HB 331-2012 Overhead Line Design
HB 331-2012 Overhead Line Design
for
HB 331-2012 Overhead line design
Licence Agreement
This is an agreement between the end user of the Product ("Licensee") and SAI Global Limited, 286 Sussex Street, Sydney
NSW 2000 AUSTRALIA, ABN 67 050 611 642.
Australian Standards means Australian Standards and includes Joint ISO/Australian Standards, Joint NZ/Australian Standards,
current Draft Australian Standards, and amendments to Australian Standards.
Concurrent Users means the maximum number of people able to access the Product at any one time, and is limited to the
number of Licences purchased.
ISO Standards means Standards published by the International Organization for Standardization (ISO), for which SAI Global is
an authorised distributor.
IEC Standards means Standards published by the International Electrotechnical Commission (IEC), for which SAI Global is an
authorised distributor.
Internal use means use of the Product within the Licensee’s organization.
Product means Australian Standards, ISO Standards and IEC Standards ordered and purchased through the InfoStore, and
downloaded as electronic PDF files.
Click on the red box above to activate the Licence Agreement scroll bar.
2. Product Availability
See publications
2.1. The Product is available via the World covering the same
Wide Web through Subject
the use of a web Area
browser. Documents are provided as PDF files,
viewable through the use of Adobe ® Acrobat ® Reader Version 7 and above.
Subscribe to our Free Newsletters about Australian Standards® in
3. Licence Agreement
Legislation; ISO, IEC, BSI and more
Learn
3.1. By using the Product thehow to Manage
Licensee Standards
agrees to be bound by theCollections Online
Licence Agreement for the Product.
3.3.b. Purchasers of network Licences for the Product may install and use the Product on a network with the number of
Concurrent Users permitted corresponding to the number of users specified in the SAI Global Infostore order. Licensees are
permitted to make paper copies of the Product for Internal use limited to the number of network users specified in the SAI Global
Infostore order only. Licensees are permitted to make one electronic copy of the Product for backup purposes.
3.4. SAI Global will not in any way provide the Licensee with an updating service for the Product. The Licensee agrees that SAI
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
HB 331—2012
Handbook
Standards Australia wishes to acknowledge the participation of the expert individuals that
contributed to the development of this Handbook through their representation on the
Committee.
Standards may also be withdrawn. It is important that readers assure themselves they are
using a current Standard, which should include any amendments that may have been
published since the Standard was published.
Detailed information about Australian Standards, drafts, amendments and new projects can
be found by visiting www.standards.org.au
Handbook
COPYRIGHT
© Standards Australia Limited
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher, unless otherwise permitted under the Copyright Act 1968.
Published by SAI Global Limited under licence from Standards Australia Limited, GPO Box
476, Sydney, NSW 2001, Australia
ISBN 978 1 74342 061 4
HB 331—2012 2
PREFACE
This Handbook was prepared by a working group of Subcommittee EL-052-05, Design of
Overhead Electrical Lines for Standards Australia/Standards New Zealand Committee
EL-052, Electrical Energy Networks, Construction and Operation. After consultation with
stakeholders in both countries, Standards Australia and Standards New Zealand decided to
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
CONTENTS
Page
STANDARD
SECTION 5 INSULATORS
5.1 Insulator design .......................................................................................................... 28
5.2 Design for pollution ................................................................................................... 28
5.3 Mechanical design of insulators ................................................................................. 28
SECTION 8 SUPPORTS
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
SECTION 10 EARTHING
10.1 Introduction ............................................................................................................... 87
10.2 Design for touch and step potential for conductive structures .................................... 87
10.3 Replacing a non-conductive pole with a conductive pole ........................................... 87
10.4 SWER earthing .......................................................................................................... 88
10.5 Risk based approach to earthing for Australia ............................................................ 88
10.6 Risk based approach to earthing for New Zealand ..................................................... 89
STANDARDS AUSTRALIA
Handbook
Overhead line design—Guide to the application of AS/NZS 7000
S E C T I O N 1 S C O P E A N D G E N E R A L
1.1 SCOPE
This Handbook is a companion to and is intended to be read in conjunction with the
Overhead Line Design Standard, AS/NZS 7000, Overhead line design—Detailed
procedures (referred to as AS/NZS 7000 in this Handbook), which is a comprehensive
treatment on the design of overhead power lines and which supersedes the ENA C(b)1
Guidelines for the Design and Maintenance of Overhead Distribution and Transmission
Lines.
1.3 STRUCTURE
This Handbook comprises 5 parts as follows:
Part 1 is a guideline and commentary on the application of AS/NZS 7000 including
commentary on some of the more complex Appendices.
Part 2 is a guide to the line design process with key areas covered in more detail.
Part 3 provides a worked example of the line design process for a 132 kV single circuit pole
line.
Part 4 contains a number of miscellaneous worked examples for a range of line components.
Part 5 covers particular topics such as special and covered conductors, line fittings and
climbing structures.
In Part 1, the Section headings (up to Section 11) in the Handbook align with the Section
headings in AS/NZS 7000, but the Clause numbers do not necessarily align.
S E C T I O N 2 D E S I G N P H I L O S O P H I E S
AS/NZS 7000. The overhead line has to perform with suitable levels of reliability and
security for the weather loads expected in the region for its intended life.
AS/NZS 7000 also refers in Notes to Table 6.1 to giving consideration to the line length,
number of circuits and proximity to other lines or infrastructure, special exposed locations
such as long span water or valley crossings, or line locations where access is difficult
(where time and cost to restore the construction can be high). In these cases a higher
security level could be adopted for a particular structure or short sections of the line, or the
whole line.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The same limit state principles apply to other components of an overhead power line (e.g.
conductor, insulator and electrical clearance). Electrical components have properties which
vary with manufacturing and weather conditions. In the electrical design, there are many
empirical relationships which have been developed from testing and experience.
AS/NZS 7000 specifies minimum requirements for electrical design. However in some
instances where higher reliability is required additional measures will need to be applied.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Despite the adoption of the above criteria there could be situations where conductors could
fail because of its wires being severed during the collapse of a support such as a tall lattice
tower.
The above strength coordination generally will only be applied to high security overhead
lines (e.g. transmission) in specific locations where the probability of exposure to severe
events is high and damage needs to be minimised.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 3 E L E C T R I C A L R E Q U I R E M E N T S
S E C T I O N 4 C O N D U C T O R S A N D O V E R HE A D
E A R T H W I R E S ( G R O U N D W I R E S )
Bare conductor selection consists of consideration of wire size, shape and material,
electrical, mechanical, environmental and economic factors. Conductor selection involves
the consideration of the following:
(a) Electrical requirements for steady state and transient current ratings, corona
discharge, audible noise, radio and televisions interference and joule losses.
(b) Mechanical requirements including annealing, drag coefficient, operating
temperature, constructability (no birdcaging or unravelling), permanent elongation,
fatigue endurance, conductor diameter, sag and strength relationship.
(c) Environmental requirements for corrosion and lightning damage.
(d) Economic requirements for cost of losses, capital costs, load profile, interest rate,
load growth, inventory costs and construction costs (ratio of tension to suspension
structures).
The conductor selection process is described in Figure 4.1.
O ve r h e a d Powe r L i n e
M VA R a t i n g
S h o r t T i m e M VA R a t i n g
Fa u l t M VA R a t i n g
Vo l t a g e R a t i n g
Vo l t a g e R a t i n g Thermal Rating
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Select Select
1. A n n e a l i n g c r i te r i a
1. C o r o n a d i s c h a r g e c r i te r i a
2. S te a d y s t a te c u r r e n t
2. A u d i b l e n o i s e c r i te r i a
3. S h o r t c i r c u i t c u r r e n t t i m e c r i te r i a
3 . R adio & television interference criteria
4. S te a d y s t a te o p e r a t i n g te m p e r a t u r e
Determine Determine
1. C o n d u c to r d i a m e te r 1. C o n d u c to r e q u i va l e n t e l e c t r i c a l c s a
2. N o. of c o n d u c to r s i n b u n d l e 2. N o of c o n d u c to r s
3 . B u n d l e d i a m e te r 3. Cost of losses
Mechanical Design
Select
1. Ty p e of c o n d u c to r s u p p o r t i n g c l a m p
2. C o n d u c to r v i b r a t i o n c o n t r o l
3. O ve r h e a d l i n e te r r a i n c a te r g o r y
4. M a x i m u m w i n d c r i te r i a
Determine
1. C o n d u c to r eve r yd ay te n s i o n
2. C o n d u c to r m a x i m u m s t r e s s
3 . S a g te n s i o n r e l a t i o n s h i p s
E nv i r o n m e n t a l D e s i g n
1. D e te r m i n e e nv i r o n m e n t a l ex p o s u r e
2. S e l e c t c o n d u c to r t y p e
New Zealand, the applicable standard for audible noise levels is NZS 6802. In Australia, the
relevant state and federal noise levels limits from the Environmental Protection Agency
apply.
4.2.4 Conductor long term electrical performance
The long term performance of a conductor is dependent on the degree of electrical and
mechanical overload and the weathering effects. Conductors will suffer some degree of
annealing (loss of mechanical strength) and this is dependent on the operating and overload
temperature on the conductor.
C o n d u c to r D a m a g e d li m i t Fa il e d li m i t
s t r e n g th li m i t s
Indicative damage and failure limits of conductors and tension fittings are illustrated in a
typical conductor stress strain characteristic illustrated in Figure 4.2 of AS/NZS 7000.
Table 4.1 of AS/NZS 7000 gives the damage and failure limit for a bare conductor.
4.3.3 Conductor fatigue and conductor everyday load horizontal tension
Conductor fatigue performance is a function of the conductor static stress and the conductor
dynamic stress. Factors that influence these stresses are illustrated in Figure 4.3.
Fa t i g u e f r e e a l u m i n i u m s t r e s s
Static stress
Te n s i l e s t r e s s - c o n d u c t o r e v e r y d a y t e n s i o n
C o n d u c to r c o n s t r u c t i o n
Bending stress
S p a n we i g h t l o a d
C o n d u c to r d i a m e te r
C o n d u c to r we i g h t
C o n d u c to r f l ex u a l s t i f f n e s s
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Compressive stress
C o n d u c to r we i g h t
Suppor t clamping forces
D y n a m i c s t r e s s - w i n d e xc i t a t i o n
Te r r a i n
Span length
Conductor self damping characteristic
C o n d u c to r c o n s t r u c t i o n
C o n d u c to r d i a m e te r
C o n d u c to r we i g h t
Damping control
As a first approximation only, assume the investment cost is the Capital Construction
(CC = cost/km), and look at ‘resistive’ losses only of the conductor (i.e. Ohm’s law
P = I2R).We can then construct the following formulae:
CC = (Peak losses) × (LLF) × (Average cost of losses/kWh) ×(h/year) × (Cap. Factor)
where
= I2Rac/km
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Peak losses
Average losses = (Peak losses) (LLF)
LLF = 0.7 LF2 + 0.3 LF (and if we assume a typical load factor of 0.65)
= 0.7 (0.652) + 0.3 (0.65)
= 0.491
Assume Avg. cost of losses = (15% Peak) + (25% Shoulder) + (60% Off Peak)
And using a typical residential time of use (TOU) tariff of:
Peak = 35.64 cents/kWh
Shoulder = 14.08 cents/kWh
Off peak = 8.14 cents/kWh
The average cost of losses = (15% peak at $0.3564/kWh)
+ (25% shoulder at $0.1408/kWh)
+ (60% off peak at $0.0814/kWh)
= $0.1375/kWh
Hours per year = 8760
Cap Factor = 12.4 (based on a 7% discount rate in perpetuity)
Therefore:
CC/km = (I2Rac/km).(0.491).($0.1375/kWh).(8760 hrs).(12.4)
And solving for the ‘break-even’ peak current under Kelvin’s law:
⎡⎛ $CC ⎞ ⎤
⎢⎜ km ⎟ × 1000 watt hours⎥
I = ⎣⎝ ⎠ ⎦
⎡⎛ Rα ⎞ ⎤
⎢⎜ ⎟ × ($0.1375) × (8760 hours) × (0.491) × (12.4) ⎥
⎣⎝ km ⎠ ⎦
All the ‘units’ cancel out in the above equation, leaving us with peak current in amps. We
can then construct Table 4.1 for some standard overhead conductors.
TABLE 4.1
APPLICATION OF KELVIN’S LAW TO SOME STANDARD CONDUCTORS
The ‘real world breakeven’ currents are considerably lower (up to half) those calculated in
Table 4.1, because we have:
(a) Ignored reactive components.
(b) Ignored the ‘cumulative’ effect of losses arising from upstream losses.
(c) Used a very low ‘cost of losses’ figure.
(d) Ignored reliability benefits of ‘heavier’ lines which have a greater resistance to
lightning, through faults, wind-blown debris etc.
A similar calculation can be carried out for LV ABC, which demonstrates that the Industry
should have selected 150 mm2 cables as the standard, rather than 95 mm 2. Generally, a
single 95 mm2 cable is suitable for villages etc., but for most urban applications, either a
single 150 mm2 cable or twin 95 mm2 cables is the ‘economic’ choice.
For distribution lines where a lower standard of load control and monitoring usually applies
it is recommended that an additional margin be applied. Maximum design temperatures of
50°C to 65°C are commonly used.
T 8 5 C ≈ 20% CBL
l o g (e l o n g a ti o n)
έ3
d e
έ2 b
c T 2 0 C ≈ 20% CBL
έ1
a
t3 t1 t4 t2 t5
l o g (ti m e)
The best example of permanent elongation, or in metallurgical terms, material creep is lead
sheeting on historical churches which slowly ‘creeps’ towards the eaves and requires
replacement every few hundred years. Textbook metallurgical creep is described
schematically in Figure 4.5. Logarithmic creep, the lower curve, occurs between about
0.3Tm and 0.4Tm, where T m is the melting point in Kelvin. For aluminium this is about the
design operating temperature for conductors as indicated in Table 4.2. The upper curve
describes creep behaviour normally encountered above about 0.4Tm. The period of
secondary creep is significantly greater than the primary and tertiary creep phases. ‘High
temperature’ creep may occur at less than 0.4Tm as the transition to 0.4Tm is not definitive.
O l i v e AC S R /G Z
I n i t i a l s t r i n g i n g te n s i o n 25% C B L @ 5 d e g C
F i n a l c o n d i t i o n 120 d e g C
E l o n g a t i o n c o n d i t i o n c o n s t a n t 20 d e g C f o r 3 0 ye a r s
Te n s i o n ( k N )
Sag(metres)
Sag
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
I n e l a s t i c a l l owa n c e
= 0 .76 m
Te n s i o n c h a n g e
= 2 kN
Te n s i o n
Time (years)
TABLE 4.2
ALUMINIUM CONDUCTOR MELTING AND
OPERATING TEMPERATURES
Kelvin Kelvin
1350 323 50
1120 358 85
6201 393 120
where
ε = permanent elongation %
t = time in hours
s = conductor stress in Pa
θ = conductor temperature in °C
A,nn = conductor constants
In most cases the conductor exposure period at elevated temperatures is very small relative
to an everyday exposure temperature assessed to be 20°C hence the Equation may be
reduced to:
ε = A × tn × sn 1 2
Typical creep test results are illustrated in Figure 4.6 and yield the creep constants A, n1, n2
and n3.
Pr i m a r y Secondar y Te r ti a r y
Hi g h te m p e r atu r e c r e e p
Elongation
(0.4T m )
Low te m p e r atu r e c r e e p
( l o g a r i th m i c c r e e p r ate)
Initial
creep
Time
T 8 5 C = 20% CBL
T 2 0 C = 4 0% CBL
T 2 0 C = 3 0% CBL
T 2 0 C = 20% CBL
initial creep
l o g ( t i m e)
At c, the conductor experiences an elevated temperature at say 16% CBL and 85°C with
duration, t3 to t4 which will result in creep accumulation of ε3 – ε2 as the conductor
behaviour moves from c to d. At d, the conductor may return to the original condition and
hence the original creep curve and transition to point e.
Thus, conductor permanent elongation may be determined for the predicted operating duty
of the transmission line. Whilst this has been illustrated as a graphical representation of the
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
creep accumulation, the application of the elongation equation knowing the conductor stress
history, exposure duration and conductor temperature allows a mathematical determination
of the creep accumulation. AS/NZS 7000, Appendix V provides a mathematical cumulative
creep equation.
Also illustrated in this example is that—
(a) the creep at a low temperature is much less than that at an elevated temperature; and
(b) the creep from one creep curve may be translated to another creep curve (i.e. from
point b to point c and also from point d to point e).
One of the most important aspects of understanding conductor permanent elongation is
determining design allowances for the long term conductor behaviour. The design
allowance for conductor elongation is necessary to account for the changes in conductor sag
and hence ground clearance over time. Design and or construction allowance generally
consists of short term prestressing conductors followed by long term design criteria by
either providing a ground clearance margin or over tensioning conductors after final
sagging. Many designers have found that a combination of these methods to compensate for
conductor permanent elongation yield a practical approach and result in the best overall
long term predictability of conductor behaviour.
Firstly, conductor prestressing takes advantage that significant wire radial and tangential
movements may be eliminated during the initial installation and loading periods. The
fundamental basis of conductor prestressing may be determined by examination of
Figure 4.6 and applying the principles of Figure 4.4. The selection of an appropriate
prestressing tension is a balance between a practical prestressing duration and a practical
prestressing tension. Significant over tensioning with small prestressing durations may
result in conductor fatigue and the over stressing of conductor fittings, insulators and
support structures. Typical and practical prestressing duration of about 3 h at about 30%
CBL may eliminate approximately 25% of the total predicted permanent elongation. During
any period of elevated prestressing care should be taken to ensure excessive conductor
vibration is controlled.
Temperature allowance is one of the longer term compensation methods. In this method,
conductor permanent elongation is equated to an equivalent conductor thermal elongation.
A temperature is determined which may be subtracted from the conductor stringing
temperature which results in the conductor being finally tensioned at a slightly elevated
conductor tension. For example, the final stringing temperature may be 15°C and 40%
permanent elongation compensation is required which may equate to a thermal elongation
of 6°C. Thus, the final sagging temperature would be 15°C – 6°C = 9°C. The selection of a
temperature allowance is limited by the allowable conductor fittings, insulators and support
structures ratings with appropriate consideration given to the possibility of longer term
conductor fatigue. Typical temperature allowances are approximately 40% of the total
predicted permanent elongation.
Sag allowance is the other long term and most common compensation method and is
illustrated in Figure 4.4.
Conductor permanent elongation is equated to a change in conductor sag over the design
life of the transmission line and a sag allowance is aggregated to the specified ground
clearance. For example, the predicted change in sag maybe 0.76 m and the specified ground
clearance is 6.7 m. Hence, the design ground clearance would be 6.7 + 0.76 = 7.46 m.
Typical sag allowances range between 40% to 100% of the total predicted permanent
elongation.
4.7.2 Empirical guidelines for temperature compensation for creep
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Typical temperature allowances for a range of conductor are shown in Table 4.3 or as
nominated by the network operator. This assumes new conductor and no pre-tensioning.
TABLE 4.3
CREEP TEMPERATURE COMPENSATION
FOR RANGE OF CONDUCTORS
AAC AAAC ACSR
Conductor tension
conductor conductor conductor
<5% CBL 0 0 0
5% CBL < and <10% CBL 5 to 10 5 to 10 0 to 5
10% CBL < and <20% CBL 10 to 20 10 to 20 5 to 10
>20% CBL 20 or higher 20 or higher 10 to 15
NOTES:
1 ACSR conductor assumes approximately 7% steel content.
2 There is no allowance needed for SC/GZ conductor.
References:
[1] Permanent Elongation of Conductors Predictor Equations and Evaluation Methods.
CIGRE Electra 75, pp 63-98, March 1981.
[2] Brennan, GF. Methodology for Assessment of Serviceability of Aged Transmission Line
Conductors. Postgraduate Thesis, Wollongong University, 1989.
[3] Drury, MD. The Effect of Prestressing on Inelastic (Creep) Behaviour of Australian
Mode Base Overhead Conductor. Postgraduate Thesis, Wollongong University, 1993.
Parabolic formula:
wL2
SAG =
8T
Catenary formula:
⎛ L ⎞
SAG = c ⎜ cosh − 1⎟
⎝ 2c ⎠
where
L = horizontal length (m)
T
c = = catenary constant (m)
w
T = horizontal tension (N)
w = weight of conductor (N/m)
S E C T I O N 5 I N S U L A T O R S
overvoltages and the mechanical stresses include the tensile, compressive or cantilever
loadings from conductor tension and weight.
Air gap clearance refers to the minimum distance which should be maintained between the
live conductor and earthed metal parts of the support to avoid flashover. The minimum air
clearance has to be maintained even under the conditions of system over-voltages with the
insulator strings in the deflected position due to the action of wind pressure. The three types
of over voltages which can occur on overhead lines are:
(a) Lightning induced.
(b) Switching surges.
(c) Power frequency over voltages.
S E C T I O N 6 B A S I S O F S T R U C T U R A L D E S I G N
In the case of concrete pole construction any steel crossarms would be expected to have
been discernibly deformed; concrete pole elements would have developed a series of open
tension cracks along the tension face of the pole, and some spalling of concrete could occur
on the compressive pole face.
In the case of lattice steel towers significant deflection of the total structure should be
evident, and localised buckling of the compression leg members and compression face
braces and some panels of bracing should become very evident.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The design should therefore be suitably proportioned to only reach this condition if the
limit state loads are exceeded. This means that the loads and loading combinations should
be determined such that the probability of this occurring is appropriately selected
considering material strength characteristics and acceptable low probability of exceeding
based loadings.
Clause 6.3 of AS/NZS 7000 sets out the approach to be adopted in design.
The limit state design approach uses a reliability based (risk of failure) approach to match
component strengths (modified by a factor to reflect strength variability) to the effect of
loads calculated on the basis of an acceptably low probability of occurrence.
φRn > effect of loads (Wn + ∑ γ x X )
where
X = the applied loads pertinent to each loading condition
are load factors which take into account variability of loads, importance of
γx =
structure, stringing, maintenance and safety considerations etc.
Wn = wind load based on selected return period wind
the strength factor which takes into account variability of material,
φ =
workmanship etc.
Rn the nominal strength of the component
Clause 6.3.4.2 of AS/NZS 7000 sets out the strength reduction factors ( φ ) to be applied for
the range of materials to be used in the various forms of construction. These factors are
based on current experience and material test characteristics.
Loads, load combinations, and load factors are provided in Clause 6.4 and Section 7 of
AS/NZS 7000 and as referred to in Section 7 of this Handbook.
S E C T I O N 7 A C T I O N O N L I N E S
7.1 INTRODUCTION
Clause 6.4 of AS/NZS 7000 sets out the philosophy and approach to be adopted in
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
determining the design loads and load combinations applied to the design of a line.
In Section 6 of AS/NZS 7000 actions (force or loads) are considered under two categories:
(a) A direct action of any force (load) applied to the supports, conductors, foundations,
and other line components.
(b) An indirect action of any imposed or constrained deformation, caused by temperature
changes, ground water variation or uneven settlement.
Actions may also be classified by their variation in time:
(i) Permanent action (G) such as self-weight of supports including foundations, fittings
and fixed equipment.
(ii) Imposed actions (Q) such as wind loads, ice loads or other imposed conductor loads.
(iii) Accidental actions (A) such as failure containment loads, flood debris loads,
avalanches, that relate to the security of the line.
Section 7 of AS/NZS 7000 then covers the more detailed derivation and application of
various load and load combinations
The wind pressures provided in Table 7.1 can be used for the majority of designs however a
detailed assessment of the design wind pressure should be undertaken in the event that:
(a) The structure height above ground is greater than 20 m. (for structures with loading
dominated by wind on the structure and its ancillaries, detailed wind calculations
should be performed if the height above ground is greater than 15 m).
(b) The average conductor height is greater than 20 m.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
(c) The line or structure is located in ‘Exposed open terrain with few or no obstructions
and water surfaces at serviceability wind speeds’ (the description provided for terrain
category 1 in AS/NZS 1170.2 Section 4.2.1).
(d) Local topography may accelerate winds acting perpendicular to the line (e.g. where
the line runs along, or along the windward side of, the crest of a hill).
(e) The design requires a security level greater than security level I (e.g. for sub-
transmission and transmission lines).
(f) An asset design life greater than 50 years is being designed for.
(g) The designer wishes to maximise the efficiency of the design. A detailed design
approach may be a preferable when developing standard structure designs for generic
application. Designs using Table 7.1 may be conservative if; the required design life
is less than 50 years; terrain categories 3 or 4 are applicable; or the design has large
spans (over 250 m).
(h) Span reduction factors should not be applied to the wind pressures provided in
Table 7.1.
TABLE 7.1
WIND PRESSURES FOR TYPES OF EQUIPMENT
(FOR 50 YEAR RETURN PERIOD WIND)
Region A1–A7 W1 B C D
Base wind
39 45 44 52 60
speed (m/s)
Base wind
913 1215 1162 1622 2160
pressure (Pa)
Suggested Cd Common wind pressures for types of
Equipment Comment factor equipment (Pa)
Round Poles Smooth 1.0 913 1215 1162 1622 2160
Round Poles Rough 1.3 1186 1580 1510 2109 2808
‘I’ Section prestressed Wide face 1.6 1460 1944 1859 2596 3456
concrete pole (or Stobie)
with chamfered edges Narrow face 1.0 913 1215 1162 1622 2160
Octagonal pole 1.4 1278 1701 1626 2271 3024
Transformers 1.5 1369 1823 1742 2434 3240
Regulators 1.2 1095 1458 1394 1947 2592
Conductors Assumed SRF = 1 1.0 913 1215 1162 1622 2160
Crossarms End 1.2 1095 1458 1394 1947 2592
Wide face 1.6 1460 1944 1859 2596 3456
Insulators Post/pin 1.2 1095 1458 1394 1947 2592
Stain/string 1.2 1095 1458 1394 1947 2592
NOTE: A factor of 1 has been used for M z,cat , M d , M s , M t and depending on the location of the line, these factors
may vary.
TABLE 7.2
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The wind load condition comprises maximum ultimate design wind speed at minimum
design ambient temperature in the particular location or region of concern. Combination of
the maximum wind and minimum temperature gives rise to the structure and conductor
design wind forces plus conductor tensions.
The most common wind load combinations are:
(A) Maximum wind and maximum conductor weight span.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 7.3
TYPICAL MAINTENANCE LOADS
adjacent structure
weight span (see Note 1)
Line worker + hook
General access and Actual duty or nominal ladder (or jury
Differential tension
maintenance design weight span mast) + rescue kit
(See Note 2)
Differential horizontal
Line worker + hook tension and vertical
Actual duty or nominal ladder (or jury component of conductor
Conductor stringing
design weight span mast) + rescue kit stringing tension
(See Note 2)
(See Note 3)
NOTES:
1 Dropped conductor:
If a conductor is lowered from the crossarm and does not reach the ground, a substantial increase in
weight span can be generated on adjacent structures. Before line workers are permitted to work on the
crossarm of adjacent structures, loads should be checked to ensure safe limits are not exceeded.
A dropped conductor should be considered a live load applied to crossarm to be accessed by personnel;
resulting weight span should be magnified by AS/NZS 7000 live load factor of 2.0 unless otherwise
approved.
Square rigging ultimate loads should be derived using a live load factor of 2.0 at the crossarm
maintenance attachment point and sheave attachment point on the tower superstructure.
2 Standard personnel access live loads for steel tower construction:
A maximum of two line workers working on a tower phase conductor crossarm/ earth wire peak is
generally assumed. A third line worker (less tools) may be located only on phase conductor crossarm to
assist rescue operation.
Working loads arising from personnel access:
(a) Live load on suspension crossarm = 2 × (line worker + tools) + hook ladder + rescue kit;
(b) Live load on earth wire crossarm = 2 × (line worker + tools) + rescue kit or jury mast and line
worker;
where:
(i) Standard line worker (including PPE, harness and tools) = 100 kg;
(ii) Standard hook ladder = 30 kg (vertically hung from end of crossarm apex) = 45 kg (used as bridge
from superstructure to crossarm apex);
(iii) Rescue kit = 10 kg;
(iv) Standard jury mast +line worker + tools = 200 kg;
(v) Standard dead weight of gondola + 2 × (line worker + tools) = 9 kN (applied load is doubled to allow
for balance of opposing force).
3 Conductor stringing:
Unbalanced conductor tensions arising from winching/stringing operations are applicable only to terminal
or section structures unless special measures are taken to strengthen suspension structures. If personnel
are required to access the crossarm during stringing operations, a live load factor of 2.0 should be applied
to conductor stringing tensions and resultant vertical component.
In general, it is expected that winches should be positioned a distance from the structure at least 4 × height
to crossarm from ground line on flat terrain and make due allowance for ground slope.
In addition consideration needs to be taken for imbalanced loads by any square rigging due to the position
of anchorage of rigging on the side points of a crossarm and the vertical component of the rigging on this
same point.
Generally square rigging loads applied at node points of the structure body by the purchase cable to the
winch are small and can be neglected.
for design of crossarm chord and bracing members. Fall arrest loads occurring on crossarm
apex should be additive with other maintenance conditions. Otherwise, fall arrest loads are
not coincidental with man-standing loads.
Minimum ultimate fall-arrest load (including LF) for a single line worker is 15 kN (see
AS/NZS 1891). The designer may need to consider the case of a simultaneous fall of two
line workers from ladders. In such cases, an ultimate fall-arrest load (including LF) of
21 kN applies.
Fall arrest loads may occur at the mid-span on other bracing members (including crossarm
top chord) if use is allowed for anchors or tie-off points. Such members will be permitted to
suffer limited damage (bending) provided connection capacity (bolt shear and member
bearing) is sufficient to withstand loads without fracture.
Fall arrests anchorages should be connected to dedicated anchorage points or to nodal brace
connections points. The designer should provide appropriate notes on structure drawings to
provide instruction to the contractor regarding approved fall arrest attachment points and
warnings of members that should not be used for anchorage.
7.4.6 Short-circuit forces
Short-circuit forces are only applicable to structures supporting very short spans and in
close proximity of a fault current source.
Typically, short-circuit forces are not critical to standard line structures. Susceptible
structures may include landing or substation yard structures or distribution support
structures and single phase support structures outside of switchyards.
Short-circuit forces may be the result of a fault occurring under a high wind are generally of
very short duration and should be added in combination with 0.25 maximum wind load.
7.4.7 Earthquake loads
Appendix C of AS/NZS 7000 sets out specific design provisions for assessing seismic
loads.
Structures of high mass or those supporting an elevated concentrated mass such as pole-
mounted transformers are susceptible to the effect of earthquake loads.
Pile foundation systems embedded in soils susceptible to liquefaction may be subjected to
lateral forces. This may then lead to excessive differential foundation movement and
distortion of the structure. Accordingly, the design should be compatible with design
foundation settlement limits.
Typically, earthquake loading is not additional to other loading events.
7.4.8 Differential settlement of structure foundations
The designer should consider potential action effects from differential settlement and
reactive clays.
In susceptible conditions, differential settlement may need to be considered in combination
with the normal operating wind load case.
The designer should consider action effects that may arise from differential settlement of
structure footings.
In general, poles and lattice towers with bolted connections are not prone to damage from
differential settlement. Structures that may be susceptible to this action affect are towers of
welded construction or those with footprints <7 m square.
Good foundation design practice is to specify <10 mm maximum differential settlement of
foundation elements for all structure types during construction and service life of the
structure.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
7.4.9 Fatigue
Fatigue should be considered for structural components subject to a high number of stress
reversals or susceptible to resonance due to high frequency wind gust effects.
Fatigue is not generally a significant design consideration for poles or free-standing towers.
Other structures and components that may require consideration of fatigue include:
(a) Fluttering of guy ropes or slender structure bracing with l/r > 250.
(b) Tall, slender masts with natural frequency <1 Hz.
(c) Guyed structures.
Common design practice to manage fatigue is to apply a lower stress limit to the component
or make provision to prevent resonance by use of stiffer members.
7.4.10 Serviceability loads
7.4.10.1 General
Under serviceability loading limit state conditions the overhead line supports should have
no discernible deflections over the life of the structure. Pole structures subject to sustained
load and bending will deflect over time due to creep within the material. Stress levels need
to be limited to the values set out in the relevant sections of AS/NZS 7000.
7.4.10.2 Load factors and tolerances
The purpose of load factors and material capacity factors is to provide a ‘design tolerance’
to account for uncertainties in the magnitude of resultant member stresses arising from
nominal design actions and variations in materials and detailing of structural components.
Factors affecting the forces applied to a structure vary from actual service loading
conditions due to construction tolerances arising from:
(a) Fabrication and construction variations.
(b) Misfit and eccentricities of structural members and connection.
(c) Over-tension of conductor at installation to compensate for long-term creep.
(d) Stringing procedures.
(e) Instrument and field measurement errors of as-built conductor tension.
(f) Conductor material variations.
(g) Equipment.
The new Standard has allowed for the reduction of unbalanced conductor tension load
factor from 1.5 to 1.25. This provision will give rise to a significant reduction in the cost of
angle and strain structures.
However, a substantial proportion of the load factor can be ‘consumed’ by conductor
over-tension for long-term creep allowance alone (10%–12% or more increase in tension
over the nominal maximum design tension is typical for large conductor sizes).
Accordingly, the designer should ensure adequate controls are implemented to manage all
potential errors or variations arising throughout the design and construction phases (e.g.
field measurement errors of as-built conductor tension) within the specified allowance.
Otherwise, a higher load factor may need to be adopted.
states.
TABLE 7.4
WIND LOADS FOR COMPONENT LIMIT STATES
M cD o nne l Cre e k
DARWIN Weip a Moreton
Co ok tow n
Cairns
Bro ome 20 0 k m
20 0 k m Tow ns v ille
B owen
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Croydon Mack ay
Ro ck hampton
O nslow Bundab erg
Zone II - Conve c tive dow ndraf t s only
Mar y b orough
Carnar von 25°
B R ISBAN E
G r af ton
G eraldton Coff s Harb our
PER T H
SYDNE Y
20 0 k m
AD EL AID E
MELBOURNE
Zone III - Sy noptic and conve c tive
FIGURE 7.1 WIND REGIONS FOR AUSTRALIAN DESIGN WIND GUST TYPES
Figure 7.1 (Figure B1 of AS/NZS 7000) shows a zoning map to determine which storm type
should be considered in design for wind. On the mainland, the regions on this map are
delineated by a boundary 200 km from the smoothed coastline. This contrasts to the
multiple narrow 50 km wide zones in AS/NZS 1170.2 for the near coastal areas. Wind
velocities are selected from AS/NZS 1170.2 as appropriate to the security level selected for
the relevant location and wind zone required in AS/NZS 7000, Figure B1.
This leaves some latitude to the designer to select the V50 value for a selected Security
Level as required in Section 6 of AS/NZS 7000.
For example in Zone 1 for Australia where cyclonic events occur AS/NZS 1170.2 provides
for wind zones C, D and B. Recent experience suggests that these arbitrary 50 km zones are
not relevant to severe Category 4 and Category 5 cyclonic events as the storm damage paths
have been observed to extend 100 km inland over a width of some 20 km. In these cases it
would be appropriate to select a V50 value from region C.
For the remainder of the non cyclonic regions within Zone 1 such as New South Wales
coastal area, only one V50 value is provided, but a higher return period value may be
adopted in some local areas where regular storm damage occurs.
For example in the coastal area immediately north of Sydney or the south east Queensland
regions, it might be prudent to adopt a V100 value or a higher security level as appropriate,
in view of the relatively high frequency of severe thunderstorms.
It should be noted that the selection of the regional wind speed is relevant to the line’s
location, and care needs to be exercised where standard designs are applied to multiple
sites. Where an overhead line is of significant length, variations in wind loading may be
required as the line passes through differing wind exposure situations.
For example, a line emanating from a coastal substation in a cyclonic region passing inland
over a coastal range to an inland supply point could pass through three significant design
wind climates that should be incorporated in the line design.
provided in Table 3.2 of AS/NZS 1170.2 being taken as 1.0 to provide for multiple changes
in direction of the route of overhead lines. In some cases it could be argued that where a
line route is in a predominate direction for its entire route and the line design is unique for
that line only, that consideration be given for a lower value direction multiplier. However,
line designs once created, usually have repeat applications on other line projects which
could have multidirectional characteristics and extreme caution is required if reduced
values of Md are used.
Cyclonic wind amplification factors Fc and Fd provided in AS/NZS 1170 are to be taken as
1.0 for all overhead lines, based on performance of overhead lines in cyclonic areas over
time. These factors are provided in AS/NZS 1170.2 to apply additional security due to some
uncertainty with wind velocities in the light of the recent incidence of several major
Category 5 events.
Performance of major transmission lines in these regions over the last 50 years has been
very good, despite some structure failures occurring. Distribution line network failures in
such extreme events occur regardless of magnitude of wind velocities primarily as a result
of airborne vegetation and building debris. Hence the value of 1.0 has been applied for all
lines in these areas.
7.6.4 Downdraft wind regions (Australia Zone II and New Zealand Region A7)
AS/NZS 7000 provides for all structures to be designed for a minimum design wind return
period. The wind return periods are selected from Table 6.1 based on the design working
life and line security level. The wind return periods are used to select applicable 3s gust
regional wind speeds from AS/NZS 1170.2.
Downdraft winds are the predominate wind that governs the design of overhead lines in
Australia with the exception of cyclonic coastal regions. The wind velocities provided in
AS/NZS 1170.2 include this type of event.
The important aspect that is different is the span reduction factor when compared to that
applicable to the larger scale synoptic wind gust events. Downdraft wind gusts are
relatively narrow and when they strike the ground observations of vegetation damage
suggests a burst swath varying from 100 m up to 1000 m in width being common
occurrences during more severe thunderstorms and hence the wind can envelop one or more
spans simultaneously.
Figure B6 of AS/NZS 7000 provides a Span Reduction Factor (SRF)
Terrain Height Multiplier Mz, cat for the common range of structure in open terrain and
heights <50 m is 1.0.
7.6.5 Tornadoes
AS/NZS 7000 identifies that these events do occur in some parts of the country but that
they are relatively rare random events and of low intensity <F2 strength when compared to
those in United States of America and Argentina. Unless a line has a very high security
requirement, it is recommended that no special loadings be generally considered.
The basic regional wind pressure (pb) as selected from Table 7.5 below for the relevant
wind region from AS/NZS 1170.2 and limit-state being considered and ps and pu represent
the corresponding basic pressures for the serviceability and strength limit-states,
respectively.
TABLE 7.5
BASIC REGIONAL PRESSURES
The same effects are also frequently found on the downwind side of a major mountain or
isolated hill ridges of even smaller scale.
The occurrence of the second phenomenon, see Item (b), is not as well-known as the first,
mainly because of more limited extensions of each hill, and the possible lack of recent
reported wind damage. Effects of this kind are generally known as ‘rotors’ and ‘vortex
streets’.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
conductors as these turbulent effects impact lines. Measures to address these effects include
an increase of phase spacing or shortening of span lengths.
This is an informative section of Appendix B and is based on localised performance of lines
over time, and these details provide application guidelines to be considered during the line
layout process in particular to minimise potential risks of wind overload due to
topographical influences. In locations where a structure position cannot be relocated to
avoid a high risk situation then a higher duty/strength structure is usually the simplest
option.
7.8 REFERENCES
[1] Current Practices regarding Frequencies and Magnitude of High Intensity Winds
CIGRE TB 256.
S E C T I O N 8 S U P P O R T S
S E C T I O N 9 F O U N D A T I O N D E S I G N
9.1 GENERAL
AS/NZS 7000 establishes some important principles for acceptable design methods
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
always available to that sector of the electricity supply industry and in particular to
distribution lines.
In addition simple design methods have been in use for distribution pole overhead lines
throughout Australia and New Zealand and overseas for many years and these overhead
lines have performed well over time. This suggests that either the design loadings have not
generally reached the failure limit state at a particular structure such as to cause failure or
that the footing design methods adopted have been conservative.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
P
Ma
G ro un d sur f a ce Va
S o il fo r c e s
do
d
R ot atio n a x is
Pos t
Z X
S o il fo r c e s Y
Fo oti n g
This design method utilizes two soil assumptions. First, it is assumed that the soil
resistance to deformation is proportional to displacement for the range of
deformations used in design. Secondly, it is assumed that the resistance to
deformation increases linearly with depth below the ground surface. This increasing
resistance to deformation is due to the confining pressure of the soil overburden. For
each case, the maximum soil pressure is limited to the allowable lateral pressure.
⎛ 8Ma ⎞
6Va + ⎜ ⎟
⎝ D ⎠
Sb
where
b = effective width of the pole in the soil perpendicular to the direction of
movement, (m)
d = minimum pole embedment depth to resist applied forces with a
maximum soil pressure of S, (m)
Ma = moment applied to foundation at ground surface, (kN.m)
ground level and has no direct relationship with the loads applied to the pole.
T ip
dt
Assumed
tip l oa di n g
p o s i ti o n
hr L
A s s u m e d c r i ti c a l c r o s s s e c ti o n fo r
d e s i g n d gl
The embedment lengths LGL are based on a simplified method, as defined in the two
Equations below and relate purely to pole height above ground hr, see Figure 9.2.
For poles where the height from the ground line (GL) to the conductors is less than
18 m, the embedment length is calculated by Equation 9.2.1, with a maximum of
3.6 m. For longer poles, up to 21 m in height, the embedment length is calculated by
Equation 9.2.2, with a maximum of 4.8 m.
LGL is determined as follows:
LGL = Min[(1 + 0.1 × hr) × (dg/250),3.6] for hr < 18 …9.2.1
LGL = Min[(1 + 0.1 × hr) × (dg/330),4.8] for hr ≥ 18 …9.2.2
where
LGL = min. embedment depth, in metres
hr = height from the ground line to the conductors, in metres
dg = diameter of the pole at the ground line (GL), in metres
Table 9.1 gives numerical values for the planting depths for the common range of pole
dimensions.
TABLE 9.1
MINIMUM EMBEDMENT DEPTH (LGL), m
Pole
diameter Height from GL (ground line) to conductor, m
at GL
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Hr
hp
hr
fbv
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
D/3
2D/3
R1
D
D/9
Pivot d e pth
R2
(a) Fo r c e s a n d r e a c ti o n s ( b) Pr e s s u r e di s tr ib u ti o n
TABLE 9.2
BEARING STRENGTH OF SOILS AT THE SERVICEABILITY LIMIT STATE
is the value obtained from Table L1 of AS/NZS 7000 (fb. is sometimes represented as C u).
9.3.5 Design method
9.3.5.1 General
Based on the above assumptions, the embedment depth (D) may be determined from the
following equation:
Hr
hp
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
hr
0. 8 5 f b u
0. 3 m
R b1
D (= k h p )
R b2
0.1 m p < 0. 8 5 f b u
For poles, particularly guyed or stayed poles, the minimum plan area of the footing required
at its lowest extremity (Afb) is calculated from the following equation:
( Fv + Fgt )
A fb = …9.2.4
Fb
where
Fgt = the sum of the vertical components of the guy or stay tensions
Fv = the sum of the vertical forces acting on the pole from loads other than Fgt
fb = the nominal maximum bearing strength of the foundation material (kPa)
Fixed embedment depth:
For this arrangement, the following assumptions are made:
(i) The embedment depth (D) is a fixed proportion (k) of the height of the top of the pole
above ground level (hp) i.e. D = khp.
(ii) The centroid of area of the upper (breast) bearer is located at 0.3 m below ground
level.
(iii) The centroid of area of the lower (toe) bearer is located at 0.1 m above the bottom of
the footing.
(iv) The foundation pressure acting on the bearers is distributed uniformly over their
contact surfaces with a maximum magnitude of 0.85 fb.
Based on the above assumptions, the reaction force on upper bearer (Rb1) is given by—
( K hp + hr − 0.1) …9.2.5
Rb1 = HR
(khp − 0.4)
b f bu D 2 − 3.6 H R D − 4.05 H R hr = 0
Which is a simple quadratic of the form ax2 + bx + c = 0
Solving for D—
12.96( H R ) 2 + 16.2 b f bu H R h r
D = 3.6 H R +
2b f bu
than 150 kPa but should not be taken as less than 0.5 m.
Embedment depths for materials with a bearing strength less than 150 kPa should be
calculated directly from Equation 9.2.9 to which a further 0.2 m has to be added. Practical
considerations of foundation materials and available excavating equipment will determine
which combination of hole diameter and embedment depth that will be economically viable
at each location.
© Standards Australia
HB 331—2012
TABLE 9.3
POLE EMBEDMENT DEPTHS FOR SOILS WITH fb = 150 kPa
58
13.5 1.3 1.1 1.0 1.8 1.5 1.3 2.6 2.1 1.8 1.7 1.5 3.3 2.7 2.4 2.1 1.9
15.0 1.4 1.2 1.0 1.9 1.6 1.4 2.7 2.2 1.9 1.7 1.6 3.5 2.8 2.4 2.2 2.0
16.5 1.5 1.2 1.1 2.0 1.7 1.5 2.8 2.3 2.0 1.8 1.7 3.6 3.0 2.6 2.3 2.1
18.0 1.5 1.3 1.1 2.1 1.7 1.5 2.9 2.4 2.1 1.9 1.7 3.8 3.1 2.7 2.4 2.2
19.5 1.6 1.3 1.2 2.2 1.8 1.6 3.0 2.5 2.2 1.9 1.8 3.9 3.2 2.8 2.5 2.3
22.0 1.6 1.4 1.2 2.3 1.9 1.6 3.2 2.6 2.3 2.1 1.9 4.1 3.4 2.9 2.6 2.4
NOTES:
1 Tabulated depths include 0.2 m additional depth added because it should be assumed that for foundation materials softer than rock the top 200 mm of material
provides no resistance to the applied forces.
2 The embedment depth should be not less than 0.5 m in any soil.
www.standards.org.au
59 HB 331—2012
soil stresses result from compression loadings in the pole due to hardware and pole weight.
The horizontal soil stresses result from bending in the pole through wind and conductor
tension. For the purpose of assessing the strength of the foundation for a pole these two
components of soil stress are assumed to be acting independently.
The pole foundations should be designed to ensure adequate performance under all
reasonable loading situations including wind, snow, ice or earthquake loads.
The pole should have:
(a) Sufficient embedment depth and width to develop the horizontal resultant design load
in the soils encountered.
(b) Sufficient end bearing area to develop the vertical design load in the soils.
In addition, in some situations the designer may wish to impose a maximum deflection
requirement (e.g. urban road crossings to limit clearance reductions or poles with lines
attached to rigid structures like buildings or substations).
9.4.2 Background
History has shown that during ‘design events’, lateral pole movements have been up to
1.5 m and require significant remedial works to be carried out for many years afterwards.
The problems include:
(a) Continually creeping/moving poles (as foundations ‘yield’).
(b) Conductor clearances to ground level compromised.
(c) Damage to service lines to customers (particularly at building connection point).
(d) Damage to adjacent poles (due to redistribution of loading) and hardware (twisting).
Inadequate pole foundations are generally not obvious until some years after pole
installation (or for existing poles, after a change in pole loading).
9.4.3 Foundation limit states
For consistency with Australian Standards, the determination of design loads and the
assessment of pole capacities should be in limit state format, i.e. the poles and components
are designed using a reliability based (risk of failure) approach. The selection of load
factors (particularly for weather related loads) and component strength is based on an
acceptable risk of failure for the loading condition being considered.
There are two limit states which are applicable for the design of overhead lines:
(a) Ultimate (strength) limit state The design capacity of the pole (including its
foundations) and components exceeds the design load.
(b) Serviceability limit state The performance of the structure or components under
commonly occurring (everyday) loads or conditions will be satisfactory e.g. excessive
pole deflection, cracking of concrete poles and vibration.
This is shown below in Figure 9.5.
25
Ulti mate L i mit S tate ( R H )
Fo u n d a t i o n C a p a c i t y ( k N )
20
“ Y ie ld”
l d” p oint
15
Damage Limit State (ØRH )
10
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S e r v i c e a b i l i t y L i m i t S t a t e ( R H /3 )
0
0 200 400 600 800 10 0 0
H o r i z o n t a l D e f l e c t i o n ( m m)
Evaluation of foundation capacity using traditional methods gave values near the ultimate
(asymptotic) limit state, resulting in unacceptably large displacements.
9.4.4 General philosophy
For distribution poles (direct buried)—foundations fail before the pole structure (i.e. the
foundation soils will deform before the pole capacity is reached).
For transmission structures—the foundation is generally designed stronger than the pole
structure (i.e. the structure will fail first). In some cases, the strength co-ordination of pole
and foundations should be considered.
9.4.5 Methods of assessment
All of the available methods of calculating pole foundation capacity were developed for
laterally loaded piles with a relatively small amount of load eccentricity (i.e. height above
ground level of load application). Distribution poles, by contrast (refer Figure 9.6), have a
very high level of load eccentricity and so the reliability of the method of calculation
needed to be verified by a programme of measuring pole displacements and, possibly, full-
scale load tests.
GL
GL
The available methods of calculation are based on a condition of limiting equilibrium in the
soil (i.e. the soil is yielding everywhere), a condition that is generally reached only after
large foundation displacement and rotation, i.e. the ultimate limit state usually adopted for
design. However, most utilities desired design limit states of relatively small pole
displacements and so it was necessary to determine capacity reduction factors (0.65) to
reduce the calculated foundation capacities from limiting equilibrium criteria to the desired
limit state displacements.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 9.4
FOUNDATION INVESTIGATION REQUIREMENTS
Line importance
Foundation investigation requirements
Level I Level II Level III
Drive over route
Walk over each site
Test pits/scala penetrometer —
Specific geotechnical advice required — —
When investigation tests are required, there should be a minimum of 3 soil tests per soil
type or 1 test per 5 km of line, whichever is the greater.
Site specific foundation investigations should be undertaken in the following circumstances
when—
(i) the line importance is high; or
(ii) there are known foundation problems and a history of failures; or
(iii) there are land instability issues; or
(iv) poles are supporting aerial plant weighing more than 1000 kg.
The water table should be based on site investigations with allowance for seasonal
fluctuations. If the water table has not specifically been determined, a level of 1 m below
the ground surface could be used.
Any site investigations should include recommendations as to the design parameters and
any further work required (e.g. proof loading, laboratory testing etc.).
site, a CPT penetration was conducted to a depth of 3 m (or until refusal) using a purpose
made rig.
A typical CPT plot is illustrated in Figure 9.7, which shows cone tip resistance (qc), friction
ratio and inferred soil type profile.
q C ( M PA ) D r (%) S u ( K P a)
pe
q
Ty
0
0 0
0
0
Li
0
60
80
80
40
40
4 8 12 16 20
20
20
10
16
12
0
0.0
0.6
1. 2
1. 8
2.4
3.0
10 5 0
Fr i c t i o n R a t i o (%)
The left-most trace is the tip resistance (qc) which is a measure of resistance to penetration
and thus soil shear strength. The second trace is the friction ratio (Rf) or ratio of sleeve
friction to penetration resistance which is useful for determining soil type (e.g. sandy soils
have a low friction ratio while clays and peats have a high ratio).
The first colour stripe indicates the soil type:
(a) Red ..................................................................................................................... Sand.
(b) Yellow .......................................................................................................... Silt-sand.
(c) Green .................................................................................................................... Silt.
(d) Aqua ............................................................................................................. Silt-clay.
(e) Blue .................................................................................................................... Clay.
(f) Black ................................................................................................................... Peat.
The second colour strip indicates susceptibility of the soil to liquefaction during
earthquakes
(i) Green ............................................................................................. Low susceptibility.
(ii) Red ............................................................................................... High susceptibility.
(iii) Orange .................................................................................................... Intermediate.
The third trace indicates relative density (Dr) for sands and silt-sands and the fourth trace
indicates the undrained shear strength (Su) for silts and clays.
9.4.8 Soil classification and mapping
For some CPT profiles, the classification is simple. Other profiles are much more complex
with inter-bedded silts, clays, sands, and silty sands. For complex soil profiles, the
classification is based on a combination of predominant soil type and computed foundation
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
capacity (taking into account the contribution of the various layers identified in the CPT
log).
Table 9.5 gives an example of 5 types of soil classifications on a soil mapping project.
TABLE 9.5
SOIL CLASSIFICATIONS AND DESCRIPTIONS
Soil classification Description Strength group
P Peat 1
P/SC Soft silts and clays 2
SC Silts and clays 3
S Sand 3
G Gravel 4
The soil classification for each site can then be marked up on a scale map and soil class
zones and boundaries can be identified using interpolation where necessary. An example is
given in Figure 9.8.
There are various methods used for direct buried pole foundation design and these are
covered in Table 9.7.
The Brinch-Hanson method is regarded as the superior method for pole structures, however
more simple techniques, such as that outlines in AS/NZS 4676 have been found to be
suitable for intermediate poles in firm soil and with small conductors.
Two basic types of lateral foundation analysis
(a) Coefficient of horizontal sub-grade reaction.
(b) Maximum stress method.
These methods do not allow for significant vertical loads (which reduce the lateral
capacity).
9.4.10 Foundation strength factors
The strength reduction factors used for ultimate design should meet the values shown in
Table 9.6 unless specific investigations are undertaken to justify a different value.
TABLE 9.6
STRENGTH REDUCTION FACTORS FOR
METHODS OF SOIL ASSESSMENT
www.standards.org.au
TABLE 9.7
COMPARISON OF FOUNDATION DESIGN METHODOLOGIES
Foundation design Formula Failure criteria Advantages Disadvantages Comment
Brinch-Hansen* Precise calculation 0.5°C at tip Considers: Complex, requires soil Strength factor of 0.65 appropriate.
modelling. Iterative analysis
• Multi layered soil
approach required.
properties
Considers free head
• Soils with both friction situation only. Stiff clays.
and cohesion
• Variable water table
• Variable bearing widths
Based on the ultimate lateral
soil resistance of the soils
Broms† Precise calculation 0.002–0.006 rad Relatively simple Cannot be used in complex Appropriate for non-cohesive and
65
at ultimate soils or variable shaft sizes cohesive soils. Broms suggested
Based on the ultimate lateral
capacity (i.e. non-uniform soils, strength factor of 0.7
soil resistance of the soils
water table). Not
Applicable for short and appropriate for high
long piles. eccentricity situations.
Considers both fixed and Very conservative.
free head restraint
* Based on short rigid piles, refer to paper ‘Brinch-Hansen, J. and Christensen, N. H. (1961). ‘The Ultimate Resistance of Rigid Piles against Transversal Forces,
Bulletin No 12, Geoteknisk Institut, Copenhagen, 16p’
† Based on short rigid piles, refer to paper ‘Broms, B.B. (1964) ‘Lateral resistance of Piles in Cohesive Soils.’ Journal of the Soil Mechanics and Foundations Division,
ASCE Vol 90, No SM2, p27-63.
© Standards Australia
HB 331—2012
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
HB 331—2012
© Standards Australia
66
New Zealand Pole length/6 Unknown Simple Not appropriate for weak Applies to firm soil and medium,
soils. Based on working sized conductors (≈15 mm) associated
stress method. with intermediate poles up to 120 m
spans
EPRI Unknown Simple Need to assess soil prior to
calculating depth.
CAISSON
PFAP
* Based on ASCE Manual
† Origin trace to the USA where it is used predominantly with firm clay soil types and with an original safety factor of 4. Referenced in ANSI 05.1-1979 ‘Specification
and Dimensions for Wood Poles’. Also Effect of Depth of Embedment on Pole Stability,’ Wood Preserving News, Vol X, No. 11, November 1932.
‡ Developed by Western Power for loose sand situations around Western Australia.
§ Depth increased to allow 200 mm for disturbed ground at surface.
www.standards.org.au
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
www.standards.org.au
67
movement. For large analysis package.
diameter/deep concrete pile
situations
P-y Method
* Formula from ‘Effect of Depth of Embedment on Pole Stability,’ Wood Preserving News, Vol X, No. 11, November 1932’
† ANSI/ASAE EP486.1 Shallow Post Foundation Design.
© Standards Australia
HB 331—2012
HB 331—2012 68
Ul ti m ate L i m i t S t ate
25
Fo u n d a t i o n C a p a c i t y ( k N )
Brinch-Hansen
20 U
Ull ti
t i m ate
a te Ca p a c i t y
“ Y i e l d” p o i nt
R a n g e of
15 U
Ull ttii m a te
ate
Ca p a c i t y of Po l e
10
S e r v i c e a b i l i t y L i m i t S t a te
0
0 200 400 600 800 10 0 0
H o r i z o n t a l D e f l e c t i o n ( m m)
HB 331—2012
© Standards Australia
70
www.standards.org.au
71 HB 331—2012
8 .0
7.0
6 .0
Applied load (KN)
5.0
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
4.0
3.0
2.0
1.0
0.0
0 20 0 400 600 800 10 0 0 120 0 14 0 0
L o a d d i s p l a c e m e n t f r o m s o i l m ov e m e n t ( m m)
A typical load displacement plot is shown in Figure 9.11. This plot shows that:
(i) The pole behaves linearly up to the ‘yield’ point i.e. there is no permanent offset after
the pole is unloaded.
(ii) There is significant post-elastic deformation above the yield load until the ultimate
capacity is reached.
(iii) There is a large reserve post-elastic capacity i.e. ultimate load/yield load greater
than 2. This results in unacceptably large pole deflections before the ultimate
foundation capacity of the pole is reached.
9.4.14 Stayed poles
The designer should take into account the flexibility of the stays and ground anchors and
the effects of the likely deformation on the pole structure. The ground anchors will move to
develop the full passive pressure wedge. If the amount of soil movement has not been
specifically determined, a value of 200 mm should be assumed.
The minimum embedment depth for poles with stays should be at least 2 m.
An anchor assembly should be capable of developing an ultimate strength equal to the
working load of the stay multiplied by a factor of safety of 2.5.
In difficult terrain, such as swampy or marshy ground conditions, special provision needs to
be made for anchoring. A swamp type anchor should be used which provides a large cross
sectional area blade. Alternatively where this does not provide sufficient ground purchase
then stay rods with reinforced concrete block and bulk concrete should be employed.
area of embedded poles are reduced. The legs of H-frames may ‘walk’ out of the
ground if neither sufficient depth nor bog shoes are provided to resist uplift. Guy
anchors may fail if the design capacity does not consider the submerged weight of the
soil.
(b) Areas where the soil is loose such as soft clay, poorly compacted sand, pliable soil, or
soil which is highly organic in nature.
(c) Locations where higher safety is desired. This may be at locations of un-guyed small
angle structures where a portion of the load is relatively permanent in nature, or at
river, line, or road crossings.
(d) Locations where poles are set adjacent to or on steep grades.
(e) Locations where poles are set adjacent to excavations, drains, retaining structures etc.
(f) Locations where more heavily loaded poles are used.
(g) Locations where underground utilities such as water or sewer are located next to the
pole.
9.4.16 Rigid pole rotation
Assumes a rigid pole (i.e. failure is a soil bearing failure) and not a flexible pile situation
(where the critical failure occurs in the foundation itself).
A rigid pole situation can be assumed to occur when:
(a) L/D ≤10 timber.
(b) L/D ≤5 concrete.
9.4.17 Pole shape
The pole embedment depth assumes a circular section below ground level. AS/NZS 7000
embedded section width should be modified by the values shown in Table 9.8 where
excavated soils are used for backfill with minimal compaction. Where well compacted
granular and imported granular material, or cement stabilised materials are used no
modification factor applies.
TABLE 9.8
MODIFICATION FACTOR FOR POLE SHAPE
TABLE 9.9
REDUCTION FACTORS FOR POLES SUBJECT TO LOADING
Pavement at the ground surface is generally not considered when calculating foundation
capacity. However, a nominal force of 1 kN can be applied at the ground line for all poles
to recognise the likely contribution from the soil surface crust.
9.4.20.4 Concrete footpath
A nominal force of 5 kN can be applied at the ground line for poles to recognise the
contribution from the concrete surfacing.
9.4.20.5 Blocking
For heavily loaded poles breast blocks (near surface) and heel blocks (near pole base) may
be added to give a substantial increase in capacity. This can be further improved by adding
cement stabilized backfill around the pole.
Po l e
G r ass ve rge
or ashphalt
To p S o il o r ashp halt
1.6 x 0. 25Ø 0. 8
B ack f ill with ( AP4 0 ) tho ro ughl y
co mp ac te d in laye r s not
e xce e do ng 150 mm
EL Breast block
0. 23
0.6
Bk N HW
DIMENSIONS IN METRES
Po l e
0. 5
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
To p S o il o r ashp halt
Reblock
B ack f ill with ( AP4 0 ) tho ro ughl y
co mp ac te d in laye r s not
e xce e do ng 150 mm
DIMENSIONS IN METRES
Po l e Po l e
0.15 M a x
Grass verge or ashphalt
Kerb
0. 8
To p S o il o r ashp halt
DIMENSIONS IN METRES
This can be further improved by replacing the SAP40 backfill with cement stabilized AP40
backfill around the pole.
Po l e
To p S o il o r ashp halt
2.0 m AP4 0 with cem ent r atio of 12 :1 ( dr y mi x )
( app rox . 20 kg ½ b ag )
0.6 m
In the case of concrete backfill, any in ground services within the concrete should be
sleeved to ensure services are not trapped.
9.4.20.9 Comparison of improvement types
Strengthening methods are compared against standard construction in Figure 9.16 and
Table 9.10.
30
Fo o t h p a t h
G r a s s Ve r g e
25
Foundation Capacit y (kN)
15
10
0
0 200 400 600 800 10 0 0
TABLE 9.10
COMPARISON OF STRENGTHENING METHODS
Configuration Improvement method Typical load at 300 mm Typical
displacement at pole tip strength factor
Free standing Grass verge 4.0 1.0
Pole, short
Sealed footpath—chip seal AP40
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
AS/NZS 7000 foundation), AS/NZS 7000 foundation depths should be increased as follows:
Slope Angle e
3 H:1V o r f l at te r < 15 d e g 0
Up to 2H:1V < 25 d e g 0. 5B
U p to 1. 5H:1V < 35 deg 1.0 B
G r e ate r th a n 1. 5H:1V > 35 deg X
GL
Interpolation between the values is acceptable. These types of foundations should not be
placed on slopes steeper than 1.5H:1V.
9.4.22 Trenches and excavations
The lateral embedment values in Table 9.3 apply only to relatively flat conditions. Where
poles are located near trenches and open excavations, some special considerations in
determining the foundation depth are needed.
X /D e
0.0 1. 3 D
0. 5 1.0 D
1.0 0. 8 D
1. 5 0.6 D
2 .0 0. 4D
2.5 0. 2 D
3.0 0
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
X
X ≤ 3D
GL
D
L L
For example:
A standard pole with 2 m embedment depth is located 2 m from a drainage ditch which is
1 m deep—
L = 2, X = 2, D = 1, then X/D = 2, from table, e = 0.4 and D = 0.4 m
New embedment depth = 2 + 0.4 = 2.4 m.
If the foundation is located on a slope that is part of a drainage ditch, the top of
AS/NZS 7000 foundation can be located at or below the bottom of the drainage ditch.
9.4.23 Land instability
Where there is potential for subsidence of the ground due to ground water changes, mining
etc., the effects on the pole and the line should be taken into consideration in the design of
the line including any mitigation measures.
Line routes over hilly areas prone to slips should be avoided.
9.4.24 Liquefaction
Liquefaction of loose saturated, cohesion-less soils (sands, silts and loose sandy gravels)
during strong earthquake shaking should be taken into consideration in the route selection
of lines.
The consequences of liquefaction should be considered, including:
(a) Foundation failure.
(b) Loss of pole or pile lateral or vertical capacity.
(c) Subsidence.
(d) Lateral spreading of slopes, embankments and ground towards river banks.
The risk of liquefaction should be consistent with the other performance requirements for
the pole or line section.
9.4.25 References
Bulletin No. 12 issued by the Geoteknisk Institut (The Danish Geotechnical Institute—
Copenhagen 1961) Topics: BRINCH HANSEN, J. The ultimate resistance of rigid piles
against transversal forces, CHRISTENSEN, NH. Model tests with transversally loaded
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 9.11
TIMBER SPECIES, STRENGTH GROUPS, NATURAL DURABILITY RATINGS
AND BRAND MARKS
Natural
Softwood (S) or Strength group Species
Standard trade common name durability
hardwood (H) (Unseasoned) brand
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
ratings
box, coast grey H S1 1 CB
gum, grey H S1 1 GG
ironbark, broad- leaved red H S1 1 BU
ironbark, grey H S1 1 GI
Blackbutt H S2 2 BB
box, grey H S2 1* GB
box, white H (S2) 2* WX
box, white topped H S2 2* WT
gum, poplar H (S2) 3* PG
gum, salmon H (S2) 3* SA
gum, spotted H S2 2 SG
ironbark, narrow-leaved red H S2 1 NI
ironbark, red H S2 1 RI
mahogany, red H (S2) 2 RM
mahogany, southern H S2 2 SM
mahogany, white H S2 1 WM
stringybark, blue-leaved H S2 3* SL
stringybark, silvertop H S2 3 SS
tallowwood H S2 1 TW
ash, silvertop H S3 3 ST
blackbutt, New England H S3 2 NA
bloodwood, brown H S3 2* BD
bloodwood, red H S3 1* RW
box, brush H S3 3 BH
box, red H S3 2* RX
box, yellow H S3 1 YB
gum, southern blue H S3 3 BG
gum, forest red H S3 2 FR
gum, maiden's H S3 3* MG
gum, mountain grey H S3 3 MT
gum, rose H S3 3 RO
gum, Sydney blue H S3 3* SY
peppermint, broad-leaved H S3 3 BT
Satinay H S3 1 S
stringybark, brown H S3 3 BS
stringybark, messmate H S3 3 MS
(continued)
Natural
Softwood (S) or Strength group Species
Standard trade common name durability
hardwood (H) (Unseasoned) brand
ratings
stringybark, red H S3 3 RS
stringybark, white H S3 2 WS
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
stringybark, yellow H S3 2 YS
turpentine H S3 1 TP
ash, alpine H S4 4 AA
ash, mountain H S4 4 MA
brownbarrel H S4 4 BL
gum, manna H S4 4 MN
gum, mountain H S4 4 MO
gum, yellow H (S4) 1 YG
peppermint, narrow-leaved H S4 3 NL
peppermint, Sydney H (S4) 3 SP
gum, river red H S5 2 RR
peppermint, black H (S5) 3* BP
pine, cypress white S S5 1* WC
pine, slash S S5 4 PS
fir, Douglas (Oregon)—North America S S5 4 DF
fir, Douglas (Oregon)—elsewhere S S6 4 DF
pine, Caribbean S (S6) 4 PB
pine, hoop S S6 4 HP
pine, loblolly S S6 4 PL
pine, maritime S (S6) 4 PM
pine, radiate S S6 4 PR
pine Corsican S (S7) 4* PC
pine, patula S (S7) 4* PP
pine, ponderosa S (<S7) 4* PW
pine, Canary Island S — 4* PI
pine, long-leaf S — 4* PF
* These durability ratings are not listed in AS 5604 and have been assigned the classification in
AS 2209.
NOTES:
1 See AS 5604 for definitions of timber natural durability ratings.
2 The strength groups assigned in the above Table are those given in AS 2878 for unseasoned timber.
Provisional strength groups are shown in brackets. These are assigned in those cases where the evidence
was inadequate to allow positive grouping at the time AS 2878 was published.
3 For information on species not listed refer to CSIRO, Forest Products or state forestry authorities.
The characteristic strengths and elastic moduli for untrimmed poles that conform in quality
to the grade requirements specified in AS 2209 are as specified in Tables 9.11 and F1 of
AS/NZS 7000 unless verified by testing of samples from the same grade.
Strength groups and joint group classifications are assigned to species in accordance with
AS 1720.2.
soils will shrink away from the pole as they dry out; the sub soil requires some distance to
provide fixity to develop restraint, and significant degradation in the zone 300 mm below
ground surface level will occur over time. In deep cracking/ reactive clays this 200 mm
allowance could be deeper unless breast logs or stabilized backfill is used.
Concrete cover is the other important consideration for providing concrete durability.
Paragraph I5 of AS/NZS 7000 sets out minimum cover requirements for varying exposure
conditions, reinforcing bar, concrete aggregate sizes and water absorption limits.
With the high characteristic compressive strengths that can be achieve through mix design,
concrete compaction (particularly by centrifugal spinning), the provision of high and
consistent standards of initial concrete curing will greatly enhance long and durable service
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Pulling
Safety/deflection poles
structure
Load cell
A
A
B C
B
C
D
D
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Distribution E
E Load cells
beams
F F
Deflection
To winch tapes
Test pole
Pulley
Winch
Winch
R e a c to r b e a m
Anchor block
Load cell
Suppor t trolley Te s t p o l e
G r a d u a te d b e a m
for deflection Jaws
measurement Suppor t trolley
Crack development during load testing should be carefully monitored and significant or
accelerated crack width development with small load increase could signify structural
design weakness at loads below 50% of ultimate capacity.
Cracks in non-prestressed poles above 40% load capacity most likely will not close up after
release of load on test, however if the pole were to experience this level of loading in
service, the self-weight load will most likely close resultant cracks.
It should be noted that the advantage of prestressing and partial prestressing tendons in pole
designs provides control of cracking under all normal service loading conditions likely to
be experienced.
For testing of concrete poles, refer to Appendix K of AS/NZS 4676.
9.8.3 Pole manufacture related design issues
9.8.3.1 General
It is most important in the production control for concrete pole manufacture to not only
ensure consistency of the concrete mix but also in the measured volume of concrete batched
and added to the moulds to ensure design wall thickness is provided. In spun poles the
internal wall can have in part minimum fines in the surface zone and hence durability of the
internal concrete may need to be enhanced by sealing off the butt to prevent ground water
ingress.
If the total internal void in circular concrete poles is sealed off top and bottom and with
through tubes for bolting, significant thermal differentials from air temperature variations
during the day will cause pressure variations internally and can cause ground water to be
pumped inside the void if any below ground opening exists.
Butt sealing of hollow poles is recommended for most applications, particularly where high
ground water tables are known to exist, or can be expected to occur after seasonal rainfall.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 1 0 E A R T H I N G
10.1 INTRODUCTION
An earthing system of overhead earth wires, earth down leads, grading rings and
counterpoise earthing addresses the following objectives:
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
given as follows:
Example 1: HV Distribution Earth (e.g. Pole mounted transformer, recloser, and air break
switch) in a CMEN urban area:
(a) Description:
Voltage = 11 kV
Fault current = 5000 A
Fault clearing time = 1s
Fault rate = 2 × 100 m span without earth wire at 40 faults per
100 km per year
Contacts per year = 40 for 4 s
Footwear = Standard distribution
Earthing resistance = 1Ω
Soil resistivity = 100 Ω/m
Prospective touch voltage = 1000 V (refer to ENA EG-0 and use an impedance
model of footwear and soil resistivity)
Prospective touch voltage
curve DU for 1 s clearing = 800 V
(b) Mitigation Options:
(i) Insulate earth (this is standard practice for HV earth down leads but may not be
practical for air break switches with exposed metal operating rod and handle).
(ii) Installation of NER or NEX to limit fault current to typically 1000 A.
(iii) Installation of grading ring—this would lower prospective touch voltage.
(iv) Reduce protection clearing times—at 0.5 s, the prospective touch limit is
4000 V.
Example 2: Conductive distribution pole in an urban area:
(i) Description:
Voltage = 33 kV
Fault current = 5000 A
Fault clearing time = 1s
Fault Rate = 2 × 100 m span without earth wire at 40 faults
per 100 km per year
Contacts per year = 40 for 4 s
Footwear = Standard distribution
Earthing resistance = 10 Ω
Soil resistivity = 100 Ω/m
available).
(B) Installation of NER or NEX to limit fault current to typically 1000 A—
prospective touch voltage reduces to 2000 V. This is still above limit.
(C) Installation of grading ring—this would lower prospective touch voltage to
around 5000 V. This is still above limit.
(D) Reduce protection clearing times—at 0.5 s, the prospective touch limit is
4000 V. The prospective touch voltage is above limit.
(E) Combination of (B) and (C)—still above limit.
(F) Combination of (B) and (D)—meets limit.
(G) Installation of underslung earth wire—this reduces prospective touch voltage to
less than 800 V (underslung earth wire is expected to reduce fault current on
stricken pole to range of 5% to 8% of previous value). This meets limits.
(H) Bond to the neutral conductor in a MEN earthing area to become a CMEN
earthed system.
(I) The installation of underslung earth wire is also effective in addressing touch
hazards on all conductive poles on the feeder.
This case study follows the risk management method as detailed in the flowchart from
Figure 10.4 of AS/NZS 7000.
(a) Step 1: Basic data
(i) The prospective earth fault current at the source substation is 7 kA.
(ii) The resistance to earth of the 11 kV transformer (including the associated MEN
system) is 10 Ω.
(iii) The resistivity of wet concrete is assumed to be 50 Ω.m.
(iv) The earth fault clearing time is 0.5 s.
(v) The earth fault frequency for the line is 5 per year.
(vi) The line consists of 200 poles and does not have an overhead earth wire.
(b) Step 2: Functional requirement
The pole meets the functional requirements.
(i) All exposed metalwork is bonded.
(ii) The prospective earth fault current is more than twice the feeder pickup setting
to ensure the protection will operate.
(iii) No nearby telecommunication asset.
(c) Step 3: Calculate Maximum Earth Potential Rise (EPR)
Using parameters associated with the earth fault current path for an earth fault at the
pole, the EPR on the pole was calculated as approximately 5 kV. The parameters are:
(i) 1.2 km Dog ACSR between site and source substation.
(ii) 7 kA earth fault level at source substation.
(iii) 2 Ω source substation earth grid resistance.
(iv) 10 Ω site grid resistance.
(d) Step 4 : Prospective tolerable step and touch voltage limits
The touch voltage limit was determined from Figure 9 of the EEA Guide To Power
System Earthing Practice (also included as Figure 10.6 of AS/NZS 7000) for a fault
clearing time of 0.5 s and for a wet concrete resistivity of 50 Ω-m (footwear
included).
The step voltage limit was determined from Figure 10 of the EEA Guide to Power
System Earthing Practice for a fault clearing time of 0.5 s and for a wet concrete
resistivity of 50 Ω.m (footwear excluded).
VT (limit) = 410 V
VS (limit) = 2155 V
(e) Step 5: Is EPR ≤ VT (limit) and VS (limit)?
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The EPR on the pole is greater than the step and touch voltage limits.
VT (limit) = 410 V
EPR = 5000 V > {
VS (limit) = 2150 V
(f) Step 6: Calculate touch and step voltages
For this case study, the step and touch voltage limits were calculated using CDEGs
modelling software.
A plot of touch voltages on the pole is shown in Figure 10.2.The plot shows that the
maximum touch voltage on the pole is calculated to be 2023 V.
L EG EN D:
M a x i m u m va l u e: 20 23.14 8
M i n i m u m t h r e s h o l d: 410.0 0 0
2.0
< 20 23.15
< 18 61. 8 3
Y A X I S, m
< 170 0. 52
0. 5 < 15 3 9. 20
< 1377. 8 9
< 1216. 57
-1.0 < 10 5 5. 26
< 8 9 3.9 4
< 732.6 3
A plot of step voltages around the pole is shown in Figure 10.3. The plot shows that the
maximum step voltage around the pole is calculated to be approximately 1900 V.
L EG EN D:
M a x i m u m va l u e: 18 9 9.474
Minimum th re s h ol d: 77.18 0
3.8 < 18 9 9.47
< 1717. 24
Y A X I S, m
< 15 3 5.0 2
< 13 52.79
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
< 1170. 56
-1. 2
< 9 8 8. 3 3
< 8 0 6.10
< 6 23. 87
< 4 41.6 4
< 259.41
- 6. 2
- 6. 2 -1. 2 3. 8
X A X I S, m
(g) Step 7: Are actual touch and step voltages ≤ VT (limit) and VS (limit)?
The calculated touch voltage exceeds the touch voltage limit but the maximum step
voltage is less than the step voltage limit.
(h) Step 8: Risk assessment
The risk assessment consists of:
(i) Identify the risk by identifying all hazards and extent of hazard zones;
(ii) Compare voltage limits with calculated or measured voltages;
(iii) Estimate people exposure to the hazards. Carry out sensitivity analysis where
required.
The hazards of concern at the pole are the touch voltages onto the concrete pole. The
risk can be assessed by calculating the coincidence probability, Pc.
Pc = EFFF ...
where
EF = total duration of exposure per year (in hours)/number of hours in a year
FF = average number of hazardous EPR events per year on a pole
The frequency of earth faults for the line with 200 poles is 5 faults per year.
Therefore:
FF = 5/200 = 0.025
If, for the purpose of this case study, we assume that the pole is being touched once a
day for 5 minutes (i.e. someone leaning against the pole) for five days of the week
(i.e. λE = 260 days per year), the total duration of exposure per year will be:
Total duration of exposure = 5 minutes per day × 260 days per year/60 minutes
per hour = 21.7 hours per year
As there are 8,760 hours in a year the exposure factor will be:
EF = 21.7/8760 = 2.5 × 10−3
The coincidence probability is therefore:
Pc = 2.5 × 10-2 × 2.5 × 10-3 = 6 × 10-5
Since only one person is typically affected, N = 1 and the equivalent probability is:
Pe = NPc = 1 × 6 × 10-5 = 6 × 10-5
The risk is therefore ‘intermediate’ and should be minimised unless the risk reduction
is impractical and the costs are grossly disproportionate to the safety benefit. A cost
benefit analysis should be carried out to determine whether the costs of risk treatment
options are disproportionate to the safety benefit.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 1 1 L I N E E Q U I P M E N T — O V E R H E A D
L I N E F I T T I N G S
Coverage of overhead line fittings is given in Clause 36. The topics covered include:
(a) Hardware fittings (including rules of mating and special fittings).
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
(b) Maintenance loads (including cart loading and live line fittings).
(c) Vibration dampers.
(d) Bolt tensioning.
S E C T I O N 1 2 S T E P S I N T H E D E S I G N
P R O C E S S
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
An overview of the steps in the overhead line design process is given in the flowchart
below.
D e te r m i n e d e s i g n i n p u t s / p a r a m e te r s
S e l e c t r o u te
S e e k r o u te a p p r ova l s
C o n d u c t r o u te s u r vey
Pe r fo r m e l e c t r i c a l d e s i g n (s e l e c t c o n d u c to r s /
e a r t hw i r e s , i n s u l a to r s a n d e a r t h i n g)
D e te r m i n e s t r u c tu r e s u i te
D e te r m i n a t i o n of l o a d o n s t r u c tu r e s
S t r u c tu r a l a n d m e c h a n i c a l d e s i g n
Fo u n d a t i o n d e s i g n
Ve r i f i c a t i o n of d e s i g n
O b t a i n c o n s t r u c t i o n a p p r ova l s
Pr ov i d e d e s i g n s u p p o r t d u r i n g c o n s t r u c t i o n
D e s i g n va l i d a t i o n
D o c u m e n t a s - c o n s t r u c te d r e c o r d s
S E C T I O N 1 3 D E S I G N I N P U T S / P A R A M E T E R S
The design inputs/parameters may be determined by the electricity utility/project owner and
other situations may be determined by the designer for a proponent. These may consist of
the following:
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 1 4 R O U T E S E L E C T I O N P R O C E S S
14.1 INTRODUCTION
The aim of the route selection process is to select the lowest cost solution that meets the
technical requirements and minimises community impacts.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Appropriate consideration should be given at the route selection stage to the use of the land
proposed for the power line corridor. There are zoning maps available from local
government authorities which describe the land usage in the region.
Local jurisdiction planning instruments, particularly those regulating the clearing of trees,
may also influence the selection of the most appropriate route for the power line. Some
areas may be of high environmental significance such as aboriginal and cultural heritage or
sensitive vegetation (mangroves) and the line route will need to avoid these areas where
possible.
Where power lines traverse private property the approval of the property owner is required.
This would normally take the form of a negotiated easement detailing any restrictions on
land use necessary for reliable operation of the line.
On public land the agreement of the management agency should be obtained for the
proposed line.
Compacting the phase conductors will improve visual amenity but will increase the surface
voltage gradient on the conductors and the noise (radio interference and audible). To offset
the increase in electric field strength, a larger diameter conductor may need to be selected
to ensure the surface voltage gradient is below the corona threshold level.
Non specular conductor will reduce the initial glare of the conductors and the high corona
noise produced when the line is initially energized. Non specular conductor will make the
conductor more hydrophilic to water and minimise the water drop corona effects.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Prudent avoidance involves taking reasonable steps in any particular circumstance, and
although a precise definition cannot be given, it is possible to provide general guidance.
The aim of this Clause is to outline a range of options which may be applied in the context
of prudent avoidance for transmission and distribution situations. It remains the
responsibility of the designers to apply the principles appropriately to particular situations.
The Energy Networks Association has recommended to its members that a policy of
prudence (incorporating prudent avoidance) be applied in relation to EMF from supply
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
industry assets.
Clause 14.5.3 describes a number of specific options for prudent avoidance which may be
applied to transmission facilities.
14.5.3 Transmission
14.5.3.1 Distance
The most common method of reducing peoples’ exposure to EMFs is by selecting line
routes (i.e. siting) to avoid population centres or areas where people gather. Particular
attention should be paid to schools, child care centres and other areas where children
congregate.
Although a matter for developers/planning authorities, increased separation needs also to be
considered when new residential development is proposed adjacent to existing transmission
lines. This could involve either the sacrificing of land within the development site or the
relocation of some parts of the line.
Figure 14.1, illustrates how magnetic field strength reduces with distance from the line.
Raising the height of the supporting structures or towers, and thus the height of the
conductors, can also reduce the magnetic field strength below the line. However, the cost
and visual impact associated with the increased structure height may limit this technique to
selected portions of a line. Structure raising may be more practical for wood pole lines than
for steel tower lines, due to the cost factor.
14.5.3.2 Conductor configuration
Different arrangements of phasing can produce different magnetic field strengths for the
same line current. In general, triangular arrangements tend to provide more field
cancellation than horizontal arrangements, with lower resultant field strengths. The effect of
line geometry on magnetic field profile for a typical HV line is shown in Figure 14.1. For
the purposes of convenience, the magnetic field strengths in the graphs of this Clause are
shown in microtesla, where 1 microtesla = 10 mG.
1.4
1
M i c r o t e s l a p e r 10 0 A m p s
1. 2
2
total current
1.0 3
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
4
0. 8
0.6
0.4
0. 2
0
-50 -40 -30 -20 -10 0 10 20 30 40 50
D i s t a n c e f r o m c e n t r e l i n e (m)
NOTES:
1 Single circuit with horizontal flat configuration of phases.
2 Single circuit with triangular configuration of phases.
3 Single circuit with vertical configuration of phases.
4 Double circuit with vertical configuration of phases and with favourable phase sequence (acting to reduce
field strength).
0.6
M i c r o t e s l a p e r 10 0 A m p s
1
0. 5 2
total current
3
0.4
0. 3
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0. 2
0.1
0
-30
-26
-2 2
-18
-14
-10
10
14
18
22
26
30
-6
-2
2
6
D i s t a n c e f r o m c e n t r e l i n e (m)
1: B B 2: B B 3: B R
W W W R W W
R R R W R B
Selection of the proper phasing arrangement is usually the most effective way to reduce
magnetic fields for two circuits on the same structure or two or more circuits on the same
easement for minimal cost, if re-routing is not possible.
14.5.3.5 Split phasing
A single circuit line can be constructed as two parallel circuits with a phase arrangement
designed to achieve maximum field cancellation. This is known as the split-phase technique
and may be considered if only one circuit exists on a route. Although this form of
construction is significantly more expensive than conventional single-circuit construction, it
could be used for short sections of a line where it is desired to reduce fields within the
suggested 4% cost limitation.
14.5.3.6 Current reduction
A reduction in current will generally reduce magnetic field strengths. The reduction in field
strength is approximately proportional to the reduction in current. For a given load transfer
requirement, the only way to reduce the current is to increase the voltage. However,
because line voltage is generally fixed by system stability considerations, increasing line
voltage will seldom be feasible within the 4% cost constraint, and other design options are
likely to be preferable.
14.5.3.7 Shielding and cancellation loops
Shielding is the erection of a barrier between an EMF source and a subject to reduce the
field strength at the subject. A simple shielding barrier can substantially reduce electric
fields from transmission lines but has little effect on magnetic fields. Any object between
the source (line) and the point of interest will provide shielding or distortion of the electric
field. Common examples are buildings, trees or any other structure.
For all practical purposes there are no means to significantly reduce or screen magnetic
fields from overhead lines. In special applications, screening of individual pieces of
equipment is possible, using structures or enclosures made from special metals.
‘Cancellation’ or ‘degaussing’ loops are conducting wires suspended between adjacent
structures, above or below the phase conductors to provide both shielding and cancellation
effects.
© Standards Australia www.standards.org.au
103 HB 331—2012
They may be either ‘active’ (energised) or ‘passive’ (non energised) and rely on a current
flow in the opposite direction to cancel or reduce the overall field produced by the line. The
use of shielding or cancellation loops is still in the research phase and, while being
theoretically possible, this option is often regarded as complex, unsightly and of little
practical significance.
14.5.3.8 Undergrounding
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Because undergrounding is usually far more expensive than overhead construction, it does
not often fall into the category of prudent avoidance, with its ‘minimum cost/minimum
inconvenience’ criteria. There will be occasions, however, when partial undergrounding
may be consistent with prudent avoidance on a total cost basis, and accordingly this option
is discussed briefly below.
In underground cables, phase conductors are insulated from earth and from each other by a
relatively thin layer of solid insulation, as compared to a much larger dimension of air
insulation in the case of overhead lines. Accordingly, underground phase conductors can be
placed much closer together, providing a more effective field cancellation effect.
On the other hand, underground cables are normally buried 1 m or less below ground and
can be closer to people than an equivalent overhead line. Nevertheless, due to the
cancellation effect, the use of underground cables usually reduces the effective level of the
magnetic field at the point of interest. An exception to this might be the situation of cables
in a street area where the point of interest is the footpath or roadway immediately above the
buried cable where the field strength is still significant.
When considering undergrounding, it should be noted that, contrary to popular belief, the
ground has no magnetic field shielding property and plays no part in further field reduction.
Figure 14.3 illustrates the difference between the magnetic field profiles of overhead
transmission, distribution lines and the underground cable assuming perfect symmetry of
the phase currents in all three systems.
1.4
1. 2 1
Microtesla per
10 0 A m p s
1.0
2
0. 8
0.6 3
0.4
0. 2
0
- 50
-40
-30
-20
-10
10
20
30
40
50
0
D i s t a n c e f r o m c e n t r e l i n e (m)
NOTES:
1 Under a HV transmission line with horizontal phase configuration.
2 Under an 11 kV distribution line with horizontal phase configuration.
3 Above an underground three phase, single-core cable circuit with horizontal phase configuration and
100 mm phase separation.
A three phase underground cable in one sheath will produce a lower magnetic field than the
same capacity line constructed from three single-core cables because the conductors are
closer together and provide more effective field cancellation than three single-core cables,
especially if the latter are in flat formation.
14.5.4 Land development and easements
Land development adjacent to transmission lines often occurs after the transmission line has
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
been built. It has been suggested in some quarters that the prospect of future land
subdivision and development may create an argument for utilities adopting wider easements
in the first place. This suggestion was considered by Sir Harry Gibbs in his 1991 report. He
found no support for such a move, which would alienate additional land and increase costs
to the community. He said:
‘It would be particularly undesirable at the present time to prescribe standards or
guidelines with regard to exposure to the fields created by transmission lines or the width
of easements acquired or used for such lines.’
All transmission line easements would be affected while any potential benefit would be
restricted to a few isolated developments. Furthermore, because of the variation in magnetic
field strength profiles for the various design objectives as noted in Clause 2.1, of
AS/NZS 7000, it would be impractical to attempt to prescribe easement widths which result
in a consistent magnetic field outcome. It is suggested that the application of prudent
avoidance to land development should follow similar principles to those outlined for
transmission line development. In deciding what particular prudent option to adopt, the
developer may consult with the relevant utility in order to identify the most cost-effective
measures available for the particular circumstance.
14.5.5 Distribution lines
14.5.5.1 Siting
Due to the need to provide supply to customers, the options available to designers in siting
distribution infrastructure are limited. Distribution lines, by their very nature and function
are normally located in road reserves to provide supply to customers on both sides of the
road, although in some instances, they are located at the rear boundary of residential
properties.
Where practicable:
(a) Distribution lines should be located on the opposite side of the road from areas such
as schools, kindergartens, child-care centres and the like
(b) Distribution lines should be sited away from the walls of multi-storey buildings or
areas where children congregate
(c) Distribution lines should be located on the side of the road bordered by open spaces
where applicable
(d) Substations should be located at the electrical centre of their low voltage network, i.e.
current flows in all directions should be balanced.
(e) As with transmission lines, the benefits of community consultation and the sharing of
information should not be overlooked in the siting of distribution lines. This is
particularly relevant when high voltage overbuilds are being considered.
14.5.5.2 Design
Prudent design options which may be considered subject to their economic viability could
include:
(a) Use of aerial bundled conductor (ABC) for low voltage reticulation to provide more
effective field cancellation
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
(b) Use of offset construction (i.e. with all phases constructed on the same side of the
pole) to increase horizontal separation from the point of interest
(c) Use of underground cable in place of overhead conductors where economically
justified
(d) Use of three phase cable instead of 3 single phase cables
(e) Balancing of load across all phases to reduce neutral currents
(f) Use of insulated twisted service cable instead of open wire services to provide more
effective field cancellation
(g) For new double circuit lines, adoption of low reactance (RWB/BWR) phasing when
current flow in both circuits is in the same direction
When installing electrical facilities which involve both low voltage and high voltage, the
following options apply:
(i) When overbuilding (or underbuilding) existing facilities, the phasing on the existing
circuits should be determined and the new circuit or circuits phased to minimise the
combined magnetic field strength.
(ii) Where new or reworked subtransmission facilities are being considered on the same
structure with distribution circuits, the most effective field reduction measures may
be applied to the distribution circuits.
14.5.6 Magnetic field calculations
The magnetic field strengths for overhead (OH) lines have been modelled for a range of
standard designs for each construction. This manual has been used to determine the relative
position of conductors (conductor configuration) in relation to a reference point at ground
level (i.e. centre of the pole) for each construction. Each standard OH construction has been
modelled as a balanced 100 A per phase system at various conductor configuration heights.
The actual magnetic field strength is then found by multiplying the field strength profile by
the ratio of Actual Current per 100 A. The actual current used for the calculation should be
based on the long term average loading on the line. This is typically 50% to 75% of the
continuous current rating.
The program has been used to determine the magnetic field strength normal to the
conductors (i.e. 90°), at 1 m intervals up to 20 m either side of the centre of the pole, at a
height 1 m above the ground. A profile for each construction can then be generated from the
magnetic field strength results.
The relative position of conductors will not vary for each type of construction, but the
height of the conductor configuration above ground will vary according to the size of the
pole and the distances between poles. As the magnetic field strength is directly proportional
to the current, each standard construction i.e. (conductor configuration) is modelled and
graphed at 100 A. However field strength is not linearly proportional to the height of the
conductor configuration for each construction. Thus the field strengths have been modelled
at various conductor configuration heights above the ground at 100 A.
Interpolation between graphs for each type of standard construction is required to establish
a field strength profile at a certain conductor configuration height above ground. Due to the
variation in conductor heights above ground a minimum vertical clearance was used in
accordance with Schedule 1 below.
14.5.7 Schedule 1—Clearance of overhead electric lines
14.5.7.1 Part 1—Low voltage conductor clearance from ground
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
M a g n et i c f i e l d s t r e n g t h p r of i l e
LV ove r h e a d f l a t c o n t r u c t i o n
14
Magnetic field strength
5. 5 m
p e r 10 0 A m p s (m G )
12
6.0 m
7.0 m
10
9.0 m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t e l i n e (m)
H e i g h t o f l owe s t c o n d u c t o r t o g r o u n d
PR O PE R T Y
SIDE N
DIMENSIONS IN MILLIMETRES
M ag n et i c Fi e l d S t r e n g t h Pr of i l e
LV A BC Co n s t r u c t i o n
1.1
Magnetic Field Strength
1.0
5. 5 m
p e r 10 0 A m p s ( m G )
0.9
6.0 m
0.8
7.0 m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0.7 9.0 m
0.6
0.5
0.4
0.3
0.2
0.1
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
H e i g h t o f l ow e s t c o n d u c t o r t o g r o u n d
300 min
Suspension clamp
DIMENSIONS IN MILLIMETRES
14.5.9 11 kV Standards
The magnetic field strength profiles for the 11 kV constructions have been modelled at
heights of 5.5 m, 6 m, 7 m and 9 m per 100 A.
18
5. 5 m
Magnetic Field Strength
16 6.0 m
per 100 Amps (mG)
14 7.0 m
12 9.0 m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
10
0
-20 -15 -10 -5 0 5 10 15 20
150
DIMENSIONS IN MILLIMETRES
M ag n et i c Fi e l d S t r e n g t h Pr of i l e
11 k V O ve r h ea d Tr i a n g u l a r Co n s t r u c t i o n
20
Magnetic Field Strength
18 5. 5 m
6.0 m
p e r 10 0 A m p s (m G )
16
7.0 m
14
9.0 m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
12
10
8
6
4
2
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
Height of lowest conductor to ground
150
160 0
DIMENSIONS IN MILLIMETRES
M ag n et i c Fi e l d S t r e n g t h Pr of i l e
11 k V O ve r h ea d E x p a n d e d Tr i d e nt Co n s t r u c t i o n
16
Magnetic Field Strength
14 5.5m
6.0 m
p e r 10 0 A m p s (m G )
12
7.0 m
10 9.0 m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
H e i g h t o f l ow e s t c o n d u c t o r t o g r o u n d
5 32
8 82
DIMENSIONS IN MILLIMETRES
S t a n d a r d 11k V Ve r t i c a l D e l t a - Ru r a l Co n s t r u c t i o n
M a g n e t i c f i e l d s t r e n g t h v s Tr a n s v e r s e d i s t a n c e f r o m p o l e
M a g f i e l d p e r 10 0A p e r c c t (m G )
12
6.7m
10 7.7m
9.7m
8 13.7m
21.7m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0
-30
-24
30
-18
-6
-12
24
18
12
0
6
Tr a n s ve r s e d i s t a n c e f r o m c e n t r e o f p o l e (m)
H e i g h t of l owe s t c o n d u c to r to g r o u n d
525
10 50
Insulator
305
120 0
DIMENSIONS IN MILLIMETRES
S t a n d a r d 11kV Ve r t i c a l O f f s et - Ru r a l Co n s t r u c t i o n
M a g n e t i c f i e l d s t r e n g t h v s Tr a n s ve r s e d i s t a n c e f r o m p o l e
M a g f i e l d p e r 10 0A p e r c c t (m G )
8
7 6.7m
7.7m
6 9.7m
13.7m
5 21.7m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0
-30
-24
-18
-12
30
24
12
18
-6
6
Tr a n s ve r s e d i s t a n c e f r o m c e n t r e o f p o l e (m)
H e i g h t of l owe s t c o n d u c to r to g r o u n d
Po r c e l a i n
i n s u l a to r
10 50
305
10 50
305
DIMENSIONS IN MILLIMETRES
M ag n et i c Fi e l d S t r e n g t h Pr of i l e
3 3 k V O ve r h e a d Fl a t c o n s t r u c t i o n
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
14
12 6.7m
Magnetic Field Strength
7.7m
p e r 10 0 A m p s ( m G )
10
9.7m
8 13.7m
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
H e i g h t o f l ow e s t c o n d u c t o r t o g r o u n d
150
150
DIMENSIONS IN MILLIMETRES
M ag n et i c Fi e l d S t r e n g t h Pr of i l e
3 3 k V O ve r h ea d Tr i a n g u l a r Co n s t r u c t i o n
14
Magnetic Field Strength
12 6.7m
p e r 10 0 A m p s ( m G )
7.7m
10
9.7m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
8 13.7m
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
H e i g h t o f l ow e s t c o n d u c t o r t o g r o u n d
150
800
150
DIMENSIONS IN MILLIMETRES
9
Mag field per 100A per cct (mG) 8 6.7m
7.7m
7 9.7m
13.7m
6
21.7m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0
-30
-24
-18
-12
30
24
12
18
-6
6
Tr a n s ve r s e d i s t a n c e f r o m c e n t r e o f p o l e (m)
Height of lowest conductor to ground.
E a r thwi r e 150
1200
25° 900
1200
S hi e l di n g
angle
150
600
1400
Po r c e l a i n
600
i n s u l a to r
560 nominal
305
1600 nominal
DIMENSIONS IN MILLIMETRES
4
3
2
1
0
-30
-24
-18
-12
12
18
24
30
-6
6
Transverse distance from centre of pole (m)
Height of lowest conductor to ground
E a r thwi r e 150
1200
25° 900
1200
S hi e l di n g
angle
150
Po r c e l a i n
1400 i n s u l a to r
1200
560 nominal
305
1200
DIMENSIONS IN MILLIMETRES
M a g n et i c Fi e l d S t r e n g t h Pr of i l e
110 k V Co n c r et e Po l e S i n g l e C i r c u i t t r i a n g u l a r
16
Magnetic Field Strength
14 6.7m
7.7m
p e r 10 0 A m p s ( m G )
12 9.7m
10 13.7m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
21.7m
8
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
Height of lowest conductor to ground
100
2000
2305
4000
4305
6000
6305
DIMENSIONS IN MILLIMETRES
M a g n e t i c F i e l d Pr o f i l e (C a l c u l a t e d )
110 k V C o n c r e t e G a i n B a s e Po l e D o u b l e C i r c u i t - s a m e p h a s e d
20
Magnetic Field Strength 18 6.7m
16 7.7m
9.7m
p e r 10 0 A (m G )
14 13.7m
12 21.7m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
10
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n a l Pe r p e n d i c u l a r D i s t a n c e f r o m C e n t r e l i n e (m)
H e i g h t o f L owe s t C o n d u c t o r t o G r o u n d
E a r th
20 0 0
A A
19 0 0 23 0 0
B B
19 0 0
C C
DIMENSIONS IN MILLIMETRES
M ag n et i c Fi e l d Pr of i l e (Ca l c u l a te d )
110 k V Co n c r ete G a i n B a s e Po l e Do u b l e Cc t - r eve r s e p h a s e d
Magnetic Field Strength 20
18 6.7m
7.7m
16
9.7m
p e r 10 0 A (m G )
14 13.7m
21.7m
12
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
10
8
6
4
2
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n a l Pe r p e n d i c u l a r D i s t a n c e f r o m C e n t r e l i n e (m)
H e i g h t o f L owe s t C o n d u c t o r t o G r o u n d
E a r th
20 0 0
A C
19 0 0 23 0 0
B B
19 0 0
C A
DIMENSIONS IN MILLIMETRES
M a g n et i c Fi e l d S t r e n g t h Pr of i l e
110 k V S t e e l Towe r D o u b l e C i r c u i t - s a m e p h a s e d
25
Magnetic Field Strength
6.7m
p e r 10 0 A m p s ( m G )
20 7.7m
9.7m
13.7m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
15
21.7m
10
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
Height of lowest conductor to ground
4000 Earth
210 0
6550
A A
3800
6725
B B
3800
7020
C C
25750
23 9 6 2
4750
DIMENSIONS IN MILLIMETRES
M a g n et i c Fi e l d S t r e n g t h Pr of i l e
110 k V S t e e l Towe r D o u b l e C i r c u i t - r eve r s e p h a s e d
25
Magnetic Field Strength
6.7m
20
p e r 10 0 A m p s ( m G )
7.7m
9.7m
13.7m
15
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
21.7m
10
0
-20 -15 -10 -5 0 5 10 15 20
H o r i zo n t a l p e r p e n d i c u l a r d i s t a n c e f r o m c e n t r e l i n e (m)
Height of lowest conductor to ground
4000 Earth
210 0
6 5 50
A C
3800
6725
B B
3800
70 20
C A
25750
23 9 6 2
4750
DIMENSIONS IN MILLIMETRES
S E C T I O N 1 5 S E E K R O U T E A P P R O V A L S
There are many stakeholders which may need to be consulted for the overhead line. Formal
approvals may be required from some stakeholders. The stakeholder list may include:
(a) Road authorities (main roads and councils).
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 1 6 C O N D U C T R O U T E S U R V E Y
16.1 GENERAL
In the route survey the following information is typically identified:
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
C o n d u c to r i n n o r m a l
p o s i ti o n d u r i n g s till C o n d u c to r i n b l ow n
wi n d c o n di ti o n s o u t p o s i ti o n a t
n o m i n a te d w i n d
pressure
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Ws1 W b1 Wc W b1 Ws 2
Easement boundar y
Tr a n s m i s s i o n s t r u c tu r e
transmission line out of alignment with structures on the parallel transmission line.
C o n d u c to r i n b l ow n
C o n d u c to r i n n o r m a l o u t p o s i ti o n a t
p o s i ti o n d u r i n g s till n o m i n a te d w i n d
wi n d c o n di ti o n s pressure
Wp 2 Wb2 Wc 2 Wb2 Ws 2
Easement
boundary
Tr a n s m i s s i o n
s tr u c tu r e
As adjacent transmission lines can be of differing voltages, the minimum easement width
adopted is therefore the greater of the two calculations defined by Equation 16.2 or 16.3:
Weasement_1 = Ws1 + 2 Wb1 + Wc1 + Wp1 + Wc2 + Wb2 + Ws 2 . . . (16.2)
Where the individual terms in Equations 16.2, 16.3 and Figure 16.2 are defined as follows:
Ws1 and Ws2 = Horizontal electrical safety clearance blown out conductor to
easement edge
These dimensions represent the required safety clearance from blown-out conductor
to easement edge.
Wb1 and Wb2 = Maximum conductor blowout
These dimensions represent the maximum conductor blowout for both Transmission
Line 1 and Transmission Line 2.
Wc1 and Wc2 = Circuit/phase spacing
These dimensions represent the circuit/phase spacing that is dictated by the structure
body width.
phases on Line 1
The minimum required electrical clearance for safe and reliable operation of both
parallel transmission lines when conductors on Line 2 blow-out towards structures or
phases on adjacent Line 1.
Wi = Insulator swing
Allowance for insulator swing.
To determine an adequate spacing between adjacent transmission circuits, consideration
needs to be given to maintenance activities performed on one circuit, while the adjacent
circuits are energised. Maintenance work can utilise equipment such as cranes, large
elevated work platforms and helicopters and these also need to be accounted for in
determining appropriate centre-line separation and electrical clearances between adjacent
circuits.
(d) Low Growth Zone is the space below the clearance zone where vegetation is allowed
which will not have a height of more than a specified distance, depending on the
circumstance
R i s k m a n a g e m e n t zo n e
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
AP
AA
L ow g r ow t h
zo n e
BP BV
TABLE 16.1
URBAN AREAS—BARE WIRE CONDUCTOR CLEARANCE TO VEGETATION
Clearance zone Low growth zone
Type of powerline Vertical above Horizontal Vertical below Max vertical
conductor above conductor conductor above ground
1.0 m (urban)
Bare low voltage 2.0 m 1.0 m
2.0 m (rural)
4.0 m
2.0 m (urban)
Bare 11 kV, 33 kV 3.0 m 2.0 m
3.0 m (rural)
Typical clearance distances for low voltage Aerial Bundled Cable and Insulated Service
Cable are shown in Table 16.2.
TABLE 16.2
URBAN AND RURAL AREAS—LVABC AND INSULATED SERVICE CABLE
CLEARANCE TO VEGETATION
Clearance zone Low growth zone
Type of powerline Vertical above Horizontal above Vertical below Max vertical
conductor conductor conductor above ground
0.5 m (urban)
Aerial bundled cable 0.5 m 1.0 m
1.0 m (rural) 4.0 m
Insulated service cable 0.5 m 0.5 m 0.5 m
In New Zealand, the statutory requirements for the safe distance requirements between
vegetation are defined in the Electricity (Hazards from Trees) Regulations 2003. Vegetation
Growth Limit Zones are specified in Tables 1 and 2 of these regulations. The distances
should be measured under still air, everyday temperatures.
16.3.4 Special considerations for high reliability lines (e.g. transmission lines) or lines
with long spans
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
On high reliability lines (e.g. transmission lines), special consideration should be given to
extend the vegetation clearing to meet the higher levels of security and reliability for the
line. The extended clearance may include clearing to the sky (refer Figure 16.4) and
allowance for blow out of the conductors in the mid sections of the line. Allowance for
blowout will also apply for powerlines with long spans.
Cl e a r to s k y
AP AP
C C
Low g r ow th
BW zo n e BV
S E C T I O N 1 7 E L E C T R I C A L D E S I G N
TABLE 17.1
AMBIENT TEMPERATURES AND WIND SPEEDS FOR CONDUCTOR RATINGS
References
[1] Electricity Supply Association of Australia, D(b)5 (1998), Current Rating of Bare
Overhead Line Conductors published by Standards Association of Australia.
[2] MORGAN, VT. Thermal Behaviour of Electrical Conductors, Steady, Dynamic and
Fault-Current Ratings. Published in Brisbane by John Wiley and Sons Inc, 1991.
[3] ‘Standard Line Ratings Methodology for Transmission Network Services Providers’.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Overhead earth wires are used to shield the line from lightning strikes and are usually
installed on high reliability lines operating at sub-transmission and transmission voltage
levels. They are also installed on overhead distribution lines for short distances (typically
800 m) out of a substation to protect the substation equipment from damaging over
voltages. One earth wire is usually sufficient to cater for shielding flashovers on structures
below 20 m, but higher structures will need two earth wires to achieve effective shielding.
With a single earth wire, the shielding angle is usually in the range of 30° to 40°.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
where
lwood = Impulse strength of wood
linsulator = Impulse strength of insulator
When an overhead earth wire is installed on powerlines, generally a down lead is run to
earth to provide a low resistance path to ground. A low pole footing resistance not only
reduces the probability of lightning induced back flashovers but also offers the following
advantages:
(i) Reduces risk of injury to persons or animals due to rises in earth potential at the
structure and the surrounding soil.
(ii) Provides a low impedance path for earth faults to ensure there is sufficient fault
current to operate protection relays
17.4 TRANSPOSITIONS
Transpositions may be required on long power lines or heavily loaded lines to reduce the
level of negative sequence voltage unbalance and reduce the interference in adjacent
telecommunication circuits.
The receiving end voltage imbalance on high voltage lines is affected by the geometry of
the phase conductors and electrical loading on these conductors. The geometry of the phase
conductors will affect the reactance (inductive and capacitive).
The voltage unbalance is generated by high current loading in the unbalanced impedances.
Over long distances (typically greater than 20 km), this may lead to significant voltage
imbalance and lead to overloading of certain types of electrical equipment (e.g. motors).
To balance this effect, lines are transposed (electrically moved in their physical position) at
intervals along the line. A complete barrel roll consists of 2 transposition structures to break
the feeder into 3 approximately equal sections where each phase conductor occupies each
position. There may need to be 2 or more transpositions in a very long feeder.
Transpositions may reduce the electrical interference in adjacent metallic
telecommunications circuits.
TABLE 17.2
GUIDE FOR SELECTING INSULATORS IN
CONTAMINATED ENVIRONMENTS
ESDD range Minimum nominal specific
Contamination (see Note 1) creepage distance (see Note 2)
severity
g/mm 2 mm/kV
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Light 0 to 1.2 16
Medium 1.2 to 2.0 20
Heavy 2.0 to 3.0 25
Very heavy Above 3.0 31
NOTES:
1 ESDD is the equivalent salt deposit density.
2 Ratio of leakage distance measured between phase and earth over the r.m.s phase to
phase voltage of the highest voltage of the equipment.
3 Consideration should be given to increasing the creepage distances is areas where there
are long periods without rainfall or very close to the marine coast.
References
[1] AS 1824.2—1985, Insulation coordination, Part 2: Application guide.
[2] IEC TS 60815-1, Selection and dimensioning of high-voltage insulators intended for
use in polluted conditions, Part 1: Definitions, information and general principles.
[3] IEC TS 60815-2, Selection and dimensioning of high-voltage insulators intended for
use in polluted conditions, Part 2: Ceramic and glass insulators for a.c. systems.
[4] IEC TS 60815-3, Selection and dimensioning of high-voltage insulators intended for
use in polluted conditions, Part 3: Polymer insulators for a.c. systems.
[5] AS 4436, Guide for the selection of insulators in respect of polluted conditions.
17.6.3 Design for power frequency voltages (wet withstand requirement)
The line insulation should be designed to withstand the maximum voltage expected on the
line. Overhead powerlines usually operate at 1.1 per unit voltage to take into account the
effects of voltage drop with loading and there is the possibility that with capacitors on the
line, the powerline could operate up to 1.4 per unit which can be regarded as the maximum
dynamic overvoltage.
Maximum dynamic overvoltage can occur during faults and load rejection. (1.4 per unit is
for a three phase power system that is effectively earthed e.g. the neutral is earthed). The
wet power frequency withstand voltage of the line insulation should be selected to exceed
this maximum dynamic overvoltage.
17.6.4 Design for switching surge voltages
Switching surge over voltages up to 3 per unit peak voltage can arise when overhead lines
are switched. The extent of this overvoltage is dependent on (1) the point of voltage wave
when the line is switched, (2) the capacitance or amount of trapped charges on the line and
(3) other equipment connected to the line. When high speed auto reclosing is installed,
overvoltage can exceed 3 per unit voltage, particularly on transmission lines. In these cases,
it would be common to install surge arresters on the line to limit the over voltages to the
designed line insulation.
A good coverage on the design for switching surge is given in AS 1824.2. When designing
for switching surges, one of the parameters which is difficult to obtain is the switching
surge impulse voltage. There are 2 main types of electrical tests conducted on insulators;
one being the lightning impulse and the other the power frequency flashover (wet and dry).
Switching tests have been conducted in laboratories and the flashover voltages have been
inconsistent and found to be dependent on the shape of the surge, the type of electrodes and
the presence of earth planes.
In lieu of adequate test data on switching surges a good approximation for the switching
surge flashover voltage is 0.8 times the lightning impulse flashover voltage.
The insulator parameter that determines the insulator impulse performance (i.e. switching
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 17.3
11 kV INSULATOR TYPES AND PERFORMANCE
Wet power
Minimum failing Minimum creepage Dry lightning
String insulator units frequency
load, kN distance, mm impulse, kVp
withstand, kVp
Clevis tongue—Normal 70 280 95 40
Clevis tongue—Fog 70 360 95 40
Ball socket—Normal 70 280 95 40
Ball socket—Fog 70 360 95 40
11 kV insulators
Pin—Normal 7 180 95 30
Pin—Fog 7 360 95 30
Shackle type SH.11 22 180 95 30
18 (cantiliver)
Line post—Tie top 425 150 38
6 (axial)
12 (cantiliver)
Line post—Clamp top 425 150 38
18 (axial)
Standoff line post with 12 (cantiliver)
425 150 38
Trunnion clamp 18 (axial)
8 (cantiliver)
Station post 360 95 38
1.2 (kNm torsional)
8.25 Ordinary
Mechanical
Load (OML)
Composite long rod 360 95 38
25 Maximum
Mechanical
Load (MML)
TABLE 17.4
33 kV INSULATOR TYPES AND PERFORMANCE
Wet power
Minimum failing Minimum creepage Dry lightning
33 kV insulator units frequency
load, kN distance, mm impulse, kVp
withstand, kVp
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Example:
Select a suitable disc insulator string for a 33 kV line subject to extreme contamination.
Normal disc profiles have a creepage length of 300 mm and fog discs of 400 mm.
System highest voltage = 36 kV
Minimum nominal specific creepage distance = 31 mm/kV for extreme contamination
Required creepage distance for 36 kV = 1116 mm
Number of normal discs = 1116/300 = 3.72 → 4 discs
Number of fog discs = 1116/400 = 2.79 → 3 discs
Select a suitable disc insulator string for a 275 kV line subject to heavy contamination. Use
normal or fog disc profiles where the creepage length is 300 mm normal and 400 mm for
fog.
System highest voltage = 300 kV
Minimum nominal specific creepage distance = 25 mm/kV for heavy contamination
Required creepage distance for 300 kV = 7500 mm
Number of normal discs = 7500/300 = 25 discs
Number of fog discs = 7500/400 = 18.75 → 19 discs
17.6.6 Insulator mechanical design
The loads on an insulator can be calculated using the Limit State methodology outlined in
Section 2 of AS/NZS 7000. There are three states for the mechanical design of insulators
identified in AS/NZS 7000, these being the—
(a) Everyday load;
(b) Serviceable wind load; and
(c) Ultimate strength or failure containment load.
The guidelines for the strength factor for insulators are given in Table 6.2 of AS/NZS 7000.
wire coming in contact with live conductors. Mitigations methods for either scenario are
given below:
(a) Conductor failure protection
Stay wires within 2.4 m of the ground should be earthed in accordance with Clause 11
10 of AS/NZS 7000 unless they are insulated by means of an insulator placed in the
stay wire.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The stay wire insulator should be placed so its lowest point is not less than 2.4 m
above the ground. The stay wire insulator should also be placed so it is lower than the
lowest conductor, excluding any underslung earth wire.
The wet flashover voltage of the insulator should be 50% greater than the highest
conductor on the pole phase to earth voltage.
(b) Broken stay wire protection
A failed stay wire can fall onto live conductors and bring an energized stay wire
closer than 2.4 m in height from the ground. Figure 17.1 shows various broken stay
wire scenarios.
To protect for these scenarios, more than one stay wire insulator may be required.
21. 5 m p o l e 21. 5 m p o l e
B r o ke n s t ay w wii r e c o u
ull d B r o ke n s t ay wwii r e 8.5
p ote nti a ll llyy b e live a n d u l ate d - s afe
i n s ul
a c c e s s iib
b l e to tthh e p u b lilic
18. 5 m p o l e 18. 5 m p o l e
B r o ke n s t ay wwii r e
B r o ke n s t ay wwii r e i n s u
ull a
ate
te d 5.9 5.5
i n s ul ate d - s afe
th e r efo r e a l ow r i s k to th e p u b li c
DIMENSIONS IN MILLIMETRES
Conductive structure—a structure made from conductive materials e.g. steel and steel
reinforced concrete. The structure may be a stay wire and stay anchor where no stay
insulator is used (or where an electrically inadequate stay insulator is used).
Non-conductive structure—a structure made from non-conductive materials e.g. timber and
fibre reinforced polymer.
Earth potential rise (EPR)—the rise in potential (voltage) of an earthing system used to
dissipate fault currents to remote earth, also known as ground potential rise (GPR) in
Britain.
17.8.3 Non-conductive structures
A non-conductive pole does not need to be earthed, in which case there is no step or touch
problem. When a non-conductive pole is earthed then the down lead is usually insulated so
that the touch potential problem is mitigated. Insulation need only extend from below
ground to 2.4 m above ground. The level of insulation should be adequate to withstand the
prospective touch potential that exists under fault conditions. A step potential hazard may
still exist but this can be mitigated by extending the insulation below the surface as
indicated in Table 17.5 for uniform soil resistivity.
TABLE 17.5
MAXIMUM STEP POTENTIAL FOR 2.5 m VERTICAL
ELECTRODE—PARTIALLY INSULATED
Depth of insulation below ground Max. step potential (%EPR)
0.0 m 68%
0.3 m 16%
0.6 m 9%
0.9 m 5%
RS RS RS
RP RP RP
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
For an infinite number of poles with identical footing resistance and an infinite number of
equal span lengths, the equivalent resistance of the earthing system (ladder network) is:
2
RS ⎛R ⎞
R EQ = + ⎜ S ⎟ + RS R P . . . (17.2)
2 ⎝ 2 ⎠
where
RS = the resistance of each span of overhead earth wire (series)
RP = the footing resistance of each pole (parallel)
The earth fault current IF is split as shown in Figure 17.3. The current flowing to earth via
the faulted pole of footing resistance RP is given by Equation (17.3).
IF
RA If RP RB
⎛ RAB ⎞
I f = I F ⎜⎜ ⎟⎟
⎝ RP + RAB ⎠
. . . (17.3)
R R
RAB = A B
RA + RB
where
IF = the fault current
If = the portion of fault current flowing to ground via the pole earthing
RA, RB = the equivalent resistance of the earthing network either side of the faulted
pole
For an earth fault at the first pole outside a substation, RA is assumed to be the resistance of
the substation earth grid and RB can be estimated using the equivalent resistance (REQ ). The
first pole may be within the influence zone of the substation grid and its resistance may be
lower than predicted and difficult to measure.
For an earth fault several spans away from a substation, RA and RB can be estimated using
REQ.
Figure 17.4 shows that the size of the overhead earth wire can significantly influence REQ.
Figure 17.5 is based on the assumption that the fault occurs remotely from the ends of the
line and that RAB = REQ/2. In this instance, the portion of the fault current (If/IF) conducted
to ground via the faulted pole is influenced by the resistance of the overhead earth wire, the
span length and the footing resistance of each pole. Sizing the overhead earth wire is the
single most important decision for mitigating the step and touch potential hazard created by
high fault currents in a conventional network. Neutral earthing resistors and other
techniques mentioned in U8.6 of AS/NZS 7000 may be used to limit earth fault currents.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
1.4
Ladder
Resistance
1. 2
R S - r e s i s t a n c e o f s p a n o f O H E W (Ω )
20 Ω
1.0
18 Ω
16 Ω
0.8
14 Ω
12 Ω
0.6
10 Ω
8 Ω
0.4
6 Ω
4 Ω
0.2
2 Ω
0.0
0 10 20 30 40 50 60 70 80 90 10 0
R P - p o l e f o o t i n g r e s i s t a n c e (Ω)
20.0
30 %
25 %
16.0
R E Q - l a d d e r r e s i s t a n c e ( )
20 %
15 %
12.0
10 %
8.0
5%
4.0
If / I F
0.0
0 10 20 30 40 50 60 70 80 90 100
R P - p o l e f o o t i n g r e s i s t a n c e ( )
where
If = the portion of the fault current flowing to ground via the pole earthing
RP = d.c. or low frequency footing resistance of the pole earthing system
The proportion of the fault current flowing to ground (If) via any pole may be determined
by any of the following methods:
(a) A field measurement (most accurate).
(b) A detailed computer model.
(c) An estimate such as given by Equation (17.3) (least accurate).
The footing resistance requires:
(i) A field measurement (most accurate when done correctly).
(ii) An estimation based on electrode geometry and soil resistivity (least accurate).
The value of the footing resistance can be measured using the fall-of-potential method.
Erroneous measurements are possible so it is important that competent personnel are used
where required. Seasonal variations in measurements will occur depending upon ground
moisture and these need to be considered when assessing the hazard.
The fault current (IF) is usually calculated from a computer model of the network which
includes future capacity increases. The fault impedance is the parallel resistance of RA, RP
and RB plus the arc resistance however assuming zero impedance will give higher fault
currents. Single phase to ground faults and double phase to ground faults should be
investigated. Whilst a three phase to ground fault or a phase to phase fault may result in a
higher fault current, it does not flow to ground.
It is also possible to measure step and touch potentials using a four terminal earth tester.
Refer to Figure 17.6 and Figure 17.7. The current probe needs to be outside the influence of
the pole earthing system and away from uninsulated buried metallic objects. Any overhead
earth wire should be disconnected for testing unless specialised equipment is employed.
C o n d u c tive p o l e o r d ow n l e a d
V
R A PPA R E N T = V
I
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
V TO U C H = I f x R A PPA R E N T
1m
LEGEND:
R APPARENT = apparent resistance as measured using an earth tester
V TOUCH = prospective touch potential with current If flowing to earth
V STEP = prospective step potential with current If flowing to earth
V = voltage measured internally by the earth tester
I = current measured internally by the earth tester
C o n d u c tive p o l e o r d ow n l e a d
V
V R A PPA R E N T =
I
V S T E P = I f x R A PPA R E N T
1m
TABLE 17.6
STEP AND TOUCH POTENTIALS FOR VARIOUS DESIGNS
Design type* Depth to horizontal Circumscribing Max. touch Max. step
electrodes circle radius potential potential
m m %EPR %EPR
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Each design has a vertical electrode to a depth of 2.5 m to simulate either the butt earth of a
non-conductive pole or the foundation depth of a conductive pole. The soil is assumed to be
of uniform resistivity. The touch distance and the step distance are taken as 1 m.
Any attempt to improve the footing resistance should be directed vertically and not
horizontally otherwise there will be a transfer of unwanted potential that will alter the
tabulated results. This can be achieved by using earth stakes at the vertices of the grading
ring.
S E C T I O N 1 8 S T R U C T U R E S U I T E
18.1 GENERAL
A suite of structures need to be selected or developed appropriate for the line route and
conductor. The structure suite would generally consist of in-line, small angle, heavy angle,
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
tee-off and termination structures. The duty of the structures may be determined by:
(a) Design working life.
(b) Material type.
(c) Number of circuits.
(d) Economics.
(e) Environmental (termite, acid sulphate soils).
(f) Height (underbuild, clearances, vegetation).
(g) Conductor tension.
(h) Wind and weight span (corridor width).
(i) Terrain.
(j) Stayed structures.
(k) Constructability.
(l) Maintenance (live line or dead line).
(m) Structure top geometry (electrical clearances, lightning performance, EMF and the
crossarm).
(n) Line equipment (electrical and mechanical design of insulators, hardware).
S E C T I O N 1 9 L A Y O U T D E S I G N P R O C E S S
19.1 GENERAL
The layout design process involves the survey of the line route and capture of all features
adjacent to the proposed centreline of the line; selection of a suitable suite of structure
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
types, the location of these structures on a line centre-line , the profiling of the conductors
and the calculation of wind, weight and ruling spans and structure heights. The layout
design should ensure the following outcomes are met:
(a) Acceptable electrical clearances to structures and ground for the voltage of line.
(b) Maximum adjacent span ratio selected to ensure longitudinal loading on insulators
and supports do not cause failures under adverse environmental conditions. The
adjacent span ratio is typically less than 3:1 (where there is free movement of
conductors on insulators) or 2:1 (where there is no free movement of conductors on
insulators)
(c) Weight to wind span ratio greater than 0.7 to ensure there are acceptable electrical
clearances on structures under wind conditions.
(d) Acceptable clearance of structures and conductors alignment to objects (e.g.
buildings, swimming pools, billboards).
(e) Set back on roads appropriate to the speed of the road. These set backs can be
reduced where there are kerbing or natural barriers (drain or mounds).
(f) Suitable foundation integrity (e.g. avoid excessive side slopes).
(g) Co-ordination with other authorities and services (road, rail, water,
telecommunication and aerial operations).
(h) Provide data files and profile details of the line construction details sufficient to
enable the construction of the line.
Designers need to ensure that the ground and environmental conditions are factored into the
layout process and need to consider for example the existence of steep slopes, existing and
future services, heritage sites, sensitive environmental areas, etc.
The weight span Lv and the wind span Lh can be measured from the longitudinal profile
drawing (Figure 19.1) and the ratio Lv/Lh calculated. Another method of determining Lv/Lh
for structure B (in Figure 19.1) is:
Lv 2bCv
R= =1+ (Based on the parabola) . . . (19.1)
Lh L1 L2
where
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
When the conductor supports of three consecutive structures are co-linear i.e. b = 0 then
Lv/Lh = 1. When b < 0 then Lv/Lh < 1 and this is the situation where insulator swing may
violate electrical clearances under transverse wind. Deciding whether Lv/Lh is greater than
or less than one is easily checked by using a ruler on the profile drawing to determine
whether ‘b’ is positive or negative.
C
B
Lv
L1 L2
2Lh
maximum allowable insulator string swing angle from vertical for the light
φ =
moderate or high wind condition
Weights, which effectively increase the weight span, can be added to the conductor to limit
the swing angle, however consideration needs to be given to their effect on electrical
clearances. The weights may be placed on the conductor but away from the structure to
preserve original clearances to the superstructure. In this case damper placement will be
relative to the outboard weight clamp instead of the conductor suspension clamp. Except
when used on bridging strings, weights are usually used to remedy layout errors.
A minimum allowable ratio (R′) of weight to wind span will be generated for each wind
condition, typically three. This is done for each suspension structure type and conductor
combination used on the line. When spotting suspension structures manually, it is
impractical to calculate the weight span under three wind conditions and check the spotted
ratio (R) against the allowable ratio (R′) for each trial structure location. To alleviate the
effort, it is much simpler to define a single, minimum ratio for each structure type and
conductor combination. For convenience, the weight span at the maximum operating
temperature is used because this condition is used to ensure adequate ground clearance
during the layout phase. In some instances an ice condition may govern the design.
usually small. The smallest ratio can be used for a given layout design. This will lead to
slightly conservative insulator swing angles.
R2 ≥ R2′
Cv2
1+ (R1 − 1) ≥ R2′
C v1 . . . (19.4)
C v1
R1 ≥ 1 + (R2′ − 1)
Cv2
where
the spotted weight span to wind span ratio at the maximum operating
R1 =
temperature
R2 = the allowable weight span to wind span ratio under the design wind condition
Since there may be up to three wind conditions to check, then the spotted weight span to
wind span ratio (R) should be greater than the maximum value derived using Equation 19.4
for all of the design wind conditions.
C max
Rmax, light ≥ 1 +
Clight
(
′ −1
Rlight )
C max
Rmax, moderate ≥ 1 + (Rmoderate
′ − 1)
C moderate . . . (19.5)
C max
Rmax, high ≥ 1 +
C high
(
′ −1
Rhigh )
R = max ( Rmax, light , Rmax, moderate , Rmax, high )
where
C max = catenary constant at the maximum operating condition
Clight vertical component of catenary constant at the light, moderate and
C moderate = high wind conditions for the layout section based on the design
Chigh tension and assumed ruling span
R′light minimum allowable ratio of weight span (at light, moderate or high
R′moderate wind) to wind span required for the suspension structure and
=
R′high conductor combination to limit insulator swing angles
(Equation 19.2)
R max, light minimum layout ratio of weight span (at maximum operating
R′max, moderate = temperature) to wind span required to limit the suspension insulator
R′max, high swing angles at light, moderate and high winds
minimum layout ratio of weight span to wind span that satisfies the
R = suspension insulator swing requirements under all design wind
conditions
When manually spotting, this simple check is performed for each trial location of a
suspension structure that has no deviation angle. Modern layout software checks the
insulator swing for all phases and their respective deviations, for several weather cases and
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
conductor ages. The software can be used for asymmetrical structures (e.g. wishbone and
flying angle) where a minimum and a maximum swing angle are specified. In these cases
the orientation of the structure is important. Calculations are performed with the transverse
wind direction from both sides of the line.
During the spotting phase the conductor system is modelled using the ruling span
assumption, i.e. equal tensions in all spans. However analysis (checking) can be done using
a finite element model with either stiff or flexible structures. Suspension insulator weight,
wind area and length are also accounted for.
19.8 TERRAIN
A 3-dimensional GIS-type (Geographic Information System) terrain model is normally used
to provide flexibility and compatibility with modern electronic surveying equipment and
mapping techniques.
Terrain and longitudinal profile data is normally collected electronically (total station,
photogrammetry, lidar, etc.) and subsequently downloaded into ASCII terrain files. A
terrain model normally includes information about the location and type of surface terrain
or above-terrain points. Above terrain points are normally referred to as ‘obstacle’ points.
There are two ways to describe an obstacle point, either—
(a) by its height above a ground point and the coordinates of that ground point; or
(b) locate the top of the obstacle directly with its own coordinates.
Before generating a terrain, one should decide on broad categories of terrain or obstacle
points which have unique requirements. These requirements include minimum code
clearances to be met above or to the side of the points as well as symbols to be used to
display these points on the final drawings.
19.9 CLEARANCES
If a point is an obstacle described by its height above the ground, clearances is determined
by the distance between that point and the ground. If a point is an aerial obstacle, vertical
clearances are required both above and below that point.
If the feature code is a ground point that will be used to draw a ground profile or a point
that should be by-passed when drawing the ground profile (for example the top of an
obstacle), minimum required vertical clearances above (and below for aerial points) and
minimum horizontal clearances are required to the side of these points for the voltages
selected.
(c) Key features to be surveyed (fences, gates, roads, trees, railway lines, existing
services).
(d) Land use and limitations/constraints.
(e) Centreline and line deviations.
(f) Coordinate system and height datum.
(g) Vegetation height/type.
(h) Side slope constraints.
19.12 ALIGNMENT
The centreline alignment (or alignments) of a typical line project need to be defined before
any layout design can be performed. In the plan view, the alignments consist of straight line
segments between PI points (points of inflection). With an XYZ terrain model, the
alignments are defined in the plan view by selecting the PI points.
Once there is at least one alignment defined, it is possible to create—
(a) other independent unconnected alignments;
(b) alignment branches; or
(c) alignment loops.
When multiple alignments have been obtained, it is then possible to build lines on all.
Values for the maximum offset for profile view (MOPV) and the maximum offset for
centre-line ground profile (MOCGP) are then selected. All ground or obstacle points within
the MOPV (measured from the centre-line) are displayed with the appropriate symbols in
the various profile views, whether on screen or on a sheet of paper. Points outside the
MOPV are not displayed in the profile views. In addition, any structure or wire with an
offset greater than MOPV will not be shown in the profile view.
The centre-line is defined in the plan view as the collection of straight line segments
connecting alignment corners. The centre-line ground profile is theoretically the
intersection of vertical planes going through the centre-line and the ground. However,
because the terrain data may be defined at discrete points within the line corridor, there is a
need for rules to define how the profile is displayed on drawings. The ground profile line
displayed is a line that joins all ground points within a specified offset from the centre-line.
That offset (MOCGP), is for two widths. The points are joined in ascending order of
stations. For example, if one selects a MOCGP of 3 m, then the profile line will pass
through all the points within 3 m of the centre-line.
If there is significant side slope (perpendicular to the line) the line profile may look jagged
when it joins points of significantly different elevations on alternate sides of the centre-line.
If the jaggedness of the profile line is objectionable, one may draw separate side profiles.
One may also generate additional interpolated centre line and side profile points using a
Triangulated Irregular Network (TIN) model of the terrain or by using breaklines.
profiles, to find the elevations of arbitrary points or to locate points at the intersection of
latticed tower legs or guys with the ground.
conductors with modern equipment, i.e. to create a XYZ terrain model. A limited and less
accurate alternative is to obtain the locations of terrain, structure and conductor points from
existing drawings or from scanned images of these drawings. These drawings can be
displayed in the background of the profile view. Once the drawings are properly positioned
in the profile view, PFL location points can then be digitized.
It is generally not recommended to use existing drawings as templates for building models
of older lines because of the potential accumulation of errors at each step of the process.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The original survey may have been inaccurate. The nature of the terrain below and in the
vicinity of the line may have changed over the years. The as-built locations of the conductor
attachment points may not be well reflected by the drawing. The catenary curves showing
the positions of the conductors at a stipulated temperature may have been based on crude
assumptions not reflecting actual sagging conditions and creep effects. These curves may
have been drawn with templates not adjusted to the actual ruling spans in the lines. The
digitizing process itself, through scaling and clicking on lines of finite thicknesses, will also
add errors.
However, there are cases where one would want to quickly build a line model on top of a
raster drawing. Care should be taken so that the scanned drawing clearly shows labelled
station and elevation axes, with the station axis ideally labelled with true stations, as well as
line angle locations.
Assumptions:
(a) The analysis involves a single wire (conductor), in one or more spans, between dead
ends, i.e. it is assumed that there is no interaction between the wire and other phases
of the same electrical circuit or conductors in other circuits.
(b) The horizontal component of tension along the conductor in all the spans of the
tension Section between dead ends is constant, i.e. all intermediate supports are
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
assumed to be perfectly flexible in the longitudinal direction. This may not be very
accurate in the case of rigid post insulators and short suspension insulators subjected
to large vertical loads. It is usually considered sufficiently accurate in view of all the
other uncertainties and approximations associated with line design.
(c) Based on the horizontal component of its tension, the geometry of each span is
determined as the equilibrium configuration of a span is always a ‘catenary’. The
catenary lies in the plane defined by the chord length of the span and the resultant
wire load per unit length, UR, which is assumed to have constant magnitude and
direction at any point along the conductor in a given span. UR is based on the
direction of the chord (a straight line), even though actual points along the conductor
are below the chord. Without wind, UR is vertical and oriented downward. With
wind, UR is not vertical and it defines the swing angle of the span plane.
The catenary constant is the ratio H/UR, where H is the horizontal component of tension
and UR the load per unit length of conductor. H is constant throughout the span.
The ruling span is calculated using:
For level spans—
n
∑ L3i
i =1
Lr = . . . 19.6
n
∑ Li
i =1
n
∑ L4i
i =1
Lr = . . . 19.7
n
∑ Ii
i =1
where
Ii = L2i + hi2
the chord length between the supports of span i
Li = the horizontal span length of span i
hi = the support height difference of span i
n = the number of spans in the section between strain structures
For a single level, dead-end span the ruling span is Lr = L. However, for a single inclined
dead-end span, Lr = L2/I.
Limitations:
(i) All the spans need to be subjected to the same loading, i.e. this level of modelling is
not capable of analysing situations with different ice thicknesses in various spans.
(ii) There is no way to study the effect of slack re-allocation due to moving a conductor
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
19.19.3 Finite Element (FE) modelling accounting for interaction between wires
This modelling is similar to modelling above, except that all the wires between two limiting
infinitely rigid dead end structures (the ends of the model) are analysed simultaneously,
thus accounting for the possibility of some longitudinal interaction between the phases. If a
termination structure is being checked for strength with potentially different loads on each
side, the limiting termination structures are at the ends of the tension sections to the left and
to the right of the structure being checked. If not a limiting dead end, a termination
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
structure is treated as any other structure as far as its flexibility is concerned. The
interaction between the conductors is accounted for through the flexibility matrices of the
supporting structures between the limiting terminations. With the above model, it is not
necessary to consider structure flexibility (unless two flexibility numbers are specified at
each support).
With this level, software determines a flexibility matrix at each structure. A flexibility
matrix is just a device to represent the behaviour of a flexible structure without having to
model it in its entirety when it is connected to supported wires (Peyrot and Goulois, 1978).
Structure flexibility matrices may be determined automatically for Finite Element
structures. Therefore, there is no additional complexity required if already using FE
structures. Flexibility matrices include flexibility coefficients. Consider two insulator
attachment points, I and J. These points can arbitrarily be located in space, for example ‘I’
could be a ground wire attachment point and ‘J’ the structure attachment point of the
insulator supporting the lower left phase of a double circuit tower. If a single unit
longitudinal load is applied at point I, the corresponding longitudinal displacement J, I at
point J is the flexibility coefficient F.
For a transmission structure with N attachment points, the I, J N × N symmetrical matrix
that includes all the coefficients F is called the structure longitudinal flexibility matrix. If,
instead, there is a restriction to longitudinal loads and longitudinal displacements, and
consideration given to both transverse and longitudinal unit loads and their corresponding
displacements, a flexibility matrix of size 2N × 2N is generated. This is in fact the
flexibility matrix used by the computer software at each structure location when the wire
system is modelled at FE considering wires.
Usefulness and practicality of method:
This method only works with FE structures, as the flexibility matrices for all the structures
are automatically re-calculated by programs when needed. FE with conductors has all the
advantages of FE without conductors without its limitations: it accounts for the interaction
between the conductors and does not require an assumption of a flexibility value.
However, there will be an order of magnitude more computer time when using FE as
compared to RS. This modelling is the recommended method when there are longitudinal
load issues in lines supported by flexible poles and frames.
Assumptions and limitations:
If a termination structure is being checked for loads or is part of a tension section for which
tensions are calculated, its flexibility matrix, if available, is taken into account.
(a) Interaction between the conductors is modelled through structure flexibility matrices
which are inherently linear. Thus the nonlinear effects of extremely flexible poles and
frames (which may account for 10% to 20% of the stresses) cannot be accounted for.
Guyed structures, which are also highly nonlinear, may not exhibit the correct
behaviour.
(b) The effect on the equilibrium of the system of the wind load applied directly to the
structures cannot be taken into account.
S E C T I O N 2 0 S T R UC T U R A L A N D
M E C H A N I C AL D E S I G N
The layout design will provide the appropriate wind spans and tensions required by the
structures.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The structure strength is determined by the limit state loads—the loading conditions and
load factors are contained in Table 7.3 of AS/NZS 7000.
For distribution poles, the relevant loading conditions are:
(a) Maximum loading (wind, snow and ice).
(b) Everyday condition sustained load.
(c) Failure containment.
(d) Maintenance.
S E C T I O N 2 1 D E S I G N V E R I F I C A T I O N
The line design process is an iterative process and requires final technical review and
verification. The main items include:
(a) Electrical clearances.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 2 2 D E T AI L D E S I G N
D O C U M E N T AT I O N
The documentation submitted as part of the detail design package may include:
(a) Structure schedule.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 2 3 C O N S T R U C T I O N A P P R O V A L S
The local network project owner may need to certify that the design is acceptable for
construction. This may include checking that the detail design documentation is complete.
The construction approvals may include:
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
(a) Payment of appropriate fees (e.g. workplace health and safety, EPA).
(b) Obtaining traffic and road closure permits.
(c) Obtaining vegetation permits.
(d) Specific site induction training.
(e) Engagement of Authority inspectors to supervise the work.
S E C T I O N 2 4 D E S I G N S U P P O R T F O R
C O N S T R U C T I O N
The designer may need to provide support during construction. This may include:
(a) Structure relocation.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 2 5 A S - C O N S T R U C T E D
D O C U M E N T AT I O N
The designer may need to provide assistance for as-constructed documentation. This may
include:
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 2 6 S C O P E O F P R O J E C T
26.1 GENERAL
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
A new single circuit 132 kV line is required to be designed and constructed in a coastal area
in Australia in Region A (1 to 7 according to AS/NZS 1170) for a 50 year design working
life and line security level of 1. The line route goes across 10 km of private property on a
30 m wide easement and a further 1 km along a council road to a new substation. Concrete
poles are proposed for the section along the easement and wood poles along the road
reserve. The intermediate concrete poles utilize a steel crossarm construction (refer
Figure 26.1) with suspension insulators and provide a climbing corridor. The wood poles
utilize line post construction with no climbing corridor (refer Figure 26.2).
10
Ear thwire shielding angle 40°
28 0 0
1910
110 0
Crossarm A
20 º low wind 28 0 0
swing 10 0 Pa
9 fog t ype
insulator s = 1715
3
ine 0
el 0
Liv n 11
o
R
A/ Crossarm C
M
370 0 8 ap ai
p r n te
oa na
Live line ch nc
A / R of f 9 0 0 12 e
4 00
9
7 1
950
Hand reach 50 0
Crossarm B 130 0
35º moderate
wind swing 300Pa
70º high wind
swing 500Pa
ELEVATION
11
1000 R1700
6 1000 Square
7
climbing corridor
Hand-reach
clearance 1000 Square
6 climbing
envelope corridor
7
R1700
Hand-reach
PL A N - L AT T I C E TO W E R clearance PL A N - P O L E
envelope
DIMENSIONS IN MILLIMETRES
100
2000
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
2305
4000
4305
6000
6305
DIMENSIONS IN MILLIMETRES
C o n c r e te Po l e s
1 2 3
C o n d u c to r
4
15C 5% CBL
Wo o d Po l e s
5
C o n d u c to r
15C 5% CBL
6
Substa
ati
ti o n
The summer noon conductor ratings are based on the following parameters:
(a) Ambient temperature 35°C (this is a probabilistic value and may differ from the
temperature used for line components).
(b) Wind speed 1.0 m/s.
(c) Wind Direction 90° to the line.
(d) Emissivity 0.85 (industrial weathered).
(e) Absorptivity 0.85.
To calculate the summer emergency rating, increase the wind speed from 1.0 m/s to 2.0 m/s.
26.3.4 Maximum conductor temperatures
The maximum conductor temperature for the conductor is:
For ACSR and AAAC conductor—90°C
AS 1531 specifies requirements for aluminium conductors.
26.3.5 Fault current and clearing times
26.3.5.1 General
The maximum 3 phase and phase to ground fault current on the line is 20 kA. The Circuit
Breaker (CB) fail clearing time is 250 ms. In this project, there is auto-reclose facility on
the CB.
26.3.5.2 Earthwires
The earthwires will be an OPGW with a conductor diameter of 14.3 mm. This is a standard
size with a fault current rating of 100 kA2s.
26.3.6 Lightning performance
The desired lightning performance of the single circuit line is 2 outages per 100 km per
year. The keraunic level to be used in the calculations is 30 thunderdays per year.
26.3.7 Earthing resistance
The footing resistance distribution for the line will be:
(a) 90% less than 10 Ω.
(b) 98% less than 20 Ω.
The line is situated in a moderately contaminated area, being coastal where the required
creepage length is 25 mm/kVp-p (IEC 60815).
The insulation must also withstand a maximum dynamic overvoltage of 1.4 pu.
26.3.9 Switching surge performance
The maximum design switching surge is 3.0 pu. The design outage rate is 1 outage every
1000 switching operations.
26.3.10 Insulation
The insulation for the concrete pole section is ceramic disc insulation and in accordance
with the requirements of AS 4398 and AS 1154.
The insulation for the wood pole section is composite line post insulation.
26.3.11 Maximum surface voltage gradient
The maximum surface voltage gradient on the conductor to ensure RIV and audible noise
will not cause annoyance to the public is 16.0 kV/cm.
26.3.12 Maximum electric and magnetic field levels
Electric field calculations is calculated using a voltage of 145 kV and lowest conductor
height of 11 m.
Magnetic fields should be minimised where possible with the lowest conductor height
assumed to be 11 m.
26.3.13 Electrical clearances
Electrical clearances for 132 kV are found in AS/NZS 7000 as detailed below:
(a) Impulse and switching clearance under moderate wind (Table 3.4) .............. 1300 mm.
(b) Power frequency clearance under low wind (Table 3.4) ................................. 500 mm.
(c) Maintenance approach (autoreclose on) under low wind (Table 3.5) ............ 1100 mm.
(d) Live line working (autoreclose off) under low wind (Table 3.5) ..................... 900 mm.
(e) Hand reach, centre of pole to power frequency envelope (Appendix FF) ...... 1300 mm.
The minimum air gap separation from conductor to earth must be 1.4 m. The minimum
phase to phase separation must be 1.9 m. No live line or maintenance approach clearances
are required on the pole.
26.3.14 Mechanical design
The line is located in a coastal area in Region A according to AS/NZS 1170. The design
working life is 50 years and the relevant wind speeds are given in Table 7.1. The design
wind loading (ultimate wind load) on the concrete and wood poles to be a minimum of
1300 Pa, and on the conductors, 900 Pa.
Appropriate component strength factors must be used to size the structural components.
26.3.15 Corrosion resistance of structures and materials
For this project all steelwork to be hot dipped galvanised to AS/NZS 4680 with a minimum
coverage of 600 g.m-2. The concrete poles can be non-prestressed or prestressed. Stays to
use a galvanized stay rod and be installed with a guy insulator. In soils regarded as
corrosive additional protection must be provided to the stay rod. (such as concrete
encasement and anticorrosive wrapping). All earthing ground material is copper for the
concrete and timber poles.
26.3.16 Foundations and stays
The foundations to be designed to relevant Standards or Codes to meet the static and
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
A conductor ratings program has identified the following conductors which achieve this
rating with the following maximum temperatures.
(a) 19/4.75 AAC Taurus at 80°C.
(b) 19/4.75 AAAC Oxygen at 80°C.
(c) 30/7/3.50 ACSR/GZ Lime at 85°C.
The characteristics of these conductors are given in Table 26.1.
TABLE 26.1
CHARACTERISTICS OF CONDUCTOR TYPES
AAAC1120 ACSR/GZ
Characteristic AAC Taurus
Oxygen Lime
Mass (kg/m) 0.925 0.925 1.32
Diameter (mm) 23.8 23.8 24.5
CBL (kN) 50.9 73.6 121.0
Modulus E (GPa) 56 65 80
2
CSA (mm ) 336.7 336.7 356
DC Resistance (ohms/km) 0.0857 0.0884 0.10
TABLE 26.2
SAGS FOR VARIOUS SPANS AND TENSIONS
Hp = Hg + Mg + Msag + Dp + De
where
Hg = is required ground clearance
Mg = ground clearance margin (allow for errors)
Msag = maximum sag at mid span
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 26.3
ASSUMED PARAMETERS FOR DETERMINING POLE HEIGHT
Parameter Concrete pole Wood pole
Hg 6.7 m 6.7 m
Mg 0.5 m 0.5 m
Dp 3.7 m 2.0 m
De 3.7 m 2.0 m
The calculated height of poles is given in Table 26.4 for the concrete and wood pole
sections.
TABLE 26.4
HEIGHT OF POLES ABOVE GROUND FOR CONCRETE
POLE AND WOOD POLE SECTIONS
Section AAC AAAC1120 ACSR/GZ
Concrete pole 27.6 24.2 23.0
Wood pole 18.0 16.3 15.7
NOTE: Maximum sag is taken at maximum operating temperature.
The length of pole needs to allow for the embedment depth. As an approximation, the
embedment depth = 10% of pole length +0.8 m
The estimated length of pole is given in Table 26.5.
TABLE 26.5
APPROXIMATE LENGTH OF POLES FOR CONCRETE POLE
AND WOOD POLE SECTIONS
Section AAC AAAC1120 ACSR/GZ
Concrete pole 31.5 28.0 26.5
Wood pole 21.0 19.0 18.4
lower the availability. It is therefore necessary to keep the spans sufficiently short to keep
the pole heights to below this length.
26.4.7 Overall comparison between conductors
Table 26.6 gives an overall comparison between the various conductors.
TABLE 26.6
COMPARISON BETWEEN CONDUCTORS
Design Parameter AAC AAAC1120 ACSR/GZ
Capital cost of
Lowest Marginally higher Significantly higher
conductor
Resistance and losses Lowest Marginally higher Marginally higher
Diameter (mm)
23.8 23.8 24.5
(See Note 1)
Surface voltage
gradient (kV/cm) 10.9 10.9 10.7
(See Note 2)
Horizontal tension at
20% CBL (kN) 10.18 14.72 24.2
(see Note 3)
Concrete and timber
Highest cost for Moderate cost for all Highest cost for angle
pole cost
intermediate structures and terminations
(See Note 4)
Highest cost for
Moderate cost for all Highest cost for angle
Foundation cost intermediate
structures and term foundations
foundations
Single compression Single compression 2 Part compression
Jointing cost
sleeve sleeve sleeve
Long term performance Good in most Good in most Moderate in coastal
(See Note 5) environments environments environments
NOTES:
1 The larger the diameter the higher wind span and wind loading on intermediate and suspension structures.
2 The Surface voltage gradients were calculated using an electromagnetic field program. An acceptable level
is <16 kV/cm.
3 The higher the conductor tensions, the higher the loads on angle and termination structures and
foundations.
4 Concrete pole cost can increase considerably above 24 m. Timber poles are scarce above 21.5 m in length.
Large concrete poles are considerably heavier than timber and steel.
5 Table Y2 of AS/NZS 7000 provides guidance for the long term performance.
because of previous good long term performance and because the introduction of a new
conductor like AAAC in their network may introduce additional deployment and spare
costs.
It is common practice for utilities to select ACSR conductor in cyclonic areas to mitigate
potential cascade failures from broken conductor conditions.
E a r th e d s tr u c tu r e
Windloading FT
Minimum phase/
ground clearance
We i g ht l oa di n g F W
TABLE 26.7
BLOW OUT CALCULATIONS FOR 300 m SPAN OF OXYGEN
CONDUCTOR AT 500 Pa WIND
Conductor Type Oxygen
Actual span length 300 m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
In the road corridor, the maximum span lengths are assumed to be 120 m. The blow out
calculation is given in Table 26.8.
TABLE 26.8
BLOW OUT CALCULATIONS FOR 120 m SPAN OF OXYGEN
CONDUCTOR AT 500 Pa WIND
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The road authority would normally provide an alignment for a pole in the road reserve. This
is typically 3 m. The conductors will in the still air condition be located in the road reserve.
The options for the line designer to secure the line are as follows:
(i) Acquire an easement which covers the excursion into private property. This is
estimated to be:
Easement width = (Dc + Di + blowout swing + Electrical clearance to
structures – 3)
where
Dc = Horizontal distance of conductors from pole centre
= 2.5 m
Di = Horizontal swing of insulators
= 0.0 m
Blowout = 2.1 m
Clearance to structures = 4.6 m
Easement width = 6.2 m (pole deflection has not been included)
(ii) Accept the conductors will blow into private property under wind conditions and that
there are no structures existing or likely to be constructed in the 6 m of the front
boundary. Councils normally have development conditions on building applications.
26.5.4 Lightning outage predictions
A lightning prediction program such as ‘Flash’ or ‘T-Flash’ can be used to estimate the
shielding failure and backflashover outages on the 132 kV powerline.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The ‘Flash’ program was used to predict the performance of the concrete pole line. The
parameters used in the calculation were as follows:
(a) Earthwire and Conductor geometry as per Figure 26.1.
(b) Thunderday level of 30 (design parameter from above).
(c) Ground flash density of 1.5 strokes per sq km (based on 30 thunderday level).
(d) Average ground footing resistance = 10 Ω.
(e) Earthwire sagged at 80% of conductor sag.
The results from the program were:
(i) Backflashover rate = 0.62 outages/100 km/year
(ii) Shielding failure flashover rate = 0.05 outages/100 km/year
(iii) Total flashover rate = 0.67 outages/100 km/year
(iv) A desirable outage rate for a 132 kV line is up to 2.0 outages per 100 km/year.
Some of the critical parameters (average ground resistance and ground flash density) were
varied to assess how the outage rates would change. These studies are given in Table 26.9
TABLE 26.9
LIGHTNING OUTAGE PREDICTIONS (CHANGING PARAMETERS)
Shielding failure
Backflashover Total flashover
Changed parameter flashover rate
rate 100 km/year rate 100 km/year
100 km/year
Base case 0.62 0.05 0.67
Ave ground resistance = 20 Ω 2.13 0.05 2.18
Ave ground resistance = 5 Ω 0.24 0.05 0.29
2
GFD = 3.0 strokes/km 1.23 0.11 1.34
NOTE: The lightning outage rate will vary depending on—
(a) the lightning prediction program;
(b) the parameters chosen for ground flash density, structure and earth surge impedances; and
(c) the method for calculating shielding failure flashovers.
Some transmission utilities stipulate a ground footing resistance of 5 Ω or less for the first
2.5 km out of a substation for insulation coordination and to achieve a virtual lightning
proof zone. Based on an outage rate of 0.29 per 100 km/year for a ground resistance to 5 Ω,
the probability that a lighting strike will cause a flashover of a 2.5 km section of line is
estimated at 1 in 140 years (100/2.5/.29).
26.5.5 Magnetic field calculations
A magnetic field program was used to plot the magnetic field under the 132 kV power line.
The geometry used was in accordance with Figure 26.1 and the assumed height of the
lowest conductor was 10 m. Magnetic field calculations are normally performed at 1 m
above ground.
Figure 26.5 shows the magnetic field under the power line for a current of 100 A in the
conductors for an easement width of 40 m. The magnetic fields will vary in proportion with
line current and the normal current loading (not emergency) should be used for assessing
magnetic fields for the line. For example, although the 132 kV line has a normal rating of
170 MVA, a 132 kV network is normally designed with N-1 contingency so the normal
current loading on the 132 kV line would be less than half of the 170 MVA rating i.e. 85
MVA (370 A). The values in Figure 26.5 need to be scaled up by a factor of 3.7 to derive
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
9.0 0
M a g n et i c Fi e l d (m G)
8 .0 0
7.0 0
6 .0 0
5.00
4.0 0
3.00
2.0 0
1.0 0
0.0 0
9 0
8. 0
7 0
6. 0
5 0
4 0
3. 0
2 0
1 0
0. 0
-9 00
-8 00
-7 0 0
-6 00
-5 00
-4 00
-3 00
-2 00
-1 0 0
0. 0
1. 0
2. 0
3. 0
4. 0
5. 0
00
7. 0
8. 0
9. 0
10 0 0
11 0 0
12 . 0 0
13 . 0 0
14 . 0 0
15 . 0 0
16 . 0 0
17 0 0
18 0 0
19 . 0 0
20.00
0
-1 . 0
-1 . 0
-1 0
-1 . 0
-1 0
-1 . 0
-1 . 0
-1 0
-1 . 0
-1 . 0
.0
0
0
0
0
0
0
0
0
.0
.
.
.
.
.
.
.
.
6.
.
.
0
-2
D i s t a n c e (m)
FIGURE 26.5 MAGNETIC FIELDS ON SINGLE CIRCUIT 132 kV LINE (PER 100 A)
26.5.6 Electrical design of transmission line insulation. pollution, clean and wet
Constant definitions
kV ≡ V 103 kiloVolt
puV ≡ 1 per unit voltage
Input data
Spac ≡ 146 mm Unit spacing between insulator discs
Creeplf ≡ 432 mm Creepage distance for disc. 292 mm for normals, 432 mm for fogs
Lh ≡ 400 mm Length of hardware in suspension string
Pollution
CreeperkVhp ≡ 25 mm kV–1 Pollution requirement. mm/kV line to line. IEC 60815-16
light, 20 medium, 25 heavy, 31 very heavy
Environment
273 + 20
δ ≡ 0.95 Relative air density. 0.95 for sea level and 35°C = 0.951
273 + 35
Humidity correction factor. For 20% rel humidity and 35°C moisture
H0 ≡ 1.025
content of air is 8 g/m3 and H0 is 1.025
Exponent for air correction factor. For 9 discs, spacing is 1314 mm
n ≡ 0.93
and n is 0.88
© Standards Australia www.standards.org.au
183 HB 331—2012
Electrical—Voltage
σss ≡ 10% Standard deviation for switching surge
σins ≡ 5% Standard deviation for insulator string
Switching surge flashover rate. Expected number of switching
SSFR ≡ 104
surges between flashovers
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Nhpsus = 9
Required number of tension insulator discs allowing for one
Nhptens = Nhpsus + 1
broken disc in string
Nhptens = 10
Lhpstring = Nhpsus Spac + Lp Length of insulator string including hardware
Lhpstring = 1714 mm
Power frequency clean and wet conditions
Determine insulation for wet conditions then no correction is required for humidity.
Vφφnom
VφGrms = OVcon Maximum continuous 50 Hertz phase to ground RMS voltage
3
VφGrms = 83.8 kV
VφG max = VφGrms OVdyn Maximum dynamic 50 Hertz phase to ground RMS voltage
VφG max = 117.4 kV
n
VφGwith ⎛H ⎞
= VφGmax ⎜ 0 ⎟ R Required 50 Hertz wet withstand RMS voltage
⎝ δ ⎠
VφGwith = 168.8 kV
Switching surge
VφGss = VφGrms 2 OVsw Peak switching surge phase to ground voltage
VφGss = 355.7 kV
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
VφGssl Peak switching surge phase to ground voltage for insulator string
= VφGssc R
taking into account number of strings in the line
VφGssl = 511 kV
VφGssl
VφGsseqi = Equivalent impulse phase to ground for peak switching surge
k
VφGsseqi = 639 kV
Results
Vφφrms = 145.2 kV
Pollution
Creephpr = 3630 mm Minimum required creepage length
Required number of suspension insulator discs, no allowance for
Nhpsus = 9
one broken disc in string
Required number of tension insulator discs—allow one disc
Nhptens = 10
extra to ensure flashover is across suspension/bridging string
Lhpstring = 1714 mm Length of insulator string including hardware
Power frequency clean and wet conditions
VφGrms = 84 kV Maximum continuous 50 Hertz phase to ground RMS voltage
VφGmax = 117 kV Maximum dynamic 50 Hertz phase to ground RMS voltage
VφGwith = 169 kV Required 50 Hertz wet withstand RMS voltage
4 normal discs or 5 fog discs required for this wet power frequency voltage
Switching surge
VφGss = 356 kV Peak switching surge phase to ground voltage
VφGssc Peak switching surge phase to ground voltage for one insulator
= 382 kV
string & corrected to standard pressure and humidity
VφGssl Peak switching surge phase to ground voltage for insulator string
= 511 kV
taking into account number of strings in the line
VφGsseqi = 639 kV Equivalent impulse phase to ground for peak switching surge
7 normal discs or 7 fog discs are required for this lightning impulse.
In summary, based on the pollution requirements there are 9 discs required for suspension
and bridging strings. In practice, 10 discs are installed in strain positions to ensure any
flashover on tensions structures are across the bridging string.
For the wood pole section, the electrical specification for the long rod and line post
insulators are as follows:
(a) Wet power frequency withstand voltage = 175 kV.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Example 3:
Calculate the strength of a composite line post insulator used to support Oxygen conductor
in a clamp top with a weight of 0.925 kg/m, weight span of 200 m, and strung to everyday
tension of 20% CBL.
Limit state load condition—everyday load
Conductor weight force = 0.925 × 9.806 × 200 = 1814 N
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Longitudinal load for 3:1 adjacent span ratio, and max operating temperature of
75°C = 5200 N
Conductor tension multiplier = 1.25
Limit state longitudinal design load = 6500 N
Resultant bending moment load = (2270 2
)
+ 6500 2 = 6900 N
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Component strength factor for composite post insulator = 0.9 (Table 6.2 of AS/NZS 7000)
Insulator ultimate design cantilever load = 6900/0.9 = 7650 N
Transverse compressive load = 0.0238 × 1300 × 200 = 6188 N
Compression load multiplier = 1.00
Limit state transverse compressive load = 6188 N
Combining bending and compressive loads—simplified method:
Compressive strength of 2.5 inch line post = 50 kN
Derating factor = 1 – (6188/50 000) = 0.88
Insulator ultimate design cantilever load = 7650/0.88 = 8690N
Comments:
The determining state is the failure containment load where the factored ultimate design
cantilever load is 8690 N.
A 2.5 inch post insulator is typically rated at 12.5 kN ultimate cantilever strength and is
recommended for this ultimate load
For spans much higher than 200 m, the combined loads may exceed the 12.5 kN ultimate
design cantilever strength. Design options to support the failure containment load for the
long spans include:
(a) Brace 2.5 inch post with a long rod insulator
(b) Limit the line layout to an adjacent span ratio of 2 or less
(c) Use a 3 inch post which has a MDCL of around 9 kN
Example 4:
Calculate the strength of a suspension composite long rod used to support oxygen conductor
with a weight of 0.925 kg/m, weight and wind span of 400 m, and strung to everyday
tension of 20% CBL. For broken conductor condition assume a wind of 0.25 of ultimate
wind (900 Pa).
Limit state condition—everyday load
Conductor weight load = 0.925 × 9.806 × 400 N = 3628 N
Conductor weight multiplier = 1.25
Limit state conductor weight load = 4535
Assume no longitudinal load due to free swinging insulator
Component strength factor for long rod insulator = 0.5 (Table 6.2 of AS/NZS 7000) and
long term strength)
Insulator specified mechanical load = 4535/0.5 = 9070 N
Limit state condition—ultimate strength state under 1300 Pa wind
Conductor weight = 0.925 × 9.806 × 400 N = 3628 N
Conductor weight multiplier = 1.25
www.standards.org.au © Standards Australia
HB 331—2012 188
2
Resultant load = + 15470 2 = 16120 N
Component strength factor for long rod insulator = 0.7 (Table 6.2 of AS/NZS 7000) and
short term strength)
Insulator specified mechanical load = 16120/0.7 = 23028 N
Limit state condition—failure containment load under broken conductor
Longitudinal load = 16 800 N (at 225 Pa wind)
Residual Static Load = 0.7
Longitudinal load with load relief = 11760 N
Tension load multiplier = 1.25
Limit state tension load = 14700 N
Component strength factor for long rod insulator = 0.7 (Table 6.2 of AS/NZS 7000) and
short term strength)
Insulator specified mechanical load = 14700/0.7 = 21000 N
Comments:
(a) The determining state is the ultimate strength state under 1300 Pa wind
(b) The minimum recommended size for the suspension insulator is 111 kN (specified
mechanical load). The SML is a one minute withstand load.
(c) If a ceramic disc insulator would be used, then the recommended minimum size is
70 kN (minimum breaking load).
(d) The minimum recommended strengths are based on the requirement to achieve a
design life comparable to other line components
Example 5:
This example applies a more rigorous approach to the application of AS/NZS 7000 to check
the strength capacity of tension ceramic disc insulator string for a terminal tower. The
string is made up of 11 × 70 kN normal disc insulators.
The design criteria as follows:
Zone 1, Wind region A4, Md = 1.0, Mt = 1.0, Ms = 1.0, Terrain category 2
Line security level = 1 and design working life = 50 years
Oxygen conductor strung at everyday tension of 20% CBL (refer Table Z1 of
AS/NZS 7000)
Wind span = 200 m, weight span = 400 m
Ruling span = 330 m, tension section = 4000 m
Average height of conductor = 20 m
Wind direction orthagonal to line direction.
Find load components for maximum transverse wind condition (refer Table 7.3 of
AS/NZS 7000), note that this may not be the governing condition)
© Standards Australia www.standards.org.au
189 HB 331—2012
Find Ftw
Conductor tension at EDT = 14.72 kN
Wind pressure = 1.065 kPa
SRF = 0.59 for tension span of 4000 m
Wind pressure on conductor = 0.628 kPa
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
F1 ( Lo a d f r o m e a r thwi r e)
1.9 m
F2 ( Lo a d f r o m A Ph a s e)
1. 8 5 m
F3 ( Lo a d f r o m B Ph a s e)
1. 8 5 m
F4 ( Lo a d f r o m C Ph a s e)
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
d1 F w
( Lo a d o n p o l e)
d2
d3
d4
4°
d ev i a t i o n
Earthwire and Conductor tensions at 900 Pa can be found with a sag tension program to be:
Tx earthwire = 22 900 N
Tx conductor = 30 700 N
⎛ d + d 3 + d 4 ⎞ Fwφ
Tip load = F1 + F2,3, 4 ⎜⎜ 2 ⎟⎟ +
⎝ d1 ⎠ 2
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
where
F1 = θ
PW × OD × Wd + 2 Tx sin
2
= 900 × 0.143 × 300 + 2 × 1.25 × 22900 × sin 2
= 5859 N
F2, F3, F4 = 900 × 0.238 × 300 + 2 × 1.25 × 30700 × sin 2
= 9103 N
Fwφ = Pwφ × OD × d1
= 1300 × 0.6 × 24
= 18720 N
Ultimate tip load = 38.1 kN
Axial Loads:
Self weight of 24 m/30 kN pole assumed to be = 2500 kg
3 × Conductor + Earthwire weight for 300 m weight span = 1000 kg
Crossarm, insulators and associated hardware = 500 kg
Limit state axial load = 1.1 × 4000 kg or 44 kN
26.7.2 Selection of pole
26.7.2.1 General
The general steps in the structural design process are:
(a) Apply design loads and incorporate component strength factor to determine ultimate
strength of structure
(b) Select pole strength and length (based on estimated foundation depth) that exceeds
the ultimate factored loads (in this example, a 30 kN pole)
(c) Check deflections for serviceability limit state loads:
(i) short duration (electrical clearances).
(ii) sustained (creep/crack control).
(d) Check combined axial and bending moment loads using formula:
⎛ M * ⎞ ⎛ N C* ⎞
⎜ ⎟+⎜ ⎟ ≤1
⎜ φM ⎟ ⎜ φN ⎟
⎝ ⎠ ⎝ ⎠
Axial loads which consist of self-weight of structure and conductor weight loads are
considered to be negligible (less than 10% of the compressive capability of pole) and
can therefore be neglected.
(e) Check bending stresses on pole critical sections.
E
FE
A
FA
B
FB
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
R1
FC C
L1
4 5°
LC R2
L2
Vertical load at base of pole = vertical component of stays + self-weight of pole + vertical
load of conductors and fittings = 121 kN.
Assuming a base disc or biscuit 1100 diameter is used to distribute the compression load
and control settlement under the axial load.
Resulting bearing pressure under base = 127 kPa.
This would be satisfactory in firm soils.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
where
θ
F1 = PW × OD × Wd + 2 Tx sin
2
= 900 × 0.143 × 120 + 2 × 1.25 × 8193 × sin 20
= 8573 N
F2, F3, F4 = 900 × 0.238 × 120 + 2 × 1.25 × 9010 × sin 20
= 10275 N
Fwφ = Pwφ × OD × d1
This strength is at the limit for wood poles and as poles degrade overtime, the ultimate
strength will reduce. The designer has a number of options to address this as follows:
(a) Reduce the conductor tensions.
(b) Reduce the span length (this will however increase the deviation angle).
(c) Install a concrete pole with a minimum ultimate strength 40 kN (38 kN/0.95 CSF).
(d) Install a ground stay in longitudinal road direction to meet the 5% tension loads and
install a slack span between Poles 4 and 5.
Considerations for un-stayed pole:
For an un-stayed pole, deflection limits need to be considered to ensure electrical
clearances are met and complaints are minimized from the public. The recommended
deflection limits are:
Serviceable wind loads (typically 750 Pa wind on pole and 500 Pa on conductors) –5% of
the pole length out of ground
26.7.5 Pole tip load calculation for structure 7 (stayed timber pole)
(a) Consider at first an unstayed pole—assuming transverse wind (90° to line)
(i) Ultimate tip load = 30.9 kN.
(ii) Everyday tip load = 12.8 kN.
(iii) Component strength factor for wood pole = 0.75.
(iv) Ultimate strength of pole to meet ultimate load = 41.2 kN.
(v) Servicability strength of pole to meet everyday load = 17.0 kN.
(vi) Select 20 kN ultimate strength pole with stay.
(b) Ground stay design assuming pin joint and no shear at ground level
(i) Ultimate tip load due to wind load = 30.9 kN.
(ii) Angle of stay = 45°.
(iii) Tension in stay at tip = 30.9 × 1.414 = 43.8 kN.
(iv) Component strength factor φ for transmission stay = 0.7 (Table 6.2 of
AS/NZS 7000).
(v) Ultimate strength of stay = 62.5 kN.
(vi) Select 19/2.0 SC/GZ staywire (CBL = 74.4 kN).
(b) Provide return path for fault current to ensure protective devices (relays, circuit
breakers and fuses) operate to isolate the faulted circuit.
(c) Minimise Earth Potential Rise (EPR) hazards—by connecting all non-current carrying
metallic conductors together and to earth.
(d) Telecommunication bearer—with optical fibres (OPGW).
26.8.2 Selection of overhead earthwires
Earthwires do not necessarily need to be made from high conductivity materials, and where
fault currents are low are commonly made from galvanized or aluminium clad steel.
The earthwire size is determined by the assuming a maximum acceptable temperature that
causes minimum permanent damage to the metallic strands or the fibres. As outlined in
AS/NZS 7000, the effect of cumulative heating of the earthwire when the line is reclosed
under short circuit conditions should be considered.
The cross-sectional area of the earthwire conductor is primarily determined by the
prospective earth fault or power follow fault current, rather than lightning currents, as the
duration of power fault currents will generally be much longer. The maximum operating
temperature for various conductors subjected to short circuit currents are shown in
Table 26.10
TABLE 26.10
CONDUCTOR MAXIMUM OPERATING TEMPERATURE
(10% LOSS OF STRENGTH)
The earthwire specified for the 132 kV line is 14.5 mm diameter OPGW with a minimum
outer strand of 3 mm. The OPGW contains an inner aluminium tube and metallic wires of
aluminium clad steel and aluminium alloy. A typical 14.5 mm OPGW has a fault current
rating of 20 kA for 0.3 s.
26.8.3 Ground earthing design
The desired average earthing resistance for the 132 kV is 10 Ω. This provides an acceptable
lightning performance for the line. A conductive pole such as concrete can be part of the
earthing system coupled with various other ground earthing methods such as:
(a) Earth rods including deep drilled electrodes.
(b) Counterpoise wires.
(c) Grading ring (generally at a distance of 1 m around the pole).
I E/W I E/W
If
I p = 5 - 10% I f
Vo l t a g e p r of il e
To u c h Pote nti a l
R e S te p Pote nti a l
I x p R pe
GPR = p
FIGURE 26.8 EARTH FAULT CURRENT AND TOUCH AND STEP POTENTIALS
Given that the overhead 132 kV pole line has an overhead 14.5 mm OPGW earthwire of
resistance 0.35 Ω/m and the assumed footing resistance is 10 Ω, the expected fault current
down the structure is around 5% (See Clause 17.8.4). For a 20 000 A fault current, the
prospective ground potential rise is therefore 10 000 V (1000 A × 10 Ω).
If a person stands 1 m away from the conductive pole, the prospective touch potential is in
the range of 25% to 50% of the ground potential rise. The maximum expected touch
potential is therefore 5000 V.
Using the EG0 Risk Basked Approach to Earthing outlined in Section 10 of AS/NZS 7000,
the applicable touch voltage curve from Figure 10.1 of AS/NZS 7000 is TU (contact with
transmission asset in urban interface location). For a 0.2 s clearing (which is typical for a
132 kV line), the allowable touch voltage is 7000 V.
Given that the expected touch potential of 5000 V is less than the allowable touch voltage
of 7000 V, the earthing design is acceptable.
There may be specific pole locations where mitigation may be required as outlined in EG0,
such as:
(a) Adjacent to public meeting places.
(b) Adjacent to water recreation areas.
(c) Adjacent to metallic fences.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 2 7 W O R K E D E X A M P L E S F O R
V A R I O U S L I N E C OM P O N E N T S
Example 1:
Single circuit 19/3.25 AAC at 33 kV 3 phase on pin insulators in a delta configuration with
a span of 200 m. What is the mid span vertical separation required between phases if a cross
arm with a separation of 2.1 m between outer phases is used?
Sag at 50°C is 6.07 m and sited in Region A.
U
X 2 + (1.2Y ) 2 ≥ + k D + li
150
36
1.05 2 + (1.2Y ) 2 ≥ + 0.4 6.07 + 0
150
where
∴X = 1.05
U = 36 (assume 1.1 p.u. operating voltage)
k = 0.4
D = 6.07
li = 0
Y ≥ 0.55
Therefore required minimum vertical separation for centre phase is 0.55 m.
Example 2:
Upper circuit 19/3.25 AAC at 33 kV 3 phase on pin insulators in a delta configuration with
a span of 200 m located directly above the lower circuit. The lower circuit conductor is
19/.064 copper at 11 kV. The lower circuit has a 120° phase differential to the upper circuit.
What is the mid-span vertical separation required between circuits if a cross arm with a
separation of 2.1 m between outer phases is used?
Sag at 50°C is 6.07 m for 19/3.25 AAC and 5.81 m for 19/.064 copper sited in Region Type
A.
Because the circuits are located vertically above each other, the horizontal component is
taken as zero; and
= 22.9 kV
where
∴X = 0
U = 22.9 (the difference in the vector r.m.s. potential of the circuit voltages)
k = 0.4 (Region A)
D = 6.07 (greater of the two sags)
li = 0 (Pin insulators)
U
X 2 + (1.2Y ) 2 ≥ + k D + li
150
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
22.9
0 + (1.2Y ) 2 ≥ + 0.4 6.07 + 0
150
1.2Y ≥ 1.138
1.138
Y≥
1. 2
Y ≥ 0.948
Example 3: Separation where conductors go from vertical to flat or triangular
For similar geometric configurations (horizontal to horizontal or vertical to vertical) the
radial spacing formula below is a good formula to use as the closest conductor separation at
mid span
However, for dissimilar geometric configurations, the closest separation may not be at mid
span.
In order to determine the point of minimum separation, the separations must be iterative
checked along the line by determining the X and Y coordinates and then calculating the
spacing.
Determining the minimum separation between conductors for a delta to vertical
construction arrangement 1 given in Figure 27.1
0.900
0.9 0 0
0.320
0.9 0 0
DIMENSIONS IN METRES
Figure 27.1 can be simplified to X and Y plane view as shown Figure 27.2 and Figure 27.3,
respectively.
0.9 0 0
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0.4 50
0.9 0 0
DIMENSIONS IN METRES
0.9 0 0
0.0 29
0. 320
0.9 0 0
DIMENSIONS IN METRES
Using the radial separation formula, the spacing can be determined as per Table 27.1 for
construction arrangement 1. Table 27.1 shows the minimum separation is no longer at the
midpoint, but at 46% of the length from the delta end of the line.
TABLE 27.1
RADIAL SPACING BETWEEN CONDUCTORS FOR CONSTRUCTION
ARRANGEMENT 1
Location
10 20 25 30 40 46 50 60 70 80 90 100
(% of span)
Radial
0.84 0.73 0.68 0.63 0.58 0.566 0.57 0.61 0.70 0.81 0.94 1.08
Separation (m)
X Separation (m) 0.81 0.72 0.675 0.63 0.54 0.486 0.45 0.36 0.27 0.18 0.09 0
Y Separation (m) 0.198 0.076 0.015 0.046 0.168 0.2412 0.29 0.412 0.534 0.656 0.778 0.9
Interestingly, the spacing between the conductors can be increased by simply changing the
attachment points to construction arrangement 2 as shown in Figures 27.4 and 27.5 below.
The middle phase on the delta structure moved from the middle phase to the top attachment
on the vertical structure.
0.900
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0.9 0 0
0.320
0.9 0 0
DIMENSIONS IN METRES
The X view stays the same as in Figure 27.2, but the Y view is significantly changed.
0.9 0 0
0.610
0. 320
0.9 0 0
DIMENSIONS IN METRES
Re-calculating the conductor radial separation from construction arrangement 2 shows the
closest point of separation has changed to be at 42% of the length from the delta end, as
shown in Table 27.2. However, more importantly the separation has increased from 0.566 m
to 0.8524 m for the same size poles, cross arms and insulators.
Table 27.2 Radial spacing between conductors for construction arrangement 2 with the
middle phase on the delta structure moved from the middle phase to the top attachment on
the vertical structure
TABLE 27.2
RADIAL SPACING BETWEEN CONDUCTORS FOR CONSTRUCTION
ARRANGEMENT 2
Location
10 20 25 30 40 42 50 60 70 80 90 100
(% of span)
Radial
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
0.93 0.89 0.88 0.87 0.8546 0.8543 0.8593 0.88 0.91 0.96 1.01 1.08
Separation (m)
X Separation
0.81 0.72 0.675 0.63 0.54 0.522 0.45 0.36 0.27 0.18 0.09 0
(m)
Y Separation
0.378 0.436 0.465 0.494 0.552 0.5636 0.61 0.668 0.726 0.784 0.842 0.9
(m)
Comparing the above construction arrangements and standard mid span formula, as shown
in Table 27.3 below, it can be shown that using the mid span formula the calculation would
have shown the radial separation would have been adequate for either construction 1 or 2
arrangements. However, construction 1 would not have achieved the minimum separation
46% along the length of the line. Construction 2 would though have always had adequate
separation
Using the formula in AS/NZS 7000, inserting the calculated X and Y values at the point of
minimum separation and varying the k factor the following results are evident.
TABLE 27.3
SEPARATIONS FOR CONSTRUCTION 1 AND 2
Meets
I
(X ) + (1.2Y )
X Y U Tensioning D
2 2 k +k ( D + li ) C(b)1
150
m m kV % CLB m Y/N
Midpoint separation for construction 1 and 2
0.45 0.29 0.570 22 0.4 25 1.69 0.667 Y
0.45 0.61 0.860 22 0.4 25 1.69 0.667 Y
Minimum separation for construction 1
0.486 0.2412 0.566 22 0.4 25 1.69 0.667 N
Minimum separation for construction 2
0.522 0.5636 0.854 22 0.4 25 1.69 0.667 Y
(a) Calculate the strength of a tension ceramic disc insulator used for moon conductor,
spanning 100 m and strung to everyday tension of 20% CBL.
Limit state condition—failure containment load at 900 Pa
Conductor tension at 900 Pa = 8617 N
Multiplier for tension loads = 1.25
Limit state design tension load = 10 770
Component strength factor for ceramic insulator = 0.8 (refer Table 6.2 of
AS/NZS 7000) and unverified strength)
Minimum insulator ultimate strength = 10 770/0.8 = 13460 N
Refer to Note 1 in Appendix CC which states insulator strength to be greater than
conductor CBL or coordination of strength between conductor, insulator, fittings,
crossarm and structure.
Historically, the industry has used a ceramic disc insulator with a minimum standard
of 70 kN to provide a suitable reliability and life.
(b) Calculate the strength of a ceramic line post insulator used to support moon conductor
in a clamp top with a weight of 0.34 kg/m, weight span of 100 m, and strung to
everyday tension of 20% CBL.
Limit state condition—everyday load
Conductor weight = 0.34 × 9.806 × 100 N = 333 N
Conductor weight multiplier = 1.25
Limit state vertical design load = 416 N
Longitudinal load for 2:1 adjacent span ratio (75 m and 150 m spans), and max
operating temperature of 75°C = 890 N
Tension load multiplier = 1.25
Limit state tension design load = 1109 N
Resultant bending moment load = (416 2
)
+ 1109 2 = 1184 N
Component strength factor for ceramic post insulator = 0.8 (Table 6.2 of
AS/NZS 7000)
Insulator minimum failing load = 1184/0.8 = 1480 N
Limit state condition—serviceable wind load at 500 Pa
Conductor weight = 0.34 × 9.806 × 100 N = 333 N
Conductor weight multiplier = 1.25
Limit state vertical design load = 416 N
Longitudinal load for 2:1 adjacent span ratio, and max operating temperature of
75°C = 890 N
Tension load multiplier = 1.25
For pin insulators, determine the resultant horizontal load at the conductor connection
point.
Insulator mass = 50 kg
Vertical load on insulator = 50 × 9.81 = 490 N
For the sustained load case (see Figure 27.6):
Transverse load = 2 × Fte × sin(20°/2) = 750 N
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
F te = 216 0 N
750 N
20 °
D evi ati o n
F te = 216 0 N
S u s t a i n e d Loa d Ca s e ( N o W i n d )
T = 5°C
F t w = 5 3 52 N
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
9 0 0 Pa wi n d 2 X F t w X s i n (10 °)
= 18 58 N
F t w = 5 3 52 N
+8.18
Te n s i o n
+ 4.14
A x i a l Fo r c e
Diagram (kN)
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
- 4.14
Compression
-14.72
Te n s i o n o n U p p e r
S u r fa c e
4.49
3. 3 9
1.4 5
1.9 5
Bending Moment
0. 8 4 D i a g r a m ( k N m)
1.4 5
1. 8 0
0. 8 3
0.97 0. 8 3
S h e a r Fo r c e D i a g r a m
(kN)
11. 5
FIGURE 27.9 AXIAL FORCE, BENDING MOMENT AND SHEAR FORCE DIAGRAMS
f c′ = 40 MPa
Design of Timber to AS 1720.1
A reference for the design of timber is the Standards Australian Timber Design Handbook,
HB 108.
While unseasoned timber is specified by its nominal size, e.g. 100 × 100, for design
purposes, the convention is to subtract 3 mm from the cross-sectional dimensions as a
manufacturing tolerance. For design purposes, the size is therefore 97 × 97.
The maximum design actions at the strength limit state are (see Figure 27.9):
High Compression
Zo n e = 4 6 0 m m
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Buckled Shape
C o m p r e s s i o n Le n g th = 120 0 m m
Equation 3.5(1) of AS 1720.1:2010 governs and the section size exceeds the code
requirements by 15%.
Thus, the timber cross arm utilization is 115%.
27.2.5 Selection of steel crossarm
The proposed steel section is a 100 × 100 × 6 SHS, grade C350.
For a 100 mm high cross arm, the previously calculated bending moments, axial and shear
forces are suitable. Bending moments are calculated by using the vertical distance between
the centreline of the cross arm and the conductor at the top of the insulator. The maximum
design actions are:
Bending moment = 4.49 kNm
Axial force = 14.72 kN (compression)
Shear force = 11.5 kN
(a) Simplified Method (See Figure 27.12):
The bending moment induces an extreme fibre stress of:
(4.49 × 106 Nm/m)/(60.7 × 103 mm3) = 74 MPa
The axial force induces a uniform stress of:
(14.72 × 103 N)/(2130 mm2) = 7 MPa
+ 74 + 67
+ =
The maximum stress that the section can tolerate is equal to:
Capacity Factor × Yield Stress = 0.9 × 350 = 315 MPa. The section utilization
is 81/315 = 26%
Component Utilization
description %
Pin insulator 73
Timber crossarm 115
Steel crossarm 19
Utilizations less than 100% indicate some reserve capacity, i.e. can accommodate load
increase or a smaller element could be considered.
Utilizations greater than 100% indicate that the element is overloaded and has a reduced
safety factor, i.e. a larger element or a reduction of loads could be considered.
Further items that should be checked are:
(i) Shear strength of timber cross arm.
(ii) Shear strength of bolts in timber.
TX PZ TX
/2 /2
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
F1 ( Lo a d f r o m e a r thwi r e)
2.4 m
F2 ( Lo a d f r o m A Ph a s e)
1. 5 m
F3 ( Lo a d f r o m B Ph a s e)
1. 5 m
F4 ( Lo a d f r o m C Ph a s e)
d1 F w
( Lo a d o n p o l e)
d2
d3
d4
20 °
d ev i a t i o n
Input:
Pole height = 17.4 m
Earth wire = Libra AAC (Tx = 5000 N)
Conductors = Pluto AAC (Tx = 13000 N)
Line deviation = 20°
Wind span = 180 m
Average pole OD = 0.4 m
Wind pressure = 900 Pa on conductor/OHEW, and
= 1300 Pa on pole
⎛ d + d 3 + d 4 ⎞ Fwφ
Tip load = F1 + F2,3,4 ⎜ 2 ⎟⎟ +
⎜ d1 2
⎝ ⎠
© Standards Australia www.standards.org.au
217 HB 331—2012
θ
F1 = Pw × OD × Wd + 2T sin
2
Ultimate tip load = 28.4 kN
27.3.3 Selection of pole
27.3.3.1 Wood pole
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
27.3.3.1.1 General
Select a pole with a limit state design load of 28.4 kN
Preserved wood pole component strength factor = 0.72 (Table 6.2 of AS/NZS 7000 for
range)
Ultimate strength of wood pole = 28.4/0.72 = 39.4 kN
Wood poles typically decay during their life and designers may choose a pole with a higher
strength to achieve a longer design life.
27.3.3.1.2 Considerations for un-stayed wood pole
For an un-stayed pole, deflection limits need to be considered to ensure electrical
clearances are met and complaints are minimized from the public. The recommended
deflection limits are:
Serviceable wind loads (typically 750 Pa wind on pole and 500 Pa on conductors) –5% of
the pole length out of ground
27.3.3.1.3 Consideration for stayed pole
A stayed pole should be designed to meet the following conditions:
(a) Poles should be self-supporting under every day load conditions without stay (should
not suffer failure due to loss of stay)everyday load = 16 kN
Component strength factor for wood pole = 0.72
Ultimate strength of pole to meet everyday load = 22 kN
(b) If ground stay used and attached to top of pole
Ultimate tip load due to wind load = 28.4 kN
Angle of stay = 45°
Tension in stay = 28.4 × 1.414 = 40 kN
Multiplier for tension loads = 1.25
Limit state tension load in stay = 50 kN
Component strength factor for distribution stay = 0.8 (Table 6.2 of AS/NZS 7000)
Ultimate strength of stay = 62.5 kN – select SC/GZ stay wire of 19/2.00
(CBL = 74.4 kN)
Compressive load in pole due to stay = 28.4 kN
Compressive strength of wood pole with 300 mm dia is typically around 250 kN
Ratio of compressive load to compressive strength = 11%
Ultimate strength of pole to allow for stay load = 20 × 1.11 = 22 kN
NOTE: If using an angle of stay larger than 45°, the tension in the stay and compressive load in
the pole will increase.
pointed crossarms, the orthogonal components of conductor load (relative to the structure
geometry shown in Figure 27.15) are:
FL = (H1 cosθ1 – N1 sinθ1) – (H2 cosθ2 – N2 sinθ2)
FT = (H1 sinθ1 + N1 cosθ1) + (H2 sinθ2 + N2 cosθ2)
Fv = V1 + V2
At a structure with square crossarms, the load contribution from each span should be
assessed independently so that torsional loading on the crossarm can be considered.
Dir pon
co
ec
m
C o n d u c to r s u p p o r t
tio nt o
n o
e
f tr wind
an
f
sve
rse
1 2
rt H
po H2
sup 1
N2 N1
n ex t
To
t or
uc
nd
co
t
ou
n
w Pl a n V i ew
lo
B
FT = N1 + N2
Fv = V1 + V2
The transverse and vertical components of tension are calculated using —
N1 = Lh1Wh1
N2 = Lh2Wh2
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
V1 = Lv1Wv1
V2 = Lv2Wv2
where
FL, FT, FV = longitudinal, transverse and vertical (to the structure) component
of conductor load at the conductor support
H1, H2 = left and right longitudinal (to the span) component of conductor
tension
N1, N2 = left and right transverse (to the span) component of conductor
tension
V1, V2 = left and right vertical component of conductor tension
Lh1, Lh2 = left and right partial wind spans such that Lh = Lh1 + Lh2
Lv1, Lv2 = left and right partial weight spans such that Lv = Lv1 + Lv2
Wh1, Wh2 = left and right transverse (to the span) component of distributed
conductor load
Wv1, Wv2 = left and right vertical component of distributed conductor load
120 0 120 0
400
20 0
LV B r a cke t - AB C
10 20 0
870 0
23 0 0
DIMENSIONS IN MILLIMETRES
Pole details:
Mixed Australian hardwood classified to AS 1720.1—1997 as strength group S4—
stress grade F17 (i.e. Jarrah, Ash type eucalypts)
Unseasoned, unpreserved and unshaved timber
Top diameter 300 mm
Ground line diameter 400 mm
Height above ground 10.2 m (i.e. depth in ground 2.3 m)
Crossarm size: 100 × 150 mm
11 kV insulators are ALP 11/275
The soil conditions are specified in three layers: 0-0.5 m of loose gravel with sand,
0.5–1.0 m of firm cohesive soil and 1.0 m or more of very stiff cohesive soil.
Calculations:
Use the approximate wind pressures based on Clause 3.4.1 of AS/NZS 7000 .
Conductor tensions are abbreviated as follows: for everyday load condition—EDT (i.e.
everyday tension) and for short duration load condition—MWT (i.e. maximum wind
tension).
Intact conductor tension (F t ) under average wind 15°C 0.5 kPa F t = 2.96 kN
Intact conductor tension (F t ) under average wind 15°C 0.5 kPa F t = 6.23 kN
Assuming that the pole met the design criteria the foundation can be designed using the
ESAA Brinch Hansen Pile program.
Using a foundation strength factor φ = 0.5 for foundations relying on empirical assessment
from Table 3.1 , the ultimate ground line moment as calculated above is—
BMult = 132 kNm and the ultimate shear load at ground line is:
Hult = Wn + 1.1Gs + 1.25Gc + 1.25 Ft
= 4.64 + 0.032 + 3 × 0.029 + 0.8 × 3 + 1.64 + 1.2 × 3 × 1.25 + 2.1 × 1.25
= 15.92 kN
By entering the ultimate loads and soil properties for each soil layer, the ESAA BH Pile
program delivers a minimum depth requirement of …. m for a foundation diameter of
0.8 m.
Once a satisfactory pole and footing design for the maximum wind load condition is
achieved, a similar calculation may be followed for failure containment, maintenance and
serviceability conditions as appropriate.
Vc
11 k V
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
24 0 0
Vc
LV
800
Vs
315 KvA Tr a n s fo r m e r
M a s s = 15 4 0 kg
50 0
6000
Vtran
11 k V a n d LV
DIMENSIONS IN MILLIMETRES
TABLE 27.4
PRINCIPAL DESIGN PARAMETERS
Item Detail Reference
Line Location Coastal plain North Island—
near Palmerston North
Soil Type Soft/Firm clays max depth Table 3.2 NZS 1170.5
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 27.5
LINE DESIGN PARAMETERS
Component Detail Reference
TABLE 27.6
POLE DETAILS
Item Assumed pole details
characteristically flexible and ductile. In addition pole footings also demonstrate ability to
absorb any overload with soil deformation.
27.7.1.3 Conductor vertical load
The maximum vertical load from the conductor is calculated as follows:
transverse Y axis:
AND
100% in Y axis and 30% simultaneously applied in the X axis. (C1 5.3.1.2 NZS 1170.5)
27.7.1.7 Equivalent tip loads
The equivalent simultaneous tip loads are calculated as follows:
Equivalent Pole tip capacity X axis = 6.0/9.2 × 31.14 = 20.30 kN
Equivalent pole tip capacity Y axis = 0.30 × 20.30 = 6.0 kN
Assumed section properties X axis tip load rated capacity = 8 kN
Assumed section properties Y axis tip load rated capacity = 22 kN
This would indicate:
For this site a single pole would be OK if rotated 90 degrees for one load direction
combination but grossly inadequate in the other simultaneous load combination direction.
Solution here would be to use twin poles with shear bolts to provide a composite pole.
Therefore because of the significant increment in vertical mass of the additional pole we
need to refine calculations for a twin pole solution:
Assumed section properties Y axis tip load rated capacity of a single pole = 22 kN
Capacity of twin composite poles in Y axis = 2 × Single pole = 44 kN
This indicates that solution is satisfactory for the one direction but not for the X axis and
we would need to increase the tip load capacity of the pole element to say 12 kN in X axis.
NOTES:
1 The composite action of twin poles can be increased by providing higher shear transfer
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
μC (T )gZRS pT12
Δ=
4π 2
where
Δ = the seismic displacement at centre of mass (m)
μ = ductility coefficient
g = 9.81 ms-2
T1 = the fundamental period of the structure (s)
C(T), Z, R, Sp are factors in NZS 1170.5
Now
Δ = the seismic displacement at centre of mass (m)
μ = ductility coefficient = 1.25
g = 9.81 ms-2
T1 = the fundamental period of the structure (s) = 2.0 s
C(T) = 0.66
Z = 0.38
R = 0.35 for 50 year return period
Sp = 1.3 – 0.3 m = 1.65 (NZS 1170.5, Clause 4.4.2)
μC (T )gZRS pT12
Δ=
4π 2
= (1.25 × 0.66 × 9.806 × 038 ×0.35 ×1.65 × 4)/(4 × 3.1416 × 3.1416)
= 0.179 m (179 mm)
This is a significant horizontal displacement that reflects peak expected movement.
Local subsoil strata may however dissipate or reduce or amplify this displacement.
The pole arrangement and force diagram are as given in Figures 27.18 and 27.19.
Line En d p o l e
Pull di r e c ti o n
S t ay
9.2 m
Ground line
1.8 m
Single circuit
Vc
TC TH
TS Stay
TV
VS
Seismic actions
The pole is a PSC concrete pole with the details given in Table 27.7.
TABLE 27.7
POLE DETAILS
Item Assumed Pole Details
Pole type 11 m PSC Rectangular I
Section
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 27.8
LINE DESIGN PARAMETERS
Component Detail Reference
Pole type 11.0 m Prestressed
concrete
Conductor ‘Dog’ ACSR LV and 11 kV
Earthwire Nil
Wind span 100 m
Weight span 100 m
Deviation angle 0 degrees
Conductor every day 3.29 kN
tension
Conductor self weight 0.396 kg/m
The seismic load is determined using the equivalent static method (Clause 6.2 of
NZS 1170.5).
Assuming normal I section PSC poles this force is to be resisted at the level of the
transformer mounting bracket with 100% in X axis and 30% simultaneously applied in the
transverse Y axis;
AND
100% in Y axis and 30% simultaneously applied in the X axis. (C1.5.3.1.2, NZS 1170.5).
27.7.2.6 Equivalent tip loads
The equivalent simultaneous tip loads are calculated as follows:
These forces need to be applied at the tip attachment
Equivalent pole tip capacity X axis = 22.13 kN
Equivalent pole tip capacity Y axis = 0.30 × 22.13 = 6.6 kN
Assumed section properties X axis tip load rated capacity = 8 kN
Assumed section properties Y axis tip load rated capacity = 22 kN
27.7.2.7 Conclusions from review of analysis:
For this site a single pole with its major strength axis at right angles to the line and
restrained in the weaker longitudinal axis by a back stay on one side and aerial conductors
on the other – would be assumed to have adequate capacity.
Keep in mind that with the seismic displacement Δ at centre of mass of almost 200 mm as
previously estimated, there may be some concern if differential movements occurred
between the stay anchorage and the pole. This would have a low probability of occurrence,
and if it occurred the weaker element would be most probably the staywire and would result
in the pole leaning into the conductor span with the soil foundation yielding.
The total overhead line system (foundation, pole structure, conductors, stays) is in fact, a
very flexible and elastic system and experience has shown that seismic force impacts
generally have minimal effect on the structural security of overhead lines.
However, there is always a risk that isolated structures may be subjected to seismic forces
and effects that will cause them to sink vertically in liquefaction areas, be vertically or
horizontally displaced, lean or to be structurally damaged.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 2 8 S P E C I A L C O N D U C T O R S
Conventional conductors induce a large wind pressure wake load whereas low drag
conductor induce a narrower wake and thus a lower wake load as illustrated in Figure 28.1.
The narrower wake is achieved by designing the wire shape to shift the air flow separation
point towards the wake shadow region of the conductor surface.
The drag coefficient of conventional conductor is shown in blue in Figure 28.2. Also shown
in Figure 28.2 in red is the drag coefficient of a specially designed ‘low drag aerodynamic
conductor.’ Furthermore, the typical range of Australian wind speeds between 30 m/s and
40 m/s is shown.
1. 3
1. 2
1.1
1.0
CX
0. 9
0. 8
0.7
0.6
0. 5
5 15 25 3 5 4 5 5 5 65
W i n d s p e e d s ( m /s )
In this example, at 40 m/s the ratio of the conductor drag coefficient for a conventional
conductor and a low drag aerodynamic conductor is about 1.5.
Thus, the conventional conductor may be replaced with a low drag aerodynamic conductor
with about a 50% increase in diameter and this allows an increase in conductor csa of about
200% without any increase in conductor wind load. Thus single conductors may be replaced
with either single larger conductors or perhaps with multiple smaller conductors. Smaller
conductors are more efficient in dissipating heat by natural convection than larger
conductors. This may also influence the selection of smaller bundled conductors rather than
single larger conductors particularly for sub transmission line applications.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
TABLE 28.1
COMPARISON OF DIFFERENT ALUMINIUM
Typical operating temperature
Conductivity Min. tensile strength
Type of aluminium °C
%IACS MPa Continuous Emergency
Aluminium 1350 61 160–200 100 120
Aluminium alloy 1120 59 230–250 90 120
Aluminium alloy 6201A 54 315–325 90 120
Thermal resistant TAL 60 165–190 150 180
High strength thermal resistant KTAL 60 190–250 150 180
Ultra thermal resistant ZTAL 60 165–190 200 240
TABLE 28.2
COMPARISON OF DIFFERENT CORE WIRES
GZ steel HS 1230–1320
205 11.5
GZ steel EHS 1770
Of particular interest are the invar or nickel based steel, the aluminium oxide matrix and the
carbon fibre all of which have very low coefficient of linear expansion and present
additional options for consideration in uprating existing overhead lines. The aluminium
oxide matrix and the carbon fibre also have a low mass and thus the strength to mass ratio is
much greater than that of an equivalent steel wire.
Given the variety of aluminium and steel wires, Table 28.3 details some of the types of
conductor constructions, the associated nomenclature and an indicative comparative rating
for a given conductor sag and span criteria.
TABLE 28.3
COMPARISON OF ‘SPECIAL’ CONDUCTORS
≈400 mm 2 Comparison operating current A Ratio
acsr 1020 1
tacsr 1630 1.6
accc 1650 1.62
ztacsr 1960 1.93
tacir 2060 2.02
ztacir 2110 2.07
accr 2550 ≈ 2.5
Compared to an ACSR, ‘special’ high temperature low sag conductors allow significant
increases in thermal rating and this is perhaps best illustrated in Figure 28.3 for some of the
conductors mentioned.
11
10
Sag (m)
9
AC S R
8 Z TAC I R
X TAC I R
7
AC C F
6
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
50 10 0 15 0 20 0 25 0 300
Conductor temperature (ºC)
Thus, it may be concluded that replacing existing conductors with ‘special’ conductors will
allow significant increases in the thermal rating of existing lines without any increase in
conductor wind load.
28.4 REFERENCES
[1] Guidelines for increased utilization of existing overhead transmission lines. CIGRE
TB 353; WG B2.13, August 2008.
[2] BRENNAN, GF. ‘Overhead Line Conductors’ An eleven part series, Australian
Transmission and Distribution Issue 4, 2005 to Issue 6, 2007 inclusive.
[3] BRENNAN, GF. ‘Uprating Existing Overhead Lines’ A four part series, Australian
Transmission and Distribution 2010 to 2011 inclusive.
S E C T I O N 2 9 C O N D U C T O R C L A S H I N G
29.1 GENERAL
Under short circuit conditions, conductors experience forces of attraction and repulsion due
to electromagnetic force from the fault current in the conductors. If the fault current is large
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
and experienced for a long enough time the movement can be substantial and cause
conductor clashing (particularly on distribution lines). For phase-to-phase faults the
conductor movement is more pronounced as the fault current is very high and the protection
clearance times are typically long.
Fe e d e r CB tr ip s d u e to
th e s e c o n d a r y fa ul t of th e
c l a s h i n g c o n d u c to r s
R a di a l
d i s t r ib u t i o n
fe e d e r
Recloser
trips due
S u b s t a ti o n to d ow n - Initial shor t
b u s b a r S e c o n d a r y fa u l t d u e to stream circuit fault -
c l a s h i n g c o n d u c to r s fault d ow n s t r e a m
of r e c l o s e r
The repulsion forces can be great enough to exceed wind force design limits.
Conductor clashing has a higher probability of occurrence when the fault occurs on two
adjacent conductors at the same height and the conductor has low weight. Conductor
clashing can be avoided or mitigated by the following measures:
(a) Introduce a vertical spacing between conductors.
performed with formula provided in the following EPRI publication, Bathold L.O., Clayton
R.E., Grant I.S., Longo V.J., Stewart J.R and Wilson D.D., Transmission Line Reference
Book: 115-138 kV Compact Line Design, EPRI, 1978.
S E C T I O N 3 0 L O W V O L T A G E A E R I A L
B U N D L E D C A B L E
30.1 GENERAL
LVABC may be used as—
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
30.2 SUPPORTS
Mechanical support fittings, including pole fittings, strain clamps and suspension clamps,
should comply with the requirements of AS 3766.
(a) The first element to fail should be the suspension support by failure of the suspension
clamp or the pole hardware supporting the suspension clamp. The cable should not be
allowed to slip through the suspension clamp as this causes insulation damage,
especially if an insulation piercing connector is fitted near the support.
(b) The second element to fail should be mains and service tee connections to minimize
the number of live cables lying on the ground.
(c) The third element to fail should be the pole hardware supporting the strain clamp.
(d) This should be followed by pole footing failure, cable failure and pole failure.
30.4 CLEARANCES
The clearance requirements of Section 3 of AS/NZS 7000 for Insulated Conductor,
U ≤1000 V apply to LVABC.
(b) Conditions relating to building owners painting the LVABC and any attachments to
further harmonize the cable with the facade.
(c) Liabilities for damage to the cable system resulting from failure of the building or its
facade.
(d) Liabilities for any damage done to the facade resulting from the attachment of the
cable system.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
30.7 CLEARANCES
Where the cable is in excess of 300 mm from the facade of the building which supports it,
the requirements of Section 3 of AS/NZS 7000 apply.
The minimum clearance from any part of the facade of the building which supports it, to
any position the cable may assume due to the influence of load current and solar radiation,
should be as specified in Table 30.1. Mechanical barriers or enclosures may be used to
reduce these clearances.
TABLE 30.1
CLEARANCES FOR FACADE SYSTEMS
Clearance
Minimum permissible
(see Facade situation Comments
clearances, m
Figure 30.1)
This should be increased
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
C
D
C
B
B
30.8 REFERENCES
[1] SEBIRE, J and GEELAN, G. Mechanical Design and Co-ordinated Mechanical
Failure of Low Voltage ABC Lines. Distribution 2000, May 1991, Sydney Australia.
[2] MORGAN, VT. The Current Rating of Aerial Bundled Cables. Distribution 2000,
May 1991, Sydney Australia.
[3] SEBIRE, J. The Facade Mounting of Low Voltage ABC. Distribution 2000, May
1991, Sydney Australia.
S E C T I O N 3 1 H I G H V O L T A G E A E R I A L
B U N D L E D C A B L E
31.1 GENERAL
HVABC is fully insulated for the service voltage. There are three types, as follows:
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
(a) Metallic Screened High Voltage Aerial Bundled Cable (to AS/NZS 3599.1)—
MSHVABC.
(b) Non-metallic Screened High Voltage Aerial Bundled Cable (to AS/NZS 3599.2)—
NMSHVABC.
(c) Self-supporting High Voltage Aerial Bundled Cable (not currently covered by an
Australian Standard).
In Self-supporting High Voltage Aerial Bundled Cable the mechanical load has to be
transferred to the insulated conductors and is supported at intermediate structures on line
insulators rated for the nominal operating voltage. Cables at low tension are tensioned with
clamps similar to LVABC strain clamps but at higher tensions the bundle is opened out and
bare conductor terminations are fitted to the core conductors.
The rest of this Clause covers MSHVABC and NMSHVABC only, which use a support
conductor to carry the mechanical load.
31.2 MECHANICAL
MSHVABC and NMSHVABC consist of three cores wrapped around a support conductor.
In both types the support conductor mechanically supports the cable bundle and in
NMSHVABC it also provides electrical earthing.
The cable bundle is supported at intermediate supports on suspension clamps with the
support conductor firmly clamped and the cores clamped sufficiently to prevent the cores
slipping relative to the support conductor. Measures should be taken to maintain the
insulation screens of the three cores of NMSHVABC and the metallic screens of
MSHVABC within the prospective touch voltage limits in Section 10 of AS/NZS 7000 by
earthing at appropriate intervals.
On strain or tension structures the support conductor is separated from the bundle and
terminated using standard bare conductor fittings. In both cable types measures should be
taken to prevent the cores slipping relative to the support conductor and again measures
should be taken to maintain the insulation screens or metallic screens within appropriate
potentials.
At intermediate supports consideration may also be given to using line fittings specifically
designed to cause the cable to separate from its support at a predetermined load, such as
that caused by a falling tree or limb.
31.3 ELECTRICAL
In MSHVABC the fault return path is provided by the metallic screens in each core, but
measures should be taken to ensure that the support conductor is not damaged by the
passage of fault current to the extent that it cannot support the cable for mechanical loading
and ground clearance considerations.
In NMSHVABC the support conductor should be effectively earthed to ensure that it—
(a) maintains the outer semi-conducting insulation screen potentials at acceptable levels
under all operating conditions; and
31.4 CLEARANCES
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The clearance requirements of Clause 3 for U >1000 V, Insulated with Earthed Screen,
apply to HVABC.
31.5 REFERENCES
[1] WILLIAMSON, CE, CHEALES, JA, and MCLEOD, D. Overview of Insulated HV
Overhead Systems and Applications. Distribution 2000, May 1991, Sydney Australia.
[2] COULTER, R, SEBIRE, J and MCLEOD, D. Some Design Aspects of High Voltage
Non-metallic Screened Aerial Bundled Cable Systems. Distribution 2000, May 1991,
Sydney Australia.
[3] KENT, H, CLAY, J, RICHTER, K and MCLEOD, D. Economic and Technical
Considerations of High Voltage Insulated Overhead Lines. Distribution 2000,
November 1993, Melbourne Australia.
[4] SEBIRE, J, PIASENTIN, S and SOUPROUNOVICH, K. The Development,
Introduction and Experience with HVABC in the State Electricity Commission of
Victoria. Distribution 2000, November 1993, Melbourne Australia.
S E C T I O N 3 2 C O V E R E D C O N D U C T OR
SYSTE MS
32.1 GENERAL
Covered conductor manufactured to AS/NZS 3675 may be used in a similar manner to an
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
open wire 11 to 33 kV bare overhead system, except that the following should apply:
(a) The system should include adequate protection to prevent burn down at support
points. Such matters as lightning surge protection, fault clearing times and the need
for fault current limitation should be considered.
(b) When attaching covered conductors to insulators, special measures should be taken to
manage radio interference voltage and leakage currents, particularly in high pollution
areas.
(c) Clearance between phases may be reduced (see Clause 3.7.3 Note 3 of
AS/NZS 7000).
(d) Clearance to trees may be reduced.
(e) Consideration may be given to reducing the permissible limits of approach for safe
working conditions.
Covered conductor to AS/NZS 3675 contains a water blocking compound to prevent the
migration of water under the covering and between the wires. Covered conductors have
previously been used in Australia without water blocking. These conductors suffered
corrosion of the conductor under the covering and eventual failure. The corrosion also
contributed to conductor burn down.
32.4 CLEARANCES
The clearance requirements of Clause 3 for U ≥1000 V, Bare or Covered, apply to CC.
The clearance requirements of Clause 3 for U ≥1000 V, Insulated without earthed screen,
apply to CCT, providing that the covering thickness is appropriate to the operating voltage.
32.5 REFERENCES
[1] WILLIAMSON, CE, CHEALES, JA, and MCLEOD, D. Overview of Insulated HV
Overhead Systems and Applications. Distribution 2000, May 1991, Sydney Australia.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The insulated phase conductors are supported on specially designed insulated spacer
brackets as shown in Figure 32.2. There is a single phase bracket for single phase systems.
N
M e s s e n g e r wi r e
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Ph a s e c a b l e
C A
E
(a) Ph a s e c o nf i g u ati o n
T S -1 s t i r r u p
( b) In s t a ll s ti r r ip a n d a nti - sway b a r
The spacer brackets supporting the phase conductors, which means virtually no tension is
on the phase conductors. The low tension on the phase conductors means the spans can be
considerable and are only limited by the strength of the catenary wire. The Hendrix system
of construction allows long spans in heavily treed areas.
The covered conductor has three layers of insulation, as shown in Figure 32.3. The inner
core is a stranded and compacted aluminium conductor. The next layer is a semi-conductive
layer laid on the stranded conductor for stress relief. A low density polyethylene LDPE is
the laid over the semi conductive layer, which has high insulation properties and to improve
flexibility. A tough outer layer of high density polyethylene is laid over the HDPE for
protection against rubbing against hard and sharp objects impinging on the surfaces e.g. tree
branches and bird attack.
4
3
2
1
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
The advantages of the spacer covered conductor system are the same as those given for
CCT plus:
(a) Span lengths are virtually only limited to the strength of the catenary wire and height
of the poles.
(b) It has a natural lightning protection shield provided by the overhead catenary wire.
(c) Should the conductor insulation be damaged the circuit can remain in service as the
phase conductors are strung on insulators and insulated spacer brackets.
(d) The system has a breakaway failure system, like that used for HVABC, however it
will withstand a greater force before breaking away.
The disadvantage with all covered conductor systems is that an earth fault may be difficult
to see by conventional IDMT type earth fault relays. When covered conductor systems are
used as a minimum sensitive earth fault relays should be deployed. However, there are
some more exotic relays that can be used that use harmonics to detect low grade earth
faults. It could be argued that the likelihood of a fully screen HVABC system is less likely
to experience undetected earth faults due to the proximity of the screen, though non
detection can still occur.
32.7 CLEARANCES
The clearance requirements of Section 3 of AS/NZS 7000 for U > 1000 V, Bare or Covered,
apply to CC.
The clearance requirements of Section 3 of AS/NZS 7000 for U > 1000 V, insulated without
earthed screen, apply to CCT, providing that the covering thickness is appropriate to the
operating voltage.
(d) Surge arresters may be of the gap (refer Figure 32.4 for Current Limiting Arching
Horn—CLAH) or gapless type and may have a disconnection isolator at the base of
the arresters to protect the arrester against internal failure (refer Figure 32.5). This
also aids in fault detection.
D i s c h a r g e c o n n e c to r
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
A i r g a p 20 m m
A d j u s t a b l e n otc h e d h o m
Cu r r e nt- li m i ti n g e l e m e nt
Bird cap
Line
c o n n e c ti o n
Po l y m e r i c cable
s u r g e a r r e s te r
Support
B r a c ke t
I n s u l a te d
b r a c ke t
Disconnect
d evi c e E a r th
cable
32.9 REFERENCES
[1] WILLIAMSON, CE, CHEALES, JA, and MCLEOD, D. Overview of Insulated HV
Overhead Systems and Applications. Distribution 2000, May 1991, Sydney Australia.
[2] ELFORD, RF, KATO, K, NAGASAKA, H, and MATSUMOTO, J. Development and
Introduction of Aerial Insulated Unscreened Conductor (IUC) in South Australia.
Distribution 2000, May 1991, Sydney Australia.
[3] KENT, H, CLAY, J, RICHTER, K and MCLEOD, D. Economic and Technical
Considerations of High Voltage Insulated Overhead Lines. Distribution 2000,
November 1993, Melbourne Australia.
[4] HINKKURI, A, LEHTINEN, I and NOPONEN, K. On the Design and Experience
with High Voltage Covered Conductor Systems. Distribution 2000, November 1993,
Melbourne Australia.
S E C T I O N 3 3 O V E R H E A D L I N E S I N T R A F F I C
C O R R I D O R S O R P R O X I M I T Y T O O T H E R
S E R V I C E S
33.1.1 General
Pole locations in traffic corridors are influenced by factors including traffic speed, traffic
volume, road deviation and traffic calming devices (roundabouts, chicanes, etc.),
embankments (cut or fill slopes) next to the road, frangibility of the pole, road kerbing and
parking.
Poles can be positioned closer to the road where there is a permanent barrier between the
poles and the road. Barriers can take the form of natural items such as kerbs, trees, rocks,
and crash barriers such as walls, wire rope, W-barrier, etc.
Frangible poles can typically be positioned closer to the road because they absorb the
impact of the vehicle to a greater extent than non-frangible poles.
Setback requirements will vary with the jurisdiction and various Codes of Practice exist at
both local and state government level. Supply Authorities should endeavour to work with
relevant road transport authorities, such as Councils, Shires and Main Roads Departments,
to position poles in mutually acceptable positions.
Guidance to setbacks and barriers is provided in:
(a) AS/NZS 1158.1.2.
(b) Austroads publications and guidelines for rural and urban road design.
(c) AS/NZS 3845.
33.1.2 Special considerations for slip based poles
Slip based poles should not be used in areas with high pedestrian based activity. The slip
based poles are unsuitable for these areas as these poles are deliberately designed to fall
over after vehicle impact to lessen the damage to the vehicle occupants. Having these poles
fall over in high pedestrian areas introduces an unacceptable risk. High pedestrian areas are
schools, shopping centres, major entrances/exits to sporting or entertainment venues, and
train or bus stations entrances/exits.
documents are: EEA Guide to Safety Management of Power Line Waterway Crossings and
Maritime New Zealand: New Zealand System of Buoys and Beacons. The design process
includes liaison with the local maritime jurisdiction to ascertain likely vessel heights and
determination of maximum water levels prior to layout design in order to achieve the
required safety clearances. Guidance on appropriate signage and marking is also provided
in AS 6947.
A worked example using the risk based NSW guide is given below.
EXAMPLE 3—NEW CROSSINGS KOOLKHAN TO MACLEAN #2 66kV
This is a worked example to assist in assessing three new 66 kV (overhead or submarine)
crossings in accordance with the Crossings of NSW Navigable Waters: Electricity Industry
Code.
Aim:
Essential Energy is planning to construct three new river crossings and wishes to determine
the appropriate type of crossing to construct (overhead or submarine) and, if an overhead
crossing is appropriate, the minimum design height as well as the signage requirements.
The Situation:
Three new 66 kV electrical crossings are proposed for a section of the Koolkhan to Maclean
overhead line on the South Arm of the Clarence River near Tyndale. The three crossings are
located within 5 km of each other.
Two fixed road bridges exist in this section of waterway, one located at Maclean and the
other at Brushgrove prevent large sailing vessels from entering from the main arm of the
Clarence River.
Communicate and Consult:
Consultations are required with NSW Maritime as navigation safety regulator. Consultation
is also required with the local Council, Manly Hydraulics Laboratory, property owners,
users of the river including the charter vessel industry, local marina operators, local sailing
clubs, commercial vessel operators, etc. If work involves state road infrastructure the
RTA’s involvement, prior to the work commencing is required. The RTA’s asset
section will need to be contacted where a river bed will be disturbed adjacent to state road
infrastructure. The RTA’s Bridge Maintenance Planner will need to be notified in regards to
sign posting on bridges with state significance.
Results of the Consultations:
The major issue from consultation is that Maritime agreed in principle that a maximum
vessel height of 12m for all necessary new overhead work was appropriate for this
section of waterway.
Risk Analysis:
Step 1—Establish risk context:
Some issues arising from consultations include:
The section of river is deemed navigable and is sufficiently deep and wide enough
(typically 100 m–200 m in parts) to attract both motorised vessels and trailerable yachts
Trailerable yachts may well navigate parts of the river with or without sail. The majority of
this section of the Clarence River is mostly orientated North South.
The distance of navigable water between the two low level bridges is approximately 21 km
with two boats ramps apparent.
(a) Small sailing boats e.g. a trailer sailer would be able to navigate on the section of
river between Brushgrove and MacLean
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
(b) There are several private jetties along the river where small power vessels are located
(c) There are two existing LV, eight 11 kV and one existing 66 kV crossings. Signage
indicating safe navigable heights from 7.9 m through to 12.2 m
(d) In major flood conditions, that frequently occur in the Clarence, this section of river
is used by motorised SES. vessels.
Incident History: There are no recorded incidents in this section of the Clarence River.
Code Compliance: For the crossings to comply with the Code:
Manly Hydraulics (MHL) Sydney provided a Highest Astonomical Tide (HAT) Figure for
this crossing of 0.67 m Australian Height Datum (AHD) ±0.05 m. (November 18 2009).
The majority of vessels that could possibly navigate this section of the Clarence River
would have a maximum vessel height of 12 m. It would be considered very rare for a vessel
with a mast height exceeding 12 m to navigate in the South Arm section of the Clarence
River between the Maclean and Brushgrove bridges.
Maximum expected water level above AHD: = HAT + Wave effects
= 0.67 + 0.05 + 0.3
= 1.02 m
Maximum height of vessels expected: =12 m
Electrical Clearance for 66 kV (from AS 6947): = 0.8 m
Safety margin: =2.2 m
Initial height calculations: = 1.02 + 12 + 0.8 + 2.2
Minimum design height of crossing above AHD: = 16.02 m
Maximum vessel height indicated on signs for this crossing
example: =12 m
Step 2—Categorize risk likelihoods and consequences:
Likelihood: Given the crossing’s location, limited sailboat use and no previous incidents
reported in the area it is considered from Essential Energy’s corporate risk management
procedure = Rare.
Consequence: A range of consequences are possible but the most significant of these would
range from extensive injuries requiring hospitalisation to a fatality or multiple fatalities, i.e.
from Essential Energy’s corporate risk management procedure= Major/Catastrophic.
Risk Rating: from Essential Energy’s corporate risk management procedure the risk
rating= Moderate (Tolerable) therefore the crossings may be constructed as an overhead
crossings.
Step 3—Determine residual risk and appropriate action:
From Step 2 above it can be seen that the risk rating is tolerable if the minimum height of
the overhead crossing is designed to 16.02m above AHD.
Conclusion:
The crossings can be installed as overhead construction with minimum design height of
16.02 m above AHD.
NOTE: Crossing heights will require checking after 4 weeks of operation to verify that the
assigned crossing heights have been obtained.
In order to better utilize service corridors and improve visual amenity joint use of
infrastructure with other utilities should be considered where it can be effectively
implemented.
It is important to coordinate with nearby utility services to avoid both physical and
electrical interference. Overhead power-lines can electrically interfere with other utility
services by creating Earth Potential Rise (EPR) and Low Frequency Induction (LFI)
hazards. EPR may occur where high voltage earths are installed in the vicinity of these
services. LFI can occur where overhead power lines are run in parallel and in close
proximity with utility services that are conductive (i.e. oil, gas and water pipelines,
telecommunications equipment and road control equipment).
Prior to commencement of line construction, arrangements should be made with the
relevant utilities to locate assets (in order to avoid damage during construction) and
coordinate joint use arrangements where agreed.
Particular consideration should be given to step and touch potentials and induced voltages
associated with the line which could impact on the operation of other services.
Publications relevant to the coordination of power and telecommunication circuits include:
AS/NZS 3835.1, AS/NZS 3835.2, and Standards Australia Handbooks: HB 87, HB 88,
HB 100, HB 101, HB 102, HB 103, and HB 219.
should be fitted. Areas that may have conductors higher than some of the poles are in
valleys, across water ways and near hills.
exceptionally high ground clearance across deep valleys. Consideration should also be
given to the marking of power lines in areas where regular low-level flying operations take
place.
Guidance on the marking of power lines in Australia for the purposes of air navigation is
provided in AS 3891, Parts 1 and 2:
In general aerial lines should not be installed so as to cause a hazard with aircraft.
33.6.2 Types of markers
Conductors and structures in locations susceptible to aerial strike or inadvertent contact in
the vicinity of the line can be marked to improve their visibility and reduce the risk of
contact.
Marking may take the form of reflective or brightly coloured discs, flags or marker balls
attached to the cables or structures. Care should be taken to ensure that markers do not
compromise circuit clearances and overload structures.
33.6.3 Permanent markers
The fitting of permanent makers is the responsibility of the line owner. Permanent makers
may be in the form of spheres attached to the conductors as described AS 3891.
Where spheres are used, account must be taken of their weight and resistance to wind when
determining swing, sag and tension. In simple cases, the performance of the conductor may
be determined by approximating the point load of the sphere to a distributed load, but
software packages, which more accurately reflect actual condition, are available and should
be used where practicable.
33.6.4 Temporary markers
Where aircraft operations such as crop dusting are carried out in the vicinity of overhead
lines it is the responsibility of the aircraft operator to mark the location and direction of the
lines. Such markers may be attached to the conductors or supports (subject to approval of
the line owner) or placed on the ground in the vicinity of the overhead line.
33.6.5 Over crossing markers
Where inspection of overhead lines by aircraft is conducted, supports should be marked
each side of any over crossing.
place or may take place, the positioning of structures may need to be considered to
minimise the risk of contact.
This may require consideration of:
(a) Design layouts that position structures away from regular agricultural activities e.g.:
(i) Along fence lines instead of across paddocks.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 3 4 A P P L I C A T I O N O F S U R G E
A R R E S T E R S
Surge arresters can be applied to an overhead line to improve the lightning performance.
Surge arresters have been used in the following applications:
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
S E C T I O N 3 5 L I N E E Q U I P M E N T — O V E R H E A D
L I N E F I T T I N G S
35.1 FITTINGS
Fittings are used in suspension and tension string designs to attach the conductors, through
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Not recommended for high tension connections are: those arrangements shown in Figures
35.2 to 35.6.
HB 331—2012
© Standards Australia
260
www.standards.org.au
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
www.standards.org.au
261
© Standards Australia
HB 331—2012
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
HB 331—2012
© Standards Australia
262
www.standards.org.au
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
www.standards.org.au
263
© Standards Australia
HB 331—2012
HB 331—2012 264
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
Fittings are designed in Australia and New Zealand in accordance with AS/NZS 1154 and
AS/NZS 2947 with the strength ratings of 70 kN, 120 kN and 160 kN. Other international
ratings are 45 kN (railways), 125 kN (20 mm), 187 kN (old AS/NZS 1154), 210 kN, and
400 kN (AS/NZS 4435.2).
Fittings are made of forged steel or ductile cast iron. Some applications require cold
temperature forging steels but this does not apply to ductile cast iron.
With regards to a twisted socket tongue, the socket allows rotation within the socket, (see
Figure 35.7), however the security device in the socket is often required to be in a position
to be easily removed from the tower live line (see Clause 35.6).
T
B A
All of these calculations are made on new materials with assumed ‘manufacturer-declared’
strengths. The interest is accommodation of the possibility that the strength of some line
component has degraded. The degradation is both difficult to discover and very difficult to
quantify. Coupling these problems with the unclear ability to describe an acceptable factor
of safety underscores the point that a definitive solution does not exist.
It is noted above that the placement of a point load in the form of a cart or person on a span
of conductor increases the conductor’s tension and that the increase is greater in shorter
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
T EN S I O N IN CR E AS E D E V ELO PED BY CA R T
T EN S I O N IN CR E AS E, (% of c a r t we i g ht)
4 0 0%
3 5 0%
3 0 0%
250%
20 0%
150%
18 0 m s p a n
10 0%
305 m span
50%
425 m s p a n
0%
10 20 30 40 50 60 70
CA R T P O S I T I O N , (% of s p a n)
S E C T I O N 3 6 C L I M B I N G A N D W O R K I N G A T
H E I G H T S
construction industries to make work sites safer and this has necessitated changes in work
practices.
The following sets out an approach for construction and maintenance work practices on
overhead lines, in an effort to enhance safety.
designed to provide for linepersons to use a portable fall-arrest system in accordance with
AS/NZS 1891. Consideration may be given to installing a permanent static line or rail fall-
arrest system in accordance with AS/NZS 1891.4.
For overhead line construction and maintenance activities this requires the provision of the
following to minimize risk of potential injury with attachment at all times to provide either
‘restrained fall’, ‘limited free fall’, or ‘free fall’ restraint.
36.4.2 ‘Restrained fall’ fall arrest
A combination of anchorage placement and fixed length restraint line or pole strap length,
which will permit only a restrained fall. This also requires a 12 kN ultimate strength
anchorage for the restraint devices. Any structural element used for the attachment of the
restraint lanyard or pole strap should be capable of supporting this load as a single point
load application, in a deformed state but without failure.
36.4.3 ‘Limited free fall’ fall arrest
A combination of anchorage placement and fixed restraint line or length of pole strap which
will permit only a limited free fall to <600 mm.
This requires the anchorage point to have a 12 kN ultimate strength capacity for a single
person.
36.4.4 ‘Free fall’ fall arrest
A combination of anchorage placement and fixed restraint line or length of pole strap which
will permit only a limited free fall to <2000 mm.
This requires the anchorage point to have a 15 kN ultimate strength capacity for a single
person.
pole strap, in a ‘restrained fall’ position, and this requires the selection of anchorage points
with at least 12 kN ultimate capacity. Any structural load carrying or redundant brace
member fixed with a single 16 mm diameter bolt at each end can provide this load restraint
capacity in a non-deformed or deformed state.
In general, attachment should be at bracing node points wherever possible in order to
provide containment of any potential lanyard movement, and afford more secure anchorage.
The following anchorage capacities are required to be provided by the structure design:
(a) Inertia reel attachment points for work on cross-arm tips—15 kN.
(b) Attachment to bracing node points for work on E/W peak—15 kN.
(c) Attachment to bracing node points—15 kN.
(d) Typical static line attachment point above climbing step bolts—21 kN (2 persons).
Figure 36.1 provides a typical arrangement of anchorage points for work on lattice steel
structures.
In climbing in an attached mode, the location of anchorage points should always be selected
above the waist position, in order to control inadvertent potential fall/slip height and
consequential injury and to avoid potential pendulum effects in the event of a fall. Hence on
crossarms with a sloping top chord there is a limit to how far a person can translate towards
the crossarm tip before he needs to use an alternative restrain device such as an inertia reel
as indicated in Figure 36.1.
It has become a practice in some areas to attach lanyards to step bolts. It must be
understood that step bolts less than 20 mm diameter have strength limitations. In particular
16 mm diameter step bolts have exhibited low ductility and strength and should not be used
for attachment purposes.
In e r ti a r e e l at t a c h m e nt p o i nt s fo r
wo r k o n c r o s s a r m tip s - 15 k N
At t a c h m e nt to b r a c i n g n o d e p o i nt s
fo r wo r k o n E / W p e a k - 15 k N
Ty p i c a l s t ati c li n e at t a c h m e nt
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
p o i nt a b ove c li m b i n g s te p b o l t s
At t a c h m e n t to b r a c i n g
n o d e p o i nt s - 15 k N
At t a c h m e n t to 20 m m s te p
b o l t s , o r a n c h o r l o o p s -12 k N
D O N OT AT TAC H TO 16 m m
S T E P B O LT S
L i m i t of l a nya r d at t a c h m e nt a n c h o r a g e
r e s tr a i nt - In e r ti a r e e l m u s t b e u s e d
b eyo n d thi s p o i nt
L i m i t of l a nya r d at t a c h m e nt a n c h o r a g e
r e s tr a i nt - at t a c h m e nt p o i nt m u s t b e
a b ove wa i s t p o s i ti o n o n c r o s s a r m s
( E xc e pt fo r live li n e a c c e s s i n c r o u c h e d
p o s i ti o n to c r o s s - a r m tip b u t wi th
at t a c h m e nt a lways a b ove wa i s t)
APPENDIX A
REFERENCED DOCUMENTS
AS
1154 Insulator and conductor fittings for overhead power lines
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
AS
4436 Guide for the selection of insulators in respect of polluted conditions
4799 Installation of underground utility services and pipelines within railway
boundaries
5604 Timber—Natural durability ratings
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
AS/NZS
2344 Limits of electromagnetic interference from overhead a.c. powerlines and
high voltage equipment installations in the frequency range 0.15 to 1000
MHz
2947 Insulators—Porcelain and glass for overhead power lines—Voltages greater
than 1000 V a.c.
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
ENA
EG-0 EG-0 Power system earthing guide
Part 1: Management principles
ESAA
D(b) 5 Current rating of bare overhead line conductors
ASCE MANUALS No. 72 and 52
Licensed to Mr David Tombling on 4 April 2012. 1 user personal user licence only. Storage, distribution or use on network prohibited (10287015).
NENS
05 National Fall Protection Guidelines for the electricity industry
EEA
EEA Guide to Safety Management of Power Line Waterway Crossings and
Maritime New Zealand: New Zealand System of Buoys and Beacons
EEA Guide to Power System Earthing Practice
EEA/NZ
Use of personal fall arrest systems
Guide—Operation and maintenance of elevating work platforms
EN
50341 Overhead Electrical Lines Exceeding Ac 45 Kv (series)
ACKNOWLEDGEMENTS
The EL-052 Committee would like to acknowledge the contributors to this Handbook from
the following working group members.
Grant Bailey
Gary Brennan
Jim Brooks
Greg Bruce
Greg Chapman
Bart Clulow
Chris Dalitz
Peter Dulhunty
David Eccles
Leith Elder
Robert Fairweather
John Giles
Tony Gillespie
Henry Hawes
Angus Ketley
Colin Lee
Ross McLennan
David Morato
Dennis Munn
Colin Nye
Carl Rathbone
Robert Rogerson
Bryan Symmonds
Standards Australia
Standards Australia develops Australian Standards® and other documents of public benefit and national interest.
These Standards are developed through an open process of consultation and consensus, in which all interested
parties are invited to participate. Through a Memorandum of Understanding with the Commonwealth Government,
Standards Australia is recognized as Australia’s peak non-government national standards body. Standards Australia
also supports excellence in design and innovation through the Australian Design Awards.
Australian Standards®
Committees of experts from industry, governments, consumers and other relevant sectors prepare Australian
Standards. The requirements or recommendations contained in published Standards are a consensus of the views
of representative interests and also take account of comments received from other sources. They reflect the latest
scientific and industry experience. Australian Standards are kept under continuous review after publication and are
updated regularly to take account of changing technology.
International Involvement
Standards Australia is responsible for ensuring the Australian viewpoint is considered in the formulation of
International Standards and that the latest international experience is incorporated in national Standards. This role is
vital in assisting local industry to compete in international markets. Standards Australia represents Australia at both
the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC).