GINLONG TECHNOLOGIES CO.,LTD.
S6-GR1P(2.5-6)K-S
Solis Single Phase Grid-Tied Inverters
Features:
• String current up to 16A
• Integrated with zero export power control function
• Light weight with compact design for easy installation
• 2 MPPT design with precise MPPT algorithm
Models:
英语
S6-GR1P2.5K-S / S6-GR1P3K-S
S6-GR1P3.6K-S / S6-GR1P4K-S NEW
S6-GR1P4.6K-S / S6-GR1P5K-S
S6-GR1P6K-S
www.solisinverters.com
DATASHEET S6-GR1P(2.5-6)K-S
Models 2.5K 3K 3.6K 4K 4.6K 5K 6K
Input DC
Recommended max. PV power 3.75 kW 4.5 kW 5.4 kW 6 kW 6.9 kW 7.5 kW 9 kW
Max. input voltage 550 V
Rated voltage 250 V 330 V
Start-up voltage 60 V 100 V
MPPT voltage range 50-550 V 90-550 V
Max. input current 16 A / 16 A
Max. short circuit current 22 A / 22 A
MPPT number/Max. input strings number 2/2
Output AC
Rated output power 2.5 kW 3 kW 3.6 kW 4 kW 4.6 kW 5 kW 6 kW
Max. apparent output power 2.5 kVA 3 kVA 3.6 kVA 4 kVA 4.6 kVA 5 kVA 6 kVA
Max. output power 2.5 kW 3 kW 3.6 kW 4 kW 4.6 kW 5 kW 6 kW
Rated grid voltage 1/N/PE, 220 V / 230 V
Rated grid frequency 50 Hz / 60 Hz
Rated grid output current 11.4 A / 10.9 A 13.6 A / 13 A 16 A / 15.7 A 18.2 A / 17.4 A 20.9 A / 20 A 22.7 A / 21.7 A 27.3 A / 26.1 A
Max. output current 11.4 A 13.6 A 16 A 18.2 A 20.9 A 22.7 A 27.3 A
Power factor >0.99 (0.8 leading - 0.8 lagging)
THDi <3%
Efficiency
Max. efficiency 97.3% 97.3% 97.6% 97.7%
EU efficiency 96.5% 96.6% 97.1% 97.1%
Protection
DC reverse-polarity protection Yes
Short circuit protection Yes
Output over current protection Yes
Surge protection Yes
Grid monitoring Yes
Anti-islanding protection Yes
Temperature protection Yes
Integrated AFCI (DC arc-fault circuit protection) Yes (1)
Integrated DC switch Yes
General Data
Dimensions (W*H*D) 330*371*161 mm
Weight 8.2 kg 8.3 kg 8.9 kg 9 kg
Topology Transformerless
Self-consumption (night) <1 W
Operating ambient temperature range -25 ~ +60°C
Relative humidity 0-100%
Ingress protection IP66
Cooling concept Natural convection
Max. operation altitude 4000 m
G98 or G99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1, VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 /
Grid connection standard
UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, EIFS 2018.2, IEC 62116, IEC 61727, IEC60068, IEC 61683, EN 50530, MEA, PEA
Safety/EMC standard IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-3
Features
DC connection MC4 connector
AC connection Quick connection plug
Display LED + APP
Communication RS485, USB, Optional: Wi-Fi, GPRS
(1) Activation required.