Data sheet 3RM1201-1AA04

Reversing starter, 3RM1, 500 V, 0 - 0.12 kW, 0.1 - 0.5 A, 24 V DC, screw
terminals

product brand name SIRIUS


product category Motor starter
product designation Reversing starter
design of the product with electronic overload protection
product type designation 3RM1
General technical data
trip class CLASS 10A
equipment variant according to IEC 60947-4-2 3
product function Reversing starter
● intrinsic device protection Yes
● for power supply reverse polarity protection No
suitability for operation device connector 3ZY12 Yes
insulation voltage rated value 500 V
overvoltage category III
surge voltage resistance rated value 6 kV
maximum permissible voltage for safe isolation
● between main and auxiliary circuit 500 V
● between control and auxiliary circuit 250 V
shock resistance 6g / 11 ms
vibration resistance 1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz
operating frequency maximum 1 1/s
mechanical service life (switching cycles) typical 30 000 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 03/01/2017
product function
● direct start No
● reverse starting Yes
product function short circuit protection No
Electromagnetic compatibility
EMC emitted interference according to IEC 60947-1 class A
EMC immunity according to IEC 60947-1 Class A
conducted interference
● due to burst according to IEC 61000-4-4 3 kV / 5 kHz
● due to conductor-earth surge according to IEC 2 kV
61000-4-5
● due to conductor-conductor surge according to IEC 1 kV
61000-4-5
● due to high-frequency radiation according to IEC 10 V
61000-4-6
field-based interference according to IEC 61000-4-3 10 V/m

3RM12011AA04 Subject to change without notice


7/8/2022
Page 1/5 © Copyright Siemens
electrostatic discharge according to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
conducted HF interference emissions according to Class B for the domestic, business and commercial environments
CISPR11
field-bound HF interference emission according to Class B for the domestic, business and commercial environments
CISPR11
Safety related data
protection class IP on the front according to IEC IP20
60529
touch protection on the front according to IEC 60529 finger-safe
Main circuit
number of poles for main current circuit 3
design of the switching contact Hybrid
design of the switching contact as NO contact for OUT, electronic, 24 V DC, 15 mA
signaling function
adjustable current response value current of the 0.1 ... 0.5 A
current-dependent overload release
minimum load [%] 20 %; from set rated current
type of the motor protection solid-state
operating voltage rated value 48 ... 500 V
relative symmetrical tolerance of the operating 10 %
voltage
operating frequency 1 rated value 50 Hz
operating frequency 2 rated value 60 Hz
relative symmetrical tolerance of the operating 10 %
frequency
operational current
● at AC at 400 V rated value 0.5 A
● at AC-3 at 400 V rated value 0.5 A
● at AC-53a at 400 V at ambient temperature 40 °C 0.5 A
rated value
ampacity when starting maximum 4A
operating power for 3-phase motors at 400 V at 50 Hz 0 ... 0.12 kW
Inputs/ Outputs
input voltage at digital input
● at DC rated value 24 V
● with signal <0> at DC 0 ... 5 V
● for signal <1> at DC 15 ... 30
input current at digital input
● for signal <1> at DC 11 mA
● with signal <0> at DC 1 mA
number of CO contacts for auxiliary contacts 1
operational current of auxiliary contacts at AC-15 at 3A
230 V maximum
operational current of auxiliary contacts at DC-13 at 1A
24 V maximum
Control circuit/ Control
type of voltage of the control supply voltage DC
control supply voltage at DC rated value 19.2 ... 30 V
relative negative tolerance of the control supply 20 %
voltage at DC
relative positive tolerance of the control supply 25 %
voltage at DC
control supply voltage 1 at DC rated value 24 V
operating range factor control supply voltage rated
value at DC
● initial value 0.8
● full-scale value 1.25
control current at DC
● in standby mode of operation 25 mA
● when switching on 150 mA
● during operation 70 mA
inrush current peak
● at DC at 24 V 300 mA

3RM12011AA04 Subject to change without notice


7/8/2022
Page 2/5 © Copyright Siemens
● at DC at 24 V at switching on of motor 140 mA
duration of inrush current peak
● at DC at 24 V 80 ms
● at DC at 24 V at switching on of motor 80 ms
power loss [W] in auxiliary and control circuit
● in switching state OFF
— with bypass circuit 0.6 W
● in switching state ON
— with bypass circuit 1.68 W
Response times
ON-delay time 60 ... 90 ms
OFF-delay time 60 ... 90 ms
Power Electronics
operational current
● at 40 °C rated value 0.5 A
● at 50 °C rated value 0.5 A
● at 55 °C rated value 0.5 A
● at 60 °C rated value 0.5 A
Installation/ mounting/ dimensions
mounting position vertical, horizontal, standing (observe derating)
fastening method screw and snap-on mounting onto 35 mm standard mounting rail
height 100 mm
width 22.5 mm
depth 141.6 mm
required spacing
● with side-by-side mounting
— forwards 0 mm
— backwards 0 mm
— upwards 50 mm
— downwards 50 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— backwards 0 mm
— upwards 50 mm
— at the side 3.5 mm
— downwards 50 mm
Ambient conditions
installation altitude at height above sea level maximum 4 000 m; For derating see manual
ambient temperature
● during operation -25 ... +60 °C
● during storage -40 ... +70 °C
● during transport -40 ... +70 °C
environmental category during operation according to IEC 3K6 (no ice formation, only occasional condensation), 3C3 (no salt
60721 mist), 3S2 (sand must not get into the devices), 3M6
relative humidity during operation 10 ... 95 %
air pressure according to SN 31205 900 ... 1 060 hPa
Communication/ Protocol
protocol is supported
● PROFINET IO protocol No
● PROFIsafe protocol No
product function bus communication No
protocol is supported AS-Interface protocol No
Connections/ Terminals
type of electrical connection screw-type terminals for main circuit, screw-type terminals for control
circuit
● for main current circuit screw-type terminals
● for auxiliary and control circuit screw-type terminals
wire length for motor unshielded maximum 100 m
type of connectable conductor cross-sections

3RM12011AA04 Subject to change without notice


7/8/2022
Page 3/5 © Copyright Siemens
● for main contacts
— solid 1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
— finely stranded with core end processing 1x (0,5 … 4 mm²), 2x (0,5 … 1,5 mm²)
● at AWG cables for main contacts 1x (20 ... 12), 2x (20 ... 14)
connectable conductor cross-section for main
contacts
● solid or stranded 0.5 ... 4 mm²
● finely stranded with core end processing 0.5 ... 4 mm²
connectable conductor cross-section for auxiliary
contacts
● solid or stranded 0.5 ... 2.5 mm²
● finely stranded with core end processing 0.5 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid 1x (0,5 ... 2,5 mm²), 2x (1,0 ... 1,5 mm²)
— finely stranded with core end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1 mm²)
● at AWG cables for auxiliary contacts 1x (20 ... 14), 2x (18 ... 16)
AWG number as coded connectable conductor cross
section
● for main contacts 20 ... 12
● for auxiliary contacts 20 ... 14
UL/CSA ratings
operating voltage at AC
● according to UL rated value 480 V
● according to CSA rated value 400 V
Certificates/ approvals
General Product Approval EMC

Confirmation

Declaration of
Test Certificates other Railway
Conformity

Type Test Certific- Confirmation Special Test Certific-


ates/Test Report ate

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RM1201-1AA04
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RM1201-1AA04
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RM1201-1AA04
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RM1201-1AA04&lang=en

3RM12011AA04 Subject to change without notice


7/8/2022
Page 4/5 © Copyright Siemens
last modified: 6/21/2022

3RM12011AA04 Subject to change without notice


7/8/2022
Page 5/5 © Copyright Siemens