Diesel Generator Set
K50 Series
1000-1200 kWe, 1250-1500 kVA Prime
Reliable and Durable Standard Scope
®
Cummins ‘K50 series’ diesel engine with strong regrindable Engine: Cummins® ‘K50 series’ direct injection, water
crankshaft, high strength connecting rod, low pressure fuel cooled engine, 16 cylinder, 4 stroke, rated at 1500 RPM,
lines, STC (Step Timing Controls) injectors and high volume conforming to ISO 3046 / IS 13018 has the following
coolant system make ‘K50 series’ generating sets, more specifications:
reliable and durable. Engines have clocked millions of hours n Cummins PT fuel pump
operating in some of the world’s most demanding conditions.
Current engines are regularly upgraded with new technologies n Cummins heavy duty ESTC injectors
for better performance and economy. The ultimate proof of n Holset turbocharger, pulse tuned exhaust manifold,
superior performance and reliability is the fact that Cummins® stainless steel exhaust flexible connections
entities worldwide source these engines from Cummins India n Radiator or heat exchanger, coolant inhibitor
for their markets.
n Plate type lube oil cooler
n Outboard aftercoolers
Unmatched Warranty n Full flow paper element filters - fuel, lube oil and by-pass
®
Cummins ‘K50 series’ diesel engine generating sets are a n Dry type replaceable paper element air cleaner with
truly cost effective solution to long term power need backed restriction indicator
by industry best, 2 years / 5000 hrs warranty, for the entire n Flywheel housing & flywheel to suit single / double bearing
generating set. alternator
With superior experience in technology, design capability and n Holset flexible coupling for double bearing alternator
commitment reliability and quality we offer an unmatched n Starting motor - Electric, battery charging alternator
5 years or 5000 hours (including above 2 years) warranty n Cummins PowerCommand® microprocessor based genset
coverage on 5 critical components (5C) of the engine – controller
Cylinder Head, Camshaft, Crankshaft, Cylinder Block,
Connecting Rod against manufacturing defect. n First fill lube oil and coolant
Alternator: Stamford brushless alternator
Cummins Advantage
n Seperately excited, self-regulated - Class ‘H’ insulation
Special features of Cummins® ‘K50 series’ engines like STC
(Step Timing Controls) injectors, low temperature aftercooler, n Salient pole revolving field
square cumbustion chamber, optimised turbocharging and n Single bearing
precision heavy duty camshaft make these engines the n PMG standard
ultimate in exceptional fuel efficiency all across the operating n Space heater & RTD & BTD’s only sensor -
range. (without scanner)
Accessories:
Single Source Power Assurance
n Silencer suitably optimized to reduce noise
Design, manufacture and testing of engine, alternator and
other accessories is done by Cummins Group of companies n Sturdy base rail
for optimum performance and is backed by a countrywide n 990 ltrs. free standing fuel tank
product support network with a single source responsibility for n 4x12 V dry, uncharged batteries with connecting leads
the entire package. and terminals
Diesel Generator Set K50 Series Specification Sheet
Optionals Alternator Data
Engine: Oil/Coolant heater, No cool, PHE, Air starter n Line-to-neutral and line-to-line AC volts
n 3-phase AC current
Alternator: Double Bearing
n Frequency
Control Panel: PC3.3- Bargraph for PC3.3 Panel with kW, Power
factor, Frequency, Current, Voltage - Remote HMI AMF control n kW, kvar, power factor kVA (three phase and total)
panel, Battery charger, Remote/Auto start panel, Auto/ Manual
synchronizing panel, Audio/Visual annunciation for faults, Auxiliary Engine Data
output relays and remote annunciators. n DC voltage
n Engine speed
n Lube oil pressure
Control panel: n Coolant temperature/ low level
PowerCommand® PC 3.3 n Comprehensive FAE data (where applicable)
The PowerCommand® control
system is an integrated Other Data
microprocessor based generator n Genset model data
set control system providing n Start attempts, starts, running hours, kW hours
voltage regulation, engine
n Load profile (operating hours at % load in 5% increments)
protection, alternator protection,
operator interface and isochronous n Fault history
governing. n Data logging and fault simulation (requires InPower)
Standard control functions
AmpSentryTM - Includes integral AmpSentryTM protection, which Digital Governing
provides a full range of alternator protection function which are n Integrated digital electronic isochronous governor
matched to the alternator provided.
n Temperature dynamic governing
Power Management - Control function provides battery
monitoring, testing and a smart starting control system. Digital Voltage Regulation
Advanced Control Methodology - Three phase sensing, n Integrated digital electronic voltage regulator
FET based full wave rectified voltage regulation and a PWM output n 3-phase, 4-wire line-to-line sensing
for stable operation with all load types.
n Configurable torque matching
Communications Interface - Control comes standard with
PCCNet and Modbus interface. AmpSentryTM AC Protection
Regulation Compliant - Prototype tested: UL, CSA and n AmpSentryTM protective relay
CE compliant. n Over current and short circuit shutdown
Service - InPower™ PC-based service tool available for detailed n Over current warning
diagnostics, setup, data logging and fault simulation. n Single and three phase fault regulation
Reliable Design - For reliable operations in harsh environment. n Over and under voltage shutdown
Multi-language support n Over and under frequency shutdown
Independent of PC / laptop for setting up n Overload warning with alarm contact
n Reverse power and reverse var shutdown
Operator panel features n Field overload
Operator panel features - The operator panel, in addition
to the alternator, displays the Utility/ AC Bus data. Engine protection
n Battery voltage monitoring, protection and testing
Operator / Display Functions
n 320 x 240 pixels graphic LED backlight LCD with bar graph
n Over speed shutdown
for displaying electrical parameters n Low oil pressure warning and shutdown
n Auto, manual, start, stop, fault reset and lamp test/panel n High coolant temperature warning and shutdown
lamp switches n Low coolant level warning or shutdown
n Alpha-numeric display with pushbuttons n Low coolant temperature warning
n LED lamps indicating genset running, remote start, not in auto, n Fail to start (over crank) shutdown
common shutdown, common warning, manual run mode, n Fail to crank shutdown
auto mode and stop
n Cranking lockout
n Sensor failure indication
Paralleling Control Functions
n Low fuel level warning or shutdown
n Digital frequency synchronization and voltage matching
n Isochronous kW and kvar load sharing controls
Telematics Offerings
n Droop kW and kvar control
n Fault Code Alerts on Email & SMS
n Sync check
n Advisory Services
n Extended paralleling (Peak Shave/Base Load)
n Fuel Level Monitoring on Email & SMS
n Digital power transfer control (AMF) provides load transfer
n Multiple Gensets Central Monitoring
operation in open or closed transition or soft (ramping)
transfer mode n Automatic Reports Generation
Diesel Generator Set K50 Series Specification Sheet
Control functions
n Time delay start and cool down
n Real time clock for fault and event time stamping
n Exerciser clock and time of day start/stop
n Data logging
n Cycle cranking
n Load shed/ dump as per configurable priority
n Configurable inputs and outputs (4)
n Remote emergency stop
Options
n Auxiliary output relays and remote annunciators
Technical Data
Generator set specifications
Model C1250 D5 P C1500 D5 P
Prime Power Rating kVA 1250 1500
Output Voltage and Frequency 415 Volts, 50 Hz 415 Volts, 50 Hz
Power Factor 0.8 (lag) 0.8 (lag)
No. of phases 3 phase 3 phase
Engine specifications
Make Cummins Cummins
Model KTA 50 G3 KTA 50 G8-I
No. of cylinders 16 ‘Vee’ 16 ‘Vee’
Aspiration Turbocharged-Aftercooled Turbocharged-Aftercooled
Bore and Stroke 159 mm x 159 mm 159 mm x 159 mm
Displacement 50.3 ltrs 50.3 ltrs
Output - Prime 1470 bhp (1097 kWm) 1735 bhp (1294 kWm)
Fuel consumption @ 75% load with Radiator & Fan 190.8 ltr/hr 231 ltr/hr
Fuel consumption @ 100% load with Radiator & Fan 251.8 ltr/hr 301.7 ltr/hr
Total wet weight ( engine + radiator) 6824 kg 7205 kg
Length x Width x Height (engine) 2978 x 2080 x 1780 mm 2978 x 2080 x 1780 mm
Compression Ratio 13.9:1 14.9 : 1
Piston Speed 7.95 m/s 7.95 m/s
Governor / Class Electronic / A1 Electronic / A1
Lubricating oil sytem capacity 177 ltrs 177 ltrs
Coolant capacity (engine + radiator) 440 ltrs 510 ltrs
Combustion air intake @ 100% load (+/- 5%) 81.6 m3/min 95.5 m3/min
Fan air flow across radiator 27357 ltrs/sec 28400 ltrs/sec
Exhaust Temperature 529oC 481oC
Alternator specifications
Make Stamford Stamford
Frame size / Model No. HCK6Z S7L1D-C41
Voltage Regulation + 0.5% + 0.5%
Insulation Class H Class H
Standard Enclosure IP 23 IP 23
Winding Pitch 2 / 3 Pitch 2 / 3 Pitch
Stator Winding Double layer lap Double layer lap
Rotor Dynamically balanced Dynamically balanced
Wave form distortion No load < 1.8 %, no No load < 1.8 %,
distorting / balanced linear load < 5 % distorting / balanced linear load < 5 %
Telephone interference Factor Better than 50 Better than 50
Total Harmonic Factor Better than 2% Better than 2%
Conformance standards
n IS/IEC 60034-1 n IS 1460 n ISO 8528 n ISO 3046 n IS 13018 n ISO 9001
Rating definitions
Prime Power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent
overload capability is available in accordance with ISO 3046.
n Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460
n Fuel consumption tolerance is +5%
Diesel Generator Set K50 Series Specification Sheet
Typical Open Genset Dimensions
Genset Rating Length Width Height Wet Weight## Std. Fuel Tank Capacity
Mode (kVA) (mm) (mm) (mm) (kgs.) Capacity (Ltrs - External)
C1250 D5 P 1250 kVA 5212 2179 3001 11235 990
C1500 D5 P 1500 kVA 5380 2513 3219 13476 990
##Approximate Weight
Authorised Representative
Cummins Power Generation Offices
Bengaluru: Tel.: (080) 2325 9161 / 63, 2325 9165 / 67
Fax: (080) 2325 9164
Chandigarh: Tel.: (0172) 224 0371-73
Fax: (0172) 224 0372
Chennai: Tel.: (044) 2446 8110 / 2446 8113
Fax: (044) 2491 1120
Gurgaon: Tel.: (0124) 391 0900-01
Fax : (0124) 391 0916
Hyderabad: Tel.: (040) 2340 9970 / 2340 9980
Fax. (040) 2340 9990
Jaipur: Tel.: (0141) 236 4944
Fax: (0141) 403 8794
Kolkata: Tel.: (033) 2287 8065 / 2287 2481
Fax: (033) 2290 3839
Lucknow: Tel.: (0522) 230 5049 / 230 5059
Fax: (0522) 230 5035
Mohali: Tel.: (0172) 224 0371 / 72 / 73
Fax: (0172) 224 0371 / 72 / 73
Vadodara: Tel.: (0265) 233 0627 / 3053627
Fax: (0265) 234 0623
https://www.facebook.com/cumminsindiaofficial/
https://www.instagram.com/cumminsindiaofficial/
Cummins India Limited
Power Systems Business Unit
https://www.cummins.com/en/in/products/diesel-generators Cummins India Office Campus
Tower-A, 8th Floor, S. No. 21,
Balewadi, Pune - 411 045 (India)
“Our energy working for you.”
Phone: +91 20 6706 7000
Cummins is registered trademarks of Cummins Inc. Toll Free: 1800-210-2525*
Specifications are subject to change without notice. Email:
[email protected]PSBU/020/K50/1250-1500kVA/HD/MP/Revision-4 www.cummins.com