A6V11705292 Datasheet POS8.44xx - en
A6V11705292 Datasheet POS8.44xx - en
4440/109
Room operator units
Basic Documentation
A6V11471220_en--_e
2021-09-06
Table of Contents
2 | 70 A6V11471220_en--_e
About this document 1
Revision history
All product names listed in the table are registered (®) or not registered (™)
trademarks of the owner listed in the table. We forgo the labeling (e.g. using the
symbols ® and ™) of trademarks for the purposes of legibility based on the
reference in this section.
Copyright This document may be duplicated and distributed only with the express permission
of Siemens, and may be passed on only to authorized persons or companies with
the required technical knowledge.
Quality assurance These documents were prepared with great care.
● The contents of all documents are checked at regular intervals.
● All necessary corrections are included in subsequent versions.
● Documents are automatically amended as a consequence of modifications and
corrections to the products described.
Please make sure that you are aware of the latest document revision date.
If you find any lack of clarity while using this document, or if you have any criticisms
or suggestions, please contact the nearest branch office. Addresses for Siemens
regional companies are available at www.siemens.com/sbt.
Document use/ request Before using our products, it is important that you read the documents supplied
to the reader with or ordered at the same time as the products (equipment, applications, tools
etc.) carefully and in full.
We assume that persons using our products and documents are authorized and
properly trained and have the requisite technical knowledge to use our products as
intended.
Additional information on products and applications is available:
A6V11471220_en--_e 3 | 70
1 About this document
Reference documents
4 | 70 A6V11471220_en--_e
Product overview 2
Type summary
2 Product overview
2.2 Features
● Measurement of room temperature (POS8.4420/109)
● Measurement of room temperature and humidity (POS8.4440/109)
● Keys to adjust the room temperature setpoint, ventilation, domestic hot water,
scheduler settings depending on the controller application
● LCD display of room temperature, operating modes, humidity (only for
POS8.4440/109), scheduler, notification, and clock setting
● Operation with 8 pushbuttons
● 2-wire interface to the controller through KNX PL-Link
● Power supply of the room operator unit over KNX PL-Link
● LCD display with backlight
POS8.44 QMX3.P
POS9 QBM97
A6V11471220Z01
POS3.xx15 POL903.00
A6V11471220_en--_e 5 | 70
2 Product overview
Mechanical design
2.5 Diagrams
To find the location of the KNX PL-Link plug, refer to Mechanical design
NOTICE! Users can choose either pair of the pins to connect.
NOTICE
Wires are NOT interchangeable!
The device is protected against faulty wiring, but communications does not work
on interchanged wires. The KNX / KNX PL-Link bus MUST NOT be connected to
the tool plug, only the tool.
6 | 70 A6V11471220_en--_e
Product overview 2
Diagrams
Tool plug
Connector Pin Description
+ KNX PL-Link (positive)
A6V11471220_en--_e 7 | 70
2 Product overview
Dimensions
2.6 Dimensions
Unit: mm
8 | 70 A6V11471220_en--_e
Important information on safety and disposal 3
General regulations
A6V11471220_en--_e 9 | 70
3 Important information on safety and disposal
Disposal
3.4 Disposal
The device is considered an electronic device for disposal in
accordance with European Directive and may not be disposed of as
domestic waste.
● Use only designated channels for disposing the devices.
● Comply with all local and currently applicable laws and
regulations.
10 | 70 A6V11471220_en--_e
Mounting and installation 4
Preparation
4.1 Preparation
Check package contents Check the package contents for visible signs of transport damage and for
completeness.
Do not install parts damaged during shipment. Contact your Siemens
representative in the event of damaged parts.
Check operating Note the information in the data sheet of these operating instructions before
conditions installing the device:
● Climatic ambient conditions
● Protection classes
Check locations
● The devices are suitable for wall mounting and panel mounting.
● Recommended height: 1.50 m above the floor.
● Do not mount the devices in recesses, shelves, behind curtains or doors, or
above or near heat sources.
● Avoid direct solar radiation and drafts.
● Seal the conduit box or the installation tube if any, as air currents can affect
sensor readings.
● Adhere to allowed ambient conditions.
A6V11471220_en--_e 11 | 70
4 Mounting and installation
Mounting instructions
● Remove the breakout on the housing before putting the cable into the gaining
channel.
● If 4-wire cables are used for daisy chain wiring, remove the cable coating, as it
will not fit in the gaining channel.
Cable ducts on the wall
● Keep a distance of at least 20 mm from the base plate to any object above the
base plate such as cable ducts to snap the device cover onto the base plate.
Panel mounting
12 | 70 A6V11471220_en--_e
Mounting and installation 4
Mounting instructions
Dismounting/service
A6V11471220_en--_e 13 | 70
5 Engineering
5 Engineering
TempOutsideEff
Process Data
IR.ind
TempOutsideEff
Management Data
ObjectType 390
Configuration Data
OutsideSensorZone Value (U8Z8)
TempRoomEff
14 | 70 A6V11471220_en--_e
Engineering 5
Process Data
IR.ind
TempRoomEff
Management Data
ObjectType 390
Configuration Data
BuildingZone Value (U8Z8)
Room Value (U8Z8)
Subzone Value (U8Z8)
HumRelRoomEff
Process Data
IR.ind
HumRelRoomEff
Management Data
ObjectType 390
Configuration Data
BuildingZone Value (U8Z8)
Room Value (U8Z8)
Subzone Value (U8Z8)
A6V11471220_en--_e 15 | 70
5 Engineering
16 | 70 A6V11471220_en--_e
Engineering 5
Unoccupied mode
A6V11471220_en--_e 17 | 70
5 Engineering
Management Data
ObjectType 391
Configuration Data
BuildingZone Value (U8Z8)
Room Value (U8Z8)
Subzone Value (U8Z8)
PrioThreshPresenceStatusLocked Value (N8Z8)
(DPT_ID =
7.010)
18 | 70 A6V11471220_en--_e
Engineering 5
Temporary mode
BA-Model
Binary-Calc-Value ResetTmpFanRequest Analog-Calc-Value ManualFanSpeed Analog-Proc-Value TemporaryFanRemainTime Multistate-Proc-Value TemporaryFanMode
Binary-Calc-Value KitchenHoodRequest Binary-Calc-Value ManualFanMode Present-Value 15 min Present-Value FirePlaceMode
Binary-Calc-Value FirePlaceRequest
None
Binary-Calc-Value FanBoostRequest FanBoostMode
State-Text
FirePlaceMode
Present-Value Active
PL-1:PR=FSSM. KitchenHoodMode
Update-Count n
TmpFanMode
I/O-Address PL-1:PR=FSSM.
PL-1:PR=FSSM. RemainTime;
I/O-Address TmpFanMode;
I/O-Address FanBoostReq; Analog-Proc-Value FanSpeedEff GEO=24.6.1;
GEO=24.6.1;
GEO=24.6.1;
{ }
LTE IR (Trigger) FanBoostReq
TmpFanModeRemainTime LTE IR (15min)
LTE IR (Trigger) FirePlaceReq
LTE IR (Trigger) KitchenHoodReq
TmpFanMode LTE IR (FirePlace) [cASA-4.2-100-N]
LTE IR (Trigger) ResetTmpFanReq new optional FSSM
output process signals
Config-Property-Client for temporary HRV fan
NumberOfSteps Property_W (3) operation
[cASA-4.2-100-N]
new optional FSSM
input process signals FSSM Configuration Data
for temporary HRV fan Geographical Zone 24.6.1
operation PrioThreshFanSpeedUserLocked 7
PrioDirectControl 8
}
LTE W (false) FanSpeedUserLocked FanBoostReq LTE IR (Trigger) LTE IR (...) FanSpeedEffWhy
{
FanSpeedUserMinIN FirePlaceReq LTE IR (Trigger) TmpFanModeRemainTime
LTE IR (15min)
FanSpeedUserMaxIN KitchenHoodReq LTE IR (Trigger)
LTE IR (FirePlace) TmpFanMode
ResetTmpFanReq LTE IR (Trigger)
[cASA-4.2-100-N] [cASA-4.2-100-N]
Management Data new optional UFS new optional UHD
Management Data
output process signals input process signals
UFS Discovery & Diagnostic Data for temporary HRV fan for temporary HRV fan UHD Discovery & Diagnostic Data
operation operation
UFS Configuration Data UFS Configuration Data
RU Device Object
[cASA-4.2-100-N]
parameters to enable/ Configuration Data
disable operation of EnableFanBoostOp true
temporary fan modes EnableFirePlaceOp true
at runtime EnableKitchenHoodOp true
A6V11471220_en--_e 19 | 70
5 Engineering
Temperature setpoint
20 | 70 A6V11471220_en--_e
Engineering 5
A6V11471220_en--_e 21 | 70
5 Engineering
22 | 70 A6V11471220_en--_e
Engineering 5
BA-Model
Binary Calculated Value Multistate-Calculated-Value Multistate-Process-Value Binary Process Value
Present-Value Active Present-Value Auto Present-Value Normal Present-Value Inactive
Number-of-States 5 Priority-Array …. Priority-Array ….
Auto Present-Priority 16 Present-Priority 16
Normal Number-of-States 4
State-Text Reduced Why-Indication [16] x
Off/FrostProtect
Normal
LegioProtect
Reduced
State-Text
Off/FrostProtect
LegioProtect
Update-Count n Update-Count n Update-Count n Update-Count n
PL-1:PR=DHWSM. PL-1:PR=DHWSM. PL-1:PR=DHWSM. PL-1:PR=DHWSM.
I/O-Address DHWPushUser; I/O-Address DHWModeUser; I/O-Address DHWModeEff; I/O-Address DHWPushActive;
APP=DHW.1; APP=DHW.1; APP=DHW.1; APP=DHW.1;
Configuration Data
DHW Zone 1
PrioThreshDHWModeUserLocked 7
PrioDirectControl 8
A6V11471220_en--_e 23 | 70
5 Engineering
Operation of DHW
setpoint via Room Unit
24 | 70 A6V11471220_en--_e
Engineering 5
BA-Model
Analog-Calculated-Value Analog-Process-Value Analog-Process-Value
Present-Value 58°C Present-Value 65°C Present-Value 58°C
Units °C Priority-Array …. Priority-Array ….
Present-Priority 15 Present-Priority 15
Min-Present-Value 45°C Units °C Units °C
Max-Present-Value 60°C Why-Indication [16] x Why-Indication [16] x
represent represent
represent
Configuration Data
DHW Zone 1
PrioThreshTempDHWSetpUserLocked 7
A6V11471220_en--_e 25 | 70
5 Engineering
Visualization of DHW
Temperature
26 | 70 A6V11471220_en--_e
Engineering 5
BA-Model
Analog-Process-Value
Present-Value 53°C
Units °C
PL-1:PR=DHWTS.
I/O-Address TempDHWEff;
APP=DHW.1;
represent
Configuration Data
DHW Zone 1
Management Data
Configuration Data
DHW Zone 1
A6V11471220_en--_e 27 | 70
5 Engineering
Scheduler
28 | 70 A6V11471220_en--_e
Engineering 5
BA-Peripheral-Device-Object
I/O-Address PL-1:DL=5;
A6V11471220_en--_e 29 | 70
5 Engineering
Adjust clock
30 | 70 A6V11471220_en--_e
Engineering 5
BA-Model
Device-Object
Local-Time 10:36:28
Local-Date 31-05-2010; Monday
UTC-Offset 120
Daylight-Savings-Status true
Firmware
(OS)
LTE Broadcast
LTE IR (2010-05-1;Mon;10:36:28;SuTi) SystemClock
(DPT_ID =
7.010)
A6V11471220_en--_e 31 | 70
5 Engineering
Notification: Alarm /
Service
BA-Model
MPV-Object APV-Object MPV-Object MPV-Object APV-Object MPV-Object
MTV-Object MTV-Object
Error- Error- Error- Maintenance- Maintenance- Maintenance-
Error- Maintenance-
Indication- Code- Cmd-State- Indication- Code- Cmd-State-
Cmd-RU Cmd-RU
RU RU RU RU RU RU
AlarmAcknowledge
MaintenanceAcknowledge AlarmInfo_CS
AlarmReset MaintenanceInfo_CS
MaintenanceReset
32 | 70 A6V11471220_en--_e
Engineering 5
Auxiliary input
A6V11471220_en--_e 33 | 70
5 Engineering
BA-Model
Multistate-Process-Value Multistate-Process-Value
Present-Value Economy Present-Value HardwareContact
Priority-Array ….
Present-Priority 7
Why-Indication[16] x Number-of-States 4
Number-of-States 4
Auto
Protection
RUManualPermanent
Manual override of HVACMode via Economy State-Text
Multistate-Input-Object State-Text RUManualTemporary
a hardware contact will normally Precomfort
HardwareContact
Present-Value EconomySwitch result in Present-Priority=7 Comfort
Update-Count n Update-Count n
PL-1:PR=RSMHD. PL-1:PR=RSMHD.
I/O-Address HVACModeEff; I/O-Address HVACModeDeterm;
GEO=24.6.1; GEO=24.6.1;
represent represent
Management Data
ON
UHD Discovery & Diagnostic Data
AWAY
UHD Configuration Data
Geographical Zone 24.6.1
34 | 70 A6V11471220_en--_e
Engineering 5
A6V11471220_en--_e 35 | 70
6 Commissioning
Programming pin and service LED
6 Commissioning
Prerequisites Before commissioning a room operator unit, make sure an application is
downloaded onto the connected controller, from where the functions are
downloaded into the room operator unit.
After successful commissioning, the room operator unit displays the default
operating page defined in the application loaded in the controller.
Automatic In a 1:1 connection, i.e. only one room operator unit connecting to one controller,
commissioning (1:1 when powered up via the KNX bus for the first time, the room operator unit
connection) automatically commissions itself.
After successful commissioning, the room operator unit displays the default
operating page defined in the application loaded in the room automation station.
6.1.1 Addressing
1. Briefly press the programming pin (< 2 s).
The device enters programming mode; the service LED is continuously on.
The tool identifies and assigns the currently active device.
2. After the device is commissioned, deactivate programming mode by shortly
pressing the programming pin (< 2 s). The service LED goes off.
Note:
● Programming mode returns to “disabled” each time the device restarts.
● Addressing and commissioning can be done automatically if a POS3.xx15
is connected to the device.
36 | 70 A6V11471220_en--_e
Commissioning 6
Programming pin and service LED
NOTICE
This operation resets all user-defined data and configuration settings to
factory default.
This operation is irreversible.
A6V11471220_en--_e 37 | 70
7 Technical data
7 Technical data
Power supply
Operating voltage KNX PL-Link DC 21...30 V
Interfaces
Type of port between controller and room KNX PL-Link
operating unit KNX PL-Link
Standard KNX connector Wire diameter 0.8 mm, max. 1.0 mm (solid conductors
only)
Sensor data
Temperature Sensor Measuring element NTC resistance sensor
38 | 70 A6V11471220_en--_e
Technical data 7
UL Compliance UL916
NOTICE
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turning the device off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and receiver.
● Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
● Consult the dealer or an experienced radio/TV technician for help.
Weight 145 g
Weight 146 g
A6V11471220_en--_e 39 | 70
8 Functions
8 Functions
Elements Functions
Home mode / Away mode / Temporary mode
/ /
/ Auto / Manual
Manual
Ventilation page
Temperature page
Notification page
Clock page
Wait
Start
List
Reset
Confirm
40 | 70 A6V11471220_en--_e
Functions 8
Elements Functions
Cancel
Go back
/ Exit / next
Edit
Delete
Time
Switch point
Outside temperature
Room temperature
A6V11471220_en--_e 41 | 70
9 Operation
Ventilation page
9 Operation
In temporary mode
42 | 70 A6V11471220_en--_e
Operation 9
Temperature page
In away mode
In home mode
22.0
6
A6V11471220_en--_e 43 | 70
9 Operation
Domestic hot water page
In temporary mode
44 | 70 A6V11471220_en--_e
Operation 9
Notification page
Alarm notification When an event comes in, e.g., event number 1236, the following is displayed.
The screen blinks until it gets acknowledged.
Note: stands for type 1: Alarm notification. When a new alarm comes in, it
overrides the existing one. The screen continues to show type 1.
Then press button 5 to send a request to the controller to acknowledge all alarms.
The following is displayed while waiting for the feedback from the controller.
A6V11471220_en--_e 45 | 70
9 Operation
Notification page
With only notifications left, press button 7 to enter the reset page.
On the reset page, press 3 or 7 to switch between notification and reset page.
The notifications are deleted after resetting and the screen returns to the
notification page.
46 | 70 A6V11471220_en--_e
Operation 9
Notification page
A6V11471220_en--_e 47 | 70
9 Operation
Clock page
Service notifications disappear and the screen returns to the notification page after
the device receives a maintenance, normal and Acked (acknowledged) feedback
from the controller.
48 | 70 A6V11471220_en--_e
Operation 9
Standard and expert settings
From the above page, press button 8 to enter the following page to further edit the
scheduler:
A6V11471220_en--_e 49 | 70
9 Operation
Standard and expert settings
Expert settings From the default page, long-press buttons 6 and 8 simultaneously to enter the
expert settings page:
50 | 70 A6V11471220_en--_e
Operation 9
Standby page
When no operation occurs on the screen for a while, the room operator units turns
off backlighting and displays the standby page automatically. There are 5 types of
standby pages. Users can select from the standard settings P02.
Press any button to activate backlighting and any button again to enter the default
page.
A6V11471220_en--_e 51 | 70
10 Appendix
Parameters
10 Appendix
10.1 Parameters
Parameters for standard
settings Parameters Description Default
P01 Backlighting level: 1, 2, …, 10 5
52 | 70 A6V11471220_en--_e
Appendix 10
Object list
PID_IO_LIST 71 25 U16 / R ---- Array which lists for acc. KNX Standard,
PDT_UNSIGNE each object index the chapter 3/5/1
D_INT[ ] Object Type Resources,
PID_IOLIST
A6V11471220_en--_e 53 | 70
10 Appendix
Object list
Type 7: 7 7.1.2.9.3
All others: reserved
DevTypeID 24 1 N16U32 / R ---- Used for device type DPT definition: SD-
6 PDT_GENERIC identification and T060.0601_EN_SARB
_06 compatibility check _Data_Aquisition
DPT_DeviceTy between configuration 7.1.2.9.3
peID data and device
capabilities (Interface /
Object List Version)
ObjectIndex 29 1 R Rea
d.ind
54 | 70 A6V11471220_en--_e
Appendix 10
Object list
lue8_Z
65533 1 10 "Applica Interface 1 1 U16 / R ---- Devices that do not PLACE HOLDER!!
tion Object type PDT_UNSIGNE support the Application
Block D_INT Block Alarm Source,
Alarm shall also insert a
Source / placeholder
Application Block /
KNX Interface Object
(Object Type
SUBSTITUTE,
ID=65’533) in its place
A6V11471220_en--_e 55 | 70
10 Appendix
Object list
UI_Tstd 11 1 U8 / RW ---- Delay Time since last The default display will
1 DPT_Value_1_ operation in [sec] be loaded if no
Ucount This time is fixed for operations on the RU
4min10sec . in the period of
UI_Tstd.
56 | 70 A6V11471220_en--_e
Appendix 10
Object list
A6V11471220_en--_e 57 | 70
10 Appendix
Object list
58 | 70 A6V11471220_en--_e
Appendix 10
Object list
providing the
remaining duration of
an activated temporary
HRV fan mode.
TmpFanModeRemain
Time will be zero if no
temporary HRV fan
mode is active or in
case of an activated
Kitchen Hood mode
which is not
automatically
terminated by timeout.
A6V11471220_en--_e 59 | 70
10 Appendix
Object list
between timed or
indefinite fan mode
and to indicate the
validity of input
property
TmpFanModeRemain
Time.
TmpFanModeCountdo
wn is provided by ABI
FSSM
ObjectIndex 29 1 R ----
60 | 70 A6V11471220_en--_e
Appendix 10
Object list
ObjectIndex 29 1 R Rea
d.ind
PresenceStat 15 1 DPT_Bool RW W-
usLocked 5 ind
A6V11471220_en--_e 61 | 70
10 Appendix
Object list
62 | 70 A6V11471220_en--_e
Appendix 10
Object list
A6V11471220_en--_e 63 | 70
10 Appendix
Object list
'=> cASA-[T022.S031-
2]-SARB-Data-
Mapping-HVAC
64 | 70 A6V11471220_en--_e
Appendix 10
Object list
visualized on PL-Link
Room Units like RU-B
A6V11471220_en--_e 65 | 70
10 Appendix
Object list
Sensor
110 1 21 HVACS Interface 1 1 U16 / R ---- HVAC Schedulers ABI HVACS is a proxy
- HVAC Object type PDT_UNSIGNE to map and represent
Schedul D_INT the BA-Weekly-
er Schedule on PL-Link
ObjectIndex 29 1 U8 /
PDT_UNSIGNE
D_CHAR
U8 /
DPT_Value_1_
Ucount
ObjectIndex 29 1 U8 / R Rea
PDT_UNSIGNE d.ind
D_CHAR
U8 /
DPT_Value_1_
Ucount
66 | 70 A6V11471220_en--_e
Appendix 10
Object list
A6V11471220_en--_e 67 | 70
10 Appendix
Object list
• Local copy of
property
DHWModeUserEff
becomes valid if the
1st DHWModeUserEff
message is received
68 | 70 A6V11471220_en--_e
Appendix 10
Object list
A6V11471220_en--_e 69 | 70