• Outdoor Units • R-410A • RZQS125-140C7V1B

1 Features

A7 iC 0ny 4U k 1 S - r 5 o A2t o 01 i d 1S l t4Q puZ- S•RO Outdoor units for pair, twin, triple, double twin application • During start up, the room can be cooled down or heated very quickly.
Once the temperature in the room has reached its set point, the low
• The Sky Air Inverter is developed for use in shops, restaurants and
small offices. This innovative Daikin unit provides a more power operation starts to save energy.
comfortable environment and offers great savings in energy • Daikin outdoor units are neat and sturdy and can be mounted easily
consumption to shop and office owners. on a roof or terrace or simply placed against an outside wall.
• The use of inverter type outdoor units results in an air conditioning • Outdoor units are fitted with either a swing or scroll compressor,
system with a high energy efficiency and very low sound level renowned for low noise and high energy efficiency
• An inverter driven compressor allows the capacity to be adjusted • A special acryl precoated fin for anti-corrosion treatment on the heat
precisely to match variations in room and outside temperatures. exchanger ensures greater resistance against severe weather
conditions

51
1

1014 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

2 Specifications

2-1 NOMINAL CAPACITY AND


RZQS125C7V1B RZQS140C7V1B
NOMINAL INPUT
For Indoor Units
combination
FCHQ125C7VEB FCHQ140C7VEB
indoor units +
outdoor units
Cooling Standard kW
12.5 14.0
capacity
Heating Standard kW
14.0 16.0
capacity
Power Input Cooling Standard kW 3.88 4.98
Heating Standard kW 4.11 4.98
For EER Nominal 3.22 2.81
combination COP Nominal 3.41 3.21
indoor units + Energy Label Cooling A C
outdoor units
Heating B C
Annual energy consumption kWh 1940 2490
Indoor Units FCQ125C7VEB FCQ140C7VEB
Cooling Standard kW
12.5 14.0
capacity
Heating Standard kW
14.0 16.0
capacity
Power Input Cooling Standard kW 4.14 5.36
Heating Standard kW 4.52 5.69
For EER Nominal 3.02 2.61
combination COP Nominal 3.1 2.81
indoor units +
Energy Label Cooling B D
outdoor units
Heating D
Annual energy consumption kWh 2070 2680

Cooling
Indoor Units
Standard kW
FBQ125B8V3B

12.5
FBQ140B8V3B

13.4
51
capacity 2
Heating Standard kW
14.0 15.5
capacity
Power Input Cooling Standard kW 4.40 4.77
Heating Standard kW 4.24 4.83
For EER Nominal 2.84 2.81
combination COP Nominal 3.30 3.21
indoor units +
Energy Label Cooling C
outdoor units
Heating C
Annual energy consumption kWh 2200 2385
Indoor Units FHQ125BVV1B
Cooling Standard kW
12.5
capacity
Heating Standard kW
14.0
capacity
Power Input Cooling Standard kW 4.58
Heating Standard kW 4.96
For EER Nominal 2.73
combination COP Nominal 2.82
indoor units + Energy Label Cooling D
outdoor units
Heating D
Annual energy consumption kWh 2290
Indoor Units FDQ125B8V3B
Cooling Standard kW
12.5
capacity
Heating Standard kW
14.0
capacity
Power Input Cooling Standard kW 4.45
Heating Standard kW 4.08

• Split Sky Air • Outdoor Units 1015


• Outdoor Units • R-410A • RZQS125-140C7V1B

2 Specifications

2-1 NOMINAL CAPACITY AND


RZQS125C7V1B RZQS140C7V1B
NOMINAL INPUT
For EER Nominal 2.81
combination COP Nominal 3.43
indoor units +
Energy Label Cooling C
outdoor units
Heating B
Annual energy consumption kWh 2225

2-2 TECHNICAL SPECIFICATIONS RZQS125C7V1B RZQS140C7V1B


Casing Colour Ivory White
Material Painted galvanised steel
Dimensions Unit Height mm 1170 1170
Width mm 900 900
Depth mm 320 320
Packing Height mm 1349 1349
Width mm 980 980
Depth mm 420 420
Weight Unit kg 103 103
Packed Unit kg 114 114
Heat Dimensions Length mm 857
Exchanger Nr of Rows 2 2
Fin Pitch mm 1.4 1.4
Nr of Passes 6 6
Face m²
0.98 0.98
Area
Nr of Stages 52 52
Tube type Hi-XSS(8)
Fin Type WF fin

51 Fan Type
Treatment Anti-corrosion treatment (PE)
Direct Drive Propeller
2 Discharge direction Horizontal
Quantity 2 2
Air Flow Rate Cooling m³/min 100 97
(nominal at 230V) Heating m³/min 88 88
Motor Quantity 2 2
Model Brushless DC Motor
Motor Speed Steps 8 8
(nominal) Cooling rpm 850 830
Heating rpm 740 740
Fan Motor Output W 70 70
Compressor Quantity 1 1
Motor Model JT100G-VD
Model Inverter
Type Hermetically sealed scroll compressor
Motor W
2200 2200
Output
Crankcase W
33 33
Heater
Operation Cooling Min °CDB -5 -5
Range Max °CDB 46 46
Heating Min °CWB -15 -15
Max °CWB 15.5 15.5
Sound Level Cooling Sound dBA
67 68
(nominal) Power
Sound dBA
51 52
Pressure
Heating Sound dBA
53 54
Pressure
Sound Level Sound Pressure dBA
49 50
(Night quiet)

1016 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

2 Specifications

2-2 TECHNICAL SPECIFICATIONS RZQS125C7V1B RZQS140C7V1B


Refrigerant Type R-410A
Charge kg 3.7 3.7
Control Expansion valve (electronic type)
Nr of Circuits 1 1
Refrigerant Oil Type Daphne FVC68D
Charged Volume l 1.0 1.0
Piping Liquid (OD) Quantity 1 1
connections Type Flare connection
Diameter mm
9.52 9.52
(OD)
Gas Quantity 1 1
Type Flare connection
Diameter mm
15.9 15.9
(OD)
Drain Quantity 3 3
Type Hole
Diameter mm
26 26
(OD)
Piping Length Minimum m 5 5
Maximum m 50 50
Equivalent m 95 95
Chargeless m 30 30
Additional Refrigerant kg/m
see installation manual 4PW34874-1
Charge
Installation Maximum m
height 30.0 30.0
difference
Max. internunit level m
0.5 0.5
difference
Heat Insulation Both liquid and gas pipes 51
Defrost Method Pressure equalising 2
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
Safety Devices High pressure switch
Fan motor thermal protector
Fuse
Standard Item Tie-wraps
Accessories Quantity 2 2
Item Installation manual
Quantity 1 1
Notes Nominal cooling capacities are based on : indoor temperature : 270CDB, 190CWB, outdoor temperature : 350CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 200CDB, outdoor temperature : 70CDB, 60CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m

2-3 ELECTRICAL SPECIFICATIONS RZQS125C7V1B RZQS140C7V1B


Power Supply Name V1
Phase 1 1
Frequency Hz 50 50
Voltage V 230 230
Voltage range Minimum V -10%
Maximum V +10%
Current Recomended fuses A 32 32
Wiring For Power Remark See installation manual 4PW34874-1
connections Supply
For connection Remark See installation manual 4PW34874-1
with indoor
Power Supply Intake Outdoor unit only
Notes See separate drawings for electrical data

• Split Sky Air • Outdoor Units 1017


• Outdoor Units • R-410A • RZQS125-140C7V1B

3 Electrical data

RZQS125-140C
Unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLA

Max. 50Hz 264V


Min. 50Hz 198V

51
3

Max. 50Hz 264V


Min. 50Hz 198V

3D057296
SYMBOLS NOTES
MCA : Min. Circuit Amps (A) 1 RLA is based on the following conditions:
TOCA : Total Over Current Amps (A) Power supply: 50Hz - 230V
Cooling
MFA : Max. Fuse Amps (A) (See note 7) Indoor temperature 27°CDB/19°CWB
MSC : MSC means the max. current during the Outdoor temperature 35°CDB
starting of compressor. (A) Heating
Indoor temperature 20.0°CDB
RLA : Rated Load Amps (A)
Outdoor temperature 7.0°CDB/6.0°CWB
OFM : Outdoor Fan Motor (A) 2 TOCA means the total value of each OC set
IFM : Indoor Fan Motor 3 Voltage range
FLA : Full Load Amps Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
kW : Fan Motor Rated Output (kW) above listed operation range limits
4 Maximum allowable voltage unbalance between phases is 2%
5 MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
6 Select wire size based on the larger value of MCA or TOCA
7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
8 For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the
document title of your choice.

1018 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

4 Options

Available options for RZQS100-140C7V1B

Kit name
Name of option
RZQS125C7V1B RZQS140C7V1B
Central drain pan kit KKPJ5F180
Refrigerant branch piping Twin KHRQ22M20TA
Triple KHRQ127H
Double twin KHRQ22M20TA (3x)
Demand adaptor KRP58M51
3TW26739-1E

51
4

• Split Sky Air • Outdoor Units 1019


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-1 Combination table
RZQS 125-140C
Possible combinations and standard capacity for twin, triple and double twin operation
Possible indoor combination
Simultaneous operation
Twin Triple Double twin

Outdoor models Out Out Out

In In In In In In In In In

60-60 50-50-50 35-35-35-35


RZQS125C7V1B
(KHRQ22M20TA) (KHRQ127H) (3x KHRQ22M20TA)
71-71 50-50-50 35-35-35-35
RZQS140C7V1B
(KHRQ22M20TA) (KHRQ127H) (3x KHRQ22M20TA)

3TW29169-3

NOTES
1 Possible indoor units:FCQH71C, FCQ35-71C, FFQ35-60BV, FHQ35-71B, FBQ35-71B, FAQ71B
2 Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3 When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the
main unit.In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).
4 Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.

51
5

1020 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-2 Cooling capacity tables
RZQS125C (Pair + twin/triple/double twin)

Cooling
Coefficient of power input. (-)

Capacity range Rated point

Cooling capacity (kW)


Cooling capacity
Indoor Outdoor temp. (°CDB)
EWB EDB 25 30 35 40
TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(°C) (°C)
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 11.4 7.73 0.76 11.4 7.81 0.89 11.7 8.14 0.99 11.3 7.90 1.09
18.0 25 13.1 8.48 0.83 12.7 8.32 0.91 12.2 8.12 1.00 11.8 7.88 1.10
19.0 27 13.3 8.45 0.84 12.9 8.29 0.91 12.5 8.09 1.00 12.0 7.86 1.10
19.5 27 13.5 8.44 0.84 13.1 8.28 0.91 12.6 8.08 1.00 12.1 7.85 1.10
22.0 30 14.2 8.33 0.85 13.8 8.18 0.92 13.3 7.99 1.01 12.8 7.76 1.11
24.0 32 14.7 8.21 0.85 14.3 8.06 0.93 13.8 7.88 1.02 13.3 7.67 1.12
3D057300

NOTES SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
(m3/min)
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
AFR:
BF:
EWB:
Air flow rate
Bypass factor
Entering wet bulb temp. (°CWB)
51
3. On the tables Q show rated capacity and rated coefficient of power input. EDB: Entering dry bulb temp. (°CDB)
4. SHC is based on each EWB and EDB TC: Total cooling/heating capacity (kW)
5
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) SHC: Sensible heating capacity (kW)
Add SHC* to SHC. PI: Power input (kW)
5. Capacities are based on following conditions: (comp.+indoor+outdoor fan motor)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) CPI: Coefficient of power input. (-)
Corresponding refrigerant piping length : 5.0 m
Level difference :0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
Caution:
8. Heating capacity include the drop of frost formation. TC and SHC are shown by kW
9. Air flow rate and BF are tabulated below.
(Pair)
Model FCQH125C FCQ125C FBQ125 FHQ125 FDQ125
AFR 32.5 27.5 35 30 45
(BF) (0.19) (0.19) (0.14) (0.13) (0.25) (Twin)
(Triple) Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 AFR 13.5x2 15x2 19x2 17x2
AFR 12.5x3 12x3 14x3 13x3 (BF) (0.21x2) (0.11x2) (0.11x2) (0.2x2)
(BF) (0.21x3) (0.16x3) (0.15x3) (0.1x3) (Double twin)

10. Rated power input of each model is tabulated below. Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
(Pair) AFR 10.5x4 10x4 11.5x4 13x4
Model FCQH125C FCQ125C FBQ125 FHQ125 FDQ125 (BF) (0.28x4) (0.25x4) (0.15x4) (0.2x4)
Cooling 3.88 4.14 4.40 4.58 4.45
Heating 4.11 4.52 4.24 4.96 4.08
(Twin)
(Triple)
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2
Cooling 4.36 4.41 4.48 4.76 Cooling 4.36 4.41 4.48 4.76
Heating 4.76 4.42 4.42 4.92 Heating 4.76 4.42 4.42 4.92
(Double twin)
Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
Cooling 4.36 4.41 4.48 4.76
Heating 4.76 4.42 4.42 4.92

• Split Sky Air • Outdoor Units 1021


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-2 Cooling capacity tables
RZQS140C (Pair + twin/triple/double twin)

Cooling
Coefficient of power input. (-)

Capacity range Rated point


Cooling capacity (kW)
Cooling capacity
Indoor Outdoor temp. (°CDB)
EWB EDB 25 30 35 40
TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(°C) (°C)
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 12.8 8.66 0.76 12.7 8.74 0.89 13.1 9.12 0.99 12.6 8.84 1.09
18.0 25 14.6 9.50 0.83 14.2 9.31 0.91 13.7 9.09 1.00 13.2 8.82 1.10
19.0 27 15.0 9.47 0.84 14.5 9.29 0.91 14.0 9.07 1.00 13.4 8.80 1.10
19.5 27 15.1 9.45 0.84 14.7 9.27 0.91 14.1 9.05 1.00 13.6 8.79 1.10
22.0 30 15.9 9.33 0.85 15.4 9.16 0.92 14.9 8.95 1.01 14.3 8.69 1.11
24.0 32 16.5 9.20 0.85 16.0 9.03 0.93 15.5 8.83 1.02 14.9 8.59 1.12
3D057301

NOTES SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
(m3/min)
51 2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
AFR:
BF:
EWB:
Air flow rate
Bypass factor
Entering wet bulb temp. (°CWB)
3. On the tables Q show rated capacity and rated coefficient of power input. EDB: Entering dry bulb temp. (°CDB)
5 4. SHC is based on each EWB and EDB TC: Total cooling/heating capacity (kW)
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) SHC: Sensible heating capacity (kW)
Add SHC* to SHC. PI: Power input (kW)
5. Capacities are based on following conditions: (comp.+indoor+outdoor fan motor)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) CPI: Coefficient of power input. (-)
Corresponding refrigerant piping length : 5.0 m
Level difference :0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
Caution:
8. Heating capacity include the drop of frost formation. TC and SHC are shown by kW
9. Air flow rate and BF are tabulated below.
(Pair)
Model FCQH140C FCQ140C
AFR 32.5 27.5
(BF) (0.20) (0.22) (Twin)
(Triple) Model FCQ71Cx2 FBQ71x2 FHQ71x2 FAQ71x2
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 AFR 15.5x2 19x2 17x2 19x2
AFR 12.5x3 12x3 14x3 13x3 (BF) (0.19x2) (0.11x2) (0.1x2) (0.08x2)
(BF) (0.21x3) (0.16x3) (0.15x3) (0.1x3) (Double twin)

10. Rated power input of each model is tabulated below. Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
(Pair) AFR 10.5x4 10x4 11.5x4 13x4
Model FCQH140C FCQ140C (BF) (0.28x4) (0.25x4) (0.15x4) (0.2x4)
Cooling 4.98 5.36
Heating 4.98 5.69
(Twin)
(Triple)
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Model FCQ71Cx2 FBQ71x2 FHQ71x2 FAQ71x2
Cooling 5.36 5.12 5.21 5.25 Cooling 5.36 5.21 5.25 5.25
Heating 5.55 5.70 5.64 5.70 Heating 5.55 5.64 5.70 5.63
(Double twin)
Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
Cooling 5.36 5.12 5.21 5.25
Heating 5.55 5.70 5.64 5.70

1022 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-2 Cooling capacity tables
RZQS140C (Pair)

Cooling
Coefficient of power input. (-)

Cooling capacity (kW) Rated point


Capacity range
Cooling capacity
Indoor Outdoor temp. (°CDB)
EWB EDB 25 30 35 40
TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(°C) (°C)
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 12.3 8.29 0.76 12.2 8.37 0.89 12.5 8.73 0.99 12.1 8.46 1.09
18.0 25 14.0 9.09 0.83 13.6 8.91 0.91 13.1 8.70 1.00 12.6 8.44 1.10
19.0 27 14.4 9.06 0.84 13.9 8.89 0.91 13.4 8.68 1.00 12.8 8.42 1.10
19.5 27 14.5 9.05 0.84 14.1 8.87 0.91 13.5 8.66 1.00 13.0 8.41 1.10
22.0 30 15.2 8.93 0.85 14.7 8.77 0.92 14.3 8.57 1.01 13.7 8.32 1.11
24.0 32 15.8 8.81 0.85 15.3 8.64 0.93 14.8 8.45 1.02 14.3 8.22 1.12
3TW28149-1

NOTES SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
(m3/min)
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
AFR:
BF:
EWB:
Air flow rate
Bypass factor
Entering wet bulb temp. (°CWB)
51
3. On the tables Q show rated capacity and rated coefficient of power input. EDB: Entering dry bulb temp. (°CDB)
4. SHC is based on each EWB and EDB TC: Total cooling/heating capacity (kW)
5
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) SHC: Sensible heating capacity (kW)
Add SHC* to SHC. PI: Power input (kW)
5. Capacities are based on following conditions: (comp.+indoor+outdoor fan motor)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) CPI: Coefficient of power input. (-)
Corresponding refrigerant piping length : 7.5 m
Level difference :0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
Caution:
8. Heating capacity include the drop of frost formation. TC and SHC are shown by kW
9. Air flow rate and BF are tabulated below.
(Pair)
FBQ140
AFR 35
(BF) (0.14)
10. Rated power input of each model is tabulated below.
(Pair)
Outdoor RZQS140C7
Indoor FBQ140B8
Cooling 4.97kW
Heating 4.99kW

• Split Sky Air • Outdoor Units 1023


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-2 Cooling capacity tables
RZQS125-140C
Capacity in function of field piping length for non-inverter

Capacity (%)

Field piping length (m)

51 Cooling
3TW29069-3

5 Heating

1024 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-3 Heating capacity tables
RZQS125C (Pair + twin/triple/double twin)

Heating
Coefficient of power input. (-)

Capacity range Rated point

Heating capacity (kW)


Heating capacity
Indoor Outdoor temp. (°CWB)
EDB −15 −10 −5 0 6 10
TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(°C)
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.O 8.83 1.05 9.76 1.11 10.7 1.16 11.6 1.22 14.0 0.92 15.1 0.97
18.O 8.82 1.10 9.74 1.15 10.7 1.21 11.6 1.27 14.0 0.96 15.1 1.01
20.0 8.81 1.14 9.73 1.20 10.7 1.26 11.6 1.32 14.0 1.00 15.1 1.05
21.O 8.81 1.16 9.73 1.22 10.6 1.28 11.6 1.34 14.0 1.02 15.1 1.07
22.O 8.80 1.18 9.72 1.24 10.6 1.31 11.6 1.37 14.0 1.04 15.1 1.09
24.0 8.79 1.22 9.71 1.29 10.6 1.35 11.5 1.42 14.0 1.08 15.0 1.13
3D057300

NOTES SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
AFR:
BF:
EWB:
Air flow rate
Bypass factor
Entering wet bulb temp.
(m3/min)

(°CWB)
51
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
EDB:
TC:
Entering dry bulb temp.
Total cooling/heating capacity
(°CDB)
(kW)
5
SHC* = SHC correction for other dry bulb SHC: Sensible heating capacity (kW)
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC. PI: Power input (kW)
5. Capacities are based on following conditions: (comp.+indoor+outdoor fan motor)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB CPI: Coefficient of power input. (-)
(heating)
Corresponding refrigerant piping length : 5.0 m
Level difference :0m Caution:
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type. TC and SHC are shown by kW
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
Model FCQH125C FCQ125C FBQ125 FHQ125 FDQ125
AFR 32.5 27.5 35 30 45 (Twin)
(BF) (0.19) (0.19) (0.14) (0.13) (0.25) Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2
(Triple) AFR 13.5x2 15x2 19x2 17x2
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 (BF) (0.21x2) (0.11x2) (0.11x2) (0.2x2)
AFR 12.5x3 12x3 14x3 13x3 (Double twin)
(BF) (0.21x3) (0.16x3) (0.15x3) (0.1x3) Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
10. Rated power input of each model is tabulated below. AFR 10.5x4 10x4 11.5x4 13x4
(Pair) (BF) (0.28x4) (0.25x4) (0.15x4) (0.2x4)
Model FCQH125C FCQ125C FBQ125 FHQ125 FDQ125
Cooling 3.88 4.14 4.40 4.58 4.45
Heating 4.11 4.52 4.24 4.96 4.08 (Twin)
(Triple) Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Cooling 4.36 4.41 4.48 4.76
Cooling 4.36 4.41 4.48 4.76 Heating 4.76 4.42 4.42 4.92
Heating 4.76 4.42 4.42 4.92 (Double twin)
Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
Cooling 4.36 4.41 4.48 4.76
Heating 4.76 4.42 4.42 4.92

• Split Sky Air • Outdoor Units 1025


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-3 Heating capacity tables
RZQS140C (Pair + twin/triple/double twin)

Heating
Coefficient of power input. (-)

Capacity range
Rated point
Heating capacity (kW)
Heating capacity
Indoor Outdoor temp. (°CWB)
EDB −15 −10 −5 0 6 10
TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(°C)
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.O 9.82 1.05 10.8 1.11 11.9 1.16 12.9 1.22 16.0 0.92 17.3 0.97
18.O 9.80 1.10 10.8 1.15 11.8 1.21 12.9 1.27 16.0 0.96 17.2 1.01
20.0 9.79 1.14 10.8 1.20 11.8 1.26 12.9 1.32 16.0 1.00 17.2 1.05
21.O 9.79 1.16 10.8 1.22 11.8 1.28 12.8 1.34 16.0 1.02 17.2 1.07
22.O 9.78 1.18 10.8 1.24 11.8 1.31 12.8 1.37 16.0 1.04 17.2 1.09
24.0 9.77 1.22 10.8 1.29 11.8 1.35 12.8 1.42 16.0 1.08 17.2 1.13
3D057301

NOTES SYMBOLS

51 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
AFR:
BF:
EWB:
Air flow rate
Bypass factor
Entering wet bulb temp.
(m3/min)

(°CWB)
5 3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
EDB:
TC:
Entering dry bulb temp.
Total cooling/heating capacity
(°CDB)
(kW)
SHC* = SHC correction for other dry bulb SHC: Sensible heating capacity (kW)
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC. PI: Power input (kW)
5. Capacities are based on following conditions:
(comp.+indoor+outdoor fan motor)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB CPI: Coefficient of power input. (-)
(heating)
Corresponding refrigerant piping length : 5.0 m
Level difference :0m Caution:
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type. TC and SHC are shown by kW
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
Model FCQH140C FCQ140C
AFR 32.5 27.5 (Twin)
(BF) (0.20) (0.22) Model FCQ71Cx2 FBQ71x2 FHQ71x2 FAQ71x2
(Triple) AFR 15.5x2 19x2 17x2 19x2
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 (BF) (0.19x2) (0.11x2) (0.1x2) (0.08x2)
AFR 12.5x3 12x3 14x3 13x3 (Double twin)
(BF) (0.21x3) (0.16x3) (0.15x3) (0.1x3) Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
10. Rated power input of each model is tabulated below. AFR 10.5x4 10x4 11.5x4 13x4
(Pair) (BF) (0.28x4) (0.25x4) (0.15x4) (0.2x4)
Model FCQH140C FCQ140C
Cooling 4.98 5.36
Heating 4.98 5.69 (Twin)
(Triple) Model FCQ71Cx2 FBQ71x2 FHQ71x2 FAQ71x2
Model FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 Cooling 5.36 5.21 5.25 5.25
Cooling 5.36 5.12 5.21 5.25 Heating 5.55 5.64 5.70 5.63
Heating 5.55 5.70 5.64 5.70 (Double twin)
Model FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
Cooling 5.36 5.12 5.21 5.25
Heating 5.55 5.70 5.64 5.70

1026 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

5 Capacity tables
5-3 Heating capacity tables
RZQS140C (Pair)

Heating
Coefficient of power input. (-)

Heating capacity (kW) Rated point

Heating capacity
Indoor Outdoor temp. (°CWB)
EDB −15 −10 −5 0 6 10
TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(°C)
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.O 9.51 1.05 10.5 1.11 11.5 1.16 12.5 1.22 15.5 0.92 16.8 0.97
18.O 9.49 1.10 10.5 1.15 11.4 1.21 12.5 1.27 15.5 0.96 16.7 1.01
20.0 9.48 1.14 10.5 1.20 11.4 1.26 12.5 1.32 15.5 1.00 16.7 1.05
21.O 9.48 1.16 10.5 1.22 11.4 1.28 12.4 1.34 15.5 1.02 16.7 1.07
22.O 9.47 1.18 10.5 1.24 11.4 1.31 12.4 1.37 15.5 1.04 16.7 1.09
24.0 9.46 1.22 10.5 1.29 11.4 1.35 12.4 1.42 15.5 1.08 16.7 1.13
3TW28149-1

NOTES SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions. AFR: Air flow rate (m3/min) 51
BF: Bypass factor
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition. EWB: Entering wet bulb temp. (°CWB) 5
3. On the tables Q show rated capacity and rated coefficient of power input. EDB: Entering dry bulb temp. (°CDB)
4. SHC is based on each EWB and EDB TC: Total cooling/heating capacity (kW)
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB)
SHC: Sensible heating capacity (kW)
Add SHC* to SHC. PI: Power input (kW)
5. Capacities are based on following conditions: (comp.+indoor+outdoor fan motor)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB CPI: Coefficient of power input. (-)
(heating)
Corresponding refrigerant piping length : 7.5 m
Level difference :0m Caution:
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type. TC and SHC are shown by kW
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
FBQ140
AFR 35
(BF) (0.14)
10. Rated power input of each model is tabulated below.
(Pair)
Outdoor RZQS140C7
Indoor FBQ140B8
Cooling 4.97kW
Heating 4.99kW

• Split Sky Air • Outdoor Units 1027


• Outdoor Units • R-410A • RZQS125-140C7V1B

6 Dimensional drawing & centre of gravity


6-1 Dimensional drawing
RZQS125-140C
Hole for anchor bolt
4-M12 1 Gas pipe connection J15.9 flare
2 Liquid pipe connection - J9.5 flare
3 Service port (in the unit)
4 Grounding terminal M5 (in switch box)
5 Refrigerant piping intake
6 Power supply wiring intake (knock out hole J34)
7 Control wiring intake (Knock out hole J27)
8 Drain outlet

3TW26364-1

51
6

1028 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

6 Dimensional drawing & centre of gravity


6-2 Centre of gravity
RZQS125-140C

4TW29169-4

51
6

• Split Sky Air • Outdoor Units 1029


• Outdoor Units • R-410A • RZQS125-140C7V1B

7 Piping diagram

RZQS125-140C (Pair)

Electronic
expansion
valve

Heat exchanger
Filter Filter

4-way valve

Heat exchanger
High pressure
Low pressure switch
sensor

Field piping J9.5 C1220T-0 Service port


Compressor 5/16″
Filter
Field piping J15.9 C1220T-0

Accumulator

Indoor unit Heating


Outdoor unit
Stop valve Cooling
(with service port 5/16’ flare)

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW29165-1

51 RZQS125-140C (Twin)

7
Electronic
expansion valve
Heat exchanger

Filter Filter Heat exchanger

Field piping
4-way valve
Filter Field piping

Indoor unit

High pressure
Low pressure switch
sensor

Heat exchanger

Field piping J9.5 Service port


Branch duct
connection 5/16″
Compressor
Option
Field piping J15.9

Accumulator

Field piping
Outdoor unit
Heating
Cooling
Filter Field piping

Note: 1. The pipes between the branch and the indoor units should have the same size as
Stop valve
(with service port 5/16’ flare) the indoor connections.
Indoor unit

3TW29165-2
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

1030 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

7 Piping diagram

RZQS125-140C (Triple)
Indoor unit
Heat exchanger

Electronic
expansion valve

Stop valve Heat exchanger


(with service port 5/16’ flare) Filter
Filter
Field piping

Filter Field piping

Indoor unit
Heat exchanger 4-way valve

Field piping J9.5 Low pressure High pressure


sensor switch

Field piping

Filter Field piping


Field piping J15.9

Indoor unit Service port


Heat exchanger 5/16″
Branch duct Compressor
connection
Option
Accumulator

Note: 1. The pipes between the branch and the indoor units Outdoor unit
should have the same size as the indoor connections.

Heating
Field piping Cooling
Filter Field piping

3TW29165-3
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

RZQS125-140C (Double twin)


Heat exchanger Indoor unit
51
7
Electronic
expansion
valve

Field piping
Heat exchanger
Filter Field piping Filter Filter

Heat exchanger Indoor unit


Field piping
J9.5

4-way valve
Field piping
J15.9

Field piping
Low pressure High pressure
Filter Field piping sensor switch

Heat Indoor unit Branch duct


exchanger connection
Option Field piping J9.5
Service
Compressor port
Field piping J15.9 5/16″

Accumulator
Field piping
Outdoor unit
Filter Field piping
Stop valve
(with service port 5/16’ flare) Heating
Cooling
Heat exchanger
Field piping
J9.5

Field piping
J15.9

Field piping Note: 1. The pipes between the branch and the indoor
units should have the same size as the indoor connections.
Filter Field piping

3TW29165-4
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split Sky Air • Outdoor Units 1031


• Outdoor Units • R-410A • RZQS125-140C7V1B

8 Wiring diagram
8-1 Wiring diagram
RZQS125-140C
A1P : Printed circuit board (Main)
A2P : Printed circuit board (INV.)
A3P : Printed circuit board (Noise filter)
A4P : Printed circuit board Indoor
BS1∼BS4 : Push button switch
C1∼C4 : Capacitor
DS1 : Dip switch
E1HC : Crankcase heater
F1U,F3U,F4U: Fuse (T 6.3A/250V) Outdoor
F6U : Fuse (T 5.0A/250V)
H1P∼H7P : Light emitting diode (service monitor
orange)
: Prepare test ----------- Flickering
[H2P] : Malfunction detection--- Light up
HAP Light emitting diode (service monitor
green)
(A1P) (Note4)
K1R : Magnetic relay (Y1S)
K4R : Magnetic relay (E1HC)
K10R : Magnetic relay
K11R : Magnetic relay
L1R : Reactor
M1C : Motor (compressor)
M1F : Motor (fan) (upper)
M2F : Motor (fan) (lower)
PS : Switching power supply
Q1DI : Field earth leak detector (30mA)
R1 : Resistor
R2 : Resistor
R1T : Thermistor (Air)
R2T : Thermistor (Discharge)
R3T : Thermistor (Suction)
R4T : Thermistor (Heat exchanger)
R5T : Thermistor (heat exchanger middle)
R6T : Thermistor (Liquid)
RC : Signal receiver circuit
R10T : Thermistor (fin)
S1NPH : Pressure sensor(High)
S1PH : Pressure switch (High) El. comp. assy front
TC : Signal transmission circuit (Position of elements)
V1R : Power module
V2R,V3R : Diode module
Position of
V1T : IGBT compressor
X1M : Terminal strip (Power supply) terminal
Y1E : Electronic expansion valve
Y1S : Solenoid valve (4 way valve)
Wire entrance
Z1C∼Z3C : Noise filter (ferrite core)
Z1F∼Z4F : Noise filter
(Back) (Front)
Notes:
1. This wiring diagram only applies to the outdoor unit
2. L: Live, N: Neutral, : Field wiring
3. : Terminal strip : Connector : Connection
: Protective earth (screw) : Relay connector
: Noiseless earth : Terminal
4. Refer to the optional manual, for connection wiring to X6A.
5. Refer to the ’wiring diagram sticker’ (on back of front plate) on how to use BS1∼BS4 and DS1 switch
6. Do not operate the unit by short-circuiting protection device S1PH
7. Colours: WHT: White / RED: Red / BLU: Blue / BRN: Brown / GRN: Green / YLW: Yellow / ORG: Orange / BLK: Black 2TW29166-1
8. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all
switches are set to be off.

51
8

1032 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

9 Sound data
9-1 Sound pressure spectrum
RZQS125CV1 - Cooling RZQS125CV1 - Heating
Sound pressure level (dB)

Sound pressure level (dB)

3TW29167-1 Octave band center frequency (Hz) 3TW29167-2 Octave band center frequency (Hz)

NOTES NOTES

1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal operation condition 2 Data is valid at nominal operation condition
3 dB(A) = A-weighted sound pressure level (A-scale 3 dB(A) = A-weighted sound pressure level (A-scale
according to IEC) according to IEC)
4 Reference acoustic pressure 0dB = 20µPa Measuring location 4 Reference acoustic pressure 0dB = 20µPa Measuring location
(discharge side) (discharge side)

RZQS140CV1 - Cooling RZQS140CV1 - Heating


51
9
Sound pressure level (dB)

Sound pressure level (dB)

3TW29177-1 Octave band center frequency (Hz) 3TW29177-2 Octave band center frequency (Hz)

NOTES NOTES

1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal operation condition 2 Data is valid at nominal operation condition
3 dB(A) = A-weighted sound pressure level (A-scale 3 dB(A) = A-weighted sound pressure level (A-scale
according to IEC) according to IEC)
4 Reference acoustic pressure 0dB = 20µPa Measuring location 4 Reference acoustic pressure 0dB = 20µPa Measuring location
(discharge side) (discharge side)

• Split Sky Air • Outdoor Units 1033


• Outdoor Units • R-410A • RZQS125-140C7V1B

9 Sound data
9-2 Sound power spectrum
RZQS125CV1 RZQS140CV1
Sound power level (dB)

Sound power level (dB)

3TW29167-3 3TW29177-3
Octave band center frequency (Hz) Octave band center frequency (Hz)

NOTES NOTES

1 dB(A) = A-weighted sound pressure level (A-scale according to IEC) 1 dB(A) = A-weighted sound pressure level (A-scale according to IEC)
2 Reference acoustic intensity 0dB = 10E-6µW/m2 2 Reference acoustic intensity 0dB = 10E-6µW/m2
3 Measured according to ISO 3744 3 Measured according to ISO 3744

51
9

1034 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQS125-140C7V1B

10 Installation
10 - 1 Installation method
RZQS125∼140C

A. Non stacked installation


Legend

Suction side obstacle

Discharge side obstacle

Left side obstacle

Right side obstacle

Top side obstacle

Obstacle is present

In these cases, close the bottom of


the installation frame to prevent
discharged air from being
bypassed.

In these cases, only 2 units can be


installed.

This situation is not allowed.

Figures between ( ) indicate the dimensions


only for the 100-125-140 class models.
B. Stacked installation

1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet

51
10

Do not stack more than one unit.


About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.

C. Multiple-row installation

1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral
connection per row

Relation of dimensions of H, A, and L are shown in the


table below.
L A
0 < L ≤ 1/2 H 150 (250)
L≤H
1/2 H < L 200 (300)
H<L Installation impossible

3TW26739-4

• Split Sky Air • Outdoor Units 1035


• Outdoor Units • R-410A • RZQS125-140C7V1B

11 Operation range

RZQS125-140C Cooling
Model name
RZQS125C7V1B
RZQS140C7V1B

Heating

Allowable range of operation (pull-down)


Outdoor temp. (°CDB)

Operation range

Allowable range of operation


Outdoor temp. (°CWB)

Operation range
(warming-up)
Indoor temp. (°CWB) Indoor temp. (°CDB)
Notes:
- Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing).
- To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed
to wind.
3TW29063-1A