DC Inverter Air Source Heat Pumps (Monoblock Type)
1. Working source temperature range: -25℃ to 45℃
2. Control Object: water tank temperature
(Setting range: Heating: 30℃~75℃; Cooling: 32℃~12℃)
3. Control Way: wire controller
4. Water Pump: start/stop according to water tank temp
5. Working Modes: hot water/heating/cooling/hot water+cooling/hot water+heating
CGK030V4P,CGK-030V4P
CGK040V4P,CGK-040V4P
CGK050V4P,CGK-050V4P
CGK060V4P,CGK-060V4P
Guangzhou Sprsun New Energy Technology Development Co., Ltd.
Installation Diagram
Standard Materials
Name Description Picture Name Description Picture Name Description Picture
Hydropilic
Aluminium foil and
High Pressure SENSATA
Condenser Plate Heat Exchanger Evaporator internal thread
Sensor 0-4.6MPa
copper pipe heat
exchanger
FUJIKOKI
HIGHLY Rotary Expansion Low Pressure SENSATA
Compressor Electronic expansion
Compressor Valve Sensor 0-2.0MPa
valve
corrugated board
4-way valve SANHUA DC Fan Match- well DC Fan Package case / plywood
case
CHICO Touch screen
Controller water pump SHIMGE
Controller 4.3”
Functions
1. How to Start Electric Heater?
There are two kinds of electric heaters: backup electric heater and crank heater. The
corresponding electric heater can be enabled in M04 menu.
In heating mode (without defrosting), start backup electric heater when all the following conditions are met:
(1) Enable the backup electric heater function;
(2) Ambient temperature≤the ambient temperature when starting electric heater (default value 0℃);
(3) Target temperature ≤ heating temperature set point - deviation value under electric heating (default
value 5℃);
(4) It takes more than 5min to start the compressor (adjustable);
In heating mode (without defrosting), turn off backup electric heater if any of the following conditions is met:
(1) Ambient temperature ≥ the ambient temperature when starting electric heater + 3℃;
(2) Target temperature ≥ heating temperature set point;
(3) Ambient temperature sensor error;
(4) Power off.
2. How to Enter Defrosting?
When the air-cooled unit is in the heating mode, the outdoor coil works as evaporator. If the outdoor
temperature is too low, frost may form on the coil, which means that the working efficiency of the unit will be
reduced. In this case, the heating mode should be temporarily switched to the cooling mode for defrosting,
and then return to the heating mode, so that the unit can resume its high efficiency.
Defrosting Conditions:
Defrosting will be enabled when the following conditions are met at the same time:
(1) Time between two defrosting cycles ≥ defrosting interval, unit: min, default value: 45;
(2) Ambient temperature ≤ defrosting ambient temperature, lasting for 2s, default value is 15℃ (this
condition is ignored when there is ambient temperature sensor error);
(3) Ambient temperature - evaporation temperature ≥ defrosting temperature difference, lasting for 2min,
the default value is 5℃; this condition is ignored when there is ambient temperature sensor error;
(4) Evaporation temperature ≤ defrosting set point, lasting for 2s, default value -1℃;
Defrosting set point: according to the compensation of ambient temperature, the lower the ambient
temperature is, the lower the setting point will be.
Implementing the manual forced defrosting command will ignore the above entry conditions.
Defrosting will quit if any of the following conditions is met:
(1) Defrosting time ≥ maximum defrosting time, the default value is 8min;
(2) Condensation/coil temperature ≥ the setting point of exiting defrosting, default value 15℃;
(3) Power off.
R290 DC inverter heat pump for Heating /Cooling /Hot Water
( Minus 25C to 45C )
Main features/advantages:
1. Capacity range: 9.5kW~18kW.
2.Workingrange: -25°℃~43℃.
3. 5.5 inch touch color screen controller
4. Cascade/ wifi app /IOT platform / RS485 function/SG ready
5. Multiple language in the controller
6. Ful DCinverter technology.
7 A+++ ErP energy label, CE
8. High quality parts
9. Lower noise
Model CGK030V4P-B CGK050V4P-B CGK-030V4P-B CGK-050V4P-B
Operation Ambint Temp.(℃) -25~45
Operation water Temp.(℃) 10~70(DHW)
Operation water Temp.(℃) 10~70(Heating)
Operation water Temp.(℃) 12~30(Cooling)
Power Supply / Refrigerant V/Hz/Ph 220-240/50/1 220-240/50/1 380-420/50/3 380-420/50/3
Max. Heating Capacity (A7℃/W35℃) kW 9.1 15.2 9.1 15.2
C.O.P (A7℃/W35℃) W/W 4.2 3.9 4.2 3.9
Heating Capacity Min./Max.(A7 ℃/W35℃) kW 3.15 / 9.10 5.60 / 15.20 3.15 / 9.10 5.60 / 15.20
Heating Power Input Min./Max.(A7 ℃/W35℃) W 626 / 2167 1125 / 3900 626 / 2167 1125 / 3900
C.O.P Min./Max.(A7 ℃/W35℃) W/W 4.2 / 5.03 3.90 / 4.98 4.2 / 5.03 3.90 / 4.98
Max. Heating Capacity(A7℃/W45℃) kW 8.60 14.5 8.60 14.5
C.O.P (A7℃/W45℃) W/W 3.52 3.23 3.52 3.23
Heating Capacity Min./Max.(A7 ℃/W45℃) kW 2.90 / 8.60 5.40 / 14.50 2.90 / 8.60 5.40 / 14.50
Heating power input Min./Max.(A7 ℃/W45℃) W 757 / 2443 1427 / 4489 757 / 2443 1427 / 4489
C.O.P Min./Max.(A7 ℃/W45℃) W/W 3.52 / 3.83 3.23 / 3.78 3.52 / 3.83 3.23 / 3.78
Max. Cooling Capacity(A35℃/W18℃) kW 7.04 13.6 7.04 13.6
E.E.R (A35℃/W18℃) W/W 3.43 3.28 3.43 3.28
Cooling Capacity Min./Max.(A35 ℃/W18℃) kW 2.64 / 7.04 5.20 / 13.60 2.64 / 7.04 5.20 / 13.60
Cooling Power Input Min./Max.(A35 ℃/W18℃) W 677 / 2052 1403 / 4146 677 / 2052 1403 / 4146
E.E.R Min./Max.(A35℃/W18℃) W/W 3.43 / 3.90 3.28 / 3.71 3.43 / 3.90 3.28 / 3.71
Max. Cooling Capacity(A35℃/W7℃) kW 5.63 10.2 5.63 10.2
E.E.R(A35℃/W7℃) W/W 2.66 2.60 2.66 2.60
Cooling Capacity Min./Max.(A35 ℃/W7℃) kW 2.10 / 5.63 4.52 / 10.20 2.10 / 5.63 4.52 / 10.20
Cooling Power Input Min./Max.(A35 ℃/W7℃) W 612 / 2117 1520 / 3923 612 / 2117 1520 / 3923
E.E.R Min./Max.(A35℃/W7℃) W/W 2.66 / 3.43 2.60 / 2.97 2.66 / 3.43 2.60 / 2.97
Max Power Input kW 4.00 6.30 4.00 6.30
Max Current A 19.14 30.14 8.44 13.29
Wire diameter mm² 4.0 6.0 2.5 4.0
Fuse or circuitbreakerer A 32A 40A 13A 20A
Compressor Brand HIGHLY HIGHLY HIGHLY HIGHLY
Type - Quantity/System
Refrigerant / Suggested Input Kg R290/0.75 R290/1.20 R290/0.75 R290/1.20
Type / DC DC DC DC
Quantity / 1 2 1 2
Fan Airflow m3/h 3000 5000 3000 5000
Rated Fan Speed RPM 900 900 900 900
Rated power W 116 116*2 116 116*2
Type / Plate Heat Exchan Plate Heat Exchang Plate Heat Exchange Plate Heat Exchanger
Water Side Heat Exch ger er r
Water Pressure Drop kPa 20 25 20 25
anger
Piping Connection Inch G1" G1" G1" G1"
Pump model / APM25-9- APF25-12-130E APM25-9- APF25-12-130E FPWM1
Max Water Pump Head m 130SPWM19 FPWM1
12 130SPWM1
9 12
Allowable Water Flow Min./Rated./Max. L/S 0.27 0.43 0.72 0.45 0.73 1.21 0.27 0.43 0.72 0.45 0.73 1.21
Noise Level (Sound Pressure) dB(A) 42 46 42 46
Noise Level (Sound Pressure) dB(A) 55 59 55 59
Moisture Resistance / IPX4 IPX4 IPX4 IPX4
Net Dimension(L×D×H) mm 1110*475*810 1110*475*1355 1110*475*810 1110*475*1355
Carton packing Dimension(L×D×H) mm 1165*505*960 1165*505*1520 1165*505*960 1165*505*1520
Splint packing Dimension(L×D×H) mm 1200*530*970 1200*530*1510 1220*530*970 1200*530*1510
Net Weight kg 106 151 106 151
Carton gross Weight kg 119 166 119 166
Splint gross Weight kg 142 188 142 188
Container Loading Capacity (20/40HQ) number 44 / 92 22 / 48 44 / 92 22 / 48
Pdesignh(35/55℃) kW 6.751/6.559 12.582/11.476 6.751/6.559 12.582/11.476
SCOP(35/55℃) kWh/kWh 4.76/3.58 4.73/3.62 4.76/3.58 4.73/3.62
SCOPon(35/55℃) kWh/kWh 4.78/3.59 4.75/3.63 4.78/3.59 4.75/3.63
QH(35/55℃) kWh/year 13935/13560 25995/23709 13935/13560 25995/23709
QHE(35/55℃) kWh/year 2927/3789 5493/6547 2927/3789 5493/6547
Ƞs,h(35/55℃) -- 187.4%/140.2% 186.3%/141.9% 187.4%/140.2% 186.3%/141.9%
Seasonal space heating energyefficiency classes: (According -- A+++ A+++ A+++ A+++
(EU)Noenergyefficiency
Seasonal space heating 811/2013 Table classes:
2) (According -- A++ A++ A++ A++
(EU)No 811/2013
Note: (1)Table 1) condition: water inlet/outlet temperature: 30℃/35℃, Ambient temperature: DB 7℃/WB 6℃;
Heating
(2) Heating condition: water inlet/outlet temperature: 40℃/45℃, Ambient temperature: DB 7℃/WB 6℃;
(3) Cooling condition: water inlet/outlet temperature: 23℃/18℃, Ambient temperature: DB35℃/WB24℃;
(4) Cooling condition: water inlet/outlet temperature: 12℃/7℃, Ambient temperature: DB35℃/WB24℃;
Heating Capacity at Different Conditions Heating Capacity at Different Conditions
Model CGK030V4P -B/CGK-030V4P-B Model CGK050V4P/CGK -050V4P
Heating capacity (kW) Heating capacity (kW)
Air temp ℃ Air temp ℃
30/35 35/40 40/45 45/50 50/55 55/60 60/65 65/70 70/75 30/35 35/40 40/45 45/50 50/55 55/60 60/65 65/70 70/75
-25 3.42 3.35 3.29 3.12 2.97 -25 6.67 6.52 6.41 6.23 5.98
-20 4.24 4.15 4.07 3.83 3.65 3.43 -20 7.89 7.73 7.64 7.45 7.30
-15 4.97 4.86 4.75 4.53 4.42 4.24 4.03 3.78 -15 9.37 9.13 8.98 8.63 8.48 8.37 8.01 7.86
-7 6.37 6.18 6.01 5.85 5.64 5.35 4.97 3.88 4.64 -7 11.69 11.17 10.68 10.45 10.21 10.12 10.05 9.29 8.39
-2 7.24 7.13 7.04 6.82 6.61 6.38 6.02 5.18 3.81 -2 12.92 12.56 12.21 11.93 11.69 11.45 10.98 10.15 9.03
2 8.04 7.92 7.82 7.56 7.34 7.05 6.73 6.02 4.23 2 14.04 13.65 13.27 12.97 12.71 12.45 11.93 11.03 9.82
7 9.10 8.93 8.82 8.54 8.28 8.03 7.85 7.13 5.20 7 15.29 14.82 14.51 14.18 13.87 13.51 12.98 12.25 11.34
12 9.20 9.01 8.76 8.43 8.18 7.96 7.73 6.85 5.08 12 16.55 15.98 15.21 14.86 14.41 14.05 13.55 12.83 11.94
20 8.83 8.61 8.40 7.95 7.49 7.21 7.02 6.32 5.43 20 15.23 14.61 14.05 13.80 13.56 13.33 12.96 12.42 11.67
Heating Capacity at Different Conditions Heating Capacity at Different Conditions
Model CGK030V4P -B/CGK-030V4P-B Model CGK050V4P/CGK -050V4P
COP (kW/kW) COP (kW/kW)
Air temp ℃ Air temp ℃
30/35 35/40 40/45 45/50 50/55 55/60 60/65 65/70 70/75 30/35 35/40 40/45 45/50 50/55 55/60 60/65 65/70 70/75
-25 1.80 1.70 1.59 1.48 1.31 -25 2.05 1.92 1.81 1.67 1.52
-20 2.20 2.05 1.92 1.73 1.56 1.35 -20 2.29 2.14 2.03 1.83 1.75
-15 2.49 2.30 2.15 1.96 1.79 1.62 1.45 1.19 -15 2.62 2.40 2.26 2.05 1.92 1.79 1.61 1.50
-7 3.07 2.82 2.57 2.34 2.15 1.91 1.70 1.21 1.03 -7 3.01 2.71 2.48 2.37 2.12 1.96 1.84 1.65 1.41
-2 3.30 3.05 2.81 2.56 2.32 2.13 1.98 1.50 1.08 -2 3.32 2.94 2.59 2.35 2.18 2.06 1.95 1.74 1.56
2 3.73 3.48 3.17 2.85 2.62 2.35 2.13 1.82 1.16 2 3.43 3.10 2.88 2.61 2.42 2.29 2.08 1.93 1.64
7 4.20 3.91 3.57 3.21 2.93 2.62 2.30 1.99 1.39 7 3.86 3.53 3.23 2.90 2.69 2.48 2.22 2.05 1.83
12 5.18 4.61 4.18 3.74 3.33 2.92 2.50 2.25 1.53 12 4.43 4.02 3.68 3.38 2.93 2.64 2.41 2.26 1.98
20 5.93 5.20 4.69 4.02 3.52 3.08 2.72 2.52 1.85 20 5.13 4.62 4.01 3.75 3.34 2.96 2.68 2.42 2.12