New Microsoft Word Document
New Microsoft Word Document
Calibration
- Calibration is the act or result of quantitative comparison between a known standard and the
output of the measuring system.
- If the output-input response of the system is linear, then a single-point calibration is
sufficient.
- However, if the system response is non-linear, then a set of known standard
inputs to the measuring system are employed for calibrating the corresponding outputs of
the system.
- Calibration refers to the act of evaluating and adjusting the precision and accuracy of
measurement equipment.
- Instrument calibration is intended to eliminate or reduce bias in an instrument's readings
over a range for all continuous values.
Precision is the degree to which repeated measurements under unchanged conditions
show the same result
Accuracy is the degree of closeness of measurements of a quantity to its actual true
value.
- In general use, calibration is often regarded as including the process of adjusting the output
or indication on a measurement instrument to agree with value of the applied standard,
within a specified accuracy.
- There are three main reasons for having instruments calibrated:
1. To ensure readings from an instrument are consistent with other measurements.
2. To determine the accuracy of the instrument readings.
3. To establish the reliability of the instrument i.e. that it can be trusted.
- Calibration is carried out by agencies of the metrological service, using reference standards
and base standards.
- Governmental calibration is obligatory for measuring devices used in reporting material
value, for government tests and expert examinations, and for recording national and
international sports records, and also for calibration of the original base standards.
- All other measuring devices are calibrated by the appropriate departments.
Calibration Standards
- Calibration Standards of measurements can be classified according to their function and
type of application as:
International standards
- International standards are devices designed and constructed to the specifications of an
international forum.
- They represent the units of measurements of various physical quantities to the highest
possible accuracy that is attainable by the use of advanced techniques of production
and measurement technology.
- These standards are maintained by the International Bureau of Weights and Measures at
Sevres, France. For example, the International Prototype kilogram, wavelength of Kr86
orange-red lamp and cesium clock are the international standards for mass, length and time,
respectively.
- However, these standards are not available to an ordinary user for purposes of day-to-day
comparisons and calibrations.
Primary standards
- Primary standards are devices maintained by standards organizations / national
laboratories in different parts of the world.
- These devices represent the fundamental and derived quantities and are calibrated
independently by absolute measurements.
- These are the most precise and accurate physical standards, which are derived from
international standards.
- They specify the most stringent conditions and are used only at rare intervals for
comparison with secondary standards.
- One of the main functions of maintaining primary standards is to calibrate / check and certify
secondary reference standards.
- Like international standards, these standards also are not easily available to an ordinary
user of instruments for verification / calibration of working standards. These standards are
not portable.
Secondary standards
- Secondary standards are basic reference standards employed by industrial measurement
laboratories.
- These are derived from primary standards. They are portable and are often used as national
standards.
- They are less precise than primary standards but are still very precise.
- They are used at rare intervals to calibrate tertiary and working standards. These are
maintained by the concerned laboratory.
- One of the important functions of an industrial laboratory is the maintenance and periodic
calibration of secondary standards against primary standards of the national standards
laboratory / organization.
- In addition, secondary standards are freely available to the ordinary user of instruments for
checking and calibration of working standards.
Working standards
- These are high-accuracy devices that are commercially available and are duly checked
and certified against either the primary or secondary standards.
- For example, a standard cell and a standard resistor are the working standards of voltage
and resistance, respectively.
- Working standards are very widely used for calibrating general laboratory instruments, for
carrying out comparison measurements or for checking the quality (range of accuracy) of
industrial products.
Calibration Procedure
- The process of calibration involves the estimation of uncertainty between the values
indicated by the measuring instrument and the true value of the input.
- Calibration may be called for:
a new instrument
after an instrument has been repaired or modified
when a specified time period has elapsed
when a specified usage (operating hours) has elapsed
before and/or after a critical measurement
after an event, for example
o after an instrument has had a shock, vibration, or has been exposed to an
adverse condition which potentially may have put it out of calibration or damage it
o sudden changes in weather
whenever observations appear questionable or instrument indications do not match the
output of surrogate instruments
As specified by a requirement, e.g., customer specification, instrument manufacturer
recommendation.
- There are four types of calibration:
Primary calibration, which is performed when a measuring device is put into circulation
from production or returned from repair;
Periodic calibration, which is conducted during use or storage of a device;
Special calibration, which results from the need for immediate verification of the good
condition of a device; and
Inspection calibration, which is performed during metrological inspections of
enterprises, supply centers, warehouses, and commercial organizations.
Calibration Concepts
- There are two fundamental operations involved in calibrating any instrument:
Testing the instrument to determine its performance,
Adjusting the instrument to perform within specification.
- Testing the instrument requires collecting sufficient data to calculate the instrument's
operating errors.
- This is typically accomplished by performing a multiple point test procedure that includes the
following steps.
Using a process variable simulator that matches the input type of the instrument, set a
known input to the instrument.
Using an accurate calibrator, read the actual (or reference) value of this input.
Read the instrument's interpretation of the value by using an accurate calibrator to
measure the instrument output.
- By repeating this process for a series of different input values, you can collect sufficient data
to determine the instrument's accuracy.
- Depending upon the intended calibration goals and the error calculations desired, the test
procedure may require from 5 to 21 input points.
- The first test that is conducted on an instrument before any adjustments are made is called
the As-Found test.
- If the accuracy calculations from the As-Found data are not within the specifications for the
instrument, then it must be adjusted.
- Adjustment is the process of manipulating some part of the instrument so that its input to
output relationship is within specification. For conventional instruments, this may be zero
and span screws.
- For HART instruments, this normally requires the use of a communicator (handheld or PC)
to convey specific information to the instrument.
- After adjusting the instrument, a second multiple point test is required to characterize the
instrument and verify that it is within specification over the defined operating range. This is
called the As-Left test.
Error Calculations
- Error calculations are the principal analysis performed on the As-Found and As-Left test
data.
- There are several different types of error calculations, most of which are defined in the
publication "Process Instrumentation Terminology".
- They are usually expressed in terms of the percent of ideal span which is defined as:
% span = (reading - low range) / (high range - low range) x 100
- The first step in the data analysis is to convert the engineering unit values for input and
output into percent of span. Then for each point, calculate the error, which is the deviation of
the actual output from the expected output.
The Maximum error is the most common value used to evaluate an instrument's
performance. If a computer program is not used to analyze the test data, it is often the
only error considered and is taken to be the largest deviation from the ideal output.
By itself, the maximum error does not give a complete indication of an instrument's
performance. With the availability of computer software to facilitate calculations, other
error values are gaining popularity including zero error, span error, linearity error, and
hysteresis error.
Zero error is defined as the error of a device when the input is at the lower range value.
Span error is defined as the difference between the actual span and the ideal span,
expressed as a percentage of the ideal span.
Linearity error is a measure of how close the error of the instrument over its operating
range approaches a straight line. Unfortunately, there are three different methods used to
calculate this, resulting in an independent linearity, a terminal based linearity, and a zero
based linearity. In practice, it is best to choose one method and apply it consistently. Note
that the calculation of linearity error is also greatly facilitated by a curve fit of the error
data.
Hysteresis error is a measure of the dependence of the output at a given input value
upon the prior history of the input. This is the most difficult error to measure since it
requires great care in the collection of data, and it typically requires at least 9 data points
to develop reasonable curves for the calculations. Thus a technician must collect at least
five data point traversing in one direction, followed by at least four more in the opposite
direction, so that each leg has five points, including the inflection point.
If any of these errors is greater than or equal to the desired accuracy for a test, then the
instrument has failed and must be adjusted.
Hand-Held Device
- This is a mobile/portable device which is a small, handheld computing device, typically
having a display screen with touch input and/or a miniature keyboard and weighing less than
0.91kg.
- A handheld computing device has an operating system (OS), and can run various types
of application software.
- Most handheld devices can also be equipped with Wi-Fi, Bluetooth, and GPS capabilities
that can allow connections to the Internet and other Bluetooth-capable devices, such as an
automobile or a microphone headset.
- It delivers messages and performance data to the operator and is used to support
installation, configuration, provisioning, calibration and maintenance and network
performance.
6. a) i) State the four steps in the operation of programmable logic controller (PLC)
There are four basic steps in the operation of all PLCs; Input Scan, Program Scan, Output Scan,
and Housekeeping. These steps continually take place in a repeating loop.
(i) Input Scan: Detects the state of all input devices that are connected to the PLC
(ii) Program Scan: Executes the user created program logic
(iii) Output Scan: Energizes or de-energize all output devices that are connected to the PLC.
(iv) Housekeeping: Operational commands to the controlled devices. This step includes
communications with programming terminals, internal diagnostics, etc...
ii) Explain with aid of examples the following PLC programming languages
I) Functional block diagrams
II) Instruction lists
(i) Function Block Diagram (FBD) - A graphical language for depicting signal and data flows
through re-usable function blocks. FBD is very useful for expressing the interconnection of
control system algorithms and logic
(ii) Ladder Diagram (LD): Traditional ladder logic is graphical programming language. Initially
programmed with simple contacts that simulated the opening and closing of relays, Ladder Logic
programming has been expanded to include such functions as counters, timers, shift registers, and
math operations
(iii) Instruction List (IL): A low level “assembler like” language that is based on similar instructions
list languages found in a wide range of today’s PLCs.
LD
R1
MPC
RESET
LD
PRESS_1
ST
MAX_PRESS
RESET
LD 0
:
A_X43
ST
(iv) Structured Text (ST) – A high level text language that encourages structured programming. It has a
language structure (syntax) that strongly resembles PASCAL and supports a wide range of standard
functions and operators. For example;
b) Write an instruction list for the ladder diagram provided in fig below
(i) UTP
PRO: Most flexible; cheapest cable (but requires expensive support components); easy to
install; easy to add users; may be able to use existing phone cable if data grade
CON: Shortest usable cable length; susceptible to electrical interference; unsecure; generally
not good for use between buildings
(ii) Shielded twisted pair (STP) is similar to UTP except it contains a copper braid jacket to ‘shield’ the
wires from electrical interference. It can support transmissions over greater distances than UTP.
(iii) Fiber-Optic
PRO: Fastest transmission rate; not susceptible to electrical interference; secure; good for
use between buildings
CON: Most expensive; relatively difficult to work with
(iv) Coaxial Cable
PRO: Flexible and easy to install; relatively good resistance to electronic interference;
electronic support components are relatively inexpensive
CON: Short cable length; more expensive than UTP; unsecure; hard to change
configuration; thinnet generally not good for use between buildings
d) With aid of a diagram, describe the mesh topology used in industrial networks and state its
advantage.
In a mesh network, devices are connected with many redundant
interconnections between network nodes. In a true mesh topology every
node has a connection to every other node in the network. There are two
types of mesh topologies:
(i) Full mesh topology occurs when every node has a circuit
connecting it to every other node in a network. Full mesh is
very expensive to implement but yields the greatest amount of
redundancy, so in the event that one of those nodes fails, network traffic can be directed
to any of the other nodes. Full mesh is usually reserved for backbone networks.
(ii) Partial mesh topology is less expensive to implement and yields less redundancy than
full mesh topology. With partial mesh, some nodes are organized in a full mesh scheme
but others are only connected to one or two in the network. Partial mesh topology is
commonly found in peripheral networks connected to a full meshed backbone.
Advantages
- Point-to-point line configuration makes identification and isolation of faults easy.
- Messages travel through a dedicated line, directly to the intended recipient; privacy and
security are thus enhanced.
- Should a fault occur in a given link, only those communications between that specific
pair of devices sharing the link will be affected.
- Dedicated links ensure that each connection carries its own data load, thereby preventing
the sort of traffic problems that may arise in shared-link architectures.
Disadvantages
- The more extensive the network, in terms of scope or of physical area, the greater the
investment necessary to build it will be, due, among other considerations, to the amount
of cabling and the number of hardware ports it will require. For this reason, such
networks are uncommon.
- Because every device must be connected to every other device, installation and
reconnection are difficult.
2521/202 INDUSTRIAL CONTROL SYSTEMS
Oct/Nov 2012
6 a) Draw a labeled block diagram of the internal architecture of a Programmable Logic
Controller (PLC) and state the function of each block
b) Describe the following Programmable Logic Controller (PLC) system styles
i) Unitary
ii) Modular
iii) Rack Mounting
(i) Unitary: The Unitary PLC is typically the smallest and least expensive. It would be used in a
small machine or fixed application such as overhead door controls or a stand-alone parts
inspection system. They are not expandable so the application is limited to on-board I/O.
There are, however, some very powerful units available with built in GSM, color screens,
and web servers. Most have 1 or 2 analog I/O channels as well as a high speed input and
pulse train output for simple motion control.
(ii) Modular: The Modular PLCs start with a processor with a few or no on-board I/O. They
typically mount to a DIN rail and sometimes require a separate power supply. Additional I/O
as well as specialty modules also snap onto the DIN rail and plug into the processor or
adjacent module. Modular PLCs are used in applications where a higher I/O count is needed
or when using specialty modules such as quadrature encoders, thermocouple inputs, etc.
They are also useful in small applications that have options or “upgrades” available to the
end user. Systems can be expanded (within certain limits) without adding additional rack
space.
(iii) Rack Mounting PLCs are usually more expensive, expandable, and powerful than
unitary or modular PLCs. The rack provides a power and communication backplane that
greatly increases the communication rate between the processor and the modules as well as
allowing some specialty modules to communicate with each other without the processor. In
some brands, multiple processors can be in the same rack and share the inputs. Racks also
allow for redundant processors for critical systems such as waste water pumps or fire control
systems. The types of modules available for rack systems are far more extensive than
modular systems. The number of available I/O points is also much higher in the rack
systems. Around 1000 for some modular PLCs versus over 100,000 for the same brand of
rack system
7 a) With the aid of a block diagram, explain how a PLC process input from the sensors
Input scan: During the input scan, the current status of every input module is stored in the
input image (memory) table, bringing it up-to-date. Thus all the status of the input devices
(which in turn is connected to the input module) is updated in the input memory table.
Program scan: Following the input scan, the CPU enters its user program execution, or
program scan. The execution involves starting at the program's first instruction, then
moving on to the second instruction and carrying out its execution sequence. This
continues to the last program instruction. Throughout the user-program execution, the CPU
continually keeps its output image (memory) table up-to-date.
Output scan: During program scan, the output modules themselves are not kept
continually up to date.
Instead, the entire output image table is transferred to the output modules during the output
scan which comes after the program execution. Thus the output devices are activated
accordingly during the output scan.
b) Using OSI reference model diagram indicate different encapsulation process at every peer-
to peer communication layer of two Remote Terminal Unit (RTU) of a SCADA system
starting with the top most down to the lowest layers.
c) An Alarm system is used in conjunction with an automated bottling system in a milk
bottling plant. A conveyer belt carries empty bottles that are to be filled with milk. The
alarm goes off in any of the conditions occurs.
- Milk tank is empty and bottles are in conveyor belt.
- There are no bottles in the conveyer and there is milk in the tank.
- There is milk in the tank and bottles on the conveyor belt but electric power is off.
- There is no milk in the tank, no bottles on the conveyor belt and electric power is off.
i) Write down a Boolean expression for the alarm system.
ii) Implement this system using a PLC ladder diagram.
c) With the aid of a block diagram, describe the construction of a Programmable Logic
Controller
In the figure, the heart of the “PLC” is in the center, i.e., the Processor or CPU (Central
Processing Unit).
The CPU regulates the PLC program, data storage, and data exchange with I//O
modules.
Input and output modules are the media for data exchange between field devices and
CPU. It tells CPU the exact status of field devices and also acts as a tool to control
them.
A programming device is a computer loaded with programming software, which
allows a user to create, transfer and make changes in the PLC software.
Memory provides the storage media for the PLC program as well as for different data.
OR
CPU or processor: The main processor (Central Processing Unit or CPU) is a
microprocessor-based system that executes the control program after reading the status
of field inputs and then sends commands to field outputs.
I/O section: I/O modules act as “Real Data Interface” between field and PLC CPU.
The PLC knows the real status of field devices, and controls the field devices by means
of the relevant I/O cards.
Programming device: A CPU card can be connected with a programming device
through a communication link via a programming port on the CPU.
Operating station: An operating station is commonly used to provide an "Operating
Window" to the process. It is usually a separate device (generally a PC), loaded with
HMI (Human Machine Software).
Star Topology
A star topology is designed with each node (file server, workstations, and peripherals) connected directly
to a central network hub, switch, or concentrator.
Data on a star network passes through the hub, switch, or concentrator before continuing to its
destination. The hub, switch, or concentrator manages and controls all functions of the network. It also
acts as a repeater for the data flow. This configuration is common with twisted pair cable; however, it can
also be used with coaxial cable or fiber optic cable.
Advantages of a Star Topology
Easy to install and wire.
No disruptions to the network when connecting or removing devices.
Easy to detect faults and to remove parts.
Disadvantages of a Star Topology
Requires more cable length than a linear topology.
If the hub, switch, or concentrator fails, nodes attached are disabled.
More expensive than linear bus topologies because of the cost of the hubs, etc.
Ring Network Topology: A local-area network (LAN) whose topology is a ring. That is, all
of the nodes are connected in a closed loop. Messages travel around the ring, with each
node reading those messages addressed to it. One of the advantages of ring networks is that
they can span larger distances than other types of networks, such as bus networks, because
each node regenerates messages as they pass through it.
Mesh network Topology: The mesh network topology employs either of two schemes, called full
mesh and partial mesh. In the full mesh topology, each workstation is connected directly to each of
the others. In the partial mesh topology, some workstations are connected to all the others, and some
are connected only to those other nodes with which they exchange the most data.
Tree Network Topology: The tree network topology uses two or more star networks connected
together. The central computers of the star networks are connected to a main bus. Thus, a tree
network is a bus network of star networks.
d) With the aid of a ladder program and a process control figure, explain how a converter can
be used in a machine to direct 6 products to a packaging box and 12 products to another
box simultaneously.
The control of a machine which is required to direct 6 products along one path for
packaging in a box and then 12 products along another path the packaging in another
box.
A deflector plate might be controlled by a photocell sensor which gives an output every
time a product passes it. Thus the numb rod pulse from the sensor has to be counted and
used to control the deflector.
On rung 1, each time the photo sensor is triggered it causes C1’s count to increase.
When C1, the six product counter, reaches six it causes the deflector to activate.
On rung 3, while the deflector is activated C2, the 12 products counter, and starts
counting the products. On rung 4, after 12 products are counted the counters are reset
and the process starts again.
The process can also be reset at anytime using the start button.
d) Explain how zero and span errors are corrected in measuring instruments
Zero and span errors are corrected by performing a calibration. Most instruments are
provided with a means of adjusting the zero and span of the instrument, along with
instructions for performing this adjustment.
- The zero adjustment is used to produce a parallel shift of the input-output curve.
- The span adjustment is used to change the slope of the input-output curve.
- Linearization error may be corrected if the instrument has a linearization adjustment.
If the magnitude of the nonlinear error is unacceptable and it cannot be adjusted, the
instrument must be replaced.
2601/201 CONTROL SYSTEMS AND PROGRAMMABLE LOGIC
CONTROLLERS
Oct/Nov 2011
ii) Distinguish between supervisory control and data acquisition and distributed control
system
A DCS is a process-oriented system and it treats the control of the process, (the
chemical plant, refinery or whatever) as its main task, and it presents data to operators
as part of its job.
A SCADA system is data gathering oriented; and the control center and operators are its
focus. However, the remote equipment is merely there to collect the data - though it
may also do some very complex process control.
A DCS operator station is intimately connected with its input/output signals (I/O)
through local wiring, communication buses (e.g. Field Bus, networks) etc. When the
DCS operator wants to see information he/she usually makes a request directly to the
field I/O and gets a response. Field events can directly interrupt the system and advise
the operator.
A SCADA system must continue to operate when field communications have failed.
The ‘quality’ of data shown to the operator is an important facet of SCADA system
operation. SCADA systems often provide special ‘event’ processing mechanisms to
handle conditions that occur between data acquisition periods.
There are many other differences, but they tend to involve a lot of detail. The underlying points
are:
A SCADA system needs to transfer secure data and control signals over a potentially
slow, unreliable communications medium, and needs to maintain a database of ‘last
known good values’ for prompt operator display. It frequently needs to do event
processing and data quality validation. Redundancy is usually handled in a distributed
manner.
A DCS is always connected to its data source, so it does not need to maintain a database
of ‘current values’. Redundancy is usually handled by parallel equipment, not by
diffusion of information around a distributed database.
b) With the aid of a diagram, explain how PLC’s can be used to control water level in a tank
ii) With aid of a labeled block diagram, explain the hardware architecture of a SCADA
system
Basic layers in a SCADA system can be classified in two parts generally: the “client layer”
which caters for the man machine interaction and the “data server layer” which handles most
of the process data control activities. The data servers communicate with devices in the field
through process controllers.
Process controllers, e.g. PLCs, are connected to the data servers either directly or via
networks or fieldbuses. Data servers are connected to each other and to client stations via an
Ethernet LAN.
The RTU connects to physical equipment. Typically, an RTU converts the electrical signals from the
equipment to digital values such as the open/closed status from a switch or a valve, or measurements
such as pressure, flow, voltage or current. By converting and sending these electrical signals out to
equipment the RTU can control equipment, such as opening or closing a switch or a valve, or setting
the speed of a pump.
Supervisory Station; The term “Supervisory Station” refers to the servers and software responsible for
communicating with the field equipment (RTUs, PLCs, etc), and then to the HMI software running on
workstations in the control room, or elsewhere.
In smaller SCADA systems, the master station may be composed of a single PC. In larger SCADA
systems, the master station may include multiple servers, distributed software applications, and
disaster recovery sites.
To increase the integrity of the system the multiple servers will often be configured in a dual-
redundant or hot-standby formation providing continuous control and monitoring in the event of a
server failure.
b i) State and explain four user configurable open system (UCOS) components
UCOS is a control system that employs object-oriented techniques at every level of its system
architecture. It includes a number of subsystems which segment the functionality of UCOS.
This includes an Engineering Workstation Subsystem, an Operator Workstation Subsystem,
and a Field Control Unit (FCU) Controller Subsystem. The subsystems communicate via a
Control Network.
Engineering Workstation (EWS) used for project development. The EWS is the
development tool where control schemes are configured then downloaded to the OWS,
FCU, and SDS. The entire project is configured using a single integrated tool based on
graphical Windows standards. Graphical techniques are also used to define the logical
relationships among the devices in a process area. Project configuration begins by defining
the system architecture: workstations, field control units (FCUs), I/O, networking, etc.
Graphical techniques are also used to define the logical relationships among the control
elements for multiple devices.
Operator Workstation (OWS) for operator interface. This is used to monitor and control
the process. It uses the project screens created during project development and animates
them based on real-time data received from field control units and field data servers.
Authorized operators can monitor detailed activities for many types of devices and send
commands using standard faceplate command windows and group displays.
Field Control Unit (FCU) for control logic execution and direct scanning of I/O. The
FCU provides I/O services by monitoring and controlling I/O across standard networks and
data highways. The FCU can provide simultaneous support for multiple vendors’ I/O and
I/O networks. The variety of platform and form-factor options supported by the FCU
allows incorporation of distributed, distinct I/O subsystems into common control
strategies.
Control Network. System supports redundant and non-redundant fiber optic and Ethernet
local networks using the TCP/IP networking protocol for standardized, advanced
application connectivity. The LAN/WAN can be extended to other sites inside or outside
the plant using such remote communications technologies as satellite, radio, microwave,
and dial-up running such standard protocols as TCP/IP, Modbus, OPC, DDE
I/O Subsystem supporting I/O from all industry standard suppliers. The same logic can be
solved to manipulate different I/O subsystems from different manufacturers without having
to change any of the programming or operational parameters of the configured system.
SCADA Data Server (SDS) for interfacing data from intelligent devices, such as PLCs,
Fieldbus technologies, RTUs, PLC I/O, and other third-party devices
Process Historical Archiver (PHA) for storing and retrieving historical data collected by
the FCU, SDS or any other intelligent device in the system
microFCU: is a small, low-powered PLC that executes sequential and regulatory logic and
directly scans onboard I/O. It can replace RTUs at a significant reduction in cost and power
consumption – plus it can provide local intelligent control of devices, which RTUs can't
do.
Networking cables are used to connect one network device to other network devices or
to connect two or more computers to share resources. Different types of network cables
like Coaxial cable, Optical fiber cable, Twisted Pair cables are used depending on the
network's topology, protocol and size. The devices can be separated by a few meters (e.g.
via Ethernet) or nearly unlimited distances (e.g. via the interconnections of the Internet).
Twisted pair cabling is a form of wiring in which pairs of wires (the forward and
return conductors of a single circuit) are twisted together for the purposes of
canceling out electromagnetic interference (EMI) from other wire pairs and from
external sources. This type of cable is used for home and corporate Ethernet
networks. There are two types of twisted pair cables: shielded, unshielded. STP is
commonly used in Token Ring networks and UTP in Ethernet networks where it is
referred to as "10baseT and above." Transmission rates vary between 10-1000
Mbps.
Fiber-optic cable consists of a thin cylinder of glass surrounded by glass cladding,
encased in protective outer sheath. Fiber-optic cable is very fast (100 -1000
Mbps). It can transmit over long distances (2 km +) but is expensive.
Coaxial cable has a single copper conductor at its center. A plastic layer provides
insulation between the center conductor and a braided metal shield. The metal
shield helps to block any outside interference. Coaxial cable comes in two
versions: Thinnet and Thicknet. Thinnet is about 1/4 inch in diameter and is very
flexible and easy to work with. In contrast, Thicknet is about 1/2 inch in diameter
and not very flexible. Coax transmits at 10 Mbps.
Star topology: This is the Ethernet topology, the most common at management and shop floor
levels. It has the advantage of being very flexible to run and repair. The end stations are linked
together via an intermediate device (repeater, switch). Failure of a node does not prevent the
network as a whole from working, though the intermediate device linking the nodes together is
a point of weakness.
Bus topology: This is one of the simplest layouts; all the elements are wired together along the
same transmission line. The word bus refers to the physical line. This topology is easily
implemented and the failure of a node or element does not prevent the other devices from
working. Machine and sensor level networks, otherwise known as field buses, use this system.
The bus topology is implemented by linking devices together in a chain or to the main cable via
a connection box (TAP)
c) With aid of a diagram explain the importance of calibration of equipment and products.
To ensure readings from an instrument are consistent with other measurements.
To determine the accuracy of the instrument readings.
To establish the reliability of the instrument i.e. that it can be trusted.