Adwea Standard S Cps Scms (Rev.0 2006)
Adwea Standard S Cps Scms (Rev.0 2006)
CONTROL-PROTECTION-SUPERVISION
( SPECIFICATION )
CONTENTS
1 GENERAL ....................................................................................................................... 3
1.1 Drawings ........................................................................................................................... 4
1.2 Equipment Identification and Color Codes ....................................................................... 4
2 TECHNICAL DESCRIPTION ...................................................................................... 4
2.1 SCMS System Requirements ............................................................................................ 4
2.1.1 Basic Design Requirements............................................................................................... 4
2.1.2 Requirements on Manufacturer's Experience and Local Support ..................................... 5
2.1.3 Control System Architecture ............................................................................................. 6
2.1.4 Control Points.................................................................................................................... 7
2.1.5 Tele-control Communication Interface ............................................................................. 7
2.1.6 Functional Requirements................................................................................................... 8
2.1.7 Functional Description .................................................................................................... 11
2.1.8 System Performance and Redundancy Requirements ..................................................... 14
2.1.9 Software Requirements ................................................................................................... 18
2.1.10 LAN Communication Requirements............................................................................... 19
2.1.11 Maintenance Requirements ............................................................................................. 20
2.2 SCMS Equipment & Services ......................................................................................... 20
2.2.1 Bay Control Units (BCUs) .............................................................................................. 20
2.2.2 Bay-Station Level Communication ................................................................................. 22
2.2.3 Database Computers (Front-End Computers) ................................................................. 22
2.2.4 Supervision and Self-diagnostics .................................................................................... 23
2.2.5 Operator Workstation ...................................................................................................... 24
2.2.6 Engineering Workstation................................................................................................. 25
2.2.7 Printer and Logger........................................................................................................... 25
2.2.8 Digital and Analogue Annunciators ................................................................................ 25
2.2.9 Global Positioning System (GPS) Receiver .................................................................... 25
2.2.10 UPS.................................................................................................................................. 26
2.2.11 Fault Analysis Interface................................................................................................... 26
2.2.12 Trouble Shooting, Maintenance and Programming Tools............................................... 26
3 TESTING AND INSPECTION.................................................................................... 29
3.1 Functional Tests .............................................................................................................. 29
3.2 Documentation ................................................................................................................ 29
3.3 SCADA System Data List (Tables)................................................................................. 30
1 GENERAL
This specification covers the design, manufacture, factory testing, marking, packing, shipping,
transportation to site, installation, configuration, on-site testing and commissioning of Substation
Control & Monitoring System (SCMS). The specification describes the requirements for SCMS
on ADWEA’s substations, and shall be individually applicable to 400, 220, 132, 33, 22 and 11
kV substations or any combinations of them. In case of substations designed with both EHV/HV
and MV power systems, separate SCMS systems shall be provided for independent monitoring
and control of the respective substation plant items owned and shared by the Transmission and
Distribution Companies. Both systems, however, shall be capable of exchanging information
with a firewall protection through an appropriate technique (switches, bridges, or routers) which
shall be decided during the design and engineering phase of the contract.
It should be noted that the intent of this specification is to provide for work herein described to
be fully complete in every detail for providing SCMS control in the respective substations.
Bidder/Contractor, in accepting the contract, shall furnish all apparatus, appliances, material
software and labour necessary to complete the job. This shall include all items that are not
specifically mentioned or included in the specification, but needed to complete the work, without
extra cost to ADWEA.
For SCMS requirements, the specification contains descriptions and definitions of the
functionality, performance, architecture and documentation for the system. Technical data sheets,
architecture drawings, and other documents also form part of the specifications.
The SCMS shall conform in all respects to high standards of engineering design and
workmanship, and should be capable of performing continuous commercial operation within the
parameters guaranteed by the Bidder/Contractor in a manner acceptable to ADWEA.
Bidder/Contractor should be aware that ADWEA will reject the whole SCMS supply during the
design and engineering phase of the project, if the performance of the similar system was not
satisfactory from the previous installations and, if the control scheme offered is not in
accordance with the technical specifications and the guaranteed parameters.
The SCMS offered shall be complete in all respects necessary for their effective and trouble free
operation with full coordination and integration of substation control and protection.
For applicable technical standards, tests, reference shall be made to:
¾ S-CONT-GEN - General Requirements
(Applicable Technical Standards, Tests, etc.)
For Substation Control & Monitoring System Cubicle requirements, reference shall be made to
Standard Technical Specification, Part:
¾ S-CUB - Cubicles and Enclosures
1.1 Drawings
Typical Drawings for the Substation Control & Monitoring System provided in the Drawings
Section are as follows:
Drawing No. Title
ADWEA CPS 01 01 SCMS System Block Diagram of a 132kV, 220 kV or 400 kV
Substation (Typical Only)
ADWEA CPS 01 02 SCMS System Block Diagram of a 400/220 kV Gridstation (Typical
Only)
ADWEA CPS 01 03 SCMS System Block Diagram of a 33kV and/or 11 kV Substation
(Typical Only)
ADWEA CPS 01 04 SCMS System Block Diagram of a HV/MV Substation (Typical
Only)
2 TECHNICAL DESCRIPTION
enquiry document. The system offered shall provide reliable, safe and efficient operation of the
substation plant items at all times with an availability figure of 99.98 percent.
All control system equipment and control points shall be powered by a secure means of supply
derived from the substation 110 V batteries. AC driven components such as system/database and
printer servers, workstation computers, monitors, printers and other peripheral devices shall
remain operational in the event of AC supply failure, drawing auxiliary power from an UPS
connected to a dual input supply from both the 110 V station batteries and an incoming AC
supply.
Data acquisition modules, digital and analogue, in both decentralized units (eg. BCU or BCPU)
and common units shall be provided with 25% spare capacity after meeting the scope of Work in
accordance with the specification. However, for main computers (Database Computers), the
equipment shall be supplied with adequate memory for the required task with 25 percent spare
capacity for future use. The hard disc capacity should be adequate to satisfy the requirements of
the operating system, support and diagnostic, and application software with 40 percent spare
capacity.
The SCMS components and equipment shall be completely assembled and tested only at the
original manufacturer's workshop, e.g. wiring of boards, desks, etc., including installations of
internals, test of equipment, including combinations, i.e. systems of control, supervision and
protection equipment. All equipment shall be subjected to the full type and routine tests at the
workshop (manufacturer’s test field/laboratory) prior to shipment to site.
All instrumentation and control equipment shall be capable of continuous satisfactory operation
within the specified accuracy during a change of the supply voltage within the limits specified.
The Bidder/Contractor/Manufacturer shall also assure all software and hardware components of
SCMS have been proof tested and no replacement would be required during lifetime of
equipment. Where replacement of components required due to faulty operation and software
problems, the manufacturer shall provide a detail technical report evidencing the cause of failure
and remedies proposed. A guarantee shall be provided in particular for all software processes for
a period of 5 years from the date of commissioning of new/replaced SCMS components.
In addition to the above, the Bidder/Contractor shall provide a list of spares predicted as being
required during the first 5 years of operation, and additionally over the design lifetime of the
SCMS. The Bidder/Contractor shall quote only with a fixed price escalation formula for these
spares.
Also, the Bidder/Contractor shall offer contract agreement to build-up support organization to
tackle and trouble-shoot all kinds of technical problems relating to SCMS system, which shall
cover but not be limited to maintenance, up-gradation and expansion of the presently offered
system.
automatically or manually once the failure has been corrected. The IEC-101 shall perform a half-
duplex operation as a polling protocol on 4 a wire modem circuit.
The interoperability task of IEC 101 protocol must be split into defining and drafting different
parts of the data communication process, such as transmission formats, control procedures,
performance and so on. The interface platform (hardware and firmware) shall not be restricted to
running a single subset of IEC 101 protocol. The NCC/DMS should scan periodically for
information on status change, alarms, events, metering values, tap-position indications, control
commands, parameter loading, integrated totals, file transfer, and station initialisation.
Changeover of the signalling line between the SCMS and the NCC/DMS shall not result in loss
or duplication of data (generally the NCC/DMS signals to the SCMS on one line, whilst the
SCMS signals to the NCC/DMS on both lines). The physical interface shall be designed suitably
to perform on an unbalanced mode as per V.24/V.28 ITU-T recommendations, as well as on a
balanced mode as per X.24/X.27 recommendations. For the balanced mode, the interface should
support a transfer speed of up to 64 kbps.
2. Pperiodical measurement of analogue values and display of process values on the screen
displays such as three-phase volts (phase to phase, phase to neutral), three-phase and
neutral amps (average and maximum demand), frequency, power factor (values followed
only by lead, UPF or lag qualification.), active and reactive power, transformer winding /
oil temperature with graphical representation / trend curves and energy calculation in every
half-hour in tabular form. High/Low limit excursions of measurands shall be alarmed and
programmable. The ratios chosen in case of multitap CTs for measurement should match
with those selected for protection functions to facilitate analysis of faults and
abnormalities.
3. Power cable sealing ends (insulation liquid level) monitoring through dedicated transducer
inputs.
4. Fire Fighting system monitoring through dedicated transducer inputs.
5. Airconditioning system monitoring through dedicated transducer inputs.
6. GIS on-line SF6-gas monitoring through dedicated transducer inputs.
7. Acquisition, printout and display of substation name (on top of alarm page), substation
events, individual feeder and substation equipment alarms with date and time stamp.
Event/alarm time resolution shall be one milli-second or better.
8. Acquisition of status with plausibility checks, of the circuit breakers, isolators and earthing
switches, status of truck positions for CBs and VTs.
9. Performance of automatic sequential control functions, such as taking any feeder in/out of
service, bus transfer, transformer loading, transformer paralleling and auto-changeover
schemes as required for ensuring security of supply.
10. Statistical metering and analogue trend reporting highlighting abnormalities.
11. Performance of supervised operations (Close/Open) on the feeder circuit breakers, bus bar
and line isolators, bus bar and line earthing switches, capacitor bank contactors etc.
12. Data processing, command handling, cyclic and limit violation update of measured values,
and bay interlocking are some of the standard functions to be performed by the bay units
before forwarding information with time tagging to the substation information level.
Accuracy of measured values when connected to metering transformer cores shall be 1
(one) percent.
13. System functioning shall not require multiple alarm acknowledgement or manual entries
(at different workstation) for the same alarm event.
14. Multiple windows facility with size selectable.
15. Alarm annunciation and management. Classification of alarms with major, minor and low
priority levels (1-3). Alarms shall provide audible and visual indications. Alarms should be
displayed on different colours for the various levels. They should also be printed on a
logger, and be displayed at workstations.
16. Scheduled logging facility for providing the paper log record with a chronological list of
events.
17. Record of number of operations of plant and various plant devices (breakers, tap changers
etc.).
18. Operator manual entry facility (e.g. tags or flags etc designed to meet the company's safety
requirements).
19. Transfer of control between SCMS and SCADA (NCC/ /DMS).
20. Station-wide switchgear and bay interlocking and transformer parallel operation logic.
21. Communication between the different levels of the control system architecture via the
optical fibre communication sub system.
22. Performance of check-synchronising function (including over-riding feature) as part of
BCU. Check-synchronising function to check synchronising condition across the breaker
before closing at all control points (Local Control Point, Substation Level Control Point,
and Remote Level Control at NCC/ /DMS). A bypass facility shall be provided.
23. Auto-reclosing activation /blocking of OHL feeders.
24. Switching on/off protection and load shedding functions
25. In-built security by password accesses. Four programmable (by System Manager)
authorisation levels including monitoring (view), control, engineering and system manager
levels with respective multiple password organisation for access control.
26. Reporting of acquired data in user defined formats (intuitive numerical and graphical
presentation).
27. Setting and parameter downloading to relays, and uploading and evaluation of stored
internal data without interrupting the real-time on-line field communications through a
reliable informative interface.
28. Automatic upload, storage and archiving of disturbance recorder files, without interruption
of the real time data communications through a reliable informative interface.
29. Storage and archiving of process data.
30. Resetting of electrical trip lockout relays.
31. Periodic recording of station outdoor/indoor (GIS, SCMS, relay, battery, LVAC/DC
system rooms) ambient temperatures with alarms for abnormalities.
32. Simultaneous communication on the two channels (i.e. parallel transmission) or on any one
channel (selection controlled at NCC/ /DMS).
33. Self-supervision with display of system alarms and hardware status, including
communication links.
34. Time synchronisation through GPS receiver.
35. Under-frequency load shedding (through a separate set of U/F relays) and load curtailment.
36. Real-time reporting of fault locating functions of distance relays into SCMS database.
37. Voltage regulation function (the voltage regulation relay shall be a stand-alone device and
not an integral part of the station level software application) for the following purposes:
− To provide automatic and manual control over the transformer on-load tap changer
(OLTC)
− To maintain transformer secondary voltage within preset limits. The AVC relay shall
support two voltage levels of dead-band to ensure that the post tapping voltage of the
busbar is sufficiently close to the selected target voltage. Dead-band 1 is used to
initiate tapping and dead-band 2 used to end tapping
− To compensate line voltage drop due to load current
− To control energised but unloaded transformers (homing)
− To facilitate safe parallel operation of transformers
− To monitor and alarm abnormal voltages and operating conditions (e.g. target voltage
not achievable). Details are to be finalised during the design stage, subject to the
approval of ADWEA.
38. Automatic reactive power switching (Capacitor Bank Control - to be coordinated with tap
change control) and parameter set switching.
39. Reverse blocking function (IEC 61850-5 series) for protection of radial MV feeders.
40. Point-on-wave switching of circuit breakers (IEC 61850-5 series) requiring a time
resolution of 0.1 ms for a precise time tag to allow circuit breaker closure at the zero
crossing of the voltage waveform.
41. Power quality measurement (swells, sags, interruptions, harmonic levels).
42. Plant item information
43. Any other requirements in line with IEC 61850
44. On line Help
OLTC operation from the operator HMI.Further more, an emergency stop command shall
be provided to initiate instant cut off of power supply to the OLTC motor, as well as a
logic to inhibit parallel operation of more than two or three (to be adjusted as parameter)
transformers, if specified. The design shall be inclusive of a generic list of features to
prevent closing of a bus coupler/bus section if transformers are operating on unequal taps,
and indicate and safeguard against OLTC incomplete operation. The scheme shall provide
indication of raise/lower operation in progress, loss of dc control supply, motor overload
trip or loss of motor ac supply, unequal tap position of paralleled transformers, etc. Other
features include a voltmeter function for indication of transformer secondary voltage, a
winding temperature indicator (separately for primary and secondary sides) and a tap
position indicator, etc. The design shall be modular for the possibility of extension of
circuits to accommodate more future transformers. To drive the tap change mechanism, a
raise or lower command pulse of the order of 2 seconds is required. Any command to the
tap change mechanism should be responded with a tap change in progress signal (TCIP).
This signal must be received within 10 seconds of initiation of a tap change control pulse.
If a runaway tap change condition is detected the tap change motor must be tripped off-
line. The tap position indicator shall cater for up to 25 or more depending upon the
requirement. The tap changer operation must be blocked when the measured system
voltage falls below 80 percent of nominal, and transformer load exceeds 125 percent of
nominal. The tap change operation must not drive the system voltage by more than 1.5 kV
per minute. If more than one tap control action is required, then it shall be possible to delay
each subsequent tap by an inter tap delay time. This should be adjustable between 0 to 120
sec in 10 sec increments. For local control, manual tap raise / lower push buttons, tap
position indicator, and voltmeter shall be provided for each transformer on the tap change
cubicle.
• Check Synchronising
The synchronising control shall be presented with a pop-up window identifying the breaker
to be operated. The scheme shall employ an automatic approach whereby a selected
breaker is automatically closed once the synchronising conditions on either side of the
breaker are within limits. At workstations during an operator-initiated synchro-checked
breaker close sequence, the Running, Incoming, and Phase angle volts (RIP) shall be
displayed in a predefined area of the monitor screen. An independent hardwired manual
synchro check facility shall be provided (to facilitate control during emergency operating
conditions) with a common check synchronising relay mounted in the bus coupler/section
local control panel with synchro check / bypass selection switches in the respective feeder
bays. Also, automatic support of dead bus or dead line conditions shall be included.
• Alarm and Event Handling
Alarm conditions reflect an abnormal condition in the substation process, which are to be
reported in alarm lists for acknowledgement and action. Substation alarms are of two
types-digital alarms and limit violation alarms, respectively.
Events are the status changes related to the position of devices/components which are
reported in the Event list.
Event list contains both alarms and events.
Digital alarms are reported for any violation from the normal state. An alarm of this type
remains on the appropriate alarm summary display until the status point returns to its
normal state and the operator has acknowledged the alarm.
Included in limit violation alarms shall be voltage, current (both magnititude and
displacement for V&I), frequency, power factor and power measurements exceeding
limits, temperatures, pressures etc.
In addition to electrical plant, both main and ancillary, alarms, alarms from the control
system itself shall be handled. These alarms shall include UPS and printer failure,
communication failures (substation internal and NCC/ /DMS), hardware and software
failure, watchdog system failure, power supply unit failure, etc.
Alarm handling facility shall include chattering suppression (suppression of an alarm for X
minutes when it occurs Y times in Z seconds), inhibition of alarms during a test sequence,
reannunciation of an alarm if it is left unacknowledged for more than a defined period of
time, the presentation of alarms with the calculation of the time of each alarm as a relative
time from a single time reference, etc.
User log-in and log-out shall be reported as an event. Programmable automatic timed log-
out function shall be provided if the system remain untouched for defined time interval.
• The module failure, communication failure, data flow too high, loss of power, loss of
chronology, printer failure etc.
• The module failure should consist of hardware faults (CPUs, memory, power supply, I/O
board) and software faults (operating system, application software, supervision application
software, self-test software, etc.).
A loss of power may not cause the loss of configuration data. This data shall be stored in
EPROMS, EEPROMS, or RAM with back-up battery having a design life of 10 years or more.
After restoration of power the system shall restart automatically. During start-up all output
contacts shall be reset and blocked until after the completion of the restart with all settings being
set to the default status.
To enhance availability neither fans nor mechanical disk drives or any other constantly moving
mechanical components are acceptable for use in the bay units or the substation database
computers. All central components, such as substation computers, operator HMIs,
communication links to NCC/ /DMS, etc., shall be provided in redundant configuration with
self-monitoring and automatic switchover facilities. See also the respective system block
drawings. An availability of 99.98% shall be obtained and proved by calculation.
The redundancy required shall furthermore be fully extended into design of the communication
interfaces and media. This principle of redundancy should ensure at least the following features:
• Outage of one member of each pair of duplicated components shall not result in any
reduction of functionality
• Outage of one communication link from individual feeder bay or common unit to the
central components shall not affect any other communication link between the central
components and all other feeder or common units.
The above requirements may be obtained by means of:
• Duplicated bus-systems with dual-port technique
• Star configurations
• Ring Topology
• And/or any feasible combination of above.
The Bidder/Contractor shall clearly define how the architecture offered in his Bid meets the
availability/redundancy requirements. Therefore, a system block diagram has to be submitted
with the offer.
The normal activity condition produces a moderate load on the communication system over the
period of one minute defined as result of the following changes:
- 2 status changes
- 7 alarms
- 15 analogue values exceeding the set values
- Alarm Acknowledgement on occurrence
- Display requests every 30 sec.
While processing, encoding and transmitting the above data, when averaged over the one minute
period as mentioned above the CPU loading of the database computer shall not exceed 40%.
High activity condition
The high activity condition produces a high load on the communication system over the period
of one minute defined as result of the following changes:
- 20 status changes
- 70 alarms
- 35 analogue values exceeding the set values
- Alarm Acknowledgement on occurrence
- Display requests every 30 sec.
While processing, encoding and transmitting the above data, when averaged over the one minute
period as mentioned above the CPU loading of the database computer shall not exceed 60%.
Crisis condition
This represents a major network disturbance resulting in a large number of alarms, status
changes and analogue changes at the substation resulting in:
- ≥ 80 % of equipped systems showing alarm/event changes
- ≥ 80 % of equipped systems showing status changes
- 80 % of equipped systems analogue values exceeding set values
- Alarm Acknowledgement on occurrence
- Display requests every 20 sec.
- In crisis condition the above changes occur once per 30 sec for a period of 5 minutes.
Under crisis conditions the system shall perform with no data loss without undue delay in the
processing and display of data and information at the SCP operator interface.
• The latest release of software shall be supplied and tested at FAT. Consideration to
updating the software package shall be given before expiration of warranty.
• A minimum program development shall be required for any special software, which has to
be developed to meet the requirements of this specification. The Bidder/Contractor shall
detail the function(s), which necessitate this work and provide an estimate of the work
involved. Confirmation that the program will be supported for a minimum of 15 years is
also required.
• It shall be the responsibility of the Bidder/Contractor to obtain any licenses required for the
operation of the software.
• The Bidder/Contractor shall indemnify ADWEA against all claims of infringement of any
patent, registered design, copyright, trademark or trade name or other intellectual property
right.
• The GPS time reference shall be extended to the SCMS system, sub-system and other IEDs
using IRIG B or other approved interface.
• The SCMS system, and test and diagnosis instruments using standard serial interface, e.g.
RS 232 or as per manufacturer’s standard.
BCUs shall provide digital inputs for a variety of purposes including local/ remote indications,
alarm annunciation, sequence of events, interlock logic, automatic control sequence, and
transformer tap change control, etc.
Transformer tap position indication shall be processed as either a digital input or an analogue
input.
EPROM capacity, there shall be 40 percent extra spare capacity available as the extension
capacity.
records from protection equipment. The DBCs shall update the real-time system database, and
transmit the required data to its communication processors, which shall pass it on to the network
control centre and/or the HMI(s).
Beside the general tasks mentioned, the substation control unit shall perform enhanced
automation functions which include but not be limited to:
• Station wide automatic control sequences
• Busbar voltage simulation and tap change control
• Logic for paralleling of transformer banks
• Auto changeover logic as required for the Security of Supply
• Station wide interlocking
• Processing of analogue values, e.g. threshold monitoring and alarming
• Command output time monitoring, including the reset of the output contacts after
successful switching.
The system shall provide all usual programmable logical controller (PLC) functions to enable
ADWEA to create own automation functions.
DBCs shall be supplied with a database holding two types of circular buffer memory. The first
memory shall provide a queue for the real time active data to be transferred upstream to NCC/
/DMS and the second shall retain a large archive at station level. This database capability shall
not be less than 50000 binary signals.
• Communication architecture
• Protection relay interface (showing both numerical and non-numerical relays)
• LVAC, UPS & DC system diagram
• Measurement Trends
• Load Shedding
• Load Curtailment
2.2.10 UPS
An Uninterrupted Power Supply (UPS) with a minimum rating of not less than 5 kVA for all AC
powered devices shall be provided, reference shall be made to Standard Technical Specification,
Part:
¾ S-PCS-UPS - Uninterruptible Power Supply
• Long time observation and -archiving (i.e. for later analysis of intermittent faults)
• Plausibility check of user inputs when tele-control messages are edited
• Documentation of test sessions in a data file or on the printer
• Listing and recording with and without filtering function
• Editing of messages and sequences
• Receiving and transmitting of messages
• Transmitting of sequences
• Automatic test sequences
• ON-LINE- and OFF-LINE operation
• Channels with a freely selectable protocol variant
• Filter function with
− Channel overlapping filter
− Channel specific, protocol dependent filter functions i.e. for the station number
− Programmable system reaction
− ON-LINE and OFF-LINE, which allows filtering of archived data.
• Storing of messages sent with time signals, with the interpreting and display of the content
• Detection and interpreting of faults (telegram- and procedure faults)
• Passive check with transmit and receive
• Active test with automatic send mechanism
• Filtering.
The laptop workstation shall be configurable in software by the system manager. As required, it
shall also be configurable to access relay / fault recording function data available at the
engineering workstation. The modem / communication system shall be of the ‘dial up’ type,
suitable for connecting to a public switched telephone network.
Swivel chairs (6numbers) complete with castors shall be supplied to match the desks. Chairs
shall be supplied to give optimum body support and comfort during use. The chairs and their
upholstery shall be of approved design, the construction and finish of which shall be to
ADWEA’s approval.
Event log printers which are not free standing shall be mounted on suitable robust stands, the
design and finish of which shall have to be agreed with ADWEA.
the SCMS shall be tested at the manufacturer’s works (FAT) by simulation thereby proving the
compliance with the specified scope.
The test configuration shall, besides the standard SCMS functions, allow for testing:
• Performance of operation including switching-over of all redundant components
• Sequence of event recording function under normal, high and crisis conditions
• Automatic transformer regulations in both independent and master/follower modes
• Feeder interlocking
• Substation interlocking (reduced testing with all typical feeders only).
The commissioning at the site (SAT) shall also require detailed checks, including end-to-end
checks between SCMS and NCC/ /DMS, to verify the complete installation.
The Bidder/Contractor shall propose FAT and SAT procedures, which shall be subject to
approval by ADWEA.
3.2 Documentation
The documentation shall be provided covering five basic areas such as design, installation,
operating instructions, maintenance instructions, and record and tests. Documentation should
reflect the actual equipment and system as accepted by ADWEA.
In addition to the requirements for documentation stipulated in general for this specification for
the SCMS system the following documentation shall be included in the offer:
• Technical bulletin of each piece of hardware to be used
• Technical bulletin of software to be used
• List of references for SCMS installations using the offered type of equipment and software
• The design intent (Scope of hardware and software supply, and function set-up of the
SCMS covering all central, common and feeder types of SCMS units
• List of applicable quality assurance, environmental and electrical standards
• Typical scheme drawings
• Space requirements for SCMS hardware
• Schedule of proposed Factory and Site Tests (FAT / SAT) including test procedures and
formats
• Time schedule for design, manufacture, testing, installation and commissioning.
SCADA
Description of SCADA Signal Type
Signal
Type
TM Analogue Tele-measurement
Please note that the SCADA tables indicated below are for guidance only and may not
necessarily reflect the configuration and/or the requirements of the Switchgear and/or equipment
as specified under the Scope of Work/Supply.
The SCADA tables for the MV Switchgear and/or equipment shall essentially follow the ones as
provided below.
After award of contract, the Bidder/Contractor shall adopt, amend and complete these tables in
accordance with the actual configuration of the Switchgear and/or equipment to be provided and
these new tables shall be subject to final approval by ADWEA during the design stage.
To add the following in the list:
Protection In/Out
Transformer oil level
GIS cooling system status and failures
Capacitor Bank alarms such as status of stages, isolator/fuse status
LVAC, DC and UPS alarms
Various DC and AC supply failures
Overload trips for feeders
Broken Conductor trip for OHL
Sensitive earth fault trip for OHL
SCADA POWER CIRCUIT TYPES Trans- OHL/ Busbar Bus Tie/ Common
Signal former Cable Coupler (Station)
Feeder
Type SCADA Signal Name SCADA SIGNALS
TELE-MEASUREMENT
TM Voltage X x
TM Active Power X x
TM Reactive Power X x
TM Current (3 Phase) X x x
TM Transformer Tap Position X
TM Frequency BB – 1A x
TM Frequency BB – 1B x
TM Frequency BB – 2A x
TM Frequency BB – 2B x
TM Voltage BB – 1A x
TM Voltage BB – 1B x
TM Voltage BB – 2A x
TM Voltage BB – 2B x
TM Bus to Bus Phase Shift Angle x
TM Ambient Temperature inside (SCMS and x
GIS and various Rooms as specified)
TM Ambient Temperature Outside x
TM Transformer/Reactor Winding and Oil X
Temperature
SCADA POWER CIRCUIT TYPES Trans- OHL/ Busbar Bus Tie/ Common
Signal former Cable Coupler (Station)
Feeder
Type SCADA Signal Name SCADA SIGNALS
SCADA POWER CIRCUIT TYPES Trans- OHL/ Busbar Bus Tie/ Common
Signal former Cable Coupler (Station)
Feeder
Type SCADA Signal Name SCADA SIGNALS
SCADA POWER CIRCUIT TYPES Trans- OHL/ Busbar Bus Tie/ Common
Signal former Cable Coupler (Station)
Feeder
Type SCADA Signal Name SCADA SIGNALS
ALARM INPUT
SS Main 1 Protection Trip x x
SS Main 2 Protect. Trip x
SS Backup Protection Trip x
SS Auto Reclose Operated x
SS Main 1 Carrier Receive/Send x
SS Main 2 Carrier Receive/Send x
nd
SS Main-2 Protection Trip (2 Zone etc.)
SS Main 1 Protection Faulty Alarm x x
SS Main 2 Protection Faulty Alarm x
SS Back up Protection Faulty Alarm x
SS Trip Circuit 1 and 2 Faulty Alarm x x x
SS Protection DC Supply 1 Trip x x x
SS Protection DC Supply 2 Trip x x x
SS VT Fail Alarm x x
SS Transformer Buchholz Trip x
SS Transformer Buchholz Alarm x
SS Transformer Differential Trip x
SS Transformer Differential Relay Faulty x
SS Transformer SBEF Relay Trip x
SS Transformer REF Relay Faulty x
SS Transformer Overcurrent - Pry Trip x
SS Transformer Overcurrent – Sec Trip x
SS Transformer Overcurrent Relay (Py/Sy) x
Faulty
SS Transformer Pressure Relief Trip x
SS Transformer Pressure Relief Alarm x
SCADA POWER CIRCUIT TYPES Trans- OHL/ Busbar Bus Tie/ Common
Signal former Cable Coupler (Station)
Feeder
Type SCADA Signal Name SCADA SIGNALS
SCADA POWER CIRCUIT TYPES Trans- OHL/ Busbar Bus Tie/ Common
Signal former Cable Coupler (Station)
Feeder
Type SCADA Signal Name SCADA SIGNALS
SCADA POWER CIRCUIT TYPES Trans- OHL/ Busbar Bus Tie/ Common
Signal former Cable Coupler (Station)
Feeder
Type SCADA Signal Name SCADA SIGNALS
COMMAND OUTPUT
DC Busbar 1 Isolator (OPEN / CLOSE) x x x
DC Busbar 2 Isolator (OPEN / CLOSE) x x x
DC Circuit Breaker (OPEN / CLOSE) x x x
DC Feeder Isolator (OPEN / CLOSE) x x x
DC Feeder Earth Switch (OPEN / CLOSE) x x
DC Tap Changer control (Raise / Lower) x
DC Tap Changer control (Auto / Manual) x
DC Dummy Circuit Breaker (OPEN/CLOSE) x
DC Synchro Override Function (ON / OFF) x x
DC Auto Reclose (ON/OFF) x
SC Trip / Lock out relay “ Reset” x x x