0% found this document useful (0 votes)
29 views44 pages

Flatair - Agu - Msl60e-0701 12-2006 - LQ

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views44 pages

Flatair - Agu - Msl60e-0701 12-2006 - LQ

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

Application guide

FLATAIR - FLCK/FLHK

Providing indoor climate comfort

MSL60E-0701 12-2006
Congratulations you have made a wise choice and we feel sure that it will meet your expectation

INDEX

CONTENTS PAGE

• GENERAL DESCRIPTION 2-3


• DENOMINATION 4
• PRODUCT RANGE 5
• PHYSICAL DATA 6-8
• ELECTRICAL DATA 9-10
• FAN SERVICES 11
• SOUND DATA 12
• CAPACITIES TABLE 13-19
• UNIT DIMENSIONS 20-31
• BLOWER DIMENSIONS
STANDARD AND OPTIONAL 32-35
• UNIT INSTALLATION 36-37
• PIPES CONNEXIONS 38
• ELECTRICAL CONNEXIONS 39
• OPERATING LIMITS 40
• OPTIONS 41-42

Lennox have been providing environmental solutions since 1895, our range of FLATAIR continues to meet the
standards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs and
uncompromising attention to detail. Engineered to last, simple to maintain and Quality that comes as standard.
Information on local contacts at www.lennoxeurope.com.

All the technical and technological information contained in this manual, including any drawing and technical
descriptions provided by us, remain the property of Lennox and must not be utilised (except in the operation of
this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
1
GENERAL DESCRIPTION
The horizontal air conditioning units, range Flatair, cooling only or heat pump are air condensed units designed
for small shopping center and housing. Those units have two sections: outdoors and indoors. They can be supplied
either compact or on split system.
Due to their small dimensions they are designed for false ceiling and can be placed in air conducts both indoors
and outdoors.
A wide range of optionals, completed-factory assembled are also available.

FURNITURE FAN
Painted in galvanized metal furniture, high resistant Outdoor and indoor fans are centrifugal with an
to corrosion. The units are provided with metal assembled engine, statically balancing, with a low
profiles, capable of withstanding the unit and able sound level.
as well of installing the unit hung from the ceiling or Those fans are assembled to the inserted panel of
mounted on the floor. the units and split from upper side of the fan with
The panel are easily inter exchangeable, giving insulated materials to void vibrations.
several air suction and return alternatives.
The outdoor sections are equipped with a meta grilles
with in the blower panel " except in models 24-28-
EXCHANGER
30 and in the duct discharge to avoid damages (in Made-up with copper pipes and aluminium wings,
the whole models). designed to get a high heating transfer.
An insulation with a protection of mesh is used in Their dimensions and design of the circuits have
indoor units with a classification of M1 and F1, been specially worked to obtain the maximum
certifying that the material is auto-extinguishable performance of the exchanger increasing the power
and avoiding the fumes inside the room to be of the unit and reducing the consumption.
aconditionned. The auto extinguishable insulation
M1 is used in indoor units.
COOLING CIRCUIT
COMPRESSORS
Carried out with welded deshydratable copper pipes
All units are provided with scroll compressor, cooling with pressuring outlets with plugged valves in the
by a suction gas with thermic protection inside the suction and liquid lines both indoors and outdoor
engine, so no other additional protection is required. units.
It is mounted on anti-vibration devices both external In unit 24-28-30 the pressuring outlets in the outdoor
and internal. section are approachable from the outer part of the
On units 24/28/30 the compressors have a screwed unit.
connection into the pipe- Thus, they can be more The unit is equipped with both high-low pressure
easily to assembled. switches with an automatic rearm. It also has a
In heat pump units the compressors are provided dehumidifying filter, expansion system with
with a crankcase heater to heat the oil in the restrictors in units 10-12-16; stoppage of
compressor so that a suitable lubrication can take impurities/dirts and air reducing valves in units 22-
place. 24-28-30. The heat pump units are equipped as
well with a suction pump battery to avoid the leaks
to the compressor, reversible valves to reserve the
AIR FILTER cycle of unidirectional valve.

Washable air filter; auto extinguishable material with


M1 classification, high efficiency filtrate with G2
ELECTRICAL CIRCUIT
classification. It can be removed through the upper Designed according to EN 60204-1 normative
and the sizes. hermetically sealed to avoid condensation. With
protective fuses for compressors and fans. All the
engines in compressors and fans have internal
thermic protectors and an electronic control plate
controls the unit.

2
GENERAL DESCRIPTION

CONTROL
Made up with a printed control circuit plate for the opening unit and with a walled terminal thermostat to be placed
in the room to be aconditioned; with sound output inside the terminal and with a sound installed in the outdoor
batteries for the regulation of the system.
With a LCD display with alarm visualization, exclusive connection with two files between terminal thermostat and
electrical box in the unit, possibility to adjust internal parameters. automatic restarting and high pressure control
ON/OFF on unit models 22-24-28-30, with well intelligent defrosting control adapted to ambient conditions in each
moment and each side (for small heat pump).

PHOTOGRAPHY CORRESPONDING TO A TERMINAL THERMOSTAT.

OPTIONS
• Heating electrical heater, type armoured pipe to be mounted into the unit.
• Hot water coil.
• Head pressure control ON/OFF for models 10-12-16.
• Crankcase for units cooling only.
• Main switch.
• Phase sequencer (3 phase unit).
• Hot gas bypass valve.
• Control programmable controller.
• Remote duct sensor on return.
• Ambient remote sensor.
• Thermostatic freecooling.
• Sound muffler.
• External mounting kit.
• Freecooling external mounted kit.
• Outdoor air filter.

3
DENOMINATION

PACKAGED UNITS

F L C K 22
Unit size.
Type of unit Type of refrigerant Approximately cooling
Horizontal compact A: R-22 capacity in kW.
FLATAIR K: R-407C
Application
C: Cooling only
H: Heat pump

INDOOR UNIT + OUTDOOR UNIT


K F C K 22
Unit size.
Approximate cooling
Type of unit Type of unit capacity in kW.
K: Outdoor unit FLATAIR
Type of refrigerant
L: Indoor unit
Application A: R-22
C: Cooling only K: R-407C
H: Heat pump O: R-22 y R-407C
X: Cooling only and heat pump units

4
RANGE PRODUCT

UNITS COOLING ONLY WITH REFRIGERANT R-407C


NOMINAL NOMINAL
OUTDOOR INDOOR CAPACITY W CONSUMPTION kW
MODEL V / Ph / 50 Hz
UNIT UNIT
COOLING COOLING
FLCK 10 KFCK 10 230V/1Ph
LFXO 10 9.800 3,68
FLCK 10 KFCK 10 230-400V/3Ph

FLCK 12 KFCK 12 LFXO 12 230-400V/3Ph 11.800 4,57

FLCK 16 KFCK 16 LFXO 16 230-400V/3Ph 15.300 6,40

FLCK 22 KFCK 22 LFCK 22 230-400V/3Ph 19.500 8,09

FLCK 24 KFCK 24 LFCK 24 230-400V/3Ph 22.000 9,02

FLCK 28 KFCK 28 LFCK 28 230-400V/3Ph 26.300 10,40

FLCK 30 KFCK 30 LFCK 30 230-400V/3Ph 28.100 12,20

UNITS HEAT PUMP WITH REFRIGERANT R-22


NOMINAL NOMINAL
OUTDOOR INDOOR CAPACITY W CONSUMPTION kW
MODEL UNIT UNIT V / Ph / 50 Hz
COOLING H. PUMP COOLING H. PUMP
FLHA 10 KFHA 10 230V/1Ph
LFXO 10 9.400 10.300 3,50 2,93
FLHA 10 KFHA 10 230-400V/3Ph

FLHA 12 KFHA 12 LFXO 12 230-400V/3Ph 11.300 12.300 4,31 3,44

FLHA 16 KFHA 16 LFXO 16 230-400V/3Ph 14.700 15.600 6,11 4,94

FLHA 22 KFHA 22 LFHA 22 230-400V/3Ph 19.200 20.000 7,92 6,60

FLHA 24 KFHA 24 LFHA 24 230-400V/3Ph 21.000 22.800 8,80 7,80

FLHA 28 KFHA 28 LFHA 28 230-400V/3Ph 26.000 27.000 10,36 8,43

FLHA 30 KFHA 30 LFHA 30 230-400V/3Ph 27.600 29.800 11,78 9,43

UNITS HEAT PUMP WITH REFRIGERANT R-407C


NOMINAL NOMINAL
OUTDOOR INDOOR CAPACITY W CONSUMPTION kW
MODEL UNIT UNIT V / Ph / 50 Hz
COOLING H. PUMP COOLING H. PUMP
FLHK 10 KFHK 10 230V/1Ph
LFXO 10 9.800 10.000 3,68 3,16
FLHK 10 KFHK 10 230-400V/3Ph
FLHK 12 KFHK 12 LFXO 12 230-400V/3Ph 11.800 12.000 4,57 4,11

FLHK 16 KFHK 16 LFXO 16 230-400V/3Ph 15.300 15.500 6,40 5,60

FLHK 22 KFHK 22 LFHK 22 230-400V/3Ph 19.500 20.200 8,09 6,74

FLHK 24 KFHK 24 LFHK 24 230-400V/3Ph 22.000 22.500 9,02 8,60

FLHK 28 KFHK 28 LFHK 28 230-400V/3Ph 26.300 27.000 10,40 9,20

FLHK 30 KFHK 30 LFHK 30 230-400V/3Ph 28.100 28.700 12,20 10,32

5
PHYSICAL DATA (COOLING ONLY)

R-407C

SET FLCK 10 FLCK 12 FLCK 16 FLCK 22 FLCK 24 FLCK 28 FLCK 30

Cooling capacity (*) kW 9,8 11,8 15,3 19,5 22,0 26,3 28,1

DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 1250 1250 1330 1520 1800 1800 1800

NET WEIGHT Kg 200 205 280 325 405 425 430

OUTDOOR UNIT KFCK 10 KFCK 12 KFCK 16 KFCK 22 KFCK 24 KFCK 28 KFCK 30

COMPRESSOR No. / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
FAN
Maximum air flow m3 /h. 3500 3400 4950 5900 6600 6400 6400
Minimum air flow m3 /h. 2350 2400 3750 4350 4500 5000 5250
Maximum available pressure (1) Pa 100 90 120 150 160 120 100

NET WEIGHT Kg 130 135 180 195 265 275 285


DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 820 820 830 900 1025 1025 1025
PIPES CONNEXIONS
Liquid 3/8'' 3/8'' 1/2'' 5/8'' 5/8'' 5/8'' 5/8''
Gas 3/4'' 3/4'' 7/8'' 7/8'' 1-1/8'' 1-1/8'' 1-1/8''

INDOOR UNIT LFXO 10 LFXO 12 LFXO 16 LFCK 22 LFCK 24 LFCK 28 LFCK 30

FAN
Maximum air flow m3 /h. 2350 2300 3700 5350 6300 6000 6000
Minimum air flow m3 /h. 1500 1650 2400 3200 4000 4250 4500
Maximum available pressure (1) Pa 120 110 160 180 240 200 180

NET WEIGHT Kg 70 70 100 130 140 150 150


DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 430 430 500 620 775 775 775
PIPES CONNEXIONS
Liquid 3/8'' 3/8'' 1/2'' 5/8'' 5/8'' 5/8'' 5/8''
Gas 3/4'' 3/4'' 7/8'' 7/8'' 1-1/8'' 1-1/8'' 1-1/8''

(*) Air intake temperature in the indoor exchanger 27ºC DB/19ºC WB DB.- Dry bulb temperature
(*) Air intake temperature in the outdoor exchanger: 35ºC DB WB.- Wet bulb temperature
(1) With admissible minimum air flow.

6
PHYSICAL DATA UNITS HEAT PUMP
R-22

SET FLHA 10 FLHA 12 FLHA 16 FLHA 22 FLHA 24 FLHA 28 FLHA 30

Cooling capacity (*) kW 9,4 11,3 14,7 19,2 21,0 26,0 27,6

Heating capacity (**) kW 10,3 12,3 15,6 20,0 22,8 27,0 29,8
DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 1250 1250 1330 1520 1800 1800 1800
NET WEIGHT Kg 205 210 285 330 410 430 435

OUTDOOR UNIT KFHA 10 KFHA 12 KFHA 16 KFHA 22 KFHA 24 KFHA 28 KFHA30

COMPRESSOR No. / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
FAN
Maximum air flow m3 /h. 3500 3400 4950 5900 6600 6400 6400
Minimum air flow m3 /h. 2350 2400 3750 4350 4500 5000 5250
Maximum available pressure (1) Pa 100 90 120 150 160 120 100

NET WEIGHT Kg 135 140 185 200 270 280 285


DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 820 820 830 900 1025 1025 1025
PIPES CONNEXIONS
Liquid 3/8'' 3/8'' 1/2'' 5/8'' 5/8'' 5/8'' 5/8''
Gas 3/4'' 3/4'' 7/8'' 7/8'' 1-1/8'' 1-1/8'' 1-1/8''

INDOOR UNIT LFXO 10 LFXO 12 LFXO 16 LFHA 22 LFHA 24 LFHA 28 LFHA30

FAN
Maximum air flow m3 /h. 2350 2300 3700 5350 6300 6000 6000
Minimum air flow m3 /h. 1500 1650 2400 3200 4000 4250 4500
Maximum available pressure (1) Pa 120 110 160 180 240 200 180

NET WEIGHT Kg 70 70 100 130 140 150 150


DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 430 430 500 620 775 775 775
PIPES CONNEXIONS
Liquid 3/8'' 3/8'' 1/2'' 5/8'' 5/8'' 5/8'' 5/8''
Gas 3/4'' 3/4'' 7/8'' 7/8'' 1-1/8'' 1-1/8'' 1-1/8''

(*) Air intake temperature in the indoor exchanger: 27ºC DB/19ºC WB DB.- Dry bulb temperature
(*) Air intake temperature in the outdoor exchanger: 35ºC DB WB.- Wet bulb temperature
(**) Air intake temperature in the indoor exchanger: 20ºC DB / 12ºC WB (1) With admissible minimum air flow.
(**) Air intake temperature in the outdoor exchanger: 7ºC DB / 6ºC WB

7
PHYSICAL DATA UNITS HEAT PUMP
R-407C

SET FLHK 10 FLHK 12 FLHK 16 FLHK 22 FLHK 24 FLHK 28 FLHK 30

Cooling capacity (*) kW 9,8 11,8 15,3 19,5 22,0 26,3 28,1

Heating capacity (**) kW 10,0 12,0 15,5 20,2 22,5 27,0 28,7

DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 1250 1250 1330 1520 1800 1800 1800
NET WEIGHT Kg 205 210 285 330 410 430 435

OUTDOOR UNIT KFHK 10 KFHK 12 KFHK 16 KFHK 22 KFHK 24 KFHK 28 KFHK 30

COMPRESSOR No. / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
FAN
Maximum air flow m3 /h. 3500 3400 4950 5900 6600 6400 6400
Minimum air flow m3 /h. 2350 2400 3750 4350 4500 5000 5250
Maximum available pressure (1) Pa 100 90 120 150 160 120 100

NET WEIGHT Kg 135 140 185 200 270 280 285


DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 820 820 830 900 1025 1025 1025
PIPES CONNEXIONS
Liquid 3/8'' 3/8'' 1/2'' 5/8'' 5/8'' 5/8'' 5/8''
Gas 3/4'' 3/4'' 7/8'' 7/8'' 1-1/8'' 1-1/8'' 1-1/8''

INDOOR UNIT LFXO 10 LFXO 12 LFXO 16 LFHK 22 LFHK 24 LFHK 28 LFHK 30

FAN
Maximum air flow m3 /h. 2350 2300 3700 5350 6300 6000 6000
Minimum air flow m3 /h. 1500 1650 2400 3200 4000 4250 4500
Maximum available pressure (1) Pa 120 110 160 180 240 200 180

NET WEIGHT Kg 70 70 100 130 140 150 150


DIMENSIONS
Height mm. 495 495 595 595 645 645 645
Width mm. 1250 1250 1300 1450 1500 1500 1500
Depth mm. 430 430 500 620 775 775 775
PIPES CONNEXIONS
Liquid 3/8'' 3/8'' 1/2'' 5/8'' 5/8'' 5/8'' 5/8''
Gas 3/4'' 3/4'' 7/8'' 7/8'' 1-1/8'' 1-1/8'' 1-1/8''

(*) Air intake temperature in the indoor exchanger: 27ºC DB/19ºC WB DB.- Dry bulb temperature
(*) Air intake temperature in the outdoor exchanger: 35ºC DB WB.- Wet bulb temperature
(**) Air intake temperature in the indoor exchanger: 20ºC DB / 12ºC WB (1) With admissible minimum air flow.
(**) Air intake temperature in the outdoor exchanger: 7ºC DB / 6ºC WB

8
ELECTRICAL DATA

R-22
UNIT MODELS FLHA 10 FLHA 12 FLHA 16 FLHA 22 FLHA 24 FLHA 28 FLHA 30

230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power
Total power in cooling cycle kW 3,50 4,31 6,11 7,92 8,80 10,36 11,78
Total power in heating cycle kW 2,93 3,44 4,94 6,60 7,80 8,43 9,43

Maximum current 24,3


Total current A
31,7/18,3 37,2/21,5 39,8/23,0 44,0/25,4 52,0/30,0
22,4/12,9 25,0/14,4
101
Start up current A
97/52 104/56 145/73 193/110 182/108 226/132 240/136

UNIT MODELS KFHA 10 KFHA 12 KFHA 16 KFHA 22 KFHA 24 KFHA 28 KFHA 30

230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power
Compressor (cooling cycle) kW 2,60 3,41 4,11 5,02 5,85 7,41 8,83
Compressor (heating cycle) kW 2,03 2,54 2,94 3,70 4,85 5,48 6,48
Fan outdoor section kW 0,52 0,52 1,10 1,60 1,60 1,60 1,60

Total power in cooling cycle kW 3,12 3,93 5,21 6,62 7,45 9,01 10,43
Total power in heating cycle kW 2,55 3,06 3,50 5,30 6,45 7,08 8,08
Maximum current
18,6
Compressor A 16,7/7,2 19,3/8,7 19,9/11,5 22,4/12,9 25,3/14,6 28,5/16,3 36,5/21,0
3,1 3,1
Fan outdoor section A
4,8/2,8 7,4/4,3 8,1/4,7 8,1/4,7 8,1/4,7
21,7
Total current A
19,8/10,3 22,4/11,8 24,7/14,3 29,8/17,2 33,4/19,3 36,6/21,0 44,6/25,7
98
Start up current A 94/49 101/53 138/69 185/105 174/104 218/128 232/132

UNIT MODELS LFXO 10 LFXO 12 LFXO 16 LFHA 22 LFHA 24 LFHA 28 LFHA 30

230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power kW 0,38 0,38 0,90 1,30 1,35 1,35 1,35
2,6 2,6
Maximum current A
7/4 7,4/4,3 7,4/4,3 7,4/4,3 7,4/4,3
7,8 7,8
Start up current A
21/13 22/14 22/14 22/14 22/14

9
ELECTRICAL DATA
R-407C
UNIT MODELS FLCK 10 FLCK 12 FLCK 16 FLCK 22 FLCK 24 FLCK 28 FLCK 30
FLHK 10 FLHK 12 FLHK 16 FLHK 22 FLHK 24 FLHK 28 FLHK 30
230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power
Total power in cooling cycle kW 3,68 4,57 6,40 8,09 9,02 10,40 12,20
Total power in heating cycle kW 3,16 4,11 5,60 6,74 8,60 9,20 10,32
Maximum current
24,3
Total current A
22,4/12,9 25,0/14,4 31,7/18,3 37,2/21,5 39,8/23,0 44,0/25,4 52,0/30,0
101
Start up current A
97/52 104/56 145/73 193/110 182/108 226/132 240/136

UNIT MODELS KFCK 10 KFCK 12 KFCK 16 KFCK 22 KFCK 24 KFCK 28 KFCK 30


KFHK 10 KFHK 12 KFHK 16 KFHK 22 KFHK 24 KFHK 28 KFHK 30
230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power
Compressor (cooling cycle) kW 2,78 3,67 4,40 5,19 6,07 7,45 9,25
Compressor (heating cycle) kW 2,26 3,21 3,60 3,84 5,65 6,25 7,37
Fan outdoor section kW 0,52 0,52 1,10 1,60 1,60 1,60 1,60

Total power in cooling cycle kW 3,30 4,19 5,50 6,79 7,67 9,05 10,85
Total power in heating cycle kW 2,78 3,73 4,70 5,44 7,25 7,85 8,97
Maximum current 18,6
Compressor A 16,7/7,2 19,3/8,7 19,9/11,5 22,4/12,9 25,3/14,6 28,5/16,3 36,5/21,0
3,1 3,1
Fan outdoor section A
4,8/2,8 7,4/4,3 8,1/4,7 8,1/4,7 8,1/4,7
21,7
Total current A
19,8/10,3 22,4/11,8 24,7/14,3 29,8/17,2 33,4/19,3 36,6/21,0 44,6/25,7
98
Start up current A
94/49 101/53 138/69 185/105 174/104 218/128 232/132

LFCK 22 LFCK 24 LFCK 28 LFCK 30


UNIT MODELS LFXO 10 LFXO 12 LFXO 16
LFHK 22 LFHK 24 LFHK 28 LFHK 30
230V/ 1Ph
Voltage V/f (50 Hz)
230V-400V/ 3Ph
Rated absorbed power kW 0,38 0,38 0,90 1,30 1,35 1,35 1,35
2,6 2,6
Maximum current A
7/4 7,4/4,3 7,4/4,3 7,4/4,3 7,4/4,3
7,8 7,8
Start up current A
21/13 22/14 22/14 22/14 22/14

10
FAN SERVICES

INDOOR UNITS AIR FLOW m3/h


MODELS 10 12 16 22 24 28 30
0 2350 2300 3700 5350 6300 6000 6000
10 2275 2250 3625 5200 6225 5925 5925
20 2240 2200 3550 5090 6140 5860 5860
AVAILABLE STATIC PRESSURE Pa.
30 2190 2150 3475 4960 6100 5800 5800
40 2140 2100 3400 4850 6010 5725 5725
50 2080 2040 3320 4725 5930 5650 5650
60 2025 1975 3240 4610 5875 5600 5600
70 1975 1925 3160 4505 5790 5510 5510
80 1925 1860 3090 4400 5710 5440 5440
NOMINAL 90 1840 1800 3000 4300 5620 5350 5350
AIR FLOW 100 1775 1730 2915 4160 5540 5275 5275
110 1625 1650 2825 4040 5450 5190 5190
120 1500 --- 2750 3925 5350 5100 5100
130 --- --- 2670 3800 5320 5000 5000
140 --- --- 2580 3700 5150 4910 4910
160 --- --- 2400 3525 4940 4700 4700
180 --- --- --- 3200 4700 4500 4500
200 --- --- --- --- 4425 4250 ---
220 --- --- --- --- 4175 --- ---
240 --- --- --- --- 4000 --- ---

AIR FLOW m3/h


OUTDOOR UNITS
MODELS 10 12 16 22 24 28 30
0 3500 3400 4950 5900 6600 6400 6400
10 3410 3325 4850 5800 6490 6300 6300
AVAILABLE STATIC PRESSURE Pa.

20 3300 3160 4750 5700 6340 6200 6200


30 3190 3075 4625 5600 6225 6100 6100
40 3080 2980 4525 5495 6100 5980 5980
50 2970 2890 4425 5390 5960 5870 5870
60 2840 2790 4325 5280 5850 5725 5725
70 2700 2690 4225 5180 5710 5600 5600
80 2560 2580 4125 5075 5600 5490 5490
NOMINAL
90 2410 2400 4040 4975 5480 5375 5375
AIR FLOW
100 2350 --- 3940 4875 5350 5250 5250
110 --- --- 3840 4775 5200 5100 ---
120 --- --- 3750 4675 5090 5000 ---
130 --- --- --- 4575 4950 --- ---
140 --- --- --- 4460 4800 --- ---
150 --- --- --- 4350 4650 --- ---
160 --- --- --- --- 4500 --- ---
NOTE:
Keep in mind reduction on air flow and static pressure services if you use mufflers or external air filter.
(See: page 42 fan services).

11
TECHNICAL DATA

SOUND LEVEL IN INDOOR UNITS

LFCK 22 LFCK 24 LFCK 28 LFCK 30


UNIT MODELS LFXO 10 LFXO 12 LFXO 16 LFHK 22 LFHK 24 LFHK 28 LFHK 30
LFHA 22 LFHA 24 LFHA 28 LFHA 30
Sound pressure level
dBA 49 48 49 57 59 56 55
(Lp) (*)

(*) Sound pressure level estimated, radiated by indoor unit fans on site with normal acoustic absorption, measured
to a discharged distance of 2m of the unit depending on suction or discharge.

SOUND LEVEL IN OUTDOOR UNITS

KFCK 10 KFCK 12 KFCK 16 KFCK 22 KFCK 24 KFCK 28 KFCK 30


UNIT MODELS KFHK 10 KFHK 12 KFHK 16 KFHK 22 KFHK 24 KFHK 28 KFHK 30
KFHA 10 KFHA 12 KFHA 16 KFHA 22 KFHA 24 KFHA 28 KFHA 30
Sound pressure level
dBA 43 43 45 49 49 48 48
(Lp) (*)

(*) Measured in free field condition at a distance of 10m (depending on suction or in duct discharge)

SOUND LEVEL OUTDOOR UNIT + MUFFLER (OPTIONAL)

KFCK 16 KFCK 22 KFCK 24 KFCK 28 KFCK 30


UNIT MODELS KFHK 16 KFHK 22 KFHK 24 KFHK 28 KFHK 30
KFHA 16 KFHA 22 KFHA 24 KFHA 28 KFHA 30

Sound pressure level (Lp) (*) dBA 43 45 45 45 45

(*) Setting a muffler (optional) directly connected to the discharge of outdoor fan of the unit measured in free-field
condition at a distance of 10m. (depending on no suction and discharge installation duct).

12
COOLING CAPACITIES

R-407C
FLCK / FLHK 10 FLCK / FLHK 12

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 9,20 8,89 8,56 8,19 7,77 10,99 10,62 10,22 9,77 9,27
15°C WB SENSIBLE 7,08 6,93 6,77 6,59 6,40 7,98 7,79 7,59 7,37 7,12
24°C DB TOTAL 9,89 9,56 9,20 8,81 8,36 11,79 11,39 10,96 10,49 9,95
17°C WB SENSIBLE 7,59 7,44 7,28 7,10 6,90 8,50 8,31 8,11 7,88 7,63
27°C DB TOTAL 10,62 10,27 9,80 9,46 8,98 12,64 12,22 11,80 11,25 10,67
19°C WB SENSIBLE 8,08 7,93 7,70 7,59 7,39 9,00 8,81 8,64 8,38 8,12
29°C DB TOTAL 11,40 11,02 10,61 10,15 9,63 13,56 13,11 12,61 12,06 11,43
21°C WB SENSIBLE 8,07 7,92 7,76 7,57 7,37 8,99 8,80 8,59 8,36 8,10
32°C DB TOTAL 12,22 11,82 11,38 10,88 10,31 14,54 14,05 13,52 12,93 ---
23°C WB SENSIBLE 8,54 8,38 8,22 8,04 7,86 9,46 9,27 9,06 8,83 ---

FLCK / FLHK 16 FLCK / FLHK 22

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 14,24 13,72 13,17 12,59 11,96 17,99 17,36 16,69 15,96 15,16
15°C WB SENSIBLE 10,96 10,71 10,45 10,17 9,87 14,58 14,28 13,97 13,63 13,27
24°C DB TOTAL 15,34 14,78 14,20 13,57 12,90 19,40 18,74 18,03 17,25 16,39
17°C WB SENSIBLE 11,77 11,52 11,25 10,97 10,68 15,74 15,45 15,13 14,79 14,42
27°C DB TOTAL 16,50 15,92 15,30 14,62 13,89 20,92 20,22 19,50 18,63 17,71
19°C WB SENSIBLE 12,55 12,30 12,04 11,75 11,45 16,86 16,57 16,30 15,92 15,54
29°C DB TOTAL 17,75 17,13 16,46 15,74 14,96 22,56 21,81 21,00 20,11 19,13
21°C WB SENSIBLE 12,55 12,30 12,03 11,75 11,44 16,87 16,58 16,26 15,92 15,55
32°C DB TOTAL 19,07 18,41 17,70 16,93 --- 24,31 23,51 22,64 21,69 20,63
23°C WB SENSIBLE 13,28 13,03 12,77 12,48 --- 17,95 17,65 17,34 17,00 16,62

FLCK / FLHK 24 FLCK / FLHK 28

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 20,62 19,87 19,09 18,28 17,43 24,63 23,71 22,77 21,80 20,81
15°C WB SENSIBLE 16,37 16,01 15,64 15,26 14,87 19,08 18,64 18,19 17,73 17,26
24°C DB TOTAL 22,19 21,39 20,56 19,69 18,79 26,45 25,48 24,48 23,45 22,39
17°C WB SENSIBLE 17,62 17,26 16,89 16,51 16,11 20,47 20,03 19,57 19,11 18,65
27°C DB TOTAL 23,88 23,02 22,00 21,21 20,25 28,40 27,37 26,30 25,21 24,08
19°C WB SENSIBLE 18,33 18,47 18,00 17,72 17,32 21,81 21,37 20,92 20,46 19,99
29°C DB TOTAL 25,20 24,78 23,83 22,85 21,82 30,50 29,40 28,26 27,10 ---
21°C WB SENSIBLE 18,82 18,46 18,09 17,71 17,31 21,78 21,34 20,89 20,43 ---
32°C DB TOTAL 27,65 26,67 25,65 24,59 23,50 32,73 31,56 30,35 29,11 ---
23°C WB SENSIBLE 19,98 19,62 19,25 18,87 18,47 23,06 22,62 22,11 21,71 ---

DB - Dry Bulb
WB - Wet Bulb
13
COOLING CAPACITIES

R-407C
FLCK / FLHK 30

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE


TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 26,37 25,39 24,39 23,35 22,29
15°C WB SENSIBLE 20,08 19,60 19,12 18,62 18,12
24°C DB TOTAL 28,30 27,25 26,18 25,08 ---
17°C WB SENSIBLE 21,50 21,02 20,53 20,03 ---
27°C DB TOTAL 30,36 29,25 28,10 26,93 ---
19°C WB SENSIBLE 22,86 22,38 21,89 21,40 ---
29°C DB TOTAL 32,57 31,39 30,18 28,92 ---
21°C WB SENSIBLE 22,83 22,35 21,86 21,36 ---
32°C DB TOTAL 34,93 33,67 32,37 31,03 --- DB - Dry Bulb
23°C WB SENSIBLE 24,13 23,65 23,13 22,66 --- WB - Wet Bulb

CALCULATION OF COOLING CAPACITY DEPENDING ON AIR FLOW

CORRECTION COEFFICIENT TO FIX


MODELS 10-12-16-22
TO THE CAPACITY OF DIFFERENT
INDOOR AIR FLOW Air flow minimum nominal maximum
Cooling capacity x0,97 x1,00 x1,01
Sensible capacity x0,90 x1,00 x1,03

MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,95 x1,00 x1,02

CORRECTION COEFFICIENT TO FIX TO


THE CAPACITY OF DIFFERENT MODELS 10-12-16-22
OUTDOOR AIR FLOW
Air flow minimum nominal maximum
Cooling capacity x0,97 x1,00 x1,01
Sensible capacity x0,97 x1,00 x1,01

MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,98 x1,00 x1,01

14
COOLING CAPACITIES

R-22
FLHA 10 FLHA 12

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 8,73 8,46 8,18 7,88 7,55 10,60 10,27 9,92 9,52 9,07
15°C WB SENSIBLE 6,82 6,69 6,56 6,42 6,26 7,81 7,65 7,47 7,28 7,06
24°C DB TOTAL 9,34 9,06 8,76 8,44 8,10 11,33 10,99 10,61 10,18 9,69
17°C WB SENSIBLE 7,31 7,18 7,05 6,90 6,75 8,32 8,15 7,97 7,78 7,55
27°C DB TOTAL 9,99 9,69 9,40 9,03 8,67 12,12 11,75 11,30 10,89 10,35
19°C WB SENSIBLE 7,78 7,65 7,52 7,37 7,22 8,80 8,64 8,46 8,26 8,03
29°C DB TOTAL 10,69 10,37 10,03 9,67 9,28 12,96 12,57 12,13 11,63 11,05
21°C WB SENSIBLE 7,75 7,62 7,49 7,35 7,20 8,77 8,61 8,43 8,22 7,99
32°C DB TOTAL 11,42 11,08 10,71 10,33 9,92 13,86 13,43 12,96 12,42 11,78
23°C WB SENSIBLE 8,19 8,07 7,93 7,79 7,64 9,23 9,06 8,88 8,67 8,43

FLHA 16 FLHA 22

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 13,56 13,11 12,62 12,09 11,50 17,62 17,09 16,50 15,85 15,08
15°C WB SENSIBLE 10,48 10,27 10,04 9,78 9,50 14,35 14,10 13,82 13,52 13,17
24°C DB TOTAL 14,54 14,06 13,55 12,98 12,35 18,91 18,35 17,74 17,04 16,21
17°C WB SENSIBLE 11,23 11,02 10,79 10,53 10,26 15,45 15,21 14,94 14,63 14,28
27°C DB TOTAL 15,58 15,07 14,70 13,93 13,26 20,26 19,69 19,20 18,30 17,40
19°C WB SENSIBLE 11,96 11,74 11,51 11,26 10,98 16,51 16,28 16,01 15,71 15,34
29°C DB TOTAL 16,69 16,15 15,57 14,93 14,23 21,71 21,11 20,43 19,64 18,63
21°C WB SENSIBLE 11,92 11,71 11,48 11,23 10,95 16,46 16,23 15,97 15,66 15,28
32°C DB TOTAL 17,86 17,28 16,66 15,99 15,24 22,22 22,60 21,88 21,02 19,86
23°C WB SENSIBLE 12,61 12,39 12,16 11,91 11,64 17,46 17,24 16,98 16,67 16,26

FLHA 24 FLHA 28

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 19,56 18,94 18,32 17,68 17,02 24,36 23,69 22,77 21,88 20,92
15°C WB SENSIBLE 15,75 15,46 15,16 14,87 14,56 18,96 18,59 18,20 17,78 17,33
24°C DB TOTAL 20,98 20,33 19,66 18,98 18,29 26,07 25,24 24,36 23,41 22,38
17°C WB SENSIBLE 16,94 16,65 16,36 16,06 15,76 20,31 19,94 19,54 19,12 18,66
27°C DB TOTAL 22,50 21,81 21,00 20,39 19,65 27,88 26,99 26,00 25,03 23,92
19°C WB SENSIBLE 18,10 17,81 17,51 17,22 16,92 21,61 21,23 20,83 20,40 19,94
29°C DB TOTAL 24,15 23,41 22,66 21,90 21,12 29,82 28,86 27,84 26,74 25,55
21°C WB SENSIBLE 18,06 17,77 17,48 17,18 16,88 21,52 21,14 20,74 20,31 19,85
32°C DB TOTAL 25,90 25,11 24,32 23,51 22,68 31,85 30,82 29,72 28,54 27,26
23°C WB SENSIBLE 19,16 18,88 18,59 18,30 18,00 22,75 22,37 21,96 21,53 21,06

DB - Dry Bulb
WB - Wet Bulb
15
COOLING CAPACITIES

R-22
FLHA 30

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE


TEMPERATURE CAPACITY OUTDOOR UNIT ºC DRY BULB
INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C
21°C DB TOTAL 25,76 24,93 24,39 23,08 22,02
15°C WB SENSIBLE 19,70 19,30 18,87 18,41 17,90
24°C DB TOTAL 27,55 26,66 25,70 24,66 23,52
17°C WB SENSIBLE 21,05 20,64 20,21 19,74 19,23
27°C DB TOTAL 29,44 28,48 27,60 26,33 25,10
19°C WB SENSIBLE 22,35 21,94 21,50 21,02 20,51
29°C DB TOTAL 31,45 30,42 29,30 28,10 26,77
21°C WB SENSIBLE 22,26 21,84 21,40 20,92 20,40
32°C DB TOTAL 33,57 32,45 31,25 29,94 ---
DB - Dry Bulb
23°C WB SENSIBLE 23,48 23,06 22,61 22,13 --- WB - Wet Bulb

CALCULATION OF COOLING CAPACITY DEPENDING ON AIR FLOW

CORRECTION COEFFICIENT TO FIX


MODELS 10-12-16-22
TO THE CAPACITY OF DIFFERENT
INDOOR AIR FLOW Air flow minimum nominal maximum
Cooling capacity x0,97 x1,00 x1,01
Sensible capacity x0,90 x1,00 x1,03

MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,95 x1,00 x1,02

CORRECTION COEFFICIENT TO FIX TO


THE CAPACITY OF DIFFERENT MODELS 10-12-16-22
OUTDOOR AIR FLOW
Air flow minimum nominal maximum
Cooling capacity x0,97 x1,00 x1,01
Sensible capacity x0,97 x1,00 x1,01

MODELS 24-28-30
Air flow minimum nominal maximum
Cooling capacity x0,98 x1,00 x1,01
Sensible capacity x0,98 x1,00 x1,01

16
HEATING CAPACITIES
R-407C
FLHK 10 FLHK 12

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 6,83 7,61 8,49 10,06 11,95 14,10 8,37 9,31 10,35 12,13 14,25 16,66
15°C DB
T. consumption 2,63 2,70 2,79 2,94 3,14 3,38 3,33 3,44 3,57 3,79 4,06 4,38
Total capacity 6,82 7,59 8,47 10,02 11,88 13,99 8,37 9,30 10,32 12,08 14,16 16,52
18°C DB 2,77 2,84 2,93 3,09 3,30 3,55
T. consumption 3,49 3,61 3,74 3,97 4,26 4,61
Total capacity 6,82 7,58 8,46 10,00 11,83 13,92 8,37 9,29 10,30 12,00 14,10 16,42
20°C DB
T. consumption 2,86 2,94 3,03 3,16 3,41 3,67 3,60 3,73 3,86 4,11 4,40 4,77
Total capacity 6,82 7,587 8,44 9,94 11,75 13,76 8,37 9,27 10,27 11,97 13,98 16,21
24°C DB
T. consumption 3,06 3,15 3,25 3,43 3,66 3,93 3,84 3,97 4,12 4,38 4,71 5,12

FLHK 16 FLHK 22
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 10,64 11,87 13,26 15,67 18,57 21,86 13,80 15,43 17,24 20,42 24,35 28,97
15°C DB
T. consumption 4,66 4,80 4,97 5,27 5,65 6,11 5,86 5,98 6,13 6,39 6,75 7,20
Total capacity 10,60 11,82 13,20 15,58 18,44 21,67 13,76 15,37 17,17 20,32 24,20 28,75
18°C DB 4,84 4,99 5,17 5,48 5,88 6,36
T. consumption 6,07 6,21 6,36 6,64 7,00 7,48
Total capacity 10,58 11,80 13,16 15,50 18,36 21,55 13,73 15,34 17,14 20,20 24,10 28,60
20°C DB
T. consumption 4,97 5,13 5,31 5,60 6,04 6,53 6,23 6,37 6,53 6,74 7,19 7,68
Total capacity 10,56 11,76 13,11 15,42 18,18 21,29 13,70 15,30 17,07 20,15 23,91 28,29
24°C DB
T. consumption 5,24 5,41 5,61 5,95 6,39 6,90 6,57 6,72 6,89 7,19 7,60 8,10

FLHK 24 FLHK 28
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 15,76 17,47 19,36 22,61 26,53 31,04 19,02 21,06 23,34 27,29 32,11 37,68
15°C DB
T. consumption 7,17 7,39 7,63 8,04 8,55 9,17 7,71 7,91 8,14 8,56 9,09 9,75
Total capacity 15,75 17,44 19,31 22,52 26,37 30,80 19,01 21,03 23,27 27,18 31,92 37,41
18°C DB 7,46 7,69 7,94 8,37 8,91 9,55
T. consumption 8,03 8,24 8,49 8,92 9,49 10,18
Total capacity 15,75 17,43 19,28 22,50 26,27 30,65 19,01 21,01 23,24 27,00 32,41 37,24
20°C DB
T. consumption 7,66 7,90 8,16 8,60 9,15 9,82 8,25 8,47 8,73 9,20 9,77 10,48
Total capacity 15,75 17,41 19,23 22,34 26,07 30,34 19,04 21,01 23,20 27,00 31,60 36,92
24°C DB
T. consumption 8,07 8,33 8,61 9,08 9,68 10,38 8,71 8,96 9,24 9,73 10,35 11,11

FLHK 30

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE


TEMPERATURE kW OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 20,04 22,17 24,55 28,71 33,80 39,74
15°C DB
T. consumption 8,45 8,69 8,96 9,44 10,06 10,82
Total capacity 20,06 22,17 24,53 28,63 33,67 39,51
18°C DB 8,82 9,08 9,36 9,87 10,52 11,32
T. consumption
Total capacity 20,09 22,18 24,52 28,70 33,58 39,37
20°C DB
T. consumption 9,08 9,34 9,64 10,32 10,84 11,68
Total capacity 20,67 22,24 24,54 28,55 33,43 39,11
24°C DB DB - Dry Bulb
T. consumption 9,62 9,91 10,23 10,80 11,53 12,42 WB - Wet Bulb
17
HEATING CAPACITIES
R-22
FLHA 10 FLHA 12

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 7,13 7,94 8,84 10,38 12,22 14,30 8,51 9,48 10,53 12,33 14,47 16,90
15°C DB
T. consumption 2,51 2,56 2,63 2,73 2,86 3,02 2,87 2,96 3,05 3,19 3,36 3,57
Total capacity 7,12 7,92 8,81 10,33 12,15 14,19 8,52 9,47 10,52 12,30 14,41 16,79
18°C DB 2,62 2,68 2,74 2,85 2,99 3,16
T. consumption 3,00 3,09 3,18 3,34 3,52 3,74
Total capacity 7,12 7,91 8,79 10,30 12,09 14,12 8,52 9,47 10,51 12,30 14,36 16,72
20°C DB
T. consumption 2,70 2,76 2,82 2,93 3,08 3,26 3,10 3,18 3,28 3,44 3,63 3,86
Total capacity 7,11 7,89 8,76 10,25 12,01 13,98 8,54 9,47 10,49 12,23 14,27 16,57
24°C DB
T. consumption 2,87 2,93 3,00 3,12 3,27 3,46 3,29 3,38 3,48 3,66 3,87 4,12

FLHA 16 FLHA 22
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 10,95 12,14 13,46 15,74 18,45 21,51 13,70 15,30 17,08 20,13 23,73 27,80
15°C DB
T. consumption 4,25 4,34 4,44 4,62 4,85 5,15 5,64 5,76 5,90 6,15 6,47 6,85
Total capacity 10,93 12,11 13,42 15,67 18,33 21,35 13,66 15,24 17,00 20,02 23,60 27,64
18°C DB 4,42 4,51 4,62 4,81 5,05 5,36
T. consumption 5,82 5,95 6,09 6,35 6,68 7,08
Total capacity 10,93 12,09 13,39 15,60 18,26 21,24 13,64 15,20 16,95 20,00 23,52 27,53
20°C DB
T. consumption 4,55 4,64 4,74 4,94 5,19 5,51 5,94 6,08 6,23 6,60 6,84 7,25
Total capacity 10,92 12,07 13,35 15,53 18,11 21,02 13,60 15,14 16,86 19,82 23,34 27,29
24°C DB
T. consumption 4,81 4,90 5,01 5,22 5,49 5,83 6,21 6,35 6,51 6,80 7,16 7,59

FLHA 24 FLHA 28
AIR ENTRY AIR ENTRY TEMPERATURE INTO THE AIR ENTRY TEMPERATURE INTO THE
TEMPERATURE kW OUTDOOR UNIT ºC WET BULB OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C12°C 18°C -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 15,82 17,61 19,54 22,80 26,69 31,18 18,61 20,68 22,98 26,93 31,67 37,08
15°C DB
T. consumption 6,69 6,86 7,04 7,32 7,67 8,10 7,23 7,40 7,58 7,90 8,30 8,78
Total capacity 15,81 17,58 19,48 22,70 26,53 30,97 18,60 20,66 22,93 26,84 31,51 36,82
18°C DB 3,93 7,10 7,28 7,58 7,95 8,40
T. consumption 7,51 7,69 7,88 8,22 8,64 9,14
Total capacity 15,81 17,56 19,45 22,80 26,44 30,83 18,60 20,65 22,91 27,00 31,40 36,65
20°C DB
T. consumption 7,09 7,27 7,46 7,80 8,14 8,61 7,71 7,89 8,09 8,43 8,87 9,38
Total capacity 15,82 17,55 19,41 22,53 26,26 30,58 18,59 20,63 22,86 26,68 31,19 36,31
24°C DB
T. consumption 7,44 7,64 7,83 8,16 8,56 9,06 8,11 8,31 8,53 8,90 9,36 9,91

FLHA 30

AIR ENTRY AIR ENTRY TEMPERATURE INTO THE


TEMPERATURE kW OUTDOOR UNIT ºC WET BULB
INDOOR UNIT -8°C -4°C 0°C 6°C 12°C 18°C
Total capacity 20,51 22,78 25,30 29,64 34,85 40,79
15°C DB
T. consumption 7,89 8,10 8,34 8,75 9,26 9,87
Total capacity 20,51 22,78 25,28 29,58 34,71 40,54
18°C DB 8,21 8,44 8,69 9,12 9,65 10,29
T. consumption
Total capacity 20,52 22,77 25,27 29,80 34,62 40,38
20°C DB
T. consumption 8,44 8,67 8,93 9,43 9,92 10,59
Total capacity 20,54 22,78 25,25 29,46 34,43 40,05
24°C DB DB - Dry Bulb
T. consumption 8,90 9,16 9,44 9,92 10,51 11,21 WB - Wet Bulb

18
HEATING CAPACITIES

CALCULATION OF HEATING POWER DEPENDING ON AIR FLOW

CORRECTION COEFFICIENT TO FIX MODELS 10-12-16-22


TO THE CAPACITY OF DIFFERENT
INDOOR AIR FLOW Air flow minimum nominal maximum
Heating capacity x0,98 x1,00 x1,01
Total consumption x0,98 x1,00 x1,01

MODELS 24-28-30
Air flow minimum nominal maximum
Heating capacity x0,91 x1,00 x1,03
Total consumption x0,98 x1,00 x1,01

CORRECTION COEFFICIENT TO FIX MODELS 10-12-16-22


TO THE CAPACITY OF DIFFERENT
OUTDOOR AIR FLOW Air flow minimum nominal maximum
Heating capacity x0,98 x1,00 x1,01
Total consumption x0,98 x1,00 x1,01

MODELS 24-28-30
Air flow minimum nominal maximum
Heating capacity x0,91 x1,00 x1,03
Total consumption x0,98 x1,00 x1,01

19
UNITS DIMENSIONS

SIDE D

MODELS 10-12 SIDE A


SIDE C
(Packaged units)
OUTDOOR INDOOR
SECTION SECTION

SIDE B

1250
1250
820
32

305 Electrical box


20
27

25
495
425

303

Drainage
outside thread
3/4'' Male

184
452
B
E Oval hole of
D
349
123 SI 20 x12
50
25
Power supply SIDE Thermostat connection
A
40

connection

60
1250
1250 25 80
430
14

40 Detail drawing of
159

2255
unit anchor support
495
303

422

Unit anchor
support
4
90 73
280
4
Distanc 430 40
e betwe 109
en hole
s 1300

D Air filter
E
D
SIDE
C SI

20
DIMENSIONS SPLIT SYSTEM MODELS 10-12
(Split unit)
SIZE D
Pipes
connections
Outdoor Indoor
unit unit
Electrical heater/ Electrical
SIDE A

Hot water coil heater


(optional) supply

SIDE C
Electrical
interconnection
between indoor
unit

Electrical fan
SIDE B supply
Drainage Drainage
outside thread outside thread
3/4'' Male 3/4'' Male
Outdoor unit Cooling interconnection pipe
820 1250 Electrical box
32

305
20
27

25
425

495

Drainage
303

outside thread
3/4'' Male

Unit anchor
support 184 Detail drawing of
1,6
452 71 B unit anchor support
E
D Oval hole of
349
123 SI 20 x12
Power supply 50
connection SIDE Thermostat connection 25
A
40

Indoor unit Air filter


430 1250 60
25 80
14

40
159

Drainage 25 Gas pipe


outside thread Liquid pipe
495

3/4'' Male
303

422

Unit anchor
support
90
280 1,6
32
430
109
Distanc
e betwe
en hole D
s 1300 E
D
SI
Electric
al SIDE
heater C
supply
21
UNITS DIMENSIONS
SIZE D

MODEL 16
(Packaged units) SIDE A
SIDE C

OUTDOOR INDOOR
SECTION SECTION

SIDE B

1300
1330
Power supply connection
830
32

320
20 Thermostat connection
27

25
595
500

355

Drainage
outside thread
3/4'' Male

249
422
B
E
D
324
123 SI Oval hole of
20 x12
50
SIDE 25
A
Electrical box
40

1300
1330 60
25 80
500
25

40
182

2255 Detail drawing of


unit anchor support
595
355

517

Unit anchor
support
5
98
324 74

500 4
Distanc 125 47
e betwe
en hole Air filter
s 1350

D
E
SIDE D
C SI

22
DIMENSIONS SPLIT SYSTEM MODEL 16
(Split unit)
SIDE D

Cooling
connections
Outdoor Indoor
unit unit
Electrical
Electrical heater/ heater
SIDE A

Hot water coil supply


(optional)

SIDE C
Electrical
interconnection
between indoor
unit
Electrical fan
supply
SIDE B Drainage Drainage
outside thread outside thread
3/4'' Male 3/4'' Male
Outdoor unit Cooling interconnection pipe
830 1300 Electrical box
32

320 Power supply connection


20 Thermostat connection
27

25
Drainage
595
500

outside thread
355

3/4'' Male

Unit anchor 249


1,6
support 422 72 Detail drawing of
B unit anchor support
324 Oval hole of
123 E 20 x12
D
SIDE SI 50
A 25
40

Indoor unit
500 1300 60
25 80
25

40 Gas pipe
182

25
Liquid pipe
Drainage
595
355

outside thread
517

3/4'' Male Unit anchor


support

98
324 1,6
39
500
Electric 125
al Distanc
heater e betwe
en hole
supply s 1350 D
E
D
SI
Air filter
SIDE
C

23
UNITS DIMENSIONS
SIDE D

MODEL 22 SIDE A SIDE C

(Packaged units) OUTDOOR INDOOR


SECTION SECTION

SIDE B

1450
1520
900
36,5

47

25
595

Electrical
497

connection
355

supply Drainage
outside thread
3/4'' Male

Thermostat 262
connection 462
B
E
324
S ID
92
Oval hole of
SIDE 20 x12
A 50
25
40

1450
1520
32
620 300 Electrical box 60
25 80
26

40
193

2255
595

Detail drawing of
515,5
355

unit anchor support


F

Unit anchor
107 4 support
324 81

591 3
Distanc 42 59
e betwe
en hole
s 1500
Air filter
D
E
SIDE D
C SI

24
DIMENSIONS SPLIT SYSTEM MODEL 22
(Split unit)
SIDE D
SIDE D
Cooling pipe
interconnection
Outdoor Indoor
unit unit

SIDE C
Electrical heater/
SIDE A

Hot water coil Electrical


(optional) heater
supply

SIDE C
Electrical fan
supply

Electrical
interconnection
between indoor
unit
SIDE B Drainage
outside thread Drainage
Outdoor unit 3/4'' Male outside thread 3/4'' Male

Power Drainage Gas pipe Electrical box


Cooling pipes outside thread
supply connection 900 1450
connection 3/4'' Male
900 1450 32
300
36,5

47

25

595
497

595
355

1
Distanc 79
262 e betwe
en hole
462 s 1500
D
E
324
92 E
B ID
D S
Thermostat SI Electrical
SIDE
connection SIDE interconnection C
A Liquid pipe
between indoor
unit Unit anchor
Indoor unit Air filter
support
620 1450
Gas pipe
26

40
193

25
Liquid pipe
515,5
355

595

Unit anchor Detail drawing of


support unit anchor support
Oval hole of
20 x12
107 50
324 1
51 25
591
Distanc 42
40

e betwe
en hole
s 1500
D
Electric E 60
al S ID 25 80
heater SIDE
supply C

25
UNITS DIMENSIONS
SIDE D

MODELS 24-28-30 SIDE A


(Packaged units) SIDE C

OUTDOOR INDOOR
SECTION SECTION

SIDE B

1500
1800

1025

25
645

Drainage
outside thread
355

3/4'' Male
214

490
398 B
E
410 103 S ID

SIDE
A

Electrical box
Thermostat Power
connection supply 1500
connection 1800

Oval hole of 775 677


124
26

20 x12
40
223,5

50
25 2255
645
537
40

355

565,5

60
25 80
95 8
327 74
Detail drawing of 9
unit anchor support Distanc 658 93
e betwe 82
en hole
s 1550
Unit anchor Air filter
support D
SIDE E
C D
SI

26
DIMENSIONS SPLIT SYSTEM MODELS 24-28-30
SIDE C
(Split unit)
SIDE F

Cooling
connections
Outdoor Indoor
unit unit
Electrical heater/
Hot water coil Electrical
(optional)

SIDE D
heater
SIDE A

supply
Electrical
interconnection

SIDE E
between indoor
unit

Electrical fan
supply

SIDE B Drainage
outside thread Drainage
3/4'' Male outside thread
3/4'' Male
Drainage outside
Outdoor unit thread 3/4'' Male
Electrical
interconnection Gas pipe Liquid pipe
between indoor
1025 1500 unit 1500
1025
25 677
124

645
645
355

537
214

490 6
398 Distanc 91
e betw
een ho
410 les 1550
103
B Unit anchor D
SIDE E E
D SIDE D
A SI support C SI
Electrical box Thermostat Power
connection supply Indoor unit
connection 775 1500
Gas pipe
26

Detail drawing of 40
223,5

unit anchor support 25

Liquid pipe
645
355

565,5

Oval hole of 50
20 x12 25 Unit anchor
support
40

95
327 6
60 66
25 80
658
Distanc 82
e betwe
en hole
s 1550
F
E
D
Electric SI
al
heater SIDE
supply E
Air filter
27
DIMENSIONS FREECOOLING

MODELS 10-12
FREECOOLING 1-DAMPER
1250
1250

820
32

305
20
27

495
25
425

303

Drainage
outside thread First damper
184 freecooling
452 3/4'' Male

349
123 Electrical box
Power supply connection 159 200
25
Thermostat connection

480
303

480

F
90
280
5
Distanc 455 45 73
4
e betwe 81
en hole
s 1300 4
40
FREECOOLING 2-DAMPER
Air filter

1250
1250

820
32

305
20
27

495

25
425

303

Drainage First damper


outside thread freecooling
184
3/4'' Male
452

349
123 Electrical box
Power supply connection 200 200
159

25
Thermostat connection
480
303

480

90
280
5 4
Distanc 455 45 73
e betwe 81
en hole 4
s 1300
40

Air filter
Second damper
freecooling
28
DIMENSIONS FREECOOLING

MODEL 16
FREECOOLING 1-DAMPER
1300
1330
Power supply connection
830
32

320
20
27

595
25
500

355

Thermostat connection

Drainage
outside thread First damper
249 3/4'' Male freecooling
422

324 Electrical box


123
200
182 23
25

586
355

586

F
98
324
5
455 45 5
Distanc
e betwe 147 74
en hole
s 1350 4
47
FREECOOLING 2-DAMPER
Air filter

1300
1330
Power supply connection
830
32

320
20
27

595

25
500

Thermostat connection
355

Drainage First damper


outside thread freecooling
249 3/4'' Male
422

324 Electrical box


123
200 23 200
182

25
586
355

586

98
324
5
455 45 5
Distanc 147 74
e betwe
en hole 4
s 1350
47

Air filter
Second damper
freecooling
29
DIMENSIONS FREECOOLING

MODEL 22
FREECOOLING 1-DAMPER
1450
1520

900
36,5

47
25

595
497

355
Thermostat
connection
Drainage
outside thread
262 3/4'' Male
462
Power supply
connection 324
92 1450
1520
32 Electrical
620 300 box

200
20
193

2255

595
556
515,5
355

F
First damper
107
324 freecooling
0
58 14
591 8 Air filter
Distanc 48
FREECOOLING 2-DAMPER e betwe
en hole 93
s 1500 5

1450
1520 Air filter
900
36,5

47

25
595
497

355

Thermostat
connection

Drainage
outside thread
262 3/4'' Male
462
Power supply
connection 324
92 1450
1520
32 Electrical
620 300 box

200 20 200
193

2255
595
556
355

556

First damper
107 freecooling
324
0
58 4
Distanc
580 81 Air filter
e betwe 48
en hole 93
s 1500 5

Air filter
Second damper Freecooling
30
DIMENSIONS FREECOOLING

MODELS 24-28-30
FREECOOLING 1-DAMPER
1500
1800

1025

25

645
355

Drainage
214

outside thread
490 3/4'' Male
398 1500
410 1800
103
Electrical box 775 677
Thermostat Power supply

26
connection connection 200
223,5

83
2255

645
537
355

565,4

95
327 5
70 6
658 91 First damper
Distanc 82 freecooling
FREECOOLING 2-DAMPER e betwe
en hole 71
s 1550 7

1500
1800
Air filter
1025

25
645
355

Drainage
214

outside thread
490 3/4'' Male
398
410 1500
103 1800
Electrical box
Thermostat Power supply 775 677
connection connection
200 83 200
223,5

2255
645
537
355

641

95
327 5
70 6
91 First damper
705
Distanc
e betwe 56 freecooling
en hole 1
s 1550 77

Air filter
Second damper freecooling
31
UNIT OPENING SIZES MODELS 10-12

OUTDOOR SECTION

368 349

303

495
E.B.

495
123

303
349

170

38
STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
OPENING OPENING

B1 D1 184 452 452 269

495

425
495
425
43

43
IL

COMPRESSOR
D0
CO

B0 O
IL
C
R

STANDARD OPTIONAL
OO

R
O B0 B1
O EXTRACTOR EXTRACTOR
ND

TD OPENING OPENING
I

U
O

INDOOR SECTION
EXTERNAL INTERNAL 280 90
FAN FAN C0 90 280

A0
159
E.B.

303

A1 C1
495

495
303

STANDARD EXECUTION
170

OPTIONAL EXECUTION
ELECTRICAL BOX STANDARD OPTIONAL
C0 BLOWER C1 BLOWER
OPENING OPENING
14
14
495

495
422

422

430 109 430


27

STANDARD AIR OPTIONAL AIR


D0 RETURN D1 RETURN
OPENING OPENING

32
UNIT OPENING SIZES MODEL 16

OUTDOOR SECTION

428 324

355
595

595
E.B.

355
324 123

213

58
STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
OPENING OPENING

249 422 422 304

595

500
500

595
B1 D1

63
63

STANDARD OPTIONAL
IL

COMPRESSOR
D0 B0 B1
CO

B0 IL EXTRACTOR EXTRACTOR
O OPENING
C OPENING
OR

R
O
DO

O
TD
I N

U
O
INDOOR SECTION
98 324 324 98
27

OUTDOOR INDOOR
FAN FAN C0
182

A0
355
595
E.B.

595
355

A1 C1
213

STANDARD CONFIGURATION
STANDARD OPTIONAL
OPTIONAL CONFIGURATION C0 BLOWER BLOWER
C1
OPENING OPENING
ELECTRICAL BOX
25

25
595

595
517

517

500 125 500

STANDARD AIR OPTIONAL AIR


D0 RETURN D1 RETURN
OPENING OPENING

33
UNIT OPENING SIZES MODEL 22

OUTDOOR SECTION

193
355
391,5 324

595

595
324 92

355
193
STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
OPENING OPENING

262 462 462 384

595

497
595
497
B1 D1
E.B.

COMPRESSOR

61
61
IL
CO

STANDARD OPTIONAL
B0 IL D0 B0 EXTRACTOR B1 EXTRACTOR
OR

O
C OPENING OPENING
DO

R
O
IN

O
TD
U
O INDOOR SECTION
107 324 324 107

EXTERNAL INTERNAL
C0
193

FAN FAN
A0
355
595
595
355

A1 C1
193

STANDARD EXECUTION STANDARD OPTIONAL


OPTIONAL EXECUTION C0 BLOWER C1 BLOWER
OPENING OPENING
ELECTRICAL BOX
26

26
515,5

515,5
595

595

591 42,5 15 591

STANDARD AIR OPTIONAL AIR


D0 RETURN D1 RETURN
OPENING OPENING

34
UNIT OPENING SIZES MODELS 24-28-30

OUTDOOR SECTION

103 410

214
355

645
645

355
410 103

214
B0 D1

STANDARD OPTIONAL
A0 BLOWER A1 BLOWER
COMPRESSOR
OPENING OPENING
IL

D0
CO

40
R
OO
ND
IL
E.B.

CO

677 174
I

222 677
OR

537

537
DO

645

645
T
OU

C0
EXTERNAL INTERNAL

68
A0 FAN FAN

STANDARD OPTIONAL
B0 EXTRACTOR B1 EXTRACTOR
A1 C1 OPENING OPENING (*)

STANDARD EXECUTION INDOOR SECTION


OPTIONAL EXECUTION 95 327 327 258

ELECTRICAL BOX
223

355

(*) ONLY AVAILABLE WHEN UNIT IS


645
645

DELIVER ON SPLIT SYSTEM


355

213

B0

STANDARD OPTIONAL
C0 BLOWER C1 BLOWER
COMPRESSOR
B1 OPENING OPENING
26

26
CO

E.B.
IL

565,5

565,5
645

645

EXTERNAL
FAN

A0

658 82 107 658

STANDARD AIR OPTIONAL AIR


D0 RETURN D1 RETURN
A1 OPENING OPENING

35
UNIT INSTALLATION

UNIT LOCATION AND WEIGHT DISTRIBUTION


The bedplate is made up of three galvanized metal channels, capable of withstanding the weight of the units
whether hung from the ceiling or mounted on the floor.
If the unit is floor mounted, then should be isolated with shock absorbing material such as anti-vibration or pads.
If used, consult the weight distribution table below to make the correct selection. Keep in mind that fans rotate at
approximately 850 rpm.
If the unit is hung, M-10 threaded rods should be used along with shock absorbing ceiling supports.

UNIT HUNG WITH RODS UNIT INSTALLED ON SHOCK ABSORBERS

Ceiling supports
(shock absorbers)

Floor supports
(shock absorbers)

Y Y
MODELS 10-12-16-22 MODELS 24-28-30
D C D
C Indoor Sec.
Indoor Sec.
Fan. il Fan.
Co
il Co

E B E
B
G G
Comp.
Outdoor Sec. Outdoor Sec.
C

YG il
oi

YG Co
l

Comp. Fan. Fan.


F X
F X

A A
XG G POINT: Centre of gravity XG

TABLE 1: Point CENTRE OF GRAVITY


WEIGHT DISTRIBUTION (Kg)
WEIGHT DISTRIBUTION COORDINATES (G) (mm.)
AND CENTRE OF Model A B C D E F Total XG YG
GRAVITY COORDINATES
10 35 65 10 20 40 35 205 585 590

12 35 65 15 20 40 35 210 565 615

16 70 60 15 30 80 30 285 630 600

22 80 70 20 40 75 45 330 710 685

24 90 100 15 65 85 55 410 760 815

28 95 110 20 65 85 55 430 715 825

30 95 110 25 70 80 55 435 705 825

36
UNIT INSTALLATION

FREE SPACE FOR INSTALLATION


Clearance around the unit for service and maintenance.

er
et
m
1

1 mete
r

er 1 mete
et r
m
1

For the unit with optional FREECOOLING, it should be kept in mind that the bedplate anchors
cannot be used to hang the unit.
Consult others options for outdoor mounting or changes in position of the air return duct if the unit
is to be hung.

If the unit is going to be hung using the anchor supports and the optional air return opening, the
supports must be repositioned so that the air filter may be removed.
To move the supports, unscrew them from the inside and fix them again using the holes located
next to the initial position.

DRAINS

All indoor sections of these units ( and the outdoors section for the Heat Pump) have a ¾” steel threaded drain
pipe welded to the condensation tray.

Drain pipe

2%
2%
Trap

One PVC drain trap is supplied with the cooling-only units, and two with the heat pump units.
Connect the trap/s to the drain pipe/s on the unit and mount the drain pipe with at least a 2% incline from the trap.
Also slightly tip the unit (2%) toward the drainage side. Check the condensation trays are clean and free from dirt
and other debris from the works and that water drains correctly.

37
PIPE CONNECTIONS

To determine the pipe connections between outdoor and indoor units follow data:
A,B,C : Placement units
L : Total length.
1 = Gas pipe line.
2%
2 = Liquid pipe line.

OUTDOOR UNIT INDOOR UNIT


B
OUTDOOR UNIT 2%
2 1
2%
A 1 2
L
L

2
OUTDOOR UNIT INDOOR UNIT
1

L
C
2%
2%
INDOOR UNIT

PLACEMENT A : In gas pipe line is 1 necessary to install on vertical base a trap as well as a trap in the upper
base each 8m. The minimum speed suction must be below 6m/s.
PLACEMENT B : Do the cooling line pipe inclination to the outdoor unit. Pay attention in distance of more than 10m
and avoid collapse on pipe lines installation.
PLACEMENT C : It is necessary to install on the base pipe a vertical trap. It is not necessary intermediate trap.

TABLE 2: SELECTION ON PIPE LINES

UNIT - MODEL
PIPES LINE
10 12 16 22 24 28 30
Liquid 3/8" 3/8" 1/2" 5/8" 5/8" 5/8'' 5/8''
0 to 10 m.
Gas 3/4" 3/4" 7/8" 7/8" 11/8" 11/8" 11/8"
Liquid 3/8" 3/8" 5/8" 5/8" 5/8" 5/8'' 3/4''
Total line length 10 to 30 m.
Gas 7/8" 7/8" 7/8" 11/8" 11/8" 11/8" 13/8"
30 to 50 m. Liquid 1/2" 1/2" 5/8" 5/8" 3/4'' 3/4'' 3/4''
Gas 7/8" 7/8" 11/8" 11/8" 13/8" 13/8" 13/8"
Liquid 3/8" 3/8" 1/2" 5/8" 5/8" 5/8'' 5/8''
Unit connections
Gas 3/4" 3/4" 7/8" 7/8" 11/8" 11/8" 11/8"
Maximum vertical line length (m.) 15 15 15 15 15 15 15
Maximum number of bends 12 12 12 12 12 12 12

- IN EACH CASE THE GAS PIPE MUST BE ISOLATED.


- THE HORIZONTAL PIPE MUST HAVE AN INCLINATION OF 2 % TO THE OUTDOOR UNIT.
- THE MAXIMUM SPEED ON LINE CAN BE SUPERIOR OF 15m/seg.

Between length of 30 and 50m superior you have to make a recalculation according to our technical
commercial department or distribution itself to maintain certain aspects how to make the installation
(additional charge of oil, solenoid valves etc...)

38
ELECTRICAL CONNECTION
Electrical
1 Electrical supply. box 4
2 Connection indoor / outdoor unit.
Indoor 2 Outdoor thermostat
unit unit control
3 Electrical heater power supply. 1
Electronic
4 Connection thermostat control. 3 Card
POWER SUPPLY 2
Nr. OF CABLES x SECTION (mm )
230V SINGLE-PHASE
UNITS 1 1 2 3 4
UNIT Connection
PE N L X1 MODEL Power supply Power supply outdoor-indoor unit Electrical heater Shielded
WITHOUT WITH electrical WITHOUT power supply Cable
electrical heater. heater. electrical heater.

10 3x4 3 x 16 5 x 1,5 3x4+2x1 2x1


1N ~ 230V - 50 Hz + PE

2
POWER SUPPLY Nr. OF CABLES x SECTION (mm )
230V THREE-PHASE
1 1 2 3 4
UNITS UNIT Connection
MODEL Power supply Power supply Electrical heater Shielded
WITHOUT WITH electrical outdoor-indoor unit power supply Cable
electrical heater. heater. WITHOUT
PE L1 L2 L3 electrical heater.
X1
10 4x4 4 x 10 5 x 1,5 4x4+2x1 2x1
12 4x4 4 x 10 5 x 1,5 4x4+2x1 2x1

16 4x6 4 x 16 4 x 2,5 + 2 x 1 4x4+2x1 2x1

22 4 x 10 4 x 16 4 x 2,5 + 2 x 1 4x4+2x1 2x1


3 ~ 230V - 50 Hz + PE
24 4 x 10 4 x 25 4 x 2,5 + 2 x 1 4x4+2x1 2x1

28 4 x 10 4 x 25 4 x 2,5 + 2 x 1 4x4+2x1 2x1

30 4 x 16 4 x 25 4 x 2,5 + 2 x 1 4x4+2x1 2x1

2
Nr. OF CABLES x SECTION (mm )
POWER SUPPLY UNIT 1 1 2 3 4
400V THREE-PHASE MODEL Power supply Power supply Connection Electrical heater Shielded
WITHOUT WITH electrical outdoor-indoor unit power supply Cable
UNITS electrical heater. heater. WITHOUT
electrical heater.
10 5 x 2,5 5x4 5 x 1,5 4 x 2,5 + 2 x 1 2x1

PE L1 L2 L3 N X1 12 5 x 2,5 5x4 5 x 1,5 4 x 2,5 + 2 x 1 2x1


16 5x4 5x6 4 x 1,5 + 2 x 1 4 x 2,5 + 2 x 1 2x1
22 5x4 5 x 10 4 x 1,5 + 2 x 1 4 x 2,5 + 2 x 1 2x1
24 5x4 5 x 10 4 x 1,5 + 2 x 1 4 x 2,5 + 2 x 1 2x1
3N ~ 400V - 50 Hz + PE
28 5x4 5 x 10 4 x 1,5 + 2 x 1 4 x 2,5 + 2 x 1 2x1
30 5x6 5 x 10 4 x 1,5 + 2 x 1 4 x 2,5 + 2 x 1 2x1

The sections have been calculated for a length no longer than 50m and a voltage drop of 10V.
VOLTAGE OPERATING LIMITS
MODELS VOLTAGE LIMIT
10 230 V-1Ph-50Hz 198-264 V -1Ph- 50Hz
230 V-3Ph-50Hz 180-242 V -3Ph- 50Hz
10-12-16-22
400 V-3Ph-50Hz 342-462 V -3Ph- 50Hz
230 V-3Ph-50Hz 198-264 V -3Ph- 50Hz
24-28-30
400 V-3Ph-50Hz 342-462 V -3Ph- 50Hz

39
OPERATING LIMITS

OPERATING LIMITS FOR (COOLING ONLY) UNITS

MAXIMUM TEMPERATURES MINIMUM TEMPERATURES

INDOOR 32ºC DB / 23ºC WB 21ºC DB / 15ºC WB


TEMPERATURE
COOLING CYCLE
OPERATION OUTDOOR DEPENDING ON MODEL 0ºC (MODELS 22/24/28/30)
TEMPERATURE (TABLE 1) 19ºC (MODELS 10/12/16) (*)
-10ºC(**)

(*) With condensation pressure control (optional), 0ºC minimum outdoor operating temperature.
(**) With kit got gas bypass valve.

OPERATING LIMITS FOR (HEATING PUMP) UNITS

MAXIMUM TEMPERATURES MINIMUM TEMPERATURES

INDOOR
32ºC DB / 23ºC WB 21ºC DB / 15ºC WB
COOLING CYCLE TEMPERATURE
OPERATION OUTDOOR DEPENDING ON MODEL 0ºC (MODELS 22/24/28/30)
TEMPERATURE (TABLE 1) 19ºC (MODELS 10/12/16) (*)
-10ºC(**)

INDOOR
TEMPERATURE 27ºC DB 15ºC DB
HEATING CYCLE
OPERATION OUTDOOR
TEMPERATURE 24ºC DB / 18ºC WB -10ºC DB / -11ºC WB

(*) With condensation pressure control (optional), 0ºC minimum outdoor operating temperature.
(**) With kit got gas bypass valve.

DB.- Dry Bulb Temperature


WB.- Wet Bulb Temperature

TABLE 1- COOLING CYCLE MAXIMUM OUTDOOR OPERATING TEMPERATURES

MODELS WITH REFRIGERANT R-407C

MODELS 10 12 16 22 24 28 30

Rated outdoor flow 45 43 44 45 46 42 41

Minimum outdoor flow 43 43 41 41 42 39 38

MODELS WITH REFRIGERANT R-22

MODELS 10 12 16 22 24 28 30

Rated outdoor flow 48 48 47 48 48 46 44

Minimum outdoor flow 46 45 45 46 44 42 40

40
OPTIONS

ELECTRIC HEATER
Optionally, these units can contain shielded element electric heating batteries that are mounted on the inside of the unit in the schematic
opposite.
The electric heater must get its power from the unit’s electrical box.

MODELS LFXO 10 12-16-22 24-28-30


POWER kW 6 9 6 9 7,5 12
230 / I 26,1 ---- ---- ---- ---- ----
MAXIMUM (A) 230 / III
CURRENT 15,1 22,7 15,1 22,7 18,9 30,2
400 / III 8,7 13,1 8,7 13,1 10,9 17,4
WEIGHTS Kg (*) 7 7 8
STAGES 1 1 1
(*) Add to the unit's weight.

HOT WATER COIL


It is based on a refrigerating coil made of copper tubing with aluminum swirl fins with
water inlet and outlet connections.
It is supplied mounted inside the unit as picture shows.
DIFFERENCE IN TEMPERATURES WATER WATER COIL AIR Nr WEIGHT WATER
MODELS BETWEEN HOT WATER INTAKE FLOW PRESSURE PRESSURE ROWS OUTLET
FLC/FLH AND THE AIR WHICH ENTERS DROP DROP Kg DIAMETER
INDOOR UNIT THE COIL Inches
L/H kPa Pa
nominal-minimum
50ºC 60ºC 70ºC air flow
CAPACITY IN W
10-12
9000 11000 12800 500 0,5 35-30 2 4 3/4"
CAPACITY IN W
16
14500 17500 20400 1000 1,5 35-30 2 5 3/4"
CAPACITY IN W
22
15000 18000 21000 1000 1,5 30-25 2 6 3/4"
CAPACITY IN W
24-28-30
24500 29500 34400 1500 3 25-20 2 7 3/4"

PROTECTION AGAINST FREEZING:


• Use glycol water. GLYCOL IS THE ONLY EFFECTIVE PROTECTION AGAINST FREEZING.
• Regulation components should be used and in addition security components if they are needed.
• Drain the installation. You must ensure that the manual or automatic air vents have been installed on all high points in the system.
In order to drain the system check that all the drain cocks have been installed on all low points of the system.

A HEATING COIL FROZEN DUE TO LOW AMBIENT CONDITIONS IS NOT COVERED BY THE WARRANTY.

MAIN SWITCH
The main switch is located on the access panel to the electrical box in the outdoor section in such a way that the unit is disconnected
when the panel is opened.
(Refer to the size diagram a pages 20 to 31 to see the position of the electrical box access panel).
Check to make sure that the main switch is large enough to handle the current for the unit if electric heaters are installed.
PHASE SEQUENCER (THREE-PHASE UNIT)
The phase sequencer is located in the electrical box in the outdoor section, thus assuring that the unit will not begin operation while
the phase connection of the compressor is not correct. Should this occur, then just switch two phase connections.
ON/OFF CONDENSATION PRESSURE CONTROL (MODELS 10-12-16)
Consists of a pressure switch, which starts and stops the outdoor fan regulating the condensation temperature, thus the unit will be
able to operate in the cooling cycle when the outdoor temperature is below 19ºC (until 0ºC).
HOT GAS BYPASS VALVE
The purpose of the BYPASS valve is to make it possible for the unit to operate at low outdoor temperatures (until -10°C), to be used
in cooling-only and heat-pump units in the cooling cycle.
It regulates the capacity of the compressor by injecting hot gas from the compressor discharge side to the evaporator.
CONTROL USING A PROGRAMMABLE CONTROLLER.
With the programmable controller option, the desired temperature can be programmed in the area 24 hours a day, 7 days a week.
REMOTE ROOM-TEMPERATURE SENSOR, REMOTE DUCT SENSOR
These sensors may be used in conjunction with remote controller, allowing the controller to be mounted in a room away from the
conditioned space.
- REMOTE DUCT SENSOR: The sensor will be located in the return air duct, detecting the air temperature of the air being air conditioned.
- REMOTE ROOM-TEMPERATURE SENSOR: The sensor will be placed in the area to be air conditioned.
FREECOOLING THERMOSTAT KIT
The Freecooling Thermostat Kit will only operate in cooling-only or heat-pump units in the cooling cycle. This is an energy saving
system that regulates the dampers doors through which outdoor air is taken in when the outdoor temperature is lower than the area
to be air conditioned.
This kit consists of the damper, a motor, power card and a controller with specific programming, safety thermostat for air discharge
and outdoor sensor, completely factory-assembled.
CRANKCASE HEATER (COOLING-ONLY UNITS)
When the unit is operating at low outdoor temperatures it is advisable to fit a crankcase heater.
The purpose of the heater is to keep the oil in the compressor at the correct temperature while the compressor is stopped so that it
can be properly lubricated when started again.
41
OPTIONS

41
400
SOUND MUFFLER
Available for models 16, 22, 24, 28, 30.

420
Field assembled, designed to be installed at the extractor opening of the outdoor

660
unit in order to reduce noise, particularly when the outdoor unit is installed without
ducts, free discharge.
This kit contains the sound muffler and adapter parts for fixing it to the unit.
660 600
Adapter parts
OUTDOOR MOUNTING KIT
Sound muffler
Field assembly.
This option has to be ordered for packaged units when they will be installed outside.
The kit includes an air filter and grille for outdoor air intake which should be installed on the suction side of the outdoor unit, an anti-
rain hood which should be installed on the discharge side of the outdoor fan. For units 10-12-16 it includes also an anti-rain plate
which should be installed on the electrical box. Anti-rain plate
Anti-rain hood (only models 10-12-16)
DIMENSIONS C
MODELS
A B C D E F G D
10-12 180 432 459 280 313 356 104
16 180 507 429 311,8 364 330 104 B E

22 180 505 470 304,9 363 332 96,5


G
24-28-30 180 544 685 304,9 363 418 96,5 Air filter
A
F
Outdoor air intake
FREECOOLING EXTERNAL MOUNTED KIT
Field assembly.
This option has to be ordered for packaged units with freecooling when they will be installed outside, it includes:
- FREECOOLING 1-DAMPER: It includes an outdoor air inlet grille to cover damper and actuator.
- FRECOOLING 2-DAMPER: It includes an anti-rain cap to cover return air damper.
External mounted freecooling 2-damper
H G C B
DIMENSIONS
I F A MODELS
A B C D E F G H I
10-12 200 465 400 635 187,4 162 192 461 153
D 16 200 460 600 723 163 174 192 456 174
22 200 600 600 708 187,5 159 192,5 592 159
24-28-30 200 712 600 784 187,5 158,5 191 706 158,5
E

External mounted freecooling 1-damper

OUTDOOR AIR FILTER KIT


Field assembly.
The outdoor air filter should be installed on the outdoor air inlet of the outdoor unit and is recommended when working in heavily
contaminated area that may soil or clog the outdoor Coil.

ADDITIONAL DROP CHARGE FOR MODELS


EXTERNAL AIR FILTER (OPTIONAL) 10 12 16 22 24 28 30
Nominal flow 30 Pa 30 Pa 30 Pa 30 Pa 30 Pa 30 Pa 30 Pa
Minimum flow 25 Pa 25 Pa 25 Pa 25 Pa 25 Pa 25 Pa 25 Pa
Max. available pressure
for minimum flow 75 Pa 65 Pa 95 Pa 125 Pa 145 Pa 95 Pa 75 Pa

ADDITIONAL DROP CHARGE FOR MODELS


SOUND MUFFLER (OPTIONAL) 16 22 24 28 30
Nominal flow 25 Pa 60 Pa 80 Pa 75 Pa 75 Pa
Minimum flow 20 Pa 45 Pa 70 Pa 60 Pa 60 Pa
Max. available pressure 95 Pa 90 Pa 95 Pa 45 Pa 25 Pa
for minimum flow

ADDITIONAL DROP CHARGE FOR MODELS


SOUND MUFFLER (OPTIONAL) 16 22 24 28 30
+ Nominal flow 55 Pa 90 Pa 110 Pa 105 Pa 105 Pa
OUTDOOR AIR FILTER (OPTIONAL)
Minimum flow 40 Pa 70 Pa 95 Pa 85 Pa 85 Pa
Max. available pressure 65 Pa 45 Pa 25 Pa 20 Pa 0 Pa
for minimum flow
42
www.lennoxeurope.com

BELGIUM, LUXEMBOURG RUSSIA Due to Lennox’s ongoing commitment to quality,


www.lennoxbelgium.com www.lennoxrussia.com the Specifications, Ratings and Dimensions are
subject to change without notice and without
incurring liability.
CZECH REPUBLIC SLOVAKIA Improper installation, adjustment, alteration,
www.lennoxczech.com www.lennoxdistribution.com service or maintenance can cause property
damage or personal injury.
Installation and service must be performed by a
FRANCE SPAIN qualified installer and servicing agency.
www.lennoxfrance.com www.lennoxspain.com

GERMANY UKRAINE
www.lennoxdeutschland.com www.lennoxukraine.com

NETHERLANDS UNITED KINGDOM AND IRELAND


www.lennoxnederland.com www.lennoxuk.com

POLAND OTHER COUNTRIES


www.lennoxpolska.com www.lennoxdistribution.com

PORTUGAL
www.lennoxportugal.com

MSL60E-0701 12-2006

You might also like