Q4160

FIRE RATING CERTIFICATIONS

• BS 5867 Type B & C


• BS EN 13773
• IMO 7
• M1
• B1
• UNI 9177
This document is the translation of the French
certificate n° 20-01517 L on August 31rst 2020,
delivered by IFTH.

MATERIAL REACTION TO FIRE CLASSIFICATION


REPORT PREPARED IN COMPLIANCE WITH AMENDED 5 OF THE FRENCH HOME OFFICE
REGULATION DATED NOVEMBER 21ST, 2002 (OFFICIAL GAZETTE DATED DECEMBER 31, 2002)
Valid five years from issue date

CERTIFICATE N° 20-01517 L
And appendices of 6 pages
MATERIAL presented by: SMD CONTRACT LTD
Pittman Way,Fulwood, Preston
PR2 9ZD LANCASHIRE
ENGLAND
TRADE NAME: Q4160 Printed 100 % Polyester

BRIEF DESCRIPTION: Fabric 100% inherent fire resistant polyester.


Measured surface weight: about 280 g/m²
Measured thickness: about 0,50 mm
Colours: stripes printed (green-grey-pink)
TEST REPORT: N° 20-01517 E1-V1 on August 31rst 2020
TESTS: Electrical burner test
Flame persistence test
Dripping test.

CLASSIFICATION:
M1
CLASSIFICATION DURATION (article 5 of appendix 2) : unlimited unless otherwise specified
given the criteria resulting from the tests described in the enclosed test report.
The classification indicated does not mean that materials marketed comply with the test samples and must not be considered as a qualification certificate as defined by French
law dated March 14, 2016.

N.B.: Only integral copies of this document may be made by photocopying the classification report and/or the classification report and
enclosed test report.
Issued in Lyon, France, on August 31rst 2020

Lucile Multari Léa Monin


Engineer Tests and Trials Engineer Tests and Trials

Siège Social : 14 rue des reculettes – 75013 PARIS  Tél : +33 (0)1 44 08 19 00  Fax :+33 (0)1 44 08 19 39  www.ifth.org
SIRET 433 430 832 00108 – NAF 729Z – TVA : FR 39 433430832 – CENTRE TECHNIQUE INDUSTRIEL (LOI DU 22 JUILLET 1948 – ARRETE DU 14 AVRIL 2000)
ENRQ_11 v1 01/19
FLAMMABILITY TEST CERTIFICATE - 77427
COMPANY DETAILS: SMD TEXTILES LTD,
UNIT F2, PITTMAN WAY, FULWOOD, PRESTON PR2 9ZD

CONTACT NAME(S): EMMA LOCKWOOD


TEL: 01772 665263
EMAIL: [email protected]

DATE RECEIVED: 12/09/2019


DATE TESTED: 18/09/2019
DATE ISSUED: 19/09/2019
PO NUMBER: NOT STATED

SAMPLE DESCRIPTION: Q4160 HAVEN AUTUMN


COLOUR: Q4130/HAVENAUT
COMPOSITION: INHERENTLY FLAME RETARDANT 100% POLYESTER
QUALITY/ BATCH REF: P114395
SAMPLE END USE: CURTAINING
MANUFACTURER: O.G
SUPPLIER/BUYER: SMD

SPECIFICATION/REQUIRMENT:
IMO FTP Part 7: 2010 – Test for vertically supported textiles and films.

PRE-TREATMENT:
No wetting procedure had been carried out. The results obtained in this report relate only to the tested specimens as
received.

CONDITIONING:
The specimens had been conditioned for at least 24 hrs in a specified atmosphere at 20 ± 50C and 65 ± 5% r h.

Authorised By:

Zeb Alam Mark Jones Karen Brooks


Operations Director Quality Manager Managing Director

Please note: this test results issued on this certificate refer only to the item tested and therefore doesn’t relate to the lot or
batch of the product / sample. This test certificate shall not be duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park,
Manchester, M17 1RN. T: 0161 50 50 650 E: [email protected]

Page 1 of 2
FLAMMABILITY TEST CERTIFICATE - 77427
TEST RESULTS BEFORE WASH FACE FABRIC:
Test Results (Warp) 1 2 3 4 5
Application Time (as determined by pre-testing): 15s (EDGE) 15s (EDGE) 15s (EDGE) 15s (EDGE) 15s (EDGE)
After Flame time: 0.0 0.0 0.0 0.0 0.0
Flame reached an edge: NO NO NO NO NO
Charred Length: (mm) 91 79 104 77 58
Ignition of Cotton Wool (Y/N) NO NO NO NO NO
Occurrence of surface flash (Y/N) NO NO NO NO NO
Specimen Result: PASS PASS PASS PASS PASS

Test Results (Weft) 1 2 3 4 5


Application Time (as determined by pre-testing): 15s (EDGE) 15s (EDGE) 15s (EDGE) 15s (EDGE) 15s (EDGE)
After Flame time: 0.0 0.0 0.0 0.0 0.0
Flame reached an edge: NO NO NO NO NO
Charred Length: (mm) 66 50 64 74 61
Ignition of Cotton Wool (Y/N) NO NO NO NO NO
Occurrence of surface flash (Y/N) NO NO NO NO NO
Specimen Result: PASS PASS PASS PASS PASS

*after flame time ≤5s for any specimen.


*no flame propagation to the edges for any specimen.
*no ignition of the cotton wool for any specimen.
*average char length ≤ 150mm.
*no occurrence of surface flash more than 100mm from the point of ignition

CONCLUSION:
The sample supplied meets the performance criteria as stated in paragraph 3 of IMO FTP Part 7: 2010.

END OF REPORT

Please note: the test results issued on this certificate refer only to the item tested and therefore doesn’t relate to the lot or
batch of the product / sample. This test certificate shall not be duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park,
Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]

Page 2 of 2
Our Ref: SW/PN/RM 13 September 2017

Report 304189 Page 1 of 4

SMD Contracts Limited


Unit F2 Pittman Way
Fulwood
Preston
PR2 9ZD Contact: Katie Hamblett

DATE RECEIVED : 13 SEPTEMBER 2017


REPUTED FIBRE CONTENT : NOT GIVEN
FABRIC DESCRIPTION : WOVEN
COLOUR/DESIGN : Q4160
END USE : CURTAINING
ORDER NUMBER : CONTRACTS 14

REQUEST: FIRE TESTS ACCORDING TO BS 5867 - 2:2008


Fabrics for curtains, drapes and window blinds – Part 2: Flammability requirements –
specification. Type C Performance.

COMMENTS: The sample submitted complies with the flammability requirements of BS5867-
2:2008 for Type C performance.

S. WISEMAN P. NEESAM
LABORATORY DIRECTOR HEAD OF FLAMMABILITY

This report shall not be reproduced except in full without the written approval of HSTTS. In all circumstances, results of tests are implied as
referring only to the sample supplied and should not be construed or interpreted on any other basis. The comments given in the report are for
guidance only and are not part of the results. Opinions and interpretations expressed herein are outside the scope of UKAS accreditation

118 Lupton Avenue Leeds LS9 6ED England


Tel: 0044 (0)113 248 8830 Fax: 0044 (0)113 248 0239 Email: [email protected]
Registered no. 2899980 VAT No. 613 4310 86
Our Ref: SW/PN/RM 13 September 2017

Report 304189 Page 2 of 4

FIRE TESTS ACCORDING TO BS 5867 - 2:2008


Fabrics for curtains, drapes and window blinds – Part 2: Flammability requirements –
specification. Type C Performance.

Procedure

Specimens of fabric, Q4160 were subjected to the test methods described in BS EN ISO 15025:2002,
procedure ‘A’, in the as received condition and after 50 Wash cycles according to BS EN ISO 6330,
Program 2A.

Flame application times of 5,15,20,30 sec were used.

BS 5867 states that: -

Type C Performance Requirements

No part of any hole nor any part of the lowest boundary of any flame shall reach the top edge or either
vertical edge of the sample specimen and there shall be no separation of any flaming debris from any
specimen, or if the mean afterflame or afterglow times exceed 2.5 s, the fabric shall be deemed not to
comply with the requirements for type “C” of this British Standard

Results

The following test results relate only to the ignitability of the combination of materials under the
particular conditions of test; they are not intended as a means of assessing the full potential fire hazard of
the materials in use.
They also only relate to the materials tested. They do not guarantee to represent the performance of
production materials.

Original condition Warp/Length Weft/Width


5 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

118 Lupton Avenue Leeds LS9 6ED England


Tel: 0044 (0)113 248 8830 Fax: 0044 (0)113 248 0239 Email: [email protected]
Registered no. 2899980 VAT No. 613 4310 86
Our Ref: SW/PN/RM 13 September 2017

Report 304189 Page 3 of 4

Original condition Warp/Length Weft/Width


15 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

Original condition Warp/Length Weft/Width


20 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

Original condition Warp/Length Weft/Width


30 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

After Cleansing Warp/Length Weft/Width


5 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

118 Lupton Avenue Leeds LS9 6ED England


Tel: 0044 (0)113 248 8830 Fax: 0044 (0)113 248 0239 Email: [email protected]
Registered no. 2899980 VAT No. 613 4310 86
Our Ref: SW/PN/RM 13 September 2017

Report 304189 Page 4 of 4

After Cleansing Warp/Length Weft/Width


15 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

After Cleansing Warp/Length Weft/Width


20 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

After Cleansing Warp/Length Weft/Width


30 seconds 1↑ 2↓ 3← 4→
Afterflame 0.0 0.0 0.0 0.0
Afterglow 0.0 0.0 0.0 0.0
Flame to Edge? No No No No
Hole to Edge? No No No No
Flaming Debris? No No No No
Mean Afterflame 0.0
Mean Afterglow 0.0

Comments

The sample submitted complies with the flammability requirements of BS5867-2:2008 for Type C
performance.

118 Lupton Avenue Leeds LS9 6ED England


Tel: 0044 (0)113 248 8830 Fax: 0044 (0)113 248 0239 Email: [email protected]
Registered no. 2899980 VAT No. 613 4310 86
PROCES-VERBAL DE CLASSEMENT DE REACTION AU FEU
D’UN MATERIAU PREVU A L’ARTICLE 5
DE L’ARRÊTE DU 21 NOVEMBRE 2002
Valable 5 ans à partir de la date de délivrance

PROCES-VERBAL N° 20-01516 L
et 1 annexe de 6 pages
MATERIAU présenté par : SMD CONTRACT LTD
Pittman Way,Fulwood, Preston
PR2 9ZD LANCASHIRE
ROYAUME-UNI

MARQUE COMMERCIALE : SOUL Q4160 Plain Dye 100 % Polyester

DESCRIPTION SOMMAIRE : Tissu 100% polyester FR ignifugé dans la masse


Masse surfacique mesurée : environ 280 g/m²
Epaisseur mesurée : environ 0,5 mm
Coloris : Rouge
RAPPORT D’ESSAI : N° 20-01516 E1-V1 du 31 août 2020
NATURE DES ESSAIS : Brûleur électrique
Propagation de flamme
Essai pour matériaux fusibles

CLASSEMENT :
M1
DURABILITE du classement (Article 5 de l’annexe 2) : non limitée a priori.

Compte tenu des critères résultant des essais décrits dans le rapport d’essai annexé.
Ce document atteste uniquement des caractéristiques de l'échantillon soumis aux essais et ne préjuge pas des caractéristiques de produits similaires. Il ne constitue
donc pas une certification de produits au sens de l'article L.433-3 l'Ordonnance n°2016-301 du 14 mars 2016 relative au code de la consommation

NOTA : Sont seules autorisées les reproductions intégrales et par photocopie du présent procès-verbal de classement ou de l’ensemble
procès-verbal de classement et rapport d’essai annexé.
A Lyon, le 31 août 2020

Lucile MULTARI Léa Monin


Ingénieur Tests et Essais Ingénieur Tests et Essais

Siège Social : 14 rue des reculettes – 75013 PARIS  Tél : +33 (0)1 44 08 19 00  Fax :+33 (0)1 44 08 19 39  www.ifth.org
SIRET 433 430 832 00108 – NAF 729Z – TVA : FR 39 433430832 – CENTRE TECHNIQUE INDUSTRIEL (LOI DU 22 JUILLET 1948 – ARRETE DU 14 AVRIL 2000)
ENRQ_10 v1 01/19
Ecully, 31/08/2020

SMD CONTRACT LTD


Mme LOCKWOOD Emma
Pittman Way,Fulwood, Preston
PR2 9ZD LANCASHIRE
ROYAUME-UNI

IFTH reference : DL200702-041


TEST REPORT N° 20-01517 E1 - V1

The copie of this document is only authorised in its integral version

PURPOSE OF THE REQUEST

Customer reference : Date of request : 02/07/2020

Samples supplied on : 27/07/2020


Purchase order : commande validée
N° CE/CL :
Subject :
N° CQ :

SAMPLE(S) REFERENCE(S)

20-01517-001 : Q4160 Printed 100 % Polyester

This report has been approved electronically according to the norm requirements NF EN ISO/CEI 17025
Siège Social : 14 rue des Reculettes - 75013 PARIS ● Tél : +33 (0)1 44 08 19 00 ● Fax : +33 (0)1 44 08 19 39 ● www.ifth.org
SIRET 433 430 832 00108 - NAF 7219Z - TVA : FR 39 433430832 - CENTRE TECHNIQUE INDUSTRIEL (LOI DU 22 JUILLET 1948 - ARRETE DU 14 AVRIL 2000)

Page 1 sur 6
TEST REPORT N° 20-01517 E1 - V1

DETAILS OF RESULTS

20-01517-001 Q4160 Printed 100 % Polyester

Buildings material - Reaction to fire - Electrical burner test


NF P 92-503 (1995)

Test carried out according to COFRAC accreditation

PROCESS CONDITIONS

Conditioning of specimens before tests : (23 ± 2)° C and (50 ± 5) % RH during minimum 7 days
Number of tested specimens : 4
Testing location : Ecully
Date of the test : 26/08/2020

RESULTS

Specimen 1
specimen tested Printed
Side tested Front side
Direction tested Warp direction
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Fall of fragment fired No
Carbonized length (in mm) 160
Carbonized width between 45 and 60 cm (in mm) /
Afterglow with spread on more than 25 cm (in mm) No
Specimen 2
specimen tested Printed
Side tested Front side
Direction tested Weft direction
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Fall of fragment fired No
Carbonized length (in mm) 180
Carbonized width between 45 and 60 cm (in mm) /
Afterglow with spread on more than 25 cm (in mm) No
Specimen 3
specimen tested Printed
Side tested Back side
Direction tested Warp direction
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Fall of fragment fired No
Carbonized length (in mm) 140
Carbonized width between 45 and 60 cm (in mm) /
Afterglow with spread on more than 25 cm (in mm) No
Specimen 4
specimen tested Printed
Side tested Back side
Direction tested Weft direction
Times of ignitions (in s) /

Page 2 sur 6
TEST REPORT N° 20-01517 E1 - V1

Durations of ignitions (in s) 0


Fall of not ardent drops Yes
Fall of ardent drops No
Fall of fragment fired No
Carbonized length (in mm) 200
Carbonized width between 45 and 60 cm (in mm) /
Afterglow with spread on more than 25 cm (in mm) No
Eprouvette 1
Average of carbonized lengthes (in mm) 170
Average of carbonized widthes between 45 and 60 cm (in mm) /
Drilling by fusion without ignition or with ignition < or = 5 s Yes
Maximum duration of ignition (in s) 0
Fall of ardent drops or fragment fired No
Afterglow with spread on more than 25 cm (in mm) No

Page 3 sur 6
TEST REPORT N° 20-01517 E1 - V1

DETAILS OF RESULTS

20-01517-001 Q4160 Printed 100 % Polyester

Buildings material - Reaction to fire - Dripping test.


NF P 92-505 (1995)

Test carried out according to COFRAC accreditation

PROCESS CONDITIONS

Conditioning of specimens before tests : (23 ± 2)° C and (50 ± 5) % RH during minimum 7 days
Number of tested specimens : 4
Testing location : Ecully
Date of the test : 26/08/2020

RESULTS

Specimen 1
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Specimen 2
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Specimen 3
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Specimen 4
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Eprouvette 1
At least one sample ignited cotton No

Page 4 sur 6
TEST REPORT N° 20-01517 E1 - V1

DETAILS OF RESULTS

20-01517-001 Q4160 Printed 100 % Polyester

Buildings material - Reaction to fire - Flame persistance test and speed of the spread of flame.
NF P 92-504 (1995)

Test carried out according to COFRAC accreditation

PROCESS CONDITIONS

Conditioning of specimens before tests : (23 ± 2)° C and (50 ± 5) % RH during minimum 7 days
Number of tested specimens : 4
Testing location : Ecully
Date of the test : 26/08/2020

RESULTS

Specimen 1
Specimen tested Printed
Side tested Front side
Direction tested Warp direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Specimen 2
Specimen tested Printed
Side tested Front side
Direction tested Weft direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Specimen 3
Specimen tested Printed
Side tested Back side
Direction tested Warp direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Specimen 4
Specimen tested Printed
Side tested Back side
Direction tested Weft direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Eprouvette 1
Maximum duration of ignition (in s) 0
Fall of ardent drops or fragment fired No

Page 5 sur 6
TEST REPORT N° 20-01517 E1 - V1

SAMPLE DESCRIPTION ANNOUNCED BY THE CLIENT

20-01517-001 Q4160 Printed 100 % Polyester

Composition Tissu 100% polyester FR ignifugé dans la masse / fabric 100% inherent fire resistant polyester.

Measured Mass per unit area Environ/About 280 g/m²

Measured Thickness Environ/About 0,50 mm

Color Imprimé rayures (vert-gris-rose) / stripes printed (green-grey-pink)

Test requested by SMD Contracts Ltd

Name and address of the SMD Contracts Ltd


producer Pittman Way, Fullwood
Preston, England
PR2 9ZD
Name and address of the SMD Contracts Ltd
supplier Pittman Way, Fullwood
Preston, England
PR2 9ZD

Cedric ROSSARD
Laboratory Manager

Versions

Version 1 : Report creation

I.F.T.H. service clientèle


Avenue Guy de Collongue - 69134 ECULLY CEDEX
FRANCE
SIRET 433 430 832 00017

Number of pages : 6 Appendices : 0

If test reports, interpretation reports, comments, advice or observations are translated into a foreign language, only the version in French is valid.
« The uncertainity associated to the result was not explicitely taken in consideration to declare the conformity to the specification. Conformities are given only for the results
associated to a specification. Results of this test report are only valid for specimens subjected to testing at IFTH.»

* End of report *
Page 6 sur 6
FLAMMABILITY TEST CERTIFICATE – 85903
COMPANY DETAILS: SMD CONTRACTS
SMD GROUP LTD, UNIT F2, PITTMAN WAY, FULWOOD, PRESTON, PR2 9ZD

CONTACT NAME(S): EMMA LOCKWOOD


TEL: 01772 651199
EMAIL: [email protected],
[email protected]

DATE RECEIVED: 23/11/2020


DATE TESTED: 27/11/2020
DATE ISSUED: 30/11/2020
PO NUMBER: NOT STATED

SAMPLE DESCRIPTION: Q4160 REGAN JADE


COLOUR: NOT STATED
QUALITY/BATCH REF: NOT STATED
COMPOSITION: 100% IFR POLYESTER
MODEL REF: NOT STATED
SAMPLE END USE: CONTRACT UPHOLSTERY
MANUFACTURER: NOT STATED
SUPPLIER/BUYER: SMD CONTRACTS

REQUIRMENT/CLASSIFICATION:
BS EN 13773: 2003 – Textiles and textile products – Burning behaviour – Curtains and drapes classification scheme

TEST METHODS:
BS EN 1101: 1996 – Burning behaviour of curtains & drapes. Detailed procedure to determine the ignitibility of vertically
orientated specimens (Small flame)

BS EN 13772: 2011 – Textiles and textile products – Burning behaviour – Curtains & Drapes – Measurement of flame spread of
vertically oriented specimens with large ignition source

PRE-TREATMENT:
Prior to conditioning one set of six specimens had been subjected to 12 standard wash cycles in accordance with BS EN ISO
10528: 1995 Procedure A, then line dried in ambient atmospheric conditions.

CONDITIONING:
The sample was conditioned for at least 24 hrs in a specified atmosphere at 20 ± 20C and 65 ± 5% r h.

Authorised By:

Zeb Alam Mark Jones Karen Brooks


Operations Director General Manager Managing Director

Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured
value(s) marked* are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the
expanded test uncertainty Uk=2 (approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test
results issued on this certificate refer only to the item under test as supplied by the customer. This test certificate shall not be
duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]

Page 1 of 3
FLAMMABILITY TEST CERTIFICATE – 85903
TEST RESULTS: BS EN 1101: 1996 (BEFORE WASH)

TEST NUMBER FLAME APPLICATION TIME RESULT TEST NUMBER FLAME APPLICATION TIME RESULT
1 1s No-Ignition 7 15s No-Ignition
2 2s No-Ignition 8 20s No-Ignition
3 3s No-Ignition 9 20s No-Ignition
4 4s No-Ignition 10 20s No-Ignition
5 5s No-Ignition 11 20s No-Ignition
6 10s No-Ignition 12 20s No-Ignition

TEST RESULTS: BS EN 13772: 2011

Test Criteria 1 2 3 4 5 6
Surface Side Tested A or B A A A A A A
Specimen Direction: ↑ ↓ ↑ → ← →
Application Time: 10 10 10 10 10 10
Flaming Duration: 0.0 0.0 0.0 0.0 0.0 0.0
1st Marker thread Severed? NS NS NS NS NS NS
3rd Marker thread Severed? NS NS NS NS NS NS
Flaming Debris NO NO NO NO NO NO
Damage Length: (mm) 130 135 138 125 124 130
Result CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1

A = FACE SIDE
NS = NOT SEVERED

Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured
value(s) marked* are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the
expanded test uncertainty Uk=2 (approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test
results issued on this certificate refer only to the item under test as supplied by the customer. This test certificate shall not be
duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]

END OF REPORT
Page 2 of 3
FLAMMABILITY TEST CERTIFICATE – 85903
TEST RESULTS: BS EN 1101: 1996 (AFTER WASH)

TEST NUMBER FLAME APPLICATION TIME RESULT TEST NUMBER FLAME APPLICATION TIME RESULT
1 1s No-Ignition 7 15s No-Ignition
2 2s No-Ignition 8 20s No-Ignition
3 3s No-Ignition 9 20s No-Ignition
4 4s No-Ignition 10 20s No-Ignition
5 5s No-Ignition 11 20s No-Ignition
6 10s No-Ignition 12 20s No-Ignition

TEST RESULTS: BS EN 13772: 2011 AFTER WASH

Test Criteria 1 2 3 4 5 6
Surface Side Tested A or B A A A A A A
Specimen Direction: ↑ ↓ ↑ → ← →
Application Time: 10 10 10 10 10 10
Flaming Duration: 0.0 0.0 0.0 0.0 0.0 0.0
1st Marker thread Severed? NS NS NS NS NS NS
3rd Marker thread Severed? NS NS NS NS NS NS
Flaming Debris NO NO NO NO NO NO
Damage Length: (mm) 125 130 128 140 135 111
Result CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1

A = FACE SIDE
NS = NOT SEVERED

CLASSIFICATION

CLASS IGNITIBILITY FLAME SPREAD


1
Non Ignition according to EN 1101 1st Marker thread not severed, no flaming debris, according to EN 13772
2
Non Ignition according to EN 1101 3rd Marker thread not severed, no flaming debris, according to EN 13772
3
Non Ignition according to EN 1101 3rd Marker thread severed, and/or flaming debris, according to EN 13772

4 Ignition according to EN 1101 3rd Marker threads not severed, and no flaming debris, according to EN 1102

5 Ignition according to EN 1101 3rd Marker threads severed, and/or flaming debris, according to EN 1102

CONCLUSION:
The sample supplied has achieved a CLASS 1 in accordance with BS EN 13773: 2003, before & after 12 wash cycles

Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured
value(s) marked* are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the
expanded test uncertainty Uk=2 (approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test
results issued on this certificate refer only to the item under test as supplied by the customer. This test certificate shall not be
duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]

END OF REPORT
Page 3 of 3
Test Certificate 81022 - 1
Report Details
Report Number 81022 - 1 Date Submitted 05-Mar-20
Service Requested BS 5867-2: 2008 - Type C Date Issued 13-Mar-20

Customer Details
Company Name SMD CONTRACTS
Customer Contact SARAH WEST Company Address UNIT F2; PITTMAN WAY
Customer Ref/PO FULWOOD
LANCASHIRE
PR2 9ZD

Sample Details As supplied by the customer


Sample Description HELBECK Q4160

Fibre Composition 100% POLYESTER FR

Quality/Batch Ref BATCH 118164-1-1


Colour MIDNIGHT

Sample End Use CONTRACT DRAPERY

Model Ref Q4160 Manufacturer


Supplier / Buyer SMD HOLDINGS LTD.

Performance Requirement:
BS 5867-2: 2008 Type C – Flammability requirements specification – Fabrics for curtains, drapes and window blinds.

Test Method:
BS EN ISO 15025: 2002 Procedure A (Surface Ignition) – Protective clothing – Protection against heat and flame. Methods of test for limited flame
spread.

Pre-Treatment:
Prior to testing, one set of specimens had been subjected to 50 standard wash cycles in accordance with BS EN ISO 15028 (Standard) and then line
dried in ambient atmospheric conditions.

Conditioning:
The sample was conditioned for at least 24 hrs in a specified atmosphere at 20 ± 2°C and 65 ± 5% r h.

Pass / Fail Criteria:


No Part of any hole nor any part of the lowest boundary of any flame shall reach the top edge or either vertical edge of the sample. If any part of any
hole or any part of the lowest boundary of any flame, reaches the top edge or either vertical edge, or if there is any separation of any flaming debris
droplets in the testing from any specimen, or if the mean after flame or afterglow times exceed 2.5 seconds the fabrics shall be deemed not to
comply with the requirements for type “C” of BS 5867-2

Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured value(s) marked*
are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the expanded test uncertainty Uk=2
(approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test results issued on this certificate refer only to the
item under test as supplied by the customer. This test certificate shall not be duplicated.
T: 0161 5050 650 E: [email protected] A: Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN
Copyright IFS Laboratories Limited
Page 1 of 3
Test Certificate 81022 - 1

Test Results
Test 1 - Before Wash 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Surface Tested: Face Back Face Back Face Back Face Back

Specimen Direction: ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ →

Application Time: 5 Seconds 5 Seconds 15 Seconds 15 Seconds 20 Seconds 20 Seconds 30 Seconds 30 Seconds

Flaming Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Afterglow Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Hole Formed: Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Hole Reached the Edge: No No No No No No No No No No No No No No No No

Flame Reached the Edge: No No No No No No No No No No No No No No No No

Flaming Debris: No No No No No No No No No No No No No No No No

Damage Length [mm]: 41 50 36 40 43 35 43 43 48 46 46 46 48 44 53 48

Damge Width [mm]: 16 17 26 28 26 20 19 20 19 23 21 27 14 20 20 21

Average After Flame < 2.5S 0.0

Average After Glow < 2.5S 0.0

Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured value(s) marked*
are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the expanded test uncertainty Uk=2
(approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test results issued on this certificate refer only to the
item under test as supplied by the customer. This test certificate shall not be duplicated.
T: 0161 5050 650 E: [email protected] A: Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN
Copyright IFS Laboratories Limited
Page 2 of 3
Test Certificate 81022 - 1

Test 2 - After Wash 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Surface Tested: Face Back Face Back Face Back Face Back

Specimen Direction: ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ →

Application Time: 5 Seconds 5 Seconds 15 Seconds 15 Seconds 20 Seconds 20 Seconds 30 Seconds 30 Seconds

Flaming Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Afterglow Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Hole Formed: Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Hole Reached the Edge: No No No No No No No No No No No No No No No No

Flame Reached the Edge: No No No No No No No No No No No No No No No No

Flaming Debris: No No No No No No No No No No No No No No No No

Damage Length [mm]: 31 28 34 51 46 37 40 31 30 38 43 46 34 32 46 42

Damge Width [mm]: 26 21 16 22 19 19 30 28 21 27 22 25 21 27 20 23

Average After Flame < 2.5S 0.0

Average After Glow < 2.5S 0.0

Overall Result: PASS


The sample supplied meets the type C performance requirement of BS 5867-2: 2008 when tested in accordance with BS EN ISO 15025: 2002 Procedure A (Surface
Ignition) before and after cleansing.

Authorised Signature:

Mark Jones
Quality Manager

Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured value(s) marked*
are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the expanded test uncertainty Uk=2
(approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test results issued on this certificate refer only to the
item under test as supplied by the customer. This test certificate shall not be duplicated.
T: 0161 5050 650 E: [email protected] A: Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN
Copyright IFS Laboratories Limited
Page 3 of 3