SMP Io Distributed Io Platform Catalog Ca912005en
SMP Io Distributed Io Platform Catalog Ca912005en
Contents
DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PRODUCT OVERVIEW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
BENEFITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PRODUCT CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . 3
I/O FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SMP I/O MANAGER SOFTWARE . . . . . . . . . . . . . . . . . . . . . . 4
SMP TOOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SMP I/O PLATFORM SPECIFICATIONS . . . . . . . . . . . . . . . . . . 6
TYPE TESTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TEMPERATURE DERATING . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DIMENSION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Technical Data CA912005EN SMP™I/O Distributed I/O Platform
Issue date October 2019
Software
• SMP I/O Manager Software for device management
• Seamless integration with the SMP Gateway
Figure 1. Typical application, deployed behind an SMP
Gateway automation platform Security
• Built-in firewall to limit connections to specific IP addressses
or subnetworks
System
• Error detection features to ensure data integrity
• Integrated watchdog timer
• Internal clock synchronization using IRIG-B
• Local/Remote control button for safe system maintenance
Protocols
• DNP3 Serial or TCP/IP links
Figure 2. Typical application, deployed as a stand alone unit • IEC 61850 GOOSE messaging
2 www.eaton.com/smartgrid
SMP™I/O Distributed I/O Platform Technical Data CA912005EN
Issue date October 2019
• Each relay output is monitored by an input point that SMP I/O Manager software
provides the state of a second auxiliary contact. If the
auxiliary contact does not match the requested output state, The SMP I/O Manager software automatically locates all SMP
data quality is marked as bad, and the front-panel LED turns I/O devices connected to the network segment. Select the
red. appropriate SMP I/O and perform the following operations:
• Outputs are protected against single component failure. The • Configure TCP/IP and RS-485 communications settings
relay control circuit is designed so that the failure of a single
• Configure DNP3 settings
component cannot accidentally energize the relay.
• Configure the built-in firewall to limit connections to specific
• Trip/close pair, latch, pulse, pulse to open and pulse to close
IP addresses or subnetworks
support
• Possibility to lock the settings to prevent accidental or
Behavior Descripton malevolent configuration changes
Trip-close pair One address is used to control two relays. When the master
station sends an Open command, the first relay is pulsed.
When the master station sends a Close command, the sec-
ond relay is pulsed. Trip-close relays are paired as follows:
1- 2, 3-4, 5-6 and 7-8. The two built-in relays can also be
paired.
Latch Energize or de-energize the relay upon reception of a master
station command.
Pulse Energize the relay for a specified duration. The duration can
be preset or provided by the master station.
Pulse to open and Two separate addresses are used to control the relay. The
pulse to close master station pulses one address to energize the relay, and
a different address to de-energize the relay.
Communications
The SMP I/O is accessible via the DNP3 protocol over RS-485 or SMP Tools
TCP/IP. It has one RS-485 serial port and one Ethernet connector
(copper or fiber). The SMP I/O is designed to integrate seamlessly with the
SMP Gateway automation platform. The SMP Config tool
The SMP I/O is compatible with any DNP3 master station. It is provides a quick configuration wizard that detects the SMP I/O
a level 2 DNP3 device and thus supports report-by-exception for configuration and automatically sets up all DNP3 indexes, default
reduced bandwidth usage. names and descriptions. You will only need to configure output
The SMP I/O’s clock can be synchronized by the DNP3 protocol, modes and input processing functions.
or by an external IRIG-B time source for greater accuracy.
• 1 x RS-485 serial interface
• 1 x 10/100 Mb/s Ethernet port (metallic or fiber LC)
• Secured remote maintenance using transparent connection
when used with an SMP Gateway automation platform
Configuration
Configuring the SMP I/O is a simple two-step process. First,
you connect the device to your network and configure the
communication settings using the SMP I/O Manager application.
Then, you use SMP Config to attach the SMP I/O to an SMP
Gateway automation platform and configure the operation of
binary outputs and the processing of binary inputs.
You can also use SMP I/O Manager to perform all configuration
steps for applications where the SMP I/O is not used with an
SMP Gateway automation platform.
Figure 4. SMP Tool from SMP Manager (SMP Gateway
automation platform software application)
The SMP Gateway HMI provides an easy way to view all I/O
signals using a standard web browser.
4 www.eaton.com/smartgrid
SMP™I/O Distributed I/O Platform Technical Data CA912005EN
Issue date October 2019
www.eaton.com/smartgrid 5
Technical Data CA912005EN SMP™I/O Distributed I/O Platform
Issue date October 2019
Wall-mount unit:
4 in. H x 11.9 in. W x 6.85 in. L
101 mm H x 302 mm W x 174 mm L
Warranty 5 year limited
Operating temperature Rack-mount unit: See temperature derating section for continuous
-40 °C to 80 °C* (-40 °F to 176 °F) maximum operation.
Wall-mount unit:
-40 °C to 75 °C* (-40 °F to 167 °F)
Storage temperature -40 °C to 85 °C (-40 °F to 185 °F)
Humidity 5% to 95%, non-condensing
MTBF MIL-HDBK-217 22.5 years at 25°C
Telcordia SR-232 35.36 years at 25°C
Maximum altitude 2000 m
Terminal blocks I/O connection 300V / 15A max
28-12 AWG Solid Wire
30-12 AWG Stranded Wire
Wire screw max torque = 6 in-lbf Terminal block
screw max torque = 4 in-lbf
6 www.eaton.com/smartgrid
SMP™I/O Distributed I/O Platform Technical Data CA912005EN
Issue date October 2019
Independent inputs, opto-isolated 24 VDC On: 18.3 - 30 VDC, Off: 5.5 VDC
48 VDC On: 37.5 - 60 VDC, Off: 10.5 VDC
110 VDC On: 82.5 – 137.5 VDC, Off: 21.3 VDC
125 VDC On: 91.5 – 156 VDC, Off: 23.5 VDC
220 VDC On: 169.5 - 275VDC, Off: 42.2 VDC
250 VDC On: 187.5 – 312.5 VDC, Off: 46.5 VDC
Current sink Error Detection Circuit (EDC) input option 4 mA maximum
Non-EDC input option 2 mA maximum
Hysteresys ratio 10% noise immunity guarantee All voltage detection threshold
Output relays Form C relays (built-in) 300 VAC/150 VDC, 12.5 J MOV protection across
Form A relays (output card) contact pairs
Operating time Pickup 7 ms typical
Dropout 4 ms typical
Rating 8 A at 250 VAC resistive All relay types
10 A at 30 VDC resistive
0.4 A at 125 VDC resistive
0.2 A at 150 VDC resistive
½ HP at 125 VAC
1/4 HP at 250 VAC
Rated insulation voltage 300 V RMS All relay types
Maximum voltage 400 VAC / 150 VDC All relay types
Continious carry 10A @ 85 °C All relay types
Maximum load 75 A for 1 second All relay types
www.eaton.com/smartgrid 7
Technical Data CA912005EN SMP™I/O Distributed I/O Platform
Issue date October 2019
Type tests
This section presents all tests that were conducted on the SMP I/O platform.
Environmental
Dry heat IEC 60068-2-2:1974 85°C, 16 hours
Cold IEC 60068-2-2:1974 -40°C, 24 hours
5 cold boots in 16 hours
Sinusoidal vibration - response IEC 60255-21-1:1988, Class 1 0.5 g from 10-150 Hz all axis
Sinusoidal vibration – endurance IEC 60255-21-1:1988, Class 2 2 g from 10-150 Hz all axis
Shock resistance IEC 60255-21-2:1988, Class 1 5 g all axis powered
15 g all axis
Sinusoidal vibration – seismic IEC 60255-21-3:1993, Method A, Class 2 2 g all axis powered
10 g all axis
Sinusoidal vibration – stationary IEC 870-2-2:1996, Class B 1 g and 1.5 g from 2-500 Hz all axis
Damp heat, steady state IEC 600068-2-78:2001 40°C, 93% relative humidity, 4 days
Damp heat, cyclic IEC 60068-2-30:1980 + A1:1985 25-55°C, 6 Cycles, 95% relative humidity
Flammability UL94-V0 System
UL224 VW-1 Internal harnesses
Electromagnetic Interference (EMI)
Impulse IEC 60255-5:2000 5 kV 0.5 J on supply
IEEE C37.90-1989 5 kV 0.5 J on relay outputs
5 kV 0.5 J on digital inputs
5 kV 0.5 J on IRIG-B inputs
5 kV 0.5 J on analog inputs
Dielectric IEC 60255-5:2000 2500 VAC - 3500 VDC on relay BO (I/O)
IEEE C37.90-1989 3000 VAC - 4000 VDC on digital inputs
2500 VAC - 4000 VDC on IRIG-B input
500 VAC - 1000 VDC on RJ 45 port
1500 VAC - 2100 VDC on relay CPU
1500 VAC – 2100 VDC on analog inputs
Electrostatic discharge immunity IEC 61000-4-2: 2001, Level 4 8 kV contact on enclosure
IEC 60255-22-2: 1996 8 kV contact on RJ-45 shield 8 kV contact on LC shield
IEEE 37.90.3-2001 15 kV air on supply contacts
15 kV air on IRIG-B contacts 15 kV air on RS-485 contacts
15 kV air on relay contacts
15 kV air on digital input contacts
15 kV air on analog inputs
Radiated RF immunity IEC 61000-4-3: 2000, Level 3 10 V/m 80-1000 MHz
Fast transient/burst immunity IEC 61000-4-4: 1995 + A1: 2000, Level 4 4 kV at 2.5 kHz on supply
2 kV at 5 kHz on all other ports
Surge immunity IEC 61000-4-5: 2001, Level 4 4 kV common on all ports
2 kV differential on all ports
2 kV common on all analog inputs
Conducted RF immunity IEC 61000-4-6: 2004, Level 3 140 dBµV (10 Vrms) from 150 kHz to 80 MHz
Magnetic field immunity IEC 61000-4-8:2001 1000 A/m for 3 seconds
100 A/m for 1 minute
Damp oscillatory wave immunity and surge IEC 61000-4-12: 1995 + A1: 2000, Level 3 2.5 kV common on all ports 1 kV differential on all ports
withstand capability immunity IEC 60255-22-1: 2005
RF radiated disturbance IEC CISPR-22: 1997 + A1: 2000, Class A
RF conducted disturbance IEC CISPR-22: 1997 + A1: 2000, Class A
Supply
Voltage variation immunity for AC IEC 61000-4-11:1994 + A1: 2001 90 ms without reboot
equipment
Polarity inversion for DC equipment SN-62.1008d: 1997 For 1 minute
8 www.eaton.com/smartgrid
SMP™I/O Distributed I/O Platform Technical Data CA912005EN
Issue date October 2019
www.eaton.com/smartgrid 9
Technical Data CA912005EN SMP™I/O Distributed I/O Platform
Issue date October 2019
Temperature derating
Table 10. Ambient temperature reduction (oC) for I/O cards
Rack-Mount enclosure with CPU Board and Copper ∆T ≥ 5ºC ; Ta = 85oC – (IOA + IOB + IOC + IOD) ∆T is the SUM of I/O slot temperature derating
Ethernet Interface o o (IOA + IOB + IOC + IOD)
∆T ≤ 5 C ; Ta = 80 C
Rack-Mount enclosure with CPU Board and Fiber ∆T ≥ 17oC ; Ta = 85oC – (IOA + IOB + IOC + IOD) Ta is the ambient temperature
Ethernet Interface A, B and C are referring to the expansion card
Wall-Mount Enclosure (All configurations) Ta = 75oC – (IOA + IOB + IOC + IOD) slot identification
10 www.eaton.com/smartgrid
SMP™I/O Distributed I/O Platform Technical Data CA912005EN
Issue date October 2019
Dimension drawings
www.eaton.com/smartgrid 11
Technical Data CA912005EN SMP™I/O Distributed I/O Platform
Issue date October 2019
12 www.eaton.com/smartgrid
SMP™I/O Distributed I/O Platform Technical Data CA912005EN
Issue date October 2019
Ordering information
www.eaton.com/smartgrid 13
Technical Data CA912005EN SMP™I/O Distributed I/O Platform
Issue date October 2019
14 www.eaton.com/smartgrid
SMP™I/O Distributed I/O Platform Technical Data CA912005EN
Issue date October 2019
www.eaton.com/smartgrid 15
To learn more, visit
Eaton.com/smartgrid
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com