Dtdo
Dtdo
doc
PROTECT
Electronics Co. Ltd
EuroProt
complex protection
DTD-EP
Three-phase differential protection
Factory configuration
User’s manual
Versions:
DTD-2 V3.xx,
DTDZ-2+U (dist.rec.) V3.xx,
DTD-3 V3.xx,
DTD-3 [5*3CT] V3.xx
DTD-2 [Io] V3.xx,
Document ID: EX–13-15059-12
CONTENTS
1 FIELD OF APPLICATION ............................................................................................ 5
1.1 THE MAIN CHARACTERISTICS OF THE COMPLEX DIFFERENTIAL PROTECTION ............... 6
1.2 THE MAIN FEATURES OF THE HARDWARE .................................................................... 7
2 THE OPERATION OF THE PROTECTIVE FUNCTIONS ...................................... 8
2.1 DIFFERENTIAL PROTECTION FUNCTIONS ...................................................................... 8
2.1.1 Realisation of the differential protection functions............................................ 8
2.1.2 The parameter setting....................................................................................... 15
2.1.3 Outputs of the differential protection function ................................................. 16
2.2 PHASE OVERCURRENT FUNCTION............................................................................... 17
2.2.1 Realisation of the phase overcurrent function ................................................. 17
2.2.2 Parameter setting ............................................................................................. 17
2.2.3 Outputs of the overcurrent functions................................................................ 19
2.3 EARTH FAULT PROTECTION ....................................................................................... 21
2.3.1 Realisation of the earth fault protection........................................................... 21
2.3.2 Parameters of the function ............................................................................... 21
2.3.3 Digital outputs of the function.......................................................................... 22
2.4 ADDITIONAL FUNCTIONS ........................................................................................... 23
2.4.1 The digital software matrix .............................................................................. 23
2.4.2 Programming PROTLOG equations ................................................................ 26
2.4.3 Application of the digital inputs ....................................................................... 29
2.4.4 Application of the relay outputs ....................................................................... 30
2.4.5 Circuit breaker control function....................................................................... 30
2.4.6 The integrated disturbance recorder function.................................................. 30
2.4.7 The free programmable timers ......................................................................... 33
2.4.8 The LED indication .......................................................................................... 33
2.4.9 Latching............................................................................................................ 34
2.4.10 Displayed messages.......................................................................................... 36
2.4.11 The displayed information (On-line window, summary).................................. 37
2.4.12 The self-check functions ................................................................................... 40
3 COMMUNICATION WITH THE DEVICE............................................................... 42
3.1 THE MENU SYSTEM .................................................................................................... 42
3.1.1 The „Events” menu .......................................................................................... 42
3.1.2 The „Test” menu .............................................................................................. 45
3.1.3 The „Chk” menu .............................................................................................. 45
3.1.4 The „Version” menu ........................................................................................ 45
3.1.5 The „Param.” menu ......................................................................................... 45
3.1.6 Parameters related to the communication ....................................................... 46
3.1.7 Password .......................................................................................................... 46
3.2 CONNECTING THE DEVICE TO AN EXTERNAL PC ........................................................ 46
4 THE OPTIONAL LOCAL SCADA FUNCTIONS..................................................... 46
8 INFORMATION ............................................................................................................ 47
1 Field of application
The EuroProt type complex protection in respect of hardware and software is a modular
device. The modules are assembled and configured according to the requirements, then the
functions are determined - within the hardware limitations - by the software. This document
describes the individual characteristics of a specific application: the factory configuration
DTD-EP complex differential protection. The general description of the members of the
EuroProt type complex protection family can be found in document “EuroProt complex
protection, hardware and software description and user’s manual” (further “EuroProt
manual”).
The DTD-EP complex numerical device realises three-phase differential protection function,
which can be applied to high speed and selective protection of high voltage transformers,
generators and generator-transformer units.
This manual describes several versions. The main information concerning these versions are
summarised in the Table below:
The device does not require matching intermediate current transformers. The turns ratio and
the phase shift due to the connection group of the transformers are matched by the software of
the differential protection.
The device includes separate overcurrent protection functions for all voltage levels of the
transformer.
As an option the included control (SCADA) functions can extend the device to the complex
field unit of the network.
The main characteristics of the DTD-EP complex differential protection are as follows:
The main characteristics of the optional SCADA functions in the device can be as follows:
The SCADA functions are performed by a dedicated controller of the CPU module, or
optionally a separate SCADA module can be involved,
The optional high resolution graphic LCD can realise comprehensive local control and
supervisory functions,
The device performs the protection and the SCADA functions of high voltage transformers.
The design and the operation of the EuroProt devices are described in the document
„EuroProt manual”.
The device can be operated by the integrated man-machine interface (2x16 character LCD an
6 push-buttons on the front panel), but the operation is more convenient using a connected
external PC, running the „Protect for Windows” operating program, developed by Protecta
Co. Ltd. Both possibilities are described in details in the document „EuroProt manual”.
The external communication can be performed via the RS 232 serial interface of the front
panel (isolated against 2 kV) or via fibre optic interface on the rear side of the device. The
application of these communication interfaces is described in the document „EuroProt
manual” as well.
Compiled by: Approved by: Date: Page: 7 / 47
Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
The DTD-EP type complex numerical protection contains the following protection functions:
The protection functions are fully independent from each other, and the setting is independent
too. The outputs are managed by the software matrix, each of them can be enabled or disabled
individually. By appropriate parameter setting, they can be programmed for latching.
The precondition of the correct operation of the DTD-EP type differential protection function
is the correct matching of the currents, and the correct handling of the different transformer
connection groups.
Current matching
When setting the parameters of the device the primary rated currents of the main transformers
on all (two or three) sides of the transformer must be selected (AV1, AV2, and AV3 in
primary Amperes). These parameters are needed only to display the measured currents scaled
in primary values.
U1
Isetting1
Isetting1 U2 Isetting 2
Iset1% = 100% , Iset 2% = 100% = 100% ,
CT 1 CT 2 CT 2
and:
U1
Isetting
U3 Isetting 3
Iset 3% = 100% = 100%
CT 3 CT 3
Where U1, U2 and U3 are the rated voltage values of the transformer (in case of regulating
coils these are the central values).
The Isetting1 defined value is free to choose. It is usual to be selected as the rated current of
the transformer on the primary side Isetting1 = Itrn1. This Isetting1 will be the reference
value for displaying the Id % differential current and for the Is % restraint current (when it is
considered on the secondary side, it is Isetting2, etc.).
The matching of the phase shift of the transformer is solved by a simple parameter setting,
which is the code value of the transformer’s connection group. (e.g. Yd11). In a differential
protection for a transformer with two voltage levels the code values are listed in Table 2
(parameter: Setting code: [0-11]), and that for a transformer with three voltage levels in Table
3 (parameter: Setting code: [0-71]).
1 Yy0 U1 U2 00
2 Dy1 U1 U2 300
3 Yd1 U1 U2 300
4 Dy5 U1 U 1500
2
5 Yd5 U1 1500
U2
6 Dd6 U1 1800
U2
7 Yy6 U1 1800
U2
8 Dy7 U2 U1 2100 (-1500)
α
jα
The meaning of phase shift is: U2 = U1.e .
CT1 CT2
K L L K
U1 U2
k l l k
to the protection
Side 1 Side 2
Connection
As the Figure indicates, the connections of the CT marked with same letters are located near
to the transformer
Table 2. Phase shift code values for a transformer with two voltage levels
protection
Table 3. Phase shift code values for a transformer with three voltage levels
Compiled by: Approved by: Date: Page: 11 / 47
Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
The differential protection function detects internal fault based on sampled phase current
comparison received from all sides of the transformer. “Rectified average” values are
calculated for a half period of the network frequency, and then the evaluation is performed in
all sampling time steps, in each millisecond. If significant difference is detected in 15
consecutive steps, this means internal fault, and trip command is generated.
In sampled current comparison the regulating range of the transformer and the errors of the
current transformers must be considered as well. This is solved by a „percentage” restraint
characteristic. If the point in the co-ordinate system defined by the Id% differential current and
the IS% restraint current is located in the upper part of the figure below, the protection
operates, and after 15 consecutive steps with the same decision it generates a trip command.
Diff.
current
áId %)
400
300
f3=200%
f2=20%
100
f1=50% f1=20%
NO OPERATION
50
20 Restraint
IS % current
0 100 200 300 400 500 600
The IS % „Restraint current” and the Id % difference current is explained with the following
formulas.
The IS % „Restraint current” in transformers with two voltage levels is calculated by:
I1 I2
100% 100%
CT1 + CT 2
I1 I2 Iset1 Iset2
+
Isetting1 Isetting2
IS % = 100% = 100%
2 2
I1 I2
I1 I2 100% 100%
I d % = + 100% = CT1 + CT 2 100%
Isetting1 Isetting2 Iset1 Iset2
The IS % „Restraint current” in transformers with three voltage levels is calculated by:
I1 I2 I3
100% 100% 100%
CT1 + CT 2 + CT 3
I1 I2 I3 Iset1 Iset2 Iset3
+ +
Isetting1 Isetting2 Isetting3
IS % = 100% = 100%
2 2
I1 I2 I3
I1 I3 100% 100% 100%
I2
I d % = + + 100% = CT1 + CT 2 + CT3 100%
Isetting1 Isetting2 Isetting3 Iset1 Iset2 Iset3
f1% This is the setting value of the horizontal section of the tripping characteristic, which
defines the basic sensitivity of the differential function. The value is expressed as
percent of the Iset1 current setting value. The differential protection can operate if: Id% >f1%
f2% This is the slope setting of the second section of the differential characteristic. This slope
is needed mainly because of the voltage regulation range of the transformer. The
differential function is balanced in the medium position of the tap-changer, any other position
generates a differential current. The second section of the characteristic starts in the origin,
and the section above the first section is valid only. The differential protection operates if the
Id % differential current is above the percent value defined by the Is % current and the f2
slope setting. The differential protection can operate if: Id% >f2%/100*IS%.
f3% The third section of the characteristic is needed because the possible saturation of the
main current transformers. The slope of this section is constant: tgα=2. The starting
point of this section on the vertical axis of the co-ordinate system is a negative value defined
by f3, it is valid only above the second section of the characteristic. The differential protection
can operate if the differential current is above this line too: Id% > (2*IS % – f3%).
f2h% To prevent false tripping because of the high inrush current of the transformer, the
differential protection is provided wit a second harmonic restraint. The second
harmonic restraint prevents the operation of the differential protection, if the second harmonic
content of the differential current is above the f2h setting, which is expressed as %. This
means: Id2h% >f2h% (Id2h% is the percentage value of the second harmonic content in
differential current, related to the basic harmonic).
Id>>% There is a possibility to set a high current value of the differential current, above
which the function generates an immediate trip command without restraint
calculation. The setting value is referred to the Isetting1 value, and it is expressed in %. If this
stage operates, the differential protection function generates a trip command within 15...20
ms.
If the differential current is above the characteristic lines, the normal operating time of the
differential protection function is about 20 ... 25 ms, (if the high current setting stage operates,
the time delay is about 10 … 15 ms.
Fig. 2 Parameters of the differential protection for transformers with two voltage levels
(Protect for Windows).
Fig. 3 Parameters of the differential protection for transformers with three voltage levels
(Protect for Windows).
To enable or disable the differential protection function a special parameter is assigned: (On
the PC: Id>, Id>> stages, enabled/disabled, on the LCD: IdEna +/-).
The assignment of the 16 (K1…K16) output relays of the device is made using the software
matrix (see below, in the Chapter „The digital software matrix” ). In the versions DTD-3
V3.xx and DTD-3 [5*3AV] V3.xx additional 8 (K17…K24) output relays can be
programmed using the PROTLOG equations (see below in the Chapter „Programming the
PROTLOG equations”).
The row of the differential protection function as the software matrix input is:
On the PC screen: Id>,
On the LCD: Mx Id>
For the PROTLOG programing the input variable received from the differential protection
function is:
Id>, (with latching: *Id>)
The latching of the function can be programmed on the LCD with the following parameter:
„MxSId”
On the PC the latching is set as the following Figure shows:
In the devices designed for transformers with two voltage levels (DTD-2 V3.xx, DTDZ-
2+U(dist.rec) V3.xx) the factory configurations realise one stage overcurrent function for the
high voltage side, and two-stage definite time overcurrent protection function on the lover
voltage side.
In the devices designed for transformers with three voltage levels (DTD-3 V3.xx, DTD-3
[5*3CT] V3.xx) the factory configurations realise one stage overcurrent function for the high
voltage side, and for both medium voltage sides as well
The algorithm calculates with numerical Fourier analysis the basic harmonic component of
the current, and this is compared with the setting value. If the basic harmonic component is
above the setting, the function starts the time counter, the expiry of which generates a trip
command.
The measurement and the comparison are performed independently in all three phases, the
timer however is common for the three phases, and the trip command is common too.
The phase overcurrent function needs the following parameter setting, as it is shown on Fig.
6. and 7. The Figures are PC screen snap-shots from the Protect for Windows operating
software:
Fig. 6 Parameters of the overcurrent protection function for transformers with two voltage
levels (Protect for Windows)
Fig. 7 Parameters of the overcurrent protection function for transformers with three voltage
levels (Protect for Windows)
The enabling of the overcurrent protection functions is programmed with parameter setting:
on the LCD of the device the parameters I>1Ena, I>2Ena, I>3Ena and I2>>Ena are to be
changed to 1 (yes). On the external PC the Protect for Windows software shows „ ” or
„ ”.
The programming of the 16 output relays (K1…K16) of the DTD-EP factory configuration is
performed with software matrix (see below in Chapter „The digital software matrix”). The
versions DTD3V31 and DTD5 contain additional 8 (K17…K24) output relay, which can be
programmed using the PROTLOG equations (see below in chapter „Programming the
PROTLOG equations”). In both methods external control functions can be realised as well.
External PC External PC
I>1R I>1R
I>1S I>S
I>1T I>1T
I>1 [t] I>1 [t]
I>>2 I>2
I>>2 [t] I>2 [t]
I>2 I>3
I>2 [t] I>3 [t]
The latching of the status signals for can be programmed using an external PC, as it is
indicated in Fig.10:
Fig. 10 Latching the status signals of the overcurrent function, two voltage levels
(Protect for Windows).
Fig. 11 Latching the status signals of the overcurrent function, three voltage levels
(Protect for Windows).
On the LCD the same parameters are indicated with MxS prefix.
the phase overcurrents protection may not operate at the same time.
The zero sequence current (3Io) is calculated as the sum of the phase currents, and it is
measured on the independent zero sequence current input as well.
Ir+Is+It
3Io
The settings related to the earth-fault protection on the connected PC screen (Parameters of
other functions are masked):
The zero sequence overcurrent functions provide inputs for the PROTLOG equations. (The
outputs of the PROTLOG equations can be directed to relay outputs using the software
matrix.) :
PROTLOG Explanation
input
StIo> Starting of the low current setting stage of the earth fault protection (if it is
enabled, latching is possible)
StIo>t Trip command of the low current setting stage of the earth fault protection (if
it is enabled, latching is possible).
StIo>> Starting of the high current setting stage of the earth fault protection (if it is
enabled, latching is possible)
StIo>>t Trip command of the high current setting stage of the earth fault protection (if
it is enabled, latching is possible).
Using the software matrix the status signals of the individual protection functions or internal
status signals of the self-check function can be marshalled to output relays. The inputs of the
matrix are the status signals; the outputs are the relay contacts.
The most convenient way to program the matrix is the application of the Protect for Windows
software, running on an external PC. The logic connection between the OR connection of the
inputs and outputs is established by changing the appropriate matrix element from „-„ to „+”
by clicking with the mouse on the appropriate element.
The matrix can be programmed with the man-machine interface of the device as well. In this
case to the input signals (matrix rows) the binary sum of the code values of the outputs must
be assigned (see details in the document „EuroProt manual”).
Fig. 12 matrix of a device designed for transformers with two voltage levels
(Protect for Windows)
Fig. 13 matrix of a device designed for transformers with three voltage levels
(Protect for Windows)
The binary code values of the matrix columns (outputs) are listed in Fig. 14:
The matrix inputs (matrix-rows), which can be assigned to the outputs are listed in Fig. 15:
The optically isolated inputs can be used to process the status signals of the mechanical
transformer protections.
Fig. 17 The PROTLOG inputs for transformers with three voltage levels
The PROTLOG equations can be programmed with external PC only, using the „Protect for
Windows” operating program’s graphic editor possibility (The LCD of the device does not
support this programming).
The method of graphical equation editor is described in details in the document „EuroProt
manual”.
The factory configuration of the DTD-EP device is extended with 8 digital inputs. The first
seven inputs are connected to digital timers, and additionally the first four can be programmed
for drop-off delay or for starting delay, all others are pre-programmed for starting delay. The
first seven status signals serve as inputs for the software matrix, and all of them can be
applied as input variables of the PROTLOG equations. The „Protect for Windows” operating
program, running on an external PC supports the programming:
The „reset time delayed” means that the timer delays the drop-off of the status signal. This
can be changed to „oper. time delayed” which means that the status is set with time delay.
The LCD of the device displays these parameters as follows (they can be found in menu I>):
The latching programmed in the device can be acknowledged and reset by pressing the SW”
push-button on the front panel of the device. Input8 or Input7 optically isolated digital inputs
can be used for acknowledgement. The selection is with parameter setting:
The integrated disturbance recorder function records the status of the first four inputs only.
The program of the DTD-2 hardware configuration supports 16 output relays, the program of
the configuration for transformers with three voltage levels uses 24 output relay contacts. Out
of them the first 16 output relay contacts can be programmed with the software matrix (see
Chapter „The digital software matrix”). In the version for transformers with three voltage
levels additional 8 output relay contacts are assigned to the PROTLOG equation outputs (see
Chapter „The PROTLOG equations”).
The integrated disturbance recorder function records the status of the first four output relay
contacts only.
A dedicated window of the „Protect for Windows” operating program supports generating
manual close or open commands to the circuit breaker, but the DTD factory configurations do
not support circuit breaker control function.
The CPU module includes an integrated disturbance recorder function, which records sampled
analogue values and digital status signals. This function does not have own man-machine
interface, it can communicate with and external PC via fibre optic connection. The records
can be analysed on the screen of the external PC, they can be printed or sent to the central
engineering workstation for further evaluation.
Fig. 22. Recorded analogue signals (DTD-2 V3.xx and DTDZ-2+Udist.rec) V3.xx version).
Fig. 23 Recorded analogue signals (DTD-3V3.xx and DTD3 [5*3CT] V3.xx version).
The integrated disturbance recorder function has factory setting. There is only one possibility
for the user to influence the operation of the recorder: using the Protect for Windows program
logic equations can be edited to trigger the recording (see Chapter „PROTLOG equations”
and the document „EeuroProt manual”).
There are no free programmable timers in the DTD-EP factory configurations. If it is needed,
the timers dedicated to external input signals can be used (see Chapter „Application of the
digital inputs”).
If any of the protection functions generate a trip command, the seven LED signals on the front
panel enable quick information about the events. The assigned meaning of the seven LED-s is
as follows:
2.4.9 Latching
All matrix rows and the LED-s can be programmed for latching (for latching the „-„ character
must be changed for „+” by clicking with he mouse)
Fig. 28 Latching in devices designed for transformers with two voltage levels (PC).
Fig. 29 Latching in devices designed for transformers with three voltage levels (PC).
The messages are not displayed in the real event sequence, but they are arranged according to
the list of the table above.
The messages and the error signals of the self-check function are logged in the event log as
well, which can store up to 50 events. In the digital event sequence the events are logged with
1 ms time resolution; here 300 events can be stored. The events are not deleted by the
acknowledgement. The event log can be displayed with the LCD of the front panel, and the
contents of the event log and the content of the event sequence log can be evaluated using the
connected PC or by the SCADA system too. (See detailed description in the document
„EuroProt manual”).
The measured values (phase currents) and calculated values (difference of the currents,
restraint currents), the status information of the protective functions (starting, trip signals),
status of the digital inputs and output relays, accumulated counter values and additional
service information can be displayed in the On-line window of the connected PC (see the
following figure and details in the document „EuroProt manual”).
Fig. 32 The full On-line window for transformers with two voltage levels
Fig. 33 The full On-line window for transformers with three voltage levels
In the „Test” menu of the LCD sequencially the following information can be displayed:
Value Explanation
Idr Differentrial current in phase R
Ids Differentrial current in phase S
Idt Differentrial current in phase T
Isr Restraint current in phase R
Iss Restraint current in phase S
Ist Restraint current in phase T
I1r Primary current RMS value, side 1, phase R
I1s Primary current RMS value, side 1, phase S
I1t Primary current RMS value, side 1, phase T
I2r Primary current RMS value, side 2, phase R
I2s Primary current RMS value, side 2, phase S
I2t Primary current RMS value, side 2 phase T
3IoMeas. 3Io measured primary current RMS value
3IoCalc. 3Io calculated primary current RMS value
DTD 1.Status : Status information No. 1 (see details below)
DTD 2.Status : Status information No. 2 (see details below)
Fig. 34 On-line information of the LCD of the device for transformers with two voltage levels
The explanation of the status information (see last two items in Figure above) can be found in
the document „EPU-2002”. The displayed items are listed below.
The LCD of the EuroProt device displays the status information at the end of the „Test”
menu. As an example the first status word:
DTD-EP 1.status:
In this window the show that the binary values are refreshing. Character means activ
state of the status signal, means inactive state.
8.7.6.5.4.3.2.1.
The meaning of the status values is configured in the program of the device. They are listed in
the table below:
Further in the „Test” menu there are counter values. The four counters are listed in the tables
below:
The correct operation of the program system is supervised by the „Watch-dog” circuit.
Additionally there are continuous and cyclic self-check functions programmed in the factory
configuration. The self-check function detects internal errors of the hardware system.
In case of any detected errors the status is changing in the CHK input of the software matrix.
Optionally this variable integrates the error signals of the circuit breaker supervision system
as well. This status signal can be marshalled to the available output contacts by programming
the software matrix.
If the device is extended by a CB circuit supervision module, it can continuously monitor the
healthy state of the CB ON and OFF circuits. The method of supervision and its usage is
described in the document „EuroProt manual”.
The CB circuit supervision module includes three optically isolated inputs. One of them
connects the TRIP1 circuit, the second the TRIP2, the third the ON circuit.
Events Test/Chk
Version Param.
When selecting the Events menu, the last evaluated event is displayed on the LCD. The push-
button ↓ steps to the previous event (the push-button ↑ steps back). The following table lists
the possible events:
Message Explanation
Id>> tripped Trip command of the high-set differential protection
Id>R tripped Trip command of the differential protection in phase R
Id>S tripped Trip command of the differential protection in phase S
Id>T tripped Trip command of the differential protection in phase T
I>R1 started Overcurrent protection start, side 1, phase R
I>S1 started Overcurrent protection start, side 1, phase S
I>T1 started Overcurrent protection start, side 1, phase T
I>1[t] tripped Overcurrent protection trip, side 1
I>R2 started Overcurrent protection start, side 2, phase R
I>S2 started Overcurrent protection start, side 2, phase S
I>T2 started Overcurrent protection start, side 2, phase T
I>2[t] tripped Overcurrent protection trip, side 2
I>R3 started Overcurrent protection start, side 3, phase R
I>S3 started Overcurrent protection start, side 3, phase S
I>T3 started Overcurrent protection start, side 3, phase T
I>3[t] tripped Overcurrent protection trip, side 3
3Io>> started Zero sequence high set overcurrent protection start
3Io>>[t] tripped Zero sequence high set overcurrent protection trip
3Io> started Zero sequence overcurrent protection start
3Io> [t] tripped Zero sequence overcurrent protection trip
The short messages in the table are displayed with the exact time of the event. The following
table lists the possible events:
Event Explanation
ID>R Trip command of the differential protection in phase R
ID>S Trip command of the differential protection in phase S
ID>T Trip command of the differential protection in phase T
I>1R Overcurrent protection start, side 1, phase R
I>1S Overcurrent protection start, side 1, phase S
I>1T Overcurrent protection start, side 1, phase T
I>1[t] Overcurrent protection trip, side 1
I>>2R High set overcurrent protection start, side 2, phase R
I>>2S High set overcurrent protection start, side 2, phase S
I>>2T High set overcurrent protection start, side 2, phase T
I>>2[t] High set overcurrent protection trip, side 1
I>2R Overcurrent protection start, side 2, phase R
I>2S Overcurrent protection start, side 2, phase S
I>2T Overcurrent protection start, side 2, phase T
I>2[t] Overcurrent protection trip, side 2
INPUT1 INPUT1 status signal set
INPUT2 INPUT2 status signal set
INPUT3 INPUT3 status signal set
INPUT4 INPUT4 status signal set
INPUT5 INPUT5 status signal set
INPUT6 INPUT6 status signal set
INPUT7 INPUT7 status signal set
OUTPUTS DISABLED All outputs are disabled
K1 K1 output contact operated
K2 K2 output contact operated
K3 K3 output contact operated
K4 K4 output contact operated
K5 K5 output contact operated
K6 K6 output contact operated
K7 K7 output contact operated
K8 K8 output contact operated
AD error A/D error detected
2hBlock Second harmonic restraint operated
EEPROM ERROR EEPROM error detected
INPUT8/ACKN INPUT8 is set to external acknowledgement
Id>>R High set differential protection trip command, phase R
Id>>S High set differential protection trip command, phase S
Id>>T High set differential protection trip command, phase T
K9 K9 output contact operated
K10 K10 output contact operated
K11 K11 output contact operated
K12 K12 output contact operated
K13 K13 output contact operated
K14 K14 output contact operated
K15 K15 output contact operated
K16 K16 output contact operated
3Io>> Zero sequence high set vercurrent protection start
3Io>>[t] Zero sequence high set overcurrent protection trip
3Io> Zero sequence vercurrent protection start
3Io>[t] Zero sequence overcurrent protection trip
Fig. 35 Possible events as displayed in the „Events” menu of the LCD,
for transformers with two voltage levels
Event Explanation
ID>R Trip command of the differential protection in phase R
ID>S Trip command of the differential protection in phase S
ID>T Trip command of the differential protection in phase T
I>1R Overcurrent protection start, side 1, phase R
I>1S Overcurrent protection start, side 1, phase S
I>1T Overcurrent protection start, side 1, phase T
I>1[t] Overcurrent protection trip, side 1
I>2R Overcurrent protection start, side 2, phase R
I>2S Overcurrent protection start, side 2, phase S
I>2T Overcurrent protection start, side 2, phase T
I>2[t] Overcurrent protection trip, side 2
I>3R Overcurrent protection start, side 3, phase R
I>3S Overcurrent protection start, side 3, phase S
I>3T Overcurrent protection start, side 3, phase T
I>3[t] Overcurrent protection trip, side 3
INPUT1 INPUT1 status signal set
INPUT2 INPUT2 status signal set
INPUT3 INPUT3 status signal set
INPUT4 INPUT4 status signal set
INPUT5 INPUT5 status signal set
INPUT6 INPUT6 status signal set
INPUT7 INPUT7 status signal set
OUTPUTS DISABLED All outputs are disabled
K1 K1 output contact operated
K2 K2 output contact operated
K3 K3 output contact operated
K4 K4 output contact operated
K5 K5 output contact operated
K6 K6 output contact operated
K7 K7 output contact operated
K8 K8 output contact operated
AD error A/D error detected
2hBlock Second harmonic restraint operated
EEPROM ERROR EEPROM error detected
INPUT8/ACKN INPUT8 is set to external acknowledgement
Id>>R High set differential protection trip command, phase R
Id>>S High set differential protection trip command, phase S
Id>>T High set differential protection trip command, phase T
K9 K9 output contact operated
K10 K10 output contact operated
K11 K11 output contact operated
K12 K12 output contact operated
K13 K13 output contact operated
K14 K14 output contact operated
K15 K15 output contact operated
K16 K16 output contact operated
3Io>> Zero sequence high set vercurrent protection start
3Io>>[t] Zero sequence high set overcurrent protection trip
3Io> Zero sequence vercurrent protection start
3Io>[t] Zero sequence overcurrent protection trip
Fig. 36 Possible events as displayed in the „Events” menu of the LCD,
for transformers with three voltage levels
In this menu first the measured values are displayed in primary Amperes. The navigation is
supported by the arrows push-buttons (↓ and ↑).
The displayed measured and calculated values, the counters and status signals in the „Test”
menu is described in details in the Chapter „Information displayed on the LCD”.
In this menu the parameter setting can be checked without need of password input. New
setting in this menu is not possible, for setting enter „Param.” parameter setting menu.
In this menu the device type, the version of the configuration and the time of programming
can be seen:
The upper row shows the type of the factory configuration, the lower one displays the date of
the version and the version identifier.
The Param. (parameter setting) menu supports the parameter setting for the protection and
automatics functions, the communication and the software matrix. The user can enter this
menu with password only. The detailed description can be found in the document „EuroProt
manual”.
The list of the parameters, the setting ranges and the setting steps are in the function
descriptions above.
The parameter setting of the communication function is unified for all EuroProt devices. This
is described in the document „ EuroProt manual”.
3.1.7 Password
The password protection is unified for all EuroProt devices. This is described in the document
„ EuroProt manual”.
The operating software is the „Protect for Windows” program. This program and the files
related to the factory configuration (.bla, .gra or .blk, .grf, and additionally the .dok file) is
delivered with the device, and it is stored in the program memory of the CPU as well. Details
of the operation of this program pleas find in the document „ EuroProt manual”.
In the CPU module of the device a dedicated micro-controller is assigned to perform local
SCADA functions. This is supported by the large, high resolution graphic LCD, which is an
option of the device. The usage of the SCAD function is unified for all EuroProt devices. This
is described in the document „ EuroProt manual”.
The arrangement of the front panel, the module configuration, the „Protect for Windows” files
(.bla, .gra or .blk, .grf, and additionally .dok), and the connection arrangement depend on the
configuration. These files and additional documents are attached to the device.
6 Size
The sizes of the different configurations are given in the document „ EuroProt manual”. The
related information is attached to the device.
7 Ordering information
Ordering of the device is helped by filling the ordering sheet, which is the attachment of the
ordering. This includes the following information:
8 Information