C9.8 - MAR 00 104133 CS 2315 02120 0001 - 03 - Stair - 01
C9.8 - MAR 00 104133 CS 2315 02120 0001 - 03 - Stair - 01
WIDT
H
(MIN)
150
STAIR STRINGER HANDRAIL (TYP)
STAIR STRINGER
200 (MAX)
6 THK CHQD PLT
PFC150x75x18
SHALL BE SHOP ASSEMBLED (TREAD)
PFC150x75x18
750/900/1200
PFC150x75x18
25
750/900/1200
25
35
50
DN UP
70
DN UP
SLOTTED HOLE 20
30 14X30 FOR
14 DIA HOLE M12 BOLT
FOR M12 BOLT 30 150
10 THK
300
END PLATE
STAIR STRINGER
PFC150x75x18
SECTION B
750/900/1200
(SCALE 1:5) -
(SCALE 1:25) -
CONCRETE FLOOR
(MIN)
WP
150
STAIR STRINGER STAIR STRINGER
2100
CL OF COLUMN SECTION A
(SCALE 1:25) -
300
FOR CONNECTION DETAILS
REFER STANDARD DRAWING NO.
MAR-00-104133-CS-2315-02120-0002
A WP
TOGR NOSING (REFER NOTE-13)
-
750/900/1200
C B
- WP TOGR
-
100
TYPICAL STAIR TREAD PLAN
10 P)
(T
(MIN) MAR-00-104133-CS-2315-02120-0002
Y
2100
2400 (MAX)
FOR HANDRAIL REFER
3200 (MAX)
STANDARD DRAWING NO.
MAR-00-104133-CS-2315-02122 TREAD
(TYP)
ONE RISER
0
IR
35
E
R
S
STRINGER
MIN EFFECTIVE 4480 (MAX) PFC260x75x28
WP (TYP)
WIDT
H EQUALLY PLACED TREAD TOP OF PLINTH
GRADE/HPP
EARTHING BOSS MIN EFFECTIVE
WP TOGR E (REFER NOTE 10)
LIN WIDT
H
NG (1000 FOR 750 WIDE STAIR)
SI (1000 FOR 900 WIDE STAIR)
NO
(1200 FOR 1200 WIDE STAIR)
FOR CONNECTION DETAILS
100 REFER STANDARD DRG NO. 1
EQUALLY PLACED RISER
10 )
3200 (MAX)
35
E
R
S
750/900/1200
IN FOR DETAIL OF FOUNDATION REFER STD
NOS C
L OF
DRG NO. MAR-00-104133-CS-2315-02120-0002 TOP WP
1 EQUALLY PLACED TREAD MIN EFFECTIVE 25 25 THIS DRAWING SHALL BE READ IN CONJUNCTION WITH
0002 WIDT
H DRG NO. MAR-00-104133-CS-2315-02120-0002
(1000 FOR 750 WIDE STAIR)
(1000 FOR 900 WIDE STAIR)
TYPICAL ELEVATION OF STEEL STAIR (TYPE-1) (1200 FOR 1200 WIDE STAIR)
(SCALE 1:25) (TYP) L50x50x6 (TYP)
C
L OF
BOT WP
5
(STIFFENING BRACES)
APPROVED FOR CONSTRUCTION
DETAIL OF STIFFENING BRACES
13.THE CHEQUERED PLATE NON-SKID NOSING SHALL BE PAINTED WITH YELLOW PAINT. (SCALE 1:25)
(BOTTOM PLAN OF STAIR)
12.ALL STAIR TREADS SHALL BE HOT DIP GALVANIZED AS PER ISO-1461.
11.COLUMN DETAILS WILL BE PROVIDED IN RESPECTIVE GA DRAWINGS. (BRACING APPLIES TO STAIR FLIGHTS WITH A VERTICAL
HEIGHT GREATER THAN 3200)
Petrofac 03 04-AUG-21 ASB WS/RMAKB/VP APPROVED FOR CONSTRUCTION
02 07-JUL-21 MUH WS/RMAKB/VP ISSUED FOR REVIEW
10.STAIR STRINGERS SHALL BE PROVIDED WITH EARTHING BOSS AS PER ELECTRICAL REQUIREMENT. Petrofac E&C Oman LLC. 01 30-MAY-21 MUH WS/RMAKB/VP ISSUED FOR REVIEW
9. MINIMUM 2100 MM HEADROOM CLEARANCE IS APPLICABLE FOR ALL TYPES OF STAIR ARRANGEMENTS.
(BRACING SHALL BE AT BOTTOM OF STRINGER)
Petrofac JOB NO - JI2046
8. A SINGLE STAIRWAY SHALL NOT HAVE MORE THAN 20 RISERS WITHOUT A CHANGE IN DIRECTION. STANDARD DRAWING - MAR-00-104133-CS-2315-02122-0001
7. THE MAXIMUM NUMBER OF RISERS IN A SINGLE FLIGHT SHALL BE NOT GREATER THAN 16, CLIMBING HEIGHT OF HANDRAILS FOR PLATFORMS 0002 & 0003 SOM000MM0612-AA
PCAP CONTROL ID # 000
INDIVIDUAL FLIGHT SHALL NOT EXCEED 3200mm. IF MORE RISERS ARE REQUIRED LANDING SHALL BE PROVIDED. STANDARD DRAWING - GRATING MAR-00-104133-CS-2315-02121-0001
6. RISERS SHALL BE NOT LESS THAN 180mm OR NOT MORE THAN 200mm HIGH. ARRANGEMENT AND DETAILS 1:10
STANDARD DRAWING-STEEL STRUCTURE - MAR-00-104133-CS-7880-02501-0001
MARMUL
5. ALL STRUCTURAL STEEL WORKS FOR STAIRWAYS SHALL BE PAINTED AS PER SP-1246.
A1-PDO.DWG (SP-2065)
4. ALL HAZARDOUS SHARP EDGES AND CORNERS SHALL BE GROUND SMOOTH. GENERAL NOTES, LEGEND AND ABBREVIATIONS & 0002
MAR-00-104133-CX-7880-02501-0001
MGCP 00
3. SHOP WELDING SHALL BE MAXIMIZED. STANDARD DRAWING -CONCRETE STRUCTURE -
2. STANDARD DRAWING-STEEL STRUCTURE - GENERAL NOTES, LEGEND AND ABBREVIATIONS GENERAL NOTES, LEGEND AND ABBREVIATIONS & 0002
STANDARD DRAWING
REFER DRG NO. MAR-00-104133-CS-7880-02501-0001
1. ALL DIMENSIONS ARE IN mm, ELEVATIONS & CO-ORDINATES ARE IN M (UNO). STANDARD DRAWING FOR STEEL
MASTER DRAWING REVISION STAIR SHEET-1 OF 2
NOTES REFERENCE DRAWINGS MAR 00 104133 CS 2315 02120 0001 03
LAST SAVED BY SAHABUDEEN.A ON 04/08/2021 5:48 PM PLOTTED BY SAHABUDEEN A ON 8/4/2021 5:49 PM FILENAME: \\DS.PETROFAC.LOCAL\MCTPROJECTDATA\JI2046\10.ENGINEERING DISCIPLINE\04.CIVIL & STRUCTURAL\4.0 ENGINEERING\4.02 DRAWINGS\01. STANDARD DRAWING\13 - STAIRCASE\AFC\NATIVE\MAR-00-104133-CS-2315-02120-0001_03.DWG