Technical data sheet                                                      F680-150SHP
Butterfly Valve with Lug types
Reinforced Teflon Seat, 316 Stainless Steel
 Type overview
 Type                                                                                                                             DN
 F680-150SHP                                                                                                                      80
 Technical data
                                 Functional data    Valve Size                                    3" [80]
                                                    Fluid                                         chilled or hot water, up to 60% glycol, steam
                                                    Fluid Temp Range (water)                      -22...400°F [-30...204°C]
                                                    Body Pressure Rating                          ANSI Class 150
                                                    Close-off pressure ∆ps                        285 psi
                                                    Flow characteristic                           modified equal percentage, unidirectional
                                                    Servicing                                     maintenance-free
                                                    Flow Pattern                                  2-way
                                                    Leakage rate                                  0%
                                                    Controllable flow range                       quarter turn, mechanically limited
                                                    Cv                                            228
                                                    Maximum Inlet Pressure (Steam)                50 psi
                                                    Maximum Velocity                              32 FPS
                                                    Lug threads                                   5/8-11 UNC
                                      Materials     Valve body                                    Carbon steel full lug (ASME B16.34)
                                                    Stem                                          17-4 PH stainless steel
                                                    Seat                                          RPTFE
                                                    Pipe connection                               ASME/ANSI class 150 flange
                                                    Bearing                                       glass backed PTFE
                                                    Disc                                          316 stainless steel
                                                    Gland Seal                                    TFE
                                                    Gear operator materials                       Gears - hardened steel
                            Suitable actuators      Non-Spring                                    PRB(X)
                                                                                                  GMB(X)
                                                    Spring                                        (2*AFB(X))
                                                    Electrical fail-safe                          PKRB(X)
                                                                                                  GKRB(X)
 Safety notes
                                                   • WARNING: This product can expose you to lead which is known to the State of California to
                                                     cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov
www.belimo.com                                     F680-150SHP • en-us • 2021-11-24 • Subject to change                                    1/4
                                              Technical data sheet                                                     F680-150SHP
 Product features
                    Flow/Mounting details
 Dimensions
 Type                                                                                                                     DN
 F680-150SHP                                                                                                              80
                                             A                 B          C          D           E         F       Number of Bolt Holes
                                             18.0" [457]   1.9" [49] 20.0" [509] 17.0" [431] 3.5" [89] 3.5" [89]           4
www.belimo.com                              F680-150SHP • en-us • 2021-11-24 • Subject to change                                  2/4
                           Technical data sheet                                                        F680-150SHP
                          A                  B          C          D            E          F       Number of Bolt Holes
                          10.9" [277]    1.9" [49] 17.9" [454] 13.2" [336] 4.9" [124] 4.9" [125]           4
                 GM N4
                          A                 B          C          D            E          F        Number of Bolt Holes
                          9.1" [231]    1.9" [49] 13.9" [354] 10.0" [254] 3.9" [100] 3.9" [100]            4
www.belimo.com           F680-150SHP • en-us • 2021-11-24 • Subject to change                                     3/4
                        Technical data sheet                                                       F680-150SHP
                 PR
                       A                 B          C          D            E          F       Number of Bolt Holes
                       14.1" [358]   1.9" [49] 19.8" [502] 14.5" [368] 5.2" [133] 5.2" [133]           4
                 PK
                       A                 B          C          D            E          F     Number of Bolt Holes
                       12.0" [304]   1.9" [49] 22.4" [570] 17.5" [445] 4.9" [124] 4.9" [125]          4
                       A                 B           C           D           E        F      Number of Bolt Holes
                       11.7" [298]   1.9" [49] 18.5" [470] 15.0" [381] 3.5" [89] 3.5" [89]           4
www.belimo.com        F680-150SHP • en-us • 2021-11-24 • Subject to change                                   4/4
                                                    Technical data sheet                                            GMX24-MFT-T-X1 N4
NEMA 4, Modulating Control, Non-Spring
Return, Direct Coupled, 24 V, Multi-Function
Technology®
 Technical data
                                Electrical data    Nominal voltage                              AC/DC 24 V
                                                   Nominal voltage frequency                    50/60 Hz
                                                   Nominal voltage range                        AC 19.2...28.8 V / DC 21.6...28.8 V
                                                   Power consumption in operation               8W
                                                   Power consumption in rest position           2.5 W
                                                   Transformer sizing                           11 VA
                                                   Electrical Connection                        Terminal blocks
                                                   Overload Protection                          electronic throughout 0...95° rotation
                              Functional data      Operating range Y                            2...10 V
                                                   Operating range Y note                       4...20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor)
                                                   Input Impedance                              100 kΩ for 2...10 V (0.1 mA), 500 Ω for 4...20
                                                                                                mA, 1500 Ω for PWM, On/Off and Floating point
                                                   Operating range Y variable                   Start point 0.5...30 V
                                                                                                End point 2.5...32 V
                                                   Operating modes optional                     variable (VDC, on/off, floating point)
                                                   Position feedback U                          2...10 V
                                                   Position feedback U note                     Max. 0.5 mA
                                                   Position feedback U variable                 VDC variable
                                                   Direction of motion motor                    selectable with switch 0/1
                                                   Manual override                              under cover
                                                   Angle of rotation                            Max. 95°
                                                   Angle of rotation note                       adjustable with mechanical stop
                                                   Running Time (Motor)                         150 s / 90°
                                                   Running time motor variable                  90...150 s
                                                   Noise level, motor                           45 dB(A)
                                                   Position indication                          Mechanically, 5...20 mm stroke
                                   Safety data     Power source UL                              Class 2 Supply
                                                   Degree of protection IEC/EN                  IP66/67
                                                   Degree of protection NEMA/UL                 NEMA 4X
                                                   Enclosure                                    UL Enclosure Type 4X
                                                   Agency Listing                               cULus acc. to UL60730-1A/-2-14, CAN/CSA
                                                                                                E60730-1:02, CE acc. to 2014/30/EU and
                                                                                                2014/35/EU
                                                   Quality Standard                             ISO 9001
                                                   Ambient humidity                             Max. 100% RH
                                                   Ambient temperature                          -22...122°F [-30...50°C]
                                                   Ambient temperature note                     -40...50°C for actuator with integrated heating
                                                   Storage temperature                          -40...176°F [-40...80°C]
                                                   Servicing                                    maintenance-free
www.belimo.com                                    GMX24-MFT-T-X1 N4 • en-us • 2022-11-02 • Subject to change                              1/3
                                                      Technical data sheet                                                GMX24-MFT-T-X1 N4
                                         Weight      Weight                                           9.9 lb [4.5 kg]
                                       Materials     Housing material                                 Die cast aluminium and plastic casing
                                      Footnotes     †Rated Impulse Voltage 800V, Type action 1, Control Pollution Degree 3.
 Accessories
                           Electrical accessories   Description                                                                   Type
                                                    Battery backup system, for non-spring return models                           NSV24 US
                                                    Battery, 12 V, 1.2 Ah (two required)                                          NSV-BAT
                                                    Service Tool, with ZIP-USB function, for programmable and                     ZTH US
                                                    communicative Belimo actuators, VAV controller and HVAC performance
                                                    devices
                   Factory add-on option only       Description                                                                   Type
                                                    Heater, with adjustable thermostat                                            N4 Heater Add-on
                                                                                                                                  24V (-H)
 Electrical installation
                                                     INSTALLATION NOTES
                                                     Actuators with appliance cables are numbered.
                                                     Provide overload protection and disconnect as required.
                                                     Actuators may also be powered by DC 24 V.
                                                     Only connect common to negative (-) leg of control circuits.
                                                     A 500 Ω resistor (ZG-R01) converts the 4...20 mA control signal to 2...10 V.
                                                     Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 V line.
                                                     For triac sink the Common connection from the actuator must be connected to the Hot
                                                     connection of the controller. Position feedback cannot be used with a triac sink controller; the
                                                     actuator internal common reference is not compatible.
                                                     IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).
                                                     Actuators are provided with a numbered screw terminal strip instead of a cable.
                                                     Actuators may be controlled in parallel. Current draw and input impedance must be observed.
                                                     Master-Slave wiring required for piggy-back applications. Feedback from Master to control
                                                     input(s) of Slave(s).
                                                     Meets cULus requirements without the need of an electrical ground connection.
                                                     Warning! Live electrical components!
                                                     During installation, testing, servicing and troubleshooting of this product, it may be necessary
                                                     to work with live electrical components. Have a qualified licensed electrician or other individual
                                                     who has been properly trained in handling live electrical components perform these tasks.
                                                     Failure to follow all electrical safety precautions when exposed to live electrical components
                                                     could result in death or serious injury.
 Wiring diagrams
 On/Off                                                                      Floating Point
www.belimo.com                                      GMX24-MFT-T-X1 N4 • en-us • 2022-11-02 • Subject to change                                   2/3
                      Technical data sheet                                       GMX24-MFT-T-X1 N4
 VDC/mA Control                             PWM Control
 Override Control                           Primary - Secondary
www.belimo.com      GMX24-MFT-T-X1 N4 • en-us • 2022-11-02 • Subject to change                3/3