FLATAIR - FLCK/FLHK
MSL60E-0701 12-2006
Congratulations you have made a wise choice and we feel sure that it will meet your expectation
INDEX
CONTENTS PAGE
Lennox have been providing environmental solutions since 1895, our range of FLATAIR continues to meet the
standards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs and
uncompromising attention to detail. Engineered to last, simple to maintain and Quality that comes as standard.
Information on local contacts at www.lennoxeurope.com.
All the technical and technological information contained in this manual, including any drawing and technical
descriptions provided by us, remain the property of Lennox and must not be utilised (except in the operation of
this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
1
GENERAL DESCRIPTION
The horizontal air conditioning units, range Flatair, cooling only or heat pump are air condensed units designed
for small shopping center and housing. Those units have two sections: outdoors and indoors. They can be supplied
either compact or on split system.
Due to their small dimensions they are designed for false ceiling and can be placed in air conducts both indoors
and outdoors.
A wide range of optionals, completed-factory assembled are also available.
FURNITURE FAN
Painted in galvanized metal furniture, high resistant Outdoor and indoor fans are centrifugal with an
to corrosion. The units are provided with metal assembled engine, statically balancing, with a low
profiles, capable of withstanding the unit and able sound level.
as well of installing the unit hung from the ceiling or Those fans are assembled to the inserted panel of
mounted on the floor. the units and split from upper side of the fan with
The panel are easily inter exchangeable, giving insulated materials to void vibrations.
several air suction and return alternatives.
The outdoor sections are equipped with a meta grilles
with in the blower panel " except in models 24-28-
EXCHANGER
30 and in the duct discharge to avoid damages (in Made-up with copper pipes and aluminium wings,
the whole models). designed to get a high heating transfer.
An insulation with a protection of mesh is used in Their dimensions and design of the circuits have
indoor units with a classification of M1 and F1, been specially worked to obtain the maximum
certifying that the material is auto-extinguishable performance of the exchanger increasing the power
and avoiding the fumes inside the room to be of the unit and reducing the consumption.
aconditionned. The auto extinguishable insulation
M1 is used in indoor units.
COOLING CIRCUIT
COMPRESSORS
Carried out with welded deshydratable copper pipes
All units are provided with scroll compressor, cooling with pressuring outlets with plugged valves in the
by a suction gas with thermic protection inside the suction and liquid lines both indoors and outdoor
engine, so no other additional protection is required. units.
It is mounted on anti-vibration devices both external In unit 24-28-30 the pressuring outlets in the outdoor
and internal. section are approachable from the outer part of the
On units 24/28/30 the compressors have a screwed unit.
connection into the pipe- Thus, they can be more The unit is equipped with both high-low pressure
easily to assembled. switches with an automatic rearm. It also has a
In heat pump units the compressors are provided dehumidifying filter, expansion system with
with a crankcase heater to heat the oil in the restrictors in units 10-12-16; stoppage of
compressor so that a suitable lubrication can take impurities/dirts and air reducing valves in units 22-
place. 24-28-30. The heat pump units are equipped as
well with a suction pump battery to avoid the leaks
to the compressor, reversible valves to reserve the
AIR FILTER cycle of unidirectional valve.
2
GENERAL DESCRIPTION
CONTROL
Made up with a printed control circuit plate for the opening unit and with a walled terminal thermostat to be placed
in the room to be aconditioned; with sound output inside the terminal and with a sound installed in the outdoor
batteries for the regulation of the system.
With a LCD display with alarm visualization, exclusive connection with two files between terminal thermostat and
electrical box in the unit, possibility to adjust internal parameters. automatic restarting and high pressure control
ON/OFF on unit models 22-24-28-30, with well intelligent defrosting control adapted to ambient conditions in each
moment and each side (for small heat pump).
OPTIONS
• Heating electrical heater, type armoured pipe to be mounted into the unit.
• Hot water coil.
• Head pressure control ON/OFF for models 10-12-16.
• Crankcase for units cooling only.
• Main switch.
• Phase sequencer (3 phase unit).
• Hot gas bypass valve.
• Control programmable controller.
• Remote duct sensor on return.
• Ambient remote sensor.
• Thermostatic freecooling.
• Sound muffler.
• External mounting kit.
• Freecooling external mounted kit.
• Outdoor air filter.
3
DENOMINATION
PACKAGED UNITS
F L C K 22
Unit size.
Type of unit Type of refrigerant Approximately cooling
Horizontal compact A: R-22 capacity in kW.
FLATAIR K: R-407C
Application
C: Cooling only
H: Heat pump
4
RANGE PRODUCT
5
PHYSICAL DATA (COOLING ONLY)
R-407C
Cooling capacity (*) kW 9,8 11,8 15,3 19,5 22,0 26,3 28,1
DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 1250 1250 1330 1520 1800 1800 1800
COMPRESSOR No. / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
FAN
Maximum air flow m3 /h. 3500 3400 4950 5900 6600 6400 6400
Minimum air flow m3 /h. 2350 2400 3750 4350 4500 5000 5250
Maximum available pressure (1) Pa 100 90 120 150 160 120 100
FAN
Maximum air flow m3 /h. 2350 2300 3700 5350 6300 6000 6000
Minimum air flow m3 /h. 1500 1650 2400 3200 4000 4250 4500
Maximum available pressure (1) Pa 120 110 160 180 240 200 180
(*) Air intake temperature in the indoor exchanger 27ºC DB/19ºC WB DB.- Dry bulb temperature
(*) Air intake temperature in the outdoor exchanger: 35ºC DB WB.- Wet bulb temperature
(1) With admissible minimum air flow.
6
PHYSICAL DATA UNITS HEAT PUMP
R-22
Cooling capacity (*) kW 9,4 11,3 14,7 19,2 21,0 26,0 27,6
Heating capacity (**) kW 10,3 12,3 15,6 20,0 22,8 27,0 29,8
DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 1250 1250 1330 1520 1800 1800 1800
NET WEIGHT Kg 205 210 285 330 410 430 435
COMPRESSOR No. / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
FAN
Maximum air flow m3 /h. 3500 3400 4950 5900 6600 6400 6400
Minimum air flow m3 /h. 2350 2400 3750 4350 4500 5000 5250
Maximum available pressure (1) Pa 100 90 120 150 160 120 100
FAN
Maximum air flow m3 /h. 2350 2300 3700 5350 6300 6000 6000
Minimum air flow m3 /h. 1500 1650 2400 3200 4000 4250 4500
Maximum available pressure (1) Pa 120 110 160 180 240 200 180
(*) Air intake temperature in the indoor exchanger: 27ºC DB/19ºC WB DB.- Dry bulb temperature
(*) Air intake temperature in the outdoor exchanger: 35ºC DB WB.- Wet bulb temperature
(**) Air intake temperature in the indoor exchanger: 20ºC DB / 12ºC WB (1) With admissible minimum air flow.
(**) Air intake temperature in the outdoor exchanger: 7ºC DB / 6ºC WB
7
PHYSICAL DATA UNITS HEAT PUMP
R-407C
Cooling capacity (*) kW 9,8 11,8 15,3 19,5 22,0 26,3 28,1
Heating capacity (**) kW 10,0 12,0 15,5 20,2 22,5 27,0 28,7
DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 1250 1250 1330 1520 1800 1800 1800
NET WEIGHT Kg 205 210 285 330 410 430 435
COMPRESSOR No. / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
FAN
Maximum air flow m3 /h. 3500 3400 4950 5900 6600 6400 6400
Minimum air flow m3 /h. 2350 2400 3750 4350 4500 5000 5250
Maximum available pressure (1) Pa 100 90 120 150 160 120 100
FAN
Maximum air flow m3 /h. 2350 2300 3700 5350 6300 6000 6000
Minimum air flow m3 /h. 1500 1650 2400 3200 4000 4250 4500
Maximum available pressure (1) Pa 120 110 160 180 240 200 180
(*) Air intake temperature in the indoor exchanger: 27ºC DB/19ºC WB DB.- Dry bulb temperature
(*) Air intake temperature in the outdoor exchanger: 35ºC DB WB.- Wet bulb temperature
(**) Air intake temperature in the indoor exchanger: 20ºC DB / 12ºC WB (1) With admissible minimum air flow.
(**) Air intake temperature in the outdoor exchanger: 7ºC DB / 6ºC WB
8
ELECTRICAL DATA
R-22
UNIT MODELS FLHA 10 FLHA 12 FLHA 16 FLHA 22 FLHA 24 FLHA 28 FLHA 30
230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power
Total power in cooling cycle kW 3,50 4,31 6,11 7,92 8,80 10,36 11,78
Total power in heating cycle kW 2,93 3,44 4,94 6,60 7,80 8,43 9,43
230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power
Compressor (cooling cycle) kW 2,60 3,41 4,11 5,02 5,85 7,41 8,83
Compressor (heating cycle) kW 2,03 2,54 2,94 3,70 4,85 5,48 6,48
Fan outdoor section kW 0,52 0,52 1,10 1,60 1,60 1,60 1,60
Total power in cooling cycle kW 3,12 3,93 5,21 6,62 7,45 9,01 10,43
Total power in heating cycle kW 2,55 3,06 3,50 5,30 6,45 7,08 8,08
Maximum current
18,6
Compressor A 16,7/7,2 19,3/8,7 19,9/11,5 22,4/12,9 25,3/14,6 28,5/16,3 36,5/21,0
3,1 3,1
Fan outdoor section A
4,8/2,8 7,4/4,3 8,1/4,7 8,1/4,7 8,1/4,7
21,7
Total current A
19,8/10,3 22,4/11,8 24,7/14,3 29,8/17,2 33,4/19,3 36,6/21,0 44,6/25,7
98
Start up current A 94/49 101/53 138/69 185/105 174/104 218/128 232/132
230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power kW 0,38 0,38 0,90 1,30 1,35 1,35 1,35
2,6 2,6
Maximum current A
7/4 7,4/4,3 7,4/4,3 7,4/4,3 7,4/4,3
7,8 7,8
Start up current A
21/13 22/14 22/14 22/14 22/14
9
ELECTRICAL DATA
R-407C
UNIT MODELS FLCK 10 FLCK 12 FLCK 16 FLCK 22 FLCK 24 FLCK 28 FLCK 30
FLHK 10 FLHK 12 FLHK 16 FLHK 22 FLHK 24 FLHK 28 FLHK 30
230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power
Total power in cooling cycle kW 3,68 4,57 6,40 8,09 9,02 10,40 12,20
Total power in heating cycle kW 3,16 4,11 5,60 6,74 8,60 9,20 10,32
Maximum current
24,3
Total current A
22,4/12,9 25,0/14,4 31,7/18,3 37,2/21,5 39,8/23,0 44,0/25,4 52,0/30,0
101
Start up current A
97/52 104/56 145/73 193/110 182/108 226/132 240/136
Total power in cooling cycle kW 3,30 4,19 5,50 6,79 7,67 9,05 10,85
Total power in heating cycle kW 2,78 3,73 4,70 5,44 7,25 7,85 8,97
Maximum current 18,6
Compressor A 16,7/7,2 19,3/8,7 19,9/11,5 22,4/12,9 25,3/14,6 28,5/16,3 36,5/21,0
3,1 3,1
Fan outdoor section A
4,8/2,8 7,4/4,3 8,1/4,7 8,1/4,7 8,1/4,7
21,7
Total current A
19,8/10,3 22,4/11,8 24,7/14,3 29,8/17,2 33,4/19,3 36,6/21,0 44,6/25,7
98
Start up current A
94/49 101/53 138/69 185/105 174/104 218/128 232/132
10
FAN SERVICES
11
TECHNICAL DATA
(*) Sound pressure level estimated, radiated by indoor unit fans on site with normal acoustic absorption, measured
to a discharged distance of 2m of the unit depending on suction or discharge.
(*) Measured in free field condition at a distance of 10m (depending on suction or in duct discharge)
(*) Setting a muffler (optional) directly connected to the discharge of outdoor fan of the unit measured in free-field
condition at a distance of 10m. (depending on no suction and discharge installation duct).
12
COOLING CAPACITIES
R-407C
FLCK / FLHK 10 FLCK / FLHK 12
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 9,20 8,89 8,56 8,19 7,77 10,99 10,62 10,22 9,77 9,27
15°C WB SENSIBLE 7,08 6,93 6,77 6,59 6,40 7,98 7,79 7,59 7,37 7,12
24°C DB TOTAL 9,89 9,56 9,20 8,81 8,36 11,79 11,39 10,96 10,49 9,95
17°C WB SENSIBLE 7,59 7,44 7,28 7,10 6,90 8,50 8,31 8,11 7,88 7,63
27°C DB TOTAL 10,62 10,27 9,80 9,46 8,98 12,64 12,22 11,80 11,25 10,67
19°C WB SENSIBLE 8,08 7,93 7,70 7,59 7,39 9,00 8,81 8,64 8,38 8,12
29°C DB TOTAL 11,40 11,02 10,61 10,15 9,63 13,56 13,11 12,61 12,06 11,43
21°C WB SENSIBLE 8,07 7,92 7,76 7,57 7,37 8,99 8,80 8,59 8,36 8,10
32°C DB TOTAL 12,22 11,82 11,38 10,88 10,31 14,54 14,05 13,52 12,93 ---
23°C WB SENSIBLE 8,54 8,38 8,22 8,04 7,86 9,46 9,27 9,06 8,83 ---
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 14,24 13,72 13,17 12,59 11,96 17,99 17,36 16,69 15,96 15,16
15°C WB SENSIBLE 10,96 10,71 10,45 10,17 9,87 14,58 14,28 13,97 13,63 13,27
24°C DB TOTAL 15,34 14,78 14,20 13,57 12,90 19,40 18,74 18,03 17,25 16,39
17°C WB SENSIBLE 11,77 11,52 11,25 10,97 10,68 15,74 15,45 15,13 14,79 14,42
27°C DB TOTAL 16,50 15,92 15,30 14,62 13,89 20,92 20,22 19,50 18,63 17,71
19°C WB SENSIBLE 12,55 12,30 12,04 11,75 11,45 16,86 16,57 16,30 15,92 15,54
29°C DB TOTAL 17,75 17,13 16,46 15,74 14,96 22,56 21,81 21,00 20,11 19,13
21°C WB SENSIBLE 12,55 12,30 12,03 11,75 11,44 16,87 16,58 16,26 15,92 15,55
32°C DB TOTAL 19,07 18,41 17,70 16,93 --- 24,31 23,51 22,64 21,69 20,63
23°C WB SENSIBLE 13,28 13,03 12,77 12,48 --- 17,95 17,65 17,34 17,00 16,62
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 20,62 19,87 19,09 18,28 17,43 24,63 23,71 22,77 21,80 20,81
15°C WB SENSIBLE 16,37 16,01 15,64 15,26 14,87 19,08 18,64 18,19 17,73 17,26
24°C DB TOTAL 22,19 21,39 20,56 19,69 18,79 26,45 25,48 24,48 23,45 22,39
17°C WB SENSIBLE 17,62 17,26 16,89 16,51 16,11 20,47 20,03 19,57 19,11 18,65
27°C DB TOTAL 23,88 23,02 22,00 21,21 20,25 28,40 27,37 26,30 25,21 24,08
19°C WB SENSIBLE 18,33 18,47 18,00 17,72 17,32 21,81 21,37 20,92 20,46 19,99
29°C DB TOTAL 25,20 24,78 23,83 22,85 21,82 30,50 29,40 28,26 27,10 ---
21°C WB SENSIBLE 18,82 18,46 18,09 17,71 17,31 21,78 21,34 20,89 20,43 ---
32°C DB TOTAL 27,65 26,67 25,65 24,59 23,50 32,73 31,56 30,35 29,11 ---
23°C WB SENSIBLE 19,98 19,62 19,25 18,87 18,47 23,06 22,62 22,11 21,71 ---
DB - Dry Bulb
WB - Wet Bulb
13
COOLING CAPACITIES
R-407C
FLCK / FLHK 30
MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,95 x1,00 x1,02
MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,98 x1,00 x1,01
14
COOLING CAPACITIES
R-22
FLHA 10 FLHA 12
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 8,73 8,46 8,18 7,88 7,55 10,60 10,27 9,92 9,52 9,07
15°C WB SENSIBLE 6,82 6,69 6,56 6,42 6,26 7,81 7,65 7,47 7,28 7,06
24°C DB TOTAL 9,34 9,06 8,76 8,44 8,10 11,33 10,99 10,61 10,18 9,69
17°C WB SENSIBLE 7,31 7,18 7,05 6,90 6,75 8,32 8,15 7,97 7,78 7,55
27°C DB TOTAL 9,99 9,69 9,40 9,03 8,67 12,12 11,75 11,30 10,89 10,35
19°C WB SENSIBLE 7,78 7,65 7,52 7,37 7,22 8,80 8,64 8,46 8,26 8,03
29°C DB TOTAL 10,69 10,37 10,03 9,67 9,28 12,96 12,57 12,13 11,63 11,05
21°C WB SENSIBLE 7,75 7,62 7,49 7,35 7,20 8,77 8,61 8,43 8,22 7,99
32°C DB TOTAL 11,42 11,08 10,71 10,33 9,92 13,86 13,43 12,96 12,42 11,78
23°C WB SENSIBLE 8,19 8,07 7,93 7,79 7,64 9,23 9,06 8,88 8,67 8,43
FLHA 16 FLHA 22
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 13,56 13,11 12,62 12,09 11,50 17,62 17,09 16,50 15,85 15,08
15°C WB SENSIBLE 10,48 10,27 10,04 9,78 9,50 14,35 14,10 13,82 13,52 13,17
24°C DB TOTAL 14,54 14,06 13,55 12,98 12,35 18,91 18,35 17,74 17,04 16,21
17°C WB SENSIBLE 11,23 11,02 10,79 10,53 10,26 15,45 15,21 14,94 14,63 14,28
27°C DB TOTAL 15,58 15,07 14,70 13,93 13,26 20,26 19,69 19,20 18,30 17,40
19°C WB SENSIBLE 11,96 11,74 11,51 11,26 10,98 16,51 16,28 16,01 15,71 15,34
29°C DB TOTAL 16,69 16,15 15,57 14,93 14,23 21,71 21,11 20,43 19,64 18,63
21°C WB SENSIBLE 11,92 11,71 11,48 11,23 10,95 16,46 16,23 15,97 15,66 15,28
32°C DB TOTAL 17,86 17,28 16,66 15,99 15,24 22,22 22,60 21,88 21,02 19,86
23°C WB SENSIBLE 12,61 12,39 12,16 11,91 11,64 17,46 17,24 16,98 16,67 16,26
FLHA 24 FLHA 28
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 19,56 18,94 18,32 17,68 17,02 24,36 23,69 22,77 21,88 20,92
15°C WB SENSIBLE 15,75 15,46 15,16 14,87 14,56 18,96 18,59 18,20 17,78 17,33
24°C DB TOTAL 20,98 20,33 19,66 18,98 18,29 26,07 25,24 24,36 23,41 22,38
17°C WB SENSIBLE 16,94 16,65 16,36 16,06 15,76 20,31 19,94 19,54 19,12 18,66
27°C DB TOTAL 22,50 21,81 21,00 20,39 19,65 27,88 26,99 26,00 25,03 23,92
19°C WB SENSIBLE 18,10 17,81 17,51 17,22 16,92 21,61 21,23 20,83 20,40 19,94
29°C DB TOTAL 24,15 23,41 22,66 21,90 21,12 29,82 28,86 27,84 26,74 25,55
21°C WB SENSIBLE 18,06 17,77 17,48 17,18 16,88 21,52 21,14 20,74 20,31 19,85
32°C DB TOTAL 25,90 25,11 24,32 23,51 22,68 31,85 30,82 29,72 28,54 27,26
23°C WB SENSIBLE 19,16 18,88 18,59 18,30 18,00 22,75 22,37 21,96 21,53 21,06
DB - Dry Bulb
WB - Wet Bulb
15
COOLING CAPACITIES
R-22
FLHA 30
MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,95 x1,00 x1,02
MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,98 x1,00 x1,01
16
HEATING CAPACITIES
R-407C
FLHK 10 FLHK 12
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 6,83 7,61 8,49 10,06 11,95 14,10 8,37 9,31 10,35 12,13 14,25 16,66
15°C DB
T. consumption 2,63 2,70 2,79 2,94 3,14 3,38 3,33 3,44 3,57 3,79 4,06 4,38
Total capacity 6,82 7,59 8,47 10,02 11,88 13,99 8,37 9,30 10,32 12,08 14,16 16,52
18°C DB 2,77 2,84 2,93 3,09 3,30 3,55
T. consumption 3,49 3,61 3,74 3,97 4,26 4,61
Total capacity 6,82 7,58 8,46 10,00 11,83 13,92 8,37 9,29 10,30 12,00 14,10 16,42
20°C DB
T. consumption 2,86 2,94 3,03 3,16 3,41 3,67 3,60 3,73 3,86 4,11 4,40 4,77
Total capacity 6,82 7,587 8,44 9,94 11,75 13,76 8,37 9,27 10,27 11,97 13,98 16,21
24°C DB
T. consumption 3,06 3,15 3,25 3,43 3,66 3,93 3,84 3,97 4,12 4,38 4,71 5,12
FLHK 16 FLHK 22
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 10,64 11,87 13,26 15,67 18,57 21,86 13,80 15,43 17,24 20,42 24,35 28,97
15°C DB
T. consumption 4,66 4,80 4,97 5,27 5,65 6,11 5,86 5,98 6,13 6,39 6,75 7,20
Total capacity 10,60 11,82 13,20 15,58 18,44 21,67 13,76 15,37 17,17 20,32 24,20 28,75
18°C DB 4,84 4,99 5,17 5,48 5,88 6,36
T. consumption 6,07 6,21 6,36 6,64 7,00 7,48
Total capacity 10,58 11,80 13,16 15,50 18,36 21,55 13,73 15,34 17,14 20,20 24,10 28,60
20°C DB
T. consumption 4,97 5,13 5,31 5,60 6,04 6,53 6,23 6,37 6,53 6,74 7,19 7,68
Total capacity 10,56 11,76 13,11 15,42 18,18 21,29 13,70 15,30 17,07 20,15 23,91 28,29
24°C DB
T. consumption 5,24 5,41 5,61 5,95 6,39 6,90 6,57 6,72 6,89 7,19 7,60 8,10
FLHK 24 FLHK 28
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 15,76 17,47 19,36 22,61 26,53 31,04 19,02 21,06 23,34 27,29 32,11 37,68
15°C DB
T. consumption 7,17 7,39 7,63 8,04 8,55 9,17 7,71 7,91 8,14 8,56 9,09 9,75
Total capacity 15,75 17,44 19,31 22,52 26,37 30,80 19,01 21,03 23,27 27,18 31,92 37,41
18°C DB 7,46 7,69 7,94 8,37 8,91 9,55
T. consumption 8,03 8,24 8,49 8,92 9,49 10,18
Total capacity 15,75 17,43 19,28 22,50 26,27 30,65 19,01 21,01 23,24 27,00 32,41 37,24
20°C DB
T. consumption 7,66 7,90 8,16 8,60 9,15 9,82 8,25 8,47 8,73 9,20 9,77 10,48
Total capacity 15,75 17,41 19,23 22,34 26,07 30,34 19,04 21,01 23,20 27,00 31,60 36,92
24°C DB
T. consumption 8,07 8,33 8,61 9,08 9,68 10,38 8,71 8,96 9,24 9,73 10,35 11,11
FLHK 30
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 7,13 7,94 8,84 10,38 12,22 14,30 8,51 9,48 10,53 12,33 14,47 16,90
15°C DB
T. consumption 2,51 2,56 2,63 2,73 2,86 3,02 2,87 2,96 3,05 3,19 3,36 3,57
Total capacity 7,12 7,92 8,81 10,33 12,15 14,19 8,52 9,47 10,52 12,30 14,41 16,79
18°C DB 2,62 2,68 2,74 2,85 2,99 3,16
T. consumption 3,00 3,09 3,18 3,34 3,52 3,74
Total capacity 7,12 7,91 8,79 10,30 12,09 14,12 8,52 9,47 10,51 12,30 14,36 16,72
20°C DB
T. consumption 2,70 2,76 2,82 2,93 3,08 3,26 3,10 3,18 3,28 3,44 3,63 3,86
Total capacity 7,11 7,89 8,76 10,25 12,01 13,98 8,54 9,47 10,49 12,23 14,27 16,57
24°C DB
T. consumption 2,87 2,93 3,00 3,12 3,27 3,46 3,29 3,38 3,48 3,66 3,87 4,12
FLHA 16 FLHA 22
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 10,95 12,14 13,46 15,74 18,45 21,51 13,70 15,30 17,08 20,13 23,73 27,80
15°C DB
T. consumption 4,25 4,34 4,44 4,62 4,85 5,15 5,64 5,76 5,90 6,15 6,47 6,85
Total capacity 10,93 12,11 13,42 15,67 18,33 21,35 13,66 15,24 17,00 20,02 23,60 27,64
18°C DB 4,42 4,51 4,62 4,81 5,05 5,36
T. consumption 5,82 5,95 6,09 6,35 6,68 7,08
Total capacity 10,93 12,09 13,39 15,60 18,26 21,24 13,64 15,20 16,95 20,00 23,52 27,53
20°C DB
T. consumption 4,55 4,64 4,74 4,94 5,19 5,51 5,94 6,08 6,23 6,60 6,84 7,25
Total capacity 10,92 12,07 13,35 15,53 18,11 21,02 13,60 15,14 16,86 19,82 23,34 27,29
24°C DB
T. consumption 4,81 4,90 5,01 5,22 5,49 5,83 6,21 6,35 6,51 6,80 7,16 7,59
FLHA 24 FLHA 28
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 15,82 17,61 19,54 22,80 26,69 31,18 18,61 20,68 22,98 26,93 31,67 37,08
15°C DB
T. consumption 6,69 6,86 7,04 7,32 7,67 8,10 7,23 7,40 7,58 7,90 8,30 8,78
Total capacity 15,81 17,58 19,48 22,70 26,53 30,97 18,60 20,66 22,93 26,84 31,51 36,82
18°C DB 3,93 7,10 7,28 7,58 7,95 8,40
T. consumption 7,51 7,69 7,88 8,22 8,64 9,14
Total capacity 15,81 17,56 19,45 22,80 26,44 30,83 18,60 20,65 22,91 27,00 31,40 36,65
20°C DB
T. consumption 7,09 7,27 7,46 7,80 8,14 8,61 7,71 7,89 8,09 8,43 8,87 9,38
Total capacity 15,82 17,55 19,41 22,53 26,26 30,58 18,59 20,63 22,86 26,68 31,19 36,31
24°C DB
T. consumption 7,44 7,64 7,83 8,16 8,56 9,06 8,11 8,31 8,53 8,90 9,36 9,91
FLHA 30
18
HEATING CAPACITIES
MODELS 24-28-30
Air flow minimum nominal maximum
Heating capacity x0,91 x1,00 x1,03
Total consumption x0,98 x1,00 x1,01
MODELS 24-28-30
Air flow minimum nominal maximum
Heating capacity x0,91 x1,00 x1,03
Total consumption x0,98 x1,00 x1,01
19
UNITS DIMENSIONS
SIDE D
SIDE B
1250
1250
820
32
25
495
425
303
Drainage
outside thread
3/4'' Male
184
452
B
E Oval hole of
D
349
123 SI 20 x12
50
25
Power supply SIDE Thermostat connection
A
40
connection
60
1250
1250 25 80
430
14
40 Detail drawing of
159
2255
unit anchor support
495
303
422
Unit anchor
support
4
90 73
280
4
Distanc 430 40
e betwe 109
en hole
s 1300
D Air filter
E
D
SIDE
C SI
20
DIMENSIONS SPLIT SYSTEM MODELS 10-12
(Split unit)
SIZE D
Pipes
connections
Outdoor Indoor
unit unit
Electrical heater/ Electrical
SIDE A
SIDE C
Electrical
interconnection
between indoor
unit
Electrical fan
SIDE B supply
Drainage Drainage
outside thread outside thread
3/4'' Male 3/4'' Male
Outdoor unit Cooling interconnection pipe
820 1250 Electrical box
32
305
20
27
25
425
495
Drainage
303
outside thread
3/4'' Male
Unit anchor
support 184 Detail drawing of
1,6
452 71 B unit anchor support
E
D Oval hole of
349
123 SI 20 x12
Power supply 50
connection SIDE Thermostat connection 25
A
40
40
159
3/4'' Male
303
422
Unit anchor
support
90
280 1,6
32
430
109
Distanc
e betwe
en hole D
s 1300 E
D
SI
Electric
al SIDE
heater C
supply
21
UNITS DIMENSIONS
SIZE D
MODEL 16
(Packaged units) SIDE A
SIDE C
OUTDOOR INDOOR
SECTION SECTION
SIDE B
1300
1330
Power supply connection
830
32
320
20 Thermostat connection
27
25
595
500
355
Drainage
outside thread
3/4'' Male
249
422
B
E
D
324
123 SI Oval hole of
20 x12
50
SIDE 25
A
Electrical box
40
1300
1330 60
25 80
500
25
40
182
517
Unit anchor
support
5
98
324 74
500 4
Distanc 125 47
e betwe
en hole Air filter
s 1350
D
E
SIDE D
C SI
22
DIMENSIONS SPLIT SYSTEM MODEL 16
(Split unit)
SIDE D
Cooling
connections
Outdoor Indoor
unit unit
Electrical
Electrical heater/ heater
SIDE A
SIDE C
Electrical
interconnection
between indoor
unit
Electrical fan
supply
SIDE B Drainage Drainage
outside thread outside thread
3/4'' Male 3/4'' Male
Outdoor unit Cooling interconnection pipe
830 1300 Electrical box
32
25
Drainage
595
500
outside thread
355
3/4'' Male
Indoor unit
500 1300 60
25 80
25
40 Gas pipe
182
25
Liquid pipe
Drainage
595
355
outside thread
517
98
324 1,6
39
500
Electric 125
al Distanc
heater e betwe
en hole
supply s 1350 D
E
D
SI
Air filter
SIDE
C
23
UNITS DIMENSIONS
SIDE D
SIDE B
1450
1520
900
36,5
47
25
595
Electrical
497
connection
355
supply Drainage
outside thread
3/4'' Male
Thermostat 262
connection 462
B
E
324
S ID
92
Oval hole of
SIDE 20 x12
A 50
25
40
1450
1520
32
620 300 Electrical box 60
25 80
26
40
193
2255
595
Detail drawing of
515,5
355
Unit anchor
107 4 support
324 81
591 3
Distanc 42 59
e betwe
en hole
s 1500
Air filter
D
E
SIDE D
C SI
24
DIMENSIONS SPLIT SYSTEM MODEL 22
(Split unit)
SIDE D
SIDE D
Cooling pipe
interconnection
Outdoor Indoor
unit unit
SIDE C
Electrical heater/
SIDE A
SIDE C
Electrical fan
supply
Electrical
interconnection
between indoor
unit
SIDE B Drainage
outside thread Drainage
Outdoor unit 3/4'' Male outside thread 3/4'' Male
47
25
595
497
595
355
1
Distanc 79
262 e betwe
en hole
462 s 1500
D
E
324
92 E
B ID
D S
Thermostat SI Electrical
SIDE
connection SIDE interconnection C
A Liquid pipe
between indoor
unit Unit anchor
Indoor unit Air filter
support
620 1450
Gas pipe
26
40
193
25
Liquid pipe
515,5
355
595
e betwe
en hole
s 1500
D
Electric E 60
al S ID 25 80
heater SIDE
supply C
25
UNITS DIMENSIONS
SIDE D
OUTDOOR INDOOR
SECTION SECTION
SIDE B
1500
1800
1025
25
645
Drainage
outside thread
355
3/4'' Male
214
490
398 B
E
410 103 S ID
SIDE
A
Electrical box
Thermostat Power
connection supply 1500
connection 1800
20 x12
40
223,5
50
25 2255
645
537
40
355
565,5
60
25 80
95 8
327 74
Detail drawing of 9
unit anchor support Distanc 658 93
e betwe 82
en hole
s 1550
Unit anchor Air filter
support D
SIDE E
C D
SI
26
DIMENSIONS SPLIT SYSTEM MODELS 24-28-30
SIDE C
(Split unit)
SIDE F
Cooling
connections
Outdoor Indoor
unit unit
Electrical heater/
Hot water coil Electrical
(optional)
SIDE D
heater
SIDE A
supply
Electrical
interconnection
SIDE E
between indoor
unit
Electrical fan
supply
SIDE B Drainage
outside thread Drainage
3/4'' Male outside thread
3/4'' Male
Drainage outside
Outdoor unit thread 3/4'' Male
Electrical
interconnection Gas pipe Liquid pipe
between indoor
1025 1500 unit 1500
1025
25 677
124
645
645
355
537
214
490 6
398 Distanc 91
e betw
een ho
410 les 1550
103
B Unit anchor D
SIDE E E
D SIDE D
A SI support C SI
Electrical box Thermostat Power
connection supply Indoor unit
connection 775 1500
Gas pipe
26
Detail drawing of 40
223,5
Liquid pipe
645
355
565,5
Oval hole of 50
20 x12 25 Unit anchor
support
40
95
327 6
60 66
25 80
658
Distanc 82
e betwe
en hole
s 1550
F
E
D
Electric SI
al
heater SIDE
supply E
Air filter
27
DIMENSIONS FREECOOLING
MODELS 10-12
FREECOOLING 1-DAMPER
1250
1250
820
32
305
20
27
495
25
425
303
Drainage
outside thread First damper
184 freecooling
452 3/4'' Male
349
123 Electrical box
Power supply connection 159 200
25
Thermostat connection
480
303
480
F
90
280
5
Distanc 455 45 73
4
e betwe 81
en hole
s 1300 4
40
FREECOOLING 2-DAMPER
Air filter
1250
1250
820
32
305
20
27
495
25
425
303
349
123 Electrical box
Power supply connection 200 200
159
25
Thermostat connection
480
303
480
90
280
5 4
Distanc 455 45 73
e betwe 81
en hole 4
s 1300
40
Air filter
Second damper
freecooling
28
DIMENSIONS FREECOOLING
MODEL 16
FREECOOLING 1-DAMPER
1300
1330
Power supply connection
830
32
320
20
27
595
25
500
355
Thermostat connection
Drainage
outside thread First damper
249 3/4'' Male freecooling
422
586
355
586
F
98
324
5
455 45 5
Distanc
e betwe 147 74
en hole
s 1350 4
47
FREECOOLING 2-DAMPER
Air filter
1300
1330
Power supply connection
830
32
320
20
27
595
25
500
Thermostat connection
355
25
586
355
586
98
324
5
455 45 5
Distanc 147 74
e betwe
en hole 4
s 1350
47
Air filter
Second damper
freecooling
29
DIMENSIONS FREECOOLING
MODEL 22
FREECOOLING 1-DAMPER
1450
1520
900
36,5
47
25
595
497
355
Thermostat
connection
Drainage
outside thread
262 3/4'' Male
462
Power supply
connection 324
92 1450
1520
32 Electrical
620 300 box
200
20
193
2255
595
556
515,5
355
F
First damper
107
324 freecooling
0
58 14
591 8 Air filter
Distanc 48
FREECOOLING 2-DAMPER e betwe
en hole 93
s 1500 5
1450
1520 Air filter
900
36,5
47
25
595
497
355
Thermostat
connection
Drainage
outside thread
262 3/4'' Male
462
Power supply
connection 324
92 1450
1520
32 Electrical
620 300 box
200 20 200
193
2255
595
556
355
556
First damper
107 freecooling
324
0
58 4
Distanc
580 81 Air filter
e betwe 48
en hole 93
s 1500 5
Air filter
Second damper Freecooling
30
DIMENSIONS FREECOOLING
MODELS 24-28-30
FREECOOLING 1-DAMPER
1500
1800
1025
25
645
355
Drainage
214
outside thread
490 3/4'' Male
398 1500
410 1800
103
Electrical box 775 677
Thermostat Power supply
26
connection connection 200
223,5
83
2255
645
537
355
565,4
95
327 5
70 6
658 91 First damper
Distanc 82 freecooling
FREECOOLING 2-DAMPER e betwe
en hole 71
s 1550 7
1500
1800
Air filter
1025
25
645
355
Drainage
214
outside thread
490 3/4'' Male
398
410 1500
103 1800
Electrical box
Thermostat Power supply 775 677
connection connection
200 83 200
223,5
2255
645
537
355
641
95
327 5
70 6
91 First damper
705
Distanc
e betwe 56 freecooling
en hole 1
s 1550 77
Air filter
Second damper freecooling
31
UNIT OPENING SIZES MODELS 10-12
OUTDOOR SECTION
368 349
303
495
E.B.
495
123
303
349
170
38
STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
OPENING OPENING
495
425
495
425
43
43
IL
COMPRESSOR
D0
CO
B0 O
IL
C
R
STANDARD OPTIONAL
OO
R
O B0 B1
O EXTRACTOR EXTRACTOR
ND
TD OPENING OPENING
I
U
O
INDOOR SECTION
EXTERNAL INTERNAL 280 90
FAN FAN C0 90 280
A0
159
E.B.
303
A1 C1
495
495
303
STANDARD EXECUTION
170
OPTIONAL EXECUTION
ELECTRICAL BOX STANDARD OPTIONAL
C0 BLOWER C1 BLOWER
OPENING OPENING
14
14
495
495
422
422
32
UNIT OPENING SIZES MODEL 16
OUTDOOR SECTION
428 324
355
595
595
E.B.
355
324 123
213
58
STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
OPENING OPENING
595
500
500
595
B1 D1
63
63
STANDARD OPTIONAL
IL
COMPRESSOR
D0 B0 B1
CO
B0 IL EXTRACTOR EXTRACTOR
O OPENING
C OPENING
OR
R
O
DO
O
TD
I N
U
O
INDOOR SECTION
98 324 324 98
27
OUTDOOR INDOOR
FAN FAN C0
182
A0
355
595
E.B.
595
355
A1 C1
213
STANDARD CONFIGURATION
STANDARD OPTIONAL
OPTIONAL CONFIGURATION C0 BLOWER BLOWER
C1
OPENING OPENING
ELECTRICAL BOX
25
25
595
595
517
517
33
UNIT OPENING SIZES MODEL 22
OUTDOOR SECTION
193
355
391,5 324
595
595
324 92
355
193
STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
OPENING OPENING
595
497
595
497
B1 D1
E.B.
COMPRESSOR
61
61
IL
CO
STANDARD OPTIONAL
B0 IL D0 B0 EXTRACTOR B1 EXTRACTOR
OR
O
C OPENING OPENING
DO
R
O
IN
O
TD
U
O INDOOR SECTION
107 324 324 107
EXTERNAL INTERNAL
C0
193
FAN FAN
A0
355
595
595
355
A1 C1
193
26
515,5
515,5
595
595
34
UNIT OPENING SIZES MODELS 24-28-30
OUTDOOR SECTION
103 410
214
355
645
645
355
410 103
214
B0 D1
STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
COMPRESSOR
OPENING OPENING
IL
D0
CO
40
R
OO
ND
IL
E.B.
CO
677 174
I
222 677
OR
537
537
DO
645
645
T
OU
C0
EXTERNAL INTERNAL
68
A0 FAN FAN
STANDARD OPTIONAL
B0 EXTRACTOR B1 EXTRACTOR
A1 C1 OPENING OPENING (*)
ELECTRICAL BOX
223
355
213
B0
STANDARD OPTIONAL
C0 BLOWER C1 BLOWER
COMPRESSOR
B1 OPENING OPENING
26
26
CO
E.B.
IL
565,5
565,5
645
645
EXTERNAL
FAN
A0
35
UNIT INSTALLATION
Ceiling supports
(shock absorbers)
Floor supports
(shock absorbers)
Y Y
MODELS 10-12-16-22 MODELS 24-28-30
D C D
C Indoor Sec.
Indoor Sec.
Fan. il Fan.
Co
il Co
E B E
B
G G
Comp.
Outdoor Sec. Outdoor Sec.
C
YG il
oi
YG Co
l
A A
XG G POINT: Centre of gravity XG
36
UNIT INSTALLATION
er
et
m
1
1 mete
r
er 1 mete
et r
m
1
For the unit with optional FREECOOLING, it should be kept in mind that the bedplate anchors
cannot be used to hang the unit.
Consult others options for outdoor mounting or changes in position of the air return duct if the unit
is to be hung.
If the unit is going to be hung using the anchor supports and the optional air return opening, the
supports must be repositioned so that the air filter may be removed.
To move the supports, unscrew them from the inside and fix them again using the holes located
next to the initial position.
DRAINS
All indoor sections of these units ( and the outdoors section for the Heat Pump) have a ¾” steel threaded drain
pipe welded to the condensation tray.
Drain pipe
2%
2%
Trap
One PVC drain trap is supplied with the cooling-only units, and two with the heat pump units.
Connect the trap/s to the drain pipe/s on the unit and mount the drain pipe with at least a 2% incline from the trap.
Also slightly tip the unit (2%) toward the drainage side. Check the condensation trays are clean and free from dirt
and other debris from the works and that water drains correctly.
37
PIPE CONNECTIONS
To determine the pipe connections between outdoor and indoor units follow data:
A,B,C : Placement units
L : Total length.
1 = Gas pipe line.
2%
2 = Liquid pipe line.
2
OUTDOOR UNIT INDOOR UNIT
1
L
C
2%
2%
INDOOR UNIT
PLACEMENT A : In gas pipe line is 1 necessary to install on vertical base a trap as well as a trap in the upper
base each 8m. The minimum speed suction must be below 6m/s.
PLACEMENT B : Do the cooling line pipe inclination to the outdoor unit. Pay attention in distance of more than 10m
and avoid collapse on pipe lines installation.
PLACEMENT C : It is necessary to install on the base pipe a vertical trap. It is not necessary intermediate trap.
UNIT - MODEL
PIPES LINE
10 12 16 22 24 28 30
Liquid 3/8" 3/8" 1/2" 5/8" 5/8" 5/8'' 5/8''
0 to 10 m.
Gas 3/4" 3/4" 7/8" 7/8" 11/8" 11/8" 11/8"
Liquid 3/8" 3/8" 5/8" 5/8" 5/8" 5/8'' 3/4''
Total line length 10 to 30 m.
Gas 7/8" 7/8" 7/8" 11/8" 11/8" 11/8" 13/8"
30 to 50 m. Liquid 1/2" 1/2" 5/8" 5/8" 3/4'' 3/4'' 3/4''
Gas 7/8" 7/8" 11/8" 11/8" 13/8" 13/8" 13/8"
Liquid 3/8" 3/8" 1/2" 5/8" 5/8" 5/8'' 5/8''
Unit connections
Gas 3/4" 3/4" 7/8" 7/8" 11/8" 11/8" 11/8"
Maximum vertical line length (m.) 15 15 15 15 15 15 15
Maximum number of bends 12 12 12 12 12 12 12
Between length of 30 and 50m superior you have to make a recalculation according to our technical
commercial department or distribution itself to maintain certain aspects how to make the installation
(additional charge of oil, solenoid valves etc...)
38
ELECTRICAL CONNECTION
Electrical
1 Electrical supply. box 4
2 Connection indoor / outdoor unit.
Indoor 2 Outdoor thermostat
unit unit control
3 Electrical heater power supply. 1
Electronic
4 Connection thermostat control. 3 Card
POWER SUPPLY 2
Nr. OF CABLES x SECTION (mm )
230V SINGLE-PHASE
UNITS 1 1 2 3 4
UNIT Connection
PE N L X1 MODEL Power supply Power supply outdoor-indoor unit Electrical heater Shielded
WITHOUT WITH electrical WITHOUT power supply Cable
electrical heater. heater. electrical heater.
2
POWER SUPPLY Nr. OF CABLES x SECTION (mm )
230V THREE-PHASE
1 1 2 3 4
UNITS UNIT Connection
MODEL Power supply Power supply Electrical heater Shielded
WITHOUT WITH electrical outdoor-indoor unit power supply Cable
electrical heater. heater. WITHOUT
PE L1 L2 L3 electrical heater.
X1
10 4x4 4 x 10 5 x 1,5 4x4+2x1 2x1
12 4x4 4 x 10 5 x 1,5 4x4+2x1 2x1
2
Nr. OF CABLES x SECTION (mm )
POWER SUPPLY UNIT 1 1 2 3 4
400V THREE-PHASE MODEL Power supply Power supply Connection Electrical heater Shielded
WITHOUT WITH electrical outdoor-indoor unit power supply Cable
UNITS electrical heater. heater. WITHOUT
electrical heater.
10 5 x 2,5 5x4 5 x 1,5 4 x 2,5 + 2 x 1 2x1
The sections have been calculated for a length no longer than 50m and a voltage drop of 10V.
VOLTAGE OPERATING LIMITS
MODELS VOLTAGE LIMIT
10 230 V-1Ph-50Hz 198-264 V -1Ph- 50Hz
230 V-3Ph-50Hz 180-242 V -3Ph- 50Hz
10-12-16-22
400 V-3Ph-50Hz 342-462 V -3Ph- 50Hz
230 V-3Ph-50Hz 198-264 V -3Ph- 50Hz
24-28-30
400 V-3Ph-50Hz 342-462 V -3Ph- 50Hz
39
OPERATING LIMITS
(*) With condensation pressure control (optional), 0ºC minimum outdoor operating temperature.
(**) With kit got gas bypass valve.
INDOOR
32ºC DB / 23ºC WB 21ºC DB / 15ºC WB
COOLING CYCLE TEMPERATURE
OPERATION OUTDOOR DEPENDING ON MODEL 0ºC (MODELS 22/24/28/30)
TEMPERATURE (TABLE 1) 19ºC (MODELS 10/12/16) (*)
-10ºC(**)
INDOOR
TEMPERATURE 27ºC DB 15ºC DB
HEATING CYCLE
OPERATION OUTDOOR
TEMPERATURE 24ºC DB / 18ºC WB -10ºC DB / -11ºC WB
(*) With condensation pressure control (optional), 0ºC minimum outdoor operating temperature.
(**) With kit got gas bypass valve.
MODELS 10 12 16 22 24 28 30
MODELS 10 12 16 22 24 28 30
40
OPTIONS
ELECTRIC HEATER
Optionally, these units can contain shielded element electric heating batteries that are mounted on the inside of the unit in the schematic
opposite.
The electric heater must get its power from the unit’s electrical box.
A HEATING COIL FROZEN DUE TO LOW AMBIENT CONDITIONS IS NOT COVERED BY THE WARRANTY.
MAIN SWITCH
The main switch is located on the access panel to the electrical box in the outdoor section in such a way that the unit is disconnected
when the panel is opened.
(Refer to the size diagram a pages 20 to 31 to see the position of the electrical box access panel).
Check to make sure that the main switch is large enough to handle the current for the unit if electric heaters are installed.
PHASE SEQUENCER (THREE-PHASE UNIT)
The phase sequencer is located in the electrical box in the outdoor section, thus assuring that the unit will not begin operation while
the phase connection of the compressor is not correct. Should this occur, then just switch two phase connections.
ON/OFF CONDENSATION PRESSURE CONTROL (MODELS 10-12-16)
Consists of a pressure switch, which starts and stops the outdoor fan regulating the condensation temperature, thus the unit will be
able to operate in the cooling cycle when the outdoor temperature is below 19ºC (until 0ºC).
HOT GAS BYPASS VALVE
The purpose of the BYPASS valve is to make it possible for the unit to operate at low outdoor temperatures (until -10°C), to be used
in cooling-only and heat-pump units in the cooling cycle.
It regulates the capacity of the compressor by injecting hot gas from the compressor discharge side to the evaporator.
CONTROL USING A PROGRAMMABLE CONTROLLER.
With the programmable controller option, the desired temperature can be programmed in the area 24 hours a day, 7 days a week.
REMOTE ROOM-TEMPERATURE SENSOR, REMOTE DUCT SENSOR
These sensors may be used in conjunction with remote controller, allowing the controller to be mounted in a room away from the
conditioned space.
- REMOTE DUCT SENSOR: The sensor will be located in the return air duct, detecting the air temperature of the air being air conditioned.
- REMOTE ROOM-TEMPERATURE SENSOR: The sensor will be placed in the area to be air conditioned.
FREECOOLING THERMOSTAT KIT
The Freecooling Thermostat Kit will only operate in cooling-only or heat-pump units in the cooling cycle. This is an energy saving
system that regulates the dampers doors through which outdoor air is taken in when the outdoor temperature is lower than the area
to be air conditioned.
This kit consists of the damper, a motor, power card and a controller with specific programming, safety thermostat for air discharge
and outdoor sensor, completely factory-assembled.
CRANKCASE HEATER (COOLING-ONLY UNITS)
When the unit is operating at low outdoor temperatures it is advisable to fit a crankcase heater.
The purpose of the heater is to keep the oil in the compressor at the correct temperature while the compressor is stopped so that it
can be properly lubricated when started again.
41
OPTIONS
41
400
SOUND MUFFLER
Available for models 16, 22, 24, 28, 30.
420
Field assembled, designed to be installed at the extractor opening of the outdoor
660
unit in order to reduce noise, particularly when the outdoor unit is installed without
ducts, free discharge.
This kit contains the sound muffler and adapter parts for fixing it to the unit.
660 600
Adapter parts
OUTDOOR MOUNTING KIT
Sound muffler
Field assembly.
This option has to be ordered for packaged units when they will be installed outside.
The kit includes an air filter and grille for outdoor air intake which should be installed on the suction side of the outdoor unit, an anti-
rain hood which should be installed on the discharge side of the outdoor fan. For units 10-12-16 it includes also an anti-rain plate
which should be installed on the electrical box. Anti-rain plate
Anti-rain hood (only models 10-12-16)
DIMENSIONS C
MODELS
A B C D E F G D
10-12 180 432 459 280 313 356 104
16 180 507 429 311,8 364 330 104 B E
GERMANY UKRAINE
www.lennoxdeutschland.com www.lennoxukraine.com
PORTUGAL
www.lennoxportugal.com
MSL60E-0701 12-2006