UG3669 FIELD MAINTENANCE ONLY

ALL VERSIONS LISTED IN FMO ARE SUPERSEDED BY THEIR CURRENT VERSION FOUND INSIDE THE UNDERGROUND
CONSTRUCTION STANDARD MANUAL.

REVISION HISTORY:
XX/XX/2023: MOVED TO FMO

1998 - 2023 San Diego Gas & Electric Company. All rights reserved. Removal of this copyright notice without permission is not permitted under law.

REV CHANGE DR BY DSN APV DATE REV CHANGE DR BY DSN APV DATE
C F
B E
A ORIGINAL ISSUE ARC JA FRC KRG - D
Indicates Latest Revision Completely Revised X New Page Information Removed
SDG&E ELECTRIC UNDERGROUND FIELD MAINTENANCE ONLY STANDARDS
SHEET FMO
1 OF 1 600A SUBSURFACE/SURFACE OPERABLE UG3669
4-WAY SF-6 GAS SWITCH (VISTA)
SCOPE: THIS STANDARD SHOWS A SUBSURFACE/SURFACE OPERABLE 600A (VISTA) SF-6 GAS SWITCH.

67 7/8"

7
3

WAY 4 WAY 3 WAY 2 WAY 1


33"
28 3/4"
6
6

8
35"
8

WAY 1 WAY 2 WAY 3 WAY 4

U ND
C LO
1 1 1 1 1 1 1 1 1 1 1 1
S & C VOLTAGE INDICATOR S & C VOLTAGE INDICATOR S & C VOLTAGE INDICATOR S & C VOLTAGE INDICATOR
PHASING PHASING PHASING PHASING PHASING PHASING PHASING PHASING PHASING PHASING PHASING PHASING
PIN 1 PIN 1 PIN 1 PIN 1 PIN 1 PIN 1 PIN 1 PIN 1 PIN 1 PIN 1 PIN 1 PIN 1

SE

RO
TEST TEST TEST TEST
WINDOW PHASE 1 PHASE 1 PHASE 1 WINDOW PHASE 1 PHASE 1 PHASE 1 WINDOW PHASE 1 PHASE 1 PHASE 1 WINDOW PHASE 1 PHASE 1 PHASE 1
INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR

TEST TEST TEST TEST


BUTTOM BUTTOM BUTTOM BUTTOM

DETAIL 1
PHOTOCELL PHOTOCELL PHOTOCELL PHOTOCELL

G
2 OP E N
6
DETAIL 1
9
N LY
CEO
EXTERNAL GAUGE
10
AN
TEN
AIN
(IF INSTALLED)
FIGURE 1 M
SEE TABLES 3 & 4
FI ELD
TABLE 1 TABLE 2
ELECTRICAL RATINGS SF-6 GAS SWITCH
VOLTAGE 15.5KV 600A STOCK NUMBER DESIGN UNITS
BIL 95KV STEEL S708998 4WY-V
4-WAY
CURRENT, CONTINUOUS 600A STAINLESS S704700 4WY-SV
LOADMAKE AND LOADBREAK 600A
MOMENTARY AND FAULT CLOSE (RMS, SYMMETRICAL) 12,500A

1998 - 2023 San Diego Gas & Electric Company. All rights reserved. Removal of this copyright notice without permission is not permitted under law.

REV CHANGE DR BY DSN APV DATE REV CHANGE DR BY DSN APV DATE
C MOVED FROM UG3670 EDM JIK - - 12/28/2021 F
B REFERENCES UPDATE - DG TR MDJ 06/01/2016 E
A DRAWING UPDATE - DG TR MDJ 05/31/2016 D MOVED TO FMO ARC JA FRC KRG -

X Indicates Latest Revision Completely Revised New Page Information Removed


SDG&E ELECTRIC UNDERGROUND FIELD MAINTENANCE ONLY STANDARDS
SHEET FMO
1 OF 2 600A SUBSURFACE/SURFACE OPERABLE UG3669.1
4-WAY SF-6 GAS SWITCH (VISTA)
FIGURE 2
4-WAY ONE LINE DIAGRAM

TABLE 3 TABLE 4
SWITCH PARTS LIST SF-6 GAS SWITCH
ITEM DESCRIPTION WEIGHT
ITEM
(LBS)
1 OPERATING PANEL AND CONNECTION DIAGRAM
MANUAL 1,100
2 SF-6 FILL VALVE
SCADA 1,300
3 GROUND LUG

4 NAME PLATE

5 PRESSURE GAUGE (UNDERWINDOW)

6 PRESSURE RELIEF VALVE

7 600A BUSHING ASSEMBLY

8 MOUNTING ANGLES

9 OPERATING MECHANISMS

10 MOTOR OPERATORS (SCADA ONLY)

INSTALLATION:
A. 4-WAY VISTA SWITCH SHALL BE INSTALLED WITH THE OPERATING MECHANISMS UP FOR THE 3317. BOLT THE SWITCH TO THE
SUPPORTS SUPPLIED WITH THE 3317 HANDHOLE. FOR VAULT INSTALLATION USE 54-INCH STAINLESS STEEL LEGS (S457180). BOLT
SWITCH TO THE WALL USING THE 24-INCH BRACKET SUPPLIED WITH LEG KIT.
BILL OF MATERIALS: NONE
NOTES:
I. PRESSURE GAUGE IS LOCATED UNDER THE LEFT HAND SIDE WINDOW. IT IS TEMPERATURE AND ALTITUDE COMPENSATED.
II. SWITCHES ARE DELIVERED FROM THE SUPPLIERS WITH ALL THE PARTS LISTED IN THE PARTS LIST.
III. OPERATION SELECTOR PREVENTS INADVERTENT OPERATION FROM THE CLOSED POSITION DIRECTLY TO THE GROUND POSITION
AND VICE VERSA.
IV. THE SWITCHES SHALL BE USED WITH POLYETHYLENE CABLES AND 600A ELBOW TEES.
REFERENCE:
a. FOR SWITCH IDENTIFICATION, SEE UG3213, UG3214, UG3215, UG3216, UG3217, AND UG3218. N LY
CEO
b. FOR EQUIPMENT COMBINATION GUIDELINES FOR SWITCHES IN MANHOLES, SEE UG3649.
AN
c. FOR SWITCH INSTALLATION IN A 3317 HANDHOLE, SEE UG3671. T EN
MAIN
d. FOR SWITCH CONNECTIONS, SEE UG4181.
LD
e. FOR SWITCH APPLICATION, SEE DM6111. FIE

1998 - 2023 San Diego Gas & Electric Company. All rights reserved. Removal of this copyright notice without permission is not permitted under law.

REV CHANGE DR BY DSN APV DATE REV CHANGE DR BY DSN APV DATE
C MOVED FROM UG3670 EDM JIK - - 12/28/2021 F
B REFERENCES UPDATE - DG TR MDJ 06/01/2016 E
A DRAWING UPDATE - DG TR MDJ 05/31/2016 D MOVED TO FMO ARC JA FRC KRG -

X Indicates Latest Revision Completely Revised New Page Information Removed


SDG&E ELECTRIC UNDERGROUND FIELD MAINTENANCE ONLY STANDARDS
SHEET FMO
2 OF 2 600A SUBSURFACE/SURFACE OPERABLE UG3669.2
4-WAY SF-6 GAS SWITCH (VISTA)