33kV OHL-ABU AJRAM Line Specs
33kV OHL-ABU AJRAM Line Specs
Reference Document
PTS-12ED404 : Scope of Work \Technical Specifications
EA-869538 : Relaying & Metering one line diagram
Line Details
29.00 Km
Relay details
Relay Type : P54691AK7M0820M
Make : ALSTOM
Rated current : 1A
Protection Functions : 87L-1
CT Details
CT Ratio : 1200-600
Adopted Ratio : 1200 /1A
CT Secondary : 1A
Class : TPS
Vk : 1200V@1200A tap
System Details
VT Ratio :
VT Primary : 33kV
VT Secondary : 115V
Frequency : 60Hz
Fault Current : 25000A
X/R Ratio (AS per SEC practice) : 28.2
Source Reactance Xs : (Ph volt./Ph.cu)*sin(ATAN(X/R))
: (33 x 1000 x sin(ATAN(28.2))
sqrt(3) x 25000
: 0.762 ohm
Source Resistance Rs : (Ph volt./Ph.cu)*cos(ATAN(X/R))
: (33 x 1000 x cos(ATAN(28.2))
sqrt(3) x 25000
: 0.027 ohm
Delta Char Angle : 87.97deg
Source Impedance : (Rs + j Xs)
: 0.0270 + j 0.7620
Zs : 0.7625 L 87.97 deg
Line Details
Total Length of the Line : 29.000 Km
Positive resistance : 0.21
Positive reactance : 0.29
Zero resistance : 0.21
Configuration
k1 : The lower percentage bias setting used when the bias current is below I S2.
This provides stability for small CT mismatches, whilst ensuring good sensitivity to
resistive faults under heavy load conditions.
k2 : The higher percentage bias setting used to improve relay stability under heavy
through fault current conditions.
IS1 = 2.5 x Ic
IS1 = 0.002 A
If we consider a single end fault with no load but fault current I, the minimum operating fault current is
Idiff = I
Ibias = 1/2 I
Phase Is1 0.2-2In 0.20 In The minimum pick-up level of the relay.
Phase Is2 1-30In 2.0 In The bias current threshold, above which
the higher percentage bias k2 is used
Phase k1 30-150% 30% The lower percentage bias setting used when the
PIT time 0-0.2s 0.2sec This timer is initiated upon receipt of PIT flag in
the message.
Ph CT correction 1-8 1 To compensate CT ratios mismatch between
terminals.
compensation None,Cap Cha, None Type of compensation
Vector group
suseptance 10nS - 10S N/A Compensation, set to Cap Charging
PIT I selection Local / Remote Local Current to be used for permissive Intertrip
bias_curve
x-Is2
Relay Bias Curve
y-Is1
4.50
k1 4.25 k2 Ibais Idiff
0.30 4.00 1.50 ## ##
3.75
0.30 3.50 1.50 ## ##
0.30 3.25 1.50 ## ##
3.00 Percentage
0.30 2.75 1.50 ## ##
2.50 Operate
2.25
Idiff=I1+I2
2.00
1.75
1.50
1.25
1.00 Percentage Restrain
0.75
0.50
0.25
Is1 0.00
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
Is2
Ibias=(|I1|+|I2|)/2
CT Details
CT Ratio : 1200-600
Adopted Ratio : 1200/1A
CT Secondary : 1A
Class : TPS
System Details
VT Primary : 33kV
VT Secondary : 115V
Voltage : 33kV
Frequency : 60Hz
Actual Fault current : 25000A
X/R Ratio : 28.2
Source Reactance Xs : Ph volt./Ph.cu)*sin(ATAN(X/R))
: (33 x 1000 x sin(ATAN(28.2))
sqrt(3) x 25000
: 0.762 ohm
Source Resistance Rs : (Ph volt./Ph.cu)*cos(ATAN(X/R))
: (33 x 1000 x cos(ATAN(28.2))
sqrt(3) x 25000
: 0.027 ohm
Delta Char Angle : 87.97deg
Line Length : 29.000 Km
Z2 = 64.453 54.41721
The Line Angle = 54 deg
Therefore actual Zone 2 reach, Z2 = 64.453 L 54 deg (secondary)
Umin = 29700 V
The maximum full load current = 1000 A Considered 80% breaker rating
Set the V< Blinder voltage threshold at the recommended 70% of Vn = 0.7 x 115/1.732 (L-G voltage)
= 46.48 V
1.4
Rarc = (17500 x L) / If
If = Maximum expected phase-phase fault current (A);
L = Maximum phase conductor separation (m); = 2m
Rarc = Arc resistance, calculated from the van Warrington formula (W).
1.4
Rarc for Ph-E fault = 28707d/IF
Length of arc is assumed as (d) = 4.00 m
DEF
Since it is parallel line "DEF" polarizing based on negative sequence is recommended
DELTA
Delta charge angle = source impedance angle
= 15% of In = 180.00A
= 19% = 20.9V
= = 13.8V
= = 118.80A
or 9.9% of In
Mode: Advanced
Line Parameters
Parameter Setting Remarks
Group# Group1
Line length 29.000km
Line Impedance 42.9669 ohm (secondary Value)
Line angle 54.0deg
Residual Comp 0.3
Residual Angle -154.0deg
Mutual Comp Disabled
KZm Mutual Set: N/A
KZm Mutual Angle: N/A
Mutual cut-off (k): N/A
Phase Sequence: ABC
CB Tripping Mode 3pole
Ground Distance
Distance Element-Phase
Parameter Setting Remarks
Z1 Ph. Reach 36.52 /In ohm all ohmic values are secondary
Z1 Ph. Angle 54.4deg
R1 Ph. Resistive 19.19 /In ohm
Z1 Tilt Top Line -5.0deg
Z1 Ph. Sensit. Iph>1 75mA
Distance Element-Ground
Parameter Setting Remarks
TRIP ON CLOSE
SOTF Status ExtendedExtPulse
SOTF Delay N/A
SOTF Tripping 000001
TOR Status disabled
TOR Tripping disabled
TOC Reset Delay 1.0s
SOTF Pulse 1.0s
TOC Delay 200ms
Z1 EXTENSION
Z1 Ext. Scheme Disabled
LOSS OF LOAD
LOL Scheme Disabled
IN > DIRECTIONAL
IN > Char Angle -60deg
IN> Polarisation zero Seq
Protection Function (Non Directional Overcurrent and Earth fault -50/51& 50N/51N)
CT RATIO : 1200 / 1 A
Voltage Rating : 33kV
max full load current : 1000 A Considered 80% breaker rating
51 settings:
- 51 is the Time delayed non-directional relay
- 51 is used as a back up protection for downstream faults. Therefore the operating time depends on
the operating time of the T/F HV overcurrent protection & Bus Tie
- The pickup characteristics should be more than the maximum operating load of the Line
- A pickup settinq of 120 % of the maximum operating load of the Line is proposed.
Maximum load on the line = 1000 A Considered 80% breaker rating
Pickup setting : = 1.20 x Max load current
( 51P Current Set ) = 1.20 x 1000
= 1200 A (CT primary)
= 1.00 A (CT Secondary)
(I> Current Set ) = 1.00 of In
Characteristics = IEC Norm Inverse
Time Multiplier Setting
Plug Setting Multiplier (PSM) for 51 relay = Fault Current / Pickup Current
= 25000.0 / 1200 = 20.84
PSM for TR 51LV relay = 20.00 (Note: If calculated PSM>20, then PSM=20)
Required operating time = = Grading margin + operating time of OG feeder relay
= 400 + 877
I>3 function IEC Def Time IEC Def Time the tripping characteristic
>3 Time Delay 0.0 S 0.0 S the time-delay for the definite
time setting
0.0 0.0 the time multiplier setting
of the IEC IDMT characteristic.
Remaining Advanced settings ( Left as default)
51N settings:
- 51 N is the Time delayed non-directional Earth Fault relay
- 51 N is used as a back up protection for downstream earth faults. Therefore the operating time
depends on the operating time of the T/F HV O/C & Bus section relays
- The pickup characteristics should be more than the standing unbalance current
as seen by the system and the CT's. This has to be checked at site during commsg.
As an assumption, this standing unbalance may be taken as 30% of the max load current
Summarising (51N)
( I0> Function ) ON
( I0> Current Set ) 0.25 xIn
( I0> Characterstics ) IEC Norm Inverse
( I0> TMS ) 0.39
50N settings:
- 50N is the Instantaneous non-directional Earthfault protection relay
- 50N is used as a back up high speed protection . This will be in addition to the protection
offered by the line protection
- A pickup settinq of 50 % of the maximum operating load of the Line is proposed.
Maximum load on the line = 1000 A Considered 80% breaker rating
Pickup setting : = 0.50 x Max load current
( 50N Current Set ) = 0.50 x 1000
= 500 A (CT primary)
= 0.42 A (CT Secondary)
(I0>> Current Set ) = 0.42 of In
( As no co-ordination is required with downstream relays)
Recommended Time Settinq = 0.3 s
Characterstics IEC Def Time
Summarising (50N)
( I0>> Function ) ON
( I0>> Current Set ) 0.42 xIn
( I0>> Characterstics ) IEC Def Time
( I0>> Time Delay ) 0.3 S
IN>1 function IEC Norm Inv IEC Def Time the tripping characteristic
IN>3 function IEC Def Time IEC Def Time the tripping characteristic
IN>3 Time Delay 0.0 S 0.0 S the time-delay for the definite
time setting
0.0 0.0 the time multiplier setting
of the IEC IDMT characteristic.
Remaining Advanced settings ( Left as default)
Reference Document
PTS-12ED404 : Scope of Work \Technical Specifications
EA-869538 : Relaying & Metering one line diagram
Relay details
Relay Type with approved relay ordering code : 7SD5221-5DB99-9HM7+L0R+M2A+N2J
Make : SIEMENS
Rated current : 1A
Protection Functions : 87L-1/21-1/67N-1
CT Details
CT Ratio : 1200-600
Adopted Ratio : 1200 /1A
CT Secondary : 1A
Class : TPS
Vk : 1200V@1200A tap
System Details
VT Ratio :
VT Primary : 33kV
VT Secondary : 115V
Frequency : 60Hz
Fault Current (AS PER PTS # 73 OF 92) : 25000A
X/R Ratio (AS PER PTS # 73 OF 92) : 28.2
Source Reactance Xs : (Ph volt./Ph.cu)*sin(ATAN(X/R))
: (33 x 1000 x sin(ATAN(28.2))
sqrt(3) x 25000
Xs : 0.762 ohm
Source Resistance Rs : (Ph volt./Ph.cu)*cos(ATAN(X/R))
: (33 x 1000 x cos(ATAN(28.2))
sqrt(3) x 25000
Rs : 0.027 ohm
Delta Char Angle : 87.97deg
Source Impedance : (Rs + j Xs)
: 0.0270 + j 0.7620
Zs : 0.7625 L 87.97 deg
Line Details
29.00 Km
Zs + ZL = (0.027+j0.762) + (5.9798+j8.3578 )
= 6.007 +j 9.120
= 10.9203 L 56.63 deg
= 33/1.732 = 1744.746 A
10.920 ohm
= 1.745 KA
= 2.09 KA
IdUnre = IdUnre1
CT Ratio
IdUnre = 2.09 KA
1200 /1A
= 1.745 A
Recommended Setting for IdUnre = 5 xIBase
Line Impedance
Calculated Sec Impedance Zsec = N x Z prim in ohm Where Zprim = Primary Impedance in ohm
Line Impedance secondary = Line Impedance primary x N
= 10.277 L 54.42 x 4.181
= 42.97 ohm
Select Line Angle = 54 deg for convenience
Therefore set Line Impedance and Line Angle:
= 42.97 L 54 deg ohm
Umin = 29700 V
= 71.077 * 0.85
Rloadmin Secondary = 60.4 ohm
= 31.78 + 3
= 34.78 deg
= 35 deg
1.4
(Arc Resistance) Rarc = (28710 x L) / If
RFPPmin Rarc
If = Maximum expected phase-phase fault current (A);
L = Maximum phase conductor separation (m); = 5 m
Rarc = Arc resistance, calculated from the van Warrington formula (W).
To cover max. fault resistance IF = V / Ztot
Ztotal = 2 (Zs+ZL)
= 2(Rs+R1) +j 2(Xs+X1)
= 12.0136 +j 18.2396
= 21.84 L 56.63 deg
= 21.841 L 56.63
For a Ph-Ph fault, Fault current IF IF = 33x1000/21.84
at the end of the Line IF = 1510.92A
Rarc for Ph-Ph fault (Primary) = 28710 x 5 / ( 1511^1.4 )
= 5.082 ohm
Rarc for Ph-Ph fault(Secondary) = 5.082 x 4.181
= 21.25 ohm
Min allowed resistive reach RFPPmin 21.25 ohm
As per relay manual Phase resistive reach should be less than 3 time reactance part of the impedance
reach of that zone
Setting of Resistive reach zone1 3 . X1 = 89.1 ohm
RFPP1 = 71.28 ohm
As per relay manual resistive reach should be less than 4.5 time reactance part of the impedance
reach of that zone
Setting of Resistive reach zone1 4.5 . X01 = 133.7 ohm
RFPE1 = 106.92 ohm
Setting of Resistive reach reverse zone4 4.5 . X04 < 55.0 ohm
= 55.04 ohm (should be more than Rarc)
for faults on the entire line. It is not necessary to cover all distance protection zones. A safety margin of at least 10% is recommended. In order to
get operation from distance zones, the phase selection outputs STCNDZ or STCNDI must be connected to input STCND on distance zones.
= atan (X1L+XN)
(R1L+RN)
XN = (X0L-X1L)/3
RN = (R0L-R1L)/3
X1L = 34.944
R1L = 25.002
X0L = 34.944
R0L = 25.002
XN = 0
RN = 0
= 54.445 deg
Resistive reach
In the same way as for phase-to-earth fault, the reach is automatically calculated based on the
setting of X1. The reach will be X1/tan(60°) =X1/SQR(3).
System Details
CT RATIO : 1200 / 1 A
Voltage Rating : 33kV
max full load current : 1000 A Considered 80% breaker rating
51 settings:
- 51 is the Time delayed non-directional relay
- 51 is used as a back up protection for downstream faults. Therefore the operating time depends on
the operating time of the T/F HV overcurrent protection & Bus Tie
- The pickup characteristics should be more than the maximum operating load of the Line
- A pickup settinq of 120 % of the maximum operating load of the Line is proposed.
Maximum load on the line = 1000 A Considered 80% breaker rating
Pickup setting : = 1.20 x Max load current
( 51P Current Set ) = 1.20 x 1000
= 1200 A (CT primary)
= 1.00 A (CT Secondary)
(I> Current Set ) = 1.00 of In
Characteristics = IEC Norm Inverse
Plug Setting Multiplier (PSM) for 51 relay = Fault Current / Pickup Current
= 25000 / 1200 = 20.84
PSM for TR 51LV relay = 20.00 (Note: If calculated PSM>20, then PSM=20)
Required operating time = = Grading margin + operating time of OG feeder relay
= 400 + 877
Required operating time = 1277 ms
To achive this operating time, TMS setting has to set as follows
1.277 = 0.14 / {(PSM)0.02 -1} x TMS
1.277 0.14 20.00 0.02 0.57
Therefore TMS = ( / ) x {( ) -1} =
Recommended Setting:
Pickup setting : = 0.5 x fault Current
= 0.5 x 25000
= 12500 A (CT primary)
= 10.41 A (CT Secondary)
( As no co-ordination is required with downstream relays)
Recommended Time Settinq = 0.2 s
Characterstics IEC Def Time
Summarising (50 ABC)
( I>> Function ) ON
( I>> Current Set ) 10.41 xIn
( I>> Characterstics ) IEC Def Time
( I>> Time Delay ) 0.2 S
51N settings:
- 51 N is the Time delayed non-directional Earth Fault relay
- 51 N is used as a back up protection for downstream earth faults. Therefore the operating time
depends on the operating time of the T/F HV O/C & Bus section relays
- The pickup characteristics should be more than the standing unbalance current
as seen by the system and the CT's. This has to be checked at site during commsg.
As an assumption, this standing unbalance may be taken as 30% of the max load current
Plug Setting Multiplier (PSM) for 51 relay = Fault Current / Pickup Current
= 25000 / 300 = 83.34
PSM for TR 51LV relay = 20.00 (Note: If calculated PSM>20, then PSM=20)
Required operating time = = Grading margin + operating time of OG feeder relay
= 400 + 469
Required operating time = 869 ms
To achive this operating time, TMS setting has to set as follows
0.869 = 0.14 / {(PSM)0.02 -1} x TMS
0.869 0.14 20.00 0.02 0.39
Therefore TMS = ( / ) x {( ) -1} =
Summarising (51N)
( I0> Function ) ON
( I0> Current Set ) 0.25 xIn
( I0> Characterstics ) IEC Norm Inverse
( I0> TMS ) 0.39
50N settings:
- 50N is the Instantaneous non-directional Earthfault protection relay
- 50N is used as a back up high speed protection . This will be in addition to the protection
offered by the line protection
- A pickup settinq of 50 % of the maximum operating load of the Line is proposed.
ECOMM= POTT, hence the POTT scheme is enabled, below Setting are recommendedfor Current reversal and Weak end in-
Setting Parameter Setting Range Setting Remarks
Z3RBD (Zone 3 reverse block time delay (cycles)) 3 TBC
EBLKD (Echo block time delay (cycles)) 10 TBC
ETDPU (Echo time delay pickup (cycles)) 2 TBC
EDURD ( Echo duration time delay 10 TBC
EWFC (Weak infeed trip) Y, N, SP N TBC
PT1 (General permissive trip received) SELOGIC equation INxxx Depending on
EPTDIR (Enable directional element Y, N N
Reference Document
PTS-12ED404 : Scope of Work \Technical Specifications
EA-869538 : Relaying & Metering one line diagram
Line Details
21.00 Km
Relay details
Relay Type : P54691AK7M0820M
Make : ALSTOM
Rated current : 1A
Protection Functions : 87L-1
CT Details
CT Ratio : 1200-600
Adopted Ratio : 1200 /1A
CT Secondary : 1A
Class : TPS
Vk : 1200V@1200A tap
System Details
VT Ratio :
VT Primary : 33kV
VT Secondary : 115V
Frequency : 60Hz
Fault Current : 25000A
X/R Ratio (AS per SEC practice) : 28.2
Source Reactance Xs : (Ph volt./Ph.cu)*sin(ATAN(X/R))
: (33 x 1000 x sin(ATAN(28.2))
sqrt(3) x 25000
: 0.762 ohm
Source Resistance Rs : (Ph volt./Ph.cu)*cos(ATAN(X/R))
: (33 x 1000 x cos(ATAN(28.2))
sqrt(3) x 25000
: 0.027 ohm
Delta Char Angle : 87.97deg
Source Impedance : (Rs + j Xs)
: 0.0270 + j 0.7620
Zs : 0.7625 L 87.97 deg
Line Details
Total Length of the Line : 21.000 Km
Positive resistance : 0.21
Positive reactance : 0.29
Zero resistance : 0.21
Zero reactance : 0.29
k1 : The lower percentage bias setting used when the bias current is below I S2.
This provides stability for small CT mismatches, whilst ensuring good sensitivity to
resistive faults under heavy load conditions.
k2 : The higher percentage bias setting used to improve relay stability under heavy through
fault current conditions.
IS1 = 2.5 x Ic
IS1 = 0.002 A
If we consider a single end fault with no load but fault current I, the minimum operating fault current is
Idiff = I
Ibias = 1/2 I
Phase Is1 0.2-2In 0.20 In The minimum pick-up level of the relay.
Phase Is2 1-30In 2.0 In The bias current threshold, above which
the higher percentage bias k2 is used
Phase k1 30-150% 30% The lower percentage bias setting used when the
PIT time 0-0.2s 0.2sec This timer is initiated upon receipt of PIT flag in
the message.
Ph CT correction 1-8 1 To compensate CT ratios mismatch between
terminals.
compensation None,Cap Cha, None Type of compensation
Vector group
suseptance 10nS - 10S N/A Compensation, set to Cap Charging
PIT I selection Local / Remote Local Current to be used for permissive Intertrip
bias_curve
Relayy-Is1
x-Is2
Bias Curve
4.50
k1 4.25 k2 Ibais Idiff
4.00
0.30 1.50 ## ##
3.75
0.30
3.50 1.50 ## ##
3.25
0.30 1.50 ## ##
3.00 Percentage
0.30
2.75 1.50 ## ##
2.50 Operate
Idiff=I1+I2
2.25
2.00
1.75
1.50
1.25
1.00 Percentage Restrain
0.75
0.50
0.50
0.25
Is1 0.00
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
Is2
Ibias=(|I1|+|I2|)/2
CT Details
CT Ratio : 1200-600
Adopted Ratio : 1200/1A
CT Secondary : 1A
Class : TPS
System Details
VT Primary : 33kV
VT Secondary : 115V
Voltage : 33kV
Frequency : 60Hz
Actual Fault current : 25000A
X/R Ratio : 28.2
Source Reactance Xs : Ph volt./Ph.cu)*sin(ATAN(X/R))
: (33 x 1000 x sin(ATAN(28.2))
sqrt(3) x 25000
: 0.762 ohm
Source Resistance Rs : (Ph volt./Ph.cu)*cos(ATAN(X/R))
: (33 x 1000 x cos(ATAN(28.2))
sqrt(3) x 25000
: 0.027 ohm
Delta Char Angle : 87.97deg
Line Length : 21.000 Km
: 7.442 L 54.42
Umin = 29700 V
The maximum full load current = 1000 A Considered 80% breaker rating
With 110% Overload Capacity
Set the V< Blinder voltage threshold at the recommended 70% of Vn = 0.7 x 115/1.732 (L-G voltage)
= 46.48 V
1.4
Rarc = (17500 x L) / If
If = Maximum expected phase-phase fault current (A);
L = Maximum phase conductor separation (m); = 2m
Rarc = Arc resistance, calculated from the van Warrington formula (W).
=
Setting of Resistive reach zone4 = 30% of Max allowed reach
=
DEF
Since it is parallel line "DEF" polarizing based on negative sequence is recommended
DELTA
Delta charge angle = source impedance angle
= 15% of In = 180.00A
= 19% = 20.9V
= = 13.8V
= = 118.80A
or 9.9% of In
Mode: Advanced
Line Parameters
Parameter Setting Remarks
Group# Group1
Line length 21.000km
Line Impedance 31.11 ohm (secondary Value)
Line angle 54.0deg
Residual Comp 0.3
Residual Angle -154.0deg
Mutual Comp Disabled
KZm Mutual Set: N/A
KZm Mutual Angle: N/A
Mutual cut-off (k): N/A
Phase Sequence: ABC
CB Tripping Mode 3pole
Ground Distance
Parameter Setting Remarks
Distance Element-Phase
Parameter Setting Remarks
Z1 Ph. Reach 26.45 /In ohm all ohmic values are secondary
Z1 Ph. Angle 54.4deg
R1 Ph. Resistive 19.19 /In ohm
Z1 Tilt Top Line -5.0deg
Z1 Ph. Sensit. Iph>1 75mA
Distance Element-Ground
Parameter Setting Remarks
Z1 Gnd Reach 26.45 /In ohm
TRIP ON CLOSE
SOTF Status ExtendedExtPulse
SOTF Delay N/A
SOTF Tripping 000001
TOR Status disabled
TOR Tripping disabled
TOC Reset Delay 1.0s
SOTF Pulse 1.0s
TOC Delay 200ms
Z1 EXTENSION
Z1 Ext. Scheme Disabled
LOSS OF LOAD
LOL Scheme Disabled
IN > DIRECTIONAL
IN > Char Angle -60deg
IN> Polarisation zero Seq
IN > Vnpol Set 6.497V
Protection Function (Non Directional Overcurrent and Earth fault -50/51& 50N/51N)
CT RATIO : 1200 / 1 A
Voltage Rating : 33kV
max full load current : 1000 A Considered 80% breaker rating
51 settings:
- 51 is the Time delayed non-directional relay
- 51 is used as a back up protection for downstream faults. Therefore the operating time depends on
the operating time of the T/F HV overcurrent protection & Bus Tie
- The pickup characteristics should be more than the maximum operating load of the Line
- A pickup settinq of 120 % of the maximum operating load of the Line is proposed.
Maximum load on the line = 1000 A Considered 80% breaker rating
Pickup setting : = 1.20 x Max load current
( 51P Current Set ) = 1.20 x 1000
= 1200 A (CT primary)
= 1.00 A (CT Secondary)
(I> Current Set ) = 1.00 of In
Characteristics = IEC Norm Inverse
Time Multiplier Setting
Plug Setting Multiplier (PSM) for 51 relay = Fault Current / Pickup Current
= 25000.0 / 1200 = 20.84
PSM for TR 51LV relay = 20.00 (Note: If calculated PSM>20, then PSM=20)
Required operating time = = Grading margin + operating time of OG feeder relay
= 400 + 877
Required operating time = 1277 ms
To achive this operating time, TMS setting has to set as follows
I>3 function IEC Def Time IEC Def Time the tripping characteristic
>3 Time Delay 0.0 S 0.0 S the time-delay for the definite
time setting
0.0 0.0 the time multiplier setting
of the IEC IDMT characteristic.
Remaining Advanced settings ( Left as default)
51N settings:
- 51 N is the Time delayed non-directional Earth Fault relay
- 51 N is used as a back up protection for downstream earth faults. Therefore the operating time
depends on the operating time of the T/F HV O/C & Bus section relays
- The pickup characteristics should be more than the standing unbalance current
as seen by the system and the CT's. This has to be checked at site during commsg.
As an assumption, this standing unbalance may be taken as 30% of the max load current
Summarising (51N)
( I0> Function ) ON
( I0> Current Set ) 0.25 xIn
( I0> Characterstics ) IEC Norm Inverse
( I0> TMS ) 0.39
50N settings:
- 50N is the Instantaneous non-directional Earthfault protection relay
- 50N is used as a back up high speed protection . This will be in addition to the protection
offered by the line protection
- A pickup settinq of 50 % of the maximum operating load of the Line is proposed.
Maximum load on the line = 1000 A Considered 80% breaker rating
Pickup setting : = 0.50 x Max load current
( 50N Current Set ) = 0.50 x 1000
= 500 A (CT primary)
= 0.42 A (CT Secondary)
(I0>> Current Set ) = 0.42 of In
( As no co-ordination is required with downstream relays)
Recommended Time Settinq = 0.3 s
Characterstics IEC Def Time
Summarising (50N)
( I0>> Function ) ON
( I0>> Current Set ) 0.42 xIn
( I0>> Characterstics ) IEC Def Time
( I0>> Time Delay ) 0.3 S
IN>1 function IEC Norm Inv IEC Def Time the tripping characteristic
IN>3 function IEC Def Time IEC Def Time the tripping characteristic
IN>3 Time Delay 0.0 S 0.0 S the time-delay for the definite
time setting
0.0 0.0 the time multiplier setting
of the IEC IDMT characteristic.
Remaining Advanced settings ( Left as default)
Reference Document
PTS-12ED404 : Scope of Work \Technical Specifications
EA-869538 : Relaying & Metering one line diagram
Relay details
Relay Type with approved relay ordering code : 7SD5221-5DB99-9HM7+L0R+M2A+N2J
Make : SIEMENS
Rated current : 1A
Protection Functions : 87L-1/21-1/67N-1
CT Details
CT Ratio : 1200-600
Adopted Ratio : 1200 /1A
CT Secondary : 1A
Class : TPS
Vk : 1200V@1200A tap
System Details
VT Ratio :
VT Primary : 33kV
VT Secondary : 115V
Frequency : 60Hz
Fault Current (AS PER PTS # 73 OF 92) : 25000A
X/R Ratio (AS PER PTS # 73 OF 92) : 28.2
Source Reactance Xs : (Ph volt./Ph.cu)*sin(ATAN(X/R))
: (33 x 1000 x sin(ATAN(28.2))
sqrt(3) x 25000
Xs : 0.762 ohm
Source Resistance Rs : (Ph volt./Ph.cu)*cos(ATAN(X/R))
: (33 x 1000 x cos(ATAN(28.2))
sqrt(3) x 25000
Rs : 0.027 ohm
Delta Char Angle : 87.97deg
Source Impedance : (Rs + j Xs)
: 0.0270 + j 0.7620
Zs : 0.7625 L 87.97 deg
Line Details
21.00 Km
Zs + ZL = (0.027+j0.762) + (4.3302+j6.0522 )
= 4.357 +j 6.814
= 8.0882 L 57.40 deg
= 33/1.732 = 2355.676 A
8.088 ohm
= 2.356 KA
= 2.83 KA
IdUnre = IdUnre1
CT Ratio
IdUnre = 2.83 KA
1200 /1A
= 2.356 A
Line Impedance
Calculated Sec Impedance Zsec = N x Z prim in ohm Where Zprim = Primary Impedance in ohm
Line Impedance secondary = Line Impedance primary x N
= 7.442 L 54.42 x 4.181
= 31.11 ohm
Select Line Angle = 54 deg for convenience
Therefore set Line Impedance and Line Angle:
= 31.11 L 54 deg ohm
Umin = 29700 V
= 71.077 * 0.85
Rloadmin Secondary = 60.4 ohm
= 31.78 + 3
= 34.78 deg
= 35 deg
1.4
(Arc Resistance) Rarc = (28710 x L) / If
RFPPmin Rarc
If = Maximum expected phase-phase fault current (A);
L = Maximum phase conductor separation (m); = 5 m
Rarc = Arc resistance, calculated from the van Warrington formula (W).
To cover max. fault resistance IF = V / Ztot
Ztotal = 2 (Zs+ZL)
= 2(Rs+R1) +j 2(Xs+X1)
= 8.7144 +j 13.6284
= 16.18 L 57.40 deg
= 16.176 L 57.4
As per relay manual Phase resistive reach should be less than 3 time reactance part of the impedance
reach of that zone
Setting of Resistive reach zone1 3 . X1 = 64.5 ohm
RFPP1 = 51.63 ohm
As per relay manual resistive reach should be less than 4.5 time reactance part of the impedance
reach of that zone
Setting of Resistive reach zone1 4.5 . X01 = 96.8 ohm
RFPE1 = 77.44 ohm
Setting of Resistive reach reverse zone4 4.5 . X04 < 39.9 ohm
= 39.85 ohm (should be more than Rarc)
= atan (X1L+XN)
(R1L+RN)
XN = (X0L-X1L)/3
RN = (R0L-R1L)/3
X1L = 25.304
R1L = 18.105
X0L = 25.304
R0L = 18.105
XN = 0
RN = 0
= 54.445 deg
Resistive reach
In the same way as for phase-to-earth fault, the reach is automatically calculated based on the
setting of X1. The reach will be X1/tan(60°) =X1/SQR(3).
System Details
CT RATIO : 1200 / 1 A
Voltage Rating : 33kV
max full load current : 1000 A Considered 80% breaker rating
51 settings:
- 51 is the Time delayed non-directional relay
- 51 is used as a back up protection for downstream faults. Therefore the operating time depends on
the operating time of the T/F HV overcurrent protection & Bus Tie
- The pickup characteristics should be more than the maximum operating load of the Line
- A pickup settinq of 120 % of the maximum operating load of the Line is proposed.
Maximum load on the line = 1000 A Considered 80% breaker rating
Pickup setting : = 1.20 x Max load current
( 51P Current Set ) = 1.20 x 1000
= 1200 A (CT primary)
= 1.00 A (CT Secondary)
(I> Current Set ) = 1.00 of In
Characteristics = IEC Norm Inverse
Plug Setting Multiplier (PSM) for 51 relay = Fault Current / Pickup Current
= 25000 / 1200 = 20.84
PSM for TR 51LV relay = 20.00 (Note: If calculated PSM>20, then PSM=20)
Required operating time = = Grading margin + operating time of OG feeder relay
= 400 + 877
Required operating time = 1277 ms
To achive this operating time, TMS setting has to set as follows
1.277 = 0.14 / {(PSM)0.02 -1} x TMS
1.277 0.14 20.00 0.02 0.57
Therefore TMS = ( / ) x {( ) -1} =
Recommended Setting:
Pickup setting : = 0.5 x fault Current
= 0.5 x 25000
= 12500 A (CT primary)
= 10.41 A (CT Secondary)
( As no co-ordination is required with downstream relays)
Recommended Time Settinq = 0.2 s
Characterstics IEC Def Time
Summarising (50 ABC)
( I>> Function ) ON
( I>> Current Set ) 10.41 xIn
( I>> Characterstics ) IEC Def Time
( I>> Time Delay ) 0.2 S
51N settings:
- 51 N is the Time delayed non-directional Earth Fault relay
- 51 N is used as a back up protection for downstream earth faults. Therefore the operating time
depends on the operating time of the T/F HV O/C & Bus section relays
- The pickup characteristics should be more than the standing unbalance current
as seen by the system and the CT's. This has to be checked at site during commsg.
As an assumption, this standing unbalance may be taken as 30% of the max load current
Plug Setting Multiplier (PSM) for 51 relay = Fault Current / Pickup Current
= 25000 / 300 = 83.34
PSM for TR 51LV relay = 20.00 (Note: If calculated PSM>20, then PSM=20)
Required operating time = = Grading margin + operating time of OG feeder relay
= 400 + 469
Required operating time = 869 ms
To achive this operating time, TMS setting has to set as follows
0.869 = 0.14 / {(PSM)0.02 -1} x TMS
0.869 0.14 20.00 0.02 0.39
Therefore TMS = ( / ) x {( ) -1} =
Summarising (51N)
( I0> Function ) ON
( I0> Current Set ) 0.25 xIn
( I0> Characterstics ) IEC Norm Inverse
( I0> TMS ) 0.39
50N settings:
- 50N is the Instantaneous non-directional Earthfault protection relay
- 50N is used as a back up high speed protection . This will be in addition to the protection
offered by the line protection
- A pickup settinq of 50 % of the maximum operating load of the Line is proposed.
ECOMM= POTT, hence the POTT scheme is enabled, below Setting are recommendedfor Current reversal and Weak end in-
Setting Parameter Setting Range Setting Remarks
Z3RBD (Zone 3 reverse block time delay (cycles)) 3 TBC
EBLKD (Echo block time delay (cycles)) 10 TBC
ETDPU (Echo time delay pickup (cycles)) 2 TBC
EDURD ( Echo duration time delay 10 TBC
EWFC (Weak infeed trip) Y, N, SP N TBC
PT1 (General permissive trip received) SELOGIC equation INxxx Depending on
EPTDIR (Enable directional element Y, N N