POS8.4420/109; POS8.

4440/109
Room operator units
Basic Documentation

A6V11471220_en--_e

2021-09-06
Table of Contents

1 About this document ....................................................................................3


1.1 Revision history ...............................................................................................3
1.2 Before you start ...............................................................................................3
1.3 Reference documents .....................................................................................4
2 Product overview ..........................................................................................5
2.1 Type summary .................................................................................................5
2.1.1 Equipment combinations .................................................................5
2.2 Features ..........................................................................................................5
2.3 System topology ..............................................................................................5
2.4 Mechanical design ...........................................................................................6
2.5 Diagrams .........................................................................................................6
2.5.1 Connection terminals .......................................................................6
2.5.2 Connection diagrams .......................................................................7
2.6 Dimensions ......................................................................................................8
3 Important information on safety and disposal ...........................................9
3.1 General regulations .........................................................................................9
3.2 Device-specific regulations..............................................................................9
3.3 Notes on EMC optimization .............................................................................9
3.4 Disposal .........................................................................................................10
4 Mounting and installation ...........................................................................11
4.1 Preparation ....................................................................................................11
4.2 Mounting instructions ....................................................................................12
5 Engineering ..................................................................................................14
6 Commissioning ...........................................................................................36
6.1 Programming pin and service LED ...............................................................36
6.1.1 Addressing .....................................................................................36
6.1.2 Connection test ..............................................................................36
6.1.3 Reset to factory setting ..................................................................37
7 Technical data .............................................................................................38
8 Functions .....................................................................................................40
9 Operation .....................................................................................................42
9.1 Ventilation page .............................................................................................42
9.2 Temperature page .........................................................................................43
9.3 Domestic hot water page...............................................................................44
9.4 Notification page ............................................................................................44
9.5 Clock page ....................................................................................................48
9.6 Scheduler settings .........................................................................................48
9.7 Standard and expert settings ........................................................................49
9.8 Standby page ................................................................................................51
10 Appendix ......................................................................................................52
10.1 Parameters ....................................................................................................52
10.2 Object list .......................................................................................................52

2 | 70 A6V11471220_en--_e
About this document 1
Revision history

1 About this document

1.1 Revision history


Revision Date Changes Section
e Sep 2021 Added info for Chapter 5 and
blinking screen Chapter 9
d May 2021 Added info for Chapter 7
POS8.4440/109
about humidity
c October 2020 Canceled Chapter 2.1.1
POS3.3515/100
b August, 2019 Added chapter Chapter 5 and
“Engineering” and Chapter 10
“Object list”
a November, 2018 First edition All

1.2 Before you start


Trademarks The table below lists the third-party trademarks used in this document and their
legal owners. The use of trademarks is subject to international and domestic
provisions of the law.

Trademarks Legal owner


KNX® KNX Association, B - 1831 Brussels-Diegem Belgium
http://www.knx.org/

All product names listed in the table are registered (®) or not registered (™)
trademarks of the owner listed in the table. We forgo the labeling (e.g. using the
symbols ® and ™) of trademarks for the purposes of legibility based on the
reference in this section.
Copyright This document may be duplicated and distributed only with the express permission
of Siemens, and may be passed on only to authorized persons or companies with
the required technical knowledge.
Quality assurance These documents were prepared with great care.
● The contents of all documents are checked at regular intervals.
● All necessary corrections are included in subsequent versions.
● Documents are automatically amended as a consequence of modifications and
corrections to the products described.
Please make sure that you are aware of the latest document revision date.
If you find any lack of clarity while using this document, or if you have any criticisms
or suggestions, please contact the nearest branch office. Addresses for Siemens
regional companies are available at www.siemens.com/sbt.
Document use/ request Before using our products, it is important that you read the documents supplied
to the reader with or ordered at the same time as the products (equipment, applications, tools
etc.) carefully and in full.
We assume that persons using our products and documents are authorized and
properly trained and have the requisite technical knowledge to use our products as
intended.
Additional information on products and applications is available:

A6V11471220_en--_e 3 | 70
1 About this document
Reference documents

● On the intranet (for Siemens employees only) at


https://workspace.sbt.siemens.com/content/00001123/default.aspx
● At your next Siemens branch office www.siemens.com/sbt or at your system
suppliers.
● From the support team in the headquarters fieldsupport-
[email protected] if no local contact is available.
Siemens assumes no liability to the extent allowed under the law for any losses
resulting from a failure to comply with the aforementioned points or for the
improper compliance of the same.

1.3 Reference documents


Ref. Document title Document number
[1] Data sheet A6V11519429

[2] Mounting instructions A6V10733764

4 | 70 A6V11471220_en--_e
Product overview 2
Type summary

2 Product overview

2.1 Type summary


Product Stock number Feature LCD Minimal
number display order
Temperature Humidity
with size
sensor sensor
backlight
POS8.4420/109 S55625-H422-A100 Yes No Yes 20

POS8.4440/109 S55625-H444-A100 Yes Yes Yes 20

2.1.1 Equipment combinations


Type Type no. Document ID Description
Controller POS3.5715/100 A6V11417931 For HVAC controlling,
switching and monitoring
functions

2.2 Features
● Measurement of room temperature (POS8.4420/109)
● Measurement of room temperature and humidity (POS8.4440/109)
● Keys to adjust the room temperature setpoint, ventilation, domestic hot water,
scheduler settings depending on the controller application
● LCD display of room temperature, operating modes, humidity (only for
POS8.4440/109), scheduler, notification, and clock setting
● Operation with 8 pushbuttons
● 2-wire interface to the controller through KNX PL-Link
● Power supply of the room operator unit over KNX PL-Link
● LCD display with backlight

2.3 System topology

POS8.44 QMX3.P

POS9 QBM97
A6V11471220Z01

POS3.xx15 POL903.00

A6V11471220_en--_e 5 | 70
2 Product overview
Mechanical design

2.4 Mechanical design

1 Gasket for panel mounting 4 KNX PL-Link bus connector

2 Base plate with 5 Jack connector for tool connection


● screw holes for all common conduit
boxes
● guide channels for wiring from center,
up, or bottom

3 Room operator unit

2.5 Diagrams

2.5.1 Connection terminals


KNX PL-Link plug
Connector Pin Description
+ KNX PL-Link (positive)

- KNX PL-Link (negative)

To find the location of the KNX PL-Link plug, refer to Mechanical design
NOTICE! Users can choose either pair of the pins to connect.

NOTICE
Wires are NOT interchangeable!
The device is protected against faulty wiring, but communications does not work
on interchanged wires. The KNX / KNX PL-Link bus MUST NOT be connected to
the tool plug, only the tool.

6 | 70 A6V11471220_en--_e
Product overview 2
Diagrams

Tool plug
Connector Pin Description
+ KNX PL-Link (positive)

- KNX PL-Link (negative)

2.5.2 Connection diagrams


Operation

R1 The device - room operating unit (POS8.44xx)


N1 The controller - room automation station
Twisted pair

A6V11471220_en--_e 7 | 70
2 Product overview
Dimensions

2.6 Dimensions
Unit: mm

Fig. 1: Dimensions for housing

Fig. 2: Dimensions for mounting

8 | 70 A6V11471220_en--_e
Important information on safety and disposal 3
General regulations

3 Important information on safety and


disposal
This section explains general and system-specific regulations for mains and
operating voltages. It includes important information for your safety and the safety
of the entire plant.

3.1 General regulations


Comply with the following general regulations during engineering and execution:
● Electrical and mains power regulations for the given country.
● Other applicable, national regulations.
● Building installation regulations for the given country.
● Regulations of the utility company.
● Diagrams, cable lists, dispositions, specifications, and orders by the customer
or authorized engineering office.
● Third-party regulations, for example, by the general contractor or building
owner.
The electrical safety for building automation and control systems by Siemens is
essentially based on safely separating low voltage from mains voltage.

3.2 Device-specific regulations


KNX bus supply Note permissible line lengths and topologies when planning and installing
controllers and field devices featuring KNX bus connection. Make sure the bus
supply complies with the KNX standard.
Maintenance The device is maintenance free. Only the manufacturer can maintain the device.

3.3 Notes on EMC optimization


Cable ducts When setting up cable ducts, separate strongly interfering cables from susceptible
entities.
Cable types ● Interfering cables: Motor cables especially from motors supplied by inverters,
energy-supplying cables.
● Susceptible entities: Control cables, low voltage cables, interface cables, LAN
cables, digital and analog signal cables.
Separate cables ● Both types of cables can be in the same cable duct, but in separate
compartments.
● If no three-sided, closed duct with separating wall is available, the interfering
cables must be separated by at least 150 mm from the others or placed in
separate ducts.
● Crossings of strongly interfering cables with possibly susceptible entities must
be at a right angle.
● In rare cases, signal and interfering power cables may be run in parallel,
resulting in a high interference risk.
Unscreened cables It is recommended to use unscreened cables. Comply with the manufacturer's
installation recommendations for selecting unscreened cables. In general,
unshielded twisted pair cables have sufficient EMC properties for technical
building applications (including data applications) and do not require coupling to
surrounding earth.

A6V11471220_en--_e 9 | 70
3 Important information on safety and disposal
Disposal

3.4 Disposal
The device is considered an electronic device for disposal in
accordance with European Directive and may not be disposed of as
domestic waste.
● Use only designated channels for disposing the devices.
● Comply with all local and currently applicable laws and
regulations.

10 | 70 A6V11471220_en--_e
Mounting and installation 4
Preparation

4 Mounting and installation


Comply with the following notes as well as the Mounting instructions
(A6V10733764) to mount the room operation unit.

4.1 Preparation
Check package contents Check the package contents for visible signs of transport damage and for
completeness.
Do not install parts damaged during shipment. Contact your Siemens
representative in the event of damaged parts.
Check operating Note the information in the data sheet of these operating instructions before
conditions installing the device:
● Climatic ambient conditions
● Protection classes
Check locations

● The devices are suitable for wall mounting and panel mounting.
● Recommended height: 1.50 m above the floor.
● Do not mount the devices in recesses, shelves, behind curtains or doors, or
above or near heat sources.
● Avoid direct solar radiation and drafts.
● Seal the conduit box or the installation tube if any, as air currents can affect
sensor readings.
● Adhere to allowed ambient conditions.

A6V11471220_en--_e 11 | 70
4 Mounting and installation
Mounting instructions

4.2 Mounting instructions


Mounting instructions ● Mounting instructions A6V10733764 are enclosed with the devices.
Wall mounting

● Remove the breakout on the housing before putting the cable into the gaining
channel.
● If 4-wire cables are used for daisy chain wiring, remove the cable coating, as it
will not fit in the gaining channel.
Cable ducts on the wall

● Keep a distance of at least 20 mm from the base plate to any object above the
base plate such as cable ducts to snap the device cover onto the base plate.
Panel mounting

12 | 70 A6V11471220_en--_e
Mounting and installation 4
Mounting instructions

Dismounting/service

A6V11471220_en--_e 13 | 70
5 Engineering

5 Engineering
TempOutsideEff

UHD (User HVAC Display)

Process Data

IR.ind
TempOutsideEff

Management Data

ObjectType 390

Configuration Data
OutsideSensorZone Value (U8Z8)

TempRoomEff

14 | 70 A6V11471220_en--_e
Engineering 5

UHD (User HVAC Display)

Process Data

IR.ind
TempRoomEff

Management Data

ObjectType 390

Configuration Data
BuildingZone Value (U8Z8)
Room Value (U8Z8)
Subzone Value (U8Z8)

HumRelRoomEff

UHD (User HVAC Display)

Process Data

IR.ind
HumRelRoomEff

Management Data

ObjectType 390

Configuration Data
BuildingZone Value (U8Z8)
Room Value (U8Z8)
Subzone Value (U8Z8)

Parameters required to realize the full function:

A6V11471220_en--_e 15 | 70
5 Engineering

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 390 = UHD DPT_PropData
Object Type Type (DPT_ID
= 7.010)

TempOutsideEf OTS.155 ---- IR.ind Process Data DPT_TempHV


f Input ACAbs_Z

local copy *) 155 R --- Diagnostic


Value

TempRoomEff RTS.155 ---- IR.ind Process Data DPT_TempHV


Input ACAbs_Z

local copy *) 157 R --- Diagnostic


Value

HumRelRoomE RRHS.155 ---- IR.ind Process Data DPT_RelValue


ff Input _Z

local copy *) 172 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

OutsideSensor 104 R/W --- Configuration DPT_UCountV


Zone Data alue8_Z

Setting of HVAC Mode

SARB HVAC Room Unit


User HVAC Display UHD
User HVAC RoomSettings UHRS
RoomGroup 24.6.1
RoomGroup 24.6.1
LTE IR(PreComf) HVACModeEff
HVACModeUser LTE IR (Auto)
LTE IR (Auto) HVACModeUserEff LTE IR (16) HVACModeEffWhy

LTE W (false) HVACModeUserLocked


Management Data
LTE W (Auto; HVACModeUserLimit Device Configuration UHD Discovery & Diagnostic Data
Comfort; Eco) Data TxtCatalog
Management Data -… UHD Configuration Data
UHRS Discovery & Diagnostic Data - Life Safety
Geographical Zone 24.6.1
- Equipm Protect
-… TxtRefHVACModeEffWhy TxtRef [1..n]
UHRS Configuration Data -… ….. …..
Geographical Zone 24.6.1 - Manual Control
- Scheduler
….. …..
- ...

Parameters required to realize the full function:

16 | 70 A6V11471220_en--_e
Engineering 5

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 384 = UHRS DPT_PropData
Object Type Type (DPT_ID
= 7.010)

HVACModeUs 55 R IR.req Process Data DPT_HVACMo


er Output de_Z

HVACModeUs 156 R/W W.ind Process Data DPT_Bool


erLocked Input

HVACModeUs RSMHD.57 ---- IR.ind Process Data DPT_HVACMo


erEff Input de_Z

local copy *) 157 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 390 = UHD DPT_PropData
Object Type Type (DPT_ID
= 7.010)

HVACModeEff RSMHD.51 ---- IR.ind Process Data DPT_HVACMo


Input de_Z

local copy *) 163 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

Unoccupied mode

A6V11471220_en--_e 17 | 70
5 Engineering

Building Automation Device


BA-Model
BA-Binary-Calculated-Value BA-Binary-Process-Value
Present-Value 1 Present-Value 1
Tracking-Value 1 Present-Priority 16 Priority-Array
Reliability No-fault Why-Indication[16] x 1 -
Out-of-Service false Relinquish-Default 0 2 -
Status-Flags: Reliability No-fault 3 -
Overridden false Out-of-Service false 4 -
Out-of-Service false Status-Flags: 5 -
Fault false Overridden false 6 -
In-Alarm false Out-of-Service false 7 -
Inactive-Text unoccupied Fault false 8 -
Active-Text occupied In-Alarm false 9 -
Inactive-Text unoccupied 10 -
I/O-Address PL-1:PR=UPS. Active-Text occupied 11 -
PresenceStatus; I/O-Address 12 -
PL-1:PR=UPS.
GEO=24.6.1; 13 -
PresenceStatusEff; 14 -
Update-Count 267 GEO=24.6.1;
Event-State normal 15 -
Event-State normal 16 1

PL-Link Data Acquisition

UPS (User Presence Switch)


Transforms
Binary transform BA → KNX IR.req
f(PresentValue) PresenceStatusEff
Transform:
if PresPrioBA < PrioThreshPresenceStatusLocked
Complex transform BA -> KNX W.req PresenceStatusLocked := true
f(Present-Priority, PrioThreshPresenceStatusLocked)
PresenceStatusLocked else
PresenceStatusLocked := false
Complex transform BA -> KNX IR.req endif
f(Present-Priority) or f(Why-Indication)
PresenceStatusEffWhy
Binary transform KNX → BA Transform: dependent on support by
f(PresenceStatus); firmware and control progs:
PresenceStatusEffWhy contains either the
numerical value of Present-Priority or
IR.ind (Why-Indication + offset)
PresenceStatus

Management Data
ObjectType 391

Configuration Data
BuildingZone Value (U8Z8)
Room Value (U8Z8)
Subzone Value (U8Z8)
PrioThreshPresenceStatusLocked Value (N8Z8)

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 391 = UPS DPT_PropData
Object Type Type

(DPT_ID =
7.010)

PresenceStatu 51 R/W IR.req Process Data DPT_Occupan


s Output cy

PresenceStatu 155 R/W W.ind Process Data DPT_Bool


sLocked Input

PresenceStatu UPS.156 ---- IR.ind Process Data DPT_Occupan


sEff Input cy

local copy *) 201 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

18 | 70 A6V11471220_en--_e
Engineering 5

Temporary mode

Building Automation Device


Room Control Room 1

BA-Model
Binary-Calc-Value ResetTmpFanRequest Analog-Calc-Value ManualFanSpeed Analog-Proc-Value TemporaryFanRemainTime Multistate-Proc-Value TemporaryFanMode
Binary-Calc-Value KitchenHoodRequest Binary-Calc-Value ManualFanMode Present-Value 15 min Present-Value FirePlaceMode
Binary-Calc-Value FirePlaceRequest
None
Binary-Calc-Value FanBoostRequest FanBoostMode
State-Text
FirePlaceMode
Present-Value Active
PL-1:PR=FSSM. KitchenHoodMode
Update-Count n
TmpFanMode
I/O-Address PL-1:PR=FSSM.
PL-1:PR=FSSM. RemainTime;
I/O-Address TmpFanMode;
I/O-Address FanBoostReq; Analog-Proc-Value FanSpeedEff GEO=24.6.1;
GEO=24.6.1;
GEO=24.6.1;

represent represent represent represent represent

PL-Link Data Acquisition Fan Speed Setpoint Manager FSSM

Room Group 24.6.1


FanSpeedEff LTE IR (33.3%)
FanSpeedUserEff LTE IR (Auto)
FanSpeedUserLocked LTE W (false)
FanSpeedEffWhy LTE IR (8)

LTE IR (Auto) FanSpeedUser FanSpeedUserMinIN LTE W (0%)


FanSpeedUserMaxIN LTE W (100%)

{ }
LTE IR (Trigger) FanBoostReq
TmpFanModeRemainTime LTE IR (15min)
LTE IR (Trigger) FirePlaceReq
LTE IR (Trigger) KitchenHoodReq
TmpFanMode LTE IR (FirePlace) [cASA-4.2-100-N]
LTE IR (Trigger) ResetTmpFanReq new optional FSSM
output process signals
Config-Property-Client for temporary HRV fan
NumberOfSteps Property_W (3) operation
[cASA-4.2-100-N]
new optional FSSM
input process signals FSSM Configuration Data
for temporary HRV fan Geographical Zone 24.6.1
operation PrioThreshFanSpeedUserLocked 7
PrioDirectControl 8

PL-Link RU-B Room Unit


User HVAC Display UHD
User FanSpeed Settings UFS
RoomGroup 24.6.1
RoomGroup 24.6.1
LTE IR (33.3%) FanSpeedEff
LTE IR (Auto) FanSpeedUserEff FanSpeedUser LTE IR (Auto)

}
LTE W (false) FanSpeedUserLocked FanBoostReq LTE IR (Trigger) LTE IR (...) FanSpeedEffWhy

{
FanSpeedUserMinIN FirePlaceReq LTE IR (Trigger) TmpFanModeRemainTime
LTE IR (15min)
FanSpeedUserMaxIN KitchenHoodReq LTE IR (Trigger)
LTE IR (FirePlace) TmpFanMode
ResetTmpFanReq LTE IR (Trigger)

[cASA-4.2-100-N] [cASA-4.2-100-N]
Management Data new optional UFS new optional UHD
Management Data
output process signals input process signals
UFS Discovery & Diagnostic Data for temporary HRV fan for temporary HRV fan UHD Discovery & Diagnostic Data
operation operation
UFS Configuration Data UFS Configuration Data

RU Device Object
[cASA-4.2-100-N]
parameters to enable/ Configuration Data
disable operation of EnableFanBoostOp true
temporary fan modes EnableFirePlaceOp true
at runtime EnableKitchenHoodOp true

Parameters required to realize the full function:

A6V11471220_en--_e 19 | 70
5 Engineering

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 390 = UHD DPT_PropData
Object Type Type (DPT_ID
= 7.010)

TmpFanMode FSSM.166 ---- IR.ind Process Data DPT_TmpFan


Input Mode

local copy *) 208 R --- Diagnostic


Value

TmpFanModeR FSSM.167 ---- IR.ind Process Data DPT_TimePeri


emainTime Input odMin

local copy *) 209 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 393 = UFS DPT_PropData
Object Type Type (DPT_ID
= 7.010)

FanBoostReq 162 R IR.req Process Data DPT_Trigger


Output

FirePlaceReq 163 R IR.req Process Data DPT_Trigger


Output

KitchenHoodR 164 R IR.req Process Data DPT_Trigger


eq Output

ResetTmpFan 165 R IR.req Process Data DPT_Trigger


Req Output

FanBoostProlo 166 R IR.req Process Data DPT_TimePeri


ngTime Output odMin

FirePlaceProlo 167 R IR.req Process Data DPT_TimePeri


ngTime Output odMin

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

Temperature setpoint

20 | 70 A6V11471220_en--_e
Engineering 5

SARB HVAC Room Unit


User HVAC RoomSettings UHRS User HVAC Display UHD

RoomGroup 24.6.1 RoomGroup 24.6.1


LTE IR (+1K) TempRoomSetpUserOffsetEff TempRoomSetpUserOffset LTE IR (+1K)
LTE IR (21°C) TempRoomSetpAbsEff
LTE W (false) TempRoomSetpUserOffsetLocked

LTE W (-3K) TempRoomSetpUserOffsetMin LTE IR (15) TempRoomSetpAbsEffWhy

LTE W (+3K) TempRoomSetpUserOffsetMax


Device Configuration Management Data
Data TxtCatalog
Management Data UHD Discovery & Diagnostic Data
-…
UHRS Discovery & Diagnostic Data - Life Safety
- Equipm Protect UHD Configuration Data
-… Geographical Zone 24.6.1
UHRS Configuration Data - Holiday
TxtRefTempRoomSetpAbsEffWhy TxtRef [1..n]
Geographical Zone 24.6.1 - Manual Control
- Scheduler ….. …..
….. …..
- ...

Monitoring of outside temperature Monitoring of room temperature

SARB HVAC Room Unit SARB HVAC Room Unit


User HVAC Display UHD
User HVAC Display UHD

Outside Sensor Zone 1


RoomGroup 24.6.1
LTE IR (-8.5°C) TempOutsideEff
LTE IR (22.3°C) TempRoomEff

Management Data Management Data


UHD Discovery & Diagnostic Data UHD Discovery & Diagnostic Data

UHD Configuration Data UHD Configuration Data


Outside Sensor Zone 1 Geographical Zone 24.6.1
….. ….. ….. …..

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 384 = UHRS DPT_PropData
Object Type Type (DPT_ID
= 7.010)

TempRoomSet 52 R IR.req Process Data DPT_TempHV


pUserOffset Output ACRel_Z

TempRoomSet 158 R/W W.ind Process Data DPT_TempHV


pUserOffsetMin Input, ACRel_Z
IN Configuration
Data

TempRoomSet 159 R/W W.ind Process Data DPT_TempHV


pUserOffsetMa Input, ACRel_Z
xIN Configuration
Data

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
TempRoomSet 160 R/W W.ind Process Data DPT_Bool
pUserOffsetLoc Input
ked

TempRoomSet RSMHD.58 ---- IR.ind Process Data DPT_TempHV


pUserOffsetEff Input ACRel_Z

local copy *) 161 R --- Diagnostic


Value

A6V11471220_en--_e 21 | 70
5 Engineering

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
StepIncrement 171 R/W --- Configuration DPT_Value_1_
HMI_TRSetpU Data Ucount
sOffset

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

DHW mode operation via


Room Unit

22 | 70 A6V11471220_en--_e
Engineering 5

Building Automation Device


Control Program

BA-Model
Binary Calculated Value Multistate-Calculated-Value Multistate-Process-Value Binary Process Value
Present-Value Active Present-Value Auto Present-Value Normal Present-Value Inactive
Number-of-States 5 Priority-Array …. Priority-Array ….
Auto Present-Priority 16 Present-Priority 16
Normal Number-of-States 4
State-Text Reduced Why-Indication [16] x
Off/FrostProtect
Normal
LegioProtect
Reduced
State-Text
Off/FrostProtect
LegioProtect
Update-Count n Update-Count n Update-Count n Update-Count n
PL-1:PR=DHWSM. PL-1:PR=DHWSM. PL-1:PR=DHWSM. PL-1:PR=DHWSM.
I/O-Address DHWPushUser; I/O-Address DHWModeUser; I/O-Address DHWModeEff; I/O-Address DHWPushActive;
APP=DHW.1; APP=DHW.1; APP=DHW.1; APP=DHW.1;

represent represent represent


represent

PL-Link Data Acquisition


DHW Setpoint Manager DHWSM
DHWZone 1
LTE IR (Auto) DHWModeUser DHWModeUserEff LTE IR (Auto)
DHWModeUserLocked LTE W (false) optional output:
„Why“ value may
DHWModeEff LTE IR (Normal)
be derived from BA
DHWModeEffWhy LTE IR (...) Present-Priority or
Why-Indication

LTE IR (Trigger) DHWPushUser DHWPushActive LTE IR (false)

Configuration Data
DHW Zone 1
PrioThreshDHWModeUserLocked 7
PrioDirectControl 8

PL-Link Room Unit


User DHW Settings UDHWSET User HVAC Display UHD
DHWZone 1 DHWZone 1
LTE IR (Auto) DHWModeUserEff DHWModeUser LTE IR (Auto)
LTE IR (Normal) DHWModeEff optional input
LTE W (false) DHWModeUserLocked LTE IR (...) DHWModeEffWhy

LTE IR (false) DHWPushActive DHWPushUser LTE IR (Trigger)


Device Configuration
Data TxtCatalog Management Data
Management Data -…
- Equipm Protect Configuration Data
Configuration Data -…
- Manual Control DHW Zone 1
DHW Zone 1
- Scheduler TxtRefDHWModeEffWhy TxtRef [1..n]
- ...

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 390 = UHD DPT_PropData
Object Type Type (DPT_ID
= 7.010)

DHWModeEff DHWSM.51 ---- IR.ind Process Data DPT_DHWMod


Input e_Z

local copy *) 213 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

A6V11471220_en--_e 23 | 70
5 Engineering

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 181 = DPT_PropData
Object Type UDHWSET Type (DPT_ID
= 7.010)

DHWModeUse 51 R IR.req Process Data DPT_DHWMod


r Output e_Z

DHWModeUse 156 R/W W.ind Process Data DPT_Bool


rLocked Input

DHWModeUse DHWSM.56 ---- IR.ind Process Data DPT_DHWMod


rEff Input e_Z

local copy *) 254 R --- Diagnostic


Value

DHWZoneCont 101 R/W --- Configuration DPT_UCountV


roller Data alue8_Z

Operation of DHW
setpoint via Room Unit

24 | 70 A6V11471220_en--_e
Engineering 5

Building Automation Device


Control Program

BA-Model
Analog-Calculated-Value Analog-Process-Value Analog-Process-Value
Present-Value 58°C Present-Value 65°C Present-Value 58°C
Units °C Priority-Array …. Priority-Array ….
Present-Priority 15 Present-Priority 15
Min-Present-Value 45°C Units °C Units °C
Max-Present-Value 60°C Why-Indication [16] x Why-Indication [16] x

Update-Count n Update-Count n Update-Count n

PL-1:PR=DHWSM. PL-1:PR=DHWSM. PL-1:PR=DHWSM.


I/O-Address TempDHWSetpUser; I/O-Address TempDHWSetpEff; I/O-Address TempDHWSetpUserEff;
APP=DHW.1; APP=DHW.1; APP=DHW.1;

represent represent
represent

PL-Link Data Acquisition


DHW Setpoint Manager DHWSM
DHWZone 1
TempDHWSetpEff LTE IR (65°C) optional output:
LTE IR (…) „Why“ value may
TempDHWSetpEffWhy
be derived from BA
Present-Priority or
Why-Indication
TempDHWSetpUserEff LTE IR (58°C)

TempDHWSetpUserLocked LTE W (false)

TempDHWSetpUserMinIN LTE W (45°C)


LTE IR (58°C) TempDHWSetpUser
TempDHWSetpUserMaxIN LTE W (60°C)

Configuration Data
DHW Zone 1
PrioThreshTempDHWSetpUserLocked 7

PL-Link Room Unit


User DHW Settings UDHWSET User HVAC Display UHD
DHWZone 1 DHWZone 1
LTE W (58°C) TempDHWSetpUserEff TempDHWSetpUser LTE IR (58°C) LTE IR (65°C) TempDHWSetpEff optional input
LTE IR (...) TempDHWSetpEffWhy
LTE W (false) TempDHWSetpUserLocked

LTE W (45°C) TempDHWSetpUserMinIN

LTE W (60°C) TempDHWSetpUserMaxIN Device Configuration


Data TxtCatalog Management Data
Management Data -…
- Equipm Protect Configuration Data
Configuration Data -…
DHW Zone 1 - Manual Control DHW Zone 1
TempDHWSetpUserMin 20°C - Scheduler TxtRefTempDHWSetpEffWhy TxtRef [1..n]
TempDHWSetpUserMax 70°C - ...

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 390 = UHD DPT_PropData
Object Type Type (DPT_ID
= 7.010)

TempDHWSet DHWSM.55 ---- IR.ind Process Data DPT_TempHV


pEff Input ACAbs_Z

local copy *) 211 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

A6V11471220_en--_e 25 | 70
5 Engineering

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 181 = DPT_PropData
Object Type UDHWSET Type (DPT_ID
= 7.010)

TempDHWSet 52 R IR.req Process Data DPT_TempHV


pUser Output ACAbs_Z

TempDHWSet DHWSM.162 ---- IR.ind Process Data DPT_TempHV


pUserEff Input ACAbs_Z

local copy *) 246 R --- Diagnostic


Value

TempDHWSet 158 R/W W.ind Process Data DPT_TempHV


pUserMinIN Input, ACAbs_Z
Configuration
Data

TempDHWSet 159 R/W W.ind Process Data DPT_TempHV


pUserMaxIN Input, ACAbs_Z
Configuration
Data

TempDHWSet 160 R/W W.ind Process Data DPT_Bool


pUserLocked Input

DHWZoneCont 101 R/W --- Configuration DPT_UCountV


roller Data alue8_Z

Visualization of DHW
Temperature

26 | 70 A6V11471220_en--_e
Engineering 5

Building Automation Device


Control Program

BA-Model
Analog-Process-Value

Present-Value 53°C
Units °C

PL-1:PR=DHWTS.
I/O-Address TempDHWEff;
APP=DHW.1;

represent

PL-Link Data Acquisition


DHW Temperature Sensor DHWTS (proxy)
DHWZone 1

TempDHWEff LTE IR (53°C)

Configuration Data
DHW Zone 1

PL-Link Room Unit


User HVAC Display UHD
DHWZone 1
LTE IR (53°C) TempDHWEff

Management Data

Configuration Data
DHW Zone 1

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 390 = UHD DPT_PropData
Object Type Type (DPT_ID
= 7.010)

TempDHWEff DHWTS.155 ---- IR.ind Process Data DPT_TempHV


Input ACAbs_Z

local copy *) 210 R --- Diagnostic


Value

BuildingZone 101 R/W --- Configuration DPT_UCountV


Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

A6V11471220_en--_e 27 | 70
5 Engineering

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 181 = DPT_PropData
Object Type UDHWSET Type (DPT_ID
= 7.010)

DHWPushActiv DHWSM.163 ---- IR.ind Process Data DPT_Bool


e Input

local copy *) 252 R --- Diagnostic


Value

DHWZoneCont 101 R/W --- Configuration DPT_UCountV


roller Data alue8_Z

Scheduler

28 | 70 A6V11471220_en--_e
Engineering 5

Building Automation Device

Engineering & Operation & Control


Commissioning Monitoring Program
configure & operate & automate
commission monitor & control

Building Automation Model

BA-Peripheral-Device-Object

Present-Value operational BA-Schedule-Object OpMSched


Peripheral-Dev-Type “RU_B“
Weekly-Schedule
Mo Tu We Th Fr Sa Su
IO-Extension PDO-Config-“RU_B“ … … … … … … …
Enable-Weekly-Sched-Op true … … … … … … …
… … … … … … …
... ... … … … … … … …
... ... ... ... ... ... ...

I/O-Address PL-1:DL=5;

PL-Link Data Acquisition

Configuration Property Client ABI HVACS (proxy)


ABI CPC-“RU_B“
Update RU_B BA-Client
configuration data

Device-N° Device5 KNX Property Server

PL-Link HVAC Room Unit


KNX Property Client of remote ABI HVACS

Device Configuration Data


EnableScheduleOperation true

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 110 = HVACS DPT_PropData
Object Type Type (DPT_ID
= 7.010)

HVACSDailyPr 231 R/W --- Daily Program DPT_HVACSS


og_Mo 1) Monday witchPoint

HVACSDailyPr 232 R/W --- Daily Program DPT_HVACSS


og_Tu 1) Tuesday witchPoint

HVACSDailyPr 233 R/W --- Daily Program DPT_HVACSS


og_We 1) Wednesday witchPoint

A6V11471220_en--_e 29 | 70
5 Engineering

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
HVACSDailyPr 234 R/W --- Daily Program DPT_HVACSS
og_Th 1) Thursday witchPoint

HVACSDailyPr 235 R/W --- Daily Program DPT_HVACSS


og_Fr 1) Friday witchPoint

HVACSDailyPr 236 R/W --- Daily Program DPT_HVACSS


og_Sa 1) Saturday witchPoint

HVACSDailyPr 237 R/W --- Daily Program DPT_HVACSS


og_Su 1) Sunday witchPoint

Adjust clock

30 | 70 A6V11471220_en--_e
Engineering 5

Building Automation Device


Control Program

BA-Model
Device-Object
Local-Time 10:36:28
Local-Date 31-05-2010; Monday
UTC-Offset 120
Daylight-Savings-Status true

Firmware
(OS)

PL-Link Data Acquisition


System Clock SCLO (Master)
LTE Broadcast

SystemClock LTE IR (2010-05-31;Mon;10:36:28;SuTi)

RelToGMT LTE IR (120min)

Optional feature; no real use


SCLO Configuration Data case on PL-Link so far
Peripheral Zone 0 => not implemented in a 1st step
SCLOMode Master
SystemClockHeartbeat 10min
EnableSystemClockSetting false Fixed configuration

PL-Link Room Unit


SystemClock SCLO (Slave)

LTE Broadcast
LTE IR (2010-05-1;Mon;10:36:28;SuTi) SystemClock

LTE IR (120min) RelToGMT

Optional feature; no real use Management Data


case on PL-Link so far SCLO Discovery & Diagnostic Data
=> not implemented in a 1st step
2010-05-31
LocalClock
Mon;10:36:28

SCLO Configuration Data


Peripheral Zone 0
SCLOMode Slave Fixed configuration
SystemClockTimeout 21min
EnableSystemClockSetting false

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 1001 = SCLO DPT_PropData
Object Type Type

(DPT_ID =
7.010)

SystemClock 51 R IR.req Process Data DPT_DateTime


Output

A6V11471220_en--_e 31 | 70
5 Engineering

Notification: Alarm /
Service

When alarm is active, the screen blinks until it gets acknowledged.


Building Automation Device
Control Program ‚Alarm’ Control Program ‚Maintenance’
Detection Aggregate State Detection Aggregate State
Detection Detection
& Select Machine & Select Machine

BA-Model
MPV-Object APV-Object MPV-Object MPV-Object APV-Object MPV-Object
MTV-Object MTV-Object
Error- Error- Error- Maintenance- Maintenance- Maintenance-
Error- Maintenance-
Indication- Code- Cmd-State- Indication- Code- Cmd-State-
Cmd-RU Cmd-RU
RU RU RU RU RU RU

PL-Link Data Acquisition


Alarm Source ALSRC

AlarmAcknowledge
MaintenanceAcknowledge AlarmInfo_CS
AlarmReset MaintenanceInfo_CS
MaintenanceReset

Technical Building Infrastructure


PL-Link Room Unit RU-B
Alarm Sink ALSNK

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 1003 = ALSNK DPT_PropData
Object Type device-specific Type
Device Object (DPT_ID =
7.010)

AlarmInfo_CS ALSRC.254 --- IR.ind Process Data DPT_AlarmInfo


Input _CS

local copy 1) 230 R --- Diagnostic


Value

AlarmAcknowle ALSRC.55 --- W.req Process Data DPT_Ack


dge Output

local copy 2) 228 R --- Diagnostic


Value

AlarmReset ALSRC.56 --- W.req Process Data DPT_Reset


Output

32 | 70 A6V11471220_en--_e
Engineering 5

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
local copy 2) 229 R --- Diagnostic
Value

MaintenanceInf ALSRC.194 --- IR.ind Process Data DPT_AlarmInfo


o_CS Input _CS

local copy 1) 227 R --- Diagnostic


Value

MaintenanceAc ALSRC.192 --- W.req Process Data DPT_Ack


knowledge Output

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
local copy 2) 225 R --- Diagnostic
Value

MaintenanceR ALSRC.193 --- W.req Process Data DPT_Reset


eset Output

local copy 2) 226 R --- Diagnostic


Value

Auxiliary input

A6V11471220_en--_e 33 | 70
5 Engineering

Building Automation Device


Control Program

BA-Model
Multistate-Process-Value Multistate-Process-Value
Present-Value Economy Present-Value HardwareContact
Priority-Array ….
Present-Priority 7
Why-Indication[16] x Number-of-States 4
Number-of-States 4
Auto
Protection
RUManualPermanent
Manual override of HVACMode via Economy State-Text
Multistate-Input-Object State-Text RUManualTemporary
a hardware contact will normally Precomfort
HardwareContact
Present-Value EconomySwitch result in Present-Priority=7 Comfort
Update-Count n Update-Count n

PL-1:PR=RSMHD. PL-1:PR=RSMHD.
I/O-Address HVACModeEff; I/O-Address HVACModeDeterm;
GEO=24.6.1; GEO=24.6.1;

represent represent

I/O Data Acquisition PL-Link Data Acquisition


RoomSetpoint Manager RSMHD
Room Group 24.6.1

HVACModeUserEff LTE IR (Manual, Economy)

HVACModeUserLocked LTE W (true)

HVACModeEff LTE IR (Economy)


In case of manual override of HVACMode via a hardware
contact it is recommended to lock HVAC Mode operation
HVACModeEffWhy LTE IR (...)
on the Room Unit.
With Present-Priority < PrioThreshHVACModeUserLocked
the output HVACMOdeUserLocked will be true
HVACModeDeterm LTE IR (HardwareContact)

RSMHD Configuration Data [cASA-4.2-170-N]


new process signal to indicate
Geographical Zone 24.6.1
manual override of HVAC Mode via
PrioThreshHVACModeUserLocked 8
a hardware contact
IO-Function PrioDirectControl 8

PL-Link OEM specific HVAC Room Unit


User HVAC Display UHD

1..3 RoomGroup 24.6.1


Switch

LTE IR(Economy) HVACModeEff

LTE IR (HardwareContact) HVACModeDeterm

Management Data
ON
UHD Discovery & Diagnostic Data
AWAY
UHD Configuration Data
Geographical Zone 24.6.1

Parameters required to realize the full function:

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
Interface 1 R --- 390 = UHD DPT_PropData
Object Type Type (DPT_ID
= 7.010)

HVACModeEff RSMHD.51 ---- IR.ind Process Data DPT_HVACMo


Input de_Z

local copy *) 163 R --- Diagnostic


Value

HVACModeDet RSMHD.243 ---- IR.ind Process Data DPT_HVACMo


erm Input deDeterm

local copy *) 217 R --- Diagnostic


Value

34 | 70 A6V11471220_en--_e
Engineering 5

Property Property Property LTE service Description KNX


name identifier access Datapoint
Type (DPT)
BuildingZone 101 R/W --- Configuration DPT_UCountV
Data alue8_Z

Room 102 R/W --- Configuration DPT_UCountV


Data alue8_Z

Subzone 103 R/W --- Configuration DPT_UCountV


Data alue8_Z

A6V11471220_en--_e 35 | 70
6 Commissioning
Programming pin and service LED

6 Commissioning
Prerequisites Before commissioning a room operator unit, make sure an application is
downloaded onto the connected controller, from where the functions are
downloaded into the room operator unit.
After successful commissioning, the room operator unit displays the default
operating page defined in the application loaded in the controller.
Automatic In a 1:1 connection, i.e. only one room operator unit connecting to one controller,
commissioning (1:1 when powered up via the KNX bus for the first time, the room operator unit
connection) automatically commissions itself.
After successful commissioning, the room operator unit displays the default
operating page defined in the application loaded in the room automation station.

6.1 Programming pin and service LED


The devices come with a programming pin and a red service LED on the rear.

6.1.1 Addressing
1. Briefly press the programming pin (< 2 s).
 The device enters programming mode; the service LED is continuously on.
The tool identifies and assigns the currently active device.
2. After the device is commissioned, deactivate programming mode by shortly
pressing the programming pin (< 2 s). The service LED goes off.
Note:
● Programming mode returns to “disabled” each time the device restarts.
● Addressing and commissioning can be done automatically if a POS3.xx15
is connected to the device.

6.1.2 Connection test


1. Press the programming pin (>5 s and <20 s) to test the KNX PL-Link
connection. After releasing the programming pin, testing of the KNX PL-Link
connection starts; the service LED flashes (1/4 s on, 7/4 s off).
After approximately 12 s, the test result is displayed:

36 | 70 A6V11471220_en--_e
Commissioning 6
Programming pin and service LED

- If the test is positive, the LED is lit continuously.


- If the test fails, the LED flashes (1 s on, 1 s off).
2. Briefly press the programming pin (<2 s) to stop displaying the result of the
connection test. The service LED goes off.

6.1.3 Reset to factory setting


Press the programming pin (>20 s). The device is locked and reboots within 8 s.
The controller removes it from its device list. During this time, the device can safely
be removed from the network.
NOTICE! The LED is off during this procedure.
If the bus plug remains connected, the device acts like a newly inserted device
requiring automated or manual configuration.

NOTICE
This operation resets all user-defined data and configuration settings to
factory default.
This operation is irreversible.

A6V11471220_en--_e 37 | 70
7 Technical data

7 Technical data
Power supply
Operating voltage KNX PL-Link DC 21...30 V

Max power consumption 7...10 mA

Interfaces
Type of port between controller and room KNX PL-Link
operating unit KNX PL-Link

Baud rate 9.6 kbps

Protocol KNX PL-LINK

Standard KNX connector Wire diameter 0.8 mm, max. 1.0 mm (solid conductors
only)

Cable type 2-core twisted pair, stranded, solid

Single cable length (from room automation <1000 m


station to room operating unit)

Section 0.5…1.5 mm²

Bus line polarity PL+, PL-

Bus terminating resister not required

Sensor data
Temperature Sensor Measuring element NTC resistance sensor

Measuring range 0...50 °C

Measuring accuracy (5...30 °C) ±0.8 °C

Measuring accuracy (25 °C) ±0.5 °C

Humidity Sensor Measuring range 10 %...95 % r.h.


(only for Accuracy (r.h. 20 %...80 %) ±4 % at 25 °C
POS8.4440/109)
Accuracy (r.h. 0 %...20 %, 80 %...95 %) ±6 % at 25 °C

Ambient conditions and protection classification


Housing protection ● IP30
Protection standard as per EN 60529 ● IP33 for surface part

Insulation protection class Class III

Climatic ambient conditions


● Normal operation ● Environmental conditions: Class 3K5
Temperature 0...50 °C
Air humidity <85% r.h.
● Transport ● Environmental conditions: Class 2K3
Temperature -25...70 °C
Air humidity <95% r.h.

Mechanical ambient conditions


Normal operation Class 3M2
Transport Class 2M2

38 | 70 A6V11471220_en--_e
Technical data 7

Standards, directives and approvals


EU conformity (CE) A6V11210253 *)

RCM conformity to EMC emission standard A6V11210257 *)

IC Compliance CAN ICE-3(B)/NMB-3(B)

UL Compliance UL916

FCC Compliance Part 15 of the FCC rules. Operation is subject to


the following two conditions: 1) this device may
not cause harmful interference, and 2) this device
must accept any interference received, including
interference that may cause undesired operation.

Environmental compatibility The product environmental declaration


(A6V10733777 *) contains data on
environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).

*) Documents can be downloaded at the following address:


http://siemens.com/bt/download

NOTICE
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turning the device off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and receiver.
● Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
● Consult the dealer or an experienced radio/TV technician for help.

General data (POS8.4420/109)


Color Signal white (RAL9003)

Weight 145 g

General data (POS8.4440/109)


Color Signal white (RAL9003)

Weight 146 g

A6V11471220_en--_e 39 | 70
8 Functions

8 Functions

Elements Functions
Home mode / Away mode / Temporary mode
/ /

Temporary mode: Ventilation boost / Fire place


/

HVAC Mode: Comfort / Economy / Unoccupied / Protection


/ / /

/ Auto / Manual

Manual

Ventilation page

Temperature page

Domestic hot water page

Notification page

Clock page

General page / Expert page


/

/ Indicates an operable element

Wait

Start

List

Alarm (A-alarm) notification abnormal and unacknowledged

Alarm(A-alarm) notification normal and unacknowledged

Alarm (A-alarm) notification abnormal and acknowledged

Alarm (A-alarm) notification normal and acknowledged

Service (B-alarm) notification abnormal and unacknowledged

Service (B-alarm) notification normal and unacknowledged

Service (B-alarm) notification abnormal and acknowledged

Acknowledge all notifications

Reset

Confirm

40 | 70 A6V11471220_en--_e
Functions 8

Elements Functions
Cancel

Go back

/ Exit / next

+/- Increase / decrease

Add a switch point

Edit

Delete

1234567 1=Monday, 2=Tuesday, …, 6=Saturday, 7=Sunday

Time

Switch point

Time scheduler bar

Read parameter mode

Outside temperature

Room temperature

Auxiliary input for comfort mode

Auxiliary input for economy mode

Auxiliary input for unoccupied mode

Auxiliary input for protection mode

Auxiliary input for ventilation boost mode

Auxiliary input for fire place mode

Auxiliary input for kitchen hood mode

A6V11471220_en--_e 41 | 70
9 Operation
Ventilation page

9 Operation

9.1 Ventilation page


Start-up page When the device is switched on, the startup page displays product-related
information including product model, software version, and SN number for 3
seconds. Then the screen turns to the home page.
In home mode

Buttons 1 and 5 Toggle through home mode, temporary mode and


away mode

Buttons 2 and 6 Toggle between auto mode and manual mode

Buttons 3 and 7 ● In auto mode: No function (no arrow symbols


displayed)
● In manual mode: Toggle through HVAC
mode: comfort, economy, unoccupied, and
protection

Button 4 and 8 Toggle through different pages: Ventilation,


temperature, domestic hot water, notification and
clock

In temporary mode

42 | 70 A6V11471220_en--_e
Operation 9
Temperature page

Button 1 and 5 Toggle through home mode, temporary mode and


away mode

Button 2 and 6 Toggle between temporary modes: Ventilation


boost and fire place

Button 3 No function (no arrow symbol displayed)

Button 7 Press to start the selected temporary mode:


Ventilation boost or fire place

Button 4 and 8 Toggle through different pages: Ventilation,


temperature, domestic hot water, notification and
clock.

In away mode

Buttons 1 and 5 Toggle through home mode, temporary mode and


away mode

Buttons 2, 3, 4, 6, 7 and 8 No function (no arrow symbols displayed)

9.2 Temperature page

In home mode

22.0
6

Buttons 1 and 4 Toggle through home mode, temporary mode and


away mode

Buttons 2 and 5 Increase or decrease the temperature

Buttons 3 and 6 Toggle through different pages: Ventilation,


temperature, domestic hot water, notification and
clock

A6V11471220_en--_e 43 | 70
9 Operation
Domestic hot water page

9.3 Domestic hot water page


In home mode

Buttons 1 and 5 Toggle through home mode, temporary mode and


away mode

Buttons 2 and 6 Toggle between auto mode and manual mode

Buttons 3 and 7 Increase or decrease temperature

Buttons 4 and 8 Toggle through different pages: Ventilation,


temperature, domestic hot water, notification and
clock

In temporary mode

Buttons 1 and 5 Toggle through home mode, temporary mode and


away mode

Buttons 2, 3 and 6 No function (no arrow symbol displayed)

Button 7 Press to start the selected temporary mode:


Domestic hot water

Buttons 4 and 8 Toggle through different pages: ventilation,


temperature, domestic hot water, notification and
clock.

9.4 Notification page


Press button 4 or 8 from the default page to enter the notification page.
With no pending notification, the following is displayed:

44 | 70 A6V11471220_en--_e
Operation 9
Notification page

Alarm notification When an event comes in, e.g., event number 1236, the following is displayed.
The screen blinks until it gets acknowledged.

Press any button to enter the next page:

Note: stands for type 1: Alarm notification. When a new alarm comes in, it
overrides the existing one. The screen continues to show type 1.

Press button 3 or 7 to go to the following page.

Then press button 5 to send a request to the controller to acknowledge all alarms.
The following is displayed while waiting for the feedback from the controller.

A6V11471220_en--_e 45 | 70
9 Operation
Notification page

The following is displayed automatically after all alarms are acknowledged.

With only notifications left, press button 7 to enter the reset page.
On the reset page, press 3 or 7 to switch between notification and reset page.

The notifications are deleted after resetting and the screen returns to the
notification page.

46 | 70 A6V11471220_en--_e
Operation 9
Notification page

Service notification For events , , , , or , there is no pop up screen. To check the


notifications, press button 4 or 8 on the default page to enter the notification page
as below:

Note: stands for type 2: Service notification. A new service notification


overrides the existing one. The screen continues to show type 2.

With unacknowledged notifications, press button 7 to go to the following page:

Press button 5 to send a request to the controller to acknowledge all notifications.


The following page is displayed while waiting for the feedback from the controller.

A6V11471220_en--_e 47 | 70
9 Operation
Clock page

The following is displayed automatically after all notifications are acknowledged.

Service notifications disappear and the screen returns to the notification page after
the device receives a maintenance, normal and Acked (acknowledged) feedback
from the controller.

9.5 Clock page

Buttons 1, 2, 3, 6, and 7 No function (no arrow symbols displayed)

Button 5 Press to edit the time and date

Buttons 4 and 8 Toggle through different pages: Ventilation,


temperature, domestic hot water, notification and
clock

9.6 Scheduler settings


From the default page, long-press button 2 to enter the scheduler settings for
ventilation:

48 | 70 A6V11471220_en--_e
Operation 9
Standard and expert settings

Button 1 Press to exit and save the settings

Buttons 2 and 6 Press to select a weekday

Buttons 3, 4, 5 and 7 No function (no arrow symbols displayed)

Button 8 Press to edit the scheduler settings for the


selected weekday

From the above page, press button 8 to enter the following page to further edit the
scheduler:

Button 1 Press to exit and save the settings

Buttons 2, 4 and 6 No function (no arrow symbol displayed)

Buttons 3 and 7 Toggle through switch points

Button 5 Press to add a switch point

Button 8 Press to edit the switch point

A maximum of 15 switching points can be added.

9.7 Standard and expert settings


Standard settings From the default page, long-press button 8 to enter the standard settings page as
below:

A6V11471220_en--_e 49 | 70
9 Operation
Standard and expert settings

Button 1 Press to exit and save the settings

Buttons 2 and 6 Press to select a setting

Buttons 3 and 7 Toggle through the parameters

Buttons 4, 5 and 8 No function (no arrow symbols displayed)

Expert settings From the default page, long-press buttons 6 and 8 simultaneously to enter the
expert settings page:

Button 1 Press to exit and save the settings

Buttons 2 and 6 Press to select a setting

Buttons 3 and 7 Toggle through the parameters

Buttons 4, 5 and 8 No function (no arrow symbols displayed)

For detailed information about the parameters, refer to Parameters [➙ 52].

50 | 70 A6V11471220_en--_e
Operation 9
Standby page

9.8 Standby page

When no operation occurs on the screen for a while, the room operator units turns
off backlighting and displays the standby page automatically. There are 5 types of
standby pages. Users can select from the standard settings P02.
Press any button to activate backlighting and any button again to enter the default
page.

A6V11471220_en--_e 51 | 70
10 Appendix
Parameters

10 Appendix

10.1 Parameters
Parameters for standard
settings Parameters Description Default
P01 Backlighting level: 1, 2, …, 10 5

P02 Standby page types: 1, 2, …, 5 1


1: room temperature
2: room temperature and time
3: room temperature, time and outside air
temperature
4: room temperature, time, outside air
temperature and customer logo
5: room temperature, time, outside air
temperature and relative humidity

P03 Room operator unit temperature 0.0 K


correction: -3.0…3.0 K

P04 Temperature unit: °C and °F °C

P05 Date format: DD-MM-YYYY


DD-MM-YYYY;
MM-DD-YYYY;
YYYY-MM-DD

Parameters for expert


settings Parameters Description Default
P01…P05 As above As above

P51 Restart the room operator unit by pressing N/A


button 6

10.2 Object list


ObjTy ObjIns ObjI Function Property PI Arra PDT/DPT R/ LTE- Description Comments
pe tance dx Block D ySiz W Servi
e ce

0 1 0 DeviceO PID_OBJEC 1 1 U16 / R ---- Device object: SD-


bject T_TYPE PDT_UNSIGNE T060.0601_EN_SARB
D_INT _Data_Acquisition
7.1.2.9.1

PID_SERIAL 11 1 N16U32 / R ---- KNX Serial Number of


_NUMBER PDT_GENERIC the device in which it
_06, is contained
[DPT_SerNum
(DPT_ID =
221.001)]

PID_MANUF 12 1 U16 / R ---- Code assigned by the


ACTURER_I PDT_UNSIGNE KNX Association to
D D_INT identify the
manufacturer of the
device.
253 / 0x00FD =
Siemens Schweiz AG

PID_DEVICE 14 1 B8 / RW ---- VerifyMode Contol for KNX Standard:


_CONTROL PDT_BITSET8 UserMemery_Write chapter 3-5-1, clause
[DPT_Device_ Service is done via 4.2.14
Control this property. Bit2 is PID_DEVICE_CONTR

52 | 70 A6V11471220_en--_e
Appendix 10
Object list

(DPT_ID = the Verify-Mode Flag. OL


21.002)] When using chapter 3-5-2, clause
connectionless 3.19
UserMemWrite, then DM_UserMem_Write
verifyMode shall be
active

PID_ORDER 15 1 PDT_GENERIC R ---- manufacturer specific DPT-ID out of


_INFO _10 Order Information proprietary range, as
DPT_OrderInfo Specified in Synco
(DPT-ID =
60110.60002)

PID_ROUTIN 51 1 U8 / RW ---- This Property shall KNX Standard,


G_COUNT PDT_UNSIGNE include the default chapter 3-5-1, clause
D_CHAR value for the hop 4.3.2
count. (This is a PID_ROUTING_COU
parameter for the NT
Network Layer of the
device.). It shall be
used to adjust the
default value of the
hop count parameter
of the Network Layer

PID_PROG_ 54 1 B8 / RW ---- Bit 0 = Programming


MODE PDT_BITSET8 Mode
all other bits reserved
for future use

PID_PRODU 55 1 PDT_GENERIC R ---- manufacturer specific DPT-ID out of


CT_ID _10 device type proprietary range, as
DPT_Product_I For this property, Specified in Synco
dentification Synco rules apply:
(DPT-ID = Serial Number, Device
60110.60002) Family, Device Variant
(concatenated)

PID_MAX_A 56 1 U16 / R ---- maximal supported Default = 60 bytes


PDU_LENGT PDT_UNSIGNE APDU-length for
H D_INT management of the
device

PID_SUBNE 57 1 U8 / R ---- Subnetwork Address


T_ADDR PDT_UNSIGNE part (high octet) of the
D_CHAR Individual Address

PID_DEVICE 58 1 U8 / R ---- Device Address part


_ADDR PDT_UNSIGNE (low octet) of the
D_CHAR Individual Address

PID_IO_LIST 71 25 U16 / R ---- Array which lists for acc. KNX Standard,
PDT_UNSIGNE each object index the chapter 3/5/1
D_INT[ ] Object Type Resources,
PID_IOLIST

DevIdent 24 1 U16U32U8N8 / R IR.re Used for SARB


1 PDT_GENERIC q localization,
_08 communication test.
Sent with an LTE-
InfoReport after power
up and periodically if
DevIdentAutoSend is
enabled

DevIdentAut 24 1 B1 / RW ---- Enables DPT definition: SD-


oSend 2 PDT_BINARY_I PID_DEVICE_IDENT T060.0601_EN_SARB
NFORMATION to be sent _Data_Aquisition
B1 / spontaneously at 7.1.2.9.3
DPT_Enable power up and in
regular intervals

DevIdentHop 24 1 N8 / RW ---- Defines the used hop DPT definition: SD-


CountType 3 PDT_ENUM8 count for DevIdent: T060.0601_EN_SARB
DPT_HopCount 0: PSD defined _Data_Aquisition
1: 0

A6V11471220_en--_e 53 | 70
10 Appendix
Object list

Type 7: 7 7.1.2.9.3
All others: reserved

DevIdentTrig 24 1 B1 / RW W.in Triggers sending of


ger 4 PDT_BINARY_I d DevIdent when
NFORMATION DevIdentAutoSend is
B1 / false.
DPT_Trigger This is an LTE-Write-
Input

ConnectionT 24 1 N8 / RW ---- Used for Feedback DPT definition: SD-


estState 5 PDT_ENUM8 from AD during T060.0601_EN_SARB
DPT_Connectio connection test. _Data_Aquisition
nTestState 0: PSD written value, 7.1.2.9.3
No test in progress
1: AD written value,
Connection OK.
2: PSD written value,
Test in Progress

DevTypeID 24 1 N16U32 / R ---- Used for device type DPT definition: SD-
6 PDT_GENERIC identification and T060.0601_EN_SARB
_06 compatibility check _Data_Aquisition
DPT_DeviceTy between configuration 7.1.2.9.3
peID data and device
capabilities (Interface /
Object List Version)

3 1 7 Applicati Interface 1 1 U16 / R ---- Device Management, belongs to S-Mode


on Object type PDT_UNSIGNE access (write) by ETS Interface
Program D_INT during download
Object (àpartly part of S-
Mode Interface)

PID_LOAD_ 5 1 PDT_CONTRO RW ---- [Wichert, Stefan] APO- KNX DOC 03_05_01


STATE_CON L LSM will be used for DPT-ID out of
TROL DPT_LoadCont download control of proprietary range, as
rol parameter properties Specified in Synco
(DPT-ID = for AB's RTS, UHRS,
20.60081) UHD, …
This property shall
be reserved for ETS
tool in S-Mode. An
empty LSM
transformation
function shall be
implemented to keep
compliant with KNX
specification.

50100 1 9 Extende Interface 1 1 U16 / R ----


d Object type PDT_UNSIGNE
Device D_INT
Object

PID_LOAD_ 5 1 PDT_CONTRO RW ---- LSM for control of FW common use intended


STATE_CON L upgrade for devices from I BT
TROL DPT_LoadCont CPS supporting FW-
rol Upgrade
(DPT-ID =
20.60081)

ObjectIndex 29 1 R Rea
d.ind

Apartment 10 1 U8Z8 / RW ----


1 DPT_UcountVa
lue8_Z

Room 10 1 U8Z8 / RW ----


2 DPT_UcountVa
lue8_Z

Subzone 10 1 U8Z8 / RW ----


3 DPT_UcountVa

54 | 70 A6V11471220_en--_e
Appendix 10
Object list

lue8_Z

ACS Product 51 1 PT_GENERIC_ R ---- Contains serial no., DPT-ID out of


ID 12 device family etc. proprietary range, as
DPT_AcsProdu is constant for a given Specified in Synco
ctId device.
(DPT-ID = For more details, see
60112.60000) Synco specification
documents

PlantImageId 53 1 DPT_GENERIC R ----


entification _10

Device Ident 90 1 DPT_GENERIC R ----


_10

VersionArray 91 1 U5U5U6 / R ---- Array-Field with Index M.V.R (U5U5U6).


DPT_Version 1: Firmware-Version of Here M(magic) is not
the Device; used.
Additional Array-Fields V(version).R(Revision)
may be used for before formal release
further version-info, is 0.1
e..g. HW-Version

FW_Upgrade 12 16 PT_UNSIGNED R ---- Checksum for FW


_Checksum 1 _CHAR upgrade. The
checksum algorithm is
MD2.

FW_Upgrade 12 1 U32 / R ---- New FW image file


_Length 2 PDT_UNSIGNE length
D_LONG
DPT_Value_4_
Ucount
(12.001)

AutoSyncAd 12 1 B1 / RW ---- - 0 Disable the auto


dress 3 DPT_Enable synchronize the ARS
address to RTS,
RAQS and RRHS
- 1 Enable the auto
synchronize the ARS
address to RTS,
RAQS and RRHS

65533 1 10 "Applica Interface 1 1 U16 / R ---- Devices that do not PLACE HOLDER!!
tion Object type PDT_UNSIGNE support the Application
Block D_INT Block Alarm Source,
Alarm shall also insert a
Source / placeholder
Application Block /
KNX Interface Object
(Object Type
SUBSTITUTE,
ID=65’533) in its place

52318 1 11 POS89 Interface 1 1 U16 / R ---- This object is used for


DO Object type PDT_UNSIGNE Device Locking
Device D_INT Function (LTE-
Object Runtime Command in
Geographical Zone)
and holds all RU
device specific
parameters, such as
backlight setting,
sound setting etc.

PID_LOAD_ 5 1 PDT_CONTRO RW ---- LSM for control of the


STATE_CON L bootloader
TROL DPT_LoadCont
rol
(DPT-ID =
20.60081)

ObjectIndex 29 1 U8 / R Rea needed for Object => SD-


PDT_UNSIGNE Index Discovery via T060.0601_EN_SARB

A6V11471220_en--_e 55 | 70
10 Appendix
Object list

D_CHAR d.ind LTE-Read onto this _Data_Aquisition:


U8 / Property 7.1.2.10.1
DPT_Value_1_ KNX Standard,
Ucount chapter 3-5-1,
PID_OBJECT_INDEX

Apartment 10 1 U8Z8 / RW ----


1 DPT_UcountVa
lue8_Z

Room 10 1 U8Z8 / RW ----


2 DPT_UcountVa
lue8_Z

Subzone 10 1 U8Z8 / RW ----


3 DPT_UcountVa
lue8_Z

UI_Tstd 11 1 U8 / RW ---- Delay Time since last The default display will
1 DPT_Value_1_ operation in [sec] be loaded if no
Ucount This time is fixed for operations on the RU
4min10sec . in the period of
UI_Tstd.

Bklight_level 11 1 U8 / RW ---- DPT 5.004 --> [0… The brightness of the


4 DPT_Percent_ 255%] with resolution backlight. (0~100%)
U8 1% --> shift to Extended
Allow only range Device Object,
[0 ..100%]; Property 97
U8 / DPT_Percent_U8 (DisplayBacklightValu
is also used by Synco eOn), since already
Living Central introduced in Synco
Apartment Unit for the living product range?
Backlight Brightness Decision: No, since
there's anyway a
conflict in assignement
of the Property ID (97)
in ExtDevObject

Bklight_Tidl 11 1 U8 / RW ---- Delay Time since last Backlight’s waiting


5 DPT_Value_1_ operation in [sec]; time to turn off when
Ucount This time is fixed for no operations on the
3min30sec . RU.

UI_DefaultPa 11 1 N8 / RW ---- This property decides


ge 8 PDT_ENUM8 the default page in a
multipage page set.

Bootloader_ 12 16 PT_UNSIGNED R ---- Checksum for


Checksum 1 _CHAR bootloader upgrade.
The checksum
algorithm is MD2.

Bootloader_L 12 1 U32 / R ---- New bootloader image


ength 2 PDT_UNSIGNE file length
D_LONG
DPT_Value_4_
Ucount
(12.001)

FW_BuildNu 12 1 U16 / R ---- Incremental build


m 3 DPT_Value_2_ number for each FW
Ucount release

Bootloader_ 12 1 U5U5U6 / R ---- Bootloader's version M.V.R (U5U5U6).


Version 4 DPT_Version information Here M(magic) is not
used.
V(version).R(Revision)
before formal release
is 0.1

EnableSched 20 1 DPT_Enable RW ---- [T022.S055-


ulerOperatio 1 2D040.001] Property-
n List of ABI CPC-
“RU_B”

56 | 70 A6V11471220_en--_e
Appendix 10
Object list

EnableSyste 20 1 DPT_Enable RW ---- [T022.S055-


mClockSettin 2 2D040.001] Property-
g List of ABI CPC-
“RU_B”

EnableFanB 20 1 DPT_Enable RW ----


oostOp 3

EnableFirePl 20 1 DPT_Enable RW ----


aceOp 4

EnableKitche 20 1 DPT_Enable RW ----


nHoodOp 5

EnableHeatin 20 1 DPT_Enable RW ----


gScreen 6

EnableDHW 20 1 DPT_Enable RW ----


Screen 7

321 1 13 RTS - Interface 1 1 U16 / R ---- "Room temperature


Room Object type PDT_UNSIGNE sensor". Read only
Temper D_INT
ature
Sensor

ObjectIndex 29 1 U8 / R Rea needed for Object => SD-


PDT_UNSIGNE d.ind Index Discovery via T060.0601_EN_SARB
D_CHAR LTE-Read onto this _Data_Aquisition:
U8 / Property 7.1.2.10.1
DPT_Value_1_ KNX Standard,
Ucount chapter 3-5-1,
PID_OBJECT_INDEX

TempRoom 51 1 V16Z8 / R IR.re


DPT_TempHV q
ACAbs_Z

Apartment 10 1 U8Z8 / RW ----


1 DPT_UcountVa
lue8_Z

Room 10 1 U8Z8 / RW ----


2 DPT_UcountVa
lue8_Z

Subzone 10 1 U8Z8 / RW ----


3 DPT_UcountVa
lue8_Z

TempCorrVal 11 1 V16Z8 / RW ----


ue 1 DPT_TempHV
ACRel_Z

TempCOVCo 11 1 V16Z8 / RW ----


ndition 2 DPT_TempHV
ACRel_Z

TempRoomH 11 1 U16 / RW ---- Repetition time for


eartbeat 5 DPT_TimePerio cyclic sending of the
dSec room temperature
process value output,
if no COV condition
occurs since last
sending.

TempRoom 11 1 U16 / RW ---- Minimum repetition


MinRepTime 6 DPT_TimePerio time for sending of the
dSec room temperature
process value output.

390 1 14 UHD - Interface 1 1 U16 / R ----


User Object type PDT_UNSIGNE
HVAC D_INT
Display

ObjectIndex 29 1 U8 / R Rea needed for Object => SD-

A6V11471220_en--_e 57 | 70
10 Appendix
Object list

PDT_UNSIGNE d.ind Index Discovery via T060.0601_EN_SARB


D_CHAR LTE-Read onto this _Data_Aquisition:
U8 / Property 7.1.2.10.1
DPT_Value_1_ KNX Standard,
Ucount chapter 3-5-1,
PID_OBJECT_INDEX

TempOutside 15 1 V16Z8 / R IR.in Outside temperature


Eff 5 DPT_TempHV d value provided by the
ACAbs_Z Automation Device (°
C) *)
Field Description Sup.
Unit Default
Temperature Outside
temperature value
M °C. cs
STATUS Bitset M
Bit 0 - OutOfService
Sensor out of service
M t/f false
Bit 1 - Fault Sensor
value is corrupted M t/f
false
Bit 2 - Overridden
Sensor is temporarily
overridden O t/f false
Bit 3 - InAlarm Sensor
is in alarm O t/f false
Bit 4 - AlarmUnAck
Acknowledgement of
alarm O t/f false
all other bits are
reserved

TempRoomE 15 1 V16Z8/PDT_G R IR.in Resulting (may be


ff 7 ENERIC_03/DP d averaged) room
T_TempHVAC temperature value
Abs_Z provided by the
Automation Device (°
C) *)

TempRoomS 16 1 V16Z8 / R IR.in Absolute Room => cASA-[T022.S031-


etpAbsEff 1 DPT_TempHV d Temperature Setp 2]-SARB-Data-
ACAbs_Z requested by the Mapping-HVAC
user,calculated from
the HVACMode and
TempRoomSetpUserO
ffset

HVACModeE 16 1 N8Z8 / R IR.in Effective HVACMode


ff 3 DPT_HVACMo d calculated by the
de_Z Automation Device
based on
HVACModeUser
request, Scheduler
etc.

ComfortProlo 16 1 DPT_State R IR.in information if comfort => cASA-[T022.S031-


ngEff 8 d prolongation is active 2]-SARB-Data-
or not Mapping-HVAC
0=inactive; 1 = active

TmpFanMod 20 1 N8 / R IR.in TmpFanMode refers to Enumeration value


e 8 PDT_ENUM8 d the optional process - 0: None
input property of AB - 1: FanBoostMode
UHD to indicate on the - 2: FirePlaceMode
Room Unit (e.g. RU-B) - 3: KitchenHoodMode
if a temporary HRV fan
mode is active

TmpFanMod 20 1 U16 / R IR.in TmpFanModeRemain => cASA-[T022.S035-


eRemainTim 9 DPT_TimePerio d Time refers to the 2I055] Fan operation:
e dSec optional process input Fan Boost/Fire
property of AB UHD Place/Kitchen Hood

58 | 70 A6V11471220_en--_e
Appendix 10
Object list

providing the
remaining duration of
an activated temporary
HRV fan mode.
TmpFanModeRemain
Time will be zero if no
temporary HRV fan
mode is active or in
case of an activated
Kitchen Hood mode
which is not
automatically
terminated by timeout.

TempDHWEf 21 1 V16Z8 / R IR.in TempDHWEff refers to


f 0 DPT_TempHV d the process input
ACAbs_Z property of AB UHD to
indicate the effective
DHW temperature for
visualization purposes
on PL-Link Room
Units.
TempDHWEff is
calculated by the BA-
Device, e.g. an
average of
upper/lower DHW
sensors in the DHW
storage tank

TempDHWS 21 1 V16Z8 / R IR.in TempDHWSetpEff


etpEff 1 DPT_TempHV d refers to the process
ACAbs_Z input property of AB
UHD to indicate the
currently effective
DHW temperature
setpoint for
visualization purposes
on PL-Link Room
Units.

DHWModeEf 21 1 N8Z8 R IR.in DHWModeEff refers to


f 3 d the process input
property of AB UHD to
indicate the currently
effective DHW
operating mode for
visualization.

DelayedHVA 17 1 N8 R IR.in DelayedHVACModeEff


CModeEff 1 d refers to the
proprietary and
optional process input
property to indicate if a
manually triggered
room operating mode
is delayed by an
application specific
function (e.g.
unoccupied selection
and delayed HOME
(Comfort) -> AWAY
(Economy) transition).
DelayedHVACModeEff
is provided by ABI
RSMHD

TmpFanMod 21 1 DPT_State R IR.in TmpFanModeCountdo


eCountdown 6 d wn refers to the
optional and
proprietary process
input property of AB
UHD to differentiate

A6V11471220_en--_e 59 | 70
10 Appendix
Object list

between timed or
indefinite fan mode
and to indicate the
validity of input
property
TmpFanModeRemain
Time.
TmpFanModeCountdo
wn is provided by ABI
FSSM

Apartment 10 1 U8Z8 / RW ----


1 DPT_UcountVa
lue8_Z

Room 10 1 U8Z8 / RW ----


2 DPT_UcountVa
lue8_Z

Subzone 10 1 U8Z8 / RW ----


3 DPT_UcountVa
lue8_Z

OutsideSens 10 1 U8Z8 / RW ---- Outside sensor zone


orZone 4 DPT_UcountVa for TempOutside
lue8_Z

DHWZone 10 1 U8Z8 / RW ---- DHWZone refers to


5 DPT_UcountVa the configuration
lue8_Z property of AB UHD to
define the number of
the DHW zone to
connect AB UHD with
ABIs DHWSM and
DHWTS.

HVACModeD 21 1 DPT_HVACMo R IR.in HVACModeDeterm => [T022.S035-


eterm 7 deDeterm d refers to the 2I010.100] Temporary
proprietary and manual HVAC Mode
optional process input (OEM specific feature)
property to indicate => [T022.S035-
how HVACModeEff is 2I010.110] Manual
currently determined. HVAC Mode via HW
HVACModeDeterm is contact (OEM specific
provided by ABI feature)
RSMHD

1001 1 15 SCLO - Interface 1 1 U16 / R ---- RTC display on the


System Object type PDT_UNSIGNE screen
Clock D_INT

ObjectIndex 29 1 R ----

SystemClock 51 1 U8[r4U4][r3U5][ R IR.in Received Time, date and


U3U5][r2U6][r2 d SystemClock weekday are required
U6]B16 / information from to display:
DPT_DateTime Automation Device Fri, 9, 14:24
DPT_ID = which is always 6E 01 01 00 00 00 00
19.001 master SCLO; 00 --> 10.1.1 0:0:0
updated every 10
minutes

Remark: this datapoint


is currently defined as
S-Mode group objects
with a predefined,
fixed group address
For use on SARB, the
BA-Device will send
SystemClock with an
LTE-InfoReport

Data type definition:


03_07_02 3.20

60 | 70 A6V11471220_en--_e
Appendix 10
Object list

This input signal is


used by SCLO slave
to synchronise its local
clock: i.e.
SystemClock
information is copied
to LocalClock.

SystemClock 52 1 U8[r4U4][r3U5][ R W.re SystemClockSetting => KNX Standard,


Setting U3U5][r2U6][r2 q refers to the process chapter 7/1/1, FB
U6]B16 / input property of ABI System Clock, clause
DPT_DateTime SCLO to write the Input
DPT_ID = master clock via a PL- SystemClockSetting
19.001 Link peripheral device. => [T022.S032-2I015]
• Input Setting of Local-Date
SystemClockSetting and -Time via Room
can be accessed using Unit
LTE Write service and
broadcast addressing
or individual property
addressing.
• [cASA-4.2-050-N]
Implementation of
input
SystemClockSetting is
optional.
If implemented, the
input shall be activated
/ deactivated by the
engineered
configuration
parameter
EnableSystemClockSe
tting of ABI SCLO.
[end-cASA-4.2-050-N]
• [cASA-4.0]
This process signal
will not be
implemented in a 1st
step since there is no
real use case to adjust
date & time
information of the BA
Device via PL-Link.
[end-cASA-4.0]

391 1 16 UPS - Interface 1 1 U16 / R ----


User Object type PDT_UNSIGNE
Presenc D_INT
e Switch

ObjectIndex 29 1 R Rea
d.ind

PresenceStat 51 1 DPT_Occupanc R IR.re


us y q

PresenceStat 15 1 DPT_Bool RW W-
usLocked 5 ind

PresenceStat 20 1 DPT_Occupanc R IR.in


usEff 1 y d

Apartment 10 1 U8Z8 / RW ----


1 DPT_UcountVa
lue8_Z

Room 10 1 U8Z8 / RW ----


2 DPT_UcountVa
lue8_Z

Subzone 10 1 U8Z8 / RW ----


3 DPT_UcountVa
lue8_Z

A6V11471220_en--_e 61 | 70
10 Appendix
Object list

393 1 17 UFS - Interface 1 1 U16 / R ---- Fan Speed user's


User Object type PDT_UNSIGNE setting
Fan D_INT
Speed
Setting

ObjectIndex 29 1 U8 / R Rea needed for Object => SD-


PDT_UNSIGNE d.ind Index Discovery via T060.0601_EN_SARB
D_CHAR LTE-Read onto this _Data_Aquisition:
U8 / Property 7.1.2.10.1
DPT_Value_1_ KNX Standard,
Ucount chapter 3-5-1,
PID_OBJECT_INDEX

FanBoostRe 16 1 B1 / R IR.re FanBoostReq refers to => cASA-[T022.S035-


q 2 PDT_BINARY_I q the optional process 2I055] Fan operation:
NFORMATION output property of AB Fan Boost/Fire
UFS representing a Place/Kitchen Hood
trigger command
requested by the room
occupant to initiate the
temporary Fan Boost
fan mode in HRV
applications

FirePlaceRe 16 1 B1 / R IR.re FirePlaceReq refers to => cASA-[T022.S035-


q 3 PDT_BINARY_I q the optional process 2I055] Fan operation:
NFORMATION output property of AB Fan Boost/Fire
UFS representing a Place/Kitchen Hood
trigger command
requested by the room
occupant to initiate the
temporary Fire Place
fan mode in HRV
applications.

KitchenHood 16 1 B1 / R IR.re KitchenHoodReq => cASA-[T022.S035-


Req 4 PDT_BINARY_I q refers to the optional 2I055] Fan operation:
NFORMATION process output Fan Boost/Fire
property of AB UFS Place/Kitchen Hood
representing a trigger
command requested
by the room occupant
to initiate the
temporary Kitchen
Hood fan mode in
HRV applications.

ResetTmpFa 16 1 B1 / R IR.re ResetTmpFanReq => cASA-[T022.S035-


nReq 5 PDT_BINARY_I q refers to the optional 2I055] Fan operation:
NFORMATION process output Fan Boost/Fire
property of AB UFS Place/Kitchen Hood
representing a trigger
command requested
by the room occupant
to cancel an activated
temporary fan mode in
HRV applications.

FanBoostPro 16 1 U16 / R IR.re FanBoostProlongTime => [T022.S035-


longTime 6 PDT_UNSIGNE q refers to the optional 2I058.020] Operation
D_INT process output of ‘Fan Boost’, ‘Fire
property of AB UFS to Place’ prolong time
adjust the duration of settings
the temporary Fan
Boost ventilation mode
in HRV applications.

FirePlaceProl 16 1 U16 / R IR.re FirePlaceProlongTime => [T022.S035-


ongTime 7 PDT_UNSIGNE q refers to the optional 2I058.020] Operation
D_INT process output of ‘Fan Boost’, ‘Fire
property of AB UFS to Place’ prolong time
adjust the duration of settings
the temporary Fire

62 | 70 A6V11471220_en--_e
Appendix 10
Object list

Place ventilation mode


in HRV applications.

Apartment 10 1 U8Z8 / RW ----


1 DPT_UcountVa
lue8_Z

Room 10 1 U8Z8 / RW ----


2 DPT_UcountVa
lue8_Z

Subzone 10 1 U8Z8 / RW ----


3 DPT_UcountVa
lue8_Z

384 1 18 UHRS - Interface 1 1 U16 / R ---- Room temperature set


User Object type PDT_UNSIGNE point. User's setting
HVAC D_INT
Room
Settings

ObjectIndex 29 1 U8 / R Rea needed for Object => SD-


PDT_UNSIGNE d.ind Index Discovery via T060.0601_EN_SARB
D_CHAR LTE-Read onto this _Data_Aquisition:
U8 / Property 7.1.2.10.1
DPT_Value_1_ KNX Standard,
Ucount chapter 3-5-1,
PID_OBJECT_INDEX

TempRoomS 52 1 V16Z8 / R IR.re Setpoint shift (Method


etpUserOffse DPT_TempHV q A)
t ACRel_Z

ComfortProlo 53 1 B1 / R IR.re Trigger to start an


ngUser DPT_Trigger q additional period of
Comfort Mode
1 = Trigger (0 not
used)

HVACModeU 55 1 N8Z8 / R IR.re HVACMode user


ser DPT_HVACMo q request:
de_Z 0 = AUTO 1 = Comfort
2 = Standby
(PreComfort) 3 =
Economy 4 =
Building.Prot.

HVACModeU 15 1 B1 / DPT_Bool RW W.in 0: Locked = false; Binary information for


serLocked 6 d 1: Locked =true locking operation of
HVAC Mode;
=> cASA-[T022.S031-
2]-SARB-Data-
Mapping-HVAC

HVACModeU 15 1 N8Z8 / R IR.in Result of => cASA-[T022.S031-


serEff 7 DPT_HVACMo d HVACModeUser and 2]-SARB-Data-
de_Z RSMHD internal Mapping-HVAC
settings. It is delivered
by RSMHD

TempRoomS 15 1 V16Z8 / RW W.in Runtime process value => cASA-[T022.S031-


etpUserOffse 8 DPT_TempHV d for Max. negative 2]-SARB-Data-
tMinIN ACRel_Z Offset of Mapping-HVAC
TempRoomSetpUserO
ffset

TempRoomS 15 1 V16Z8 / RW W.in Runtime process value => cASA-[T022.S031-


etpUserOffse 9 DPT_TempHV d for Max. positive 2]-SARB-Data-
tMaxIN ACRel_Z Offset of Mapping-HVAC
TempRoomSetpUserO
ffset

TempRoomS 16 1 B1 / DPT_Bool RW W.in 0: Locked = false; Binary information for


etpUserOffse 0 d 1: Locked =true locking operation of
tLocked RoomTemperature
Setting;

A6V11471220_en--_e 63 | 70
10 Appendix
Object list

'=> cASA-[T022.S031-
2]-SARB-Data-
Mapping-HVAC

TempRoomS 16 1 V16Z8 / R IR.in => cASA-[T022.S031-


etpUserOffse 1 DPT_TempHV d 2]-SARB-Data-
tEff ACRel_Z Mapping-HVAC

StepIncreme 17 1 U8 / RW ---- This property is a Default Value = 1


ntHMI_TRSe 1 DPT_Value_1_ factor value (integer),
tpUsOffset Ucount with which the
smallest locally
defined step increment
(in current units) is
multiplied. The result
is the StepIncrement
on the HMI available
to the user

Apartment 10 1 U8Z8 / RW ----


1 DPT_UcountVa
lue8_Z

Room 10 1 U8Z8 / RW ----


2 DPT_UcountVa
lue8_Z

U Subzone 10 1 U8Z8 / RW ----


3 DPT_UcountVa
lue8_Z

TempRoomS 11 1 V16Z8 / RW ---- Config value for Max. => cASA-[T022.S031-


etpUserOffse 3 DPT_TempHV negative Offset of 2]-SARB-Data-
tMin ACRel_Z TempRoomSetpUserO Mapping-HVAC
ffset

TempRoomS 11 1 V16Z8 / RW ---- Config value for Max. => cASA-[T022.S031-


etpUserOffse 4 DPT_TempHV positive Offset of 2]-SARB-Data-
tMax ACRel_Z TempRoomSetpUserO Mapping-HVAC
ffset

1003 1 19 ALSNK Interface 1 1 U16 / R ---- ALSNK acts as Alarm


- Alarm Object type PDT_UNSIGNE Sink in the Room Unit
Sink D_INT with the purpose to
indicate and
acknowledge Alarm
and Maintenance
information (basic
Alarm functionality)

ObjectIndex 29 1 U8 / R ---- needed for Object => SD-


PDT_UNSIGNE Index Discovery via T060.0601_EN_SARB
D_CHAR LTE-Read onto this _Data_Aquisition:
U8 / Property 7.1.2.10.1
DPT_Value_1_ KNX Standard,
Ucount chapter 3-5-1,
PID_OBJECT_INDEX

AlarmInfo_C 23 1 PT_GENERIC_ R IR.in AlarmInfo_CS refers to


S 0 13 d the process input
property of AB ALSNK
to indicate Alarm Code
and Alarm State
information from ABI
ALSRC to be
visualized on PL-Link
Room Units like RU-B

MaintenanceI 22 1 PT_GENERIC_ R IR.in MaintenanceInfo_CS


nfo_CS 7 13 d refers to the process
input property of AB
ALSNK to indicate
Maintenance Code
and Maintenance
State information from
ABI ALSRC to be

64 | 70 A6V11471220_en--_e
Appendix 10
Object list

visualized on PL-Link
Room Units like RU-B

AlarmAckno 22 1 PDT_BINARY_I R W.re AlarmAcknowledge


wledge 8 NFORMATION q refers to the process
/ DPT_Ack output property of AB
ALSNK to trigger the
acknowledgement of
an unacknowledged
Alarm indication via
PL-Link Room Units
like RU-B.
AB ALSNK acts as a
property client to write
input
AlarmAcknowledge of
the remote ABI
ALSRC

AlarmReset 22 1 PDT_BINARY_I R W.re AlarmReset refers to This feature of AB


9 NFORMATION q the process output ALSNK is optional and
/ DPT_Reset property of AB ALSNK will not be supported
to trigger the reset of in a 1st step.
the locked state of the
BA-Device (caused by
an Alarm indication)
via PL-Link Room
Units like RU-B.
AB ALSNK acts as a
property client to write
input AlarmReset of
the remote ABI
ALSRC

Maintenance 22 1 PDT_BINARY_I R W.re MaintenanceAcknowle


Acknowledge 5 NFORMATION q dge refers to the
/ DPT_Ack process output
property of AB ALSNK
to trigger the
acknowledgement of
an unacknowledged
Maintenance
indication via PL-Link
Room Units like RU-B.
AB ALSNK acts as a
property client to write
input
MaintenanceAcknowle
dge of the remote ABI
ALSRC

Maintenance 22 1 PDT_BINARY_I R W.re MaintenanceReset This feature of AB


Reset 6 NFORMATION q refers to the process ALSNK is optional and
/ DPT_Reset output property of AB will not be supported
ALSNK to trigger the in a 1st step.
reset of the locked
state of the BA-Device
(caused by an
Maintenance
indication) via PL-Link
Room Units like RU-B.
AB ALSNK acts as a
property client to write
input
MaintenanceReset of
the remote ABI
ALSRC

337 1 20 RRHS - Interface 1 1 U16 / R ---- Local Room Relative


Room Object type PDT_UNSIGNE Air Humidity Sensor
Relative D_INT
Humidit
y

A6V11471220_en--_e 65 | 70
10 Appendix
Object list

Sensor

110 1 21 HVACS Interface 1 1 U16 / R ---- HVAC Schedulers ABI HVACS is a proxy
- HVAC Object type PDT_UNSIGNE to map and represent
Schedul D_INT the BA-Weekly-
er Schedule on PL-Link

ObjectIndex 29 1 U8 /
PDT_UNSIGNE
D_CHAR
U8 /
DPT_Value_1_
Ucount

HVACSDaily 23 15 DPT_HVACSS R ---- Daily Program Monday


Prog_Mo 1 witchPoint

HVACSDaily 23 15 DPT_HVACSS R ---- Daily Program


Prog_Tu 2 witchPoint Tuesday

HVACSDaily 23 15 DPT_HVACSS R ---- Daily Program


Prog_We 3 witchPoint Wednesday

HVACSDaily 23 15 DPT_HVACSS R ---- Daily Program


Prog_Th 4 witchPoint Thursday

HVACSDaily 23 15 DPT_HVACSS R ---- Daily Program Friday


Prog_Fr 5 witchPoint

HVACSDaily 23 15 DPT_HVACSS R ---- Daily Program


Prog_Sa 6 witchPoint Saturday

HVACSDaily 23 15 DPT_HVACSS R ---- Daily Program Sunday


Prog_Su 7 witchPoint

181 1 22 UDHWS Interface 1 1 U16 / R ---- User DHW Setttings


ET - Object type PDT_UNSIGNE
User D_INT
DHW
Settings

ObjectIndex 29 1 U8 / R Rea
PDT_UNSIGNE d.ind
D_CHAR
U8 /
DPT_Value_1_
Ucount

TempDHWS 52 1 V16Z8 / R IR.re TempDHWSetpUser => KNX Standard,


etpUser DPT_TempHV q refers to the process chapter 7/11/3, 2.8.4.3
ACAbs_Z output property of AB Output
UDHWSET to adjust TempDHWSetpUser
the DHW temperature => [T022.S040-
setpoint for DHW 3D015.070]
‘Normal’ mode TempDHWSetpUserEf
• Supported Z8-States: f
OutOfService => [T022.S040-
• Default Value (after 3D015.080]
powerup) = TempDHWSetpUserMi
OutOfService nIN
• TempDHWSetpUser => [T022.S040-
must not be sent after 3D015.090]
a reboot of the Room TempDHWSetpUserM
Unit. Transmission of axIN
TempDHWSetpUser
may be triggered by
user interaction on the
HMI only.
• Heartbeat: no

DHWPushUs 53 1 B1 / R IR.re DHWPushUser refers => KNX Standard,


er DPT_Trigger q to the process output chapter 7/11/3, clause
property of AB 2.8.4.4 Output
UDHWSET to trigger DHWPushUser
the DHW push
function and to load

66 | 70 A6V11471220_en--_e
Appendix 10
Object list

the DWH storage tank


once to the ‘Normal’
temperature setpoint.
• Default Value (after
powerup) = 0
• DHWPushUser is a
trigger signal that must
not be sent after a
powerup.
DHWPushUser may
be triggered by user
interaction on the HMI
only.

DHWModeU 51 1 N8Z8 / R IR.re DHWModeUser refers => KNX Standard,


ser DPT_DHWMod q to the process output chapter 7/11/3, clause
e_Z property of AB 2.8.4.2 Output
UDHWSET to change DHWModeUser
the DHW user
operating mode via a
Room Unit.
• Supported Z8-States:
OutOfService
• Default Value (after
powerup) =
OutOfService
• DHWModeUser must
not be sent after a
reboot of the Room
Unit. Transmission of
DHWModeUser may
be triggered by user
interaction on the HMI
only.
• Heartbeat: no

DHWModeU 15 1 B1 / DPT_Bool RW W.in DHWModeUserLocke


serLocked 6 d d refers to the
proprietary input
process signal of AB
UDHWSET to lock or
enable the manual
operation of
DHWModeUser on the
Room Unit.

DHWModeU 25 1 N8Z8 / R IR.in DHWModeUserEff => KNX Standard,


serEff 4 DPT_DHWMod d refers to the process chapter 7/11/3, clause
e_Z input property of AB 2.8.4.7 Input
UDHWSET to indicate DHWModeUserEff
the effective user-
request ‘Auto’ or
‘Manual’ for the DHW
operating mode.
• Supported Z8-States:
none (for received PL-
Link message)
• Default Value (after
powerup) of local copy
of property
DHWModeUserEff
= ‘void’, e.g. with Z8
‘OutOfService’
=> local firmware
decision to encode the
‘void’ state
• After a reboot of the
Room Unit the local
copy of property
DHWModeUserEff
remains ‘void’ until the
1st DHWModeUserEff
message is received.

A6V11471220_en--_e 67 | 70
10 Appendix
Object list

• Local copy of
property
DHWModeUserEff
becomes valid if the
1st DHWModeUserEff
message is received

DHWPushAc 25 1 B1 / DPT_Bool R IR.in DHWPushActive


tive 2 d refers to the process
intput property of AB
UDHWSET to indicate
whether the DHW
push function is active
or not. This
information may be
used by the Room Unit
for visualization

TempDHWS 24 1 V16Z8 / R IR.in TempDHWSetpUserEf => [T022.S040-


etpUserEff 6 DPT_TempHV d f refers to the process 3D015.010]
ACAbs_Z input property of AB TempDHWSetpUser
UDHWSET to indicate => [T022.S040-
the effective user 3D015.360]
defined DHW TempDHWSetpUserMi
temperature setpoint n
for ‘Normal’ mode
• DWW temperature
setpoint editing shall
start with the current
value of property
TempDHWSetpUserEf
f.
• After the
transmission of
process signal
TempDHWSetpUser,
AB UDHWSET shall
immediately update of
local copy of
TempDHWSetpUserEf
f with the new setpoint.
Later on, updated
feedback information
TempDHWSetpUserEf
f will be received from
ABI DHWSM within
1..2s to confirm or
correct the previous
user setpoint settings

TempDHWS 15 1 V16Z8 / R/ W.in TempDHWSetpUserMi => [T022.S040-


etpUserMinI 8 DPT_TempHV W d nIN refers to the 3D015.010]
N ACAbs_Z process input property TempDHWSetpUser
of AB UDHWSET to => [T022.S040-
define the dynamic 3D015.360]
lower limit to adjust the TempDHWSetpUserMi
DHW temperature n
setpoint and to define
the lower limit of
process signal
TempDHWSetpUser

TempDHWS 15 1 V16Z8 / R/ W.in TempDHWSetpUserM => [T022.S040-


etpUserMaxI 9 DPT_TempHV W d axIN refers to the 3D015.010]
N ACAbs_Z process input property TempDHWSetpUser
of AB UDHWSET to => [T022.S040-
define the dynamic 3D015.370]
upper limit to adjust TempDHWSetpUserM
the DHW temperature ax
setpoint and to define
the upper limit of
process signal
TempDHWSetpUser

68 | 70 A6V11471220_en--_e
Appendix 10
Object list

TempDHWS 16 1 B1 / DPT_Bool R/ W.in TempDHWSetpUserL


etpUserLock 0 W d ocked refers to the
ed proprietary input
process signal of AB
UDHWSET to lock or
enable the manual
adjustment of
TempDHWSetpUser
on the Room Unit.

TempDHWS 16 1 V16Z8 / R/ ---- TempDHWSetpUserMi => [T022.S040-


etpUserMin 1 DPT_TempHV W n refers to the 3D015.070]
ACAbs_Z configuration property TempDHWSetpUserEf
of AB UDHWSET to f
define the static outer => [T022.S040-
lower limit to edit the 3D015.080]
setpoint TempDHWSetpUserMi
TempDHWSetpUser nIN

TempDHWSetpUserMi
n may be used to
initialize
TempDHWSetpUser

TempDHWSetpUserMi
n shall be used to
initialize
TempDHWSetpUserMi
nIN

TempDHWS 16 1 V16Z8 / R/ ---- TempDHWSetpUserM => [T022.S040-


etpUserMax 2 DPT_TempHV W ax refers to the 3D015.090]
ACAbs_Z configuration property TempDHWSetpUserM
of AB UDHWSET to axIN
define the static outer
upper limit to edit the
setpoint
TempDHWSetpUser

TempDHWSetpUserM
ax shall be used to
initialize
TempDHWSetpUserM
axIN

DHWZone_C 10 1 U8Z8 R/ ---- DHWZone refers to => KNX Standard,


ontroller 1 /DPT_UcountV W the KNX standardized chapter 7/11/3, clause
alue8_Z configuration property 2.2.4.14 Parameter:
to define the number DHWZone_Controller
of the DHW zone to => [T022.S037-
connect ABI DHWSM 2I010.015] Attaching
with ABs USHWSET ABI DHWSM to the
and UHD. BA-Model
• Supported Z8-States: => [T022.S037-
OutOfService 2I020.010] Attaching
• Supported-Z8- ABI DHWSM to the
Commands: BA-Model
NormalWrite, SetOSV
& ResetOSV
• Default value = 1

A6V11471220_en--_e 69 | 70
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

© Siemens Switzerland Ltd, 2021


Technical specifications and availability subject to change without notice.

A6V11471220_en--_e