E9 To E28 NKR Service Manual - PDF - Industrial Air
E9 To E28 NKR Service Manual - PDF - Industrial Air
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the products dealt with in this service information by anyone else could result in serious injury or death.
WARNING This indication shows the possibility of causing death or serious injury.
CAUTION This indication shows the possibility of causing injury or damage to properties.
Carry out test running to confirm that no abnormality occurs after the servicing. Then, explain to user the
operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating
instructions for future reference.
WARNING
2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.
4. Engage authorized dealer or specialist for installation and servicing. If installation or servicing done by the user is defective, it will cause
water leakage, electrical shock or fire.
5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.
6. Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, fire
or electrical shock.
7. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done,
the set will drop and cause injury.
8. For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet
must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
9. This equipment is strongly recommended to install with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it
may cause electrical shock and fire in case equipment breakdown or insulation breakdown.
10. Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to installation instruction
CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force
will be acted on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the connection.
11. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause
heat-up or fire at the connection point of terminal, fire or electrical shock.
12. When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration
cycle (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
13. Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb up to
outdoor unit and cross over the handrail and causing accident.
14. This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
telephone. Otherwise, it may cause electric shock in case equipment breakdown or insulation breakdown.
15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
16. Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
17. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
may break and cause refrigerant gas leakage.
18. For R410A models, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause
abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A materials.
Thickness of copper pipes used with R410A must be more than 0.8mm. Never use copper pipes thinner than 0.8mm.
It is desirable that the amount of residual oil is less than 40 mg/10m.
3
WARNING
19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration piping
and valves at opened condition will caused suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc).
20. During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of compressor while compressor is
operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion,
injury etc.)
21. After completion of installation or service, confirm there is no leakage or refrigerant gas. It may generate toxic gas when the refrigerant
contacts with fire.
22. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire.
23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
24. Must not use other parts except original parts described in catalog and manual.
25. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.
CAUTION
1. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the
unit, it may cause fire.
2. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage
the furniture.
3. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
may break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
6. Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use
a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).
7. Power supply connection to the air conditioner. Connect the power supply cord of the air conditioner to the mains using one of the following
methods.
Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries,
permanent connection of this room air conditioner to the power supply is prohibited.
i. Power supply connection to the receptacle using a power plug. Use an approved 15/16A (3/4~1.75HP) or 16A (2.0HP) or 20A (2.5HP) or
25A (3.0HP) power plug with earth pin for the connection to the socket.
ii. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A (3/4~2.0HP), 20A (2.5HP) or
25A (3.0HP) circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap.
8. Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts.
Take care of the liquid refrigerant, it may cause frostbite.
9. Installation or servicing work: It may need two people to carry out the installation or servicing work.
10. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
11. Do not sit or step on the unit, you may fall down accidentally.
12. Do not touch the sharp aluminium fins or edges of metal parts.
If you are required to handle sharp parts during installation or servicing, please wear hand glove.
Sharp parts may cause injury.
4
2. Specification
Indoor CS-E7NKR
Model
Outdoor CU-E7NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 0.85 2.05 2.40 0.85 2.05 2.40
Capacity BTU/h 2900 6990 8180 2900 6990 8180
kcal/h 730 1760 2060 730 1760 2060
Running Current A - 2.2 - - 2.2 -
Input Power W 200 460 590 200 460 590
W/W 4.25 4.46 4.07 4.25 4.46 4.07
Cooling
5
Type Cross-Flow Fan
Material ASG20K1
Motor Type Transistor (8-poles)
Input Power W 47.3 - 47.3
Output Power W 40
Cool rpm 630
QLo
Heat rpm 650
Indoor Fan
6
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
7
Indoor CS-E9NKR
Model
Outdoor CU-E9NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 0.90 2.60 3.00 0.90 2.60 3.00
Capacity BTU/h 3070 8870 10200 3070 8870 10200
kcal/h 770 2240 2580 770 2240 2580
Running Current A - 2.6 - - 2.5 -
Input Power W 210 550 780 210 550 780
W/W 4.29 4.73 3.85 4.29 4.73 3.85
Cooling
8
Type Cross-Flow Fan
Material ASG20K1
Motor Type Transistor (8-poles)
Input Power W 47.3 - 47.3
Output Power W 40
Cool rpm 630
QLo
Heat rpm 690
Indoor Fan
9
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
10
Indoor CS-E12NKR
Model
Outdoor CU-E12NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 0.90 3.50 4.00 0.90 3.50 4.00
Capacity BTU/h 3070 11900 13600 3070 11900 13600
kcal/h 770 3010 3440 770 3010 3440
Running Current A - 3.9 - - 3.8 -
Input Power W 210 830 1.10k 210 830 1.10k
W/W 4.29 4.22 3.64 4.29 4.22 3.64
Cooling
11
Type Cross-Flow Fan
Material ASG20K1
Motor Type Transistor (8-poles)
Input Power W 47.3 - 47.3
Output Power W 40
Cool rpm 650
QLo
Heat rpm 770
Indoor Fan
12
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
13
Indoor CS-E15NKR
Model
Outdoor CU-E15NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 0.90 4.40 5.00 0.90 4.40 5.00
Capacity BTU/h 3070 15000 17100 3070 15000 17100
kcal/h 770 3780 4300 770 3780 4300
Running Current A - 5.5 - - 5.3 -
Input Power W 215 1.20k 1.60k 215 1.20k 1.60k
W/W 4.19 3.67 3.13 4.19 3.67 3.13
Cooling
14
Type Cross-Flow Fan
Material ASG20K1
Motor Type Transistor (8-poles)
Input Power W 94.8 - 94.8
Output Power W 40
Cool rpm 640
QLo
Heat rpm 790
Indoor Fan
15
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
16
Indoor CS-E18NKR
Model
Outdoor CU-E18NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 0.90 5.00 6.00 0.90 5.00 6.00
Capacity BTU/h 3070 17100 20500 3070 17100 20500
kcal/h 770 4300 5160 770 4300 5160
Running Current A - 6.1 - - 5.9 -
Input Power W 230 1.30k 2.05k 230 1.30k 2.05k
W/W 3.91 3.85 2.93 3.91 3.85 2.93
Cooling
17
Type Cross-Flow Fan
Material ASG30K1
Motor Type Transistor (8-poles)
Input Power W 94.8 - 94.8
Output Power W 40
Cool rpm 870
QLo
Heat rpm 850
Indoor Fan
18
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
19
Indoor CS-E21NKR
Model
Outdoor CU-E21NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 1.70 6.30 7.10 1.70 6.30 7.10
Capacity BTU/h 5800 21500 24200 5800 21500 24200
kcal/h 1460 5420 6110 1460 5420 6110
Running Current A - 8.3 - - 8.1 -
Input Power W 440 1.80k 2.20k 440 1.80k 2.20k
W/W 3.86 3.50 3.23 3.86 3.50 3.23
Cooling
20
Type Cross-Flow Fan
Material ASG30K1
Motor Type Transistor (8-poles)
Input Power W 94.8 - 94.8
Output Power W 40
Cool rpm 860
QLo
Heat rpm 910
Indoor Fan
21
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
22
Indoor CS-E24NKR
Model
Outdoor CU-E24NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 1.70 7.10 8.10 1.70 7.10 8.10
Capacity BTU/h 5800 24200 27600 5800 24200 27600
kcal/h 1460 6110 6970 1460 6110 6970
Running Current A - 9.7 - - 9.4 -
Input Power W 430 2.11k 2.48k 430 2.11k 2.48k
W/W 3.95 3.36 3.27 3.95 3.36 3.27
Cooling
23
Type Cross-Flow Fan
Material ASG30K1
Motor Type Transistor (8-poles)
Input Power W 94.8 - 94.8
Output Power W 40
Cool rpm 890
QLo
Heat rpm 960
Indoor Fan
24
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
25
Indoor CS-E28NKR
Model
Outdoor CS-E28NKR
Performance Test Condition AS
Phase, Hz Single, 50
Power Supply
V 230 240
Min. Mid. Max. Min. Mid. Max.
kW 2.30 8.00 8.60 2.30 8.00 8.60
Capacity BTU/h 7840 27300 29300 7840 27300 29300
kcal/h 1980 6880 7400 1980 6880 7400
Running Current A - 11.2 - - 10.9 -
Input Power W 460 2.39k 2.70k 460 2.39k 2.70k
W/W 5.00 3.35 3.19 5.00 3.35 3.19
Cooling
26
Type Cross-Flow Fan
Material ASG30K1
Motor Type Transistor (8-poles)
Input Power W 94.8 - 94.8
Output Power W 40
Cool rpm 970
QLo
Heat rpm 1000
Indoor Fan
27
Inner Diameter mm 16
Drain Hose
Length mm 650
Fin Material Aluminium (Pre Coat)
28
3. Features
Inverter Technology
o Wider output power range
o Energy saving
o Quick Cooling
o Quick Heating
o More precise temperature control
Environment Protection
o Non-ozone depletion substances refrigerant (R410A)
Quality Improvement
o Random auto restart after power failure for safety restart operation
o Gas leakage protection
o Prevent compressor reverse cycle
o Inner protector to protect compressor
o Noise prevention during soft dry operation
Operation Improvement
o Quiet mode to reduce the indoor unit operating sound
o Powerful mode to reach the desired room temperature quickly
o 24-hour timer setting
Serviceability Improvement
o Breakdown Self Diagnosis function
29
4. Location of Controls and Components
4.1 Indoor Unit
30
5. Dimensions
5.1 Indoor Unit
5.1.1 CS-E7NKR CS-E9NKR CS-E12NKR CS-E15NKR
31
5.1.2 CS-E18NKR CS-E21NKR CS-E24NKR CS-E28NKR
32
5.2 Outdoor Unit
5.2.1 CU-E7NKR CU-E9NKR CU-E12NKR
33
5.2.3 CU-E28NKR
34
6. Refrigeration Cycle Diagram
6.1 CU-E7NKR
35
6.2 CU-E9NKR CU-E12NKR
36
6.3 CU-E15NKR CU-E18NKR
37
6.4 CU-E21NKR
38
6.5 CU-E24NKR CU-E28NKR
39
7. Block Diagram
7.1 CU-E7NKR CU-E9NKR CU-E12NKR
40
7.2 CU-E15NKR CU-E18NKR CU-E21NKR
41
7.3 CU-E24NKR
42
7.4 CU-E28NKR
43
8. Wiring Connection Diagram
8.1 Indoor Unit
44
8.2 Outdoor Unit
8.2.1 CU-E7NKR CU-E9NKR CU-E12NKR
45
8.2.2 CU-E15NKR CU-E18NKR
46
8.2.3 CU-E21NKR
47
8.2.4 CU-E24NKR
48
8.2.5 CU-E28NKR
49
9. Electronic Circuit Diagram
9.1 Indoor Unit
50
9.2 Outdoor Unit
9.2.1 CU-E7NKR CU-E9NKR CU-E12NKR
51
9.2.2 CU-E15NKR CU-E18NKR
52
9.2.3 CU-E21NKR
53
9.2.4 CU-E24NKR
54
9.2.5 CU-E28NKR
55
10. Printed Circuit Board
10.1 Indoor Unit
10.1.1 Main Printed Circuit Board
56
10.1.3 Receiver Printed Circuit Board
57
10.1.6 Human Activity Sensor Printed Circuit Board
58
10.2 Outdoor Unit
10.2.1 CU-E7NKR CU-E9NKR CU-E12NKR
59
10.2.2 CU-E15NKR CU-E18NKR
60
10.2.3 CU-E21NKR CU-E24NKR
61
10.2.4 CU-E28NKR
62
10.2.5 Noise Filter Printed Board
(CU-E21NKR)
63
11. Installation Instruction
11.1 Select the Best Location 11.1.3 Indoor/Outdoor Unit Installation
(For E7/9/12/15/18/21/24NKR only) Diagram
64
11.2 Indoor Unit
11.2.1 How to Fix Installation Plate 11.2.2 To Drill a Hole in the Wall and
The mounting wall shall be strong and solid enough to Install a Sleeve of Piping
prevent it from vibration.
1 Insert the piping sleeve to the hole.
2 Fix the bushing to the sleeve.
3 Cut the sleeve until it extrudes about 15 mm
from the wall.
CAUTION
When the wall is hollow, please be sure to use the
sleeve for tube assembly to prevent dangers caused
by mice biting the connection cable.
○
B : For left side piping, piping connection for
liquid should be about g from this line.
: For left side piping, piping connection for gas
should be about h from this line.
1 Mount the installation plate on the wall with 5 11.2.3 Indoor Unit Installation
screws or more (at least 5 screws).
(If mounting the unit on the concrete wall,
consider using anchor bolts.)
o Always mount the installation plate
horizontally by aligning the marking-off
line with the thread and using a level
gauge.
2 Drill the piping plate hole with ø70 mm hole-
core drill.
o Line according to the left and right side of
the installation plate. The meeting point
of the extended line is the center of the
hole. Another method is by putting
measuring tape at position as shown in
the diagram above. The hole center is
obtained by measuring the distance
namely 128 mm for left and right hole
respectively.
o Drill the piping hole at either the right or
the left and the hole should be slightly
slanting to the outdoor side.
65
11.2.3.1 For the right rear piping
66
11.2.4 Connect the Cable to the Indoor Unit
1 The inside and outside connecting cable can
be connected without removing the front grille.
2 Connection cable between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 x 1.5 mm2 flexible
cord, type designation 245 IEC 57 or heavier
cord.
3 Bind all the indoor and outdoor connecting
cable with tape and route the connecting
cable via the escapement.
4 Remove the tapes and connect the
connecting cable between indoor unit and
outdoor unit according to the diagram below.
5 Secure the connecting cable onto the control board with the holder (clamper).
o Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s
respectively.
o Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
67
11.2.4.1 Cutting and flaring the piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end
down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
68
11.3 Outdoor Unit
11.3.1 Install the Outdoor Unit
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt or nails.
Model A B C D
E7***
540 mm 160 mm 18.5 mm 330 mm
E9***, E12***
E15***
E18***, E21*** 613 mm 131 mm 16 mm 360.5 mm
E24***
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
69
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
o Be sure to check for gas leakage.
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in the step e above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step e.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
70
6 Secure the power supply cord and connecting cable onto the control board with the holder.
7 Attach the control board cover back to the original position with the screw.
8 For wire stripping and connection requirement, refer to instruction 11.2.4 of the indoor unit.
WARNING
This equipment must be properly earthed.
Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
Always ensure all above connections compliant with national wire rules.
71
12. Installation Instruction
12.1 Select the Best Location 12.1.3 Indoor/Outdoor Unit Installation
(For E28NKR only) Diagram
Example: E28***
If the unit is installed at 12 m distance, the quantity of
additional refrigerant should be 60 g .... (12-10) m x
30 g/m = 60 g.
72
12.2 Indoor Unit
12.2.1 How to Fix Installation Plate 12.2.2 To Drill a Hole in the Wall and
The mounting wall shall be strong and solid enough to Install a Sleeve of Piping
prevent it from vibration.
1 Insert the piping sleeve to the hole.
2 Fix the bushing to the sleeve.
3 Cut the sleeve until it extrudes about 15 mm
from the wall.
CAUTION
When the wall is hollow, please be sure to use the
sleeve for tube assembly to prevent dangers caused
by mice biting the connection cable.
○
B : For left side piping, piping connection for
liquid should be about g from this line.
: For left side piping, piping connection for gas
should be about h from this line.
73
12.2.3.1 For the right rear piping
74
12.2.4 Connect the Cable to the Indoor Unit
1 The inside and outside connecting cable can
be connected without removing the front grille.
2 Connection cable between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 x 1.5 mm2 flexible
cord, type designation 245 IEC 57 or heavier
cord.
3 Bind all the indoor and outdoor connecting
cable with tape and route the connecting
cable via the escapement.
4 Remove the tapes and connect the
connecting cable between indoor unit and
outdoor unit according to the diagram below.
5 Secure the connecting cable onto the control board with the holder (clamper).
o Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s
respectively.
o Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
75
12.2.4.1 Cutting and flaring the piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end
down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
76
12.3 Outdoor Unit
12.3.1 Install the Outdoor Unit
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 If installing the unit to a concrete base or other solid base, use M10 or W3/8 bolts and nuts to secure the unit,
and ensure that the unit is fully upright and level.
(The anchor bolt positions are shown in the diagram at the right side.)
In particular, install the unit at a distance from the neighbouring building which conforms to regulations
specified by local noise emission regulation standards.
2 Do not install the outdoor unit to the building’s roof.
3 If there is a possibility that vibration may be transmitted to the rooms of the building, place rubber insulation
between the unit and the installation surface.
77
The cardboard must be removed before installation of piping work.
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
o Be sure to check for gas leakage.
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in the step e above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step e.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
78
4 Connecting cable between outdoor unit and DRED (Demand response enabling devices) shall be double
insulation layer, polychloroprene sheathed (>50V) with size 4 x (0.5 mm2 to 2.0 mm2) cable or flexible cord,
where the maximum allowable length is 30m.
5 Connect the power supply cord and connecting cable between indoor unit and outdoor unit according to the
diagram below.
6 Secure the power supply cord and connecting cable onto the control board with the holder.
7 Select required direction and apply protective bushing provided in accessories to protect cables from sharp
edges.
8 Once all wiring work has been completed, tie the wires and cords together with the binding strap so that they
do not touch other parts such as the compressor and pipes.
9 Attach the control board cover back to the original position with screw.
10 For wire stripping and connection requirement, refer to instruction 12.2.4 of indoor unit.
WARNING
This equipment must be properly earthed.
Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
Always ensure all above connections compliant with national wire rules.
79
13. Operation Control
13.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
80
13.1.5 Automatic Operation
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
Every 10 minutes, the indoor temperature is judged.
For the 1st judgment
o If indoor intake temperature - remote control setting temperature ≥ 2°C, COOL mode is decided.
o If -2°C ≤ indoor intake temperature - remote control setting temperature < 2°C, DRY mode is decided.
o If indoor intake temperature - remote control setting temperature < -2°C, HEAT mode is decided.
Remote control ○ ○ ○ ○ ○
Tab Hi Me+ Me Me- Lo
[Heating]
o Fan motor’s number of rotation is determined according to remote control setting.
Remote control ○ ○ ○ ○ ○
Tab SHi Me+ Me Me- Lo
81
o The indoor fan will operate according to pattern below.
[Heating]
o According to indoor pipe temperature, automatic heating fan speed is determined as follows.
82
13.4 Airflow Direction
There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by
vertical vanes).
Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner is
stopped using remote control, the vane will shift to close position.
Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the
vane will shift to close position.
83
Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below
and the positions of the vane are as Figure 2 above.
Pattern 1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°) 90 68 78 102 112
Control condition
o Quiet operation start condition
When “POWERFUL/QUIET” button at remote control is pressed twice.
POWERFUL/QUIET LED illuminates (low intensity).
Control contents
o Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB (some models more than 3dB).
o Fan speed for quiet operation is reduced from setting fan speed.
Control condition
o Quiet operation start condition
When “POWERFUL/QUIET” button at remote control is pressed.
POWERFUL/QUIET LED illuminates. (low intensity)
84
Control contents
o Fan speed manual
Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
Fan speed for quiet operation is reduced from setting fan speed.
o Fan Speed Auto
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
85
13.10 Indication Panel
LED POWER TIMER POWERFUL nanoe-G AUTO COMFORT QUIET
Color Green Orange Orange Blue Green Green
POWERFUL Mode AUTO COMFORT QUIET Mode
Light ON Operation ON Timer Setting ON nanoe-G ON
ON ON ON
POWERFUL Mode AUTO COMFORT QUIET Mode
Light OFF Operation OFF Timer Setting OFF nanoe-G OFF
OFF OFF OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.
Timer control
o When ON Timer activates when unit stops, previous operation resumes and restored last saved nanoe-G
operation status.
o When ON Timer activates during any operation, no change on current operation.
o When OFF Timer activates during any operation, all operation stops and the latest nanoe-G operation status
is saved.
Indicator
o When nanoe-G starts, nanoe-G indicator ON.
86
Remote Control Receiving Sound
o Normal Operation Î nanoe-G Operation : Beep
o Nanoe-G Operation Î Normal Operation : Beep
o Stop Î nanoe-G individual Operation : Beep
o Nanoe-G individual Operation Î Stop : Long Beep
Power failure
o During nanoe-G individual operation, if power failure occurs, after power resumes, nanoe-G individual
operation resumes immediately.
o During combination operation, if power failure occurs, after power resumes, combination operation resume
immediately.
o nanoe-G operation status is not memorized after OFF the unit. After OFF the unit, when the operation is ON
again, air conditioner operates without nanoe-G operation.
87
o Troubleshooting method
Press nanoe-G button or OFF/ON button to stop the operation and check the nanoe-G connector at PCB.
After that, press nanoe-G button again to confirm the nanoe-G indicator do not blinks.
The 24 timer counter will be clear after 10 minutes of normal operation or when operation stops.
Troubleshooting method
Press nanoe-G button or OFF/ON button to stop the operation.
Change nanoe-G high voltage power supply or main PCB.
When Lo-feedback voltage supplied to nanoe-G system during nanoe-G operation ON, nanoe-G
indicator and Timer indicator stop blinking.
88
ECO NAVI stop conditions:
o When ECO NAVI button is pressed again.
o When unit is OFF by OFF/ON button.
o When unit is OFF when OFF TIMER activates.
o When unit is OFF by AUTO OFF/ON button at indoor unit.
o When POWERFUL, QUIET operation activates.
o When ◄► button is pressed.
89
13.13.1.1 Signal Detection
Human Activity sensor will turns on according to infrared sensors signal detection.
However, once the Human Activity Indicator is ON, it will maintain ON status for 5 seconds. If there is no signal
detection from either infrared sensor, the final display condition will be kept until absence status.
90
13.13.1.7 Setting Position Judgment
According to installation position when there is only one activity area detected, the horizontal airflow direction
louver position is fixed according to chart below:
When 2 activity areas have been detected, according to Human Activity Level, the timing of horizontal airflow
direction louver steps at the targeted activity areas is judged.
When 3 activity areas have been detected, according to Human Activity Level the timing of horizontal airflow
louver steps at the targeted activity areas is judged.
When 3 activity areas have same activity level, the horizontal airflow direction louver will swing left and right.
91
13.13.2.1 ECONAVI Demo Mode
To enable ECO DEMO mode:
Operation details
The target area will maintain for 5 seconds before changeover to next detection.
If no activity detection, the last action will maintain for 30 seconds before changeover to human absence status.
92
13.13.2.2 Infrared Sensor Abnormality
Abnormality detection:
o Connector disconnection / Wire cut abnormality
Sensor judge Hi level continuously for 25 seconds
o Circuit abnormality
70 seconds after power ON, if infrared sensor judge Lo level continuously for 25 seconds
When error code happened, the unit is able to operate without AUTO COMF / ECO NAVI.
During ECO NAVI is ON, when CHECK signal received, if either sensors has abnormality, the 4 times
abnormality counter is ignored, ECO NAVI Indicator will blink immediately and error code is memorized.
The unit could operate without ECO NAVI or AUTO COMF.
The ECO NAVI indicator blinking could be cancelled by pressing ECO NAVI button again.
If the Infrared sensor has no abnormality, the CHECK process will end and continue with normal operation.
93
13.13.3 Sunlight Sensor
During ECONAVI operation, the sunlight sensor detects sunlight intensity coming through windows and
differentiates between sunny and cloudy or night to further optimize energy saving by adjusting the temperature.
Sunlight judgment is as following
94
13.13.3.3 Judge Ambient Condition
According to sunlight intensity over a period of time, the system will analyze the ambient condition is sunny,
cloudy or night.
Operation details
o The sunlight sensor check mode will be operated for 5 minutes.
o During check mode, the ON and OFF timer will be memorized but it operation be ignored.
o During check mode, if the sunlight sensor check code is retransmitted, the 5 minutes counter will be reset.
o During check mode, if sunlight sensor detected the sunlight intensity value above minimum level, the
ECONAVI indicator turns ON. Else if sunlight sensor detected sunlight intensity value below minimum level,
the ECONAVI indicator is OFF.
To disable sunlight sensor check mode
o After check mode is ended (5 minutes counter elapsed), press AUTO OFF/ON button at indoor unit.
o If the sunlight sensor detected sunlight intensity is at abnormal range, the check mode will be ended.
Please check for error code.
95
13.13.3.6 Sunlight Sensor Abnormality
Abnormality detection:
o When ECONAVI is ON, if the sunlight intensity value below minimum level continuously for 24 hours, the
sunlight sensor disconnection error counter will increase by 1 time. If the ECONAVI is OFF, the 24 hours
timer will be reset, but the sunlight sensor disconnection error counter will not be reset.
Error Code judgment
o When sunlight sensor disconnection error counter reached 15 times. H70 occurred.
o No TIMER indicator or ECONAVI indicator blink.
When error code happened, the unit is able to operate without sunlight sensor.
96
14. Protection Control
14.1 Protection Control For All Operations
14.1.1 Restart Control (Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
97
14.1.4 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 107°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. (“F97” is indicated.)
98
14.1.7 Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
99
14.2.5 Dew Prevention Control 1
To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.
o When Cooling or Dry mode is operated more than 20 minutes or more.
This control stopped if:
o Compressor stopped.
o Remote control setting changed (fan speed / temperature).
o Outdoor air temperature and indoor intake temperature changed.
Fan speed will be adjusted accordingly in this control.
100
14.3.4 Low Temperature Compressor Oil Return Control
In heating operation, if the outdoor temperature falls below -10°C (E7 ~ 18NK), -8°C (E21 ~ 28NK) when
compressor starts, the compressor frequency will be regulated up to 600 seconds.
101
15. Servicing Mode
15.1 Auto OFF/ON Button
The Auto OFF/ON button may be used together with remote control to set / change the advance setting of air
conditioner operation.
There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor
unit. The indoor unit will only operate when received signal with same transmission code from remote control.
This could prevent signal interference when there are 2 or more indoor units installed nearby together.
To change remote control transmission code, short or open jumpers at the remote control printed circuit
board.
During Remote Control Number Switch Mode, press any button at remote control to transmit and store
the transmission code to the EEPROM.
102
4 REMOTE CONTROL RECEIVING SOUND OFF/ON MODE
The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed
continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote
Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset” button at remote
control.
After Auto OFF/ON Button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON
Mode is restarted.
103
15.2.2 RESET (RC)
To clear and restore the remote control setting to factory default.
o Press once to clear the memory
15.2.4 TIMER ▲
To change indoor unit indicator’s LED intensity
o Press continuously for 5 seconds.
15.2.5 TIMER ▼
To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F)
o Press continuously for 10 seconds.
104
16. Troubleshooting Guide
16.1 Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard)
electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air
Such problems include insufficient insulation, problem with the Mpa Temperature
2
(kg/cm G) (°C)
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the refrigeration Cooling Mode 0.9 ~ 1.2 (9 ~ 12) 12 ~ 16
cycle depends on various conditions, the standard values for them Heating Mode 2.3 ~ 2.9 (23 ~ 29) 36 ~ 45
are shown in the table on the right.
*Condition: • Indoor fan speed = High
• Outdoor temperature 35°C at the cooling
mode and 7°C at the heating mode
• Compressor operates at rated frequency
105
16.1.1 Relationship between the condition of the air conditioner and pressure and
electric current
Inefficient compression Ò Ô Ô Ò Ô Ô
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
106
16.2 Breakdown Self Diagnosis Function
16.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)
Once abnormality has occurred during operation, 6 When the latest abnormality code on the main
the unit will stop its operation, and Timer LED unit and code transmitted from the remote
blinks. controller are matched, power LED will light
Although Timer LED goes off when power supply up for 30 seconds and a beep sound
is turned off, if the unit is operated under a (continuously for 4 seconds) will be heard. If
breakdown condition, the LED will light up again. no codes are matched, power LED will light up
In operation after breakdown repair, the Timer for 0.5 seconds and no sound will be heard.
LED will no more blink. The last error code 7 The breakdown diagnosis mode will be
(abnormality) will be stored in IC memory. canceled unless pressing the CHECK button
continuously for 5 seconds or operating the
16.2.2 To Make a Diagnosis unit for 30 seconds.
8 The same diagnosis can be repeated by
1 Timer LED start to blink and the unit turning power on again.
automatically stops the operation.
2 Press the CHECK button on the remote
controller continuously for 5 seconds.
3 “- -” will be displayed on the remote controller
display.
Note: Display only for “- -”. (No transmitting
signal, no receiving sound and no Power LED
blinking.)
4 Press the “TIMER” ▲ or ▼ button on the
remote controller. The code “H00” (no
abnormality) will be displayed and signal will
be transmitted to the main unit.
5 Every press of the button (up or down) will
increase abnormality numbers and transmit
abnormality code signal to the main unit.
6 When the latest abnormality code on the main
unit and code transmitted from the remote
controller are matched, power LED will light
up for 30 seconds and a beep sound
(continuously for 4 seconds) will be heard. If 16.2.4 To Clear Memorized Error Code
no codes are matched, power LED will light up after Repair (Protective
for 0.5 seconds and no sound will be heard. Operation)
7 The breakdown diagnosis mode will be
canceled unless pressing the CHECK button 1 Turn power on (in standby condition).
2 Press the AUTO button for 5 seconds (A beep
continuously for 5 seconds or operating the
unit for 30 seconds. receiving sound) on the main unit to operate
8 The LED will be off if the unit is turned off or the unit at Forced Cooling Operation modes.
3 Press the CHECK button on the remote
the RESET button on the main unit is pressed.
controller for about 1 second with a pointed
object to transmit signal to main unit. A beep
16.2.3 To Display Memorized Error sound is heard from main unit and the data is
Code (Protective Operation) cleared.
1 Turn power on.
2 Press the CHECK button on the remote 16.2.5 Temporary Operation (Depending
controller continuously for 5 seconds. On Breakdown Status)
3 “- -” will be displayed on the remote controller
1 Press the AUTO button (A beep receiving
display.
sound) on the main unit to operate the unit.
Note: Display only for “- -”. (No transmitting
signal, no receiving sound and no Power LED (Remote control will become possible.)
2 The unit can temporarily be used until
blinking.)
repaired.
4 Press the “TIMER” ▲ or ▼ button on the
remote controller. The code “H00” (no
abnormality) will be displayed and signal will
be transmitted to the main unit. The power
LED lights up. If no abnormality is stored in
the memory, three beeps sound will be heard.
5 Every press of the button (up or down) will
increase abnormality numbers and transmit
abnormality code signal to the main unit.
107
16.3 Error Code Table
108
109
16.4 Self-diagnosis Method
16.4.1 H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal
transmission is checked whether it is normal.
Malfunction Caused
Faulty indoor unit PCB.
Faulty outdoor unit PCB.
Indoor unit-outdoor unit signal transmission error due to wrong wiring.
Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the
indoor and outdoor units.
Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting
110
16.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched)
Malfunction Decision Conditions
During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit or outdoor unit PCBs mounted.
Indoor unit or outdoor unit PCBs defective.
Indoor-outdoor unit signal transmission error due to wrong wiring.
Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor
and outdoor units.
Troubleshooting
111
16.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor intake air
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
112
16.4.4 H15 (Compressor Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
113
16.4.5 H16 (Outdoor Current Transformer Open Circuit)
Malfunction Decision Conditions
A current transformer (CT) is detected by checking the compressor running frequency (≥ rated frequency) and
CT detected input current (less than 0.65A) for continuously 20 seconds.
Malfunction Caused
CT defective
Outdoor PCB defective
Compressor defective (low compression)
Troubleshooting
114
16.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor
(feedback of rotation > 2550rpm or < 50rpm)
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to Hall IC malfunction.
Operation error due to faulty indoor unit PCB.
Troubleshooting
115
16.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
116
16.4.8 H25 (e-ion Air Purifying System Abnormal)
Malfunction Decision Conditions
During standby of cooling and heating operation, e-ion breakdown occurs and air conditioner stops operation.
Malfunction Caused
Faulty indoor main PCB.
Faulty indoor e-ion power module.
Troubleshooting
117
16.4.9 H27 (Outdoor Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
118
16.4.10 H28 (Outdoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
119
16.4.11 H30 (Compressor Discharge Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
120
16.4.12 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
121
16.4.13 H33 (Unspecified Voltage between Indoor and Outdoor)
Malfunction Decision Conditions
The supply power is detected for its requirement by the indoor/outdoor transmission.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit and outdoor unit PCBs used.
Indoor unit or outdoor unit PCB defective.
Troubleshooting
122
16.4.14 H34 (Outdoor Heat Sink Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor heat sink
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
123
16.4.15 H36 (Outdoor Gas Pipe Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
124
16.4.16 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
125
16.4.17 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor.
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to Hall IC malfunction.
Operation error due to faulty outdoor unit PCB.
Troubleshooting
126
16.4.18 H98 (Indoor High Pressure Protection)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Caused
Air short circuit at indoor unit
Clogged indoor unit air filter
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty indoor unit fan motor
Excessive refrigerant
Clogged expansion valve or strainer
Faulty indoor pipe temperature sensor
Faulty indoor unit PCB
Troubleshooting
127
16.4.19 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Caused
Air short circuit at indoor unit
Clogged indoor unit air filter
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty indoor unit fan motor
Refrigerant shortage (refrigerant leakage)
Clogged expansion valve or strainer
Faulty indoor pipe temperature sensor
Faulty indoor unit PCB
Troubleshooting
128
16.4.20 F11 (4-way valve Abnormality)
Malfunction Decision Conditions
When heating operation, when indoor pipe temperature is below 10°C
When cooling operation, when indoor pipe temperature is above 45°C
Malfunction Caused
Connector in poor contact
Faulty sensor
Faulty outdoor unit PCB
4-way valve defective
Troubleshooting
129
16.4.21 F17 (Indoor Standby Units Freezing Abnormality)
Malfunction Decision Conditions
When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor
pipe temperature is below -1.0°C
Remark:
When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor
unit and H39 to other indoor unit(s).
Malfunction Caused
Wrong wiring connection
Faulty sensor
Faulty expansion valve
Troubleshooting
130
16.4.22 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at
the outdoor unit main PCB senses abnormal high DC voltage level.
Malfunction Caused
DC voltage peak due to power supply surge.
DC voltage peak due to compressor windings not uniform.
Faulty outdoor PCB.
Troubleshooting
131
16.4.23 F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
During cooling, compressor frequency = Fcmax.
During heating, compressor frequency > Fhrated.
During cooling and heating operation, running current: 0.65A < I < 1.65A.
During cooling, indoor intake - indoor pipe < 4°C
During heating, indoor pipe - indoor intake < 5°C
Multi Models Only
Gas shortage detection 1: A gas shortage is detected by checking the CT-detected input current value
and the compressor running frequency. During startup and operating of cooling and heating, input
current < 8.78/256 (A/Hz) x compressor running frequency + 0.25.
Gas shortage detection 2: A gas shortage is detected by checking the difference between indoor pipe
temperature and indoor intake air temperature during cooling and heating.
Malfunction Caused
Faulty indoor intake air or pipe temperature sensor
2/3 way valve closed
Refrigerant shortage (refrigerant leakage)
Clogged expansion valve or strainer
Faulty outdoor unit
Poor compression of compressor
Troubleshooting
132
16.4.24 F93 (Compressor Rotation Failure)
Malfunction Decision Conditions
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuit.
Malfunction Caused
Compressor terminal disconnect
Faulty Outdoor PCB
Faulty compressor
Troubleshooting
133
16.4.25 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
Air short circuit at indoor unit
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty outdoor unit fan motor
Excessive refrigerant
Clogged expansion valve or strainer
Faulty outdoor pipe temperature sensor
Faulty outdoor unit PCB
Troubleshooting
134
16.4.26 F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling and heating, when IPM temperature data (100°C) is detected by the IPM temperature
sensor.
Multi models only
o Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated.
o Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is
detected by the heat sink temperature sensor.
Malfunction Caused
IPM overheats due to short circuit of hot discharge air flow.
IPM overheats due to defective of outdoor fan motor.
IPM overheats due to defective of internal circuitry of IPM.
IPM overheats due to defective IPM temperature sensor.
Multi Models Only
o Compressor OL connector poor contact.
o Compressor OL faulty.
Troubleshooting
135
16.4.27 F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the
compressor tank temperature sensor.
Malfunction Caused
Faulty compressor tank temperature sensor
2/3 way valve closed
Refrigerant shortage (refrigerant leakage)
Faulty outdoor unit PCB
Faulty compressor
Troubleshooting
136
16.4.28 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is
detected by checking the input current value being detected by current transformer (CT) with the compressor
running.
Malfunction Caused
Excessive refrigerant.
Faulty outdoor unit PCB.
Troubleshooting
137
16.4.29 F99 (Output Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an output over-current (DC peak current value at IPM Prevention
Control) is detected by checking the current that flows in the inverter DC peak sensing circuitry.
Malfunction Caused
Faulty outdoor unit PCB
Faulty compressor
Troubleshooting
Tester’s negative terminal Power transistor (+) UVW Power transistor (-) UVW
Tester’s positive terminal UVW Power transistor (+) UVW Power transistor (-)
Normal resistance Several kΩ to several MΩ
Abnormal resistance 0 or ∞
138
17. Disassembly and Assembly Instructions
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.
139
17.1.1.3 To remove discharge grille
140
17.1.1.4 To remove control board
141
142
17.2 CS-E18NK CS-E21NK CS-E24NK CS-E28NK
17.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal
Procedures
143
17.2.1.3 To remove power electronic controller
144
17.2.1.4 To remove discharge grille
145
146
17.3 Outdoor Electronic Controller Removal Procedure
17.3.1 CU-E7NKR CU-E9NKR CU-E12NKR
Caution! When handling electronic controller, be careful of electrostatic discharge.
Fig.1
Fig.4
2 Remove the 8 screws of the Front Panel.
Fig.2
Fig.5
3 Remove the screw of the Terminal Board
Cover.
4 Remove the Top Cover of the Control Board
by 4 hooks.
Fig.6
Fig.3
147
17.3.2 CU-E15NKR CU-E18NKR CU-E21NKR
1 Remove the 4 screws of the Top Panel.
4 Remove the Control Board.
Fig.4
Fig.2
Fig.5
3 Remove the Top Cover of the Electronic
Controller.
Caution! When handling electronic controller, be careful of
electrostatic discharge.
Fig.3
148
17.3.3 CU-E24NKR
1 Remove the 4 screws of the Top Panel. 4 Remove the Control Board.
Fig.4
Fig.2 Fig.5
Fig.3
149
18. Technical Data
18.1 Operation Characteristics
18.1.1 CU-E7NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 7.5m
230 240
18.800
18.300
Temperature (°C)
Outlet Air
17.800
17.300
16.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
2.300
2.100
Capacity (kW)
Cooling
1.900
1.700
1.500
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
2.600
2.400
2.200
Current
(A)
2.000
1.800
1.600
1.400
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
1.400
1.300
Pressure (MPa)
Gas Side Piping
1.200
1.100
1.000
0.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
150
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
17.300
Temperature (°C)
Outlet Air 17.200
17.100
17.000
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.150
Capacity (kW)
2.100
Cooling
2.050
2.000
3 4 5 6 7 8 9 10 11 12 13 14 15
1.250
Pressure (MPa)
Gas Side Piping
1.200
1.150
1.100
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.211
2.209
2.207
Current
2.205
(A)
2.203
2.201
2.199
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
151
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 7.5m
230 240
44.700
42.700
40.700
Temperature (°C)
38.700
36.700
Outlet Air
34.700
32.700
30.700
28.700
26.700
24.700
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.640
3.140
Capacity (kW)
2.640
Heating
2.140
1.640
1.140
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.500
3.300
3.100
Current
2.900
(A)
2.700
2.500
2.300
2.100
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.000
2.800
2.600
Pressure (MPa)
Gas Side Piping
2.400
2.200
2.000
1.800
1.600
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
152
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
34.200
34.100
Temperature (°C)
Outlet Air 34.000
33.900
33.800
33.700
33.600
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.800
2.780
Capacity (kW)
2.760
Heating
2.740
2.720
2.700
3 4 5 6 7 8 9 10 11 12 13 14 15
2.180
2.170
Pressure (MPa)
Gas Side Piping
2.160
2.150
2.140
2.130
2.120
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.950
2.900
Current
2.850
(A)
2.800
2.750
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
153
18.1.2 CU-E9NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 7.5m
230 240
18.000
17.500
Temperature (°C)
17.000
Outlet Air
16.500
16.000
15.500
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
3.000
2.800
Capacity (kW)
2.600
Cooling
2.400
2.200
2.000
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
2.900
2.700
2.500
Current
(A)
2.300
2.100
1.900
1.700
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
1.200
1.100
Pressure (MPa)
Gas Side Piping
1.000
0.900
0.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
154
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
16.000
Temperature (°C)
Outlet Air 15.900
15.800
15.700
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.620
2.600
Capacity (kW)
Cooling
2.580
2.560
2.540
3 4 5 6 7 8 9 10 11 12 13 14 15
1.040
Pressure (MPa)
Gas Side Piping
1.035
1.030
1.025
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.630
2.610
2.590
2.570
Current
(A)
2.550
2.530
2.510
2.490
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
155
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 7.5m
230 240
45.600
43.600
41.600
Temperature (°C)
39.600
37.600
Outlet Air
35.600
33.600
31.600
29.600
27.600
25.600
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
4.500
4.000
Capacity (kW)
3.500
Heating
3.000
2.500
2.000
1.500
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
4.200
4.000
3.800
3.600
Current
3.400
(A)
3.200
3.000
2.800
2.600
2.400
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.300
3.100
2.900
Pressure (MPa)
Gas Side Piping
2.700
2.500
2.300
2.100
1.900
1.700
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
156
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
35.600
35.400
Temperature (°C)
Outlet Air 35.200
35.000
34.800
34.600
34.400
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
3.600
3.550
Capacity (kW)
3.500
Heating
3.450
3.400
3.350
3 4 5 6 7 8 9 10 11 12 13 14 15
2.390
2.370
2.350
Pressure (MPa)
Gas Side Piping
2.330
2.310
2.290
2.270
2.250
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
3.550
3.500
3.450
Current
(A)
3.400
3.350
3.300
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
157
18.1.3 CU-E12NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 7.5m
230 240
17.000
16.500
Temperature (°C)
16.000
Outlet Air
15.500
15.000
14.500
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
3.900
3.700
Capacity (kW)
3.500
Cooling
3.300
3.100
2.900
2.700
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
4.200
4.000
3.800
3.600
Current
(A)
3.400
3.200
3.000
2.800
2.600
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
1.100
1.050
Pressure (MPa)
Gas Side Piping
1.000
0.950
0.900
0.850
0.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
158
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
14.950
14.900
Temperature (°C)
Outlet Air
14.850
14.800
14.750
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
3.520
3.500
Capacity (kW)
3.480
Cooling
3.460
3.440
3.420
3 4 5 6 7 8 9 10 11 12 13 14 15
0.974
0.972
Pressure (MPa)
Gas Side Piping
0.970
0.968
0.966
0.964
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
3.960
3.940
3.920
3.900
Current
3.880
(A)
3.860
3.840
3.820
3.800
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
159
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 7.5m
230 240
50.800
48.800
46.800
44.800
Temperature (°C)
42.800
Outlet Air
40.800
38.800
36.800
34.800
32.800
30.800
28.800
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
6.100
5.600
5.100
Capacity (kW)
4.600
Heating
4.100
3.600
3.100
2.600
2.100
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
6.900
6.400
5.900
Current
(A)
5.400
4.900
4.400
3.900
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.600
3.400
3.200
Pressure (MPa)
Gas Side Piping
3.000
2.800
2.600
2.400
2.200
2.000
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
160
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
40.500
40.000
Temperature (°C)
Outlet Air
39.500
39.000
38.500
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
4.900
4.850
Capacity (kW)
4.800
Heating
4.750
4.700
4.650
4.600
3 4 5 6 7 8 9 10 11 12 13 14 15
2.750
2.700
Pressure (MPa)
Gas Side Piping
2.650
2.600
2.550
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
5.650
5.600
5.550
Current
5.500
(A)
5.450
5.400
5.350
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
161
18.1.4 CU-E15NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 5m
230 240
14.800
14.300
Temperature (°C)
13.800
Outlet Air
13.300
12.800
12.300
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
5.300
5.100
4.900
Capacity (kW)
4.700
Cooling
4.500
4.300
4.100
3.900
3.700
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
6.700
6.200
5.700
Current
5.200
(A)
4.700
4.200
3.700
3.200
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
0.970
0.950
Pressure (MPa)
Gas Side Piping
0.930
0.910
0.890
0.870
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
162
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
13.750
13.700
Temperature (°C)
13.650
Outlet Air
13.600
13.550
13.500
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
4.500
4.400
Capacity (kW)
Cooling
4.300
4.200
4.100
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0.960
0.950
0.940
Pressure (MPa)
Gas Side Piping
0.930
0.920
0.910
0.900
0.890
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
5.500
5.450
5.400
5.350
Current
(A)
5.300
5.250
5.200
5.150
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
163
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 7.5m
230 240
53.700
51.700
49.700
Temperature (°C)
47.700
45.700
Outlet Air
43.700
41.700
39.700
37.700
35.700
33.700
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
7.200
6.200
Capacity (kW)
5.200
Heating
4.200
3.200
2.200
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
8.400
7.900
7.400
Current
6.900
(A)
6.400
5.900
5.400
4.900
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.800
3.600
3.400
Pressure (MPa)
Gas Side Piping
3.200
3.000
2.800
2.600
2.400
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
164
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
41.500
41.000
Temperature (°C)
40.500
Outlet Air
40.000
39.500
39.000
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
5.600
5.400
Capacity (kW)
Heating
5.200
5.000
4.800
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2.900
2.800
Pressure (MPa)
Gas Side Piping
2.700
2.600
2.500
2.400
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
6.800
6.600
6.400
Current
(A)
6.200
6.000
5.800
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
165
18.1.5 CU-E18NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 5m
230 240
16.200
15.700
Temperature (°C)
15.200
Outlet Air
14.700
14.200
13.700
13.200
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
6.200
5.700
Capacity (kW)
Cooling
5.200
4.700
4.200
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
7.100
6.600
6.100
Current
5.600
(A)
5.100
4.600
4.100
3.600
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
0.970
0.950
Pressure (MPa)
Gas Side Piping
0.930
0.910
0.890
0.870
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
166
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
14.850
14.800
Temperature (°C)
Outlet Air 14.750
14.700
14.650
14.600
14.550
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
5.100
5.000
Capacity (kW)
Cooling
4.900
4.800
4.700
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0.960
0.950
0.940
Pressure (MPa)
Gas Side Piping
0.930
0.920
0.910
0.900
0.890
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
6.100
6.050
6.000
5.950
Current
5.900
(A)
5.850
5.800
5.750
5.700
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
167
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 7.5m
230 240
53.400
51.400
49.400
Temperature (°C)
47.400
45.400
Outlet Air
43.400
41.400
39.400
37.400
35.400
33.400
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
8.600
7.600
Capacity (kW)
6.600
Heating
5.600
4.600
3.600
2.600
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
9.300
8.800
8.300
Current
7.800
(A)
7.300
6.800
6.300
5.800
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.500
3.300
Pressure (MPa)
Gas Side Piping
3.100
2.900
2.700
2.500
2.300
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
168
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
40.000
39.500
Temperature (°C)
39.000
Outlet Air
38.500
38.000
37.500
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
6.400
6.200
Capacity (kW)
Heating
6.000
5.800
5.600
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2.700
2.600
Pressure (MPa)
Gas Side Piping
2.500
2.400
2.300
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
8.000
7.800
7.600
Current
7.400
(A)
7.200
7.000
6.800
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
169
18.1.6 CU-E21NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 5m
230 240
15.800
15.300
14.800
Temperature (°C)
14.300
Outlet Air
13.800
13.300
12.800
12.300
11.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
7.300
6.800
Capacity (kW)
6.300
Cooling
5.800
5.300
4.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
8.800
8.300
7.800
Current
(A)
7.300
6.800
6.300
5.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
1.030
0.980
Pressure (MPa)
Gas Side Piping
0.930
0.880
0.830
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
170
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
15.100
14.900
Temperature (°C)
Outlet Air 14.700
14.500
14.300
14.100
13.900
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
6.500
6.400
Capacity (kW)
Cooling
6.300
6.200
6.100
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
0.900
0.800
Pressure (MPa)
Gas Side Piping
0.700
0.600
0.500
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
8.500
8.450
8.400
8.350
Current
8.300
(A)
8.250
8.200
8.150
8.100
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
171
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 7.5m
230 240
52.600
50.600
48.600
Temperature (°C)
46.600
Outlet Air
44.600
42.600
40.600
38.600
36.600
34.600
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
9.200
8.200
7.200
Capacity (kW)
Heating
6.200
5.200
4.200
3.200
2.200
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
10.600
10.100
9.600
9.100
Current
8.600
(A)
8.100
7.600
7.100
6.600
6.100
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.800
3.600
3.400
Pressure (MPa)
Gas Side Piping
3.200
3.000
2.800
2.600
2.400
2.200
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
172
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
40.600
39.600
Temperature (°C)
38.600
Outlet Air
37.600
36.600
35.600
34.600
33.600
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
7.700
7.200
Capacity (kW)
6.700
Heating
6.200
5.700
5.200
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
3.000
2.800
Pressure (MPa)
Gas Side Piping
2.600
2.400
2.200
2.000
1.800
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
9.300
8.800
8.300
Current
7.800
(A)
7.300
6.800
6.300
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
173
18.1.7 CU-E24NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 5m
230 240
14.200
13.700
Temperature (°C)
13.200
Outlet Air
12.700
12.200
11.700
11.200
10.700
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
7.900
7.400
Capacity (kW)
6.900
Cooling
6.400
5.900
5.400
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
9.800
9.300
8.800
Current
(A)
8.300
7.800
7.300
6.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
1.020
0.970
Pressure (MPa)
Gas Side Piping
0.920
0.870
0.820
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
174
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
13.800
13.600
Temperature (°C)
Outlet Air 13.400
13.200
13.000
12.800
12.600
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
7.300
7.200
Capacity (kW)
Cooling
7.100
7.000
6.900
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
0.920
0.870
0.820
Pressure (MPa)
Gas Side Piping
0.770
0.720
0.670
0.620
0.570
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
9.900
9.800
9.700
Current
(A)
9.600
9.500
9.400
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
175
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 5m
230 240
55.100
53.100
51.100
Temperature (°C)
49.100
47.100
Outlet Air
45.100
43.100
41.100
39.100
37.100
35.100
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
10.400
9.400
8.400
Capacity (kW)
7.400
Heating
6.400
5.400
4.400
3.400
2.400
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
12.000
11.000
10.000
Current
(A)
9.000
8.000
7.000
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
3.800
Pressure (MPa)
Gas Side Piping
3.300
2.800
2.300
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
176
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
43.000
41.000
Temperature (°C)
Outlet Air
39.000
37.000
35.000
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
8.300
7.800
Capacity (kW)
7.300
Heating
6.800
6.300
5.800
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
3.100
2.900
Pressure (MPa)
Gas Side Piping
2.700
2.500
2.300
2.100
1.900
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
10.800
10.300
9.800
9.300
Current
(A)
8.800
8.300
7.800
7.300
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
177
18.1.8 CU-E28NKR
Cooling Characteristic
[Condition] Indoor temperature: 27/19°C
Remote condition: High fan speed
Comp. Hz: Fc
Piping Length: 5m
230 240
14.200
13.700
Temperature (°C)
13.200
Outlet Air
12.700
12.200
11.700
11.200
10.700
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
9.100
8.600
Capacity (kW)
8.100
Cooling
7.600
7.100
6.600
6.100
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
11.400
10.900
10.400
Current
9.900
(A)
9.400
8.900
8.400
7.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
0.970
0.920
Pressure (MPa)
Gas Side Piping
0.870
0.820
0.770
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor Air Temperature (°C)
178
Piping Length Characteristic
[Condition] Indoor temperature: 27/19°C, 35/-°C
Remote condition: High fan speed
Comp. Hz: Fc
230 240
13.800
13.600
Temperature (°C)
Outlet Air 13.400
13.200
13.000
12.800
12.600
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
8.200
8.100
Capacity (kW)
Cooling
8.000
7.900
7.800
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
0.840
0.790
Pressure (MPa)
Gas Side Piping
0.740
0.690
0.640
0.590
0.540
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
11.500
11.400
11.300
11.200
Current
(A)
11.100
11.000
10.900
10.800
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
179
Heating Characteristic
[Condition] Indoor temperature: 20/-°C
Remote condition: High fan speed
Comp. Hz: Fh
Piping Length: 5m
230 240
55.100
53.100
51.100
Temperature (°C)
49.100
47.100
Outlet Air
45.100
43.100
41.100
39.100
37.100
35.100
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
11.700
10.700
9.700
Capacity (kW)
8.700
Heating
7.700
6.700
5.700
4.700
3.700
2.700
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
14.400
13.400
12.400
Current
(A)
11.400
10.400
9.400
8.400
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
4.400
3.900
Pressure (MPa)
Gas Side Piping
3.400
2.900
2.400
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
Outdoor Air Temperature (°C)
180
Piping Length Characteristic
[Condition] Indoor temperature: 20/-°C, 7/6°C
Remote condition: High fan speed
Comp. Hz: Fh
230 240
42.000
41.000
40.000
Temperature (°C)
Outlet Air 39.000
38.000
37.000
36.000
35.000
34.000
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
9.500
9.000
Capacity (kW)
8.500
Heating
8.000
7.500
7.000
6.500
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
3.200
3.000
Pressure (MPa)
Gas Side Piping
2.800
2.600
2.400
2.200
2.000
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
12.800
12.300
11.800
11.300
Current
10.800
(A)
10.300
9.800
9.300
8.800
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Piping Length (m)
181
18.2 Sensible Capacity Chart
CU-E7NKR
CU-E9NKR
182
CU-E12NKR
CU-E15NKR
183
CU-E18NKR
CU-E21NKR
184
CU-E24NKR
CU-E28NKR
185
19. Exploded View and Replacement Parts List
19.1 Indoor Unit
19.1.1 CS-E7NKR CS-E9NKR CS-E12NKR CS-E15NKR
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
186
REF
PART NAME & DESCRIPTION QTY. CS-E7NKR CS-E9NKR CS-E12NKR CS-E15NKR REMARK
NO.
1 CHASSIS COMPLETE 1 CWD50C1653 ← ← ←
2 FAN MOTOR 1 ARW7628AC ← ← ARW7627AC O
3 CROSS FLOW FAN COMPLETE 1 CWH02C1076 ← ← ←
4 BEARING ASS’Y 1 CWH64K1006 ← ← ←
5 SCREW - CROSS FLOW FAN 1 CWH551146 ← ← ←
6 ION GENERATOR 1 CWH94C0043 ← ← ←
7 EVAPORATOR 1 CWB30C4225 CWB30C4210 CWB30C3741 CWB30C3363
8 FLARE NUT (LIQUID) 1 CWT251030 ← ← ←
9 FLARE NUT (GAS) 1 CWT251031 ← CWT251073 ←
10 HOLDER SENSOR 1 CWH32143 ← ← ←
11 CONTROL BOARD CASING 1 CWH102449 ← ← ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2357 ← ← ← O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C6997 CWA73C6998 CWA73C6999 CWA73C6937 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← ← ← O
15 ELECTRONIC CO. - INDICATOR & RECEIVER 1 CWA746634 ← ← ← O
16 SENSOR COMPLETE 1 CWA50C2122 ← ← ← O
17 SENSOR COMPLETE (ECO) 1 CWA50C2809 ← ← ← O
18 ELECTRONIC CONTROLLER (ECO SENSOR-L) 1 CWA745791 ← ← ← O
19 ELECTRONIC CONTROLLER (ECO SENSOR-R) 1 CWA746206 ← ← ← O
20 ELECTRONIC CONTROLLER (COMPARATOR) 1 CWA746653 ← ← ← O
21 LEAD WIRE - PCB ECO 1 CWA67C9785 ← ← ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407 ← ← ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ← ← ←
24 INDICATOR HOLDER 1 CWD933406 ← ← ←
25 CONTROL BOARD FRONT COVER 1 CWH13C1247 ← ← ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3235 ← ← ←
27 BACK COVER CHASSIS 1 CWD933233 ← ← ←
28 FULCRUM 1 CWH621131 ← ← ←
29 VERTICAL VANE 8 CWE241374 ← ← ←
30 CONNECTING BAR 1 CWE261250 ← ← ←
31 CONNECTING BAR 1 CWE261256 ← ← ←
32 AIR SWING MOTOR 1 CWA98K1016 ← ← ← O
33 AIR SWING MOTOR 1 CWA981264 ← ← ← O
34 CAP - DRAIN TRAY 1 CWH521096 ← ← ←
35 HORIZONTAL VANE 1 CWE24C1385 ← ← ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4143 ← ← ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5445 ← ← ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1723 ← ← ←
39 GRILLE DOOR 1 CWE14C1090 ← ← ←
40 AIR FILTER 2 CWD001279 ← ← ←
41 SCREW - FRONT GRILLE 3 XTT4+16CFJ ← ← ←
42 CAP - FRONT GRILLE 2 CWH521227 ← ← ←
43 DRAIN HOSE 1 CWH851173 ← ← ←
44 INSTALLATION PLATE 1 CWH361134 ← ← ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ← ← ←
46 REMOTE CONTROL COMPLETE (BACKLIT) 1 CWA75C4151 ← ← ←
50 BAG 1 CWG861497 ← ← ←
51 SHOCK ABSORBER (LEFT) 1 CWG713386 ← ← ←
52 SHOCK ABSORBER (RIGHT) 1 CWG713387 ← ← ←
53 C.C. CASE 1 CWG567355 ← ← ←
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
187
19.1.2 CS-E18NKR CS-E21NKR CS-E24NKR CS-E28NKR
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
188
REF
PART NAME & DESCRIPTION QTY. CS-E18NKR CS-E21NKR CS-E24NKR CS-E28NKR REMARK
NO.
1 CHASSIS COMPLETE 1 CWD50C1623 ← ← ←
2 FAN MOTOR 1 ARW7627AC ← ← ← O
3 CROSS FLOW FAN COMPLETE 1 CWH02C1077 ← ← ←
4 BEARING ASS’Y 1 CWH64K1006 ← ← ←
5 SCREW - CROSS FLOW FAN 1 CWH551146 ← ← ←
6 ION GENERATOR 1 CWH94C0043 ← ← ←
7 EVAPORATOR 1 CWB30C2900 CWB30C4226 CWB30C4227 CWB30C3855
8 FLARE NUT (LIQUID) 1 CWT251030 ← ← ←
9 FLARE NUT (GAS) 1 CWT251032 ← CWT251033 ←
10 HOLDER SENSOR 1 CWH32143 ← ← ←
11 CONTROL BOARD CASING 1 CWH102449 ← ← ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2357 ← ← ← O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C6938 CWA73C6941 CWA73C6942 CWA73C6945 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← ← ← O
15 ELECTRONIC CO. - INDICATOR & RECEIVER 1 CWA747271 ← ← ← O
16 SENSOR COMPLETE 1 CWA50C2122 ← CWA50C2782 ← O
17 SENSOR COMPLETE (ECO) 1 CWA50C2826 ← ← ← O
18 ELECTRONIC CONTROLLER (ECO SENSOR-L) 1 CWA745791 ← ← ← O
19 ELECTRONIC CONTROLLER (ECO SENSOR-R) 1 CWA746206 ← ← ← O
20 ELECTRONIC CONTROLLER (COMPARATOR) 1 CWA746653 ← ← ← O
21 LEAD WIRE - PCB ECO 1 CWA67C9934 ← ← ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407A ← ← ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ← ← ←
24 INDICATOR HOLDER 1 CWD933406 ← ← ←
25 CONTROL BOARD FRONT COVER 1 CWH13C1247 ← ← ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3242 ← ← ←
27 BACK COVER CHASSIS 1 CWD933031 ← ← ←
28 FULCRUM 2 CWH621138 ← ← ←
29 VERTICAL VANE 11 CWE241374 ← ← ←
30 CONNECTING BAR (RIGHT) 1 CWE261257 ← ← ←
31 CONNECTING BAR (LEFT) 1 CWE261258 ← ← ←
33 AIR SWING MOTOR 1 CWA98K1018 ← ← ← O
32 AIR SWING MOTOR 1 CWA981241 ← ← ← O
34 CAP - DRAIN TRAY 1 CWH521096 ← ← ←
35 HORIZONTAL VANE 1 CWE24C1392 ← ← ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4143 ← ← ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5452 CWE11C5446 ← ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1728 ← ← ←
39 GRILLE DOOR 1 CWE14C1090 ← ← ←
40 AIR FILTER 2 CWD001283 ← ← ←
41 SCREW - FRONT GRILLE 3 XTT4+16CFJ ← ← ←
42 CAP - FRONT GRILLE 3 CWH521227 ← ← ←
43 DRAIN HOSE 1 CWH851173 ← ← ←
44 INSTALLATION PLATE 1 CWH361098 ← ← ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ← ← ←
46 REMOTE CONTROL COMPLETE (BACKLIT) 1 CWA75C4151 ← ← ←
50 BAG 1 CWG861498 ← ← ←
51 SHOCK ABSORBER (LEFT) 1 CWG713402 ← ← ←
52 SHOCK ABSORBER (RIGHT) 1 CWG713403 ← ← ←
53 C.C. CASE 1 CWG567455 ← ← ←
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
189
19.2 Outdoor Unit
19.2.1 CU-E7NKR CU-E9NKR CU-E12NKR
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
190
REF. NO. DESCRIPTION & NAME QTY. CU-E7NKR CU-E9NKR CU-E12NKR REMARK
1 BASE PAN ASS'Y 1 CWD52K1277 ← ←
2 SOUND PROOF MATERIAL 1 CWG302314 CWG302719 ←
3 FAN MOTOR BRACKET 1 CWD541167 ← ←
4 SCREW - FAN MOTOR BRACKET 2 CWH551217 ← ←
5 FAN MOTOR 1 ARS6411AC ← ← O
6 SCREW - FAN MOTOR MOUNT 4 CWH55252J ← ←
7 PROPELLER FAN ASS’Y 1 CWH03K1066 ← ←
8 NUT - PROPELLER FAN 1 CWH56053J ← ←
9 COMPRESSOR 1 5RS092XCD21 5RS102XNA21 ← O
10 ANTI - VIBRATION BUSHING 3 CWH50077 ← ←
11 NUT - COMPRESSOR MOUNT 3 CWH56000J ← ←
12 CONDENSER COMPLETE 1 CWB32C3637 CWB32C3218 ←
13 CAPILLARY TUBE ASSY 1 CWB15K1398 CWT01C5681 CWT01C5680
14 DISCHARGE MUFFLER 1 CWB121010 ← ←
15 HOLDER - COUPLING 1 CWH351233 ← ←
16 2 WAYS VALVE (LIQUID) 1 CWB021564 CWB021400 ← O
17 3 WAYS VALVE (GAS) 1 CWB011581 CWB011374 CWB011367 O
19 REACTOR 1 G0C193J00002 ← ←
20 TERMINAL COVER 1 CWH171039A ← ←
21 NUT - TERMINAL COVER 1 CWH7080300J ← ←
22 SOUND PROOF BOARD 1 CWH151274 ← ←
23A SOUND PROOF MATERIAL 1 CWG302315 CWG302726 ←
23B SOUND PROOF MATERIAL 1 CWG302316 CWG302701 ←
24 SENSOR CO. - COMP TEMP 1 CWA50C2830 ← ← O
26 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7002R CWA73C7003R CWA73C7004R O
27 TERMINAL BOARD ASSY 1 CWA28K1110J ← ← O
28 CABINET SIDE PLATE (R) 1 CWE04C1296 ← ←
29 SENSOR CO. - AIR AND COND TEMP 1 CWA50C2825 ← ← O
30 CABINET SIDE PLATE (L) 1 CWE041580A CWE041579A ←
31 CABINET FRONT PLATE ASSY 1 CWE06C1360 ← ←
32 CABINET TOP PLATE 1 CWE031148A ← ←
34 CONTROL BOARD COVER (R) 1 CWH13C1253 ← ←
38 4 WAYS VALVE 1 CWB001037J ← ←
39 V-COIL COMPLETE 1 CWA43C2447 ← ←
40 WIRE NET 1 CWD041166A ← ←
41 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900 ← ←
42 ELECTRONIC CONT. - DEMAND 1 CWA746558 ← ← O
43 CRANKCASE HEATER 1 CWA341044 ← ←
46 OPERATING INSTRUCTION 1 CWF568746 ← ←
47 INSTALLATION INSTRUCTION 1 CWF615541 ← ←
48 CONTROL BOARD COVER (TOP) 1 CWH131473 ← ←
49 STRAINER 1 CWB11025 - ←
50 HOLDER SENSOR 1 CWH32143 ← ←
51 BAG 1 CWG861078 ← ←
52 BASE BOARD - COMPLETE 1 CWG62C1144 ← ←
53 SHOCK ABSORBER (RIGHT) 1 CWG713415 ← ←
54 SHOCK ABSORBER (LEFT) 1 CWG713416 ← ←
55 C.C. CASE 1 CWG566848 ← ←
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
191
19.2.2 CU-E15NKR CU-E18NKR
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
192
REF. NO. DESCRIPTION & NAME QTY. CU-E15NKR CU-E18NKR REMARK
1 BASE PAN ASS'Y 1 CWD52K1191 ←
2 ANTI - VIBRATION BUSHING 3 CWH50077 ←
3 COMPRESSOR 1 5RD132XFA21 ← O
4 NUT - COMPRESSOR MOUNT 3 CWH56000J ←
5 SOUND PROOF MATERIAL 1 CWG302629 ←
6 FAN MOTOR BRACKET 1 CWD541126 ←
7 FAN MOTOR 1 CWA951620 ← O
8 SCREW - FAN MOTOR BRACKET 3 CWH551217 ←
9 SCREW - FAN MOTOR MOUNT 3 CWH551040J ←
10 PROPELLER FAN ASS’Y 1 CWH001019 ←
11 NUT - PROPELLER FAN 1 CWH561092 ←
12 CONDENSER COMPLETE 1 CWB32C3229 CWB32C3230
14 EXPANSION VALVE 1 CWB051016J ←
15 4 WAYS VALVE 1 CWB001026J ←
16 STRAINER 1 CWB11094 ←
18 HOLDER - COUPLING 1 CWH351227 ←
19 3 WAYS VALVE (GAS) 1 CWB011338 ← O
20 2 WAYS VALVE (LIQUID) 1 CWB021292 ← O
22 SOUND PROOF BOARD 1 CWH151198 ←
23 TERMINAL COVER 1 CWH171039A ←
24 NUT - TERMINAL COVER 1 CWH7080300J ←
25 SENSOR CO. - COMP TEMP 1 CWA50C2656 ← O
26 HOLDER SENSOR 1 CWH711010 ←
27 V-COIL COMPLETE - 4-WAY VALVE 1 CWA43C2169J ←
28 V-COIL COMPLETE - EXP.VALVE 1 CWA43C2257 ←
30 SENSOR CO. - AIR AND COND TEMP 1 CWA50C2517 ←
31 REACTOR 1 G0C153J00007 ←
33 TERMINAL BOARD ASSY 1 CWA28K1110J ← O
38 ELECTRONIC CONTROLLER - MAIN 1 CWA73C6862R CWA73C6927R O
40 CONTROL BOARD COVER (TOP) 1 CWH131333 ←
41 CABINET SIDE PLATE (L) 1 CWE041320A CWE041317A
42 HANDLE 1 CWE161010 ←
43 CABINET SIDE PLATE (R) 1 CWE041318A ←
45 CABINET FRONT PLATE ASSY 1 CWE06K1063 CWE06K1084
46 WIRE NET 1 CWD041128A ←
47 CABINET TOP PLATE 1 CWE031083A ←
48 CONTROL BOARD COVER (R) 1 CWH13C1185 ←
56 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900 ←
58 SOUND PROOF MATERIAL 1 CWG302521 ←
59 SOUND PROOF MATERIAL 1 CWG302656 ←
62 RECEIVER 1 CWB14011 ←
63 CAPACITOR - FM 1 DS461305QP-A ← O
64 CRANKCASE HEATER 1 CWA341044 ←
65 ELECTRONIC CONTROLLER 1 CWH14C8772 ← O
66 OPERATING INSTRUCTION 1 CWF568746 ←
67 INSTALLATION INSTRUCTION 1 CWF615541 ←
68 SOUND PROOF MATERIAL 1 CWG302766 ←
69 SOUND PROOF MATERIAL 1 - CWG302636
70 BAG 1 CWG861154 ←
71 BASE BOARD - COMPLETE 1 CWG62C1082 ←
72 SHOCK ABSORBER (RIGHT) 1 CWG712879 ←
193
73 SHOCK ABSORBER (LEFT) 1 CWG712880 ←
74 C.C. CASE 1 CWG565614 ←
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
194
19.2.3 CU-E21NKR
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
195
REF. NO. DESCRIPTION & NAME QTY. CU-E21NKR REMARK
1 BASE PAN ASS'Y 1 CWD52K1190
2 ANTI - VIBRATION BUSHING 3 CWH50055
3 PACKING 3 CWB81043
4 COMPRESSOR 1 5KD240XAF21 O
5 NUT - COMPRESSOR MOUNT 3 CWH561049
9 FAN MOTOR BRACKET 1 CWD541126
10 FAN MOTOR 1 CWA951671 O
11 SCREW - FAN MOTOR BRACKET 3 CWH551217
12 SCREW - FAN MOTOR MOUNT 3 CWH551040J
13 PROPELLER FAN ASS’Y 1 CWH001019
14 NUT - PROPELLER FAN 1 CWH561092
15 CONDENSER COMPLETE 1 CWB32C2440
16 TUBE ASSY (CAP. TUBE) 1 CWT01C4686
21 RECEIVER 1 CWB14030
22 4 WAYS VALVE 1 CWB001026J
24 HOLDER - COUPLING 1 CWH351057
25 3 WAYS VALVE (GAS) 1 CWB011364 O
26 2 WAYS VALVE (LIQUID) 1 CWB021434 O
27 SOUND PROOF BOARD 1 CWH151277
28 TERMINAL COVER 1 CWH171039A
29 NUT - TERMINAL COVER 1 CWH7080300J
30 SENSOR CO. - COMP TEMP 1 CWA50C2656 O
31 HOLDER SENSOR 1 CWH711010
32 V-COIL COMPLETE 1 CWA43C2169J
35 SENSOR CO. - AIR AND COND TEMP 1 CWA50C2517 O
36 REACTOR 1 G0C452J00002
38 TERMINAL BOARD ASSY 1 CWA28K1076J O
39 TERMINAL BOARD ASSY 1 CWA28K1162 O
40 ELECTRONIC CONTROLLER - MAIN 1 CWA73C6930R O
41 CONTROL BOARD COVER (TOP) 1 CWH131333
42 CABINET SIDE PLATE (L) 1 CWE041317A
43 HANDLE 1 CWE161010
44 CABINET SIDE PLATE (R) 1 CWE041319A
46 CABINET FRONT PLATE ASSY 1 CWE06K1063
47 WIRE NET 1 CWD041128A
48 CABINET TOP PLATE 1 CWE031083A
49 CONTROL BOARD COVER (R) 1 CWH13C1185
51 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900
53 SOUND PROOF MATERIAL 1 CWG302245
54 SOUND PROOF MATERIAL 1 CWG302246
55 CAPACITOR - FM 1 DS461305QP-A O
56 ELECTRONIC CONT. - NOISE FILTER 1 CWA746646
57 CAPILLARY TUBE ASSY 1 CWT027938
58 ELECTRONIC CONTROLLER 1 CWH14C8772 O
59 TERMINAL BOARD ASSY 1 CWA28K1242 O
60 CRANKCASE HEATER 1 CWA341047
61 OPERATING INSTRUCTION 1 CWF568746
62 INSTALLATION INSTRUCTION 1 CWF615541
65 BAG 1 CWG861154
66 BASE BOARD - COMPLETE 1 CWG62C1082
67 SHOCK ABSORBER (RIGHT) 1 CWG712879
196
68 SHOCK ABSORBER (LEFT) 1 CWG712880
69 C.C. CASE 1 CWG565614
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
197
19.2.4 CU-E24NKR
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
198
REF. NO. DESCRIPTION & NAME QTY. CU-E24NKR REMARK
1 BASE PAN ASS'Y 1 CWD52K1190
2 ANTI - VIBRATION BUSHING 3 CWH50055
3 PACKING 3 CWB81043
4 COMPRESSOR 1 5KD240XAF21 O
5 NUT - COMPRESSOR MOUNT 3 CWH561049
9 FAN MOTOR BRACKET 1 CWD541127
10 FAN MOTOR 1 EHDS80C60AC O
11 SCREW - FAN MOTOR BRACKET 3 CWH551217
12 SCREW - FAN MOTOR MOUNT 3 CWH551323
13 PROPELLER FAN ASS’Y 1 CWH00K1006
14 NUT - PROPELLER FAN 1 CWH561092
15 CONDENSER COMPLETE 1 CWB32C3295
16 TUBE ASSY (CAP. TUBE) 1 CWT01C5849
17 DISCHARGE MUFFLER 1 CWB121013
21 RECEIVER 1 CWB14030
22 4 WAYS VALVE 1 CWB001026J
24 HOLDER - COUPLING 1 CWH351057
25 3 WAYS VALVE (GAS) 1 CWB011363 O
26 2 WAYS VALVE (LIQUID) 1 CWB021464 O
27 SOUND PROOF BOARD 1 CWH151277
28 TERMINAL COVER 1 CWH171039A
29 NUT - TERMINAL COVER 1 CWH7080300J
30 SENSOR CO. - COMP TEMP 1 CWA50C2656 O
31 HOLDER SENSOR 1 CWH711010
32 V-COIL COMPLETE 1 CWA43C2169J
35 SENSOR CO. - AIR AND COND TEMP 1 CWA50C2517 O
36 REACTOR 1 G0C452J00002
38 TERMINAL BOARD ASSY 1 CWA28K1076J O
39 TERMINAL BOARD ASSY 1 CWA28K1162 O
40 ELECTRONIC CONTROLLER - MAIN 1 CWA73C6931R O
41 CONTROL BOARD COVER (TOP) 1 CWH131333
42 CABINET SIDE PLATE (L) 1 CWE041317A
43 HANDLE 1 CWE161010
44 CABINET SIDE PLATE (R) 1 CWE041319A
46 CABINET FRONT PLATE ASSY 1 CWE06K1063
47 WIRE NET 1 CWD041128A
48 CABINET TOP PLATE 1 CWE031083A
49 CONTROL BOARD COVER (R) 1 CWH13C1185
51 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900
53 SOUND PROOF MATERIAL 1 CWG302245
54 SOUND PROOF MATERIAL 1 CWG302246
56 ELECTRONIC CONT. - NOISE FILTER 1 CWA746792 O
57 TUBE ASSY (CAP. TUBE & RECEIVER) 1 CWT01C5851
58 ELECTRONIC CONTROLLER 1 CWH14C8772 O
59 TERMINAL BOARD ASSY 1 CWA28K1281 O
60 CRANKCASE HEATER 1 CWA341047
61 OPERATING INSTRUCTION 1 CWF568746
62 INSTALLATION INSTRUCTION 1 CWF615541
64 BAG 1 CWG861154
65 BASE BOARD - COMPLETE 1 CWG62C1081
66 SHOCK ABSORBER (RIGHT) 1 CWG712879
199
67 SHOCK ABSORBER (LEFT) 1 CWG712880
68 C.C. CASE 1 CWG565546
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
200
19.2.5 CU-E28NKR
201
202
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
203
REF. NO. DESCRIPTION & NAME QTY. CU-E28NKR REMARK
1 BASE PAN ASS'Y 1 CWD52K1295
2 COMPRESSOR 1 5KD240XAF21 O
3 ANTI - VIBRATION BUSHING 3 CWH50055
4 NUT - COMPRESSOR MOUNT 3 CWH561049
5 PACKING 3 CWB811017
6 CRANKCASE HEATER 1 CWA341080
7 CONDENSER COMPLETE 1 CWB32C3300
8 SOUND PROOF MATERIAL 1 CWG302246
9 DISCHARGE MUFFLER 1 CWB121013
11 3 WAYS VALVE (GAS) 1 CWB011251 O
12 4 WAYS VALVE 1 CWB001026J
13 2 WAYS VALVE (LIQUID) 1 CWB021330 O
14 STRAINER 2 CWB111032
18 SOUND PROOF MATERIAL 1 CWG302245
19 SOUND PROOF BOARD 1 CWH151294
20 V-COIL COMPLETE - 4-WAY VALVE 1 CWA43C2169J
21 V-COIL COMPLETE - EXP.VALVE 1 CWA43C2128J
23 SENSOR CO. - COMP TEMP 1 CWA50C2656 O
24 SENSOR CO. - AIR AND COND TEMP 1 CWA50C2652 O
25 CABINET REAR PLATE - COMPLETE 1 CWE02C1043
26 CONTROL BOARD A'SSY 1 CWH10K1158
27 TERMINAL BOARD ASSY 1 CWA28K1162 O
28 TERMINAL BOARD ASSY 1 CWA28K1076J O
30 ELECTRONIC CONT. - CAPACITOR 1 CWA746775 O
31 ELECTRONIC CONTROLLER - NF 1 CWA746758 O
33 ELECTRONIC CONTROLLER - MAIN 1 CWA73C6934R O
34 REACTOR 1 G0C452J00002
36 TERMINAL COVER 1 CWH171039A
37 NUT - TERMINAL COVER 1 CWH7080300J
38 FAN MOTOR BRACKET 1 CWD54K1063
39 SCREW - FAN MOTOR BRACKET 2 CWH551040J
40 FAN MOTOR (UPPER) 1 ARW8405AC O
40a FAN MOTOR (BOTTOM) 1 ARW8406AC O
41 SCREW - FAN MOTOR MOUNT 8 CWH55252J
42 PROPELLER FAN ASS’Y 2 CWH03K1065
43 NUT - PROPELLER FAN 2 CWH56053J
44 CABINET FRONT PLATE ASSY 1 CWE06C1408
45 DISCHARGE GRILLE 2 CWE201075
46 CABINET SIDE PLATE ASS'Y 1 CWE04K1022A
47 WIRE NET 1 CWD041129A
48 CABINET TOP PLATE 1 CWE03C1095
49 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900
51 L-SHAPED PLATE (FRONT) 1 CWD601074A
52 L-SHAPED PLATE (BACK) 1 CWD601075A
53 CABINET FRONT PLATE 1 CWE061092A
59 HOLDER SENSOR 3 CWH711010
61 EXPANSION VALVE 1 CWB051018J
62 INSTALLATION INSTRUCTION 1 CWF615542
63 OPERATING INSTRUCTION 1 CWF568746
64 ELECTRONIC CONTROLLER 1 CWA746558 O
65 TERMINAL BOARD ASSY 1 CWA28K1281 O
66 RECEIVER 1 CWB14017
67 BAG 1 CWG861239
68 BASE BOARD - COMPLETE 1 CWG62C1086
69 SHOCK ABSORBER (RIGHT) 2 CWG712852
204
70 SHOCK ABSORBER (LEFT) 1 CWG712854
71 C.C.CASE 1 CWG567822
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
Printed in Malaysia
FB0712 - 0
205