Structural Engineering Division: Subject
Structural Engineering Division: Subject
To,
RE (Reach-3)
MMP Peshawar
(Peshawar Sustainable Bus Rapid Transit Project Reach-III)
Pressure Gauge Reading (Psi) 1000 2000 3000 4000 5000 6000 7000
Calibrated Load (kg) 15000 28200 42000 56000 69200 84400 98000
Calibrated Pressure (Psi) 1077.50 2025.70 3017.00 4022.67 4970.87 6062.73 7039.67
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(inch)
(#)
(kg) (kg)
1 0.377 3 0.376 0.11 0.111 3800 4800 76200 75630 96200 95600 0.90 11.3
2 0.365 3 0.370 0.11 0.107 3800 4800 76200 78030 96200 98600 0.90 11.3
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Diameter/
Load
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.417 3/8 0.395 0.11 0.123 5300 6000 106200 95270 120300 107900 0.80 10.0
2 0.420 3/8` 0.396 0.11 0.123 5200 6000 104200 92910 120300 107200 0.80 10.0
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and two samples for bend test
Bend Test
3/8" Dia Bar Bend Test Through 180º is Satisfactory
3/8" Dia Bar Bend Test Through 180º is Satisfactory
To,
Resident Engineer
ACE (Pvt) Ltd
Construction of Administration Block & Appartment New Campus of GCU at KSK Campus –
Package-3
Reference # CED/TFL 29435 (Dr. Ali Ahmed) Dated: 12-01-2018
Reference of the request letter # RE/ACE Arts/GCU/ECC/188 Dated: 10-01-2018
Elongation
Yield load
Breaking
Weight
Diameter/
Load
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.434 3/8 0.403 0.11 0.128 4600 6000 92200 79510 120300 103800 0.90 11.3
2 0.427 3/8 0.400 0.11 0.126 4800 6200 96200 84240 124300 108900 1.00 12.5
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
3/8" Dia Bar Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.369 3/8 0.371 0.11 0.108 3100 4800 62200 63070 96200 97700 1.20 15.0
2 0.367 3/8 0.370 0.11 0.108 3100 4800 62200 63380 96200 98200 1.20 15.0
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile test
Bend Test
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.367 3/8 0.371 0.11 0.108 4000 5000 80200 81750 100200 102200 1.20 15.0
2 0.368 3/8 0.371 0.11 0.108 4000 4900 80200 81500 98200 99900 1.00 12.5
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
3/8" Dia Bar Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Diameter/
Load
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.370 3/8 0.372 0.11 0.109 3700 4900 74200 75020 98200 99400 1.10 13.8
2 0.402 3/8 0.388 0.11 0.118 3300 5200 66200 61590 104200 97100 0.90 11.3
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile test
Bend Test
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.371 3/8 0.373 0.11 0.109 3600 5500 72200 72770 110200 111200 1.10 13.8
2 0.372 3/8 0.373 0.11 0.109 4100 5500 82200 82720 110200 111000 1.00 12.5
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
3/8" Dia Bar Bend Test Through 180º is Satisfactory
Yield Stress
Designation
Elongation
Yield load
X Section
Breaking
Ultimate
% Elongation
Stress
Load
Area
Remarks
Sr. No.
- - - - - - - - - - -
- - - - - - - - - - -
- - - - - - - - - - -
- - - - - - - - - - -
Only Two Samples for Tensile and One Sample for Bend Test
Bend Test
Strip Taken from MS Pipe 16" Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(inch)
(#)
(kg) (kg)
1 0.369 3 0.372 0.11 0.108 3800 5000 76200 77220 100200 101600 0.90 11.3
2 0.367 3 0.370 0.11 0.108 4300 5300 86200 87950 106200 108400 0.90 11.3
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.378 3 0.376 0.11 0.111 3500 5400 70200 69340 108200 107000 1.10 13.8
2 0.368 3 0.371 0.11 0.108 3500 5200 70200 71410 104200 106100 1.10 13.8
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Load
Diameter/ Area Yield Stress Ultimate Stress
% Elongation
Size (in2) (psi) (psi)
Remarks
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(inch)
(#)
(kg) (kg)
1 0.368 3 0.371 0.11 0.108 4000 4600 80200 81420 92200 93700 1.00 12.5
2 0.374 3 0.374 0.11 0.110 4500 5200 90200 90330 104200 104400 1.00 12.5
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile test
Bend Test
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.415 10 10.01 0.11 0.122 3400 5200 68200 61440 104200 94000 1.30 16.3
2 0.412 10 9.98 0.11 0.121 3200 5000 64200 58190 100200 91000 1.40 17.5
3 0.399 10 9.81 0.11 0.117 3100 4900 62200 58320 98200 92200 1.20 15.0
4 0.402 10 9.85 0.11 0.118 3300 5300 66200 61600 106200 99000 1.20 15.0
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only four samples for tensile and two samples for bend test
Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory
10mm Dia Bar Bend Test Through 180º is Satisfactory
To
Project Engineer – Civil
Grid Solution Pakistan (Private) limited
Procurement of 220/132kV GIS Plant, Design, Supply, Installation, Testing &
Commissioning at Ghazi Road Lahore
cited above. Two R.C.C. Pipes as received by us have been tested. The results are
tabulated as under.
Proof load
Thickness
Ultimate
Diameter
Diameter
External
Ultimate
Nominal
Internal
Loaded
Length
Length
Stress
Stress
Proof
Total
Load
Wall
Size
Sr.
No
.
(mm) (m) (m) (mm) (mm) (mm) (Kg) (Kg) N/m/mm N/m/mm
1 225 2.371 2.270 280.00 224.52 27.74 7200 9400 138.59 180.93
2 300 2.375 2.222 405.00 310.66 47.17 12100 13500 171.96 191.86
Witness by Amjad Tufail (S.E NESPAK)
Elongation
Yield load
Breaking
Weight
Diameter/ Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
(inch)
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(kg) (kg)
1 0.390 3 0.382 0.11 0.114 3600 5900 72200 69300 118300 113600 0.75 9.4
2 0.395 3 0.385 0.11 0.116 3600 5900 72200 68260 118300 111900 1.10 13.8
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Diameter/
Load
Area Yield Stress Ultimate Stress
% Elongation
Size
(in2) (psi) (psi)
Remarks
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(inch)
(#)
(kg) (kg)
1 0.422 3 0.398 0.11 0.124 4900 6100 98200 87020 122300 108400 1.10 13.8
2 0.427 3 0.400 0.11 0.126 4900 6100 98200 85950 122300 107000 1.20 15.0
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
Elongation
Yield load
Breaking
Weight
Load
% Elongation
Size (in2) (psi) (psi)
Remarks
Sr. No.
Nominal
Nominal
Nominal
Nominal
(lbs/ft)
Actual
Actual
Actual
Actual
(inch)
(inch)
(#)
(kg) (kg)
1 0.383 3 0.378 0.11 0.112 2800 4200 56200 54870 84200 82400 1.00 12.5
2 0.385 3 0.380 0.11 0.113 2800 4300 56200 54520 86200 83800 1.40 17.5
3 4.285 10 1.266 1.27 1.260 26400 42000 45900 46200 72900 73500 2.10 26.3
4 4.283 10 1.266 1.27 1.259 27400 44600 47600 47980 77500 78100 2.00 25.0
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Note: only four samples for tensile and two samples for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
#10 Bar Bend Test Through 180º is Satisfactory