The document provides wind load calculations for a building with a mono-slope roof. It includes basic wind parameters, building inputs, exposure constants, gust factor calculation, roof pressures, and components and cladding zone pressures. Calculated values include wind speed, gust factor, roof pressures, and zone pressures.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views2 pages

WPFOutpu

The document provides wind load calculations for a building with a mono-slope roof. It includes basic wind parameters, building inputs, exposure constants, gust factor calculation, roof pressures, and components and cladding zone pressures. Calculated values include wind speed, gust factor, roof pressures, and zone pressures.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MecaWind v2406

Software Developer: Meca Enterprises Inc., www.meca.biz, Copyright © 2020


Calculations Prepared by:
Date: May 23, 2024

Basic Wind Parameters


Wind Load Standard = ASCE 7-16 Exposure Category = C
Wind Design Speed = 128.0 mph Risk Category = II
Structure Type = Building Building Type = Open

General Wind Settings


Incl_LF = Include ASD Load Factor of 0.6 in Pressures = True
DynType = Dynamic Type of Structure = Rigid
Zg = Altitude (Ground Elevation) above Sea Level = 70.000 ft
Bdist = Base Elevation of Structure = 0.000 ft
SDB = Simple Diaphragm Building = False
O_Kd = Override the Directionality Factor 'Kd' = 0.850
MWFRSType = MWFRS Method Selected = Ch 27 Pt 1

Topographic Factor per Fig 26.8-1


Topo = Topographic Feature = None
Kzt = Topographic Factor = 1.000

Building Inputs
RoofType: Roof Type = MonoSlope h : Mean Roof Height = 10.000 ft
L : Width Normal to Ridge = 37.000 ft D : Length Along Ridge = 48.000 ft
WindFlow: Wind Flow Method = Clear Slope : Slope of Roof = 0.0 Deg
Frames : Incl Transverse Frames = False n : Number of Frames = 8
e : Solidity Ratio = 0.350

Exposure Constants per Table 26.11-1:


Alpha: Table 26.11-1 Const = 9.500 Zg: Table 26.11-1 Const = 900.000 ft
At: Table 26.11-1 Const = 0.105 Bt: Table 26.11-1 Const = 1.000
Am: Table 26.11-1 Const = 0.154 Bm: Table 26.11-1 Const = 0.650
C: Table 26.11-1 Const = 0.200 Eps: Table 26.11-1 Const = 0.200

Gust Factor Calculation:


Gust Factor Category I Rigid Structures - Simplified Method
G1 = For Rigid Structures (Nat. Freq.>1 Hz) use 0.85 = 0.85
Gust Factor Category II Rigid Structures - Complete Analysis
Zm = Max(0.6 * Ht, Zmin) = 15.000 ft
Izm = Cc * (33 / Zm) ^ 0.167 = 0.228
Lzm = L * (Zm / 33) ^ Eps = 427.057
B = Structure Width Normal to Wind = 48.000 ft
Q = (1 / (1 + 0.63 * ((B + Ht) / Lzm)^0.63))^0.5 = 0.921
G2 = 0.925*((1+0.7*Izm*3.4*Q)/(1+0.7*3.4*Izm)) = 0.883
Gust Factor Used in Analysis
G = Lessor Of G1 Or G2 = 0.850

Open Building Along Ridge Pressures per Fig 27.3-7 - Wind 90 Deg
All wind pressures include a load factor of 0.6

Roof Var Start End CnA CnB Pressure Pressure


Dist Dist PnA PnB
ft ft psf psf
-------- ------ ------ ------ ----- -------- --------
Roof_1 0.000 10.000 -0.800 0.800 -12.32 12.32
Roof_2 10.000 20.000 -0.600 0.500 -9.24 7.70
Roof_3 20.000 48.000 -0.300 0.300 -4.62 4.62

Notes Roof Pressures:


Start Dist = Start Dist from Windward Edge End Dist = End Dist from Windward Edge
CnA = Cn for Load Case A CnB = Cn for Load Case B
PnA = qh*G*CnA {Eqn 27.4-3} PnB = qh*g*CnB {Eqn 27.4-3]
+ Pressures Acting TOWARD Surface - Pressures Acting AWAY from Surface

5/23/2024 9:06:36 AM 1/2


Components And Cladding (C&C) Calculations per Ch 30 Part 5:
h = Mean Roof Height above grade = 10.000 ft
Kh = Z < 15 ft [4.572 m]--> (2.01 * (15/zg)^(2/Alpha) {Table 26.10-1}= 0.849
Kzt = Topographic Factor is 1 since no Topographic feature specified = 1.000
LF = Load Factor based upon ASD Design = 0.60
qh = (0.00256 * Kh * Kzt * Kd * Ke * V^2) * LF = 18.11 psf
Theta = Roof Slope = 0.0 Deg
LHD = Least Horizontal Dimension: Min(B, L) = 37.000 ft
a1 = Min(0.1 * LHD, 0.4 * h) = 3.700 ft
a = Max(a1, 0.04 * LHD, 3 ft [0.9 m]) = 3.700 ft

Wind Pressures for C&C per


All wind pressures include a load factor of 0.6

Description Width Span Area 1/3 Zone Cn Cn p p


Rule Pos Neg Pos Neg
ft ft ft ft psf psf
----------- ----- ----- ----- ---- ---- ----- ------ ----- ------
Zone 1 0.000 0.000 0.000 No 1 1.200 -1.100 18.47 -16.94
Zone 2 0.000 0.000 0.000 No 2 1.800 -1.700 27.71 -26.17
Zone 3 0.000 0.000 0.000 No 3 2.400 -3.300 36.95 -50.81

Cn = Net Pressure Coefficient taken from Fig 30.7-1, 2 and 4


p = Wind Pressure: qh * G * Cn [Eqn 30.7-1]

Components and Cladding (C&C) Zone Summary per Ch 30 Pt 5:


h = Mean Roof Height above grade = 10.000 ft
Kh = Z < 15 ft [4.572 m]--> (2.01 * (15/zg)^(2/Alpha) {Table 26.10-1}= 0.849
Kzt = Topographic Factor is 1 since no Topographic feature specified = 1.000
LF = Load Factor based upon ASD Design = 0.60
qh = (0.00256 * Kh * Kzt * Kd * Ke * V^2) * LF = 18.11 psf
Theta = Roof Slope = 0.0 Deg
LHD = Least Horizontal Dimension: Min(B, L) = 37.000 ft
a1 = Min(0.1 * LHD, 0.4 * h) = 3.700 ft
a = Max(a1, 0.04 * LHD, 3 ft [0.9 m]) = 3.700 ft

Wind Pressure Summary for C&C Zones based Upon Areas Ch 30 Pt 5


All wind pressures include a load factor of 0.6

Zone | Figure | A <= | 13.69 > A >= 54.76 sq ft | A >=


| | 13.69 sq ft | | 54.76 sq ft
psf psf psf
---- - ------------- - ------------ - ------------------------ - ------------
1 | Figure 30.7-1 | 18.47 -16.94 | 18.47 -16.94 | 18.47 -16.94
2 | Figure 30.7-1 | 27.71 -26.17 | 27.71 -26.17 | 18.47 -16.94
3 | Figure 30.7-1 | 36.95 -50.81 | 27.71 -26.17 | 18.47 -16.94

* A is effective wind area for C&C: Span Length * Effective Width


* Effective width need not be less than 1/3 of the span length
* Maximum and minimum values of pressure shown.
* + Pressures acting toward surface, - Pressures acting away from surface
* Per Para 30.2.2 the Minimum Pressure for C&C is 9.60 psf [0.460 kPa] {Includes LF}

5/23/2024 9:06:36 AM 2/2