 R2S03
M 20 R2S03
RL-25 Q7.0 37 R1S01 Q7.0 22 R2S03 R14 RECTIFIER FEEDER H09 (R14VB52) VCB OPEN S016-25 - 4084 4085 CO - - - - - - - - - - - - - - - - - -
RL-26 Q7.1 38 R1S01 Q7.1 23 R2S03 R14 RECTIFIER FEEDER H09 (R14VB52) VCB CLOSE S016-26 - 4084 4086 CO - - - - - - - - - - - - - - - - - -
RL-27 Q7.2 39 R1S01 Q7.2 26 R2S03 R14 RECTIFIER FEEDER D1 DCCB OPEN S016-27 - 5097 5099 CO - - - - - - - - - - - - - - - - - -
RL-28 Q7.3 40 R1S01 Q7.3 27 R2S03 R14 RECTIFIER FEEDER D1 DCCB CLOSE S016-28 - 5097 5098 CO - - - - - - - - - - - - - - - - - -
RL-29 Q7.4 41 R1S01 Q7.4 32 R2S03 R14 RECTIFIER FEEDER D2 DCCB OPEN S016-29 - 5101 5103 CO - - - - - - - - - - - - - - - - - -
RL-30 Q7.5 42 R1S01 Q7.5 33 R2S03 R14 RECTIFIER FEEDER D2 DCCB CLOSE S016-30 - 5101 5102 CO - - - - - - - - - - - - - - - - - -
RL-31 Q7.6 43 R1S01 Q7.6 36 R2S03 R14 RECTIFIER FEEDER D3 DCCB OPEN S016-31 - 5105 5107 CO - - - - - - - - - - - - - - - - - -
RL-32 Q7.7 44 R1S01 Q7.7 37 R2S03 R14 RECTIFIER FEEDER D3 DCCB CLOSE S016-32 - 5105 5106 CO - - - - - - - - - - - - - - - - - -
L+ 39 R2S03
M 40 R2S03
FR0 FR0 34 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - -
ONAND
THECOMMON
32 CO
FR1 FR1 35 FR1 - - - ENABLE CONTACT RETURN LINE - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 UE0 31 - - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 UE1 35 - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - -
ZS1 ZS1 1 ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
ZS2 ZS2 2 ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - - - - - - - - - - - - -
RL-33 Q8.0 4 R1S02 Q8.0 2 R2S04 R14 TRACK FEEDER D31 DCCB OPEN S017-1 - 5067 5070 CO - - - - - - - - - - - - - - - - - -
RL-34 Q8.1 5 R1S02 Q8.1 3 R2S04 R14 TRACK FEEDER D31 DCCB CLOSE S017-2 - 5067 5069 CO - - - - - - - - - - - - - - - - - -
RL-35 Q8.2 6 R1S02 Q8.2 6 R2S04 R14 TRACK FEEDER D31 LINE TEST CONTROL ON S017-3 - 5067 5120 CO - - - - - - - - - - - - - - - - - -
RL-36 Q8.3 7 R1S02 Q8.3 7 R2S04 R14 TRACK FEEDER D31 LINE TEST CONTROL OFF S017-4 5067 5068 CO
RL-37 Q8.4 8 R1S02 Q8.4 12 R2S04 R14 TRACK FEEDER D32 DCCB OPEN S017-5 - 5072 5075 CO - - - - - - - - - - - - - - - - - -
RL-38 Q8.5 9 R1S02 Q8.5 13 R2S04 R14 TRACK FEEDER D32 DCCB CLOSE S017-6 - 5072 5074 CO - - - - - - - - - - - - - - - - - -
RL-39 Q8.6 10 R1S02 Q8.6 16 R2S04 R14 TRACK FEEDER D32 LINE TEST CONTROL ON S017-7 - 5072 5121 CO - - - - - - - - - - - - - - - - - -
RL-40 Q8.7 11 R1S02 Q8.7 17 R2S04 R14 TRACK FEEDER D32 LINE TEST CONTROL OFF S017-8 5072 5073 CO
L+ 19 R2S04
M 20 R2S04
RL-41 Q9.0 15 R1S02 Q9.0 22 R2S04 R14 TRACK FEEDER D37 DCCB OPEN S017-9 - 5077 5080 CO - - - - - - - - - - - - - - - - - -
RL-42 Q9.1 16 R1S02 Q9.1 23 R2S04 R14 TRACK FEEDER D37 DCCB CLOSE S017-10 - 5077 5079 CO - - - - - - - - - - - - - - - - - -
RL-43 Q9.2 17 R1S02 Q9.2 26 R2S04 R14 TRACK FEEDER D37 LINE TEST CONTROL ON S017-11 - 5077 5122 CO - - - - - - - - - - - - - - - - - -
RL-44 Q9.3 18 R1S02 Q9.3 27 R2S04 R14 TRACK FEEDER D37 LINE TEST CONTROL OFF S017-12 5077 5078 CO
RL-45 Q9.4 19 R1S02 Q9.4 32 R2S04 R14 AUXILIARY TRANSFORMER H11 VCB OPEN S017-13 - 4087 4088 CO - - - - - - - - - - - - - - - - - -
RL-46 Q9.5 20 R1S02 Q9.5 33 R2S04 (R14VB60)
R14 AUXILIARY TRANSFORMER H11 VCB CLOSE S017-14 - 4087 4089 CO - - - - - - - - - - - - - - - - - -
RL-47 Q9.6 21 R1S02 Q9.6 36 R2S04 (R14VB60)
R14 DC COMMON EQUIPMENT D07 (OVPD) CONTACTOR RESET S017-15 - 4103 4104 CO - - - - - - - - - - - - - - - - - -
RL-48 Q9.7 22 R1S02 Q9.7 37 R2S04 R14 DC COMMON EQUIPMENT D07 (OVPD) CONTACTOR CLOSE S017-16 - 4105 4106 CO - - - - - - - - - - - - - - - - - -
L+ 39 R2S04
M 40 R2S04
RL-49 Q10.0 26 R1S02 Q10.0 2 R2S05 - SPARE S017-19 - 5067 5068 - - - - - - - - - - - - - - - - - -
RL-50 Q10.1 27 R1S02 Q10.1 3 R2S05 - SPARE S017-20 - 5072 5073 - - - - - - - - - - - - - - - - - -
RL-51 Q10.2 28 R1S02 Q10.2 6 R2S05 R14 DUMMY CB VCB OPEN/CLOSE (MOST SIGNIFICANT internal - - - CO - - - - - - - - - - - - - - - - - -
RL-52 Q10.3 29 R1S02 Q10.3 7 R2S05 R14 DUMMY CB BIT) OPEN/CLOSE (LEAST SIGNIFICANT
VCB wiring
internal - - - CO - - - - - - - - - - - - - - - - - -
RL-53 Q10.4 30 R1S02 Q10.4 12 R2S05 R14 TRACK FEEDER D38 BIT)
DCCB OPEN wiring
S017-21 - 5082 5085 CO - - - - - - - - - - - - - - - - - -
RL-54 Q10.5 31 R1S02 Q10.5 13 R2S05 R14 TRACK FEEDER D38 DCCB CLOSE S017-22 - 5082 5084 CO - - - - - - - - - - - - - - - - - -
RL-55 Q10.6 32 R1S02 Q10.6 16 R2S05 R14 TRACK FEEDER D38 LINE TEST CONTROL ON S017-23 - 5082 5123 CO - - - - - - - - - - - - - - - - - -
RL-56 Q10.7 33 R1S02 Q10.7 17 R2S05 R14 TRACK FEEDER D38 LINE TEST CONTROL OFF S017-24 - 5082 5083 CO - - - - - - - - - - - - - - - - - -
L+ 19 R2S05
M 20 R2S05
RL-57 Q11.0 37 R1S02 Q11.0 22 R2S05 - SPARE S017-25 - - - - - - - - - - - - - - - - - - - - - -
RL-58 Q11.1 38 R1S02 Q11.1 23 R2S05 - SPARE S017-26 - - - - - - - - - - - - - - - - - - - - -
RL-59 Q11.2 39 R1S02 Q11.2 26 R2S05 - SPARE S017-27 - - - - - - - - - - - - - - - - - - - - -
RL-60 Q11.3 40 R1S02 Q11.3 27 R2S05 - SPARE S017-28 - - - - - - - - - - - - - - - - - - - - -
RL-61 Q11.4 41 R1S02 Q11.4 32 R2S05 - SPARE S017-29 - - - - - - - - - - - - - - - - - - - - -
RL-62 Q11.5 42 R1S02 Q11.5 33 R2S05 - SPARE S017-30 - - - - - - - - - - - - - - - - - - - - -
RL-63 Q11.6 43 R1S02 Q11.6 36 R2S05 - SPARE S017-31 - - - - - - - - - - - - - - - - - - - - -
RL-64 Q11.7 44 R1S02 Q11.7 37 R2S05 - SPARE S017-32 - - - - - - - - - - - - - - - - - - - - -
L+ 39 R2S05
M 40 R2S05
FR0 FR0 34 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - - - - - - - - - - - - - -
ONAND
THECOMMON
32 CO
FR1 FR1 35 FR1 - - - ENABLE CONTACT RETURN LINE - - - - - - - - - - - - - - - - - - - - - - -
ON THE 32 CO
UE0 UE0 45 UE0 31 - - +110V DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - -
UE1 UE1 46 UE1 35 - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - - - - - - - - - - - - - -
Q12.0 2 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q12.1 3 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q12.2 6 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q12.3 7 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q12.4 12 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q12.5 13 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q12.6 16 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q12.7 17 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS14 [RS14] 152 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE) SCADA / RTU CONFIGURATION INFORMATION


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Range (mA) Values Of-State Value
Terminal Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal to to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
No. Terminal Pin No. Terminal Pin No. (+ve) (-ve) Delay LL L H HH
No. No. (sec)

L+ 19 R2S06
M 20 R2S06
Q13.0 22 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q13.1 23 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q13.2 26 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q13.3 27 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q13.4 32 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q13.5 33 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q13.6 36 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
Q13.7 37 R2S06 - SPARE CO - - - - - - - - - - - - - - - - - -
L+ 39
M 40
- - - R14 TRACKFEEDER (SPARE 1) DCCB OPEN TBD - 5087 5090 CO - - - - - - - - - - - - - - - - - -
- - - R14 TRACKFEEDER (SPARE 1) DCCB CLOSE TBD - 5087 5089 CO - - - - - - - - - - - - - - - - - -
- - - R14 TRACKFEEDER (SPARE 1) LINE TEST OVERRIDE CLOSE TBD - 5087 5088 CO - - - - - - - - - - - - - - - - - -
- - - R14 TRACKFEEDER (SPARE 2) DCCB OPEN TBD - 5092 5095 CO - - - - - - - - - - - - - - - - - -
- - - R14 TRACKFEEDER (SPARE 2) DCCB CLOSE TBD - 5092 5094 CO - - - - - - - - - - - - - - - - - -
- - - R14 TRACKFEEDER (SPARE 2) LINE TEST OVERRIDE CLOSE TBD - 5092 5093 CO - - - - - - - - - - - - - - - - - -
- - - R14 TRACKFEEDER (SPARE 1) LINE TEST CONTROL ON TBD - 5067 5124 CO - - - - - - - - - - - - - - - - - -
- - - R14 TRACKFEEDER (SPARE 2) LINE TEST CONTROL ON TBD - 5067 5125 CO - - - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS14 [RS14] 153 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -


ZS2 ZS2 2 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-2 I4.0 4 R0S7 I4.0 1 R0S02 R15 RING MAIN H03 (R15VB40)(TO R16) CONTROL SELECTOR SWITCH S005-3 - 1004 1005 SB - LOCAL REMOTE - - -

DI-4 I4.1 5 R0S7 I4.1 2 R0S02 R15 RING MAIN H03 (R15VB40)(TO R16) O/C EARTH FAULT TRIP S005-4 - 1006 1007 SB - RESET OPERATED - - -

DI-6 I4.2 6 R0S7 I4.2 3 R0S02 R15 RING MAIN H03 (R15VB40)(TO R16) SOLKOR TRIP S005-5 - 1006 1008 SB - RESET OPERATED - - -

DI-8 I4.3 7 R0S7 I4.3 4 R0S02 R15 RING MAIN H03 (R15VB40)(TO R16) OVERLOAD ALARM S005-6 - 1006 1009 SB - NORMAL OPERATED - - -

DI-10 I4.4 8 R0S7 I4.4 5 R0S02 R15 RING MAIN H03 (R15VB40)(TO R16) PILOT WIRE ALARM S005-7 - - - SB - NORMAL OPERATED - - -

DI-12 I4.5 9 R0S7 I4.5 6 R0S02 R15 RING MAIN H03 (R15VB40)(TO R16) TRIP CCT SUPERVISION ALARM S005-8 - 1010 1011 SB - NORMAL OPERATED - - -

DI-14 I4.6 10 R0S07 I4.6 7 R0S02 R15 RING MAIN H04 (R15VB41)(TO R10) CONTROL SELECTOR SWITCH S005-13 - 1019 1020 SB - LOCAL REMOTE - - -

DI-16 I4.7 11 R0S07 I4.7 8 R0S02 R15 RING MAIN H04 (R15VB41)(TO R10) O/C EARTH FAULT TRIP S005-14 - 1021 1022 SB - RESET OPERATED - - -

UM0 UM0 12 R0S07 - 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW0 UW0 13 R0S07 - 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 11 R0S02 R15 RING MAIN H04 (R15VB41)(TO R10) SOLKOR TRIP S005-15 - 1021 1023 SB - RESET OPERATED - - -

DI-20 I5.1 16 R0S07 I5.1 12 R0S02 R15 RING MAIN H04 (R15VB41)(TO R10) OVERLOAD ALARM S005-16 - 1021 1024 SB - NORMAL OPERATED - - -

DI-22 I5.2 17 R0S07 I5.2 13 R0S02 R15 RING MAIN H04 (R15VB41)(TO R10) PILOT WIRE ALARM S005-17 - - - SB - NORMAL OPERATED - - -

DI-24 I5.3 18 R0S07 I5.3 14 R0S02 R15 RING MAIN H04 (R15VB41)(TO R10) TRIP CCT SUPERVISION ALARM S005-18 - 1025 1026 SB - NORMAL OPERATED - - -

DI-26 I5.4 19 R0S07 I5.4 15 R0S02 R15 RING MAIN H05 (R15VB42)(TO R14) CONTROL SELECTOR SWITCH S005-23 - 1034 1035 SB - LOCAL REMOTE - - -

DI-28 I5.5 20 R0S07 I5.5 16 R0S02 R15 RING MAIN H05 (R15VB42)(TO R14) O/C EARTH FAULT TRIP S005-24 - 1036 1037 SB - RESET OPERATED - - -

DI-30 I5.6 21 R0S07 I5.6 17 R0S02 R15 RING MAIN H05 (R15VB42)(TO R14) SOLKOR TRIP S005-25 - 1036 1038 SB - RESET OPERATED - - -

DI-32 I5.7 22 R0S07 I5.7 18 R0S02 R15 RING MAIN H05 (R15VB42)(TO R14) OVERLOAD ALARM S005-26 - 1036 1039 SB - NORMAL OPERATED - - -

UM1 UM1 23 R0S07 1L+ 19 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW1 UW1 24 R0S07 1M 20 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 21 R0S02 R15 RING MAIN H05 (R15VB42)(TO R14) PILOT WIRE ALARM S005-27 - 1036 1040 SB - NORMAL OPERATED - - -

DI-36 I6.1 27 R0S07 I6.1 22 R0S02 R15 RING MAIN H05 (R15VB42)(TO R14) TRIP CCT SUPERVISION ALARM S005-28 - 1041 1042 SB - NORMAL OPERATED - - -

DI-38 I6.2 28 R0S07 I6.2 23 R0S02 R15 RECTIFIER FEEDER H01 (R15VB50) CONTROL SELECTOR SWITCH S005-33 - 1050 1051 SB - LOCAL REMOTE - - -

DI-40 I6.3 29 R0S07 I6.3 24 R0S02 R15 RECTIFIER FEEDER H01 (R15VB50) O/C EARTH FAULT TRIP S005-34 - 1052 1053 SB - RESET OPERATED - - -

DI-42 I6.4 30 R0S07 I6.4 25 R0S02 R15 RECTIFIER FEEDER H01 (R15VB50) OVERLOAD TRIP S005-35 - 1052 1054 SB - RESET OPERATED - - -

DI-44 I6.5 31 R0S07 I6.5 26 R0S02 R15 RECTIFIER FEEDER H01 (R15VB50) TRIP CCT SUPERVISION ALARM S005-36 - 1062 1063 SB - NORMAL OPERATED - - -

DI-46 I6.6 32 R0S07 I6.6 27 R0S02 R15 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-37 - 1052 1055 SB - RESET OPERATED - - -

DI-48 I6.7 33 R0S07 I6.7 28 R0S02 R15 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-38 - 1052 1056 SB - NORMAL OPERATED - - -

UM2 UM2 34 R0S07 - 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW2 UW2 35 R0S07 - 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 31 R0S02 R15 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S006-1 - 1052 1057 SB - RESET OPERATED - - -

DI-52 I7.1 38 R0S07 I7.1 32 R0S02 R15 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S006-2 - 1052 1058 SB - NORMAL OPERATED - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 154 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-54 I7.2 39 R0S07 I7.2 33 R0S02 R15 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S006-3 - 1052 1059 SB - RESET OPERATED - - -

DI-56 I7.3 40 R0S07 I7.3 34 R0S02 R15 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S006-4 - 1052 1060 SB - NORMAL OPERATED - - -

DI-58 I7.4 41 R0S07 I7.4 35 R0S02 R15 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S006-5 - 1052 1061 SB - RESET OPERATED - - -

DI-60 I7.5 42 R0S07 I7.5 36 R0S02 R15 RECTIFIER 1 FRAME EARTH ALARM S006-6 - - - SB - NORMAL OPERATED - - -
DI-62 I7.6 43 R0S07 I7.6 37 R0S02 R15 RECTIFIER 1 FRAME EARTH TRIP S006-7 - 1064 1065 SB - RESET OPERATED - - -
DI-64 I7.7 44 R0S07 I7.7 38 R0S02 R15 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S006-8 - 1066 1067 SB - NORMAL OPERATED - - -
UM3 UM3 45 R0S07 2L+ 39 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S07 2M 40 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S08 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 1 R0S03 R15 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S006-11 - 1068 1069 SB - RESET OPERATED - - -
DI-68 I8.1 5 R0S08 I8.1 2 R0S03 R15 RECTIFIER 1 DIODE OVER TEMP ALARM S006-12 - 1070 1071 SB - NORMAL OPERATED - - -
DI-70 I8.2 6 R0S08 I8.2 3 R0S03 R15 RECTIFIER 1 DIODE OVER TEMP TRIP S006-13 - 1072 1073 SB - RESET OPERATED - - -
DI-72 I8.3 7 R0S08 I8.3 4 R0S03 R15 RECTIFIER FEEDER D1 REVERSE CURRENT TRIP S008-18 - 2045 2046 SB - RESET OPERATED - - -

DI-74 I8.4 8 R0S08 I8.4 5 R0S03 R15 RECTIFIER 1 SURGE ARRESTOR ALARM S006-15 - - - SB - NORMAL OPERATED - - -
DI-76 I8.5 9 R0S08 I8.5 6 R0S03 R15 RECTIFIER 1 SURGE ARRESTOR TRIP S006-16 - - - SB - RESET OPERATED - - -
DI-78 I8.6 10 R0S08 I8.6 7 R0S03 R15 RECTIFIER 1 FILTER CIRCUIT ALARM S006-17 - - - SB - NORMAL OPERATED - - -
DI-80 I8.7 11 R0S08 I8.7 8 R0S03 R15 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S006-18 - 1080 1081 SB - NORMAL OPERATED - - -

UM0 UM0 12 R0S08 - 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW0 UW0 13 R0S08 - 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 11 R0S03 R15 RECTIFIER FEEDER H02 (R15VB51) CONTROL SELECTOR SWITCH S006-23 - 2004 2005 SB - LOCAL REMOTE - - -

DI-84 I9.1 16 R0S08 I9.1 12 R0S03 R15 RECTIFIER FEEDER H02 (R15VB51) O/C EARTH FAULT TRIP S006-24 2006 2007 SB - RESET OPERATED - - -

DI-86 I9.2 17 R0S08 I9.2 13 R0S03 R15 RECTIFIER FEEDER H02 (R15VB51) OVERLOAD TRIP S006-25 - 2006 2008 SB - RESET OPERATED - - -

DI-88 I9.3 18 R0S08 I9.3 14 R0S03 R15 RECTIFIER FEEDER H02 (R15VB51) TRIP CCT SUPERVISION ALARM S006-26 - 2016 2017 SB - NORMAL OPERATED - - -

DI-90 I9.4 19 R0S08 I9.4 15 R0S03 R15 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-27 - 2006 2009 SB - RESET OPERATED - - -

DI-92 I9.5 20 R0S08 I9.5 16 R0S03 R15 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-28 - 2006 2010 SB - NORMAL OPERATED - - -

DI-94 I9.6 21 R0S08 I9.6 17 R0S03 R15 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-31 - 2006 2011 SB - RESET OPERATED - - -

DI-96 I9.7 22 R0S08 I9.7 18 R0S03 R15 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-32 - 2006 2012 SB - NORMAL OPERATED - - -

UM1 UM1 23 R0S08 1L+ 19 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW1 UW1 24 R0S08 1M 20 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 21 R0S03 R15 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-33 - 2006 2013 SB - RESET OPERATED - - -

DI-100 I10.1 27 R0S08 I10.1 22 R0S03 R15 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-34 - 2006 2014 SB - NORMAL OPERATED - - -

DI-102 I10.2 28 R0S08 I10.2 23 R0S03 R15 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-35 - 2006 2015 SB - RESET OPERATED - - -

DI-104 I10.3 29 R0S08 I10.3 24 R0S03 R15 RECTIFIER 2 FRAME EARTH ALARM S006-36 - - - SB - NORMAL OPERATED - - -
DI-106 I10.4 30 R0S08 I10.4 25 R0S03 R15 RECTIFIER 2 FRAME EARTH TRIP S006-37 - 2018 2019 SB - RESET OPERATED - - -
DI-108 I10.5 31 R0S08 I10.5 26 R0S03 R15 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-38 - 2020 2021 SB - NORMAL OPERATED - - -
DI-110 I10.6 32 R0S08 I10.6 27 R0S03 R15 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S007-1 - 2022 2023 SB - RESET OPERATED - - -
DI-112 I10.7 33 R0S08 I10.7 28 R0S03 R15 RECTIFIER 2 DIODE OVER TEMP ALARM S007-2 - 2024 2025 SB - NORMAL OPERATED - - -
UM2 UM2 34 R0S08 - 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 UW2 35 R0S08 - 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 31 R0S03 R15 RECTIFIER 2 DIODE OVER TEMP TRIP S007-3 - 2026 2027 SB - RESET OPERATED - - -
DI-116 I11.1 38 R0S08 I11.1 32 R0S03 R15 RECTIFIER FEEDER D2 REVERSE CURRENT TRIP S008-24 - 2054 2055 SB - RESET OPERATED - - -

DI-118 I11.2 39 R0S08 I11.2 33 R0S03 R15 RECTIFIER 2 SURGE ARRESTOR ALARM S007-5 - - - SB - NORMAL OPERATED - - -
DI-120 I11.3 40 R0S08 I11.3 34 R0S03 R15 RECTIFIER 2 SURGE ARRESTOR TRIP S007-6 - - - SB - RESET OPERATED - - -
DI-122 I11.4 41 R0S08 I11.4 35 R0S03 R15 RECTIFIER 2 FILTER CIRCUIT ALARM S007-7 - - - SB - NORMAL OPERATED - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 155 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-124 I11.5 42 R0S08 I11.5 36 R0S03 R15 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S007-8 - 2034 2035 SB - NORMAL OPERATED - - -

DI-126 I11.6 43 R0S08 I11.6 37 R0S03 - SPARE S007-11 - - - - - - - - -


DI-128 I11.7 44 R0S08 I11.7 38 R0S03 - SPARE S007-12 - - - - - - - - -
UM3 UM3 45 R0S08 2L+ 39 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S08 2M 40 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S09 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 1 R0S04 - SPARE S007-13 - - - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 2 R0S04 - SPARE S007-14 - - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 3 R0S04 - SPARE S007-15 - - - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 4 R0S04 - SPARE S007-16 - - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 5 R0S04 - SPARE S007-17 - - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 6 R0S04 - SPARE S007-18 - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 7 R0S04 - SPARE S007-21 - - - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 8 R0S04 - SPARE S007-22 - - - - - - - - -
UM0 UM0 12 R0S09 - 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S09 - 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 11 R0S04 - SPARE S007-23 - - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 12 R0S04 - SPARE S007-24 - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 13 R0S04 - SPARE S007-25 - - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 14 R0S04 - SPARE S007-26 - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 15 R0S04 - SPARE S007-27 - - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 16 R0S04 - SPARE S007-28 - - - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 17 R0S04 - SPARE S007-31 - - - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 18 R0S04 - SPARE S007-32 - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 156 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UM1 UM1 23 R0S09 1L+ 19 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW1 UW1 24 R0S09 1M 20 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 21 R0S04 - SPARE S007-33 - - - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 22 R0S04 - SPARE S007-34 - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 23 R0S04 - SPARE S007-35 - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 24 R0S04 - SPARE S007-36 - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 25 R0S04 - SPARE S007-37 - - - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 26 R0S04 - SPARE S007-38 - - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 27 R0S04 R15 AUXILIARY TRANSFORMER H06 CONTROL SELECTOR SWITCH S008-3 - 1089 1090 SB - LOCAL REMOTE - - -
(R15VB60)
DI-176 I14.7 33 R0S09 I14.7 28 R0S04 R15 AUXILIARY TRANSFORMER H06 O/C EARTH FAULT TRIP S008-4 - 1091 1092 SB - RESET OPERATED - - -
(R15VB60)
UM2 UM2 34 R0S09 - 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 UW2 35 R0S09 - 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 31 R0S04 R15 AUXILIARY TRANSFORMER H06 TRIP CCT SUPEVISION ALARM S008-5 - 1098 1099 SB - NORMAL OPERATED - - -
(R15VB60)
DI-180 I15.1 38 R0S09 I15.1 32 R0S04 R15 AUXILIARY TRANSFORMER H06 PRESSURE GAUGE TRIP S008-6 - 1091 1093 SB - RESET OPERATED - - -
(R15VB60)
DI-182 I15.2 39 R0S09 I15.2 33 R0S04 R15 11KV PANEL CONTROL CIRCUIT SUPERVISION S008-7 - 1091 1095 SB - NORMAL OPERATED - - -

DI-184 I15.3 40 R0S09 I15.3 34 R0S04 R15 AUXILIARY TRANSFORMER H06 LIQUID LEVEL LOW TRIP S008-8 - 1091 1094 SB - RESET OPERATED - - -
(R15VB60)
DI-186 I15.4 41 R0S09 I15.4 35 R0S04 R15 AUXILIARY TRANSFORMER H06 WINDING TEMP HIGH ALARM S008-11 - - - SB - NORMAL OPERATED - - -
(R15VB60)
DI-188 I15.5 42 R0S09 I15.5 36 R0S04 R15 AUXILIARY TRANSFORMER H06 WINDING TEMP HIGH TRIP S008-12 - - - SB - RESET OPERATED - - -
(R15VB60)
DI-190 I15.6 43 R0S09 I15.6 37 R0S04 R15 AUXILIARY TRANSFORMER H06 LIQUID TEMP HIGH ALARM S008-13 - 1091 1096 SB - NORMAL OPERATED - - -
(R15VB60)
DI-192 I15.7 44 R0S09 I15.7 38 R0S04 R15 AUXILIARY TRANSFORMER H06 LIQUID TEMP HIGH TRIP S008-14 - 1091 1097 SB - RESET OPERATED - - -
(R15VB60)
UM3 UM3 45 R0S09 2L+ 39 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S09 2M 40 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S10 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 1 R1S02 R15 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S008-17 - 2043 2044 SB - LOCAL REMOTE - - -

DI-196 I16.1 5 R0S10 I16.1 2 R1S02 R15 RECTIFIER FEEDER D1 TRIP CCT SUPERVISION ALARM S012-24 - 2047 2048 SB - NORMAL OPERATED - - -

DI-198 I16.2 6 R0S10 I16.2 3 R1S02 R15 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S008-23 - 2052 2053 SB - LOCAL REMOTE - - -

DI-200 I16.3 7 R0S10 I16.3 4 R1S02 R15 RECTIFIER FEEDER D2 TRIP CCT SUPERVISION ALARM S012-25 - 2056 2057 SB - NORMAL OPERATED - - -

DI-202 I16.4 8 R0S10 I16.4 5 R1S02 R15 RECTIFIER FEEDER D3 CONTROL SELECTOR SWITCH S008-27 - - - SB - LOCAL REMOTE - - -

DI-204 I16.5 9 R0S10 I16.5 6 R1S02 R15 RECTIFIER FEEDER D3 TRIP CCT SUPERVISION ALARM S008-28 - - - SB - NORMAL OPERATED - - -

DI-206 I16.6 10 R0S10 I16.6 7 R1S02 R15 TRACK FEEDER D33 CONTROL SELECTOR SWITCH S008-33 - 2063 2064 SB - LOCAL REMOTE - - -

DI-208 I16.7 11 R0S10 I16.7 8 R1S02 R15 TRACK FEEDER D33 INSTANT OVERCURRENT S008-34 - 2065 2066 SB - RESET OVERCURRENT/ - - -
OPERATED

UM0 UM0 12 R0S10 - 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW0 UW0 13 R0S10 - 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 11 R1S02 R15 TRACK FEEDER D33 TRANSFER TRIP R15DB33&34 FROM R16 S008-35 - 3083 3084 SB - RESET OPERATED - - -

DI-212 I17.1 16 R0S10 I17.1 12 R1S02 R15 TRACK FEEDER D33 RATE OF RISE TRIP S008-36 - 2067 2068 SB - RESET OPERATED - - -
DI-214 I17.2 17 R0S10 I17.2 13 R1S02 R15 TRACK FEEDER D33 UNDERVOLTAGE TRIP S008-37 - - - SB - RESET OPERATED - - -
DI-216 I17.3 18 R0S10 I17.3 14 R1S02 R15 TRACK FEEDER D33 LINE TESTING S008-38 - 2069 2070 SB - COMPLETED IN PROGRESS - - -
DI-218 I17.4 19 R0S10 I17.4 15 R1S02 R15 TRACK FEEDER D33 LINE IMPEDANCE LOW S009-1 - 2071 2072 SB - NORMAL OPERATED - - -
DI-220 I17.5 20 R0S10 I17.5 16 R1S02 R15 TRACK FEEDER D33 TRIP CCT SUPERVISION ALARM S009-2 - 2073 2074 SB - NORMAL OPERATED - - -

DI-222 I17.6 21 R0S10 I17.6 17 R1S02 R15 TRACK FEEDER D33 TRANSFER TRIP S009-3 - 3077 3078 SB - RESET OPERATED - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 157 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-224 I17.7 22 R0S10 I17.7 18 R1S02 R15 TRACK FEEDER D33 LINE TEST CONTROL SELECTOR SWITCH S009-4 - 2105 2106 SB - OFF ON - - -

UM1 UM1 23 R0S10 1L+ 19 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW1 UW1 24 R0S10 1M 20 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 21 R1S02 R15 TRACK FEEDER D34 CONTROL SELECTOR SWITCH S009-7 - 2078 2079 SB - LOCAL REMOTE - - -

DI-228 I18.1 27 R0S10 I18.1 22 R1S02 R15 TRACK FEEDER D34 INSTANT OVERCURRENT S009-8 - 2080 2081 SB - RESET OVERCURRENT/ - - -
OPERATED

DI-230 I18.2 28 R0S10 I18.2 23 R1S02 R15 TRACK FEEDER D34 TIME DELAY OVERCURRENT ALARM S009-11 - - - SB - NORMAL OPERATED - - -

DI-232 I18.3 29 R0S10 I18.3 24 R1S02 R15 TRACK FEEDER D34 RATE OF RISE TRIP S009-12 - 2082 2083 SB - RESET OPERATED - - -
DI-234 I18.4 30 R0S10 I18.4 25 R1S02 R15 TRACK FEEDER D34 UNDERVOLTAGE TRIP S009-13 - - - SB - RESET OPERATED - - -
DI-236 I18.5 31 R0S10 I18.5 26 R1S02 R15 TRACK FEEDER D34 LINE TESTING S009-14 - 2084 2085 SB - COMPLETED IN PROGRESS - - -
DI-238 I18.6 32 R0S10 I18.6 27 R1S02 R15 TRACK FEEDER D34 LINE IMPEDANCE LOW S009-15 - 2086 2087 SB - NORMAL OPERATED - - -
DI-240 I18.7 33 R0S10 I18.7 28 R1S02 R15 TRACK FEEDER D34 TRIP CCT SUPERVISION ALARM S009-16 - 2088 2089 SB - NORMAL OPERATED - - -

UM2 UM2 34 R0S10 - 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW2 UW2 35 R0S10 - 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 31 R1S02 R15 TRACK FEEDER D34 TRANSFER TRIP S009-17 - - - SB - RESET OPERATED - - -
DI-244 I19.1 38 R0S10 I19.1 32 R1S02 R15 TRACK FEEDER D34 LINE TEST CONTROL SELECTOR SWITCH S009-18 - 2107 2108 SB - OFF ON - - -

DI-246 I19.2 39 R0S10 I19.2 33 R1S02 R15 TRACK FEEDER D35 CONTROL SELECTOR SWITCH S009-23 - 2093 2094 SB - LOCAL REMOTE - - -

DI-248 I19.3 40 R0S10 I19.3 34 R1S02 R15 TRACK FEEDER D35 INSTANT OVERCURRENT S009-24 - 2095 2096 SB - RESET OVERCURRENT/ - - -
OPERATED

DI-250 I19.4 41 R0S10 I19.4 35 R1S02 R15 TRACK FEEDER D35 TIME DELAY OVERCURRENT ALARM S009-25 - - - SB - NORMAL OPERATED - - -

DI-252 I19.5 42 R0S10 I19.5 36 R1S02 R15 TRACK FEEDER D35 RATE OF RISE TRIP S009-26 - 2097 2098 SB - RESET OPERATED - - -
DI-254 I19.6 43 R0S10 I19.6 37 R1S02 R15 TRACK FEEDER D35 UNDERVOLTAGE TRIP S009-27 - - - SB - RESET OPERATED - - -
DI-256 I19.7 44 R0S10 I19.7 38 R1S02 R15 TRACK FEEDER D35 LINE TESTING S009-28 - 2099 2100 SB - COMPLETED IN PROGRESS - - -
UM3 UM3 45 R0S10 2L+ 39 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S10 2M 40 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S11 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 1 R1S03 R15 TRACK FEEDER D35 LINE IMPEDANCE LOW S009-31 - 2101 2102 SB - NORMAL OPERATED - - -
DI-260 I20.1 5 R0S11 I20.1 2 R1S03 R15 TRACK FEEDER D35 TRIP CCT SUPERVISION ALARM S009-32 - 2103 2104 SB - NORMAL OPERATED - - -

DI-262 I20.2 6 R0S11 I20.2 3 R1S03 R15 TRACK FEEDER D35 TRANSFER TRIP S009-33 - 3079 3080 SB - RESET OPERATED - - -
DI-264 I20.3 7 R0S11 I20.3 4 R1S03 R15 TRACK FEEDER D35 LINE TEST CONTROL SELECTOR SWITCH S009-34 - 2109 2110 SB - OFF ON - - -

DI-266 I20.4 8 R0S11 I20.4 5 R1S03 R15 TRACK FEEDER D36 CONTROL SELECTOR SWITCH S009-37 - 3004 3005 SB - LOCAL REMOTE - - -

DI-268 I20.5 9 R0S11 I20.5 6 R1S03 R15 TRACK FEEDER D36 INSTANT OVERCURRENT S009-38 - 3006 3007 SB - RESET OVERCURRENT/ - - -
OPERATED

DI-270 I20.6 10 R0S11 I20.6 7 R1S03 R15 TRACK FEEDER D36 TIME DELAY OVERCURRENT ALARM S010-1 - - - SB - NORMAL OPERATED - - -

DI-272 I20.7 11 R0S11 I20.7 8 R1S03 R15 TRACK FEEDER D36 RATE OF RISE TRIP S010-2 - 3008 3009 SB - RESET OPERATED - - -
UM0 UM0 12 R0S11 - 19 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S11 - 20 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 11 R1S03 R15 TRACK FEEDER D36 UNDERVOLTAGE TRIP S010-3 - - - SB - RESET OPERATED - - -
DI-276 I21.1 16 R0S11 I21.1 12 R1S03 R15 TRACK FEEDER D36 LINE TESTING S010-4 - 3010 3011 SB - COMPLETED IN PROGRESS - - -
DI-278 I21.2 17 R0S11 I21.2 13 R1S03 R15 TRACK FEEDER D36 LINE IMPEDANCE LOW S010-5 - 3012 3013 SB - NORMAL OPERATED - - -
DI-280 I21.3 18 R0S11 I21.3 14 R1S03 R15 TRACK FEEDER D36 TRIP CCT SUPERVISION ALARM S010-6 - 3014 3015 SB - NORMAL OPERATED - - -

DI-282 I21.4 19 R0S11 I21.4 15 R1S03 R15 TRACK FEEDER D36 TRANSFER TRIP S010-7 - - - SB - RESET OPERATED - - -
DI-284 I21.5 20 R0S11 I21.5 16 R1S03 R15 TRACK FEEDER D36 LINE TEST CONTROL SELECTOR SWITCH S010-8 - 3087 3088 SB - OFF ON - - -

DI-286 I21.6 21 R0S11 I21.6 17 R1S03 R15 TRACK FEEDER D37 CONTROL SELECTOR SWITCH S010-13 - 3019 3020 SB - LOCAL REMOTE - - -

DI-288 I21.7 22 R0S11 I21.7 18 R1S03 R15 TRACK FEEDER D37 INSTANT OVERCURRENT S010-14 - 3021 3022 SB - RESET OVERCURRENT/ - - -
OPERATED

UM1 UM1 23 R0S11 1L+ 19 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 158 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UW1 UW1 24 R0S11 1M 20 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -


DI-290 I22.0 26 R0S11 I22.0 21 R1S03 R15 TRACK FEEDER D37 TIME DELAY OVERCURRENT ALARM S010-15 - - - SB - NORMAL OPERATED - - -

DI-292 I22.1 27 R0S11 I22.1 22 R1S03 R15 TRACK FEEDER D37 RATE OF RISE TRIP S010-16 - 3023 3024 SB - RESET OPERATED - - -
DI-294 I22.2 28 R0S11 I22.2 23 R1S03 R15 TRACK FEEDER D37 UNDERVOLTAGE TRIP S010-17 - - - SB - RESET OPERATED - - -
DI-296 I22.3 29 R0S11 I22.3 24 R1S03 R15 TRACK FEEDER D37 LINE TESTING S010-18 - 3025 3026 SB - COMPLETED IN PROGRESS - - -
DI-298 I22.4 30 R0S11 I22.4 25 R1S03 R15 TRACK FEEDER D37 LINE IMPEDANCE LOW S010-21 - 3027 3028 SB - NORMAL OPERATED - - -
DI-300 I22.5 31 R0S11 I22.5 26 R1S03 R15 TRACK FEEDER D37 TRIP CCT SUPERVISION ALARM S010-22 - 3029 3030 SB - NORMAL OPERATED - - -

DI-302 I22.6 32 R0S11 I22.6 27 R1S03 R15 TRACK FEEDER D37 TRANSFER TRIP S010-23 - 3081 3082 SB - RESET OPERATED - - -
DI-304 I22.7 33 R0S11 I22.7 28 R1S03 R15 TRACK FEEDER D37 LINE TEST CONTROL SELECTOR SWITCH S010-24 - 3089 3090 SB - OFF ON - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 159 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UM2 UM2 34 R0S11 - 39 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW2 UW2 35 R0S11 - 40 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 31 R1S03 R15 TRACK FEEDER D38 CONTROL SELECTOR SWITCH S010-27 - 3034 3035 SB - LOCAL REMOTE - - -

DI-308 I23.1 38 R0S11 I23.1 32 R1S03 R15 TRACK FEEDER D38 INSTANT OVERCURRENT S010-28 - 3036 3037 SB - RESET OVERCURRENT/ - - -
OPERATED

DI-310 I23.2 39 R0S11 I23.2 33 R1S03 R15 TRACK FEEDER D38 TIME DELAY OVERCURRENT ALARM S010-31 - - - SB - NORMAL OPERATED - - -

DI-312 I23.3 40 R0S11 I23.3 34 R1S03 R15 TRACK FEEDER D38 RATE OF RISE TRIP S010-32 - 3038 3039 SB - RESET OPERATED - - -
DI-314 I23.4 41 R0S11 I23.4 35 R1S03 R15 TRACK FEEDER D38 UNDERVOLTAGE TRIP S010-33 - - - SB - RESET OPERATED - - -
DI-316 I23.5 42 R0S11 I23.5 36 R1S03 R15 TRACK FEEDER D38 LINE TESTING S010-34 - 3040 3041 SB - COMPLETED IN PROGRESS - - -
DI-318 I23.6 43 R0S11 I23.6 37 R1S03 R15 TRACK FEEDER D38 LINE IMPEDANCE LOW S010-35 - 3042 3043 SB - NORMAL OPERATED - - -
DI-320 I23.7 44 R0S11 I23.7 38 R1S03 R15 TRACK FEEDER D38 TRIP CCT SUPERVISION ALARM S010-36 - 3044 3045 SB - NORMAL OPERATED - - -

UM3 UM3 45 R0S11 2L+ 39 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW3 UW3 46 R0S11 2M 40 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S12 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-322 I24.0 4 R0S12 I24.0 1 R1S04 R15 TRACK FEEDER D38 TRANSFER TRIP S010-37 - - - SB - RESET OPERATED - - -
DI-324 I24.1 5 R0S12 I24.1 2 R1S04 R15 TRACK FEEDER D38 LINE TEST CONTROL SELECTOR SWITCH S010-38 - 3091 3092 SB - OFF ON - - -

DI-326 I24.2 6 R0S12 I24.2 3 R1S04 R15 DC COMMON EQUIPMENT (OVPD) CONTACTOR CONTROL SELECTOR S011-3 - 3051 3052 SB - LOCAL REMOTE - - -
SWITCH
DI-328 I24.3 7 R0S12 I24.3 4 R1S04 R15 DC COMMON EQUIPMENT (OVPD) OVERVOLTAGE ALARM S011-4 - 3053 3054 SB - NORMAL OPERATED - - -

DI-330 I24.4 8 R0S12 I24.4 5 R1S04 R15 AC/DC SYSTEM MAINS FAILED ALARM S011-5 - 3055 3056 SB - NORMAL OPERATED - - -
DI-332 I24.5 9 R0S12 I24.5 6 R1S04 R15 AC/DC SYSTEM 110V HIGH VOLTAGE ALARM S011-6 - 3063 3064 SB - NORMAL OPERATED - - -
DI-334 I24.6 10 R0S12 I24.6 7 R1S04 R15 AC/DC SYSTEM AC EARTH FAULT TRIP S011-7 - - - SB - RESET OPERATED - - -
DI-336 I24.7 11 R0S12 I24.7 8 R1S04 R15 AC/DC SYSTEM CHARGER FAILURE S011-8 - 3061 3062 SB - NORMAL OPERATED - - -
UM0 UM0 12 R0S12 - 19 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S12 - 20 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-338 I25.0 15 R0S12 I25.0 11 R1S04 R15 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S011-11 - 3057 3058 SB - NORMAL OPERATED - - -

DI-340 I25.1 16 R0S12 I25.1 12 R1S04 R15 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S011-12 - 3065 3066 SB - NORMAL OPERATED - - -
DI-342 I25.2 17 R0S12 I25.2 13 R1S04 R15 AC/DC SYSTEM 11KV CONTROL VOLTAGE S011-13 - 3067 3068 SB - NORMAL FAULT/ - - -
OPERATED
DI-344 I25.3 18 R0S12 I25.3 14 R1S04 R15 AC/DC SYSTEM 750V CONTROL VOLTAGE S011-14 - 3069 3070 SB - NORMAL FAULT/ - - -
OPERATED
DI-346 I25.4 19 R0S12 I25.4 15 R1S04 R15 AC/DC SYSTEM 110V DC COMMON FEEDER S011-15 - 3071 3072 SB - NORMAL FAULT/ - - -
OPERATED
DI-348 I25.5 20 R0S12 I25.5 16 R1S04 R15 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S011-16 - 3073 3074 SB - NORMAL OPERATED - - -

DI-350 I25.6 21 R0S12 I25.6 17 R1S04 R15 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT ALARM S011-17 - 5001 5002 SB - NORMAL OPERATED - - -

DI-352 I25.7 22 R0S12 I25.7 18 R1S04 R15 COMMON EQUIPMENT FIRE PROTECTION ALARM S011-18 - 5003 5004 SB - RESET OPERATED - - -

UM1 UM1 23 R0S12 1L+ 19 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW1 UW1 24 R0S12 1M 20 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-354 I26.0 26 R0S12 I26.0 21 R1S04 R15 COMMON EQUIPMENT INTRUDER ALARM S011-21 - 5005 5006 SB - NORMAL OPERATED - - -
DI-356 I26.1 27 R0S12 I26.1 22 R1S04 R15 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM S011-22 - 5007 5008 SB - NORMAL OPERATED - - -

DI-358 I26.2 28 R0S12 I26.2 23 R1S04 R15 MVAC SYSTEM FAULT ALARM S011-23 - 5009 5010 SB - NORMAL OPERATED - - -
DI-360 I26.3 29 R0S12 I26.3 24 R1S04 R15 ROOMS OVERTEMPERATURE ALARM S011-24 - 5011 5012 SB - NORMAL OPERATED - - -
DI-362 I26.4 30 R0S12 I26.4 25 R1S04 R15 VOLTAGE STABILIZER FAULT ALARM S011-25 - 5013 5014 SB - NORMAL OPERATED - - -
DI-364 I26.5 31 R0S12 I26.5 26 R1S04 - SPARE S011-26 - - - - - - - - -
DI-366 I26.6 32 R0S12 I26.6 27 R1S04 R15 MVAC MOTORISED DAMPER NO.1 POSITION S011-27 - 5015 5016 SB - OPEN CLOSED - - -
DI-368 I26.7 33 R0S12 I26.7 28 R1S04 - SPARE S011-28 - - - - - - - - -
UM2 UM2 34 R0S12 - 39 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 UW2 35 R0S12 - 40 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-370 I27.0 37 R0S12 I27.0 31 R1S04 R15 MVAC MOTORISED DAMPER NO.2 POSITION S011-31 - 5017 5018 SB - OPEN CLOSED - - -
DI-372 I27.1 38 R0S12 I27.1 32 R1S04 - SPARE S011-32 - - - - - - - - -
DI-374 I27.2 39 R0S12 I27.2 33 R1S04 R15 MVAC MOTORISED DAMPER NO.3 POSITION S011-33 - 5019 5020 SB - OPEN CLOSED - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 160 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-376 I27.3 40 R0S12 I27.3 34 R1S04 - SPARE S011-34 - - - - - - - - -


DI-378 I27.4 41 R0S12 I27.4 35 R1S04 R15 MVAC VENTILATION FAN NO.1 FLOW SWITCH S011-35 - 5021 5022 SB - OPEN CLOSED - - -
DI-380 I27.5 42 R0S12 I27.5 36 R1S04 R15 MVAC VENTILATION FAN NO.1 FAULT ALARM S011-36 - 5023 5024 SB - NORMAL OPERATED - - -
DI-382 I27.6 43 R0S12 I27.6 37 R1S04 R15 MVAC VENTILATION FAN NO.1 EMERGENCY STOP S011-37 - 5025 5026 SB - RESET OPERATED - - -

DI-384 I27.7 44 R0S12 I27.7 38 R1S04 R15 MVAC VENTILATION FAN NO.1 CONTROL SELECTOR SWITCH S011-38 - 5027 5028 SB - LOCAL AUTO - - -

UM3 UM3 45 R0S12 2L+ 39 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW3 UW3 46 R0S12 2M 40 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S13 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-386 I28.0 4 R0S13 I28.0 1 R0S05 R15 MVAC VENTILATION FAN NO.2 FLOW SWITCH S012-1 - 5029 5030 SB - OPEN CLOSED - - -
DI-388 I28.1 5 R0S13 I28.1 2 R0S05 R15 MVAC VENTILATION FAN NO.2 FAULT ALARM S012-2 - 5031 5032 SB - NORMAL OPERATED - - -
DI-390 I28.2 6 R0S13 I28.2 3 R0S05 R15 MVAC VENTILATION FAN NO.2 EMERGENCY STOP S012-3 - 5033 5034 SB - RESET OPERATED - - -

DI-392 I28.3 7 R0S13 I28.3 4 R0S05 R15 MVAC VENTILATION FAN NO.2 CONTROL SELECTOR SWITCH S012-4 - 5035 5036 SB - LOCAL AUTO - - -

DI-394 I28.4 8 R0S13 I28.4 5 R0S05 R15 MVAC VENTILATION FAN NO.3 FLOW SWITCH S012-5 - 5037 5038 SB - OPEN CLOSED - - -
DI-396 I28.5 9 R0S13 I28.5 6 R0S05 R15 MVAC VENTILATION FAN NO.3 FAULT ALARM S012-6 - 5039 5040 SB - NORMAL OPERATED - - -
DI-398 I28.6 10 R0S13 I28.6 7 R0S05 R15 MVAC VENTILATION FAN NO.3 EMERGENCY STOP S012-7 - 5041 5042 SB - RESET OPERATED - - -

DI-400 I28.7 11 R0S13 I28.7 8 R0S05 R15 MVAC VENTILATION FAN NO.3 CONTROL SELECTOR SWITCH S012-8 - 5043 5044 SB - LOCAL AUTO - - -

UM0 UM0 12 R0S13 - 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW0 UW0 13 R0S13 - 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-402 I29.0 15 R0S13 I29.0 11 R0S05 R15 MVAC VENTILATION FAN NO.4 FLOW SWITCH S012-11 - 5045 5046 SB - OPEN CLOSED - - -
DI-404 I29.1 16 R0S13 I29.1 12 R0S05 R15 MVAC VENTILATION FAN NO.4 FAULT ALARM S012-12 - 5047 5048 SB - NORMAL OPERATED - - -
DI-406 I29.2 17 R0S13 I29.2 13 R0S05 R15 MVAC VENTILATION FAN NO.4 EMERGENCY STOP S012-13 - 5049 5050 SB - RESET OPERATED - - -

DI-408 I29.3 18 R0S13 I29.3 14 R0S05 R15 MVAC VENTILATION FAN NO.4 CONTROL SELECTOR SWITCH S012-14 - 5051 5052 SB - LOCAL AUTO - - -

DI-410 I29.4 19 R0S13 I29.4 15 R0S05 R15 MVAC VENTILATION FAN NO.5 FLOW SWITCH S012-15 - 5053 5054 SB - OPEN CLOSED - - -
DI-412 I29.5 20 R0S13 I29.5 16 R0S05 R15 MVAC VENTILATION FAN NO.5 FAULT ALARM S012-16 - 5055 5056 SB - NORMAL OPERATED - - -
DI-414 I29.6 21 R0S13 I29.6 17 R0S05 R15 MVAC VENTILATION FAN NO.5 EMERGENCY STOP S012-17 - 5057 5058 SB - RESET OPERATED - - -

DI-416 I29.7 22 R0S13 I29.7 18 R0S05 R15 MVAC VENTILATION FAN NO.5 CONTROL SELECTOR SWITCH S012-18 - 5059 5060 SB - LOCAL AUTO - - -

UM1 UM1 23 R0S13 1L+ 19 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW1 UW1 24 R0S13 1M 20 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-418 I30.0 26 R0S13 I30.0 21 R0S05 R15 380V NETWORK PROTECTION RELAYS COMMON ALARM S012-21 - 5015 5016 SB - RESET OPERATED - - -

DI-420 I30.1 27 R0S13 I30.1 22 R0S05 - SPARE S012-22 - 5063 - - - - - - -


DI-422 I30.2 28 R0S13 I30.2 23 R0S05 - SPARE S012-23 - 5065 - - - - - - -
DI-424 I30.3 29 R0S13 I30.3 24 R0S05 - SPARE S006-14 - - - - - - - - -
DI-426 I30.4 30 R0S13 I30.4 25 R0S05 - SPARE S007-4 - - - - - - - - -
DI-428 I30.5 31 R0S13 I30.5 26 R0S05 - SPARE S012-26 - - - - - - - - -
DI-430 I30.6 32 R0S13 I30.6 27 R0S05 - SPARE S012-27 - - - - - - - - -
DI-432 I30.7 33 R0S13 I30.7 28 R0S05 - SPARE S012-28 - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 161 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UM2 UM2 34 R0S13 - 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW2 UW2 35 R0S13 - 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-434 I31.0 37 R0S13 I31.0 31 R0S05 R15 RING MAIN H03 (R15VB40)(TO R16) VCB OPENED S005-1 - 1001 1002 DB - DISCONNECT OPEN - - -

DI-436 I31.1 38 R0S13 I31.1 32 R0S05 R15 RING MAIN H03 (R15VB40)(TO R16) VCB CLOSED S005-2 - 1001 1003 DB - - - CLOSED ERROR -

DI-438 I31.2 39 R0S13 I31.2 33 R0S05 R15 RING MAIN H04 (R15VB41)(TO R10) VCB OPENED S005-11 - 1016 1017 DB - DISCONNECT OPEN - - -

DI-440 I31.3 40 R0S13 I31.3 34 R0S05 R15 RING MAIN H04 (R15VB41)(TO R10) VCB CLOSED S005-12 - 1016 1018 DB - - - CLOSED ERROR -

DI-442 I31.4 41 R0S13 I31.4 35 R0S05 R15 RING MAIN H05 (R15VB42)(TO R14) VCB OPENED S005-21 - 1031 1032 DB - DISCONNECT OPEN - - -

DI-444 I31.5 42 R0S13 I31.5 36 R0S05 R15 RING MAIN H05 (R15VB42)(TO R14) VCB CLOSED S005-22 - 1031 1033 DB - - - CLOSED ERROR -

DI-446 I31.6 43 R0S13 I31.6 37 R0S05 R15 RECTIFIER FEEDER H01 (R15VB50) VCB OPENED S005-31 - 1047 1048 DB - DISCONNECT OPEN - - -

DI-448 I31.7 44 R0S13 I31.7 38 R0S05 R15 RECTIFIER FEEDER H01 (R15VB50) VCB CLOSED S005-32 - 1047 1049 DB - - - CLOSED ERROR -

UM3 UM3 45 R0S13 UM3 39 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW3 UW3 46 R0S13 UW3 40 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S14 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-450 I32.0 4 R0S14 I32.0 1 R0S06 R15 RECTIFIER FEEDER H02 (R15VB51) VCB OPENED S006-21 - 2001 2002 DB - DISCONNECT OPEN - - -

DI-452 I32.1 5 R0S14 I32.1 2 R0S06 R15 RECTIFIER FEEDER H02 (R15VB51) VCB CLOSED S006-22 - 2001 2003 DB - - - CLOSED ERROR -

DI-454 I32.2 6 R0S14 I32.2 3 R0S06 R15 AUXILIARY TRANSFORMER H06 VCB OPENED S008-1 - 1086 1087 DB - DISCONNECT OPEN - - -
(R15VB60)
DI-456 I32.3 7 R0S14 I32.3 4 R0S06 R15 AUXILIARY TRANSFORMER H06 VCB CLOSED S008-2 - 1086 1088 DB - - - CLOSED ERROR -
(R15VB60)
DI-458 I32.4 8 R0S14 I32.4 5 R0S06 R15 RECTIFIER FEEDER D1 DCCB OPENED S008-15 - 2040 2041 DB - DISCONNECT OPEN - - -
DI-460 I32.5 9 R0S14 I32.5 6 R0S06 R15 RECTIFIER FEEDER D1 DCCB CLOSED S008-16 - 2040 2042 DB - - - CLOSED ERROR -
DI-462 I32.6 10 R0S14 I32.6 7 R0S06 R15 RECTIFIER FEEDER D2 DCCB OPENED S008-21 - 2049 2050 DB - DISCONNECT OPEN - - -
DI-464 I32.7 11 R0S14 I32.7 8 R0S06 R15 RECTIFIER FEEDER D2 DCCB CLOSED S008-22 - 2049 2051 DB - - - CLOSED ERROR -
UM0 UM0 12 R0S14 - 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S14 - 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-466 I33.0 15 R0S14 I33.0 11 R0S06 R15 RECTIFIER FEEDER D3 DCCB OPENED S008-25 - - - DB - DISCONNECT OPEN - - -
DI-468 I33.1 16 R0S14 I33.1 12 R0S06 R15 RECTIFIER FEEDER D3 DCCB CLOSED S008-26 - - - DB - - - CLOSED ERROR -
DI-470 I33.2 17 R0S14 I33.2 13 R0S06 R15 TRACK FEEDER D33 DCCB OPENED S008-31 - 2060 2061 DB - DISCONNECT OPEN - - -
DI-472 I33.3 18 R0S14 I33.3 14 R0S06 R15 TRACK FEEDER D33 DCCB CLOSED S008-32 - 2060 2062 DB - - - CLOSED ERROR -
DI-474 I33.4 19 R0S14 I33.4 15 R0S06 R15 TRACK FEEDER D34 DCCB OPENED S009-5 - 2075 2076 DB - DISCONNECT OPEN - - -
DI-476 I33.5 20 R0S14 I33.5 16 R0S06 R15 TRACK FEEDER D34 DCCB CLOSED S009-6 - 2075 2077 DB - - - CLOSED ERROR -
DI-478 I33.6 21 R0S14 I33.6 17 R0S06 R15 TRACK FEEDER D35 DCCB OPENED S009-21 - 2090 2091 DB - DISCONNECT OPEN - - -
DI-480 I33.7 22 R0S14 I33.7 18 R0S06 R15 TRACK FEEDER D35 DCCB CLOSED S009-22 - 2090 2092 DB - - - CLOSED ERROR -
UM1 UM1 23 R0S14 1L+ 19 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S14 1M 20 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-482 I34.0 26 R0S14 I34.0 21 R0S06 R15 TRACK FEEDER D36 DCCB OPENED S009-35 - 3001 3002 DB - DISCONNECT OPEN - - -
DI-484 I34.1 27 R0S14 I34.1 22 R0S06 R15 TRACK FEEDER D36 DCCB CLOSED S009-36 - 3001 3003 DB - - - CLOSED ERROR -
DI-486 I34.2 28 R0S14 I34.2 23 R0S06 R15 TRACK FEEDER D37 DCCB OPENED S010-11 - 3016 3017 DB - DISCONNECT OPEN - - -
DI-488 I34.3 29 R0S14 I34.3 24 R0S06 R15 TRACK FEEDER D37 DCCB CLOSED S010-12 - 3016 3018 DB - - - CLOSED ERROR -
DI-490 I34.4 30 R0S14 I34.4 25 R0S06 R15 TRACK FEEDER D38 DCCB OPENED S010-25 - 3031 3032 DB - DISCONNECT OPEN - - -
DI-492 I34.5 31 R0S14 I34.5 26 R0S06 R15 TRACK FEEDER D38 DCCB CLOSED S010-26 - 3031 3033 DB - - - CLOSED ERROR -
DI-494 I34.6 32 R0S14 I34.6 27 R0S06 R15 DC COMMON EQUIPMENT (OVPD) CONTACTOR OPENED S011-1 - 3049 3050 DB - DISCONNECT OPEN - - -

DI-496 I34.7 33 R0S14 I34.7 28 R0S06 R15 DC COMMON EQUIPMENT (OVPD) CONTACTOR CLOSED S011-2 - 3047 3048 DB - - - CLOSED ERROR -

UM2 UM2 34 R0S14 - 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW2 UW2 35 R0S14 - 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-498 I35.0 37 R0S14 I35.0 31 R0S06 R15 DUMMY CB VCB OPENED internal - - - DB - DISCONNECT OPEN - - -
wiring
DI-500 I35.1 38 R0S14 I35.1 32 R0S06 R15 DUMMY CB VCB CLOSED internal - - - DB - - - CLOSED ERROR -
wiring

Unrestricted 749775924.xlsx/RS15 [RS15] 162 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-502 I35.2 39 R0S14 I35.2 33 R0S06 - SPARE S012-33 - - - - - - - - -


DI-504 I35.3 40 R0S14 I35.3 34 R0S06 - SPARE S012-34 - - - - - - - - -
DI-506 I35.4 41 R0S14 I35.4 35 R0S06 - SPARE S012-35 - - - - - - - - -
DI-508 I35.5 42 R0S14 I35.5 36 R0S06 - SPARE S012-36 - - - - - - - - -
DI-510 I35.6 43 R0S14 I35.6 37 R0S06 - SPARE S012-37 - - - - - - - - -
DI-512 I35.7 44 R0S14 I35.7 38 R0S06 - SPARE S012-38 - - - - - - - - -
UM3 UM3 45 R0S14 2L+ 39 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S14 2M 40 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
- - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
I36.0 1 R1S05 - SPARE - - - - - - - - - -
I36.1 2 R1S05 - SPARE - - - - - - - - - -
I36.2 3 R1S05 - SPARE - - - - - - - - - -
I36.3 4 R1S05 - SPARE - - - - - - - - - -
I36.4 5 R1S05 - SPARE - - - - - - - - - -
I36.5 6 R1S05 - SPARE - - - - - - - - - -
I36.6 7 R1S05 - SPARE - - - - - - - - - -
I36.7 8 R1S05 - SPARE - - - - - - - - - -
- 19 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
- 20 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
I37.0 11 R1S05 - SPARE - - - - - - - - - -
I37.1 12 R1S05 - SPARE - - - - - - - - - -
I37.2 13 R1S05 - SPARE - - - - - - - - - -
I37.3 14 R1S05 - SPARE - - - - - - - - - -
I37.4 15 R1S05 - SPARE - - - - - - - - - -
I37.5 16 R1S05 - SPARE - - - - - - - - - -
I37.6 17 R1S05 - SPARE - - - - - - - - - -
I37.7 18 R1S05 - SPARE - - - - - - - - - -
1L+ 19 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
1M 20 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
I38.0 21 R1S05 - SPARE - - - - - - - - - -
I38.1 22 R1S05 - SPARE - - - - - - - - - -
I38.2 23 R1S05 - SPARE - - - - - - - - - -
I38.3 24 R1S05 - SPARE - - - - - - - - - -
I38.4 25 R1S05 - SPARE - - - - - - - - - -
I38.5 26 R1S05 - SPARE - - - - - - - - - -
I38.6 27 R1S05 - SPARE - - - - - - - - - -
I38.7 28 R1S05 - SPARE - - - - - - - - - -
- 39 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
- 40 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
I39.0 31 R1S05 - SPARE - - - - - - - - - -
I39.1 32 R1S05 - SPARE - - - - - - - - - -
I39.2 33 R1S05 - SPARE - - - - - - - - - -
I39.3 34 R1S05 - SPARE - - - - - - - - - -
I39.4 35 R1S05 - SPARE - - - - - - - - - -
I39.5 36 R1S05 - SPARE - - - - - - - - - -
I39.6 37 R1S05 - SPARE - - - - - - - - - -
I39.7 38 R1S05 - SPARE - - - - - - - - - -
2L+ 39 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
2M 40 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 163 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R1S03 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - -


ZS2 ZS2 2 R1S03 - - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R1S03 IW.256 1 R3S02 R15 RING MAIN H03 (R15VB40)(TO R16) CURRENT S014-1 - 6001 - AI - - - - - 4 to
TB2-1 (-) IW.256 5 R1S03 IW.256 21 R3S02 - - S014-2 - - 6002 - - - - - - to
TB2-2 (+) IW.258 6 R1S03 IW.258 2 R3S02 R15 RING MAIN H04 (R15VB41)(TO R10) CURRENT S014-3 - 6003 - AI - - - - - 4 to
TB2-2 (-) IW.258 7 R1S03 IW.258 22 R3S02 - - S014-4 - - 6004 - - - - - - to
TB2-3 (+) IW.260 8 R1S03 IW.260 3 R3S02 R15 RING MAIN H05 (R15VB42)(TO R14) CURRENT S014-5 - 6005 - AI - - - - - 4 to
TB2-3 (-) IW.260 9 R1S03 IW.260 23 R3S02 - - S014-6 - - 6006 - - - - - - to
TB2-4 (+) IW.262 10 R1S03 IW.262 4 R3S02 R15 RECTIFIER FEEDER H01 (R15VB50) CURRENT S014-7 - 6007 - AI - - - - - 4 to
TB2-4 (-) IW.262 11 R1S03 IW.262 24 R3S02 - - S014-8 - - 6008 - - - - - - to
TB2-5 (+) IW.264 15 R1S03 IW.264 5 R3S02 R15 RECTIFIER FEEDER H02 (R15VB51) CURRENT S014-9 - 6009 - AI - - - - - 4 to
TB2-5 (-) IW.264 16 R1S03 IW.264 25 R3S02 - - S014-10 - - 6010 - - - - - - to
TB2-6 (+) IW.266 17 R1S03 IW.266 6 R3S02 R15 AUXILIARY TRANSFORMER H06 CURRENT S014-11 - 6011 - AI - - - - - 4 to
TB2-6 (-) IW.266 18 R1S03 IW.266 26 R3S02 (R15VB60)
- - S014-12 - - 6012 - - - - - - to
TB2-7 (+) IW.268 19 R1S03 IW.268 7 R3S02 R15 AC BUSBAR VOLTAGE S014-13 - 6041 - AI - - - - - 4 to
TB2-7 (-) IW.268 20 R1S03 IW.268 27 R3S02 - - S014-14 - - 6042 - - - - - - to
TB2-8 (+) IW.270 21 R1S03 IW.270 8 R3S02 R15 TRACK FEEDER D33 DC CURRENT S014-15 - 6017 - AI - - - - - -20 to
TB2-8 (-) IW.270 22 R1S03 IW.270 28 R3S02 - - S014-16 - - 6018 - - - - - - to
TB2-9 (+) IW.272 26 R1S03 IW.272 9 R3S02 R15 TRACK FEEDER D34 DC CURRENT S014-17 - 6019 - AI - - - - - -20 to
TB2-9 (-) IW.272 27 R1S03 IW.272 29 R3S02 - - S014-18 - - 6020 - - - - - - to
TB2-10 (+) IW.274 28 R1S03 IW.274 10 R3S02 R15 TRACK FEEDER D35 DC CURRENT S014-19 - 6021 - AI - - - - - -20 to
TB2-10 (-) IW.274 29 R1S03 IW.274 30 R3S02 - - S014-20 - - 6022 - - - - - - to
TB2-11 (+) IW.276 30 R1S03 IW.276 11 R3S02 R15 TRACK FEEDER D36 DC CURRENT S014-21 - 6023 - AI - - - - - -20 to
TB2-11 (-) IW.276 31 R1S03 IW.276 31 R3S02 - - S014-22 - - 6024 - - - - - - to
TB2-12 (+) IW.278 32 R1S03 IW.278 12 R3S02 R15 TRACK FEEDER D37 DC CURRENT S014-23 - 6025 - AI - - - - - -20 to
TB2-12 (-) IW.278 33 R1S03 IW.278 32 R3S02 - - S014-24 - - 6026 - - - - - - to
TB2-13 (+) IW.280 37 R1S03 IW.280 13 R3S02 R15 TRACK FEEDER D38 DC CURRENT S014-25 - 6027 - AI - - - - - -20 to
TB2-13 (-) IW.280 38 R1S03 IW.280 33 R3S02 - - S014-26 - - 6028 - - - - - - to
TB2-14 (+) IW.282 39 R1S03 IW.282 14 R3S02 R15 RECTIFIER 1 DC CURRENT S014-27 - 6029 - AI - - - - - 4 to
TB2-14 (-) IW.282 40 R1S03 IW.282 34 R3S02 - - S014-28 - - 6030 - - - - - - to
TB2-15 (+) IW.284 41 R1S03 IW.284 15 R3S02 R15 RECTIFIER 1 DC VOLTAGE S014-29 - 6031 - AI - - - - - 4 to
TB2-15 (-) IW.284 42 R1S03 IW.284 35 R3S02 - - S014-30 - - 6032 - - - - - - to
TB2-16 (+) IW.286 43 R1S03 IW.286 16 R3S02 R15 RECTIFIER 2 DC CURRENT S014-31 - 6033 - AI - - - - - 4 to
TB2-16 (-) IW.286 44 R1S03 IW.286 36 R3S02 - - S014-32 - - 6034 - - - - - - to
ZS1 ZS1 1 R1S04 ZS1 R3S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R1S04 ZS2 R3S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
TB2-17 (+) IW.288 4 R1S04 IW.288 1 R3S03 R15 RECTIFIER 2 DC VOLTAGE S014-33 - 6035 - AI - - - - - 4 to
TB2-17 (+) IW.288 5 R1S04 IW.288 21 R3S03 - - S014-34 - - 6036 - - - - - - to
TB2-18 (+) IW.290 6 R1S04 IW.290 2 R3S03 R15 DC BUSBAR DC VOLTAGE S014-35 - 6037 - AI - - - - - 4 to
TB2-18 (-) IW.290 7 R1S04 IW.290 22 R3S03 - - S014-36 - - 6038 - - - - - - to
TB2-19 (+) IW.292 8 R1S04 IW.292 3 R3S03 R15 NEGATIVE BUSBAR DC RETURN CURRENT S014-37 - 6043 - AI - - - - - 4 to
TB2-19 (-) IW.292 9 R1S04 IW.292 23 R3S03 - - S014-38 - - 6044 - - - - - - to
TB2-20 (+) IW.294 10 R1S04 IW.294 4 R3S03 R15 MVAC SYSTEM INDOOR TEMP 1 S014-39 - 6075 - AI - - - - - 0 to
TB2-20 (-) IW.294 11 R1S04 IW.294 24 R3S03 - - S014-40 - - 6076 - - - - - - to
TB2-21 (+) IW.296 15 R1S04 IW.296 5 R3S03 R15 MVAC SYSTEM INDOOR TEMP 2 S014-41 - 6077 - AI - - - - - 0 to
TB2-21 (-) IW.296 16 R1S04 IW.296 25 R3S03 - - S014-42 - - 6078 - - - - - - to
TB2-22 (+) IW.298 17 R1S04 IW.298 6 R3S03 R15 MVAC SYSTEM INDOOR TEMP 3 S014-43 - 6079 - AI - - - - - 0 to
TB2-22 (-) IW.298 18 R1S04 IW.298 26 R3S03 - - S014-44 - - 6080 - - - - - - to
TB2-23 (+) IW.300 19 R1S04 IW.300 7 R3S03 R15 MVAC SYSTEM INDOOR TEMP 4 S014-45 - 6081 - AI - - - - - 0 to
TB2-23 (-) IW.300 20 R1S04 IW.300 27 R3S03 - - S014-46 - - 6082 - - - - - - to
TB2-24 (+) IW.302 21 R1S04 IW.302 8 R3S03 R15 MVAC SYSTEM INDOOR TEMP 5 S014-47 - 6083 - AI - - - - - 0 to
TB2-24 (-) IW.302 22 R1S04 IW.302 28 R3S03 - - S014-48 - - 6084 - - - - - - to
TB2-25 (+) IW.304 26 R1S04 IW.304 9 R3S03 R15 380V NETWORK LB01 MAIN ACB (1200A) CURRENT S014-49 - 6085 - AI - - - - - 4 to
TB2-25 (-) IW.304 27 R1S04 IW.304 29 R3S03 - - S014-50 - - 6086 - - - - - - to
TB2-26 (+) IW.306 28 R1S04 IW.306 10 R3S03 R15 380V NETWORK LB01 MAIN ACB (1200A) VOLTAGE S014-51 - 6087 - AI - - - - - 4 to
TB2-26 (-) IW.306 29 R1S04 IW.306 30 R3S03 - - S014-52 - - 6088 - - - - - - to
TB2-27 (+) IW.308 30 R1S04 IW.308 11 R3S03 R15 380V NETWORK LB21 - TO S501 500A MCCB NO.1 CURRENT S014-53 - 6089 - AI - - - - - 4 to
TB2-27 (-) IW.308 31 R1S04 IW.308 31 R3S03 - - S014-54 - - 6090 - - - - - - to
TB2-28 (+) IW.310 32 R1S04 IW.310 12 R3S03 R15 380V NETWORK LB21 - TO S500 500A MCCB NO.2 CURRENT S014-55 - 6091 - AI - - - - - 4 to
TB2-28 (-) IW.310 33 R1S04 IW.310 32 R3S03 - - S014-56 - - 6092 - - - - - - to
TB2-29 (+) IW.312 37 R1S04 IW.312 13 R3S03 R15 380V NETWORK LB12 STANDBY SOURCE (300A) CURRENT S014-57 - 6093 - AI - - - - - 4 to
TB2-29 (-) IW.312 38 R1S04 IW.312 33 R3S03 - - S014-58 - - 6094 - - - - - - to
TB2-30 (+) IW.314 39 R1S04 IW.314 14 R3S03 R15 380V NETWORK LB12 STANDBY SOURCE VOLTAGE S014-59 - 6095 - AI - - - - - 4 to

Unrestricted 749775924.xlsx/RS15 [RS15] 164 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

TB2-30 (-) IW.314 40 R1S04 IW.314 34 R3S03 - - S014-60 - - 6096 - - - - - - to


TB2-31 (+) IW.316 41 R1S04 IW.316 15 R3S03 - SPARE S014-61 - - - - - - - - - to
TB2-31 (-) IW.316 42 R1S04 IW.316 35 R3S03 - - S014-62 - - - - - - - - - to
TB2-32 (+) IW.318 43 R1S04 IW.318 16 R3S03 - SPARE S014-63 - - - - - - - - - to
TB2-32 (-) IW.318 44 R1S04 IW.318 36 R3S03 - - S014-64 - - - - - - - - - to
S110-RD - - R1S04 - R3S03 - - - - - - - - - - - - -
S110-BK - - R1S04 - R3S03 - - - - - - - - - - - - -
S112-BL - - R1S04 - R3S03 - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 165 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - R1S04 - R3S03 - - - - - - - - - - - - -


ZS1 ZS1 R3S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 R3S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
TB2-1 (+) IW.320 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-1 (-) IW.320 R3S04 - - - - - - - - - - - - to
TB2-2 (+) IW.322 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-2 (-) IW.322 R3S04 - - - - - - - - - - - - to
TB2-3 (+) IW.324 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-3 (-) IW.324 R3S04 - - - - - - - - - - - - to
TB2-4 (+) IW.326 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-4 (-) IW.326 R3S04 - - - - - - - - - - - - to
TB2-5 (+) IW.328 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-5 (-) IW.328 R3S04 - - - - - - - - - - - - to
TB2-6 (+) IW.330 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-6 (-) IW.330 R3S04 - - - - - - - - - - - - to
TB2-7 (+) IW.332 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-7 (-) IW.332 R3S04 - - - - - - - - - - - - to
TB2-8 (+) IW.334 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-8 (-) IW.334 R3S04 - - - - - - - - - - - - to
TB2-9 (+) IW.336 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-9 (-) IW.336 R3S04 - - - - - - - - - - - - to
TB2-10 (+) IW.338 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-10 (-) IW.338 R3S04 - - - - - - - - - - - - to
TB2-11 (+) IW.340 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-11 (-) IW.340 R3S04 - - - - - - - - - - - - to
TB2-12 (+) IW.342 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-12 (-) IW.342 R3S04 - - - - - - - - - - - - to
TB2-13 (+) IW.344 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-13 (-) IW.344 R3S04 - - - - - - - - - - - - to
TB2-14 (+) IW.346 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-14 (-) IW.346 R3S04 - - - - - - - - - - - - to
TB2-15 (+) IW.348 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-15 (-) IW.348 R3S04 - - - - - - - - - - - - to
TB2-16 (+) IW.350 R3S04 - SPARE - - - - - - - - - - to
TB2-16 (-) IW.350 R3S04 - - - - - - - - - - - - to
ZS1 ZS1 1 R1S01 ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R1S01 ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
RL-01 Q4.0 4 R1S01 Q4.0 2 R2S02 R15 RING MAIN H03 (R15VB40)(TO R16) VCB OPEN S015-1 - 4001 4002 CO - - - - - -
RL-02 Q4.1 5 R1S01 Q4.1 3 R2S02 R15 RING MAIN H03 (R15VB40)(TO R16) VCB CLOSE S015-2 - 4001 4003 CO - - - - - -
RL-03 Q4.2 6 R1S01 Q4.2 6 R2S02 R15 RING MAIN H04 (R15VB41)(TO R10) VCB OPEN S015-3 - 4004 4005 CO - - - - - -
RL-04 Q4.3 7 R1S01 Q4.3 7 R2S02 R15 RING MAIN H04 (R15VB41)(TO R10) VCB CLOSE S015-4 - 4004 4006 CO - - - - - -
RL-05 Q4.4 8 R1S01 Q4.4 12 R2S02 R15 RING MAIN H05 (R15VB42)(TO R14) VCB OPEN S015-5 - 4007 4008 CO - - - - - -
RL-06 Q4.5 9 R1S01 Q4.5 13 R2S02 R15 RING MAIN H05 (R15VB42)(TO R14) VCB CLOSE S015-6 - 4007 4009 CO - - - - - -
RL-07 Q4.6 10 R1S01 Q4.6 16 R2S02 R15 RECTIFIER FEEDER H01 (R15VB50) VCB OPEN S015-7 - 4010 4011 CO - - - - - -
RL-08 Q4.7 11 R1S01 Q4.7 17 R2S02 R15 RECTIFIER FEEDER H01 (R15VB50) VCB CLOSE S015-8 - 4010 4012 CO - - - - - -
- - - - L+ 19 R2S02
- - - - M 20 R2S02
RL-09 Q5.0 15 R1S01 Q5.0 22 R2S02 R15 RECTIFIER FEEDER H02 (R15VB51) VCB OPEN S015-9 - 4013 4014 CO - - - - - -
RL-10 Q5.1 16 R1S01 Q5.1 23 R2S02 R15 RECTIFIER FEEDER H02 (R15VB51) VCB CLOSE S015-10 - 4013 4015 CO - - - - - -
RL-11 Q5.2 17 R1S01 Q5.2 26 R2S02 - SPARE S015-11 - - - - - - - - -
RL-12 Q5.3 18 R1S01 Q5.3 27 R2S02 - SPARE S015-12 - - - - - - - - -
RL-13 Q5.4 19 R1S01 Q5.4 32 R2S02 R15 RECTIFIER FEEDER D1 DCCB OPEN S015-13 - 4101 4103 CO - - - - - -
RL-14 Q5.5 20 R1S01 Q5.5 33 R2S02 R15 RECTIFIER FEEDER D1 DCCB CLOSE S015-14 - 4101 4102 CO - - - - - -
RL-15 Q5.6 21 R1S01 Q5.6 36 R2S02 R15 RECTIFIER FEEDER D2 DCCB OPEN S015-15 - 4105 4107 CO - - - - - -
RL-16 Q5.7 22 R1S01 Q5.7 37 R2S02 R15 RECTIFIER FEEDER D2 DCCB CLOSE S015-16 - 4105 4106 CO - - - - - -
- - - - L+ 39 R2S02
- - - - M 40 R2S02
RL-17 Q6.0 26 R1S01 Q6.0 2 R2S03 - SPARE S015-17 - - - - - - - - -
RL-18 Q6.1 27 R1S01 Q6.1 3 R2S03 - SPARE S015-18 - - - - - - - - -
RL-19 Q6.2 28 R1S01 Q6.2 6 R2S03 R15 TRACK FEEDER D33 DCCB OPEN S015-19 - 4071 4074 CO - - - - - -
RL-20 Q6.3 29 R1S01 Q6.3 7 R2S03 R15 TRACK FEEDER D33 DCCB CLOSE S015-20 - 4071 4073 CO - - - - - -
RL-21 Q6.4 30 R1S01 Q6.4 12 R2S03 R15 TRACK FEEDER D33 LINE TEST CONTROL ON S015-21 - 4071 4063 CO - - - - - -
RL-22 Q6.5 31 R1S01 Q6.5 13 R2S03 R15 TRACK FEEDER D33 LINE TEST CONTROL OFF S015-22 - 4071 4072 CO - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 166 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-23 Q6.6 32 R1S01 Q6.6 16 R2S03 R15 TRACK FEEDER D34 DCCB OPEN S015-23 - 4076 4079 CO - - - - - -
RL-24 Q6.7 33 R1S01 Q6.7 17 R2S03 R15 TRACK FEEDER D34 DCCB CLOSE S015-24 - 4076 4078 CO - - - - - -
- - - - L+ 19 R2S03
- - - - M 20 R2S03
RL-25 Q7.0 37 R1S01 Q7.0 22 R2S03 R15 TRACK FEEDER D34 LINE TEST CONTROL ON S015-25 - 4076 4064 CO - - - - - -
RL-26 Q7.1 38 R1S01 Q7.1 23 R2S03 R15 TRACK FEEDER D34 LINE TEST CONTROL OFF S015-26 4076 4077 CO - - - - - -
RL-27 Q7.2 39 R1S01 Q7.2 26 R2S03 R15 TRACK FEEDER D35 DCCB OPEN S015-27 - 4081 4084 CO - - - - - -
RL-28 Q7.3 40 R1S01 Q7.3 27 R2S03 R15 TRACK FEEDER D35 DCCB CLOSE S015-28 - 4081 4083 CO - - - - - -
RL-29 Q7.4 41 R1S01 Q7.4 32 R2S03 R15 TRACK FEEDER D35 LINE TEST CONTROL ON S015-29 - 4081 4065 CO - - - - - -
RL-30 Q7.5 42 R1S01 Q7.5 33 R2S03 R15 TRACK FEEDER D35 LINE TEST CONTROL OFF S015-30 4081 4082 CO
RL-31 Q7.6 43 R1S01 Q7.6 36 R2S03 - SPARE S015-31 - - - - - - - - -
RL-32 Q7.7 44 R1S01 Q7.7 37 R2S03 - SPARE S015-32 - - - - - - - - -
- - - - L+ 39 R2S03 - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - -
ON THE 32
ENABLE CO
CONTACT AND COMMON RETURN LINE
- - - - M 40 R2S03 - - - - - - - - - - - -
ON THEDC
32 SUPPLY
CO
FR0 FR0 34 R1S01 FR0 - - - +110V (COMMAND VOLTAGE INPUT) - - - - - - - - - - -
FR1 FR1 35 R1S01 FR1 - - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - -
UE0 UE0 45 R1S01 UE0 31 -
UE1 UE1 46 R1S01 UE1 35 -
ZS1 ZS1 1 R1S02 ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R1S02 ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
RL-33 Q8.0 4 R1S02 Q8.0 2 R2S04 R15 TRACK FEEDER D36 DCCB OPEN S016-1 - 4086 4089 CO - - - - - -
RL-34 Q8.1 5 R1S02 Q8.1 3 R2S04 R15 TRACK FEEDER D36 DCCB CLOSE S016-2 - 4086 4088 CO - - - - - -
RL-35 Q8.2 6 R1S02 Q8.2 6 R2S04 R15 TRACK FEEDER D36 LINE TEST CONTROL ON S016-3 - 4086 4066 CO - - - - - -
RL-36 Q8.3 7 R1S02 Q8.3 7 R2S04 R15 TRACK FEEDER D36 LINE TEST CONTROL OFF S016-4 4086 4087 CO
RL-37 Q8.4 8 R1S02 Q8.4 12 R2S04 R15 TRACK FEEDER D37 DCCB OPEN S016-5 - 4091 4094 CO - - - - - -
RL-38 Q8.5 9 R1S02 Q8.5 13 R2S04 R15 TRACK FEEDER D37 DCCB CLOSE S016-6 - 4091 4093 CO - - - - - -
RL-39 Q8.6 10 R1S02 Q8.6 16 R2S04 R15 TRACK FEEDER D37 LINE TEST CONTROL ON S016-7 - 4091 4067 CO - - - - - -
RL-40 Q8.7 11 R1S02 Q8.7 17 R2S04 R15 TRACK FEEDER D37 LINE TEST CONTROL OFF S016-8 4091 4092 CO
- - - - L+ 19 R2S04
- - - - M 20 R2S04
RL-41 Q9.0 15 R1S02 Q9.0 22 R2S04 R15 TRACK FEEDER D38 DCCB OPEN S016-9 - 4096 4099 CO - - - - - -
RL-42 Q9.1 16 R1S02 Q9.1 23 R2S04 R15 TRACK FEEDER D38 DCCB CLOSE S016-10 - 4096 4098 CO - - - - - -
RL-43 Q9.2 17 R1S02 Q9.2 26 R2S04 R15 TRACK FEEDER D38 LINE TEST CONTROL ON S016-17 - 4071 4068 CO - - - - - -
RL-44 Q9.3 18 R1S02 Q9.3 27 R2S04 R15 TRACK FEEDER D38 LINE TEST CONTROL OFF S016-18 4096 4097 CO
RL-45 Q9.4 19 R1S02 Q9.4 32 R2S04 R15 AUXILIARY TRANSFORMER H06 VCB OPEN S016-13 - 4016 4017 CO - - - - - -
RL-46 Q9.5 20 R1S02 Q9.5 33 R2S04 (R15VB60)
R15 AUXILIARY TRANSFORMER H06 VCB CLOSE S016-14 - 4016 4018 CO - - - - - -
RL-47 Q9.6 21 R1S02 Q9.6 36 R2S04 (R15VB60)
R15 DC COMMON EQUIPMENT (OVPD) CONTACTOR RESET S016-15 - 4039 4040 CO - - - - - -
RL-48 Q9.7 22 R1S02 Q9.7 37 R2S04 R15 DC COMMON EQUIPMENT (OVPD) CONTACTOR CLOSE S016-16 - 4041 4042 CO - - - - - -
- - - - L+ 39 R2S04
- - - - M 40 R2S04
RL-49 Q10.0 26 R1S02 Q10.0 2 R2S05 R15 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT internal - - - CO - - - - - -
RL-50 Q10.1 27 R1S02 Q10.1 3 R2S05 R15 DUMMY CB BIT) OPEN/CLOSE (LEAST SIGINIFICANT
VCB wiring
internal - - - CO - - - - - -
RL-51 Q10.2 28 R1S02 Q10.2 6 R2S05 - BIT) SPARE wiring
S016-19 - - - - - - - - -
RL-52 Q10.3 29 R1S02 Q10.3 7 R2S05 - SPARE S016-20 - - - - - - - - -
RL-53 Q10.4 30 R1S02 Q10.4 12 R2S05 - SPARE S016-21 - - - - - - - - -
RL-54 Q10.5 31 R1S02 Q10.5 13 R2S05 - SPARE S016-22 - - - - - - - - -
RL-55 Q10.6 32 R1S02 Q10.6 16 R2S05 - SPARE S016-23 - - - - - - - - -
RL-56 Q10.7 33 R1S02 Q10.7 17 R2S05 - SPARE S016-24 - - - - - - - - -
- - - - L+ 19 R2S05
- - - - M 20 R2S05
RL-57 Q11.0 37 R1S02 Q11.0 22 R2S05 - SPARE S016-25 - - - - - - - - -
RL-58 Q11.1 38 R1S02 Q11.1 23 R2S05 - SPARE S016-26 - - - - - - - - -
RL-59 Q11.2 39 R1S02 Q11.2 26 R2S05 - SPARE S016-27 - - - - - - - - -
RL-60 Q11.3 40 R1S02 Q11.3 27 R2S05 - SPARE S016-28 - - - - - - - - -
RL-61 Q11.4 41 R1S02 Q11.4 32 R2S05 - SPARE S016-29 - - - - - - - - -
RL-62 Q11.5 42 R1S02 Q11.5 33 R2S05 - SPARE S016-30 - - - - - - - - -
RL-63 Q11.6 43 R1S02 Q11.6 36 R2S05 - SPARE S016-31 - - - - - - - - -
RL-64 Q11.7 44 R1S02 Q11.7 37 R2S05 - SPARE S016-32 - - - - - - - - -
- - - - L+ 39 R2S05
- - - - M 40 R2S05
FR0 FR0 34 R1S02 FR0 - - - - - - - - - - - - - - -
FR1 FR1 35 R1S02 FR1 - - - - - - - - - - - - - - -
UE0 UE0 45 R1S02 UE0 31 - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 167 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)


New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules)
Modules Modules RTU Modules)
Modules Modules Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UE1 UE1 46 R1S02 UE1 35 - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 168 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS15 [RS15] 169 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS15 [RS15] 170 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 171 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS15 [RS15] 172 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - NO 0 - - - - - - - - - NC NC - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 173 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

Unrestricted 749775924.xlsx/RS15 [RS15] 174 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS15 [RS15] 175 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC NC - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 176 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - C NC - -

- - NO 0 - - - - - - - - - - - NC C

Unrestricted 749775924.xlsx/RS15 [RS15] 177 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 178 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - -
20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
20 0 to 200 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 10.400 11.600 - - 76.000 90.250 - - 10.080 11.220
20 0 to 200 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - 10.400 11.600 - - 76 90.25 - - 10.080 11.220
20 0 to 100 A ac - - 1.0% - - 42 50 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 10.720 12.000 - - 39.9 47.5 - - 10.384 11.600
20 0 to 15 kV ac - - 1.0% 1.0 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 5.067 14.560 16.907 17.227 0.950 10.395 11.495 11.78 5.013 15.088 16.261 16.565
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375 2850 -8.143 -6.786 6.786 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375 2850 -8.143 -6.786 6.786 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375 2850 -8.143 -6.786 6.786 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375 2850 -8.143 -6.786 6.786 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
20 0 to 5000 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 12.000 13.600 - - 2375 2850 - - 11.600 13.120
20 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 19.200 19.680 - - 902.5 931 - - 18.440 18.896
20 0 to 5000 A dc - - 1.0% - - 2500 3000 0.05 0.05 0.05 0.05 C NC NC C
- - to - - - - - - - 12.000 13.600 - - 2375 2850 - - 11.600 13.120
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
20 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 19.200 19.680 - - 902.5 931 - - 18.440 18.896
20 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 10.640 12.480 19.200 19.680 394.250 556.500 902.5 931 10.308 12.904 18.440 18.896
20 0 to 4000 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.000 20.000 - - 3325 3800 - - 17.300 19.200
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.600 30.400 3.800 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 9.5 15.75 26.6 30.4 3.800 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.6 30.4 3.800 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.6 30.4 3.800 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 9.500 15.750 26.6 30.4 3.800 6.300 10.640 12.160
20 0 to 1200 A ac - - 1.0% - - 1080 1200 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 1026 1140 - - 17.680 19.200
20 0 to 220 V ac - - 1.0% 198 209 - - 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 18.400 19.200 #VALUE! #VALUE! 188.100 219.450 #VALUE! #VALUE! 17.680 19.960 #VALUE! #VALUE!
20 0 to 500 A ac - - 1.0% - - 450 500 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 427.5 475 - - 17.680 19.200
20 0 to 500 A ac - - 1.0% - - 450 500 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 427.5 475 - - 17.680 19.200
20 0 to 300 A ac - - 1.0% - - 270 300 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 256.5 285 - - 17.680 19.200
20 0 to 220 V ac - - 1.0% 198 209 - - 5.00% 5.00% 5.00% 5.00% C NC NC C

Unrestricted 749775924.xlsx/RS15 [RS15] 179 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - to - - - - - 18.400 19.200 #VALUE! #VALUE! 188.100 219.450 #VALUE! #VALUE! 17.680 19.960 #VALUE! #VALUE!
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 180 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 181 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 182 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION
Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH

- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS15 [RS15] 183 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -


ZS2 ZS2 2 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -

DI-2 I4.0 4 R0S7 I4.0 R0S02 R16 RING MAIN H03 (R16VB40)(TO R13) CONTROL SELECTOR SWITCH S005-3 - 1004 1005 SB - LOCAL REMOTE - - -
DI-4 I4.1 5 R0S7 I4.1 R0S02 R16 RING MAIN H03 (R16VB40)(TO R13) O/C EARTH FAULT TRIP S005-4 - 1006 1007 SB - RESET OPERATED - - -
DI-6 I4.2 6 R0S7 I4.2 R0S02 R16 RING MAIN H03 (R16VB40)(TO R13) SOLKOR TRIP S005-5 - 1006 1008 SB - RESET OPERATED - - -
DI-8 I4.3 7 R0S7 I4.3 R0S02 R16 RING MAIN H03 (R16VB40)(TO R13) OVERLOAD ALARM S005-6 - 1006 1009 SB - NORMAL OPERATED - - -
DI-10 I4.4 8 R0S7 I4.4 R0S02 R16 RING MAIN H03 (R16VB40)(TO R13) PILOT WIRE ALARM S005-7 - 1006 1010 SB - NORMAL OPERATED - - -
DI-12 I4.5 9 R0S7 I4.5 R0S02 R16 RING MAIN H03 (R16VB40)(TO R13) TRIP CCT SUPERVISION ALARM S005-8 - 1011 1012 SB - NORMAL OPERATED - - -
DI-14 I4.6 10 R0S07 I4.6 R0S02 R16 RING MAIN H04 (R16VB41)(TO R15) CONTROL SELECTOR SWITCH S005-13 - 1019 1020 SB - LOCAL REMOTE - - -
DI-16 I4.7 11 R0S07 I4.7 R0S02 R16 RING MAIN H04 (R16VB41)(TO R15) O/C EARTH FAULT TRIP S005-14 - 1021 1022 SB - RESET OPERATED - - -
UM0 UM0 12 R0S07 UM0 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S07 UW0 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - -
DI-18 I5.0 15 R0S07 I5.0 R0S02 R16 RING MAIN H04 (R16VB41)(TO R15) SOLKOR TRIP S005-15 - 1021 1023 SB - RESET OPERATED - - -
DI-20 I5.1 16 R0S07 I5.1 R0S02 R16 RING MAIN H04 (R16VB41)(TO R15) OVERLOAD ALARM S005-16 - 1021 1024 SB - NORMAL OPERATED - - -
DI-22 I5.2 17 R0S07 I5.2 R0S02 R16 RING MAIN H04 (R16VB41)(TO R15) PILOT WIRE ALARM S005-17 - 1021 1025 SB - NORMAL OPERATED - - -
DI-24 I5.3 18 R0S07 I5.3 R0S02 R16 RING MAIN H04 (R16VB41)(TO R15) TRIP CCT SUPERVISION ALARM S005-18 - 1026 1027 SB - NORMAL OPERATED - - -
DI-26 I5.4 19 R0S07 I5.4 R0S02 R16 RING MAIN H05 (R16VB42)(TO R14) CONTROL SELECTOR SWITCH S005-23 - 1034 1035 SB - LOCAL REMOTE - - -
DI-28 I5.5 20 R0S07 I5.5 R0S02 R16 RING MAIN H05 (R16VB42)(TO R14) O/C EARTH FAULT TRIP S005-24 - 1036 1037 SB - RESET OPERATED - - -
DI-30 I5.6 21 R0S07 I5.6 R0S02 R16 RING MAIN H05 (R16VB42)(TO R14) SOLKOR TRIP S005-25 - 1036 1038 SB - RESET OPERATED - - -
DI-32 I5.7 22 R0S07 I5.7 R0S02 R16 RING MAIN H05 (R16VB42)(TO R14) OVERLOAD ALARM S005-26 - 1036 1039 SB - NORMAL OPERATED - - -
UM1 UM1 23 R0S07 UM1 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S07 UW1 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-34 I6.0 26 R0S07 I6.0 R0S02 R16 RING MAIN H05 (R16VB42)(TO R14) PILOT WIRE ALARM S005-27 - 1036 1040 SB - NORMAL OPERATED - - -
DI-36 I6.1 27 R0S07 I6.1 R0S02 R16 RING MAIN H05 (R16VB42)(TO R14) TRIP CCT SUPERVISION ALARM S005-28 - 1041 1042 SB - NORMAL OPERATED - - -
DI-38 I6.2 28 R0S07 I6.2 R0S02 R16 RECTIFIER FEEDER H01 (R16VB50) CONTROL SELECTOR SWITCH S005-33 - 1050 1051 SB - LOCAL REMOTE - - -
DI-40 I6.3 29 R0S07 I6.3 R0S02 R16 RECTIFIER FEEDER H01 (R16VB50) O/C EARTH FAULT TRIP S005-34 - 1052 1053 SB - RESET OPERATED - - -
DI-42 I6.4 30 R0S07 I6.4 R0S02 R16 RECTIFIER FEEDER H01 (R16VB50) OVERLOAD TRIP S005-35 - 1052 1054 SB - RESET OPERATED - - -
DI-44 I6.5 31 R0S07 I6.5 R0S02 R16 RECTIFIER FEEDER H01 (R16VB50) TRIP CCT SUPERVISION ALARM S005-36 - 1062 1063 SB - NORMAL OPERATED - - -
DI-46 I6.6 32 R0S07 I6.6 R0S02 R16 RECT 1 TRANSFORMER SUDDEN PRESSURE TRIP S005-37 - 1052 1055 SB - RESET OPERATED - - -
DI-48 I6.7 33 R0S07 I6.7 R0S02 R16 RECT 1 TRANSFORMER PRESSURE RELIEF ALARM S005-38 - 1052 1056 SB - NORMAL OPERATED - - -
UM2 UM2 34 R0S07 UM2 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 UW2 35 R0S07 UW2 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-50 I7.0 37 R0S07 I7.0 R0S02 R16 RECT 1 TRANSFORMER LIQUID LEVEL LOW TRIP S006-1 - 1052 1057 SB - RESET OPERATED - - -
DI-52 I7.1 38 R0S07 I7.1 R0S02 R16 RECT 1 TRANSFORMER WINDING TEMP HIGH ALARM S006-2 - 1052 1058 SB - NORMAL OPERATED - - -
DI-54 I7.2 39 R0S07 I7.2 R0S02 R16 RECT 1 TRANSFORMER WINDING TEMP HIGH TRIP S006-3 - 1052 1059 SB - RESET OPERATED - - -
DI-56 I7.3 40 R0S07 I7.3 R0S02 R16 RECT 1 TRANSFORMER LIQUID TEMP HIGH ALARM S006-4 - 1052 1060 SB - NORMAL OPERATED - - -
DI-58 I7.4 41 R0S07 I7.4 R0S02 R16 RECT 1 TRANSFORMER LIQUID TEMP HIGH TRIP S006-5 - 1052 1061 SB - RESET OPERATED - - -
DI-60 I7.5 42 R0S07 I7.5 R0S02 R16 RECTIFIER 1 FRAME EARTH ALARM S006-6 - - - SB - NORMAL OPERATED - - -
DI-62 I7.6 43 R0S07 I7.6 R0S02 R16 RECTIFIER 1 FRAME EARTH TRIP S006-7 - 1064 1065 SB - RESET OPERATED - - -
DI-64 I7.7 44 R0S07 I7.7 R0S02 R16 RECTIFIER 1 DIODE DEFECT ALARM-SINGLE S006-8 - 1066 1067 SB - NORMAL OPERATED - - -
UM3 UM3 45 R0S07 UM3 R0S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S07 UW3 R0S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S08 ZS1 R0S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S08 ZS2 R0S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-66 I8.0 4 R0S08 I8.0 R0S03 R16 RECTIFIER 1 DIODE DEFECT TRIP-MULTI S006-11 - 1068 1069 SB - RESET OPERATED - - -
DI-68 I8.1 5 R0S08 I8.1 R0S03 R16 RECTIFIER 1 DIODE OVER TEMP ALARM S006-12 - 1070 1071 SB - NORMAL OPERATED - - -
DI-70 I8.2 6 R0S08 I8.2 R0S03 R16 RECTIFIER 1 DIODE OVER TEMP TRIP S006-13 - 1072 1073 SB - RESET OPERATED - - -
DI-72 I8.3 7 R0S08 I8.3 R0S03 R16 RECTIFIER FEEDER D1 REVERSE CURRENT TRIP S008-18 - 2045 2046 SB - RESET OPERATED - - -
DI-74 I8.4 8 R0S08 I8.4 R0S03 R16 RECTIFIER 1 SURGE ARRESTOR ALARM S006-15 - - - SB - NORMAL OPERATED - - -
DI-76 I8.5 9 R0S08 I8.5 R0S03 R16 RECTIFIER 1 SURGE ARRESTOR TRIP S006-14 - - - SB - RESET OPERATED - - -
DI-78 I8.6 10 R0S08 I8.6 R0S03 R16 RECTIFIER 1 FILTER CIRCUIT ALARM S007-4 - - - SB - NORMAL OPERATED - - -
DI-80 I8.7 11 R0S08 I8.7 R0S03 R16 RECTIFIER 1 AUXILIARY SUPPLY FAILURE ALARM S006-18 - 1080 1081 SB - NORMAL OPERATED - - -
UM0 UM0 12 R0S08 UM0 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S08 UW0 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-82 I9.0 15 R0S08 I9.0 R0S03 R16 RECTIFIER FEEDER H02 (R16VB51) CONTROL SELECTOR SWITCH S006-23 - 2004 2005 SB - LOCAL REMOTE - - -

DI-84 I9.1 16 R0S08 I9.1 R0S03 R16 RECTIFIER FEEDER H02 (R16VB51) O/C EARTH FAULT TRIP S006-24 - 2006 2007 SB - RESET OPERATED - - -

DI-86 I9.2 17 R0S08 I9.2 R0S03 R16 RECTIFIER FEEDER H02 (R16VB51) OVERLOAD TRIP S006-25 - 2006 2008 SB - RESET OPERATED - - -

DI-88 I9.3 18 R0S08 I9.3 R0S03 R16 RECTIFIER FEEDER H02 (R16VB51) TRIP CCT SUPERVISION ALARM S006-26 - 2016 2017 SB - NORMAL OPERATED - - -

DI-90 I9.4 19 R0S08 I9.4 R0S03 R16 RECT 2 TRANSFORMER SUDDEN PRESSURE TRIP S006-27 - 2006 2009 SB - RESET OPERATED - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 184 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-92 I9.5 20 R0S08 I9.5 R0S03 R16 RECT 2 TRANSFORMER PRESSURE RELIEF ALARM S006-28 - 2006 2010 SB - NORMAL OPERATED - - -
DI-94 I9.6 21 R0S08 I9.6 R0S03 R16 RECT 2 TRANSFORMER LIQUID LEVEL LOW TRIP S006-31 - 2006 2011 SB - RESET OPERATED - - -
DI-96 I9.7 22 R0S08 I9.7 R0S03 R16 RECT 2 TRANSFORMER WINDING TEMP HIGH ALARM S006-32 - 2006 2012 SB - NORMAL OPERATED - - -
UM1 UM1 23 R0S08 UM1 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S08 UW1 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-98 I10.0 26 R0S08 I10.0 R0S03 R16 RECT 2 TRANSFORMER WINDING TEMP HIGH TRIP S006-33 - 2006 2013 SB - RESET OPERATED - - -
DI-100 I10.1 27 R0S08 I10.1 R0S03 R16 RECT 2 TRANSFORMER LIQUID TEMP HIGH ALARM S006-34 - 2006 2014 SB - NORMAL OPERATED - - -
DI-102 I10.2 28 R0S08 I10.2 R0S03 R16 RECT 2 TRANSFORMER LIQUID TEMP HIGH TRIP S006-35 - 2006 2015 SB - RESET OPERATED - - -
DI-104 I10.3 29 R0S08 I10.3 R0S03 R16 RECTIFIER 2 FRAME EARTH ALARM S006-36 - - - SB - NORMAL OPERATED - - -
DI-106 I10.4 30 R0S08 I10.4 R0S03 R16 RECTIFIER 2 FRAME EARTH TRIP S006-37 - 2018 2019 SB - RESET OPERATED - - -
DI-108 I10.5 31 R0S08 I10.5 R0S03 R16 RECTIFIER 2 DIODE DEFECT ALARM-SINGLE S006-38 - 2020 2021 SB - NORMAL OPERATED - - -
DI-110 I10.6 32 R0S08 I10.6 R0S03 R16 RECTIFIER 2 DIODE DEFECT TRIP-MULTI S007-1 - 2022 2023 SB - RESET OPERATED - - -
DI-112 I10.7 33 R0S08 I10.7 R0S03 R16 RECTIFIER 2 DIODE OVER TEMP ALARM S007-2 - 2024 2025 SB - NORMAL OPERATED - - -
UM2 UM2 34 R0S08 UM2 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 UW2 35 R0S08 UW2 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-114 I11.0 37 R0S08 I11.0 R0S03 R16 RECTIFIER 2 DIODE OVER TEMP TRIP S007-3 - 2026 2027 SB - RESET OPERATED - - -
DI-116 I11.1 38 R0S08 I11.1 R0S03 R16 RECTIFIER FEEDER D2 REVERSE CURRENT TRIP S008-24 - 2054 2055 SB - RESET OPERATED - - -
DI-118 I11.2 39 R0S08 I11.2 R0S03 R16 RECTIFIER 2 SURGE ARRESTOR ALARM S007-5 - - - SB - NORMAL OPERATED - - -
DI-120 I11.3 40 R0S08 I11.3 R0S03 R16 RECTIFIER 2 SURGE ARRESTOR TRIP S007-6 - 2030 2031 SB - RESET OPERATED - - -
DI-122 I11.4 41 R0S08 I11.4 R0S03 R16 RECTIFIER 2 FILTER CIRCUIT ALARM S007-7 - 2032 2033 SB - NORMAL OPERATED - - -
DI-124 I11.5 42 R0S08 I11.5 R0S03 R16 RECTIFIER 2 AUXILIARY SUPPLY FAILURE ALARM S007-8 - 2034 2035 SB - NORMAL OPERATED - - -
DI-126 I11.6 43 R0S08 I11.6 R0S03 - SPARE S007-11 - - - - - - - - -
DI-128 I11.7 44 R0S08 I11.7 R0S03 - SPARE S007-12 - - - - - - - - -
UM3 UM3 45 R0S08 UM3 R0S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S08 UW3 R0S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S09 ZS1 R0S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S09 ZS2 R0S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-130 I12.0 4 R0S09 I12.0 R0S04 - SPARE S007-13 - - - - - - - - -
DI-132 I12.1 5 R0S09 I12.1 R0S04 - SPARE S007-14 - - - - - - - - -
DI-134 I12.2 6 R0S09 I12.2 R0S04 - SPARE S007-15 - - - - - - - - -
DI-136 I12.3 7 R0S09 I12.3 R0S04 - SPARE S007-16 - - - - - - - - -
DI-138 I12.4 8 R0S09 I12.4 R0S04 - SPARE S007-17 - - - - - - - - -
DI-140 I12.5 9 R0S09 I12.5 R0S04 - SPARE S007-18 - - - - - - - - -
DI-142 I12.6 10 R0S09 I12.6 R0S04 - SPARE S007-21 - - - - - - - - -
DI-144 I12.7 11 R0S09 I12.7 R0S04 - SPARE S007-22 - - - - - - - - -
UM0 UM0 12 R0S09 UM0 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S09 UW0 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-146 I13.0 15 R0S09 I13.0 R0S04 - SPARE S007-23 - - - - - - - - -
DI-148 I13.1 16 R0S09 I13.1 R0S04 - SPARE S007-24 - - - - - - - - -
DI-150 I13.2 17 R0S09 I13.2 R0S04 - SPARE S007-25 - - - - - - - - -
DI-152 I13.3 18 R0S09 I13.3 R0S04 - SPARE S007-26 - - - - - - - - -
DI-154 I13.4 19 R0S09 I13.4 R0S04 - SPARE S007-27 - - - - - - - - -
DI-156 I13.5 20 R0S09 I13.5 R0S04 - SPARE S007-28 - - - - - - - - -
DI-158 I13.6 21 R0S09 I13.6 R0S04 - SPARE S007-31 - - - - - - - - -
DI-160 I13.7 22 R0S09 I13.7 R0S04 - SPARE S007-32 - - - - - - - - -
UM1 UM1 23 R0S09 UM1 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S09 UW1 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-162 I14.0 26 R0S09 I14.0 R0S04 - SPARE S007-33 - - - - - - - - -
DI-164 I14.1 27 R0S09 I14.1 R0S04 - SPARE S007-34 - - - - - - - - -
DI-166 I14.2 28 R0S09 I14.2 R0S04 - SPARE S007-35 - - - - - - - - -
DI-168 I14.3 29 R0S09 I14.3 R0S04 - SPARE S007-36 - - - - - - - - -
DI-170 I14.4 30 R0S09 I14.4 R0S04 - SPARE S007-37 - - - - - - - - -
DI-172 I14.5 31 R0S09 I14.5 R0S04 - SPARE S007-38 - - - - - - - - -
DI-174 I14.6 32 R0S09 I14.6 R0S04 R16 AUXILIARY TRANSFORMER H06 CONTROL SELECTOR SWITCH S008-3 - 1089 1090 SB - LOCAL REMOTE - - -
(R16VB60)
DI-176 I14.7 33 R0S09 I14.7 R0S04 R16 AUXILIARY TRANSFORMER H06 O/C EARTH FAULT TRIP S008-4 - 1091 1092 SB - RESET OPERATED - - -
(R16VB60)

Unrestricted 749775924.xlsx/RS16 [RS16] 185 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UM2 UM2 34 R0S09 UM2 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW2 UW2 35 R0S09 UW2 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-178 I15.0 37 R0S09 I15.0 R0S04 R16 AUXILIARY TRANSFORMER H06 TRIP CCT SUPEVISION ALARM S008-5 - 1098 1099 SB - NORMAL OPERATED - - -
(R16VB60)
DI-180 I15.1 38 R0S09 I15.1 R0S04 R16 AUXILIARY TRANSFORMER H06 PRESSURE GAUGE TRIP S008-6 - 1091 1093 SB - RESET OPERATED - - -
(R16VB60)
DI-182 I15.2 39 R0S09 I15.2 R0S04 R16 AUXILIARY TRANSFORMER H06 CONTROL CIRCUIT SUPERVISION S008-7 - 1091 1095 SB - NORMAL OPERATED - - -
(R16VB60)
DI-184 I15.3 40 R0S09 I15.3 R0S04 R16 AUXILIARY TRANSFORMER H06 LIQUID LEVEL LOW TRIP S008-8 - 1091 1094 SB - RESET OPERATED - - -
(R16VB60)
DI-186 I15.4 41 R0S09 I15.4 R0S04 R16 AUXILIARY TRANSFORMER H06 WINDING TEMP HIGH ALARM S008-11 - - - SB - NORMAL OPERATED - - -
(R16VB60)
DI-188 I15.5 42 R0S09 I15.5 R0S04 R16 AUXILIARY TRANSFORMER H06 WINDING TEMP HIGH TRIP S008-12 - - - SB - RESET OPERATED - - -
(R16VB60)
DI-190 I15.6 43 R0S09 I15.6 R0S04 R16 AUXILIARY TRANSFORMER H06 LIQUID TEMP HIGH ALARM S008-13 - 1091 1096 SB - NORMAL OPERATED - - -
(R16VB60)
DI-192 I15.7 44 R0S09 I15.7 R0S04 R16 AUXILIARY TRANSFORMER H06 LIQUID TEMP HIGH TRIP S008-14 - 1091 1097 SB - RESET OPERATED - - -
(R16VB60)
UM3 UM3 45 R0S09 UM3 R0S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S09 UW3 R0S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S10 ZS1 R1S02 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S10 ZS2 R1S02 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-194 I16.0 4 R0S10 I16.0 R1S02 R16 RECTIFIER FEEDER D1 CONTROL SELECTOR SWITCH S008-17 - 2043 2044 SB - LOCAL REMOTE - - -
DI-196 I16.1 5 R0S10 I16.1 R1S02 R16 RECTIFIER FEEDER D1 TRIP CCT SUPERVISION ALARM S006-16 - 2047 2048 SB - NORMAL OPERATED - - -
DI-198 I16.2 6 R0S10 I16.2 R1S02 R16 RECTIFIER FEEDER D2 CONTROL SELECTOR SWITCH S008-23 - 2052 2053 SB - LOCAL REMOTE - - -
DI-200 I16.3 7 R0S10 I16.3 R1S02 R16 RECTIFIER FEEDER D2 TRIP CCT SUPERVISION ALARM S006-17 - 2056 2057 SB - NORMAL OPERATED - - -
DI-202 I16.4 8 R0S10 I16.4 R1S02 R16 RECTIFIER FEEDER D3 CONTROL SELECTOR SWITCH S008-27 - - - SB - LOCAL REMOTE - - -
DI-204 I16.5 9 R0S10 I16.5 R1S02 R16 RECTIFIER FEEDER D3 TRIP CCT SUPERVISION ALARM S008-28 - - - SB - NORMAL OPERATED - - -
DI-206 I16.6 10 R0S10 I16.6 R1S02 R16 TRACK FEEDER D33 CONTROL SELECTOR SWITCH S008-33 - 2063 2064 SB - LOCAL REMOTE - - -
DI-208 I16.7 11 R0S10 I16.7 R1S02 R16 TRACK FEEDER D33 INSTANT OVERCURRENT S008-34 - 2065 2066 SB - RESET OVERCURRENT/ - - -
OPERATED
UM0 UM0 12 R0S10 UM0 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S10 UW0 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-210 I17.0 15 R0S10 I17.0 R1S02 R16 TRACK FEEDER D33 TRANSFER TRIP(R16DB33&34 FROM S008-35 - 3081 3082 SB - RESET OPERATED - - -
R15)
DI-212 I17.1 16 R0S10 I17.1 R1S02 R16 TRACK FEEDER D33 RATE OF RISE TRIP S008-36 - 2067 2068 SB - RESET OPERATED - - -
DI-214 I17.2 17 R0S10 I17.2 R1S02 R16 TRACK FEEDER D33 UNDERVOLTAGE TRIP S008-37 - - - SB - RESET OPERATED - - -
DI-216 I17.3 18 R0S10 I17.3 R1S02 R16 TRACK FEEDER D33 LINE TESTING S008-38 - 2069 2070 SB - COMPLETED IN PROGRESS - - -
DI-218 I17.4 19 R0S10 I17.4 R1S02 R16 TRACK FEEDER D33 LINE IMPEDANCE LOW S009-1 - 2071 2072 SB - NORMAL OPERATED - - -
DI-220 I17.5 20 R0S10 I17.5 R1S02 R16 TRACK FEEDER D33 TRIP CCT SUPERVISION ALARM S009-2 - 2073 2074 SB - NORMAL OPERATED - - -
DI-222 I17.6 21 R0S10 I17.6 R1S02 R16 TRACK FEEDER D33 TRANSFER TRIP S009-3 - 3077 3078 SB - RESET OPERATED - - -
DI-224 I17.7 22 R0S10 I17.7 R1S02 R16 TRACK FEEDER D33 LINE TEST CONTROL SELECTOR S009-4 - 2105 2106 SB - OFF ON - - -
SWITCH
UM1 UM1 23 R0S10 UM1 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S10 UW1 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-226 I18.0 26 R0S10 I18.0 R1S02 R16 TRACK FEEDER D34 CONTROL SELECTOR SWITCH S009-7 - 2078 2079 SB - LOCAL REMOTE - - -
DI-228 I18.1 27 R0S10 I18.1 R1S02 R16 TRACK FEEDER D34 INSTANT OVERCURRENT S009-8 - 2080 2081 SB - RESET OVERCURRENT/ - - -
OPERATED
DI-230 I18.2 28 R0S10 I18.2 R1S02 R16 TRACK FEEDER D34 TIME DELAY OVERCURRENT ALARM S009-11 - - - SB - NORMAL OPERATED - - -
DI-232 I18.3 29 R0S10 I18.3 R1S02 R16 TRACK FEEDER D34 RATE OF RISE TRIP S009-12 - 2082 2083 SB - RESET OPERATED - - -
DI-234 I18.4 30 R0S10 I18.4 R1S02 R16 TRACK FEEDER D34 UNDERVOLTAGE TRIP S009-13 - - - SB - RESET OPERATED - - -
DI-236 I18.5 31 R0S10 I18.5 R1S02 R16 TRACK FEEDER D34 LINE TESTING S009-14 - 2084 2085 SB - COMPLETED IN PROGRESS - - -
DI-238 I18.6 32 R0S10 I18.6 R1S02 R16 TRACK FEEDER D34 LINE IMPEDANCE LOW S009-15 - 2086 2087 SB - NORMAL OPERATED - - -
DI-240 I18.7 33 R0S10 I18.7 R1S02 R16 TRACK FEEDER D34 TRIP CCT SUPERVISION ALARM S009-16 - 2088 2089 SB - NORMAL OPERATED - - -
UM2 UM2 34 R0S10 UM2 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 UW2 35 R0S10 UW2 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-242 I19.0 37 R0S10 I19.0 R1S02 R16 TRACK FEEDER D34 TRANSFER TRIP S009-17 - - - SB - RESET OPERATED - - -
DI-244 I19.1 38 R0S10 I19.1 R1S02 R16 TRACK FEEDER D34 LINE TEST CONTROL SELECTOR S009-18 - 2107 2108 SB - OFF ON - - -
SWITCH
DI-246 I19.2 39 R0S10 I19.2 R1S02 R16 TRACK FEEDER D35 CONTROL SELECTOR SWITCH S009-23 - 2093 2094 SB - LOCAL REMOTE - - -
DI-248 I19.3 40 R0S10 I19.3 R1S02 R16 TRACK FEEDER D35 INSTANT OVERCURRENT S009-24 - 2095 2096 SB - RESET OVERCURRENT/ - - -
OPERATED
DI-250 I19.4 41 R0S10 I19.4 R1S02 R16 TRACK FEEDER D35 TIME DELAY OVERCURRENT ALARM S009-25 - - - SB - NORMAL OPERATED - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 186 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-252 I19.5 42 R0S10 I19.5 R1S02 R16 TRACK FEEDER D35 RATE OF RISE TRIP S009-26 - 2097 2098 SB - RESET OPERATED - - -
DI-254 I19.6 43 R0S10 I19.6 R1S02 R16 TRACK FEEDER D35 UNDERVOLTAGE TRIP S009-27 - - - SB - RESET OPERATED - - -
DI-256 I19.7 44 R0S10 I19.7 R1S02 R16 TRACK FEEDER D35 LINE TESTING S009-28 - 2099 2100 SB - COMPLETED IN PROGRESS - - -
UM3 UM3 45 R0S10 UM3 R1S02 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S10 UW3 R1S02 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S11 ZS1 R1S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S11 ZS2 R1S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-258 I20.0 4 R0S11 I20.0 R1S03 R16 TRACK FEEDER D35 LINE IMPEDANCE LOW S009-31 - 2101 2102 SB - NORMAL OPERATED - - -
DI-260 I20.1 5 R0S11 I20.1 R1S03 R16 TRACK FEEDER D35 TRIP CCT SUPERVISION ALARM S009-32 - 2103 2104 SB - NORMAL OPERATED - - -
DI-262 I20.2 6 R0S11 I20.2 R1S03 R16 TRACK FEEDER D35 TRANSFER TRIP S009-33 - 3078 3079 SB - RESET OPERATED - - -
DI-264 I20.3 7 R0S11 I20.3 R1S03 R16 TRACK FEEDER D35 LINE TEST CONTROL SELECTOR S009-34 - 2109 2110 SB - OFF ON - - -
SWITCH
DI-266 I20.4 8 R0S11 I20.4 R1S03 R16 TRACK FEEDER D36 CONTROL SELECTOR SWITCH S009-37 - 3004 3005 SB - LOCAL REMOTE - - -
DI-268 I20.5 9 R0S11 I20.5 R1S03 R16 TRACK FEEDER D36 INSTANT OVERCURRENT S009-38 - 3006 3007 SB - RESET OVERCURRENT/ - - -
OPERATED
DI-270 I20.6 10 R0S11 I20.6 R1S03 R16 TRACK FEEDER D36 TIME DELAY OVERCURRENT ALARM S010-1 - - - SB - NORMAL OPERATED - - -
DI-272 I20.7 11 R0S11 I20.7 R1S03 R16 TRACK FEEDER D36 RATE OF RISE TRIP S010-2 - 3008 3009 SB - RESET OPERATED - - -
UM0 UM0 12 R0S11 UM0 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S11 UW0 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-274 I21.0 15 R0S11 I21.0 R1S03 R16 TRACK FEEDER D36 UNDERVOLTAGE TRIP S010-3 - - - SB - RESET OPERATED - - -
DI-276 I21.1 16 R0S11 I21.1 R1S03 R16 TRACK FEEDER D36 LINE TESTING S010-4 - 3010 3011 SB - COMPLETED IN PROGRESS - - -
DI-278 I21.2 17 R0S11 I21.2 R1S03 R16 TRACK FEEDER D36 LINE IMPEDANCE LOW S010-5 - 3012 3013 SB - NORMAL OPERATED - - -
DI-280 I21.3 18 R0S11 I21.3 R1S03 R16 TRACK FEEDER D36 TRIP CCT SUPERVISION ALARM S010-6 - 3014 3015 SB - NORMAL OPERATED - - -
DI-282 I21.4 19 R0S11 I21.4 R1S03 R16 TRACK FEEDER D36 TRANSFER TRIP S010-7 - - - SB - RESET OPERATED - - -
DI-284 I21.5 20 R0S11 I21.5 R1S03 R16 TRACK FEEDER D36 LINE TEST CONTROL SELECTOR S010-8 - 3087 3088 SB - OFF ON - - -
SWITCH
DI-286 I21.6 21 R0S11 I21.6 R1S03 R16 TRACK FEEDER (SPARE 1) CONTROL SELECTOR SWITCH S010-13 - 3019 3020 SB - LOCAL REMOTE - - -
DI-288 I21.7 22 R0S11 I21.7 R1S03 R16 TRACK FEEDER (SPARE 1) INSTANT OVERCURRENT S010-14 - 3021 3022 SB - RESET OVERCURRENT/ - - -
OPERATED
UM1 UM1 23 R0S11 UM1 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S11 UW1 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-290 I22.0 26 R0S11 I22.0 R1S03 R16 TRACK FEEDER (SPARE 1) TIME DELAY OVERCURRENT ALARM S010-15 - - - SB - NORMAL OPERATED - - -
DI-292 I22.1 27 R0S11 I22.1 R1S03 R16 TRACK FEEDER (SPARE 1) RATE OF RISE TRIP S010-16 - 3023 3024 SB - RESET OPERATED - - -
DI-294 I22.2 28 R0S11 I22.2 R1S03 R16 TRACK FEEDER (SPARE 1) UNDERVOLTAGE TRIP S010-17 - - - SB - RESET OPERATED - - -
DI-296 I22.3 29 R0S11 I22.3 R1S03 R16 TRACK FEEDER (SPARE 1) LINE TESTING S010-18 - 3025 3026 SB - COMPLETED IN PROGRESS - - -
DI-298 I22.4 30 R0S11 I22.4 R1S03 R16 TRACK FEEDER (SPARE 1) LINE IMPEDANCE LOW S010-21 - 3027 3028 SB - NORMAL OPERATED - - -
DI-300 I22.5 31 R0S11 I22.5 R1S03 R16 TRACK FEEDER (SPARE 1) TRIP CCT SUPERVISION ALARM S010-22 - 3029 3030 SB - NORMAL OPERATED - - -
DI-302 I22.6 32 R0S11 I22.6 R1S03 R16 TRACK FEEDER (SPARE 1) TRANSFER TRIP S010-23 - - - SB - RESET OPERATED - - -
DI-304 I22.7 33 R0S11 I22.7 R1S03 R16 TRACK FEEDER (SPARE 1) LINE TEST CONTROL SELECTOR S010-24 - 3089 3090 SB - OFF ON - - -
SWITCH
UM2 UM2 34 R0S11 UM2 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 UW2 35 R0S11 UW2 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-306 I23.0 37 R0S11 I23.0 R1S03 R16 TRACK FEEDER (SPARE 2) CONTROL SELECTOR SWITCH S010-27 - 3034 3035 SB - LOCAL REMOTE - - -
DI-308 I23.1 38 R0S11 I23.1 R1S03 R16 TRACK FEEDER (SPARE 2) INSTANT OVERCURRENT S010-28 - 3036 3037 SB - RESET OVERCURRENT/ - - -
OPERATED
DI-310 I23.2 39 R0S11 I23.2 R1S03 R16 TRACK FEEDER (SPARE 2) TIME DELAY OVERCURRENT ALARM S010-31 - - - SB - NORMAL OPERATED - - -
DI-312 I23.3 40 R0S11 I23.3 R1S03 R16 TRACK FEEDER (SPARE 2) RATE OF RISE TRIP S010-32 - 3038 3039 SB - RESET OPERATED - - -
DI-314 I23.4 41 R0S11 I23.4 R1S03 R16 TRACK FEEDER (SPARE 2) UNDERVOLTAGE TRIP S010-33 - - - SB - RESET OPERATED - - -
DI-316 I23.5 42 R0S11 I23.5 R1S03 R16 TRACK FEEDER (SPARE 2) LINE TESTING S010-34 - 3040 3041 SB - COMPLETED IN PROGRESS - - -
DI-318 I23.6 43 R0S11 I23.6 R1S03 R16 TRACK FEEDER (SPARE 2) LINE IMPEDANCE LOW S010-35 - 3042 3043 SB - NORMAL OPERATED - - -
DI-320 I23.7 44 R0S11 I23.7 R1S03 R16 TRACK FEEDER (SPARE 2) TRIP CCT SUPERVISION ALARM S010-36 - 3044 3045 SB - NORMAL OPERATED - - -
UM3 UM3 45 R0S11 UM3 R1S03 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S11 UW3 R1S03 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 187 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R0S12 ZS1 R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -


ZS2 ZS2 2 R0S12 ZS2 R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-322 I24.0 4 R0S12 I24.0 R1S04 R16 TRACK FEEDER (SPARE 2) TRANSFER TRIP S010-37 - - - SB - RESET OPERATED - - -
DI-324 I24.1 5 R0S12 I24.1 R1S04 R16 TRACK FEEDER (SPARE 2) LINE TEST CONTROL SELECTOR S010-38 - 3091 3092 SB - OFF ON - - -
SWITCH
DI-326 I24.2 6 R0S12 I24.2 R1S04 R16 DC COMMON EQUIPMENT (OVPD) CONTACTOR CONTROL SELECTOR S011-3 - 3051 3052 SB - LOCAL REMOTE - - -
SWITCH
DI-328 I24.3 7 R0S12 I24.3 R1S04 R16 DC COMMON EQUIPMENT (OVPD) OVERVOLTAGE ALARM S011-4 - 3053 3054 SB - NORMAL OPERATED - - -
DI-330 I24.4 8 R0S12 I24.4 R1S04 R16 AC/DC SYSTEM MAINS FAILED ALARM S011-5 - 3055 3056 SB - NORMAL OPERATED - - -
DI-332 I24.5 9 R0S12 I24.5 R1S04 R16 AC/DC SYSTEM 110V HIGH VOLTAGE ALARM S011-11 - 3063 3064 SB - NORMAL OPERATED - - -
DI-334 I24.6 10 R0S12 I24.6 R1S04 R16 AC/DC SYSTEM AC EARTH FAULT TRIP S011-7 - 3059 3060 SB - RESET OPERATED - - -
DI-336 I24.7 11 R0S12 I24.7 R1S04 R16 AC/DC SYSTEM CHARGER FAILURE S011-8 - 3061 3062 SB - NORMAL OPERATED - - -
UM0 UM0 12 R0S12 UM0 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S12 UW0 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-338 I25.0 15 R0S12 I25.0 R1S04 R16 AC/DC SYSTEM CHARGER OUTPUT FAILURE ALARM S011-6 - 3057 3058 SB - NORMAL OPERATED - - -
DI-340 I25.1 16 R0S12 I25.1 R1S04 R16 AC/DC SYSTEM 110V LOW VOLTAGE ALARM S011-12 - 3065 3066 SB - NORMAL OPERATED - - -
DI-342 I25.2 17 R0S12 I25.2 R1S04 R16 AC/DC SYSTEM 11KV CONTROL VOLTAGE S011-13 - 3067 3068 SB - NORMAL FAULT/ - - -
OPERATED
DI-344 I25.3 18 R0S12 I25.3 R1S04 R16 AC/DC SYSTEM 750V CONTROL VOLTAGE S011-14 - 3069 3070 SB - NORMAL FAULT/ - - -
OPERATED
DI-346 I25.4 19 R0S12 I25.4 R1S04 R16 AC/DC SYSTEM 110V DC COMMON FEEDER S011-15 - 3071 3072 SB - NORMAL FAULT/ - - -
OPERATED
DI-348 I25.5 20 R0S12 I25.5 R1S04 R16 AC/DC SYSTEM 110V DC EARTH FAULT ALARM S011-16 - 3073 3074 SB - NORMAL OPERATED - - -
DI-350 I25.6 21 R0S12 I25.6 R1S04 R16 COMMON EQUIPMENT FIRE PROTECTION SYSTEM FAULT S011-17 - 5001 5002 SB - NORMAL OPERATED - - -
ALARM
DI-352 I25.7 22 R0S12 I25.7 R1S04 R16 COMMON EQUIPMENT FIRE PROTECTION ALARM S011-18 - 5003 5004 SB - RESET OPERATED - - -
UM1 UM1 23 R0S12 UM1 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S12 UW1 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-354 I26.0 26 R0S12 I26.0 R1S04 R16 COMMON EQUIPMENT INTRUDER ALARM S011-21 - 5005 5006 SB - NORMAL OPERATED - - -
DI-356 I26.1 27 R0S12 I26.1 R1S04 R16 COMMON EQUIPMENT SCADA UPS MAINS FAILED ALARM S011-22 - 5007 5008 SB - NORMAL OPERATED - - -
DI-358 I26.2 28 R0S12 I26.2 R1S04 R16 MVAC SYSTEM FAULT ALARM S011-23 - 5009 5010 SB - NORMAL OPERATED - - -
DI-360 I26.3 29 R0S12 I26.3 R1S04 R16 ROOMS OVERTEMPERATURE ALARM S011-24 - 5011 5012 SB - NORMAL OPERATED - - -
DI-362 I26.4 30 R0S12 I26.4 R1S04 R16 VOLTAGE STABILIZER FAULT ALARM S011-25 - 5013 5014 SB - NORMAL OPERATED - - -
DI-364 I26.5 31 R0S12 I26.5 R1S04 - SPARE S011-26 - - - - - - - - -
DI-366 I26.6 32 R0S12 I26.6 R1S04 R16 MVAC MOTORISED DAMPER NO.1 POSITION S011-27 - - - SB - OPEN CLOSED - - -
DI-368 I26.7 33 R0S12 I26.7 R1S04 - SPARE S011-28 - - - - - - - - -
UM2 UM2 34 R0S12 UM2 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - 200 - - -
UW2 UW2 35 R0S12 UW2 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-370 I27.0 37 R0S12 I27.0 R1S04 R16 MVAC MOTORISED DAMPER NO.2 POSITION S011-31 - 5017 5018 SB - OPEN CLOSED - - -
DI-372 I27.1 38 R0S12 I27.1 R1S04 - SPARE S011-32 - - - - - - - - -
DI-374 I27.2 39 R0S12 I27.2 R1S04 R16 MVAC MOTORISED DAMPER NO.3 POSITION S011-33 - 5019 5020 SB - OPEN CLOSED - - -
DI-376 I27.3 40 R0S12 I27.3 R1S04 - SPARE S011-34 - - - - - - - - -
DI-378 I27.4 41 R0S12 I27.4 R1S04 R16 MVAC VENTILATION FAN NO.1 FLOW SWITCH S011-35 - 5021 5022 SB - OPEN CLOSED - - -
DI-380 I27.5 42 R0S12 I27.5 R1S04 R16 MVAC VENTILATION FAN NO.1 FAULT ALARM S011-36 - 5023 5024 SB - NORMAL OPERATED - - -
DI-382 I27.6 43 R0S12 I27.6 R1S04 R16 MVAC VENTILATION FAN NO.1 EMERGENCY STOP S011-37 - 5025 5026 SB - RESET OPERATED - - -
DI-384 I27.7 44 R0S12 I27.7 R1S04 R16 MVAC VENTILATION FAN NO.1 CONTROL SELECTOR SWITCH S011-38 - 5027 5028 SB - LOCAL AUTO - - -
UM3 UM3 45 R0S12 UM3 R1S04 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S12 UW3 R1S04 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S13 ZS1 R0S05 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S13 ZS2 R0S05 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-386 I28.0 4 R0S13 I28.0 R0S05 R16 MVAC VENTILATION FAN NO.2 FLOW SWITCH S012-1 - 5029 5030 SB - OPEN CLOSED - - -
DI-388 I28.1 5 R0S13 I28.1 R0S05 R16 MVAC VENTILATION FAN NO.2 FAULT ALARM S012-2 - 5031 5032 SB - NORMAL OPERATED - - -
DI-390 I28.2 6 R0S13 I28.2 R0S05 R16 MVAC VENTILATION FAN NO.2 EMERGENCY STOP S012-3 - 5033 5034 SB - RESET OPERATED - - -
DI-392 I28.3 7 R0S13 I28.3 R0S05 R16 MVAC VENTILATION FAN NO.2 CONTROL SELECTOR SWITCH S012-4 - 5035 5036 SB - LOCAL AUTO - - -
DI-394 I28.4 8 R0S13 I28.4 R0S05 R16 MVAC VENTILATION FAN NO.3 FLOW SWITCH S012-5 - 5037 5038 SB - OPEN CLOSED - - -
DI-396 I28.5 9 R0S13 I28.5 R0S05 R16 MVAC VENTILATION FAN NO.3 FAULT ALARM S012-6 - 5039 5040 SB - NORMAL OPERATED - - -
DI-398 I28.6 10 R0S13 I28.6 R0S05 R16 MVAC VENTILATION FAN NO.3 EMERGENCY STOP S012-7 - 5041 5042 SB - RESET OPERATED - - -
DI-400 I28.7 11 R0S13 I28.7 R0S05 R16 MVAC VENTILATION FAN NO.3 CONTROL SELECTOR SWITCH S012-8 - 5043 5044 SB - LOCAL AUTO - - -
UM0 UM0 12 R0S13 UM0 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 UW0 13 R0S13 UW0 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-402 I29.0 15 R0S13 I29.0 R0S05 R16 MVAC VENTILATION FAN NO.4 FLOW SWITCH S012-11 - 5045 5046 SB - OPEN CLOSED - - -
DI-404 I29.1 16 R0S13 I29.1 R0S05 R16 MVAC VENTILATION FAN NO.4 FAULT ALARM S012-12 - 5047 5048 SB - NORMAL OPERATED - - -
DI-406 I29.2 17 R0S13 I29.2 R0S05 R16 MVAC VENTILATION FAN NO.4 EMERGENCY STOP S012-13 - 5049 5050 SB - RESET OPERATED - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 188 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

DI-408 I29.3 18 R0S13 I29.3 R0S05 R16 MVAC VENTILATION FAN NO.4 CONTROL SELECTOR SWITCH S012-14 - 5051 5052 SB - LOCAL AUTO - - -
DI-410 I29.4 19 R0S13 I29.4 R0S05 R16 MVAC VENTILATION FAN NO.5 FLOW SWITCH S012-15 - 5053 5054 SB - OPEN CLOSED - - -
DI-412 I29.5 20 R0S13 I29.5 R0S05 R16 MVAC VENTILATION FAN NO.5 FAULT ALARM S012-16 - 5055 5056 SB - NORMAL OPERATED - - -
DI-414 I29.6 21 R0S13 I29.6 R0S05 R16 MVAC VENTILATION FAN NO.5 EMERGENCY STOP S012-17 - 5057 5058 SB - RESET OPERATED - - -
DI-416 I29.7 22 R0S13 I29.7 R0S05 R16 MVAC VENTILATION FAN NO.5 CONTROL SELECTOR SWITCH S012-18 - 5059 5060 SB - LOCAL AUTO - - -
UM1 UM1 23 R0S13 UM1 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 UW1 24 R0S13 UW1 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-418 I30.0 26 R0S13 I30.0 R0S05 R16 380V NETWORK PROTECTION RELAYS COMMON ALARM S012-21 - 5015 5016 SB - NORMAL OPERATED - - -

DI-420 I30.1 27 R0S13 I30.1 R0S05 - SPARE S012-22 - 5063 5064 - - - - - -


DI-422 I30.2 28 R0S13 I30.2 R0S05 - SPARE S012-23 - 5065 5066 - - - - - -
DI-424 I30.3 29 R0S13 I30.3 R0S05 - SPARE S012-24 - - - - - - - - -
DI-426 I30.4 30 R0S13 I30.4 R0S05 - SPARE S012-25 - - - - - - - - -
DI-428 I30.5 31 R0S13 I30.5 R0S05 - SPARE S012-26 - - - - - - - - -
DI-430 I30.6 32 R0S13 I30.6 R0S05 - SPARE S012-27 - - - - - - - - -
DI-432 I30.7 33 R0S13 I30.7 R0S05 - SPARE S012-28 - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 189 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

UM2 UM2 34 R0S13 UM2 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -


UW2 UW2 35 R0S13 UW2 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
DI-434 I31.0 37 R0S13 I31.0 R0S05 R16 RING MAIN H03 (R16VB40)(TO R13) VCB OPENED S005-1 - 1001 1002 DB - DISCONNECT OPEN - - -
DI-436 I31.1 38 R0S13 I31.1 R0S05 R16 RING MAIN H03 (R16VB40)(TO R13) VCB CLOSED S005-2 - 1001 1003 DB - - - CLOSED ERROR -
DI-438 I31.2 39 R0S13 I31.2 R0S05 R16 RING MAIN H04 (R16VB41)(TO R15) VCB OPENED S005-11 - 1016 1017 DB - DISCONNECT OPEN - - -
DI-440 I31.3 40 R0S13 I31.3 R0S05 R16 RING MAIN H04 (R16VB41)(TO R15) VCB CLOSED S005-12 - 1016 1018 DB - - - CLOSED ERROR -
DI-442 I31.4 41 R0S13 I31.4 R0S05 R16 RING MAIN H05 (R16VB42)(TO R14) VCB OPENED S005-21 - 1031 1032 DB - DISCONNECT OPEN - - -
DI-444 I31.5 42 R0S13 I31.5 R0S05 R16 RING MAIN H05 (R16VB42)(TO R14) VCB CLOSED S005-22 - 1031 1033 DB - - - CLOSED ERROR -
DI-446 I31.6 43 R0S13 I31.6 R0S05 R16 RECTIFIER FEEDER H01 (R16VB50) VCB OPENED S005-31 - 1047 1048 DB - DISCONNECT OPEN - - -
DI-448 I31.7 44 R0S13 I31.7 R0S05 R16 RECTIFIER FEEDER H01 (R16VB50) VCB CLOSED S005-32 - 1047 1049 DB - - - CLOSED ERROR -
UM3 UM3 45 R0S13 UM3 R0S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S13 UW3 R0S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 ZS1 1 R0S14 ZS1 R0S06 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R0S14 ZS2 R0S06 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
DI-450 I32.0 4 R0S14 I32.0 R0S06 R16 RECTIFIER FEEDER H02 (R16VB51) VCB OPENED S006-21 - 2001 2002 DB - DISCONNECT OPEN - - -

DI-452 I32.1 5 R0S14 I32.1 R0S06 R16 RECTIFIER FEEDER H02 (R16VB51) VCB CLOSED S006-22 - 2001 2003 DB - - - CLOSED ERROR -

DI-454 I32.2 6 R0S14 I32.2 R0S06 R16 AUXILIARY TRANSFORMER H06 VCB OPENED S008-1 - 1086 1087 DB - DISCONNECT OPEN - - -
(R16VB60)
DI-456 I32.3 7 R0S14 I32.3 R0S06 R16 AUXILIARY TRANSFORMER H06 VCB CLOSED S008-2 - 1086 1088 DB - - - CLOSED ERROR -
(R16VB60)
DI-458 I32.4 8 R0S14 I32.4 R0S06 R16 RECTIFIER FEEDER D1 DCCB OPENED S008-15 - 2040 2041 DB - DISCONNECT OPEN - - -
DI-460 I32.5 9 R0S14 I32.5 R0S06 R16 RECTIFIER FEEDER D1 DCCB CLOSED S008-16 - 2040 2042 DB - - - CLOSED ERROR -
DI-462 I32.6 10 R0S14 I32.6 R0S06 R16 RECTIFIER FEEDER D2 DCCB OPENED S008-21 - 2049 2050 DB - DISCONNECT OPEN - - -
DI-464 I32.7 11 R0S14 I32.7 R0S06 R16 RECTIFIER FEEDER D2 DCCB CLOSED S008-22 - 2049 2051 DB - - - CLOSED ERROR -
UM0 UM0 12 R0S14 UM0 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) S012-9 - - - - - - - - - -
UW0 UW0 13 R0S14 UW0 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) S012-10 - - - - - - - - - -
DI-466 I33.0 15 R0S14 I33.0 R0S06 R16 RECTIFIER FEEDER D3 DCCB OPENED S008-25 - - - DB - DISCONNECT OPEN - - -
DI-468 I33.1 16 R0S14 I33.1 R0S06 R16 RECTIFIER FEEDER D3 DCCB CLOSED S008-26 - - - DB - - - CLOSED ERROR -
DI-470 I33.2 17 R0S14 I33.2 R0S06 R16 TRACK FEEDER D33 DCCB OPENED S008-31 - 2060 2061 DB - DISCONNECT OPEN - - -
DI-472 I33.3 18 R0S14 I33.3 R0S06 R16 TRACK FEEDER D33 DCCB CLOSED S008-32 - 2060 2062 DB - - - CLOSED ERROR -
DI-474 I33.4 19 R0S14 I33.4 R0S06 R16 TRACK FEEDER D34 DCCB OPENED S009-5 - 2075 2076 DB - DISCONNECT OPEN - - -
DI-476 I33.5 20 R0S14 I33.5 R0S06 R16 TRACK FEEDER D34 DCCB CLOSED S009-6 - 2075 2077 DB - - - CLOSED ERROR -
DI-478 I33.6 21 R0S14 I33.6 R0S06 R16 TRACK FEEDER D35 DCCB OPENED S009-21 - 2090 2091 DB - DISCONNECT OPEN - - -
DI-480 I33.7 22 R0S14 I33.7 R0S06 R16 TRACK FEEDER D35 DCCB CLOSED S009-22 - 2090 2092 DB - - - CLOSED ERROR -
UM1 UM1 23 R0S14 UM1 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) S012-19 - - - - - - - - - -
UW1 UW1 24 R0S14 UW1 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) S012-20 - - - - - - - - - -
DI-482 I34.0 26 R0S14 I34.0 R0S06 R16 TRACK FEEDER D36 DCCB OPENED S009-35 - 3001 3002 DB - DISCONNECT OPEN - - -
DI-484 I34.1 27 R0S14 I34.1 R0S06 R16 TRACK FEEDER D36 DCCB CLOSED S009-36 - 3001 3003 DB - - - CLOSED ERROR -
DI-486 I34.2 28 R0S14 I34.2 R0S06 R16 TRACK FEEDER (SPARE 1) DCCB OPENED S010-11 - 3016 3017 DB - DISCONNECT OPEN - - -
DI-488 I34.3 29 R0S14 I34.3 R0S06 R16 TRACK FEEDER (SPARE 1) DCCB CLOSED S010-12 - 3016 3018 DB - - - CLOSED ERROR -
DI-490 I34.4 30 R0S14 I34.4 R0S06 R16 TRACK FEEDER (SPARE 2) DCCB OPENED S010-25 - 3031 3032 DB - DISCONNECT OPEN - - -
DI-492 I34.5 31 R0S14 I34.5 R0S06 R16 TRACK FEEDER (SPARE 2) DCCB CLOSED S010-26 - 3031 3033 DB - - - CLOSED ERROR -
DI-494 I34.6 32 R0S14 I34.6 R0S06 R16 DC COMMON EQUIPMENT (OVPD) CONTACTOR OPENED S011-1 - 3049 3050 DB - DISCONNECT OPEN - - -
DI-496 I34.7 33 R0S14 I34.7 R0S06 R16 DC COMMON EQUIPMENT (OVPD) CONTACTOR CLOSED S011-2 - 3047 3048 DB - - - CLOSED ERROR -
UM2 UM2 34 R0S14 UM2 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) S012-29 - - - - - - - - - -
UW2 UW2 35 R0S14 UW2 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) S012-30 - - - - - - - - - -
DI-498 I35.0 37 R0S14 I35.0 R0S06 R16 DUMMY CB VCB OPENED internal - - - DB - DISCONNECT OPEN - - -
wiring
DI-500 I35.1 38 R0S14 I35.1 R0S06 R16 DUMMY CB VCB CLOSED internal - - - DB - - - CLOSED ERROR -
wiring
DI-502 I35.2 39 R0S14 I35.2 R0S06 - SPARE S012-33 - - - - - - - - -
DI-504 I35.3 40 R0S14 I35.3 R0S06 - SPARE S012-34 - - - - - - - - -
DI-506 I35.4 41 R0S14 I35.4 R0S06 - SPARE S012-35 - - - - - - - - -
DI-508 I35.5 42 R0S14 I35.5 R0S06 - SPARE S012-36 - - - - - - - - -
DI-510 I35.6 43 R0S14 I35.6 R0S06 - SPARE S012-37 - - - - - - - - -
DI-512 I35.7 44 R0S14 I35.7 R0S06 - SPARE S012-38 - - - - - - - - -
UM3 UM3 45 R0S14 UM3 R0S06 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 UW3 46 R0S14 UW3 R0S06 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
ZS1 R1S05 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 R1S05 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
I36.0 R1S05 - SPARE - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 190 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

I36.1 R1S05 - SPARE - - - - - - - - - -


I36.2 R1S05 - SPARE - - - - - - - - - -
I36.3 R1S05 - SPARE - - - - - - - - - -
I36.4 R1S05 - SPARE - - - - - - - - - -
I36.5 R1S05 - SPARE - - - - - - - - - -
I36.6 R1S05 - SPARE - - - - - - - - - -
I36.7 R1S05 - SPARE - - - - - - - - - -
UM0 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW0 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
I37.0 R1S05 - SPARE - - - - - - - - - -
I37.1 R1S05 - SPARE - - - - - - - - - -
I37.2 R1S05 - SPARE - - - - - - - - - -
I37.3 R1S05 - SPARE - - - - - - - - - -
I37.4 R1S05 - SPARE - - - - - - - - - -
I37.5 R1S05 - SPARE - - - - - - - - - -
I37.6 R1S05 - SPARE - - - - - - - - - -
I37.7 R1S05 - SPARE - - - - - - - - - -
UM1 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW1 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
I38.0 R1S05 - SPARE - - - - - - - - - -
I38.1 R1S05 - SPARE - - - - - - - - - -
I38.2 R1S05 - SPARE - - - - - - - - - -
I38.3 R1S05 - SPARE - - - - - - - - - -
I38.4 R1S05 - SPARE - - - - - - - - - -
I38.5 R1S05 - SPARE - - - - - - - - - -
I38.6 R1S05 - SPARE - - - - - - - - - -
I38.7 R1S05 - SPARE - - - - - - - - - -
UM2 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW2 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -
I39.0 R1S05 - SPARE - - - - - - - - - -
I39.1 R1S05 - SPARE - - - - - - - - - -
I39.2 R1S05 - SPARE - - - - - - - - - -
I39.3 R1S05 - SPARE - - - - - - - - - -
I39.4 R1S05 - SPARE - - - - - - - - - -
I39.5 R1S05 - SPARE - - - - - - - - - -
I39.6 R1S05 - SPARE - - - - - - - - - -
I39.7 R1S05 - SPARE - - - - - - - - - -
UM3 R1S05 - +24V DC SUPPLY (REFERENCE VOLTAGE) - - - - - - - - - - -
UW3 R1S05 - 0V DC SUPPLY (COMMON POTENTIAL) - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 191 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

ZS1 ZS1 1 R1S03 ZS1 R1S02 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - -


ZS2 ZS2 2 R1S03 ZS2 R1S02 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - - -
TB2-1 (+) IW.256 4 R1S03 IW.256 1 R3S02 R16 RING MAIN H03 (R16VB40)(TO R13) CURRENT S014-1 - 6001 - AI - - - - - 4 to
TB2-1 (-) IW.256 5 R1S03 IW.256 21 R3S02 - - S014-2 - - 6002 - - - - - - to
TB2-2 (+) IW.258 6 R1S03 IW.258 2 R3S02 R16 RING MAIN H04 (R16VB41)(TO R15) CURRENT S014-3 - 6003 - AI - - - - - 4 to
TB2-2 (-) IW.258 7 R1S03 IW.258 22 R3S02 - - S014-4 - - 6004 - - - - - - to
TB2-3 (+) IW.260 8 R1S03 IW.260 3 R3S02 R16 RING MAIN H05 (R16VB42)(TO R14) CURRENT S014-5 - 6005 - AI - - - - - 4 to
TB2-3 (-) IW.260 9 R1S03 IW.260 23 R3S02 - - S014-6 - - 6006 - - - - - - to
TB2-4 (+) IW.262 10 R1S03 IW.262 4 R3S02 R16 RECTIFIER FEEDER H01 (R16VB50) CURRENT S014-7 - 6007 - AI - - - - - 4 to
TB2-4 (-) IW.262 11 R1S03 IW.262 24 R3S02 - - S014-8 - - 6008 - - - - - - to
TB2-5 (+) IW.264 15 R1S03 IW.264 5 R3S02 R16 RECTIFIER FEEDER H02 (R16VB51) CURRENT S014-9 - 6009 - AI - - - - - 4 to
TB2-5 (-) IW.264 16 R1S03 IW.264 25 R3S02 - - S014-10 - - 6010 - - - - - - to
TB2-6 (+) IW.266 17 R1S03 IW.266 6 R3S02 R16 AUXILIARY TRANSFORMER H06 (R16VB60) CURRENT S014-11 - 6011 - AI - - - - - 4 to
TB2-6 (-) IW.266 18 R1S03 IW.266 26 R3S02 - - S014-12 - - 6012 - - - - - - to
TB2-7 (+) IW.268 19 R1S03 IW.268 7 R3S02 R16 AC BUSBAR VOLTAGE S014-13 - 6041 - AI - - - - - 4 to
TB2-7 (-) IW.268 20 R1S03 IW.268 27 R3S02 - - S014-14 - - 6042 - - - - - - to
TB2-8 (+) IW.270 21 R1S03 IW.270 8 R3S02 R16 TRACK FEEDER D33 DC CURRENT S014-15 - 6017 - AI - - - - - -20 to
TB2-8 (-) IW.270 22 R1S03 IW.270 28 R3S02 - - S014-16 - - 6018 - - - - - - to
TB2-9 (+) IW.272 26 R1S03 IW.272 9 R3S02 R16 TRACK FEEDER D34 DC CURRENT S014-17 - 6019 - AI - - - - - -20 to
TB2-9 (-) IW.272 27 R1S03 IW.272 29 R3S02 - - S014-18 - - 6020 - - - - - - to
TB2-10 (+) IW.274 28 R1S03 IW.274 10 R3S02 R16 TRACK FEEDER D35 DC CURRENT S014-19 - 6021 - AI - - - - - -20 to
TB2-10 (-) IW.274 29 R1S03 IW.274 30 R3S02 - - S014-20 - - 6022 - - - - - - to
TB2-11 (+) IW.276 30 R1S03 IW.276 11 R3S02 R16 TRACK FEEDER D36 DC CURRENT S014-21 - 6023 - AI - - - - - -20 to
TB2-11 (-) IW.276 31 R1S03 IW.276 31 R3S02 - - S014-22 - - 6024 - - - - - - to
TB2-12 (+) IW.278 32 R1S03 IW.278 12 R3S02 R16 TRACK FEEDER (SPARE 1) DC CURRENT S014-23 - 6025 - AI - - - - - -20 to
TB2-12 (-) IW.278 33 R1S03 IW.278 32 R3S02 - - S014-24 - - 6026 - - - - - - to
TB2-13 (+) IW.280 37 R1S03 IW.280 13 R3S02 R16 TRACK FEEDER (SPARE 2) DC CURRENT S014-25 - 6027 - AI - - - - - -20 to
TB2-13 (-) IW.280 38 R1S03 IW.280 33 R3S02 - - S014-26 - - 6028 - - - - - - to
TB2-14 (+) IW.282 39 R1S03 IW.282 14 R3S02 R16 RECTIFIER 1 DC CURRENT S014-27 - 6029 - AI - - - - - 4 to
TB2-14 (-) IW.282 40 R1S03 IW.282 34 R3S02 - - S014-28 - - 6030 - - - - - - to
TB2-15 (+) IW.284 41 R1S03 IW.284 15 R3S02 R16 RECTIFIER 1 DC VOLTAGE S014-29 - 6031 - AI - - - - - 4 to
TB2-15 (-) IW.284 42 R1S03 IW.284 35 R3S02 - - S014-30 - - 6032 - - - - - - to
TB2-16 (+) IW.286 43 R1S03 IW.286 16 R3S02 R16 RECTIFIER 2 DC CURRENT S014-31 - 6033 - AI - - - - - 4 to
TB2-16 (-) IW.286 44 R1S03 IW.286 36 R3S02 - - S014-32 - - 6034 - - - - - - to
ZS1 ZS1 1 R1S04 ZS1 R1S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R1S04 ZS2 R1S03 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
TB2-17 (+) IW.288 4 R1S04 IW.288 1 R3S03 R16 RECTIFIER 2 DC VOLTAGE S014-33 - 6035 - AI - - - - - 4 to
TB2-17 (+) IW.288 5 R1S04 IW.288 21 R3S03 - - S014-34 - - 6036 - - - - - - to
TB2-18 (+) IW.290 6 R1S04 IW.290 2 R3S03 R16 DC BUSBAR DC VOLTAGE S014-35 - 6037 - AI - - - - - 4 to
TB2-18 (-) IW.290 7 R1S04 IW.290 22 R3S03 - - S014-36 - - 6038 - - - - - - to
TB2-19 (+) IW.292 8 R1S04 IW.292 3 R3S03 R16 NEGATIVE BUSBAR DC RETURN CURRENT S014-37 - 6043 - AI - - - - - 4 to
TB2-19 (-) IW.292 9 R1S04 IW.292 23 R3S03 - - S014-38 - - 6044 - - - - - - to
TB2-20 (+) IW.294 10 R1S04 IW.294 4 R3S03 R16 MVAC SYSTEM INDOOR TEMP 1 S014-39 - 6075 - AI - - - - - 0 to
TB2-20 (-) IW.294 11 R1S04 IW.294 24 R3S03 - - S014-40 - - 6076 - - - - - - to
TB2-21 (+) IW.296 15 R1S04 IW.296 5 R3S03 R16 MVAC SYSTEM INDOOR TEMP 2 S014-41 - 6077 - AI - - - - - 0 to
TB2-21 (-) IW.296 16 R1S04 IW.296 25 R3S03 - - S014-42 - - 6078 - - - - - - to
TB2-22 (+) IW.298 17 R1S04 IW.298 6 R3S03 R16 MVAC SYSTEM INDOOR TEMP 3 S014-43 - 6079 - AI - - - - - 0 to
TB2-22 (-) IW.298 18 R1S04 IW.298 26 R3S03 - - S014-44 - - 6080 - - - - - - to
TB2-23 (+) IW.300 19 R1S04 IW.300 7 R3S03 R16 MVAC SYSTEM INDOOR TEMP 4 S014-45 - 6081 - AI - - - - - 0 to
TB2-23 (-) IW.300 20 R1S04 IW.300 27 R3S03 - - S014-46 - - 6082 - - - - - - to
TB2-24 (+) IW.302 21 R1S04 IW.302 8 R3S03 R16 MVAC SYSTEM INDOOR TEMP 5 S014-47 - 6083 - AI - - - - - 0 to
TB2-24 (-) IW.302 22 R1S04 IW.302 28 R3S03 - - S014-48 - - 6084 - - - - - - to
TB2-25 (+) IW.304 26 R1S04 IW.304 9 R3S03 R16 380V NETWORK LB01 MAIN ACB (1200A) CURRENT S014-49 - 6085 - AI - - - - - 4 to
TB2-25 (-) IW.304 27 R1S04 IW.304 29 R3S03 - - S014-50 - - 6086 - - - - - - to
TB2-26 (+) IW.306 28 R1S04 IW.306 10 R3S03 R16 380V NETWORK LB01 MAIN ACB (1200A) VOLTAGE S014-51 - 6087 - AI - - - - - 4 to
TB2-26 (-) IW.306 29 R1S04 IW.306 30 R3S03 - - S014-52 - - 6088 - - - - - - to
TB2-27 (+) IW.308 30 R1S04 IW.308 11 R3S03 R16 380V NETWORK LB21 - TO S550 500A MCCB NO.1 CURRENT S014-53 - 6089 - AI - - - - - 4 to
TB2-27 (-) IW.308 31 R1S04 IW.308 31 R3S03 - - S014-54 - - 6090 - - - - - - to
TB2-28 (+) IW.310 32 R1S04 IW.310 12 R3S03 R16 380V NETWORK LB22 - TO S540 500A MCCB NO.2 CURRENT S014-55 - 6091 - AI - - - - - 4 to
TB2-28 (-) IW.310 33 R1S04 IW.310 32 R3S03 - - S014-56 - - 6092 - - - - - - to
TB2-29 (+) IW.312 37 R1S04 IW.312 13 R3S03 R16 380V NETWORK LB12 STANDBY SOURCE (300A) CURRENT S014-57 - 6093 - AI - - - - - 4 to
TB2-29 (-) IW.312 38 R1S04 IW.312 33 R3S03 - - S014-58 - - 6094 - - - - - - to
TB2-30 (+) IW.314 39 R1S04 IW.314 14 R3S03 R16 380V NETWORK LB12 STANDBY SOURCE VOLTAGE S014-59 - 6095 - AI - - - - - 4 to
TB2-30 (-) IW.314 40 R1S04 IW.314 34 R3S03 - - S014-60 - - 6096 - - - - - - to

Unrestricted 749775924.xlsx/RS16 [RS16] 192 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

TB2-31 (+) IW.316 41 R1S04 IW.316 15 R3S03 - SPARE S014-61 - - - - - - - - - to


TB2-31 (-) IW.316 42 R1S04 IW.316 35 R3S03 - - S014-62 - - - - - - - - - to
TB2-32 (+) IW.318 43 R1S04 IW.318 16 R3S03 - SPARE S014-63 - - - - - - - - - to
TB2-32 (-) IW.318 44 R1S04 IW.318 36 R3S03 - - S014-64 - - - - - - - - - to
S110-RD - - R1S04 - R1S03 - - - - - - - - - - - - -
S110-BK - - R1S04 - R1S03 - - - - - - - - - - - - -
S112-BL - - R1S04 - R1S03 - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 193 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-A - - R1S04 - R1S03 - - - - - - - - - - - - -


ZS1 ZS1 R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 R1S04 - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
TB2-1 (+) IW.320 1 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-1 (-) IW.320 21 R3S04 - - - - - - - - - - - - to
TB2-2 (+) IW.322 2 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-2 (-) IW.322 22 R3S04 - - - - - - - - - - - - to
TB2-3 (+) IW.324 3 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-3 (-) IW.324 23 R3S04 - - - - - - - - - - - - to
TB2-4 (+) IW.326 4 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-4 (-) IW.326 24 R3S04 - - - - - - - - - - - - to
TB2-5 (+) IW.328 5 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-5 (-) IW.328 25 R3S04 - - - - - - - - - - - - to
TB2-6 (+) IW.330 6 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-6 (-) IW.330 26 R3S04 - - - - - - - - - - - - to
TB2-7 (+) IW.332 7 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-7 (-) IW.332 27 R3S04 - - - - - - - - - - - - to
TB2-8 (+) IW.334 8 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-8 (-) IW.334 28 R3S04 - - - - - - - - - - - - to
TB2-9 (+) IW.336 9 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-9 (-) IW.336 29 R3S04 - - - - - - - - - - - - to
TB2-10 (+) IW.338 10 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-10 (-) IW.338 30 R3S04 - - - - - - - - - - - - to
TB2-11 (+) IW.340 11 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-11 (-) IW.340 31 R3S04 - - - - - - - - - - - - to
TB2-12 (+) IW.342 12 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-12 (-) IW.342 32 R3S04 - - - - - - - - - - - - to
TB2-13 (+) IW.344 13 R3S04 - SPARE - - - - AI - - - - - -20 to
TB2-13 (-) IW.344 33 R3S04 - - - - - - - - - - - - to
TB2-14 (+) IW.346 14 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-14 (-) IW.346 34 R3S04 - - - - - - - - - - - - to
TB2-15 (+) IW.348 15 R3S04 - SPARE - - - - AI - - - - - 0 to
TB2-15 (-) IW.348 35 R3S04 - - - - - - - - - - - - to
TB2-16 (+) IW.350 16 R3S04 - SPARE - - - - - - - - - - to
TB2-16 (-) IW.350 36 R3S04 - - - - - - - - - - - - to
ZS1 ZS1 1 R1S01 ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R1S01 ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
RL-01 Q4.0 4 R1S01 Q4.0 2 R2S02 R16 RING MAIN H03 (R16VB40)(TO R13) VCB OPEN S015-1 - 4001 4002 CO - - - - - -
RL-02 Q4.1 5 R1S01 Q4.1 3 R2S02 R16 RING MAIN H03 (R16VB40)(TO R13) VCB CLOSE S015-2 - 4001 4003 CO - - - - - -
RL-03 Q4.2 6 R1S01 Q4.2 6 R2S02 R16 RING MAIN H04 (R16VB41)(TO R15) VCB OPEN S015-3 - 4004 4005 CO - - - - - -
RL-04 Q4.3 7 R1S01 Q4.3 7 R2S02 R16 RING MAIN H04 (R16VB41)(TO R15) VCB CLOSE S015-4 - 4004 4006 CO - - - - - -
RL-05 Q4.4 8 R1S01 Q4.4 12 R2S02 R16 RING MAIN H05 (R16VB42)(TO R14) VCB OPEN S015-5 - 4007 4008 CO - - - - - -
RL-06 Q4.5 9 R1S01 Q4.5 13 R2S02 R16 RING MAIN H05 (R16VB42)(TO R14) VCB CLOSE S015-6 - 4007 4009 CO - - - - - -
RL-07 Q4.6 10 R1S01 Q4.6 16 R2S02 R16 RECTIFIER FEEDER H01 (R16VB50) VCB OPEN S015-7 - 4010 4011 CO - - - - - -
RL-08 Q4.7 11 R1S01 Q4.7 17 R2S02 R16 RECTIFIER FEEDER H01 (R16VB50) VCB CLOSE S015-8 - 4010 4012 CO - - - - - -
L+ 19 R2S02
M 20 R2S02
RL-09 Q5.0 15 R1S01 Q5.0 22 R2S02 R16 RECTIFIER FEEDER H02 (R16VB51) VCB OPEN S015-9 - 4013 4014 CO - - - - - -
RL-10 Q5.1 16 R1S01 Q5.1 23 R2S02 R16 RECTIFIER FEEDER H02 (R16VB51) VCB CLOSE S015-10 - 4013 4015 CO - - - - - -
RL-11 Q5.2 17 R1S01 Q5.2 26 R2S02 - SPARE S015-11 - - - - - - - - -
RL-12 Q5.3 18 R1S01 Q5.3 27 R2S02 - SPARE S015-12 - - - - - - - - -
RL-13 Q5.4 19 R1S01 Q5.4 32 R2S02 R16 RECTIFIER FEEDER D1 DCCB OPEN S015-13 - 4101 4103 CO - - - - - -
RL-14 Q5.5 20 R1S01 Q5.5 33 R2S02 R16 RECTIFIER FEEDER D1 DCCB CLOSE S015-14 - 4101 4102 CO - - - - - -
RL-15 Q5.6 21 R1S01 Q5.6 36 R2S02 R16 RECTIFIER FEEDER D2 DCCB OPEN S015-15 - 4104 4106 CO - - - - - -
RL-16 Q5.7 22 R1S01 Q5.7 37 R2S02 R16 RECTIFIER FEEDER D2 DCCB CLOSE S015-16 - 4104 4105 CO - - - - - -
L+ 39
M 40
RL-17 Q6.0 26 R1S01 Q6.0 2 R2S03 - SPARE S015-17 - - - - - - - - -
RL-18 Q6.1 27 R1S01 Q6.1 3 R2S03 - SPARE S015-18 - - - - - - - - -
RL-19 Q6.2 28 R1S01 Q6.2 6 R2S03 R16 TRACK FEEDER D33 DCCB OPEN S015-19 - 4071 4074 CO - - - - - -
RL-20 Q6.3 29 R1S01 Q6.3 7 R2S03 R16 TRACK FEEDER D33 DCCB CLOSE S015-20 - 4071 4073 CO - - - - - -
RL-21 Q6.4 30 R1S01 Q6.4 12 R2S03 R16 TRACK FEEDER D33 LINE TEST CONTROL ON S015-21 - 4071 4063 CO - - - - - -
RL-22 Q6.5 31 R1S01 Q6.5 13 R2S03 R16 TRACK FEEDER D33 LINE TEST CONTROL OFF S015-22 4071 4072 CO
RL-23 Q6.6 32 R1S01 Q6.6 16 R2S03 R16 TRACK FEEDER D34 DCCB OPEN S015-23 - 4076 4079 CO - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 194 Printed on: 04/30/2024


LIGHT RAIL TELECOMMUNICATION -SCADA SYSTEM
SCADA RTU/MARSHALLING BOXES POINT SCHEDULE - Rectifier Station RS01
Drawn by: Dicky Li
Contract No.: K1005-20E Designed by: Jeco Chan Revision Date
Document No.: XXXX Checked by: Chris Leung A 2022/12/01
Approved by: Simon Chiu

PHYSICAL INTERFACE (TERMINATION TABLE)

New RTU New RTU (Internal S7-400 S7-1500 RTU S7-1500 Description of Primary Equipment (Description Point Name (Description Line 2) Existing / New Marshalling Box Point Logical State 0 State 1 State 2 State 3 Transducer Output
Wiring at RTU Module (Internal Wiring at Module Line 1) Type Name (SB or DB) (SB or DB) (DB only) (DB only) Range (mA)
Terminal No. Modules Modules
Modules) Modules Modules
RTU Modules) Core No. KSK Terminal Terminal (00) (01) (10) (11) to
Terminal Pin No. Terminal Pin No. (+ve) (-ve)
No. No.

RL-24 Q6.7 33 R1S01 Q6.7 17 R2S03 R16 TRACK FEEDER D34 DCCB CLOSE S015-24 - 4076 4078 CO - - - - - -
L+ 19 R2S03
M 20 R2S03
RL-25 Q7.0 37 R1S01 Q7.0 22 R2S03 R16 TRACK FEEDER D34 LINE TEST CONTROL ON S015-25 - 4076 4064 CO - - - - - -
RL-26 Q7.1 38 R1S01 Q7.1 23 R2S03 R16 TRACK FEEDER D34 LINE TEST CONTROL OFF S015-26 4076 4077 CO
RL-27 Q7.2 39 R1S01 Q7.2 26 R2S03 R16 TRACK FEEDER D35 DCCB OPEN S015-27 - 4081 4084 CO - - - - - -
RL-28 Q7.3 40 R1S01 Q7.3 27 R2S03 R16 TRACK FEEDER D35 DCCB CLOSE S015-28 - 4081 4083 CO - - - - - -
RL-29 Q7.4 41 R1S01 Q7.4 32 R2S03 R16 TRACK FEEDER D35 LINE TEST CONTROL ON S015-29 - 4081 4065 CO - - - - - -
RL-30 Q7.5 42 R1S01 Q7.5 33 R2S03 R16 TRACK FEEDER D35 LINE TEST CONTROL OFF S015-30 4081 4082 CO
RL-31 Q7.6 43 R1S01 Q7.6 36 R2S03 - SPARE S015-31 - - - - - - - - -
RL-32 Q7.7 44 R1S01 Q7.7 37 R2S03 - SPARE S015-32 - - - - - - - - -
L+ 39 R2S03
M 40 R2S03
FR0 FR0 34 R1S01 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - -
ENABLE CONTACTONANDTHECOMMON
32 CO RETURN LINE
FR1 FR1 35 R1S01 FR1 - - - - - - - - - - - - - -
ON THE 32 COVOLTAGE INPUT)
UE0 UE0 45 UE0 31 - - +110V DC SUPPLY (COMMAND - - - - - - - - - - -
UE1 UE1 46 UE1 35 - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - -
ZS1 ZS1 1 R1S02 ZS1 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
ZS2 ZS2 2 R1S02 ZS2 - - - CONNECTOR MONITORING (PULL LOOP) - - - - - - - - - - -
RL-33 Q8.0 4 R1S02 Q8.0 2 R2S04 R16 TRACK FEEDER D36 DCCB OPEN S016-1 - 4086 4089 CO - - - - - -
RL-34 Q8.1 5 R1S02 Q8.1 3 R2S04 R16 TRACK FEEDER D36 DCCB CLOSE S016-2 - 4086 4088 CO - - - - - -
RL-35 Q8.2 6 R1S02 Q8.2 6 R2S04 R16 TRACK FEEDER D36 LINE TEST CONTROL ON S016-3 - 4086 4066 CO - - - - - -
RL-36 Q8.3 7 R1S02 Q8.3 7 R2S04 R16 TRACK FEEDER D36 LINE TEST CONTROL OFF S016-4 4086 4087 CO
RL-37 Q8.4 8 R1S02 Q8.4 12 R2S04 R16 TRACK FEEDER (SPARE 1) DCCB OPEN S016-5 - 4091 4094 CO - - - - - -
RL-38 Q8.5 9 R1S02 Q8.5 13 R2S04 R16 TRACK FEEDER (SPARE 1) DCCB CLOSE S016-6 - 4091 4093 CO - - - - - -
RL-39 Q8.6 10 R1S02 Q8.6 16 R2S04 R16 TRACK FEEDER (SPARE 1) LINE TEST CONTROL ON S016-7 - 4091 4067 CO - - - - - -
RL-40 Q8.7 11 R1S02 Q8.7 17 R2S04 R16 TRACK FEEDER (SPARE 1) LINE TEST CONTROL OFF S016-8 - 4091 4092 CO
L+ 19 R2S04
M 20 R2S04
RL-41 Q9.0 15 R1S02 Q9.0 22 R2S04 R16 TRACK FEEDER (SPARE 2) DCCB OPEN S016-9 - 4096 4099 CO - - - - - -
RL-42 Q9.1 16 R1S02 Q9.1 23 R2S04 R16 TRACK FEEDER (SPARE 2) DCCB CLOSE S016-10 - 4096 4098 CO - - - - - -
RL-43 Q9.2 17 R1S02 Q9.2 26 R2S04 R16 TRACK FEEDER (SPARE 2) LINE TEST CONTROL ON S017-17 - 4096 4068 CO - - - - - -
RL-44 Q9.3 18 R1S02 Q9.3 27 R2S04 R16 TRACK FEEDER (SPARE 2) LINE TEST CONTROL OFF S017-18 - 4096 4097 CO
RL-45 Q9.4 19 R1S02 Q9.4 32 R2S04 R16 AUXILIARY TRANSFORMER H06 VCB OPEN S016-13 - 4016 4017 CO - - - - - -
RL-46 Q9.5 20 R1S02 Q9.5 33 R2S04 (R16VB60)
R16 AUXILIARY TRANSFORMER H06 VCB CLOSE S016-14 - 4016 4018 CO - - - - - -
RL-47 Q9.6 21 R1S02 Q9.6 36 R2S04 (R16VB60)
R16 DC COMMON EQUIPMENT (OVPD) CONTACTOR RESET S016-15 - 4039 4040 CO - - - - - -
RL-48 Q9.7 22 R1S02 Q9.7 37 R2S04 R16 DC COMMON EQUIPMENT (OVPD) CONTACTOR CLOSE S016-16 - 4041 4042 CO - - - - - -
L+ 39 R2S04
M 40 R2S04
RL-49 Q10.0 26 R1S02 Q10.0 2 R2S05 R16 DUMMY CB VCB OPEN/CLOSE (MOST SIGINIFICANT internal - - - CO - - - - - -
RL-50 Q10.1 27 R1S02 Q10.1 3 R2S05 R16 DUMMY CB BIT)
VCB OPEN/CLOSE (LEAST SIGINIFICANT wiring
internal - - - CO - - - - - -
RL-51 Q10.2 28 R1S02 Q10.2 6 R2S05 - BIT) SPARE wiring
S016-19 - - - - - - - - -
RL-52 Q10.3 29 R1S02 Q10.3 7 R2S05 - SPARE S016-20 - - - - - - - - -
RL-53 Q10.4 30 R1S02 Q10.4 12 R2S05 - SPARE S016-21 - - - - - - - - -
RL-54 Q10.5 31 R1S02 Q10.5 13 R2S05 - SPARE S016-22 - - - - - - - - -
RL-55 Q10.6 32 R1S02 Q10.6 16 R2S05 - SPARE S016-23 - - - - - - - - -
RL-56 Q10.7 33 R1S02 Q10.7 17 R2S05 - SPARE S016-24 - - - - - - - - -
L+ 19 R2S05
M 20 R2S05
RL-57 Q11.0 37 R1S02 Q11.0 22 R2S05 - SPARE S016-25 - - - - - - - - -
RL-58 Q11.1 38 R1S02 Q11.1 23 R2S05 - SPARE S016-26 - - - - - - - - -
RL-59 Q11.2 39 R1S02 Q11.2 26 R2S05 - SPARE S016-27 - - - - - - - - -
RL-60 Q11.3 40 R1S02 Q11.3 27 R2S05 - SPARE S016-28 - - - - - - - - -
RL-61 Q11.4 41 R1S02 Q11.4 32 R2S05 - SPARE S016-29 - - - - - - - - -
RL-62 Q11.5 42 R1S02 Q11.5 33 R2S05 - SPARE S016-30 - - - - - - - - -
RL-63 Q11.6 43 R1S02 Q11.6 36 R2S05 - SPARE S016-31 - - - - - - - - -
RL-64 Q11.7 44 R1S02 Q11.7 37 R2S05 - SPARE S016-32 - - - - - - - - -
L+ 39 R2S05
M 40 R2S05
FR0 FR0 34 R1S02 FR0 - - - ENABLE CONTACT AND COMMON RETURN LINE - - - - - - - - - - -
ENABLE CONTACTONANDTHECOMMON
32 CO RETURN LINE
FR1 FR1 35 R1S02 FR1 - - - - - - - - - - - - - -
ON THE 32 COVOLTAGE INPUT)
UE0 UE0 45 R1S02 UE0 31 - - +110V DC SUPPLY (COMMAND - - - - - - - - - - -
UE1 UE1 46 R1S02 UE1 35 - - +110 DC SUPPLY (COMMAND VOLTAGE INPUT) - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 195 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS16 [RS16] 196 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS16 [RS16] 197 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS16 [RS16] 198 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 199 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC NC - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -

Unrestricted 749775924.xlsx/RS16 [RS16] 200 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 201 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - YES 0 - - - - - - - - - C NC - -

- - YES 0 - - - - - - - - - - - NC C

- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - YES 0 - - - - - - - - - C NC - -
- - YES 0 - - - - - - - - - - - NC C
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - C NC - -

- - NO 0 - - - - - - - - - - - NC C

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -

Unrestricted 749775924.xlsx/RS16 [RS16] 202 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC NC - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - NO 0 - - - - - - - - - NC C - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 203 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - -
20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
20 0 to 400 A ac - - 1.0% - - 300 380 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 16.000 19.200 - - 285 361 - - 15.400 18.440
20 0 to 200 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 10.400 11.600 - - 76.000 90.250 - - 10.080 11.220
20 0 to 200 A ac - - 1.0% - - 80 95 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 10.400 11.600 - - 76 90.25 - - 10.080 11.220
20 0 to 100 A ac - - 1.0% - - 42 50 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 10.720 12.000 - - 39.9 47.5 - - 10.384 11.600
20 0 to 15 kV ac - - 1.0% 1.0 9.9 12.1 12.4 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 5.067 14.560 16.907 17.227 1.050 10.395 11.495 11.78 5.120 15.088 16.261 16.565
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 8.000 8.571 -2850.000 -2375.000 2520 2850 -8.143 -6.786 7.200 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 8.000 8.571 -2850 -2375 2520 2850 -8.143 -6.786 7.200 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 8.000 8.571 -2850.000 -2375.000 2520 2850 -8.143 -6.786 7.200 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2800 3000 5.00% 5.00% 10.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 8.000 8.571 -2850.000 -2375.000 2520 2850 -8.143 -6.786 7.200 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850.000 -2375.000 2375 2850 -8.143 -6.786 6.786 8.143
+20 -7000 to +7000 A dc - - 1.0% -3000 -2500 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - -8.571 -7.143 7.143 8.571 -2850 -2375 2375 2850 -8.143 -6.786 6.786 8.143
20 0 to 5000 A dc - - 1.0% - - 2500 3000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 12.000 13.600 - - 2375 2850 - - 11.600 13.120
20 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 19.200 19.680 - - 902.5 931 - - 18.440 18.896
20 0 to 5000 A dc - - 1.0% - - 2500 3000 0.05 0.05 0.05 0.05 C NC NC C
- - to - - - - - - - 12.000 13.600 - - 2375 2850 - - 11.600 13.120
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
20 0 to 1000 V dc - - 1.0% - - 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 19.200 19.680 - - 902.5 931 - - 18.440 18.896
20 0 to 1000 V dc - - 1.0% 415 530 950 980 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 10.640 12.480 19.200 19.680 435.750 556.500 902.5 931 10.972 12.904 18.440 18.896
20 0 to 4000 A dc - - 1.0% - - 3500 4000 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.000 20.000 - - 3325 3800 - - 17.300 19.200
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 10.500 15.750 26.600 30.400 4.200 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 10.5 15.75 26.6 30.4 4.200 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 10.500 15.750 26.6 30.4 4.200 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 10.500 15.750 26.6 30.4 4.200 6.300 10.640 12.160
20 0 to 50 deg - - 1.0% 10 15 28 32 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 4.000 6.000 11.200 12.800 10.500 15.750 26.6 30.4 4.200 6.300 10.640 12.160
20 0 to 1200 A ac - - 1.0% - - 1080 1200 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 1026 1140 - - 17.680 19.200
20 0 to 220 V ac - - 1.0% 198 209 - - 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 18.400 19.200 #VALUE! #VALUE! 188.100 219.450 #VALUE! #VALUE! 17.680 19.960 #VALUE! #VALUE!
20 0 to 500 A ac - - 1.0% - - 450 500 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 427.5 475 - - 17.680 19.200
20 0 to 500 A ac - - 1.0% - - 450 500 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 427.5 475 - - 17.680 19.200
20 0 to 300 A ac - - 1.0% - - 270 300 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - - - 18.400 20.000 - - 256.5 285 - - 17.680 19.200
20 0 to 220 V ac - - 1.0% 198 209 - - 5.00% 5.00% 5.00% 5.00% C NC NC C
- - to - - - - - 18.400 19.200 #VALUE! #VALUE! 188.100 219.450 #VALUE! #VALUE! 17.680 19.960 #VALUE! #VALUE!

Unrestricted 749775924.xlsx/RS16 [RS16] 204 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 205 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - - - -
+10 C NC NC C
- - - - -
+20 C NC NC C
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - to - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 206 Printed on: 04/30/2024


SCADA / RTU CONFIGURATION INFORMATION

Transducer Output Actual Range of Engineering SOE Change- Jitter Alarm Limit Deadband of Alarm Limit Alarm Priority
Range (mA) Values Of-State Value
to Units Time LL L H HH LL L H HH Alm 0 or Alm 1 or Alm 2 or Alm 3 or
Delay LL L H HH
(sec)
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -

Unrestricted 749775924.xlsx/RS16 [RS16] 207 Printed on: 04/30/2024