POWER SYSTEM ANALYSIS

Texas Instruments Philippines Inc. Design and Build for


Office and Stockroom Building

Project: TIPI Design and Build for Office and Stockroom Building
Loakan Rd, PEZA
Baguio City

Client: Susalum Corporation


SAL - Bldg. Sta Rosa - Tagaytay Highway
Sitio Muzon, Brgy. Putingkahoy, Silang, Cavite

Submitted: February 29, 2024

Prepared by:

Kevin C. Fajardo, PEE

Lic.no 4876
TIN no 413 934 057
PTR no 2809426
Issued on 1/8/2024
Issued at Baliuag, Bulacan

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
Table of Contents
1. Project Summary..................................................................................................... 1
1.1 Major objectives of the studies: ........................................................................ 1
1.2 Project Data .................................................................................................. 1
2. Executive Summary ................................................................................................. 1
2.1 Voltage Drop ................................................................................................. 1
2.2 Short Circuit Calculation .................................................................................. 1
2.3 Protective Device Coordination ......................................................................... 1
2.4 Arc Flash Evaluation ....................................................................................... 1
3. Methodology ........................................................................................................... 2
3.1 Voltage Drop/Load Flow Calculation .................................................................. 2
3.2 Short Circuit Calculation .................................................................................. 2
3.3 Protective Device Coordination ......................................................................... 3
3.4 Arc Flash Analysis .......................................................................................... 3
4. Findings and recommendations .................................................................................. 5
4.1 Voltage Drop ................................................................................................. 5
4.2 Short Circuit ................................................................................................. 5
4.3 Protective Device Coordination ......................................................................... 5
4.4 Arc Flash Evaluation ....................................................................................... 5
5. Closing Remarks...................................................................................................... 6

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
1. Project Summary

A power system analysis for Texas Instruments Philippines Inc. located at Loakan
Road, Baguio. Load flow analysis calculation, short circuit analysis, protection
coordination and arc flash analysis are performed to verify system safety and adequacy.

1.1 Major objectives of the studies:

• Verify if voltage drop on the panels are within tolerable limits using load flow
analysis, taking into account the existing equipment
• Determine calculated fault duties, taking into account the existing equipment as a
reference for new equipment ratings
• Recommend protective device settings which selectively isolate faults in a manner
which is consistent with the basic system design and applicable codes and
standards. These recommendations will be given to achieve an optimum balance
between protection and selective fault isolation.
• Determine arc flash incident energy levels and PPE requirements.

1.2 Project Data

Calculations were based on data provided by Susalum Corporation and Texas


Instruments Philippines Inc. All input data are shown on Appendix 1.

2. Executive Summary

2.1 Voltage Drop

Voltage drop across all panels are within acceptable limits. Please refer to Section 4
for more details.

2.2 Short Circuit Calculation

All devices within the project scope were found to have acceptable short circuit
interrupting ratings when compared to system fault duties. Please refer to Sections
3.2 and 4.1 and Appendix 1, 3, 4 for more detailed information.

2.3 Protective Device Coordination

The recommended device settings provided in this report should provide adequate
system protection and coordination. However, there are cases of unavoidable non-
selectivity between protective devices. Please refer to Section 3.3 and 4.3 and
Appendix 5 & 6 for more detailed information.

2.4 Arc Flash Evaluation

The arc flash hazard calculations within this study are based on the as-found
settings. As such, all protective devices must be verified to be still set as per this
study prior to the application of the corresponding arc flash hazard labels. No work
should be done on or around any energized equipment without the use of a proper
level of PPE and adequate training. Please refer to Sections 3.4 and 4.4 and
Appendix 7 for more detailed information.

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0 1
3. Methodology

PTW SKM software is used to come up with the following calculations:

3.1 Voltage Drop/Load Flow Calculation

A Load Flow Study is conducted on a power system to evaluate the adequacy of


continuous and emergency overload ratings of cables, transformers, and protective
devices. The Study may also be used to determine anticipated low, or high, voltage levels
on various sections of the power system under various loading conditions. The software
uses the exact, iterative solution to come up with the calculation.

PEC recommends a voltage drop not more than 5%.

3.2 Short Circuit Calculation

Three phase, line to line, single line to ground and double line to ground faults are
calculated to determine the highest fault current as a reference for equipment short circuit
withstand and interrupting ratings.

Three phase fault calculation:

Ø =

Where:
I3Øpu = Per unit three-phase fault
E = Per unit voltage, equal to 1
Z1 = Positive sequence impedance

Single line to ground fault:


=

Where:
ISLGpu = Per unit single line to ground fault
Z1 = Positive sequence impedance
Z2 = Negative sequence impedance
Z0 = Zero sequence impedance

Line to Line fault:



=

Double Line to Ground Fault


=

=−

=−

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0 2
Where:
= Phase A positive sequence current
= Phase A negative sequence current
= Phase A zero sequence current

The calculation uses 100MVA base for all scenarios. The summary of the calculated faults
to be used as basis for kAIC and Short Circuit Withstand Ratings for devices and
equipment are shown in Appendix 3

3.3 Protective Device Coordination

The intent of the protective device coordination analysis is to evaluate, and if


necessary, recommend overcurrent protective device setting adjustments to yield
optimum power system performance, reliability and safety. In many cases the
above goals conflict with one another and compromises must be made based on
system criticality and facility operating philosophy. Where necessary, the
recommended settings were chosen to maximize system reliability while minimizing
conditions of jeopardized system selectivity.

System selectivity is most often illustrated by the use of Time-Current Curves


(TCC’s) which graphically illustrate the overcurrent responses of protective devices
to overcurrent events. The specific manufacturer specified time-current
characteristics of the overcurrent devices are plotted on logarithmic graphs. Other
electrical equipment characteristics such as, but not limited to, transformer damage,
transformer inrush, motor starting and generator decrement can also be plotted on
the same graphs to help with the analysis. Protective device setting tables and
TCC’s for the system studied are included in the Appendices.

3.4 Arc Flash Analysis

Arc flash evaluations are used in conjunction with the client’s/facility operator’s
safety policy to determine the required personal protective equipment (PPE) when
working on or near energized equipment. Many electrical injuries are burns that are
the result from exposure to the energies liberated during an arcing fault. The burns
are typically second and third degree in nature and are often fatal.

The calculation method used is in accordance with the Philippine Electrical Code
2017, IEEE 1584-2018 Guide for Performing Arc-Flash Hazard Calculations and NFPA
70E-2021 Standard for Electrical Safety in the Workplace

The arc flash analysis will determine the incident energy level on each operable
equipment while energized to guide personnel on appropriate PPE to wear while
working:

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0 3
Incident
Energy PPE DESCRIPTION
(cal/cm2)
Long sleeve shirt & pants or coverall (nonmelting or untreated
0-1.2 natural fiber), safety glasses/goggles, leather gloves, hearing
protection

Arc-rated (AR) long sleeve shirt & AR pants or AR coverall or AR


flash suit, AR face shield & AR balaclava or AR flash suit hood, hard
1.2-12
hat, safety glasses/goggles, hearing protection, leather gloves,
leather footwear

Arc-rated (AR) long sleeve shirt & AR pants or AR coverall and/or AR


>12 flash suit, AR flash suit hood, AR gloves, hard hat, safety
glasses/goggles, hearing protection, leather footwear

Based on the PPE descriptions detailed above, all resulting arc flash hazard labels will
be similar to that as shown below.

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0 4
4. Findings and recommendations

4.1 Voltage Drop

All panels have acceptable voltage drop values as shown by the load flow analysis in
Appendix 2.

4.2 Short Circuit

Based on the calculation of the maximum possible fault current on all locations, the actual
ratings of installed devices are evaluated if it can safely isolate faulted circuits and
withstand mechanical damage brought by short circuits. All devices within the project
scope were found to have acceptable short circuit ratings when compared to system fault
duties. Complete short circuit analysis input & output reports as well as device evaluation
tables are contained in the Appendices.

4.3 Protective Device Coordination

The recommended device settings provided in this report should provide adequate system
protection and coordination. However, there are a few cases of unavoidable non-
selectivity between levels of protective devices as indicated by the overlapping of
characteristic curves. These cases are inevitable due to the particular characteristics of
each device. The recommended settings were chosen to maximize system reliability while
minimizing conditions of jeopardized system selectivity. It is recommended to implement
the settings as indicated in the Appendix and thoroughly test the devices to assure proper
operation within the manufacturer’s tolerances. See Appendix 6 for more details on the
device characteristic curves.

4.4 Arc Flash Evaluation

The arc flash hazard calculations within this study are based on the recommended
settings. As such, all recommended settings must be successfully implemented prior to
the application of the corresponding arc flash hazard labels. These recommended settings
were typically chosen to provide optimum protective device selectivity while minimizing the
resulting arc flash incident energy at each location where possible. No work should be
done on or around any energized equipment without the use of a proper level of PPE and
adequate training. An arc flash hazard summary/data table and labels are included in the
Appendix which provides full details of the analysis and the results.

IMPORTANT NOTE: The Arc flash hazard analysis methods and calculations used within
this study are based on the protective devices operating as designed and being applied,
maintained and tested as per the manufacturer’s specifications and accepted industry
standards. Periodic maintenance and testing of the electrical equipment is highly
recommended as endorsed by the NFPA-70B Standard, Recommended Standard for
Electrical Equipment Maintenance, to confirm the safe and acceptable operation of the
power system equipment and protective devices.

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0 5
5. Closing Remarks

Power system studies are an important part of the electrical engineering processes and
continuously proves to provide safe, reliable and efficient systems. A full power system
study that includes voltage drop calculation, load flow analysis, short circuit analysis,
protection coordination and arc flash analysis is highly recommended.

This study is intended for use by qualified individuals to help facilitate the installation,
operation, maintenance and safety of the electrical power system as depicted. Modification
of equipment, changes to system configuration, adjustment of trip-unit settings, and/or
failure to properly maintain equipment may invalidate these results.

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0 6
Appendix 1: Study Input Data

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
Project: 20240124PSS - TIPI
Base Project
Texas Instruments Philippines Inc.
TIPI Office and Stockroom Building

DAPPER Fault Analysis Input Report (English)

Utilities

Contribution Bus In/Out Nominal -------- Contribution Data -------- PU (100 MVA Base)
From Name Name Service Voltage Duty Units X/R R PU X PU

PH5-1B-1 BUS-0001 In 480 3P: 1,000 MVA 45.00 Pos: 0.002 0.100
SLG: 0 MVA 8.00 10,000,000.000
Zero: 10,000,000.000

PH5-1B-2 BUS-0002 In 480 3P: 1,000 MVA 45.00 Pos: 0.002 0.100
SLG: 0 MVA 8.00 10,000,000.000
Zero: 10,000,000.000

Motors

Contribution # of Bus In/Out Nominal --------- Contribution Data -------- PU (100 MVA Base)
From Name Motors Name Service Voltage Base kVA Xd" X/R R PU X PU

MTRI-AHU-1 1 BUS-0025 In 480 35.00 0.1507 4.90 87.912 430.680

MTRI-AHU-2 1 BUS-0026 In 480 35.00 0.1507 4.90 87.912 430.680

Cables

Cable From Bus In/Out Qty Length ------ Cable Description ------ Per Unit (100 MVA Base)
Name To Bus Service /Ph Feet Size Cond. Type Duct Type Insul R pu jX pu

1
Cable From Bus In/Out Qty Length ------ Cable Description ------ Per Unit (100 MVA Base)
Name To Bus Service /Ph Feet Size Cond. Type Duct Type Insul R pu jX pu

CBL-AHU-1 DP-4 In 1 200 50 Copper Steel Conduit PVC Pos: 10.4141 4.7734
Zero: 12.5069 2.9314

DISC-AHU-1

CBL-AHU-2 DP-5 In 1 200 50 Copper Steel Conduit PVC Pos: 10.4167 4.7743
Zero: 12.5087 2.9340

DISC-AHU-2

CBL-DP-1 SEC-XF2-TX-1 In 2 49 175 Copper Steel Conduit PVC Pos: 2.2175 2.8430
Zero: 2.4052 1.7513

DP-1

CBL-DP1-UPS SEC-XF2-TX-4 In 2 49 175 Copper Steel Conduit PVC Pos: 2.2175 2.8430
Zero: 2.4052 1.7513

DP1-UPS

CBL-DP-2 SEC-XF2-TX-2 In 2 49 175 Copper Steel Conduit PVC Pos: 2.2175 2.8430
Zero: 2.4052 1.7513

DP-2

CBL-DP2-UPS BUS-0042 In 2 49 175 Copper Steel Conduit PVC Pos: 2.2175 2.8430
Zero: 2.4052 1.7513

DP2-UPS

CBL-DP-3 SEC-XF2-TX-3 In 2 49 175 Copper Steel Conduit PVC Pos: 2.2175 2.8430
Zero: 2.4052 1.7513

DP-3

2
Cable From Bus In/Out Qty Length ------ Cable Description ------ Per Unit (100 MVA Base)
Name To Bus Service /Ph Feet Size Cond. Type Duct Type Insul R pu jX pu

CBL-DP3-UPS SEC-XF2-TX-6 In 2 49 125 Copper Steel Conduit PVC Pos: 3.0705 2.9567
Zero: 3.3889 1.7513

DP3-UPS

CBL-DP-4 MDP In 1 49 60 Copper Steel Conduit PVC Pos: 2.1354 1.1531


Zero: 2.4621 0.7047

DP-4

CBL-DP-5 MDP In 1 49 60 Copper Steel Conduit PVC Pos: 2.1354 1.1531


Zero: 2.4621 0.7047

DP-5

CBL-MDP BUS-0002 In 5 984 100 Copper Steel Conduit PVC Pos: 5.3813 4.3563
Zero: 6.3208 2.6906

MDP

CBL-MDP-UPS BUS-0001 In 5 984 100 Copper Steel Conduit PVC Pos: 5.3813 4.3563
Zero: 6.3208 2.6906

MDP-UPS

CBL-P1 DP-1 In 1 66 60 Copper Steel Conduit PVC Pos: 15.1627 8.1879


Zero: 17.4826 5.0037

PNL-P1

CBL-P-2FA DP-2 In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-2FA

3
Cable From Bus In/Out Qty Length ------ Cable Description ------ Per Unit (100 MVA Base)
Name To Bus Service /Ph Feet Size Cond. Type Duct Type Insul R pu jX pu

CBL-P-2FA-UPS DP2-UPS In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-2FA-UPS

CBL-P-2FB DP-2 In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-2FB

CBL-P-2FB-UPS DP2-UPS In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-2FB-UPS

CBL-P-2FC DP-3 In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-2FC

CBL-P-2FC-UPS DP3-UPS In 1 55 125 Copper Steel Conduit PVC Pos: 6.8648 6.6106
Zero: 7.5767 3.9155

PNL-P-2FC-UPS

CBL-P-IDF DP-3 In 1 40 60 Copper Steel Conduit PVC Pos: 9.2456 4.9926


Zero: 10.6601 3.0510

PNL-P-IDF

CBL-P-IDF-UPS DP3-UPS In 1 40 60 Copper Steel Conduit PVC Pos: 9.2456 4.9926


Zero: 10.6601 3.0510

PNL-P-IDF-UPS

4
Cable From Bus In/Out Qty Length ------ Cable Description ------ Per Unit (100 MVA Base)
Name To Bus Service /Ph Feet Size Cond. Type Duct Type Insul R pu jX pu

CBL-P-LG DP-1 In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-LG

CBL-P-LG-UPS DP1-UPS In 1 55 60 Copper Steel Conduit PVC Pos: 12.7088 6.8636


Zero: 14.6551 4.1964

PNL-P-LG-UPS

CBL-P-LP DP-3 In 1 50 30 Copper Steel Conduit PVC Pos: 23.1023 6.5875


Zero: 27.7598 4.0796

PNL-P-LP

CBL-P-LP-UPS DP1-UPS In 1 50 30 Copper Steel Conduit PVC Pos: 23.1081 6.5863


Zero: 27.7540 4.0761

PNL-P-LP-UPS

CBL-P-UG DP-1 In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-UG

CBL-P-UG-UPS DP1-UPS In 1 55 60 Copper Steel Conduit PVC Pos: 12.7126 6.8648


Zero: 14.6577 4.1952

PNL-P-UG-UPS

CBL-XF2-TX-1 MDP In 1 148 200 Copper Steel Conduit PVC Pos: 2.2422 3.1391
Zero: 2.3383 1.9219

PRI-XF2-TX-1

5
Cable From Bus In/Out Qty Length ------ Cable Description ------ Per Unit (100 MVA Base)
Name To Bus Service /Ph Feet Size Cond. Type Duct Type Insul R pu jX pu

CBL-XF2-TX-2 MDP In 1 148 200 Copper Steel Conduit PVC Pos: 2.2422 3.1391
Zero: 2.3383 1.9219

PRI-XF2-TX-2

CBL-XF2-TX-3 MDP In 1 148 200 Copper Steel Conduit PVC Pos: 2.2415 3.1384
Zero: 2.3396 1.9232

PRI-XF2-TX-3

CBL-XF2-TX-4 MDP-UPS In 1 148 200 Copper Steel Conduit PVC Pos: 2.2415 3.1384
Zero: 2.3396 1.9232

PRI-XF2-TX-4

CBL-XF2-TX-5 MDP-UPS In 1 148 200 Copper Steel Conduit PVC Pos: 2.2415 3.1384
Zero: 2.3396 1.9232

PRI-XF2-TX-5

CBL-XF2-TX-6 MDP-UPS In 1 148 200 Copper Steel Conduit PVC Pos: 2.2415 3.1384
Zero: 2.3396 1.9232

PRI-XF2-TX-6

2-Winding Transformers

Xformer In/Out ------------------Primary & Secondary--------------- Nominal Z PU (100 MVA Base)


Name Service Bus Conn. Volts FLA kVA R pu jX pu

XF2-TX-1 In PRI-XF2-TX-1 D 480 120 100.0 Pos: 5.1890 17.2360


WG 208 278 Zero: 5.1890 17.2360

SEC-XF2-TX-1

6
Xformer In/Out ------------------Primary & Secondary--------------- Nominal Z PU (100 MVA Base)
Name Service Bus Conn. Volts FLA kVA R pu jX pu

XF2-TX-2 In PRI-XF2-TX-2 D 480 120 100.0 Pos: 5.1890 17.2360


WG 208 278 Zero: 5.1890 17.2360

SEC-XF2-TX-2

XF2-TX-3 In PRI-XF2-TX-3 D 480 120 100.0 Pos: 5.1890 17.2360


WG 208 278 Zero: 5.1890 17.2360

SEC-XF2-TX-3

XF2-TX-4 In PRI-XF2-TX-4 D 480 120 100.0 Pos: 5.1890 17.2360


WG 208 278 Zero: 5.1890 17.2360

SEC-XF2-TX-4

XF2-TX-5 In PRI-XF2-TX-5 D 480 120 100.0 Pos: 5.1890 17.2360


WG 208 278 Zero: 5.1890 17.2360

BUS-0042

XF2-TX-6 In PRI-XF2-TX-6 D 480 120 100.0 Pos: 5.1890 17.2360


WG 208 278 Zero: 5.1890 17.2360

SEC-XF2-TX-6

7
Appendix 2: Load Flow Summary Report

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
Project: 20240124PSS - TIPI
Base Project
Texas Instruments Philippines Inc.
TIPI Office and Stockroom Building

Load Flow Summary Report

Load Flow Study Settings

Include Source Impedance Yes Bus Voltage Drop % 5.00


Solution Method Exact (Iterative) Branch Voltage Drop % 3.00
Load Specification Connected Load

Swing Generators

Source In/Out Service Vpu Angle kW kvar VD% Utility Impedance

PH5-1B-1 In 1.00 0.00 149.0 113.7 0.01 0.00 +j 0.10

PH5-1B-2 In 1.00 0.00 223.9 170.3 0.02 0.00 +j 0.10

Buses

Bus Name In/Out Service Design Volts LF Volts Angle Degree PU Volts %VD

DISC-AHU-1 In 480 468 0.01 0.98 2.45

DISC-AHU-2 In 480 468 0.01 0.98 2.45

DP-1 In 208 201 -0.49 0.97 3.26

1
Bus Name In/Out Service Design Volts LF Volts Angle Degree PU Volts %VD

DP1-UPS In 208 203 -0.41 0.98 2.42

DP-2 In 208 201 -0.56 0.97 3.46

DP2-UPS In 208 202 -0.54 0.97 2.80

DP-3 In 208 200 -0.65 0.96 3.72

DP3-UPS In 208 202 -0.52 0.97 2.84

DP-4 In 480 470 -0.04 0.98 2.05

DP-5 In 480 470 -0.04 0.98 2.05

MDP In 480 471 -0.05 0.98 1.96

MDP-UPS In 480 474 -0.03 0.99 1.31

PNL-P1 In 208 201 -0.46 0.96 3.60

PNL-P-2FA In 208 200 -0.52 0.96 3.95

PNL-P-2FA-UPS In 208 201 -0.50 0.97 3.28

PNL-P-2FB In 208 200 -0.52 0.96 3.95

PNL-P-2FB-UPS In 208 201 -0.50 0.97 3.28

PNL-P-2FC In 208 199 -0.59 0.96 4.46

2
Bus Name In/Out Service Design Volts LF Volts Angle Degree PU Volts %VD

PNL-P-2FC-UPS In 208 201 -0.55 0.97 3.31

PNL-P-IDF In 208 200 -0.64 0.96 3.91

PNL-P-IDF-UPS In 208 202 -0.50 0.97 3.02

PNL-P-LG In 208 200 -0.45 0.96 3.72

PNL-P-LG-UPS In 208 202 -0.37 0.97 2.88

PNL-P-LP In 208 200 -0.59 0.96 4.00

PNL-P-LP-UPS In 208 202 -0.35 0.97 2.69

PNL-P-UG In 208 201 -0.48 0.97 3.35

PNL-P-UG-UPS In 208 203 -0.40 0.97 2.51

Cables

From Bus Component In/Out %VD kW kvar kVA LF Amps PF


To Bus Name Service Loss Loss Loss Rating %

BUS-0001 CBL-MDP-UPS In 1.30 149.0 113.7 187.5 225.5 0.80

MDP-UPS 1.9 1.5 2.4 18.8

3
From Bus Component In/Out %VD kW kvar kVA LF Amps PF
To Bus Name Service Loss Loss Loss Rating %

BUS-0002 CBL-MDP In 1.95 223.9 170.3 281.3 338.4 0.80

MDP 4.3 3.4 5.5 28.2

BUS-0042 CBL-DP2-UPS In 0.24 53.4 40.0 66.7 190.1 0.80

DP2-UPS 0.1 0.1 0.2 27.6

DP-1 CBL-P1 In 0.35 15.8 11.8 19.7 56.5 0.80

PNL-P1 0.1 0.0 0.1 33.2

DP-1 CBL-P-LG In 0.47 25.3 18.9 31.5 90.5 0.80

PNL-P-LG 0.1 0.1 0.2 53.2

DP-1 CBL-P-UG In 0.09 5.1 3.8 6.3 18.2 0.80

PNL-P-UG 0.0 0.0 0.0 10.7

DP1-UPS CBL-P-LG-UPS In 0.46 25.2 18.9 31.5 89.7 0.80

PNL-P-LG-UPS 0.1 0.1 0.2 52.8

DP1-UPS CBL-P-LP-UPS In 0.27 9.5 7.1 11.9 33.9 0.80

PNL-P-LP-UPS 0.0 0.0 0.0 29.5

4
From Bus Component In/Out %VD kW kvar kVA LF Amps PF
To Bus Name Service Loss Loss Loss Rating %

DP1-UPS CBL-P-UG-UPS In 0.09 5.1 3.8 6.3 18.0 0.80

PNL-P-UG-UPS 0.0 0.0 0.0 10.6

DP-2 CBL-P-2FA In 0.49 26.6 20.0 33.3 95.7 0.80

PNL-P-2FA 0.2 0.1 0.2 56.3

DP-2 CBL-P-2FB In 0.49 26.6 20.0 33.3 95.7 0.80

PNL-P-2FB 0.2 0.1 0.2 56.3

DP2-UPS CBL-P-2FA-UPS In 0.49 26.6 20.0 33.3 95.1 0.80

PNL-P-2FA-UPS 0.1 0.1 0.2 55.9

DP2-UPS CBL-P-2FB-UPS In 0.49 26.6 20.0 33.3 95.1 0.80

PNL-P-2FB-UPS 0.1 0.1 0.2 55.9

DP-3 CBL-P-2FC In 0.73 39.5 29.6 49.3 142.2 0.80

PNL-P-2FC 0.3 0.2 0.4 83.7

DP-3 CBL-P-IDF In 0.18 13.5 10.1 16.8 48.5 0.80

PNL-P-IDF 0.0 0.0 0.0 28.5

5
From Bus Component In/Out %VD kW kvar kVA LF Amps PF
To Bus Name Service Loss Loss Loss Rating %

DP-3 CBL-P-LP In 0.28 9.5 7.1 11.9 34.4 0.80

PNL-P-LP 0.0 0.0 0.0 29.9

DP3-UPS CBL-P-2FC-UPS In 0.48 39.3 29.5 49.2 140.6 0.80

PNL-P-2FC-UPS 0.2 0.2 0.2 49.3

DP3-UPS CBL-P-IDF-UPS In 0.18 13.5 10.1 16.8 48.1 0.80

PNL-P-IDF-UPS 0.0 0.0 0.0 28.3

DP-4 CBL-AHU-1 In 0.40 28.1 21.1 35.1 43.2 0.80

DISC-AHU-1 0.1 0.1 0.1 28.8

DP-5 CBL-AHU-2 In 0.40 28.1 21.1 35.1 43.2 0.80

DISC-AHU-2 0.1 0.1 0.1 28.8

MDP CBL-DP-4 In 0.09 28.2 21.1 35.2 43.2 0.80

DP-4 0.0 0.0 0.0 25.4

MDP CBL-DP-5 In 0.09 28.2 21.1 35.2 43.2 0.80

DP-5 0.0 0.0 0.0 25.4

6
From Bus Component In/Out %VD kW kvar kVA LF Amps PF
To Bus Name Service Loss Loss Loss Rating %

MDP CBL-XF2-TX-1 In 0.22 46.4 35.3 58.3 71.6 0.80

PRI-XF2-TX-1 0.1 0.1 0.1 19.9

MDP CBL-XF2-TX-2 In 0.25 53.8 41.0 67.6 83.0 0.80

PRI-XF2-TX-2 0.1 0.1 0.2 23.0

MDP CBL-XF2-TX-3 In 0.30 63.1 48.3 79.5 97.6 0.79

PRI-XF2-TX-3 0.1 0.2 0.3 27.1

MDP-UPS CBL-XF2-TX-4 In 0.19 40.1 30.5 50.4 61.4 0.80

PRI-XF2-TX-4 0.1 0.1 0.1 17.1

MDP-UPS CBL-XF2-TX-5 In 0.25 53.7 41.0 67.6 82.4 0.80

PRI-XF2-TX-5 0.1 0.1 0.2 22.9

MDP-UPS CBL-XF2-TX-6 In 0.25 53.3 40.7 67.1 81.7 0.79

PRI-XF2-TX-6 0.1 0.1 0.2 22.7

SEC-XF2-TX-1 CBL-DP-1 In 0.21 46.2 34.6 57.7 165.2 0.80

DP-1 0.1 0.1 0.1 23.9

7
From Bus Component In/Out %VD kW kvar kVA LF Amps PF
To Bus Name Service Loss Loss Loss Rating %

SEC-XF2-TX-2 CBL-DP-2 In 0.24 53.4 40.0 66.7 191.4 0.80

DP-2 0.1 0.1 0.2 27.7

SEC-XF2-TX-3 CBL-DP-3 In 0.28 62.7 47.0 78.3 225.1 0.80

DP-3 0.1 0.2 0.2 32.6

SEC-XF2-TX-4 CBL-DP1-UPS In 0.18 39.9 29.9 49.9 141.7 0.80

DP1-UPS 0.1 0.1 0.1 20.5

SEC-XF2-TX-6 CBL-DP3-UPS In 0.29 53.0 39.8 66.2 188.6 0.80

DP3-UPS 0.1 0.1 0.2 33.1

2-Winding Transformers

From Bus Component In/Out %VD kW kvar kVA LF Amps PF


Name Service Rating %
To Bus Loss Loss Loss

PRI-XF2-TX-1 XF2-TX-1 In 0.86 46.3 35.2 58.2 72.0 0.80

SEC-XF2-TX-1 0.2 0.6 0.6 59.5

PRI-XF2-TX-2 XF2-TX-2 In 1.00 53.6 40.9 67.4 83.0 0.80

SEC-XF2-TX-2 0.2 0.8 0.9 69.0

8
From Bus Component In/Out %VD kW kvar kVA LF Amps PF
Name Service Rating %
To Bus Loss Loss Loss

PRI-XF2-TX-3 XF2-TX-3 In 1.18 63.0 48.1 79.3 98.0 0.79

SEC-XF2-TX-3 0.3 1.1 1.2 81.1

PRI-XF2-TX-4 XF2-TX-4 In 0.74 40.1 30.4 50.3 61.0 0.80

SEC-XF2-TX-4 0.1 0.4 0.5 51.0

PRI-XF2-TX-5 XF2-TX-5 In 1.00 53.6 40.8 67.4 82.0 0.80

BUS-0042 0.2 0.8 0.8 68.5

PRI-XF2-TX-6 XF2-TX-6 In 0.99 53.2 40.6 66.9 82.0 0.80

SEC-XF2-TX-6 0.2 0.8 0.8 68.0

9
Appendix 3: Short Circuit Report

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
Project: 20240124PSS - TIPI
Base Project
Texas Instruments Philippines Inc.
TIPI Office and Stockroom Building

ANSI Complete Fault Report


A_FAULT Settings

Fault Type 3 Phase+Unbalanced LV Duty Yes Int Duty Yes


Faulted Bus All Buses LV Report Complete Int Report Complete
Include Tap No Mom Duty Yes Solution Method E/Z
Pre-fault Voltage 1.0000 Mom Report Complete NACD Option Interpolated

Low Voltage 3 Phase and Unbalanced

Fault Location Bus Fault Duty X/R -----Asym kA----- Sequence Equivalent
Bus Name Voltage kA MVA Max RMS Avg RMS Impedance pu R +jX

DISC-AHU-1 480 3 Phase: 6.02 5.0 0.69 6.02 6.02 Z1: 19.99 0.04 0.02
SLG: 0.00 0.0 1.00 0.00 --- Z2: 19.99 --- ---
LL: 5.21 2.5 --- --- --- 13,597,840.00
Z0: --- ---
LLG Gnd Return kA: 0.000 LLG: 5.21 2.5 --- --- ---

DISC-AHU-2 480 3 Phase: 6.02 5.0 0.69 6.02 6.02 Z1: 19.99 0.04 0.02
SLG: 0.00 0.0 1.00 0.00 --- Z2: 19.99 --- ---
LL: 5.21 2.5 --- --- --- 13,597,840.00
Z0: --- ---
LLG Gnd Return kA: 0.000 LLG: 5.21 2.5 --- --- ---

DP-1 208 3 Phase: 8.84 3.2 1.90 9.16 9.01 Z1: 31.38 0.01 0.01
SLG: 10.02 2.1 2.03 10.46 --- Z2: 31.38 --- ---
LL: 7.66 1.6 --- --- --- Z0: 20.45 --- ---
LLG Gnd Return kA: 11.538 LLG: 9.29 1.9 --- --- ---

DP1-UPS 208 3 Phase: 8.81 3.2 1.84 9.10 8.96 Z1: 31.49 0.01 0.01
SLG: 9.99 2.1 1.97 10.40 --- Z2: 31.49 --- ---
LL: 7.63 1.6 --- --- --- Z0: 20.45 --- ---
LLG Gnd Return kA: 11.522 LLG: 9.25 1.9 --- --- ---

DP-2 208 3 Phase: 8.84 3.2 1.90 9.16 9.01 Z1: 31.38 0.01 0.01
SLG: 10.02 2.1 2.03 10.46 --- Z2: 31.38 --- ---
LL: 7.66 1.6 --- --- --- Z0: 20.45 --- ---
LLG Gnd Return kA: 11.538 LLG: 9.29 1.9 --- --- ---

1
Low Voltage 3 Phase and Unbalanced

Fault Location Bus Fault Duty X/R -----Asym kA----- Sequence Equivalent
Bus Name Voltage kA MVA Max RMS Avg RMS Impedance pu R +jX

DP2-UPS 208 3 Phase: 8.81 3.2 1.84 9.10 8.96 Z1: 31.49 0.01 0.01
SLG: 9.99 2.1 1.97 10.40 --- Z2: 31.49 --- ---
LL: 7.63 1.6 --- --- --- Z0: 20.45 --- ---
LLG Gnd Return kA: 11.522 LLG: 9.25 1.9 --- --- ---

DP-3 208 3 Phase: 8.85 3.2 1.90 9.16 9.01 Z1: 31.38 0.01 0.01
SLG: 10.02 2.1 2.03 10.46 --- Z2: 31.38 --- ---
LL: 7.66 1.6 --- --- --- Z0: 20.45 --- ---
LLG Gnd Return kA: 11.538 LLG: 9.29 1.9 --- --- ---

DP3-UPS 208 3 Phase: 8.67 3.1 1.75 8.91 8.79 Z1: 32.01 0.01 0.01
SLG: 9.82 2.0 1.85 10.14 --- Z2: 32.01 --- ---
LL: 7.51 1.6 --- --- --- Z0: 20.84 --- ---
LLG Gnd Return kA: 11.315 LLG: 9.16 1.9 --- --- ---

DP-4 480 3 Phase: 13.15 10.9 0.81 13.16 13.16 Z1: 9.15 0.02 0.01
SLG: 0.00 0.0 1.00 0.00 --- Z2: 9.15 --- ---
LL: 11.39 5.5 --- --- --- 13,597,830.00
Z0: --- ---
LLG Gnd Return kA: 0.000 LLG: 11.39 5.5 --- --- ---

DP-5 480 3 Phase: 13.15 10.9 0.81 13.16 13.16 Z1: 9.15 0.02 0.01
SLG: 0.00 0.0 1.00 0.00 --- Z2: 9.15 --- ---
LL: 11.39 5.5 --- --- --- 13,597,830.00
Z0: --- ---
LLG Gnd Return kA: 0.000 LLG: 11.39 5.5 --- --- ---

MDP 480 3 Phase: 17.64 14.7 0.90 17.66 17.65 Z1: 6.82 0.01 0.01
SLG: 0.00 0.0 1.00 0.00 --- Z2: 6.82 --- ---
LL: 15.28 7.3 --- --- --- 13,597,830.00
Z0: --- ---
LLG Gnd Return kA: 0.000 LLG: 15.28 7.3 --- --- ---

MDP-UPS 480 3 Phase: 17.21 14.3 0.83 17.22 17.22 Z1: 6.99 0.01 0.01
SLG: 0.00 0.0 1.00 0.00 --- Z2: 6.99 --- ---
LL: 14.91 7.2 --- --- --- 14,142,140.00
Z0: --- ---
LLG Gnd Return kA: 0.000 LLG: 14.91 7.2 --- --- ---

PNL-P1 208 3 Phase: 5.94 2.1 1.21 5.97 5.96 Z1: 46.74 0.01 0.02
SLG: 6.50 1.4 1.13 6.53 --- Z2: 46.74 --- ---
LL: 5.14 1.1 --- --- --- Z0: 34.70 --- ---
LLG Gnd Return kA: 7.180 LLG: 6.46 1.3 --- --- ---

PNL-P-2FA 208 3 Phase: 6.29 2.3 1.27 6.33 6.31 Z1: 44.16 0.01 0.01
SLG: 6.92 1.4 1.20 6.96 --- Z2: 44.16 --- ---
LL: 5.44 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.688 LLG: 6.83 1.4 --- --- ---

2
Low Voltage 3 Phase and Unbalanced

Fault Location Bus Fault Duty X/R -----Asym kA----- Sequence Equivalent
Bus Name Voltage kA MVA Max RMS Avg RMS Impedance pu R +jX

PNL-P-2FA-UPS 208 3 Phase: 6.27 2.3 1.24 6.31 6.29 Z1: 44.30 0.01 0.01
SLG: 6.90 1.4 1.19 6.94 --- Z2: 44.30 --- ---
LL: 5.43 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.677 LLG: 6.81 1.4 --- --- ---

PNL-P-2FB 208 3 Phase: 6.29 2.3 1.27 6.33 6.31 Z1: 44.16 0.01 0.01
SLG: 6.92 1.4 1.20 6.96 --- Z2: 44.16 --- ---
LL: 5.44 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.688 LLG: 6.83 1.4 --- --- ---

PNL-P-2FB-UPS 208 3 Phase: 6.27 2.3 1.24 6.31 6.29 Z1: 44.30 0.01 0.01
SLG: 6.90 1.4 1.19 6.94 --- Z2: 44.30 --- ---
LL: 5.43 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.677 LLG: 6.81 1.4 --- --- ---

PNL-P-2FC 208 3 Phase: 6.29 2.3 1.27 6.33 6.31 Z1: 44.16 0.01 0.01
SLG: 6.92 1.4 1.20 6.96 --- Z2: 44.16 --- ---
LL: 5.44 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.688 LLG: 6.83 1.4 --- --- ---

PNL-P-2FC-UPS 208 3 Phase: 6.73 2.4 1.51 6.84 6.78 Z1: 41.24 0.01 0.01
SLG: 7.54 1.6 1.49 7.65 --- Z2: 41.24 --- ---
LL: 5.83 1.2 --- --- --- Z0: 28.03 --- ---
LLG Gnd Return kA: 8.560 LLG: 7.29 1.5 --- --- ---

PNL-P-IDF 208 3 Phase: 6.84 2.5 1.37 6.91 6.88 Z1: 40.56 0.01 0.01
SLG: 7.59 1.6 1.33 7.66 --- Z2: 40.56 --- ---
LL: 5.93 1.2 --- --- --- Z0: 28.62 --- ---
LLG Gnd Return kA: 8.518 LLG: 7.41 1.5 --- --- ---

PNL-P-IDF-UPS 208 3 Phase: 6.72 2.4 1.30 6.77 6.75 Z1: 41.30 0.01 0.01
SLG: 7.45 1.5 1.26 7.50 --- Z2: 41.30 --- ---
LL: 5.82 1.2 --- --- --- Z0: 29.25 --- ---
LLG Gnd Return kA: 8.347 LLG: 7.29 1.5 --- --- ---

PNL-P-LG 208 3 Phase: 6.29 2.3 1.27 6.33 6.31 Z1: 44.16 0.01 0.01
SLG: 6.92 1.4 1.20 6.96 --- Z2: 44.16 --- ---
LL: 5.44 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.688 LLG: 6.83 1.4 --- --- ---

PNL-P-LG-UPS 208 3 Phase: 6.27 2.3 1.25 6.31 6.29 Z1: 44.30 0.01 0.01
SLG: 6.90 1.4 1.19 6.94 --- Z2: 44.30 --- ---
LL: 5.43 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.677 LLG: 6.81 1.4 --- --- ---

3
Low Voltage 3 Phase and Unbalanced

Fault Location Bus Fault Duty X/R -----Asym kA----- Sequence Equivalent
Bus Name Voltage kA MVA Max RMS Avg RMS Impedance pu R +jX

PNL-P-LP 208 3 Phase: 5.43 2.0 0.91 5.44 5.43 Z1: 51.10 0.02 0.01
SLG: 5.78 1.2 0.83 5.78 --- Z2: 51.10 --- ---
LL: 4.70 1.0 --- --- --- Z0: 42.21 --- ---
LLG Gnd Return kA: 6.162 LLG: 5.87 1.2 --- --- ---

PNL-P-LP-UPS 208 3 Phase: 5.41 2.0 0.90 5.42 5.42 Z1: 51.27 0.02 0.01
SLG: 5.77 1.2 0.82 5.77 --- Z2: 51.27 --- ---
LL: 4.69 1.0 --- --- --- Z0: 42.21 --- ---
LLG Gnd Return kA: 6.154 LLG: 5.85 1.2 --- --- ---

PNL-P-UG 208 3 Phase: 6.29 2.3 1.27 6.33 6.31 Z1: 44.16 0.01 0.01
SLG: 6.92 1.4 1.20 6.96 --- Z2: 44.16 --- ---
LL: 5.44 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.688 LLG: 6.83 1.4 --- --- ---

PNL-P-UG-UPS 208 3 Phase: 6.27 2.3 1.24 6.31 6.29 Z1: 44.30 0.01 0.01
SLG: 6.90 1.4 1.19 6.94 --- Z2: 44.30 --- ---
LL: 5.43 1.1 --- --- --- Z0: 32.13 --- ---
LLG Gnd Return kA: 7.677 LLG: 6.81 1.4 --- --- ---

4
Momentary 3 Phase

-----Sym Fault Duty----- ---------Mom kA--------- --------Crest kA--------


Fault Location Bus kA MVA X/R Sym*1.6 Based on Sym*2.7 Based on Equivalent
Bus Name Voltage X/R X/R
R +jX

5
Momentary Unbalanced

Fault Location Bus ---Sym Fault Duty--- X/R --Mom. Fault Duty-- Sequence
Bus Name Voltage kA MVA kA*1.6 Based on X/R Impedance pu

6
Interrupting 3 Phase and Unbalanced

Fault Location Bus -----Init Sym Fault----- Equivalent Seq. -------Interrupting Fault kA-----
Bus Name Voltage kA X/R R +jX Imp. pu 2 cyc. 3 cyc. 5 cyc. 8 cyc.

3 Phase: Z1: 3Ph.Sym:


SLG: --- --- Z2: Tot:

NACD: LL: --- --- --- Z0: SLG Sym:


LLG Gnd Return kA: LLG: --- --- --- Tot:

7
Appendix 4: Device Evaluation

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
CB-AHU-1 Passed Compact NSX160, TM100D 480 0.81 13.15
DP-4 100A, 2-4 Poles, IEC 500 50.00
SCHNEIDER ELECTRIC NSX160-H 96.00 26.30

CB-AHU-2 Passed Compact NSX160, TM100D 480 0.81 13.15


DP-5 100A, 2-4 Poles, IEC 500 50.00
SCHNEIDER ELECTRIC NSX160-H 96.00 26.30

CB-DP-4 Passed LA 480 0.90 17.64


MDP 125-400A 480 30.00
SQUARE D LA 100.00 58.80

CB-DP-5 Passed LA 480 0.90 17.64


MDP 125-400A 480 30.00
SQUARE D LA 100.00 58.80

CB-P-2FA Passed Compact NSX160, TM160D 208 2.03 10.02


DP-2 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 25.05

CB-P-2FA-UPS Passed Compact NSX160, TM160D 208 1.97 9.99


DP2-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 24.98

CB-P-2FB Passed Compact NSX160, TM160D 208 2.03 10.02


DP-2 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 25.05

CB-P-2FB-UPS Passed Compact NSX160, TM160D 208 1.97 9.99


DP2-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 24.98

CB-P-2FC Passed LA 208 2.03 10.02


DP-3 125-400A 240 42.00
SQUARE D LA 86.67 23.85
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
CB-P-2FC-UPS Passed LA 208 1.85 9.82
DP3-UPS 125-400A 240 42.00
SQUARE D LA 86.67 23.39

CB-P-IDF Passed Compact NSX160, TM160D 208 2.03 10.02


DP-3 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 25.05

CB-P-IDF-UPS Passed Compact NSX160, TM160D 208 1.85 9.82


DP3-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 24.56

CB-P-LG Passed Compact NSX160, TM160D 208 2.03 10.02


DP-1 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 25.05

CB-P-LG-UPS Passed Compact NSX160, TM160D 208 1.97 9.99


DP1-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 24.98

CB-P-LP Passed Compact NSX160, TM100D 208 2.03 10.02


DP-3 100A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 25.05

CB-P-LP-UPS Passed Compact NSX160, TM100D 208 1.97 9.99


DP1-UPS 100A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 24.98

CB-P-UG Passed Compact NSX160, TM160D 208 2.03 10.02


DP-1 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 25.05

CB-P-UG-UPS Passed Compact NSX160, TM160D 208 1.97 9.99


DP1-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 24.98
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
CB-P1 Passed Compact NSX160, TM160D 208 2.03 10.02
DP-1 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 25.05

CB-XF2-TX-1 Passed LC 480 0.90 17.64


MDP 300-600A 480 65.00
SQUARE D LC 100.00 27.14

CB-XF2-TX-2 Passed LC 480 0.90 17.64


MDP 300-600A 480 65.00
SQUARE D LC 100.00 27.14

CB-XF2-TX-3 Passed LA 480 0.90 17.64


MDP 125-400A 480 30.00
SQUARE D LA 100.00 58.80

CB-XF2-TX-4 Passed LA 480 0.83 17.21


MDP-UPS 125-400A 480 30.00
SQUARE D LA 100.00 57.37

CB-XF2-TX-5 Passed LA 480 0.83 17.21


MDP-UPS 125-400A 480 30.00
SQUARE D LA 100.00 57.37

CB-XF2-TX-6 Passed LA 480 0.83 17.21


MDP-UPS 125-400A 480 30.00
SQUARE D LA 100.00 57.37

MAIN CB-DP-1 Passed LA 208 2.03 10.02


DP-1 125-400A 480 30.00
SQUARE D LA 43.33 33.39

MAIN CB-DP-2 Passed LA 208 2.03 10.02


DP-2 125-400A 480 30.00
SQUARE D LA 43.33 33.39
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
MAIN CB-DP-3 Passed LA 208 2.03 10.02
DP-3 125-400A 480 30.00
SQUARE D LA 43.33 33.40

MAIN CB-DP-4 Passed LA 480 0.81 13.15


DP-4 125-400A 480 30.00
SQUARE D LA 100.00 43.84

MAIN CB-DP-5 Passed LA 480 0.81 13.15


DP-5 125-400A 480 30.00
SQUARE D LA 100.00 43.84

MAIN CB-DP1-UPS Passed LA 208 1.97 9.99


DP1-UPS 125-400A 480 30.00
SQUARE D LA 43.33 33.31

MAIN CB-DP2-UPS Passed LA 208 1.97 9.99


DP2-UPS 125-400A 480 30.00
SQUARE D LA 43.33 33.31

MAIN CB-DP3-UPS Passed LA 208 1.85 9.82


DP3-UPS 125-400A 480 30.00
SQUARE D LA 43.33 32.74

MAIN CB-MDP Passed (*N3) Masterpact NT LF, 5.0 & 5.0A 480 0.90 17.64
MDP LSI, 100-1200A, UL 480 100.00
SQUARE D NT LF 100.00 17.64

MAIN CB-MDP-UPS Passed (*N3) Masterpact NT LF, 5.0 & 5.0A 480 0.83 17.21
MDP-UPS LSI, 100-1200A, UL 480 100.00
SQUARE D NT LF 100.00 17.21

MAIN CB-P-2FA Passed Compact NSX160, TM160D 208 1.20 6.92


PNL-P-2FA 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.30
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
MAIN CB-P-2FA-UPS Passed Compact NSX160, TM160D 208 1.19 6.90
PNL-P-2FA-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.26

MAIN CB-P-2FB Passed Compact NSX160, TM160D 208 1.20 6.92


PNL-P-2FB 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.30

MAIN CB-P-2FB-UPS Passed Compact NSX160, TM160D 208 1.19 6.90


PNL-P-2FB-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.26

MAIN CB-P-2FC Passed LA 208 1.20 6.92


PNL-P-2FC 125-400A 240 42.00
SQUARE D LA 86.67 16.47

MAIN CB-P-2FC-UPS Passed LA 208 1.49 7.54


PNL-P-2FC-UPS 125-400A 240 42.00
SQUARE D LA 86.67 17.94

MAIN CB-P-IDF Passed Compact NSX160, TM160D 208 1.33 7.59


PNL-P-IDF 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 18.98

MAIN CB-P-IDF-UPS Passed Compact NSX160, TM160D 208 1.26 7.45


PNL-P-IDF-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 18.62

MAIN CB-P-LG Passed Compact NSX160, TM160D 208 1.20 6.92


PNL-P-LG 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.30

MAIN CB-P-LG-UPS Passed Compact NSX160, TM160D 208 1.19 6.90


PNL-P-LG-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.26
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
MAIN CB-P-LP Passed Compact NSX160, TM100D 208 0.83 5.87
PNL-P-LP 100A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 14.67

MAIN CB-P-LP-UPS Passed Compact NSX160, TM100D 208 0.82 5.85


PNL-P-LP-UPS 100A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 14.62

MAIN CB-P-UG Passed Compact NSX160, TM160D 208 1.20 6.92


PNL-P-UG 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.30

MAIN CB-P-UG-UPS Passed Compact NSX160, TM160D 208 1.19 6.90


PNL-P-UG-UPS 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 17.26

MAIN CB-P1 Passed Compact NSX160, TM160D 208 1.13 6.50


PNL-P1 160A, 2-4 Poles, IEC 220 40.00
SCHNEIDER ELECTRIC NSX160-B 94.55 16.26

SW-AHU-1 Unknown (No Lib) 480 0.69 *6.02


BUS-0025

SW-AHU-2 Unknown (No Lib) 480 0.69 *6.02


BUS-0026

TYP CB-P-2FA Passed C60BP, Curve B 120 1.20 6.92


PNL-P-2FA 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.19

TYP CB-P-2FA-UPS Passed C60BP, Curve B 120 1.19 6.90


PNL-P-2FA-UPS 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.02
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
TYP CB-P-2FB Passed C60BP, Curve B 120 1.20 6.92
PNL-P-2FB 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.19

TYP CB-P-2FB-UPS Passed C60BP, Curve B 120 1.19 6.90


PNL-P-2FB-UPS 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.02

TYP CB-P-2FC Passed C60BP, Curve B 120 1.20 6.92


PNL-P-2FC 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.19

TYP CB-P-2FC-UPS Passed C60BP, Curve B 120 1.49 7.54


PNL-P-2FC-UPS 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 75.36

TYP CB-P-IDF Passed C60BP, Curve B 120 1.33 7.59


PNL-P-IDF 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 75.90

TYP CB-P-IDF-UPS Passed C60BP, Curve B 120 1.26 7.45


PNL-P-IDF-UPS 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 74.47

TYP CB-P-LG Passed C60BP, Curve B 120 1.20 6.92


PNL-P-LG 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.19

TYP CB-P-LG-UPS Passed C60BP, Curve B 120 1.19 6.90


PNL-P-LG-UPS 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.03

TYP CB-P-LP Passed C60BP, Curve B 120 0.83 5.87


PNL-P-LP 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 58.69
Date: 2/29/2024

Device Evaluation

Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Device/Bus Status Description Voltage (V) X/R INT kA C-L kA Remarks


Manufacturer Bus/Device/ Rating% Calc/Dev/Series Rating% Calc/Dev/ Rating%
TYP CB-P-LP-UPS Passed C60BP, Curve B 120 0.82 5.85
PNL-P-LP-UPS 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 58.49

TYP CB-P-UG Passed C60BP, Curve B 120 1.20 6.92


PNL-P-UG 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.19

TYP CB-P-UG-UPS Passed C60BP, Curve B 120 1.19 6.90


PNL-P-UG-UPS 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 69.02

TYP CB-P1 Passed C60BP, Curve B 120 1.13 6.50


PNL-P1 0.5-63A, IEC, 1-Pole 240 10.00
SCHNEIDER ELECTRIC C60BP 50.00 65.05

(*N3) Calc Arc Flash Line/Load Side Evaluation result is Dangerous!


(*Device Voltage) Device did not pass. Device is either Marginal (100%) or Failed (100%) of device voltage rating.
(*Calc INT kA) Device did not pass. Device is either Marginal (95%) or Failed (100%) of device library interrupting rating.
Appendix 5: Protective Device Settings

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP-1 CB-P-LG 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP-1 CB-P-UG 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP-1 MAIN CB-DP-1 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 350.0A INST 2 (2243.5A)
350.0A

DP1-UPS CB-P-LG-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP1-UPS CB-P-LP-UPS 100A, 2-4 Poles, IEC NSX160-B 100.0A Thermal (0.7-1 x In) 1 (100A)
Thermal Magnetic 100.0A INST (Fixed) Fixed (800A)
100.0A Reflex (Fixed) Fixed (2000A)

DP1-UPS CB-P-UG-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP1-UPS MAIN CB-DP1-UPS 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 350.0A INST 2 (2243.5A)
350.0A

Recommended Circuit Breaker Settings - Page 1


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
DP-2 CB-P-2FA 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP-2 CB-P-2FB 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP-2 MAIN CB-DP-2 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 350.0A INST 2 (2243.5A)
350.0A

DP2-UPS CB-P-2FA-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP2-UPS CB-P-2FB-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP2-UPS MAIN CB-DP2-UPS 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 350.0A INST 2 (2243.5A)
350.0A

DP-3 CB-P-2FC 125-400A LA 225.0A Thermal Curve


Thermal Magnetic 175.0A INST LO (875A)
175.0A

Recommended Circuit Breaker Settings - Page 2


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
DP-3 CB-P-IDF 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP-3 CB-P-LP 100A, 2-4 Poles, IEC NSX160-B 100.0A Thermal (0.7-1 x In) 1 (100A)
Thermal Magnetic 100.0A INST (Fixed) Fixed (800A)
100.0A Reflex (Fixed) Fixed (2000A)

DP-3 MAIN CB-DP-3 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 350.0A INST 2 (2243.5A)
350.0A

DP3-UPS CB-P-2FC-UPS 125-400A LA 225.0A Thermal Curve


Thermal Magnetic 175.0A INST LO (875A)
175.0A

DP3-UPS CB-P-IDF-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

DP3-UPS MAIN CB-DP3-UPS 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 350.0A INST 2 (2243.5A)
350.0A

DP-4 CB-AHU-1 100A, 2-4 Poles, IEC NSX160-H 100.0A Thermal (0.7-1 x In) 1 (100A)
Thermal Magnetic 100.0A INST (Fixed) Fixed (800A)
100.0A Reflex (Fixed) Fixed (2000A)

Recommended Circuit Breaker Settings - Page 3


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
DP-4 MAIN CB-DP-4 125-400A LA 150.0A Thermal Curve
Thermal Magnetic 150.0A INST HI (1500A)
150.0A

DP-5 CB-AHU-2 100A, 2-4 Poles, IEC NSX160-H 100.0A Thermal (0.7-1 x In) 1 (100A)
Thermal Magnetic 100.0A INST (Fixed) Fixed (800A)
100.0A Reflex (Fixed) Fixed (2000A)

DP-5 MAIN CB-DP-5 125-400A LA 150.0A Thermal Curve


Thermal Magnetic 150.0A INST LO (750A)
150.0A

MDP CB-DP-4 125-400A LA 150.0A Thermal Curve


Thermal Magnetic 150.0A INST HI (1500A)
150.0A

MDP CB-DP-5 125-400A LA 150.0A Thermal Curve


Thermal Magnetic 150.0A INST LO (750A)
150.0A

MDP CB-XF2-TX-1 300-600A LC 300.0A Thermal Curve


Thermal Magnetic 300.0A INST 2 (1683A)
300.0A

MDP CB-XF2-TX-2 300-600A LC 300.0A Thermal Curve


Thermal Magnetic 300.0A INST 2 (1683A)
300.0A

Recommended Circuit Breaker Settings - Page 4


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
MDP CB-XF2-TX-3 300-600A LC 300.0A Thermal Curve
Thermal Magnetic 300.0A INST 2 (1683A)
300.0A

MDP MAIN CB-MDP LSI, 100-1200A, UL NT LF 1200.0A LTPU/LTD (A 0.4-1.0 x S) 1 (800A); 4


Static Trip 800.0A STPU (1.5-10 x LTPU) 3 (2400A)
800.0A STD (INST-0.4) 0.1 (I^s T Off)
INST (2-15 x S) 6 (4800A)

MDP-UPS CB-XF2-TX-4 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 300.0A INST LO (1500A)
300.0A

MDP-UPS CB-XF2-TX-5 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 300.0A INST LO (1500A)
300.0A

MDP-UPS CB-XF2-TX-6 125-400A LA 400.0A Thermal Curve


Thermal Magnetic 300.0A INST LO (1500A)
300.0A

MDP-UPS MAIN CB-MDP-UPS LSI, 100-1200A, UL NT LF 1200.0A LTPU/LTD (A 0.4-1.0 x S) 1 (800A); 8


Static Trip 800.0A STPU (1.5-10 x LTPU) 3 (2400A)
800.0A STD (INST-0.4) 0.1 (I^s T Off)
INST (2-15 x S) 4 (3200A)

PNL-P1 MAIN CB-P1 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

Recommended Circuit Breaker Settings - Page 5


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
PNL-P1 TYP CB-P1 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-2FA MAIN CB-P-2FA 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-2FA TYP CB-P-2FA 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-2FA-UPS MAIN CB-P-2FA-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-2FA-UPS TYP CB-P-2FA-UPS 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-2FB MAIN CB-P-2FB 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-2FB TYP CB-P-2FB 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

Recommended Circuit Breaker Settings - Page 6


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
PNL-P-2FB-UPS MAIN CB-P-2FB-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-2FB-UPS TYP CB-P-2FB-UPS 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-2FC MAIN CB-P-2FC 125-400A LA 225.0A Thermal Curve


Thermal Magnetic 175.0A INST LO (875A)
175.0A

PNL-P-2FC TYP CB-P-2FC 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-2FC-UPS MAIN CB-P-2FC-UPS 125-400A LA 225.0A Thermal Curve


Thermal Magnetic 175.0A INST LO (875A)
175.0A

PNL-P-2FC-UPS TYP CB-P-2FC-UPS 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-IDF MAIN CB-P-IDF 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

Recommended Circuit Breaker Settings - Page 7


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
PNL-P-IDF TYP CB-P-IDF 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 30.0A INST Fixed (120A)
30.0A

PNL-P-IDF-UPS MAIN CB-P-IDF-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-IDF-UPS TYP CB-P-IDF-UPS 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 30.0A INST Fixed (120A)
30.0A

PNL-P-LG MAIN CB-P-LG 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-LG TYP CB-P-LG 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-LG-UPS MAIN CB-P-LG-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-LG-UPS TYP CB-P-LG-UPS 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

Recommended Circuit Breaker Settings - Page 8


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
PNL-P-LP MAIN CB-P-LP 100A, 2-4 Poles, IEC NSX160-B 100.0A Thermal (0.7-1 x In) 1 (100A)
Thermal Magnetic 100.0A INST (Fixed) Fixed (800A)
100.0A Reflex (Fixed) Fixed (2000A)

PNL-P-LP TYP CB-P-LP 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-LP-UPS MAIN CB-P-LP-UPS 100A, 2-4 Poles, IEC NSX160-B 100.0A Thermal (0.7-1 x In) 1 (100A)
Thermal Magnetic 100.0A INST (Fixed) Fixed (800A)
100.0A Reflex (Fixed) Fixed (2000A)

PNL-P-LP-UPS TYP CB-P-LP-UPS 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-UG MAIN CB-P-UG 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

PNL-P-UG TYP CB-P-UG 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

PNL-P-UG-UPS MAIN CB-P-UG-UPS 160A, 2-4 Poles, IEC NSX160-B 160.0A Thermal(0.7-1 x In) 1 (160A)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
160.0A Reflex (Fixed) Fixed (2000A)

Recommended Circuit Breaker Settings - Page 9


Device Settings
Circuit Breakers

Device Manufacturer / Frame (A)


Device Name in Model / Description / Frame/ Trip (A) Recommended Settings
Device Location Trip Type Ampacity Range Model Plug (A) Type (Range) Setting (Value)
Thermal Magnetic 160.0A INST (Fixed) Fixed (1280A)
PNL-P-UG-UPS TYP CB-P-UG-UPS 0.5-63A, IEC, 1-Pole C60BP 63.0A Thermal (Fixed)
Thermal Magnetic 20.0A INST Fixed (80A)
20.0A

Recommended Circuit Breaker Settings - Page 10


Appendix 6: TCC

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
CURRENT IN AMPERES

100

10K
1K
0.5 1 10 MAIN CB-MDP-UPS
1000 SQUARE D
CBL-XF2-TX-3 Masterpact NT LF, 5.0 & 5.0A
CBL-XF2-TX-4 800A
CBL-DP1-UPS
XF2-TX-4 800APlug
Settings
LTPU/LTD (A0.4-1.0 x S) 1 (800A); 8
STPU (1.5-10 x LTPU) 3 (2400A)
STD (INST-0.4) 0.1 (I^s T Off)
INST (2-15 x S) 4 (3200A)

100 MDP-UPS
480V
XF2-TX-4
CB-XF2-TX-4
SQUARE D
LA
300A
300APlug
Settings
Thermal Curve
INST LO (1500A)
10
MAIN CB-MDP-UPS
CBL-XF2-TX-4
CBL-XF2-TX-3 1-200/ph Copper
148ft

TIME IN SECONDS
360A
CB-XF2-TX-4 CBL-DP1-UPS P
XF2-TX-4
S 480V/208V
CBL-XF2-TX-4 100kVA
1.80%Z
MAIN CB-DP1-UPS 1
CBL-DP1-UPS
2-175/ph Copper
49ft
690A
CB-P-LG-UPS

MAIN CB-DP1-UPS
SQUARE D
TX Inrush LA
0.10 350A
350APlug
Settings
Thermal Curve
INST 2 (2243.5A)

DP1-UPS
208V

CB-P-LG-UPS
0.01 SCHNEIDER ELECTRIC
Compact NSX160, TM160D
160A
160APlug
Settings
Thermal(0.7-1 x In) 1 (160A)
INST (Fixed) Fixed (1280A)
Reflex (Fixed) Fixed (2000A)
Actual Current = Displayed Current x 10 at 480 V

RECOMMENDED 01_MDP & DP UPS February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
CURRENT IN AMPERES

100

10K
1K
0.5 1 10
1000
CBL-P-LG-UPS

CB-P-LG-UPS
SCHNEIDER ELECTRIC
Compact NSX160, TM160D
100 160A
160APlug
Settings
Thermal(0.7-1 x In) 1 (160A)
INST (Fixed) Fixed (1280A)
CB-P-LG-UPS Reflex (Fixed) Fixed (2000A)

CBL-P-LG-UPS
1-60/ph Copper
10 55ft
170A

CBL-P-LG-UPS

TIME IN SECONDS
MAIN CB-P-LG-UPS
SCHNEIDER ELECTRIC
Compact NSX160, TM160D
MAIN CB-P-LG-UPS 160A
160APlug
Settings
1 Thermal(0.7-1 x In) 1 (160A)
INST (Fixed) Fixed (1280A)
TYP CB-P-LG-UPS Reflex (Fixed) Fixed (2000A)

PNL-P-LG-UPS
208V

L-P-LG-UPS
87Amps
0.10 31 kVA

TYP CB-P-LG-UPS
SCHNEIDER ELECTRIC
C60BP, Curve B
20A
20APlug
Settings
Thermal (Fixed)
INST Fixed (80A)
0.01

Actual Current = Displayed Current x 10 at 208 V

RECOMMENDED 02_TYPICAL 150A CIRCUIT February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
CURRENT IN AMPERES

100

10K
1K
0.5 1 10
1000
CBL-P-LP-UPS

CB-P-LP-UPS
SCHNEIDER ELECTRIC
Compact NSX160, TM100D
100 100A
100APlug
Settings
Thermal (0.7-1 x In) 1 (100A)
INST (Fixed) Fixed (800A)
Reflex (Fixed) Fixed (2000A)

CBL-P-LP-UPS
1-30/ph Copper
10 50ft
115A

CBL-P-LP-UPS

TIME IN SECONDS
MAIN CB-P-LP-UPS
CB-P-LP-UPS SCHNEIDER ELECTRIC
Compact NSX160, TM100D
100A
100APlug
Settings
1 Thermal (0.7-1 x In) 1 (100A)
MAIN CB-P-LP-UPS
INST (Fixed) Fixed (800A)
Reflex (Fixed) Fixed (2000A)
PNL-P-LP-UPS
208V
TYP CB-P-LP-UPS
L-P-LP-UPS
33Amps
12 kVA
0.10
TYP CB-P-LP-UPS
SCHNEIDER ELECTRIC
C60BP, Curve B
20A
20APlug
Settings
Thermal (Fixed)
INST Fixed (80A)
0.01

Actual Current = Displayed Current x 10 at 208 V

RECOMMENDED 03_TYPICAL 100A CIRCUIT February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
CURRENT IN AMPERES

100

10K
1K
0.5 1 10
1000
CBL-AHU-1

MTRI-AHU-1 100

CB-AHU-1
SCHNEIDER ELECTRIC
Compact NSX160, TM100D
100A
CB-AHU-1 100APlug
Settings
Thermal (0.7-1 x In) 1 (100A)
INST (Fixed) Fixed (800A)
10 Reflex (Fixed) Fixed (2000A)
CBL-AHU-1

CBL-AHU-1
1-50/ph Copper

TIME IN SECONDS
200ft
150A

DISC-AHU-1
480V
1
VFD-AHU-1

SW-AHU-1
Settings

0.10

MTRI-AHU-1
35 kVA

0.01

Actual Current = Displayed Current x 1 at 480 V

RECOMMENDED 04_AHU-1/2 February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
CURRENT IN AMPERES

100

10K
1K
0.5 1 10
1000

100

MAIN CB-MDP
SQUARE D
Masterpact NT LF, 5.0 & 5.0A
MAIN CB-MDP 800A
800APlug
Settings
LTPU/LTD (A0.4-1.0 x S) 1 (800A); 4
STPU (1.5-10 x LTPU) 3 (2400A)
10 STD (INST-0.4) 0.1 (I^s T Off)
INST (2-15 x S) 6 (4800A)
CB-XF2-TX-1

MDP

TIME IN SECONDS
CB-DP-4
480V

CB-DP-4
SQUARE D
LA
1 150A
150APlug
Settings
Thermal Curve
INST HI (1500A)

CB-XF2-TX-1
SQUARE D
LC
0.10 300A
300APlug
Settings
Thermal Curve
INST 2 (1683A)

0.01

Actual Current = Displayed Current x 10 at 480 V

RECOMMENDED 05_MDP February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
CURRENT IN AMPERES

100

10K
1K
0.5 1 10
1000
CBL-XF2-TX-1
CBL-DP-1
XF2-TX-1 CB-XF2-TX-1
SQUARE D
LC
300A
300APlug
Settings
Thermal Curve
INST 2 (1683A)
100
CBL-XF2-TX-1
1-200/ph Copper
XF2-TX-1 148ft
360A

P
XF2-TX-1
CB-XF2-TX-1
S 480V/208V
10 100kVA
1.80%Z
MAIN CB-DP-1
CBL-XF2-TX-1

TIME IN SECONDS
CBL-DP-1
2-175/ph Copper
CB-P1 CBL-DP-1 49ft
690A
1

MAIN CB-DP-1
SQUARE D
LA
350A
350APlug
Settings
Thermal Curve
INST 2 (2243.5A)
TX Inrush
0.10

DP-1
208V
CB-P1
SCHNEIDER ELECTRIC
Compact NSX160, TM160D
160A
0.01 160APlug
Settings
Thermal(0.7-1 x In) 1 (160A)
INST (Fixed) Fixed (1280A)
Reflex (Fixed) Fixed (2000A)

Actual Current = Displayed Current x 10 at 480 V

RECOMMENDED 06_DP1,2,3 UPS&UNREG February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
CURRENT IN AMPERES

100

10K
1K
0.5 1 10
1000
CBL-DP-4

100 CB-DP-4
SQUARE D
LA
150A
150APlug
Settings
Thermal Curve
INST HI (1500A)

10 CBL-DP-4
MAIN CB-DP-4 1-60/ph Copper
49ft
170A

TIME IN SECONDS
CBL-DP-4

CB-DP-4 MAIN CB-DP-4


SQUARE D
LA
150A
CB-AHU-1 1 150APlug
Settings
Thermal Curve
INST HI (1500A)

DP-4
480V

CB-AHU-1
SCHNEIDER ELECTRIC
0.10 Compact NSX160, TM100D
100A
100APlug
Settings
Thermal (0.7-1 x In) 1 (100A)
INST (Fixed) Fixed (800A)
Reflex (Fixed) Fixed (2000A)

0.01

Actual Current = Displayed Current x 10 at 480 V

RECOMMENDED 07_DP3 February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
Appendix 7: Arc Flash Calculation

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
Arc Flash Summary
Hazard Level Count Percentage PPE

0 - 1.2 cal/cm² 19 70% Long sleeve shirt & pants or coverall (nonmelting or untreated natural fiber), safety glasses/goggles, leather gloves, hearing protection

Arc-rated (AR) long sleeve shirt & AR pants or AR coverall or AR flash suit, AR face shield & AR balaclava or AR flash suit hood, hard hat, safety glasses/goggles,
1.2 - 12 cal/cm² 0 0%
hearing protection, leather gloves, leather footwear
Arc-rated (AR) long sleeve shirt & AR pants or AR coverall and/or AR flash suit, AR flash suit hood, AR gloves, hard hat, safety glasses/goggles, hearing protection,
>12 cal/cm² 8 30%
leather footwear

Inadequate 0 0% Overdutied equipment from the short-circuit evaluation

Total: 27 100%
Date: 2/29/2024

Arc Flash Table


(Based on Recommended settings)
Project Name TIPI Design and Build for Office and Stockroom Building
Client Susalum Corporation

Incident
Protective Bus Bolted Prot Dev Prot Dev Trip/Delay Box Box Box Arc Flash Working Limited Restricted Energy
Device Voltage Fault Bolted Fault Arcing Fault Time Equip Electrode Width Height Depth Gap Glove Boundary Distance Approach Approach (cal/cm 2 PPE
Bus Name Name (V) (kA) (kA) (kA) (sec) Type Config (in) (in) (in) (mm) Class (in) (in) (in) (in) Scenario ) Level
DISC-AHU-1 CB-AHU-1 480 5.800 5.800 4.180 0.012 PNL HCB 12 14 10 25 00 8 18 42 12 Normal 0.23 0 - 1.2 cal/cm²
DISC-AHU-2 CB-AHU-2 480 5.800 5.800 4.180 0.012 PNL HCB 12 14 10 25 00 8 18 42 12 Normal 0.23 0 - 1.2 cal/cm²
DP-1 (LineSide) CB-XF2-TX-1 208 8.810 8.810 4.380 2.000 PNL VCBB 12 14 10 25 00 89 18 42 12 Normal 21.35 >12 cal/cm²
DP1-UPS (LineSide) CB-XF2-TX-4 208 8.810 8.810 3.750 2.000 PNL VCBB 12 14 10 25 00 80 18 42 12 Normal 17.73 >12 cal/cm²
DP-2 (LineSide) CB-XF2-TX-2 208 8.810 8.810 4.380 2.000 PNL VCBB 12 14 10 25 00 89 18 42 12 Normal 21.35 >12 cal/cm²
DP2-UPS (LineSide) CB-XF2-TX-5 208 8.810 8.810 3.750 2.000 PNL VCBB 12 14 10 25 00 80 18 42 12 Normal 17.73 >12 cal/cm²
DP-3 (LineSide) CB-XF2-TX-3 208 8.810 8.810 4.380 2.000 PNL VCBB 12 14 10 25 00 89 18 42 12 Normal 21.35 >12 cal/cm²
DP3-UPS (LineSide) CB-XF2-TX-6 208 8.670 8.670 4.310 2.000 PNL VCBB 12 14 10 25 00 88 18 42 12 Normal 20.92 >12 cal/cm²
DP-4 (LineSide) CB-DP-4 480 12.820 12.820 10.400 0.017 PNL VCBB 12 14 10 25 00 11 18 42 12 Normal 0.49 0 - 1.2 cal/cm²
DP-5 (LineSide) CB-DP-5 480 12.820 12.820 10.400 0.017 PNL VCBB 12 14 10 25 00 11 18 42 12 Normal 0.49 0 - 1.2 cal/cm²
MDP (LineSide) MaxTripTime @2.0s 480 17.210 17.210 14.090 2.000 PNL VCBB 12 14 10 25 00 187 18 42 12 Normal 82.49 >12 cal/cm²
MDP-UPS (LineSide) MaxTripTime @2.0s 480 17.210 17.210 14.090 2.000 PNL VCBB 12 14 10 25 00 187 18 42 12 Normal 82.49 >12 cal/cm²
PNL-P1 (LineSide) CB-P1 208 5.920 5.920 2.850 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-2FA (LineSide) CB-P-2FA 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-2FA-UPS (LineSide) CB-P-2FA-UPS 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-2FB (LineSide) CB-P-2FB 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-2FB-UPS (LineSide) CB-P-2FB-UPS 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-2FC (LineSide) CB-P-2FC 208 6.270 6.270 3.030 0.017 PNL VCBB 12 14 10 25 00 5 18 42 12 Normal 0.12 0 - 1.2 cal/cm²
PNL-P-2FC-UPS (LineSide) CB-P-2FC-UPS 208 6.730 6.730 3.270 0.017 PNL VCBB 12 14 10 25 00 5 18 42 12 Normal 0.13 0 - 1.2 cal/cm²
PNL-P-IDF (LineSide) CB-P-IDF 208 6.820 6.820 3.320 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.09 0 - 1.2 cal/cm²
PNL-P-IDF-UPS (LineSide) CB-P-IDF-UPS 208 6.720 6.720 3.270 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.09 0 - 1.2 cal/cm²
PNL-P-LG (LineSide) CB-P-LG 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-LG-UPS (LineSide) CB-P-LG-UPS 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-LP (LineSide) CB-P-LP 208 5.410 5.410 2.590 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.07 0 - 1.2 cal/cm²
PNL-P-LP-UPS (LineSide) CB-P-LP-UPS 208 5.410 5.410 2.590 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.07 0 - 1.2 cal/cm²
PNL-P-UG (LineSide) CB-P-UG 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
PNL-P-UG-UPS (LineSide) CB-P-UG-UPS 208 6.270 6.270 3.030 0.012 PNL VCBB 12 14 10 25 00 4 18 42 12 Normal 0.08 0 - 1.2 cal/cm²
Appendix 8: Single Line Diagram

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
PH5-1B-2
3PH 1000 MVA, X/R=45.00
X/R=8.00

CBL-MDP
5-100/ph Copper
984ft
1200A

MAIN CB-MDP
SQUARE D
Masterpact NT LF, 5.0 & 5.0A
800A
800A Plug

MDP
480V

CB-XF2-TX-1 CB-XF2-TX-2 CB-XF2-TX-3 CB-DP-4 CB-DP-5


SQUARE D SQUARE D SQUARE D SQUARE D SQUARE D
LC LC LC LA LA
300A 300A 300A 150A 150A
300A Plug 300A Plug 300A Plug 150A Plug 150A Plug

CBL-XF2-TX-1 CBL-XF2-TX-2 CBL-XF2-TX-3


1-200/ph Copper 1-200/ph Copper 1-200/ph Copper
148ft 148ft 148ft
360A 360A 360A

P P P
XF2-TX-1 XF2-TX-2
XF2-TX-3
480V/208V 480V/208V
S S S 480V/208V
100 kVA 100 kVA
100 kVA
1.80%Z 1.80%Z
1.80%Z

CBL-DP-1 CBL-DP-2 CBL-DP-3 CBL-DP-4 CBL-DP-5


2-175/ph Copper 2-175/ph Copper 2-175/ph Copper 1-60/ph Copper 1-60/ph Copper
49ft 49ft 49ft 49ft 49ft
690A 690A 690A 170A 170A

MAIN CB-DP-1 MAIN CB-DP-2 MAIN CB-DP-3 MAIN CB-DP-4 MAIN CB-DP-5
SQUARE D SQUARE D SQUARE D SQUARE D SQUARE D
LA LA LA LA LA
350A 350A 350A 150A 150A
350A Plug 350A Plug 350A Plug 150A Plug 150A Plug

DP-1 DP-2 DP-3 DP-4 DP-5


208V 208V 208V 480V 480V

CB-P1 CB-P-LG CB-P-UG CB-P-2FA CB-P-2FB CB-P-2FC CB-P-IDF CB-P-LP CB-AHU-1 CB-AHU-2
SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SQUARE D SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC
Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM160D LA Compact NSX160, TM160D Compact NSX160, TM100D Compact NSX160, TM100D Compact NSX160, TM100D
160A 160A 160A 160A 160A 175A 160A 100A 100A 100A
160A Plug 160A Plug 160A Plug 160A Plug 160A Plug 175A Plug 160A Plug 100A Plug 100A Plug 100A Plug

CBL-P1 CBL-P-LG CBL-P-UG CBL-P-2FA CBL-P-2FB CBL-P-2FC CBL-P-IDF CBL-P-LP CBL-AHU-1 CBL-AHU-2
1-60/ph Copper 1-60/ph Copper 1-60/ph Copper 1-60/ph Copper 1-60/ph Copper 1-60/ph Copper 1-30/ph Copper 1-50/ph Copper 1-50/ph Copper
1-60/ph Copper
66ft 55ft 55ft 55ft 55ft 40ft 50ft 200ft 200ft
55ft
170A 170A 170A 170A 170A 170A 115A 150A 150A
170A

DISC-AHU-1 DISC-AHU-2
MAIN CB-P1 MAIN CB-P-LG MAIN CB-P-UG MAIN CB-P-2FA MAIN CB-P-2FB MAIN CB-P-2FC MAIN CB-P-IDF MAIN CB-P-LP 480V 480V
SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SQUARE D SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC
Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM160D LA Compact NSX160, TM160D Compact NSX160, TM100D VFD-AHU-1 VFD-AHU-2
160A 160A 160A 160A 160A 175A 160A 100A
160A Plug 160A Plug 160A Plug 160A Plug 160A Plug 175A Plug 160A Plug 100A Plug

PNL-P1 PNL-P-LG PNL-P-UG PNL-P-2FA PNL-P-2FB PNL-P-2FC PNL-P-IDF PNL-P-LP SW-AHU-1 SW-AHU-2
208V 208V 208V 208V 208V 208V 208V 208V

L-P1 L-P-LG L-P-UG L-P-2FA L-P-2FB L-P-2FC L-P-IDF L-P-LP


19.6 kVA 31.4 kVA 6.3 kVA 33.1 kVA 33.1 kVA 49 kVA 16.8 kVA 11.9 kVA

TYP CB-P1 TYP CB-P-LG TYP CB-P-UG TYP CB-P-2FA TYP CB-P-2FB TYP CB-P-2FC TYP CB-P-IDF TYP CB-P-LP MTRI-AHU-1 MTRI-AHU-2
SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC 35 kVA 35 kVA
C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B
20A 20A 20A 20A 20A 20A 30A 20A
20A Plug 20A Plug 20A Plug 20A Plug 20A Plug 20A Plug 30A Plug 20A Plug

Drawing: UNREG February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
PH5-1B-1
3PH 1000 MVA, X/R=45.00
X/R=8.00

CBL-MDP-UPS
5-100/ph Copper
984ft
1200A

MAIN CB-MDP-UPS
SQUARE D
Masterpact NT LF, 5.0 & 5.0A
800A
800A Plug

MDP-UPS
480V

CB-XF2-TX-4 CB-XF2-TX-5 CB-XF2-TX-6


SQUARE D SQUARE D SQUARE D
LA LA LA
300A 300A 300A
300A Plug 300A Plug 300A Plug

CBL-XF2-TX-4 CBL-XF2-TX-5 CBL-XF2-TX-6


1-200/ph Copper 1-200/ph Copper 1-200/ph Copper
148ft 148ft 148ft
360A 360A 360A

P P P
XF2-TX-4 XF2-TX-5 XF2-TX-6
S 480V/208V S 480V/208V S 480V/208V
100 kVA 100 kVA 100 kVA
1.80%Z 1.80%Z 1.80%Z

CBL-DP1-UPS CBL-DP2-UPS CBL-DP3-UPS


2-175/ph Copper 2-175/ph Copper 2-125/ph Copper
49ft 49ft 49ft
690A 690A 570A

MAIN CB-DP1-UPS MAIN CB-DP2-UPS MAIN CB-DP3-UPS


SQUARE D SQUARE D SQUARE D
LA LA LA
350A 350A 350A
350A Plug 350A Plug 350A Plug

DP1-UPS DP2-UPS DP3-UPS


208V 208V 208V

CB-P-LG-UPS CB-P-UG-UPS CB-P-LP-UPS CB-P-2FA-UPS CB-P-2FB-UPS CB-P-2FC-UPS CB-P-IDF-UPS


SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SQUARE D SCHNEIDER ELECTRIC
Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM100D Compact NSX160, TM160D Compact NSX160, TM160D LA Compact NSX160, TM160D
160A 160A 100A 160A 160A 175A 160A
160A Plug 160A Plug 100A Plug 160A Plug 160A Plug 175A Plug 160A Plug

CBL-P-LG-UPS CBL-P-UG-UPS CBL-P-LP-UPS CBL-P-2FA-UPS CBL-P-2FB-UPS CBL-P-2FC-UPS CBL-P-IDF-UPS


1-60/ph Copper 1-60/ph Copper 1-30/ph Copper 1-60/ph Copper 1-60/ph Copper 1-125/ph Copper 1-60/ph Copper
55ft 55ft 50ft 55ft 55ft 55ft 40ft
170A 170A 115A 170A 170A 285A 170A

MAIN CB-P-LG-UPS MAIN CB-P-UG-UPS MAIN CB-P-LP-UPS MAIN CB-P-2FA-UPS MAIN CB-P-2FB-UPS MAIN CB-P-2FC-UPS MAIN CB-P-IDF-UPS
SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SQUARE D SCHNEIDER ELECTRIC
Compact NSX160, TM160D Compact NSX160, TM160D Compact NSX160, TM100D Compact NSX160, TM160D Compact NSX160, TM160D LA Compact NSX160, TM160D
160A 160A 100A 160A 160A 175A 160A
160A Plug 160A Plug 100A Plug 160A Plug 160A Plug 175A Plug 160A Plug

PNL-P-LG-UPS PNL-P-UG-UPS PNL-P-LP-UPS PNL-P-2FA-UPS PNL-P-2FB-UPS PNL-P-2FC-UPS PNL-P-IDF-UPS


208V 208V 208V 208V 208V 208V 208V

L-P-LG-UPS L-P-UG-UPS L-P-LP-UPS L-P-2FA-UPS L-P-2FB-UPS L-P-2FC-UPS L-P-IDF-UPS


31.4 kVA 6.3 kVA 11.9 kVA 33.1 kVA 33.1 kVA 49 kVA 16.8 kVA

TYP CB-P-LG-UPS TYP CB-P-UG-UPS TYP CB-P-LP-UPS TYP CB-P-2FA-UPS TYP CB-P-2FB-UPS TYP CB-P-2FC-UPS TYP CB-P-IDF-UPS
SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC
C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B C60BP, Curve B
20A 20A 20A 20A 20A 20A 30A
20A Plug 20A Plug 20A Plug 20A Plug 20A Plug 20A Plug 30A Plug

Drawing: UPS February 29, 2024


Project: TIPI Office and Stockroom Building Ref.:
Client: Texas Instruments Philippines Inc.
Appendix 9: Arc Flash Labels

PSS-1603-2402-01 R2 Texas Instruments Philippines Inc. 02/29/2024 Kevin Fajardo, PEE PSSv1.0
WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
8 in Arc Flash Boundary 80 in Arc Flash Boundary
0.23 cal/cm^2 Incident Energy at 18 in 17.7 cal/cm^2 Incident Energy at 18 in
Arc-rated shirt & pants or arc-rated
PPE No Arc-rated PPE Required PPE
coverall or arc-rated arc flash suit
480 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: DISC-AHU-1 Location: DP1-UPS

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
8 in Arc Flash Boundary 89 in Arc Flash Boundary
0.23 cal/cm^2 Incident Energy at 18 in 21.3 cal/cm^2 Incident Energy at 18 in
Arc-rated shirt & pants or arc-rated
PPE No Arc-rated PPE Required PPE
coverall or arc-rated arc flash suit
480 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: DISC-AHU-2 Location: DP-2

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
89 in Arc Flash Boundary 80 in Arc Flash Boundary
21.3 cal/cm^2 Incident Energy at 18 in 17.7 cal/cm^2 Incident Energy at 18 in
Arc-rated shirt & pants or arc-rated Arc-rated shirt & pants or arc-rated
PPE PPE
coverall or arc-rated arc flash suit coverall or arc-rated arc flash suit
208 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: DP-1 Location: DP2-UPS


WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
89 in Arc Flash Boundary 11 in Arc Flash Boundary
21.3 cal/cm^2 Incident Energy at 18 in 0.49 cal/cm^2 Incident Energy at 18 in
Arc-rated shirt & pants or arc-rated
PPE PPE No Arc-rated PPE Required
coverall or arc-rated arc flash suit
208 VAC Shock Risk when cover is removed 480 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: DP-3 Location: DP-5

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
88 in Arc Flash Boundary 187 in Arc Flash Boundary
20.9 cal/cm^2 Incident Energy at 18 in 82.5 cal/cm^2 Incident Energy at 18 in
Arc-rated shirt & pants or arc-rated Arc-rated shirt & pants or arc-rated
PPE PPE
coverall or arc-rated arc flash suit coverall or arc-rated arc flash suit
208 VAC Shock Risk when cover is removed 480 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: DP3-UPS Location: MDP

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
11 in Arc Flash Boundary 187 in Arc Flash Boundary
0.49 cal/cm^2 Incident Energy at 18 in 82.5 cal/cm^2 Incident Energy at 18 in
Arc-rated shirt & pants or arc-rated
PPE No Arc-rated PPE Required PPE
coverall or arc-rated arc flash suit
480 VAC Shock Risk when cover is removed 480 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: DP-4 Location: MDP-UPS


WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
4 in Arc Flash Boundary 4 in Arc Flash Boundary
0.08 cal/cm^2 Incident Energy at 18 in 0.08 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: PNL-P1 Location: PNL-P-2FB

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
4 in Arc Flash Boundary 4 in Arc Flash Boundary
0.08 cal/cm^2 Incident Energy at 18 in 0.08 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: PNL-P-2FA Location: PNL-P-2FB-UPS

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
4 in Arc Flash Boundary 5 in Arc Flash Boundary
0.08 cal/cm^2 Incident Energy at 18 in 0.12 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: PNL-P-2FA-UPS Location: PNL-P-2FC


WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
5 in Arc Flash Boundary 4 in Arc Flash Boundary
0.13 cal/cm^2 Incident Energy at 18 in 0.08 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: PNL-P-2FC-UPS Location: PNL-P-LG

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
4 in Arc Flash Boundary 4 in Arc Flash Boundary
0.09 cal/cm^2 Incident Energy at 18 in 0.08 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: PNL-P-IDF Location: PNL-P-LG-UPS

WARNING WARNING
Arc Flash and Shock Risk Arc Flash and Shock Risk
Appropriate PPE Required Appropriate PPE Required
4 in Arc Flash Boundary 4 in Arc Flash Boundary
0.09 cal/cm^2 Incident Energy at 18 in 0.07 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed 208 VAC Shock Risk when cover is removed
00 Glove Class 00 Glove Class
42 in Limited Approach 42 in Limited Approach
12 in Restricted Approach 12 in Restricted Approach

Location: PNL-P-IDF-UPS Location: PNL-P-LP


WARNING
Arc Flash and Shock Risk
Appropriate PPE Required
4 in Arc Flash Boundary
0.07 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed
00 Glove Class
42 in Limited Approach
12 in Restricted Approach

Location: PNL-P-LP-UPS

WARNING
Arc Flash and Shock Risk
Appropriate PPE Required
4 in Arc Flash Boundary
0.08 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed
00 Glove Class
42 in Limited Approach
12 in Restricted Approach

Location: PNL-P-UG

WARNING
Arc Flash and Shock Risk
Appropriate PPE Required
4 in Arc Flash Boundary
0.08 cal/cm^2 Incident Energy at 18 in
PPE No Arc-rated PPE Required
208 VAC Shock Risk when cover is removed
00 Glove Class
42 in Limited Approach
12 in Restricted Approach

Location: PNL-P-UG-UPS