RCEL

Electric Actuators 015–250

INSTALLATION B. ELECTRIC WIRING


1. Mounting on valve, see instruction A.
2. Electric wiring, see instruction B. NOTE: Electric wiring must be carried out
3. Adjustment, see instruction C. by qualified personnel only!
4. Manual operation, see instruction D. 1. Loosen the screws on the cover and lift it off.
2. Check the voltage marked on the actuator
NOTE: label.
Only electric wiring, acc. to instruction B,
3. Connect according to the enclosed wiring
is required when the actuator is delivered
diagram or, if the actuator is of standard
from Remote Control mounted on a valve.
design, according to the wiring diagram below.
It is adjusted and ready for operation.
The wiring diagram is drawn in unaffected
position (the valve in intermediate position).
WARNING 4. Test run the actuator from the intermediate
Remove power before the cover position checking that the actuator turns in
is dismantled! the correct direction.
The actuator must be handled with the
utmost care when the cover is removed 5. Test run the actuator and check that the
and the power connected! limit switches work correctly.
6. Check that the cable entries and possible
A. MOUNTING ON VALVE blind plug are sealed.
1. Operate the valve manually to fully open 7. Mount the cover.
or fully closed position before the actuator
is mounted. Wiring diagram No NS 12000C. Standard
2. Operate the actuator manually (see in-
struction D) to fully open or fully closed

Instruction No 438B
RED
position. T.P
BLUE
3. Check that the actuator and valve stem N
G/F WHITE
are in correct position. Please note, valve HEATER 20W
and actuator must be in the same mode L1 2 CTS 2 CLS
(fully open / fully closed) prior to the OVER
3
2
1
OTS 3 1
2 OLS
assembly. TORQUE
LAMP
3 1
3 1

YELLOW
4. Mount the actuator on the valve and check CLOSED
LAMP
BLACK
that the actuator and valve stems are cent- OPEN
LAMP
ORANGE
ered and aligned. If a mounting bracket is OPEN
used, the fit must be checked so that no CLOSE
BLUE

distortion or play exists. RED

G/F WHITE
5. Operate the valve manually with the aid of 2 ACLS
CLS CLOSE LIMIT SWITCH
3 1
PINK
the actuator handwheel and check that the OLS
CTS
OPEN LIMIT SWITCH
TORQUE CLOSE LIMIT SWITCH
OTS TORQUE OPEN LIMIT SWITCH
valve moves with normal resistance. YELLOW
2 AOLS ACLS AUX. CLOSE LIMIT SWITCH
1 AOLS AUX. OPEN LIMIT SWITCH
6. Check that all screws are correctly tighte- BROWN 3
TP THERMAL PROTECTOR

ned YELLOW
CUSTOMER WIRING ACTUATOR WIRING

Tel +46 (0)23 587 00 www.remotecontrol.se Fax +46 (0)23 587 45


Ref No 438B / Art No 980438
C. ADJUSTMENT (c) Adjustment of torque switches:
1. Make the final cam adjustments for the limit The torque switches are adjusted from factory
switches (if necessary) acc. to instruction (a) to protect actuator and valve against overload-
below. ing and should normally not be adjusted.
2. Make the final adjustments of the mechanical Should adjustment however be necessary,
limit stops (if necessary) acc. to instruction (b) please contact our technicians before adjusting.
below.
3. Run the actuator from one end position to the D. MANUAL OPERATION
other a number of times. 1. Pull the engagement lever towards the
handwheel until it remains in position.
4. Adjust the indicator disc for visual indication
so that it relates to the valve position. 2. Turn the handwheel until the valve reaches
the required position.
5. Test run the actuator and check that the limit
indicators are working correctly. 3. Turn clockwise to close and anti-clockwise
to open.
6. Mount the cover.
NOTE!
(a) Adjustment of cams for limit switches: The engagement lever returns automatically
1. Operate the actuator manually to closed to auto-position when the actuator is
position. operated electrically.
2. Adjust the cam for closed position (lower
cam marked CLS).
3. Operate the actuator manually to open
position.
4. Adjust the cam for open position (upper cam
marked OLS).
5. Test run the actuator.

(b) Adjustment of mechanical limit stops for


soft-seated valves:
1. Operate the actuator electrically to closed
position.
2. Adjust the right set screw for closed position
so that it makes contact, back one turn and
tighten the lock nut.
3. Operate the actuator electrically to open
position.
4. Adjust the left set screw for open position so
that it makes contact, back one turn and
tighten the lock nut.
Open adjustment Closed adjustment
(For adjustment of metal-seated butterfly valves,
please contact our technicians.)

Remote Control Sweden AB, Kontrollvägen 15, SE-791 45 Falun . SWEDEN