GEP550-2
Diesel Generator Set
Exclusively from your Cat ® dealer
EU Stage II Emissions Compliant
Suitable for Mobile Applications in the European Community
Output Ratings
Generating Set Model Prime* Standby*
380-415V,50Hz 500.0 kVA 550.0 kVA
400.0 kW 440.0 kW
- - -
- -
* Refer to ratings definitions on page 4.
Ratingsatat .8
Ratings powerfactor.
0.8power factor
Technical Data
Engine Make & Model: Perkins 2506C-E15TAG2
Alternator Model: LL6114F
Base Frame Type: Heavy Duty Fabricated Steel
Circuit Breaker Type: 3 Pole MCCB
Frequency: 50 Hz 60 Hz
Engine Speed: RPM 1500 -
Fuel Tank Capacity: litres (US gal) 928 (245.2)
Fuel Consumption, Prime: l/hr (US gal/hr) 102.4 (27.1) -
Fuel Consumption, Standby : l/hr (US gal/hr) 111.8 (29.5) -
Engine Techncial Data
Physical Data Lubrication system
Manufacturer: Perkins Oil Filter Type: Eco, Full Flow
Model: 2506C-E15TAG2 Total Oil Capacity l (US gal): 62.0 (16.4)
No. of Cylinders/Alignment: 6 / In Line Oil Pan l (US gal): 53.0 (14.0)
Cycle: 4 Stroke Oil Type: API CI4 15W-40
Induction: Turbocharged Air To Air Cooling Method: Water
Charge Cooled
Cooling Method: Water
Governing Type: Electronic Performance 50 Hz 60 Hz
Governing Class: ISO 8528 G2
Engine Speed: RPM 1500 -
Compression Ratio: 16.0:1
Gross Engine Power: kW (hp)
Displacement: l (cu.in) 15.2 (927.6)
-Standby: 487.0 (653.0) -
Bore/Stroke: mm (in) 135.0 (5.3)/167.0 (6.6)
-Prime: 443.0 (594.0) -
Moment of Inertia: kg m² (lb. in²) 4.29 (14660)
BMEP: kPa (psi)
Engine Electrical System: -Standby: 2717.0 (394.0) -
-Voltage/Ground: 24/Negative -Prime: 2471.0 (358.4) -
-Battery Charger Amps: 70 Regenerative Power: kW 50.0 -
Weight: kg (lb) - Dry: 1633 (3600)
- Wet: 1714 (3779)
Fuel System
Fuel Filter Type: Replaceable Element
Air System 50 Hz 60 Hz Recommended Fuel: Class A2 Diesel
Fuel Consumption: l/hr (US gal/hr)
Air Filter Type: Paper Element 18"
110% 100% 75% 50%
Combustion Air Flow:
Load Load Load Load
m³/min (cfm) -Standby: 32.0 (1130) -
Prime
-Prime: 30.5 (1077) -
50 Hz 111.8 (29.5) 102.4 (27.1) 78.4 (20.7) 53.4 (14.1)
Max. Combustion Air Intake
60 Hz - - - -
Restriction: kPa (in H2O) 6.2 (24.9) -
Radiator Cooling Air Flow:
Standby
m³/min (cfm) 660.0 (23308) -
50 Hz 111.8 (29.5) 85.7 (22.6) 58.4 (15.4)
External Restriction to
60 Hz - - -
Cooling Air Flow: Pa (in H2O) 125 (0.5) -
(based on diesel fuel with a specific gravity of 0.85 and conforming to
BS2869, Class A2)
Cooling System 50 Hz 60 Hz Exhaust System 50 Hz 60 Hz
Cooling System Capacity: Silencer Type: Level 1
l (US gal) 38.3 (10.1) - Silencer Noise Reduction SD150 (1)
Water Pump Type: Centrifugal Pressure Drop Across
Heat Rejected to Water & Silencer System: kPa (in Hg) 0.28 (0.083) -
Lube Oil: kW (Btu/min) Silencer Noise Reduction
-Standby: 179.0 (10180) - Level: dB 15 -
-Prime: 157.0 (8928) - Max. Allowable Back
Heat Radiation to Room: Pressure: kPa (in. Hg) 6.8 (2.0) -
kW (Btu/min) -Standby: 71.0 (4038) - Exhaust Gas Flow:
-Prime: 63.0 (3583) - m³/min (cfm) -Standby: 87.0 (3072) -
Radiator Fan Load: kW (hp) 16.0 (21.5) - -Prime: 81.0 (2860) -
Exhaust Gas Temperature: °C (°F)
m³/min (cfm) -Standby: 528 (982) -
Cooling system designed to operate in ambient conditions up to 50°C -Prime: 514 (957) -
(122°F). Contact your local Olympian dealer for power ratings at specific
site conditions.
Consult your Olympian representative for more information
Alternator Performance Data
50 Hz 60 Hz
Data Item 415/240V 400/230V 380/220V 220/127V
230/115V 220/110V
200/115V
Motor Starting
Capability* kVA 1296 1213 1106 1438 - - - - -
Short Circuit
Capacity** % 300 300 300 300 300 300 300 300 300
Reactances:
Per Unit
Xd 2.850 3.070 3.400 2.330 - - - - -
X'd 0.150 0.160 0.180 0.120 - - - - -
X''d 0.103 0.111 0.123 0.084 - - - - -
Reactances shown are applicable to standby ratings.
* Based on 30% voltage dip.
** With optional Permanent Magnet generator or AREP excitation.
Alternator Technical Data
Physical Data Operating Data
Manufacturer: OLYMPIAN Overspeed: RPM 2250
Model: LL6114F Voltage Regulation (steady state) (% ): +/- 0.5
No. of Bearings: 1 Wave Form NEMA = TIF: 50
Insulation Class: H Wave Form IEC = THF: 2.0%
Winding Pitch - Code: 2/3 - 6 Total Harmonic Content LL/LN: 2.0%
Supression is in line with European
Wires: 12 Radio Interference: Standard EN61000-6
Ingress Protection Rating: IP23 Radiant Heat: kW (Btu/min)
Excitation System: -50 Hz: 27.1 (1541)
SHUNT
-60 Hz: -
AVR Model: R450
Consult your Olympian representative for more information
Technical Data
3 Phase Ratings and Performance at 50 Hz, 1500 RPM 3 Phase Ratings and Performance at 60 Hz, - RPM
Voltage Prime Standby Voltage Prime Standby
kVA kW kVA kW kVA kW kVA kW
415/240V 500.0 400.0 550.0 440.0
400/230V 500.0 400.0 550.0 440.0
380/220V 500.0 400.0 550.0 440.0
230/115V 500.0 400.0 550.0 440.0
220/127V 460.0 368.0 506.0 404.8
220/110V 500.0 400.0 550.0 440.0
200/115V 500.0 400.0 550.0 440.0
Weights & Dimensions
Weights: kg (lb) Dimensions: mm (in)
Net (+ lube oil) 3920 (8642) Length 3700 (145.7)
Wet (+ lube oil & coolant) 3958 (8726) Width 1100 (43.3)
Fuel, lube oil & coolant 4742 (10454) Height 2143 (84.4)
Note: General configuration not to be used
for installation. See general dimension
drawings for detail.
Definitions General Data
Standby Rating Documents
These ratings are applicable for supplying continuous electrical A full set of operation and maintenance manuals and circuit wiring
power (at variable load) in the event of a utility power failure. No diagrams.
overload is permitted on these ratings. The alternator on this model
is peak continuous rated (as defined in ISO 8528-3).
Quality Standards
BS4999, BS5000, BSEN60034, BSEN61000, IEC60034.
Prime Rating
These ratings are applicable for supplying continuous electrical
power (at variable load) in lieu of commercially purchased power.
There is no limitation to the annual hours of operation and this Warranty
model can supply 10% overload power for 1 hour in 12 hours. All equipment carries full manufacturer's warranty.
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) air inlet temp,
100m (328ft) A.S.L. 30% relative humidity. Fuel consumption data
at full load with diesel fuel with specific gravity of 0.85 and
conforming to BS2869: 1998, Class A2.
Information contained in this publication may be considered confidential. www.Cat-ElectricPower.com
Information contained in this publication may be considered confidential.
Market: International Discretion
Discretionisisrecommended
recommended when
when distributing.
distributing.
Materials
Materialsand
andspecifications
specifications are
are subject to change
subject to changewithout
withoutnotice.
notice. © 2010 Caterpillar
LEHF6377-05
LEHF6377-04 (09-10)
(09/10) CAT,CAT,
CATERPILLAR, theirtheir
CATERPILLAR, respective logos
respective OLYMPIAN,
logos, OLYMPIAN, "Caterpillar Yellow",
“Caterpillar andthe
Yellow,” the "Power
“Power Edge"
Edge” trade
trade dress,
dress as well
as well as as All rights reserved.
corporate andand
corporate product identity
product used
identity usedherein,
herein,are
aretrademarks
trademarks of Caterpillar
Caterpillarandandmay
may not
not bebe used
used without
without permission.
permission. Printed in U.S.A.
278-687