14 Test Equipment and Accessories / 7PA
7PA30 Three-phase
Trip circuit supervision
Description
The relay is for supervision of the trip cir-
cuit of a circuit breaker with three selective
trip coils. The trip circuit wiring is super-
vised from the positive supply to the nega-
tive supply whilst the circuit breaker is
open or closed.
Functions
The design, quality and rugged construc-
tion of the relay make it suitable for appli-
cations requiring high levels of reliability/
dependability. The high degree of
protection guarantees reliable operation
over a wide temperature range, even under
extreme environmental conditions.
The relay has been tested in accordance
with IEC, EN and IEEE standards. The re-
lay is CE marked. The supervision current
is always less than 1.4 mA thus avoiding
unwanted operation of the trip coil. Cor-
rect operation is shown via a green LED.
Fig. 14/8 Connection diagram for 3-phase relay
Standard voltages and consumption
VN Voltage range Consumption Impedance Pickup
per phase Drop out Voltage
V DC V DC mA kΩ/s V DC
24/30 18 - 33 35 20 between 12 and 18
60 42 - 66 20 44 36 and 42
110/125 77 - 138 20 94 66 and 77
220 154 - 275 15 200 132 and 154
Drop-out time: between 150 ms and 400 ms
Selection and ordering data Description Order No.
7PA30 trip circuit supervision (three-phase) 7PA30o2-3AA00-o
Auxiliary voltage
24/30 V DC 1
60 V DC 2
110/125 V DC 3
220 V DC 4
14
Socket
without socket 0
with flush-mounting socket 7XP9010-4 1
with surface-mounting socket 7XP9012-0 2
Accessories Description Order No.
Socket as spare part
Flush mounting 7XP9010-4
Surface mounting 7XP9012-0
14/12 Siemens SIP · Edition No. 6
14 Test Equipment and Accessories / 7PA
7PA30 Single-phase
Trip circuit supervision
Description
The relay is for supervision of the trip cir-
cuit of a circuit breaker with one trip coil.
The trip circuit wiring is supervised from
the positive supply to the negative supply
whilst the circuit breaker is open or closed.
Functions
The design, quality and rugged construc-
tion of the relay make it suitable for appli-
cations requiring high levels of reliability/
dependability. The high degree of
protection guarantees reliable operation
over a wide temperature range, even under
extreme environmental conditions.
The relay has been tested in accordance
with IEC, EN and IEEE standards. The re-
lay is CE marked. The supervision current Fig. 14/9 Connection diagram for 1-phase relay
is always less than 1.4 mA thus avoiding
unwanted operation of the trip coil. Cor-
rect operation is shown via a green LED. Standard voltages and consumption
VN Voltage range Consumption Impedance Pickup
per phase Drop out Voltage
V DC V DC mA kΩ/s V DC
14/30 18 - 33 32 20 between 12 and 18
60 42 - 66 18 44 36 and 42
110/125 77 - 138 18 94 66 and 77
220 154 - 275 13 200 132 and 154
Drop-out time: between 150 ms and 400 ms
Selection and ordering data Description Order No.
7PA30 trip circuit supervision (single-phase) 7PA30o2-1AA00-o
Auxiliary voltage
24/30 V DC 1
60 V DC 2
110/125 V DC 3
220 V DC 4
Socket
without socket 0
with flush-mounting socket 7XP9011-0 1
with surface-mounting socket 7XP9013-0 2
14
Accessories Description Order No.
Socket as spare part
Flush mounting 7XP9011-0
Surface mounting 7XP9013-0
Siemens SIP · Edition No. 6 14/13