ET401 / ET402
IGNITION TRANSFORMER
PRODUCT HANDBOOK
INSTALLATION INSTRUCTIONS
The applicable regulations must be observed when
mounting the device and carrying out the electrical
connections. Particular attention must be given to
method used to install the H.T. cables. Avoid
unnecessary lengths, sharp bends over hard edges,
extremely high temperatures etc., any of which could
give rise to reduced performance or possible problems.
The length of power line is about 0.5 m, connect the
wires with their terminals: brown-live wire, blue-null wire,
yellow/green-ground wire.
For trouble-free operation, the correct spark gap at the
ignition electrodes must be observed, supply voltage
reductions of minus 15% and low as well as high
ambient temperatures can give rise to problems The
positioning of the H.T. ignition cables with regard to TV
and radio interference is also extremely important. The
cables should be kept short, run as close together as
possible and should not cross or be in contact with any
other power cables or fittings. See "Technical data" for
INTRODUCTION recommended settings.
ET serial ignition transformer with high voltage cable
connection pin and power cable, suitable to be installed HIGH VOLTAGE CABLE FASTEN CLIP
in burner control box, can be wildly used with oil, gas High voltage cable fasten clip is a self-lock clip.
and dual fuel burners. Enables big spark deformation Insert the cable to clip, then fold it till to the lock
on burners with a high fire-rating or high combustion-air position.
velocity. In addition to this, it generates the lowest
electromagnetic interferences of all known electronic
ignition devices, which is especially important if the
burner has to comply with EN 55014-2. ET serial
ignition transformer combines a low power consump-
tion with a low inrush current.
The operation must be intermittent ignition, work-cycle
limit of 3 minutes, in which the ignition time is less than
1 minute, it means 33 % E.D. in 3 minutes
CAUTION
Improper operation will cause personal
CONSTRUCTIONAL FEATURES injury or equipment damage, Disconnect the
ET serial ignition transformer adopt transistorised power connection before installation.
oscillator to produce a high frequency voltage which is
then increased to 14 kV, compare with conventional Must be well earthed!
iron cored transformer, despite they are very compact When Ignition transformer is working,
dimensions, they have outstanding performance. The access to high voltage terminal is strictly
dimensions of the housing and fixing holes are such prohibited!
that it can be mounted underneath the burner control
box wiring base. When control fail, the ignition transformer
ET serial ignition transformer supply with 3 cores power ignite continuously, may cause overheating
cable, ET401 has 1 high voltage output pin connection, damage.
suitable for use with gas burners. ET402 has 2 high
voltage output pin connections, suitable for use with oil,
gas and dual fuel burners. The pin diameter is Ø1 mm ELECTRIC SHOCK PROTECTION
(Show in dimension drawing). Connect with high Must consider the electric shock protection.
voltage cable with fasten clip. , make sure the end-users can not access the
parts not proper insulated without tool. The
ignition system must be fully insulated with the
metal parts not earthed and the parts without
electric shock protection.
1 50043240-001 REV.A
TECHNICAL DATA
Model ET 401 ET 402
Power supply 230 V~ (-15 ~ +10%), 0.25 A, 50/60 Hz
Ignition voltage output > 14 kV amp > 2 x 7 kV amp
Secondary current < 40 mA rms
Secondary frequency 20 kHz
High voltage output connection pin Ø1mm Pin 2 x Ø1mm Pin
Rating 33 % E.D. in 3 minutes
Spark gap 3-5 mm
Ignition cable type Cable plug,the self-lock clip provided
Insulation standard IP40
Permissable ambient -15°C …+60°C
Weight (g) 290 300
ET 401/402 DIMENSIONS
Front View Side View
侧视图
High Voltage Cable
Connection Pin