CES 161-2015 ES-1999 Plumbing Services of Buildings
CES 161-2015 ES-1999 Plumbing Services of Buildings
Ethiopian Standard
First Edition
2015
ICS: 71.100.40
Published by Ethiopian Standards Agency
© ESA
CES 161
Contents Page
INTRODUCTION ...................................................................................................................1
ii
© ESA
CES 161
© ESA
iii
CES 161
iv
© ESA
CES 161
© ESA
v
CES 161
vi © ESA
CES 161
ANNEX A ..........................................................................................................................215
ANNEX B ..........................................................................................................................217
ANNEX C ..........................................................................................................................219
ANNEX D ..........................................................................................................................221
ANNEX E ...........................................................................................................................225
ANNEX F ...........................................................................................................................227
ANNEX G ..........................................................................................................................229
ANNEX H ..........................................................................................................................235
vii
© ESA
CES 161
ANNEX I ............................................................................................................................243
ANNEX J ...........................................................................................................................249
ANNEX K ..........................................................................................................................251
ANNEX L ...........................................................................................................................255
viii © ESA
CES 161
Foreword
This Ethiopian Standard has been prepared under the direction of the Technical Committee for Building Structures and
Elements of Building (TC 42) and published by the Ethiopian Standards Agency (ESA).
In the preparation the Addis Ababa Univerisity reviewed the draft document under the supervision of Ministry of
Construction.
Acknowledgment has been made for the organizations for their concern to contribute to the effort of national
standardization.
© ESA
ix
ETHIOPIAN STANDARD CES 161
1.1 Scope
(1) This Standard lays down requirements for and given recommendations on the design,
installation, testing and maintenance of plumbing fixtures, water supply for domestic and
fire-fighting systems, drainage and venting and disposal systems for water-borne domestic
wastes, and storm-water drainage system within premises.
(2) A list of symbols in common use has been included in this Standard.
1.2 Definition
1.2.1 General
(1) Unless otherwise expressly stated, the following words and terms shall, for the purposes
of this code, have the meanings shown in this section.
(2) Words stated in the present tense include the future; words stated in the masculine
gender include the feminine and neuter; the singular number includes the plural and the
plural the singular.
(3) Where terms are not defined in this code and are defined in other Codes, such terms
shall have the meanings ascribed to them as in those codes.
(4) Where terms are not defined through the methods authorized by this section, such
terms shall have ordinarily accepted meanings such as the context implies.
1.2.2 Terminology
Access Cover: A removable plate, usually secured by bolts or screws, to permit access to
a pipe or pipe fitting for the purposes of inspection, repair or cleaning.
Adapter Fitting: An approved connecting device that suitably and properly joins or adjusts
pipes and fittings which do not otherwise fit together.
Air Admittance Valve: One-way valve designed to allow air to enter the plumbing drainage
system when negative pressures develop in the piping system. The device shall close by
gravity and seal the vent terminal at zero differential pressure (no flow conditions) and
under positive internal pressures. The purpose of an air admittance valve is to provide a
method of allowing air to enter the plumbing drainage system without the use of a vent
extended to open air and to prevent sewer gases from escaping into a building.
Air Break (Drainage System): A piping arrangement in which a drain from a fixture,
appliance or device discharges indirectly into another fixture, receptacle or interceptor at a
point below the flood level rim and above the trap seal.
© ESA 1
CES 161
Access Panel: Removable panel mounted in a frame, normally secured with screws and
mounted in a wall or ceiling, to provide access to concealed appurtenances or items which
may require maintenance.
Air Gap: The unobstructed vertical distance through the free atmosphere between the
lowest opening of a water service pipe of fixed outlet supplying water to a fixture or
receptacle and the highest possible water level of such fixture or receptacle.
Air Valve: A valve that releases air from a pipeline automatically without loss of water, or
introduce air into a line automatically if the internal pressure becomes less than that of the
atmosphere
Alternative Engineered Design: A plumbing system that performs in accordance with the
intent and provides an equivalent level of performance for the protection of public health,
safety and welfare.
Appliance: A receptacle with necessary appurtenances designed for a specific purpose the
use or operation of which results in a discharge into the sanitary drainage system.
Authority Having Jurisdiction: The Authority which has been created by a statute and
which for the purpose of administering the Code/Part may authorize a committee or an
official to act on its behalf, hereinafter called the ‘Authority’.
Back Siphonage: The flowing back of used, contaminated, or polluted water from a
plumbing fixture or vessel into a water supply due to a reduced pressure in such pipe (see
Backflow).
Back Up: A condition where the wastewater may flow back into another fixture or
compartment but not back into the potable water system.
Backflow: The flow of water or other liquids, mixtures or substances into the distributing
pipes of a system of supply of potable water from any source or sources other than its
intended source.
Base Flood Elevation: A reference point, determined in accordance with the building code,
based on the depth or peak elevation of flooding, including wave height, which has a 1
percent (lOO-year flood) or greater chance of occurring in any given year.
Battery of Fixtures: Any group of two or more similar adjacent fixtures which discharge
into a common horizontal waste or soil pipe.
Bedding: The material on which the pipe is laid and which provides support for the pipe.
Bedding can be concrete, granular material or the prepared trench bottom
2 © ESA
CES 161
Branch:
(1) Special form of sewer pipe used for making connections to a sewer or water main. The
various types are called ‘T’, ‘Y’, ‘T–Y’, double Y and V branches, according to their
respective shapes.
Branch Soil Pipe: A pipe connecting one or more soil appliances to the main soil pipe.
Branch Soil Waste Pipe: A pipe connecting one or more soil and/or waste appliances to
the main soil waste pipe (one pipe system).
Branch Ventilating Pipe: A pipe, one end of which is connected to the system adjacent to
the trap of an appliance and the other to a main ventilating pipe or a drain-ventilating pipe. It
is fitted to prevent loss of water seal from a trap owing to partial vacuum, back-pressure, or
surging caused by air movement within the pipe system. It also provides ventilation for the
branch waste pipe.
Branch Waste Pipe: A pipe connecting one or more waste appliances to the main waste
pipe.
Branch Discharge Pipe: A common discharge pipe to which plumbing-fixture traps at any
one floor level are connected.
Branch Drain: A line or pipes installed to discharge into another line or at a point of
access; i.e., a manhole.
Branch Vent: A vent connecting one or more individual vents with a vent stack or stack
vent.
Building Drain: That part of the lowest piping of a drainage system that receives the
discharge from soil, waste and other drainage pipes inside and that extends 30 inches (762
mm) in developed length of pipe beyond the exterior walls of the building and conveys the
drainage to the building sewer.
Building Trap: A device, fitting or assembly of fittings installed in the building drain to
prevent circulation of air between the drainage system of the building and the building
sewer.
Building Drainage: A drainage system consists of appliances, their traps and discharge
pipes, a soil or/and waste stack, graded discharge branch pipes, a building drain and a
building sewer with external drains, manholes and other appurtenances.
© ESA 3
CES 161
Building Sewer: That part of the horizontal piping of a drainage system which extends
from the end of the building drain to a public sewer, a treatment unit or cesspool.
Cesspool: A covered watertight tank used for receiving and storing sewage from premises
which cannot be connected to a public sewer and where ground conditions prevent the use
of on-site treatment works including a septic tank.
Chute: A vertical pipe system passing from floor to floor provided with ventilation and inlet
openings for receiving refuse from successive floors and ending at the ground floor on the
top of the collecting chambers.
Circuit Vent: A vent that connects to a horizontal drainage branch and vents two traps to a
maximum of eight traps or trapped fixtures connected into a battery.
Cleanout: A small access opening in a pipe or pipe fitting arranged to facilitate the clearing
of obstructions and fitted with removable cap or plug.
Cleaning Eye: An access opening in a pipe or pipe fitting arranged to facilitate the cleaning
obstructions and fitted with removable cover.
Combination Fixture: A fixture combining one sink and laundry tray or a two- or three-
compartment sink or laundry tray in one unit.
Combination Waste And Vent System: A specially designed system of waste piping
embodying the horizontal wet venting of one or more sinks or floor drains by means of a
common waste and vent pipe adequately sized to provide free movement of air above the
flow line of the drain.
Communication Pipe: That part of the service pipe, extending from the water main up to
the water meter (see Figure 1.1)
Common Vent: A vent connecting at the junction of two fixture drains or to a fixture branch
and serving as a vent for both fixtures.
Concealed Fouling Surface: Any surface of a plumbing fixture which is not readily visible
and is not scoured or cleansed with each fixture operation.
Conductor: A pipe inside the building that conveys storm water from the roof to a storm or
combined building drain.
Construction Documents: All of the written, graphic and pictorial documents prepared or
assembled for describing the design, location and physical characteristics of the elements
of the project necessary for obtaining a building permit. The construction drawings shall be
drawn to an appropriate scale.
Consumer: Any person who uses or is supplied water or on whose application such water
is supplied by the Authority.
4 © ESA
CES 161
Consumer’s Pipe: The portion of service pipe used for supply of water and which is not the
property of the Authority (see Figure 1-1).
Cover:
(1) A removable plate for permitting access to a pipe, fitting, vessel or appliance.
(2) The vertical distance between the top of the barrel of a buried pipe or other construction
and the surface of the ground
Dead End: A branch leading from a soil, waste or vent pipe; a building drain; or a building
sewer, and terminating at a developed length of 2 feet (610 mm) or more by means of a
plug, cap or other closed fitting.
Depth of Manhole: The vertical distance from the top of the manhole cover to the outgoing
invert of the main drain channel
Depth of Water Seal: The depth of water that would have to be removed from a full trap
before air could pass through the trap.
Developed Length: A total length along the center line of a pipe and fittings including all
bends.
Design Flood Elevation: The elevation of the "design flood," including wave height,
relative to the datum specified on the community's legally designated flood hazard map.
Discharge Pipe: A pipe for carrying sewage (waste water) from any fixture (appliance) or
floor waste fully to a branch (common) discharge pipe, stack or drain.
Distributing Pipe: Means any pipe (other than an overflow pipe or a flush pipe) conveying
water from a storage cistern or from any other pressure source (apart from main’s pressure)
to one or more fixtures or appliance (see Figure 1.1).
Downpipe: A conduit for the conveyance of roof water from an outlet of a gutter, box
receiver or sump to another roof or ground level or storm-water drain.
© ESA 5
CES 161
Drain: A pipe installed or laid within the property boundary, intended to convey sewage,
storm water, sub-soil water, etc under gravity.
Drain Ventilating Pipe: A pipe installed to provide flow of air to or from a drain to prevent
undue concentration of foul air in the drain. The main soil pipe or main waste pipe may
serve as drain ventilating pipe wherever their upper portions, which do not receive
discharges, are extended to the roof level and let open to air.
Drainage Fittings: Type of fitting or fittings utilized in the drainage system. Drainage
fittings are similar to cast-iron fittings, except that instead of having a bell and spigot,
drainage fittings are recessed and tapped to eliminate ridges on the inside of the installed
pipe.
Drainage Fixture Unit (DFU): A measure of the probable discharge into the drainage
system by various types of plumbing fixtures. The drainage fixture-unit value for a particular
fixture depends on its volume rate of drainage discharge, on the time duration of a single
drainage operation and on the average time between successive operations.
Drainage System: Piping within a public or private premise that conveys sewage,
rainwater or other liquid wastes to a point of disposal. A drainage system does not include
the mains of a public sewer system or a private or public sewage treatment or disposal
plant.
(1) Building gravity: A drainage system that drains by gravity into the building sewer.
(2) Sanitary: A drainage system that carries sewage and excludes storm, surface and
ground water.
(3) Storm: A drainage system that carries rainwater, surface water, subsurface water and
similar liquid wastes.
Drop Manhole: A manhole installed in a sewer where the elevation of the incoming sewer
considerably exceeds that of the outgoing sewer; a vertical waterway outside the manhole
is provided to divert the waste from the upper to the lower level so that it does not fall freely
into the manhole except at peak rate of flow.
Drop Pipe: Vertical section of drain jointing the drains at different levels.
Duct: An enclosure designed to accommodate water pipes and fittings and other services if
required and constructed so that access to the interior can be obtained either through its
length or at specified points by removal of a cover or covers.
E-waste: A popular informal name for electronic products nearing the end of their “useful
life” such as computers, televisions, VCRs, stereos, copiers, fax machines, microwaves and
washing machines. Many of these products can be reused, refurbished or recycled.
Electronic discards is one of the fastest growing segments of many countries’ waste
stream. Certain components of these products contain materials that render them
hazardous, depending on their condition and density.
6 © ESA
CES 161
Faucet: A valve end of a water pipe through which water is drawn from or held within the
pipe.
Fire Hose Reel: A length of fire fighting hose which is connected to a valved water supply
and is wound on a reel.
Fire Hydrant: A fitting installed in a water pipeline which provides a valved outlet (above or
below ground) to permit a controlled supply of water.
Fittings: Fittings shall mean coupling, flange, branch, bend, tees, elbows, unions, waste
with plug, P or S trap with vent, stop ferrule, stop tap, bib tap, pillar tap, globe tap, ball
valve, cistern storage tank, baths, water-closets, boiler, geyser, pumping set with motor and
accessories, meter, hydrant, valve and any other article used in connection with water
supply, drainage and sanitation.
Fixture Unit: A quantity in terms of which the load producing effects on the plumbing
system of different kinds of plumbing fixtures is expressed on some arbitrarily chosen scale.
Float Operated Valve: Ball valves or ball taps and equilibrium valves operated by means
of a float taken from the pipeline for fire fighting.
Fixture Branch: A drain serving two or more fixtures that discharges to another drain or to
a stack.
Fixture Drain: The drain from the trap of a fixture to a junction with any other drain pipe.
Fixture Fitting:
(1) Supply fitting: A fitting that controls the volume and/or directional flow of water and is
either attached to or accessible from a fixture, or is used with an open or atmospheric
discharge
(2) Waste fitting: A combination of components that conveys the sanitary waste from the
outlet of a fixture to the connection to the sanitary drainage system.
Flushing Cistern: A cistern provided with a device for discharging the stored water rapidly
into a water close pan or urinal.
French Drain or Rubble Drain: A shallow trench filled with coarse rubble, clinker, or
similar material with or without field drain pipes.
Foul Water: Any water contaminated by soil or any domestic waste water.
Grade (Gradient): The inclination expressed as the percentage of unit rise to horizontal
distance.
Gully (Trapped): An assembly used in a waste water system which provides a water seal
to prevent odours and gases from escaping into a building or into the atmosphere in the
proximity of the assembly.
© ESA 7
CES 161
Hydrant Valve: A valve controlling flow of water from the fire hydrant outlet with provision
for attachment of a fire hose.
Horizontal Branch Drain: A drainage branch pipe extending laterally from a soil or waste
stack or building drain, with or without vertical sections or branches, that receives the
discharge from two or more fixture drains or branches and conducts the discharge to the
soil or waste stack or to the building drain.
Horizontal Pipe: Any pipe or fitting that makes an angle of less than 45 degrees (0.79 rad)
with the horizontal.
Individual Vent: A pipe installed to vent a fixture trap and connects with the vent system
above the fixture served or terminates in the open air.
Inlet Pit: Chamber with an inlet, which may be side entry (herb inlet), granted inlet (gully-
grating) or combination, that permits the entry of storm water to a storm water drain and
allow access to the drain for maintenance purposes (see Figure H-2, ANNEX H, for kerb
and granted inlets).
Intercepting Trap: A trap used to aerially disconnect the building drain from the sewer.
Junction: A plumbing fitting used to connect a branch pipe or channel to a main pipe or
channel.
Leader: An exterior drainage pipe for conveying storm water from roof or gutter drains to an
approved means of disposal.
Local Vent Stack: A vertical pipe to which connections are made from the fixture side of
traps and through which vapor or foul air is removed from the fixture or device utilized on
bedpan washers.
Manhole: Working chamber with cover constructed on a drain or sewer within which a
person may inspect, test or clear and remove obstruction in safety.
Nominal Size (DN): A numerical designation of the size of a pipe, bend or branch fitting,
which is a convenient round number approximately equal to a manufactured dimension.
Offset: The pipe and fittings used to provide continuity between pipes whose axes are
parallel but not collinear.
8 © ESA
CES 161
Paved Area: An area (a road or path, etc) covered with pointed stones, pointed brick,
concrete, asphalt, etc to make a hard and tight surface.
Pipe System: The system to be adopted will depend on the type and planning of the
building in which it is to be installed and will be one of the following:
(1) Single stack system (see Fig.1. 2): The one pipe system in which there is no trap
ventilation.
(2) Single stack — Partially Vented: A via media between the one-pipe system and the
single stack system (see one-pipe system, partially ventilated).
(3) One-pipe system (see Fig.1. 3): The system of plumbing in which the wastes from the
sinks, baths and wash basins, and the soil pipe branches are all collected into one main
pipe, which is connected, directly to the drainage system. Gully traps and waste pipes are
completely dispersed with, but all the traps of the water closets, basins, etc, are completely
ventilated to preserve the water seal.
(4) One-pipe system — Partially vented (also called single stack, partially ventilated): A
system in which there is one soil pipe into which all water closets, baths, sinks, and basins
discharge. In addition, there is a relief vent, which ventilates only the traps of water closets.
(5) Two-pipe system (see Fig.1. 4): The system of plumbing in which soil and waste pipes
are distinct and separate. The soil pipes being connected to the drain direct and waste
pipes through a trapped gully. All traps of all appliances are completely ventilated in this
system.
Puff Ventilation: The ventilation provided for waste traps in two-pipe system, in order to
preserve the water seal.
Plumbing: The practice, materials and fixtures utilized in the installation, maintenance,
extension and alteration of all piping, fixtures, plumbing appliances and plumbing
appurtenances, within or adjacent to any structure, in connection with sanitary drainage or
storm drainage facilities; venting systems; and public or private water supply systems.
© ESA 9
CES 161
Plumbing System: Includes the water supply and distribution pipes; plumbing fixtures and
traps; water-treating or water-using equipment; soil, waste and vent pipes; and sanitary and
storm sewers and building drains; in addition to their respective connections, devices and
appurtenances within a structure or premises.
Potable Water: Water which is satisfactory for drinking, culinary and domestic purposes
and meets the requirements of the Authority
Residual Head: The head available at any particular point in the distribution system
Roding: A system of road which are progressively jointed to clear drainage lines.
Roughing Work: The installation of all parts of the plumbing system which is completed
prior to the installation of fixtures.
Sand Trap: A chamber (may be a space provided within an inlet pit or a separate pit made
for the sole purpose) designed to intercept and retain sand or silt in a storm water drainage
system.
Septic Tank: A water-tight receptacle which receives the discharge of a drainage system or
part thereof, designed and constructed so as to retain solids, digest organic matter through
a period of detention and allow the liquids to be disposed off elsewhere.
Service Pipe: So much of any pipe for supplying water from a main to any premises as is
subject to water pressure from that main (see Figure 1.1).
Sewer: A conduit for the carriage of sewage which is usually vested in the local sewerage
authority.
Siphonage: The siphoning away of water seals in fixture traps due to negative pressure.
10 © ESA
CES 161
Soakaway Pit: A pit dug into permeable ground, filled with broken stone, bricks or large
granular material and usually covered, where liquid may seep away into the ground.
Soffit: The highest point of the internal surface of a pipe at any cross section.
Soil Appliances: A sanitary appliance for the collection and discharge of excretory matter.
Soil Waste: The discharge from water closets, urinals, slop hopper, stable yard or cowshed
gullies and similar appliances.
Sprinkler System: An assembly of pipe work graded in size, erected throughout a building
and which sprinkler heads are installed at prescribed intervals. The pipe work is connected
to a set of installation (e.g. control valves, etc) for the operation of the system.
Stack: Any vertical waste water drainage or vent pipe including offsets extending through
more than one floor level.
Stack Vent: The extension of a soil or" waste stack above the highest horizontal drain
connected to the stack.
Stack Venting: A method of venting a fixture or fixtures through the soil or waste stack
Storage Cistern: Any cistern or water tank other than a flushing cistern in which water is
stored at atmospheric pressure, the water being normally received through a float control
valve set at a predetermined level and incorporating an air gap.
Storm Water Drain: The conduit of a storm water drainage installation normally laid
underground for the collection and conveyance of storm water from a premise to the storm
water system.
Storm Water Pit: A chamber constructed within a storm water drain in order to provide
access for inspecting, testing or the clearance of obstructions.
Supply Pipe: So much of any service pipe as is not a communication pipe (see Figure 1.1)
(2) A drain intended to disperse into the sub-soil from a septic tank.
Surface Water: Natural water from the ground surface, paved areas and roofs.
Systems of Drainage:
© ESA 11
CES 161
(1) Combined system: A system in which foul water (sewage) and surface water are
conveyed by the same sewers and drains.
(2) Separate system: A system in which foul water (sewage) and surface water are
conveyed by the separate sewers and drains.
(3) Partially separate system: A modification of the separate system in which part of the
surface water is conveyed by the foul (sanitary) sewers and drains
Trap: Any fitting designed to retain a water seal for the purpose of preventing the passage
of gases.
Trap Water Seal: The water retained in a trap which acts as a barrier to the passage of air
though the trap.
Tundish: A fitting into which pipe work can discharge with an air gap.
Under Drain: A two pipe subsurface effluent disposal system with the pipes laid at different
elevations, with fine gravel media in between.
Vent Pipe: A pipe installed to provide a flow of air to or from a drainage system or to
provide a circulation of air within such system to protect trap seals from siphonage and
back pressure.
Wall-Hung Water Closet: A wall-mounted water closet installed in such a way that the
fixture does not touch the floor.
Waste: The discharge from any fixture, appliance, area or appurtenance that does not
contain fecal matter.
Water Fittings: Includes pipes (other than mains), taps, cocks, valves, ferrules, meters,
cisterns, baths, water closets, soil pans and other similar apparatus used in connection with
the supply and use of water.
Water Main (Street Main): A pipe laid by the water undertakers for the purpose of giving a
general supply of water as distinct from a supply to individual consumers and includes any
apparatus used in connection with such a pipe.
Water Service: That part of the cold water supply pipe work from the water main up to an
including the putlet valves at fixtures or appliances.
Water Supplier: Any regional or sub regional water supply organization including water
authorities.
Water Supply System: Water supply system of a building or premises consists of the
water service pipe, the water distribution pipes, and the necessary connecting pipes,
fittings, control valves, and all appurtenances in or adjacent to the building or premises
Waste Appliance: A sanitary appliance for the collection and discharge of water after use
for ablutionary, culinary and other domestic purpose.
12 © ESA
CES 161
© ESA 13
CES 161
14 © ESA
CES 161
© ESA 15
CES 161
16 © ESA
CES 161
SECTION 2 ADMINISTRATION
The Ministry of Urban Development and Construction, the Authority which has been
created by a statute and which, for the purpose of administering the Code/Part, may
authorize a committee or an official or an agency to act on its behalf, hereinafter called the
‘Authority’.
Every consumer, requiring a new supply of water or any extension or alteration to the
existing supply shall apply in writing in the prescribed form (see Annex A) to the Authority.
In the case of large housing colonies or where new services are so situated that it will be
necessary for the Authority to lay new mains or extend an existing main, full information
about the proposed housing scheme shall be furnished to the Authority; information shall
also be given regarding their phased requirements of water supply with full justification.
Such information shall include site plans, showing the layout of roads, footpaths, building
and boundaries and indicating there on the finished line and level of the roads or footpaths
and water supply lines and appurtenances.
On completion of the plumbing work for the water supply system, the licensed plumber shall
give a completion certificate in the prescribed form (see Annex B) to the Authority for
getting the water connection from the mains.
No person shall install or carry out any water-borne sanitary installation or drainage
installation or any works in connection with anything existing or new buildings or any other
premises without obtaining the previous sanction of the Authority. The owner shall make an
application in the prescribed form (see Annex C) to the Authority to carry out such a work.
A site plan of the premises on which the building is to be situated or any such work is to be
carried out shall be prepared drawn to a scale not smaller than 1:500. The site plan of the
building premises shall show:
(2) The position of the municipal sewer and the direction of flow in it;
© ESA 17
CES 161
(3) The invert level of the municipal sewer, the road level, and the connection level of the
proposed drain connecting the building in relation to the sewer,
(4) The angle at which the drain from the building joins the sewer; and
(5) The alignment, sizes and gradients of all drains and also of surface drains, if any.
A separate site plan is not necessary if the necessary particulars to be shown in such a site
plan are already shown in the drainage plan.
The application (2.2.2.1) shall be accompanied by a drainage plan drawn to a scale of not
smaller than 1:100 and furnished along with the building plan. The plans shall show the
following:
(1) Every floor of the building in which the pipes or drains are to be used;
(2) The position, forms, level and arrangement of the various parts of such building,
including the roof thereof;
(3) All new drains as proposed with their sizes and gradients;
(4) Invert levels of the proposed drains with corresponding ground levels;
(5) The position of every manhole, gully, soil and waste pipe, ventilating pipe, rain water
pipe, water-closet, urinal, latrine, bath, lavatory, sink, trap or other appliances in the
premises proposed to be connected to any drain and the following colors are recommended
for indicating sewers, wastewater pipes, rainwater pipes and on existing work.
(6) The position of refuse chute, inlet hopper and collection chamber.
In the case of an alteration or addition to an existing building, this clause shall be deemed
to be satisfied if the plans as furnished convey sufficient information for the proposals to be
readily identified with previous sanctioned plans and provided the locations of tanks and
other fittings are consistent with the structural safety of the building.
The plans for the building drainage shall in every case be accompanied by specifications for
the various items of work involved. This information shall be supplied in the prescribed from
given in Annex D.
In respect of open drains, cross-sectional details shall be prepared to a scale not smaller
than 1:50 showing the ground and invert levels and any arrangement already existing or
proposed for the inclusion of any or exclusion of all storm water from the sewers.
18 © ESA
CES 161
At the completion of the plumbing installation work, the licensed plumber shall give a
completion certificate in the prescribed form, which is given in Annex E.
The work which is required to be carried out under the provisions of this Section shall be
executed only by a licensed plumber under the control of the Authority and shall be
responsible to carry out all lawful directions given by the Authority. No individual shall
engage in the business of plumbing unless so licensed under the provisions of this Section.
The Authority shall establish standards and procedure for the qualification, examination and
licensing of plumbers and shall issue licenses to such persons who meet the qualifications
thereof and successfully pass the examination.
All licenses issued by the Authority shall be valid for a period of minimum two years and
shall expire on the date indicated on the license, but may be renewed, upon payment of
fees prescribed by the Authority, for further period of two years each, at a time the expired
license not renewed within prescribed time of the expiry of the license may he renewed
upon payment of the penalty prescribed by the Authority.
The Authority may suspend or revoke any license for non- compliance of the conditions
under which the license has been given, or breach of any regulations of the water supply
undertaking. Before a license may be suspended or revoked, the licensee shall have notice
in writing, enumerating the charges against him, and be entitled to a hearing by a duly
authorized board or officer of the Authority. The licensee shall be given an opportunity to
present testimony, oral or written, and shall have the right to cross- examination. A person
whose license has been revoked shall not be permitted to reapply for a license within two
years from the date of revocation.
2.4.1 Inspection
The officer deputed by the Authority may inspect at any time without notice any work done by
licensed plumber or place of business.
© ESA 19
CES 161
Every licensed plumber shall pay lawful demands made by the Authority for:
(1) Repairs to roads, drains, pipes, mains or any fittings or appliances connected therewith
or any other property whatsoever whether belonging to the Authority or not;
(3) Fees for licenses for the time being in force for carrying out trades.
No licensed plumber shall make any water connection or any addition or alteration in fittings
and appliances to carry out any other work in or with reference to public streets, pipes,
sewers, drains, without obtaining sanction of the Authority.
In execution of any work, the pipes, fittings, appliances and material used shall conform to
relevant Ethiopian Standards or approved by the Authority.
Every licensed plumber shall proceed with any work undertaken by him diligently and in a
proper workman like manner and shall not cause any delay in the execution thereof without
sufficient cause.
Every licensed plumber shall report to the Authority defect noticed by him in any premises
in connection with any water pipes, fittings or other appliances causing waste of water or in
connection with any drains, water closets, privies, urinals or any fittings, appliances
connection therewith rendering such drains privy or urinal insufficient or otherwise
objectionable for sanitary reasons.
20 © ESA
CES 161
3.1 Scope
(1) This section deals with the selection, installation, and maintenance of sanitary fixtures.
3.2 Materials
3.2.1 Quality
(1) Sanitary fixtures shall have smooth impervious surfaces, be free from defects and
concealed fouling surfaces and shall be of approved standards in quality and design (see
Clause 3.2.2).
(1) All sanitary fixtures shall comply with the relevant Ethiopian Standards or equivalent and
shall be acceptable on the approval of the Building Official.
(1) Before deliver, arrangement should be made for storage of fixtures under cover to
prevent damage.
(2) Upon delivery, all fixtures should be checked carefully to ensure that they satisfy
provisions of Section 3.2
(3) Handling and storage of fixtures shall confirm to the manufacturer’s and/or supplier’s
interaction.
(4) All accessories such as traps, taps, brackets, seats, cisterns, etc should be checked
and, if appropriate, grouped together.
(1) (a) Adequate ventilation of all sanitary accommodation including bath rooms and
kitchens should be provided.
(b) Windows or sky light opening direct to the external air should be made wherever
possible.
(2) (a) Care should be taken to prevent the transmission of noise from sanitary fixtures
to areas such as sitting rooms, class rooms and public areas.
(b) Noise can be reduced by proper attention to pipe work, siting and fixing of the
fixture.
© ESA 21
CES 161
(3) Bath and shower compartments shall have walls constructed of smooth, non-corrosive
and non-absorbent waterproof material to a height of non less than 1.8m above the floor.
3.3.2 Fixture
(1) Fixtures should be selected and installed to allow all connections to be correctly made
initially and so as to be easily disconnected for subsequent maintenance or replacement.
(2) Where fixtures will be subjected to heavy use, as in public conveniences, schools,
hospitals, factories, etc, they should be robust in construction and designed to withstand
misuse.
3.3.3 Hygiene
(1) (a) Sanitary fixtures should be designed, assembled and fitted so as to avoid
harbouring dirt.
(b) Where fixtures abut a floor and/or a wall or walls, the joint between the fixtures
and the floor and/or the walls should be impermeable.
(2) Shower traps and surrounding areas should be cleansable specially in the case of
communal showers.
(3) (a) Sanitary fixtures should be installed in a manner to afford easy access for
cleaning.
3.3.4 Support
3.3.4.1 General
(1) The design, choice and fixing of supports for sanitary fixtures are important and
consideration should be given to the dead weight of fixtures the load which may be placed
in it or on it and the nature of the structure to which it is to be fixed.
(2) All fixing screws should be of non-ferrous metal or stainless steel, and any low-carbon
steel in brackets or other supports should be galvanized, whether subsequently painted or
not.
3.3.4.2 Brackets
(1) Brackets should be of adequate strength and securely fixed having regard to the
cantilever effect of the weight of the fixture fully loaded.
(1) Larger and heavier sanitary fixtures, such as ablution fountains, shall be fixed direct to
the floor. Great care should also be taken to ensure that they are bedded solidly on a level
and even base.
22 © ESA
CES 161
(2) Other lighter fixtures such as WC pans and pedestal wash basins shall also be fixed
direct to the floor on a level and even base.
(3) Appliances on pedestals or legs shall be fastened to walls to give stability, expect in
those cases where the whole fitting is designed to be self supporting.
(1) The scale of provision of sanitary fixtures for the various types of occupancies shall be
as specified in NBCE Part 6.
3.5.1 General
(1) Care should be taken at all times, and particularly after fixing, to protect fixtures from
damage. Glazed, enameled and plated surfaces of fixtures can be irreparably damaged by
carelessness during subsequent operations.
(2) Water supply and discharge pipes should be installed before fixtures are put in place.
Before installing fixtures, it should be ensured that the discharge pipe is clear or
obstruction. Joints between fixtures and traps and/or pipes should be of the union or
detachable type.
3.5.2 Bath-tubs
3.5.2.1 Selection
(1) Bath-tub is intended for bodily immersion in a reclining position and it should have a flat
bottom with a fall to the outlet.
(2) Anti-slip surfaces, if provided, should not interfere with comfort or ease of cleaning and
draining.
3.5.2.2 Installation
(1) Support should be adequate for the weight of the fixture, use and water and sufficiently
unyielding to obviate strain on service connections.
(2) Supports should be adjustable to permit a bath-tab should be horizontal and care should
be taken to make a permanently watertight seal between the wall and the edge of the bath.
3.5.3.1 Selection
(1) Bodily ablutions under running water are more hygienic than washing by bodily
immersion in a bath. In addition, a shower unit is more economical in energy and water
consumption and convenient to use.
© ESA 23
CES 161
(2) Shower units shall be selected in accordance with approved standard (see Section 3.2).
3.5.3.2 Installation
(1) (a) Shower units should be installed in rooms that are adequately ventilated to
reduce the possibility of condensation.
(c) Shower trays should be laid on a smooth and structurally sound base and shall
be and made watertight with acceptable material.
(2) (a) Public shower rooms shall be drained in such a manner that no waste water from
any head will pass over areas occupied by other users.
(b) Traps shall be constructed so that a shower tray may be securely fastened to the
trap at the seepage entrance, making a watertight joint between the shower
tray and the trap.
3.5.4 Bidets
3.5.4.1 Selection
(1) There are two main types of bidets – over-rim water feed and submersible spray.
(2) Either of the bidets in (1) above may be with pedestal (more frequently fitted), or wall
mounted (used where an unrestricted floor is required).
3.5.4.2 Installation
(2) Where fixing screws are used, they should be non-ferrous or stainless steel.
(3) Wall-hung type bidets may be fixed directly to load bearing walls by bolts or,
alternatively and for non-load bearing walls, by bolting to a support frame.
3.5.5 Sinks
3.5.5.1 Selection
(1) The most hard-wearing material for sinks is stainless steel. Fire-clay sinks are hard-
wearing and strong, but care has to be taken in the use of utensils to avoid chipping,
especially on the front edge of the sink. Enamel steel sinks require careful use to prevent
chipping the enamel.
3.5.5.2 Installation
24 © ESA
CES 161
(2) Where sinks are built into table-top units, care shall be taken to seal the joint between
the bowl rim and the surrounding to prevent water seeping below the surface of the table
top.
3.5.6 WC Pans
3.5.6.1 Selection
(1) (a) A single flushing should clear all normal faecal matter from the WC pan, the
flush being so distributed over the internal surface of the pan as to cleanse
every part thereof without any of the contents of flushing water splashing on to
the seat or the floor.
(b) WCs should be selected so that noise produced while flushing is minimum.
(2) Wash down WC pans have horizontal outlets and require purpose-made connector to
connect them to the drainage systems.
(3) Siphonic WC pans depend upon siphonic action generate in the trap for the removal of
the contents when flushed. The area of exposed water in siphonic pans is usually greater
than in the washdown type with less chance of the pan being soiled. Siphonic WC pans
have a quieter flush than washwoen types but are more prone to blocking.
(3) Squatting WC pans are designed to be used without a seat and consist of a floor level
bowl with a squatting plate, i,e impervious surround which normally has slightly raised foot
treads.
3.5.6.2 Installation
(1) To prevent the penetration of moisture, the joint between the underside of the WC
pedestal and the floor should be sealed.
(2) All pedestal-type WC pans should be secured to the floor using stainless steel or non-
ferrous fixing screws.
(3) Where pedestal WC pans are installed on solid floors, it is essential that provision be
made in the floor to receive the fixing screws.
(4) If cement mortar is used for bedding (normally 1:3 mix), a thin layer should be applied
only to that part of the pedestal which is in contact with the floor.
(5) Wall-hung type WC pans may be fixed directly to load bearing walls by bolts, or
alternatively and for non-load bearing walls, by bolting to a support frame.
3.5.7.1 Selection
(1) WC seats and covers should be smooth and non absorbent. Ring sears are the simplest
type of seats and the most suitable for general use.
© ESA 25
CES 161
(2) Open-front seats are mostly used in male sanitary blocks in such buildings as industrial
and commercial premises and public conveniences, as being less likely to be fouled than
ring seat.
3.5.7.2 Installation
(1) The seat and cover, where fitted, should be properly fixed direct to the WC pan with
hinges. Compressible protective washers should be used between the hinge fixings and
both sides of the ceramic-ware. When raised, all seats and covers should travel though an
angle greater than 900 to ensure stability.
3.5.8.1 Selection
(1) Flushing cisterns shall have a flushing capacity sufficient to properly flush WC bowls
with which they are connected.
(2) The float-operated valve should close tight and be selected to suit the water pressure
and to ensure a refilling time of not longer than 2.0 min,
3.5.8.2 Installation
(1) A 32.0mm minimum inside diameter flush pipes is required for high level cistern and a
(1) Flush valves should be installed so that they will be readily accessible for maintenance.
(2) When the value is operated, it shall complete the cycle of operation automatically,
opening fully and closing positively under the service pressure.
(3) At each operation, the value shall deliver water in sufficient volume and at a rate that will
thoroughly flush the fixture and refill the fixture trap.
(4) Means shall be provided for regulating the flush valve flow.
(5) Not more than one fixture shall be served by a single flush valve.
26 © ESA
CES 161
3.5.11 Urinals
3.5.11.1 Selection
(1) (a) Still urinal is heavy, takes up more space, and unless designed with great care
with all angles rounded, it is more difficult to keep clean.
(b) It affords greater privacy than other types and is better able to withstand rough
usage.
(c) Flushing should be by means of a spreader to each stall to clean the whole
surface likely to be fouled.
(2) (a) Bowl urinal are less restrictive to planning and are more suitable for use where
floor movement might occur.
(b) Spreader should be provided to ensure that the flushing water washes the whole
of the internal surface of the bowl likely to be fouled.
(c) Bowl urinals are recommended only where responsibility in use can be
anticipated, as they are vulnerable to misuse.
(d) Independent divisions securely bolted to the wall surface should be used for
privacy.
(3) (a) Trough urinals should be rigidly supported along the whole of their length and
should discharge to a trapped outlet.
(b) Flushing may be by spreader to other means which can produce an even curtain
of water against the back of the urinal.
3.5.11.2 Installation
(1) The area behind, under and around urinals should be carefully made (made smooth and
non-absorbent) to take into account water and urine penetration.
(2) (a) The maximum fun of channel (through urinal) to an outlet should not exceed
2400.0mm.
(c) Trough urinal should preferably be made so that the front lip is 600.0mm high for
men on 500.0mm high for junior boys.
3.5.12.1 Selection
© ESA 27
CES 161
(2) Fire clay can be used, but is subject to the disadvantage of chipping, and it usually
needs replacement.
(4) Porcelain channeled sheet steel is suitable for light duty, but better service is usually
obtained from porcelain channeled cast iron for normal and heavy duty.
3.5.12.2 Installation
(1) The following types of support are normally used for the installation of wash basins;
(b) A pedestal securely fixed to the floor. The basin should be properly bedded on
the pedestal and anchored to the wall. It may be advisable to carry the weight of
the basin on wall fixings.
(c) Insert into a table top. Care should be taken to seal the joint between the rim and
the surround to prevent water seeping below the surface of the table top.
(1) Floor drains shall be rust-resistant and provided with removable strainers or gratings
(2) Floor drains shall be of a size to serve sufficiently the purpose for which they are
intended (see Clause 5.8.3.6.2).
3.6.1 Inspection
(1) Upon completion of the work, all fixtures, materials and workmanship should be carefully
examined for defects and for faults in installation which should be corrected before the
fixtures are handed over for use.
3.6.2 Maintenance
3.6.2.1 General
(1) Fixture should be cleaned frequently to maintain them in good sanitary condition and to
preserve their appearance.
(2) The removal of faulty tap and valve washers should receive prompt attention to avoid
waste of water and damage to the value seating and the surface of the fixture.
(3) Cleaning materials containing corrosive alkalis, abrasives or acids should not be used
because they damage fixtures and/or discharge pipe.
(4) The instruction of the manufacturer of the fixtures and of the cleaning and/or de-scaling
materials should be followed.
28 © ESA
CES 161
(1) For the removal of scale, encrustation and other deposits, acid and alkali-based
cleaning materials should be used with caution to avoid damage to the appliance and
pipework and/or injury to the cleaning operatives.
© ESA 29
CES 161
4.1 Scope
(1) This section covers basic requirements of water supply and distribution for residential,
commercial and other types of buildings, including traffic terminal stations and gives
recommendations on the design, installation, testing, commissioning and maintenance of
water supply and distribution services.
(2) It covers the system of pipes, fittings and connected appliances (fixtures) installed to
supply buildings.
(3) This section deals only with low temperature systems; it does not cover systems that are
designed to operate with steam or high temperature hot water.
(4) This section does not take into consideration the requirements of water supply for
industrial plants and processes and other purposes.
4.2 Materials
4.2.1 General
(1) The plumbing system shall have durable material, free from defective workmanship and
so designed and installed as to give satisfactory service for its reasonable expected life.
(2) Materials that have been used for a purpose other than the distribution of potable water
shall not be subsequently used in a potable water system.
(3) Every length of pipe and every fitting shall have case, stamped or indelibly marked on it
the maker’s name or mark and the weight or class or quality of the product, or it shall be
marked in accordance with the relevant standard; and such markings shall be visible after
installation.
(4) Water distribution pipes and fittings shall be of brass, copper, cast iron, UPVC,
galvanized malleable iron, galvanized wrought iron, and galvanized steel, PEX, PPR or
other approved materials manufactured to recognized standards may be used for water
distribution system. All materials used in the water supply system, except valves and similar
devices, shall be of a like material, unless and otherwise approved by the Authority Having
Jurisdiction.
(1) All pipes and fittings for the water supply system shall comply with the relevant
Ethiopian Standards or equivalent standards approved by the Building Official.
30 © ESA
CES 161
(1) Lead
(a) No pipe or pipe fittings or storage cistern made from lead or internally lined with
lead shall be used in new installations.
(b) Repairs to existing lead services shall be by replacement with other approved
materials.
(c) The repair or partial replacement of lead piping with copper piping shall be
avoided unless galvanic action is prevented.
(2) Copper
(a) Copper is generally resistant to corrosion and is suitable for hot and cold water
applications. Where supply waters are capable of dissolving an undue amount of
copper such that either:
(b) Galvanized steel pipe work should not be used connected to and, especially,
downstream from copper pipe work; otherwise it will be subjected to accelerated
corrosion.
(a) Galvanized steel pipe shall be jointed only by screwed connections; under no
circumstances shall welded or brazed joints be used because this would damage
the galvanizing. Site bending of galvanized tube will also damage the galvanizing;
in view of this or where it is necessary to change direction pre-formed bends shall
be used. Galvanized tubes offer only marginal protection against corrosion, and
shall be protected from corrosion especially where installed below ground.
(a) Plastic pipes shall not be installed close to source of heat or in direct sunlight;
otherwise their performance is impaired.
(b) Where pipes are installed above ground, consideration shall be given to
accommodate thermal movements.
© ESA 31
CES 161
(a) No pipe, pipe fitting or storage cistern intended for conveying or storing wateshall
be lined or coated internally with coal, tar or any substance that includes coal-tar.
(b) Recommendations for the protective coating against corrosion of iron and steel
pipes, fittings and cisterns shall be referred to approved standards.
(1) Materials installed in the system shall be so handled and installed as to avoid damages
so that the quality of the material will not be impaired.
(2) Check delivery documents and certificates against specification; examine marks and
labels and condition of materials and components.
(3) Handle all materials and components with appropriate care to prevent damage, soiling
and contamination.
(a) In a secure shelter or compound under cover and on bases or racking prepared
in advance of deliveries.
(c) Protect polyethylene or any plastic tube and pipe from direct sunlight.
(a) Communicate to establish and agree the positions of pipe work and fittings in
relation to other services, appliances, and any requirements for first and
subsequent fixing stages.
(b) Inspect all components immediately before assembly and discard any
components that are damaged.
(1) The following factors shall be taken into account in selecting materials to be used in a
water service:
(a) Cost,
32 © ESA
CES 161
(g) Durability.
(2) Every part of a water installation shall be cable of operating effectively under the
conditions which it will experience in service. Accordingly;
(a) Every pipe, pipe joint and connected fitting used for domestic water supply shall
be capable of withstanding, without damage or deterioration, sustained
temperature of up to 400C for cold water installation and up to 700C, with
occasional short-term excursions up to 1000C to allow for malfunctions, for
heated water installations.
(b) Every draw-off tap shall be capable of operating effectively at any water
temperature and internal water pressure to which it is to be subject.
(3) (a) If pipes, pipe joints or connected fittings are of dissimilar metals, necessary
measures shall be taken to prevent corrosion.
4.3.1 General
(1) Any cold water tap which is likely to be used for drinking water and all such taps not
connected directly to the potable water supply mains shall be supplied from a storage
cistern which is protected in accordance with clause 4.3.4.
(2) No drinking water point shall be installed at the end of a long pipe where only small
volumes of water are drawn-off.
(3) To reduce the risk of stagnation, the layout of the pipe work should be arranged, where
possible, so that fittings downstream of a drinking water point have a high demand.
(4) All premises intended for human habitation, occupancy, or use shall be provided with
supply of potable water. This water supply shall not be connected with unsafe water
resources, nor shall it be subject to the hazards of backflow.
(5) Plumbing fixtures, devices and appurtenances shall be provided with water in sufficient
volume and at pressures adequate to enable them to function properly and without undue
noise under normal conditions of use. There should be at least a residual head of 0.5 bar (5
m) at the consumer’s tap at critical water outlet and whenever fixtures or fixture fittings that
require a residual pressure higher than 0.5 bar are installed, that minimum residual
pressure shall be provided.
© ESA 33
CES 161
(6) Plumbing system shall be designed, installed and adjusted to use the optimum quantity
of water consistent with proper performance and cleaning.
4.3.2.1 General
(1) Public water suppliers are obliged to provide a supply of wholesome water which is
suitable and safe for drinking and culinary or cooking purposes.
(1) Potable water is water which is satisfactory for drinking, culinary and other domestic
purposes. The quality of water to be used for this purpose shall be as per the prevailing
standards at the time of application. The national drinking water quality standard for
Ethiopia is shown in Table 4-1. WHO drinking water guideline values for chemicals that
have health significance are also indicated in Annex K.
34 © ESA
CES 161
Maximum permissible
Parameter Unit
level
PHYSICAL
Odor - Unobjectionable
Taste - Unobjectionable
Turbidity NTU 5
Color TCU 15
CHEMICAL
Total hardness mg/L as CaCO3 300
Total dissolved solids mg/L 1000
Total iron mg/L 0.3
Manganese mg/L 0.01
Ammonia (NH3+NH4+) mg/L 1.5
Residual free chlorine mg/L as MBAS 0.5
Anionic surfactants mg/L 1.0
Magnesium mg/L 50
Calcium mg/L 75
Copper mg/L 2
Zinc mg/L 5
Sulfate mg/L 250
Chloride mg/L 250
Total alkalinity mg/L 200
Sodium mg/L 200
Potassium mg/L 1.5
Aluminum mg/L 0.2
pH - 6.5-8.5
Barium mg/L 0.7
Total mercury mg/L 0.001
Cadmium mg/L 0.003
Arsenic mg/L 0.01
Cyanide mg/L 0.07
Nitrite mg/L 3
Nitrate mg/L 50
Phenolic compounds as phenol mg/L 0.002
Lead mg/L 0.01
Boron mg/L 0.3
Selenium mg/L 0.01
Fluoride mg/L 1.5
Chromium mg/L 0.05
Pesticides
Lindane mg/L 2
Aldrin/Dieldrine mg/L 0.03
1,2 Dichloroethane mg/L 30
BACTERIOLOGICAL
Total viable organisms Colonies per 100 mL Must not be detectable
Faecal streptococci MPN per 100 mL Must not be detectable
Coliform organisms MPN per 100 mL Must not be detectable
E.Coli MPN per 100 mL Must not be detectable
© ESA 35
CES 161
(1) Non-potable water may be used for flushing water closets and urinals and other
appliances not requiring potable water, provided such water shall not be accessible for
drinking or culinary purposes.
(1) In buildings where dual water distribution systems are installed, one potable and the
other Non-potable water, each system shall be identified either by color code or metal tags,
or other appropriate methods as may be approved by the Authority Having Jurisdiction.
Each outlet on the non-potable water line that may be unknowingly used for drinking or
domestic purpose shall be posted: DANGER - UNSAFE WATER.
(2) Potable and Non potable water systems installed shall be clearly identified by the
following color code.
(b) Non potable – Yellow background with black lettering, with words
(a) Each system shall be identified with a colored band to designate the liquid being
conveyed, and the direction of normal flow shall be clearly shown. The minimum size of the
letters and length of the color field shall confirm to Table 4.2.
(b) A colored identification band shall be indicated every 6 meters, but at least once per
room and shall be visible from the floor level.
36 © ESA
CES 161
4.3.4.1 General
(1) Water supply installations shall be carried out so that delivered water is not liable to
become contaminated to the extent that it is hazardous to health or is unfit for its intended
use.
(2) The installation in (1) above, in particular, shall not adversely affect drinking water in any
of the following ways;
(a) By materials in contact with water being unsuitable for the purpose (see Clause
4.3.4.2).
(b) By cross connection between pipes conveying water supplied by the water
undertaker with pipes conveying water from some other source.
(2) No pipe, fitting or storage cistern shall be lined or coated internally with coal tar or with
any material which will affect the quality of potable water.
(b) Fixed not less than 600.0mm above the surface of the ground likely to the
contaminated.
(2) No plastic pipe shall be laid where oil or petrol leakage or spillage should be expected to
occur (unless suitable measures are taken to prevent contact of any oil or petrol with the
plastic pipes) or where possible migration of petroleum materials and phenols from
contaminated soils might occur.
© ESA 37
CES 161
4.3.4.3.1 General
(1) Positive measures shall be taken to prevent:
(b) The backflow of water from the installation to the supply mains; and
(c) Pumping on supply pipes (without the permission of the water supplier) which
may cause backflow in adjacent pipes as shown in Figure 4.1.
(1) Every draw-off tap or similar fitting installed to discharge water into a sink, was basin,
bath or similar appliance shall be installed so that the vertical distance between the point of
discharge of the fitting and the spill-over level of the receiving appliance shall not be less
than that indicated in Table 4.3 for the size of the fittings concerned.
(2) Where it is not possible to provide a minimum air gap, the water outlet shall be protected
with approved method of backflow prevention satisfactory to the Building Official.
(b) Installed and arranged so that the vertical distance between each point of
discharge of water and the spill-over level of the bidet shall not be less than that
indicated in Table 4.3 for the size of the water inlet fitting concerned.
38 © ESA
CES 161
(1) Every supply pipe conveying water to a cistern (whether or not fitted to a float-operated
valve) shall be provided with air gaps (see Table 4.3) above the spill-over level of the
cistern if:
(b) The cistern is a flushing cistern or is holding water for non-domestic purposes.
(2) Paragraph (1b) above shall not apply to a supply pipe conveying water to a cistern:
(a) Holding water supplied for domestic purposes and complying with clause 4.4 for
which no protection is required;
(b) Fitted with a float-operated value of a reducing flow type which will prevent back
siphonage through it if a vacuum occurs in the feed pipe.
(1) No supply pipe or cistern used for conveying or receiving water supplied by a public
water supplier shall be connected so that it can receive or convey water for any non-
domestic purpose or water that is not supplied by a public water supplier.
(1) Consumption of residential buildings depends on type of delivery of water to the end
consumer and the living standard of the community. Table 4.4 shows the residential water
requirements.
© ESA 39
CES 161
i. Low consumption is dwelling unit with only one wet corner, fitted with shower, Hand wash
basin, WC, traditional kitchen without kitchen sink, but with manual Laundry trough.
ii. Medium consumption is dwelling unit with two wet corners, fitted with shower, Bath tub, Hand
wash basin, WC, kitchen sink and laundry sink or machine.
iii. High consumption is dwelling unit with more than two wet corners, fitted with all mentioned in
(ii) above and sauna facilities and others.
(1) Minimum requirements for water supply for buildings other than residences shall be in
accordance with Table 4.5.
Consumption per
Type of building occupancy
head per day [l]
(a) Factories with bathroom
(i) with canteen 50
(ii) without canteen 40
(b) Factories without bathroom
(i) with canteen 35
(ii) without canteen 25
(c) Hospitals (per bed)
(i) Number of beds not exceeding 150-250
100
(ii) Number of beds exceeding 100 250 – 350
(d) Nursing homes and medical quarters 135
(e) Hostels (without canteen service) 100
(f) Dormitories with canteen service 135
(g) Hotels (per bed)
(i) Up to 4 star 200
(ii) 5 stars and above 350
(h) Offices 35
(i) Restaurants (per seat) 75
(j) Bars (per seat) 50
(k) Cinemas and theatres (per seat) 15
(l) Schools
(i) Day Schools 25
(ii) Boarding schools (including 135
canteen)
40 © ESA
CES 161
Minimum requirements for water supply for traffic terminal stations shall be in accordance
with Table 4.6.
Without Bathing
No. Nature of Station/Terminal Facilities
(liters/capita)
4.3.5.4 Water supply for fire fighting purposes (refer Fire Code – ES-3964)
Due reference should be made to the fire code (ES-3964) to estimate the water supply
requirements for firefighting purpose as a function of building type and material and the fire
extinguishing system.
4.4.1 General
(a) To provide against interruptions of the supply caused by repairs to mains, etc;
(d) To maintain a storage for the fire fighting requirement of the building
(2) Every storage tank shall be easily accessible and placed in such a position as to enable
thorough inspection and cleaning to be carried out. In large storage tanks, the outlet shall
be at the end opposite the inlet to avoid stagnation of the water.
(3) Storage cisterns and their lids for domestic water supply purposes should not impart
taste, color, odor or toxicity to the water, nor promote microbial growth.
(4) The water may be stored either in overhead tanks (OHT) and/or underground tanks
(UGT) and storage cisterns above 5000 liter capacity shall be divided into two or more
compartments or tanks to avoid interruption of the water supply when carrying out cleaning,
inspection or maintenance of the cistern without interfering with the water supply system.
© ESA 41
CES 161
(b) Where necessary, lined or coated with a material suitable for use in contact with
potable water and must not deform unduly in use;
(e) Supported on a firm level base capable of withstanding the weight of the cistern
when filled with water to the rim;
(f) Provided with inlet (including float-operated valve or other approved type control
system), outlet, overflow and drain pipes.
(1) No cistern shall be buried or sunk in the ground unless special measures are taken to
avoid leakage and protect the cistern from ingress of contaminants.
(2) Unless used only for non-potable water, every underground cistern shall be protected
from ingress of surface water or ground water and such cisterns shall be well ventilated and
protected from ingress of animals and insects and accessible for maintenance.
(3) The underground tanks should not be located in low lying areas or near any public or
private sewer, septic tank, leaching pool or soakage pit to prevent any contamination. For
tanks with at least one side exposed to a basement, it is safer to discharge the overflow into
the basement level provided that the basement has proper drainage system.
(4) The tank structure shall also be designed to carry the load due to fire tender movement.
(5) There shall be no common wall between the tanks storing safe water and tanks storing
water from unsafe sources.
(1) Cisterns mounted within the premises of a building shall be well ventilated and protected
from ingress of birds, animals and insects and provided with access to the interior of the
cistern for maintenance.
(3) There should be no common wall between the tanks storing safe water and tanks
storing water from unsafe sources.
(4) In tall buildings, the top of the tank shall be provided with the safe ladder or staircase.
The top slab shall be provided with railing or a parapet wall.
42 © ESA
CES 161
(1) Manholes: Provide adequate number of manholes for access and repair. The manholes
shall made of corrosion resistant material ( For example, cast iron, reinforced cement
concrete, steel fiber reinforced concrete, galvanized steel, high density polyethylene, fiber
glass reinforced plastic or such other materials acceptable to the Authority). Manholes shall
be provided with locking arrangement to avoid misuse and tampering.
(2) Ladders: Tanks higher than 1m deep shall be provided with internal corrosion steps or
ladders according to the depth to enable a person to reach the bottom of the tank.
(3) Overflow Pipe: Each tank shall be provided with an overflow pipe made of rigid,
corrosion resistance material, preferably terminating above the ground level to act as a
‘Warning Pipe’ to indicate overflow conditions. The size of the overflow pipe shall be
adequate to accept the flow. The overflow pipe size shall be at least one size higher than
the inlet pipe. When the inlet pipe diameter is large, two or more overflow pipes of
equivalent cross section may be provided. The overflow of the tank should be well above
(preferably 600 mm) the external surface level and terminate as a warning pipe with a
mosquito proof grating. Care must be taken to prevent backflow of local surface water into
the tank in case of local flooding. Otherwise the overflow must be terminated in a safer
manner as per the site conditions. For tanks with at least one side exposed to a basement,
it is safer to discharge the overflow into the basement level provided that the basement has
proper drainage system.
(4) Vent Pipes: Tanks shall be provided with vent pipes to prevent development of pressure
in the tank which might result in NO FLOW condition or inward collapse of the tank.
(5) Scour/Drain Pipe: Each tank shall be provided with a scour pipe with an accessible drain
valve located at their lowest point with the floor of the cisterns laid to a slight fall to the
drains for emptying the tank.
(6) Connection of Overflow and Scour/Drain Pipe: Under no circumstances tank overflow
and scour pipe shall be connected to any drain, gully trap or manhole to prevent back flow
and contamination of the water. All such connections shall be discharged over a grating
with an air gap of minimum 50 mm. All overflow and vent pipes shall be provided with a
mosquito proof corrosion resistant grating to prevent ingress of mosquito, vermin and other
insects.
(7) The top slab of the tank must be suitable sloped away from its, centre for proper
drainage of the rainwater.
(8) Tanks on terraces and above ground shall be supported by appropriate structural
members so as to transfer the load of the tank and the water directly on the structural
members of the building.
© ESA 43
CES 161
(a) The heights of connection to outlet pipes (heights up to the invert of outlet pipes)
above the bottom of a gravity cistern of capacity 5000.0 liter and above shall not
be less than 80.0mm.
(b) Such heights shall not be less than 50.0mm for cisterns of capacity less than
5000.0 liter.
(d) For pump-suction cisterns, the height of connection of suction pipes shall comply
with the provisions of clause 4.4.6.
(e) For jointing steel pipe to a storage tank, the end of the pipe shall be screwed,
passed through a hole in the tank and secured by back nuts, both inside and
outside. For jointing copper pipe to steel or copper tank, a connector of non-
ferrous material shall be used. The connector shall have a shoulder to bear on
the outside of the tank and shall be secured by a back nut inside.
(10) Inlet Pipes: Inlet pipes and float-operated control valves shall confirm to the
following:
(a) Except for interconnected cisterns arranged to store water at the same level,
every pipe supplying water to a storage cistern shall be fitted with a float-
operated valve or some other equally effective and approved device to control the
inflow of water and maintain it at the required level.
(b) The water level shall be at least 50.0 mm below the lowest point of the lowest
overflow pipe connection.
(c) The inlet control device shall be suitable for the particular application, bearing in
mind the supply pressure and the temperature of the water in the cistern.
(d) Every float-operated valve shall be securely fixed to the storage cistern it supplies
and, where necessary, braced to prevent the thrust of the float causing the valve
to move and so effect the water level.
(1) In designing the storage capacity, consideration shall be taken of the pattern of water
use in the premises concerned, hours of supply to fill up the storage tanks, likely frequency
and duration of breakdown in supply from the water supplier’s mains and consequences of
exhausting storage.
General guidelines for calculation of the minimum recommended capacity of storage tanks
shall be as follows:
(a) In case only elevated water tank is provided, it may be taken as 33 to 50 percent
of one day’s requirement;
(b) In case only underground water tanks is provided, it may be taken as 50 to150
percent of one day’s requirement; and
44 © ESA
CES 161
(1) (a) The effective storage capacity shall be taken as the measurement between the
normal water level in the cistern or tank and the low water level designated ‘X’ as
shown in Figure 4.2.
(b) Low water level ‘X’ is taken to be the lowest level before a vortex is created
causing the pump to draw air.
(c) The effective depth is then multiplied by the average surface area of the storage
to obtain the effective capacity.
(2) Where the suction pipe is taken from the side of the storage, as shown in Figure 4.2 (b)
and (e), the clearance between the base of the storage and the lowest part of the pump-
suction pipe shall not be less than the dimension B as given in the figure.
(3) (a) Where a suction pipe draws from a sump in the base of a storage, the sump
length shall be not less than the dimensions indicated in Figure 4.2 (d), (e) and
(f).
(b) In addition, the sump width shall be not less than 3.6D where D is the nominal
diameter of the suction pipe.
(c) The point of entry shall be located centrally across the width of the sump.
(4) When an approved vertex inhibitor is installed, the following variation to the dimensions
given in (3) above shall apply:
(a) Dimension A in Figure 4.2 may be disregarded and low water level X may be
taken as the level at which vortex action commences.
(b) Dimension B in Figure 4.2 may be taken from the base of the tank to the level at
which a vertex action commences in Figure 4.2(a).
Note: (i) Vortex inhibitors are not suitable for use in sump.
(5) Where arrangements depicted in Figure 4.2 are not applicable, different intake design
may be accepted in agreement with Building Official.
© ESA 45
CES 161
46 © ESA
CES 161
4.5.1 Pipes
(1) For water supply pipes and fittings refer to clause 4.2 and any approved standards.
(1) The flow from any water main to any water service pipe, and within the water service
pipes, shall be controlled by means of isolating valves (stop valves and service valves), the
location as specified in Table 4.7.
4.6.1 General
(1) Electrically driven centrifugal pumping plant are normally used and pumps shall be
duplicated and use alternatively
(2) Where prudent, provision shall be made for the pumps to be supplied by an alternative
power supply in the event of mains failure.
(3) Pumps may be of either a horizontal or vertical type, directly coupled to their electric
motors.
(4) Pumps shall be sized so that each pump is capable of overcoming the static lift plus the
friction losses in the pipe work and valves.
(5) Where pumps are connected directly to the service pipe, full allowance shall be made
when calculating the required pump head for the pressure already in the service pipe, since
the pump head is added to this and does not cancel out an existing pressure.
(6) The fittings of motors with sleeve-type super-silent bearings shall be considered in order
to achieve quite running.
(7) (a) Automatic control of a pumping plant is essential and pressure switches, level
switches or high-level and low-level electrodes will give reliable control. Other
methods of control, both mechanical and electrical, can be adopted.
(b) Pumping equipment shall be controlled via a pump selector switch and an
ON/OFF/AUTO Control.
(d) Pumps shall be controlled to limit the number of starts per hour to within the
capacity of the pump.
© ESA 47
CES 161
Type of
Location
valve
(a) General
Notes: (i) Stop valve is a valve which can be operated to stop the flow in a pipeline.
(ii) Service valve is a valve which can be operated to stop the flow into an appliance or fixture.
(8) (a) Most small air compressor used for charging pneumatic pressure vessels or
pressure tanks are of the reciprocating type, shall be either air or water cooled.
(b) The air to be compressed shall be drawn from a clean cool source and should be
protected from contamination.
(1) A pump room shall be of adequate size to accommodate all the plant and also to
provide adequate space for maintenance and replacement of parts.
(2) A pump room shall be dry, ventilated and protected from flooding.
(3) Entry of birds and small animals shall be prevented and access should be restricted to
authorized persons
48 © ESA
CES 161
(b) Have vibration eliminators at the base of the pump, in the suction side and the
delivery side of the pump so as to minimize the transmission of noise into the
building structure and along the piping system and the prevent undue stress
being placed on the pump;
(c) Have isolation valves on the delivery side and the suction side of the pump;
(d) Have a non-return valve on the delivery side of the pump before the isolation
valve;
(e) Have pressure gauges on the inlet and outlet of the pump; and
(2) Water meters to be installed inside buildings shall be fixed with the distance not more
than 1.5m above floor level and readily visible for reading.
(3) Water meters to be installed below ground level shall be located in a chamber that has a
cover removable by one person and provided with a base that enable drainage. Where
liable to vehicular damage, water meters shall be protected.
© ESA 49
CES 161
(4) Water meters DN 50 mm or larger in size shall be supported independently of the pipe
work.
(1) The sizes of the pipes and fittings used in a water service shall be such that will provide
an adequate rate of delivery of water without recourse to wasteful over sizing.
(2) The installation shall be sized so that design flow rates given in Table 4.8 shall be
available at each outlet when only that outlet is open and at all outlets for most of the time.
The pipes and fittings shall also be sized so that the water velocity in any pipe does not
exceed those given in Table 4.11.
(3) (a) In small, simple installations such as those in small dwellings, it is often
possible to size pipes on the basis of experience and convention.
(b) In all other cases, the pipe sizes shall be calculated in accordance with good
engineering practice.
(4) The amount of either hot or cold water used in any building is variable, depending on the
type of occupancy and time of day. Optimum pipe sizes shall be designed to meet peak
demand.
(5) All premises intended for human habitation, occupancy, or use shall be provided with
supply of potable water. This water supply shall not be contaminated with unsafe water
sources, nor shall it be subject to the hazards backflow.
(6) Plumbing fixtures, devices and appurtenances shall be provided with water in sufficient
volume and at pressures adequate to enable them to function properly and without undue
noise under normal conditions of use.
(7) The system shall be designed, installed and adjusted to use the optimum quantity of
water consistent with proper performance and cleaning.
(8) The system shall be designed and installed with safety devices to safeguard against
dangers from contamination, explosion, overheating, etc.
(1) Pipes and fittings shall be sized so that the flow rates for individual draw-offs are equal
to the design flow rates shown in table 4.8 and during simultaneous discharges the
minimum flow rates shall be maintained on each tap.
50 © ESA
CES 161
Design Minimum
flow Loading
Outlet fitting flow rate
rate (l/s) units
l/s
Notes:
(1) Flushing troughs are advisable where likely use of WCs is more than once per minute.
(2) Mixer fittings use less water than separate taps, but this can be disregarded in sizing.
(3) Flow rates to shower mixers vary according to type fitted. Manufacturers should be consulted.
(4) Manufacturers should be consulted for flow rates to washing machines and dishwashers for other
than a single dwelling.
(5) For cistern fed urinals demand is very low and can usually be ignored. Alternatively, use the
continuous flow.
(2) Loading units should not be used for outlet fittings having high peak demands, e.g.
those in industrial installations. In these cases use the continuous flow.
(3) BS 6700 does not give loading units for sink tap DN 20 or pressure flushing valve for
WCs or urinals.
Pipe sizes shall ensure adequate flow rates at appliances and avoid problems that lead to
(see Figure 4.3):
© ESA 51
CES 161
(a) inadequate delivery from outlets and possibly no delivery at some outlets during
simultaneous use;
(b) some variation in temperature and pressure at outlets, especially showers and
other mixers;
(3) In smaller, straightforward installations such as single dwellings, pipes are often sized
on the basis of experience and convention.
(4) In larger and more complex buildings, or with supply pipes that are very long, it is
necessary to use a recognized method of calculation such as that shown in sections 4.8.3.1
and 4.8.3.2.
52 © ESA
CES 161
The procedure below is followed by an explanation of each step with appropriate examples.
(c) Obtain the design flow rate by adding (a) and (b).
(g) Obtain the effective pipe length by adding (d), (e) and (f).
(i) Determine the head loss per metre run through pipes;
(l) Decide whether the assumed pipe size will give the design flow rate in (c) without
exceeding the permissible head loss in (k).
In pipe sizing it is usual to make an assumption of the expected pipe size and then prove
whether or not the assumed size will carry the required flow.
In most buildings it is unlikely that all the appliances installed will be used simultaneously.
As the number of outlets increases the likelihood of them all being used at the same time
decreases. Therefore it is economic sense to design the system for likely peak flows based
on probability theory using loading units, rather than using the possible maximum flow rate.
© ESA 53
CES 161
(a) Loading units: a loading unit is a factor or number given to an appliance which
relates the flow rate at its terminal fitting to the length of time in use and the
frequency of use for a particular type and use of building (probable usage).
Loading units for various appliances are given in table 4.8. By multiplying the
number of each type of appliance by its loading unit and adding the results, a
figure for the total loading units can be obtained. This is converted to a design
flow rate using Figure 4.4. An example using loading units is given in Figure 4.5.
(b) Continuous: flows for some appliances, such as automatic flushing cisterns, the
flow rate must be considered as a continuous flow instead of applying probability
theory and using loading units. For such appliances the full design flow rate for
the outlet fitting must be used, as given in Table 4.8. However, in the example
shown in Figure 4.5, the continuous flow for the two urinals of 0.008 l/s (from
table 4.8) is negligible and can be ignored for design purposes.
(c) Design flow rate: the design flow rate for a pipe is the sum of the flow rate
determined from loading units (a) and the continuous flows (b).
(d) Find the measured pipe length. Figure 4.6 is an example showing how the
measured pipe length is found. Therefore, from figure 4.4, the required flow rate
for the system is 0.7 l/s.
(e) and (f) Find the equivalent pipe lengths for fittings and draw-offs. For
convenience the frictional resistances to flow through fittings are expressed in
terms of pipe lengths having the same resistance to flow as the fitting. Hence the
term ‘equivalent pipe length’ (see table 4.9). For example, a 20 mm elbow offers
the same resistance to flow as a 20 mm pipe 0.8 m long. Figure 4.7 shows the
equivalent pipe lengths for the fittings in the example in Figure 4.6.
Table 4-9 Equivalent pipe length (copper, galvanized steel and plastics)
54 © ESA
CES 161
(g) Effective pipe length. The effective pipe length is the sum of the measured pipe
length (d) and the equivalent pipe lengths for fittings (e) and draw-offs (f).
Therefore, for the example shown in Figure 4.6 the effective pipe length would be:
Measured pipe length 4.75 m
Equivalent pipe lengths
elbows 2 × 0.8 = 1.6 m
tee 1 × 1.0 = 1.0 m
stopvalve 1 × 7.0 = 7.0 m
taps 2 × 3.7 = 7.4 m
check valves 2 × 4.3 = 8.6 m
Effective pipe length = 30.35 m
© ESA 55
CES 161
56 © ESA
CES 161
© ESA 57
CES 161
Figure 4-7 Examples of equivalent pipe length (using the example from Figure 4-6)
(i) In Pascal, the Pascal (Pa) being the SI unit for pressure.
(iv) As meters head, that is, the height of the water column from the water
level to the draw-off point.
In the sizing of pipes, any of these units can be used. However, meter head shall be used
for giving a more visual indication of pressure that compares readily to the height and
position of fittings and storage vessels in the building.
(h) Available head. This is the static head or pressure at the pipe or fitting under
consideration, measured in meter head (see Figure 4.3).
58 © ESA
CES 161
(i) Head loss through pipes. The loss of head (pressure) through pipes due to
frictional resistance to water flow is directly related to the length of the pipe run
and the diameter of the pipe. Pipes of different materials will have different head
losses, depending on the roughness of the bore of the pipe and on the water
temperature. Copper, stainless steel and plastics pipes have smooth bores and
only pipes of these materials are considered in this section.
(j) Head loss through fittings. In some cases it is preferable to subtract the likely
resistances in fittings (particularly draw-offs) from the available head, rather than
using equivalent pipe lengths. Table 4.10 gives typical head losses in taps for
average flows compared with equivalent pipe lengths. Figures 4.8 and 4.9
provide a method for determining head losses through stop valves and float-
operated valves respectively.
Note: Where meters are installed in a pipeline the loss of head through the meter shall be deducted from the
available head.
Table 4-10 Typical head losses and equivalent pipe lengths for taps
In the example in Figure 4-6 a pipe size of 20 mm has been assumed. This pipe size must
give the design flow rate without the permissible head loss being exceeded. If it does not, a
fresh pipe size must be assumed and the procedure worked through again.
Figure 4-10 relates pipe size to flow rate, flow velocity and head loss. Knowing the
assumed pipe size and the calculated design flow rate, the flow velocity and the head loss
can be found from the figure as follows.
(1) Draw a line joining the assumed pipe size (20 mm) and the design flow rate (0.4 l/s).
(2) Continue this line across the velocity and head loss scales.
(3) Check that the loss of head (0.12 m/m run) does not exceed the calculated permissible
head loss of 1.48 m/m run.
(4) Check that the flow velocity (1.4 m/s) is not too high by referring to 4.11.
© ESA 59
CES 161
60 © ESA
CES 161
© ESA 61
CES 161
62 © ESA
CES 161
The tabular method uses a work sheet which can be completed as each of the steps is
followed in the pipe sizing procedure. An example of the method follows with some
explanation of each step.
(1) Make a diagram of the pipeline or system to be considered (see Figure 4.11).
(2) Number the pipes beginning at the point of least head, numbering the main pipe run
first, then the branch pipes.
(3) Make a table to show the loading units and flow rates for each stage of the main run.
Calculate and enter loading units and flow rates; see Figure 4.11.
(a) Add up loading units for each stage (each floor level);
(3) Calculate percentage demand (number of stages for which frictional resistances need
be allowed). See Figure 4.13.
See Figure 4.12, using the data shown in Figures 4.11 and 4.13.
64
© ESA 63
CES 161
Therefore only 60% of the installation need be considered. For example, if we were
designing for a multi-storey building 20 storeys high, only the first 12 storeys need to be
calculated. However, in the example followed here, the whole system has been sized
because the last fitting on the run has a high flow rate in continuous use. For branches only
the pipes to the largest draw off, i.e. the bath tap, need be sized.
64 © ESA
CES 161
Convert loading units to flow rate (figure 4.4) (3) Flow rate (l/s)
Make assumption as to pipe size (inside diameter) (4) Pipe size (mm diameter)
Work out frictional resistance per metre (figure 4.10) (5) Loss of head (m/m run)
Measure length of pipe under consideration (7) Measured pipe run (m)
Consider frictional resistances in fittings (table 4.11 and (8) Equivalent pipe length (m)
figures 4.8 and 4.9
Add head consumed in column 10 to progressive head (11) Progressive head (m)
in previous row of
Compare progressive head with available head to (13) Final pipe size (mm)
confirm pipe diameter or not
© ESA 65
CES 161
66 © ESA
CES 161
(1) This system shall be adopted when adequate pressure is available throughout the day
at the municipal water distribution line which can satisfy the functionality requirements of
the building or that is sufficient to reach an elevated water tank; and municipal water supply
interruption is not expected.
(1) The water supply distribution line after the water meter shall be directly connected to
sanitary fixtures without any storage.
(1) The water distribution line after water meter shall be directly connected to elevated
water tank and the fixtures are supplied via gravity from the elevated water tank.
(1) The system shall be adopted when the requirement under 4.8.4.1(1) is not fulfilled.
(2) The system shall be used where a constant and reliable supply of power is ensured.
(1) Direct pumping from a water supply line could affect the municipal water supply system
depending on the pressure in the system. Therefore, special approval from the water supply
authorities be obtained before designing such a system.
(a) The pump shall be connected to a water distribution line after the water meter
and provides water to all fixtures without any storage.
(b) Direct pumping systems shall be used for buildings where a certain amount of
constant use of water is always occurring.
(3) Direct pumping from water supply line to elevated water tank
(a) The pump shall be connected to a water distribution line after the water meter
and delivers to an elevated water tank from which fixtures are supplied via
gravity.
(1) The municipal water shall be stored at ground or low level water reservoir and be
pumped to elevated or roof water tanks as shown in Figure 4.14.
(2) Water collected in the elevated or overhead tank shall be distributed to the various parts
of the building or fixtures via gravity system.
© ESA 67
CES 161
(3) Care shall be taken to avoid dry running of pump when the water level in the lower
reservoir reaches its minimum level.
(4) The system shall ensure automatic operation of the pumps by providing level control
switches in the elevated water tank or approved control methods.
(1) An operation of the pumps shall be regulated using an air-tight pressure vessel as
shown in Figure 4.15.
(2) The vessel capacity shall be based on the cut-in and cut-out pressure of the pumping
system depending upon allowable start/stops of the pumps and capacity shall be
determined by approved standard or manufacturer recommendation.
(3) Adequate capacity clean/filtered and free from oil of compressed air shall be connected
to feed air into the vessel, so as to maintain the required air-water ratio within the system.
4.8.4.2.4 Direct pumping from ground reservoir using Variable Speed Drive Pumps
(1) Variable speed drive pumping system shall be used where a pump with a large variation
in its pressure-discharge and speed of the pump is efficiently used to deliver water at rates
of flow as required by the system by changing its speed by varying it with the assistance of
an electronic device which will reduce the rate of flow from speed of the motor about 960
rpm to 3000 rpm.
(2) Proper dry running protection shall be provided to protect bearings and shaft seals from
being damaged using inlet pressure of the booster system or the level in the water
reservoir.
(3) Expansion joints shall be installed in the suction and delivery sides of the pump system
to:
(b) Reduce mechanical strains in connection with pressure surges in the pipe work
(c) Isolate mechanical structure born noise in the pipe work (only rubber bellows
expansion joints)
(4) It is advisable to isolate the booster system foundation from building parts by means of
vibration dampers to prevent the transmission of vibration to buildings.
68 © ESA
CES 161
© ESA 69
CES 161
4.8.5 Water pressure, pressure regulators, pressure relief valves and vacuum relief
valves
(1) Whenever the water pressure in the main or other source of supply will not provide a
residual water pressure of at least 5 meters (0.5bar), after allowing for friction and other
pressure losses, tank and a pump or other means which will provide said fifteen shall be
installed.
(2) Whenever fixtures and /or fixture fittings are installed that require residual pressure
higher than fifteen 5meters (0.5bar), that minimum residual pressure shall be provided.
70 © ESA
CES 161
(1) Where local static water pressure is high an approved type pressure regulator shall be
installed.
(3) Each such regulator and strainer shall be accessibly located and shall have the strainer
readily accessible for cleaning without removing the regulator or strainer body or
disconnecting the supply piping.
(1) Any water system provided with a check valve, backflow preventer, or a pressure-
regulating device which does not have a bypass feature at its source shall be provided with
as approved, listed adequately sized pressure relief valve or a means to control expansion.
(2) Relief valves located inside a building shall be provided with a drain, not smaller than
the relief valve outlet.
(3) No shutoff valve shall be installed between the relief valve and the system or in the
drain line.
(1) Where a hot-water storage tank or an indirect water heater is located at an elevation
above the fixture outlets in the hot-water system, a vacuum relief valve shall be installed on
the storage or heater.
(1) The hot water services shall be designed to provide, so far as is practicable, hot water at
the locations, in the quantities and at the temperatures required by the user at the least
overall cost, taking account of installation, maintenance and energy costs.
(2) In electric water heating the common practice for domestic purposes is to use storage
heaters in which water is steadily heated up to a predetermined temperature and stored
until required for use.
(3) In modern hotels and apartment blocks and service apartments, centralized storage and
distribution systems are adopted, where other energy sources such as oil, gas, heat pumps,
solar panels, etc, may be used for the generation of hot water as these options prove more
economical and convenient in heating large volumes of water for storage.
(4) When water supplied to the buildings contain dissolved salts resulting in hardness of
water, measures such as installation of water softening plants etc shall be taken to avoid
formation of scales in the hot water installations.
© ESA 71
CES 161
(1) The design of hot water supply system and its appliances shall be based on the
temperatures at which water is normally required for the various uses.
(2) In order to minimize the danger of scalding, precipitation of scale from hard water,
standing heat losses, risk of steam formation and the possibility of damage to porcelain or
other fittings and to surface finishes, a storage temperature of 60 C shall be maintained. If
soft water is used a temperature up to 65 C may be adopted.
(3) The size of the storage vessel shall be governed by the maximum short time demand of
the domestic premises depending on local conditions. The capacity of the storage vessel
shall not be less than 20 percent in excess of the required maximum short time demand.
For domestic uses the minimum capacity is recommended to be:
(c) Storage heaters of 10 liter to 30 liter 60°C may be used to supply one or two
points of draw offs depending on the use of hot water.
(d) In larger houses where a single hot water heater is intended to supply hot water
to more than one bathroom or kitchen or both, the maximum short time demand
shall be estimated and the capacity decided accordingly.
(4) Values of volume of hot water required for a bath, when cold water is mixed with it
depends on the supplied hot water temperature and are given in Table 4.12.
Table 4-12 Volume of hot water required for mixing with cold water for bathing
Storage temperature, °C 75 70 65 60 55 50
Percentage of hot water
51 55 60 66 73 82.5
required
Quantity of hot water in liter
59 63 69 76 84 95
required for a 115 liter bath
Note: Hot bath temperature at 41°C and cold water at about 5 to 5.5 °C
(5) For on-domestic uses, hot water consumption values shall be taken from good
engineering practices in agreement with the building official.
(6) The hot water storage vessel shall be fitted with a thermostat, safety valves and drain
valves.
72 © ESA
CES 161
4.9.4 Materials, location and Installation of hot water storage tanks (Vessel)
(1) Materials
(a) Under no circumstances shall un galvanized (black) mild steel pipes and fittings
be used in any part of a hot water installation, including the cold feed pipe and
the vent pipe.
(b) Materials resistant to the chemical action of water supplied shall be used in
construction of vessels and pipes.
(c) Each installation shall be restricted to one type of metal only, such as all copper
or all galvanized mild steel.
(d) When water supplied is known to have appreciable salt content, galvanized iron
vessels and pipes shall not be used.
(e) Where required it is also advisable to use vessels lined internally with glass,
stainless steel, etc.
(2) The suitability of galvanized mild steel for storage tanks depends upon the pH value of
the water and the extent of its temporary hardness. For values of pH 7.2 or less,
galvanized mild steel shall not be used. For values of pH 7.3 and above, galvanized mild
steel may be used provided the corresponding temporary hardness is not lower than those
given in Table 4.14.
Table 4-14 pH and required minimum temporary hardness to use galvanized mild
steel for hot water storage
7.3 210
7.4 150
7.5 140
7.6 110
7.7 90
7.8 80
7.9-8.5 70
© ESA 73
CES 161
(a) The storage vessel shall be so placed that the pipe runs to the most frequently
used outlets are as short as possible in order to minimize heat loss through
pipes.
(a) The hot water storage vessel and pipes shall be adequately insulated wherever
necessary to minimize heat loss.
(b) The whole external surface of the storage vessel including the cover to the hand
hole, shall be provided with a covering equivalent to not less than 75mm
thickness of thermal insulating material having a conductivity of not more than
0.05 W/(m²,°C)/mm at mean temperature of 50°C.
4.9.5.1 General
(1) The choice of the hot-water heating system (between instantaneous and hot-water
storage system) shall be made bearing in mind the objectives expressed in Clause 4.9.1
and the characteristics of the different systems. Furthermore, the system shall be sized to
meet the requirements of the user as closely as possible.
(1) In the instantaneous system, the water is heated as used, there is no storage, and the
capacity of the heater shall be equal to the peak demand.
(2) Gas-fired instantaneous water heaters installed in bath rooms shall be of the room-
sealed type.
(1) In the storage system, hot water is heated continuously or intermittently as desired.
(2) The choice between the vented and the non-vented type of installation of the storage
system shall be in accordance with the factors described below;
(a) Vented hot-water storage systems are fed with cold water from a storage cistern
which is situated above the highest outlet to provide the necessary pressure in
the system and which accommodates expansion of the water when it is heated.
An open vent pipe shall be installed from the top of the hot water storage vessel
to a point above the cold water storage cistern, into which it is arranged to
discharge. The main characteristics of vented systems are:
(i) Explosion protection is provided by the open vent pipe and the cistern,
involving no mechanical device;
(ii) The storage provides a constant low pressure and needs to be protected
against the ingress of contaminants.
74 © ESA
CES 161
(b) Non-vented systems can be fed from a storage cistern, either directly or through
a booster pump or fed from the municipal supply pipe, either directly or via a
pressure reducing valve. The main characteristics of non-vented systems are as
follows;
(ii) They allow quicker installation than vented system but involve more costly
components.
(1) Connection to hot water storage vessels shall be arranged so that the cold water feed
pipe is connected near to bottom of the vessel.
(2) The cold feed pipe shall be sized in accordance with Clause 4.8.3
(1) In systems incorporating a hot water storage vessel, the hot water draw-off shall be
arranged to be from the top of the vessel, or as near as there to as practicable.
(2) The hot water distribution pipe shall be sized in accordance with Clause 4.8.3
(3) To promote maximum economy of energy and water, the hot water distribution system
shall be designed so that the hot water appears quickly at draw-off-taps when they are
opened.
(4) (a) The length of pipe measured from the tap to the water heater or hot water
storage vessel shall be as short as possible and should not exceed the values
given in Table 4.15
(b) Where the length shown in Table 4.15 is exceeded, the pipe should be insulated.
(1) When draw-off points are situated at a distance from the hot water storage vessel or
water heater, consideration should be given to the use of separate water heater close to
those draw- off points.
© ESA 75
CES 161
(2) When the provision in (1) above is impracticable, re-circulation with flow and return
pipes to the storage vessel should be considered and the circuit should be well insulated to
reduce the heat losses from pipe runs.
(1) The energy supply to each heater shall be under effective thermostatic control to
prevent the temperature of the stored water from rising above the normal expected hot
water temperature.
(2) The energy supply to each heater shall be fitted with a temperature operated, manually
reset energy cut-out independent thermostatic control, which shall operate if the thermostat
fails and the storage vessel over heats.
(3) Adequate means of dissipating the heat input shall be made in case both the
temperature thermostat and the energy cut-out fail. This can be accomplished with either of
the following.
(a) A vent pipe capable of carrying away the maximum energy output from the heater
at the normal working pressures of the system.
(b) A temperature relief valve located within the top 20% of the water in the vessel
and preferably within 150.0 mm of the top of the vessel. The temperature relief
valve opens at a preset temperature to permit the over-heated water to escape
safely from the hot water storage heater before it boils. Valves shall not be fitted
between the temperature relief value and the heater. The water discharged from
the temperature relief valve must be removed from the point of discharge to a
safe place.
(1) (a) Whether hot or cold water is involved, it shall be ensured that no part of the
system bursts due to the hydraulic pressure to which it is subjected.
(b) The pressure in the system shall never exceed the safe working pressure of the
component parts.
(c) Where necessary, the supply pressure shall be controlled by break cisterns or by
pressure-reducing valves.
(2) (a) Where non-vented storage-type water heaters are used, an expansion relief
valve shall be fitted in the cold feed to the heater and no valves (other than a
draining tap) shall be fitted between the expansion relief valve and the heater or
hot water storage vessel. The expansion or pressure relief valve setting shall be
the maximum working pressure plus 0.5kg/cm2 to 1.5kg/cm2.
76 © ESA
CES 161
(b) Any water discharged from an expansion valve shall be discharged safely in a
similar manner to that of temperature-relief valve.
(c) In addition, provision can also be made to accommodate expansion water by one
of the following alternative methods:
(i) Allow the expansion water to travel back along the cold feed pipe,
provided that heated water cannot reach any branch cold feed outlet.
(ii) Where reverse flow along the cold feed is prevented, e.g. by check valve
or pressure reducing valve, an expansion vessel shall be provided to
accommodate expansion water. This vessel shall be sized in accordance
with the volume of water heated and the water temperature rise so as to
limit the pressure to the maximum working pressure of the system. The
expansion vessel shall accommodate an expansion equal to 4% of the
total volume of heated water.
(1) The water service pipe from street mains to a building shall be of sufficient size to
furnish an adequate flow of water to meet the requirements of the building and should
preferably be not less than 20.0 mm nominal diameter.
(1) Minimum, fairly constant residual pressure at the point of outlet discharge shall not be
less than 0.50 kg/cm2 for all appliances except for flush valves and special equipment
(which may require higher pressures) valves in accordance with manufacturer’s
requirements can be taken.
(1) Where water pressures are excessive, air chambers or other approved mechanical
devices shall be provided to reduce water hammer or line noises to such an extent that no
pressure hazard to the piping system will exist.
4.13.1 General
(1) All joints shall be gas-tight and water-tight, and no paint, varnish, or putty shall be
permitted on the joint until after the joint has been tested and approved.
(2) All joints shall be made in accordance with the manufacturer’s instructions.
(3) Care shall be taken to establish satisfactory jointing techniques for all water services
pipe work.
(4) All piping and fittings shall be cleaned internally and be made free from particles of
sand, soil, metal fillings and chips.
© ESA 77
CES 161
(1) Pipes, fittings, and components shall be handled carefully to reduce damage.
(2) Manufacturers’ advice should be followed concerning how their products should be
loaded, transported, unloaded and stored.
(1) In installation that do not have limited straight runs and many bends and offsets,
allowance for expansion and construction of the pipes shall be made by forming expansion
loops, by introducing changes of direction avoid long straight runs or by fitting proprietary
expansion joints. This is particularly important where temperature changes are considerable
(e.g. hot water distribution pip work) and where the pipe material has a relatively large
coefficient of thermal expansion (e.g. un-plasticized PVC).
(2) In installation with limited straight runs and many bends and offsets, thermal movement
is accommodating automatically.
4.13.4.1 General
(1) A designer of a water supply system should consider the advantage and disadvantages
of arranging the pipe work so that it is freely accessible for repair and maintenance.
(2) The main factors that should be considered deciding the degree of accessibility to be
provided are the following:
(b) The increase or decrease in capital or maintenance costs arising from the
provision of improved accessibility, ease of forming ducts or chases, changes of
pipe runs, ease of provision removable access panels or covers, availability of
multi-service walkways or crawl ways in which water pipes may be installed.
(c) The pipe work materials and jointing methods, reliability of joints, resistance to
both internal and external corrosion, flexibility of pipe when inserted in curved
ducts or sleeves.
(2) Where a sleeve is used for this purpose, it shall be capable of resisting external loading
and shall be sealed at each end with material of permanently flexible form to allow
movement of the pipe.
78 © ESA
CES 161
(3) The diameter of the sleeve and the radius of any bends there in shall be such as to
permit the ready insertion and withdrawal of the pipe.
(4) No sleeve intended for carrying a water pipe shall contain within it any other pipe or
cable.
(1) No pipe or pipe joint in or under a building shall be embedded in any wall or solid floor or
in any material below a solid floor at ground level except for the following (unless equivalent
method of installation satisfactory to the building official is made for the accessibility of
pipes during inspection and maintenance);
(a) The embedding of any pipe and associated pipe joints in a properly formed
chases in a wall or solid floor that is subsequently plastered or screened if the
pipes or pope joints can be exposed for repair or replacement by cutting or
chipping away the surface layers of the plaster or screed.
(b) The enclosing of any pipe and associated pipe joints in a purpose-made duct or
chase in a solid floor in such a way that the pipe and pipe joints can be exposed
for purpose of examination, repair or replacement without endangering the
structural integrity of the building.
(c) The enclosing of any pipe and associated pipe joints in a purpose-made chase in
a solid wall in such a way that the pipe and pipe joints can either be capped off
and isolated or be exposed for purposes of examination, repair or replacement
without endangering the structural integrity of the building.
(1) Pipes and pipe joints installed in ceilings shall be assessable for purposes of
examination, repair or replacement and supported adequately as specified in Clause 3.10.
(1) Valve chambers shall be provided to give access for operation and maintenance of
underground valves which may be made of brick or concrete.
(2) Alternatively, vertical guard pipes or precast concrete encasement can be provided to
enclose valves.
(3) Brick or concrete chamber shall be constructed of sufficient dimensions to permit repairs
to be carried out to the fittings.
(1) Every valve shall be sp placed that it is readily accessible for operation and
maintenance.
© ESA 79
CES 161
4.13.4.7 Cisterns
(1) Every storage cistern shall be so placed and equipped that the interior there of can be
inspected and cleaned and the float-operated valve can be maintained.
4.13.5.1 General
(b) Securely attached to the building structure, and not to any other service;
(e) Of like material or lined with a non-abrasive, inert material for that section where
contact with the pipe work many occur; and
(3) The method of supporting of spacing of pipes by means of brazing or welding a short
section of any material to the surface of each pipe shall not be permitted.
(1) The spicing for fixings of internally located piping shall be in accordance with
Table4.16.
(1) Iron pipes shall be secured by heavy weight holder-bats of iron or low carbon steel
either built in or bolted to the structure.
(1) Copper and stainless steel piping shall be secured by copper, copper-alloy, plastics
clips or brackets.
(1) Steel piping shall be secured by steel, copper alloy, suitable plastics clips or brackets.
Copper clips or brackets shall not be used for fixing steel piping.
(1) Plastics piping shall be secured by suitable metal, plastic lips or brackets. Allowance
shall be made for free lateral movement within the clips and brackets.
80 © ESA
CES 161
(1) Piping that is insulated shall be secured on clips or brackets that allow sufficient space
behind the back of the pipe and the batten or wall to which the pipe is fixed for the
insulation to be properly installed.
(1) Piping shall be housed in properly constructed builder work ducts or wall chases with
adequate supports and have access for maintenance and inspection in accordance with
Clause 4.13.4.
(1) Piping laid through notched, holes or chases shall not be subjected to external pressure
and shall be free to expand or contract. Piping though walls and floors shall be sleeved.
© ESA 81
CES 161
Un-plasticized PVC,
Steel pipes Copper pipes
and polyethylene pipes
Nominal
pipe size Horizontal Horizontal
Vertical Horizontal or Vertical Vertical
or graded or graded
pipes graded pipes pipes pipes
pipes pipes
Note: Due to water pressure effects, additional brackets, clips or hangers may be required to prevent
movements.
(1) Electrical cables and gas pipes shall not be installed within 100.0mm of any water
service.
(1) The bottom of trenches shall be carefully prepared to a firm surface so that the barrels
of the pipes, when laid, are well bedded for their whole length.
(2) Mud, rock projections, boulders, hard sport and local soft spots shall be removed and
replace with selected material consolidated to the required level.
(3) Pipes laid in the ground shall be provided with a minimum cover given in Table 4.17.
82 © ESA
CES 161
(1) In the refilling of trenches, the pipes shall be surrounded with not less than 75.0 mm of
compacted sand, or fine grained soil, with no hard-edged object permitted to come in
contact with or rest against any pipe or fitting (see Figure 4.16).
(2) Any back fill within 300.0 mm of the top of the pipe shall be free from builder’s waste
bricks, concrete pipes, rocks or similar material which would be retain on a 75.0 mm sieve.
Note: For pipes to be buried in heavy truck areas, special consideration shall be taken to protect them from
damage.
(1) Electrical cables and gas pipes shall not be installed within 600.0mm of either side of a
below ground water service. Wherever this separation cannot be achieved, the distance
from any electrical cable or gas pipe may be reduced to 300.0mm provided that, within the
exclusion zone, such electrical cable or gas pipe is suitably marked with bricks, stone
masonry or equivalent durable material painted red.
(2) Any below-ground cross-over of water service, within the exclusion zone, shall:
(c) be suitably marked with bricks, stone masonry or equivalent durable material,
painted red.
(3) Water service pipes shall not be laid in a trench excavated for a foul drain. Wherever it
is not practical to do otherwise, water pipes may be laid in the same trench as a sanitary
drain (see Figure 4.17) provided the following conditions are observed:
(a) The water service shall be located on a shelf or ledge, excavated at one side of
the trench not less than 50.0mm from the continuation of the trench, or on
compacted bedding.
(b) The underside of the water pipe is at least 100.0mm above the top of foul drain.
(c) The number of joints in the water service pipe shall be kept at a minimum
© ESA 83
CES 161
Figure 4-17 Laying of water supply pipe work in same trench as foul drains
4.14.4 Ingress of dirt
(1) Pipes shall be kept clean and, immediately before laying each pipe and fitting, shall be
thoroughly cleaned internally and the open end temporarily capped until jointing takes
place. Particular care shall be taken to keep the joints clean. After laying and jointing, the
leading end shall remain capped.
84 © ESA
CES 161
4.14.5 Corrosion
(1) Pipes passing through corrosive materials shall be provided with approved coatings,
sheathings or wrappings or other means of protection against damage from external
corrosion.
(2) Where ferrous and non-ferrous pipes or fittings are jointed together, protection against
galvanic corrosion shall be provided by:
(a) fitting a plastic connector or a short length of plastic pipe between the dissimilar
metals, for threaded type joints, or
(b) fitting an insulated gasket between flanges, insulating sleeves along the bolts,
and insulating washers under the bolt head and nut, for flange type joints.
(2) Thrust blocks shall be constructed of concrete with one side bearing against a firm
vertical face of the excavation and designed to resist the thrust produced by the test
pressure to be transmitted to the surrounding soil without the maximum bearing pressures
of the soil and the pipe work material being exceeded.
© ESA 85
CES 161
(1) Consideration shall be given to the need to locate the position of pipes and valves.
(2) Valve chambers shall be letter-coded to indicate what service is below them where
possible, durable marks should be set up to indicate the pipe service, the size, the position
and depth below the surface.
(3) In any building other than a single dwelling, every domestic and fire fighting water
supply pipes shall be clearly and indelibly marked to distinguish them from each other and
from every other pipe in the building.
(4) All pipes conveying non-potable water shall be adequately and durably identified by a
distinctive coloring paint so that they will be readily distinguished from pipes carrying
potable water.
(1) During the installation of a water supply system, records of all pipe runs, cisterns,
valves, outlets, etc. shall be kept.
86 © ESA
CES 161
(2) On completion of the work, drawings shall be prepared on durable material of the “as
fixed” installation. These record drawings shall be handed to the “building owner”.
4.16.1 General
(1) The procedures detailed in this section shall be used to ensure that:
(a) Materials and equipment installed comply with approved standards (see Clause
4.2)
(b) The work is done entirely within the specification for the job.
(c) The pipes and fittings shall be inspected on site before laying and shall be
sounded to disclose cracks. Any defective items shall be clearly marked as
rejected and forthwith removed from the site.
4.16.2 Procedure
4.16.2.1 General
(1) Inspection and tests shall be undertaken as the work proceeds. Records of all tests
required by the specification shall be kept by the installer.
4.16.2.2 Timing
(a) Interim tests – as soon as practicable after completion of the particular section,
with particular attention to all work which will be concealed.
(b) Final tests – to be carried out on completion of the work on the water services
and prior to handing over.
(2) Satisfactory completion of an interim test shall not constitute a final test.
4.16.2.3 Retests
(1) Items failing any tests shall be corrected immediately and re-tested before further work
proceeds.
4.16.3 Inspection
(1) Visual inspections shall be carried out at both interim and final testing in order to detect
faults in construction or material not shown up under test but which could lead to failure at a
later date, possibly after expiry of the contractual maintenance period.
(2) Internal pipe work: All internal pipe work shall be inspected to ensure that they are
properly supported and secured, that they are clean and free from swarf and that cisterns
are provided with correctly-fitting covers before testing takes place.
© ESA 87
CES 161
(a) Trenches shall be inspected to ensure that excavation is to the correct depth to
guard mechanical damage due to traffic or other activities.
(b) In visual inspection of pipe lines laid in open trenches, particular attention shall be
paid to the pipe bed, the line and the level of the pipe, irregularities at joints, the
correct fitting of valves, the correct installation of thrust blocks where required,
and ensure that protective coatings are undamaged.
4.16.4.1 General
After satisfactory visual inspection has been completed, hydraulic pressure testing shall be
carried out on the installation. Compressed air may be used as well for the pressure test.
(1) When the installations is complete, it shall be slowly filled with water, with the highest
draw-off point open to allow air to be expelled from the system.
(2) It is desirable that the installation then be tested hydraulically in the following way:
Subject the pipes; pipe fittings and connected appliances to a test pressure of 10.0kg/cm2
or at least two times the maximum working pressure, which ever is greater, with the
pressure applied and maintained for at least 1.0 hr. The installation, including all cisterns,
water heaters, etc shall then be inspected for leaks.
(3) Each draw-off tap, shower fitting and float-operated valve shall be checked for rate of
flow against the specified requirements. Defects revealed by any of the foregoing tests shall
be remedied and the tests repeated until a satisfactory result is obtained.
(1) After laying, jointing and anchoring, the pipeline shall be slowly and carefully filled with
water so that all air is expelled and then tested under pressure.
(2) Interim tests shall be applied to every pipeline. For buried pipelines, these shall be
carried out before backfilling is placed over the joints. Long pipelines shall be tested as the
work proceeds.
(3) Final tests shall be carried out only when all relevant work is complete. Completion for
buried pipeline includes backfilling, compaction and surface finish.
(4) Generally, the tests should be conducted before the hand-over. Where long lengths of
buried pipelines are laid clear of the general construction area, it may be practicable to
carry out final tests for complete sections as work proceeds.
(5) (a) The test pressure shall be at least twice the maximum working pressure or 10.0
kg/cm2, whichever is greater.
(b) Pressure gauges shall be checked and re-calibrated, where necessary, before
the test.
88 © ESA
CES 161
(c) To avoid the risk of contamination, water used for testing shall be obtained from
potable supply.
(1) All water storage tanks for portable water shall be cleaned and disinfected:
(b) Whenever the storage tank is taken out for inspection, repairs, painting or other
activity that might lead to contamination of water.
(2) (a) The tank shall be drained and all debris and sludge removed.
(b) The surfaces of walls, floor and operating facilities shall be thoroughly cleaned
using a high pressure water jet, sweeping, scrubbing or other similar effective
means.
(c) All water, dirt, and other material accumulated in this cleaning process shall be
flushed or otherwise removed from the tank.
(3) (a) After cleaning, the tank shall be disinfected by filling it to overflow level with
potable water to which enough chlorine is added to provide a free chlorine
residual, in the tank of not less than 10.0mg/l, at the end of retention time.
(b) The retention time shall not be less than 6.0 hr and the tank shall be drained
after disinfection and flushed out with potable water prior to being put back into
service.
(1) Water services used to supply potable water shall be protected against contamination
during storage, construction and repairs that might lead to contamination of water.
(2) On completion of the installation or repairs, water services shall be flushed at each
discharge point to remove any dirty water or debris from the service.
(3) After flushing, water services shall be chlorinated before being placed in service. Water
services shall be disinfected, so that, after retention period of 6.0 hrs, a free chorine
residual of not less than 10.0 mg/l is obtained throughout the service. After the applicable
retention period, the service shall be flushed until chorine measurements show that the
concentration in the water leaving the service is not higher than that generally prevailing in
the suppliers distribution system or is acceptable for domestic use.
© ESA 89
CES 161
4.18 Maintenance
4.18.1 General
(2) The installation shall be inspected at periods by the person responsible for
maintenance. Faults noticed on inspection shall be attended to without delay.
Any loose or missing fixings or supports shall be made good. Provision for expansion and
contraction shall be checked, particularly in the case of plastics pipe work.
4.18.2.2 Joints
Leaking joints shall be tightened or re-made or, where necessary, the pipe work shall be
renewed, to stop all leakage.
4.18.2.3 Compatibility
When carrying out renewals, the existing pipe work shall be indentified and appropriate
adaptor shall be used as necessary.
(1) When any sign of leakage from a float-operated valve (e.g. dripping from any over-flow
pipe) or tap is noticed, the fitting shall be re-washered, re-seated or replaced as necessary
to stop leakage.
(2) The action of self- closing taps shall be checked at regular intervals and any necessary
repairs or adjustments carried out.
(1) Isolating valves (stop valves and service valves) shall be operated at least once a year
to ensure free movement of working parts.
(1) Relief valves shall be operated at least once a year to check that the valve has not stuck
or become blocked.
90 © ESA
CES 161
(1) An indication of malfunction of pressure control valve shall be attended to without delay.
(2) When a pressure gauge is fitted downstream of a pressure control valve, its reading
should be checked from time to time and any changes investigated.
4.18.4 Cisterns
(1) (a) Cisterns shall be inspected from time to time to ensure that overflow pipes are
clean, that covers are adequate and securely fixed, and there are no signs of
leakage or deterioration likely to result in leakage.
(b) Cisterns storing more than 1000.0 liter drinking water shall be inspected at least
once every 6 months.
(c) Cisterns storing less than 1000.0 liter drinking water shall ne inspected at least
once a year.
(2) (a) Overflow pipes shall be examined and kept free from obstructions.
(b) Ends of overflow pipes shall be protected from entry of insects and vermin.
4.18.5 Ducts
(1) Ducts shall be kept accessible, clear of extraneous material and free from vermin.
(2) All access points should be checked to ensure that they have not been obstructed
(1) Any vessel storing water under pressure (e.g non-vented storage water heaters) shall
be inspected for indications of deterioration no less frequently than at the intervals
recommended by the manufacturer.
(1) If any part of an installation becomes redundant and, in particular, if any appliance or
fitting is disconnected, other than for the purpose of repair, maintenance or renewal, then
the whole of the pipe work supplying water to the disconnected or unused appliance or
fitting shall also be disconnected.
4.18.8 Pumps
A responsible person should be appointed to oversee the proper execution of the scheme
and the user should arrange for regular inspection and maintenance of the pump and
equipment.
© ESA 91
CES 161
5.1.1 Scope
(a) For the design, installation, testing and maintenance of Internal Drainage System
for residential and non- residential buildings.
(b) The term Internal Drainage System includes all Soil and Waste-Water drainage
pipe work within or on the buildings including any basement(s).
(c) This Section also sets out requirements regarding pipe materials and their
jointing.
Plumbing system shall be designed, installed and adjusted to use the optimum quantity of
water consistent with proper performance.
It is recommended that each family dwelling unit should have at least one water closet, one
lavatory, one kitchen wash place or a sink, and one bathing wash place or shower to meet
the basic requirements of sanitation and personal hygiene.
The drainage system shall be designed, installed and maintained to guard against fouling,
deposit of solids and clogging and with adequate cleanouts so arranged that the pipes may
be readily cleaned.
The plumbing system shall have durable material, free from defective workmanship and so
designed and installed as to give satisfactory service for its reasonable expected life.
Each fixture directly connected to the drainage system shall be equipped with a liquid seal
trap, Trap seals shall be maintained to prevent sewer gas, other potentially dangerous or
noxious fumes, or vermin from entering the building. Further, the drainage system shall be
designed to provide an adequate circulation of air in all pipes with no danger of siphonage,
aspiration, or forcing of trap seals under conditions of ordinary use by providing vent pipes
throughout the system.
Each vent terminal shall extend to the outer air and be so installed as to minimize the
possibilities of clogging and the return of foul air to the building, as it conveys potentially
92 © ESA
CES 161
noxious or explosive gases to the outside atmosphere. All vent pipes shall be provided with
a cowl.
No substance that will clog or accentuate clogging of pipes, produce explosive mixtures,
destroy the pipes or their joints, or interfere unduly with the sewage-disposal process shall
be allowed to enter the drainage system.
Wherever water closet or similar fixture shall be located in a room or compartment, it should
be properly lighted and ventilated.
5.1.2.9 Maintenance
5.1.2.10 Accessibility
All plumbing fixtures shall be so installed with regard to spacing as to be accessible for their
intended use and for cleaning. All doors, windows and any other device needing access
within the toilet shall be so located that they have proper access.
Special toilet fixtures shall be provided for the disabled with required fixtures and devices.
Plumbing system shall be installed with due regard to preservation of the structural
members and prevention of damage to walls and other surfaces.
5.1.2.13 Signage
Required public facilities shall be designated by a legible sign for each sex. Signs shall be
readily visible and located near the entrance to each toilet facility.
5.2.1.1 Water-closet
It shall essentially consist of a closet consisting of a bowl to receive excretory matter, trap
and a flushing apparatus. It is recommended to provide ablution tap adjacent to the water-
closet, preferably on right hand sidewall. The various types/style of water-closets may be:
© ESA 93
CES 161
5.2.1.2 Bidet
It is provided with hot and cold water connection. The bidet outlet should essentially
connect to soil pipe in a two-pipe system.
5.2.1.3 Urinal
It is a soil appliance and is connected to soil pipe after a suitable trap. Urinal should have
adequate provision of flushing apparatus. The various types/style of urinal may be:
Slop sink is a large sink of square shape. The appliance is used in hospitals installed in the
nurse’s station, operation theatres and similar locations for disposal of excreta and other
foul waste for washing bed pans and urine bottles/pans. It is provided with a flushing
mechanism.
5.2.2.1 Washbasin
It is of one piece construction having a combined overflow and preferably should have soap
holding recess or recesses that should properly drain into the bowl. Each basin shall have
circular waste hole through which the liquid content of the basin shall drain.
5.2.2.2 Wash-trough
5.2.2.3 Sink
It is used in kitchen and laboratory for the purpose of cleaning utensils/apparatus and also
serve the purpose of providing water for general usage. The sink may be made with or
without overflow arrangement. The sink shall be of one piece construction including
combined over flow, where provided. The sink shall have a circular waste hole into which
the interiors of the sink shall drain.
Bath tub may be of enameled steel, cast iron, gelcoated, glass fiber reinforced plastic or
may be cast-in-situ. It shall be stable, comfortable, easy to get in and out, water tight, with
94 © ESA
CES 161
anti-skid base, and easy to install and maintain. The bath tub shall be fitted with overflow
and waste pipe of nominal diameter of not less than 32 mm and 40 mm respectively.
It is a bowl fitted with a push button tap and a water bubbler or a tap with a swan neck
outlet fitting. It has a waste fitting, a trap and is connected to the waste pipe.
5.2.2.6.1 Approval
Domestic automatic clothes washers shall satisfy Ethiopian Standards.
The requirements of various soil appliances and waste appliances shall be in accordance
with accepted standards.
5.3.1 General
(1) There should be at least one water tap and arrangement for drainage in the vicinity of
each water-closet or group of water-closet in all the buildings.
(2) Each family dwelling unit on premises shall have, at least, one water-closet and one
kitchen type sink. A bath or shower shall also be installed to meet the basic requirements of
sanitation and personal hygiene.
(3) All other structures for human occupancy or use on premises shall have adequate
sanitary facilities, but in no case less than one water-closet and one other fixture for
cleaning purposes.
(1) Dwelling with individual convenience shall have at least the following fixtures:
(b) One water-closet with flushing apparatus with an ablution tap; and
© ESA 95
CES 161
(c) One tap with a floor trap or a sink in kitchen or wash place.
(2) Dwellings without individual conveniences shall have the following fixtures:
(b) One water-closet with flushing apparatus and one ablution tap bath for every two
tenements, and
(c) One bath with water tap and floor trap for every two tenements.
The requirements for fixtures for drainage and sanitation in the case of buildings other than
residences shall be in accordance with Table 5.1 to Table 5.14. The following shall be, in
addition, taken into consideration:
(1) The figures shown are based upon one (1) fixture being the minimum required for the
number of persons indicated or part thereof.
(3) Where there is the danger of exposure to skin contamination with poisonous, infectious
or irritating material, washbasin with eye wash jet and an emergency shower located in an
area accessible at all times with the passage/ right of way suitable for access to a wheel
chair, shall be provided.
(4) When applying the provision of these tables for providing the number of fixtures,
consideration shall be given to the accessibility of the fixtures.
(5) All building used for human habitation for dwelling, work, occupation, medical care or
any purpose detailed in the various tables shall be provided with minimum sanitary
facilities as per the schedule in the tables.
(6) In all types of buildings, individual toilets and pantry should be provided for executives,
and for meeting/seminar/conference rooms, etc as per the user requirement.
(7) Where food is consumed indoors, water stations may be provided in place of drinking
water fountains
96 © ESA
CES 161
© ESA 97
CES 161
i) Water – Closets (Workers & Staff) 1 for up to 25 1 for up to15 1 for up to15 1 for up to15
2 for 16 -35 2 for 16 -25 2 for 16 -25 2 for 13 -25
3 for 36 -65 3 for 26 -40 3 for 26 -40 3 for 26 -40
4 for 66 -100 4 for 41 -57 4 for 41 -57 4 for 41 -57
5 for 58 -77 5 for 58 -77
6 for 78 -100 6 for 78 -100
2.5%
iv) Washbasins 1 per 25 or part thereof 1 per 25 or part thereof 1 per 25 or part 1 per 25 or
thereof part thereof
v) Drinking water fountain 1 per every 100 or part thereof with minimum 1 per every 100 or part thereof with
one on each floor minimum one each floor
vi) Cleaner’s sink 1 on each floor 1 on each floor 1 on each floor 1 on each
floor
vii) Showers/bathing rooms
As per trade requirements
viii) Emergency shower and eye wash – – 1 per every shop floor per 500
fountain persons
Note: For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being
extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if
required by applicable Industrial and Safety laws and the Factories Act must be provided in consultations
with the user.
98 © ESA
CES 161
Table 5-3 Cinema, multiplex cinema, concerts and convention halls, theaters
SI Fixtur
Public Staff
No. es
i) Water -Closets 1 per 100 up to 400 3 per 100 up to 200 1 for up to 15 1 for up to 12
Over 400 add at 1 per Over 200 add at 2 per
250 or part thereof 100 or part thereof
ii)
1 in each water-closet 1 in each water-closet 1 in each water-closet 1 in each
iii) Ablution tap water-closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity
of water-closets and urinals
– –
Notes:
1. Some WC’s may be European style if desired.
2. Male population may be assumed as two third and female population as one-third
© ESA 99
CES 161
i) Water -Closets 1 per 200 up to 400 1 per 100 up to 200 1 for up to 15 1 for up to 12
Over 400 add at 1 per Over 200 add at 2 per 2 for 16 – 35 2 for 13 -25
250 or part thereof 150 or part thereof
ii) Ablution tap 1 in each water-closet 1 in each water-closet 1 in each water-closet 1 in each water-
closet
iii) Urinals I water tap with draining arrangements shall be provided for every 50 persons or part hereof in
the vicinity of water –closets and urinals
1 per 50 – Nil up to 6 –
iv) Washbasins 1 for 7-20
2 for 21-45
1 for every 200 or part 1 for every 200 or part 1 for up to 15 1 for up to 12
thereof. For over 400, thereof. For over 400, 2 for 16 -35 2 for 13 -25
add at 1 per 250 persons add at 1 per 250 persons
or part thereof or part thereof
v) Drinking water fountain 1 per 100 persons or part thereof
Notes:
1. Some WCs may be European style if desired.
2. Male population may be assumed as two third and female population as one-third
100 © ESA
CES 161
i) Toilet suite Private room with up to 4 patients For individual doctor’s/officer’s rooms
comprising one WC
and one washbasin
and shower stall
iii) Ablution tap One in each water- One in each water- One in each water-closet One in each
closet closet water-closet
1 Water tap with draining arrangements shall be provided for every 50 persons or part thereof in the
vicinity of water –closet and urinals
iv) Urinals 1 per 30 beds – Nil up to 6 –
1 for 7 to 20
2 for 21 -45
v) Washbasins 2 for every 30 beds or part thereof Add 1 per 1 for up to 15 1 for up to 2
additional 30 beds or part thereof 2 for 16 – 35 2 for 13 – 25
vi) Drinking water 1 per ward 1 per 100 persons or part
fountain thereof
vii) Cleaner’s sink 1 per ward -
viii) Bed pan sink 1 per ward -
ix) Kitchen sink 1 per ward -
Notes:
1. Some WC’s may be European style if desired.
2. Male population may be assumed as two-third and female population as one-third.
3. Provisions for additional and special hospital fittings where required shall be made.
© ESA 101
CES 161
iii) Ablution tap One in each water- One in each water-closets One in each water-closet One in each
closet water-closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the
vicinity of water –closets and urinals
iv) Urinals 1 per 50 persons or – Nil up to 6 –
part thereof 1 for 7 to 20
2 for 21 -45
v) Washbasins 1 per 100 persons or 2 per 100 persons or part 1 for up to 15 1 for up to 12
part thereof thereof 2 for 16 -35 2 for 13 -25
vi) Drinking water fountain 1 per 500 persons or part thereof 1 per 100 persons or part thereof
Notes:
1. Some WC’s may be European style if desired.
2. Male population may be assumed as two-third and female population as one-third.
3. Provisions for additional and special hospital fittings where required shall be made.
102 © ESA
CES 161
SI
No. Fixtures Staff toilets
Male Female
(1) (2)
(3) (4)
i) Toilet Suite comprising one WC and for individual doctor’s/Officer’s rooms
one washbasin (with optional shower
stall if building used for 24 hr)
ii) Water-closets 1 per25 persons or part thereof 1 per15 persons or part
thereof
© ESA 103
CES 161
SI
No Fixtures Patient Toilets Staff toilets
i) Water-closets 1 per 4 persons or part 1 per 4 persons or part 1 per 4 persons or part 1 per 4 persons
thereof thereof thereof or part thereof
2 for 16 -35 2 for 13 -25
ii) Ablution tap One in each water- One in each water- One in each water- One in each
closets closets closets water-closets
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the
vicinity of water –closets and urinals
iii) Washbasin 1 per 8 persons or part thereof 1 per 8 persons or part thereof
iv) Bath (Showers) 1 per 4 persons or part thereof 1 per 4 to 6 persons or part thereof
v) Drinking water 1 per 100 persons or part thereof minimum 1 per 100 persons or part thereof,
fountain 1 per floor thereof
1 per floor
vi) Cleaner’s sink 1 per floor 1 per floor
Notes:
1. Some WC’s may be European style if desired.
2. For independent housing units fixtures shall be provided as for residences
104 © ESA
CES 161
ii) Water-closets 1 per100 persons up to 2 per 100 persons up to 1 for up to15 1 for up to 12
400 200 2 for 16 -35 2 for 13 -25
Over 400 add at 1 per 250 Over 200 add at 1 per 3 for 36 –65 3 for 26 – 40
or part thereof 100 or part thereof 4 fro 66 -100 4 for 41-57
5 for 58 -77
6 for 78 -100
iii) Ablution tap One in each water-closets One in each water- One in each One in each water-closets
closets water-closets
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in
the vicinity of water –closets and urinals
Notes:
1. Some WC’s may be European style if desired.
2. Male population may be assumed as two-third and female population as one-third.
3. Provisions for additional and special hospital fittings where required shall be made.
© ESA 105
CES 161
ii) Ablution tap One in each water- One in each water-closets One in each water- One in each water-closets
closets closets
1 water tap wit draining arrangements shall be provided for every 50 persons or part thereof in the vicinity
of water-closets and urinals
Notes:
1. Some WC’s may be European style if desired.
2. Male population may be assumed as two-third and female population as one-third.
3. Provisions for additional and special hospital fittings where required shall be made.
106 © ESA
CES 161
ii) Ablution tap One in each water One in each water - One in each water - One in each water - One in each
-closet closet closet closet water -closet
1 water tap wit draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of
water –closets and urinals
iv) Washbasins 1per15 1 per 60 pupils or 1 per 40 pupils or 1 per 8 pupils or part thereof 1 per 6 pupils or
pupils or part thereof part thereof part thereof
part thereof
Notes:
1. Some WC’s may be European style if desired .
2. For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
© ESA 107
CES 161
i) Water-closets 1 per 8or 1 per 6 or 1 for up to 15 1 for up to 12 1 per 100 2 per 100
part thereof part thereof 2 for 16 -34 2 for 13-25 Up to 400 Up to 200
3 for 36 – 65 3 for 26 – 40 Over 400 Over 200
4 for 66 – 100 4 for 41 -57 add at add at
5 for 58-77 1 per 250 1 per 100
6 for 78 -100
ii) Ablution tap One in each One in each One in each water- One in each One in each One in
water- closet water-closet closet water-closet water-closet each
water-
closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the
vicinity of water –closets and urinals
108 © ESA
CES 161
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the
vicinity of water –closets and urinals
Notes:
1. Toilet facilities for individual buildings in a market should be taken some as that for office buildings.
2. Common toilets in the market buildings provide facilities for persons working in shops and their regular
visions.
3. Special toilet facilities for a large floating population of out of town buyers/sellers., labor, drivers of vehicles for
whom special toilet (public toilets)
© ESA 109
CES 161
ii) Ablution tap One in each water- One in each One in each One in each One in each
closet water-closet water-closet water-closet water-closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the
vicinity of water –closets and urinals
vi) Drinking water 2 per 1000 or part thereof 3 per 1000 or part thereof 4 per 1000 or part thereof
fountain or taps (in
common lobby for
male/female)
vii) Cleaner’s sink 1 per toilet 1 per toilet 1 per toilet 1 per toilet 1 per toilet 1 per toilet
compartment with compartment compartmen compartment compartment compartment
WC’s with WC’s t with WC’s with WC’s with WC’s with WC’s
viii) Toilet for 1 per 4000 1 per 4000 1 per 4000 1 per 4000 1 per 4000 1 per 4000
disabled
Notes:
1. Some WC’s may be European style if desired
2. Male population may be assumed as there-fifth and female population as two fifth
3. Separate provision shall be made for staff and workers.
110 © ESA
CES 161
The required water closets, lavatories, and showers or bathtubs shall be distributed equally
between the sexes based on the percentage of each sex anticipated in the occupant load.
The occupant load shall be composed of 50 percent of each sex, unless statistical data
indicate a different distribution of the sexes.
The supply lines and fittings for every plumbing fixture shall be installed so as to prevent
backflow.
Plumbing fixtures shall be installed so as to afford easy access for cleaning both the fixture
and the area around the fixture.
5.3.5.3 Setting
Fixtures shall be set level and in proper alignment with reference to adjacent walls. Water
closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be
set closer than 15 inches (381 mm) from its center to any side wall, partition, vanity or other
obstruction, or closer than 30 inches (762 mm) center-to-center between adjacent fixtures.
There shall be at least a 21-inch (533 mm) clearance in front of the water closet, urinal,
lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less
than 30 inches (762mm) wide and 60 inches (1524 mm) deep. (See Figure 5-1)
© ESA 111
CES 161
Connections between the drain and floor outlet plumbing fixtures shall be made with a floor
flange. The flange shall be attached to the drain and anchored to the structure. Connections
between the drain and wall-hung water closets shall be made with an approved extension
nipple or home adaptor. The water closet shall be bolted to the hanger with corrosion-
resistant bolts or screws. Joints shall be sealed with an approved elastomeric gasket,
flange-to-fixture connection complying with or an approved setting compound.
Floor flanges for water closets or similar fixtures shall not be less than 0.125inch (3.2 mm)
thick for brass, 0.25 inch (6.4 mm) thick for plastic, and 0.25inch (6.4mm) thick and not less
than a 2-inch (51 mm) caulking depth for cast-iron or galvanized malleable iron.
Floor flanges of hard lead shall weigh not less than 1 pound, 9 ounces (0.7 kg) and shall be
composed of lead alloy with not less than 7.75-percent antimony by weight. Closet screws
and bolts shall be of brass. Flanges shall be secured to the building structure with
corrosion-resistant screws or bolts.
Where any fixture is provided with an overflow, the waste shall be designed and installed so
that standing water in the fixture will not rise in the overflow when the stopper is closed, and
no water will remain in the overflow when the fixture is empty.
The overflow from any fixture shall discharge into the drainage system on the inlet or fixture
side of the trap.
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The
minimum slope of a horizontal drainage pipe shall be in accordance with Table5.15.
3 to 6 1/8
8 or larger 1/16
The size of the drainage piping shall not be reduced in size in the direction of the flow. A 4-
inch by 3-inch (102 mm by 76 mm) water closet connection shall not be considered as a
reduction in size.
112 © ESA
CES 161
Horizontal branches shall connect to the bases of stacks at a point located not less than 10
times the diameter of the drainage stack downstream from the stack.
Drainage piping for future fixtures shall terminate with an approved cap or plug.
In the installation or removal of any part of a drainage system, dead ends shall be
prohibited. Cleanout extensions and approved future fixture drainage piping shall not be
considered as dead ends.
All materials, fittings and sanitary appliances shall conform to ‘Building Materials’
requirements or acceptable standards.
(a) under buildings and where pipes are suspended in basements and like situations;
(b) in reaches where the velocity is more than 2.4 m/s; and
Asbestos cement pipes are commonly used for house drainage systems and they shall
conform to accepted standards. Where so desired, the life of asbestos cement pipes may
be increased by lining inside of the pipe with suitable coatings like epoxy/polyester resins
etc.
Unplasticized PVC pipes may be used for drainage purposes; however, where hot water
discharge is anticipated, the wall thickness shall be minimum 3 mm irrespective of the size
and flow load.
© ESA 113
CES 161
All connections and changes in direction of the sanitary drainage system shall be made with
approved drainage fittings. Connections between drainage piping and fixtures shall conform
to 5.3.8.
5.4.4.2 Obstructions
The fittings shall not have ledges, shoulders or reductions capable of retarding or
obstructing flow in the piping. Threaded drainage pipe fittings shall be of the recessed
drainage type.
Fittings shall be installed to guide sewage and waste in the direction of flow. Change in
direction shall be made by fittings installed in accordance with Table 5.16. Change in
direction by combination fittings, side inlets or increasers shall be installed in accordance
with Table 5.16 based on the pattern of flow created by the fitting.
Table 5-16 Fitting for change in direction
Sixteenth bend X X X
Eighth bend X X X
Sixth bend X X X
a
Quarter bend X X Xa
Short Sweep X Xa,b Xa
Long Sweep X X X
Sanitary tee Xc - -
Wye X X X
Combination X X X
wye and
eighth bend
For SI: 1 inch = 25.4 mm.
(a) The fittings shall only be permitted for a 2 –inch or smaller
fixture drain
(b) There inches or larger.
(c) For a limitation double sanitary tees, see section 5.4.4.3
114 © ESA
CES 161
Heel-inlet quarter bends shall be an acceptable means of connection, except where the
quarter bend serves a water closet. A low-heel inlet shall not be used as a wet-vented
connection. Side-inlet quarter bends shall be an acceptable means of connection for
drainage, wet venting and stack venting arrangements.
5.4.5 Cleanouts
5.4.5.1 Scope
This section shall govern the size, location, installation and maintenance of drainage pipe
cleanouts .
Cleanout plugs shall be brass or plastic, or other approved materials. Brass cleanout plugs
shall be utilized with metallic drain, waste and vent piping only, Cleanouts with plate-style
access covers shall be fitted with corrosion-resisting fasteners. Plastic cleanout plugs shall
conform to the requirements. Plugs shall have raised square or countersunk square heads.
Countersunk heads shall be installed where raised heads are a trip hazard. Cleanout plugs
with borosilicate glass systems shall be of borosilicate glass.
All horizontal drains shall be provided with cleanouts located not more than 100 feet (30
480 mm) apart.
Cleanouts shall be installed at each change of direction greater than 45 degrees (0.79 rad)
in the building drain and horizontal waste or soil lines. Where more than one change of
direction occurs in a run of piping, only one cleanout shall be required for each 40 feet (12
192 mm) of developed length of the drainage piping.
Cleanouts on concealed piping or piping under a floor slab or in a crawl space of less than
24 inches (610 mm) in height or a plenum shall be extended through and terminate flush
with the finished wall, floor or ground surface or shall be extended to the outside of the
building.
© ESA 115
CES 161
Every cleanout shall be installed to open to allow cleaning in the direction of the flow of the
drainage pipe or at right angles thereto.
Cleanouts shall be the same nominal size as the pipe they serve up to 4 inches (102 mm).
For pipes larger than 4 inches (102 mm) nominal size, the minimum size of the cleanout
shall be 4 inches (102 mm).
5.4.5.7 Clearances
Cleanouts on 6-inch (153 mm) and smaller pipes shall be provided with a clearance of not
less than18 inches (457 mm) for rodding. Cleanouts on 8-inch (203 mm) and larger pipes
shall be provided with a clearance of not less than 36 inches (914 mm) for rodding.
5.4.5.8 Access
5.5 Vents
5.5.1 General
5.5.1.1 Scope
The provisions of this section shall govern the materials, design, construction and
installation of vent systems.
The plumbing system shall be provided with a system of vent piping that will permit the
admission or emission of air so that the seal of any fixture trap shall not be subjected to a
pneumatic pressure differential of more than 1 inch of water column (249 Pa).
Every trap and trapped fixture shall be vented in accordance with one of the venting
methods specified in this section.
The vent system for a chemical waste system shall be independent of the sanitary vent
system and shall terminate separately through the roof to the open air.
The plumbing vent system shall not be utilized for purposes other than the venting of the
plumbing system.
116 © ESA
CES 161
5.5.1.5 Tests
5.5.2 Materials
5.5.2.1 Vents
The materials and methods utilized for the construction and installation of venting systems
shall comply with acceptable standards.
Sheet copper for vent pipe flashings shall conform to accepted standards and shall weigh
not less than 8 ounces per square foot (2.5 kg/m2).
Sheet lead for vent pipe flashings shall weigh not less than 3 pounds per square foot (15
kg/m2) for field-constructed flashings and not less than 2.5 pounds per square foot (12
kg/m2) for prefabricated flashings.
The vent system serving each building drain shall have at least one vent pipe that extends
to the outdoors.
5.5.3.1.1 Installation
The required vent shall be a dry vent that connects to the building drain or an extension of a
drain that connects to the building drain.
5.5.3.1.2 Size
The required vent shall be sized in accordance with Section 5.5.16.2 based on the required
size of the building drain.
A vent stack shall be required for every drainage stack that has five branch intervals or
more.
Every vent stack or stack vent shall terminate outdoors to the open air or to a stack-type air
admittance valve in accordance with Section 5.5.17.
© ESA 117
CES 161
Every vent stack shall connect to the base of the drainage stack. The vent stack shall
connect at or below the lowest horizontal branch. Where the vent stack connects to the
building drain, the connection shall be located downstream of the drainage stack and within
a distance of 10 times the diameter of the drainage stack.
Stack vents and vent stacks connected into a common vent header at the top of the stacks
and extending to the open air at one point shall be sized in accordance with the
requirements of Section 5.5.16.1. The number of fixture units shall be the sum of all fixture
units on all stacks connected thereto, and the developed length shall be the longest vent
length from the intersection at the base of the most distant stack to the vent terminal in the
open air, as a direct extension of one stack.
All open vent pipes that extend through a roof shall be terminated at least at least 7 feet
(2134 mm) above the roof.
5.5.4.2 Flashings
The juncture of each vent pipe with the roof line shall be made water tight by an approved
flashing.
An open vent terminal from a drainage system shall not be located directly beneath any
door, open able window, or other air intake opening of the
building or of an adjacent building, and any such vent terminal shall not be within 10 feet
(3048 mm) horizontally of such an opening unless it is at least 2 feet (610 mm) above the
top of such opening.
Vent terminals extending through the wall shall terminate a minimum of 10 feet (3048mm)
from the lot line and 10 feet (3048 mm) above average ground level. Vent terminals shall
not terminate under the overhang of a structure with soffit vents. Side wall vent terminals
shall be protected to prevent birds or rodents from entering or blocking the vent opening.
5.5.5.1 Connection
All individual, branch and circuit vents shall connect to a vent stack, stack vent, air
admittance valve or extend to the open air.
118 © ESA
CES 161
5.5.5.2 Grade
All vent and branch vent pipes shall be so graded and connected as to drain back to the
drainage pipe by gravity.
Every dry vent connecting to a horizontal drain shall connect above the centerline of the
horizontal drain pipe;
Every dry vent shall rise vertically to a minimum of 6 inches (152mm) above the flood level
rim of the highest trap or trapped fixture being vented.
A connection between a vent pipe and a vent stack or stack vent shall be made at least 6
inches (152 mm) above the flood level rim of the highest fixture served by the vent.
Horizontal vent pipes forming branch vents, relief vents or loop vents shall be at least 6
inches (152 mm) above the flood level rim of the highest fixture served.
Where the drainage piping has been roughed-in for future fixtures, a rough-in connection for
a vent shall be installed. The vent size shall be not less than one half the diameter of the
rough-in drain to be served. The vent rough-in shall connect to the vent system, or shall be
vented by other means as provided for in this section. The connection shall be identified to
indicate that it is a vent.
Each fixture trap shall have a protecting vent located so that the slope and the developed
length in the fixture drain from the trap weir to the vent fitting are within the requirements set
forth in Table 5.17.
Slope Distance
Size of Trap
(Inch per foot) from trap
1¼ 1/4 (feet)
5
1½ 1/4 6
2 1/4 8
3 1/8 12
4 1/8 16
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm;
1 inch per foot = 83.3 mm/m.
© ESA 119
CES 161
The total fall in a fixture drain due to pipe slope shall not exceed the diameter of the fixture
drain.
A vent shall not be installed within two pipe diameters of the trap weir.
Each trap and trapped fixture is permitted to be provided with an individual vent. The
individual vent shall connect to the fixture drain of the trap or trapped fixture being vented.
An individual vent is permitted to vent two traps or trapped fixtures as a common vent. The
traps or trapped fixtures being common vented shall be located on the same floor level.
Where the fixture drains being common vented connect at the same level, the vent
connection shall be at the interconnection of the fixture drains at different levels, the vent
shall connect as a vertical extension of the vertical drain. The vertical drain pipe connecting
the two fixture drains shall be considered the vent for the lower fixture drain, and shall be
sized in accordance with Table 5.18. The upper fixture shall not be a water closet.
Maximum Discharge
Pipe Size
from Upper
(Inches)
Fixture drain (dfu)
1½ 1
2 4
2 ½ to 3 6
For SI: 1 inch = 25.4 mm.
5.5.9 Wet venting
Any combination of fixtures within two bathroom groups located on the same floor level is
permitted to be vented by a horizontal wet vent. The wet vent shall be considered the vent
for the fixtures and shall extend from the connection of the dry vent along the direction of
the flow in the drain pipe to. The most downstream fixture drain connection to the horizontal
branch drain. Only the fixtures within the bathroom groups shall connect to the wet vented
horizontal branch drain. Any additional fixtures shall discharge downstream of the horizontal
wet vent.
120 © ESA
CES 161
Any combination of fixtures within two bathroom groups located on the same floor level is
permitted to be vented by a vertical wet vent. The vertical wet vent shall be considered the
vent for the fixtures and shall extend from the connection of the dry vent down to the lowest
fixture drain connection. Each wet-vented fixture shall connect independently to the vertical
wet vent. Water closet drains shall connect at the same elevation. Other fixture drains shall
connect above or at the same elevation as the water closet fixture drains. The dry vent
connection to the vertical wet vent shall be an individual or common vent serving one or two
fixtures.
The dry-vent connection to the wet vent shall be an individual vent or common vent to the
lavatory, bidet; shower or bathtub. In vertical wet-vent systems, the most upstream fixture
drain connection shall be a dry-vented fixture drain connection. In horizontal wet-vent
systems, not more than one wet-vented fixture drain shall discharge upstream of the dry-
vented fixture drain connection.
5.5.9.3 Size
The dry vent serving the wet vent shall be sized based on the largest required diameter of
pipe within the wet vent system served by the dry vent. The wet vent shall be of a minimum
size as specified in Table 5.19, based on the fixture unit discharge to the wet vent.
Drainage
Wet Vent Pipe size
Fixture Unit
(Inches)
Load (dfu)
1½ 1
2 4
2½ 6
3 12
For SI: 1 inch = 25. 4 mm.
A waste stack shall be considered a vent for all of the fixtures discharging to the stack
where installed in accordance with the requirements of this section.
The waste stack shall be vertical, and both horizontal and vertical offsets shall be prohibited
between the lowest fixture drain connection and the highest fixture drain connection. Every
fixture drain shall connect separately to the waste stack.
© ESA 121
CES 161
A stack vent shall be provided for the waste stack. The size of the stack vent shall be not
less than the size of • the waste stack. Offsets shall be permitted in the stack vent shall be
located at least 6 inches (152 mm) above the flood level of the highest fixture and shall be
in accordance with Section 5.5.5.5. The stack vent shall be permitted to connect with other
stack vents and vent stacks in accordance with Section 5.5.3.5.
The waste stack shall be sized based on the total discharge to the stack and the discharge
within a branch interval in accordance with Table 5.20. The waste stack shall be the same
size throughout its length.
1½ 1 2
2 2 4
2½ No limit 8
3 No limit 24
4 No limit 50
5 No limit 75
6 No limit 100
For SI: 1 inch = 25. 4 mm.
Circuit-vented horizontal branch drains are permitted to be connected together. Each group
of a maximum of eight fixtures shall be considered a separate circuit vent and shall conform
to the requirements of this section.
122 © ESA
CES 161
The circuit vent connection shall be located between the two most upstream fixture drains.
The vent shall connect to the horizontal branch and shall be installed in accordance with
Section 5.5.5.
The maximum slope of the vent section of the horizontal branch drain shall be one unit
vertical in 12 units horizontal (8-percent slope). The entire length of the vent section of the
horizontal branch drain shall be sized for the total drainage discharge to the branch.
A relief vent shall be provided for circuit vented horizontal branches receiving the discharge
of four or more water closets and connecting to a drainage stack that receives the
discharge of soil or waste from upper horizontal branches.
The relief vent shall connect to the horizontal branch drain between the stack and the most
downstream fixture drain of the circuit vent. The Relief vent shall be installed in accordance
with Section 5.5.5.
The relief vent is permitted to be a fixture drain or fixture branch for fixtures located within
the same branch interval as the circuit-vented horizontal branch. The maximum discharge
to a relief vent shall be four fixture units.
Fixtures, other than the circuit- vented fixtures, are permitted to discharge to the horizontal
branch drain. Such fixtures shall be located on the same floor as the circuit-vented fixtures
and shall be either individually or common vented.
A combination drain and vent system shall not serve fixtures other than floor drains, sinks,
lavatories and drinking fountains.
© ESA 123
CES 161
5.5.12.2 Installation
The only vertical pipe of a combination I drain and vent system shall be the connection
between the fixture drain and the horizontal combination drain and vent pipe.
5.5.12.2.1 Slope
The horizontal combination drain and vent pipe shall have a maximum slope of one-half unit
vertical in 12 units horizontal (4-percent slope). The minimum slope shall be in accordance
with Table 5.15.
5.5.12.2.2 Connection
The combination drain and vent system shall be provided with a dry vent connected at any
point within the system or the system shall connect to a horizontal drain that is vented in
accordance with one of the venting methods specified in this chapter. Combination drain
and vent systems connecting to building drains receiving only the discharge from a stack or
stacks shall be provided with a dry vent. The vent connection to the combination drain and
vent pipe shall extend vertically a minimum of6 inches (152mm) above the flood level rim of
the highest fixture being vented before offsetting horizontally.
The vent shall be sized for the total drainage fixture unit load in accordance with Section
5.5.16.2.
The fixture branch or fixture drain shall connect to the combination drain and vent within a
distance specified in Table 5.17. The combination drain and vent pipe shall be considered
the vent for the fixture.
5.5.13.1 Limitation
Island fixture venting shall not be permitted for fixtures other than sinks and lavatories.
Residential kitchen sinks with a dishwasher waste connection, a food waste grinder, or
both, in combination with the kitchen sink waste, shall be permitted to be vented in
accordance with this section.
The island fixture vent shall connect to the fixture drain as required for an individual or
common vent. The vent shall rise vertically to above the drainage outlet of the fixture being
vented before offsetting horizontally or vertically downward. The vent or branch vent for
multiple island fixture vents shall extend to a minimum of 6 inches (152 mm) above the
highest island fixture being vented before connecting to the outside vent terminal
124 © ESA
CES 161
The vent located below the flood level rim of the fixture being vented shall be installed as
required for drainage piping in accordance with this section, except for sizing. The vent
shall be sized in accordance with Section 5.5.16.2. The lowest point of the island fixture
vent shall connect full size to the drainage system. The connection shall be to a vertical
drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the
island fixture vent to permit rodding of all vent piping located below the flood level rim of the
fixtures. Rodding in both directions shall be permitted through a cleanout.
Soil and waste stacks in buildings having more than 10 branch intervals shall be provided
with a relief vent at each tenth interval installed, beginning with the top floor.
The size of the relief vent shall be equal to the size of the vent stack to which it connects.
The lower end of each relief vent shall connect to the soil or waste stack through a wye
below the horizontal branch serving the floor, and the upper end shall connect to the vent
stack through a wye not less than 3 feet (914 mm) above the floor.
Horizontal offsets of drainage stacks shall be vented where five or more branch intervals
are located above the offset. The offset shall be vented by venting the upper section of the
drainage stack and the lower section of the drainage stack.
The upper section of the drainage stack shall be vented as a separate stack with a vent
stack connection installed in accordance with Section 5.5.3.4. The offset shall be
considered the base of the stack.
The lower section of the drainage stack shall be vented by a yoke vent connecting between
the offset and the next lower horizontal branch. The yoke vent connection shall be
permitted to be a vertical extension of the drainage stack. The size of the yoke vent and
connection shall be a minimum of the size required for the vent stack of the drainage stack.
The minimum required diameter of stack vents and vent stacks shall be determined from
the· developed length and the total of drainage fixture units connected thereto in
© ESA 125
CES 161
accordance with Table 5.21, but in no case shall the diameter be less than one-half the
diameter of the drain served or less than 11/ 4 inches (32 mm).
Table 5-21 Sizes and developed length of stack vents and vent stacks
Diameter Maximum Developed Length of Vent (feet)a
of Soil or Total fixture Diameter of Vent (Inches)
Wastes Units Being
Stack Vented (dfu) 1¼ 1½ 2 2½ 3 4 5 6 8 10 12
(inches)
1¼ 2 30
1½ 8 50 150 - - - - - - - - -
1½ 10 30 100
2 12 30 75 200
2 20 26 50 150 - - - - - - -
2½ 42 30 100 300
3 10 42 150 360 1,04
3 21 - 32 110 270 0 - - - - - -
3 53 27 94 230 810
680
3 102 25 86 210 620
4 43 - 35 85 250 980 - - - - -
4 140 27 65 200 750
4 320 23 55 170 640
4 540 - - 21 50 150 580 - - - -
5 190 28 82 320 990
5 490 21 63 250 760
5 940 - - - 18 53 210 670 - - - -
5 1,400 16 49 190 590
6 500 33 130 400 1000
6 1,100 - - - - 26 100 310 780 - - -
6 2,000 22 84 260 660
6 2,900 20 77 240 600
8 1,800 - - - - 31 95 240 940 - -
8 3,400 24 73 190 720
8 5,600 20 62 160 610
8 7,600 - - - - - 18 56 140 560 -
10 4,000 31 78 310 960
10 7,200 24 60 240 740
10 11,000 - - - - - - 20 51 200 630 -
10 15,000 18 46 180 570
12 7,300 31 120 380 940
12 13,000 - - - - - - - 24 94 300 720
12 20,00 20 79 250 610
12 26,000 18 72 230 500
15 15,000 - - - - - - - 40 130 310
15 25,000 31 96 240
15 38,000 26 81 200
15 50,000 - - - - - - - - 24 74 180
For SI 1 inch=25.4mm, 1 foot = 304.8mm
(a) The developed length shall be measured from the event connection to the open air
126 © ESA
CES 161
The diameter of individual vents, branch vents, circuit vents and relief vents shall be at least
one-half the required diameter of the drain served. The required size of the drain shall be
determined in accordance with Table 5.22. Vent pipes shall not be less than 11/ 4 inches
(32 mm) in diameter. Vents exceeding 40 feet (12192mm) in developed length shall be
increased by one nominal pipe size for the entire developed length of the vent pipe. Relief
vents for soil and waste stacks in buildings having more than 10 branch intervals shall be
sized in accordance with Section 5.5.14.2.
1½ 3 2 4 8
2 6 6 10 24
2½ 12 9 20 42
3 20 20 48 72
© ESA 127
CES 161
The developed length of individual, branch, circuit and relief vents shall be measured from
the farthest point of vent connection to the drainage system to the point of connection to the
vent stack, stack vent or termination outside of the building.
Where multiple branch vents are connected to a common branch vent, the common branch
vent shall be sized in accordance with this section based on the size of the common
horizontal drainage branch that is or would be required to serve the total drainage fixture
unit (dfu) load being vented.
Branch vents exceeding 40 feet (12 192 mm) in developed length shall be increased by one
nominal size for the entire developed length of the vent pipe.
5.5.17.1 General
Vent systems utilizing air admittance valves shall comply with this section. Stack-type air
admittance valves shall conform to accepted standards. Individual and branch-type air
admittance valves shall conform to accepted standards.
5.5.17.2 Installation
The valves shall be installed in accordance with the requirements of this section and the
manufacturer's installation instructions.
Individual, branch and circuit vents shall be permitted to terminate with a connection to an
individual or branch-type air admittance valve. Stack vents and vent stacks shall be
permitted to terminate to stack-type air admittance valves. Individual and branch-type air
admittance valves shall vent only fixtures that are on the same floor level and connect to a
horizontal branch drain. The horizontal branch drain having individual and branch-type air
admittance valves shall conform to Section 5.5.17.3.1 or 5.5.17.3.2. Stack-type air
admittance valves shall conform to Section 5.5.17.3.3.
The horizontal branch drain shall connect to the drainage stack or building drain a
maximum of four branch intervals from the top of the stack.
Where the horizontal branch is located I more than four branch intervals from the top of the
stack, the horizontal branch shall be provided with a relief vent that shall connect to a vent
stack or stack vent, or extend outdoors to the open air. The relief vent shall connect to the
horizontal branch drain between the stack and the most downstream fixture drain
128 © ESA
CES 161
connected to the horizontal branch drain. The relief pipe shall be sized to relieve air
pressure inside the ejector to atmospheric pressure, but shall not be less than 11/ 4 inches
(32 mm) in size. The relief vent shall be permitted to serve as the vent for other fixtures
5.5.17.3.3 Stack
Stack-type air admittance valves shall not serve as the vent terminal for vent stacks or
stack vents that serve drainage stacks exceeding six branch intervals.
5.5.17.4 Location
Individual and branch-type air admittance valves shall be located a minimum of 4 inches
(102 mm) above the horizontal branch drain or fixture drain being vented. Stack-type air
admittance valves shall be located not less than 6 inches (152 mm) above the flood level
rim of the highest fixture being vented. The air admittance valve shall be located within the
maximum developed length permitted for the vent. The air admittance valve shall be
installed a minimum of 6 inches (152mm) above insulation materials.
Access shall be provided to all air admittance valves. The valve shall be located within a
ventilated space that allows air to enter the valve.
5.5.17.6 Size
The air admittance valve shall be rated in accordance with the standard for the size of the
vent to which the valve is connected.
Within each plumbing system, a minimum of one stack vent or vent stack shall extend
outdoors to the open air.
5.5.18.1 General
Engineered vent systems shall comply with this section for the design, submittal, approval,
inspection and testing requirements
The maximum developed length of individual fixture vents to vent branches and vent
headers shall be determined in accordance with Table 5.23 for the minimum pipe diameters
at the indicated vent airflow rates.
The individual vent airflow rate shall be determined in accordance with the following:
Qh,b = Nn,b Qv
Where:
© ESA 129
CES 161
Nn,b = Number of fixtures per header (or vent branch) + total number of fixtures
Where:
= Qw/27.8) D8/3
Individual vent airflow rates are obtained by equally distributing Qh,b into one-half the total
number of fixtures on the branch or header for more than two fixtures; for an odd number of
total fixtures, decrease by one; for one fixture, apply the full value of Qh,b.
Individual vent developed length shall be increased by 20 percent of the distance from the
vent stack to the fixture vent connection on the vent branch or header.
Table 5-23 Minimum diameter and maximum length of individual branch fixture vents
and individual fixture header vents for smooth pipes
130 © ESA
CES 161
The sizing, design and layout of the vent system shall be permitted to be determined by
approved computer program design methods.
The vent system shall be based on the air capacity requirements of the drainage system
under a peak load condition.
5.6.1 General
5.6.1.1 Scope
This section shall govern the material and installation of traps, interceptors and separators.
Each plumbing fixture shall be separately trapped by a water-seal trap, except as otherwise
permitted by this code... The vertic.al distance from the fixture outlet to the trap weir shall
not exceed 24 inches (610 mm) and the horizontal distance shall not exceed 30 inches (610
mm) measured from the centerline of the fixture outlet to the centerline of the inlet of the
trap. A fixture shall not be double trapped.
Fixture trap size shall be sufficient to drain the fixture rapidly and not less than the size
indicated in Table 5.24. A trap shall not be larger than the drainage pipe into which the trap
discharges.
© ESA 131
CES 161
132 © ESA
CES 161
A recess provided for connection of the underground trap, such as one serving a bathtub in
slab-type construction, shall have sides and a bottom of corrosion- resistant, insect- and
vermin proof construction.
Where a vitrified clay or other Brittle ware, acid-resisting trap is installed underground, such
trap shall be embedded in concrete extending 6 inches (152mm) beyond the bottom and
sides of the trap.
5.6.3.1 General
The materials and methods utilized for the construction and installation of traps,
interceptors and separators shall comply with this section and the applicable accepted
standard. The fittings shall not have ledges, shoulders or reductions capable of retarding or
obstructing flow of the piping.
5.7.1 General
Before the drainage system for a building or group of buildings is designed and constructed,
accurate information regarding the site conditions is essential. This information may vary
with the individual scheme.
Drainage fixture unit values as given in Table 5.24 designate the relative load weight of
different kinds of fixtures that shall be employed in estimating the total load carried by a soil
or waste pipe, and shall be used in connection with Tables 5.25 and 5.22 of sizes for soil,
waste and vent pipes for which the permissible load is given in terms of fixture units.
© ESA 133
CES 161
1¼ 1 1
1½ 3 3
2 21 26
2½ 24 31
3 36 42 50
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m.
(a) The minimum size of any building drain serving a water closet
shall be 3 inches
Fixtures not listed in Table5.24 shall have a drainage fixture unit load based on the outlet
size of the fixture in accordance with Table 5.26. The minimum trap size for unlisted fixtures
shall be the size of the drainage outlet but not less than 1.25 inches (32 mm).
134 © ESA
CES 161
Drainage fixture unit values for continuous and semi-continuous flow into a drainage system
shall be computed on the basis that 1gpm (0.06 Lt/s) of flow is equivalent to two fixture
units.
1¼ 2
1½ 2
2 3
2½ 4
3 5
4 6
5.8.1 Aim
The efficient collection and disposal of foul and waste water from a building is of great
importance to public health and is an essential part of the construction of the building. In
designing a drainage system for an individual building the aim shall be to provide a system
of self cleaning conduits for the conveyance of foul and waste and for the removal of such
wastes speedily and efficiently to a sewer or other outlet without risk of nuisance and
hazard to health.
(1) To achieve this aim a drainage system shall satisfy the following requirements:
(b) prevention of access of foul gases to the building and provision for their escape
from the system,
© ESA 135
CES 161
(3) Efficient and an economical plumbing system can be achieved by planning the toilets in
compact grouping with the layout of the bathrooms and observing the following guidelines:
(a) Placing of plumbing fixtures around an easily accessible pipe shaft; in high rise
buildings the pipe shafts may have to be within the building envelope and easy
provision for access panels and doors should be planned in advance, in such
cases.
(b) Adopting repetitive layout of toilets in the horizontal and vertical directions.
(c) Avoiding any conflict with the reinforced cement concrete structure by avoiding
embedding pipes in it, avoiding pipe crossings in beams, columns and major
structural elements.
(d) Identifying open terraces and areas subject to ingress of rainwater directly or
indirectly and providing for location of inlets at each level for down takes for
disposal at ground levels.
5.8.2 Layout
5.8.2.1 General
(b) The pipes should be laid in straight lines, as far as possible, in both vertical and
horizontal planes.
(c) Anything that is likely to cause irregularity of flow, as abrupt changes of direction,
shall be avoided.
(d) The pipes should be non-absorbent, durable, smooth in bore and of adequate
strength.
(f) Drains should be well ventilated, to prevent the accumulation of foul gases and
fluctuation of air pressure within the pipe, which could lead to unsealing of gully
or water-closet traps.
(g) All the parts of the drainage system should be accessible for feasibility of
inspection and practical maintenance.
136 © ESA
CES 161
In selecting one or more of the type of piping systems, the building and the layout of toilets;
relationship with other services; acceptability; and any special requirements of users, shall
be studied.
(a) This system is ideal when the location of toilets and stacks for the WCs and
waste fittings is not uniform or repetitive.
(b) In large buildings and houses with open ground and gardens the sullage water
from the waste system can be usefully utilized for gardening and agriculture.
(c) In larger and multi-storied buildings, the sullage is treated within the building for
re-use as makeup water for cooling towers for air conditioning system and is also
used for flushing water-closets provided it has absolutely no connection with any
water supply line, tank or system used for domestic and drinking supply.
(a) This system is suitable for buildings where the toilet layouts and the shafts are
repetitive. It requires less space, and is economical.
(b) Continuous flow of water in the pipe from waste appliances makes it less prone to
blockage and makes the system more efficient.
(c) The system eliminates the need for a gully trap which requires constant cleaning.
(d) The system is ideal when the main pipes run at the ceiling of the lowest floor or in
a service floor. Two-pipe system may present space and crossing problems
which this system eliminates.
(a) The single stack system (without any vent pipe) is ideal when the toilet layouts
are repetitive and there is less space for pipes on the wall.
(b) In any system so selected there should be not more than two toilet connections
per floor.
(c) The system requires minimum 100 mm diameter stack for a maximum of five
floors in a building.
(d) All the safeguards for the use of this system given in 5.8.2.2.1 shall be complied
with.
The system and the applicable safeguards under this system are the same as for single
stack system. The prime modification is to connect the waste appliances, such as wash
basin, bath tub or sink to a floor trap.
© ESA 137
CES 161
For detailed information regarding design and installation of soil, waste and ventilating
pipes, reference may be made to good practice.
(a) as far as practicable, the fixtures on a floor shall be connected to stack in order of
increasing discharge rate in the downward direction;
(b) the vertical distance between the waste branch (from floor trap or from the
individual appliance) and the soil branch connection, when soil pipe is connected
to stack above the waste pipe, shall be not less than 200 mm;
(c) depth of water seal traps from different fixtures shall be as follows:
Water closets 50 mm
Floor traps 50 mm
(d) branches and stacks which receive discharges from WC pans should not be less
than 100 mm, except where the outlet from the siphonic water closet is 80 mm, in
which case a branch pipe of 80 mm may be used. For outlet of floor traps 75 mm
diameter pipes may be used;
(e) the horizontal branch distance for fixtures from stack, bend(s) at the foot of stack
to avoid back pressure as well as vertical distance between the lowest
connection and the invert of drain shall be as shown in Figure 5.1; and
(f) for tall buildings, ground floor appliances are recommended to be connected
directly to manhole/inspection chamber.
138 © ESA
CES 161
(1) Drainage pipes shall be kept clear of all other services. Provisions shall be made during
the construction of the building for the entry of the drainage pipes. In most cases this may
be done conveniently by building sleeves or conduit pipes into or under the structure in
appropriate positions. This will facilitate the installation and maintenance of the services.
(2) Horizontal drainage piping should be so routed as not to pass over any equipment or
fixture where leakage from the line could possibly cause damage or contamination,
Drainage piping shall never pass over switch-gear or other electrical equipment. If it is
impossible to avoid these areas and piping must run in these locations, then a pan or drain
tray should be installed below the pipe to collect any leakage or condensation. A drain line
should run from this pan to a convenient floor drain or service sink.
(3) All vertical soil, waste, ventilating and antisiphonage pipes shall be covered on top with
a copper or heavily galvanized iron wire dome or cast iron terminal guards. All cast iron
pipes, which are to be painted periodically, shall be fixed to give a minimum clearance of 50
mm clear from the finished surface of the wall by means of a suitable clamps.
Note: Asbestos cement cowls maybe used in case asbestos cement pipes are used as soil pipes.
© ESA 139
CES 161
(4) Drainage pipes shall be carried to a height above the buildings as specified for
ventilating pipe (see 5.8.3.4).
A soil pipe, conveying to a drain, any solid or liquid filth, shall be circular and shall have a
minimum diameter of 100 mm.
(1) Except where it is impracticable, the soil pipe shall be situated outside the building or in
suitably designed pipe shafts and shall be continued upwards without diminution of its
diameter, and (except where it is unavoidable) without any bend or angle, to such a height
and position as to afford by means of its open end a safe outlet for foul air. The position of
the open end with its covering shall be such as to comply with the conditions set out in
5.8.3.4 relating to ventilating pipe. Even if the pipes are laid externally, the soil pipes shall
not be permitted on a wall abutting a street unless the Authority is satisfied that it is
unavoidable. Where shafts for pipes are provided, the cross-sectional area of the shaft shall
be suitable to allow free and unhampered access to the pipes and fittings proposed to be
installed in the shaft. However in no case cross-section area of the shaft shall be less than
a square of one meter side. All pipe shafts shall be provided with an access door at ground
level and facilities for ventilation.
(2) Soil pipes, whether insider or outside the pipe shall not be connected with any rainwater
pipe and there shall not be any trap in such soil pipe or between it and any drain with which
it is connected.
(4) The soil pipe shall be provided with heel rest bend which shall rest on sound footing, if
terminating at firm ground level. When the stack is terminating at the ceiling of a floor, the
bend shall be provided with sufficient structural support to cater for the stack dead weight
and the thrust developed from the falling soil/ waste. Vertical stack shall be fixed at least 50
mm clear the finished surface of the wall by means of a suitable clamps of approved type.
Every pipe in a building for carrying off the waste or overflow water from every bath,
washbasin or sink to a drain shall be of 32 mm to 50 mm diameter, and shall be trapped
immediately beneath such washbasins or sink by an efficient siphon trap with adequate
means for inspection and cleaning. Such traps shall be ventilated into the external air
whenever such ventilation is necessary to preserve the seal of the trap. Waste pipes, traps,
etc, shall be constructed of iron, lead, brass, stoneware, asbestos cement or other
approved material. The overflow pipe from washbasin, sinks, etc, shall be connected with
the waste pipe immediately above the trap. Vertical pipes carrying off waste water shall
have a minimum diameter of 75 mm.
Note: Whenever washbasins and sinks have in-built overflow arrangements, there is no need to provide
overflow pipes in such cases.
(1) Every pipe in a building for carrying off waste water to a drain shall be taken through an
external wall of the building by the shortest practicable line, and shall discharge below the
grating or surface box of the chamber but above the inlet of a properly trapped gully. The
waste pipe shall be continued upwards without any diminution in its diameter and (except
140 © ESA
CES 161
when unavoidable) without any bend or angle to such a height and position as to afford by
means of the open end of the waste pipe, a safe outlet for foul air, the position of the open
end and its covering being such as to comply with the conditions.
(2) Except where it is impracticable, the common waste pipe shall be situated outside the
building and shall be continued upwards without diminution of its diameter (except where it
is unavoidable) without any bend or angle being formed to such a height and position as to
avoid by means of the open end a safe outlet for foul air, the position of the open end and
the covering threat being such as to comply with the conditions set out in 5.8.3.4 relating to
ventilating pipe.
(3) If the waste pipe is of cast iron, it shall be firmly attached 50 mm clear of the finished
surface of the wall by means of a suitable clamps or with properly fixed holder bats or
equally suitable and efficient means.
Ventilating pipes should be so installed that water can not be retained in them. They should
be fixed vertically. Whenever possible, horizontal runs should be avoided. Ventilating pipe
shall be carried to such a height and in such a position as to afford by means of the open
end of such pipe or vent shaft, a safe outlet for foul air with the least possible nuisance.
(1) The upper end of the main ventilating pipe may be continued to the open air above roof
level as a separate pipe, or it may join the MSP and/or MWP above the floor level of the
highest appliance. Its lower end may be carried down to join the drain, at a point where air
relief may always be maintained.
(2) Branch ventilating pipes should be connected to the top of the BSP and BWP between
75 mm and 450 mm from the crown of the trap.
(3) The ventilating pipe shall always be taken to a point 1500 mm above the level of the
eaves or flat roof or terrace parapet whichever is higher or the top of any window within a
horizontal distance of 3 m. The least dimension shall be taken as a minimum and local
conditions shall be taken into account. The upper end of every ventilating pipe shall be
protected by means of a cowl.
(4) In case the adjoining building is taller, the ventilating pipe shall be carried higher than
the roof of the adjacent building, wherever it is possible.
(5) The building drain intended for carrying waste water and sewage from a building shall
be provided with at least one ventilating pipe situated as near as practicable to the building
and as far away as possible from the point at which the drain empties into the sewer or
other earner.
(a) The building drain ventilating pipe shall be of not less than 75 mm diameter
when, however, it is used as MSP or MWP. The upper portion, which does not
carry discharges, shall not be of lesser diameter than the remaining portion;
(b) The diameter of the main ventilating pipe in any case should not be less than 50
mm;
© ESA 141
CES 161
(c) A branch ventilating pipe on a waste pipe in both one-and two-pipe systems shall
be of not less than two-thirds the diameter of the branch waste ventilated pipe;
subject to a minimum of 25 mm; and
(d) A branch ventilating pipe on a soil pipe in both one-and two-pipe systems shall be
not less than 32 mm in diameter.
(a) The maximum flow in a building drain or a stack depends on the probable
maximum number of simultaneously discharging appliances. For the calculation
of this peak flow certain loading factors have been assigned to appliances in
terms of fixture units, considering their probability and frequency of use. These
fixture unit values are given in Table 5.27.
(b) For any fixtures not covered under Table 5.27, Table 5.28 may be referred to for
deciding their fixture unit rating depending on their drain or trap size.
(c) From Tables 5.27 and 5.28, the total load on any pipe in terms of fixtures units
may be calculated knowing the number and type of appliances connected to this
pipe.
(d) For converting the total load in fixture units to the peak flow in liters per minute,
Figure 5.3 is to be used.
(e) The maximum number of fixture units that are permissible various recommended
pipe size in the drainage system are given in Tables 5.29 and 5.30.
(f) Results should be checked to see that the soil, waste and building sewer pipes
are not reduced in diameter in the direction of flow. Where appliances are to be
142 © ESA
CES 161
added in fixture, these should be taken into account in assessing the pipe sizes
by using the fixture units given in Tables 5.27 and 5.28.
The maximum rate of discharge flow shall be taken as three times the average rate,
allowance being made in addition for any exceptional peak discharges. A good average
rule is to allow for a flow of liquid wastes from buildings at the rate of 3 litres per minute per
10 persons.
© ESA 143
CES 161
Table 5-28 Fixture units for fixtures based on fixture drain on trap size
144 © ESA
CES 161
Table 5-29 Maximum number of fixture units that can be connected to branches and
stacks
i 30 1 2 2 1
ii 40 3 4 8 2
iii 50 6 10 24 6
iv 65 12 20 42 9
v 75 20 30 60 16
© ESA 145
CES 161
Table 5-30 Maximum number of fixture units that can be connected to building drains
and sewers
Table 5-31 Different diameter pipes giving velocity and corresponding discharge at
minimum and maximum gradient
146 © ESA
CES 161
5.8.3.5.2 Gradients
(1) The discharge of water through a domestic drain is intermittent and limited in quantity
and, therefore, small accumulations of solid matter are liable to form in the drains between
the building and the public sewer. There is usually a gradual shifting of these deposits as
discharges take place. Gradients should be sufficient to prevent these temporary
accumulations building up and blocking the drains.
(2) When flow occurs in drain piping, it should not entirely fill the cross-section of the pipe
under flow condition. If the pipe were to flow full, pressure fluctuations would occur which
could possibly destroy the seal of the traps within the building. The approximate gradients
which give this velocity for the sizes of pipes likely to be used in building drainage and the
corresponding discharges when following half-full are given in Table5.31.
(3) In cases where it is practically not possible to conform to the ruling gradients, a flatter
gradient may be used, but the minimum velocity in such cases shall on no account be less
than 0.61 m/s and adequate flushing should be done.
(4) On the other hand, it is undesirable to employ gradients giving a velocity of flow greater
than 2.4 m/s. Where it is unavoidable, cast iron pipes shall be used. The approximate
gradients, which give a velocity of 2.4 m/s for pipes of various sizes and the corresponding
discharge when flowing half-full are given in Table 5.27.
(5) The discharge values corresponding to nominal diameter and gradient given in Table5.
27 are based on Manning’s formula (n = 0.015).
Note: Subject to the minimum size of 100mm, the sizes of pipes shall be decided in relation to the estimated
quantity of flow and the available gradient.
5.8.3.6.1 Trap
All traps shall be protected against siphonage and back pressure ensuring access to
atmospheric air for air circulation and preserving the trap seal in all conditions.
(1) A trap may be formed as an integral trap with the appliance during manufacture or may
be a separate fitting called an attached trap which may be connected to the waste outlet of
the appliance.
(2) Traps should always be of a self-cleansing pattern. A trap, which is not an integral part
of an appliance, should be directly attached to its outlet and the pipe should be uniform
throughout and have a smooth surface.
(3) The trap should have minimum size of outlet/exit, same as that of largest waste inlet
pipe.
(4) Traps for use in domestic waste installations and all other traps should be conveniently
accessible and provided with cleansing eyes or other means of cleaning.
(5) The minimum internal diameter for sanitary appliances shall be as follows:
© ESA 147
CES 161
Soil appliance
All toilets/bathrooms in a building desirably should be provided with floor drains to facilitate
cleaning.
(1) Floor drains shall connect into a trap so constructed that it can be readily cleaned and of
a size to serve efficiently the purpose for which it is intended. The trap shall be either
accessible from the floor drain or by a separate cleanout within the drain.
(2) Floor drain should be provided in mechanical equipment rooms, where pumps, boilers,
water chillers, heat exchangers and other air conditioning equipments are periodically
drained for maintenance and repair. Boiler requires drain at safety relief valve discharge.
(3) Strategically floor drains are required to be located in buildings with wet fire protection
sprinkler systems to drain water in case of activation of sprinkler heads.
5.8.3.6.3 Cleanouts
The cleanout provides access to horizontal and vertical lines and stacks to facilitate
inspection and means to remove obstructions common to all piping systems, such as solid
objects, greasy wastes, hair and the like.
(1) Cleanouts in general should be gas and water-tight, provide quick and easy plug
removal, allow ample space for rodding tools, have means of adjustments to finished floor
level, be attractive and be designed to support whatever load is directed over them.
148 © ESA
CES 161
(2) Waste lines are normally laid beneath the floor slab at a sufficient distance to provide
adequate back-fill over the joints. Cleanouts are then brought up to floor level grade by pipe
extension pieces.
(3) The size of the cleanout within a building should be the same size as the piping up to
100 mm. For larger size piping 100 mm cleanouts are adequate for their intended purpose.
(d) At the horizontal header, receiving vertical stacks and serving the purpose of
offset header.
The maximum number of drainage fixture units connected to a given size of building sewer,
building drain or horizontal branch of the building drain a given size of building drain or
horizontal branch of the building drain shall be determined using Table 5-25. The maximum
number of drainage fixture units connected to a given size of horizontal branch or vertical
soil or waste stack shall be determined using Table 5-22.
Horizontal stack offsets shall be sized as required for building drains in accordance with
Table 5-25.
Vertical stack offsets shall be sized as required for straight stacks in accordance with Table
5-22.
Where provision is made for the future installation of fixtures, those provided for shall be
considered in determining the required sizes of drain pipes.
If a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical
stack offset and the offset is located more than four branch intervals below the top of the
stack, the offset shall be vented in accordance with Section 5.5.15.
© ESA 149
CES 161
Where a horizontal stack offset is located more than four branch intervals below the top of
the stack, a horizontal branch shall not connect within the horizontal stack offset or within 2
feet (610 mm) above or below such offset.
A stack with a horizontal offset located more than four branch intervals below the top of the
stack shall be sized as follows:
(1) The portion of the stack above the offset shall be sized as for a vertical stack based on
the total number of drainage fixture units above the offset.
(2) The portion of the stack below the offset shall be sized as for the offset or based on the
total number of drainage fixture units on the entire stack, whichever is larger (See Table 5-
22, Column 5).
Where a vertical offset occurs in a soil or waste stack below the lowest horizontal branch,
change in diameter of the stack because of the offset shall not be required. If a horizontal
offset occurs in a soil or waste stack below the lowest horizontal branch, the required
diameter of the offset and the stack below it shall be determined as for a building drain in
accordance with Table 5.25.
The sizing, design and layout of the drainage system shall be permitted to be designed by
approved computer design methods.
The load shall be computed from the simultaneous or sequential discharge conditions from
fixtures, appurtenances and appliances or the peak usage design condition.
The discharge profiles for flow rates versus time from fixtures and appliances shall be in
accordance with the manufacturer's specifications.
Pipe size calculations shall be conducted with the pipe wall roughness factor (ks), in
accordance with the manufacturer's specifications and as modified for aging roughness
factors with deposits and corrosion.
150 © ESA
CES 161
Horizontal drainage piping shall be designed and installed at slopes in accordance with
Table 5.15.
© ESA 151
CES 161
6.1 Scope
(a) For the design, layout, construction, testing and maintenance of foul and
groundwater drainage system construction in the ground under and around
buildings;
(b) For the design and construction of septic tanks, cesspools and subsoil disposal
systems; and
6.2 General
(1) The layout of the drainage system should be as simple as possible. Changes of
direction and gradient should be minimized and as easy as practicable. Access points
should be provided only if blockages could not be cleared without them. Connections of
drains to other drains or to sewers should be made obliquely, and in the direction of flow.
Pipes should be laid to even gradients and any change of gradient should be combined with
an access point
(2) A drainage system should be designed, installed and maintained so as to convey and
discharge its contents without causing a nuisance or danger to health arising from leakage,
blockage or surcharge.
(3) Every building in which plumbing fixture are installed and premises having thereon,
shall have a connection to a public sewer. Where no public sewer line exists, the drains
shall be connected to a sewage disposal system approved by the Building Official.
(4) Ground water (subsoil water) should be drained from around and underneath buildings,
structures, etc. Whenever required. This should be effected through plain open-jointed
porous or perforated pipes laid in trenches or graded granular or other porous material fills
or packs around and underneath the area to be drained.
(5) Access should be provided at all bends junctions. Access, in this context, is meant to be
an inspection chamber or manhole. Inspection chambers and manholes should be sited so
as to avoid the need for acute changes in direction of flow from branch drains.
(6) For drains laid outside buildings, the following shall be satisfied.
(a) Part of pipework laid under buildings should be limited to short branches and
should be made to enter manholes (or inspection chamber) at no more than 2.0m
from the building line whenever possible.
152 © ESA
CES 161
(b) The drain trench should not impair the stability of a building. When drains are laid
parallel to the foundation, care should be taken not to undermine the foundations.
(7) For drains laid under buildings the following shall be met:
(a) The effects of possible differential settlement between the building and the drains
shall be limited to acceptable standards
(9) (a) Existing drains which are or will be disused when superseded by new
installations should be traced, grubbed up and removed.
(b) Where the requirement in (a) above is impracticable, discussed drains should be
filled with suitable material such as weak concrete, cement grout or similar
material to prevent their collapse or, in appropriate circumstances, sealed against
ingress of water and vermin.
6.3.1 General
(2) All subsoil drainage system and surface runoff due to rain shall be excluded from the
system; i.e., foul drainage system up to a treatment unit, collection point or disposal system.
(3) In determining the size and gradient of the building sewer (external drain), the following
shall be observed.
(4) The fixture-unit values contributing to the flow in a given drain shall be added and the
equivalent peak flow rate (l/s) obtained. When the drain carries continuous flows from other
sources, their rates can be added to the above peak flow rate.
(1) A pipe diameter and gradient shall be selected taking account of the provisions and
requirements in (2) to (4) below (see Figures 6-2 and 6-3).
(2) Risk of recurring blockages during normal use shall be minimized by ensuring a high
standard of drain and manhole construction throughout the system and that pipes are not
unacceptably oversized.
(3) (a) Foul drains, starting from manholes adjacent to or within buildings, should be of
minimum size DN100, except for WC discharges which should be DN150.
© ESA 153
CES 161
(b)The size of a drain pipe and its gradient should be so chosen that at peak flow,
the risk of induced trap siphonage is minimized by ensuring adequate air
movement in the drain, but not exceeding a proportional depth of 0.75.
154 © ESA
CES 161
Figure 6-1 Design for foul drainage pipes-conversion of fixture units to flow rates
© ESA 155
CES 161
Figure 6-2 Discharge capacities of drain pipes running full, 3/4, 2/3, proportional
depth (Hydraulic roughness = 0.6mm)
156 © ESA
CES 161
Figure 6-3 Discharge capacities of drain pipes running full, 3/4, 2/3 proportional
depth (hydraulic roughness = 1.5mm)
(1) A connection to a foul drain within the premises of a building should be effected via an
inspection chamber or manhole.
© ESA 157
CES 161
(2) (a) A branch connection should have an angle of entry not greater than 900 at the
internal face of an inspection chamber or manhole.
(b) Where practicable, it should be installed at half pipe level of the main channel to
provide cascade entry, and the connection so shaped as to discharge into it with
minimum turbulence and without causing backing-up into other connections.
(3) (a) Where the invert level of an incoming drain is 1.0m or more above that of the
manhole, a drop-pipe shall be provided to convey the discharge to the lower
level.
(b) Suitable access should be provided to facilitate testing and clearing of blockages.
(c) Where space is available without adversely affecting access of working space, a
drop-pipe may be installed inside a manhole.
(d) When the drop-pipe is larger than 150.omm, it should be constructed outside the
manhole and provided with structural protection and support suited to the pipe
material and ground conditions (see Figure 6-7).
(4) (a) The drain connection to a public sewer system should be agreed with the
appropriate drainage authority.
(b) The connector drain (to sewer system) should be laid so as to provide an
adequate hydraulic gradient and to ensure that the minimum length of drain is
subjected to backflow would the sewer surcharge.
(c) When a drain is connected to a septic or settlement tank, the entry velocity
should be restricted so as to ensure that quiescent conditions within the tank are
disturbed as little as possible.
(d) Provision should be made for effectively rodding the incoming drain and its
connection to any tank or unit.
Package lifting installations are available which are suitable for installation within buildings.
Floor mounted units may be particularly suited for installation in basements.
Where foul drainage from a building is to be pumped, the effluent-receiving chamber should
be sized to contain 24-hour inflow to allow for disruption in service. The capacity of the
receiving chamber should be based on the calculated daily demand of the water intake for
the building. Where only a proportion of the foul sewage is to be pumped, then the capacity
should be based pro-rata. In all pumped systems the controls should be so arranged to
optimize pump efficiency and be fitted with a suitable alarm system to alert the owner of any
malfunction.
158 © ESA
CES 161
6.4.1 General
(1) (a) All pipes for field drains should be laid to planned lines and gradients
(b) Plain pipes should be laid with open-joints; but perforated and porous pipes
should be fitted tightly together. Perforated pipes should be laid with holes
equally distributed about the vertical axis of the drain.
(c) Trenches for plain-ended or ogee0jointed pipes should be just wide enough at
the bottom to accommodate the pipes and should be trimmed to form a uniform
bed for the pipes.
(2) Where a rubble drain is required, it should be constructed by excavating a trench and
filling it with selected rubble or stone through which water can percolate. Renewal may be
necessary from time to time.
(3) (a) Where a trench drain is required, it should be constructed by excavating a trench
and laying therein open-jointed pipes, perforated or porous material.
(b) The pipes should be surrounded with fill through which water can percolate
freely.
(4) (a) Where it is essential to prevent the migration of some soil particles with
groundwater, filter drain shall be used.
(b) The pipe should be surrounded with graded granular material or a polypropylene
or fabric filter designed in accordance with acceptable engineering practice.
(5) The selection of an appropriate layout of ground-water drain shall depend on the nature
of the subsoil and the topography of the site.
(1) The laying of groundwater drains under buildings, unless and otherwise required by the
engineer, should be avoided.
(2) Should it be necessary to route a groundwater drainage system under a building, this
should be done using jointed non-porous pipes.
(1) A groundwater drainage system shall discharge through sand trap or directly into a ditch
or a watercourse.
(3) Where the alternatives in (a) or (b) above for groundwater disposal are not available; a
groundwater drainage system may discharge into a surface water through a sand trap.
© ESA 159
CES 161
(4) Under special circumstances, a groundwater drainage system may discharge into a foul
drain (after treatment) through an intercepting trap.
(1) The flow rate of ground water shall be estimated from an in-depth assessment of the
quantity of run-off likely to affect the area concerned, natural slope of the terrain around the
area, terrain soil permeability and maximum water table.
(1) Drain pipe sizing shall be in accordance with the provisions of Clause 6.3.2.
(2) Main groundwater drains should be not less than DN150, and the branches not less
than DN100.
6.5.1 General
Where a drain is to be located in a road, public place or like in an open trench, it shall be
installed as follows:
(a) It shall be laid to an even grade, straight, and have no lipped joints or internal
projections.
(c) It shall be continuously supported under the barrel, other than for cast iron and
ductile iron pipes and fittings.
(f) It shall have the interior of each pipe cleared of any foreign matter before it is laid
and prior to commissioning.
(g) It shall have a drop manhole installed to connect drains at different elevations.
(h) Where the presence of any obstacle prevents the drain from being laid at an even
grade and with the required cover, then, whenever practicable, the drain shall
pass beneath the obstacle at an even grade with a drop permitted only at the
point of connection or in any other way approved by the Building Official.
(a) When installed aboveground, shall not be within 100.0mm of any drain pipe.
160 © ESA
CES 161
(b) When installed belowground, shall not be within 600.0mm of either side of a
below ground drain. Whenever this separation cannot be achieved, the distance
may be reduced to 300mm provided that the electric cable or gas pipe is suitably
marked with bricks, stone masonry or equivalent durable material painted red,
within the exclusion zone (see Figure 6-4).
(2) Any belowground cross-over of a drain within the exclusion zone shall:
(c) Be suitably marked with bricks, stone masonry or equivalent durable material,
painted red.
(3) Stormwater pipes shall be located at least 100.0mm clear of any part of the foul drain.
The pipes shall be watertight and properly supported.
(4) The proximity of foul drain pipes to water service pipes shall be as in 4.14.3(3).
(5) Where services, other than electric cables or gas pipes, cross any part of the drain, the
service shall be not less than 25.0mm above the drain and access fir maintenance shall not
be impeded.
(1) Drains shall be laid in a manner that provides protection against mechanical damage
and deformation due to vehicular loadings.
(2) Drains shall be laid with a depth of cover, measured from the top of the pipe socket to
the finished ground surface, as specified in Table 6-1.
Figure 6-4 Exclusion zone for electric cables and gas pipes
© ESA 161
CES 161
(3) Drains constructed of materials other than cast iron or ductile iron, having less than the
minimum cover as specified in Table 6.1. shall be covered by at least 50.0mm of overlay
and then shall be paved with:
(b) 75.0mm minimum thickness of brick or concrete paving, where subject to light
vehicular traffic, or
(c) 50.0mm minimum thickness of brick or concrete paving, where not subject to
vehicular traffic.
(4) Drains below ground and under buildings may be laid with less than the minimum cover
specified in Table 6.1 provided that:
(a) 25.0mm overly separates the drain from a reinforced concrete slab; or
(5) Drains in proximity to footings and foundations shall comply with the following:
(a) Drains passing under a strip footing at not less than 450 (between the drain and
the longer side of the footing) shall have a minimum clearance of 25.0mm from
the top of the pipe to the underside of any footing.
(b) Drains laid through footings or walls, other than below-ground external walls,
shall be left with an annular space of not less than 25.0mm filled with a liner of
flexible material.
(c) Pipes may be laid through below-ground external walls provided that:
(d) Where the excavation is to be laid parallel to a footing, the excavation shall
comply with Clause 6.61 and the trench shall be located beyond a 450 angle from
the base of the footing (see Figure 6.5).
162 © ESA
CES 161
(1) Any trench excavation in which the sides are not self-supporting or when required by the
Building Official shall comply with the relevant regulations which require that these trenches
be adequately supported against collapse.
(2) Trenches shall be made with a minimum clearance of 100.0mm on each side of the
drain barrel measured to the inside of the sheeting or side of trench. The trench width up to
the level of the top of the drain shall be kept as narrow as practicable, but not less than the
above minimum clearance.
(3) Where a trench has been excavated deeper than necessary, the excess depth shall be
filled either with bedding material compacted to achieve a density as near to the original soil
density as possible or with concrete.
(4) Excavation by a machine shall not be carried out within 600.0mm of the point of
connection to the municipal sewer main or any other sewage receiving unit such as tanks,
channels, etc.
(a) Consideration shall be given to the effect on adjacent buildings and the trench.
(b) The water level shall be lowered below the base of the proposed trench and
maintained at that level during excavation, laying of the drain, and backfilling of
the trench.
(ii) The removed water shall be discharged into a location where it will not
cause a nuisance or damage.
(iii) The removed water shall not discharge, either directly or indirectly, into
sewer.
© ESA 163
CES 161
6.6.2.1 General
(1) The bed on to which drains are laid shall be adequate to continuously support the
installed drain accommodating the loads from the pipeline and surrounding ground, in
accordance with the following:
(a) In stable sand, drains shall be directly supported on the undisturbed base of the
trench provided that the base of the trench is free any rocks or tree roots.
(b) In loam, clay, rock, shale, gravel, or ground containing hard objects, drains shall
be supported on a bedding material placed in the base of the trench.
(c) Ground water or surface water entering the trench shall not disturb the bedding
materials.
6.6.2.2 Materials
(1) Materials used for bedding of rains shall comply with the following:
(a) Quarry crushed hard stone shall have a maximum aggregate size of 10.0mm.
(b) Uniform crushed hard stone shall be of size ranging from 2.5mm to 10.0mm.
(c) Sand shall be free from clay, gravel, shells, or hard particles
(d) Cement mortar shall be composed of 1:4, Portland cement to clean sand, and
clean water.
(e) Excavated material shall be free from clay, gravel, shells, or other hard particles.
164 © ESA
CES 161
6.6.2.3 Installation
(i) Extend across the full width of the base of the trench;
(ii) Be a minimum depth of 75.0mm measured below the bottom of the pipe;
and
(i) Be a minimum depth of 50.0mm measure below the barrel of the pipe;
(iv) Have pipes supported at not greater than 1.5m centres prior to placing the
mortar bedding; and
(v) Be used where the base of the trench is rock or shale and where the grade
is greater than 20%.
6.7.1 General
(1) Every drain length should accessible for maintenance, rodding and cleaning through the
provision of inspection chambers and manholes or otherwise.
(2) Inspection chambers and manholes should be provided at the head of each run of drain,
at changes in direction, gradient or pipe diameter and every 30.0m straight run of drains.
(3) Inspection chambers and manholes should be resistant to water penetration, be durable
and designed to minimize the risk of blockage.
© ESA 165
CES 161
(1) The size of inspection chambers should be such that the drain can be cleaned from the
surface.
(2) The design of manhole should permit entry without restricting operational space.
(3) Subject to the minima given in Table 6.2, internal dimensions for manholes with a
number of branches may be estimated for straight inverts as follows:
(a) Length: The length should be the sum of 100.0mm on each side of the branch
pipe, the diameter of the pipe on the side having most branches for each pipe,
plus an allowance at the downstream end for the angle of entry.
(b) Width: The width should be the sum of the widths of the benching plus 150.0mm
or the diameter of the main drain, whichever is greater. The benching width
should be 300.0mm where there are branches or 150.0mm where there is no
branch. Where manhole or inspection chambers with curved channels cannot be
avoided, their dimensions should be based on the foregoing principles.
166 © ESA
CES 161
(1) Materials of construction for inspection chambers and manholes may include:
(a) The wall thickness should be adequate to resist external pressures due to soil
and ground water, but in any case not less than 150.0mm;
(b) Durability and resistance to water penetration should be achieved by using bricks
and concrete blocks complying with the relevant standards. In addition, all mortar
joints should be completely filled and flush pointed as the work proceeds;
(c) The roofing concrete slab for brick inspection chambers and manhole should be
designed to carry the weight of any ground above plus all probable superimposed
loads.
(e) Pipes of size DN300 or larger, when built into walls, should have either one brick
relieving arch turned over the pipe to the full thickness of the brick work or a
concrete lintel or other effective means of relieving the load,
(f) The pipes in and out of manholes should be bedded on mortar and built in as the
brickwork proceeds.
(3) For inspection chambers and manholes constructed of in-situ concrete, the walls should
be of adequate thickness to resist external pressures. Roofing and base of inspection
chambers and manholes are as in (2) above.
(4) (a) Inspection chambers and manholes of precast concrete shall be built in sections.
(b) Materials, dimensions and test methods should comply with the relevant
standards.
(c) The base may be either of precast concrete or in situ concrete similar to that
described as in (2) above.
(d) Where manholes or inspection chambers are constructed wholly above the water
table, joints sealed with cement mortar can be satisfactory. In waterlogged
ground or where the water table is above the base, joints should be made
watertight, preferably using a non-rigid jointing materials such as a mastic sealant
or a rubber ring joint.
© ESA 167
CES 161
(5) Plastics manholes, if employed either as integral bases or as complete chamber units,
should comply with the relevant Ethiopian Standards or equivalent.
(1) An open channel of half-round section should extend the whole length of the inspection
chamber or manhole.
(2) A vertical benching should be formed from the top edge of the main channel to a height
not less than that of the soffit of the outlet. It should be round off to a radius of about
25.0mm and then sloped upwards to meet the wall of the chamber.
(3) (a) Side branches of diameters upto and including 150.0mm should discharge to the
main channel in the direction of flow.
(b) Vertical and side benching should be shaped so as to contain the flow without
permitting fouling and to facilitate rodding of branch drains.
(c) A branch with a diameter of more than 150.0mm should be set with the soffit level
with that of the main drain.
(4) (a) In inspection chambers and manholes of brickwork, precast concrete or in situ
concrete, main and branch channels should be bedded and jointed in 1:3 cement
mortar.
(b) To ensure that the channel and the branch junctions are properly supported, the
bedding and the benching should be laid in a single operation.
(5) Plastics channel sections are available and could be used in a similar manner to
traditional materials, but special care should be exercised to ensure adequate bonding with
the base.
(1) For brick or in-situ concrete manholes, they should be built into the wall at intervals of
between 230.0mm and 300.0mm.
(2) (a) The step irons should preferable be set and staggered in two vertical runs which
should be constant at approximately 300.0mm centres horizontally.
(b) The top step iron should be positioned so that direct access to it by an operator is
practicable and should be fixed not more than 750.0mm below the surface,
depending on the cover and slab arrangement.
(c) The lowest step iron should be fixed not more than 300.0mm above the
benching. Precast concrete manholes should have step irons let in.
168 © ESA
CES 161
(1) If the drop-pipe is outside the manhole, a continuation of the drain should be built
through the manhole wall to form a rodding eye.
(2) A drop-pipe fitted within the manhole should be able to withstand maintenance
operations and have rodding access.
(1) Covers and frames from ductile and grey cast iron, cast steel and precast concrete for
manholes and inspection chambers shall be in accordance with the relevant Ethiopian
Standards or equivalent.
(2) Covers used for manholes within buildings should be airtight and mechanically secured.
6.8.1 Interceptors
(1) (a) Interceptors shall be provided, where necessary, for the proper handling of
wastes containing grease, oil, flammable wastes, sand and other ingredients
harmful to the building drainage system and the public sewer.
(b) Only wasters having a mixture of light and heavy solids or-liquids and solids
having various specific gravities may be treated and then separated in an
interceptor.
(c) The size, type and location of each interceptor shall be approved by the Building
Official.
(2) (a) A grease and oil interceptor (separator) ,when it is deemed necessary, shall be
installed in the drainage line leading from sinks, drains or other appliances in the
following establishments:
© ESA 169
CES 161
(i) Restaurants,
(iii) Cafeterias,
(iv) Clubs or others from which grease and oil can be introduced into the
drainage system.
170 © ESA
CES 161
(b) A grease and oil intercept may not be required for kitchens of private dwelling
units.
(c) An oil interceptor shall be installed in the drainage line or section of the line
where oil or other flammable wastes can be introduced or admitted in the
© ESA 171
CES 161
(3) Sand and heavy-solids interceptors shall be so designed and located as to be readily
accessible for cleaning and shall have a water seal of not less than 150.0mm.
(4) Discharge from commercial laundries, bottling plants and slaughterhouses, which
include rags, buttons, broken glass, feathers and other solids, should be intercepted before
being discharged into the drainage system.
(5) (a) Interceptors shall be so designed that they will not become air bound if closed
covers are used (otherwise their contents might be siphoned).
(6) Each interceptor shall be so installed as to provide ready accessibility to the cover and
means for servicing and maintaining the interceptor in working and operating condition.
(b) A maintenance schedule shall be worked out to this effect alongside the design
proper.
(1) A septic tank installation shall be provided for both settlement of solids and partial
biological treatment of sewage.
(2) The design criteria shall assume that surface water and subsoil water be excluded from
entering septic tanks.
(3) Septic tanks should be watertight so that they permit neither ingress of groundwater nor
egress of sewage to the ground.
(4) Septic tanks could be constructed from bricks, stone masonry, in-situ concrete and large
precast concrete pipes.
(5) Septic tanks could also be prefabricated from steel and plastic materials.
(8) Calculation of the total capacity of septic tanks shall be made on the basis of the
number of persons to be served, water consumption and sludge production per capita and
the hydraulic detention time.
(9) The design of septic tanks shall be such that the discharge of solids in the tank effluent
is kept to a minimum.
172 © ESA
CES 161
(10) The following formula is recommended for general use where dislodging is carried
out at a reasonable number of times per year, two years, etc.
V= sed.p.q/103+u1.ac.p/103 (6.1)
Where:-
p is user population
q is water consumption per capita per day, in litres (see Table 4.4, Section 4).
(11) For rectangular tanks, at least two or three should be used in series either by
constructing two or three separate tanks or by dividing a single tank into two or three by
partitions (see Figure 6-8).
(12) (a) In all cases of (11) above, the compartments should be not less than 1200.0mm
deep below the top water level.
(b) The first compartment should have a capacity of not less than two-third of the
total tank capacity with a length of not less than twice its width and the
subsequent compartments should have a combined capacity of not less than one
third of the total capacity.
(c) In order to facilitate desludging operations, the floor of the first compartment
should have a fall of 1:4 towards the inlet end.
(13) Duplicate tanks, preferably with half calculated capacities could be provided in
parallel.
(14) The design of septic tank inlets and outlets shall be such that they facilitate
introduction of crude sewage and removed of the clarified liquid with the least possible
disturbance of the settled sludge or the surface scum.
(a) An inlet for rectangular tanks of not more than 1200.0mm wide should be a T-
shaped dip pipe not less than the nominal bore of the incoming drain, fixed inside
the tank, with the top limb rising above the scum level and the bottom jimb
extending about 450.0mm below the top water level.
(b) For tanks in excess of 1200.0mm in width, two submerged inlets having inverts at
the same level should be introduced (see Figure 6.8).
(c) A baffle should be provided 150.0mm from the inlet end of the tank, extending
150.0mm below the invert of the inlet pipe and 150.0mm above the top water
level.
© ESA 173
CES 161
(d) Where the incoming drain has a steep gradient, at least the last 12.0m should be
laid at a gradient not steeper than 1:50 in order to minimize turbulence.
(15) (a) The final outlet for tanks which are less than 1200.0mm wide should be by a
100.0mm nominal bore dip pipe fixed inside the tank in a similar manner to the
inlet dip pipe in 14(a) above and 25.0mm below it.
(b) For wider tanks, it is necessary to use a weir outlet extending the full width of the
tank and protected by a scumbcard such as suitable protected timber, plastics or
asbestos cement fixed 150.0mm from the weir and extending 150.0mm above
and 450.0mm below the top water level.
(16) (a) A roof should be provided to a septic tank, in which case it may be wholly or
partially removable and be of concrete or timber.
(b) If fixed, the roof should have adequate access openings, with covers including
those necessary for inspection and cleansing of the inlet and outlet
arrangements.
(17) Where it is not roofed, a septic tank should be provided with a protective fence to
prevent unauthorized access.
(18) (a) Septic tanks should be located as far away as practicable from buildings, water
wells and water reservoirs (underground) to prevent contamination of domestic
water supply and reduce the risk of nuisance in case of malfunctioning; i.e.
overflow through manholes, gas emission through vent pipes, etc.
174 © ESA
CES 161
(1) Where an appropriate sewer is not available and sewage treatment is impracticable,
cesspools, could be provided.
(2) Cesspools should be and remain impervious to ingress of ground or surface water and
to leakage.
(3) Cesspools should be provided only where emptying facilities are available or are
possible to introduce.
(6) Effective storage time shall depend on the population served, the water consumption
and whether there is any infiltration into the foul drains.
© ESA 175
CES 161
(7) (a) A cesspool shall be cylindrical, square or rectangular in plan to suit the condition
of the site.
(b) The depth from the cover of the access opening to the floor of the tank should not
normally exceed 4.0m on a flat site and may need to be further restricted on a
sloping site to limit the suction lift when emptying.
(8) The inlet drain should be provided with access appropriate for the drainage system and
should terminate with the pipe projection about 75.0mm clear of the inside of the wall of the
cesspool.
(10) (a) The access to cesspools should not be less than 600.0mm clear opening to
enable inspection, maintenance or removal of consolidated sludge.
(b) The chamber should be made as sage a place of work as possible and sage
methods of working should be adopted.
(11) (a) The site selected for a cesspool should not be so near to any inhabited building
as to be liable to become a source of nuisance or a danger to health ( a minimum
of 15.0m is desirable) and it is essential that not well, stream, river, spring or
aquifer likely to be used for drinking or domestic purposes is liable to be polluted.
(b) The site of the cesspool should preferably be on ground sloping away from and
sited lower than any existing building in the immediate vicinity.
(c) The prevailing wind direction should be from the buildings served towards the
cesspool.
(d) Adequate means of vehicular access should be provided to the cesspool where
emptying by tankers is envisaged.
(12) (a) When a cesspool is to be abandoned, it shall be left in a condition that is neither
dangerous nor prejudicial to health.
(b) The requirement in (a) above shall be effected by the removal of the remaining
contents and backfilling of the chamber with hardcore or similar stable, non-
compressible material, demolition of the structure within 500.0mm of ground
level, and re-instatement of the ground surface.
(1) A soakaway pit shall be used for discharging effluent into pervious subsoils such as
gravel, sand, chalk, etc at a level above that of the water table.
(2) The pit shall be covered by a slab incorporating an inspection manhole and cover.
176 © ESA
CES 161
(1) In less porous subsoils, a subsurface irrigation system percolation ditches) shall be used
as more suitable alternative.
(2) (a) Percolation ditches should be very carefully designed and should consist of a
system of field drains which should be constructed using porous or perforated
pipes, laid in trenches, with a uniform gradient which should be not steeper than
1:200.
(b)The pipes should be laid on a 150.0mm layer of clean gravel or broken stone
20.0mm to 50.0mm grade and the trenches filled to a level 50.0mm above the
pipe and covered with strips of plastics material or equivalent laid to prevent the
entry of silt.
(c) The remainder of the trench should be filled with normal soil and pipes laid at a
minimum depth of 500.0mm below the surface.
(3) If the level of water table rises to within 1.0m of the proposed invert of the irrigation
system, it is not normally advisable to use subsurface irrigation.
(1) The floor area of a subsurface drainage trench or infiltration area of a soakaway pit, At in
m2, required to disperse effluents from septic tanks shall be calculated from:
Where
(2) For effluents which have received secondary treatment followed by settlement, the area
calculation in (1) above should be reduced by 20%; i.e:
(3) The area determined should be used to calculate either a length of subsurface drainage
or, alternatively, the infiltration area of one or more shallow soakaways.
(b) Areas of undisturbed ground 2.0m wide should be maintained between parallel
tranches.
6.8.4.4 Underdrains
(1) Where underdrains are necessary, drainage trenches should be constructed not less
than 600.0mm deeper than the above trenches and the lower part filled with fine gravel (see
Figure 6-9).
© ESA 177
CES 161
(2) A second system of drainage pipes should be laid on the bottom of the trenches to
covey surplus drainage to an outfall in a surface ditch or water course.
A percolation area typically consists of a system of sub-surface irrigation pipes which allow
the effluent to percolate gradually into the surrounding soil. Biological treatment takes place
naturally in the aerated layers of soil.
Percolation mounds are essentially percolation areas placed above the natural surface of
the ground providing an aerated layer of soil to treat the effluent. Percolation areas should
be designed by the design engineer.
Land drainage pipes should not be used in a percolation trench. Access /inspection pipes
should be fitted to the end of the percolation pipes to facilitate the assessment of the proper
functioning of the percolation area and to facilitate rodding or scouring of the pipes. There
should be a maximum of five trenches attached to each distribution box when designing a
gravity system for a percolation area. On sloping sites the pipework should be installed
parallel to the contour to aid distribution of the effluent. The infiltration pipes should be
inspected before installation to ensure a clean and smooth finish on all cuts and drill holes.
Constructed wetland is the generic term used to describe both (gravel- and sand-based)
horizontal and vertical flow reed bed systems and soil-based constructed wetlands. The
main difference between a constructed wetland and other filter systems is the planting of
vegetation in the media where the thick root mass acts as a pathway for the transfer of
oxygen from the atmosphere to the root zone (rhizosphere). Pumping may or may not be
required for constructed wetland systems depending on the slope of the site and the
wetland configuration. They can be used to provide secondary or tertiary treatment to
effluent from septic tank or tertiary treatment to packaged wastewater treatment systems.
The design and construction of wetlands should comply with the BMP.
This comprises a pump chamber which transfers the partially treated effluent, (generally
from a septic tank), onto the filter at regular intervals. The filter may consist of soil, sand,
peat or other media. A range of configurations may be considered:
(a) An intermittent soil filter system (soil polishing filter is built in);
(b) An intermittent sand filter followed by a polishing filter (may be inbuilt or offset);
178 © ESA
CES 161
Where a pumped distribution system is used, an alarm should be fitted to alert the user to
any malfunction. A polishing filter should be used in conjunction with all intermittent filters.
A polishing filter is a filter system the purpose of which is to provide additional treatment of
the effluent and to reduce pollutants such as micro-organisms, phosphorous and in certain
cases nitrate nitrogen. It also provides for the hydraulic conveyance of the treated effluent
to the ground.
Packaged wastewater treatment systems may be used to treat wastewater from a building
where the site is unsuitable for a septic tank system or they may be used as an alternative
to septic tank systems.
The system should be designed for a minimum hydraulic daily load of 150 l/person/day
based on the number and size of bedrooms and a minimum organic daily load of 60g
BOD/person/day to ensure adequate treatment is provided.
All such systems must have treatment efficiency capable of meeting the minimum
applicable performance effluent standards. Monitoring and maintenance of these systems is
required to ensure that the effluent is treated to this standard. In nutrient sensitive areas,
more stringent performance standards for nitrogen and phosphorous may be necessary.
The sludge storage capacity should be checked with the manufacturer to establish the
necessary frequency of de-sludging. All package wastewater treatment systems should be
provided with an alarm to indicate operation failure.
(a) A greywater recovery system is an installation used to collect, store and treat
greywater to a suitable quality and to distribute it for particular specified
purposes.
(b) Greywater is water originating from the mains potable water supply that has been
used for bathing, washing or laundering clothes.
(d) Where a greywater recovery system is installed the following guidance should be
complied with:
© ESA 179
CES 161
(iii) The maximum stagnation period for greywater water should be 10 days
unless otherwise specified by the manufacturer.
(iv) After 10 days of stagnation, or the period specified by the manufacturer, all
stored reclaimed water (other than in the WC cistern) should be
automatically dumped to the foul drain or sewer;
(2) The work should be protected during all stages of construction and the entry of foreign
matter into any part of the systems prevented.
(i) Tests should be carried out to locate and remedy any defects in
soundness that may exist at the time of construction.
(ii) Such test should take place immediately before the work is covered up so
as to facilitate replacement of any faulty pipes or pipe fittings or to rectify
any joint defect.
(iii) Inspection of the pipeline shall reveal any defects in the support and
bedding.
180 © ESA
CES 161
(i) Testing and inspection should take place immediately before handover
when all relevant work been complete.
(a) Before any tests are applied, attention should be given to the safety of the
operatives and other persons involved in the testing operation.
(b) It is essential that proper means of access should be provided to the area of work
and the sides of any trench or excavation in which work is to be tested
adequately supported and free from hazards.
(c) All obstruction, debris and superfluous matter should be removed from sections
of pipeline, inspection chambers, manholes, or similar underground chambers
and they should be flushed out before testing.
(d) Before any tests are applied, a disc or ball-type profile testing device should be
passed through all drains and private sewers between inspection chambers,
manholes or other suitable points of access and through all accessible branch
drains.
(e) Water tightness: After laying drains and combined drains, including any
necessary concrete or other haunching or surrounding and backfilling, all pipes
up to 300 mm diameter should be capable of withstanding a final water test to a
© ESA 181
CES 161
pressure equal to 1.5 m head of water measured above the invert at the head of
the drain, or an air test ensuring that head of water on a manometer does not fall
by more than 25 mm in a period of five minutes for a 100 mm water gauge test
pressure and 12 mm for a 50 mm water gauge test pressure.
Where the drain is water tested using a stand pipe of the same diameter as the drain, the
section of the drain should be filled and left to stand for two hours and topped up.
The leakage over thirty minutes should then be measured and should not be more than
0.05 litres for each metre run of drain for a 100 mm drain - a drop in water level of 6.4
mm/m, and not more than 0.08 litres for a 150 mm drain - a drop in water level of 4.5
mm/m.
To prevent damage to the drain, the head of water at the lower end of the section should
not be more than 4 m and it may be necessary to test a drain in several sections.
(i) A water test shall be applied to every drain and to any section of an
existing drain that has been repaired
(ii) The head or water shall be at least 1.5m at the high end of the drainline
and not more than 4.0m at the lower end.
(iii) The test shall be applied by Sealing all openings except the top of the
section of the drain to be tested, filling the drain with water to the highest
level in that section; and maintaining the water at this level for a period of
2.0hrs, topping up as necessary.
(b) Interpretation of results: A change in water level in the test apparatus could be
due to one or more of the following causes, which shall be rectified or appropriate
allowances made for in the testing procedure:
182 © ESA
CES 161
(c) Air test: an air test may be applied to the completed work, either in its entirety or
in sections, in accordance with the following procedure:
(i) The air pressure test shall consist of applying a pressure of 3.0m water
head to the drain and holding this pressure for 3.0min to allow the air
temperature to stabilized.
(ii) The air supply shall then be shut off and the time taken for the pressure in
the pipe to drop from 2.5m to 2.0m head of water shall be measured.
(iii) The drain is considered to have passed the test if the time taken is greater
than 90.os for pipes of size DN225 or smaller, or 180.0s for pipes of sizes
DN300 and DN375.
(a) The design and construction of ancillary work such as inspection chambers,
manholes, oil and grease separators, sumps, septic tanks, cesspools and similar
underground structures should ensure a high level of resistance to water
penetration, both inwards and outwards.
(b) Where construction work has been effectively carried out, visual inspection may
be sufficient for acceptance without testing.
(c) Inspection should always be made to reveal any possible weaknesses in the
structure and particular attention should be paid to the following:
(i) All outlets, inlets and other connection points of the chambers or structures
should be fitted with plugs and filled with clean water up to the underside
of the covers.
(ii) The water is allowed to stand for up to 8.0hrs for absorption topping up the
level as necessary.
(iii) The criterion for acceptance (at this stage) should be that no appreciable
flow of water penetrate the structures.
(iv) Where water can be observed issuing from the outside face of the
structures at an identifiable point or points, such leakage should be
stopped.
© ESA 183
CES 161
(1) Drainage systems should be inspected at regular intervals and, where necessary,
thoroughly cleaned out at the same time. Any defects discovered should be made good.
(2) The following operations should be carried out during the periodic cleaning of a drainage
system:
(a) Covers of inspection chambers and manholes should be removed and the sides,
benching and channels cleaned.
(b) Main and branch drains should be cleaned and, afterwards, should be flushed
with clean water. Any obstructions found should be removed and not flushed into
system.
(3) The drainage system should be cleaned, as appropriate, using one or more of the
following methods:
(a) Rodding:
(ii) It is important that correctly designed proprietary ends used on the rods.
(iii) Makeshift devices attached to the ends of rods should be avoided as they
are not as effective as the correctly designed article and could become
detached and create a blockage which would be difficult to remove.
Furthermore, it is possible that such devices could cause damage to the
pipeline.
(b) High pressure jetting techniques could be suitable for use with all currently
available pipe materials and should also be considered.
(c) Shock waves could be induced and transmitted by water to the point of blockage,
where the pipe is surcharged or can be filled with water from the blockage to a
point where the shock wave is introduced.
Pipes, fittings and joints shall comply with the relevant Ethiopian Standards or equivalent
and shall be acceptable upon the approval of the Building Official.
184 © ESA
CES 161
7.1 Scope
(1) The materials to be used shall be selected to ensure satisfactory service for the life of
the installation.
7.2 Materials
(1) Factors to be taken into consideration for compliance with (1) above shall include:
(a) Cost,
(b) The nature of the ground and the possibility of chemical attack there from,
(d) The possibility of abrasion by solids in the flow, or of chemical attack of materials.
(1) Materials and components for storm water drainage should comply with the relevant
Ethiopian Standards or equivalent and shall be acceptable on the approval of the Building
Official.
7.3 Joints
(1) Gutters and downpipes should be jointed in accordance with good engineering practice.
(2) Manufactures’ instructions on the methods of jointing should be strictly following where
available.
7.4 Design
7.4.1 General
When designing drainage systems for roofs, paved and unpaved areas, it is normally
impracticable to guard against very infrequent, extremely heavy rainfall events. The
designer should aim to achieve safe evacuation of floods of 10 year return period within
reasonable time.
7.4.2 Run-off
(1) The effective catchment area of a sloping or vertical surface depending upon the angle
of descent of the rain. For purposes of design it may normally be assumed that the rain falls
at angle of one unit horizontal to two units vertical, and that its direction is such as to
produce the maximum rate of run-off to each length of gutter; this is the basis of the
recommendations described in (2) to (4).
(2) (a) The effective catchment area, Ae, for flat roofs of a freely exposed horizontal
surface is equal to the plan area of the surface (see Figure 7.1 (a)).
© ESA 185
CES 161
(b) Where slopping or vertical surface drains to a flat roof, paved or unpaved area,
the additional area of catchment should be calculated as described in (3) and (4)
below.
(3) (a) The effective catchment area, Ae, for slopping roofs of a freely exposed surface
draining to an eaves or a parapet wall gutter is equal to the plan area of the roof
plus half its maximum area in elevation (see Figure 7.1 (b). for a valley gutter,
one side of the roof will tend to be exposed to the wind and the other side will
tend to be sheltered; the method of calculating the effective catchment area is
illustrated in Figure 7.1 (c). Run-off from any vertical walls should be allowed for
(see (4) below).
(b) The effect of wind can be appreciated by noting that, compared to a horizontal
roof of the same plan width, the run-off will be 25% greater if the roof has a slope
of one unit vertical to two horizontal, and 50% greater if it has a slope of one unit
vertical to one unit horizontal.
(4) (a) Wind-driven rain will cause run-off from walls and other vertical surfaces that are
freely exposed to the wind, but where the run-off is to paved area, run-off from
vertical surfaces will normally need to be considered only where flooding of the
paved area cannot be tolerated.
(b) For a single wall, the effective catchment area, Ae, should be taken as half the
exposed vertical area of the wall. Where two or more walls form an angle of bay,
the direction of the wind should be assumed to be such that the walls, considered
together, present the maximum vertical area to the rain. The method of
calculating Ae is illustrated in Figure 7.2. Surrounding walls are of unequal height.
In the latter case the value of Ae should be increased by half the area in elevation
by which the higher wall exceeds the lower wall.
(1) Run-off from roofs, paved areas, roofs and vertical surfaces should be calculated
assuming that the surfaces are impermeable; that is, run-off coefficient value C is taken to
be 1.0. Run-off coefficient values (c) for unpaved areas should be taken from practices
conforming to local conditions. C values for some unpaved areas are given in Table 7.1.
(7.1)
Where,
I is the rainfall intensity (in mm/h) for the minimum average recurrence interval in
years and time of concentration.
186 © ESA
CES 161
IDF curves covering Ethiopia are given in consecutive Figure 7-3 (A to D). If long-term
hourly rainfall data exists for a given location, specific IDF curve shall be used in
conjunction with the regional IDF curve.
(a)
(b)
(c)
© ESA 187
CES 161
Figure 7-2 Calculation of effective catchment area, Ae, for vertical surfaces
188 © ESA
CES 161
© ESA 189
CES 161
Intensity-Duration-Frequency
Regions A1 & A4
Figure 5-9
400,0
350,0
300,0
250,0 2 Year
Intensity, mm/hr
5 Year
10 Year
200,0 25 year
50 Year
100 Year
150,0
100,0
50,0
0,0
0 10 20 30 40 50 60 70 80 90 100 110 120 130
Duration, min.
Intensity-Duration-Frequency
Regions A2 & A3
Figure 5-10
400
350
300
250 2 Year
Intensity, mm/hr
5 Year
10 Year
200 25 year
50 Year
100 Year
150
100
50
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130
Duration, min.
190 © ESA
CES 161
Intensity-Duration-Frequency
Regions B, C & D
Figure 5-11
400.0
350.0
300.0
2 Year
r 250.0
h
/ 5 Year
m
m 10 Year
, 200.0
ty
i 25 year
s
n 50 Year
e
t
n
I 150.0 100 Year
100.0
50.0
0.0
0 10 20 30 40 50 60 70 80 90 100 110 120 130
Duration, min.
© ESA 191
CES 161
Table 7-1 Recommended Runoff Coefficient C for Various Selected Land Uses
Description of Area Runoff Coefficients
(1) A roof drainage system generally comprises the following three parts:
(a) The gutter or channel that collects the flow from the roof;
(b) The outlet into which the flow from the gutter or channel discharges;
(c) The pipework (downpipe) that conveys the flow from the outlet to the drainage
system.
(2) The three parts of the drainage system in (1) above can be designed separately if the
outlet and the pipework (downpipe) are made large enough for the flow to discharge freely
from the gutter; this is the basis of the method of design described in 7.4.3.2 through
7.4.3.5. Occasionally, it is necessary to use outlets or pipe work that are smaller than those
required by this method. When this occurs, the capacity of the gutter is less than the
capacity that it has when it discharges freely; consequently another methods of design
becomes (see Section 7.4.3.2 and Annex G).
192 © ESA
CES 161
(3) Gutters and downpipes may be omitted form a roof at any height provided that is has an
area of 6.0m2 or less and provided that no roof or other surface drains onto it. Consideration
may be given to the omission of gutters and downpipes from tall structures where run-off
would be dispersed before reaching the grounds; such run-off should be directed so as to
avoid undesirable pattern, staining and splashing of windows.
(1) The method of design described subsequently (another method of design satisfactory to
the Building Official may also be used) is based on the following assumptions:
(a) The gutter slope is not steeper than 1 in 350 (i.e, it is normally level). A gutter laid
to fall will have a somewhat higher capacity, but this increase should be viewed
as an additional factor of safety.
(c) The outlets are large enough to allow the gutter to discharge freely.
(d) The distance between a stop-end and an outlet is less than 50 times the
upstream water depth, or the distance between two outlets is less than 100 times
the upstream water depth.
(2) Eaves gutters should, wherever possible, be designed to discharge freely. If the length
of an eaves gutter exceeds the limits given in (1d) above, it is necessary to reduce its
design capacity. Methods of designing gutters that can’t discharge freely or that exceed the
limits in (1d) above are given in Annex G.
(1) (a) After the run-off from roof of a building has been calculated, its direction of flow in
the gutter is determined by the position of the outlets. If a length is served by two
outlets, the flow will split equally between them even if the flow does not enter the
gutter uniformly along its length.
(b) Figure 7-4 (a) shows how the flow at each outlet in a length of gutter can be
calculated. If a strong wind blows along a gutter, the flow may be increased in
that direction.
(c) Figure 7-4(b) and 7-4(c) show how the capacity of a gutter can be used most
efficiently. In Figure 7-4(b), the outlets split the gutter into three sections, of which
the middle one collects half the flow and discharges at both ends; if the total flow
from the roof is Q, then each section of the gutter needs to have a discharge
capacity of Q/4.
(d) Figure 7-4 (c) shows a less efficient arrangement in which the outlets are
positioned at the ends of the gutter; in this case, a large gutter is required since
each section needs to have a discharge capacity of Q/2.
(2) (a) Although there is an optimum arrangement for the outlets(see (1) above), their
number and position will often be determined by the layout of the building or other
architectural factors.
© ESA 193
CES 161
(b) If for any reason internal downpipes are fitted, underfloor drainage should be
avoided where possible.
(c) Outlets for gutters should be located, where possible, near each angle; i.e, where
there is a change in direction of flow.
Note: For the same total flow, the gutter in (c) requires twice the capacity of the gutter in (b).
(1) The shape of valley gutters may often be chosen so as to conform to the cross-sectional
shape of the roof. A satisfactory shape of valley gutter is obtained if the sides are slopped
at the same slope as the roof up to a height that gives the required flow capacity, and if the
194 © ESA
CES 161
sides are then turned vertically upward in order to provide the required amount of free-
board.
(2) The fall (slope) to which the gutter is laid will depend on structural considerations and on
the material used for the gutter or gutter lining. The method of design described in (4) below
assumes that the gutter is level; a gutter laid to fall will have a somewhat higher capacity;
but this increase should be viewed as an additional factor of safety.
(3) (a) The overall depth of a gutter should be greater than the depth needed to give the
design capacity so as to prevent it from being over-topped by splashing or by
waves produced by strong winds.
(b) The amount of free-board should be taken as two-fifth of the maximum depth of
flow in the gutter, with an upper limit of 75.0mm.
(4) (a) In a level gutter, the depth of flow is greatest at the upstream end and decrease
towards the outlet. Subtracting the allowable free-board from the overall depth of
the gutter, therefore, gives the design depth of flow at the upstream end u, the
discharge that produces the depth u is the design capacity of the gutter. A level
gutter attains its maximum capacity when the outlet is large enough to allow the
gutter to discharge freely. When this occurs, the depth of the flow in the gutter
just upstream of the outlet is equal to the critical depth c.
(b) The ratio of the depth of flow at the upstream end of the gutter, u, to the critical
depth at the downstream end c, depends only upon the cross-sectional shape of
the gutter provided that the requirement of 7.4.3.2 are met. The effect of flow
resistance is normally small so that the depth of the gutter does not affect the
value of u/ c unless the gutter is longer than the limit given in 7.4.3.2(1d). c can
be read from Figure 7.5 once the upstream flow width , Bu, and the sloe width, Bs
(see Figure 7.4) of the gutter are determined. The discharge capacity, Q,
corresponding to the critical depth, c, can be calculated directly from Equations
(G-1) of Annex G if the cross-sectional shape of the gutter is known. The
calculated value of Q assumes that the outlet is large enough to allow the gutter
to discharge freely. The method of determining the capacity of trapezoidal gutters
with restricted discharge is described in G.2, Annex G.
(1) (a) Factors affecting the number and position of required outlets are detailed in
section 7.4.3.3. Two types of gutter outlets may be used. The outlet pipe may
either be connected directly to the sole of gutter, or may be connected to a box-
receiver into which the flow from the gutter first discharges.
(b) Box-receivers are preferable to outlets in the sole of the gutter because they
ensure that the flow discharges freely from the gutter and may allow smaller
outlets to be used. The use of box-receivers is recommended for valley, parapet
and boundary wall gutters
© ESA 195
CES 161
(c) The design of structural framework should take account of any internal box
receivers (see Figure 7-7 (b) or outlets in the sole of the gutter).
(2) (a) The dimensions of a box receive need to be larger enough to allow the flow to
discharge freely from the gutter to which it is connected. Typical designs for box-
receivers are shown in Figure 7-6.
(b) The minimum width of the box should not be less than the width of the flow in the
gutter at a depth equal of half the overall depth of the gutter, g. If the flow enters
the box-receiver from one direction (see Figure 7-7(a)), the length of the box in
the direction of flow should be not less than 0.75 g. If the flow enters the box-
receiver from opposite directions (see Figure 7-7 (b)); in the later case, the length
of the box should be not less than 1.5g. the top of the box should be level with
the top of the gutter except where the box is external to the building (see Figure
7.6 (a)); in the latter case, the outer edge of the box may be lowered to act as an
emergency overflow.
196 © ESA
CES 161
© ESA 197
CES 161
ES 3960:2015
(c) The depth of the box below the sole of the gutter should not be less than
h+25.0mm, where h is the depth of the water above the outlet. The method of
designing such box-receivers is described in G.4, Annex G.
(3) (a) At small depth of flow, the perimeter of an outlet (outlet in box-receiver) to a
downpipe acts as a weir while at large depths of flow the outlet acts as an orifice.
An outlet with a rounded edge has a large capacity than a sharp- edged outlet
(see Figure 7-8 (a)) having the same size of throat. A suitable type of round-
edged circular outlet is shown in Figure 7-8(b); in terms of its discharge capacity,
this type of outlet has an effective diameter,D, equal to 0.99 times its top
diameter, Do.
(b) Suitable type of tapered outlets allow smaller size of downpipes to be used
without reducing the capacity of the outlet. A tapered outlet with a top diameter Do
will have the same discharge capacity as a sharp-edged outlet of diameter Do
provided that the diameter of the throat is not less than 2/3 Do and the transition
is gradual over a distance not less than Do (see Figure 7-7(c)). Equations relating
the depth of water above an outlet, h, to the size of the outlet and the discharge,
Qi, passing through it are given in G.4.1 Annex G. The use of a grating over an
outlet will reduce its capacity; the method of designing grated outlets is described
in G.4.2, Annex G.
(4) If a downpipe is connected directly to the sole of a valley, parapet or boundary wall
gutter, it is necessary to determine whether the outlet (downpipe) is large enough to allow
the flow to discharge freely from the gutter. As a rough guide, the effective diameter of an
outlet in a rectangular gutter needs to be at least three- quarters of the width of the flow to
ensure free discharge. The method of determining whether the gutter discharge freely or
not is described in G.4.3. Outlet connected to the sides of gutter are inefficient and their use
is not recommended.
7.4.3.6 Downpipes
(1) (a) The size of circular downpipes (outlets) shall not be less than diameter 60.0mm
and that of spouts not less than diameter 50.0mm.
(b) The length of the shorter side of rectangular downpipes (outlets) shall not be less
than 60.0mm.
198 © ESA
CES 161
Di > 2Do/3
(2) Tapered outlet (vertical pipes) for valley and parapet wall gutters may be used to reduce
the size of the downpipe to not less than two-thirds of the top diameter of the outlets (see
7.4.3.5(3). Pipes sized according to these criteria will tends to flow full so that joints
between the downpipes and the gutter or box receivers should be sealed.
© ESA 199
CES 161
(3) (a) Horizontal lengths of pipe should, where possible, be given a small fall to prevent
the ponding of water.
(b) Long runs of pipework should be designed according to the standard engineering
principles for steady flow in pipes.
(c) All joints on horizontal pipes should be sealed, and access for inspection and
rodding should be provided in accordance with 7.5.2(2).
(b) Falls are required in both cases of (a) above and can be provided by the
construction of the roof of by screeding.
(c) In general, an economic scheme will include few outlets; but the number needed
may often be determined by the plan of the roof rather than by the area to be
drained.
(3) On a roof laid to falls, a water depth of upto 30mm may be acceptable if it is confined
t o relatively small area around the outlets or to a value which may be allowed by
manufacturers’ of water-roofing materials (see 7.4.3.7(1)), whichever is smaller.
(4) (a) Run-off from a flat roof may be discharged at the edge of the roof into;
(b) The eaves gutters and their outlets should be designed in the same way as in
section 7.4.3 and 7.4.3.5.
(c) The entrance to a chute acts as a weir and the width that is required can be
estimated from Equation (G-6) in G.4.1, Annex G in which Lw is the width of the
chute (in mm) and h is the head of water above the invert of the chute.
(5) (a) Run-off from a flat roof may be discharged within the perimeter of the foot into:
200 © ESA
CES 161
(b) Roof channels and their outlets should be designed in the same way as in (4)
above.
(c) Sumps and roof outlets normally act as weirs, and should be sized so as to limit
the depth given in (3) above. The depth of a sump is determined by the capacity
of the outlet that drains it, and should be not less than h+25mm where h is the
depth of water above the outlets.
(6) The procedure given in (a) through (e) hereunder may be used for determining the
required dimensions of a sump:
(a) Locate the position of the sump and calculate the rate of run-off from the
catchment areas that is drains. Where possible, the sump should be positioned
centrally.
(b) Calculate the total rate of run-off Q (in l/s) assuming that the roof is impermeable.
(c) Calculate the length of the wetted perimeter of the sump, Lw, using the
appropriate equation in G.4.1, Annex G, after selecting the design depth of water
on the roof (see section 7.4.3.7(1)). The shape of the sump should be such that
the length of each side is approximately proportional to the flow that it receives.
(c) Vertical pipe with bellmouth and grating (d) Vertical pipe either from channel or box-receiver
© ESA 201
CES 161
(e) Calculate the head h required to pass the total discharge, Q, through the outlet
using the appropriate equation in E.4.1; if the outlet is covered by grating see
G.4.2, Annex G.
(f) The depth of the sump above the level of the outlet should be a minimum of
h+25mm.
(g) The downpipe connected to the outlet should be designed in accordance with the
provisions of 7.4.3.6.
(7) (a) Ungrated roof outlets shall be designed using the appropriate equation in G.4.1,
Annex G.
(b) The capacities of grated outlets are best determined experimentally; if suitable
measurements are not available, the method described in G.4.2., Annex G, shall
be used.
(1) Appurtenances for the drainage of unpaved areas include unlined or lined channels,
storm water drains, etc.
(2) Run-off from unpaved areas should be prevented from draining onto paved areas unless
appropriate measure is taken to protect the drainage system from blockage.
(3) Design flow rates from unpaved areas should be calculated as described in 7.4.2.2.
(4) The design of drainage appurtenances for unpaved areas should be made in
accordance with good engineering practice.
(i) A paved channel or series of paved channels that collect the run-off from
the paved area,
(ii) Inlets or gullies (kerb-inlets or grated inlets (see Figure H-2, ANNEX H)
situated at intermediate points along the channels,
(iii) Terminal inlets or terminal gullies set at low points in the paved area or the
collecting channel,
202 © ESA
CES 161
(b) The design method of collecting channels and inlets in described in ANNEX H.
(Other methods of design satisfactory to the Building Official are also
acceptable.)
(2) (a) The irregular shape of the areas between buildings will often determine the
number of inlets that are required rather than the permissible area that can be
drained to an inlet. Small paved areas may be drained to central terminal inlets.
Larger areas can be split into panels with central terminal inlets, or may more
conveniently be drained by collecting channels with intermediate and terminal
inlets.
(b) The levels of a paved area should be determined in relation to the levels of the
following features:
(c) Water drainage from a paved area should not be allowed to concentrated along
the side of the building.
(d) Where the general ground levels might cause concentration of drained water in
(c) above, a reverse fall should be applied to a narrow strip around the building
so that the water is kept away from the walls.
(f) The drainage system for road entrances and approaches of public roads should
be arranged so as to prevent surface water from flowing across the entrance,
either to or from a public road.
(3) (a) The general layout of the stormwater drainage system should first be decided
and the total area then split into suitable sub-areas. The design flow from each
sub-area is then calculated as described in 7.4.2.2.
(4) (a) Intermediate inlets (kerb inlets or grated inlets (gully-gratings) are generally used
where:
© ESA 203
CES 161
(i) Kerb-inlets generally have a lower capacity than grated inlets of the same length,
but are less liable to damage by vehicles. The design of intermediate inlets is
given in ANNEX H.
(ii) Terminal inlets (terminal gullies) are situated at low points in the paved area or
collecting channel. The capacity of a terminal inlet is normally determined by the
depth and area of ponded water that can be permitted at the low point. Such
inlets should be generously sized as they are more likely to cause flooding than
intermediate inlets. The method of determining the capacity terminal inlets is
given in H-7, ANNEX H.
(a) Shall be provided to remove contamination, generally and sand or silt, from
stormwater prior to discharge to the storm water drainage system.
(b) Shall be adequately sized depending on the use of the area, the type of surface
and frequency of cleaning. However, a minimum depth of 500.0mm below the
invert of the outlet storm water drain shall be provided.
7.5 Installation
7.5.1 Gutters
(1) Eaves gutters, especially when fixed on rafter brackets, shall be given a fall to allow
from any settlement and recommended rate of fall is 1 in 350.
(2) Gutters shall be adequately supported so as to prevent sagging and ponding, and care
shall be taken that there is no sideways tilt.
7.5.2 Downpipes
(c) Downpipes that require painting should be fixed at least 30.0mm clear of the
building structure using spacers or projecting ears.
(2) One or more cleaning eyes (cleanouts) for access and rodding should be provided at
appropriate points in horizontal runs of pipe and on long vertical pipes. This is particularly
important at the foot of each down pipe and at changes in direction.
204 © ESA
CES 161
(3) It is essential that downpipes are not encased in concrete columns or structural walls
and it is important that downpipes in castings or ducts are accessible for maintenance and
replacement.
(b) Where downpipes discharge on to lower roof, especially onto a flat roof, it is
advisable to reinforce the covering of the flat roof at the point where the rainwater
shoe discharges onto it because of the excessive localized wear that can occur
under such conditions.
(1) Storm water drains shall be laid in accordance with Section 6.5.
(2) Electrical cables, gas pipes, foul drains, water services, etc, installed proximity to storm
water drains shall comply with the provisions of Section 6.5
(3) (a) Storm water drains shall be installed in a manner that provides protection against
mechanical damage and deformation.
(4) The provisions for excavation, bedding and back filling shall be as in Section 6.6
(5) (a) Storm drains shall be joined to each other by means of:
(b) Where storm water drains on grade and a vertical downpipe connect, the
upstream angle shall not be greater than 600.
(1) The design of storm water pits and inlet pits shall be in accordance with the relevant
provisions in Section 6.7.
(2) Inlet pits shall be provided with inlets in appropriate locations (see 7.4.4.2(1)).
(3) Inlets bars or gratings shall be designed and installed to withstand external pressures
(e.g. vehicle), and shall be adequately spaced in accordance with good engineering
practice.
7.5.5 Inlets
(1) Inlets shall be installed at intermediate and terminal locations (see 7.4.4.2 (1)) to permit
the entry of storm water to inlet pits.
© ESA 205
CES 161
(2) Inlets bars or gratings shall be designed and installed to withstand external pressures
(e.g. vehicle), and shall be adequately spaced in accordance with good engineering
practice.
7.6.1 Inspection
(1) The work should be visually inspected during installation to check compliance with the
specification and design.
(2) On completion of the installation, all aboveground and underground installations should
be inspected to ensure that no obstructions are present.
7.6.2 Testing
(1) (a) Each new, repaired or altered section of an internal gutter and/or internal
downpipe, when plugged and filled with water to the immediate upstream
overflow level for not less than 5.0min, shall be free from leaks.
(b) External downpipes and gutters should be tested as in for the corresponding
internal elements in (a) above where necessary.
(2) Each new, repaired, or altered section of a storm water drain shall be subject to either a
water test or an air test. The testing method shall be as described in Section 6.9
7.6.3 Maintenance
(1) (a) Gutters, downpipes and gratings should be inspected and thoroughly cleaned
before and after every rainy season, or more often if the building is in or near
dusty area, or is near to trees, or may be subject to extremes of temperature.
(b) Inlet pits, channels and storm water drains should be inspected and cleaned out
regularly. The frequency of inspection and cleaning will need to be based on local
experience. Defects should be remedied as soon as possible after being noted.
All ferrous metals require protection against corrosion and, if not supplied with an adequate
protective coating, they should be painted.
206 © ESA
CES 161
8.1 General
8.1.1 Scope
(1) Efficient collection and disposal of domestic garbage from a building or activity area is of
significant importance to public health and environmental sanitation and, therefore, an
essential part of the construction of the built in environment.
(2) The provisions relating to solid waste management given in 8.2 are applicable to wastes
in general, and specifically exclude the hazardous chemical wastes and bio-medical waste.
(1) Waste reduction is achieved by reusing some waste items, recycling selected materials
and composting of green/organic/biodegradable waste. In most of this service providers are
involved. However, the impact of waste reduction on collection and disposal services is
highly increased when waste is segregated at the source through the people, the waste
producers.
(2) Reduce: Waste prevention, or "source reduction," means consuming and throwing away
less. It includes:
(b) seeking products and packaging that are as free of toxics as possible;
(c) redesigning products to use less raw material in production, have a longer life, or
be used again after its original use.
(3) Source reduction actually prevents the generation of waste in the first place, so it is the
most preferred method of waste management and goes a long way toward protecting the
environment.
(4) Reuse: Reusing items by repairing items, donating items to charity and community
groups, or selling items; also reduces waste. Reusing products, when possible, is even
better than recycling because the item does not need to be reprocessed before it can be
used again.
Ways to Reuse: Reusing plastics, refilling bottles, using cloth napkins or towels, donating
old magazines or surplus equipment, especially to schools, reusing boxes, turning empty
jars into containers for leftover food, purchasing refillable pens and pencils.
(5) Recycle: Recycling turns materials that would otherwise become waste into valuable
resources. It generates a host of environmental, financial, and social benefits.
(6) Materials like glass, metal, plastics, and paper can be collected, separated and sent to
facilities that can process them into products.
© ESA 207
CES 161
8.2.1.1 General
Refuse chute system is a convenient and safe mode of collection of domestic solid wastes
from buildings exceeding 3 storeys. The internal diameter of the chute shall be at least 300
mm. The access to the refuse chute shall be provided from well ventilated and well
illuminated common corridor or lobby and preferably it should not be located opposite or
adjacent to entry of individual flats or lift.
Opening, with top or bottom hinged shutters with appropriate lockable latch, shall be
provided form convenient accessing of the refuse chute by users.
The collection chamber may be located in ground floor or basement level, provided
appropriate arrangement is made for:
(a) drainage of the collection pit by gravity flow to ensure its dryness,
(b) an appropriate ramp access is provided for convenient removal of garbage from
the collection pit, and
(c) satisfactory ventilation for escape of gas and odor. The floor of the chamber shall
be provided with drainage through a 100 mm diameter trap and screen to prevent
any solid matters flowing into the drain and the drain shall be connected to the
sewer line. The floor shall be finished with smooth hard surface for convenient
cleaning. The height of the collection chamber and vertical clearance under the
bottom level of garbage chute shall be such that the garbage trolley can be
conveniently placed. The collection chamber shall be provided with appropriate
shutter to prevent access of all scavenging animals like the cattle, dogs, cats,
rats, etc.
The chute may be of masonry or suitable non-corrosive material. Further the material
should be rigid with smooth internal finish, high ductility and alkali/acid resistant properties.
208 © ESA
CES 161
The size of the garbage trolley shall be adequate for the daily quantity of garbage from a
chute. For working out quantity of garbage, a standard of approximately 0.75 kg/person
may be taken.
8.2.1.6 Dumb-Waiter
In high rise buildings with more than 8 storeys, electrically operated dumb-waiters may be
used for carrying domestic garbage in packets or closed containers. For handling of
garbage by dumb-waiters in a building, a garbage chamber shall have to provide either at
ground floor or basement level and the provisions of garbage collection chamber for chute
as given in 8.2.2 shall apply.
The shutters for dumb-waiter and garbage collection chamber shall be provided with
shutters with same consideration as in the case of garbage chute. However, the dumb-
waiter shall be made child-proof.
Before feeding the garbage to compost pits the following objects need to be removed:
These separated items shall be handled separately, and may be scrapped or recycled, etc
as appropriate.
Vermi-compost treatment shall be provided to the organic wastes in composting pits located
in shade. The pits shall be used to receive the garbage in a predetermined (periodic) cyclic
order. (For example 5 pits to receive garbage in 5 days and these 5 pits together accepting
daily load of garbage.) The gross area of the composting pits may be about 0.1 m² per
person.
(1) The site for vermi-comporting shall be enclosed from all sides with appropriate fencing
(for keeping scavenging animals away) and provided with a small door for accessing the
enclosed premises.
(2) Composting pits shall be constructed either under the shade of trees (except New tree)
or created by sheeting or shade net so as to keep the pits under shade. The pits shall be
easily accessed for convenient shifting of garbage from trolleys carrying garbage.
© ESA 209
CES 161
(3) The composting pits shall be made in a manner that the pits do not have the risk of
inundation by water. This may be achieved by appropriately raising the base level of the pit
and providing weep holes from sides. Height of side walls of compost pits need to be 0.6 m
to 0.75 m high. The bottom of the pit without any lining is preferred.
(4) Initiation of composting pits shall be done by providing a 75 mm thick layer of cow dung
(fresh or partially decomposed) spreading 1 kg of vermin-compost and covering it with 75
mm to 100 mm thick layer of dry leaves/grass, etc and sprinkling of water and allowing to
decompose naturally for about 10 to 15 days.
(5) Sorted garbage free from inert and toxic matters shall be applied in the composting pit
in layers of 75 mm and spread, and covered with a layer of 75 mm thick dry leaves followed
by sprinkling of water.
(6) The compost may be removed from the bottom of the compost pit after intervals of 3 to
6 months. The compost so made may be used in appropriate horticultural and related
applications.
8.3.1 Purpose
Refuse chute system is provided in multistoried buildings for transporting and collecting in a
sanitary way the refuse from floors at different heights. The refuse is received from the
successive floor through the inlets located on the vertical system of pipes that convey
refuse through it and discharge it into the collecting chamber from where the refuse is
cleared at suitable intervals.
8.3.2 Components
This system has got three functionally important components, namely, the chutes, the inlet
hopper and the collection chamber.
(1) The chute may be carried through service shafts meant for carrying drainage pipes.
However, the location shall be mostly determined by the position of the inlet hopper and the
collecting chamber that is most convenient for the user. It should also be considered to
locate the chute away from living rooms in order to avoid noise and smell nuisance.
(2) In individual chute system, the inlet hopper shall be located in the passage near the
kitchen and in the common chute system towards the end of the common passage. Natural
ventilation should be adequate to prevent any possible odor nuisance. There should be
adequate lighting at this location. For ground floor (floor 1), the inlet hopper may be placed
at a higher level and a flight of steps maybe provided for using the same.
8.3.3 Requirements
Requirements in regard to the design and construction of refuse chute system shall be in
accordance with good practice (See Annex I).
210 © ESA
CES 161
ANNEX A
(a) I/We request that one connection be granted for the whole of the premises.
(b) I/We request that separate connections may be granted for each floor and I/we
undertake to pay the cost of the separate connections.
(c) My/Our probable requirements for trade purpose are . . . . . . . . . . . . . . . . liters per
day and for domestic purposes are . .. . . . . . . . . . . . . ... ...liters per day.
(d) Our existing supply is . . . . . . . . . . . . . . . . . . . ..liters per day. Our additional
requirement of supply is . . . . . . . . . . . . . . . . . . . . ..liters per day.
(e) The details as regards proposed additions and alterations in fittings are as follows:
....................................................................
..
....................................................................
..
Notes:
(2) The application should be signed by the owner of the premises or his constituted attorney and shall be
countersigned by the licensed plumber.
© ESA 211
CES 161
ANNEX B
Certified that I/we have completed the plumbing work of water connection No …..................
for the premises as detailed below. This may be inspected and connection given.
City.......................Sub-City ...........................District……………….House
No………………….
Existing water connection No. (if any)
......................................................................................
Owned by: ...................................................................
Owner’s address: ....................................................................................
....................................................................................
Applicant’s full name: .......................................................
Dated .....................................
Address
............................................................................................................................................
Situation
...........................................................................................................................................
Size of main ..................................on .........................
Street..........................................................................
Where main is situated ...............................................
Size of service pipe ..........................................................................
Size of ferrule ..........................................................................
No. of taps ................................................... No. of closets....................................................
No. of other fittings and appliances ........................................................................
Road cutting and repairing fee ..........................................................................
Certified that the communication and distribution pipes and all water fittings have been laid,
applied and executed in accordance with the provisions of bye-laws, and satisfactory
arrangements have been made for draining off waste water.
Connection will be made
on.............................................................................................................
Date.......................... The
Authority................................................................................
……………………………………………………………………
……………………………………………………………………..
……………………………………………………………………..
212 © ESA
CES 161
ANNEX C
Note: The application should be signed by the owner of the premises and shall be countersigned by the
licensed plumber.
219
© ESA 213
CES 161
ANNEX D
214 © ESA
CES 161
© ESA 215
CES 161
(c) Distance of nearest manhole on sewer from the point at which the drain
leaves the premises .. .. ... .. .. .. ... .. .. ... .. .. ... ... .. .. ... .. .
(18) Schedule of pipes:
Description of pipe/drain materials diameter weight method of jointing
(a) Sub-soil drains
(b) Main sewage drains
(c) Branch sewage drains
(d) Soil pipes
(e) Ventilating pipes other than soil pipes
(f) Waste pipes
(g) Rain-water pipes
(h) Anti-syphon pipes
216 © ESA
CES 161
ANNEX E
Form for licensed plumber’s completion certificate
Certified that I/we have completed the plumbing work of drainage and sanitation system for
the premises as detailed below. This may be inspected, approved and connection given.
City .........................................Sub-City……………..District…………….House No………….
Details of work:
….......................................................................................................................................
..................................................................................................................................................
......................................................................................................................................
Certified that the plumbing work of drainage and sanitation system for the premises, have
been laid, applied, executed in accordance with ES 3960: Plumbing Services of Buildings.
Drainage connection to the main sewer will be made on
.................................................................
Date ..........................
The Authority
..…………………......................................................
....................................................................................
....................................................................................
....................................................................................
© ESA 217
CES 161
ANNEX F
Percolation test
To determine the area of land required (for subsoil infiltration of septic tank effluent) a
percolation test is essential. The following method should be adopted for this purpose.
Excavate a hole 300.0mm square to a depth 250.0mm below the proposed invert level of
the land drain. Where deep drains are necessary, the hole should conform to this shape at
the bottom but may be enlarged above the 250.0mm level to enable safe excavation to be
carried out. Fill the 300mm square section of the hole to a depth of at least 250.0mm with
water and allow it to seep away overnight. Next day, refill the test section with water to a
depth of at least 250.0mm and observe the time, in seconds, for the water to seep away
completely.
Divide this by the depth in millimeters of water placed in the hole. The result gives the
average time required for the water to drop 1.0mm. The test should not be taken during
abnormal conditions such as heavy rain and severe drought. Carry out the test at least
three times and take the average.
Where deep excavations are necessary, a modified test procedure may be adopted using a
300.0mm earth auger. Bore the test hole vertically to the appropriate depth taking care to
remove all loose debris.
Make water level observation referring to fixed datum using a dip stick or some suitable
alternative water-level indicator.
The value found in this way is called the percolation value of the soil (vp in seconds) and
can be used to determine the area of drainage trench floors (walls) required to disperse
effluents.
If the percolation value exceeds 140.0s, the soil is not suitable for drain fields. From 140.0s
to 100.0s (about 10.0hr to 7.0hr to fall 250.0mm), underdrains are desirable.
218 © ESA
CES 161
ANNEX G
If a lever gutter discharges freely, the depth of flow at the downstream end is equal to the
critical depth c. (see 7.4.3.4(4), Section 7. The relationship between discharge, Q (in l/s,
and the critical depth is given by the equation.
Q = 9.90x10-5 (G-1)
Where,
Ac is the cross sectional area (in mm2) corresponding to the critical depth c
F0 = 1.010X105 (G-2)
Where,
Ao is the cross-sectional area (in mm2) corresponding to the depth o at the outlet
(calculated from G.4);
Bo is the surface width of flow (in mm) corresponding to the depth c at the outlet
(calculated from G.4).
If Fo < 1, the depth c is greater than the critical depth c and the discharge of the gutter is
restricted.
© ESA 219
CES 161
To find the depth of flow c at the upstream and of the gutter, calculate F0 from Equation G-
2, calculated Bs/Bo (where Bs is the sole width of the gutter) and use Figure G-1 to find the
value of u/o from which u can be determined.
Flow resistance causes the depth of flow at the upstream end of the gutter to be somewhat
greater than the value of u calculated in G.1 and G.2. As an approximate guide, the
increase in the upstream depth of flow due to friction will be less than 5% if the length of the
gutter is less than 50 times its upstream water depth. The increase in water depth can be
estimated as follows:
a) Calculate the Froude number Fo, from Equation 2 at the downstream end of the gutter. If
Fo 1, the gutter discharges freely; if Fo<1, the discharge is restricted.
b) Calculate the value of the ratio of Lg/d, where Lg is the length of the gutter (measured
from the outlet to the point at which the maximum depth of flow occurs), and Yd is the
depth of flow at the downstream end.
c) Estimate from Figure G-2 the percentage increases x, in the upstream depth of flow.
The depth Yuf at the upstream end taking into account the effect of friction is given by
the equation:
Yuf = Yu (G-3)
The effect of resistance can be neglected if the value of x is found to be less than 5%.
The curves in Figure G-2 are based on a Manning roughness coefficient of n=0.015 in
small gutters and n = 0.20 in large gutters.
220 © ESA
CES 161
Figure G.1 Design chart for trapezoidal gutters with restricted discharge
Where,
Qi is the total flow (in l/s) entering the outlet;
D is the effective diameter of the outlet (in mm);
h is t he head (in mm) above the top of the outlet.
The effective diameter, D, for a sharp-edged outlet is equal to the top diameter , Do (see
Figure 7.7, Section 7); for a round-edged outlet of the types shown in figure 7.7, D= 0.9Do;
for a tapered outlet of the type shown in Figure 7.7, D =Do.
© ESA 221
CES 161
The behavior of rectangular outlets is similar to that of circular outlets. If the flow at a sharp-
edged outlet is of weir type:
Qi = (G-6)
Qi = (G-7)
Where,
Lw is the length of the perimeter (in mm) along which flow enter the outlet;
A A transition from weir-type to orificial type for occurs when the head exceeds the value
of h = 2Ai/Lw
The capacities of grated for box receivers and flat roofs are best determined experimentally.
Where measurements are not available, their capacity may be determined from Equations
(G-6) and (G-7. If the outlet acts as a weir, the required value of Lw in Equation (G-6) is the
total length of the openings measured around the perimeter of the outlet. If the outlet acts
as an orifice, the value of Ai in Equation (G-7) is the total area of the openings that are
submerged by the flow; and h is the depth of water above the level of the openings.
Flow at an outlet in the sole of a gutter may be either of a weir-type or of orifice-type. The
capacity of an outlet in the sole of a gutter can be calculated from the equations for outlets
in box-receivers (see G.4.1).
In order to determine whether a gutter will discharge freely, it is necessary to compare the
head, h, at the outlet with the corresponding value of critical depth, Yc, in the gutter (found
from 7.4.3.4). If an outlet receives unequal flows from two or more direction, it is necessary
to calculate separate values of critical depth for each length of gutter. If the head at the
outlet, h, less than the critical depth Yc, the length of gutter will discharge freely; if h is
greater than Yc, the discharge of the gutter will be restricted, and the depth of the flow at the
downstream end of the gutter, Yo, will be equal to the value of h (see G.2).
222 © ESA
CES 161
Flow conditions at outlets in gutters are complex, and the above procedure contain several
simplifying assumptions. More economic design may result from the use of experimental
measurements or a more accurate method of calculation.
© ESA 223
CES 161
ANNEX H
Spacing of inlets for paved areas
H.1 General
The spacing of inlets depends upon two separate quantities the capacity of the collecting
channel and the capacity of the inlet.
The capacity of a collecting channel is calculated using the Manning equation, Equation (H-
1) The capacity of the inlet is calculated using a semi-theoretical method which relates its
capacity to its geometry and is supported by a large number of experimental
measurements.
The depth of flow in the channel is assumed to be controlled by its hydraulic resistance, and
the Manning equation is used to relate the depth of flow, Y, to discharge, Q. For a channel
of arbitrary cross-sectional shape, the Manning equation is:
Q = x (H-1)
Where,
224 © ESA
CES 161
Combining Equation (H-2) and (H-4) gives for channels of triangular cross-section the
equation:
E= 7.90 C9/6 Q7/16 (H-5)
Where C is defined by Equation (H-3).
In order to intercept all the flow in a collecting channel, a kerb-inlet should have a length Li
of clear opening given by the equation
L1= K1 E (H-6)
Where E is the value of the inlet criterion given by Equation (H-5). Any struts or bars should
be placed so as not to obstruct the flow. K1 is a factor that varies with the effective cross-
final of the collecting channel; the following values of K1 have been determined
experimentally:
Values of K1 for 12>b>24 should be interpolated linearly. If the actual length, L, of the inlet
is less than L1, then it will only intercept part of the flow in the collecting channel. The blow
that by passes the inlet, q, can be expressed as a proportion, p, of the total flow
approaching the inlet and if given by the equation:
P =1- (H-7)
H.4.1 General
Grated inlets should be installed in collecting channels as closed as possible to the kerb.
Figure H-2 shows the general case of flow to a rectangular grated inlets set in collecting
channel of triangular cross-section. Flow can by-pass an inlet in the following ways:
(a) Between the kerb and the slots of the grating (the carry-by flow, q1);
(b) Over the grating, by water passing over the bars (the carry-over flow,q2);
© ESA 225
CES 161
(c) Around the grating, by water flowing around the outside edge of the grating (the
carry-past flow, q3).
H.4.2 Carry-by-flow
The flow between the kerb and the first slot (or slots) of the grating, q1, can be expressed
as a proportion, P1, of the total flow approaching the inlet, experiments show that:
P1 = = (H-8)
Where:
d is the width of the gup (inmm) between the kerb and the first slot;
L is the length of the grating (in mm) measured along the kerb (see Figure H-2);
The length of grating, L2, required to prevent any flow passing over the bars is related to
the inlet criterion, E, by the equation:
L1 = K2 (H-9)
Where b is the cross-fall of the channel and, k2 is a constant that depends upon the design
of the grating. For a grating with bars parallel to the kerb and with transverse bars at quarter
points, k2 = 16. For heavy duty gratings with bars set at 450 to the kerb K2 =24 (see Figure
H-2). For a grating with transverse bars a value of K2= 24 can also be taken. If the actual
length of the grating, L1, is less than L2, some flow , q2, will pass over the bars. If this flow
is expressed as a proportion, P2, of the total flow approaching the inlet, it is found that:
P2 = = (H-10)
The length of grating, L3, required to prevent flow by passing the grating around its outer
edge is given by the equation.
= 2.4 E (H-11)
Where
B is the width of flow (in mm) in the collecting channel upstream if the inlet;
226 © ESA
CES 161
Wp is the distance (in mm) from the kerb to the outer edge of the grating (see Figure H-2)
If the actual length, L, of the grating is less than L3, some flow, q3, will pass around the
inlet. If this flow is expressed as a proportion, P3, of the total flow approaching the inlet,
experiments show that:
= (H-12)
A combined inlet consists of a grated inlet and an adjacent kerb inlet having the same
length as the grated inlet. This type of inlet is less susceptible to blockage than either the
grated inlet or the kerb inlet used separately; but its capacity will normally be only slightly
greater than that of the grated inlet.
The method of calculating the capacity of a combined inlet is similar to that for a gully-
grating (see H.4) apart from the following changes:
(a) Carry-by flow: The value of the constant in Equation (H-8) should be change from 24 to
16;
(b) Carry-overflow: The appropriate value of the constant K2 in Equation (H-9) should
reduced by 10%.
© ESA 227
CES 161
Terminal inlets should be located at the down-stream ends of collecting channels and at low
points in the paved area. Such inlets should be designed in the same way as grated inlets
in roofs.
228 © ESA
CES 161
H.8.1 General
The determination of the spacing of inlets should begin at the upstream end of the system
and proceed in the downstream direction. The following factors may affect the spacing of
inlets:
(a) Limitations on the maximum width and the maximum depth of flow in the collection
channel.
(b) Limitation on the amount of by-passing, if any, to be permitted at each inlet.
(c) The likelihood of blockage of the inlet and the frequency of clearing.
The capacity of an inlet can be increased if some flow is allowed to by-pass the inlet and
continue to an inlet further downstream. The increase in capacity can be significant in the
case of kerb-inlets, which have a relatively low efficiency in steep channels. The total
proportion of flow by-passing an inlet should not normally exceed one-fifth of the flow
approaching the inlet.
The following design data are required: the slop, s, and the effective side slope, b, of the
collecting channel, the relevant dimensions of the inlet L, Wp, and (see Figure H-2), the
design rainfall intensity, I, the flow (if any) by passing the upstream inlet, q, the maximum
width of flow, B, or the maximum depth, Y.
(a) Calculate the value of the channel criterion C from Equation (H-3), using the appropriate
value of Manning’s n from Table H-1.
(b) If the maximum width of flow, B, is specified, calculate the corresponding maximum
depth Y=B/b.
(c) Determine the discharge, Q, corresponding to the valves of C and Y using Equation (H-
2), then calculate the value of the inlet criterion, E, using Equation (H-5).
(e) If the proportion of flow by-passing is acceptable, calculate the area (in m2) that can be
drained, Ap, using equation.
Ap = 3600 (H-13)
Where I is in millimeters per hour, the equation assumes that the area Ap is impermeable,
(f) If the proportion of by-passing is excessive, reduce the maximum depth of flow or
change the size of the inlet; then repeat steps (a) to (e).
© ESA 229
CES 161
230 © ESA
CES 161
ANNEX I
Design and construction of refuse chutes
1. Chutes
1.1 Number of chutes-The number of chutes depends upon the convenience to the user
and the quantity of refuse to be handled between two subsequent clearings. Annex J gives
the method of calculation of quantity of refuse from residential buildings.
1.2 Individual or combined system-In continuation to 1.1, if the chute system is designed
as individual system, where each flat is served by an independent hopper, it will be to the
utmost convenience to the user. However, a common hopper may be provided in each floor
for each chute whose number is further decided by the quantity of refuse to be handled.
1.3 Material of construction - Chutes may be constructed out of asbestos cement or
R.c.c. pipe with smooth inside finish.
1.9.1 Access-Each chute pipe should be provided with an access door at intervals not
greater than every third floor.
1.9.2 Wrapping of Refuse-To help preventing spillage and blockage, the residents should
be encouraged to wrap their refuse.
1.9.3 Flushing of Chute- Y-connection at terrace level may preferably be provided in order
to direct a. water hose for cleaning purposes, if needed.
© ESA 231
CES 161
2. Inlet hopper
2.1 Location - In individual chute system, the inlet hopper shall be located in the passage
near the kitchen and in the common chute system towards the end of the common
passage. Natural ventilation should be adequate to prevent any possible odour nuisance.
There should be adequate lighting at this location. For ground floor flats the inlet hoppers
may be placed at a higher level and a flight of steps may be provided for using the same.
232 © ESA
CES 161
2.2 Design and Construction-Hopper shall be constructed such that there should be
mii1imum escape of odour or any other vapour when the hopper door is kept open or
closed that the inside portion of the hopper does not lodge any refuse while projecting it into
the chute. The door
© ESA 233
CES 161
and the frame should be fire-resistant. A typical construction of an inlet hopper is given in
Fig. 8.2.
2.2.1 Size of the Mouth and Throat - The mouth shall have a maximum size of 25 cm height
and 36 cm width. The throat should not be less than the size of the mouth. The diagonal of
the mouth should not be larger than the chute size.
2.2.2 Height of the Hopper-The hopper should be constructed at a height of 75 cm
measured from the floor level to the lower edge of the inlet opening.
2.2.3 Inner Surface - The interior of the hopper should slope towards the main chute at an
angle not less than 45° to the horizontal preferably 60° for better performance. This portion
may be specially built or may be had by providing a suitable· Y-connection. If built
specially, the
inside finish should be as smooth as possible. If provided by the use of Y-connection, it may
be of asbestos cement or cast iron or cement concrete pipe.
2.2.4 Door, Head, Frame and Receiving Unit - These should be of mild steel, cast iron or
aluminum adequately protected against corrosion. The door should be designed to be self-
closing, to have a latch for closing it securely after use and to have a rubber gasket in
between the door and the frame for ensuring gas tightness and minimizing noise. The
receiving plate
should be fitted with two retaining side plates to prevent spillage (see Fig. 8.2).
2.2.5 Counterbalance of Door-The door when not in use, should fly back to its closed
position and be firmly closed,
2.2.6 Hinge - The hinge shall be such as to satisfy the requirements in 2.2. It should not
have sharp edges to harm the user. It should be fitted such that the door' can be taken out
for maintenance.
2.2.7 Handle-There should be a handle fixed properly to the door for operating the hopper
door.
3. Collection chamber
234 © ESA
CES 161
Preferably the chamber may be lined with glazed tiles for better cleaning and up keeping.
The junctions of the walls with each other and with the floor shall be smoothly rounded off
to
prevent lodging of dust and refuse.
© ESA 235
CES 161
3.4 Cleaning and Maintenance-Provision of water tap in the vicinity and drainage facility
with a trapped gully shall be made in order to arrange for periodic cleaning of the chamber.
3.5 Shutter-There should be a cut-off plate or shutter at the chute bottom in order to close
off the chute at the time of handling refuse in the chamber or while cleaning. The shutter
shall be made of sheet iron sliding horizontally inside angle-iron rebates. These should be
made non-corrodible with proper painting.
3.6 Lighting- Adequate artificial light should ,be provided in the chamber with its control
switch located on the outside wall near entrance.
3.7 Access - There shall be easy access to the chamber for the cleaners and refuse
collectors. There should be a well paved pathway leading to the collection chamber from
the nearest road in order-to facilitate easy transport of refuse at site,
236 © ESA
CES 161
ANNEX J
Method of calculation of total refuse and guidelines for determining number of
chutes and size of collection chamber
Example:
To consider a multistoried building of20 flats with 2 flats per floor
Refuse/flat: 0.027 rn³/day.
a) No. of Chutes
1. To be decided on convenience to the user; and
2. To be decided on the total number of containers, if used in the collection chamber.
Assuming that individual hopper system will be convenient to the residents, the number of
chutes will be two.
To provide for irregularity in municipal refuse cleaning service, collection chamber be
designed to accommodate 2 days refuse.
However, a chamber of size 1·2 x 1.2 x 1.2m will be necessary as a minimum requirement.
© ESA 237
CES 161
ANNEX K
WHO drinking water quality guideline values for chemicals that have health
significance
Table K-1 Guideline values for naturally occurring chemicals that are of health
significance in drinking-water
238 © ESA
CES 161
Table K-2 Guideline values for chemicals from industrial sources and human
dwellings that are of health significance in drinking water
© ESA 239
CES 161
Table K-3 Guideline values for chemicals from agricultural activities that are of health
significance in drinking-water
240 © ESA
CES 161
Table K-4 Guideline values for chemicals used in water treatment or materials in
contact with drinking-water that are of health significance in drinking-water
© ESA 241
CES 161
ANNEX L
Symbols
242 © ESA
CES 161
© ESA 243
Organization and Objectives
The Ethiopian Standards Agency (ESA) is the national standards body of Ethiopia
established in 2010 based on regulation No. 193/2010.ESA is established due to the
restructuring o f Quality a nd Standards Authority o f Ethiopia ( QSAE) w hich w as
established in 1998.
More Information?
Contact us at the following address.
The Head Office of ESA is at Addis Ababa.