Station and Telecontrol Engineering
SICAM A8000 Series – Description
Description
The SICAM A8000 device series has been designed for lots of
different tasks, both simple and complex. Its area of application
spans the entire energy-supply chain. Customer requirements
such as IT security, scalability, flexible communication, space-
saving design, and the ability to be used in harsh conditions
were taken into account when the SICAM A8000 was being
designed. The modular SICAM A8000 series offers optimized
solutions for all kinds of performance requirements.
SICAM A8000 – Module Types
• Processor modules (up to a max. of 34 interfaces)
• Power-supply modules (DC 24 V to 60 V; DC 110 V to 220 V;
2.2 AC 230 V)
• Ethernet or serial communication expansion modules
• Interface modules for a max. of 16 expansion lines
• Binary inputs (DC 24 V; DC 48/60 V; DC 110 V; DC 220 V)
• Binary outputs (DC 24/48/60/110/220 V; AC 110/230 V)
[ph_SICAM A8000_5 devices, 1, --_--]
• Analog inputs (-20 mA/+20 mA; -10 V/+10 V; Pt 100)
Figure 2.2/1 SICAM A8000 Devices
• Analog outputs (-20 mA/+20 mA; -10 mA/+10 mA; -10 V/
+10 V)
• CP-8022: 3 x RJ45 (2 x Ethernet, 1 x RS232), 1 x RS485,
• Current/voltage inputs (1 A/5 A; LoPo; 230 V) 1 x RS232/RS485 (selectable), 1 x GPRS
The universally applicable binary or analog input/output • CP-8031: 4 x RJ45 (2 x Ethernet, 1x RS485, 1 x RS232)
modules can be plugged in any order and are suitable for even
the tightest spaces as they have a module width of 30 mm.
• CP-8050: 4 x RJ45 (2 x Ethernet, 1 x RS232, 1 x RS485), up to
12 x Ethernet or 30 x serial with CI modules
Benefits • IEC 60870-5-101/-103/-104, Modbus RTU/TCP
• They can also be used in harsh ambient temperatures due to • IEC 61850 Ed1/Ed2 client & server incl. GOOSE
the extended temperature range of -40 °C to +70 °C • DNP3 serial master/slave, TCP/IP
• The increased EMC stability of up to 5 kV (IEC 60255) qualifies • Other protocols on request
the devices for direct use in switchgears Auxiliary Voltages
• Simple engineering with the integrated Web parameterization • DC 24 V to 60 V (12 W or 45 W)
tool and the SICAM Device Manager
• It meets the most stringent cybersecurity requirements due to • DC 110 V to 220 V (12 W or 45 W)
an integrated crypto chip and IPSec encryption • AC 230 V (45 W)
• It is a safe investment as international standards such as • Can be redundant
IEC 61850 IEC 60870-5-101/-103/-104 etc. are followed. Inputs and outputs
• The modular platform offers a variety of application options • CP-8000: max. 116 I/O with up to 6 I/O modules
and reduces warehousing.
• CP-8021, CP-8022, CP-8031: max. 128 I/O with up to 8 I/O
• Adaptation to existing communication infrastructures with a modules
multitude of interfaces and the integrated GPRS module
• CP-8050: max. 2048 I/O with up to 16 expansion lines for
• The integrated short-circuit indicator functionality enables use every 8 I/O modules
in power-system monitoring.
Real-Time Clock
• You can save time and money as installation and maintenance
are really simple – plug & play • +/- 2 ppm, time synchronization using NTP protocol, SNTP
protocol
Device Characteristics
Electromagnetic Compatibility
Communication Interfaces and Protocols
• IEC 60870-2-1, IEC 61010, IEC 60255-5, IEC 61000-4, EN
• CP-8000: 3 x RJ45 (2 x Ethernet, 1 x RS232), 1 x RS485 55022, CE marking
• CP-8021: 3 x RJ45 (2 x Ethernet, 1 x RS232), 1 x RS485
28 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Series – Description
Temperature Range Example 1: High power and interfaces for complex tasks
• CP-8021, CP-8022: From -40 °C to +70 °C • Automation tasks in power distribution and transmission,
microgrids
• CP-8031, CP-8050: From -25 °C to +70 °C 7
Housing Specifications • Control and turbine regulation in hydropower plants
• Plastic housing for DIN rail mounting • Transformer control and regulation
• Dimensions of the CP-8000: 128 mm x 124 mm x 123 mm • Control and communication in railway power supply
(W/H/D) • Redundant communication gateway for different networks
and protocols
• Dimensions of the CP-8021/22/31/50, CI, power-supply
module and I/O modules: 30 mm x 132 mm x 124 mm Example 2: Everything at a glance with on-site compact solution
(W/H/D) • Use in distribution-system automation
Special Features • Optimized for use in MS switchgear
2.2
• Integrated display and function keys for CP-8000 • Power-flow control available
• Integrated Web server for configuration and diagnostics with Example 3: Without display, dimensioned to be space-saving
CP-8000/21/22, engineering using the SICAM Device Manager with slim PCB assembly
and SICAM TOOLBOX II for the A8000 series
• Network connection of solar and wind farms
• Data storage using an SD memory card (parameters and • Control and monitoring of power and gas distribution stations
device firmware)
• Freely programmable user programs according to IEC 61131-3 • Simple gateway function
• Device redundancy with CP-8050
• The security requirements of the future:
– Compliance with the BDEW white paper
– Integrated crypto chip
– TLS encryption
– IPSec encryption
– HTTPS protocol
– Security Logbook
Additionally for CP-8031 and CP-8050:
– Integrated software firewall
– Firmware signature
– Role-based access control
– Configurable system functions
– Hardware-based application layer firewall for
IEC 60870-5-104
– Automated certificate handling via the EST protocol with
SICAM Grid Pass
Fields of Application
The SICAM A8000 has virtually limitless scalability and can be
expanded at any time due to the various power levels in the
processor modules, interface modules, and the I/O modules. The
area of application for the SICAM A8000 series extends from
distribution-system automation, via the connection of renew-
able energies (wind, solar, hydro), right up to railway power
supply and industrial applications.
The I/O modules are pluggable in any order. With a module
width of 30 mm, they are suitable for even the most minimal
spatial conditions and are scalable and extendable at any time in
an almost infinitely variable manner.
7 -40 °C on request
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 29
Station and Telecontrol Engineering
SICAM A8000 Series – Fields of Application
SICAM A8000 with HSR, PRP – Ethernet Redundancy Parallel Redundancy Protocol (PRP)
Protocols for Optimal Availability
PRP is a redundancy protocol to support seamless redundancy
In order to satisfy the requirements of important time-sensitive (= no reconfiguration times in case of a failure in one of the
applications, the latest High Availability Seamless Redundancy networks). The layer-2 redundancy process was developed for
(HSR) and Parallel Redundancy Protocol (PRP) Ethernet redun- automation networks which require a high degree of availability
dancy systems have been developed in line with the latest IEC for continuous operational function.
62439-3 standard.
All data is transmitted simultaneously via 2 independent
The seamless PRP and HSR redundancy solutions are available networks (LAN A and LAN B) with the PRP structure.
for the entire Siemens SICAM A8000, SIPROTEC 4, SIPROTEC
Topology, performance, and latency can differ in the case of
Compact, SIPROTEC 5, and Reyrolle 7SR2x series.
both networks, however, the latencies must only differ up to a
High Availability Seamless Redundancy (HSR) certain upper limit. As shown in the figure, the 2 networks may
not be connected to one another.
HSR is a redundancy protocol for lossless, redundant transmis-
2.2 sion of data via Ethernet networks in ring topologies and offers The advantage of PRP compared to other protocols is that if a
redundancy without changeover times. communication is interrupted in a network, a seamless switch-
over takes place. Data losses are therefore avoided.
Every device in the network is connected via 2 Ethernet inter-
faces. The notifications are sent to both interfaces and therefore
transmitted in both directions in the ring simultaneously. 2 iden-
tical notifications arrive at the target (in a healthy state) within a
time frame. The 1st one is forwarded to the application whilst
the 2nd is discarded. The ring is monitored by cyclical HSR
management telegrams (cycle time of 2 seconds). An open ring
is signalized by a warning.
[dw_SICAM-A8000_config, 1, en_US]
Figure 2.2/3 PRP Structure
Configuration notes
[dw_SICAM-A8000_with_HSR_IEC61650-ring, 1, en_US]
• Dual Attached Nodes (DAN)
Figure 2.2/2 SICAM A8000 with HSR Devices which are connected to both networks. An interface is
available for every network connection.
Configuration notes • Single Attached Nodes (SAN)
• HSR can only be used with the CI-8520 Ethernet interface Devices which are connected to a single network via an inter-
module. face.
• Only one HSR ring is permitted per CI-8520 module. • Virtual Double Attached Nodes (VDAN)
VDANS are devices which only have one interface, but are
• The selection of the 2 interfaces for the HRS ring per CI-8520 connected to both networks via a redundancy box (RedBox).
module is arbitrary.
• HSR mode must be activated on the CI-8520 Ethernet inter- • PRP can only be used with the CI-8520 Ethernet interface
module
face in use.
Advantages
• A maximum of 512 MAC addresses are permitted per HSR
ring. • Maximum network reliability, seamless reconfiguration
• Process can be easily configured
30 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Series – Fields of Application
• Minimal wiring effort due to the use of efficient ring struc-
tures
• Cost-efficient structures
• Easily expandable by integrating additional HSR rings
• Guaranteed interoperability, standardized in IEC 62439
• Full compatibility between IEC 61850 Editions 1 and 2 as well
as all other Ethernet protocols
2.2
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 31
Station and Telecontrol Engineering
SICAM A8000 Series – Fields of Application
RetroFit with SICAM A8000 - Ready for IP Technology and
Cybersecurity by Replacing Parts
Fast and secure communication of telecontrol systems is the key
to secure, reliable electrical energy systems in today's highly
complex electrical power systems.
SICAM A8000 offers the option of fully and “securely” enjoying
the advantages of new IP technology.
Also, the whole system has components from the SICAM MIC or
TM1703MIC series.
After replacing the master control and power-supply modules,
the available telecontrol systems for the latest SICAM A8000 CP
and PS modules, your plant is now ready for integration into the [ph_SICAM A8000 devices, 1, --_--]
2.2 IT network and is optimally secured against cyber attacks. Figure 2.2/5 SICAM A8000 Devices
[ph_A8000_CP8050_Retrofit, 1, --_--]
Figure 2.2/4 SICAM A8000-CP8050 Retrofit
The free firmware updates means that, in terms of cyberse-
curity, it demonstrates the high standard expected from
Siemens. These downloads are available in our SIOS portal.
Replacement of the SICAM EMIC (CP-6010) with the associated
power-supply module (PS-66xx) results in free space of 129 mm
on the DIN rail. This can be used to expand with a max. of 2 TM-
IO modules.
Advantages
• Cybersecurity requirements in line with BDEW Whitepaper,
NERC CIP, and IEC 62351 with support for RADIUS, Syslog,
IPSec, and TLS
• Cost-effective upgrading of your telecontrol stations and
adapting to the latest technology
• Continued use of available TM/IO modules, resulting in less
need for spare parts
• Quick retrofitting due to minimal intervention in the existing
wiring
• Use of existing communication lines
• Power-supply modules for almost every auxiliary voltage
• Parameterization via SICAM TOOLBOX II, SICAM WEB, or
SICAM Device Manager
32 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Series – Fields of Application
SICAM A8000 + SIMATIC HMI – Compact, Flexible Telecontrol
and Automation System Which Can Be Combined with
SIMATIC HMI Panel
The area of application for the SICAM A8000 series extends from
distribution-system automation, via the connection of renew-
able energies (wind, solar, hydro), right up to railway power
supply and industrial applications. The fields of application
become considerably more varied in connection with the
SIMATIC HMI Panel
The SIMATIC HMI Panel offers a modern touch-panel solution on
WinCC and satisfies all requirements for HMI tasks even under
rough conditions. A unique feature is the project engineering
via SIMATIC WinCC in the TIA portal, with which the user can
benefit from previously unheard-of levels of engineering effi- 2.2
ciency.
[sc_SICAM A8000_LEDs, 1, --_--]
Examples of the visualization options include representation of
current status indications (inputs/outputs) of the coupled SICAM Figure 2.2/7 SICAM A8000 Modules with Visualized LEDs
A8000 modules in graphical format of “LEDs” or switching
objects on the one hand, and the logging of information in
event and alarm lists on the other hand.
[sc_SICAM A8000_Event List, 1, --_--]
Figure 2.2/8 Event List
[dw_SIMATIC-HMI-panel_and_SICAM-A8000, 1, en_US]
Figure 2.2/6 Connection of SIMATIC HMI to a SICAM A8000
Advantages
• Scalable from 4” to 22”, with touchscreen
• High end performance for demanding HMI applications even
in case of limited space
• High screen resolution, performance, and functionality
• RTU and panel are also designed for more demanding oper-
ating conditions
• WinCC project engineering in the new TIA portal environment
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 33
Station and Telecontrol Engineering
SICAM A8000 Series – Modules
Module Combinations You can get an overview of the different module types in the
following tables.
The SICAM A8000 series is a module combination of a power
supply, processor, and extensions, and is used for various tasks
such as control, telecontrol, automation, and communication. System Components and Technical Data
The SICAM A8000 CP-8000 compact device combines power For additional system components and technical data, refer to
supply, display with function key, as well as binary inputs and the current manual: Industry Online Support
outputs.
Module dimensions (L x W x H): 124 mm x 30 mm x 132 mm
(dimensions without DIN rail)
2.2
Compact Device CP-8000
Dimensions (W x H x D) 132 mm x 30 mm x 142 mm
Temperature range -40 °C to +70 °C
Input voltage DC 18 V to 78 V incl. tolerance
Interfaces 2 x Ethernet LAN
1 x RS232
1 x RS485 (galvanically separated)
Storage SD card up to 2 GB
Max. number of data points 20000
Special features Integrated power supply
12 DI and 8 DO integrated
Max. 116 I/O (max. 6 expansion modules)
4 function keys and display
Table 2.2/1 Compact Device
34 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Series – Modules
Processor Module CP-8021 CP-8022 CP-8031 CP-8050
Temperature range -40 °C to +70 °C -25 °C to +70 °C 8 -25 °C to +70 °C 8
Max. number of interfaces 3 x RJ45: 3 x RJ45: 4 x RJ45: 4 x RJ45:
2 x Ethernet/1 x RS232 2 x Ethernet/1 x RS232 2 x Ethernet 2 x Ethernet
1 x RS485 1 x RS232/RS485 can 1 x RS485 (serial) 1 x RS485 (serial)
be selected
1 x RS232 (serial) 1 x RS232 (serial)
1 x RS485
30 x serial (modular)
1 x GPRS
12 x Ethernet 2.2
(modular)
Storage SD up to 2 GB SD up to 4 GB SD up to 4 GB
Data points 20000 400000
Distributed archive Available
Device redundancy – – Yes Yes
Automation function (CFC/PLC, IEC 61131-3) 1 x 128 kB 1 x 128 kB 1 x 3 MB 5 x 3 MB
Table 2.2/2 Processor Modules
Power-supply modules PS-8620 PS-8622 PS-8640 PS-8642
Input voltages DC 24 V to 60 V, 12 W DC 110 V to 220 V, 12 W DC 24 to 60 V, 45 W DC110 to 220 V, 45 W
AC 100 to 240 V, 45 W
Output voltage 1 DC 5.15 V ± 2 % static, ± 3 % dynamic DC 5.15 V ± 2 % static, ± 3 % dynamic
Output current 1 0 A to 1.8 A 0 A to 2 A
Output voltage 2 DC 28.0 V ± 10 % static, ± 3 % dynamic DC 28.0 V ± 0 % static, ± 3 % dynamic9
Output current 2 0 A to 0.43 A 0 A to 1.79 A
Output voltage 3 – – DC 24 V + 0 %/ -15 %
Output current 3 – – 0.42 A
Table 2.2/3 Power-Supply Modules
8 -40 °C on request
9 for the generation of auxiliary voltage for specific transmission devices
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 35
Station and Telecontrol Engineering
SICAM A8000 Series – Modules
Communication Modules CI-8520 CI-8522 CI-8551
Communication redundancy function HSR, PRP, RSTP, line mode HSR, PRP, RSTP, line mode Tri-state mode to serial inter-
faces
Interface 5 Ethernet/LAN interfaces 5 Ethernet with 2 x SFP modules 2 x serial RS232
(optical/electrical) and 3 x
1 x serial RS485/422
sockets for electr. TP cables
2 x serial RS232/485/422
The engineering tools (SICAM TOOLBOX II and SICAM WEB) can
also be connected for programming the CP-8050.
2.2
Max. number of expansion modules 2 2 6
Operating voltage DC 28 V input DC 28 V input DC 28 V input
DC 25.2 V to 30.8 V; 2.5 W DC 25.2 V to 30.8 V; 4.5 W DC 25.2 V to 30.8 V
Table 2.2/4 Communication Modules – Only Used in Conjunction with CP-8050
Digital Input Module DI-8110 DI-8111 DI-8112 DI-8113
Inputs 16 binary inputs
2 groups each with 8 inputs
Rated voltage DC 24 V DC 48 V/60 V DC 110 V DC 220 V
Input circuits DC 18 V to 31.2 V DC 36 V to 78 V DC 82.5 V to 143 V DC 165 V to 253 V
Operating voltage DC 4.75 to 5.5 V
Current consumption 0.9 mA to 4.8 mA at 0.5 mA to 2.5 mA at 0.4 mA to 1.4 mA at 0.3 mA to 0.7 mA at
18 V to 31.2 V 36 V to 78 V 82.5 V to 143 V 165 V to 253 V
Table 2.2/5 Digital Input Modules
Digital Output Module DO-8212 DO-8221 DO-8230
Outputs 8 relay outputs (4 groups of 2) 12 relay outputs (1 group) 16 digital outputs (2 groups of 8)
Galvanic separation
Rated voltage DC 24 V to 220 V; AC 110/230 V DC 24/48/60/110/220 V10, AC DC 24 V to 60 V
230 V
10 DC 110/220 V as of CC production status
36 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Series – Modules
Digital Output Module DO-8212 DO-8221 DO-8230
Max. continuous current Standard wiring 1A Standard wiring
• 8 outputs, each max. 3 A (5 A/ • 16 outputs, each max. 0.5 A
1 min)
Wiring with derating at 5 A
• 2 outputs, each with a max. of
5A
• 6 outputs, each with a max. of 2.2
2A
or
• 4 outputs, each with a max. of
5A
• 4 outputs, each with a max. of
0 A (relay must not be acti-
vated)
46 power increase
• 4 outputs, 6 A each (max. DC
24 V +20 %; max. AC 230 V
+10 % 11
Switching power Direct voltage DC min. 50 mW at 5 V 1000 VA; 4 A at DC 250 V, L/R ≤ 40 • 78 W at DC 78 V (with power
Alternating voltage Max. 1250 VA; 5 A/AC 250 V, resis- ms12 800 VA; 3.25 A at AC 250 V, increase)
tive load cos φ ≤ 0.4 • 30 W at DC 60 V
Max. 500 VA; 2 A/AC 250 V, cos φ
• 24 W at DC 48 V
= 0.4
• 12 W at DC 24 V
Power supply Operating voltage DC 4.75 to 5.5 V DC 4.75 V to 5.5 V DC 4.75 V to 5.5 V
Power consumption 800 mW • 2 W during command output 500 mW
• 1.3 W in idle state
Table 2.2/6 Digital Output Modules
11 With a parallel connection
12 DO-8221 supports the IEC 60947-4-1 usage category for DC. DC-supported category: DC-1,3,5,6 from IEC 60747-4-1 Table 10.
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 37
Station and Telecontrol Engineering
SICAM A8000 Series – Modules
Analog Output Module AO-8380
4 outputs (4 groups of 1) All outputs galvanically separated
Current output Max. ± 20 mA to max. 500 Ω load
Max. ± 10 mA to max. 1 kΩ load
Voltage output Max. ± 10 V to min. 1 kΩ load
Resolution 0.025 % at ± 20 mA, mA to 10 mA, V to 10 V
Accuracy 0.3 % at +25 °C
0.4 % at 0 °C to +50 °C
2.2
0.7 % at -20 °C to +70 °C
0.8 % at -40 °C to +70 °C
Power supply Operating voltage DC 4.75 V to 5.5 V
The voltage is taken from the system bus.
Power consumption Max. 2200 mW
Table 2.2/7 Analog Output Module
Analog Input Modules AI-8310 AI-8320 AI-8330 AI-8340
4 analog inputs 2 groups, 2 inputs each 4 groups, each with 1 input 3 current measuring inputs 4 current inputs (250 V)
are galvanically separated
Galvanically separated Galvanically separated The current inputs are
by transformers, from each
galvanically separated by
Voltage between 2 inputs other, and from the logic
transformers, from each
of a group max. DC 600 mV voltage
other, and from the logic
voltage
Measuring range 40 Ω to 400 Ω (Pt100, Current measurement 300 V rated voltage 300 V rated voltage
Ni100) -20 mA to 0 mA to +20 mA
400 Ω to 4000 Ω (Pt1000) Voltage measurement
-10 V to 0 V to +10 V
Overrange current ~20 %,
voltage ~30 %
Resolution 10 mΩ (Pt100, Ni100) 0.004 % at ±20 mA 16 bits 16 bits
100 mΩ (Pt1000) 0.004 % at ±10 V
Noise rejection 16⅔ Hz, 50 Hz, 60 Hz 50 dB (50 Hz, 60 Hz,
16⅔ Hz)
Accuracy 0.19 % 0 °C to +50 °C 0.15 % at 25 °C
0.4 % 40 °C to +70 °C
Power supply DC 4.75 V to DC 5.5 V; DC 4.75 V to 5.5 V; max. DC 4.75 V to 5.50 V; DC 4.75 V to 5.50 V;
max. 500 mW 180 mW 300 mW 1400 mW
Table 2.2/8 Analog Input Modules
38 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Series – Modules
Analog Input Modules AI-8510 AI-8511
Properties • 3 low-power (LoPo) current • 3 low-power (LoPo) current
measuring inputs (225 mV) measuring inputs in conjunction
• 3 low-power (LoPo) voltage with adaptor module CM-8820
measuring inputs (3.25 V/√3) • 3 voltage measuring inputs (can
be set as 100 V/√3, 240 V, or
415 V/√3)
Inputs for measuring currents Input voltage at IN AC 225 mV based on IEC 60044-8
Max. input voltage AC 2.25 V
Rated frequency 50 Hz, 60 Hz (range between 45 Hz and 65 Hz) 2.2
Resolution 16 bits
Sampling 1 value/ms
Inputs for measuring voltages Input voltage UN AC 100 V/√3, AC 240 V, AC 415 V/ AC 3.25 V/√3 in accordance with
√3 in accordance with IEC 60044-7 IEC 60044-7
(parameterizable)
Max. measuring voltage 150 % UN (error condition)
Rated frequency 50 Hz, 60 Hz (range between 45 Hz and 65 Hz)
Resolution 16 bits
Sampling 1 value/ms
Internal consumption < 0.3 VA at VN = AC 240 V Internal resistance: 200 kΩ
< 0.02 VA at VN = AC 100 V/√3
Power supply Operating voltage DC 4.75 V to 5.5 V
Power consumption Max. 800 mW (typ. 625 mW)
Table 2.2/9 Analog Input Modules
LED module CM-8830
Power supply Operating voltage DC 4.75 V to 5.5 V
The voltage is picked off from the bus.
Power consumption 500 mW
Table 2.2/10 LED Module
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 39
Station and Telecontrol Engineering
SICAM A8000 Series – Modules
Current -transformer adaptor module CM-8820
Inputs for measuring currents Rated current IN 1 A/5 A (parameterizable)
Max. measuring current 200 % IN
Rated frequency 50 Hz, 60 Hz (Range between 45 Hz and 65 Hz)
Internal consumption < 0.1 W at IN = 1 A
< 0.3 at IN = 5 A
Thermal rating 10 A continuously
2.2 100 A 1 s
Outputs for measuring currents Rated voltage 225 mV at IN = 1 A based on IEC 60044-8 1.125 V at IN = 5 A
Max. voltage 2.25 V at IN = 10 A
Rated frequency 50 Hz, 60 Hz (Range between 45 Hz and 65 Hz)
Table 2.2/11 Current-Transformer Adaptor Module
Expansion Modules CI-8530 CI-8531 CI-8532 CI-8533
Power supply DC 24 V to 60 V DC 110 V to 220 V
Operating voltage DC 18 V to 78 V DC 82.5 V to 286 V
Input current 0.6/0.3/0.25 A (DC 24/48/60 V) 0.13/0.07 A (DC 110/220 V)
Output rated voltage 5.15 DCV ± 2 % static, ± 3 % dynamic
Output rated current 0 A to 1.4 A
Output power 7W
Interfaces 2 x Ethernet 2 x SFP plug-ins for optical 2 x Ethernet 2 x SFP plug-ins for optical
Ethernet Ethernet
2 x LC Multimode plug-ins 2 x LC Multimode plug-ins
are provided. are provided.
Special features Up to 8 I/O modules
Ethernet-based I/O bus support
Ring, star and daisy chain
Table 2.2/12 Expansion Modules
System Components and Technical Data
For additional system components and technical data, refer to
the current manual: Industry Online Support
40 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Series – Selection and Ordering Data
Selection and Ordering Data
Description Order No.
Compact Device
CP-8000 Compact device with display/incl. SD card 6MF2101-1AB10-0AA0
Communication interfaces 2 x Ethernet 1 x RS232, 1 x RS485
Power supply DC 24 V to 60 V
Temperature range -40 °C to +70 °C
12 DI (DC 24 V to 60 V)/8 DO relays (AC/DC max. 250 V)
Coupling
CM-6811 Coupling TM I/O module for CP-8000 6MF1113-0GJ11-0AA0
CM-6812 Coupling TM I/O adaptor 6MF1113-0GJ12-0AA0 2.2
CM-8811 Coupling SICAM I/O module for CP-8000 6MF2881-1AA00
Processor Modules
CP-8021 Processor module 3 x RJ45, 1 x RS485 6MF2802-1AA00
CP-8022 Processor module 3 x RJ45, 1 x RS485/RS485, 1 x GPRS 6MF2802-2AA00
CP-8031 Processor module 4 x RJ45 6MF2803-1AA00
CP-8050 Processor module 4 x RJ45, it can be expanded with CI-85xx 6MF2805-0AA00
Power-Supply Modules
PS-8620 DC 24 V to 60 V (12 W) 6MF2862-0AA00
PS-8622 DC 110 V to 220 V (12 W) 6MF2862-2AA00
PS-8640 DC 24 V to 60 V (45 W) 6MF2864-0AA00
PS-8642 DC 110 V to 220 V, AC 230 V (45 W) 6MF2864-2AA00
Communication Modules
CI-8520 Ethernet communication interface 6MF2852-0AA00
CI-8551 Communication interface serial 6MF2855-1AA00
Binary Inputs
DI-8110 2 x 8, DC 24 V, 1 ms 6MF2811-0AA00
DI-8111 2 x 8, DC 48 V to 60 V, 1 ms 6MF2811-1AA00
DI-8112 2 x 8, DC 110 V, 1 ms 6MF2811-2AA00
DI-8113 2 x 8, DC 220 V, 1 ms 6MF2811-3AA00
Binary Outputs
DO-8212 Binary output relay 8 x DC 24 V to 220 V/AC 230 V 6MF2821-2AA00
DO-8221 Secure command output 6MF2822-1AA00
DO-8230 DO transistor 6MC2823-0AA00
Analog Output
AO-8380 4 x, ±20 mA/±10 V 6MF2838-0AA00
Analog Inputs
AI-8310 Pt100/Ni100 (2 groups, each with 2 AI) 6MF2831-0AA00
AI-8320 4 x +/-20mA, +/-10 V 6MF2832-0AA00
AI-8330 3 x I(6 A) with AI-8340 6MF2833-0AA00
AI-8340 4 x V (250 V), 2 x DO 6MF2834-0AA00
AI-8510 3 x V (AC 100/ √3 V, AC 230 V, AC 400/ √3 V), 3 x I (LoPo) 6MF2851-0AA00
AI-8511 3 x V (LoPo), 3 x I (LoPo) 6MF2851-1AA00
Current-Transformer Adaptor Module
CM-8820 CT adaptor for AI-8510 3 x I 1 A/5 A, 225 mV 6MF2882-0AA00
LED Module
CM-8830 SICAM I/O module LED display 6MF2883-0AA00
Table 2.2/13 SICAM A8000 Series Selection and Ordering Data
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 41
Station and Telecontrol Engineering
SICAM A8000 Series – Selection and Ordering Data
Description Order No.
Continued from previous page
SICAM I/O Remote Modules
CI-8530 Ethernet expansion module for interfacing remote I/Os DC 24 V to 60 V 6MF2853-0AA00
CI-8531 SICAM I/O remote interface module F/O DC 24 V to 60 V 6MF2853-1AA00
CI-8532 Ethernet expansion module for interfacing remote I/Os DC 110 V to 220 V 6MF2853-2AA00
CI-8533 SICAM I/O remote interface module F/O DC 110 V to 220 V 6MF2853-3AA00
CM-8813 bus connector CP-8031/CP-8050 (this bus connector plug is included for CP-8031/ C53207-A5813-D481-1
CP-8050)
Licenses (OSD)
SICAM A8000 Extended processing 6MF2750-2EP00
SICAM A8000 IEC 104 firewall 6MF2750-2FW40
SICAM A8000 LXC container 6MF2750-2LX00
2.2
SICAM A8000 Redundancy 6MF2750-2RE00
SICAM A8000 Extended SICAM WEB DL 6MF2750-2WE00
SICAM Rack Solution, see Table 2.3/9
Spare Parts
CM-8812-bus connector plug SICAM I/O (this bus connector plug in included in all SICAM I/O C53207-A5812-D481-3
modules)13
CM-8813 bus connector CP-8031/CP-8050 (this bus connector plug is included for CP-8031/ C53207-A5813-D481-1
CP-8050)
Locking hook SICAM A8000 3 cm module13 C53207-A5014-D481-1
CM-0822 fieldbus interface star (4 x optical fiber) 6MF1111-0AJ22-0AA0
SD card 2 GB 6MF1213-AGA05-0AA0
SD card 512 MB (optional) 6MF1213-2GA05-0AA0
Temperature range -40 °C to 70 °C
Table 2.2/14 SICAM A8000 Series Selection and Ordering Data
13 Minimum order quantity: 10 units
42 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Rack – Description
Description
The SICAM A8000 rack solution offers the benefits of the proven
and powerful SICAM AK 3 in conjunction with the latest SICAM
A8000 platform.
Beside all the benefits offered by the SICAM A8000 CP-8050, the
rack solution goes the extra mile by allowing for a high level of
signal density to further widen its scope of applications. I/
O units in 19-inch format and the resulting small footprint
enable a wide variety of signals to be channeled into the
process.
Retrofit
By using the following components, existing legacy SICAM AK I/
O modules can easily be migrated into a SICAM A8000 rack solu-
tion and connected to a SICAM A8000 CP-8050 unit:
• SICAM CM-2843/44/46 I/O rack 2.3
• CI 2530 interfacing module
• PS-2630 or PS-2632 power-supply module
• CM-8846 adaptor for fitting the CP-8050 to a swing frame as [ph_SICAM A8000 Rack, 1, --_--]
necessary Figure 2.3/1 SICAM A8000 Rack
The following SICAM AK modules can continue to be used as
SICAM A8000 rack I/O units in conjunction with the CP-8050,
and are aligned with the product lifecycle of the SICAM A8000
CP-8050:
• SICAM DI-2112/13/14/15
• SICAM DO-2201
• SICAM DO-2210/11 incl. SM-2506
• SICAM AI-2300 incl. SM-057x
Legacy SICAM AK I/O units are also supported by the CP-8050
and can remain in operation:
• AI-2302/03
• DI-2100/10/11
• MX-2400
To continue using the process wiring of SICAM AK Ax racks, the
handle molds of the connector plugs are adapted and locked
into position in the new rack.
When the existing I/O rack does not comply with the specifica-
tions, it can easily be replaced – with all the wiring of the I/
O modules remaining in place! The same goes for the power
supply (refer to the manual for details).
Automation devices used in critical infrastructural areas are
subject to stringent requirements, also in terms of ever-evolving
cybersecurity. Thanks to the combination of the SICAM A8000
rack and the SICAM A8000 CP-8050, all safety features are state-
of-the-art and continuously improved.
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 43
Station and Telecontrol Engineering
SICAM A8000 Rack – Description
Technical Information and Combination Examples
• CM-8846 adaptor for swing-frame installation in a 19“ frame
(Figure 2.3/2)
• SICAM A8000 CI-2530: Connection interface to connect
SICAM I/O racks to a CP-8050 unit
• 1 x CI-2530 required per I/O rack
• One I/O rack can hold a total of 16 rack I/O modules
• Up to 4 I/O racks can be used
• Operating temperature -5 °C to +55 °C
• Singular of redundant power supply can be used for I/O racks [A8000_Rack_Solution_Config3_mixed_Line, 1, --_--]
supporting PS-2630 and PS-2632
Figure 2.3/4 SICAM A8000 Rack – Combination Example 2
2.3
[A8000_Rack_Swing frame mounting, 1, --_--]
Figure 2.3/2 SICAM A8000 Rack – Swing-Frame Mounting
[A8000_Rack_Solution_Config1_singular, 1, --_--]
Figure 2.3/3 SICAM A8000 Rack – Combination Example 1
44 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Rack – Modules
Power-Supply Modules PS-2630 PS-2632
Operating voltage DC 18 V to 78 V DC 82.5 V to 286 V
AC 90 V to 264 V
The 5 V output is galvanically separated and protected against continuous short-circuit
Output voltage DC 5.05 V (-1/+2 %)
Max. output voltage in case of a fault DC 6 V
Output rated current 0.5 A to 24 A 2.3
Output rated power (Pout) • 120 W at –5 °C to + 55 °C
• 120 W at +55 °C to + 70 °C
Reduction of power from + 55 °C: –10 %/3 °C
• 60 W at +70 °C
Table 2.3/1 SICAM A8000 Rack – Power-Supply Modules
I/O Remote Module CI-2530
Properties CI-2530 is an Ethernet expansion module for connecting remote rack I/Os. Up to
4 racks, each with up to 16 rack I/Os can be connected via the EbIO bus. Ring and line
topologies can be used.
• Communication with the master module CP-8050 via EbIO
• It can be installed in the CM-2846 rack
• Ethernet-connection status display via LED (LKx, PKx)
• Power supply via the bus-connector plug
• Module status display via LED (RY, ER)
• Master-module status display via LED (RY, ER)
• Rack assembly
Power supply Operating voltage DC 4.75 to DC 5.25 V
The voltage is picked off from the rack bus.
Power consumption Typ. 1.3 W
Table 2.3/2 SICAM A8000 Rack I/O Remote Module – Can only be Used in Conjunction with CP-8050
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 45
Station and Telecontrol Engineering
SICAM A8000 Rack – Modules
Rack I/O Modules DI-2112 DI-2113 DI-2114 DI-2115
Recording binary input signals
64 binary inputs, 8 additional inputs • 8 groups, 8 inputs and 1 additional input each
• Galvanic separation
• Each group has a reference potential and configurable polarity
• Sensor voltage monitoring via the auxiliary input of each group (optional)
Rated voltage DC 24 V DC 48 V to 60 V DC 110 V DC 220 V
2.3 Switching thresholds ≤ 12 V (logic "0"); ≥ 18 V ≤ 24 V (logic "0"); ≥ 36 V ≤ 55 V (logic "0"); ≥ ≤ 110 V (logic "0"); ≥
(logic "1") (logic "1") 82.5 V (logic "1") 165 V (logic "1")
Input circuits (operated with external voltage) DC 18 V to 31.2 V • DC 36 V to 70 V as DC 82.5 V to 143 V DC 165 V to 250 V
per EN 61010-1:2010
• DC 36 V to 60 V as
per
IEC 61010-1:2010/
AMD1:2016
Current consumption 1.4 mA to 5.2 mA (at 0.6 mA to 2.2 mA (at 0.4 mA to 1.1 mA (at 0.2 mA to 0.4 mA (at
18 V to 31.2 V) 36 V to 78 V) 82.5 V to 143 V) 165 V to 250 V)
Operating voltage DC 4.75 V to 5.25 V
The voltage is picked off from the rack bus.
Table 2.3/3 SICAM A8000 Rack I/O Modules – Can only be Used in Conjunction with CP-8050
I/O Module DO-2201
Properties • Processing and output according to IEC 60870-5-101/104
– Up to 40 single-point indications
• 40 digital outputs
• In terms of galvanic separation, the outputs are divided into 8 groups with 2 outputs
and 8 groups with 3 outputs
• The groups are galvanically separated from each other and within a group.
• The potential that should be switched (plus or minus) can be determined for each
output by external wiring.
• Any 2 outputs can be connected in parallel to increase switching capacity
• If an output short-circuits, it does not affect other outputs.
• Input function and status display via LEDs
Rated current (for resistive load) • 0.7 A at DC 24, 48, 60 V
• 1.0 can be achieved when connecting 2 outputs in parallel
Power supply Operating voltage DC 4.75 to DC 5.25 V
The voltage is picked off from the rack bus.
Power consumption type 0.6 W + 0.03 W for each active output
Table 2.3/4 SICAM A8000 Rack I/O Module – Can only be Used in Conjunction with CP-8050
46 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Rack – Modules
I/O Remote Module DO-2210 DO-2211
Properties • Processing and output according to IEC 60870-5-101/104
– Up to 32 pulse commands (2-pole) or
– Up to 64 pulse commands (1-pole 1 1/2 pole) or
– a combination thereof
– Secure command output
– Internal checks (IC1)
– Optional resistance check (RC1) via a SM-2506 measuring-circuit module that can
be installed 2.3
• 64 relay outputs (2 groups) plus
– 2 group outputs
– 4 pulse outputs
• Each group has a common potential.
• An intrinsic fuse circuit is produced for each group.
• The pulse outputs are current-limited via an electronic fuse.
• Input function and status display via LEDs
Max. contact voltage DC 24 V to 60 V + 30 % DC 24 V to 125 V + 20 %
Output circuits (operated with external voltage) • DC 18 V to 70 V as per EN 61010-1:2010 • DC 18 V to 150 V
• DC 18 V to 60 V as per IEC 61010-1:2010/
AMD1:2016
Rated switching capacity • 48 W/DC 24 V • 48 W/DC 24 V
• 96 W/DC 48 V • 96 W/DC 48 V
• 120 W/DC 60 V • 120 W/DC 60 V
• 250 W/DC 125 V
Operating voltage DC 5 V ± 5 %, typ. 1.0 W without SM-2506
typ. 1.6 W with SM-2506
+ 0.6 W during the command output
The voltage is picked off from the rack bus.
Table 2.3/5 SICAM A8000 Rack I/O Remote Module – Can only be Used in Conjunction with CP-8050
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 47
Station and Telecontrol Engineering
SICAM A8000 Rack – Modules
Rack I/O Modules AI-2300
For detection of analog values and counter pulses, as well as for the output of analog values
16 current inputs Max. ± 20 mA to 122.5 Ω burden
• Load voltage 2.45 V
• Overrange typ. 2 %
• Voltage between the inputs of a group max. DC 4 V
• Every 2 inputs form a group (8 groups)
2.3 • All inputs are galvanically separated from logic circuits and ground.
• The inputs of a group are not galvanically separated from each
other.
• The inputs of a group are galvanically separated from those of the
other groups and from the inputs/outputs of the input/output
modules.
Operating voltage DC 4.75 V to 5.25 V
The voltage is picked off from the rack bus.
Table 2.3/6 SICAM A8000 Rack I/O Modules – Can only be Used in Conjunction with CP-8050
48 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Rack – Modules
Submodules SM-0570 SM-0571 SM-0572 SM-0574
Overview 2 current inputs 2 resistance thermom- 2 analog outputs 2 pulse inputs
eter inputs
• Max. ± 20 mA to • The current or • Rated voltage DC 24
122.5 Ω burden • Pt100, Ni100 voltage output can V to 60 V
• Load voltage 2.45 V • Either 2-, 3- or 4- be selected for each • The pulse inputs can
• Overrange type 2 % phase technology submodule. be used as follows:
• Voltage between 2 • The inputs are • The measuring range – 2 counter inputs
inputs max. DC 4 V galvanically sepa- can be adjusted as – 1 counter input + 1 2.3
• All inputs are galvani- rated from logic follows with an control input
cally separated from circuits and ground. output current: • 1 counter input oper-
logic circuits and • The inputs are not – -20 mA to +20 mA ates 1 counter (pulse
ground. galvanically sepa- – -10 mA to +10 mA counting)
• The inputs are not rated from each – -5 mA to +5 mA – The counter has a
galvanically sepa- other. • The measuring range max. counter
rated from each can be adjusted as status of 24-bits
other. follows with and width
ouptut voltage: • The submodule func-
– -1 V to +1 V tions, which can be
– -10 V to +10 V operated autono-
mously, are operated
by way of a buffer
• This ensures that
counter functionality
and counter status
remain correct, even
in the event of a
voltage failure lasting
up to 72 hours
(counter pulse
frequency ≤ 50 Hz)
• The counter status is
either still correct or
marked as “lost” in
the event of a voltage
failure lasting longer
than 72 hours
Operating voltage DC 5 V ±5 %, typ. 0.6 W DC 5 V ±5 %, typ. 0.9 W DC 5 V ±5 %, typ. 1.5 W DC 5 V ±5 %
Table 2.3/7 SM-057x Submodules
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 49
Station and Telecontrol Engineering
SICAM A8000 Rack – Modules
Rack CM-2846
Power supply With power supply With redundant power supply
Overview The CM-2846 rack provides 17 slots for double Europe format assemblies. It has primarily
been designed for 19” (swing) frame installation, but it is also suitable for rear plate
mounting using the rear plate assembly set.
The rack (84 TE, 9 HE) can be equipped as follows (these components are not included in
the scope of delivery):
• 1 SICAM rack I/O remote module (CI-2530)
• Up to 16 SICAM rack I/O modules
2.3 – DI-2112, DI-2113, DI-2114, DI-2115
– DO-2201, DO-2210, DO-2211
– AI-2300, AI-2302, AI-2303
• 1 to 2 power-supply modules (PS-263x)
Properties • The installed rack I/O modules are connected to the EbIO, which is operated by exactly
1 master module (CP-8050/CPCi85), that may be redundant.
• Wiring peripherals using prefabricated peripheral cables CM-2890
• 2 slots for PS-263x power-supply modules
• ESD Earth Facility for connecting a ground strap when replacing a module
• Release tool included for assemblies
Slot for CI-2530 0
Slots for SICAM A8000 rack I/O modules 1 to 17
Slots for PS-263x • 1st power-supply module, left
• 2nd power-supply module, right
Operating voltage 5.1 V; supplied by the installed power-supply module PS-263x
Dimensions Height: 320 mm
Width: 483 mm
Depth: 258 mm (power-supply module is not installed)
Depth: 280 mm (power-supply module is installed)
Table 2.3/8 SICAM A8000 Rack – Can only be Used in Conjunction with CP-8050
50 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0
Station and Telecontrol Engineering
SICAM A8000 Rack – Modules
SICAM A8000 Module Rack CM-8846
The SICAM A8000 module rack CM-8846 allows you to install up
to 13 SICAM A8000 modules in one 19“ rack.
5 height units (222.25 mm) must be taken into account for the
module rack.
2.3
[dw_sicam_a8000_module-rack5, 1, --_--]
Figure 2.3/5 SICAM A8000 Module Rack CM-8846
System Components and Technical Data
For additional system components and technical data, refer to
the current manual: Industry Online Support
SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0 51
Station and Telecontrol Engineering
SICAM A8000 Rack – Selection and Ordering Data
Selection and Ordering Data
Description Order No.
Base Units
CP-8050 Master Module 6MF2805-0AA00
SICAM rack solution14
CM-2846 17-slot rack 6MF1113-0CJ46-0AA0
CM-28/46 Wall-mounting kit 6MF1313-0CH02-0AA0
CI-2530 SICAM rack I/O remote 6MF2253-0AA00
CI-2530 complete front cover 6MF2253-0FA00
CM-8846 SICAM A8000 module rack C53207-A5846-D481-1
CM-8813 CP-8031/CP-8050 bus connector (this bus-connector plug is included for CP-8031/CP-8050) C53207-A5813-D481-1
SICAM A8000 Rack – Power-Supply Modules
PS-2630 DC 24 V to 60 V 6MF1113-0CG30-0AA0
2.3
PS-2632 DC 110 V to 220 V, AC 230 V 6MF1113-0CG3-20AA0
SICAM A8000 Rack I/O Modules
DI-2112 Binary input 8x8, DC 24 VC,1 ms 6MF1013-0CB1-20AA0
Front cover DI-2112 6MF1313-0CA7-20AA0
DI-2113 Binary input 8x8, DC 48/60 V,1 ms 6MF1013-0CB13-0AA0
Front cover DI-2113 6MF1313-0CA73-0AA0
DI-2114 Binary input 8x8, DC 110 V.1 ms 6MF1013-0CB14-0AA0
Front cover DI-2114 6MF1313-0CA74-0AA0
DI-2115 Binary input 8x8, DC 220 V,1 ms 6MF1013-0CB15-0AA0
Front cover DI-2115 6MF1313-0CA75-0AA0
DO-2201 Binary output Trans 40x1, DC 24 V to 60 V 6MF1011-0CC01-0AA0
Front cover DO-2201 6MF1313-0CA76-0AA0
DO-2210 Command output DC 24 V to 60 V 6MF1011-0CC10-0AA0
Front cover DO-2210 6MF1313-0CA77-0AA0
DO-2211 Command output DC 125 V 6MF1011-0CC11-0AA0
Front cover DO-2211 6MF1313-0CA78-0AA0
AI-2300 Analog input 16x ±20 mA + 4x opt.IOM 6MF1011-0CD00-0AA0
AI-2300 front cover 6MF1313-0CA79-0AA0
Submodules
SM-0570 Analog input extension (2 x ±20 mA) 6MF1011-0AF70-0AA0
SM-0571 Analog value extension (2 x Pt100) 6MF1011-0AF71-0AA0
SM-0572 Analog output extension (2 x ±20 mA, ±1/10 V) 6MF1011-0AF72-0AA0
SM-0574 Counter input (2 x DC 24 V to 60 V) 6MF1011-0AF74-0AA0
SM-2506 M Measuring-circuit module command output DC 24 V to 60 V 6MF1011-0CF06-0AA0
Licenses (OSD)
SICAM A8000 Extended processing 6MF2750-2EP00
SICAM A8000 IEC 104 Firewall 6MF2750-2FW40
SICAM A8000 LXC Container 6MF2750-2LX00
SICAM A8000 Redundancy 6MF2750-2RE00
SICAM A8000 Extended SICAM WEB DL 6MF2750-2WE00
Accessories
CM-2890 Periphery cable crimp 5 m, 100-pole 6MF1313-1CJ00-0AA0
Handle mold for CM-2890 plug 6MF1313-0CA00-0AA1
Empty front cover 6MF1313-0CA86-0AA0
Table 2.3/9 SICAM A8000 Rack – Selection and Ordering Data
14 1x firmware license, order number 6MF2750-0EP00 is required for each SICAM I/O rack to allow you to use SICAM A8000 rack I/Os in conjunction with
SICAM A8000 CP-8050. A front cover is also required for each CI-2530.
52 SICAM ⋅ Station Automation ⋅ Catalog ⋅ Edition 5.0