ETA-23 - 0824 - 2023 - Rotho Blaas ALUMEGA Joist Bearing
ETA-23 - 0824 - 2023 - Rotho Blaas ALUMEGA Joist Bearing
I General Part
Technical Assessment Body issuing the ETA and designated according to Article
29 of the Regulation (EU) No 305/2011: ETA-Danmark A/S
3 Performance of the product and references to the methods used for its assessment
Therefore, for timber failure the load duration class and Header – support conditions
the service class are included. The different partial • The header shall be restrained against rotation and
factors M for aluminium or timber, respectively, are be free from wane under the connector.
also correctly considered.
If the header carries joists only on one side the
3.5 Mechanical resistance and stability eccentricity moment from the joists Mec = Rjoist
See annex B for characteristic load-carrying capacities (bheader/2+33 mm) shall be considered for
of the joist bearings. ALUMEGA connectors at the strength verification
of the header.
The characteristic capacities of the joist bearings are Rjoist Reaction force from the joists
determined by calculation assisted by testing as bheader Width of header
described in the EAD 130186-00-0603 clause 2.2.1.
They should be used for designs in accordance with • For a header with joists from both sides but with
Eurocode 5 or a similar national Timber Code. different reaction forces a similar consideration
applies.
The design models allow the use of fasteners described
in the table on page 12 in Annex A: Wood to wood connections
• Self-tapping screws in accordance with ETA- • Joist bearings are fastened to wood-based headers
11/0030 by bolts or screws and to wood-based joists by
• Bolts or dowels in accordance with EN 14592 dowels or screws.
• Metal anchors in accordance with an ETA
• There shall be bolts or screws and dowels in all
holes (full fastener pattern) or in a part of the holes
In the formulas in Annex B the capacities for screws
(partial fastener pattern).
calculated from the formulas of Eurocode 5 are used
assuming a thick steel plate when calculating the lateral
fastener load-carrying-capacity.
Page 6 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Thomas Bruun
Managing Director, ETA-Danmark
Page 8 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Annex A
Product details and definitions
ALUMEGA connector HV
Face mount hanger with flanges with pre-punched holes. 8.0 mm and 9.0 mm thick aluminium alloy EN AW
6082 T6 according to EN 573-3:2009.
The ALUMEGA HV are also supplied in lengths of any multiple of 60 mm, with a minimum length of 240 mm.
For the load-carrying capacity of an ALUMEGA with intermediate size, refer to the next smaller tabulated size.
Page 9 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
ALUMEGA connector HP
Face mount hanger with flanges with pre-punched holes. 8.0 mm and 9.0 mm thick aluminium alloy EN AW
6082 T6 according to EN 573-3:2009.
The ALUMEGA HP are also supplied in lengths of any multiple of 60 mm, with a minimum length of 240 mm.
For the load-carrying capacity of an ALUMEGA with intermediate size, refer to the next smaller tabulated size.
Page 10 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
ALUMEGA connector JV
Face mount hanger with flanges with pre-punched holes. 8.0 mm and 6.0 mm thick aluminium alloy EN AW
6082 T6 according to EN 573-3:2009.
The ALUMEGA JV are also supplied in lengths of any multiple of 60 mm, with a minimum length of 240 mm.
For the load-carrying capacity of an ALUMEGA with intermediate size, refer to the next smaller tabulated size.
The M12 threaded holes may be enlarged to 13 mm diameter to enable the use of smooth shank bolts.
Page 11 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
ALUMEGA connector JS
Face mount hanger with flanges with pre-punched holes. 8.0 mm and 6.0 mm thick aluminium alloy EN AW
6082 T6 according to EN 573-3:2009.
The ALUMEGA JS are also supplied in lengths of any multiple of 60 mm, with a minimum length of 240 mm.
For the load-carrying capacity of an ALUMEGA with intermediate size, refer to the next smaller tabulated size.
The M12 threaded holes may be enlarged to 13 mm diameter to enable the use of smooth shank bolts.
Page 12 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Annex B
Characteristic values of load-carrying-capacities and stiffness
Header/column aluminium T-sections are HV or HP and joist connectors are JV or JS. HP is used with HBSP
screws according to ETA-11/0030, bolts, or metal anchors. HV and JV are used with countersunk washers and
inclined VGS screws according to ETA-11/0030 as fasteners and JS is used with bolts, STA, or SBD dowels
according to EN 14592.
Possible combinations are HP+JV, HP+JS, HV+JV, and HV+JS. Combinations of T-sections and joist connectors
with different depth are also possible. Up to three two-piece ALUMEGA connectors may be arranged side by
side.
The downward and the upward directed forces are assumed to act in the middle of the joist.
Full or partial fastener patterns are foreseen. For header connections with bolts or metal anchors, there must
always be at least bolts or metal anchors in the two upper two holes for loading down or in the two lower holes
for loading up.
For ALUMEGA connectors arranged side-by-side, the load-carrying capacity of the connection is the sum of the
load-carrying capacities of the ALUMEGA connectors.
0,5
F1,HV,Rk = min n 45 4,5 kN k + 0,8 F2,Ed ; F1,alu,Rk ; F90,Rk (B.1)
350
F1,HP,Rk = min 0,78 n 0,9
H Fax,Rk ; 465 H k ; F1,alu,Rk ; F90,Rk for full fastener pattern in N (B.2)
F1,HP,Rk = min n 0,9
H Fax,Rk ; 284 H k ; F1,alu,Rk ; F90,Rk for partial fastener pattern in N (B.3)
0,5
F1,JV,Rk = min n 45 3,5 kN k + 0,8 F2,Ed ; F1,alu,Rk (B.4)
350
F1,JS,Rk = min n J,ef min ( Fv,J,Rk ; Fb,Rk ) ; F1,alu,Rk (B.5)
Where:
n45 Number of inclined screws in the header or column for HV and in the joist for JV
k Characteristic timber density in the header or column for HV and in the joist for JV
F2,Ed Characteristic action of permanent downward force F2. The design value of the permanent action is
determined by multiplying the characteristic value F2,Ed with G,inf.
F1,alu,Rk Characteristic load-carrying capacity of the bolted connection between HV or HP and JV or JS according
to EN 1999-1-1, see Table B.1. F1,alu,Rd = F1,alu,Rk / M2
F90,Rk Characteristic load-carrying capacity according to EN 1995-1-1, 8.1.4. F90,Rd = kmod F90,Rk / M
nH Number of fasteners in the 13 mm holes of the header or column for HP
Fax,Rk Characteristic withdrawal capacity of an axially loaded header or column fastener in the 13 mm holes for
HP according to EN 1995-1-1 and ETA-11/0030, Fax,Rd = kmod Fax,Rk / M
Hk ALUMEGA connector depth in mm, Hd = Hk / M2
Page 14 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Table B.1: Rotho Blaas ALUMEGA connectors: Load-carrying capacity F1,alu,Rk, F2,alu,Rk, F3,alu,Rk and F45,alu,Rk
F1,alu,Rk [kN] F2,alu,Rk [kN] F3,alu,Rk [kN] F45,alu,Rk [kN]
ALUMEGA
Total Per bolt Total Per bolt Total Per bolt Total
840 434 33,4 679 48,5 630 48,5 118
780 401 33,4 630 48,5 581 48,4 110
720 367 33,4 581 48,4 532 48,3 101
660 334 33,4 532 48,3 483 48,3 92,9
600 300 33,4 483 48,3 433 48,2 84,4
540 267 33,4 433 48,2 384 48,0 76,0
480 234 33,4 384 48,0 335 47,9 67,5
420 200 33,4 335 47,9 286 47,7 59,1
360 167 33,4 286 47,7 237 47,4 50,7
300 134 33,4 237 47,4 188 47,0 42,2
240 100 33,4 188 47,0 139 46,3 33,8
Loading down:
1
F2,HP,Rk = min ; F2,alu,Rk for headers (B.7)
2 2
1 1
+
n H Fv,H,Rk k H,2 Fax,H,Rk
1
F2,HP,Rk = min ; F2,alu,Rk for columns (B.8)
2 2
1 1
+
n H,ef Fv,H,Rk k H,2 Fax,H,Rk
F2,JS,Rk = min n J,ef min ( Fv,J,Rk ; Fb,Rk ) ;F2,alu,Rk (B.10)
Where:
k2 Parameter. k2 = 0,88 for ALUMEGA 240; k2 = 0,8 for all other ALUMEGA sizes
n45 Number of inclined screws in the header or column for HV and in the joist for JV
Fax,,Rk Characteristic withdrawal capacity of an axially loaded VGS screw for HV or JV according to EN 1995-
1-1 and ETA-11/0030, Fax,,Rd = kmod Fax,,Rk / M
ftens,k Characteristic tensile capacity of an axially loaded VGS screw for HV or JV according to ETA-11/0030,
Fax,,Rd = ftens,k / M
F2,alu,Rk Characteristic load-carrying capacity of the bolted connection between HV or HP and JV or JS according
to EN 1999-1-1, see Table B.1. F2,alu,Rd = F2,alu,Rk / M2
Page 15 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
For other patterns α is determined according to the manufacturer's technical documentation dated 02-
09-23.
LALUMEGA Connector length in mm between 240 mm and 840 mm
Fb,Rk Characteristic embedment resistance of the joist plate according to EN 1999-1-1. Fb,Rd = Fb,Rk / M2
For joists consisting of CLT where the aluminium joist plate is arranged parallel to the plane of the CLT
member, the embedment strength for CLT may be assumed as:
32 (1 − 0,015 d) k
1,2
f h,k = in N/mm²
1,1 sin 2 + cos 2 400
Angle between the load direction and the grain direction of the CLT layer in contact with the joist plate
The minimum spacing, end and edge distance requirements for dowels in CLT joists are:
a1 = (3 + 2 cos) d a2 = 3 d
a3,t = 5 d a3,c = 4 d
a4,t = 3 d a4,c = 3 d
Table B.2: ALUMEGA HP connectors: Form factors kH,2 and number of fasteners nH
ALUMEGA JS connectors: number of fasteners nJ and effective number of fasteners nJ,ef
ALUMEGA nH,full kH,2 nH,partial kH,2 ALUMEGA STA or bolt SBD
HP Full pattern Partial pattern JS nJ nJ,ef nJ nJ,ef
840 54 464 28 245 840 14 12,4 54 47,2
780 50 398 26 211 780 13 11,3 50 42,9
720 46 338 24 180 720 12 10,2 46 38,6
660 42 282 22 151 660 11 9,16 42 34,4
600 38 232 20 125 600 10 8,08 38 30,1
540 34 186 18 101 540 9 7,01 34 25,9
480 30 145 16 79,9 480 8 5,95 30 21,7
420 26 110 14 61,2 420 7 4,90 26 17,7
360 22 79,1 12 44,9 360 6 3,89 22 13,8
300 18 53,4 10 31,2 300 5 2,92 18 10,2
240 14 32,8 8 19,9 240 4 2,03 14 6,89
Page 16 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Loading up:
0,5
F3,HV,Rk = min n 45 3,8 kN k ; F3,alu,Rk (B.11)
350
1
F3,HP,Rk = min ; F3,alu,Rk for headers (B.12)
2 2
1 1
+
n H Fv,H,Rk k H,2 Fax,H,Rk
1
F3,HP,Rk = min ; F3,alu,Rk for columns (B.13)
2 2
1 1
+
n H,ef Fv,H,Rk k H,2 Fax,H,Rk
k
0,5
F3,JV,Rk = min n 45 2,1 kN ; F3,alu,Rk (B.14)
350
F3,JS,Rk = min n J,ef min ( Fv,J,Rk ; Fb,Rk ) ; F3,alu,Rk (B.15)
Where:
n45 Number of inclined screws in the header or column for HV and in the joist for JV
k Characteristic timber density in the header or column for HV and in the joist for JV
F3,alu,Rk Characteristic load-carrying capacity of the bolted connection between HV or HP and JV or JS
according to EN 1999-1-1, see Table B.1. F3,alu,Rd = F3,alu,Rk / M2
nH Number of fasteners in the 13 mm holes of the header or column for HP
Fv,H,Rk Characteristic lateral load-carrying capacity of a fastener in single shear in the 13 mm holes in the
header or column for HP according to EN 1995-1-1 and ETA-11/0030 assuming a thick plate, Fv,H,Rd =
kmod Fv,H,Rk / M
kH,2 form factor, see Table B.2
Fax,H,Rk Characteristic load-carrying capacity of an axially loaded header or column fastener in the 13 mm holes
for HP according to EN 1995-1-1 and ETA-11/0030, Fax,H,Rd = kmod Fax,H,Rk / M
nH,ef effective number of laterally loaded fasteners in the 13 mm holes for HP in the column
For full pattern and 10 mm HBSP screws: nH,ef = 2 (0,5 nH,full)0,9
For partial pattern and 10 mm HBSP screws: nH,ef = 2 (0,5 nH,partial)0,95
For partial pattern and 12 mm bolts: nH,ef = 1,58 (0,5 nH,partial)0,9
nJ,ef effective number of laterally loaded bolts or STA or SBD dowels in double shear for JS in the joist, see
Table B.2. Other SBD dowel patterns are determined according to the manufacturer's technical
documentation dated 02-09-23.
Fv,J,Rk Characteristic lateral load-carrying capacity of a dowel with two shear planes in the joist according to
EN 1995-1-1, for loading under an angle between load and grain direction, Fv,J,Rd = kmod Fv,J,Rk / M
Load grain angle for the configurations shown in Annex C pages 21 and 24.
= 25,7 ln(LALUMEGA ) − 110 [] for STA dowels
= 3,6 L0,43
ALUMEGA [] for SBD dowels
Page 17 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
For other patterns α is determined according to the manufacturer's technical documentation dated 02-
09-23.
LALUMEGA Connector length in mm between 240 mm and 840 mm
For joists consisting of CLT where the aluminium joist plate is arranged parallel to the plane of the CLT
member, the embedment strength for CLT may be assumed as:
32 (1 − 0,015 d) k
1,2
f h,k = in N/mm²
1,1 sin 2 + cos 2 400
Angle between the load direction and the grain direction of the CLT layer in contact with the joist plate
The minimum spacing, end and edge distance requirements for dowels in CLT joists are:
a1 = (3 + 2 cos) d a2 = 3 d
a3,t = 5 d a3,c = 4 d
a4,t = 3 d a4,c = 3 d
1
F45,JV,Rk = min ; F45,alu,Rk (B.18)
2 2
1 1
+
n 45 Fv,45,Rk k H,45 Fax,45,Rk
k f h b
F45,JS,Rk = min v v,k ; F45,alu,Rk (B.19)
3
Where:
n45 Number of inclined screws in the header or column for HV and in the joist for JV
Fv,45,Rk Characteristic lateral load-carrying capacity of a VGS screw in single shear according to EN 1995-1-1
assuming a thick plate, Fv,45,Rd = kmod Fv,45,Rk / M
2 4 M y,Rk
Fv,Rk = f h,k d t IL + − t IL
f h,k d
fh,k = 0,082 k d N/mm² for headers
-0,3
Fax,45,Rk Characteristic load-carrying capacity of a VGS screw in load direction F1, Fax,45,Rd = kmod Fax,45,Rk / M
0,5
0,8
Fax,45,Rk = 4,5 kN k + F2,Ed for HV
350 n 45
0,5
0,8
Fax,45,Rk = 3,5 kN k + F2,Ed for JV
350 n 45
F2,Ed Characteristic action of permanent downward force F2. The design value of the permanent action is
determined by multiplying the characteristic value F2,Ed with G,inf.
F45,alu,Rk Characteristic load-carrying capacity of the bolted connection between HV or HP and JV or JS according
to EN 1999-1-1, see Table B.1. F45,alu,Rd = F45,alu,Rk / M2
nH Number of fasteners in the 13 mm holes of the header or column for HP
Fv,H,Rk Characteristic lateral load-carrying capacity of a fastener in single shear in the 13 mm holes in the header
or column for HP according to EN 1995-1-1 and ETA-11/0030 assuming a thick plate, Fv,H,Rd = kmod Fv,H,Rk
/ M
Fax,H,Rk Characteristic withdrawal capacity of an axially loaded header or column fastener in the 13 mm holes for
HP according to EN 1995-1-1 and ETA-11/0030, Fax,H,Rd = kmod Fax,H,Rk / M
kn
k v = min 1;
112
b 0,5 +
b
kn Parameter according to Eurocode 5 equation (6.63)
b Joist width in mm
h Joist depth in mm
fv,k Characteristic joist shear strength [N/mm²] fv,Rd = kmod fv,Rk / M
Table B.3: ALUMEGA connectors: Form factors kH,45 for full and partial pattern
kH,45 full pattern kH,45 partial pattern
ALUMEGA HV JV HP HV JV HP
840 26,3 24,7 49,6 24,4 22,9 29,4
780 24,4 22,9 46,0 22,5 21,2 27,2
720 22,5 21,2 42,3 20,6 19,4 25,1
660 20,6 19,4 38,7 18,8 17,6 23,0
600 18,8 17,6 35,0 16,9 15,9 20,9
540 16,9 15,9 31,3 15,0 14,1 18,8
480 15,0 14,1 27,7 13,1 12,4 16,8
420 13,1 12,4 24,0 11,3 10,6 14,7
360 11,3 10,6 20,4 9,4 8,8 12,6
300 9,4 8,8 16,7 7,5 7,1 10,5
240 7,5 7,1 13,1 5,6 5,3 8,4
Page 19 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
B.2 ALUMEGA HP connectors fastened with bolts or metal anchors in concrete or steel
Where:
nH Number of bolts or metal anchors in the header connection; there must always be at least bolts or metal
anchors in the two upper holes for loading down or in the two lower holes for loading up
Hk ALUMEGA connector depth in mm, Hd = Hk / M2
e Distance between the load F2,Ed and the header surface, e = 33 mm
zmax Distance between the uppermost bolt or metal anchor and the lower end of the joist bearing for loading
DOWN or distance between the lowermost bolt or metal anchor and the upper end of the joist bearing for
loading UP;
Ip,H,ax Polar moment of inertia of the header fasteners where the centre of rotation may be assumed at the lower
or upper end of the ALUMEGA HP;
Fv,H,Rk Characteristic value of the lateral load-carrying-capacity per bolt or metal anchor in the header connection
Fax,H,Rk Characteristic value of the axial load-carrying-capacity per bolt or metal anchor in the header
If F1,Ed or F2,Ed or F3,Ed or F45,Ed act simultaneously, the following interaction equation shall be fulfilled:
2 2 2 2
F1,Ed F2,Ed F3,Ed F45,Ed
+ + + 1,0 (B.23)
F1,Rd F2,Rd F3,Rd F45,Rd
The slip moduli do not consider the initial slip due to oversized connector holes. The slip moduli are given
separately for HV/HP, JV/JS and aluminium connection between HV/HP and JV/JS. The resulting slip modulus is:
1
K ser = (B.24)
1 1 1
+ +
K JV / JS,ser K alu,ser K HV / HP,ser
Page 20 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Annex C
Installation of ALUMEGA connectors
Page 22 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Page 23 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Page 24 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Page 25 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Page 26 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Page 27 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Page 28 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Load direction F2, ALUMEGA HP column, non-pre-drilled holes: a3,c ≥ 7 d a4,c ≥ 3.6 d
For all other minimum spacing and distance requirements see ETA-11/0030.
Page 29 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Load direction F2, ALUMEGA HV column, non-pre-drilled holes: a1,CG ≥ 8.4 d a2,CG ≥ 4 d
Load direction F2, ALUMEGA HV header, non-pre-drilled holes: a2,CG ≥ 4 d
For all other minimum spacing and distance requirements see ETA-11/0030.
Page 30 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Load direction F2, ALUMEGA JV, non-pre-drilled holes: a1,CG ≥ 6 d a2,CG,J1 ≥ 8.4 d a2,CG,J2 ≥ 4 d
For all other minimum spacing and distance requirements see ETA-11/0030.
All fasteners must be fully embedded in the timber members and the minimum spacing and end or edge distances
of each fastener must be observed
Page 34 of 34 of European Technical Assessment no. ETA-23/0824, issued on 2023-11-21
Partial (top) and full (bottom) fastener pattern for ALUMEGA 840 HP.