System Configuration and Protection Settings

This document contains configuration settings for various protection and control functions of a relay system. It includes settings for overcurrent protection, voltage protection, thermal protection, circuit breaker monitoring and control, and digital and analog input/output mapping.

Uploaded by

dede kancil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views10 pages

System Configuration and Protection Settings

This document contains configuration settings for various protection and control functions of a relay system. It includes settings for overcurrent protection, voltage protection, thermal protection, circuit breaker monitoring and control, and digital and analog input/output mapping.

Uploaded by

dede kancil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
You are on page 1/ 10

[SYSTEM CONFIG]

System Frequency = 50Hz


Setting Dependencies = Enabled
Favourite Meters Timer = 60min
Backlight timer = 5min
Curr Set Display = Primary
E/F Curr Set Display = Primary
Select Grp Mode = Edge triggered
Clock Sync. From BI = Disabled
Disk Activity Symbol = Disabled
Archiver Blocking Time = 0.5min
Unexpected Restart Blocking = Disabled
Unexpected Restart Count = 3
Unexpected Restart Period = 1hrs
Setting Password = 340701675
Control Password = 340701675
Trip Alert = Enabled
General Alarm Alert = Enabled
Relay Identifier = KELOMPOK 1
Circuit Identifier = CIKASO

[CT/VT CONFIG]
Phase Current Input = 5A
Phase CT Ratio Prim = 400
Phase CT Ratio Sec = 5
Earth Current Input = 5A
Earth CT Ratio Prim = 400
Earth CT Ratio Sec = 5
Phase Rotation = A,B,C

[FUNCTION CONFIG]
Gn Phase Overcurrent = Enabled
Gn Cold Load = Disabled
Gn Derived E/F = Disabled
Gn Measured E/F = Enabled
Gn NPS Overcurrent = Disabled
Gn Thermal = Disabled
Gn CB Fail = Disabled
Gn Broken Conductor = Disabled
Gn Trip Cct Supervision = Disabled
Gn Close Cct Supervis'n = Disabled
Gn Inrush Detector = Disabled
Gn THD Supervision = Disabled
Gn CB Counters = Disabled
Gn I^2t CB Wear = Disabled

[CURRENT PROT'N]

[PHASE OVERCURRENT]
Gn 50 Measurement = RMS
Gn 51 Measurement = RMS

[51-1]
Gn 51-1 Element = Enabled
Gn 51-1 Setting = 0.8xIn
Gn 51-1 Char = IEC-NI
Gn 51-1 Time Mult (IEC/ANSI) = 0.075
Gn 51-1 Delay (DTL) = 5s
Gn 51-1 Min Operate Time = 0.05s
Gn 51-1 Follower DTL = 0s
Gn 51-1 Reset = 0s
Gn 51-1 Inrush Action = Off

[51-2]
Gn 51-2 Element = Disabled
Gn 51-2 Setting = 1xIn
Gn 51-2 Char = IEC-NI
Gn 51-2 Time Mult (IEC/ANSI) = 1
Gn 51-2 Delay (DTL) = 5s
Gn 51-2 Min Operate Time = 0s
Gn 51-2 Follower DTL = 0s
Gn 51-2 Reset = 0s
Gn 51-2 Inrush Action = Off

[50-1]
Gn 50-1 Element = Enabled
Gn 50-1 Setting = 3xIn
Gn 50-1 Delay = 0s
Gn 50-1 Inrush Action = Off

[50-2]
Gn 50-2 Element = Disabled
Gn 50-2 Setting = 1xIn
Gn 50-2 Delay = 0s
Gn 50-2 Inrush Action = Off

[COLD LOAD]
Gn 51c-1 Setting = 1xIn
Gn 51c-1 Char = IEC-NI
Gn 51c-1 Time Mult (IEC/ANSI) = 1
Gn 51c-1 Delay (DTL) = 5s
Gn 51c-1 Min Operate Time = 0s
Gn 51c-1 Follower DTL = 0s
Gn 51c-1 Reset = 0s
Gn 51c-2 Setting = 1xIn
Gn 51c-2 Char = IEC-NI
Gn 51c-2 Time Mult (IEC/ANSI) = 1
Gn 51c-2 Delay (DTL) = 5s
Gn 51c-2 Min Operate Time = 0s
Gn 51c-2 Follower DTL = 0s
Gn 51c-2 Reset = 0s
Cold Load = Disabled
Pick-up Time = 600s
Drop-off Time = 600s
Reduced Current = Disabled
Reduced Current Level = 0.25xIn
Reduced Current Time = 600s

[DERIVED E/F]

[51N-1]
Gn 51N-1 Element = Disabled
Gn 51N-1 Setting = 0.5xIn
Gn 51N-1 Char = IEC-NI
Gn 51N-1 Time Mult (IEC/ANSI) = 1
Gn 51N-1 Delay (DTL) = 5s
Gn 51N-1 Min Operate Time = 0s
Gn 51N-1 Follower DTL = 0s
Gn 51N-1 Reset = 0s
Gn 51N-1 Inrush Action = Off

[51N-2]
Gn 51N-2 Element = Disabled
Gn 51N-2 Setting = 0.5xIn
Gn 51N-2 Char = IEC-NI
Gn 51N-2 Time Mult (IEC/ANSI) = 1
Gn 51N-2 Delay (DTL) = 5s
Gn 51N-2 Min Operate Time = 0s
Gn 51N-2 Follower DTL = 0s
Gn 51N-2 Reset = 0s
Gn 51N-2 Inrush Action = Off

[50N-1]
Gn 50N-1 Element = Disabled
Gn 50N-1 Setting = 0.5xIn
Gn 50N-1 Delay = 0s
Gn 50N-1 Inrush Action = Off

[50N-2]
Gn 50N-2 Element = Disabled
Gn 50N-2 Setting = 0.5xIn
Gn 50N-2 Delay = 0s
Gn 50N-2 Inrush Action = Off

[MEASURED E/F]
Gn 50G Measurement = RMS
Gn 51G Measurement = RMS

[51G-1]
Gn 51G-1 Element = Enabled
Gn 51G-1 Setting = 0.15xIn
Gn 51G-1 Char = IEC-NI
Gn 51G-1 Time Mult (IEC/ANSI) = 0.05
Gn 51G-1 Delay (DTL) = 5s
Gn 51G-1 Min Operate Time = 0.05s
Gn 51G-1 Follower DTL = 0s
Gn 51G-1 Reset = 0s
Gn 51G-1 Inrush Action = Off

[51G-2]
Gn 51G-2 Element = Disabled
Gn 51G-2 Setting = 0.5xIn
Gn 51G-2 Char = IEC-NI
Gn 51G-2 Time Mult (IEC/ANSI) = 1
Gn 51G-2 Delay (DTL) = 5s
Gn 51G-2 Min Operate Time = 0s
Gn 51G-2 Follower DTL = 0s
Gn 51G-2 Reset = 0s
Gn 51G-2 Inrush Action = Off

[50G-1]
Gn 50G-1 Element = Enabled
Gn 50G-1 Setting = 0.6xIn
Gn 50G-1 Delay = 0s
Gn 50G-1 Inrush Action = Off

[50G-2]
Gn 50G-2 Element = Disabled
Gn 50G-2 Setting = 0.5xIn
Gn 50G-2 Delay = 0s
Gn 50G-2 Inrush Action = Off

[NPS OVERCURRENT]

[46IT]
Gn 46IT Element = Disabled
Gn 46IT Setting = 0.25xIn
Gn 46IT Char = IEC-NI
Gn 46IT Time Mult (IEC/ANSI) = 1
Gn 46IT Delay (DTL) = 5s
Gn 46IT Reset = 0s

[46DT]
Gn 46DT Element = Disabled
Gn 46DT Setting = 0.1xIn
Gn 46DT Delay = 0.02s

[THERMAL]
Gn 49 Thermal Overload = Enabled
Gn 49 Overload Setting = 1.05xIn
Gn 49 Time Constant = 13m
Gn 49 Capacity Alarm = Disabled
Gn 49 Capacity Alarm Setting = 50%

[SUPERVISION]

[CB FAIL]
Gn 50BF Element = Disabled
Gn 50BF Setting = 0.2xIn
Gn 50BF-I4 Setting = 0.05xIn
Gn 50BF-1 Delay = 60ms
Gn 50BF-2 Delay = 120ms

[BROKEN CONDUCTOR]
Gn 46BC U/C Guard Setting = 0.15xIn
Gn 46BC U/C Guarded = No
Gn 46BC Element = Enabled
Gn 46BC Setting = 20%
Gn 46BC Delay = 20s

[TRIP CCT SUPERVISION]


Gn 74TCS-1 = Disabled
Gn 74TCS-1 Delay = 0.4s
Gn 74TCS-2 = Disabled
Gn 74TCS-2 Delay = 0.4s
Gn 74TCS-3 = Disabled
Gn 74TCS-3 Delay = 0.4s

[CLOSE CCT SUPERVIS'N]


Gn 74CCS-1 = Disabled
Gn 74CCS-1 Delay = 0.4s
Gn 74CCS-2 = Disabled
Gn 74CCS-2 Delay = 0.4s
Gn 74CCS-3 = Disabled
Gn 74CCS-3 Delay = 0.4s
[INRUSH DETECTOR]
Gn 81HBL2 Element = Disabled
Gn 81HBL2 Bias = Cross
Gn 81HBL2 Setting = 0.2xI

[THD SUPERVISION]
Gn 81THD Element = Disabled
Gn 81THD Setting = 10%
Gn 81THD Delay = 0.1s
Gn 81THD Inrush Action = Off

[CONTROL & LOGIC]

[AUTORECLOSE PROT'N]

[AUTORECLOSE CONFIG]

[MANUAL CB CONTROL]
Gn Close CB Delay = 10s
Gn Blocked Close Delay = 5s
Gn Open CB Delay = 2s
Gn CB Controls Latched = Latch

[CIRCUIT BREAKER]
Gn Close CB Pulse = 2s
Gn Reclaim Timer = 2s
Gn CB Control Trip Time = Enabled
Gn Trip Time Alarm = 0.2s
Gn Trip Time Adjust = 0.015s
Gn CB Travel Alarm = 1s
Gn Open CB Pulse = 1s
Gn CB DBI Delay = 0s

[QUICK LOGIC]
Quick Logic = Disabled
E1 Equation = Disabled
E1 =
E1 Pickup Delay = 0s
E1 Dropoff Delay = 0s
E1 Counter Target = 1
E1 Counter Reset Mode = Off
E1 Counter Reset Time = 0s
E2 Equation = Disabled
E2 =
E2 Pickup Delay = 0s
E2 Dropoff Delay = 0s
E2 Counter Target = 1
E2 Counter Reset Mode = Off
E2 Counter Reset Time = 0s
E3 Equation = Disabled
E3 =
E3 Pickup Delay = 0s
E3 Dropoff Delay = 0s
E3 Counter Target = 1
E3 Counter Reset Mode = Off
E3 Counter Reset Time = 0s
E4 Equation = Disabled
E4 =
E4 Pickup Delay = 0s
E4 Dropoff Delay = 0s
E4 Counter Target = 1
E4 Counter Reset Mode = Off
E4 Counter Reset Time = 0s

[INPUT CONFIG]

[INPUT MATRIX]
Inhibit 51-1 = --------------
Inhibit 51-2 = --------------
Inhibit 50-1 = --------------
Inhibit 50-2 = --------------
Inhibit 51N-1 = --------------
Inhibit 51N-2 = --------------
Inhibit 50N-1 = --------------
Inhibit 50N-2 = --------------
Inhibit 51G-1 = --------------
Inhibit 51G-2 = --------------
Inhibit 50G-1 = --------------
Inhibit 50G-2 = --------------
Inhibit Cold Load = --------------
Inhibit 81HBL2 = --------------
Inhibit 81THD = --------------
Inhibit 46IT = --------------
Inhibit 46DT = --------------
Inhibit 46BC = --------------
Inhibit 49 = --------------
Reset 49 = --------------
74TCS-1 = --------------
74TCS-2 = --------------
74TCS-3 = --------------
74CCS-1 = --------------
74CCS-2 = --------------
74CCS-3 = --------------
Trig Trip Contacts = --------------
Inhibit 50BF = --------------
50BF CB Faulty = --------------
50BF Mech Trip = --------------
50BF Ext Trip = --------------
Reset CB Total Trip = --------------
Reset CB Delta Trip = --------------
Reset I^2t CB Wear = --------------
Trigger I^2t CB Wear = --------------
Reset Trip Time = --------------
General Alarm 1 = --------------
General Alarm 2 = --------------
General Alarm 3 = --------------
General Alarm 4 = --------------
General Alarm 5 = --------------
General Alarm 6 = --------------
CB Open = --------------
CB Closed = --------------
Reset Demand = --------------
Reset Start Count = --------------
Close CB = --------------
Block Close CB = --------------
Open CB = --------------
E/F Out = --------------
E/F In = --------------
Trigger Wave Rec = --------------
Trigger Fault Rec = --------------
Select Group 1 = --------------
Select Group 2 = --------------
Out Of Service Mode = --------------
Local Mode = --------------
Remote Mode = --------------
Local Or Remote Mode = --------------
Clock Sync. = --------------
Reset LEDs & O/Ps = --------------

[FUNCTION KEY MATRIX]

[BINARY INPUT CONFIG]


Inverted Inputs = ------
BI 1 Pickup Delay = 0.02s
BI 1 Dropoff Delay = 0s
BI 2 Pickup Delay = 0.02s
BI 2 Dropoff Delay = 0s
BI 3 Pickup Delay = 0.02s
BI 3 Dropoff Delay = 0s
BI 4 Pickup Delay = 0.02s
BI 4 Dropoff Delay = 0s
BI 5 Pickup Delay = 0.02s
BI 5 Dropoff Delay = 0s
BI 6 Pickup Delay = 0.02s
BI 6 Dropoff Delay = 0s
Enabled In Local = 1, 2, 3, 4, 5, 6
Enabled In Remote = 1, 2, 3, 4, 5, 6

[FUNCTION KEY CONFIG]


Enabled In Remote = --

[GENERAL ALARMS]
General Alarm-1 = ALARM 1
General Alarm-2 = ALARM 2
General Alarm-3 = ALARM 3
General Alarm-4 = ALARM 4
General Alarm-5 = ALARM 5
General Alarm-6 = ALARM 6

[OUTPUT CONFIG]

[OUTPUT MATRIX]
Protection Healthy = -----------------------
Active Setting Grp 1 = -----------------------
Active Setting Grp 2 = -----------------------
51-1 = BO3, BO4, BO5, L6
51-2 = -----------------------
50-1 = BO3, BO4, BO5, L7
50-2 = -----------------------
51N-1 = L6
51N-2 = L6
50N-1 = L6
50N-2 = L6
51G-1 = BO3, BO4, BO5, L8
51G-2 = L6
50G-1 = BO3, BO4, BO5, L9
50G-2 = L6
Cold Load Active = -----------------------
81THD = -----------------------
46IT = -----------------------
46DT = -----------------------
46BC = -----------------------
49 Trip = BO3, BO4, L9
49 Alarm = -----------------------
74TCS-1 = -----------------------
74TCS-2 = -----------------------
74TCS-3 = -----------------------
81HBL2 = -----------------------
74CCS-1 = -----------------------
74CCS-2 = -----------------------
74CCS-3 = -----------------------
General Pickup = L1
General Trip = L2
50BF-1 = -----------------------
50BF-2 = -----------------------
50BF PhA = -----------------------
50BF PhB = -----------------------
50BF PhC = -----------------------
50BF EF = -----------------------
CB Total Trip Count = -----------------------
CB Delta Trip Count = -----------------------
I^2t CB Wear = -----------------------
Trip Time Alarm = -----------------------
CB Open = -----------------------
CB Closed = -----------------------
Close CB Blocked = -----------------------
CB Alarm = -----------------------
Open CB = BO3, BO4, BO5
Phase A = L3
Phase B = L4
Phase C = L5
Derived E/F = -----------------------
Measured E/F = -----------------------
Start Count Alarm = -----------------------
User Output 1 = -----------------------
User Output 2 = -----------------------
User Output 3 = -----------------------
User Output 4 = -----------------------
User Output 5 = -----------------------
User Output 6 = -----------------------
User Output 7 = -----------------------
User Output 8 = -----------------------
Manual Close CB = -----------------------
CB Fail To Close = -----------------------
Successful Man Close = -----------------------
E/F Out = -----------------------
New Wave Stored = -----------------------
New Fault Stored = -----------------------
Out Of Service Mode = -----------------------
Local Mode = -----------------------
Remote Mode = -----------------------
BI 1 Operated = -----------------------
BI 2 Operated = -----------------------
BI 3 Operated = -----------------------
BI 4 Operated = -----------------------
BI 5 Operated = -----------------------
BI 6 Operated = -----------------------
E1 = -----------------------
E2 = -----------------------
E3 = -----------------------
E4 = -----------------------

[BINARY OUTPUT CONFIG]


Hand Reset Outputs = ------
Min Operate Time 1 = 0.1s
Min Operate Time 2 = 0.1s
Min Operate Time 3 = 0.1s
Min Operate Time 4 = 0.1s
Min Operate Time 5 = 0.1s
Min Operate Time 6 = 0.1s
Pickup Outputs = ------
Pulsed Outputs = ------

[LED CONFIG]
Self Reset LEDs = 1
PU Self Reset LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9
Green LEDs = 1
Red LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9
PU Green LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9
PU Red LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9

[PICKUP CONFIG]
Gn P/F Pickups = 51-1, 51-2, 50-1, 50-2
Gn E/F Pickups = 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2
Gn Misc Pickups = 46IT, 46DT, 81THD

[TRIP CONFIG]
Trip Contacts = BO3, BO4
Gn P/F Trips = 51-1, 51-2, 50-1, 50-2
Gn E/F Trips = 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2
Gn Misc Trips = 46IT, 46DT, 81THD
Trip Triggered = L2

[MAINTENANCE]

[CB COUNTERS]
Gn CB Total Trip Count = Disabled
Gn CB Total Trip Count Target = 100
Gn CB Total Trip Manual Open = Disabled
Gn CB Delta Trip Count = Disabled
Gn CB Delta Trip Count Target = 100
Gn CB Delta Trip Manual Open = Disabled

[I^2T CB WEAR]
Gn I^2t Counter = Disabled
Gn Alarm Limit = 10MA^2s
Gn Separation Time = 0.02s
Gn Clearance Time = 0.04s

[START COUNT]
Start Type(s) = Power On, Expected, Unexpected
Start Count Target = 100

[OUTPUT MATRIX TEST]


[DATA STORAGE]

[DEMAND/DATA LOG]
Gn Demand Window = 24hrs
Gn Demand Window Type = Fixed

[WAVEFORM STORAGE]
Gn P/F Trig Storage = 51-1, 51-2, 50-1, 50-2
Gn E/F Trig Storage = 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2
Gn Misc Current Storage = -----
Pre-trigger Storage = 50%
Record Duration = 15 Rec x 1 Sec

[FAULT STORAGE]
Gn Max Fault Rec Time = 1000ms

[EVENT STORAGE]

[COMMUNICATIONS]
COM1-RS485 Protocol = IEC60870-5-103
COM1-RS485 Station Address = 0
COM1-RS485 Baud Rate = 19200
COM1-RS485 Parity = EVEN
COM1-RS485 Mode = Remote
DNP3 Unsolicited Events = Disabled
DNP3 Destination Address = 0
DNP3 Application Timeout = 10s