0% found this document useful (0 votes)
98 views47 pages

Dtdo

This document describes a complex numerical protection device that realizes three-phase differential protection functions. The device can be applied to high speed and selective protection of high voltage transformers, generators and generator-transformer units. Several versions of the device are described for different applications with two or three voltage levels and additional functions.

Uploaded by

Moczik Attila
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views47 pages

Dtdo

This document describes a complex numerical protection device that realizes three-phase differential protection functions. The device can be applied to high speed and selective protection of high voltage transformers, generators and generator-transformer units. Several versions of the device are described for different applications with two or three voltage levels and additional functions.

Uploaded by

Moczik Attila
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 47

p:\petri\doku\europrot\pokagy\dtdio\dtd-io.

doc

PROTECT
Electronics Co. Ltd

EuroProt
complex protection
DTD-EP
Three-phase differential protection
Factory configuration
User’s manual
Versions:
DTD-2 V3.xx,
DTDZ-2+U (dist.rec.) V3.xx,
DTD-3 V3.xx,
DTD-3 [5*3CT] V3.xx
DTD-2 [Io] V3.xx,
Document ID: EX–13-15059-12

Budapest, May 2005.

Összeállította: Póka Gyula


DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Version history of the „User’s manual”:

Version Date Changes Editor


.10 16.03.2004. Application of the unified notation of the EuroProt Póka
devices
.11 01.05.2005. Minor corrections and new format Póka
.12 17.05.2005 Earth-fault protection function added Petri

Compiled by: Approved by: Date: Page: 2 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

CONTENTS
1 FIELD OF APPLICATION ............................................................................................ 5
1.1 THE MAIN CHARACTERISTICS OF THE COMPLEX DIFFERENTIAL PROTECTION ............... 6
1.2 THE MAIN FEATURES OF THE HARDWARE .................................................................... 7
2 THE OPERATION OF THE PROTECTIVE FUNCTIONS ...................................... 8
2.1 DIFFERENTIAL PROTECTION FUNCTIONS ...................................................................... 8
2.1.1 Realisation of the differential protection functions............................................ 8
2.1.2 The parameter setting....................................................................................... 15
2.1.3 Outputs of the differential protection function ................................................. 16
2.2 PHASE OVERCURRENT FUNCTION............................................................................... 17
2.2.1 Realisation of the phase overcurrent function ................................................. 17
2.2.2 Parameter setting ............................................................................................. 17
2.2.3 Outputs of the overcurrent functions................................................................ 19
2.3 EARTH FAULT PROTECTION ....................................................................................... 21
2.3.1 Realisation of the earth fault protection........................................................... 21
2.3.2 Parameters of the function ............................................................................... 21
2.3.3 Digital outputs of the function.......................................................................... 22
2.4 ADDITIONAL FUNCTIONS ........................................................................................... 23
2.4.1 The digital software matrix .............................................................................. 23
2.4.2 Programming PROTLOG equations ................................................................ 26
2.4.3 Application of the digital inputs ....................................................................... 29
2.4.4 Application of the relay outputs ....................................................................... 30
2.4.5 Circuit breaker control function....................................................................... 30
2.4.6 The integrated disturbance recorder function.................................................. 30
2.4.7 The free programmable timers ......................................................................... 33
2.4.8 The LED indication .......................................................................................... 33
2.4.9 Latching............................................................................................................ 34
2.4.10 Displayed messages.......................................................................................... 36
2.4.11 The displayed information (On-line window, summary).................................. 37
2.4.12 The self-check functions ................................................................................... 40
3 COMMUNICATION WITH THE DEVICE............................................................... 42
3.1 THE MENU SYSTEM .................................................................................................... 42
3.1.1 The „Events” menu .......................................................................................... 42
3.1.2 The „Test” menu .............................................................................................. 45
3.1.3 The „Chk” menu .............................................................................................. 45
3.1.4 The „Version” menu ........................................................................................ 45
3.1.5 The „Param.” menu ......................................................................................... 45
3.1.6 Parameters related to the communication ....................................................... 46
3.1.7 Password .......................................................................................................... 46
3.2 CONNECTING THE DEVICE TO AN EXTERNAL PC ........................................................ 46
4 THE OPTIONAL LOCAL SCADA FUNCTIONS..................................................... 46

5 ARRANGEMENT OF THE DTD-EP FACTORY CONFIGURATION ................. 46

Compiled by: Approved by: Date: Page: 3 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
6 SIZE................................................................................................................................. 46

7 ORDERING INFORMATION ..................................................................................... 47

8 INFORMATION ............................................................................................................ 47

Compiled by: Approved by: Date: Page: 4 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

1 Field of application
The EuroProt type complex protection in respect of hardware and software is a modular
device. The modules are assembled and configured according to the requirements, then the
functions are determined - within the hardware limitations - by the software. This document
describes the individual characteristics of a specific application: the factory configuration
DTD-EP complex differential protection. The general description of the members of the
EuroProt type complex protection family can be found in document “EuroProt complex
protection, hardware and software description and user’s manual” (further “EuroProt
manual”).

The DTD-EP complex numerical device realises three-phase differential protection function,
which can be applied to high speed and selective protection of high voltage transformers,
generators and generator-transformer units.

This manual describes several versions. The main information concerning these versions are
summarised in the Table below:

Version ID Date and version Explanation


DTD - 2 05.12.2003. V3.01 For transformers with two voltage levels
DTDZ – 2 16.03.2004. V3.01 For transformers with two voltage levels,
+U(dist.rec.) additional voltage inputs for disturbance
recording
DTD - 3 05.12.2003x. V3.01 For transformers with three voltage levels
DTD - 3 [5*3 CT] 19.09.2003. V3.00 For transformers with three voltage levels,
with connections to 5 CT-s
DTD – 2 [+Io] 09.06.2005. V3.11 For transformers with two voltage levels,
zero sequence OC extension

Table 1 The most common DTD versions

The device does not require matching intermediate current transformers. The turns ratio and
the phase shift due to the connection group of the transformers are matched by the software of
the differential protection.

The device includes separate overcurrent protection functions for all voltage levels of the
transformer.

As an option the included control (SCADA) functions can extend the device to the complex
field unit of the network.

Compiled by: Approved by: Date: Page: 5 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

1.1 The main characteristics of the complex differential protection


The DTD-EP complex differential protection is a member of the EuroProt device family of
PROTECTA Co. Ltd. It is a fully numerical type, microprocessor-based device.

The main characteristics of the DTD-EP complex differential protection are as follows:

The protection part of the device includes the following functions:


Three-phase differential protection function:
– Compares the sampled momentary values of the currents,
– The tripping characteristic is composed of three line sections, which can be set
independently,
– The function operates independently in all three phases,
– The restraint function is based on the average of the currents at each voltage levels,
– The function is not sensitive on transformer inrush current,
– It does not need additional matching auxiliary current transformers, the turns ratio of
the transformer and the phase shift due to the connection group of the transformer is
matched by the software,
– The faults are indicated in all three phases selectively,
– The operation time is about 20...25 ms,
– If the high current set differential protection stage operates, the reaction time is
about 10...15 ms.
The three-phase overcurrent function is provided for all voltage levels:
• In case of two voltage levels:
– The high voltage side is protected by a single-stage overcurrent
function,
– On the lower voltage side it is a two-stage function,
• In case of three voltage levels:
– On all three sides it is a single stage function,
Optional earth-fault overcurrent function:
– The low voltage side is protected by a two-stage zero sequent
overcurrent function,
The current settings and the time delay can be set individually for all sides,
The device is prepared to input the operating status signals of the mechanical
protection functions of the transformer,
The setting of all functions is independent of each other.

The main characteristics of the optional SCADA functions in the device can be as follows:

The SCADA functions are performed by a dedicated controller of the CPU module, or
optionally a separate SCADA module can be involved,
The optional high resolution graphic LCD can realise comprehensive local control and
supervisory functions,

Compiled by: Approved by: Date: Page: 6 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
The realised SCADA functions can be as follows:
• Control functions of the field:
– With local or remote operation,
– Interlocking functions,
– Generation of detailed status signals,
– Event recording function,
– Remote transmission of protection status signals (tele-protection),
– Communication with the processor-driven high resolution graphic
LCD,
• Transmission of the messages of the protection function to the SCADA system,
• Command inputs from the SCADA system and command processing,
• Command inputs from the local LCD and command processing.
Continuous and periodic self-supervision functions.
There are 16 output relays, driven by a software matrix.
The event log of the device can store up to 50 events, the event sequence recorder is
prepared for 300 digital events wit 1 ms time resolution.
The real-time clock of the device is supported by a battery supplied RAM. The clock can
be synchronised either by an external PC or by the SCADA system, and a special device
made by the Protecta Co. Ltd for synchronisation (Word Time Synchroniser GPS-OP) is
available as well.
The integrated disturbance recorder of the CPU module can store up to 11 records, the
total recording time is about 10 s.
The device can realise several measuring functions, based on the available analogue
signals.

1.2 The main features of the hardware


The DTD-EP complex digital differential protection device is a fully numerical, micro-
controller-based system. The functions are determined by the software within the limitations
of the hardware.

The device performs the protection and the SCADA functions of high voltage transformers.

The design and the operation of the EuroProt devices are described in the document
„EuroProt manual”.

The device can be operated by the integrated man-machine interface (2x16 character LCD an
6 push-buttons on the front panel), but the operation is more convenient using a connected
external PC, running the „Protect for Windows” operating program, developed by Protecta
Co. Ltd. Both possibilities are described in details in the document „EuroProt manual”.

The external communication can be performed via the RS 232 serial interface of the front
panel (isolated against 2 kV) or via fibre optic interface on the rear side of the device. The
application of these communication interfaces is described in the document „EuroProt
manual” as well.
Compiled by: Approved by: Date: Page: 7 / 47
Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2 The operation of the protective functions

The DTD-EP type complex numerical protection contains the following protection functions:

• Three-phase differential protection functions, operating


independently in all three phases,
• Three-phase overcurrent functions,
• Optional zero sequence overcurrent function,
• Processing the mechanical protections of the transformer.

The protection functions are fully independent from each other, and the setting is independent
too. The outputs are managed by the software matrix, each of them can be enabled or disabled
individually. By appropriate parameter setting, they can be programmed for latching.

The following chapters contain the description of the protection functions.

2.1 Differential protection functions


The basic function of the complex device is the three-phase differential protection.

2.1.1 Realisation of the differential protection functions

The precondition of the correct operation of the DTD-EP type differential protection function
is the correct matching of the currents, and the correct handling of the different transformer
connection groups.

Current matching

When setting the parameters of the device the primary rated currents of the main transformers
on all (two or three) sides of the transformer must be selected (AV1, AV2, and AV3 in
primary Amperes). These parameters are needed only to display the measured currents scaled
in primary values.

The matching of the currents in DTD-EP differential protection function is easy. An


appropriate Isetting1 value is to be defined, which must be calculated as transformed to all
voltage levels, and are to be expressed as percent of the rated currents of the main current
transformers (Iset1%, Iset2%, and Iset3%). This calculation assures the matching of the
normal operating currents. The calculation is based on the following formulas:

Compiled by: Approved by: Date: Page: 8 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

U1
Isetting1
Isetting1 U2 Isetting 2
Iset1% = 100% , Iset 2% = 100% = 100% ,
CT 1 CT 2 CT 2
and:
U1
Isetting
U3 Isetting 3
Iset 3% = 100% = 100%
CT 3 CT 3

Where U1, U2 and U3 are the rated voltage values of the transformer (in case of regulating
coils these are the central values).

The Isetting1 defined value is free to choose. It is usual to be selected as the rated current of
the transformer on the primary side Isetting1 = Itrn1. This Isetting1 will be the reference
value for displaying the Id % differential current and for the Is % restraint current (when it is
considered on the secondary side, it is Isetting2, etc.).

Matching the phase shift of the transformer

The matching of the phase shift of the transformer is solved by a simple parameter setting,
which is the code value of the transformer’s connection group. (e.g. Yd11). In a differential
protection for a transformer with two voltage levels the code values are listed in Table 2
(parameter: Setting code: [0-11]), and that for a transformer with three voltage levels in Table
3 (parameter: Setting code: [0-71]).

Compiled by: Approved by: Date: Page: 9 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Setting code Connection Vectors Phase shift


group =α
0 Dd0 U1 U2 00

1 Yy0 U1 U2 00

2 Dy1 U1 U2 300

3 Yd1 U1 U2 300

4 Dy5 U1 U 1500
2

5 Yd5 U1 1500
U2
6 Dd6 U1 1800
U2
7 Yy6 U1 1800
U2
8 Dy7 U2 U1 2100 (-1500)

9 Yd7 U1 2100 (-1500)


U2
10 Dy11 U2 U1 3300 (-300)

11 Yd11 U2 U1 3300 (-300)

α

The meaning of phase shift is: U2 = U1.e .

The polarity of the current transformers is explained in the following Figure:

CT1 CT2
K L L K
U1 U2
k l l k

to the protection
Side 1 Side 2
Connection

As the Figure indicates, the connections of the CT marked with same letters are located near
to the transformer

Table 2. Phase shift code values for a transformer with two voltage levels

Compiled by: Approved by: Date: Page: 10 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Connection Setting code Connection Setting code


group group
Dy1y1 0 Yy0y0 36
Dy1y5 1 Yy0y6 37
Dy1y7 2 Yy0d1 38
Dy1y11 3 Yy0d5 39
Dy1d0 4 Yy0d7 40
Dy1d6 5 Yy0d11 41
Dy5y1 6 Yy6y0 42
Dy5y5 7 Yy6y6 43
Dy5y7 8 Yy6d1 44
Dy5y11 9 Yy6d5 45
Dy5d0 10 Yy6d7 46
Dy5d6 11 Yy6d11 47
Dy7y1 12 Yd1y0 48
Dy7y5 13 Yd1y6 49
Dy7y7 14 Yd1d1 50
Dy7y11 15 Yd1d5 51
Dy7d0 16 Yd1d7 52
Dy7d6 17 Yd1d11 53
Dy11y1 18 Yd5y0 54
Dy11y5 19 Yd5y6 55
Dy11y7 20 Yd5d1 56
Dy11y11 21 Yd5d5 57
Dy11d0 22 Yd5d7 58
Dy11d6 23 Yd5d11 59
Dd0y1 24 Yd7y0 60
Dd0y5 25 Yd7y6 61
Dd0y7 26 Yd7d1 62
Dd0y11 27 Yd7d5 63
Dd0d0 28 Yd7d7 64
Dd0d6 29 Yd7d11 65
Dd6y1 30 Yd11y0 66
Dd6y5 31 Yd11y6 67
Dd6y7 32 Yd11d1 68
Dd6y11 33 Yd11d5 69
Dd6d0 34 Yd11d7 70
Dd6d6 35 Yd11d11 71

The polarity of the current transformers is explained in the following Figure:


CT2
CT1 L K
U2
l k
K L
U1 protection CT3
k l
L K
protection
U3
l k

protection
Table 3. Phase shift code values for a transformer with three voltage levels
Compiled by: Approved by: Date: Page: 11 / 47
Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

The differential protection function detects internal fault based on sampled phase current
comparison received from all sides of the transformer. “Rectified average” values are
calculated for a half period of the network frequency, and then the evaluation is performed in
all sampling time steps, in each millisecond. If significant difference is detected in 15
consecutive steps, this means internal fault, and trip command is generated.

In sampled current comparison the regulating range of the transformer and the errors of the
current transformers must be considered as well. This is solved by a „percentage” restraint
characteristic. If the point in the co-ordinate system defined by the Id% differential current and
the IS% restraint current is located in the upper part of the figure below, the protection
operates, and after 15 consecutive steps with the same decision it generates a trip command.

Diff.
current
áId %)

400

300
f3=200%

OPERATION f3=500% f3=1000%


200
f2=50%

f2=20%
100
f1=50% f1=20%
NO OPERATION
50
20 Restraint
IS % current
0 100 200 300 400 500 600

Fig. 1.Differential protection tripping characteristics

The IS % „Restraint current” and the Id % difference current is explained with the following
formulas.

Compiled by: Approved by: Date: Page: 12 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

The IS % „Restraint current” in transformers with two voltage levels is calculated by:

I1 I2
100% 100%
CT1 + CT 2
I1 I2 Iset1 Iset2
+
Isetting1 Isetting2
IS % = 100% = 100%
2 2

The Id % differential current is in transformers with two voltage levels:

 I1 I2 
 I1 I2   100% 100% 
I d % =  +  100% =  CT1 + CT 2  100%
 Isetting1 Isetting2   Iset1 Iset2 
 
 

The IS % „Restraint current” in transformers with three voltage levels is calculated by:

I1 I2 I3
100% 100% 100%
CT1 + CT 2 + CT 3
I1 I2 I3 Iset1 Iset2 Iset3
+ +
Isetting1 Isetting2 Isetting3
IS % = 100% = 100%
2 2

The Id % differential current is in transformers with three voltage levels:

 I1 I2 I3 
 I1 I3   100% 100% 100% 
I2
I d % =  + +  100% =  CT1 + CT 2 + CT3  100%
 Isetting1 Isetting2 Isetting3   Iset1 Iset2 Iset3 
 
 

Compiled by: Approved by: Date: Page: 13 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

The individual sections of the tripping characteristics are explained as follows:

f1% This is the setting value of the horizontal section of the tripping characteristic, which
defines the basic sensitivity of the differential function. The value is expressed as
percent of the Iset1 current setting value. The differential protection can operate if: Id% >f1%

f2% This is the slope setting of the second section of the differential characteristic. This slope
is needed mainly because of the voltage regulation range of the transformer. The
differential function is balanced in the medium position of the tap-changer, any other position
generates a differential current. The second section of the characteristic starts in the origin,
and the section above the first section is valid only. The differential protection operates if the
Id % differential current is above the percent value defined by the Is % current and the f2
slope setting. The differential protection can operate if: Id% >f2%/100*IS%.

f3% The third section of the characteristic is needed because the possible saturation of the
main current transformers. The slope of this section is constant: tgα=2. The starting
point of this section on the vertical axis of the co-ordinate system is a negative value defined
by f3, it is valid only above the second section of the characteristic. The differential protection
can operate if the differential current is above this line too: Id% > (2*IS % – f3%).

f2h% To prevent false tripping because of the high inrush current of the transformer, the
differential protection is provided wit a second harmonic restraint. The second
harmonic restraint prevents the operation of the differential protection, if the second harmonic
content of the differential current is above the f2h setting, which is expressed as %. This
means: Id2h% >f2h% (Id2h% is the percentage value of the second harmonic content in
differential current, related to the basic harmonic).

Id>>% There is a possibility to set a high current value of the differential current, above
which the function generates an immediate trip command without restraint
calculation. The setting value is referred to the Isetting1 value, and it is expressed in %. If this
stage operates, the differential protection function generates a trip command within 15...20
ms.

If the differential current is above the characteristic lines, the normal operating time of the
differential protection function is about 20 ... 25 ms, (if the high current setting stage operates,
the time delay is about 10 … 15 ms.

Compiled by: Approved by: Date: Page: 14 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.1.2 The parameter setting


The differential protection function – according to the explanation above – needs setting the
following parameters, as it is shown in Fig. 2.(Fig.2 is the snapshot of the Parameters Window
of the Protect for Windows software):

Fig. 2 Parameters of the differential protection for transformers with two voltage levels
(Protect for Windows).

Fig. 3 Parameters of the differential protection for transformers with three voltage levels
(Protect for Windows).

Compiled by: Approved by: Date: Page: 15 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

LCD parameter name: Min Max Step


Iset1: [%] 20 270 2
Iset2: [%] 20 270 2
Iset3: [%] ◊ 20 270 2
Id>>: [%] 800 2500 50
IdEna: +=yes + -
Phase shift code * 0 * 11 * 1
f1: [%] 20 50 2
f2: [%] 20 50 2
f3: [%] 200 2000 10
f2h: [%] 8 30 2
◊ Only for transformers with three voltage levels
* Setting range 0…71 for transformers with three voltage levels
Fig. 4 Parameters of the differential protection for transformers (LCD).

To enable or disable the differential protection function a special parameter is assigned: (On
the PC: Id>, Id>> stages, enabled/disabled, on the LCD: IdEna +/-).

2.1.3 Outputs of the differential protection function

The assignment of the 16 (K1…K16) output relays of the device is made using the software
matrix (see below, in the Chapter „The digital software matrix” ). In the versions DTD-3
V3.xx and DTD-3 [5*3AV] V3.xx additional 8 (K17…K24) output relays can be
programmed using the PROTLOG equations (see below in the Chapter „Programming the
PROTLOG equations”).

The row of the differential protection function as the software matrix input is:
On the PC screen: Id>,
On the LCD: Mx Id>
For the PROTLOG programing the input variable received from the differential protection
function is:
Id>, (with latching: *Id>)
The latching of the function can be programmed on the LCD with the following parameter:
„MxSId”
On the PC the latching is set as the following Figure shows:

Fig 5 Programming for latching

Compiled by: Approved by: Date: Page: 16 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.2 Phase overcurrent function


In the DTD-EP factory configuration the differential protection function is extended with
phase overcurrent functions as well.

In the devices designed for transformers with two voltage levels (DTD-2 V3.xx, DTDZ-
2+U(dist.rec) V3.xx) the factory configurations realise one stage overcurrent function for the
high voltage side, and two-stage definite time overcurrent protection function on the lover
voltage side.

In the devices designed for transformers with three voltage levels (DTD-3 V3.xx, DTD-3
[5*3CT] V3.xx) the factory configurations realise one stage overcurrent function for the high
voltage side, and for both medium voltage sides as well

2.2.1 Realisation of the phase overcurrent function

The algorithm calculates with numerical Fourier analysis the basic harmonic component of
the current, and this is compared with the setting value. If the basic harmonic component is
above the setting, the function starts the time counter, the expiry of which generates a trip
command.

The measurement and the comparison are performed independently in all three phases, the
timer however is common for the three phases, and the trip command is common too.

2.2.2 Parameter setting

The phase overcurrent function needs the following parameter setting, as it is shown on Fig.
6. and 7. The Figures are PC screen snap-shots from the Protect for Windows operating
software:

Fig. 6 Parameters of the overcurrent protection function for transformers with two voltage
levels (Protect for Windows)

Compiled by: Approved by: Date: Page: 17 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Fig. 7 Parameters of the overcurrent protection function for transformers with three voltage
levels (Protect for Windows)

LCD parameter name: Min Max Step


CT1: [A] 50 5000 25
I1>: [%] 30 1500 5
I>1Ena: +=yes + -
t[I>1] [ms] 0 64000 10
CT2: [A] 50 5000 25
I2>: [%] 30 1500 5
I>2Ena: +=yes + -
t[I>2] [ms] 0 64000 10
I2>>: [%] 30 1500 5
I>>2Ena: +=yes + -
t[I>>2] [ms] 0 64000 10
Fig. 8 Parameters of the overcurrent protection function for transformers with two voltage
levels (LCD)

LCD parameter name: Min Max Step


CT1: [A] 50 5000 25
I1>: [%] 30 1500 5
I>1Ena: +=yes + -
t[I>1] [ms] 0 64000 10
CT 2: [A] 50 5000 25
I2>: [%] 30 1500 5
I>2Ena: += yes + -
t[I>2] [ms] 0 64000 10
CT 3: [A] 50 5000 25
I3>: [%] 30 1500 5
I>3Ena: += yes + -
t[I>3] [ms] 0 64000 10
Fig. 9 Parameters of the overcurrent protection function for transformers with three voltage
levels (LCD)

Compiled by: Approved by: Date: Page: 18 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

The enabling of the overcurrent protection functions is programmed with parameter setting:
on the LCD of the device the parameters I>1Ena, I>2Ena, I>3Ena and I2>>Ena are to be
changed to 1 (yes). On the external PC the Protect for Windows software shows „ ” or
„ ”.

The setting of the parameters does not need any explanations.

2.2.3 Outputs of the overcurrent functions

The programming of the 16 output relays (K1…K16) of the DTD-EP factory configuration is
performed with software matrix (see below in Chapter „The digital software matrix”). The
versions DTD3V31 and DTD5 contain additional 8 (K17…K24) output relay, which can be
programmed using the PROTLOG equations (see below in chapter „Programming the
PROTLOG equations”). In both methods external control functions can be realised as well.

Mátrix rows (inputs of the matrix), related to the overcurrent functions:

For two voltage levels: For three voltage levels:

External PC LCD External PC LCD


I>1R = Mx I>1R = I>1R = Mx I>1R =
I>1S = Mx I>1S = I>1S = Mx I>1S =
I>1T = Mx I>1T = I>1T = Mx I>1T =
I>1 [t] = Mx I>1 t = I>1 [t] = Mx I>1 t =
I>>2 = Mx I>>2 = I>2 = Mx I>2 =
I>>2 [t] = Mx I>>2 t = I>2 [t] = Mx I>2 t =
I>2 = Mx I>2 = I>3 = Mx I>3 =
I>2 [t] = Mx I>2 t = I>3 [t] = Mx I>3 t =

PROTLOG equation input variables, related to the overcurrent functions:

For two voltage levels: For three voltage levels:

External PC External PC
I>1R I>1R
I>1S I>S
I>1T I>1T
I>1 [t] I>1 [t]
I>>2 I>2
I>>2 [t] I>2 [t]
I>2 I>3
I>2 [t] I>3 [t]

The variables are repeated wit *, which mean latching.

Compiled by: Approved by: Date: Page: 19 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

The latching of the status signals for can be programmed using an external PC, as it is
indicated in Fig.10:

Fig. 10 Latching the status signals of the overcurrent function, two voltage levels
(Protect for Windows).

Fig. 11 Latching the status signals of the overcurrent function, three voltage levels
(Protect for Windows).

On the LCD the same parameters are indicated with MxS prefix.

Compiled by: Approved by: Date: Page: 20 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.3 Earth fault protection


One of the main functions of the complex motor protection is the earth fault protection. This
function measures the zero sequence current partly as the sum of the three phase current,
partly the zero sequence current is measured on an independent input. The earth fault
protection is a two-stage definite time zero sequence overcurrent protection. The low current
setting stage uses the zero sequence current measured on the dedicated current input, the
decision of the high current setting stage is based on the sum of the three phase currents. The
operation of the earth-fault protection is similar to that of the phase overcurrent protection, but
beside the enabling the operation of the low current setting stage has an additional constraint
as well:

the phase overcurrents protection may not operate at the same time.

2.3.1 Realisation of the earth fault protection


In the DTD-EP factory configuration the zero sequence overcurrent function operates
independently of the phase overcurrent protection. The algorithm determines the basic
harmonic of the zero sequence current (both for the current measured on the dedicated input
and for the sum of the phase currents) and these values are compared with the settings.

The zero sequence current (3Io) is calculated as the sum of the phase currents, and it is
measured on the independent zero sequence current input as well.

Ir+Is+It
3Io

2.3.2 Parameters of the function

The function needs setting for the following parameters:

LCD Min Max Step Explanation


CTPrN[CTdevN] A 15 15000 5 Primary rated current of the current
transformers (needed for displaying the
measured current only)
3Io>/In[CtoProt]=% 10 140 1 Current setting of the low current stage related
to the zero sequence CT rated current in
percent
t[3Io>]= ms 0 64000 10 Delay time of the low current setting stage
independent of the current value
3Io> enable: - + Enabling of the zero sequence overcurrent
(+=ena.) function low current setting stage
(+= enabled)

Compiled by: Approved by: Date: Page: 21 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

3Io>>/In[CT2]:% 30 1500 Current setting of the high current stage


5
related to the phase CT’s rated current in
percent
t[3Io>>]= ms 0 64000 10 Delay time of the high current setting stage
independent of the current value
3Io>> enable: - + Enabling of the zero sequence overcurrent
(+=ena.) function high current setting stage (+=
enabled)

The settings related to the earth-fault protection on the connected PC screen (Parameters of
other functions are masked):

Fig. 2-7 Parameter setting/2


2.3.3 Digital outputs of the function

The zero sequence overcurrent functions provide inputs for the PROTLOG equations. (The
outputs of the PROTLOG equations can be directed to relay outputs using the software
matrix.) :

PROTLOG Explanation
input
StIo> Starting of the low current setting stage of the earth fault protection (if it is
enabled, latching is possible)
StIo>t Trip command of the low current setting stage of the earth fault protection (if
it is enabled, latching is possible).
StIo>> Starting of the high current setting stage of the earth fault protection (if it is
enabled, latching is possible)
StIo>>t Trip command of the high current setting stage of the earth fault protection (if
it is enabled, latching is possible).

Compiled by: Approved by: Date: Page: 22 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4 Additional functions

2.4.1 The digital software matrix

Using the software matrix the status signals of the individual protection functions or internal
status signals of the self-check function can be marshalled to output relays. The inputs of the
matrix are the status signals; the outputs are the relay contacts.

The most convenient way to program the matrix is the application of the Protect for Windows
software, running on an external PC. The logic connection between the OR connection of the
inputs and outputs is established by changing the appropriate matrix element from „-„ to „+”
by clicking with the mouse on the appropriate element.

The matrix can be programmed with the man-machine interface of the device as well. In this
case to the input signals (matrix rows) the binary sum of the code values of the outputs must
be assigned (see details in the document „EuroProt manual”).

Fig. 12 matrix of a device designed for transformers with two voltage levels
(Protect for Windows)

Compiled by: Approved by: Date: Page: 23 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Fig. 13 matrix of a device designed for transformers with three voltage levels
(Protect for Windows)

The binary code values of the matrix columns (outputs) are listed in Fig. 14:

Matrix-column element: Code value:


0
K1…K3 output relays 2 = 1h
K4 output relay 21 = 2h
K5 output relay 22 = 4h
K6 output relay 23 = 8h
K7 output relay 24 = 10h
K8 output relay 25 = 20h
K9 output relay 26 = 40h
K10 output relay 27 = 80h
K11 output relay 28 = 100h
K12 output relay 29 = 200h
K13 output relay 210 = 400h
K14 output relay 211 = 800h
K15 output relay 212 = 1000h
K16 output relay 213 = 2000h
TRIP message 214 = 4000h
Fig.14 The binary code values of the matrix columns (LCD).

Compiled by: Approved by: Date: Page: 24 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

The matrix inputs (matrix-rows), which can be assigned to the outputs are listed in Fig. 15:

Matrix-row element: Explanation:


Mx Id> Trip command of the differential protection function
Mx I>1R Starting of the overcurrent function in phase R
Mx I>1S Starting of the overcurrent function in phase S
Mx I>1T Starting of the overcurrent function in phase T
Mx I>1 t Trip command of the overcurrent function
Mx I>>2 or I>2 * Starting of the overcurrent function
Mx I>>2 t or I>2 t * Trip command of the overcurrent function
Mx I>2 or I>3 * Starting of the overcurrent function
Mx I>2 t or y I>3 t * Trip command of the overcurrent function
Mx IN1 Status signal of digital input No. 1 **
Mx IN2 Status signal of digital input No. 2 **
Mx IN3 Status signal of digital input No. 3 **
Mx IN4 Status signal of digital input No. 4 **
Mx IN5 Status signal of digital input No 5 **.
Mx IN6 Status signal of digital input No. 6 **
Mx IN7 Status signal of digital input No. 7 **
Mx CHK Fault detection of the self check function
Mx Equ1 Output of the Protlog equation No.1
Mx Equ2 Output of the Protlog equation No.2
Mx Equ3 Output of the Protlog equation No.3
Mx Equ4 Output of the Protlog equation No.4

* for transformers with three voltage levels


** See chapter „Application of the digital inputs
Fig. 15 The matrix row elements (LCD).

Compiled by: Approved by: Date: Page: 25 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4.2 Programming PROTLOG equations


The available status signals can be used to program logic equations, the result of which can be
used freely.

2.4.2.1 Inputs of the PROTLOG equations


The available status signals are listed in Fig.16 and Fig.17.
Input identifier: Explanation:
Id Trip command of the differential protection function
I>1R Starting of the overcurrent function in phase R
I>1S Starting of the overcurrent function in phase S
I>1T Starting of the overcurrent function in phase T
I>1 [t] Trip command of the overcurrent function on the primary side of the
transformer
I>>2 Starting of the high current setting overcurrent function on the secondary
side of the transformer
I>>2 [t] Trip command of the high current setting overcurrent function on the
secondary side of the transformer
I>2 Starting of the overcurrent function on the secondary side of the
transformer
I>2 [t] Trip command of the overcurrent function on the secondary side of the
transformer
Input1 [t] Status signal of digital input No. 1 with time delay
Input2 [t] Status signal of digital input No. 2 with time delay
Input3 [t] Status signal of digital input No. 3 with time delay
Input4 [t] Status signal of digital input No. 4 with time delay
Input5 [t] Status signal of digital input No. 5 with time delay
Input6 [t] Status signal of digital input No. 6 with time delay
Input7 [t] Status signal of digital input No. 7 with time delay
Input8 Status signal of digital input No. 8
2. harm. block Second harmonic blocking in the differential protection function
SW1 SW1 push-button (acknowledgement)
SW2 SW2 push-button (All trip commands disabled)
StIo> Starting of the low current setting stage of the earth fault protection
StIo>t Trip command of the low current setting stage of the earth fault
protection
StIo>> Starting of the high current setting stage of the earth fault protection
StIo>>t Trip command of the high current setting stage of the earth fault
protection
* All the status signals are repeated with *. This means latching:
Fig. 16 The PROTLOG inputs for transformers with two voltage levels

Compiled by: Approved by: Date: Page: 26 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Input identifier: Explanation:


Id> Trip command of the differential protection function
I>1R Starting of the overcurrent function in phase R
I>1S Starting of the overcurrent function in phase S
I>1T Starting of the overcurrent function in phase T
I>1 [t] Trip command of the overcurrent function on the primary side of the
transformer
I>2 Starting of the overcurrent function on the secondary side of the
transformer
I>2 [t] Trip command of the overcurrent function on the secondary side of the
transformer
I>3 Starting of the overcurrent function on the tertiary side of the
transformer
I>3 [t] Trip command of the overcurrent function on the tertiary side of the
transformer
Input1 [t] Status signal of digital input No. 1 with time delay
Input2 [t] Status signal of digital input No. 2 with time delay
Input3 [t] Status signal of digital input No. 3 with time delay
Input4 [t] Status signal of digital input No. 4 with time delay
Input5 [t] Status signal of digital input No. 5 with time delay
Input6 [t] Status signal of digital input No. 6 with time delay
Input7 [t] Status signal of digital input No. 7 with time delay
Input8 Status signal of digital input No. 8
2. harm. block Second harmonic blocking in the differential protection function
SW1 SW1 push-button (acknowledgement)
SW2 SW2 push-button (All trip commands disabled)
StIo> Starting of the low current setting stage of the earth fault protection
StIo>t Trip command of the low current setting stage of the earth fault
protection
StIo>> Starting of the high current setting stage of the earth fault protection
StIo>>t Trip command of the high current setting stage of the earth fault
protection
* All the status signals are repeated with *. This means latching:

The optically isolated inputs can be used to process the status signals of the mechanical
transformer protections.

Fig. 17 The PROTLOG inputs for transformers with three voltage levels

Compiled by: Approved by: Date: Page: 27 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4.2.2 Outputs of the PROTLOG equations

Output name Explanation


Dist.rec.level trig. Starting the disturbance recorder with signal level
Dist.rec.edge trig. Starting the disturbance recorder with signal rising edge
Us.Def.Equ 1 Equation defined by the user, directed to the software matrix
Us.Def.Equ 2 Equation defined by the user, directed to the software matrix
Us.Def.Equ 3 Equation defined by the user, directed to the software matrix
Us.Def.Equ 4 Equation defined by the user, directed to the software matrix
Fig. 18 PROTLOG equations for transformers with two voltage levels

Output name Explanation


Dist.rec.level trig. Starting the disturbance recorder with signal level
Dist.rec.edge trig. Starting the disturbance recorder with signal rising edge
K17 K17 output relay contact
K18 K18 output relay contact
K19 K19 output relay contact
K20 K20 output relay contact
K21 K21 output relay contact
K22 K22 output relay contact
K23 K23 output relay contact
K24 K24 output relay contact
Us.Def.Equ 1 Equation defined by the user, directed to the software matrix
Us.Def.Equ 2 Equation defined by the user, directed to the software matrix
Us.Def.Equ 3 Equation defined by the user, directed to the software matrix
Us.Def.Equ 4 Equation defined by the user, directed to the software matrix
Fig. 19 PROTLOG equations for transformers with three voltage levels

2.4.2.3 Programming the PROTLOG equations

The PROTLOG equations can be programmed with external PC only, using the „Protect for
Windows” operating program’s graphic editor possibility (The LCD of the device does not
support this programming).

The method of graphical equation editor is described in details in the document „EuroProt
manual”.

Compiled by: Approved by: Date: Page: 28 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4.3 Application of the digital inputs

The factory configuration of the DTD-EP device is extended with 8 digital inputs. The first
seven inputs are connected to digital timers, and additionally the first four can be programmed
for drop-off delay or for starting delay, all others are pre-programmed for starting delay. The
first seven status signals serve as inputs for the software matrix, and all of them can be
applied as input variables of the PROTLOG equations. The „Protect for Windows” operating
program, running on an external PC supports the programming:

Fig. 20 Parameters of the input timers (Protect for Windows).

The „reset time delayed” means that the timer delays the drop-off of the status signal. This
can be changed to „oper. time delayed” which means that the status is set with time delay.

The LCD of the device displays these parameters as follows (they can be found in menu I>):

LCD parameter name Min Max Step


t[IN1]: [ms] 0 64000 10
tIN1 S/D: (+=start.) 1 0
t[IN2]: [ms] 0 64000 10
tIN2 S/D: (+=start.) 1 0
t[IN3]: [ms] 0 64000 10
tIN3 S/D: (+=start.) 1 0
t[IN4]: [ms] 0 64000 10
tIN4 S/D: (+=start.) 1 0
t[IN5]: [ms] 0 64000 10
t[IN6]: [ms] 0 64000 10
t[IN7]: [ms] 0 64000 10
Fig. 21 Parameters of the input timers (LCD)

The latching programmed in the device can be acknowledged and reset by pressing the SW”
push-button on the front panel of the device. Input8 or Input7 optically isolated digital inputs
can be used for acknowledgement. The selection is with parameter setting:

On the PC: Acknowledgement: SW2 or Input8 (Toggle: SW2 or Input7)


LCD-n: IN7/Ackn.

The integrated disturbance recorder function records the status of the first four inputs only.

Compiled by: Approved by: Date: Page: 29 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4.4 Application of the relay outputs

The program of the DTD-2 hardware configuration supports 16 output relays, the program of
the configuration for transformers with three voltage levels uses 24 output relay contacts. Out
of them the first 16 output relay contacts can be programmed with the software matrix (see
Chapter „The digital software matrix”). In the version for transformers with three voltage
levels additional 8 output relay contacts are assigned to the PROTLOG equation outputs (see
Chapter „The PROTLOG equations”).

The integrated disturbance recorder function records the status of the first four output relay
contacts only.

2.4.5 Circuit breaker control function

A dedicated window of the „Protect for Windows” operating program supports generating
manual close or open commands to the circuit breaker, but the DTD factory configurations do
not support circuit breaker control function.

2.4.6 The integrated disturbance recorder function

The CPU module includes an integrated disturbance recorder function, which records sampled
analogue values and digital status signals. This function does not have own man-machine
interface, it can communicate with and external PC via fibre optic connection. The records
can be analysed on the screen of the external PC, they can be printed or sent to the central
engineering workstation for further evaluation.

The sampled analogue signals transmitted for recording are:

Recorded signal: Explanation:


I1r R phase current, primary side
I2r R phase current, secondary side
I1s S phase current, primary side
I2s S phase current, secondary side
I1t T phase current, primary side
I2t T phase current, secondary side
Ur * or 3Io meas. R phase voltage *
Us *or - S phase voltage *
Ut * or - T phase voltage *

* only in DTDZ-2+U (dist.rec.) version

Fig. 22. Recorded analogue signals (DTD-2 V3.xx and DTDZ-2+Udist.rec) V3.xx version).

Compiled by: Approved by: Date: Page: 30 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Recorded signal: Explanation:


I1r R phase current 1. side
I2r R phase current 2. side
I3r R phase current 3. side
I1s S phase current 1. side
I2s S phase current 2. side
I3s S phase current 3. side
I1t T phase current 1. side
I2t T phase current 2. side
I3t T phase current 3. side

Fig. 23 Recorded analogue signals (DTD-3V3.xx and DTD3 [5*3CT] V3.xx version).

Compiled by: Approved by: Date: Page: 31 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
The digital status signals, recorded in the disturbance recorder:

Recorded signal Explanation


Id>R Trip command of the differential protection function in phase R
Id>S Trip command of the differential protection function in phase S
Id>T Trip command of the differential protection function in phase T
Id>>R Trip command of the high set differential protection function in phase R
Id>>S Trip command of the high set differential protection function in phase S
Id>>T Trip command of the high set differential protection function in phase T
I>1R Phase overcurrent protection function start, side 1, phase R
I>1S Phase overcurrent protection function start, side 1, phase S
I>1T Phase overcurrent protection function start, side 1, phase T
I>>2R High set phase overcurrent protection function start, side 2, phase R
I>>2S High set phase overcurrent protection function start, side 2, phase S
I>>2T High set phase overcurrent protection function start, side 2, phase T
I>2R Phase overcurrent protection function start, side 2, phase R
I>2S Phase overcurrent protection function start, side 2, phase S
I>2T Phase overcurrent protection function start, side 2, phase T
3Io>> Zero sequence high set overcurrent protection function start
3Io> Zero sequence low set overcurrent protection function start
Fig. 24 Recorded status signals (DTD-2 V3.xx and DTDZ-2+U(dist.rec) V3.xx version)

Recorded signal Explanation


Id>R Trip command of the differential protection function in phase R
Id>S Trip command of the differential protection function in phase S
Id>T Trip command of the differential protection function in phase T
Id>>R Trip command of the high set differential protection function in phase R
Id>>S Trip command of the high set differential protection function in phase S
Id>>T Trip command of the high set differential protection function in phase T
I>1R Phase overcurrent protection function start, side 1, phase R
I>1S Phase overcurrent protection function start, side 1, phase S
I>1T Phase overcurrent protection function start, side 1, phase T
I>2R Phase overcurrent protection function start, side 2, phase R
I>2S Phase overcurrent protection function start, side 2, phase S
I>2T Phase overcurrent protection function start, side 2, phase T
I>3R Phase overcurrent protection function start, side 3, phase R
I>3S Phase overcurrent protection function start, side 3, phase S
I>3T Phase overcurrent protection function start, side 3, phase T
3Io>> Zero sequence high set overcurrent protection function start
3Io> Zero sequence low set overcurrent protection function start
Fig. 25 Recorded digital status signals (DTD-3 V3.xx and DTD3 [5*3CT] V3.xx version)

The integrated disturbance recorder function has factory setting. There is only one possibility
for the user to influence the operation of the recorder: using the Protect for Windows program
logic equations can be edited to trigger the recording (see Chapter „PROTLOG equations”
and the document „EeuroProt manual”).

Compiled by: Approved by: Date: Page: 32 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
As an option an additional disturbance recorder module can be ordered in the device. For this
module the triggering can be configured using the external PC, the timer settings can be
changed, (pre-fault time, etc.), the name of the individual channels can be edited, etc. The
record of this disturbance recorder module can be accessed, analysed or printed using the
external PC.

2.4.7 The free programmable timers

There are no free programmable timers in the DTD-EP factory configurations. If it is needed,
the timers dedicated to external input signals can be used (see Chapter „Application of the
digital inputs”).

2.4.8 The LED indication

If any of the protection functions generate a trip command, the seven LED signals on the front
panel enable quick information about the events. The assigned meaning of the seven LED-s is
as follows:

LED text: Explanation:


Warning LED: if the LCD contains a new message, or operator
LCD
intervention is needed (e.g. acknowledgement of parameter
changes)
Id>R Trip command of the differential protection function in phase R
Id>S Trip command of the differential protection function in phase S
Id>T Trip command of the differential protection function in phase T
I>1 Phase overcurrent protection function start, side 1
I>>2 High set phase overcurrent protection function start, side 2
I>2 Phase overcurrent protection function start, side 2
Fig. 26 LED signals on the front side (DTD-2 V3.xx and DTDZ-2+Udist.rec) V3.xx version)

LED text: Explanation:


Warning LED: if the LCD contains a new message, or operator
LCD
intervention is needed (e.g. acknowledgement of parameter
changes)
Id>R Trip command of the differential protection function in phase R
Id>S Trip command of the differential protection function in phase S
Id>T Trip command of the differential protection function in phase T
I>1 Phase overcurrent protection function start, side 1
I>2 Phase overcurrent protection function start, side 2
I>3 Phase overcurrent protection function start, side 3
Fig. 27 LED signals on the front side (DTD-3 V3.xx and DTD3 [5*3CT] V3.xx version)
The LED-s can be programmed for latching (see subsequent chapter). In this cane they keep
the signal until acknowledgement. Acknowledgement can be generated with the SW1 push-

Compiled by: Approved by: Date: Page: 33 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
button or using Input7 or Input8 digital inputs, according to the enabling with parameter
setting (see Chapter „Application of the digital input”).

2.4.9 Latching

All matrix rows and the LED-s can be programmed for latching (for latching the „-„ character
must be changed for „+” by clicking with he mouse)

Fig. 28 Latching in devices designed for transformers with two voltage levels (PC).

Fig. 29 Latching in devices designed for transformers with three voltage levels (PC).

Compiled by: Approved by: Date: Page: 34 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

LCD text: Explanation:


Mx Id> latch: /+=yes/ Trip command of the differential protection
Mx I>1R latch: /+=yes/ Overcurrent protection function start
Mx I>1S latch: /+=yes/ Overcurrent protection function start
Mx I>1T latch: /+=yes/ Overcurrent protection function start
Mx I>1[t] latch: /+=yes/ Trip command of the overcurrent protection
MxI>>2 or I>2 * latch: /+=yes/ Overcurrent protection function start
MxI>>2 t or I>2 t * latch: /+=yes/ Overcurrent protection function start
MxI>2 or I>3 * latch: /+=yes/ Overcurrent protection function start
MxI>2 t or I>3 t * latch: /+=yes/ Trip command of the overcurrent protection
Mx IN1 latch: /+=yes/ 1. input + timer timeout
Mx IN2 latch: /+=yes/ 2. input + timer timeout
Mx IN3 latch: /+=yes/ 3. input + timer timeout
Mx IN4 latch: /+=yes/ 4. input + timer timeout
Mx IN5 latch: /+=yes/ 5. input + timer timeout
Mx IN6 latch: /+=yes/ 6. input + timer timeout
Mx IN7 latch: /+=yes/ 7. input + timer timeout
Mx CHK latch: /+=yes// Self-check error detection
LED latch: /+=yes/ LED signals
* for transformers with three voltage levels
Fig. 30 Latching parameter setting (LCD).

Compiled by: Approved by: Date: Page: 35 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4.10 Displayed messages


If any of the protection function operates, or if the self-check function detected any error of
the operation, then the LCD of the front panel displays a message. The table below lists the
possible messages:

LCD messageC Explanation


EEPROM error !
RAM battery error ! The RAM memory battery discharged
A/D error ! Self-check function detected an error
Internal DC supply error !
No event stored! No new event since last readout
ALL TRIPS ARE No output is enabled, no trip command or signal is possible!
BLOCKED !
DSP processor error !
Relay tripped! Any of the protection functions generated a trip command
Id> tripped ! The differential protection function generated a trip command
I>1[t] tripped! Overcurrent protection side 1 generated trip command
I>>2[t] tripped! / High set overcurrent protection /Overcurrent protection side 2
I>2[t] tripped! ** generated trip command
I>2[t] tripped! / Overcurrent protection side 2 generated trip command
I>3[t] tripped! ** Overcurrent protection side 3 generated trip command
3Io>>[t] tripped! High set zero sequence overcurrent protection generated trip
command
3Io>[t] tripped! Low set zero sequence overcurrent protection generated trip
command
** the first message is valid for transformers with two voltage levels, the second one for
three voltage levels.

Fig. 31 The possible messages (LCD).

The messages are not displayed in the real event sequence, but they are arranged according to
the list of the table above.

The messages and the error signals of the self-check function are logged in the event log as
well, which can store up to 50 events. In the digital event sequence the events are logged with
1 ms time resolution; here 300 events can be stored. The events are not deleted by the
acknowledgement. The event log can be displayed with the LCD of the front panel, and the
contents of the event log and the content of the event sequence log can be evaluated using the
connected PC or by the SCADA system too. (See detailed description in the document
„EuroProt manual”).

Compiled by: Approved by: Date: Page: 36 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4.11 The displayed information (On-line window, summary)

The algorithms applied for protective functions – as a by-product – generate measure or


calculate several values. These values and information can be displayed on the screen of the
PC, connected via serial line, or on the small LCD or on the optional high-resolution graphic
display of the device. Additionally they are available on the optionally connected SCADA
system as well.

2.4.11.1 Information displayed on an external PC

The measured values (phase currents) and calculated values (difference of the currents,
restraint currents), the status information of the protective functions (starting, trip signals),
status of the digital inputs and output relays, accumulated counter values and additional
service information can be displayed in the On-line window of the connected PC (see the
following figure and details in the document „EuroProt manual”).

Fig. 32 The full On-line window for transformers with two voltage levels

Compiled by: Approved by: Date: Page: 37 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Fig. 33 The full On-line window for transformers with three voltage levels

Compiled by: Approved by: Date: Page: 38 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

2.4.11.2 Information displayed on the LCD

In the „Test” menu of the LCD sequencially the following information can be displayed:

Value Explanation
Idr Differentrial current in phase R
Ids Differentrial current in phase S
Idt Differentrial current in phase T
Isr Restraint current in phase R
Iss Restraint current in phase S
Ist Restraint current in phase T
I1r Primary current RMS value, side 1, phase R
I1s Primary current RMS value, side 1, phase S
I1t Primary current RMS value, side 1, phase T
I2r Primary current RMS value, side 2, phase R
I2s Primary current RMS value, side 2, phase S
I2t Primary current RMS value, side 2 phase T
3IoMeas. 3Io measured primary current RMS value
3IoCalc. 3Io calculated primary current RMS value
DTD 1.Status : Status information No. 1 (see details below)
DTD 2.Status : Status information No. 2 (see details below)
Fig. 34 On-line information of the LCD of the device for transformers with two voltage levels

The explanation of the status information (see last two items in Figure above) can be found in
the document „EPU-2002”. The displayed items are listed below.

The LCD of the EuroProt device displays the status information at the end of the „Test”
menu. As an example the first status word:

DTD-EP 1.status:

In this window the show that the binary values are refreshing. Character means activ
state of the status signal, means inactive state.

The numbering of the individual codes is right to left:

8.7.6.5.4.3.2.1.

Compiled by: Approved by: Date: Page: 39 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

The meaning of the status values is configured in the program of the device. They are listed in
the table below:

DTD-EP 1.status: Meaning:


1 - No meaning for the user
2 RStdn Trip command of the differential protection function,
phase R
3 SStdn Trip command of the differential protection function,
phase S
4 TStdn Trip command of the differential protection function,
phase T
5 - No meaning for the user
6 - No meaning for the user
7 - No meaning for the user
8 - No meaning for the user

DTDA-EP 2.status: Meaning:


1 - No meaning for the user
2 - No meaning for the user
3 - No meaning for the user
4 - No meaning for the user
5 - No meaning for the user
6 DistRec_Trig Disturbance recorder triggering
7 SF_EEPROM_ERROR SYSTEM error (EEPROM)
8 H_BATT_LOW SYSTEM error (BATTERY)

Further in the „Test” menu there are counter values. The four counters are listed in the tables
below:

For transformers with two For transformers with three


voltage levels voltage levels
Id trip counter: 0 Id trip counter: 0
I>1[t] counter: 0 I>1[t] counter: 0
I>>2[t] counter: 0 I>2[t] counter: 0
I>2[t] counter: 0 I>3[t] counter: 0

2.4.12 The self-check functions

The correct operation of the program system is supervised by the „Watch-dog” circuit.
Additionally there are continuous and cyclic self-check functions programmed in the factory
configuration. The self-check function detects internal errors of the hardware system.

Compiled by: Approved by: Date: Page: 40 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL
2.4.12.1 Internal supervision

The internal supervision covers the following items:

Error-free state of the memory for parameter storage,


Power supply of the battery supported RAM for event recording,
Correct operation of the A/D converter.

In case of any detected errors the status is changing in the CHK input of the software matrix.
Optionally this variable integrates the error signals of the circuit breaker supervision system
as well. This status signal can be marshalled to the available output contacts by programming
the software matrix.

2.4.12.2 The circuit breaker supervision system (option)

If the device is extended by a CB circuit supervision module, it can continuously monitor the
healthy state of the CB ON and OFF circuits. The method of supervision and its usage is
described in the document „EuroProt manual”.

The CB circuit supervision module includes three optically isolated inputs. One of them
connects the TRIP1 circuit, the second the TRIP2, the third the ON circuit.

Compiled by: Approved by: Date: Page: 41 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

3 Communication with the device


3.1 The menu system
The menu system of the LCD on the front panel of the device and the method of operation is
described in details in the document „EuroProt manual” this section describes the structure
of the menu only. When energised, the LCD displays the device type and the current date and
time. (month.day hour:minute:second):

DTD-2 PROTECTA DTD-3 PROTECTA


04.19 13:25:32 04.19 13:25:32

When pressing ENTER, the root menu is displayed:

Events Test/Chk
Version Param.

3.1.1 The „Events” menu

When selecting the Events menu, the last evaluated event is displayed on the LCD. The push-
button ↓ steps to the previous event (the push-button ↑ steps back). The following table lists
the possible events:
Message Explanation
Id>> tripped Trip command of the high-set differential protection
Id>R tripped Trip command of the differential protection in phase R
Id>S tripped Trip command of the differential protection in phase S
Id>T tripped Trip command of the differential protection in phase T
I>R1 started Overcurrent protection start, side 1, phase R
I>S1 started Overcurrent protection start, side 1, phase S
I>T1 started Overcurrent protection start, side 1, phase T
I>1[t] tripped Overcurrent protection trip, side 1
I>R2 started Overcurrent protection start, side 2, phase R
I>S2 started Overcurrent protection start, side 2, phase S
I>T2 started Overcurrent protection start, side 2, phase T
I>2[t] tripped Overcurrent protection trip, side 2
I>R3 started Overcurrent protection start, side 3, phase R
I>S3 started Overcurrent protection start, side 3, phase S
I>T3 started Overcurrent protection start, side 3, phase T
I>3[t] tripped Overcurrent protection trip, side 3
3Io>> started Zero sequence high set overcurrent protection start
3Io>>[t] tripped Zero sequence high set overcurrent protection trip
3Io> started Zero sequence overcurrent protection start
3Io> [t] tripped Zero sequence overcurrent protection trip
The short messages in the table are displayed with the exact time of the event. The following
table lists the possible events:

Compiled by: Approved by: Date: Page: 42 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Event Explanation
ID>R Trip command of the differential protection in phase R
ID>S Trip command of the differential protection in phase S
ID>T Trip command of the differential protection in phase T
I>1R Overcurrent protection start, side 1, phase R
I>1S Overcurrent protection start, side 1, phase S
I>1T Overcurrent protection start, side 1, phase T
I>1[t] Overcurrent protection trip, side 1
I>>2R High set overcurrent protection start, side 2, phase R
I>>2S High set overcurrent protection start, side 2, phase S
I>>2T High set overcurrent protection start, side 2, phase T
I>>2[t] High set overcurrent protection trip, side 1
I>2R Overcurrent protection start, side 2, phase R
I>2S Overcurrent protection start, side 2, phase S
I>2T Overcurrent protection start, side 2, phase T
I>2[t] Overcurrent protection trip, side 2
INPUT1 INPUT1 status signal set
INPUT2 INPUT2 status signal set
INPUT3 INPUT3 status signal set
INPUT4 INPUT4 status signal set
INPUT5 INPUT5 status signal set
INPUT6 INPUT6 status signal set
INPUT7 INPUT7 status signal set
OUTPUTS DISABLED All outputs are disabled
K1 K1 output contact operated
K2 K2 output contact operated
K3 K3 output contact operated
K4 K4 output contact operated
K5 K5 output contact operated
K6 K6 output contact operated
K7 K7 output contact operated
K8 K8 output contact operated
AD error A/D error detected
2hBlock Second harmonic restraint operated
EEPROM ERROR EEPROM error detected
INPUT8/ACKN INPUT8 is set to external acknowledgement
Id>>R High set differential protection trip command, phase R
Id>>S High set differential protection trip command, phase S
Id>>T High set differential protection trip command, phase T
K9 K9 output contact operated
K10 K10 output contact operated
K11 K11 output contact operated
K12 K12 output contact operated
K13 K13 output contact operated
K14 K14 output contact operated
K15 K15 output contact operated
K16 K16 output contact operated
3Io>> Zero sequence high set vercurrent protection start
3Io>>[t] Zero sequence high set overcurrent protection trip
3Io> Zero sequence vercurrent protection start
3Io>[t] Zero sequence overcurrent protection trip
Fig. 35 Possible events as displayed in the „Events” menu of the LCD,
for transformers with two voltage levels

Compiled by: Approved by: Date: Page: 43 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

Event Explanation
ID>R Trip command of the differential protection in phase R
ID>S Trip command of the differential protection in phase S
ID>T Trip command of the differential protection in phase T
I>1R Overcurrent protection start, side 1, phase R
I>1S Overcurrent protection start, side 1, phase S
I>1T Overcurrent protection start, side 1, phase T
I>1[t] Overcurrent protection trip, side 1
I>2R Overcurrent protection start, side 2, phase R
I>2S Overcurrent protection start, side 2, phase S
I>2T Overcurrent protection start, side 2, phase T
I>2[t] Overcurrent protection trip, side 2
I>3R Overcurrent protection start, side 3, phase R
I>3S Overcurrent protection start, side 3, phase S
I>3T Overcurrent protection start, side 3, phase T
I>3[t] Overcurrent protection trip, side 3
INPUT1 INPUT1 status signal set
INPUT2 INPUT2 status signal set
INPUT3 INPUT3 status signal set
INPUT4 INPUT4 status signal set
INPUT5 INPUT5 status signal set
INPUT6 INPUT6 status signal set
INPUT7 INPUT7 status signal set
OUTPUTS DISABLED All outputs are disabled
K1 K1 output contact operated
K2 K2 output contact operated
K3 K3 output contact operated
K4 K4 output contact operated
K5 K5 output contact operated
K6 K6 output contact operated
K7 K7 output contact operated
K8 K8 output contact operated
AD error A/D error detected
2hBlock Second harmonic restraint operated
EEPROM ERROR EEPROM error detected
INPUT8/ACKN INPUT8 is set to external acknowledgement
Id>>R High set differential protection trip command, phase R
Id>>S High set differential protection trip command, phase S
Id>>T High set differential protection trip command, phase T
K9 K9 output contact operated
K10 K10 output contact operated
K11 K11 output contact operated
K12 K12 output contact operated
K13 K13 output contact operated
K14 K14 output contact operated
K15 K15 output contact operated
K16 K16 output contact operated
3Io>> Zero sequence high set vercurrent protection start
3Io>>[t] Zero sequence high set overcurrent protection trip
3Io> Zero sequence vercurrent protection start
3Io>[t] Zero sequence overcurrent protection trip
Fig. 36 Possible events as displayed in the „Events” menu of the LCD,
for transformers with three voltage levels

Compiled by: Approved by: Date: Page: 44 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

3.1.2 The „Test” menu

In this menu first the measured values are displayed in primary Amperes. The navigation is
supported by the arrows push-buttons (↓ and ↑).

The displayed measured and calculated values, the counters and status signals in the „Test”
menu is described in details in the Chapter „Information displayed on the LCD”.

3.1.3 The „Chk” menu

In this menu the parameter setting can be checked without need of password input. New
setting in this menu is not possible, for setting enter „Param.” parameter setting menu.

3.1.4 The „Version” menu

In this menu the device type, the version of the configuration and the time of programming
can be seen:

DTD - 2 DTD - 2 +U(dist.rec)


2003.12.05.V3.01 2004.03.16.V3.01

DTD - 3 DTD - 3 [5*3 CT]


2003.12.05.V3.01 2003.09.19.V3.00

The upper row shows the type of the factory configuration, the lower one displays the date of
the version and the version identifier.

3.1.5 The „Param.” menu

The Param. (parameter setting) menu supports the parameter setting for the protection and
automatics functions, the communication and the software matrix. The user can enter this
menu with password only. The detailed description can be found in the document „EuroProt
manual”.

The list of the parameters, the setting ranges and the setting steps are in the function
descriptions above.

Compiled by: Approved by: Date: Page: 45 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

3.1.6 Parameters related to the communication

The parameter setting of the communication function is unified for all EuroProt devices. This
is described in the document „ EuroProt manual”.

3.1.7 Password

The password protection is unified for all EuroProt devices. This is described in the document
„ EuroProt manual”.

3.2 Connecting the device to an external PC


The handling of the device is more convenient and quicker than the operation with the local
man-machine interface, if the device is connected to an external PC.

The operating software is the „Protect for Windows” program. This program and the files
related to the factory configuration (.bla, .gra or .blk, .grf, and additionally the .dok file) is
delivered with the device, and it is stored in the program memory of the CPU as well. Details
of the operation of this program pleas find in the document „ EuroProt manual”.

4 The optional local SCADA functions

In the CPU module of the device a dedicated micro-controller is assigned to perform local
SCADA functions. This is supported by the large, high resolution graphic LCD, which is an
option of the device. The usage of the SCAD function is unified for all EuroProt devices. This
is described in the document „ EuroProt manual”.

5 Arrangement of the DTD-EP factory configuration


The layout of the device is described in the document „ EuroProt manual”.

The arrangement of the front panel, the module configuration, the „Protect for Windows” files
(.bla, .gra or .blk, .grf, and additionally .dok), and the connection arrangement depend on the
configuration. These files and additional documents are attached to the device.

6 Size
The sizes of the different configurations are given in the document „ EuroProt manual”. The
related information is attached to the device.

Compiled by: Approved by: Date: Page: 46 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00
DTD-EP DIFFERENTIAL PROTECTION
PROTECT
Electronics Co. Ltd USER’S MANUAL

7 Ordering information
Ordering of the device is helped by filling the ordering sheet, which is the attachment of the
ordering. This includes the following information:

• Type of the device configuration: „DTD-EP EuroProt multifunctional device,


version: DTD2V31, DTD2V31U, DTD3V31 or DTD5, factory configuration”
• Rated power supply voltage
• Rated input voltage [100 V, 200 V]
• Rated current [1 A, 5 A]
• Special requirement for contact rated current (2 A, 4 A)
• Design of the device (19” cabinet mounted, relay panel mounted or flush-mounted)
• Options (SCADA functions, etc.)

8 Information

Data of the described versions:

DTD2V31 NOD-file: DTD2V31.NOD 2004.03.18.


Version: DTD – 2 2003.12.05.V3.01
DTD2V31U NOD-file: TD2V31U.NOD 2004.03.18.
Version: DTD - 2 +U(dist.rec.) 2004.03.16.V3.01
DTD3V31 NOD-file: DTD3V31.NOD 2004.03.18.
Version: DTD – 3 2003.12.05.V3.01
DTD5 NOD-file: DTD5.NOD 2004.03.18.
Version: DTD - 3 [5*3 AV] 2003.09.19.V3.00
DTD2(+Io) NOD-file: DTD2V32A.NOD 2005.06.16.
Version: DTD - 2 (+Io) 2005.06.13.V3.00

Compiled by: Approved by: Date: Page: 47 / 47


Gyula Póka László Eperjesi 05.22.2004. Version V 3.00

You might also like