Configuration Data Sheet
August 2023
Rosemount 3051
00806-0100-4007, Rev CD
Rosemount™ 3051 Pressure Transmitter with 4–20 mA
HART®
Use this sheet for all 3051C, 3051L, and 3051CFx products with Enhanced Software (Option RK).
BOLD = Required value ◯ Select only one of the items provided
★= Default □ One or more of the listed items can be selected
Customer information
Customer: _____________________________________________________________________ Contact name: ___________________________________________________________________
Phone no:______________________________________________________________________ Fax no./email: ____________________________________________________________________
P.O./reference no.:_____________________________________________________________ P.O. line item: _____________________________________________________________________
Quote no.:______________________________________________________________________ Model no.: _______________________________________________________________________
Customer sign-off:_________________________________________________________________________________________________________________________________________________
Tagging
Hardware tag: ___________________________________________________________________________________________________________ (56 characters)
Software tag: ____________________________________________________________________________________________________________ (8 characters)
Long software tag: _______________________________________________________________________________________________________ (32 characters)
Output information
Pressure units:(1) inH2O at 68 °F★ ftH20 at 68 °F inHg at 0 °C Atm MPa g/cm2
inH2O at 4 °C mmH20 at 4 °C mmHg at 0 °C Torr Bar kg/cm2
inH2O at 60 °F mmH20 at 68 °C cmHg at 0 °C Pa mBar kg/m2
ftH2O at 4 °C cmH20 at 4 °C mHg at 0 °C hPa lb/ft2
ftH20 at 60 °F mH20 at 4 °C Psi kPa
Transfer function: Linear★ Square Root
Range points: 4 mA =__________________________________ (0★) 20 mA = ___________________________ (URL★)
1. Default values may be different outside the U.S.A. Consult an Emerson Representative.
Note
Custom configuration information below this note requires C1 option code.
Rosemount 3051 August 2023
Transmitter information
Descriptor: _______________________________________________________________________________________________________________ (16 characters)
Message: ________________________________________________________________________________________________________________ (32 characters)
Date: ____________________________ (date of calibration★)
Output information
Sensor Temperature units: °C★ °F Damping(1) (0-60 sec): ________________ (0.4 sec.)
1. For Range 0 default damping value is 3.2 seconds.
Display Parameters
✔ Pressure★ Percent of Range Level Volume
Flow rate Totalized Flow Alarm Switch State(2) Security Status(2)
Review parameters at startup(1) Hart Long Tag(2) Sensor Temperature
1. LCD Display with Local Operator Interface (M4 option) or LCD Display (M5 Option) Only.
2. Graphical LCD Display (M6 Option).
Graphical LCD Display Settings(1)
Language Selection Backlight GP/AP Unit Label Decimal Separator Bluetooth(2)
English★ Italian On★ Disable★ Period★ Enable★
French Portuguese Off Enable Comma Disable
German Chinese
Spanish Russian
1. Graphical LCD Display (M6 Option) Only.
2. Bluetooth Configuration and Maintenance (BLE Option) Only.
Process variable output assignments
Primary Variable: Pressure★ Flow Rate Totalized Flow Level Volume
Secondary Variable: Pressure Flow Rate Totalized Flow Level Volume Sensor Module Temperature★
Tertiary Variable: Pressure Flow Rate Totalized Flow Level Volume Sensor Module Temperature★
Security information
Hardware Security Switch: Enable Disabled★ Configuration Buttons(1): Enable★ Disabled
Local Operator Interface Password(2): Enable Disabled★ Software Security: Enable Disabled★
Password (4 digits)(2): _________________
1. Requires Quick Service Buttons (option D1), Analog Zero and Span (option D4), Digital Zero Trim (option DZ), or LCD with Local Operator Interface (Option M4).
2. Requires LCD with Local Operator Interface (M4 Option).
2
August 2023 Rosemount 3051
Custom Alarm and Saturation Signal Levels
Alarm: Values (mA) the transmitter outputs if it detects a gross malfunction condition.
Saturation: Values (mA) the transmitter outputs if applied pressure goes outside the 4-20 mA range values.
Alarm and Saturation levels are defined by option codes: Alarm Value: Saturation value:
21.75 mA = 20.80 mA
No option = Standard, High
CT = Standard, Low 3.725 mA = 3.90 mA
C4 = NAMUR, High 22.50 mA = 20.50 mA
CN = NAMUR, Low 3.575 mA = 3.80 mA
CR = Custom, High Enter Value (20.20 to 23.00) ____________ (mA)(1) (20.10 to 22.90) _______________ (mA)
CS = Custom, Low Enter Value (3.57 to 3.80) _______________ (mA) (3.67 to 3.90) __________________ (mA)(1)
1. High alarm must be 0.1 mA greater than high saturation value, and low saturation must be 0.1 mA greater than low alarm value.
Process Alert 1
Units of measure will automatically be set to match the previous settings for the Monitored Device Variable. Pressure along with any of the inferred process
variable alerts will be limited to the range of the transmitter. Temperature alerts are limited to -40 to 185 °F (-40 to 85 °C) with a minimum 9 °F (5 °C) difference
required between low and high alert.
Monitored Device Variable:
Pressure★ Flow Rate Totalized Flow Level Volume Sensor Module Temperature
Alert Name ____________________ (14 Characters)
Activation Trigger: Above High Side Below Low Side Inside Window Outside Window
Process alert set points define the boundaries for a designated alert window. Alerts can be set to trigger with respect to the alert window. Above the high side alert only requires a High
Alert set point and below the low side only requires a Low Alert set point. Both set points are required for inside or outside window triggers.
High Alert Value ________________ Low Alert Value _______________
Alert values are limited to the range of the transmitter and will have units of measure that are defined by the selected Monitored Device Variable. High alert must be greater than alert.
Notification Mode: Analog Output Alarm HART Status Alert Disable★
Sporadic Alert Reduction: None★ Time Delay ____________ seconds Deadband __________
Sporadic Alert Reduction Methods can be used to introduce a buffer in either time (via Time Delay 30 s maximum) or measured process variable (via Deadband) to create a buffer
between the process alert limit and alert deactivation. Deadband units of measure will automatically be set to match the previous settings for the Monitored Device Variable.
Process Alert 2
Units of measure will automatically be set to match the previous settings for the Monitored Device Variable. Pressure along with any of the inferred process
variable alerts will be limited to the range of the transmitter. Temperature alerts are limited to -40 to 185 °F (-40 to 85 °C) with a minimum 9 °F (5 °C) difference
required between low and high alert.
Monitored Device Variable:
Pressure Flow Rate Totalized Flow Level Volume Sensor Module Temperature★
Alert Name ____________________ (14 Characters)
Activation Trigger: Above High Side Below Low Side Inside Window Outside Window
Process alert set points define the boundaries for a designated alert window. Alerts can be set to trigger with respect to the alert window. Above the high side alert only requires a High
Alert set point and below the low side only requires a Low Alert set point. Both set points are required for inside or outside window triggers.
High Alert Value ________________ Low Alert Value _______________
Alert values are limited to the range of the transmitter and will have units of measure that are defined by the selected Monitored Device Variable. High alert must be greater than alert.
Notification Mode: Analog Output Alarm HART Status Alert Disable★
Sporadic Alert
None★ Time Delay ____________ seconds Deadband __________
Reduction:
Sporadic Alert Reduction Methods can be used to introduce a buffer in either time (via Time Delay 30 s maximum) or measured process variable (via Deadband) to create a buffer
between the process alert limit and alert deactivation. Deadband units of measure will automatically be set to match the previous settings for the Monitored Device Variable.
3
Rosemount 3051 August 2023
Application Specific Configuration
Application Specific Configuration is used to translate the pressure measurement to either a flow rates output or to a level output. Provide configuration
details for any variable that will be displayed or set as an output variable. Flow rate configuration is required to support flow totalizer operation and level
configuration is required to support volume operation.
Flow Rate
Flow rate units ____________ (6 characters max)
Pressure at Flow Rate: _____________ (Pressure Units)
Entered Flow Rate: _____________ (Flow Rate Units)
Pressure Cut-off: _____________ (Pressure Units)
Pressure Cut-in: _____________ (Pressure Units)
If the measured pressure is less than the cut-off value, the device will calculate zero flow.
If the measured pressure is greater that the cut-in value, the device will begin measuring the flow rate.
Range Values (required if flow rate is set to primary variable)
Lower Range Value (4 mA) _____________ (Flow Rate Units) Upper Range Value (20 mA) _____________ (Flow Rate Units)
Flow Totalizer (flow rate section must be completed)
Totalizer Mode: Totalizing Stopped★
Direction: Forward Flow Only★ Reverse Flow Only Gross (Forward + Reverse) Net (Forward - Reverse)
Totalizer Units: _______________ (6 characters max, this value should match the user defined flow units)
Flow Unit of Time Seconds★ Minutes Hours Days (Unit of time associated with the flow rate)
Unit Conversion Factor ____________
To totalize in the same units as flow, enter a value of 1. Example: if the flow unit is “lb/sec” and the totalizer unit is “lbs”, enter 1. To totalize in a different unit than flow, take the flow unit
dividend by the desired totalizer unit and enter the result in the Unit Conversion Factor box. Example: If flow unit is “gallons/sec” and the totalize unit is “thousands of gallons”, enter
0.001 (0.001=1 gallon/100 gallons).
Range Values (required if totalized flow is set to primary variable)
Lower Range Value (4 mA) _____________ (Totalizer Units) Upper Range Value (20 mA) _____________ (Totalizer Units)
4
August 2023 Rosemount 3051
Application Specific Configuration
Level
Level Units: Feet Inches★ Meters Centimeters Milimeters
Maximum Level: _____________ (Level Units)
Pressure at Maximum Level: _____________ (Pressure Units)
Minimum Level: _____________ (Level Units)
Pressure at Minimum Level: _____________ (Pressure Units)
Range Values (required if Level is set to primary variable)
Lower Range Value (4 mA) _____________ (Level Units)
Upper Range Value (20 mA) _____________ (Level Units)
Volume (Level section and strapping table must be completed)
Volume units: Gallons Imperial gallons Barrels Cubic yards Cubic feet Cubic inches★
Liters Cubic meters
Strapping table
Level and volume units of measure for the values entered below are defined in the level and volume sections above.
Entries must be greater than 0; monotonic with increasing values for both level and volume.
A minimum of 2 rows of data is required in the strapping table.
Factory configuration is limited to 10 points, the device can be configured with up to 50 points in the field.
Strapping Point Level Volume
0 _____________ _____________
1 _____________ _____________
2 _____________ _____________
3 _____________ _____________
4 _____________ _____________
5 _____________ _____________
6 _____________ _____________
7 _____________ _____________
8 _____________ _____________
9 _____________ _____________
Range values (required if volume is set to primary variable)
Lower Range Value (4 mA) _____________ (Volume Units) Upper Range Value (20 mA) _____________ (Volume Units)
5
Rosemount 3051 Configuration Data Sheet
00806-0100-4007, Rev CD August 2023