[SYSTEM CONFIG]
System Frequency = 50Hz
Setting Dependencies = Enabled
Favourite Meters Timer = 60min
Backlight timer = 5min
Curr Set Display = Primary
E/F Curr Set Display = Primary
Select Grp Mode = Edge triggered
Clock Sync. From BI = Disabled
Disk Activity Symbol = Disabled
Archiver Blocking Time = 0.5min
Unexpected Restart Blocking = Disabled
Unexpected Restart Count = 3
Unexpected Restart Period = 1hrs
Setting Password = 340701675
Control Password = 340701675
Trip Alert = Enabled
General Alarm Alert = Enabled
Relay Identifier = KELOMPOK 1
Circuit Identifier = CIKASO
[CT/VT CONFIG]
Phase Current Input = 5A
Phase CT Ratio Prim = 400
Phase CT Ratio Sec = 5
Earth Current Input = 5A
Earth CT Ratio Prim = 400
Earth CT Ratio Sec = 5
Phase Rotation = A,B,C
[FUNCTION CONFIG]
Gn Phase Overcurrent = Enabled
Gn Cold Load = Disabled
Gn Derived E/F = Disabled
Gn Measured E/F = Enabled
Gn NPS Overcurrent = Disabled
Gn Thermal = Disabled
Gn CB Fail = Disabled
Gn Broken Conductor = Disabled
Gn Trip Cct Supervision = Disabled
Gn Close Cct Supervis'n = Disabled
Gn Inrush Detector = Disabled
Gn THD Supervision = Disabled
Gn CB Counters = Disabled
Gn I^2t CB Wear = Disabled
[CURRENT PROT'N]
[PHASE OVERCURRENT]
Gn 50 Measurement = RMS
Gn 51 Measurement = RMS
[51-1]
Gn 51-1 Element = Enabled
Gn 51-1 Setting = 0.8xIn
Gn 51-1 Char = IEC-NI
Gn 51-1 Time Mult (IEC/ANSI) = 0.075
Gn 51-1 Delay (DTL) = 5s
Gn 51-1 Min Operate Time = 0.05s
Gn 51-1 Follower DTL = 0s
Gn 51-1 Reset = 0s
Gn 51-1 Inrush Action = Off
[51-2]
Gn 51-2 Element = Disabled
Gn 51-2 Setting = 1xIn
Gn 51-2 Char = IEC-NI
Gn 51-2 Time Mult (IEC/ANSI) = 1
Gn 51-2 Delay (DTL) = 5s
Gn 51-2 Min Operate Time = 0s
Gn 51-2 Follower DTL = 0s
Gn 51-2 Reset = 0s
Gn 51-2 Inrush Action = Off
[50-1]
Gn 50-1 Element = Enabled
Gn 50-1 Setting = 3xIn
Gn 50-1 Delay = 0s
Gn 50-1 Inrush Action = Off
[50-2]
Gn 50-2 Element = Disabled
Gn 50-2 Setting = 1xIn
Gn 50-2 Delay = 0s
Gn 50-2 Inrush Action = Off
[COLD LOAD]
Gn 51c-1 Setting = 1xIn
Gn 51c-1 Char = IEC-NI
Gn 51c-1 Time Mult (IEC/ANSI) = 1
Gn 51c-1 Delay (DTL) = 5s
Gn 51c-1 Min Operate Time = 0s
Gn 51c-1 Follower DTL = 0s
Gn 51c-1 Reset = 0s
Gn 51c-2 Setting = 1xIn
Gn 51c-2 Char = IEC-NI
Gn 51c-2 Time Mult (IEC/ANSI) = 1
Gn 51c-2 Delay (DTL) = 5s
Gn 51c-2 Min Operate Time = 0s
Gn 51c-2 Follower DTL = 0s
Gn 51c-2 Reset = 0s
Cold Load = Disabled
Pick-up Time = 600s
Drop-off Time = 600s
Reduced Current = Disabled
Reduced Current Level = 0.25xIn
Reduced Current Time = 600s
[DERIVED E/F]
[51N-1]
Gn 51N-1 Element = Disabled
Gn 51N-1 Setting = 0.5xIn
Gn 51N-1 Char = IEC-NI
Gn 51N-1 Time Mult (IEC/ANSI) = 1
Gn 51N-1 Delay (DTL) = 5s
Gn 51N-1 Min Operate Time = 0s
Gn 51N-1 Follower DTL = 0s
Gn 51N-1 Reset = 0s
Gn 51N-1 Inrush Action = Off
[51N-2]
Gn 51N-2 Element = Disabled
Gn 51N-2 Setting = 0.5xIn
Gn 51N-2 Char = IEC-NI
Gn 51N-2 Time Mult (IEC/ANSI) = 1
Gn 51N-2 Delay (DTL) = 5s
Gn 51N-2 Min Operate Time = 0s
Gn 51N-2 Follower DTL = 0s
Gn 51N-2 Reset = 0s
Gn 51N-2 Inrush Action = Off
[50N-1]
Gn 50N-1 Element = Disabled
Gn 50N-1 Setting = 0.5xIn
Gn 50N-1 Delay = 0s
Gn 50N-1 Inrush Action = Off
[50N-2]
Gn 50N-2 Element = Disabled
Gn 50N-2 Setting = 0.5xIn
Gn 50N-2 Delay = 0s
Gn 50N-2 Inrush Action = Off
[MEASURED E/F]
Gn 50G Measurement = RMS
Gn 51G Measurement = RMS
[51G-1]
Gn 51G-1 Element = Enabled
Gn 51G-1 Setting = 0.15xIn
Gn 51G-1 Char = IEC-NI
Gn 51G-1 Time Mult (IEC/ANSI) = 0.05
Gn 51G-1 Delay (DTL) = 5s
Gn 51G-1 Min Operate Time = 0.05s
Gn 51G-1 Follower DTL = 0s
Gn 51G-1 Reset = 0s
Gn 51G-1 Inrush Action = Off
[51G-2]
Gn 51G-2 Element = Disabled
Gn 51G-2 Setting = 0.5xIn
Gn 51G-2 Char = IEC-NI
Gn 51G-2 Time Mult (IEC/ANSI) = 1
Gn 51G-2 Delay (DTL) = 5s
Gn 51G-2 Min Operate Time = 0s
Gn 51G-2 Follower DTL = 0s
Gn 51G-2 Reset = 0s
Gn 51G-2 Inrush Action = Off
[50G-1]
Gn 50G-1 Element = Enabled
Gn 50G-1 Setting = 0.6xIn
Gn 50G-1 Delay = 0s
Gn 50G-1 Inrush Action = Off
[50G-2]
Gn 50G-2 Element = Disabled
Gn 50G-2 Setting = 0.5xIn
Gn 50G-2 Delay = 0s
Gn 50G-2 Inrush Action = Off
[NPS OVERCURRENT]
[46IT]
Gn 46IT Element = Disabled
Gn 46IT Setting = 0.25xIn
Gn 46IT Char = IEC-NI
Gn 46IT Time Mult (IEC/ANSI) = 1
Gn 46IT Delay (DTL) = 5s
Gn 46IT Reset = 0s
[46DT]
Gn 46DT Element = Disabled
Gn 46DT Setting = 0.1xIn
Gn 46DT Delay = 0.02s
[THERMAL]
Gn 49 Thermal Overload = Enabled
Gn 49 Overload Setting = 1.05xIn
Gn 49 Time Constant = 13m
Gn 49 Capacity Alarm = Disabled
Gn 49 Capacity Alarm Setting = 50%
[SUPERVISION]
[CB FAIL]
Gn 50BF Element = Disabled
Gn 50BF Setting = 0.2xIn
Gn 50BF-I4 Setting = 0.05xIn
Gn 50BF-1 Delay = 60ms
Gn 50BF-2 Delay = 120ms
[BROKEN CONDUCTOR]
Gn 46BC U/C Guard Setting = 0.15xIn
Gn 46BC U/C Guarded = No
Gn 46BC Element = Enabled
Gn 46BC Setting = 20%
Gn 46BC Delay = 20s
[TRIP CCT SUPERVISION]
Gn 74TCS-1 = Disabled
Gn 74TCS-1 Delay = 0.4s
Gn 74TCS-2 = Disabled
Gn 74TCS-2 Delay = 0.4s
Gn 74TCS-3 = Disabled
Gn 74TCS-3 Delay = 0.4s
[CLOSE CCT SUPERVIS'N]
Gn 74CCS-1 = Disabled
Gn 74CCS-1 Delay = 0.4s
Gn 74CCS-2 = Disabled
Gn 74CCS-2 Delay = 0.4s
Gn 74CCS-3 = Disabled
Gn 74CCS-3 Delay = 0.4s
[INRUSH DETECTOR]
Gn 81HBL2 Element = Disabled
Gn 81HBL2 Bias = Cross
Gn 81HBL2 Setting = 0.2xI
[THD SUPERVISION]
Gn 81THD Element = Disabled
Gn 81THD Setting = 10%
Gn 81THD Delay = 0.1s
Gn 81THD Inrush Action = Off
[CONTROL & LOGIC]
[AUTORECLOSE PROT'N]
[AUTORECLOSE CONFIG]
[MANUAL CB CONTROL]
Gn Close CB Delay = 10s
Gn Blocked Close Delay = 5s
Gn Open CB Delay = 2s
Gn CB Controls Latched = Latch
[CIRCUIT BREAKER]
Gn Close CB Pulse = 2s
Gn Reclaim Timer = 2s
Gn CB Control Trip Time = Enabled
Gn Trip Time Alarm = 0.2s
Gn Trip Time Adjust = 0.015s
Gn CB Travel Alarm = 1s
Gn Open CB Pulse = 1s
Gn CB DBI Delay = 0s
[QUICK LOGIC]
Quick Logic = Disabled
E1 Equation = Disabled
E1 =
E1 Pickup Delay = 0s
E1 Dropoff Delay = 0s
E1 Counter Target = 1
E1 Counter Reset Mode = Off
E1 Counter Reset Time = 0s
E2 Equation = Disabled
E2 =
E2 Pickup Delay = 0s
E2 Dropoff Delay = 0s
E2 Counter Target = 1
E2 Counter Reset Mode = Off
E2 Counter Reset Time = 0s
E3 Equation = Disabled
E3 =
E3 Pickup Delay = 0s
E3 Dropoff Delay = 0s
E3 Counter Target = 1
E3 Counter Reset Mode = Off
E3 Counter Reset Time = 0s
E4 Equation = Disabled
E4 =
E4 Pickup Delay = 0s
E4 Dropoff Delay = 0s
E4 Counter Target = 1
E4 Counter Reset Mode = Off
E4 Counter Reset Time = 0s
[INPUT CONFIG]
[INPUT MATRIX]
Inhibit 51-1 = --------------
Inhibit 51-2 = --------------
Inhibit 50-1 = --------------
Inhibit 50-2 = --------------
Inhibit 51N-1 = --------------
Inhibit 51N-2 = --------------
Inhibit 50N-1 = --------------
Inhibit 50N-2 = --------------
Inhibit 51G-1 = --------------
Inhibit 51G-2 = --------------
Inhibit 50G-1 = --------------
Inhibit 50G-2 = --------------
Inhibit Cold Load = --------------
Inhibit 81HBL2 = --------------
Inhibit 81THD = --------------
Inhibit 46IT = --------------
Inhibit 46DT = --------------
Inhibit 46BC = --------------
Inhibit 49 = --------------
Reset 49 = --------------
74TCS-1 = --------------
74TCS-2 = --------------
74TCS-3 = --------------
74CCS-1 = --------------
74CCS-2 = --------------
74CCS-3 = --------------
Trig Trip Contacts = --------------
Inhibit 50BF = --------------
50BF CB Faulty = --------------
50BF Mech Trip = --------------
50BF Ext Trip = --------------
Reset CB Total Trip = --------------
Reset CB Delta Trip = --------------
Reset I^2t CB Wear = --------------
Trigger I^2t CB Wear = --------------
Reset Trip Time = --------------
General Alarm 1 = --------------
General Alarm 2 = --------------
General Alarm 3 = --------------
General Alarm 4 = --------------
General Alarm 5 = --------------
General Alarm 6 = --------------
CB Open = --------------
CB Closed = --------------
Reset Demand = --------------
Reset Start Count = --------------
Close CB = --------------
Block Close CB = --------------
Open CB = --------------
E/F Out = --------------
E/F In = --------------
Trigger Wave Rec = --------------
Trigger Fault Rec = --------------
Select Group 1 = --------------
Select Group 2 = --------------
Out Of Service Mode = --------------
Local Mode = --------------
Remote Mode = --------------
Local Or Remote Mode = --------------
Clock Sync. = --------------
Reset LEDs & O/Ps = --------------
[FUNCTION KEY MATRIX]
[BINARY INPUT CONFIG]
Inverted Inputs = ------
BI 1 Pickup Delay = 0.02s
BI 1 Dropoff Delay = 0s
BI 2 Pickup Delay = 0.02s
BI 2 Dropoff Delay = 0s
BI 3 Pickup Delay = 0.02s
BI 3 Dropoff Delay = 0s
BI 4 Pickup Delay = 0.02s
BI 4 Dropoff Delay = 0s
BI 5 Pickup Delay = 0.02s
BI 5 Dropoff Delay = 0s
BI 6 Pickup Delay = 0.02s
BI 6 Dropoff Delay = 0s
Enabled In Local = 1, 2, 3, 4, 5, 6
Enabled In Remote = 1, 2, 3, 4, 5, 6
[FUNCTION KEY CONFIG]
Enabled In Remote = --
[GENERAL ALARMS]
General Alarm-1 = ALARM 1
General Alarm-2 = ALARM 2
General Alarm-3 = ALARM 3
General Alarm-4 = ALARM 4
General Alarm-5 = ALARM 5
General Alarm-6 = ALARM 6
[OUTPUT CONFIG]
[OUTPUT MATRIX]
Protection Healthy = -----------------------
Active Setting Grp 1 = -----------------------
Active Setting Grp 2 = -----------------------
51-1 = BO3, BO4, BO5, L6
51-2 = -----------------------
50-1 = BO3, BO4, BO5, L7
50-2 = -----------------------
51N-1 = L6
51N-2 = L6
50N-1 = L6
50N-2 = L6
51G-1 = BO3, BO4, BO5, L8
51G-2 = L6
50G-1 = BO3, BO4, BO5, L9
50G-2 = L6
Cold Load Active = -----------------------
81THD = -----------------------
46IT = -----------------------
46DT = -----------------------
46BC = -----------------------
49 Trip = BO3, BO4, L9
49 Alarm = -----------------------
74TCS-1 = -----------------------
74TCS-2 = -----------------------
74TCS-3 = -----------------------
81HBL2 = -----------------------
74CCS-1 = -----------------------
74CCS-2 = -----------------------
74CCS-3 = -----------------------
General Pickup = L1
General Trip = L2
50BF-1 = -----------------------
50BF-2 = -----------------------
50BF PhA = -----------------------
50BF PhB = -----------------------
50BF PhC = -----------------------
50BF EF = -----------------------
CB Total Trip Count = -----------------------
CB Delta Trip Count = -----------------------
I^2t CB Wear = -----------------------
Trip Time Alarm = -----------------------
CB Open = -----------------------
CB Closed = -----------------------
Close CB Blocked = -----------------------
CB Alarm = -----------------------
Open CB = BO3, BO4, BO5
Phase A = L3
Phase B = L4
Phase C = L5
Derived E/F = -----------------------
Measured E/F = -----------------------
Start Count Alarm = -----------------------
User Output 1 = -----------------------
User Output 2 = -----------------------
User Output 3 = -----------------------
User Output 4 = -----------------------
User Output 5 = -----------------------
User Output 6 = -----------------------
User Output 7 = -----------------------
User Output 8 = -----------------------
Manual Close CB = -----------------------
CB Fail To Close = -----------------------
Successful Man Close = -----------------------
E/F Out = -----------------------
New Wave Stored = -----------------------
New Fault Stored = -----------------------
Out Of Service Mode = -----------------------
Local Mode = -----------------------
Remote Mode = -----------------------
BI 1 Operated = -----------------------
BI 2 Operated = -----------------------
BI 3 Operated = -----------------------
BI 4 Operated = -----------------------
BI 5 Operated = -----------------------
BI 6 Operated = -----------------------
E1 = -----------------------
E2 = -----------------------
E3 = -----------------------
E4 = -----------------------
[BINARY OUTPUT CONFIG]
Hand Reset Outputs = ------
Min Operate Time 1 = 0.1s
Min Operate Time 2 = 0.1s
Min Operate Time 3 = 0.1s
Min Operate Time 4 = 0.1s
Min Operate Time 5 = 0.1s
Min Operate Time 6 = 0.1s
Pickup Outputs = ------
Pulsed Outputs = ------
[LED CONFIG]
Self Reset LEDs = 1
PU Self Reset LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9
Green LEDs = 1
Red LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9
PU Green LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9
PU Red LEDs = 1, 2, 3, 4, 5, 6, 7, 8, 9
[PICKUP CONFIG]
Gn P/F Pickups = 51-1, 51-2, 50-1, 50-2
Gn E/F Pickups = 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2
Gn Misc Pickups = 46IT, 46DT, 81THD
[TRIP CONFIG]
Trip Contacts = BO3, BO4
Gn P/F Trips = 51-1, 51-2, 50-1, 50-2
Gn E/F Trips = 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2
Gn Misc Trips = 46IT, 46DT, 81THD
Trip Triggered = L2
[MAINTENANCE]
[CB COUNTERS]
Gn CB Total Trip Count = Disabled
Gn CB Total Trip Count Target = 100
Gn CB Total Trip Manual Open = Disabled
Gn CB Delta Trip Count = Disabled
Gn CB Delta Trip Count Target = 100
Gn CB Delta Trip Manual Open = Disabled
[I^2T CB WEAR]
Gn I^2t Counter = Disabled
Gn Alarm Limit = 10MA^2s
Gn Separation Time = 0.02s
Gn Clearance Time = 0.04s
[START COUNT]
Start Type(s) = Power On, Expected, Unexpected
Start Count Target = 100
[OUTPUT MATRIX TEST]
[DATA STORAGE]
[DEMAND/DATA LOG]
Gn Demand Window = 24hrs
Gn Demand Window Type = Fixed
[WAVEFORM STORAGE]
Gn P/F Trig Storage = 51-1, 51-2, 50-1, 50-2
Gn E/F Trig Storage = 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2
Gn Misc Current Storage = -----
Pre-trigger Storage = 50%
Record Duration = 15 Rec x 1 Sec
[FAULT STORAGE]
Gn Max Fault Rec Time = 1000ms
[EVENT STORAGE]
[COMMUNICATIONS]
COM1-RS485 Protocol = IEC60870-5-103
COM1-RS485 Station Address = 0
COM1-RS485 Baud Rate = 19200
COM1-RS485 Parity = EVEN
COM1-RS485 Mode = Remote
DNP3 Unsolicited Events = Disabled
DNP3 Destination Address = 0
DNP3 Application Timeout = 10s