SM6 Schneider

The document provides information about SM6 units including their general characteristics, operating conditions, standards, and main electrical and mechanical characteristics. The units are designed for indoor installation and have compact dimensions. They can operate in temperatures from -5°C to 40°C and altitudes up to 1000m.

Uploaded by

Ben Davis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
325 views16 pages

SM6 Schneider

The document provides information about SM6 units including their general characteristics, operating conditions, standards, and main electrical and mechanical characteristics. The units are designed for indoor installation and have compact dimensions. They can operate in temperatures from -5°C to 40°C and altitudes up to 1000m.

Uploaded by

Ben Davis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

General characteristics Operating conditions

SM6 units are designed for indoor installations.


In addition to its technical characteristics,
SM6 meets requirements concerning Their compact dimensions are:
safety of life and property as well as ease • 375 to 1500 mm width
of installation, operation and protecting • 1600 to 2250 mm height
the environment.
• 840 to 1400 mm depth…
… this makes for easy installation in small rooms or prefabricated substations.

Cables are connected via the front.

All control functions are centralised on a front plate, thus simplifying operation.
PM108615

The units may be equipped with a number of accessories (relays, toroids,


instrument transformers, surge arrester, control and monitoring, etc.).

Normal operating conditions


Ambient air temperature
• Less than or equal to 40°C
• Less than or equal to 35°C on average over 24 hours
• Greater or equal to –5°C.

Altitude
• Less than or equal to 1000 m
• Above 1000 m, a derating coefficient is applied (please consult us).

Solar radiation
• No solar radiation influence is permitted.

Ambient air pollution


• No significant pollution by dust, smoke, corrosive and/or flammable gases,
vapours or salt.

Humidity
• Average relative humidity over a 24 hour period, less than or equal to 95%
• Average relative humidity over a 1 month period, less than or equal to 90%
• Average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa
• Average vapor pressure over a 1 month period, less than or equal to 1.8 kPa.

For these conditions, condensation may occasionally occur. Condensation can be


expected where sudden temperature changes occur in periods of high humidity.
To withstand the effects of high humidity and condensation, such as breakdown of
insulation, please pay attention on Civil Engineering recommendations for design
of the building or housing, by suitable ventilation and installation.

Seismic (for 24 Kv and 36 kV):


• Up to 0.5 g (horizontal) and 0.4 g (vertical)
• Class 2 for 24 kV and Class 1 for 36kV
• According to standards IEEE-693/2005 and EN 60068-3/1993 for the
24 kV and 36 kV

Severe operating conditions (please consult us).

38 | SM6 Catalog schneider-electric.com


General characteristics Standards

IEC standards
SM6 units meet all the following
standards and specifications: 62271-200 High-voltage switchgear and controlgear - Part 200:
A.C. metal-enclosed switchgear and controlgear for rated voltage
• IEC standards above 1 kV and up to and including 52 kV.
• UTE standards for SM6-24 62271-1 High-voltage switchgear and controlgear - Part 1:
• EDF specifications for SM6-24 Common specifications.
• SEISMIC standards for 24 kV 62271-103 High voltage switches - Part 1: switches for rated voltages above
1 kV and less or equal to 52 kV.
62271-105 High-voltage switchgear and controlgear - Part 105:
High voltage alternating current switch-fuse combinations.
60255 Electrical relays.
62271-100 High-voltage switchgear and controlgear - Part 100:
High-voltage alternating current circuit breakers.
62271-102 High-voltage switchgear and controlgear - Part 102: High-voltage
alternating current disconnectors and earthing switches.
61869-2 Instrument transformers - Part 1: Current transformers.
61869-3 Instrument transformers - Part 2: Voltage transformers.
60044-8 Instrument transformers - Part 8: Low Power Current Transducers.
62271-206 High-voltage prefabricated switchgear and controlgear assemblies
- Voltage presence indicating systems.
62271-304 High-voltage switchgear and controlgear - Part 304:
Design classes for indoor enclosed switchgear and controlgear for
rated voltages above 1 kV up to and including 52 kV to be used in
severe climatic conditions.

SEISMIC standards for 24kV


IEE-693 2005 IEEE Recommended Practice for Seismic Design of
Substations
EN600068-3-3 1993 Environmental testing-Part 3:
guidance, Seismic test methods for equipments

UTE standards for 24 kV


NFC 13.100 Consumer substation installed inside a building and fed by
a second category voltage public distribution system.
NFC 13.200 High voltage electrical installations requirements.
NFC 64.130 High voltage switches for rated voltage above 1 kV and less
than 52 kV.
NFC 64.160. Alternating current disconnectors and earthing switches

schneider-electric.com SM6 Catalog | 39


General characteristics Main characteristics

The hereunder values are for working temperatures from -5°C up to +40°C
PM108616

and for a setting up at an altitude below 1000 m.

Electrical characteristics
Rated voltage Ur kV 7.2 12 17.5 24 36
Insulation level
Insulation Ud 50/60 Hz, 1 min (kV rms) 20 28 38 50 70
Isolation Ud 50/60 Hz, 1 min (kV rms) 23 32 45 60 80
Insulation Up 1.2/50 µs (kV peak) 60 75 95 125 170
Isolation Up 1.2/50 µs (kV peak) 70 85 110 145 195
Breaking capacity
Transformer off load A 16
Cables off load A 31.5 50
Rated current Ir A 400 - 630 -1250 630-1250
Short-time withstand current Ik/tk (1) kA /1 s 25 630 - 1250 1250
20 (2) 630 - 1250
16 630 - 1250
12.5 400 - 630 - 1250 630-1250
Making capacity (50 Hz) Ima kA 62.5 630 NA
50 630
40 630
31.25 400 - 630 630
Maximum breaking capacity (Isc)
Units IM, IMC, IMB, IMM A 630 - 800 (3) 630
NSM-cables, NSM-busbars A 630 - 800 (3) NA
QM, QMC, QMB kA 25 20 20
PM kA 25 20
CVM kA 6.3 NA
CVM with fuses kA 25 NA
SF6 circuit breaker range 7.2 12 17.5 24 36
DM1-A, DM1-D, DM1-W kA 25 630-1250 1250
20 630-1250
DM1-S, DM1-M kA 25 630 NA
DM1-Z 25 1250 NA
DM2 kA 20 630
25 630 1250
Vacuum circuit breaker range 7.2 12 17.5 24 36
DMV-A, DMV-D kA 25 630-1250 NA
DMVL-A kA 20 630 NA
DMVL-D kA 25 630 NA
NA: Non Available
(1) 3 phases
(2) In 20 kA / 3 s for SM6-24 only, consult us
(3) In 800 A, consult us.

40 | SM6 Catalog schneider-electric.com


General characteristics Main characteristics

Endurance
PM108616

Units Mechanical endurance Electrical endurance


IM, IMC, IMB, IMM , PM, IEC 62271-103 IEC 62271-103
QM (1), QMC (1), QMB (1), 1 000 operations 100 breaks at Ir,
NSM-cables, NSM-busbars class M1 p.f. = 0.7, class E3

CVM Disconnector IEC 62271-102


1 000 operations

Vacuum contactor IEC 60470 IEC 60470


2 500 000 operations 250 000 breaks at Ir
250 000 with mechanical latching
SF6 circuit breaker range
DM1-A, Disconnector IEC 62271-102
DM1-D, 1 000 operations
DM1-M,
DM1-W, SF circuit breaker IEC 62271-100 IEC 60271- 016
DM1-Z, 10 000 operations 30 breaks at 12.5 kA for SM6-24
DM1-S, class M2 25 breaks at 25 kA for SM6-24
DM2 40 breaks at 16 kA for SM6-36
15 breaks at 25 kA for SM6-36
10 000 breaks at Ir,
p.f. = 0.7, class E2

Operating sequence O - 0.3 s - CO - 15 s - CO


O - 0.3 s - CO - 3 mn
O - 3 mn - CO - 3 mn - CO
Vacuum circuit breaker range
DMV-A, Switch IEC 62271-103 IEC 62271-103
DMV-D 1 000 operations 100 breaks at Ir,
class M1 p.f. = 0.7, class E3
Evolis circuit IEC 62271-100 IEC 62271-100
breaker 10 000 operations 100 breaks at 25kA for SM6-24 10 000
class M2 breaks at Ir,
p.f. = 0.7, class E2
DMVL-A Disconnector IEC 62271-102
DMVL-D 1 000 operations
Evolis circuit IEC 62271-100 IEC 62271-100
breaker 10 000 operations 100 breaks at 16kA for SM6-24
class M2 100 breaks at 25kA for SM6-24 10 000
breaks at Ir,
p.f. = 0.7, class E2
(1) As per recommendation IEC 62271-105, three breakings at p.f. = 0.2
800 A under 36 kV; 1400 A under 24 kV; 1730 A under 12 kV; 2600 A under 5.5 kV.

Internal arc withstand (in accordance with IEC 62271-200)


SM6-24 Basic • 12.5 kA 1 s, IAC: A-FL
• 12.5 kA 1 s, IAC: A-FLR
Advance • 16 kA 1 s, IAC: A-FLR & IAC: A-FL

• 20 kA 1 s, IAC: A-FLR & IAC: A-FL


SM6-36 • 16 kA 1 s, IAC: A-FL

schneider-electric.com SM6 Catalog | 41


General characteristics Main characteristics

Protection index
• Classes: PI (insulating partition)
• Loss of service continuity classes: LSC2A (LSC1 for metering GAM/GBM
functions)
• Units in switchboard: IP3X
• Between compartments: IP2X for SM6-24, IP2XC for SM6-36
• Cubicle: IK08 for SM6-24, IK07 for SM6-36.
Electro-magnetic compatibility
• Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4
• Compartments:
Electrical field: • 40 dB attenuation at 100 MHz
• 20 dB attenuation at 200 MHz
Magnetic field: • 20 dB attenuation below 30 MHz
According to standards IEEE-693/2005 and EN 60068-3/1993
• For 36 kV (please contact us).
Temperatures
The cubicles must be stored and installed in a dry area free from dust and with
limited temperature variations.
• For storage: from -40°C to +70°C
• For working: from -5°C to +40°C
• Other temperatures, consult us.
Seismic for 24 kV (option)
• Up to 0.5 g (horizontal) and 0.4 g (vertical)
• Class 2

42 | SM6 Catalog schneider-electric.com


General characteristics Factory-built cubicles
description

Switch and fuse protection cubicles


1 Switchgear Switch-disconnector and earthing switch in an enclosure filled
DE58646b

with SF6 and satisfying "sealed pressure system"


requirements
2

1 5 2 Busbars All in the same horizontal plane, thus enabling later


switchboard extensions and connection to existing
equipment.
4
3 Connection Accessible through front, connection to the lower switch-
disconnector and earthing switch terminals
(IM cubicles) or the lower fuse-holders (PM and QM
cubicles). This compartment is also equipped with an
earthing switch downstream from the MV fuses for the
protection units.

4 Operating Contains the elements used to operate the switch-


mechanism disconnector and earthing switch and actuate the
3
corresponding indications (positive break).

5 Low voltage Installation of a terminal block (if motor option installed),


LV fuses and compact relay devices.
If more space is required, an additional enclosure may be
added on top of the cubicle.

Options: Please, refer to the chapter "Characteristics of the functional units".

SF6 circuit breaker cubicles


DE58647b

1 Switchgear Disconnector(s) and earthing switch(es), in enclosures filled


with SF6 and satisfying "sealed pressure system"
2 requirements.
1 5 2 Busbars All in the same horizontal plane, thus enabling later
switchboard extensions and connection to existing
4 equipment.

3 Connection Accessible through front, connection to the downstream


and switchgear terminals of the circuit breaker.
Two circuit breaker offers are possible:
• SF1: combined with an electronic relay and standard
3 sensors (with or without
1 an auxiliary power supply
• SFset: autonomous set equipped with an electronic
protection system and special sensors (requiring no
auxiliary power supply).

4 Operating Contains the elements used to operate the disconnector(s),


mechanism the circuit breaker and the earthing switch and actuate the
corresponding indications.

5 Low voltage Installation of compact relay devices (Statimax) and test


terminal boxes. If more space is required, an additional
enclosure may be added on top
of the cubicle.

Options: Please, refer to the chapter "Characteristics of the functional units".

schneider-electric.com SM6 Catalog | 43


General characteristics Factory-built cubicles
description
DE58648b

Frontal vacuum type circuit breaker cubicles


2
5 1 Switchgear Load break switch and earthing switch(es), in enclosure
1
filled with SF6 and satisfying and one vacuum circuit
breaker, "sealed pressure system" requirements
4
2 Busbars All in the same horizontal plane, thus enabling later
switchboard extensions and connection to existing
equipment.
3
3 Connection Accessible through front, connection to the downstream
and switchgear terminals of the circuit breaker.
Evolis: device associated with an electronic relay and
standard sensors (with or without auxiliary source).
1
4 Operating Contains the elements used to operate the disconnector(s),
mechanism the circuit breaker and the earthing switch and actuate the
corresponding indications.

5 Low voltage Installation of compact relay devices (VIP) and test terminal
boxes.
If more space is required, an additional enclosure may be
added on top of the cubicle

Options: Please, refer to the chapter "Characteristics of the functional units".

Lateral vacuum type circuit breaker cubicles


DE58649b

1 Switchgear Disconnector(s) and earthing switch(es), in enclosure filled


2 with SF6 and satisfying and one vacuum circuit breaker,
5
1 "sealed pressure system" requirements.

2 Busbars All in the same horizontal plane, thus enabling later


4 switchboard extensions and connection to existing
equipment.

3 Connection Accessible through front, connection to the downstream


and switchgear terminals of the circuit breaker.
3 Evolis: device associated with an electronic relay and
standard sensors (with or without auxiliary source).
1 4 Operating Contains the elements used to operate the disconnector(s),
mechanism the circuit breaker and the earthing switch and actuate the
corresponding indications.

5 Low voltage Installation of compact relay devices (VIP) and test terminal
boxes.
If more space is required, an additional enclosure may be
added on top of the cubicle.

Options: Please, refer to the chapter "Characteristics of the functional units".

44 | SM6 Catalog schneider-electric.com


General characteristics Factory-built cubicles
description

Contactor cubicles
DE58650b

1 Switchgear Disconnector and earthing switch and contactor in


enclosures filled with SF6 and satisfying "sealed pressure
system" requirements.
2
1 5 2 Busbars All in the same horizontal plane, thus enabling later
switchboard extensions and connection to existing
equipment.
4
3 Connection and Accessible through front.
switchgear It is also equipped with an earthing switch downstream. The
contactor may be equipped with fuses. 2 types may be
3 used:
•• Vacuum with magnetic holding
•• Vacuum with mechanical latching.

4 Operating Contains the elements used to operate


1
mechanism the disconnector(s), the contactor and the earthing switch
4 and actuate the corresponding indications.

5 Low voltage Installation of compact relay devices and test terminal


boxes.
With basic equipment, an additional enclosure is added on
top of the cubicle.

Options: Please, refer to the chapter "Characteristics of the functional units".

schneider-electric.com SM6 Catalog | 45


General characteristics Compartments and devices
description

Busbar compartment
DE53507_LG

PM108617

The three insulated busbars are parallel-mounted. Connection is made to the upper
pads of the enclosure using a field distributor with integrated captive screws.
Ratings 400 (for SM6-24 only) - 630 - 1250 A.

Switching device
DE53508_LG

PM108618

This device is separated from the busbar compartment and the connection
compartment by the enclosure surrounding the switch, the disconnector and
the earthing switch.

Connection compartment
DE57172_LG

DE53510_LG

The network cables are connected:


• To the terminals of the switch
• To the lower fuse holders
• Or to the connection pads of the circuit breaker.

Cables may have either:


• Cold fitted cable end for dry-type

With basic equipment, the maximum allowable cross-section for cable is:
• 630 mm2 or 2 x 400 mm2 for 1250 A incoming or outgoing units
SF6 and vacuum lateral type Frontal vacuum type • 240 mm2 or 2 x 240 mm2 for incoming or outgoing units 400 - 630 A
circuit breaker circuit breaker
• 95 mm2 for transformer protection cubicles incorporating fuses.

See in functional units characteristics chapter for each unit allowable section. / The earthing switch must be closed before the cubicle may be
accessed. / The reduced depth of the cubicle makes for easy connection of all phases. / A stud incorporated in the field distributor makes it
possible to position and secure the cable-end lug with a single hand.

46 | SM6 Catalog schneider-electric.com


General characteristics Compartments and devices
description

Operating-mechanism cover
DE57173_LG

PM108619

These covers contain the various operating functions for the:


• Switch and earthing switch
• Disconnector(s)
• Circuit breaker
• Contactor
and the voltage presence indicator.
The operating-mechanism cover may be accessed with the cables and busbars
energised and without isolating the substation.
It also enables easy installation of padlocks, locks and standard LV accessories
(auxiliary contacts, trip units, motors, etc.).

Low-voltage monitoring control cabinet for SM6-24


PM108620

It enables the cubicle to be equipped with low voltage switchgear providing


protection, control, status indication and data transmission.
According to the volume, it is available in 3 versions: cover, wiring duct and cabinet.

A LV cover: Enables a very simple low voltage section to be installed such as


indication buttons, push buttons or protection relays.

B1 LV wiring duct and cabinet: Enables a large majority of low voltage


configurations to be installed. It also takes the Easergy Sepam series 20 or
A B1 B2 C series 40.

LV LV LV LV
cover wiring duct wiring duct control cabinet
B2 LV wiring duct and cabinet (240 mm): Enables a large majority of low
Height (mm): voltage to be installed.
1600 1690 1840 2050 It also takes the thermal monitoring, VAMP121.
Low Voltage option
90 240 450 C LV control cabinet: This is only used for larger low voltage accessories or
those with a depth greater than 100 mm or complex equipment, such as
Easergy Sepam series 60 or series 80, converters, control and monitoring units,
450 mm
DM105321

regulating transformers or dual secondary transformers.

C
In all cases, these volumes are accessible, with cables and busbars energised,
B2 without de-energising the substation.
B1
A

schneider-electric.com SM6 Catalog | 47


General characteristics Compartments and devices
description

Low-voltage monitoring control cabinet for SM6-36


PE58270

A LV cover: Enables a very simple low voltage section to be installed such as


indication buttons, push buttons or protection relays.The total height of the
cubicle is then 2250 mm.

A/B LV cover
B LV control cabinet: This can be used for larger low voltage accessories or
h (mm): 2250
those with a depth greater than 100 mm or complex equipment, such as
Easergy Sepam series 60 or series 80, converters, control and monitoring units,
regulating transformers or dual secondary transformers.

In all cases, these volumes are accessible, with cables and busbars energised,
without de-energising the substation.

360
DM107500

1760

48 | SM6 Catalog schneider-electric.com


General characteristics Units for switching function

Switching
DM107471

DM107472

DM107473

DM107474
IM IMC IMB IMM
Switch unit Switch unit Switch unit with earthing Switch and measurement unit,
SM6-24: 375 or 500 mm SM6-24: 500 mm disconnector, right or left outgoing line
SM6-36: 750 mm SM6-36: 750 mm right or left outgoing line SM6-24: 750 mm
SM6-24: 375 mm
SM6-36: 750 mm

Automatic transfer system


DM107475

DM107476

NSM-cables NSM-busbars
Cables power supply Busbars power supply
for main incoming line for main incoming line on right or left
and standby line and cables for standby line
SM6-24: 750 mm SM6-24: 750 mm

32 | SM6 Catalog schneider-electric.com


General characteristics Units for protection function

Fuse-switch
DM107477

DM107478

DM107479
QM QMC QMB
Fuse-switch combination unit Fuse-switch combination unit Fuse-switch combination unit
SM6-24: 375 or 500 mm SM6-24: 625 mm right or left outgoing line
SM6-36: 750 mm SM6-36: 1000 mm SM6-24: 375 mm
SM6-36: 750 mm
DM107480

PM
Fuse-switch unit
SM6-24: 375 mm
SM6-36: 750 mm

SF6 circuit-breaker
DM107481

DM107482

DM107483

DM1-A DM1-D DM1-M


Single-isolation, disconnectable Single-isolation, disconnectable circuit breaker Single-isolation,disconnectable
circuit breaker unit unit circuit breaker and measurement
SM6-24: 750 mm right or left outgoing line unit
SM6-36: 1000 mm SM6-24: 750 mm right outgoing line
SM6-36: 1000 mm SM6-24: 750 mm

schneider-electric.com SM6 Catalog | 33


Characteristics of Operating mechanisms
the functional units

Units Type of operating mechanism


The control devices required for the unit
Switch/disconnector / Circuit breaker
operating mechanisms are centralised downstream earthing switch
on the front panel. The different types of CIT CI1 CI2 CS CC RI P2
operating mechanism are presented in the IM, IMB, IMM
table opposite. IMC
(1)
Operating speeds do not depend on the PM
operator, except for the CS. QM
QMC, QMB
CM, CM2, CVM
PM108624

DM1-A, DM1-D, DM1-M, DM1-S, DM1-Z, DM2,


DMVL-A, DMVL-D
DM1-A (2), DM1-W
DMV-A, DMV-D
NSM-cables, NSM-busbars
GAM 24 kV
SM, TM, GAM 36 kV
EMB

Provided as standard / Other possibility / (1) Only SM6-36 / (2) 1250 A version

Operating mechanism types CIT CI1 CI2 CS


Load-break switch Load-break switch Load-break switch
Unit applications Disconnector
Fused switch Fuse switch combination Fuse switch combination
Mechanism
Main circuit switch Closing Opening Closing Opening Closing Opening Closing Opening
charging
Manual operating mode Hand lever Hand lever Hand lever Push button Hand lever Push button Push button Hand lever Hand lever
Electrical operating mode (option) Motor Motor Motor Coil Motor Coil Coil N/A N/A
Speed of operation 1 to 2 s 1 to 2 s 4 to 7 s 35 ms 4 to 7 s 55 ms 35 ms N/A N/A
Remote control
Remote control Remote control
Network applications network management, need of quick N/A
network management transformer protection
reconfiguration (generator source, loop)
Earthing switch Closing Opening Closing Opening N/A Closing Opening Closing Opening
Manual operating mode Hand lever Hand lever Hand lever Hand lever Hand lever Hand lever Hand lever Hand lever Hand lever

Double-function operating mechanism CIT


Switch function
• Independent-operation opening or closing by lever or motor

Earthing-switch function
• Independent-operation opening or closing by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.

Auxiliary contacts
• Switch (2 O + 2 C) *
• Switch (2 O + 3 C) and earthing switch (1 O + 1 C)
• Switch (1 C) and earthing switch (1 O + 1 C) if motor option

Mechanical indications
• Fuses blown in unit PM

Motor option
• Motor severe environment and communication
(*) Included with the motor option

68 | SM6 Catalog schneider-electric.com


Characteristics of Functional units selection
the functional units
Protection
SF6 type circuit breaker

DM1-A DM1-D DM1-D DM1-M


Single-isolation Single-isolation Single-isolation Single-isolation, disconnectable
SM6 Type DM1A --> disconnectable CB disconnectable CB. disconnectable CB. CB and measurement unit.
Outgoing line on right Outgoing line on left Outgoing line on right

DE53531_LG

DE53532_LG

DE53533_LG

DM105324
DE59715_LG

DE59212_LG
Electrical
characteristics

SF1 disconnectable circuit breaker p p p p


Disconnector and earthing switch p p p p
Three-phase busbars p p p p
Circuit breaker operating mechanism RI p p p p
Disconnector operating mechanism CS p p p p
Voltage presence indicator p p p p
Current transformers 3 CTs 3 CTs 3 CTs Please consult us
Auxiliary contacts on circuit breaker p p p p
Mechanical interlocking between circuit breaker
p p p p
Basic equipment

and disconnector
150 W heating element For SM6-36 For SM6-36 For SM6-36 For SM6-36
LSC2A p p p p
Connection pads for dry-type cables p p
Downstream earthing switch 2 kA rms making
capacity at 630 A and 25 kA rms making p
capacity at 1250 A
Three-phase bottom busbars p p
Equipment for three UTE (for SM6-24) or DIN
p
striker fuses
Version
LPCT Only with Easergy Sepam series 20, 40, 60, 80
SFset circuit breaker disconnectable
For SM6-24 For SM6-24 For SM6-24
(For 400-630 A performances)
Arc detection p p p p
Thermal monitoring p p p p
630 A busbars earthing switch cabinet (not
For SM6-24 For SM6-24
available for internal arc IEC62271-200)
Ambient monitoring p p p
Auxiliary contacts on the disconnector p p p
Protection p (Easergy Sepam & Easergy P3 relay programmable electronic units)
Cubicle options

Three voltage transformers p p p


Key-type interlocks p p p
Surge arresters p p p
1250 A three-phase upper busbars at Ir 630 A p p p
630 A cable connection by the top (no internal
p p p
arc withstand if selected)
630 A three-phase upper busbars for severe
For SM6-24 For SM6-24 For SM6-24
operating conditions for
Enlarged low-voltage control cabinet For SM6-24 For SM6-24 For SM6-24
50 W heating element For SM6-24 For SM6-24 For SM6-24
Connection pads for two dry-type single-core
For SM6-36
cables

schneider-electric.com SM6 Catalog | 59


Characteristics of Functional units selection
the functional units
Switching

IM Switch unit IMC Switch unit IMB Switch unit with IMM Switch and
earthing switch, right measurement unit, right
SM6 Type Im --> or left outgoing or left outgoing line

DE59700_LG

DE53518_LG

DE53519_LG

DE59700_LG
DE59710_LG

DE59711_LG

DE59212_LG
kA Ik/1s kA Ima

25 62.5

Electrical 20
Ir = 630 A
50

characteristics Ir = 630 A
16 40

12.5 Ir = 400 - 630 A 31.25 Ir = 400 - 630 A


Ur Ur

7.2 12 17.5 24 36 kV 7.2 12 17.5 24 36 kV

Switch and earthing switch p p p p


Three-phase busbars p p p p
CIT operating mechanism p p p p
Voltage presence indicator p p p p
Basic equipment

150 W heating element For SM6-36 For SM6-36 For SM6-36 For SM6-36
LSC2A p p p p
Connection pads for dry-type cables p p
Three-phase bottom busbars for outgoing lines p (right or left) p (right or left)
1 to 3 CTs, for SM6-24 /
Current transformers 3 CTs
3 CTs, for SM6-36
Version
CI2 operating mechanism (1) p p p p
CI1 operating mechanism (1) p For SM6-36 p p
Digital ammeter p
Surge arresters (2) p
630 A busbars earthing switch cabinet (3) For SM6-24
Ambient monitoring p
Earth fault indicators p p
Connection pads for two dry-type single-core
p p
cables for 36 kV
Motor for operating mechanism p p p
Motor with severe and communication p p p
Auxiliary contacts p p p
Key-type interlocks p p p
Cubicle options

Release units (coil) p p p


Operation counter p p p
1250 A three-phase upper busbars p p p
630 A three-phase upper busbars for severe
For SM6-24 For SM6-24 For SM6-24
operating conditions
Visibility of main contacts p p p
Pressure indicator device p p p
Enlarged low-voltage control cabinet For SM6-24 For SM6-24 For SM6-24
50 W heating element For SM6-24 For SM6-24 For SM6-24
630 A cable connection by the top (no internal
arc withstand if selected) protection using p
Sepam programmable electronic unit
Three voltage transformers p
Key-type interllocks p
Arc detection p p p p
Thermal monitoring p p p p

(1) IM / IMC: In 800 A version for SM6-24, please consult us / (2) For SM6-36 and for SM6-24 in 500 mm width cubicle / (3) Not available for internal arc IEC62271-200