Model GPY + GPU: Technical Data Submittal Document

Uploaded by

am953297
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
197 views18 pages

Model GPY + GPU: Technical Data Submittal Document

Uploaded by

am953297
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Project:

Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
Model GPY + GPU
Full Service Reduced Voltage
Wye-delta Open
Electric Fire Pump Controller
with Automatic Power Transfer Switch

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers


covered under our standard offering. Actual AS BUILT
drawings may differ from what is shown in this package.
August 2020
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

3L3 1M T3
From Automatic Power
3L2 T2
Transfer Switch*
3L1 T1

M
CR4
1M 2M T5
CR5 1S T4
2M
T6
CR5 2M
3L1
1S
1S

3L2

Built to NFPA 20 (latest edition)


• UL218 - Fire Pump Controllers
Underwriters Laboratory (UL)
• UL 1008 - Automatic power transfer switches for fire pump controllers
Standard,
Listings, FM Global Class 1321/1323
Approvals and New York City Accepted for use in the City of New York by the Department of Buildings
Certifications Seismic Certification See page 7 for details
Optional
CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
□ Standard: NEMA 2
Optional
□ NEMA 12 □ NEMA 4X-304 sst painted □ IP54
□ NEMA 3 □ NEMA 4X-304 sst brushed finish □ IP55
Enclosure □ NEMA 3R □ NEMA 4X-316 sst painted □ IP65
□ NEMA 4 □ NEMA 4X-316 sst brushed finish □ IP66
Accessories Paint Specifications
• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle • Glossy textured finish

*Please see Disconnecting Means details on page 3

This is a Marketing document. Please consult factory if additional information is required.


August 2020 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

Shortcircuit 200V to 208V 220V to 240V 380V to 415V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)

Standard 100kA
5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
Optional 150kA

Standard 50kA 200 (149) 250 (186) 350 - 450 (261 - 335) 450 - 500 (335 - 373)
5 - 500 (3.7- 373)
Optional 100kA N/A N/A 350 - 500 (261 - 373) 450 - 500 (335 - 373)

Optional 200kA 5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A

Ambient Standard: Optional:


Temperature
Rating
□ 4°C to 40°C / 39°F to 104°F □ 4°C to 55°C / 39°F to 131°F
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.
Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
Service Entrance
Suitable as service entrance equipment
Rating

Emergency Start • Flange mounted • Integrated limit switch


Handle • Pull and latch activation • Across the line start (direct on line)
• Operate shunt trip to open circuit breaker
Locked Rotor
• Factory set at 600% of motor full load current
Protector
• Trip between 8 and 20 seconds
Electrical • Voltage phase to phase (normal power)
Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (standard display at 0-300PSI)
• Externally mounted with protective cover

This is a Marketing document. Please consult factory if additional information is required.


August 2020 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)


• Power available • Deluge valve start • Pump on demand/Automatic start
• Motor run • Remote automatic start • Pump room temperature (ºF or ºC)
Visual Indications
• Periodic test • Remote manual start • Lockout
• Manual start • Emergency start
Visual only
• Alternate lock rotor current • Motor trouble • Pump on demand
• Alternate power phase reversal • Phase reversal (normal power) • Pump room alarm
• Automatic transfer switch trouble • Overcurrent • Service required
• Control voltage not healthy • Overvoltage • Undercurrent
• Invalid cut-in • Phase loss L1 • Undervoltage
• Lock rotor current • Phase loss L2 • Check weekly test solenoid
Visual & Audible
• Loss of power • Phase loss L3 • Weekly test cut-in reached
Alarms
• Low ambient temperature • Phase unbalanced
• Low water level • Pressure transducer fault detected

Visual and Audible


• ACB in OFF or tripped
• Alternate IS tripped/open
• Fail to start

DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Common pump room alarm (field re-assignable)**
• Overvoltage
• Undervoltage
Remote Alarm • Phase unbalance
Contacts • Low pump room temperature
• High pump room temperature
• Common motor trouble (field re-assignable)**
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
• Free (field programmable)**

**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.

This is a Marketing document. Please consult factory if additional information is required.


August 2020 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

• Embedded microcomputer with software PLC logic


ViZiTouch V2 • 7.0” color touch screen (HMI technology)
Operator Interface • Upgradable software
• Multi-language
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPx
• Start on pressure drop
Automatic Start • Remote start signal from automatic device
• Deluge valve start
• Start pushbutton
Manual Start • Run test pushbutton
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer ***
• Minimum run timer ***(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

***Can only be used if approved by the AHJ

This is a Marketing document. Please consult factory if additional information is required.


August 2020 Manufacturer reserves the right to modify this information without notice 5
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

Surge Suppression Surge arrestor rated to suppress surges above line voltage
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
• Operate shunt trip to open circuit breaker
Locked Rotor
• Factory set at 600% of motor full load current
Protector
• Trip between 8 and 20 seconds
• Alternate (emergency) isolating switch in the OFF position
• Alternate (emergency) voltage phase to phase
Visual Indications
• Transfer switch in normal position
• Transition timers
• Transfer switch trouble
• Alternate power phase reversal
Visual Alarms • Alternate isolating switch open/tripped
• Alternate circuit breaker open/tripped
• Alternate side locked rotor current
Transfer switch test pushbutton
Automatic Power Bypass for re-transfer and generator shutdown
Transfer Switch
Electrically operated and mechanically held in the normal or alternate position
Provision for manual operation
Remote Alarm Contacts
SPDT-8A-250VAC
• Isolating switch in the OFF position
• Transfer switch in normal position
• Transfer switch in alternate (emergency) position
Time Delays
• Momentary normal power outage override (factory set at 3 sec - field adjustable 1 to 3 sec)
• Alternate (emergency) power available delay (factory set at 3 sec - field adjustable 1 to 3 sec)
• Transfer trouble delay (factory set at 20 sec - field adjustable 1 to 60 sec)
• Retransfer to normal (factory set at 5 min - field adjustable 1 to 20 min)
• Generator cooldown (factory set at 5 min - field adjustable 1 to 20 min)
Voltage Sensing
• Transfer to alternate (normal power dropout) 85% of nominal - field adjustable 0 to 100%
• Phase reversal transfer to alternate
• Retransfer to normal (normal power pickup) 90% of nominal - field adjustable 0 to 100%
Audible Alarm (AIS Open)
4” alarm bell - 85 dB at 10ft. (3m)
Generator Start Connection
SPDT-8A-250V.AC

This is a Marketing document. Please consult factory if additional information is required.


August 2020 6
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 15014
A Tobalski Watkins Affiliate
Company
Mounting
Rigid base and wall mounting
details
Seismic
Building Test Seismic AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria Parameters
SDS z/h IP
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016

RRS for Nonstructural Components Testing


10.0
Spectral Response Acceleration (g)

1.0

0.1
0.1 1.0 10.0
Frequency, f (Hz)

Horiz. Level 1 Vert. Level 1

Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
• OSHPD Special Seismic Certification Preapproval (OSP)

This is a Marketing document. Please consult factory if additional information is required.


August 2020 Manufacturer reserves the right to modify this information without notice 7
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

A4 Flow switch provision High water reservoir level c/w visual indication
C18
and alarm contact (DPDT)
Foam pump application w/o pressure
A8
transducer and run test solenoid valve. C19 Emergency start alarm contact (DPDT)
A9 Low zone pump control function C20 Manual start alarm contact (DPDT)
A10 Middle zone pump control function C21 Deluge valve start alarm contact (DPDT)
A11 High zone pump control function C22 Remote automatic start alarm contact (DPDT)
Non-pressure actuated controller w/o pressure C23 Remote manual start alarm contact (DPDT)
A13
transducer and run test solenoid valve
High pump room temperature alarm contact
Lockout/interlock circuit from equipment C24
A16 (DPDT)
installed inside the pump room
Second set of standard alarm contacts (DPDT)
Built in alarm panel (120V.AC supervisory C25
(Typical for city of Los Angeles and Denver)
power) providing indication for:
• Audible alarm & silence pushbutton for motor Additional visual and alarm contact (Specify
B11 Cx
run, phase reversal, loss of phase. function) (DPDT)
• Pilot lights for loss of phase & supervisory Low suction pressure transducer for fresh
power available D1 water rated at 0-300PSI with visual indication
Built in alarm panel same as B11 but 220- and alarm contact
B11B
240VAC supervisory power Low suction pressure transducer for sea water
High motor temperature c/w thermoster relay D1A rated at 0-300PSI with visual indication and
B19A alarm contact
and alarm contacts (DPDT)
High motor temperature c/w PT100 relay and Pressure transducer and run test solenoid
B19B D5 valve for fresh water rated for 0-500PSI (for
alarm contacts (DPDT)
factory calibration purposes only)
Ground fault alarm detection c/w visual
B21 Pressure transducer and run test solenoid
indication and alarm contact (DPDT) D5D
valve for sea water rated for 0-500PSI
C1 Extra motor run alarm contact (DPDT)
D10 Omit mounting feet (when applicable)
C4 Periodic test alarm contact (DPDT)
High withstand rating for:
C6 Low discharge pressure alarm contact (DPDT) • 200V to 208V @ 150HP max. = 150kA*
• 200V to 208V @ 200HP = 100kA*
Low pump room temperature alarm contact
C7 • 220V to 240V @ 200HP max. = 150kA*
(DPDT)
• 220V to 240V @ 250HP = 100kA*
Low water reservoir level alarm contact D13
C10 • 380V to 415V @ 300HP max. = 150kA*
(DPDT) • 380V to 415V @ 350HP to 450HP = 100kA*
High electric motor temperature alarm contact • 440V to 480V @ 400HP max. = 150kA*
C11 • 440V to 480V @ 450HP to 500HP = 100kA*
(DPDT)
• 600V @ 500HP max. = 100kA*
High electric motor vibration c/w visual
C12 High withstand rating for:
indication and alarm contact (DPDT)
• 200V to 208V @ 150HP max. = 200kA*
Pump on demand / automatic start alarm
C14 D13B • 220V to 240V @ 200HP max. = 200kA*
contact (DPDT)
• 380V to 415V @ 300HP max. = 200kA*
C15 Pump fail to start alarm contact (DPDT) • 440V to 480V @ 400HP max. = 200kA*
C16 Control voltage healthy alarm contact (DPDT) D14 Anti-condensation heater & thermostat
Flow meter valve loop open c/w visual
C17 D14A Anti-condensation heater & humidistat
indication and alarm contact (DPDT)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory if additional information is required.


August 2020 8
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

Anti-condensation heater & thermostat & L01 Other language and English (bilingual)
D14B
humidistat
L02 French
D15 Tropicalization
L03 Spanish
D18 CE Mark with factory certificate
L04 German
Modbus with RTU frame format and RS485
D26
connection L05 Italian
Motor heater connection (external single L06 Polish
D27 phase power source and heater on/off
contact) L07 Romanian
Motor heater connection (internal single L08 Hungarian
D27A phase power source and heater on/off
contact) L09 Slovak
D28 Customized drawing set L10 Croatian
Field programmable I/O board - L11 Czech
D34A
5 Input / 5 output
L12 Portuguese
Redundant pressure transducer for fresh
D36
water rated for 0-500PSI L13 Dutch
Redundant pressure transducer for sea L14 Russian
D36A
water rated for 0-500PSI
L15 Turkish
E1 Permanent load shedding contacts
L16 Swedish
Temporary pump motor start period load
E2
shedding contacts L17 Bulgarian
Temporary & permanent load shedding L18 Thai
E3
contacts
Anti condensation heater & thermostat L19 Indonesian
F2
(alternate power section) L20 Slovenian
Anti condensation heater & humidistat
F2A L21 Danish
(alternate power section)
Anti condensation heater & thermostat & L22 Greek
F2B
humidistat (alternate power section) L23 Arabic
High withstand rating for (model GPU only) :
F6 L24 Hebrew
• 208V to 480V=150kA • 600V=100kA
L25 Chinese

Additional Options:

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory if additional information is required.


August 2020 Manufacturer reserves the right to modify this information without notice 9
Technical Data
Model GPY + GPU Electric Fire Pump Controller
with Automatic Power Transfer Switch

ViZiTouch V2 Operator Interface


®

PMS 295 PMS 361 Noir

Home

2 3

9
5 6 7 8

1 - Color touch screen 3 - Screen protector


2 - Onscreen menu 4 - Power LED (3 colors)
• HOME page 5 - START button
• ALARM page 6 - STOP button
• CONFIGURATION page 7 - TRANSFER SWITCH TEST button
• HISTORY page 8 - RUN TEST button
• SERVICE page 9 - USB port
• MANUAL page
• LANGUAGES page

This is a Marketing document. Please consult factory if additional information is required.


August 2020 10
Manufacturer reserves the right to modify this information without notice
Electric Fire Pump Controller Model: GPA/GPP/GPY
With Automatic Transfer Switch +GPU
Dimensions Built to the latest edition of the NFPA 20 standard

Sensing Line Connection - 1/2 " F.NPT

Drain - 3/8 " M.TUBE

Normal
Emergency
Power and
Power
Motor Leads
Voltage / Power Table Entrance
Entrance

Voltage Min HP Max HP

208 75 125 Notes:


220 - 240 75 125
- Standard NEMA: NEMA 2
- Standard paint : textured red RAL 3002.
380 - 400 - 415 150 200 - All dimensions are in inches [millimeters].
- Center of ViZiTouch screen: 61-5/8" [1564] from Bottom.
440 - 480 200 250 - Bottom conduit entrance through removable gland plate recommended.
- Use watertight conduit and connector only.
600 200 350 - Protect equipment against drilling chips.
- Door swing equal to door width.
- Seismic mounting to be rigid wall and base only.
Drawing for information only. Projection
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
3. Revised HP 24/01/19
Approved
2. New Logo 10/05/18 GPX-DI362 /E
1. Box Size Revision and Valve Change 21/11/17 CDL
Electric Fire Pump Controller
Reduced Voltage / Wye-Delta (Open Transition)
Model: GPY+GPU
With Automatic Transfer Switch
Wiring schematic Built to the latest edition of the NFPA 20 standard

1L3 2L3 3L3


See
1L2 2L2 3L2
GPU
1L1 2L1 Drawing 3L1

White

White

White
Black

Black

Black
17
3L3 64 66 68
3L2 65 67 69
18 20 3L1

4 2 3L1 19 21
To J2-J3-J4 To J76

2
1
3L2
NO NO +
C J40 J14 AI4
Motor Run C
TB1
NC NC -
2
1

NO NO +
C J42 J15 AI3
Power Available C
TB2
NC NC -
2
1

NO NO +
C J37 J16 AI2
Phase Reversal C
TB3
NC NC -
2
1
Red
NO NO +
C J39 J17 AI1
White
Pump Room Alarm C
TB4 Black
NC NC -
2
1
NO
NO LS1-1
C J41 LS1
Motor Trouble C
TB5 J54 LS1-2
NC NC
2
1
NO J20 UP
NO
C J55 See
(Field Programmable) C
TB6
NC J8 DOWN GPU
NC
Drawing
Black - +
J46 Red
AB
Remote Manual Start IN1

SV1-1 Brown
SV
Lockout IN2 J43 SV1-2 Blue

Remote Automatic Start J1* IN3

4
Deluge Valve J45
J2* IN4 ST 2
J25
Water Reservoir Low IN5
J44 24V in

IN6 24V out 3L2


X1 H2
1
IN7 J47 24VAC 3 X2 H1
3L1
IN8
NC
J36 CR4-1
C
CR4 CR4-2
NO

NC
J38 CR5-1
C
CR5 CR5-2
NO

GF

69
L3 68
J76 67
67
L2 66 To CT1-CT2-CT3 Legend

65 1M-2M Contactors
1S Contactor
L1 64
AB Alarm Bell
CB Circuit Breaker
CR Control Relay

J53 CT Current Transformer


EB Electric I/O Board
IS Isolating Switch
J Jumper
J4 L3 3L3 LS Limit Switch
PT Pressure Transducer
SA Surge Arrester

J3 ST Shunt Trip
L2 3L2 To 3L1-3L2-3L3
SV Solenoid Valve
VMB ViZiTouch Main Board
XTR Transformer
J2 L1 3L1

Drawing for information only.


* Remove jumper to use this feature Manufacturer reserves the right to modify this drawing without notice.
** Contact closes when emergency start is in "ON" position Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
2 Update Logo 23/04/18
Approved
1 Removed (fail safe) text from Power Available relay 20/02/17 GPY-WS610 /E
0 First issue 10/11/16 CDL
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing for Isolating Switch Built to the latest edition of the NFPA 20 standard
Power Terminals
3 Phases Notes:
Bonding Incoming Power 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
Ground 2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
L1 L2 L3
IS1

COPPER CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
5 " (127 mm) 8 " (203 mm)
Space

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (300 to 500) 1x (500) 2x (4/0 to 500) 2x (250 to 500) 2x (400 to 600) -------- -------- -------- -------- -------- --------

220 to 240 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
2x (400 to 600)
380 to 416 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (300 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (500 to 600) 2x (600) --------
2x (400 to 500)
440 to 480 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

ALUMINUM CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm) 10 " (254 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0 to 250) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 250) 1x (4/0 to 250) 1x (250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
1x(500) 90°C or
208 1x (400 to 500) 2x (300 to 500) 2x (350 to 500) 2x (600) -------- -------- -------- -------- -------- --------
2x(4/0 to 250) **

220 to 240 1x (350 to 500) 1x (500) 2x (250 to 500) 2x (300 to 500) 2x (500) 2x (600) 90°C * -------- -------- -------- -------- --------
1x (350) ** 2x (500 to 600)
380 to 416 1x (3/0 to 250) 1x (250) 1x (400 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (400 to 500) 2x (600) 90°C * 2x (600) 90°C * --------
N/A ** 2x (500)
1x (300) ** or
440 to 480 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (500) 2x (250) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (600) 2x (600) 90°C *
1x (250) 90°C *
600 1x (1 to 1/0) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 1x (500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
2 Revised logo 18/06/18
Approved
1 General Revision (added AL coverage) 10/07/17 GPX-TD602 1/2 /E
0 First issue 16/03/17 CDL
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing For GPP,GPY & GPW Built to the latest edition of the NFPA 20 standard

Notes:
Motor Terminals 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
2M 1M 2M 1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
T7 T8 T9 T1 T2 T3 T6 T4 T5 T1 T2 T3

M M
Model : GPP Models : GPW & GPY

COPPER CONDUCTORS for Motor Connection (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (2 to 3/0) 1x (1 to 2/0)

220 to 240 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 2/0)

380 to 416 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0)

440 to 480 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2)

600 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (2/0 to 3/0) 1x (3/0 to 300) 1x (250 to 300) 2x (1/0 to 300) 2x (3/0 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (1/0 to 2/0) 1x (3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (4/0 to 350) -------- -------- -------- -------- --------

380 to 416 1x (4 to 2/0) 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 350) 2x (4/0 to 350) --------

440 to 480 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300) 2x (3/0 to 350) 2x (4/0 to 350)

600 1x (6 to 2) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (250 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300)

ALUMINUM CONDUCTORS for Contactor (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (4 to 1/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0)

220 to 240 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (2 to 2/0) 1x (1 to 2/0) 1x (1/0 to 2/0)

380 to 416 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (3 to 1/0)

440 to 480 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2)

600 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (3/0) Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (2/0) 90°C * Consult Factory 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (300 to 350) -------- -------- -------- -------- --------

380 to 416 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (1/0 to 2/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (250 to 300) 2x (300 to 350) 2x (300 to 350) --------

440 to 480 1x (3 to 2/0) 1x (2 to 2/0) 1x (2/0) 90°C * 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 350) 2x (300 to 350)

600 1x (4 to 2) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * Consult Factory 2x (3/0 to 300) 2x (4/0 to 300)

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
2 Revised logo 18/06/18
Approved
1 General Revision (added AL coverage) 10/07/17 GPX-TD602 2/2 /E
0 First issue 16/03/17 CDL
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing Built to the latest edition of the NFPA 20 standard

Control Terminals (EB1) Remote Alarm Terminals (EB1)


Terminals Wire Size: Terminals Wire Size:
24 - 12 AWG 24 - 12 AWG
0.5 Nm 0.5 Nm

Normally open
2

NO
Normally closed Closes to alarm C
Opens to alarm NC
Remote Manual Start Close to start pump IN1 J25 Motor Run J40
Normally open
1
TB1
NO
Normally closed Closes to alarm
C
Opens to alarm NC

Normally open
2

NO
Normally closed Closes to alarm C
Opens to alarm NC
Lockout Close to block start IN2 J25 Power Available J42
Normally open
1
TB2
NO
Normally closed Closes to alarm C
Opens to alarm NC

Normally open
2

NO
Normally closed Closes to alarm
C
Opens to alarm NC
Remote Automatic Start Open to start pump J1* IN3 J25 J37
Phase Reversal Normally open
1
TB3
NO
Normally closed Closes to alarm C
Opens to alarm NC

Normally open
2

NO
Normally closed Closes to alarm C
Opens to alarm NC
Deluge Valve Open to start pump J2* IN4 J25 Pump Room Alarm ** J39
Normally open
1
TB4
NO
Normally closed Closes to alarm C
Opens to alarm NC

Normally open
2

NO
Normally closed Closes to alarm C

Alarm Inputs (EB1) Motor Trouble **


Opens to alarm NC
J41
Normally open
1
TB5
Terminals Wire Size: NO
24 - 12 AWG Normally closed Closes to alarm
C
0.5 Nm Opens to alarm NC

Normally open
2

NO
Normally closed Closes to alarm C
Opens to alarm NC
Water Reservoir Low Close to signal alarm IN5 J25 (Field Programmable ***) J55
Normally open
1
TB6
NO
Normally closed Closes to alarm C
Opens to alarm NC

Network Connection (VMB1)


Shielded Female Connector RJ45

Modbus TCP/IP

* Remove jumper to use this feature Drawing for information only.


** Re-assignable Manufacturer reserves the right to modify this drawing without notice.
*** Not available on GPS models Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
2 Revised logo 18/06/18
Approved
1 General Revision (added AL coverage) 10/07/17 GPX-TD603 /E
0 First issue 16/03/17 CDL
Automatic Transfer Switch Model: GPU
For Electric Fire Pump Controller
Terminal Diagram and Sizing Built to the latest edition of the NFPA 20 standard
Power Terminals
3 Phases
Incoming Power
Bonding
Ground
Notes:
1 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.

AL1 AL2 AL3

AIS1

COPPER CONDUCTORS for Isolating Switch (AIS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals AL1 - AL2 - AL3
Bending
Space 5 " (127 mm) 8 " (203 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
12 " (305 mm) 16 " (406 mm)
Space

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (300 to 500) 1x (500) 2x (4/0 to 500) 2x (250 to 500) 2x (400 to 600) -------- -------- -------- -------- -------- --------

220 to 240 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
2x (400 to 600)
380 to 416 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (300 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (500 to 600) 2x (600) --------
2x (400 to 500)
440 to 480 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

ALUMINUM CONDUCTORS for Isolating Switch (AIS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals AL1 - AL2 - AL3
Bending
5 " (127 mm) 8 " (203 mm) 10 " (254 mm)
Space

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0 to 250) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 250) 1x (4/0 to 250) 1x (250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
1x(500) 90°C or
208 1x (400 to 500) 2x (300 to 500) 2x (350 to 500) 2x (600) -------- -------- -------- -------- -------- --------
2x(4/0 to 250) **

220 to 240 1x (350 to 500) 1x (500) 2x (250 to 500) 2x (300 to 500) 2x (500) 2x (600) 90°C * -------- -------- -------- -------- --------
1x (350) ** 2x (500 to 600)
380 to 416 1x (3/0 to 250) 1x (250) 1x (400 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (400 to 500) 2x (600) 90°C * 2x (600) 90°C * --------
N/A ** 2x (500)
1x (300) ** or
440 to 480 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (500) 2x (250) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (600) 2x (600) 90°C *
1x (250) 90°C *
600 1x (1 to 1/0) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 1x (500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
** Consult Factory Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
3 Revised logo 18/06/18
Approved
2 General Revision (added AL coverage) 10/07/17 GPU-TD600 1/2 /E
1 Added terminal ratings 10/05/17 CDL
Automatic Transfer Switch Model: GPU
For Electric Fire Pump Controller
Terminal Diagram and Sizing Built to the latest edition of the NFPA 20 standard

Remote Alarm Terminals (TSB1)


Terminals Wire Size:
24 - 12 AWG
0.5 Nm

Closes when Tr. Sw. NO


in Alternate Position

A Pos.
Tr. Sw. in alternate position Opens when Tr. Sw. C
is in alternate position NC
Closes when Tr. Sw. NO
in Normal Position

N Pos.
Opens when Tr. Sw. J39
Tr. Sw. in normal position C

is in normal position NC
Opens when ACB1 NO
is in OFF or Tripped

ACB
Closes when ACB1 C
ACB1 in OFF or tripped is in OFF or tripped NC

Control Terminals (TSB1)


Terminals Wire Size:
24 - 12 AWG
0.5 Nm

Normally open NO
Closes to start generator

GEN
Generator Set Normally closed C J39
Opens to start generator NC

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
3 Revised logo 18/06/18
Approved
2 General Revision (added AL coverage) 10/07/17 GPU-TD600 2/2 /E
1 Added terminal ratings 10/05/17 CDL