ACS-WM 48VDC

Wall-Mount Switched-Mode Charger

• Modular switched-mode charger technology


• Accommodates up to four hot-swappable Cordex®
1.2kW power rectifier modules for N+1
redundancy capability
• Unity power factor with >93.9% efficiency
• Expandable to 100A output capacity
• Advanced communication capabilities
• Excellent DC output regulation
• High power density with a small compact enclosure
• High resolution touch screen color LCD display for
control and monitoring
Input Rectifier
Hi. Freq. Tx
AC Input Switched-mode Filtering
Power Conversion

Output Rectifier DC Output

The ACS-WM 48VDC charger is designed to charge all types of stationary batteries (flooded lead-
acid, VRLA and NiCad) for utility, petrochemical and industrial applications.
A compact 11RU enclosure accommodates up to four hot swappable, fan-cooled Cordex® 1.2kW rectifier modules. The ACS-WM 48VDC
charger possesses high power density, providing the most power in the least amount of wall space and requires only a single step process to
program using a touchscreen interface on the controller. Supported communication protocols include TCP/IP, Modbus, Ethernet, SNMP and
optional DNP3.

1
ACS-WM 48VDC Charger Specifications

Electrical Input Standard Features


Nominal Voltage: 176 to 276VAC (single-phase) •Full graphic LCD touch screen with virtual alphanumeric •Battery temperature compensation probe (24ft to 3/8in lug)
keyboards (480x272 pixels) •Thermal foldback/shutdown
Operating Voltage: 90 to 300VAC •High interrupting current input and output breakers (10kAIC) •AC low line foldback/shutdown
Extended Voltage: 90 to 175VAC and 277 to 300VAC (derated output power) •Reverse polarity protection •AV high voltage shutdown
•Current limit protection •Input transient protection (MOV)
Phase: Single •Soft start protection
Frequency: 45 to 70Hz
Communication Features
Nominal Current: 7.4A / 14.8A / 22.2A / 29.6A
•SNMP/Modbus via Ethernet TCP/IP (IPv4 or 6) •AC failure alarm
Power: 1.2kW / 2.4kW / 3.6kW / 4.8kW •Access web user interface via internet browser through •High/low voltage alarm
Ethernet port on CXC-HP controller •Charger failure alarm
Power Factor: >0.99 (50 to 100% load) •Common Form C alarm relay contacts •Ground fault alarm
THD: <5% at nominal input voltage up to 100% output •High voltage shutdown •DC output failure alarm

Efficiency: >93.9% (50 to 100% load) Standard Functions


Electrical Output •Automatic, scheduled or manual float charging (adjustable)
•Automatic, scheduled or manual equalize charging (adjustable)
Voltage: 42 to 58VDC •High/low voltage alarm setting (adjustable)
Control Functions: •Charge current limit (adjustable)
Current: 25A / 50A / 75A / 100A
•Automatic or manual battery testing
Load Regulation: Static <±0.5%; dynamic <±1% @ 40-90-40% load step change •Battery capacity and runtime prediction
•Temperature compensation
Line Regulation: Static <±0.1%; dynamic <±1%
•Minimum, maximum and average on input channels with date and time stamp
Transient Response: <±2% for 40 to 90% load step, 2ms recovery time Daily Statistics: •Battery current, rectifier current and AC mains voltage for prior 90 days
Ripple: <30mV rms battery eliminator On all events such as alarms, power on, any change of state of the digital inputs or other
Event Log: miscellaneous events
Mechanical Enclosure Rectifier Module
Battery Monitor: Battery test
Dimensions H × W × D (in/mm): 21.4 × 20 × 20.25 / 544 × 508 × 514 1.63 × 3.3 × 10.1 / 41.1 × 84.8 × 256.8
Options
Weight (kg/lbs): 43 / 95 1.76 / 3.9
DNP3+ communication protocol
Cabinet: NEMA 1 (black finish) NEMA 1 (black finish)

Environment Standards and Certifications

Operating Temperature: Forced cooling: −40 to 50°C (−40 to 122°F) •EN 60950
•CE EN 60950, CB Scheme
Extended Temperature: Module @ 65°C (149°F); derated output power @ >65°C (149°F) Safety: •Telcordia (Bellcore) GR-1089-CORE
Storage Temperature: −40 to 85°C (−40 to 185°F) •NEMA PE 5-1997 (R2003)

Humidity: 0 to 95% non-condensing


•EN 55022 (CISPR 22)
−500 to 3000m (−1,640 to 9843ft); derate @ −4°C/1000m above sea level •EN 61000-3-2 EN 61000-3-3
Elevation: (−7.2°F/3281ft) •EN 61000-4-2 EN 61000-4-3
•EN 61000-4-4 EN 61000-4-5
Audible Noise: <55dBa @ 1m (3ft) EMC: •EN 61000-4-6 EN 61000-4-11
Cooling: Forced •ETS 300 019-1-1 ETS 300 019-1-2
•ETS 300 753 IEC60950
MTBF: >400,000 hours •ICES-003 Class B FCC Part 15 Class B
•FCC Part 68
Heat Dissipation: <308 BTU per each rectifier module

ACSWM-HP 48VDC Part Numbers


With DNP3 Card: ACSWM-48-25-1 ACSWM-48-50-1 ACSWM-48-75-1 ACSWM-48-100-1
Without DNP3 Card: ACSWM-48-25-0 ACSWM-48-50-0 ACSWM-48-75-0 ACSWM-48-100-0
Voltage: 208 to 250VAC Voltage: 208 to 250VAC Voltage: 208 to 250VAC Voltage: 208 to 250VAC
AC Input: Phase: Single-phase Phase: Single-phase Phase: Single-phase Phase: Single-phase
Frequency: 50 to 60Hz Frequency: 50 to 60Hz Frequency: 50 to 60Hz Frequency: 50 to 60Hz
DC Output Voltage (V): 48 48 48 48
DC Output Current (A): 25 50 75 100

Alpha Technologies Services, Inc. USA: 3767 Alpha Way, Bellingham, WA 98226 Canada: 7700 Riverfront Gate, Burnaby, BC V5J 5M4
Toll Free North America: +1 800 322 5742 Outside US: +1 360 647 2360 Technical Support: +1 800 863 3364
For more information visit www.alpha.com
© 2020 Alpha Technologies Services, Inc. All Rights Reserved. Trademarks and logos are the property of Alpha Technologies Services, Inc., EnerSys 2
and its affiliates unless otherwise noted. Subject to revisions without prior notice. E. & O.E. 09/2020

You might also like