8032

Paddle-wheel flow transmitter/


threshold detector

• Indication, monitoring, transmitting and On/Off


control in one device
• Selectable outputs (transistor or relay)
• Automatic calibration: Teach-In
• Process value output: 4... 20 mA
Type 8032 can be combined with...

Type 8802-YG-I Type 8792 Type 8644-P AirLINE Type 8041 Type 8030
(2300 + 8692) Positioner Valve island with Flow sensor (only with Flow sensor (only with
ELEMENT Control valve SideControl electronic I/O SE32 remote) SE32 remote)

This intelligent transmitter/threshold detector General data


with display is designed for use in clear, neutral
Compatibility With fittings S030 (see corresponding data sheet)
or aggressive liquids and specially to switch a
Materials
valve and to establish a monitoring system or
Housing, cover PC, glass fibre reinforced
an On/Off control loop.
Front panel folio / Screws Polyester / Stainless steel
The switching points can be configured with Cable plug / connector M12 PA / PA or CuZn, nickel-plated
the 3 keys below the display. Wetted parts materials:
Fitting, sensor armature / Seal Brass, stainless steel, PVC, PP or PVDF / FKM (EPDM option)
The compact 8032 is available with On/Off Paddle-wheel / Axis, bearings PVDF / Ceramics
output or with process value output. Wall-mounted holder PVC
The remote 8032 has a transistor output. Display 8-digit LCD with backlighting
Electrical connections Cable plug acc. to EN 175301-803, free positionable male
The connection to the process in the piping is M12 connector, 5 pins or male M12 connector, 8 pins
done with standard INLINE fittings. Panel-mounted version Terminal strips
Voltage supply cable 0.5 mm2 max. cross section; max. 100 m length, shielded
Remote sensor connection 0.5 mm2 max. cross section; max. 50 m length, shielded

Complete device data (fitting S030 + electronic module SE32)


Pipe diameter DN06 to DN65
Measuring range 0.3 to 10 m/s
Medium temperature 0 to 50°C (32 to 122°F) (with PVC fitting) / 0 to 80°C (32 to
/ -15 to 100°C (5 to 212°F) (with stainless
176°F) (with PP fitting)
steel, brass or PVDF fitting)
Fluid pressure max. PN10 (145.1 PSI) (with plastic fitting) -
PN16 (232.16 PSI) (with metal fitting)
Viscosity / Pollution 300 cSt. max. / 1% max. (particle size 0.5 mm max.)
Measurement error
Teach-In ±1% of Reading1) (at the teach flow rate value)
Standard K-factor ±3% of Reading1)
Operating mode Threshold: window or hysteresis
Linearity1) ±0.5% of F.S.*
Repeatability1) ±0.4% of Reading
* F.S. = Full scale (10 m/s)
1)
Under reference conditions i.e. measuring fluid = water, ambient and water temperature = 20°C (68°F), applying the minimum inlet and
outlet pipe straights, matched inside pipe dimensions.
www.burkert.com p. 1/8
8032

Electrical data
Opertating voltage Filtered and regulated
Compact version 12-36 V DC ±10%
Remote version Depends on the sensor:
8041: 18-30 V DC
8020, 8030: 12-30 V DC
other: min. 12 V DC, max. 30 V DC
Reversed polarity of DC Protected
Current consumption
Compact version  90 mA (without load)
Remote version  50 mA (without load) + consumption of the sensor
Input
Frequency (remote version) Pulse signal: 2 to 400 Hz
input impedance: 10 k
Outputs
Transistor NPN and/or PNP (selectable), open collector, max.
700 mA, 500 mA max. per transistor if both transistor
outputs are wired, 0 to 300 Hz
NPN-output: 0.2 - 36 V DC
PNP-output: Power supply
protected against short circuit.
Relay (compact version) 3 A/250 V AC or 3 A/30 V DC;
[3 A/48 V AC or 3 A/30 V DC]2.
Process value (compact version) 4 ... 20 mA, galvanic insulation
Loop resistance: 1300  at 36 V DC, 1000  at 30 V DC,
700  at 24 V DC, 450  at 18 V DC, 200  at 12 V DC
4... 20 mA measurement error ±1%

Environment
Ambient temperature -10 to +60°C (14 to 140°F) (operating and storage)
Relative humidity 80%, without condensation

Standards, directives and approvals


Protection class IP65 with connector plugged-in and tightened correctly
Standard, directives
EMC EN 610006-2, 610006-3
Security EN 61010-1
Pressure (Fitting S030, DN06 to DN65,
in PVC, PP, PVDF, stainless steel or brass) Complying with article 3 of Chap. 3 from 97/23/CE directive.* * For the 97/23/CE pressure directive, the device can
Vibration / Shock EN 60068-2-6 / EN 60068-2-27 only be used under following conditions (depend on max.
pressure, pipe diameter and fluid).
Approvals
UL-Recognized for Type of fluid Conditions
US and Canada UL61010-1 + CAN/CSA-C22 No.61010-1 Fluid group 1,
chap. 1.3.a DN 25 only
Specific technical data of UL-recognized products for US and Canada Fluid group 2, DN 32 or
Ambient temperature 0 to +40°C (32 to 104°F) chap. 1.3.a DN > 32 and PN*DN 1000
Fluid group 1,
Height above sea level max. 2000 m
chap. 1.3.b PN*DN 2000
Intended for an inner pollution Grade of pollution 2 Fluid group 2,
Installation category Category I chap. 1.3.b DN 200
2)
if 4... 20 mA and relay

p. 2/8
8032

Operation and display


The device can be calibrated by means of the K-factor, or via the Teach-In function.
User adjustments, such as engineering units, output, filter, bargraph are carried out on site.

Indication in operating mode/Display


- measured flow
- high threshold value
- low threshold value 2-line large digital display
with 4 characters each
Parameter definition (4 digital characters and
- engineering units (International measuring units) 4 alphanumeric characters)
- K-factor/Teach-In function
- selection of switching mode (window, hysteresis)
(see main features)
Bargraph
- selection of threshold value (see main features)
- delay To scroll-up the menu or
- filter increase a value Validation key
- 10-segment bargraph (select min. and max. value)
(value or menu)
- Password protects the access to the menu
To scroll-down the menu Status of the switching output
Test or select a digit to be (red LED)

- switching threshold test with flow simulation modified


- Calibration of the 4... 20 mA current output

Main features

8032 with standard On/Off output


- 2 switching modes for the output, either hysteresis or window, inverted or not
Hysteresis mode Window mode

#ONTACT #ONTACT #ONTACT #ONTACT


(YSTERESIS ÖINVERTED (YSTERESIS ÖNOTÖINVERTED 7INDOW ÖINVERTED 7INDOW ÖNOTÖINVERTED

/,/ /() /,/ /() /,/ /()


/,/ /()

- Configurable delay before switching


- Possible outputs depending on the version: relay, transistor NPN, transistor PNP

8032 with current output for the measurement value


- 4... 20 mA output
- 4... 20 mA output + relay output

p. 3/8
8032

Design and principle of operation

The compact 8032 is built up with an The wall-mounted variant is built up


electronic module SE32 associated to with an electronic module SE32 as-
%LECTRONICÖ a fitting S030 with integrated meas- %LECTRONICÖ sociated to a wall-mounted holder. The
3% urement paddle-wheel. The electrical 3% electrical connection is provided via
connection is provided via cable plug 7ALL MOUNTED two M12 multipin connector.
&ITTING according to EN 175301-803 and/or a HOLDER
3 M12 multipin connector.

The panel-mounted variant is made up of an electronic module SE32


and a protection plate. The electrical connection is provided via a termi-
nal strip located on the protection plate.

When liquid flows through the pipe, the 4 magnets, inserted in the paddle-wheel set in rotation, produce a frequency signal in the transducer. The fre-
quency is proportional to the flow velocity of the fluid. A conversion coefficient (K factor, available in the instruction manual of the fitting S030), specific to each pipe
(size and material) enables the conversion of this frequency into a flow rate.

Installation

The SE32 electronics can easily be installed into any Bürkert INLINE fitting system Type S030 by means of a Quar-
ter-Turn. Minimum straight upstream and downstream distances must be observed. According to the pipe’s design,
necessary distances can be bigger or use a flow conditioner to obtain the best accuracy. For more information, please
refer to EN ISO 5167-1.

EN ISO 5167-1 specifies the straight inlet and outlet distances that must be complied with when installing fittings
in pipelines in order to achieve calm flow conditions. The most important layouts that could lead to turbulence in the
flow are shown below, together with the associated minimum inlet and outlet distances. These ensure calm, problem-
free measurement conditions at the measurement point.

DN = pipe diameter Fluid direction -->

Pipe diameter
Control valve 2 x 90° elbow joint
extension
ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$.

2 x 90° elbow joint 90° elbow joint Pipe diameter


3 dimensional or T-piece reduction
ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$.

The device can be installed into either horizontal or vertical pipes.

Correct Incorrect
Incorrect

Incorrect Correct
Correct Correct Incorrect

Pressure and temperature ratings must be respected according to the selected fitting material. The suitable pipe size is selected using the diagram
Flow/Velocity/DN.
The device is not designed for gas flow measurement.

p. 4/8
8032

Pressure/temperature chart

0ÖBAR !
 A: Application range for a complete device
 -ETAL
(fitting + electronics)





 06$&

06#Ö Ö00 06$&Ö0.



 06#Ö0.


 00Ö0.
 4ÖÊ#
       

Diagram Flow/Velocity/DN

Example:

• Specification of nominal flow: 10 m3/h


• Ideal flow velocity: 2... 3 m/s

For these specifications, the diagram indicates a pipe size of DN40 [or Flow rate
Not recommended
DN50 for (*) mentioned fittings] gpm m3/h
1000 l/min
3000 200
500 2000 DN 65
100
DN 50 (DN65)*
1000
200 50
DN 40 (DN50)*
500
100 DN 32 (DN40)*
20 DN 25 (DN32)*
50 200 DN 20 (DN25)*
10

100 DN 15 (DN15
20 5 or 20)*
50
10
2 DN 08
5 20
1 DN 06
10
2 0.5

5
1
0.2

0.5 2
0.1

1
0.2 0.05

0.5
0.1
0.02

0.05 0.2
0.01
0.1 0.3 0.5 1 3 5 10 m/s
0.3 0.5 1 3 5 10 30 fps
Flow velocity

* for following fitings with:


• external threads acc. to SMS 1145
• weld ends acc. to SMS 3008, BS 4825 / ASME BPE or DIN 11850 Series 2
• Clamp acc. to SMS 3017/ ISO 2852, BS 4825 / ASME BPE or DIN 32676

p. 5/8
8032

Dimensions

8032 compact
  




 

37
&,/7Ö37)4#(

&,/7Ö37)4#(



- Ö - Ö
%.Ö    PIN  PIN


DN H
[mm] [mm]
06 79.5
08 79.5
15 84.5
20 82.0
25 82.2
32 85.8
H

40 89.6
50 95.7
65 95.7

8032 wall-mounted 8032 panel-mounted


56

55





37
max. 3
min. 1

26,5


10

18

- Ö
 PIN

p. 6/8
8032

Ordering chart for transmitter/threshold detector Type 8032


A compact Type 8032 consists of:
- an electronic module SE32
- an INLINE fitting S030 (DN06 - DN65) (Refer to corresponding data sheet - has to be ordered separately)

Agreements

connection
Operating

Electrical

Item no.
Outputs
voltage

12-36 V DC NPN - Cable plug EN 175301-803* 436 474


PNP Cable plug EN 175301-803* 434 871
NPN and PNP - Free positionable male M12 connector, 5 pins 436 473
UL-Recognized for US and Canada Free positionable male M12 connector, 5 pins 553 431
Relay - Free positionable male M12 connector, 5 pins 436 475
and cable plug EN 175301-803*
4... 20 mA + - Male M12 connector, 8 pins 560 547
relay and cable plug EN 175301-803*
4... 20 mA + - Free positionable male M12 connector, 5 pins 560 402
relay and cable plug EN 175301-803
4... 20 mA - Free positionable male M12 connector, 5 pins 560 403
* Europe/Asia (G/Rc): M16 x 1.5 mm cable plug
USA/CDN (NPT): NPT1/2 cable plug

A wall- or panel- mounted Type 8032 consists of:


- a wall- or a panel- mounted electronic module SE32
- a flow sensor Type 8020, 8030, 8030-HT, 8041 or 8070 - frequency output with pulse signal
(Refer to corresponding data sheet - has to be ordered separately)
Description

connection
Electrical

Item no.
Outputs
Voltage
supply

Input

Wall-mounted 12-30 V DC Frequency NPN and PNP Free positionable male M12 connector, 5 pins and 448 861
female M12 connector, 4 pins
Panel-mounted 12-30 V DC Frequency NPN and PNP Terminal strips 558 181

Ordering chart for accessories (to be ordered separately)


Description

Item no.

Male M12 connector, 4 pins, with plastic threaded locking ring, for remote version 448 856
Male M12 connector, 4 pins, moulded on cable (2 m, shielded), for remote version 448 857
Female M12 connector, 5 pins, with plastic threaded locking ring 917 116
Female M12 connector, 5 pins, moulded on cable (2 m, shielded) 438 680
Female M12 connector, 8 pins, with plastic threaded locking ring 444 799
Female M12 connector, 8 pins,moulded on cable (2 m, shielded) 444 800
Cable plug EN 175301-803 with cable gland (Type 2508) 438 811
Cable plug EN 175301-803 with NPT1/2“ reduction without cable gland (Type 2509) 162 673

p. 7/8
8032

Interconnection possibilities with other Bürkert products

Compact version

Type 8802-GD-J -
(2301 + 8693) Type 5281 -
ELEMENT Control valve Solenoid valve
Type 6212 -
Solenoid valve

4... 20 mA output Transistor output Relay output

Type 8032 -
Compact device

Wall-or panel- mounted version

Type 8070 - Type 8041 -


For pipes DN06 to DN400

Type 8020 -
For pipes DN 06 to 400
Type 8030 -
For pipes DN06 to DN65

Frequency
input

Type 8032 - Type 8032 -


Panel-mounted Wall-mounted Type 6212 -
Solenoid valve

Transistor
output