Johnson Control Datasheet
Johnson Control Datasheet
FIG:mtgbs
3. Carefully pull the locking tabs on the right side of
the thermostat mounting base and unlock the
Printed Circuit Board (PCB). Open the PCB to the Figure 3: Securing the Thermostat
left as illustrated in Figure 2. Mounting Base to the Wall
2 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Wiring To wire the thermostat:
When an existing thermostat is replaced, remove and 1. Strip the ends of each wire 1/4 in. (6 mm) and
label the wires to identify the terminal functions. When connect them to the appropriate screw terminals as
a TEC22x6(H)-2 Series Thermostat is replaced, simply indicated in Table 1 and Figure 6 through
remove the old screw terminal blocks and reinsert them Figure 10.
onto the PCB of the replacement thermostat.
Note: For more details on wiring the
CAUTION: Risk of Electric Shock. LONWORKS network, refer to the
Disconnect power supply before making LONWORKS Network Layout Technical Bulletin
! electrical connections to avoid electric (LIT-1162150).
shock. 2. Carefully push any excess wire back into the wall.
Seal the hole in the wall with fireproof material to
CAUTION: Risk of Property Damage. prevent drafts from affecting the ambient
Do not apply power to the system before
! checking all wiring connections. Short
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
circuited or improperly connected wires
may result in permanent damage to the 4. Reattach the LONWORKS communication wires to
equipment. the LON terminal block. See Figure 5.
Note: If inserting multiple wires into the terminals, be
IMPORTANT: Make all wiring connections in sure to properly twist wires together prior to inserting
accordance with local, national, and regional them in the terminal connectors.
regulations. Do not exceed the electrical ratings of
the TEC22x6(H)-2 Series Thermostat. 5. Reattach the thermostat cover to the mounting
base (top side first).
6. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
cover.
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 3
and Three Speeds of Fan Control Installation Instructions
Three-Pole
Five-Pole Top Left Connector Top Right Connector
24 V~ 24 V~ BO5 BO5
Fan-H Fan-M Fan-L BO3
Hot Com Aux Aux
1 2 3 4 5 6 7 8
FIG:trm_blks_22x6
LON
LON
Eight-Pole Bottom Connector
9 10 11 12 13 14 15 16
4 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Isolated Contacts Isolated Contacts
• Reheat • Reheat
• Lighting • Lighting
• On/Off Actuation • On/Off Actuation
• Exhaust Fan • Exhaust Fan
Power and Fan Power and Fan
Aux Aux
Voltage-Free
Contact
• Door LON
• Remote
Supervisory
BI1 Scom BI2 UI3 Controller
Override
• Filter Alarm LON
• Service Alarm
Voltage-Free
Contact LONWORKS
Voltage-Free LON WORKS
• COC/NH Network Wires
Contact Network
• Remote NSB - OR - Normally Heat Terminal Block
• Motion Closed Contact
• Window = Cold Water
• COC/NC
Normally Cool Twist wires together
SS (Supply Sensor) Closed Contact before inserting them into
COS (Change Over Sensor) = Hot Water the terminals.
FIG:22x6wir
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 5
and Three Speeds of Fan Control Installation Instructions
Wiring To wire the thermostat:
When an existing thermostat is replaced, remove and 1. Strip the ends of each wire 1/4 in. (6 mm) and
label the wires to identify the terminal functions. When connect them to the appropriate screw terminals as
a TEC22x6(H)-2 Series Thermostat is replaced, simply indicated in Table 1 and Figure 6 through
remove the old screw terminal blocks and reinsert them Figure 10.
onto the PCB of the replacement thermostat.
Note: For more details on wiring the
CAUTION: Risk of Electric Shock. LONWORKS network, refer to the
Disconnect power supply before making LONWORKS Network Layout Technical Bulletin
! electrical connections to avoid electric (LIT-1162150).
shock. 2. Carefully push any excess wire back into the wall.
Seal the hole in the wall with fireproof material to
CAUTION: Risk of Property Damage. prevent drafts from affecting the ambient
Do not apply power to the system before
! checking all wiring connections. Short
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
circuited or improperly connected wires
may result in permanent damage to the 4. Reattach the LONWORKS communication wires to
equipment. the LON terminal block. See Figure 5.
Note: If inserting multiple wires into the terminals, be
IMPORTANT: Make all wiring connections in sure to properly twist wires together prior to inserting
accordance with local, national, and regional them in the terminal connectors.
regulations. Do not exceed the electrical ratings of
the TEC22x6(H)-2 Series Thermostat. 5. Reattach the thermostat cover to the mounting
base (top side first).
6. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
cover.
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 3
and Three Speeds of Fan Control Installation Instructions
Connecting the LONWORKS Network Setup and Adjustments
The wiring rules for the LONWORKS network differ from Thermostat Operation Overview
the wiring rules for the Metasys® N2 Bus and the
BACnet® MSTP Bus. For more details on wiring the
LONWORKS network, refer to the LONWORKS Network
Layout Technical Bulletin (LIT-1162150).
To connect the thermostat to the LONWORKS network: Backlit, plain text
LCD is easy to read
1. Connect the LONWORKS network wires to the in any condition.
LONWORKS network terminal block on the
thermostat (Figure 5 and Figure 6).
Note: There is no polarity when connecting the Room Temp
LONWORKS network wires to the thermostat; however, LEDs indicate 70.0ºF
FIG:frnt_vw_22x6
throughout the network. Five keys on the
thermostat
2. After the LONWORKS network wires are connected make operation
to the first thermostat, continue in a daisy-chained easy and intuitive.
fashion to the next device. Figure 11: Front Cover of Thermostat
Note: The LONWORKS network wiring must be twisted-
pair lines. Thermostat User Interface Keys
Do not run the LONWORKS network wiring in the same The TEC22x6(H)-2 Series Thermostat user interface
conduit as line voltage wiring (30 VAC or above) or consists of five keys on the front cover (as illustrated in
other wiring that switches power to highly inductive Figure 11). The function of each key is as follows:
loads (such as contactors, coils, motors, or • MODE key toggles among the system modes
generators). available, as defined by selecting the appropriate
The LONWORKS network requires proper termination operation sequence in the Installer Configuration
and biasing at the end of a segment (a segment is a Menu (for example Off, Heat, Cool, Auto).
physically continuous length of wire). The thermostat is • FAN key toggles among the fan modes available,
not equipped with the ability to provide this termination; as defined by selecting the appropriate fan menu
therefore, it cannot be located at the physical end of a options defined in the Installer Configuration Menu
LONWORKS network segment unless a terminator is (for example Low, Med, High, Auto).
attached. Refer to LONWORKS Network Layout
Technical Bulletin (LIT-1162150) for end-of-line • OVERRIDE key (commercial models) activates the
solutions. override function and allows access to the Installer
Configuration Menu. See the Configuring the
TEC22x6(H)-2 Series Thermostat section.
Overrides the unoccupied mode to occupied at the
local user interface for the specified TOccTime.
(TOccTime is defined by selecting the appropriate
time period in the Installer Configuration Menu.)
Note: If one of the binary inputs is configured to
operate as a remote override contact, this OVERRIDE
function is disabled.
• °C/°F key (hospitality models) changes the
temperature scale to either Celsius or Fahrenheit
and allows access to the Installer Configuration
Menu. See the Configuring the
TEC22x6(H)-2 Series Thermostat section.
Note: For hospitality models, binary inputs can
override from the unoccupied mode to occupied
mode.
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 7
and Three Speeds of Fan Control Installation Instructions
• UP/DOWN arrow keys change the configuration Dehumidification Operation (TEC2236[H]-2
parameters and activate a setpoint adjustment. and TEC2256[H]-2 Models Only)
Backlit Liquid Crystal Display (LCD) Upon detection of space humidity above the adjustable
The TEC22x6(H)-2 Series Thermostats include a humidity setpoint as sensed by the internal humidity
2-line, 8-character backlit display. Low-level sensor, dehumidification activates.
backlighting is present during normal operation, and it Note: Dehumidification operates only in Cooling
brightens when any user interface key is pressed. The mode. Dehumidification does not operate in Off or
backlight returns to low level when the thermostat is left Heating system mode.
unattended for 45 seconds.
Note: A central network command can globally lock
Light-Emitting Diodes (LEDs) out dehumidification to all thermostats.
Three LEDs are included to indicate the fan status, call If the room temperature resides in the deadband
for heat, or call for cooling: between the Cooling and Heating Setpoint:
• The FAN LED is on when the fan is on. • the thermostat forces the fan to low speed
• The HEAT LED is on when heating or reheat is on. • the chilled water valve opens to the specified
• The COOL LED is on when cooling is on. maximum value set by CoolMax
Note: An option is available within the Installer If the thermostat is in cooling demand and the room
Configuration Menu to lock out the scrolling display and temperature rises 2°F above the cooling setpoint, the
show only the Room Temperature parameter. thermostat automatically disables dehumidification. If
the thermostat is in cooling demand and the room
Status LED temperature falls below the current heating setpoint,
The status LED shows the operational status of the the thermostat disables dehumidification.
thermostat. The Status LED is a small green light under
the thermostat cover (under the LONWORKS daughter
board on the left edge when facing the thermostat).
Table 2: Status LED Explanation
Status LED Explanation
Condition
Continuously The thermostat does not have an
On application loaded in its memory.
Flashing at a The thermostat has an application
0.5 Hz rate loaded in its memory but is
unconfigured. Use a LONWORKS network
management tool to bind the thermostat
to a LONWORKS network.
Continuously The thermostat has an application
Off loaded in its memory and is bound to a
LONWORKS network.
8 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Configuring the TEC22x6(H)-2 Series When the thermostat is in the Installer Configuration
Thermostat Menu and left unattended for approximately 8 seconds,
The TEC22x6(H)-2 Series Thermostat comes from the the thermostat reverts to the Status Display Menu.
factory with default settings for all configurable Configuring the Thermostat’s Neuron®
parameters. The default settings are shown in Table 5. Identification
To reconfigure the parameters via the thermostat,
Press and hold the UP/DOWN arrow keys
follow the steps in this section.
simultaneously for five seconds to broadcast the
For additional information on commissioning and thermostat’s Neuron Identification on the LONWORKS
configuring thermostats, adding thermostats to a network.
Network Automation Engine (NAE), thermostat
If the cover is removed, you can see a green LED
mapping, and remote thermostat commanding, refer to
under the LON board flash when the thermostat
TEC22x6(H)-2 LONWORKS Networked Thermostats
broadcasts the Neuron ID. The Neuron ID is on a label
with Two Outputs and Three Speeds of Fan Control
on the Echelon® chip.
Technical Bulletin (LIT-12011175).
You cannot send the Neuron ID while in the Installer
To access the Installer Configuration Menu, press and
Configuration menu.
hold the center key for approximately 8 seconds. Once
the Installer Configuration Menu begins, release and Configuring Inputs BI1, BI2, and UI3
press the center key to scroll through the parameters When BI1 and BI2 are configured for an alarm
listed in Table 5. When the desired parameter is condition, an alarm condition is displayed locally when
displayed, use the UP/DOWN arrow keys to choose the input is closed. An alarm message is included on
the desired selection option. Then press and release the scrolling Status Display Menu and when the
the center key to continue scrolling through the message is displayed, the backlight momentarily
parameters. lights up.
Note: Pressing the FAN key during configuration The UI3 input provides changeover of hot/cold water
restarts the list of displayed parameters at the first switching or supply air temperature monitoring at the
parameter listed in Table 5. thermostat.
Each input can be configured to the Selection Options
included in Table 5.
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 9
and Three Speeds of Fan Control Installation Instructions
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation. The
modes presented are user-dependent on the sequence
of operation selected. For 2-pipe applications using a
COS, choose 0 = Cooling only. Changeover occurs
between Cooling only and Heating only. For example
sequences of operation, see Figure 12 through
Figure 17.
Table 3: Control Sequences for 2-Pipe Applications
Sequence Control Terminals Used (See Table 1.)
Curves On/Off Floating Proportional
Control Control Control
0 = Cooling Only See Figure 12. #10 NO Cool #10 Open Cool #10 Proportional Cool
#11 NC Cool #11 Close Cool
1 = Heating Only See Figure 13. #10 NO Heat #10 Open Heat #10 Proportional Heat
#11 NC Heat #11 Close Heat
2 = Cooling with Reheat See Figure 14. #6 and #7 Reheat #6 and #7 Reheat #6 and #7 Reheat
#10 NO Cool #10 Open Cool #10 Proportional Cool
#11 NC Cool #11 Close Cool
3 = Heating with Reheat See Figure 15. #6 and #7 Reheat #6 and #7 Reheat #6 and #7 Reheat
#10 NO Heat #10 Open Heat #10 Proportional Heat
#11 NC Heat #11 Close Heat
10 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
On
FIG:cl_on
FIG:ht_rht
Cooling Setpoint On Reheat Off
100%
Device Opened Off
On/Off, Floating,
or Proportional
Device Closed Output
0%
On/Off, Floating,
Temperature Increase or Proportional
(Increments of 1oF/0.5oC) Output
FIG:ht_on
Heating Setpoint Figure 15: Heating with Reheat
FIG:cl_ht_4pps
Output
Heating Setpoint Cooling Setpoint
Temperature Increase Deadband
(Increments of 1oF/0.5oC) Device
On
Opened
Figure 13: Heating Only
On Off
Device
On/Off, Floating, Heating Output Closed
Off
or Proportional
Outputs Cooling output
Temperature Increase
FIG:cl_rht
(Increments of 1oF/0.5oC)
Heating Setpoint Cooling Setpoint
Figure 16: Cooling/Heating 4-Pipe System
Deadband
Device
On
Opened
On Reheat Off
Device
Off Closed
Temperature Increase
(Increments of 1oF/0.5oC)
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 11
and Three Speeds of Fan Control Installation Instructions
On/Off, Floating, Heating Output
FIG:clht_rht_4pps
or Proportional
Cooling output
Outputs
Reheat Deadband
On Output Off Device
Opened
Device
Opened
Off
Device Device
Closed
Closed
Temperature Increase
(Increments of 1oF/0.5oC)
Figure 17: Cooling/Heating 4-Pipe System with Reheat
Configuring Automatic Fan Speed When selection option (2): Low-Med-High-Auto is
Use the Fan Menu parameter in the Installer chosen in the Fan Menu parameter, the fan operates
Configuration menu to set the available Fan Mode as shown in Figure 18. When selection option
options. Use the FAN key to select the desired Fan (3): Low-High-Auto is chosen in the Fan Menu
Mode option. parameter, the fan operates at only the low and high
settings, ignoring the medium setting (Figure 18). This
operation applies to the occupied mode when the fan is
set to Auto.
Off Off
Low
100% 2.0F°/1.0C° to
5.0F°/2.5C°
Deadband
Heating
Cooling
Valve
Valve
FIG:fn_oprtn
0%
2.5 2.0 1.5 0.5 0.5 1.5 2.0 2.5
Temperature Deviation from Setpoint, F°
12 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Installer Configuration Menu
Table 5: Installer Configuration Menu (Part 1 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
BI1 Configuration of Binary Input 1. (None): No function is associated with an input.
Default: None (Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is closed, until the TOccTime expires.
(Window): Cancels the thermostat heating or cooling action when a
window is open. The fan operation is only affected if the Fan Menu
parameter is set to (4): On-Auto and Auto is the selected fan mode.
A Window alarm appears, indicating that the window needs to be
closed to resume heating or cooling.
Note: MotionNO and MotionNC disable any local override
function.
BI2 Configuration of Binary Input 2. (None): No function is associated with an input.
Default: None (Door Dry): Door contact only has an effect if BI1 is set to MotionNO
or MotionNC. (See the BI1 parameter earlier in this table.) The
occupancy is now dictated via BI1 and BI2. Any motion detected
sets the zone to Occupied status. The thermostat remains in the
occupied mode until a DoorOpen is detected, at which point the
thermostat goes to the unoccupied mode. If the door stays open
more than the specified door time, the thermostat remains
unoccupied. (See the Door Time parameter later in this table.)
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. It can be tied into the air conditioning unit control
card, which provides an alarm should there be a malfunction.
UI3 Configuration of Universal Input 3. (None): No function is associated with an input.
Default: None (COC/NH): Change Over Contact/Normally Heat: A dry contact
input is used to signal seasonal hot/cold water changeover. The
contact closes when cold water is present. Valid for two-pipe
systems only.
(COC/NC): Change Over Contact/Normally Cool: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when hot water is present. Valid for two-pipe systems only.
(COS): Change Over analog Sensor: Used for hot/cold water
changeover switching. Valid for two-pipe systems only.
Note: Select (0): Cooling Only for SeqOpera parameter. This
allows changeover to occur between Cooling only and Heating
only. COS does not operate in Cooling with reheat, Heating with
reheat, or Cooling/Heating with reheat applications.
(SS): Supply air Sensor monitoring
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 13
and Three Speeds of Fan Control Installation Instructions
Table 5: Installer Configuration Menu (Part 2 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
MenuScro Gives the option of having the (on): The scroll is active.
display continuously scroll the (off): The scroll is inactive.
parameters.
Default: on
AutoMode Enables the Auto function (if (on): The Auto function is active (Off-Auto-Heat-Cool). Provides
Option 2 is chosen in the SeqOpera automatic changeover between heating and cooling.
parameter) to be visible within the (off): The auto function is inactive (Off-Heat-Cool).
MODE key menu. (The MODE key
is the key at the far left of the
thermostat cover.)
Default: off
C or F Provides temperature scale options (°F): Fahrenheit scale
for display. (°C): Celsius scale
Default: °F
%RH dis Enables the display of humidity (on): Display%RH
below the room temperature on the (off): No display of%RH
display. Note: Models TEC2236-2, TEC2236H-2, TEC2256-2, and
Default: off TEC2256H-2 only.
Lockout Selectable Lockout Levels for Lock Function
limiting end user keypad interaction. out
System Fan Mode Unoccupied Occupied
Default: 0 Level
Mode Setting Override Temperature
Setting Setpoints
(0) Access Access Access Access
(1) Access Access No Access Access
(2) No Access No Access Access Access
(3) No Access No Access No Access Access
(4) No Access No Access Access No Access
(5) No Access No Access No Access No Access
Pipe No Selectable number of pipes in the (2.0): Limits the number of sequences of operation available from 0
system. to 3, and enables heat/cool operation from the same output.
Default: 4.0 (4.0): Allows access to all sequences of operation from 0 to 5, and
enables heat/cool operation from different outputs.
CntrlTyp Defines the control output for the (On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
type of valves used in the 24 VAC two-position valves.
installation (TEC2226-2, (Floating): For proportional three-wire control of 24 VAC floating
TEC2226H-2, TEC2236-2, and valves.
TEC2236H-2 models only).
Default: Floating
SeqOpera Determines the sequence of (0): Cooling only (Off-Cool)
operation. (1): Heating only (Off-Heat)
Default: 1 (2): Cooling with reheat (Off-Auto*-Heat-Cool)
(3): Heating with reheat (Off-Heat)
(4**): Cooling/Heating (Off-Auto*-Heat-Cool)
(5**): Cooling/Heating with reheat (Off-Auto*-Heat-Cool)
* Auto can be disabled with the AutoMode parameter.
** Four-pipe systems only
14 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Table 5: Installer Configuration Menu (Part 3 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
Fan Menu Sets the Fan Mode options. (0): Low-Med-High: Three-speed configuration using three fan
Default: 4 relays (L-M-H). Default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H).
Default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). Default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). Default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. Default is Auto.
Note: 2 and 3 automatically cycle the fan through speeds, based
on the room temperature.
DHumidLCK Dehumidification network lockout On = Dehumidification Authorized
Typically toggled through the Off = Dehumidification Not Authorized
network. This variable enables or
disables dehumidification based on
central network requirements from
the BAS front end.
(Dehumidification models only.)
Default: on
%RH set Dehumidification setpoint. Used Range is 30 to 95%.
only if dehumidification sequence is
enabled. (Dehumidification models
only.)
Default: 50% RH
DehuHyst Dehumidification hysteresys. Used Range is 2 to 20% RH.
only if dehumidification sequence is
enabled. (Dehumidification models
only.)
Default: 5% RH
DehuCool Maximum cooling valve position Range is 20 to 100%.
when dehumidification is enabled.
This can be used to balance smaller
reheat loads installed in regards to
the capacity of the cooling coil.
(Dehumidification models only.)
Default: 100%
Unocc HT Sets the Unoccupied Heating Range: 40.0°F/4.5°C to Note: When adjusting the
setpoint value. 90.0°F/32.0°C temperature, press the UP/
Default: 62.0°F/16.5°C DOWN arrow keys to change
the temperature in
Unocc CL Sets the Unoccupied Cooling Range: 54.0°F/12.0°C to 0.5F°/0.5C° increments; press
setpoint value. 100°F/37.5°C and hold the
UP/DOWN arrow keys
Default: 80.0°F/26.5°C to change the temperature in
Heat max Sets the Occupied and Unoccupied Range: 40.0°F/4.5°C to 5.0F°/5.0C° increments.
maximum Heating setpoint values. 90.0°F/32.0°C
Default: 90.0°F/32.0°C
Cool min Sets the Occupied and Unoccupied Range: 54.0°F/12.0°C to
minimum Cooling setpoint values. 100°F/37.5°C
Default: 54.0°F/12.0°C
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 15
and Three Speeds of Fan Control Installation Instructions
Table 5: Installer Configuration Menu (Part 4 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
Set type Provides the option of temporarily (temporar): Local changes to the heating or cooling setpoints are
changing the heating or cooling temporary, and remain effective for the specified TOccTime.
setpoint by pressing the UP/DOWN (permnent): Local changes to the heating or cooling setpoints are
arrow keys. permanently stored in the thermostat memory.
Default: permnent
TOccTime Sets the duration of the Temporary Range: 0.0 to 24.0 hrs in 1-hour increments
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an Override Function enabled in
the Main User Menu (when the
thermostat is in the Unoccupied
mode)
• a temporary heating or cooling
setpoint
Default: 2.0 hrs
DoorTime Engages the Unoccupied mode if Range: 1.0 to 10.0 min in 1-minute increments
the door stays open minimally for
the time specified.
Default: 2.0 min
Deadband Sets the minimum deadband Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
between the heating and cooling increments)
setpoints.
Default: 2.0F°/1.0C°
Cal RS Sets the desired room air sensor Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
calibration (offset). The offset can increments)
be added to or subtracted from the
actual displayed room temperature.
Default: 0.0F°/0.0C°
Cal RH Offset that can be added/subtracted Range is: ± 15.0%RH in 1% RH increments
to actual displayed humidity
Default: 0% RH
16 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Table 5: Installer Configuration Menu (Part 5 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
Aux cont Determines the auxiliary contact (0) Not used, If the Sequence of Operation is set to reheat
function and configuration. or used for (2, 3, or 5), ignore this parameter.
Default: 0 reheat
(1) Auxiliary Occupied = contact closed The output
N.O. Unoccupied = contact open aligns with
occupancy.
(2) Auxiliary Occupied = contact open
N.C. Unoccupied = contact
closed
(3) Auxiliary Occupied and fan On = The output
N.O. contact closed aligns with
Unoccupied and fan On or occupancy
Off = contact open and the
fan on
(4) Auxiliary Occupied and fan On = command.
N.C. contact open
Unoccupied and fan On or
Off = contact closed
(5) Auxiliary On/Off control through the The output
auxiliary network command. The output aligns with
can be commanded through the network the
for any required auxiliary functions via a secondary
separate and dedicated network variable. network
occupancy
command.
FL time Sets the maximum actuator stroke Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
timing
Note: floating CntrlTyp
TEC2226(H)-2 and TEC2236(H)-2
models only.
Default: 1.5 min
Cph Sets the maximum number of cycles Range: 3.0 to 8.0 cycles per hour
per hour
Note: TEC2216(H)-2, on/off
CntrlTyp TEC2226(H)-2, and
TEC2236(H)-2 models only.
Default: 4.0
RA/DA Choice of direct or reverse acting (DA): Direct Acting, 0 to 100% = 0 to 10 VDC
analog output signal. (RA): Reverse Acting, 0 to 100% = -10 to 0 VDC
Note: TEC2246(H)-2 and
TEC2256(H)-2 models only.
Default: DA
Reheat Sets the duty cycle time for reheat (0): 15 minutes (four cycles per hour), for various equipment with
output (if Option 2, 3, or 5 is chosen mechanical relays or contactors controlling mechanical reheat
in the SeqOpera parameter). systems.
Default: 0 (1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
UI3 dis Displays the supply or changeover Used as a diagnostic/service help, to troubleshoot and diagnose
temperature when UI3 is configured sensor operation.
as an analog input (SS or COS).
Used as a diagnostic/service help,
to troubleshoot and diagnose
sensor operation.
Default: -40°F/-40°C
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 17
and Three Speeds of Fan Control Installation Instructions
Accessories Repair Information
All the accessories in Table 6 include mounting If the TEC22x6(H)-2 Series Thermostat fails to operate
hardware; contact the nearest Johnson Controls® within its specifications, replace the unit. For a
representative to order any of these parts. replacement TEC22x6(H)-2 Series Thermostat, contact
the nearest Johnson Controls representative.
Note: Review the technical specifications of the
optional accessories prior to their use in an application. Troubleshooting
See Table 7 and Table 8 for information on
troubleshooting the TEC22x6(H)-2 Series Thermostat.
Table 6: Accessories (Order Separately)
Code Description
Number
SEN-600-1 Remote Indoor Air Temperature Sensor
TE-6361P-1 Duct Mount Air Temperature Sensor
SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TE-636S-1 Strap-on Temperature Sensor
18 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Table 7: Troubleshooting Details (Part 2 of 2)
Symptom Cause Solution(s)
Reheat does not Wrong mode From the SeqOpera menu, set the value to 2, 3 or 5.
operate selected
Heating or cooling Wrong reversing From the Rev Valve setting select either:
does not function valve configuration 1. DA (Direct Acting) 0 to 100% = 0 to 10 VDC
properly Note: TEC2246-2, or
TEC2246H-2, 2. RA (Reverse Acting) 0 to 100% = 10 to 0 VDC
TEC2256-2, and
TEC2256H-2 only
Technical Specifications
TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification
Capability, and Three Speeds of Fan Control (Part 1 of 2)
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay/Triac On/Off and 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Contact Floating
Rating Control
Analog Proportional 0 to 10 VDC into 2k ohm Resistance (Minimum)
Output Rating Control
Fan Relay Output Rating 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Auxiliary Triac Output 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Output Rating
Digital Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm
Diameter) Recommended
LONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with a Repeater;
6,250 ft (1,905 m) Maximum (Bus Topology)
Temperature Backlit -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Range Display
Heating 40.0°F/4.5°C to 90.0°F/32.0°C
Control
Cooling 54.0°F/12.0°C to 100.0°F/38.0°C
Control
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Minimum Deadband 2F°/1C° between Heating and Cooling
Ambient Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Conditions
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability, 19
and Three Speeds of Fan Control Installation Instructions
TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification
Capability, and Three Speeds of Fan Control (Part 2 of 2)
Compliance United States UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
LONMARK® Certification 3.4 (pending)
Canada UL Listed, File E27734, CCN XAPX7, Under
CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
Europe CE Mark, EMC Directive 89/336/EEC, standards EN 61000-6-3 and EN 61000-6-1
Australia and C-Tick Mark, Australia/NZ Emissions Compliant
New Zealand
Shipping Weight 0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2009 Johnson Controls, Inc.
20 TEC22x6(H)-2 Series LONWORKS® Network Thermostats with Two Outputs, Dehumidification Capability,
and Three Speeds of Fan Control Installation Instructions
Published in U.S.A. www.johnsoncontrols.com