Fire Rating Certifications for Polyester Fabric
Fire Rating Certifications for Polyester Fabric
CERTIFICATE N° 20-01517 L
And appendices of 6 pages
MATERIAL presented by: SMD CONTRACT LTD
Pittman Way,Fulwood, Preston
PR2 9ZD LANCASHIRE
ENGLAND
TRADE NAME: Q4160 Printed 100 % Polyester
CLASSIFICATION:
M1
CLASSIFICATION DURATION (article 5 of appendix 2) : unlimited unless otherwise specified
given the criteria resulting from the tests described in the enclosed test report.
The classification indicated does not mean that materials marketed comply with the test samples and must not be considered as a qualification certificate as defined by French
law dated March 14, 2016.
N.B.: Only integral copies of this document may be made by photocopying the classification report and/or the classification report and
enclosed test report.
Issued in Lyon, France, on August 31rst 2020
Siège Social : 14 rue des reculettes – 75013 PARIS Tél : +33 (0)1 44 08 19 00 Fax :+33 (0)1 44 08 19 39 www.ifth.org
SIRET 433 430 832 00108 – NAF 729Z – TVA : FR 39 433430832 – CENTRE TECHNIQUE INDUSTRIEL (LOI DU 22 JUILLET 1948 – ARRETE DU 14 AVRIL 2000)
ENRQ_11 v1 01/19
FLAMMABILITY TEST CERTIFICATE - 77427
COMPANY DETAILS: SMD TEXTILES LTD,
UNIT F2, PITTMAN WAY, FULWOOD, PRESTON PR2 9ZD
SPECIFICATION/REQUIRMENT:
IMO FTP Part 7: 2010 – Test for vertically supported textiles and films.
PRE-TREATMENT:
No wetting procedure had been carried out. The results obtained in this report relate only to the tested specimens as
received.
CONDITIONING:
The specimens had been conditioned for at least 24 hrs in a specified atmosphere at 20 ± 50C and 65 ± 5% r h.
Authorised By:
Please note: this test results issued on this certificate refer only to the item tested and therefore doesn’t relate to the lot or
batch of the product / sample. This test certificate shall not be duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park,
Manchester, M17 1RN. T: 0161 50 50 650 E: [email protected]
Page 1 of 2
FLAMMABILITY TEST CERTIFICATE - 77427
TEST RESULTS BEFORE WASH FACE FABRIC:
Test Results (Warp) 1 2 3 4 5
Application Time (as determined by pre-testing): 15s (EDGE) 15s (EDGE) 15s (EDGE) 15s (EDGE) 15s (EDGE)
After Flame time: 0.0 0.0 0.0 0.0 0.0
Flame reached an edge: NO NO NO NO NO
Charred Length: (mm) 91 79 104 77 58
Ignition of Cotton Wool (Y/N) NO NO NO NO NO
Occurrence of surface flash (Y/N) NO NO NO NO NO
Specimen Result: PASS PASS PASS PASS PASS
CONCLUSION:
The sample supplied meets the performance criteria as stated in paragraph 3 of IMO FTP Part 7: 2010.
END OF REPORT
Please note: the test results issued on this certificate refer only to the item tested and therefore doesn’t relate to the lot or
batch of the product / sample. This test certificate shall not be duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park,
Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]
Page 2 of 2
Our Ref: SW/PN/RM 13 September 2017
COMMENTS: The sample submitted complies with the flammability requirements of BS5867-
2:2008 for Type C performance.
S. WISEMAN P. NEESAM
LABORATORY DIRECTOR HEAD OF FLAMMABILITY
This report shall not be reproduced except in full without the written approval of HSTTS. In all circumstances, results of tests are implied as
referring only to the sample supplied and should not be construed or interpreted on any other basis. The comments given in the report are for
guidance only and are not part of the results. Opinions and interpretations expressed herein are outside the scope of UKAS accreditation
Procedure
Specimens of fabric, Q4160 were subjected to the test methods described in BS EN ISO 15025:2002,
procedure ‘A’, in the as received condition and after 50 Wash cycles according to BS EN ISO 6330,
Program 2A.
No part of any hole nor any part of the lowest boundary of any flame shall reach the top edge or either
vertical edge of the sample specimen and there shall be no separation of any flaming debris from any
specimen, or if the mean afterflame or afterglow times exceed 2.5 s, the fabric shall be deemed not to
comply with the requirements for type “C” of this British Standard
Results
The following test results relate only to the ignitability of the combination of materials under the
particular conditions of test; they are not intended as a means of assessing the full potential fire hazard of
the materials in use.
They also only relate to the materials tested. They do not guarantee to represent the performance of
production materials.
Comments
The sample submitted complies with the flammability requirements of BS5867-2:2008 for Type C
performance.
PROCES-VERBAL N° 20-01516 L
et 1 annexe de 6 pages
MATERIAU présenté par : SMD CONTRACT LTD
Pittman Way,Fulwood, Preston
PR2 9ZD LANCASHIRE
ROYAUME-UNI
CLASSEMENT :
M1
DURABILITE du classement (Article 5 de l’annexe 2) : non limitée a priori.
Compte tenu des critères résultant des essais décrits dans le rapport d’essai annexé.
Ce document atteste uniquement des caractéristiques de l'échantillon soumis aux essais et ne préjuge pas des caractéristiques de produits similaires. Il ne constitue
donc pas une certification de produits au sens de l'article L.433-3 l'Ordonnance n°2016-301 du 14 mars 2016 relative au code de la consommation
NOTA : Sont seules autorisées les reproductions intégrales et par photocopie du présent procès-verbal de classement ou de l’ensemble
procès-verbal de classement et rapport d’essai annexé.
A Lyon, le 31 août 2020
Siège Social : 14 rue des reculettes – 75013 PARIS Tél : +33 (0)1 44 08 19 00 Fax :+33 (0)1 44 08 19 39 www.ifth.org
SIRET 433 430 832 00108 – NAF 729Z – TVA : FR 39 433430832 – CENTRE TECHNIQUE INDUSTRIEL (LOI DU 22 JUILLET 1948 – ARRETE DU 14 AVRIL 2000)
ENRQ_10 v1 01/19
Ecully, 31/08/2020
SAMPLE(S) REFERENCE(S)
This report has been approved electronically according to the norm requirements NF EN ISO/CEI 17025
Siège Social : 14 rue des Reculettes - 75013 PARIS ● Tél : +33 (0)1 44 08 19 00 ● Fax : +33 (0)1 44 08 19 39 ● www.ifth.org
SIRET 433 430 832 00108 - NAF 7219Z - TVA : FR 39 433430832 - CENTRE TECHNIQUE INDUSTRIEL (LOI DU 22 JUILLET 1948 - ARRETE DU 14 AVRIL 2000)
Page 1 sur 6
TEST REPORT N° 20-01517 E1 - V1
DETAILS OF RESULTS
PROCESS CONDITIONS
Conditioning of specimens before tests : (23 ± 2)° C and (50 ± 5) % RH during minimum 7 days
Number of tested specimens : 4
Testing location : Ecully
Date of the test : 26/08/2020
RESULTS
Specimen 1
specimen tested Printed
Side tested Front side
Direction tested Warp direction
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Fall of fragment fired No
Carbonized length (in mm) 160
Carbonized width between 45 and 60 cm (in mm) /
Afterglow with spread on more than 25 cm (in mm) No
Specimen 2
specimen tested Printed
Side tested Front side
Direction tested Weft direction
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Fall of fragment fired No
Carbonized length (in mm) 180
Carbonized width between 45 and 60 cm (in mm) /
Afterglow with spread on more than 25 cm (in mm) No
Specimen 3
specimen tested Printed
Side tested Back side
Direction tested Warp direction
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Fall of fragment fired No
Carbonized length (in mm) 140
Carbonized width between 45 and 60 cm (in mm) /
Afterglow with spread on more than 25 cm (in mm) No
Specimen 4
specimen tested Printed
Side tested Back side
Direction tested Weft direction
Times of ignitions (in s) /
Page 2 sur 6
TEST REPORT N° 20-01517 E1 - V1
Page 3 sur 6
TEST REPORT N° 20-01517 E1 - V1
DETAILS OF RESULTS
PROCESS CONDITIONS
Conditioning of specimens before tests : (23 ± 2)° C and (50 ± 5) % RH during minimum 7 days
Number of tested specimens : 4
Testing location : Ecully
Date of the test : 26/08/2020
RESULTS
Specimen 1
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Specimen 2
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Specimen 3
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Specimen 4
Specimen tested Printed
Times of ignitions (in s) /
Durations of ignitions (in s) 0
Fall of not ardent drops Yes
Fall of ardent drops No
Ignition of cotton No
Eprouvette 1
At least one sample ignited cotton No
Page 4 sur 6
TEST REPORT N° 20-01517 E1 - V1
DETAILS OF RESULTS
Buildings material - Reaction to fire - Flame persistance test and speed of the spread of flame.
NF P 92-504 (1995)
PROCESS CONDITIONS
Conditioning of specimens before tests : (23 ± 2)° C and (50 ± 5) % RH during minimum 7 days
Number of tested specimens : 4
Testing location : Ecully
Date of the test : 26/08/2020
RESULTS
Specimen 1
Specimen tested Printed
Side tested Front side
Direction tested Warp direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Specimen 2
Specimen tested Printed
Side tested Front side
Direction tested Weft direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Specimen 3
Specimen tested Printed
Side tested Back side
Direction tested Warp direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Specimen 4
Specimen tested Printed
Side tested Back side
Direction tested Weft direction
Durations of inflammations (in s) 0/0/0/0/0/0/0/0/0/0
Fall of not ardent drops Yes
Fall of ardent drops No
Eprouvette 1
Maximum duration of ignition (in s) 0
Fall of ardent drops or fragment fired No
Page 5 sur 6
TEST REPORT N° 20-01517 E1 - V1
Composition Tissu 100% polyester FR ignifugé dans la masse / fabric 100% inherent fire resistant polyester.
Cedric ROSSARD
Laboratory Manager
Versions
If test reports, interpretation reports, comments, advice or observations are translated into a foreign language, only the version in French is valid.
« The uncertainity associated to the result was not explicitely taken in consideration to declare the conformity to the specification. Conformities are given only for the results
associated to a specification. Results of this test report are only valid for specimens subjected to testing at IFTH.»
* End of report *
Page 6 sur 6
FLAMMABILITY TEST CERTIFICATE – 85903
COMPANY DETAILS: SMD CONTRACTS
SMD GROUP LTD, UNIT F2, PITTMAN WAY, FULWOOD, PRESTON, PR2 9ZD
REQUIRMENT/CLASSIFICATION:
BS EN 13773: 2003 – Textiles and textile products – Burning behaviour – Curtains and drapes classification scheme
TEST METHODS:
BS EN 1101: 1996 – Burning behaviour of curtains & drapes. Detailed procedure to determine the ignitibility of vertically
orientated specimens (Small flame)
BS EN 13772: 2011 – Textiles and textile products – Burning behaviour – Curtains & Drapes – Measurement of flame spread of
vertically oriented specimens with large ignition source
PRE-TREATMENT:
Prior to conditioning one set of six specimens had been subjected to 12 standard wash cycles in accordance with BS EN ISO
10528: 1995 Procedure A, then line dried in ambient atmospheric conditions.
CONDITIONING:
The sample was conditioned for at least 24 hrs in a specified atmosphere at 20 ± 20C and 65 ± 5% r h.
Authorised By:
Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured
value(s) marked* are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the
expanded test uncertainty Uk=2 (approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test
results issued on this certificate refer only to the item under test as supplied by the customer. This test certificate shall not be
duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]
Page 1 of 3
FLAMMABILITY TEST CERTIFICATE – 85903
TEST RESULTS: BS EN 1101: 1996 (BEFORE WASH)
TEST NUMBER FLAME APPLICATION TIME RESULT TEST NUMBER FLAME APPLICATION TIME RESULT
1 1s No-Ignition 7 15s No-Ignition
2 2s No-Ignition 8 20s No-Ignition
3 3s No-Ignition 9 20s No-Ignition
4 4s No-Ignition 10 20s No-Ignition
5 5s No-Ignition 11 20s No-Ignition
6 10s No-Ignition 12 20s No-Ignition
Test Criteria 1 2 3 4 5 6
Surface Side Tested A or B A A A A A A
Specimen Direction: ↑ ↓ ↑ → ← →
Application Time: 10 10 10 10 10 10
Flaming Duration: 0.0 0.0 0.0 0.0 0.0 0.0
1st Marker thread Severed? NS NS NS NS NS NS
3rd Marker thread Severed? NS NS NS NS NS NS
Flaming Debris NO NO NO NO NO NO
Damage Length: (mm) 130 135 138 125 124 130
Result CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1
A = FACE SIDE
NS = NOT SEVERED
Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured
value(s) marked* are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the
expanded test uncertainty Uk=2 (approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test
results issued on this certificate refer only to the item under test as supplied by the customer. This test certificate shall not be
duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]
END OF REPORT
Page 2 of 3
FLAMMABILITY TEST CERTIFICATE – 85903
TEST RESULTS: BS EN 1101: 1996 (AFTER WASH)
TEST NUMBER FLAME APPLICATION TIME RESULT TEST NUMBER FLAME APPLICATION TIME RESULT
1 1s No-Ignition 7 15s No-Ignition
2 2s No-Ignition 8 20s No-Ignition
3 3s No-Ignition 9 20s No-Ignition
4 4s No-Ignition 10 20s No-Ignition
5 5s No-Ignition 11 20s No-Ignition
6 10s No-Ignition 12 20s No-Ignition
Test Criteria 1 2 3 4 5 6
Surface Side Tested A or B A A A A A A
Specimen Direction: ↑ ↓ ↑ → ← →
Application Time: 10 10 10 10 10 10
Flaming Duration: 0.0 0.0 0.0 0.0 0.0 0.0
1st Marker thread Severed? NS NS NS NS NS NS
3rd Marker thread Severed? NS NS NS NS NS NS
Flaming Debris NO NO NO NO NO NO
Damage Length: (mm) 125 130 128 140 135 111
Result CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1
A = FACE SIDE
NS = NOT SEVERED
CLASSIFICATION
4 Ignition according to EN 1101 3rd Marker threads not severed, and no flaming debris, according to EN 1102
5 Ignition according to EN 1101 3rd Marker threads severed, and/or flaming debris, according to EN 1102
CONCLUSION:
The sample supplied has achieved a CLASS 1 in accordance with BS EN 13773: 2003, before & after 12 wash cycles
Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured
value(s) marked* are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the
expanded test uncertainty Uk=2 (approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test
results issued on this certificate refer only to the item under test as supplied by the customer. This test certificate shall not be
duplicated. Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN T: 0161 50 50 650 E: [email protected]
END OF REPORT
Page 3 of 3
Test Certificate 81022 - 1
Report Details
Report Number 81022 - 1 Date Submitted 05-Mar-20
Service Requested BS 5867-2: 2008 - Type C Date Issued 13-Mar-20
Customer Details
Company Name SMD CONTRACTS
Customer Contact SARAH WEST Company Address UNIT F2; PITTMAN WAY
Customer Ref/PO FULWOOD
LANCASHIRE
PR2 9ZD
Performance Requirement:
BS 5867-2: 2008 Type C – Flammability requirements specification – Fabrics for curtains, drapes and window blinds.
Test Method:
BS EN ISO 15025: 2002 Procedure A (Surface Ignition) – Protective clothing – Protection against heat and flame. Methods of test for limited flame
spread.
Pre-Treatment:
Prior to testing, one set of specimens had been subjected to 50 standard wash cycles in accordance with BS EN ISO 15028 (Standard) and then line
dried in ambient atmospheric conditions.
Conditioning:
The sample was conditioned for at least 24 hrs in a specified atmosphere at 20 ± 2°C and 65 ± 5% r h.
Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured value(s) marked*
are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the expanded test uncertainty Uk=2
(approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test results issued on this certificate refer only to the
item under test as supplied by the customer. This test certificate shall not be duplicated.
T: 0161 5050 650 E: [email protected] A: Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN
Copyright IFS Laboratories Limited
Page 1 of 3
Test Certificate 81022 - 1
Test Results
Test 1 - Before Wash 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Surface Tested: Face Back Face Back Face Back Face Back
Specimen Direction: ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ →
Application Time: 5 Seconds 5 Seconds 15 Seconds 15 Seconds 20 Seconds 20 Seconds 30 Seconds 30 Seconds
Flaming Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Afterglow Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Hole Formed: Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Flaming Debris: No No No No No No No No No No No No No No No No
Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured value(s) marked*
are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the expanded test uncertainty Uk=2
(approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test results issued on this certificate refer only to the
item under test as supplied by the customer. This test certificate shall not be duplicated.
T: 0161 5050 650 E: [email protected] A: Textile Innovation House, 1 Lyons Road, Trafford Park, Manchester, M17 1RN
Copyright IFS Laboratories Limited
Page 2 of 3
Test Certificate 81022 - 1
Surface Tested: Face Back Face Back Face Back Face Back
Specimen Direction: ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ → ↑ →
Application Time: 5 Seconds 5 Seconds 15 Seconds 15 Seconds 20 Seconds 20 Seconds 30 Seconds 30 Seconds
Flaming Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Afterglow Ceased: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Hole Formed: Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Flaming Debris: No No No No No No No No No No No No No No No No
Authorised Signature:
Mark Jones
Quality Manager
Please note: The uncertainty of measurement is taken into account when stating conformance to the specification. The measured value(s) marked*
are compared with the ‘acceptance interval” which is determined by reducing the specification limits by the expanded test uncertainty Uk=2
(approximately 95% confidence interval). Results outside these limits are declared as ‘fail’. All test results issued on this certificate refer only to the
item under test as supplied by the customer. This test certificate shall not be duplicated.