A. GENERAL
1. THE FOLLOWING CONSTRUCTION NOTES AND TYPICAL DETAILS HAS BEEN APPLIED TO ALL DRAWING 5. REINFORCING BARS HAS BEEN LAPPED A MINIMUM OF 30 BAR DIAMETERS WHERE SPLICE
AND A MORE MODIFIED DETAIL WAS PROVIDED TO MEET SPECIAL CONDITION. DOWELS FROM FOOTING OR SLABS HAS EXTENDED INTO THE BLOCK WALL A MINIMUM OF
2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, 30 BAR DIAMETERS. REBARS WAS PROPERLY TIED W/ G.I. WIRE.
MISCELLANEOUS IRON,PRE-CAST CONCRETE ETC,HAS BEEN SUBMITTED FOR ENGINEERS 6. ALL CELLS CONTAINING REINFORCING BARS OR INSERTS HAS BEEN SOLIDLY FILLED WITH
APPROVAL BEFORE FABRICATION. CONCRETE GROUT (REFER TO SPECIFICATIONS)
3. THE CONTRACTOR HAS VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN CHECK WITH 7. LAP SPLICES AND HOOKS
MECHANICAL AND ELECTRICAL CONTRACTORS FOR CONDUITS PIPES SLEEVES,ETC.,HAS BEEN ALL BARS FOR BEAMS AND COLUMN HAS BEEN LAPPED WITH A LENGTH OF 30 X BAR DIAMETER.
EMBEDDED IN CONCRETE. ALL BARS FOR SUSPENDED SLAB HAS BEEN LAPPED WITH A LENGTH OF 40 X BAR DIAMETER
4. IT WAS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING & BRACING NO MORE THAN 50% OF THE REBARS HAS BEEN SPLICED WITHIN THE REQUIRED LAP LENGTH.
OF THE STRUCTURE FOR ALL LOADS THAT HAS IMPOSED DURING CONSTRUCTION. 90° HOOKS WITH 12 X BAR DIAMETER EXTENSION(SPECIFICALLY FOR BEAMS) HAS BEEN
B. CONCRETE &REINFORCEMENT ANCHORED
1. ALL MATERIALS AND WORKMANSHIP HAS BEEN CONFORM WITH THE LATEST BUILDING CODE OF
AMERICAN CONCRETE INSTITUTE (ACI-318)
2. ALL CONCRETE HAS BEEN DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY
EIGHT (28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMPS AS FOLLOWS
400.00
3
R.C Piles 4000 PSI (20.70 MPa) 4 IN (19mm ) 5 IN. (130mm )
3. ALL REINFORCING BARS HAS BEEN CONFORM TO ASTM A615 GRADE 60 (414 MPa) SEE CONSTRUCTION NOTES FOR THE SIZE
FOR 20mmØ & LARGER BARS AND GRADE 40 (276 MPa) FOR SMALLER BARS AND SPACING OF VER. AND HOR. BARS
4. IN GENERAL THE LATEST EDITION OF ACI-315, MANUAL OF STANDARD PRACTICE DETAILING
REINFORCED CONCRETE STRUCTURES HAS BEEN ADHERED TO UNLESS OTHERWISE SHOWN
OR NOTED.
5. MINIMUM CONCRETE COVER FOR REINFORCING STEEL WAS MAINTAIN AS FOLLOWS
CHB WALL OPENING OR END WALL
3
SUSPENDED SLABS 4 IN. ( 19mm )
1
SLAB ON GRADE 1 IN. ( 38mm )
2
WALLS ABOVE GRADE 1 IN. ( 25mm )
BEAM STIRRUPS AND COLUMN TIES
WHERE CONCRETE IS EXPOSED TO
1 21 IN. ( 38mm ) CORNER WALL
EARTH BUT POURED AGAINST FORMS 2 IN. ( 50mm )
WHERE CONCRETE IS DEPOSITED RC COLUMN
DIRECTLY AGAINST EARTH 3 IN. ( 75 mm)
CHB WALL
6. SPLICES HAS BEEN SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE DOWEL BARS TO MATCH
W/ TABLE 1 (TABLE OF LAP SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE SHOWN CHB HOR. BARS
ON DRAWINGS, SPLICES HAS BEEN STAGGERED WHENEVER POSSIBLE
7. ALL ANCHOR BOLT,DOWELS, AND OTHER INSERTS,HAS BEEN PROPERLY POSITIONED &
SECURED IN PLACE PRIOR TO PLACING OF CONCRETE.
8. CONTRACTOR HAS NOTE AND PROVIDE ALL MISCELLANEOUS CURBS,SILLS,STOOLS 1-10 mm Ø VER. BAR 12 THK. EXPANSION JOINT
EQUIPMENT'S AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, w/ MASTIC FILLER
ELECTRICAL, AND MECHANICAL DRAWINGS.
12 THK. EXPANSION JOINT
9. ALL CONCRETE HAS BEEN KEPT MOIST FOR A MINIMUM OF SEVEN CONSECUTIVE DAYS 400.00
IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP FOG SPRAYING,CURING 400.00
w/ MASTIC FILLER 400.00
FOUNDATION 24 HRS
SUSPENDED SLAB EXCEPT WHEN 400.21
B
S-02
C-2 C-2 C-2
C2-F1 C2-F1 C2-F1 1
1 WF-1 WF-1
2"x6" Treated Lumber (Sill plate)
Placed on 6" CHB
WF-2
WF-1
2"x8" Treated Lumber (Sill plate)
WF-1
Placed on 2- 4" CHB
GROUND COVERED
W/ 6 MIL
POLYETHYLENE BULACAN UNIT
SHEET
C-1 C-1 C-1
C1-F1 C1-F1 C1-F1
WF-1 WF-1
2
2
WF-1
WF-1
WF-2
2"x8" Treated Lumber (Sill plate)
Placed on 2- 4" CHB
1 1
2"Dia. x12" L Bolt w/ washer 2"Dia. x12" L Bolt w/ washer
1
2"Dia. x12" L Bolt w/ washer Spaced @ 450mm O.C. Spaced @ 450mm O.C.
Spaced @ 450mm O.C. FLOOR JOIST 2"X3" ENGINEERED BAMBOO FLOOR JOIST 2"X3" ENGINEERED BAMBOO
FLOOR JOIST 2"X3" ENGINEERED BAMBOO SILL PLATE 2"X6" LUMBER SILL PLATE 2"X6" LUMBER
SILL PLATE 2"X6" LUMBER
B-1
1
2" Dia. X12" L Bolt w/ washer @ 450mm O.C.
1
2" Dia. X12" L Bolt w/ washer @ 450mm O.C.
2-FLOOR JOIST 2"X3"
FLOOR JOIST 2"X3"
ENGINEERED BAMBOO
SILL PLATE 2"X6" LUMBER ENGINEERED BAMBOO
SILL PLATE 2"X8" LUMBER BEAM ID BEAM DETAILS
10mm HORIZONTAL BAR
every 3rd Layer 10mm HORIZONTAL BAR
2" THK CONCRETE CAP W/ 2-10mm dia. every 3rd layer
2" THK CONCRETE CAP W/ 2-10mm dia.
Horizontal Bars and C-bar @300mm O.C. Horizontal Bars and C-bar @300mm O.C. 2-16mm dia. TOP BAR
6" CHB WALL WITH 10mm dia. 2-4" CHB WALL WITH 10mm dia.
VERTICAL BARS @ 600mm O.C VERTICAL BARS @ 600mm O.C
10mm dia.Stirrups 1@50mm,
B-1
SILL PLATE