Control Systems Presentation - 3
Control Systems Presentation - 3
1. Step Function
Consider the signal of following figure 1.
The signal of the Fig.1 has zero values for t < 0 and it has a value of ‘A’ for t ≥ 0.
Since the signal look a ‘step’, it is called step function or step signal.
Step function is also called displacement function.
The step signal can be defined mathematically as follows :
f(t) = A for t≥0
=0 for t<0
Unit Step Function [u(t)] Fig.1 : Step signal
A step function is said to be unit step function u(t) if it satisfies two following conditions:
a) The amplitude of unit step function is always equal to unity.
b) Unit step function u(t) is zero wherever t < 0, and is unit when t ≥ 0
The unit step signal can be defined mathematically as follows:
u(t) = 1 for t≥0
=0 for t<0
3. Parabolic Function
The parabolic function is described mathematically by following relation :
r(t) = 0 for t<0
= k.t2 for t≥0
where k is a constant.
5. Impulse Function
The impulse function is a special limiting case of the pulse function.
Consider the impulse function
(t ) lim t0 0 tA for 0 t t0
0
0 for 0 t, t0 t
Since the height of the impulse function is A/to and the duration is to, the area under the
impulse is equal to A.
As the duration to approaches zero, the height A/to approaches infinity, but the area
under the impulse remains equal to A.
Note that the magnitude of the impulse is measured by its area.
The typical time response of a control system for a specified input signal is shown in Fig.1
Steady-State Response
The steady-state response is the part of the total response that response that means
after the transient has died out.
Thus the steady-state response can still vary in a fixed pattern, such as a sine wave
or a ramp function that increases with time
Steady-State Error
The objectives of most control systems are that the system output response follows a
specific reference signal accurately in the steady-state.
The difference between the output and the reference input in the steady state was
defined as the steady-state error
3/25/2022 1:39 PM Applied Physics, University of Calcutta 6
Transient Response of First Order System
The Laplace transform of the unit-ramp function is R(s) = 1/s2, from the first order
system, the output response is given by
1 1 1 T T
Y ( s) 2 2
(T s 1) s s s s 1/ T
Taking the inverse Laplace transform on both
side of the above equation, we have
y (t ) t T Te t / T
Now, the error response of the first order
control system is given by Fig. 4 : Ramp response of 1st order system.
e (t ) r (t ) y (t ) t t T Te t / T T (1 et / T )
The steady-state error is given
The first order system under consideration will track the unit-ramp input with a steady-
state error ‘T’, which is equal to the time constant of the system, as shown in Fig. 4.
The Laplace transform of the unit-impulse input function is R(s) = 1, from the first order
system of Fig.2, the output response can be obtain as
1 1 1
Y ( s) R( s )
1 T s T s 1/ T
Taking the inverse Laplace transform on both
side of the above equation, we have
1 t / T
y (t ) e
T
The response curve given by the above
equation is shown in Fig. 5.
The unit input functions and corresponding time Fig. 5 : Impulse response of the
response of a first-order control system is given 1st order system.
the table below:
Input Functions Time Response Expression Remarks
1. Unit Impulse , 1 y(t) = e - t / T / T Integrate
2. Unit Step , 1/s y(t) = 1 - T e - t / T
3. Unit Ramp , 1/s2 y(t) = t - T + Te - t/T Differentiate
3/25/2022 1:39 PM Applied Physics, University of Calcutta 10
Transient Response of Second-Order Control System
Consider a second-order control system with unit feedback is represented by the
block diagram shown in Fig. 6.
The transfer function of the system is
Y (s) n 2
R( s ) s 2 2n s n 2
Fig. 6 : Block diagram of a second
For a unit-step function input R(s) = 1/s , order control system.
the output response of the system is
n 2 n 2 1 s 2n
Y ( s ) R( s) 2
s 2n s n 2 s ( s 2 2n s n 2 ) s s 2 2n s n 2
1 s n n d
s ( s n ) 2 d 2 1 2 ( s n ) 2 d 2
n
1 s n d s 2 2n s n 2
2 s 2 2 s ( ) 2 2 ( )2
s ( s n ) d
2 2
1 2 ( s ) 2
d
n n n n n
( s n )2 n 2 (1 2 )
n natural frequency d damplig frequency 2
( s n ) d
2
damping ratio n damping factor
where, d n 1 2
3/25/2022 1:39 PM Applied Physics, University of Calcutta 11
Taking the inverse Laplace transform of above equation, we get
n t nt
y (t ) 1 e cos(d t ) e sin(d t )
1 2
Let , cos
1
e nt
1 2 1 2
cos(d t ) sin(d t ) and 1 2 sin
e nt
1 sin cos(d t ) cos sin(d t )
1 2
e nt
1 sin (d t )
1 2
e(t ) r (t ) y (t ) 1 1
e nt
1 2
sin (n 1 2 t cos 1 )
ent
1 2 sin (n 1 2 t cos 1 )
3/25/2022 1:39 PM Applied Physics, University of Calcutta 12
A. Undamped Case ( = 0 ) :
The damping ratio is equal to the response becomes undamped and oscillations
continue indefinitely.
At zero damping i.e. = 0, the output of the system is
y (t ) 1 sin (d t 900 ) 1 cos d t
The time response characteristic of the system is shown in Fig. 7, which indicates
sustained oscillations.
Fig. 8(a) : Time response of a 2nd order system. Fig.8(b) : Error signal of a 2nd order system.
3/25/2022 1:39 PM Applied Physics, University of Calcutta 14
C. Critically Damped Case ( = 1 ) :
The expression for the response of a second order control system having = 1 when
subjected to unit step input function is derived.
Taking limits of the output equation as the value of approaches 1, the equation
derived below is obtained
y (t ) Lim 1 1
e n t
1 2
sin (n 1 2 ) t cos cos (n 1 2 ) t sin
Lim 1 1
e n t
1 2
sin (n 1 2 ) t cos (n 1 2 ) t 1 2
Now,
e n t
y (t ) Lim 1 1
1 2
n 1 2 ) t 1 2
Lim 1 1 e n t nt 1
The time response characteristic of the system is shown in Fig. 9.
The response is called critically damped response.
s1 , s2 2n jn (1 2 )
The roots s1, s2 and also the poles of transfer function expression by the system
transfer function.
The study of roots s1, s2 gives a prediction about the nature of time response.
The real part of the roots represents the damping factor and the imaginary part
represents damping frequency of oscillation.
( s ) s 2 2n s n 2 0
The characteristic equation is quadratic in s and two roots are
s1 , s2 2n jn (1 2 )
When the two roots of the characteristic equation are real and equal, we called the
system critically damped.
The critical damping occurs when = 1.
Under this condition, the damping factor is simply = n.
The ratio between the actual damping factor and the critical damping factor is known
as the damping ratio.
It is denoted by .
Actual damping factor n
Damping ratio,
Critical damping factor n
y (t ) 1
e nt
1 2
sin (n 1 2 t )
At the instant of time tr , the magnitude of response y(tr) = 1, then
1 1
e ntr
1 2
sin (n 1 2 tr )
e ntr
1 2 sin (n 1 2 tr ) 0
sin (n 1 2 tr ) 0
The solution of the equation is
n 1 2 t r
tr
d 1 2
n
The time need to reach the maximum overshoot is called peak time and denoted as tp.
We are obtain the peak time by differentiating y(t) with respect to time and letting this
equal to zero.
Since
d
t
dy (t ) e np
1
dt t t p dt
sin (d t p ) 0
1 2
n t p n t p
e cos (d t p ) d n e sin (d t p ) 0
n e
n t p cos ( t ) 1 2 sin ( t ) 0
d p d p
nt p
In the above equation, since e is finite,
This is the expression for peat time of second order control system.
The maximum positive deviation of the output with respect to its desired value is
known as maximum overshoot and denoted as Mp.
The maximum overshoot occurs at the peak time or at t = tp.
Assuming that the final value of the output is 1, Mp is obtained as follows:
sin (
n t p
e
M P y (t p ) 1 1 n 1 2t p ) 1
1 2
n
e n 1 2
sin ( n 1 )
2
1 2 n 1 2
1 2 1 2 1 2
e e e
sin ( ) sin ) 1 2
1 2 1 2 1 2
1 2
e
1 2
The maximum percent overshoot, %Mp e 100
3/25/2022 1:39 PM Applied Physics, University of Calcutta 27
Steady State Error
The steady-state error is an index of accuracy of a control system.
These error arise from the nature of input, type of the systems and from nonlinearity
of the system components.
The steady state error should be minimizing as far as possible. Consider a closed-loop
control system is shown in Fig. 16
The output of the closed loop system is
G( s)
Y ( s) R( s )
1 G ( s ) H ( s)
The error of the system is Fig. 16 : A closed-loop control system
Y (s) 1 G ( s) 1
E ( s) R(s) R(s)
G ( s) G ( s ) 1 G ( s) H ( s ) 1 G ( s) H ( s)
The steady-state error, may now be found by using of the final-value theorem as
s R( s)
ess limt e(t ) lim s 0 sE ( s ) lim s 0
1 G ( s) H ( s)
The steady-state error possessed by a closed-loop control system depends on the
input and the open-loop transfer function.
3/25/2022 1:39 PM Applied Physics, University of Calcutta 28
Static Error Constants
There are three types of static error constants.
The error constants are depends upon the input of the system.
Static error constants are
1. Static Position Error Constant ( Kp )
2. Static Velocity Error Constant ( Kv )
3. Static Acceleration Error Constant ( Ka )
This transfer function involves the term sN in the denominator, representing a pole of
multiplicity N at the origin.
The classification scheme is based on the number of integrations indicated by the
open-loop transfer function.
A system is called type 0, type 1, type 2,. . . , if N = 0, N = 1, N = 2,. . . , respectively.
Type of the system is increased, then the stability should be effected.
If G(s) is written so that each term in the numerator and denominator, except the
term sN, approaches unity as s approaches zero, then the open-loop gain K is directly
related to the steady-state error
Consider a type ‘1’ system, the open-loop transfer function with a unity feedback
is given by
K (Ta s 1)(Tb s 1)(Tc s 1) (Tm s 1)
G(s)
s (T1s 1)(T2 s 1)(T3 s 1) (Tn s 1)
1 1
ess 0
1 KP 1
Consider a type ‘2’ system, the open-loop transfer function with a unity feedback
is given by
K (Ta s 1)(Tb s 1)(Tc s 1) (Tm s 1)
G(s)
s 2 (T1s 1)(T2 s 1)(T3 s 1) (Tn s 1)
1 1
ess 0
1 KP 1
Table : Static error constants and steady state error in terms of gain K.
s 2 2 n s n 2 0 (2)
Comparing Eqs. (1) and (2), we get
n2 100 and 2 n 10
n 10 rad./ s 0.5
3/25/2022 1:39 PM Applied Physics, University of Calcutta 40
Natural frequency, n 10 rad ./ s
Damping ratio, 0.5
Damping factor, n 5 rad ./ s
Damping frequency, d n 1 2 10 1 0.25 8.66 rad ./ s
cos1 (0.5)
Rise time, tr 0.24 s
n 1 2 10 1 0.25
Peak time, tp 0.36 s
n 1 2 10 1 0.25
0.5
1 2
Maximum overshoot, % M p e 100 e 0.75
100 16.35%
4 4
Settling time, ts 0.8 s ( for 2% error )
n 0.5 10
Let us consider K1 for 75% overshoot and K2 for 25% overshoot, while T remains constant
in both the cases.
1 1/ 2 K1T K2 0.091
0.2254
2 1/ 2 K 2T K1 0.4037
K2
0.0508
K1
K1
20.
K2
The amplifier gain has to be reduced by a factor 20.