B-33:B-33 7/30/10 9:36 AM Page 1

Bulletin B-33

Series 3000 Photohelic® Pressure Switch/Gage


Specifications - Installation and Operating Instructions

2-1/2 [63.50] (4) 6-32 HOLES


1/8 FEMALE NPT HIGH 2-1/16 [52.39] EQUALLY SPACED ON
PRESSURE CONNECTION
2 [50.80] A 5-1/8 [130.18] B.C.
1/8 FEMALE NPT LOW 1-1/4
PRESSURE CONNECTION [31.75]

Ø4-3/4 Ø4-47/64
[120.65]
3-7/8 SQ [120.25] Ø5
[98.43]
[127.00]

3/4 CONDUIT Ø4 [101.60]


CONNECTION 3-7/8 [98.43] 5/8 [15.88] FACE
5-1/8 [130.18] 5-1/2 [139.70]
5/8 [15.88] PANEL O.D.
6-3/8 [161.93] MAX
4-3/8 [111.13] (7-5/8 [193.68]) MOUNTING
3/16 [4.76]
HOUSING REMOVAL RING
Fig. 1

The Photohelic® Switch/Gage is a very versatile, precise pressure SPECIFICATIONS


switch combined with the time-proven Magnehelic® pressure gage. GAGE SPECIFICATIONS
Models are available with one or two phototransistor actuated relays. Service: Air and non-combustible, compatible gases.
Gage reading is unaffected by switch operation. Easy to adjust set points Wetted Materials: Consult factory.
have knob controls. Applied pressure and switch set points are fully Accuracy: ±2% of full scale at 70°F (21.1°C). ±3% on -0 and ±4% on
visible at all times. Deadband is one pointer width - less than 1% of full -00 models.
scale. Double-pole double-throw relays can be easily interlocked to Pressure Limits: -20˝ Hg. to 25 psig (-0.677 to 1.72 bar). MP option;
provide variable deadband control. For positive, negative or differential 35 psig (2.41 bar), HP option; 80 psig (5.52 bar). 36003S – 36010S;
pressure only on 3600S models. Full scale ranges available from 0-.25 150 psig (10.34 bar). 36020S and higher; 1.2 x full scale pressure.
in w.c. to 0-6000 psig. Temperature Limits: 20 to 120°F (-6.67 to 48.9°C); Low temperature
option available.
Process Connections: 1/8˝ female NPT.
PHOTOHELIC® GAGE SENSING - HOW IT WORKS Size: 4˝ (101.6 mm) dial face, 5˝ (127 mm) O.D. x 8-1/4˝ (209.55 mm).
In a typical control application, the Photohelic® switch/gage controls Weight: 4 lb (1.81 kg).
between high and low pressure set points. When pressure changes,
reaching either set point pressure, the beam from an LED to the limiting SWITCH SPECIFICATIONS
phototransistor will be cut off by the helix-driven light shield. The Switch Type: Each setpoint has 2 Form C relays (DPDT).
resulting signal change is electronically amplified to actuate its DPDT Repeatability: ±1% of full scale.
slave relay and switching occurs. Dead band between make and break Electrical Rating: 10A @ 28 VDC, 10A @ 120, 240 VAC.
is 1% of full scale or less - just enough to assure positive, chatter-free Electrical Connections: Screw terminals.
operation. Power Requirements: 120 VAC, 50/60 Hz; 240 VAC & 24 VAC;
Power optional.
Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Set Point Adjustment: Adjustable knobs on face.

DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.com


P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
B-33:B-33 7/30/10 9:36 AM Page 2

Bulletin B-33
page 2

INSTALLATION 3. Mounting
1. Location The Photohelic® Switch/Gage is normally mounted before making
All parts of the Dwyer® Photohelic® pressure switch/gage are ruggedly electrical connections, as the electrical enclosure is independent of the
constructed and will stand a moderate amount of vibration, physical mounting means and may be removed at any time.
shock, and handling. Normal care in handling and installation is all that
is required. In cases where instrument panel vibration is severe, the Panel Mounting
panel should be a spring mounted or the amplifier-relay unit mounted Normal mounting is flush or through panel is shown in Fig. 2. Be sure to
remotely on a more stable surface. allow 4-3/8˝ extra space behind the unit for electrical enclosure removal.
Make a single 4-13/16˝ diameter hole in the panel. Insert the entire
Select a location where the ambient temperature will not exceed 120°F. Photohelic® Switch/Gage unit from the front, then slip on the mounting
Pneumatic pressure sensing lines may be run any necessary distance. ring and snap ring from the rear. Seat the snap ring in its groove, back
For example, 250 foot sensing lines will not affect accuracy but will damp up the mounting ring against snap ring and tighten the four (4) 2˝ No. 6-
the reading slightly. Do not restrict lines. If pulsating pressure or vibration 32 clamp screws provided. If behind panel space is critical, the amplifier-
causes excessive pointer oscillation or relay chatter, consult factory for relay unit can be mounted remotely. See the Remote-Relay Mounting
additional damping means. Instructions for details.

2. Position
The Photohelic® Pressure Switch/Gage may be mounted as an integral
package or the amplifier-load relay assembly and housing may be
mounted remotely from the indicating gage-phototransistor unit.
Extension cords with 7 pin plugs and receptacles are available from
Dwyer for interconnection of the two units.

The unit may be mounted in any desired position, scale vertical or


horizontal, without affecting its accuracy, but must be rezeroed if position
is changed from horizontal to vertical or vice versa. The -0 and -00
models must be mounted with the scale vertical.

Through Panel Mounting

SNAP RING GROOVE

4-13/16˝ (122 mm)


DIA. HOLE REQUIRED 1/8˝ MALE NPT PRESSURE CONNECTIONS.
FOR PANEL MOUNTING SINGLE HIGH PRESSURE CONNECTION
FOR SERIES 36000A MODELS.

Fig. 2
B-33:B-33 7/30/10 9:36 AM Page 3

Bulletin B-33
page 3
Gage Mounting with Relays Remote Remote Amplifier-Relay Unit
Where it is desirable to mount the amplifier-relay unit separate from the
gage-phototransistor unit, the gage may be mounted either as shown in
Fig. 2 (except less amplifier-relay portion) or surface mounted as shown
in Fig. 3A. Use the layout shown in Fig. 3B to locate holes. The complete
package cannot be surface mounted.

Surface Mounting

Fig. 4A

Hole Layout
Ø3/16
TYP 4 PLACES

Fig. 3A

4-9/32
[108.74]
Hole Layout (Front)

THREE 3/16 DIA.


HOLES AT 120°
SURFACE MTG.
4-9/32
3/4 DIA. HOLE [108.74]
FOR WIRE CONN.
5
[127.00] SQ

Fig. 4B
1-1/8
[28.58]
4. Pneumatic Connections & Zeroing
After installation but before making pressure connections, set the
indicating pointer exactly on the zero mark, using the zero adjust screw
located at the bottom of the front cover. Note that this adjustment can
only be made with the high and low pressure taps both open to
atmosphere.

Connect the high and low pressure taps to positive, negative, or


differential pressure sensing points. Use 1/4˝ diameter metal or other
1-1/8 instrument tubing and 1/8˝ NPT adaptors at the Dwyer®. Photohelic®
[28.58]
pressure/switch gage. Adaptors for rubber or soft plastic tubing are
Fig. 3B furnished with the instrument for use where this type of connection is
preferred.
Remote Relays Mounting
If the Photohelic® Switch/Gage is not used to sense differential pressure,
The amplifier - relay unit may be mounted remotely as shown in Fig. 4A.
one of the pressure taps must be left open to atmosphere. This will allow
Use the hole layout as shown in Fig. 4B for this option.
the reference pressure to enter. In this case, installation of a Dwyer®. No.
Additional mounting information for special requirements is available
A-331 Filter Plug or similar fitting in the reference pressure tap is
from the factory.
recommended to reduce the possibility of dust entering the instrument.

Note: If the Photohelic® switch/gage is over pressured, pointer may


‘jump” from full scale back to zero and remain there until the excess
pressure condition is relieved. Users should be aware of possible false
zero pressure indications under this conditions.
B-33:B-33 7/30/10 9:36 AM Page 4

Bulletin B-33
page 4

ELECTRICAL CONNECTIONS Terminal Board


1. Cover
The amplifier-relay unit has an easy to remove housing. Remove the SECTION B SECTION C
three (3) screws as shown in Fig. 5 and slide the housing off. Make all
the electrical connections before reinstalling and refastening the
housing.
SECTION A SECTION D
2. Conduit
Electrical access to the connection box portion of the relay housing is by
bottom opening for 3/4˝ conduit. Use of flexible conduit is recommended.
It should be supported from the panel or other suitable surface to prevent
the wiring system from exerting undue strain on the instrument. See Fig.
5. SECTION E

Mounting Details

COVER MOUNTING SCREWS


CAUTION: Do not apply electrical
current to terminals in sections B and C.
Fig. 6
Separate Ground Wire attachment is provided for by a No. 6-32 screw
on the mounting bracket near the conduit opening. An additional ground
wire connection is located on the side of the gage body for use when the
amplifier-relay unit is mounted remotely.
4-3/8 [111.13]
COVER PULL
OUT Single Set-Point instruments are furnished with the right or high set-
FLEXIBLE CONDUIT point components and circuitry in place. These are connected to
Sections A and B of the terminal board. The left or low set-point
components are omitted.

SUPPORT CONDUIT 4. Circuit Style


FROM PANEL The Photohelic® Switch/Gage is available with several factory installed
optional internal circuits. They are identified as to style by a label shown
in Fig. 7. This label is mounted prominently on the terminal board of each
instrument. The letter H denotes a circuit in which the relay can be made
Fig. 5 to latch or remain energized after pressure increase to its set-point.

Circuit Label
3. Terminal or Connection Board Layout
In Fig. 6,”Terminal Board”, Section A contains the connections for the
load or slave relay actuated by the high or right set-point. This relay is a
double pole, double throw type. The two top connections are normally CIRCUIT:
closed, the two middle connections are normally open, and the bottom POWER SUPPLY:
connections are the common pair. The relay is in its normal or De- CONTACT RATING:
Energized position when pressure is below the right hand set-point.

Section D is exactly the same as Section A except that its load or slave
relay is controlled by the low or left set-point. The De-Energized position Fig. 7
is below the left hand pointer set-point.

Section B contains the external connections to the holding coil circuit for The letter “L” denotes a circuit in which the relay can be made to latch or
the high or right set-point relay and Section C contains similar remain de-energized after pressure decrease to its set-point. Two letters
connections for the low or left set-point relay. The function and use of are required to fully identify a dual set-point unit. Thus, circuit style HH,
these connections varies somewhat depending on the circuit style of the which is standard, is a dual set-point circuit which has provisions for
instrument. See paragraphs 5 and 6 for details. latching on pressure increase to either set-point. Single relay units are
identified by the letters “SR” followed by “H” for the standard unit or “L”
Section E contains the power connections for the control unit for the special low latch unit. Units for use with other than standard 117
transformer primary. The transformer in turn supplies reduced voltage VAC will be so indicated on the label.
power for the LED, phototransistor, amplifier unit, and load relay pull in
and holding coils. Connections must always be made to this section in
order to put the unit in operation. Standard units are designed for 117
VAC input to the transformer. Special units are also available for other
voltages.
B-33:B-33 7/30/10 9:36 AM Page 5

Bulletin B-33
page 5

5. Dual Set Point Automatic Reset 9. Dual Set-Point Special Purpose Circuits
Circuit Style HH is used for simple on-off switching applications. To place Circuit Style LL may be used where manual reset following maintained
in service, connect load circuits to the appropriate terminals in Section A contact on pressure decrease to either set-point is desired. Circuit Styles
(Fig. 6) for the right set-point and Section D for the left set-point. Note the HL and LH are combination units. For special combinations of features,
the N.O. contacts are open when the gage pressure pointer is to the left special units, and detailed instructions regarding their use, consult
of the set-point pointers. No connections are necessary in Section B and factory.
C. Make external ground connections as required and connect power to
Section E for the control unit. To use circuit style LL for automatic reset, 10. Single Set-Point Photohelic® Switch/Gage
a jumper wire must be installed between the upper and lower terminals The single set-point Photohelic® Switch/Gage is furnished with the right
in sections B and/or C. set-point only. Terminals in Section A and B (Fig. 6) are connected to this
relay. Circuit Style SRH is wired or automatic reset as in paragraph 5.
6. Dual Set Point Manual Reset Manual reset is accomplished by adding a normally closed reset switch
Circuit Style HH may also be used for manual reset applications where it or push button to the circuit as described in paragraph 6.
is desired to have maintained contact on either relay following pressure
increase above its set-point. Load or signal connections are made to the 11. Single Set-Point Special
appropriate terminals in Sections A and D (as in paragraph above). Manual reset after actuation on falling pressure can be obtained by using
Connect terminals in Sections B and C through normally closed switches Circuit Style SRL. Consult the factory for special units and detailed
or push buttons as shown in Fig. 8. Use of “dry-circuit” type switches instructions regarding their use.
such as Dwyer Part No. A-601 with palladium, gold, etc. or rotary wiping
action type contacts is recommended. Make external ground 12. Placing in Service
connections as required and connect power to Section E for the control In normal operation each relay is de-energized when the pressure
unit. applied to the instrument is below its set-point. Special low-latching units
will ordinarily have to be reset before placing on the line in normal
Circuit style LL is used for manual reset applications which require that operation.
contact be maintained following pressure decrease below the set-point.
High-Low Limit Control (Circuit HH)
Load connections are made to the appropriate terminals in Sections A
and D. A normally open type manual reset switch such as Dwyer Part No. RESET JUMPERS
A-601 is connected to the terminals in sections B and C. The circuit must
be “armed” by momentarily closing the switch while the black pointer is
to the right of the set-point. From that point on, the circuit will latch on
pressure decrease below the set-point and remain latched on pressure
increase until manually reset with the optional switch.
1/6 HP*
117 VOLT
Manual Reset with Circuit HH LOAD

RESET RESET

117 VOLT LINE

*Note: For larger motors, use the Photohelic® in a maintained contact,


117 Volt Control or Push Button Circuit of the motor starter.
Fig. 9

13. Failure Mode


CAUTION: Do not apply electrical The Photohelic® Switch/Gage circuit design provides certain protection in
current to terminals in sections B and C. the event of a loss of pressure or electrical power. In either case, both
relays will de-energize, returning to their normal “zero pressure” state.
Fig. 8 The exceptions to this are models with center zero ranges. Because the
relays on all standard models are always energized when the indicating
(black) pointer is to the right of their respective set points, the relay action
7. Dual Set Point Automatic and Manual Reset Combinations on loss of pressure will depend on set-point position, since either of them
Circuit style HH may be used with either set-point wired and operating as could be located to the left of zero. As an example; if the left pointer were
in paragraph 5 and other set-point wired and operating as in paragraph set at -2 in. w.c. and negative pressure was -3 in. w.c., a loss of that
6. pressure would allow the black pointer to return to the center and thus
cause the low set-point relay to energize.
8. High Low Limit Control - Dual Set-Point
Circuit style HH may be used to control fans, dampers, pumps, etc. MAINTENANCE
between the set-points of a Photohelic® Switch/Gage. To accomplish this, Photohelic® Switch/Gages are precision instruments, expertly assembled
use one set-point relay to reset the other as shown in the wiring diagram and calibrated at the factory. They require no lubrication or periodic
Fig. 9. In this typical application, the load (for instance a fan) would be servicing. If the interior is protected from dust, dirt corrosive gases and
connected to the N.C. contacts of the right set-point relay, Section A (Fig. fluids, years of trouble-free service may be expected. Zero adjustment
6)/ On pressure rise to the right set-point, its relay would pull in and hold should be checked and reset occasionally to maintain accuracy. Any
even though pressure might then fall below that set-point, its relay would repairs necessary to either the Magnehelic® pressure gage or the
automatically be De-Energized, return to its normal position and in so electronic components should be performed by a trained instrument
doing, open the holding coil circuit from Section B (Fig. 6). The right set- mechanic. In most cases, this is best accomplished by returning the
point relay would thus be reset and the cycle could repeat. complete Photohelic® Switch/Gage to the Dwyer Instruments, Inc.
factory.
B-33:B-33 7/30/10 9:36 AM Page 6

Bulletin B-33
page 6

PHOTOHELIC® PRESSURE SWITCH/GAGE

MODEL AND RANGES

Range, Dual Scale Air Velocity Units


Range, Zero (for use with pitot tube) Range,
Inches Center Ranges, Range, Air Range Minor Zero
of Minor Inches Minor Inches of Velocity CM of Div. Center Minor Div.
Model Water Div. Model of Water Div. Model Water FPM Model Water CM Model Pascals Pascals
3000-00 0-.25 .005 3300-0 .25-0-.25 .01 3000-00AV 0-.25 300-2000 3000-15CM 0-15 .503300-250Pa 125-0-125 125-0-125
3000-0 0-.50 .01 3301 .5-0-.5 .02 3000-0AV 0-50 500-2800 3000-20CM 0-20 .503300-500Pa 250-0-250 250-0-250
3001 0-1.0 .02 3302 1-0-1 .05 3001-AV 0-1.0 500-4000 3000-25CM 0-25 .50 Range Minor Div.
3002 0-2.0 .05 3304 2-0-2 .10 3002-AV 0-2.0 1000-5600 3000-50CM 0-50 1.0 Kilo- Kilo-
3003 0-3.0 .10 3310 5-0-5 .20 3010-AV 0-10 2000-12500 3000-80CM 0-80 2.0Model Pascals Pascals
3004 0-4.0 .10 3320 10-0-10 .50 Range, 3000-100CM 0-100 2.03000-1kPa 0-1.0 .02
3005 0-5.0 .10 3330 15-0-15 MM of Minor Div. 3000-150CM 0-150 5.03000-1.5kPa 0-1.5 .05
1.0
3006 0-6.0 .20 Model Water MM 3000-200CM 0-200 5.03000-2kPa 0-2.0 .05
3008 0-8.0 .20 Minor 3000-6MM 0-6 .20 3000-250CM 0-250 5.03000-3kPa 0-3.0 .10
3010 0-10 .20 Range Div. 3000-10MM 0-10 .50 3000-300CM 0-300 10.0
3000-4kPa 0-4.0 .10
3015 0-15 .50 Model PSIG PSIG 3000-25MM 0-25 .50 Range, 3000-5kPa 0-5.0 .10
3020 0-20 .50 3201 0-1 .02 3000-50MM 0-50 1.0 Zero 3000-8kPa 0-8.0 .20
3025 0-25 .50 3202 0-2 .05 3000-80MM 0-80 2.0 Center
Minor 3000-10kPa 0-10 .20
3030 0-30 1.0 3203 0-3 .10 3000-100MM 0-100 2.0 Cm ofDiv. 3000-15kPa 0-15 .50
3040 0-40 1.0 3204 0-4 .10 Range, Model WaterCM 3000-20kPa 0-20 .50
3050 0-50 1.0 3205 0-5 .10 Zero 3300-4CM 2-0-2.10 3000-25kPa 0-25 .50
3060 0-60 2.0 3210 0-10 .20 Center Minor 3300-10CM 5-0-5.20 3000-30kPa 0-30 1.0
3080 0-80 2.0 3215 0-15 .50 MM of Div. 3300-30CM 15-0-15
1.0 Range,
3100 0-100 2.0 3220 0-20 .50 Model Water MM Minor Zero Minor
3150 0-150 5.0 3230 0-30 1.0 3300-20MM 10-0-10 .50 Range, Div. Center Div.
36003S 0-30 1.0 Model Pascals Pascals Kilo- Kilo-
36006S 0-60 2.0 3000-60Pa 0-60 2.0 Model pascals pascals
36010S 0-100 2.0 3000-125Pa 0-125 5.0 3300-1kPa .5-0-.5 .02
36020S 0-200 5.0 3000-250Pa 0-250 5.0 3300-3kPa 1.5-0-1.5 .10
36030S 0-300 10 3000-500Pa 0-500 10.0
36060S 0-600 20 3000-750Pa 0-750 25.0
36100S 0-1000 20
36300S 0-3000 100
36600S 0-6000 200
*Note: The Photohelic® pressure switch/gage may be used in an Under Writers Laboratories approved industrial control panel if the usage conforms to UL
specifications for the acceptance of unlisted components.

DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.com


P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
B-33:B-33 7/30/10 9:36 AM Page 7

Boletín B-33

El Interruptor/Indicador de Presión Photohelic® Serie 3000*


INSTRUCCIONES Y OPERACION

2-1/2 [63.50] (4) 6-32 HOLES


1/8 FEMALE NPT HIGH 2-1/16 [52.39] EQUALLY SPACED ON
PRESSURE CONNECTION
2 [50.80] A 5-1/8 [130.18] B.C.
1/8 FEMALE NPT LOW 1-1/4
PRESSURE CONNECTION [31.75]

Ø4-3/4 Ø4-47/64
[120.65]
3-7/8 SQ [120.25] Ø5
[98.43]
[127.00]

3/4 CONDUIT Ø4 [101.60]


CONNECTION 3-7/8 [98.43] 5/8 [15.88] FACE
5-1/8 [130.18] 5-1/2 [139.70]
5/8 [15.88] PANEL O.D.
6-3/8 [161.93] MAX
4-3/8 [111.13] (7-5/8 [193.68]) 3/16 [4.76] MOUNTING
HOUSING REMOVAL RING

Figura 1

El Interruptor/Indicador de Presión Photohelic® es un an interruptor ESPECIFICACIONES


de presión muy versátile y preciso, combinado con el indicador de
presión de respuesta rápida Magnehelic®. Los modelos están GAGE SPECIFICATIONS
disponibles con uno o dos fototransistores que actúan sobre relés. A la Service: Air and non-combustible, compatible gases.
lectura del indicador no le afecta la operación del interruptor. Facilidad Wetted Materials: Consult factory.
de ajuste del punto de trabajo mediante botones de control. Las presión Accuracy: ±2% of full scale at 70°F (21.1°C). ±3% on -0 and ±4% on -
aplicada y los puntos do interrupción (disparos) son claramente visibles 00 models.
en todo momento. La banda muerta tiene una anchura de menos del Pressure Limits: -20" Hg. to 25 psig (-0.677 to 1.72 bar). MP option;
1% del fondo de escala. Los relés de doble circuito, doble disparo 35 psig (2.41 bar), HP option; 80 psig (5.52 bar). 36003S – 36010S;
pueden ser facilmente entrelazados para proporcionar un control 150 psig (10.34 bar). 36020S and higher; 1.2 x full scale pressure.
variable de la banda muerta. Para presión positiva, negativa y Temperature Limits: 20 to 120°F.
diferencial; para models de un sólo relé, presión positiva sólo en modelo (-6.67 to 48.9°C) Low temperature option available.
36000S. Rangos de fondo escala disponibles de 0 - 0.25” c.a. a 0 - 6000 Process Connections: 1/8˝ female NPT.
psig. Size: 4˝ (101.6 mm) dial face, 5˝ (127 mm) O.D. x 8-1/4˝ (209.55 mm).
Weight: 4 lb (1.81 kg).
SENTIDO DEL PHOTOHELIC® -
SU FUNCIONAMIENTO SWITCH SPECIFICATIONS
Switch Type: Each setpoint has 2 Form C relays (DPDT).
En una applicación de control tipica, el interruptor/indicador Photohelic® Repeatability: ±1% of full scale.
controla entre los puntos de trabajo de alta y baja presión. Cuando la Electrical Rating: 10A @ 28 VDC, 10A @ 120, 240 VAC.
presión cambia, alcanzando cualquier presión del punto de trabajo, el Electrical Connections: Screw terminals.
haz de lud de un LED dirigido hacia el fototransistor limitador será Power Requirements: 120 VAC, 50/60 Hz; 240 VAC & 24 VAC Power
interrumpido por el escudo de luz del eje helicoidal. El cambio de la optional.
señal resultante es electronicamente amplificada para actuar sobre su Mounting Orientation: Diaphragm in vertical position. Consult factory
relé esclavo DPDT y ocasiona el disparo del interruptor. La banda for other position orientations.
muerta entre lo marcado y el corte es del 1% del fondo de escala o Set Point Adjustment: Adjustable knobs on face.
menor. Suficiente para asegurar una operación positiva y libre de
errores.
B-33:B-33 7/30/10 9:36 AM Page 8

Boletín B-33
P. 2
INSTALACION Montaje: El Photohelic® se monta normalmente antes de hacer las
conexiones eléctricas, por lo tanto la carcasa eléctrica es independiente
Localización: Todas las partes del interruptor/indicador Photohelic® de de la forma me montaje y puede ser quitada en cualquier momento.
Dwyer® están robustamente construidas para soportar una moderada
cantidad de vibración, impacto físico y manejo del mismo. Un cuidado Montaje en Panel: El montaje normal es embutir o atravesar el panel
normal en su manejo e instalación es todo lo que se precisa. En los como muestra la Fig. 2. Asegúrase de que deja un espacio extra de 4-
casos en los que la vibración del panel de instrumentos sea intensa, éste 3/8” (111 mm) detrás de la unidad; quitar la carcasa eléctrica. Hacer un
deberá estar montado sobre algún resorte, o bien, la unidad del relé- simple agujero de 4 13/16˝ (122 mm) de diametro en el panel. Inserter
amplificador estar montada en una superficie más estable. todo el Photohelic® por el frontal del panel, luego deslizar el anillo de
sujección y encajar el anillo por la parte de atrás. Coloque el anillo de
Elegir un lugar donde la temperatura ambiente no exceda de 120°F sujección en su ranura, mueva hacia atrás el anillo de sujección y una
(49°C). vez más encaje el anillo y apriete los cuatro (4) tornillos de abrazadera
de 2˝ (50 mm) No. 6-32 que se suministran. Si el espacio detrás del
Las lineas sensoras de presión neumática deben alargarse a la distancia panel es crítico, la unidad relé-amplificador se puede montar de forma
que sea necesaria. Por ejemplo, 250 pies (75 m) de lineas sensoras no remota. Ver Instrucciones de Mantaje de Relé Remoto para más
afectarán a la precisión, pero amortiguarán la lectura ligeramente. Si la detalles.
presión pulsante o la vibración dan lugar a un punto de excesiva
oscilación o el relé castañea, consultar con la fábrica para medios
adicionales de amortiguamiento. Ver accesorios adecuados con el
Boletín S-101.

Pocisión: El Photohelic® debe ser montado como un conjunto


compacto, o bien el modulo rele carga-amplificador ensamblado y su
carcasa se monta en un lugar remoto de la unidad indicador-
fototransistor. Los cables de extgension con conexion de 7 pies y los
conectores están disponibles en Dwyer para interconectar las dos
unidades.

La unidad puede estar montada en la posición que se


desee, la escala vertical u horizontal, sin que ello afecta a la precisión,
pero debe ser recalibrado el cero si la posición cambia de horizontal a
vertical o viceversa. Los models - 0 y - 00 deben estar montados con la
escala vertical.

Ranura Del Anillo De Suceccion

Ø4-13/16 [122.24]
Dianetroaguiero Tapones De Presion
Neumatica

Figura 2
Atraves del Panel de Montaje
B-33:B-33 7/30/10 9:36 AM Page 9

Boletín B-33
P. 3
Montaje del Indicador con los Relés Remotos: Donde se desee
montar la unidad relé-amplificador separada de la unidad
indicador/fototransistor, el indicador puede montarse de cualquiera de
las maneras mostra-das en la Fig. 2 (excepto la parte del relé-
amplificador) o montarse sobre superficie como se muestra en la Fig 3A.
Utilice el trazado monstrado en la Fig. 3B para localizer los agujeros. El
conjunto completo no se puede montar sobre superficie.

Figura 4A
Unidad Relé-Amplificador Remota

Figura 3A Ø3/16
Montaje Sobresuperficie TYP 4 PLACES

Tiesogujeros De Ø3/16 [4.76] Diam.


Separados 120° en la
superjiciede montaje 4-9/32
[108.74]
Agujerode 3/4" [19.05] de diam.
para conexion del cableado

4-9/32
1-1/8 [108.74]
[28.58]
5
[127.00] SQ
Figura 4B
Esquema de los Agujeros

Conecte las espitas de alta y baja presión a los puntos de presión


1-1/8 positiva, negativa o diferencial. Utilice tubo metálico de 4” NPT (3.175
[28.58] mm) del interruptor/indicador de presión Photohelic® de Dwyer®. Los
Figura 3B adaptores para tubos de caucho o de plástico blando son
Esquema del Agujero (de frente)
proporcionados con el instrumento para utilizarlos cuando se prefiera
este tipo de conexión.

Montaje Remoto de los Relés: La unidad relé-amplificador puede Si el Photohelic® no se usa para detectar presión diferencial, una de las
montarse remotamente como se muestra en la Fig. 4A. Ulice el trazado espitas de presión debe abierta a la atmósfera. Esto permitirá la entrada
de agujeros que se muestra en la Fig. 4B para esta opcion. Para mas de la presión de referencia. En este caso, se recomienda la instalación
información sobre el montaje para requerimientos especiales, consulte de un filtro de Dwyer® No. A-331 u otro similar apropiado en la espita de
con la fabrica. la presión de referencia para reducir la posibilidad de entrada de polvo
en el instrumento.
Conexiones Neumaticas y Ajuste del Cero: Después de la
instalación, pero antes de hacer las conexiones de presión, coloque el Nota: Si el interruptor/indicador Photohelic® está sobre-presionado, el
puntero de indicación (la aguja) exactamente sobre la marca del cero, puntero (aguja) “salta” desde el final de la escala hasta el cero y se
usando el tornillo de ajuste del cero situado en la parte de abajo de la mantiene ahí hasta que la condición de exceso de presión se alivia. Los
cubierta frontal. Tenga en cuenta que este ajuste sólo se pueda hacer usuarios deberían ser consecuentes de las posible indicaciones de falso
con las espitas de alta y baja presión abiertas a la atmósfera. cero bajo esta condición.
B-33:B-33 7/30/10 9:36 AM Page 10

Boletín B-33
P. 4

CONEXIONES ELECTRICAS Los instrumentos de un Punto de Trabajo se suministran con los


componentes del punto de trabajo de alta o derecho y la circuitería
1. Cubierta: La unidad relé-amplificador tiene una carcasa fácil de correspondiente. Esta está conectada a las Secciones A y B de la placa
quitar. Quite los tres (3) tornillos como se muestra en la Fig. 5 y deslice de terminales. Los componentes del punto de trabajo izquierdo o de
hacia afuera la carcasa. Haga todas las conexiones eléctircas antes de baja están omitidos.
reinstaler y reasegurar la carcasa.
4. Tipo de Circuito: El Photohelic® está disponible con varios circuitos
2. Conducto: El acceso eléctrico a la parte de la carcasa del relé de la internos opcionales instalados en fábrica. Están identificados como tipo
caja de conexión se hace abriendo un tapón para conductos de (19 mm). por una etiqueta mostrada en la Fig. 7. Esta ertiqueta se monta de forma
Se recomienda el uso de conductos flexibles. Este se sujetaría al panel prominente en la placa de terminal de cada instrumento. La letra H
u otra superficie apta para prevenir el sistema de cableado de un indica un circuito cuyo relé puede pasar a almacenar un estado eléctrico
esfuerso de tensión indebido en el instrumento. Ver Fig. 5. o retenerse energizado (activado) después de que la presión sobrepase
or un incremento su punto de trabajo.
3. Esquema del Terminal o Placa de Conexión: En la Fig. 6, “Placa
de Terminales,” la Seccion A contiene las conexiones para al relé de La letra L indica un circuito en el cual el relé pueda pasar a almancer un
carga o esclavo actuado por el punto de trabajo derecho o de alta. Este estado eléctrico o retenerse des-energizado después de que la presión
relé es de tipo doble polo, de doble circuito. Las dos conexiones sobrepase por decremento su punto de trabajo. Se necesitan dos letras
superiores son normalmente carradas, las dos del medio son para indentificar completamente una unidad de doble punto de trabajo.
normalmente abiertas y las dos de abajo son el común. El relé está en Así, el ecicuito de tipo HH, el cual es el estándar, es un circuito de doble
su posición normal o des-energizado cuando la presión está por debajo punto de trabajo, el cual está provisto para el almacenamiento do
del punto de trabejo del lado derecho (del alta). estados de corriente (latching) cuando ambos puntos de trabajo son
sobrepasados por un incremento de la presión. Las unidadas de un sólo
La Seccion D es exactamente igual que la Seccion A, excepto que su relé están identificadas por las retras SR seguidas de una H para la
relé de carga o esclavo está controlado por el punto de trabajo izquierdo unidad estánder o por una L para unidades especiales de
o de baja. La posición almacenamiento de estado de corriente (lach) en decremento. Las
des-energizada está pro debajo del punto de trabajo del lado izquierdo unidades para usar con otros estándares distinos de 117 VCA serán así
(de baja). indicados en la etiqueta.
La Seccion B contiene las conexiones externas para el mantenimiento
del circuito bobinado para relé del punto de trabajo derecho o de alta y 5. Reset Automatico de Doble Punto de Trabajo: El circuito tipo HH
la Seccion C, contiene conexiones similares para el relé del punto de se usa para aplicaciones simples de interruptor on-off. Para ponerlo en
trabajo izquierdo o de baja. La función y uso de estas conexiones varía sevicio conecte los circuitos de carga a los terminales apropiados en la
algo dependiendo del tipo de circuito del instrumento. Ver párrafos 5 y Sección A (Fig. 8) para el punto de trabajo derecho y en la Sección D
6 para más detalles. para el punto de trabajo izquierdo. No son necesarias las conexiones en
las Secciones B y C. Tenga en cuente que los contactos N.A. están
La Seccion E contiene las conexiones de alimentación para el abiertos cuando la aguja del indicador de presión está a la izquierdo de
transformador primario de la unidad de control. El transformador a los punteros de los puntos de trabajo. No es necesaria ninguna
cambio suministra un reducido voltaje de alimentación para el LED, el conexión en las Secciones B y C. Haga las conexiones externas a tierra
fototransistor, la unidad amplificadora y tirar del relé descarga y como se requieren y conecte la alimentación a la Sección E para el
mantener el bobinado. Las unidades estánder están diseñadas para 117 control de la unidad.
VCA de entrada al transformador. También están disponibles unidades Para usar el circuito tipo LL para reset automatico, se debe instalar un
especiales para otros voltajes. puente de hilo entre los terminales superior e inferior de las secciones b
y/o C.
Está provisto de una atadura para Cable Separado a Tierra mediante Seccion B Seccion C
un tornillo No. 6-32 en la repisa montada carca de la abertura del
conducto. Está localizado un cable adicional a tierra en el lateral del
cuerpo de indicación para usa lo cuando la unidad relé-amplificador está
montada remotamente.
Seccion A Seccion D

Tornillos De Montaje De La Cubierta

Seccion E

4-3/8 [111.13]
Espacio Para
Sacar La Cubierta Figura 6
Conducto Flexible Placa de Terminales

Soporte Del Conducto


Del Panel
TIPO DE CIRCUITO:
TENSION DE ALLMENTACION:
RANGO DE CONTACTO:

Figura 5
Detalles del Montaje
Figura 7 Etiqueta del Circuito
B-33:B-33 7/30/10 9:36 AM Page 11

Boletín B-33
P. 5
6. Reset Manual de Doble Punto de Trabajo: El circuito tipo HH 8. Controlo del Límite Alta Baja-Doble Punto de Trabajo: El circuito
también se puede utilizar para aplicaciones con reset manual donda se tipo HH puede usarse para controlar ventiladores, tiros, bombas, etc.,
desee hacer un contacto mantenido sobra cualquier relé después de entre los puntos de tr bajo de un Photohelic®. Para efectuar esto, use el
que la presión haya aumentado por encima de su punto de trabajo. Las relé de un punto de trabajo para hacer reset del otro como se muestra
conexiones de carga o señal se hacen a los terminales apropiados en en el diagrama eléctrico de la Fig. 9. En esta típica aplicación la carga
las Secciones A y D (como en el párrafo 5 anterior). Connectar los (por ejemplo, un ventilador) se conectaría a los contactos N.C. del relé
terminales en las secciones B y C mediante interruptores Nomalmente del punto de trabajo, Sección A (Fig. 6). Al aumentar la presión en el
Cerrado (N.C.) o pulsadores como se muestra en la Fig. 8. Se punto de trabajo derecho, su relé se cargaría y se manendría aunqué la
recomienda el uso de interruptores tip “dry-circuit” (circuito seco), tales presión pudiera caer por debajo de ese punto de trabajo. Si la presión
como el Dwyer P/N A-601 con contactos de paladio, oro, etc, o de tipo continúa cayendo hasta el punto de trabajo izquierdo, su relé se des-
rotativo protegidos del exterior. Haga las conexiones externas a tierra energizaria automáticamente, volviendo a su posición normal y, en tal
como se requiere y conecte la alimentación a la Sección E para el situación, se abre el circuito del bobinado mantenido de la Sección B
control de la unidad. (Fig. 6). El relé del punto de trabajo derecho se haría así un reset y el
icilo se repetiría.
RESET RESET

9. Circuitos de Doble Punto de Trabajo de Propósito Especial: El


circuito tipo LL se puede usar donde se desee de forma que al hacer un
reset manual se mantenga el contacto al decrecer la presión en
cualquiera de los puntos de trabajo. Los circuitos tip LH y HL son
unidades hechas con combinaciones. Para características especiales
de combinaciones, unidades especiales e instrucciones detalladas en
cuanto a su uso, consulte con la fábrica.

10. Photohelic® de un Punto de Trabajo: El Photohelic® de un punto


de trabajo derecho solamente. Los terminales de las Secciones A y B
(Fig. 6) están conectados a este relé. El circuito tipo SRH está cableado
para rese automático, come se explica en el párrafo 5 anterior. El reset
manual está efectuado para añadir un interruptor de reset tipo N.C. o un
PRECAUCION: No applicar corriente eléctricas pulsador al circuito descrito en el párrafo 6 anterior.
a los terminales de las secciones B y C.
Figura 8 Reset Manual con Circuito HH

El circuito LL se usa para aplicaciones de reset manual el las cuales se 11. Punto de Trabajo Unico Especial: Se puede obtener un reset
requiere que el contacto se mantenga despues de que la presión haya manual después de la actuación en caida de presión al usar un circuito
disminuido por debajo del punto de trabajo. tipo SRL. Consulte con la fábrica para unidades especiales e
instrucciones detalladas en cuanto a su uso.
Las conexiones de carga se hacen a los terminales apropiados en las
Secciones A y D. Se conecta un interruptor de tipo N.A, para el reset 12. Situación en Servicio: En operación normal cada rel se des-
manual, tal como el Dwyer P/N A-601, a los terminales de las Secciones energiza cuando la presión aplicada al instrumento está por debajo de
B y C. El circuito puede quedar “arruinado” por un cierre momentáneo su punto de trabajo. Las uni-dades especiales de almacenamiento de
del interruptor mientras la aguja negra está a la derecha del punto de estado eléctrico en bajada, generalmente se les tendrá que hacer un
trabajo. Desde ese punto, el circuito almacena el estado de corriente reset antes de situarías en la línea en operación normal.
cuando la presión decrece por debajo del punto de trabajo y retiene este
estado de corriente cuando la presión veulve a crecer, hasta que se 13. Modo de Fallo: El diseño del circuito del Photohelic® está provisto
hace un reset manualmente con el interruptor opcional. de cierta protección en caso de una pérdida de presión o de
alimentación eléctrica. En cualquier caso, ambos relés se des-
7. Combanaciones de Reset Manual y Automático de Doble Punto energizaran, volviendo a su estado normal de “Presión Cero.” Las
de Trabajo: El circuito tipo HH puede usarse con cualquiera de los excepciones a esto son modelos con rangos de cero centrado.
puntos de trabajo, cableado y operando como en el párrafo 5 anterior y Debido a que los relés en todos los models estánder están siempre
el otro punto de trabajo cableado y operando como en el párrafo 8. energizados cuando la aguja inidcadora está a la derecha de sus
respectivos puntos de trabajo, la acción del relé en la pérdida de presión
Puentes De Reset
dependerá de la posición del punto de trabajo, desde cualquiera de ellos
se podria localizar a la izquierda del cero. Como ejemplo: Si el puntero
izquierda estuviera ajustado a -2” c.a. y la presión negativa fuera de -3”
c.a., una pérdida de esa presión permitiría que la aguja indicadora
(negra) volviera al centro y así causa que el relé del punto de trabajo en
baja se energiza.
Carga
1/6 HP
117 V

Linea De 117 V
Nota: Para motores mayores, utilice el Photohelic en un contacto
mantenido, controle los 117 V ó pulse el boton del circuito del
estarter del motor.
Figura 9 Control de Limite Alta-Baja (Circuito HH)
B-33:B-33 7/30/10 9:36 AM Page 12

Boletín B-33
P. 6

MANTENIMIENTO Y SERVICIO

Los Interruptores/Indicadores Photohelic® de Dwyer® son instrumentos de precisión, expertamente ensamblados y calibrados en la fábrica.
No necesitan lubricación o revisiones periódicas. Si el interior está protegido del polvo, suciedad, gases corrosivos y fluídos, se pueden
esperar años de servicio sin ningún problema.

El ajuste del cero debería ser revisado y reajustado de vez en cuando para mantener la precision.

Cualquier reparación necessaria para cualquiera de los indicadores de presión Magnehelic® de Dwyer® o para los componentes electrónicos
debería ser realizada por un mecánico entranado de instrumentos. En muchos casos, la major elección es mandar al interruptor/indicador
completo Photohelic a la fábrica de Dwyer.

El Interrutor/Indicador de Presión Photohelic®

Los Modelos y Rangos

Range, Dual Scale Air Velocity Units


Range, Zero (for use with pitot tube) Range,
Inches Center Ranges, Range, Air Range Minor Zero
of Minor Inches Minor Inches of Velocity CM of Div. Center Minor Div.
Model Water Div. Model of Water Div. Model Water FPM Model Water CM Model Pascals Pascals
3000-00 0-.25 .005 3300-0 .25-0-.25 .01 3000-00AV 0-.25 300-2000 3000-15CM 0-15 .50 3300-250Pa 125-0-125 125-0-125
3000-0 0-.50 .01 3301 .5-0-.5 .02 3000-0AV 0-50 500-2800 3000-20CM 0-20 .50 3300-500Pa 250-0-250 250-0-250
3001 0-1.0 .02 3302 1-0-1 .05 3001-AV 0-1.0 500-4000 3000-25CM 0-25 .50 Range Minor Div.
3002 0-2.0 .05 3304 2-0-2 .10 3002-AV 0-2.0 1000-5600 3000-50CM 0-50 1.0 Kilo- Kilo-
3003 0-3.0 .10 3310 5-0-5 .20 3010-AV 0-10 2000-12500 3000-80CM 0-80 2.0 Model Pascals Pascals
3004 0-4.0 .10 3320 10-0-10 .50 Range, 3000-100CM 0-100 2.0 3000-1kPa 0-1.0 .02
3005 0-5.0 .10 3330 15-0-15 MM of Minor Div. 3000-150CM 0-150 5.0 3000-1.5kPa 0-1.5 .05
1.0
3006 0-6.0 .20 Model Water MM 3000-200CM 0-200 5.0 3000-2kPa 0-2.0 .05
3008 0-8.0 .20 Minor 3000-6MM 0-6 .20 3000-250CM 0-250 5.0 3000-3kPa 0-3.0 .10
3010 0-10 .20 Range Div. 3000-10MM 0-10 .50 3000-300CM 0-300 10.0 3000-4kPa 0-4.0 .10
3015 0-15 .50 Model PSIG PSIG 3000-25MM 0-25 .50 Range, 3000-5kPa 0-5.0 .10
3020 0-20 .50 3201 0-1 .02 3000-50MM 0-50 1.0 Zero 3000-8kPa 0-8.0 .20
3025 0-25 .50 3202 0-2 .05 3000-80MM 0-80 2.0 Center Minor 3000-10kPa 0-10 .20
3030 0-30 1.0 3203 0-3 .10 3000-100MM 0-100 2.0 Cm of Div. 3000-15kPa 0-15 .50
3040 0-40 1.0 3204 0-4 .10 Range, Model Water CM 3000-20kPa 0-20 .50
3050 0-50 1.0 3205 0-5 .10 Zero 3300-4CM 2-0-2 .10 3000-25kPa 0-25 .50
3060 0-60 2.0 3210 0-10 .20 Center Minor 3300-10CM 5-0-5 .20 3000-30kPa 0-30 1.0
3080 0-80 2.0 3215 0-15 .50 MM of Div. 3300-30CM 15-0-15 1.0 Range,
3100 0-100 2.0 3220 0-20 .50 Model Water MM Minor Zero Minor
3150 0-150 5.0 3230 0-30 1.0 3300-20MM 10-0-10 .50 Range, Div. Center Div.
36003S 0-30 1.0 Model Pascals Pascals Kilo- Kilo-
36006S 0-60 2.0 3000-60Pa 0-60 2.0 Model pascals pascals
36010S 0-100 2.0 3000-125Pa 0-125 5.0 3300-1kPa .5-0-.5 .02
36020S 0-200 5.0 3000-250Pa 0-250 5.0 3300-3kPa 1.5-0-1.5 .10
36030S 0-300 10 3000-500Pa 0-500 10.0
36060S 0-600 20 3000-750Pa 0-750 25.0
36100S 0-1000 20
36300S 0-3000 100
36600S 0-6000 200

©Copyright 2010 Dwyer Instruments, Inc. Printed in U.S.A. 7/10 FR# 13-440202-02 Rev.5