4     508
Electromotoric Actuators                                       SQK34.00
             for valves with 90° angle of rotation                          SQK84.00
             •   SQK34.00 operating voltage AC 230 V
             •   SQK84.00 operating voltage AC 24 V
             •   3-position control signal
             •   Nominal angle of rotation 90°
             •   Nominal torque 5 Nm
             •   For direct assembly with no need of mounting kit
             •   1 auxiliary switch for extra functions
             •   Manual adjuster and position indicator
             •   Mode of operation «AUTO» or «MAN»
             •   Reversible electromotoric actuator
Use
             For use in heating, ventilation and air conditioning systems to operate type VBF21…,
             VBG31…, VBI31…, VCI31… 3-port and 4-port slipper valves up to DN 50 (refer to
             «Equipment combinations»).
CM1N4508en
                                                                    Building Technologies
22.08.2008                                                                 HVAC Products
Type summary
                             Type          Operating voltage     Positioning signal      Positioning time for 90° at 50 Hz   Torque
                             SQK34.00           AC 230 V
                                                                     3-position                       135 s                  5 Nm
                             SQK84.00            AC 24 V
Accessories                  Type                                     Description
                             ASC9.7                                   Auxiliary switch
Order                        The actuator and accessories must be ordered separately.
                             When ordering please specify the quantity, product name and type code.
                  Example    1 actuator SQK34.00
                             1 auxiliary switch ASC9.7
Delivery                     The actuator and accessories are packed separately and delivered as individual items.
Equipment combinations
                                                Slipper valves              Actuators SQK34.00, SQK84.00              Data sheet
                            3-port valve        VBF21…, Series 02                        DN 40…50                       N4241
                                                VBI31…, Series 02                                                       N4232
                                                                                    DN 20…40 (¾…1½“)
                                                VBG31…, Series 02                                                       N4233
                            4-port valve        VCI31…, Series 02                   DN 20…40 (¾…1½“)                    N4252
Function / mechanical design
                             These electromotoric actuators require no maintenance. They have a reversible
                             synchronous motor.
                             The actuator is driven by a 3-position signal from the controller and generates a rotary
                             motion which is transferred via a pin in the slipper valve shaft to the 3-port or 4-port
                             slipper valve.
                             The actuators are supplied with a 90° angle of rotation. During automatic operation,
                             rotation is limited by two built-in end-switches.
                             The direction of operation of the actuator can be reversed (refer to «Commissioning»).
                             Direction of rotation of the actuator on delivery:
                             • Voltage at Y1 = Counter-clockwise rotation (ccw)
                             • Voltage at Y2 = Clockwise rotation (cw)
                             • No voltage        = No rotation; actuator fixed in relevant position
                                                                  1 Position indicator, can be changed manually,
                                                           1
                                                                    depending on the required direction of rotation
                                                           2
                                                                  2 Manual setting knob
                                                                    When the selector is set to «MAN», the valve can be
                                                                    operated with a manual knob.
                                                 4508Z24
                                                                  3 Selector for automatic or manual operation
                                                MAN
                             AUTO
                                              4508Z25
2/6
Building Technologies        Electromotoric Actuators                                                                   CM1N4508en
HVAC Products                                                                                                             22.08.2008
                                                                          4 Connecting terminals
                                                                          5 Coupling and cam shaft
                                                                          6 Space for auxiliary switch
                                                                          7 Auxiliary switch ASC9.7
                                                                            For on / off changeover operation. The switching
                                                                            point is adjustable.
                                                                            Factory-wired with a three-wire cable of 1.5 m.
Engineering notes
Electrical installation   The actuators must be electrically connected in accordance with local regulations and
                          with the connection diagrams.
                          Regulations and requirements to ensure the safety of people and property must
                          be observed at all times.
                          If additional functions are required, the actuator must be equipped with an auxiliary
                          switch. The relevant switching point must be noted in the plant documentation
Mounting notes
Overview of               Type                                 Mounting Instructions           Type      Mounting Instructions
Mounting Instructions     SQK34.00, SQK84.00                          M4508    74 319 0448 0   ASC9.7       G4508.1    4 319 5579 0
                          The valve and actuator can be assembled straightforwardly on site. There is no need
                          for special tools.
Orientation               90°                 90°
                                                     4716Z16
Commissioning notes
                          When commissioning the complete motorized valve consisting of actuator and slipper
                          valve, always check the wiring and test the functions. This also applies to the additional
                          auxiliary switch ASC9.7 fitted.
                          For automatic operation, the selector must be set to «AUTO»
Mode of operation
                          «AUTO» = automatic operation                                 «MAN» = manual operation
                                                                                                                                 3/6
Building Technologies     Electromotoric Actuators                                                                    CM1N4508en
HVAC Products                                                                                                           22.08.2008
Position indication
                        Manual setting «FULLY CLOSED»                   Manual setting «FULLY OPEN»
                        = no supply of heat *                           = maximum supply of heat *
                        *   If the hydraulic circuit is reverse, the removable scale fort he position indication
                            must be turned.
Direction of rotation   The actuators are factory-set to rotate in counter-clockwise (ccw) direction for opening.
                        The direction of rotation of the actuator or the slipper valve is determined by the
                        • Boiler flow (from left or right)
                        • Position of the slipper valve (hydraulic circuit)
Reversing the
direction of rotation
                                    0         1                                    0       1
                                                   Y2 Y1 N                                      Y2 Y1 N
                                                                                                          4508Z30
                                                             4508Z31
                        Control signal supplied to terminal Y1          Control signal supplied to terminal Y2
                        = counter-clockwise direction (ccw)             = clockwise direction (cw)
                        The wiring connecting terminals Y1 and Y2 must be interchanged if the direction of
                        rotation is be reversed. If an auxiliary switch is fitted, this aspect must also be taken into
                        consideration when making the electrical connections.
Setting the             The angle of rotation is factory-set to 90° and cannot be adjusted.
angle of rotation
Control                 Every actuator must be driven by a dedicated controller.
Maintenance
                        The actuators require no maintenance.
            Caution     Before performing any service work on the slipper valve or actuator:
                        • Switch off the pump and power supply
                        • Close the main shut-off valves in the pipework
                        • Release pressure in the pipes and allow them to cool down completely
                        If necessary, disconnect electrical connections from terminals.
                        The slipper valve must be re-commissioned only with the manual adjuster or the
                        actuator correctly assembled.
Disposal                The actuator contains electrical and electronic components and must not be disposed
                        of together with domestic waste.
                        Legislation may demand special handling of certain components, or it may be sensible
                        from an ecological point of view.
                        Current local legislation must be observed.
4/6
Building Technologies   Electromotoric Actuators                                                            CM1N4508en
HVAC Products                                                                                                 22.08.2008
Warranty
                                    The technical data given for these applications is valid only in conjunction with the
                                    Siemens butterfly and slipper valves as detailed under «Equipment combinations».
                                    The use of third-party valves other than those recommended by Siemens invalidates the
                                    warranty.
Technical data
                                                                                  SQK34.00                                   SQK84.00
Power supply               Operating voltage                                  AC 230 V, ± 15 %                            AC 24 V, ± 20 %
                           Frequency                                                                         50 / 60 Hz
                                                 1)
                           Power consumption                                         3 VA                                       2 VA
Control                    Positioning signal                                                                3-position
                           Parallel operation                                   parallel operation of several actuators not possible
Operating data             Positioning time for 90°                                                            135 s
                           Angle of rotation                                                            90° ± 3° (factory setting)
                                    1)
                           Torque                Starting torque                                              10 Nm
                                                Nominal torque                                                 5 Nm
Norms and standards        CE-conformity
                           EMC-directive                             2004/108/EC
                                                                                                        2)
                                                         Immunity EN 61000-6-2             Industrial
                                                         Emission EN 61000-6-3             Residential
                           Low voltage directive                     2006/95/EC
                                                  Electrical safety EN 60730-1
                           Product standards for automatic           EN 60730-2-14
                           electric controls
                           Protection standard          EN 60730                   Class II                                   Class III
                           Housing protection standard
                             Upright to horizontal                  IP42 to EN 60529
                           Environmental compatibility              ISO 14001 (Environment)
                                                                    ISO 9001 (Quality)
                                                                    SN 36350 (Environmentally compatible products)
                                                                    RL 2002/95/EG (RoHS)
Dimensions / weight        Dimensions                                                             see «Dimensions»
                           Cable glands                                                        1 x ∅ 20.5 mm (for M20)
                           Weight                                                                              0.5 kg
Materials                  Housing base, yoke                                                                 plastic
                           Cover                                                                              plastic
                                    1)
                                         These values apply at nominal voltage, at an ambient temperature of 20 °C and at the specified nominal
                                         running time
                                    2)
                                         Transformer 160 VA (e.g. Siemens 4AM 3842-4TN00-0EA0) for AC 24 V actuators
Accessories for SQK34.00, SQK84.00
 Auxiliary switch ASC9.7   Switching capacity                        AC 250 V, 10 A resistive, 3 A inductive
General                                                                    Operation                         Transport                 Storage
ambient conditions                                                        EN 60721-3-3                  EN 60721-3-2                 EN 60721-3-1
                           Environmental conditions                        Class 3K5                         Class 2K3                Class 1K3
                           Temperature                                    –15...+50 °C                   –30...+65 °C                –30...+65 °C
                           Humidity                                       5...95 % r. h.                 < 95 % r. h.                0...95 % r. h.
                                                                                                                                                      5/6
Building Technologies               Electromotoric Actuators                                                                              CM1N4508en
HVAC Products                                                                                                                               22.08.2008
Internal diagrams
 SQK34.00                 Y1                Y2 3
                                      M
                                                      c1
                                                           4508G01
                           Cm1              Cm2                      Cm1   End switch
                                   N                 4 5             Cm2   End switch
                                                                     c1    1 auxiliary switch ASC9.7
                                                                     N     Neutral conductor
                                                                     G     System potential
 SQK84.00                 Y1                Y2 3                     Y1    Control signal counter-clockwise (ccw)
                                                                     Y2    Control signal clockwise (cw)
                                      M
                                                      c1
                                                           4508G02
                           Cm1             Cm2
                                   G                 4 5
Dimensions
                          Dimensions in mm
Overall height of valve   = Installation height of slipper valve from the middle of the pipe
and actuator              + Installation height of the actuator
                          + Minimum clearance from ceiling or wall for mounting, connection,
                          operation, service etc.              f > 100 mm
                                                               ff > 200 mm
6/6                       © 2008 Siemens Switzerland Ltd                                               Subject to alteration
Building Technologies     Electromotoric Actuators                                                           CM1N4508en
HVAC Products                                                                                                  22.08.2008