Brochure Borri B9000FXS EN OMG60098revD 03-18

This document provides information about an uninterruptible power supply model B9000FXS from 60 to 300 kVA. It includes applications, highlights, features and benefits, technical data, connectivity options, and environmental specifications.

Uploaded by

Bender Argentina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views4 pages

Brochure Borri B9000FXS EN OMG60098revD 03-18

This document provides information about an uninterruptible power supply model B9000FXS from 60 to 300 kVA. It includes applications, highlights, features and benefits, technical data, connectivity options, and environmental specifications.

Uploaded by

Bender Argentina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

B9000FXS

Uninterruptible Power Supply


3-Ph from 60 to 300 kVA

Applications Highlights
• Small and medium data centres • On-line double conversion
• Networks and servers • Full IGBT technology
• Industrial control and process • Paralleling up to 1.8 MVA
automation
• Medical equipment
• Building automation
B9000FXS
Uninterruptible Power Supply
3-Ph from 60 to 300 kVA

Features and benefits Main options


● High double conversion efficiency and ● Backfeed protection bypass contactor.
ECO mode for low running costs and ● Bypass isolation transformer.
environmental impact.
● Transformers/autotransformers for
● Front access to all critical components voltage adjustment.
for easy maintenance.
● Battery voltage temperature
● Built-in inverter transformer for DC/AC compensation.
galvanic protection of industrial type
loads. ● External maintenance bypass
wall-mounted box.
● Hot connection/disconnection of parallel
units for easy system resizing. ● Battery fuse switch wall-mounted box.
● Full IGBT technology and electronic PFC, ● Associated battery cabinets for long
ensuring 0.99 input PF and THDi<3% autonomy times.
for maximum upstream sources ● Parallel kit for load sharing.
compatibility.
● Load-sync for single UPS units.
● Accurate battery management providing Load-sync box for two sets of
ripple current minimization charge paralleled UPS.
current/voltage control as per batteries
● Top cable entry.
manufacturers’ specifications and
automatic/manual battery test
for maximum battery expected life
preservation.
Dynamic Charging Mode (DCM) for
Dynamic Charging Mode (DCM)

maximum versatility in long autonomy
and low charging time applications. The battery charging current can be set
● Smart parallel management in load above the nominal, up to the DCM limit,
sharing, load synchronization of single in order to manage high capacity battery
UPS systems and load synchronization packs. The extra charging power is fed to
of two paralleled systems for optimum the battery, as long as the load does not
protection. requires it. This is a firmware enabled
● Dual DSP plus microcontroller logics for feature.
top performance and reliability.
● CAN-bus based distributed parallel
control ensuring high load sharing
accuracy and no single point of failure in
parallel systems. Bypass
● Comprehensive set of communication
options for total remote monitoring of
equipment operation. Mains Output
● Fully compliant with all international
product standards for maximum quality
guarantee.
B9000FXS technical data
Rating (kVA) 60 80 100 125 160 200 250 300
Nominal power (kW) 54 72 90 112.5 144 180 225 270
Dimensions WxDxH (mm) 815x825x1670 1200x860x1900
UPS weight (kg) 570 600 625 660 715 970 1090 1170
Battery configuration External, 300 to 312 cells, VRLA (other options)
Input
Connection type Hardwired 3w (rectifier), 4w (bypass)
400 Vac 3-phase (rectifier)
Nominal voltage
380/400/415 Vac 3-phase with neutral (bypass)
Voltage tolerance -20%, +15% (rectifier); ±10% (bypass)
Frequency and range 50/60 Hz, 45 to 65 Hz
Power factor 0.99
Current distortion (THDi) <3%
Output
Connection type Hardwired 4w
Nominal voltage 380/400/415 Vac 3-phase with neutral
Frequency 50/60 Hz
Static: ±1%;
Voltage regulation
dynamic: IEC/EN 62040-3 Class 1
Power factor Up to 0.9, lagging or leading without power derating
Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s, 200% for 100 ms;
Overload capacity
bypass: 150% continuous, 1000% for 1 cycle
Efficiency (AC/AC)* Up to 98%
Classification as per
VFI-SS-111
IEC/EN 62040-3
Connectivity and function extensions
Front panel Graphic display, mimic LED panel and keyboard, local EPO
Included: serial RS232 and USB; input terminal block for: remote emergency
power off (REPO), battery circuit breaker aux. cont., external maintenance bypass
circuit breaker aux. cont., diesel mode aux. contact.
Remote communication
Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP
(Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter;
SPDT contact relay board; remote system monitoring panel;
UPS managing and server shutdown software
Isolation transformer; transformers/autotransformers for voltage adjustment;
external maintenance bypass; custom battery cabinets; wall-mounted battery fuse
Optional function extensions
switch box; battery thermal probe; parallel kit, top cable entry;
load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request
System
Protection degree IP 20 (other options)
Colour RAL 7016 (other options)
Installation layout Wall, back to back and side by side installation allowed
Accessibility Front and top access, bottom cable entry

*according to IEC/EN 62040-3

Other features

Environmental
Operating temperature range 0°C to +40°C
Storage temperature range -10°C to +70°C
Altitude (AMSL) < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m
Audible noise at 1m (dBA) <62
Standards and certifications
Quality assurance,
environment, health and ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007
safety
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2
Environmental aspects IEC/EN 62040-4
Test and performance IEC/EN 62040-3 (VFI-SS-111)
Protection degree IEC 60529
Marking CE
B9000FXS series options
Description When do I use it

Parallel kit When the unit is to be paralleled for load sharing


LOAD

To synchronize single units’ output for no-break load


Load-sync for single units
transfers by downstream static transfer switches

LOAD A LOAD B

LOAD SYNC
To synchronize the output of two paralleled UPS systems
BOX Load-sync box for two sets of paralleled UPS for no-break load transfers by
downstream static transfer switches
LOAD A LOAD B

To be fully protected against backfeed energy


Backfeed protection bypass contactor
upon static bypass failure

Top
To allow input and output cable entry from the
cable Top cable entry in extended cabinet
entry top of the unit

OMG60098revD - 03-2018 - Due to our policy of continuous development, data in this document is subject to change without notice and becomes contractual only after written confirmation
Bypass isolation transformer To galvanically isolate UPS from load or to
in extended cabinet change system’s earth arrangement

Battery fuse switch in wall-mounted box To disconnect and protect an external battery pack

For charging voltage compensation with temperature


Battery temperature probe
(10 m cable length)

To send UPS status to PLC’s, SCADA’s or AS400’s by


Dry contact relay card
voltage free SPDT contacts

To monitor UPS status by a LED panel from a


Remote monitoring panel
remote control room (relay card required)

To send UPS status to BMS’s by RS485 connection and


RS485 ModBus-RTU port ModBus-RTU protocol.
For remote monitoring and remote service

To send UPS status to BMS’s by Ethernet connection and SNMP


or ModBus over IP protocol. To monitor UPS status by any
Web/SNMP Adapter
internet browser from workstations. To receive SMS or e-mail
alerts from the UPS on any portable device

When the Emergency Power Off (EPO) has to be


Input terminal block for remote EPO
commanded by a remote control button

Input terminal block for external manual bypass When there is an external maintenance bypass switch,
switch auxiliary contact for state monitoring

Input terminal block for external battery switch When there is an external battery switch,
auxiliary contact for state monitoring

When battery recharge has to be inhibited


Input terminal block for diesel mode contact
over genset operation
Included

Borri S.p.A. Via 8 Marzo, 2 · 52010 Bibbiena (AR) Italy · Tel. +39 0575 5351 · Fax +39 0575 561811 · [email protected] · www.borri.it