SM6 Schneider
SM6 Schneider
All control functions are centralised on a front plate, thus simplifying operation.
PM108615
Altitude
• Less than or equal to 1000 m
• Above 1000 m, a derating coefficient is applied (please consult us).
Solar radiation
• No solar radiation influence is permitted.
Humidity
• Average relative humidity over a 24 hour period, less than or equal to 95%
• Average relative humidity over a 1 month period, less than or equal to 90%
• Average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa
• Average vapor pressure over a 1 month period, less than or equal to 1.8 kPa.
IEC standards
SM6 units meet all the following
standards and specifications: 62271-200 High-voltage switchgear and controlgear - Part 200:
A.C. metal-enclosed switchgear and controlgear for rated voltage
• IEC standards above 1 kV and up to and including 52 kV.
• UTE standards for SM6-24 62271-1 High-voltage switchgear and controlgear - Part 1:
• EDF specifications for SM6-24 Common specifications.
• SEISMIC standards for 24 kV 62271-103 High voltage switches - Part 1: switches for rated voltages above
1 kV and less or equal to 52 kV.
62271-105 High-voltage switchgear and controlgear - Part 105:
High voltage alternating current switch-fuse combinations.
60255 Electrical relays.
62271-100 High-voltage switchgear and controlgear - Part 100:
High-voltage alternating current circuit breakers.
62271-102 High-voltage switchgear and controlgear - Part 102: High-voltage
alternating current disconnectors and earthing switches.
61869-2 Instrument transformers - Part 1: Current transformers.
61869-3 Instrument transformers - Part 2: Voltage transformers.
60044-8 Instrument transformers - Part 8: Low Power Current Transducers.
62271-206 High-voltage prefabricated switchgear and controlgear assemblies
- Voltage presence indicating systems.
62271-304 High-voltage switchgear and controlgear - Part 304:
Design classes for indoor enclosed switchgear and controlgear for
rated voltages above 1 kV up to and including 52 kV to be used in
severe climatic conditions.
The hereunder values are for working temperatures from -5°C up to +40°C
PM108616
Electrical characteristics
Rated voltage Ur kV 7.2 12 17.5 24 36
Insulation level
Insulation Ud 50/60 Hz, 1 min (kV rms) 20 28 38 50 70
Isolation Ud 50/60 Hz, 1 min (kV rms) 23 32 45 60 80
Insulation Up 1.2/50 µs (kV peak) 60 75 95 125 170
Isolation Up 1.2/50 µs (kV peak) 70 85 110 145 195
Breaking capacity
Transformer off load A 16
Cables off load A 31.5 50
Rated current Ir A 400 - 630 -1250 630-1250
Short-time withstand current Ik/tk (1) kA /1 s 25 630 - 1250 1250
20 (2) 630 - 1250
16 630 - 1250
12.5 400 - 630 - 1250 630-1250
Making capacity (50 Hz) Ima kA 62.5 630 NA
50 630
40 630
31.25 400 - 630 630
Maximum breaking capacity (Isc)
Units IM, IMC, IMB, IMM A 630 - 800 (3) 630
NSM-cables, NSM-busbars A 630 - 800 (3) NA
QM, QMC, QMB kA 25 20 20
PM kA 25 20
CVM kA 6.3 NA
CVM with fuses kA 25 NA
SF6 circuit breaker range 7.2 12 17.5 24 36
DM1-A, DM1-D, DM1-W kA 25 630-1250 1250
20 630-1250
DM1-S, DM1-M kA 25 630 NA
DM1-Z 25 1250 NA
DM2 kA 20 630
25 630 1250
Vacuum circuit breaker range 7.2 12 17.5 24 36
DMV-A, DMV-D kA 25 630-1250 NA
DMVL-A kA 20 630 NA
DMVL-D kA 25 630 NA
NA: Non Available
(1) 3 phases
(2) In 20 kA / 3 s for SM6-24 only, consult us
(3) In 800 A, consult us.
Endurance
PM108616
Protection index
• Classes: PI (insulating partition)
• Loss of service continuity classes: LSC2A (LSC1 for metering GAM/GBM
functions)
• Units in switchboard: IP3X
• Between compartments: IP2X for SM6-24, IP2XC for SM6-36
• Cubicle: IK08 for SM6-24, IK07 for SM6-36.
Electro-magnetic compatibility
• Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4
• Compartments:
Electrical field: • 40 dB attenuation at 100 MHz
• 20 dB attenuation at 200 MHz
Magnetic field: • 20 dB attenuation below 30 MHz
According to standards IEEE-693/2005 and EN 60068-3/1993
• For 36 kV (please contact us).
Temperatures
The cubicles must be stored and installed in a dry area free from dust and with
limited temperature variations.
• For storage: from -40°C to +70°C
• For working: from -5°C to +40°C
• Other temperatures, consult us.
Seismic for 24 kV (option)
• Up to 0.5 g (horizontal) and 0.4 g (vertical)
• Class 2
5 Low voltage Installation of compact relay devices (VIP) and test terminal
boxes.
If more space is required, an additional enclosure may be
added on top of the cubicle
5 Low voltage Installation of compact relay devices (VIP) and test terminal
boxes.
If more space is required, an additional enclosure may be
added on top of the cubicle.
Contactor cubicles
DE58650b
Busbar compartment
DE53507_LG
PM108617
The three insulated busbars are parallel-mounted. Connection is made to the upper
pads of the enclosure using a field distributor with integrated captive screws.
Ratings 400 (for SM6-24 only) - 630 - 1250 A.
Switching device
DE53508_LG
PM108618
This device is separated from the busbar compartment and the connection
compartment by the enclosure surrounding the switch, the disconnector and
the earthing switch.
Connection compartment
DE57172_LG
DE53510_LG
With basic equipment, the maximum allowable cross-section for cable is:
• 630 mm2 or 2 x 400 mm2 for 1250 A incoming or outgoing units
SF6 and vacuum lateral type Frontal vacuum type • 240 mm2 or 2 x 240 mm2 for incoming or outgoing units 400 - 630 A
circuit breaker circuit breaker
• 95 mm2 for transformer protection cubicles incorporating fuses.
See in functional units characteristics chapter for each unit allowable section. / The earthing switch must be closed before the cubicle may be
accessed. / The reduced depth of the cubicle makes for easy connection of all phases. / A stud incorporated in the field distributor makes it
possible to position and secure the cable-end lug with a single hand.
Operating-mechanism cover
DE57173_LG
PM108619
LV LV LV LV
cover wiring duct wiring duct control cabinet
B2 LV wiring duct and cabinet (240 mm): Enables a large majority of low
Height (mm): voltage to be installed.
1600 1690 1840 2050 It also takes the thermal monitoring, VAMP121.
Low Voltage option
90 240 450 C LV control cabinet: This is only used for larger low voltage accessories or
those with a depth greater than 100 mm or complex equipment, such as
Easergy Sepam series 60 or series 80, converters, control and monitoring units,
450 mm
DM105321
C
In all cases, these volumes are accessible, with cables and busbars energised,
B2 without de-energising the substation.
B1
A
A/B LV cover
B LV control cabinet: This can be used for larger low voltage accessories or
h (mm): 2250
those with a depth greater than 100 mm or complex equipment, such as
Easergy Sepam series 60 or series 80, converters, control and monitoring units,
regulating transformers or dual secondary transformers.
In all cases, these volumes are accessible, with cables and busbars energised,
without de-energising the substation.
360
DM107500
1760
Switching
DM107471
DM107472
DM107473
DM107474
IM IMC IMB IMM
Switch unit Switch unit Switch unit with earthing Switch and measurement unit,
SM6-24: 375 or 500 mm SM6-24: 500 mm disconnector, right or left outgoing line
SM6-36: 750 mm SM6-36: 750 mm right or left outgoing line SM6-24: 750 mm
SM6-24: 375 mm
SM6-36: 750 mm
DM107476
NSM-cables NSM-busbars
Cables power supply Busbars power supply
for main incoming line for main incoming line on right or left
and standby line and cables for standby line
SM6-24: 750 mm SM6-24: 750 mm
Fuse-switch
DM107477
DM107478
DM107479
QM QMC QMB
Fuse-switch combination unit Fuse-switch combination unit Fuse-switch combination unit
SM6-24: 375 or 500 mm SM6-24: 625 mm right or left outgoing line
SM6-36: 750 mm SM6-36: 1000 mm SM6-24: 375 mm
SM6-36: 750 mm
DM107480
PM
Fuse-switch unit
SM6-24: 375 mm
SM6-36: 750 mm
SF6 circuit-breaker
DM107481
DM107482
DM107483
Provided as standard / Other possibility / (1) Only SM6-36 / (2) 1250 A version
Earthing-switch function
• Independent-operation opening or closing by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
Auxiliary contacts
• Switch (2 O + 2 C) *
• Switch (2 O + 3 C) and earthing switch (1 O + 1 C)
• Switch (1 C) and earthing switch (1 O + 1 C) if motor option
Mechanical indications
• Fuses blown in unit PM
Motor option
• Motor severe environment and communication
(*) Included with the motor option
DE53531_LG
DE53532_LG
DE53533_LG
DM105324
DE59715_LG
DE59212_LG
Electrical
characteristics
and disconnector
150 W heating element For SM6-36 For SM6-36 For SM6-36 For SM6-36
LSC2A p p p p
Connection pads for dry-type cables p p
Downstream earthing switch 2 kA rms making
capacity at 630 A and 25 kA rms making p
capacity at 1250 A
Three-phase bottom busbars p p
Equipment for three UTE (for SM6-24) or DIN
p
striker fuses
Version
LPCT Only with Easergy Sepam series 20, 40, 60, 80
SFset circuit breaker disconnectable
For SM6-24 For SM6-24 For SM6-24
(For 400-630 A performances)
Arc detection p p p p
Thermal monitoring p p p p
630 A busbars earthing switch cabinet (not
For SM6-24 For SM6-24
available for internal arc IEC62271-200)
Ambient monitoring p p p
Auxiliary contacts on the disconnector p p p
Protection p (Easergy Sepam & Easergy P3 relay programmable electronic units)
Cubicle options
IM Switch unit IMC Switch unit IMB Switch unit with IMM Switch and
earthing switch, right measurement unit, right
SM6 Type Im --> or left outgoing or left outgoing line
DE59700_LG
DE53518_LG
DE53519_LG
DE59700_LG
DE59710_LG
DE59711_LG
DE59212_LG
kA Ik/1s kA Ima
25 62.5
Electrical 20
Ir = 630 A
50
characteristics Ir = 630 A
16 40
150 W heating element For SM6-36 For SM6-36 For SM6-36 For SM6-36
LSC2A p p p p
Connection pads for dry-type cables p p
Three-phase bottom busbars for outgoing lines p (right or left) p (right or left)
1 to 3 CTs, for SM6-24 /
Current transformers 3 CTs
3 CTs, for SM6-36
Version
CI2 operating mechanism (1) p p p p
CI1 operating mechanism (1) p For SM6-36 p p
Digital ammeter p
Surge arresters (2) p
630 A busbars earthing switch cabinet (3) For SM6-24
Ambient monitoring p
Earth fault indicators p p
Connection pads for two dry-type single-core
p p
cables for 36 kV
Motor for operating mechanism p p p
Motor with severe and communication p p p
Auxiliary contacts p p p
Key-type interlocks p p p
Cubicle options
(1) IM / IMC: In 800 A version for SM6-24, please consult us / (2) For SM6-36 and for SM6-24 in 500 mm width cubicle / (3) Not available for internal arc IEC62271-200