NXA Catalog en
NXA Catalog en
Italy Spain
CHINT Italia Investment S.r.l. CHINT Electrics S.L.
Add: Via A. Pacino� 28, 30033 Noale (VE) Add: Calle José Echegaray, Num 8.Parque Empresarial Las Rozas
Tel: +39 041.446614 Edificio 3, Planta Baja, Oficina 7-8.C.P: 28232 Las Rozas (Madrid)
Fax +39 041.5845900 Tel: 0034 91 636 59 98
E-mail: [email protected] Fax: 0034 91 645 95 82
E-mail: [email protected]
Czech Republic
NOARK Electric Europe s.r.o. Russia
Add: Sezemická 2757/2, 193 00 Prague 9 ООО “Чинт Электрик”
Tel: +420 226 203 120
Юридический адрес: 109544, г. Москва, б-р Энтузиастов, д. 2, этаж 19,
Email: [email protected]
ком. 71; 72
Turkey Фактический адрес: РФ, 109544, г. Москва, б-р Энтузиастов, д. 2
Тел: +7 (495) 540-61-41
CHINT Turca Elektrik Sanayi VE Ticaret Anonim Sirke�
Тел: +7 (800) 222-61-41
Add: Zumrutevler Mahallesi Ural Sokak No. 22/18 NAS PLAZA B Block E-mail: [email protected]
KAT 1, Maltepe, Istanbul
Tel: +90216 621 00 55
Fax.:+90216 621 00 50
E-mail: [email protected]
Mexico
CHINT SOLAR MEXICO S DE RL DE CV
Peru
Add: Miguel Cervantes Saavedra 169 Piso 11 CHINT LATAM (PERU) S.A.C.
Col. Granada Del. Miguel Hidalgo
C.P. 11520 CDMX, México Add.: Camino Real 348 oficina 603, San Isidro, Lima
Tel: +52 1-55-8881-6127 Tel.: +51 1 763 4917
E-mail: [email protected] Email: [email protected]
India
Egypt CHINT India Energy Solu�on Private limited
CHINT Electrics (Egypt) Co., Ltd
Discovery Tower Plot No. A-17 Ground Floor Industrial Area NXA series air circuit breaker
Add: Building B16 - Smart village, Abu Rawash - Giza, Egypt Sector 62 Noida -201309
Tel: +20 1097173769 India Hotline: - 18002707977
P.O BOX : 00202 Company: - +91 1202975057
Email: [email protected] E-mail: marke�[email protected]
+86-4001177797
Tel: +86-21-6777 7777 Http://www.chintglobal.com
Fax: +86-21-6777 7777 E-mail: [email protected]
Printed by CHINT GROUP. No part of this brochure may be used or reproduced in any manner whatsoever without written permission. CHINT is the only CHINT GROUP ALL RIGHTS Reserved Recycle Paper Printed
publisher that can modify or change the content. Parts of the pictures used in the brochure are from the Internet. Pleases contact us in any case of copyright. 2020.07
ABOUT CHINT ONE CLOUD & TWO NETS STRATEGY
Solutions and Services for Customers Optimization for Manufacturing and Supply Chain
By providing reliable products and service for clients, CHINT puts forward the concept "Great Quality." Quality control and
upgrade is divided into four systems: scientific research, quality control, marketing service and logistics distribution. These methods
Moscow
Russia
and strategies make a comprehensive upgrade to product quality and services. Emphasis on "prevention first, continuous
Spain
Germany
Prague
Venice
improvement" is the basis of an effective quality inspection system. Leading the management process of "Great Quality" in the
North America
production process controls each link of production accurately and realizes the institutional operation of quality improvement.
Frankfurt
Madrid
Europe
US
Los Angeles
Jiuquan
Xianyang
Egypt
Algeria
Shanghai
"Great Quality" is not just a slogan, but a belief rooted in each employee's work. High-quality and accuracy are the basic requirement.
Dubai Hangzhou
Asia Pacific
Starting from a routine operation by each staff to implementing a high-quality of production and service, CHINT is
Thailand
Vietnam
your most reliable partner.
Malaysia
Singapore
Service Concept
International Marketing Territory
Peru
Brazil
Logistics Center
Service Purpose
Innovative and progressive, satisfying the customers
Integrated Vertical R&D Great Quality System One-stop Services 48-Hour Response
By gathering the global Ensuring flaw-free and CHINT's concept is that Providing end-to-end
industry elites to Provide safe trouble-free products, the it is not difficult to fulfill a high one-stop services for customers
Egypt Production Base Vietnam Production Base Malaysia Production Base Thailand Solar Power Singapore Complete Electric and stable energy-saving green multi-dimensional and -quality logistics distribution at with complaints, business
Production Base Equipment Production Base
and advanced electric products. multilevel control is one time, while it is difficult to consulting and technical support
conducted through stay as accurate and prompt as by solving problems immediately
procurement, inspection, the first-time. High-efficiency and including any possible prolems
At least 5% of revenue is
invested in research and quality control and and high-precision accuracy are in advance.
development
certification. our requirement.
Shanghai Production Base Hangzhou Production Base Wenzhou Production Base Jiaxing Production Base Xianyang Production Base
Air Circuit Breaker
Overview P-003
Accessories P-019
Annex
Ⅰ Configuration P-056
Safety shutter
Arcing chamber
Shunt release
Undervoltage release
Auxiliary contact
Closed electromagnet
Intelligent controller
Operation mechanism
Energy-storage handle
Racking-handle
Breaking button
Making button
Front cover
NXA series air circuit breaker Air Circuit Breaker P-002
3
16
4
15
5
6
N
7
10
14 11
13 12
1 Trademark 9 QR code
2 Secondary wiring terminal 10 Extraction draw plate (only applicable to draw-out type)
Circuit breaker
● Operation temperature:
The electrical and mechanical characteristics are applicable to the ambient temperature
of -5℃-+40℃. NXA can also operate in the ambient temperature of -45℃-+70℃ (M type,
A type), -20℃-+70℃ (P type, H type, CD-1), the derating factor is seen in P23-24.
● Storage conditions: apply to -45℃~+70℃
● NXA can resist the following electromagnetic interference
— Overvoltage generated by electromagnetic interference
— Overvoltage caused by environment interference or a power distributing system
— Electrostatic discharge of radio waves (radio, intercom, radar and the like)
● NXA has successfully passed the test for electromagnetic compatibility specified according to
the following standards (EMC) IEC/EN 60947-2
Annex F
The test can guarantee no false tripping and no interference on tripping time
● Protection grade:
Front IP 20, other side IP 00
Connection
● Rear connection
Horizontal connection, vertical connection
● Optional accessories
Interphase barrier
Lock
Indication contact
● Standard contact
Making and breaking indication contacts
Fault tripping indication contact
● Optional accessories
Position indication contact
Spring charged indication contact
Overview Air Circuit Breaker P-004
+ =
NXA16 NXA20~NXA40
Accessories
Interphased partition Secondary wiring terminal-drawout type Secondary wiring terminal-fixed type
Rated current
Frame size 400 630 800 1000 1250 1600 2000 2500 3200 3600 4000 5000 6300
Breaking capacity
N ▪ ▪ ▪ ▪ ▪ ▪
1600A S ▪ ▪ ▪ ▪ ▪ ▪
H ▪ ▪ ▪ ▪ ▪ ▪
N
▪ ▪ ▪ ▪ ▪ ▪
2000A S
▪ ▪ ▪ ▪ ▪ ▪
H
▪ ▪ ▪ ▪ ▪ ▪
N
▪ ▪ ▪ ▪
3200A S
▪ ▪ ▪ ▪
H
▪ ▪ ▪ ▪
N
▪ ▪ ▪
4000A S
▪ ▪ ▪
H
▪ ▪ ▪
6300A H
▪ ▪ ▪
Model definition and description
N A B C
08-800A
20:2000A S: standard 10-1000A P: power type F: fixed 4: AC 400: M: manual Special
(06-20) type type 4 poles AC 400V operation requirements
12-1250A OA
code,
H: harmonic N A B C
16-1600A type such as: UVT
150
32:3200A H: advanced DC 110:
20-2000A
(16-32) type 100 DC 110V
25-2500A
0
32-3200A
40:4000A DC 220:
(32-40) 36-3600A DC 220V
40-4000A
50-5000A
63:6300A
(40-63) 63-6300A
1)
Note: Intelligent controller PT/HT type. The basic functions are the same with P/H type. T refers to the internal temperature measurement function.
2)
Manual operation does not contain motor-driven mechanism, closing electromagnet and shunt release. Motor operation contains all standard accessories of remote
operation.
3)
Auxiliary working voltage of the intelligent controller: corresponding power modules is required if DC220V or DC110V is selected.
4)
NXA16N10-AD3-AC230: frame size is 1600A, N type breaking capacity, rated current is 1000A, A type intelligent controller, draw-out type and 3 poles, control
voltage is AC 230V motor operation.
Product selection Air Circuit Breaker P-006
NXA 16 TU M 04 3 AC230
32:3200A (16-32)
H: harmonic type
20-2000A; 25-2500A
32-3200A; 36-3600A
4 poles AC 400V
N
40-4000A; 50-5000A DC 110:
40:4000A (32-40) DC 110V
63-6300A
NXA 16 CC 230VAC
Code of
Frame size Code of accessories Code of rated voltage
product
20/63:2000A-6300A
P-007 Air Circuit Breaker Product selection
NXA 16 OF C04
Code of
Frame size Code of accessories Specification of accessories
product
20/63:2000A-6300A KL: Key lock 2S1S: Two locks and one key
Note
N
P-009 Air Circuit Breaker Functions and features
Technical parameters
Features
3P 254×243.5×318.5
Fixed type
Size (width × depth × height) 4P 324×243.5×318.5
3P 308×331.5×351
Draw-out type
4P 378×331.5×351
Functions and features Air Circuit Breaker P-010
2000A
630 800 1000 1250 1600 2000
3200A
1600 2000 2500 3200
4000A
3200 3600 4000
6300A
4000 5000 6000
N
630 800 1000 1250 1600 2000 1600 2000 2500 3200 3200 3600 4000 2000 2500 -
N S H N S H N S H H
80 65 80 80 80 100 80 85 100 120
50 55 55 65 70 70 65 75 75 85
50 65 65 80 80 85 80 85 85 120
50 55 55 65 70 70 65 75 75 85
B B B B
50 65 65 65 80 85 65 85 85 100
50 55 55 65 70 70 65 75 75 75
37 42 42 37 50 50 37 50 50 -
- - - - - - - - - -
176 143 176 176 176 220 176 187 220 264
105 121 121 143 154 154 143 165 165 187
16 16 16 26 26 26 26 26 26 26
32 32 32 32
70 70 70 70
Intelligent controller
M type intelligent controller (Basic type)
Protection
All the protective threshold and time delay are set by a dial switch
1
● Overload protection
— Ture RMS long-time-delay protection
2
— Thermal memory: heat accumulation before and after tripping
13
6
● Earth fault protection
7 14 Optional four steps time-delay setting
8 15
● Neutral line overcurrent protection (4P)
16
The neutral protective threshold can be adjusted to 50%, 100% and OFF
17
9
18 ● Test function
10
Simulating 6Ir test current for test tripping
11
Protection
All the protective threshold and time delay are set by a dial switch
1
● Overload protection
2
— Ture RMS long-time-delay protection
— Thermal memory: heat accumulation before and after tripping
6
12
13
— Optional four steps time-delay setting
● Test function
1. Display window: display the current Simulating 6Ir test current for test tripping
value, the setting parameter, the
fault current, the tripping time
2. Ig indicator for earth fault ● Tripping record function
indication
3. Ir indicator for overload long- ● Ampere meter
time-delay tripping
Measure the real and effective value (RMS) of
4. Isd indicator for short circuit short-
time-delay tripping current with the precision of 2% for 40% to 150% in setting
5. Ii indicator for short circuit
tripping
6. Menu button for inquiring the dial
position and fault record
7. Rightward button: turn to the next
state when inquiring the dial
position
8. Return button: back to the previous
level or resetting
9. Overload long-time-delay current
setting
10. Short circuit short-time-delay
current setting
11. Earth fault current setting
12. Overload long-time-delay time
setting
13. Transparent cover lockhole
14. Short circuit short-time-delay time
setting
15. Neutral line protection setting
16. Earth fault time-delay setting
17. Test button for simulating 6IR
current
18. Short circuit instantaneous
current setting
P-013 Air Circuit Breaker Functions and features
Protection
Setting all protective threshold values and time-delay by button
The setting values can be displayed on LCD display window
4
— Unbalanced voltage protection
— Overvoltage and undervoltage protection
5
— Overfrequency and underfrequency protection
6 — Phase sequence protection
— Reverse power protection function
7
— Required value protection function
13
8 The required value of the real and effective value of each current is calculated within a measurement window.
14 When the required value is off limit, the protection action is carried out. The setting of a sliding time window
9
is in the menu of "setting of a measurement meter".
15
10 ·A-phase maximal required current value,
·B-phase maximal required current value,
11
·C-phase maximal required current value,
12 ·N-phase maximal required current value are respectively set for each circumstance of the required value
protection without being affected by the setting of the neutral line protection.
● Extended function
— Self-diagnosis by the intelligent controller
1. Ig indicator for earth fault
— Operation times/fault tripping/alarming/deflection recording function provides the
tripping
2. Ir indicator for overload long-
latest ten times of recording
time-delay tripping — Main contact abrasion display function for evaluating the contact abrasion degree
3. Isd indicator for short circuit short- according to mechanical life, electrical services and breaking capacities of different
time-delay tripping frames.
4. Ii indicator for short circuit — Internal clock function
tripping — A Mini-USB interface is connected with a PC to achieve the functions of protection
5. Running indicator flickering in
setting, fault record downloading, whole power quantity detection and parameter
normal running
reading of a circuit breaker.
6. LCD screen with three-color
backlight. Green stands for normal
— "test" push button
running, yellow stands for ● Electric energy meter
alarming and red stands for — Current measurement
tripping. — Voltage measurement
7. Setting button — Frequency measurement
8. Leftward button — Required value measurement
9. Upward button
— Power (active power, reactive power and apparent) measurement
10. Downward button
— Electric energy (active power, reactive power and apparent) measurement
11. Enter button
12. Rightward button
— Power factor measurement
13. Transparent cover lockhole ● LCD three-color backlight
14. Mini-USB interface Green stands for normal running, yellow stands for alarming and red stands for tripping.
15. Test button for tripping test
Functions and features Air Circuit Breaker P-014
N
— DI signal: AC230V ( Standard configuration, and others can be selected);
6
DC110V
7 — DO needs to be configured with a power supply module (24VDC output) and
13 a relay module.
8
14
● Harmonic analysis function
9
— Measurement of the fundamental wave current, the fundamental wave line voltage,
15
10 the fundamental wave phase voltage, the fundamental wave power and each 3-31
odd harmonic wave current percentage (HRIh), the harmonic voltage percentage
11
(HRUh), the total harmonic wave current distortion rate (THDi, thdi) and the total
12 harmonic wave voltage distortion rate (THDu, thdu).
— The harmonic wave percentage(HR) refers to the ratio of root-mean-square value
of the Nth harmonic wave component contained in periodic alternative current quantity
to the root-mean-square value of the fundamental wave component, and is expressed
1. Ig indicator for earth fault
in percentage.
tripping
2. Ir indicator for overload long-
time-delay tripping
3. Isd indicator for short circuit short-
time-delay tripping
4. Ii indicator for short circuit
tripping
5. Running indicator flickering in
normal running
6. LCD screen with three-color
backlight. Green stands for normal
running, yellow stands for
alarming and red stands for
tripping.
7. Setting button
8. Leftward button
9. Upward button
10. Downward button
11. Enter button
12. Rightward button
13. Transparent cover lockhole
14. Mini-USB interface
15. Test button for tripping test
P-015 Air Circuit Breaker Functions and features
Protection features
The protection features of the intelligent controller comprise inverse time characteristic and constant time characteristic. When the fault current
exceeds the set value of the inverse time limit, the controller performs constant time protection.
The inverse time limit corresponds to the feature curve I2t.
Ir current setting value range: 0.4In, 0.5 In, 0.6 In, 0.7 In, 0.8 In, 0.9 In, 1.0 In+OFF (M/A);0.4In~1.0In+OFF(P/H)
Inverse time limit action feature: I2t, wherein t=(6/N)2*tr
Note: N --- the multiple I/Ir obtained by dividing failure current by set current
t --- time delay action of the failure action
tr --- long-time-delay set value
Allowed error of the action time ±15%
Conventional factory tuning:Ir=1.0In
tr=2s@6Ir
1600 400~1600 60
2000 630~2000 60
≥3200 ≥1600 120
P-017 Air Circuit Breaker Functions and features
Measurement range Ia, Ib, Ic and IN are not less than 15In (rated current of the circuit breaker)
Below 0.1In: the measurement is inaccurate
0.1In-0.4In: the accuracy will be changed linearly from 5% to 2%
Measurement precision 0.4In-1.5In: the accuracy is 2%
>1.5In: the accuracy will be changed linearly from 2% to 15%
The measurement accuracy of the earthing current is 10%
Voltage measurement
Frequency
Power
Error: ±2.5%
Power factor
Measurement content phase splitting power factor,total power factor
Measurement range -1.00~+1.00
Electric energy
Input reactive electric energy (EQin), output reactive electric energy (Eqout)
Measurement content Input active electric energy (EPin), output active electric energy (Epout)
Total active electric energy (EPtotal), total reactive electric energy (EQtotal), total apparent electric energy (Estotal)
Total harmonic wave distortion THD: the total distortion rate of the harmonic wave relatively to the fundamental wave
THDu and thdu Thd: the total distortion rate of the harmonic wave relatively to the effective value
Amplitude wave spectrum of harmonic wave The controller can display FFT amplitude of odd harmonic wave from 3 to 31in percentage
Measurement precision of control unit ±2%
Tripping curves Air Circuit Breaker P-018
LSI curves
Ir=(0.4~1)In
1000
100
tr=(1~24)s
10
T(s)
Isd=(2~10)Ir(max50kA)
N
1
0.4
0.3
0.2
0.1 0.1
Ii=(2~15)In
(max50/63kA)
0.01
0.5 1 2 3 4 5 10 3 6 9 12 18 24 30
I(xIr) I(xIn)
Ig=(0.2~1)In or
1000 500A~1200A
100
10
T(s)
0.4
0.3
0.2
0.1 0.1
0.01
0.1 1 10
I(xIn)
Accessories: locks
Pushbutton lock
The pushbutton lock is to lock the circuit breaker by a transperant conver blocks so as to
prevent the breaking button and the making button of the circuit breaker from misoperation
and guarantee the reliable running of the circuit breaker.
Body lock
● A key lock includes four types. The latter two are applied to 2 input and 1 connect
power distribution system:
— Random lock
— One lock and one key
— Two locks and one key
— Three locks and two keys
Note:When the user separately purchases the key lock for installation, the panel needs to
be opened with a hole opener, and the hole opener is provided by the user.
Hole diameter:NXA16:Φ21mm NXA20~63:Φ24mm
After the chassis and body are locked at "Disconnected" position by a padlock, the
racking-handle cannot be inserted into racking-handle entry, and then the position
of the body cannot be changed.
Door interlock
Circuit breaker state door interlock
A cabinet door is prohibited to be opened when the circuit breaker is closed.
The cabinet door is allowed to be opened when the circuit breaker is disconnected.
Circuit breaker position door interlock
The cabinet door is prohibited to be opened when the circuit breaker is at the connected
and test part. The cabinet door is allowed to be opened when the circuit breaker is at the
disconnected position.
Note:a. If need bend the cable,make sure radian is more than 120°.
b. Check and make sure enough lubricating oil of the cable.
c. The maximum distance between two interlock circuit breakers is1.5m.
Functions and features Air Circuit Breaker P-020
Alarming contact
N
Standard configuration 1CO
Breaking capacity Current (A) / Voltage (V)
VAC(AC-15) 1.3/240, 0.75/415
Utilization category
VDC(DC-13) 0.55/110, 0.27/220
1)
Note: CO refers to a switch contact, and a one-normally-open and one-normally-closed contact is matched with a
common terminal.
2)
NO refers to a normally open contact. NC refers to a normally closed contact.
Source-changeover systems
● Mechanical interlock
1 normal and 1 replacement
2 incoming and 1 busbar
● Source-changeover controller (with adaptor)
1 normal and 1 replacement: mechanical interlock+2A type controller
2 incoming and 1 busbar: mechanical interlock+3A type controller
P-021 Air Circuit Breaker Functions and features
Characteristics
VAC 50/60HZ 220/230/240, 380/400/415
Power supply
VDC 110, 220
Operation threshold 0.85-1.1Us
Frame size: power loss (VA or W) 16: 75W; 20: 85W; 32: 110W; 40: 110W; 63: 150W
1600A frame MO 2000A~6300A frame MO Motor overcurrent ≤1min
Charging time ≤7s
Operation frequency ≤2times/min
AC110
Rated control power supply voltage Us(V)AC 220/230/240 AC 380/400/415 DC220 DC110
(not available for NXA16)
Notes:
2000A~6300A frame CC&ST
1. It must select pulse type in the automatic control system.
2. power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of
the pulse type cannot be more than 5 times/min, or the components are easily burnt.
3. Ensure that the product is in the energy storage state so that the closed electromagnet
may be energized;
4. If the product is not closed after a single power-on for 15s, must disconnect the power
on the closed electromagnet immediately.
AC110
Rated control power supply voltage Us(V)AC 220/230/240 AC 380/400/415 DC220 DC110
(not available for NXA16)
Notes:
1. It must select pulse type in the automatic control system.
2. power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of
the pulse type cannot be more than 5 times/min, or the components are easily burnt;
3. If the circuit breaker is not break by a single power-on of 15 s, must disconnect the
power on the shunt release immediately.
Functions and features Air Circuit Breaker P-022
Notes:
1. Inm=1600A under-voltage delay does not require an external delay controller.
The power-off operation is an instantaneous operation. There is no zero
voltage delay function;
2. Inm=6300A under-voltage delay does not require an external under-voltage delay
controller. There is a delay function for low voltage and power off;
N
6300A frame ASUVT 3. Inm=2000A~4000A under-voltage delay requires an external delay controller.
There is a delay operation when the power is off. There is a zero voltage delay function.
The under-voltage will not operate when the voltage returns to 85% Ue and higher,, within 1/2 delay time.
2000A frame
Ambient temperature 630A 800A 1000A 1250A 1600A 2000A
Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - - - - - -
45° - - - - - - - - 1550 - 1900 -
50° - - - - - - - - 1500 1550 1850 1900
55° - - - - - - - - 1400 1450 1800 1800
60° - - - - - - - - 1300 1350 1700 1700
3200A frame
4000A frame
6300A frame
45° - - - - - - - - - - 1550 -
2000A frame
Ambient temperature 630A 800A 1000A 1250A 1600A 2000A
N
Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - - - - - -
3200A frame
4000A frame
6300A frame
Dimension of busbar
Bolt configuration
N
16:Φ11 M10 (36~52)N·m
20~63:Φ13 M12 (61~94)N·m
Note:
a. When a copper bar selected by users is not matched with a wiring terminal of the circuit breaker, extended busbar is required to be designed
to transfer, and is designed by the users of their own. The cross section of the extended busbar cannot be less than the requirement in the table
above. The interval among the extended busbar is not less than the interval among wiring terminals of the circuit breaker.
b. After the busbar recommended in the table above is installed, the electric clearance between adjacent phases of the circuit breaker is not less
than 18mm.
c. Electrical elements are used for three-phase rectification and high-frequency inversion, such as a high-frequency induction heating furnace
(medium-frequency furnace steelmaking equipment), a solid high-frequency welding machine (such as an embedded arc electric welding
machine), vacuum heating smelting equipment (such as a monocrystalline silicon growth furnace), in load equipment by controlled silicon.
When a circuit breaker is selected, the influence on the circuit breaker by higher order harmonic component generated by controlled silicon is
required to be considered besides the influences by the environment temperature and altitude height. At the same time, capacity derating
is required, and the capacity coefficient (0.5-0.8) is recommended.
d. The electric clearance of fastening bolts of upper and lower busbar needs to be not less than 20mm after the installation of the busbar by users.
e. After the installation of the circuit breaker, the safety clearance among electrified bodies with different electric potential and between the
electrified bodies and the ground are not less than 18mm.
P-027 Air Circuit Breaker Functions and features
Rated current(A) 400 630 800 1000 1250 1600 630 800
Default setting
ratings of short 3.2 5.04 6.4 8 10 12.8 5.04 6.4
Upstream time-delay 8In(kA)
Downstream Setting ratings(kA) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8
Delayed tripping
0.1,0.2,0.3,0.4
time (s)
NM8-100 0.4 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8
40
NM8S-100 0.48(Motor) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8
NM8-250 1.8 2.484~4 2.484~6.3 2.484~8 2.484~10 2.500~12.5 3.2~16 2.484~6.3 2.484~8
180
NM8S-250 2.16(Motor) 2.981~4 2.980~6.3 2.980~8 2.980~10 2.980~12.5 3.2~16 2.980~6.3 2.980~8
10 / / / / / 13.80~16 / /
1000
12(Motor) / / / / / / / /
12.5 / / / / / / / /
1250
15.0(Motor) / / / / / / / /
Functions and features Air Circuit Breaker P-028
1000 1250 1600 2000 1600 2000 2500 3200 3200 3600 4000 4000 5000 6300
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10
2~10
2~10
2.5~12.5
2.5~12.5
2.5~12.5
3.2~16
3.2~16
3.2~16
4~20
4~20
4~20
3.2~16
3.2~16
3.2~16
4~20
4~20
4~20
5~25
5~25
5~25
6.4~32
6.4~32
6.4~32
6.4~32
6.4~32
6.4~32
7.2~36
7.2~36
7.2~36
8~40
8~40
8~40
8~40
8~40
8~40
10~50
10~50
10~50
12.6~50
12.6~50
12.6~50
N
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2.070~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2.208~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2.649~10 2.649~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2.484~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2.980~10 2.980~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
2.760~10 2.760~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
3.312~10 3.312~12.5 3.312~16 4~20 3.312~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
3.105~10 3.105~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
3.726~10 3.726~12.5 3.726~16 4~20 3.726~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
3.450~10 3.450~12.5 3.450~16 4~20 3.450~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
4.140~10 4.140~12.5 4.140~16 4.140~20 4.140~16 4.140~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
3.450~10 3.450~12.5 3.450~16 4~20 3.450~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
4.140~10 4.140~12.5 4.140~16 4.140~20 4.140~16 4.140~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
4.347~10 4.347~12.5 4.347~16 4.347~20 4.347~16 4.347~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
5.216~10 5.216~12.5 5.216~16 5.216~20 5.216~16 5.216~20 5.216~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
4.830~10 4.830~12.5 4.830~16 4.830~20 4.830~16 4.830~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
5.796~10 5.796~12.5 5.796~16 5.796~20 5.796~16 5.796~20 5.796~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
5.520~10 5.520~12.5 5.520~16 5.520~20 5.520~16 5.520~20 5.520~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50
6.624~10 6.624~12.5 6.624~16 6.624~20 6.624~16 6.624~20 6.624~25 6.624~32 6.624~32 7.2~36 8~40 8~40 10~50 12.6~50
6.900~10 6.900~12.5 6.900~16 6.900~20 6.900~16 6.900~20 6.900~25 6.900~32 6.900~32 7.2~36 8~40 8~40 10~50 12.6~50
8.280~10 8.280~12.5 8.280~16 8.280~20 8.28~16 8.280~20 8.280~25 8.280~32 8.280~32 8.280~36 8.280~40 8.280~40 10~50 12.6~50
8.694~10 8.694~12.5 8.694~16 8.694~20 8.694~16 8.694~20 8.694~25 8.694~32 8.694~32 8.694~36 8.694~40 8.694~40 10~50 12.6~50
/ 10.43~12.5 10.43~16 10.43~20 10.43~16 10.43~20 10.43~25 10.43~32 10.43~32 10.43~36 10.43~40 10.43~40 10.43~50 12.6~50
9.660~10 9.660~12.5 9.660~16 9.660~20 9.660~16 9.660~20 9.660~25 9.660~32 9.660~32 9.660~36 9.660~40 9.660~40 10~50 12.6~50
/ 11.59~12.5 11.59~16 11.59~20 11.59~16 11.59~20 11.59~25 11.59~32 11.59~32 11.59~36 11.59~40 11.59~40 11.59~50 12.6~50
/ 11.04~12.5 11.04~16 11.04~20 11.04~16 11.04~20 11.04~25 11.04~32 11.04~32 11.04~36 11.04~40 11.04~40 11.04~50 12.6~50
/ / 13.24~16 13.24~20 13.24~16 13.24~20 13.24~25 13.24~32 13.24~32 13.24~36 13.24~40 13.24~40 13.24~50 13.24~50
/ / 13.80~16 13.80~20 13.80~16 13.80~20 13.80~25 13.80~32 13.80~32 13.80~36 13.80~40 13.80~40 13.80~50 13.8~50
/ / / 16.56~20 / 16.56~20 16.56~25 16.56~32 16.56~32 16.56~36 16.56~40 16.56~40 16.56~50 16.56~50
/ / / 17.25~20 / 17.25~20 17.25~25 17.25~32 17.25~32 17.25~36 17.25~40 17.25~40 17.25~50 17.25~50
N
137.5
RESET
A
318.5
Datum X
H
OFF ON
89
143.5
137.5
50.5
127 42 100 92.5
237(Three pole) 243.5
254(Three pole) F 87
307(Four pole)
324(Four pole)
Hole size
F
10
4× 7 Datum Y
120
100
285
118.5
L
322
L1 Datum X
Installation plate
of the
circuit breaker
H L L1 Remark
5 237 254 In=400A~630A Fixed type, three pole 258
8 237 254 In=800A~1250A Fixed type, three pole
20 237 254 In=1600A Fixed type, three pole Hole size of the panel of the fixed type circuit breaker
Horizontal connection
A
Datum Y
45
N
8× 11
12.5
N pole 25
35.5
70 70 70
Datum Y
Datum Y
95 95 95 95 95
60 60 8×Ф13
6×Ф13
14
14
90
28
90
28
70 70 70 70 70
(Optional) (Optional)
Number of busbar
Number of pieces
"Rated current(A)" Three poles Four poles
A pole+C pole B pole A pole+B pole C pole+N pole
400~630 4 2 4 4
800~1250 4 2 4 4
1600 8 4 8 8
P-031 Air Circuit Breaker Installation and wiring
137.5
RESET
Datum X
H
351
OFF ON
89
137.5
176.5
83.5
连接
试验
分离
Hole size
Datum X
40
120
320
143.5
L
L1
circuit breaker
H L L1 Remark
5
Horizontal connection
A Datum Y
N
45
26.5
12.5
8× 11 25
N pole
70 70 70
Datum Y Datum Y
95 95 95
95 95
60 8×Ф13
60 6×Ф13
14
14
28
81
28
81
70 70 70 70 70
Optional Optional
Number of busbar
Number of pieces
"Rated current(A)" Three poles Four poles
A pole+C pole B pole A pole+B pole C pole+N pole
400~630 4 2 4 4
800~1250 4 2 4 4
1600 8 4 8 8
P-033 Air Circuit Breaker Installation and wiring
237
200
RESET
128.5
R
A
OFF ON
D
Datum X
H
112
128.5
150
163
55
292
F
192 (Threepole) 182 26.5
287(Fourpole) 42 219.5 82
67
Hole size
Datum Y
Datum Y
69.5
233
311
150
270
Datum X
4 × 12
4
Φ
8×
H Remark
10 In=630A
15 In=800A~1600A
20 In=2000A
Installation and wiring Air Circuit Breaker P-034
Horizontal connection
A
Datum Y 60
N
17
N pole 8× 13
.
28
42
95 95 95
A
16×Φ13
N pole 30 60
14
60
30
N pole
115
40
95 95 95 86
17
95 95 95
45
239
200
RESET
128.5
A
OFF ON
Datum X
D
H112
128.5
150
199.5
Disconnected
position
92
292 379.5 31
430
201.5(Three pole) 201.5
296.5(Four pole) F 41
Hole size
Datum Y
Hole size of the base Hole size of a panel
Datum Y
11 17
33
11
156
175
303
273
Datum X
379
11
14
17
302
66
16
172.5
11
bottom surface and the installation hole pitch Right outermost side
345 of the circuit breaker
201.5
20 In=2000A
Installation and wiring Air Circuit Breaker P-036
Horizontal connection
A
N pole
13.5
N
30
60 Datum Y
28 8× 13
39.5
95 95 95
A
16×Φ13
N pole 30 60
14
60
30
N pole
115
40
95 95 95 92.5
17
237
200
RESET
A
128.5
R
H
OFF ON
Datum X
112
128.5
150
163
55
26.5
352
42 219.5 82
227(Three pole) 212
F 67
342(Four pole)
Hole size
Datum Y Datum Y
69.5
233
311
Datum X
270
150
4× 12
362 Installation
panel of the
F circuit breaker
28.5
316(Four pole)
202.5
405
Schematic diagram of the overall size of the
bottom surface and the installation hole pitch Horizontal connection
H Remark
20 In=1600A~2500A
30 In=3200A
Installation and wiring Air Circuit Breaker P-038
Horizontal connection
A
16×Φ13
40 86
15
N极
72
40
115 115 115 96
D
A
N pole
50 12×Φ13 Datum Y 86
17
39.5
40
32×Φ13 40
86
115 115 115
239
200
RESET
128.5
R
H0
OFF ON
Datum X
112
128.5
150
Disconnected
199.5
position
92
连接 退 进
试验
分离 抽出断路器前请拔出手柄
352 349 31
231.5(Three pole) 231.5
399.5
346.5(Four pole) F
41
N
239
200
RESET
A
128.5
H1
R
H0
Datum X
OFF ON
112
128.5
150
Disconnected
199.5
position
92
连接 退 进
试验
分离 抽出断路器前请拔出手柄
352 349 31
231.5(Three pole) 231.5
399.5
346.5(Four pole) F
41
Installation and wiring Air Circuit Breaker P-040
Hole size
Datum Y
Datum Y 362
33
17
11
156
11
175
303
273
Datum X
379
N
11
3.5
14
17
66
20 47 16
Installation
162.5(Threepole) 162.5 panel of the
circuit breaker
F
277.5(Fourpole)
4
Φ
×
11
Schematic diagram of the overall size of the 405
bottom surface and the installation hole pitch
H0 H1 Remark
20 0 In=1600A~2500A
30 10+0.1
0 In=3200A
Horizontal connection
N Pole A
16×Φ13
90 50 100
25
100
50
N Pole
A
Datum Y
75
30
16×Φ13 100
25
14
39.5
N Pole
115
40
17
Datum Y
237
200
RE SE T A
128.5
R
OF F ON
Datum X
H
100
128.5
150
163
67
282.5(Three pole) 26.5
267.5
42 213.5 82
432.5(Four pole)
F
67
Hole size
Datum Y Datum Y
378
8×Φ4
4× 12
Datum X
311
240
150
270
26.5
F
28.5
Schematic diagram of the overall size of the Ratio 1:2 Hole size of the panel of the fixed type circuit breaker
bottom surface and the installation hole pitch
H Remark
16 In=3200A
20 In=3600A~4000A
Installation and wiring Air Circuit Breaker P-042
Horizontal connection
Datum Y
A
120
N
90
N pole 30 16× 11
17
39.5
150 150 150
P-043 Air Circuit Breaker Installation and wiring
A
N 45
200
RESET
128.5
+0.1
R
10 0
438.5
OFF ON
Datum X
H
Disconnected
100±0.2
position
128.5
150
10+0.1
199.5
0
98.5
284.5(Three pole) 284.5 366 31
416
434.5(Four pole)
461
F
41
Hole size
2×11×17 Datum Y
378
Datum Y
11×Φ4
11
33
156
303
273
175
Datum X
379
3.5
14
47 16
66
H Remark
26 In=3200A
30 In=3600~4000A
Installation and wiring Air Circuit Breaker P-044
Horizontal connection
Datum Y
120
A 90
N pole 16× 11
37
N
30
14
28
150 150 150
P-045 Air Circuit Breaker Installation and wiring
237
200
128.5
RESET
30
OFF ON
DatumX
释能
112
128.5
163
150
55
352
219.5 26.5
441
897 67
F 82
Hole size
Datum Y
362
DatumY
69.5
Datum X
311
270
233
150
4×Φ12
F
860
28.5
Horizontal connection
260 260
180 24×Φ15
260 DatumY
80
20
40
134
316.5 323.5
In=6300A
A
N
N pole 210 210
100 210 DatumY 155 28×Φ15
50 50 57.5 55
20
40
134
182.5 246.5 246.5
In=4000A~5000A(Four pole )
210 210
210 155 24×Φ15
DatumY
50 57.5 55
20
40
134
246.5 246.5
In=4000A~5000A(Three pole)
P-047 Air Circuit Breaker Installation and wiring
45
A
237
200
128.5
30
Datum X
112
128.5
Disconnected
150
199.5
position
92
31
454
41
923 500
Hole size
Datum Y
362
2×12×17
156
Φ11
273
303
175
Datum X
Φ14
379
3.5
66
20 47 16
785
F
11×Φ4
Installation panel of
405 the circuit breaker
Hole size of the panel of the fixed type circuit breaker Hole size of the panel of the draw-out type circuit breaker
Installation and wiring Air Circuit Breaker P-048
Horizontal connection
260 260
260 Datum Y 180 24×Φ15
80
20
40
100
113
316.5 323.5
In=6300A
A
N
N pole
100 210 210 210
28×Φ15
50 55 Datum Y
20
57.5
40
100
113
182.5 246.5 246.5
20
40
100
113
246.5 246.5
In=4000A~5000A(Three pole)
P-049 Air Circuit Breaker Installation and wiring
The installation overall dimension of an external N-phase transformer is as below when the controller is of 3P+N type.
The transformer is provided by the manufacturer. A connection copper bar and an installation support are manufactured by users.
35 4× 13
1 2
c
60
d
b
140
210
240
4 4- 10.5
1-Wiring panel 2-Busbar 3-Fixation panel 4-Transformer
30
3
Frame size a b c d
1600 45 20 40 88
a
170 2000 60 20 34 89
190
3200 80 20 35 110
4000 120 20 16 58
6300 80 20 35 110
110 50
90 40
Color: White
29
S1 Lable S2 200
234.5
200
85
20
P1 4- 8.5
88 64
Installation and wiring Air Circuit Breaker P-050
25 50
100 2.75 22.2 7
7
14
23
23
55
16
72
52
7
32.25 35.5
4.8
17.35°
N
5
Undervoltage time delay controller Installation overall dimension of undervoltage time-delay controller
which is required to be plugged in the undervoltage time-delay tripper
98 15 37.5 10.5
2× 8.5
121.5
108
129
80
2× 4.5
84.5 30 81
P-051 Air Circuit Breaker Installation and wiring
N A B C SB2 SB3
PE
-
2 4 6 8 10 12 14 16 18 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT
FU
SA
Processing
unit
AX Power supply of
a control loop
Q F X M
FU
1 3 5 7 9 11 13 15 17 19 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 57 XT
+ HL1 HL2 HL3 HL4
Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release release coil indication motor
36 38 40 42 44 46 36 38 40 42 44 46 48 50 52
37 39 41 43 45 47 37 39 41 43 45 47 49 51 53
Q-Undervoltage release F-Shunt release X-Closing coil 25#~26#: External N-phase transformer input signal contacts. Conventional products are empty.
M-Charging motor SA-Limited XT-Wiring terminal When an external transformer is required to be attached for special order of users, they are external
AX-Auxiliary contact SB1-Emergency stop button transformer signal input contacts.
SB2-Tripping push button SB3-Closing push button HL1-Failure indication lamp 27#, 28#: Undervoltage release (Connected to the main circuit)
HL2-Charging indication lamp HL3-Tripping indication lamp 29#, 30#: Shunt release
HL4-Closing indication lamp FU-Fuse (6A) 31#, 32#: Closing coil
1#, 2#: Power supply of intelligent controller 33#, 34#: Charging indication
3#~5#: Tripping alarm contact (4-common point) 34#, 35#: Charging motor
6#, 9#: Auxiliary contact, normally open contact 36#~56#: Auxiliary contact
10#~11#: Empty Conventional products are four groups of adapters, and six groups of adapters can be provided(only for AC)
12#~19#: Empty for special order for users.
20#: PE line Note: The full line section is connected, and the dot line is connected
21#~24#: Empty by customers.
Installation and wiring Air Circuit Breaker P-052
1600A frame
P/H type control unit
PSU-1
profibus DC 24V
24V
+ -
ST-DP NC
GND
D+D -
N
+ - DI0 DI1 DI2 DI3 DI4
2 4 6 8 10 12 15 17 19 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT
FU
Processing SA
unit AX Power supply of
a control loop
Q F X M
FU
1 3 5 7 9 11 13 14 16 18 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 55 XT
+ Green
-
Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release coil indication motor
release
2000-6300A frame
M/A type control unit
N A B C SB2 SB3
PE
-
2 4 6 8 10 12 14 16 18 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT
FU
Processing
SA
unit
AX AX
AX Power supply of
a control loop
Q F X M
FU
1 3 5 7 9 11 13 15 17 19 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 57 XT
+ HL1 HL2 HL3 HL4
Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release release coil indication motor
Four groups of adapters (Default) Five groups of adapters Three-open three-closed auxiliary contact Q-Undervoltage release F-Shunt release X-Closing coil
M-Charging motor SA-Limited switch XT-Wiring terminal
36 38 40 42 44 46 36 38 40 42 44 46 48 50 36 38 40 42 44 46 AX-Auxiliary contact SB1-Emergency stop button SB2-Tripping push button
SB3-Closing push button HL1-Failure indication lamp
HL2-Charging indication lamp HL3-Tripping indication lamp
HL4-Closing indication lamp FU-Fuse (6A)
1#, 2#: Power supply of intelligent controller
3#~5#: Tripping alarm contact (4-common point)
6#~9#: Auxiliary contact, normally open contact
10#~11#: Empty
12#~19#: Empty
20#: PE line
37 39 41 43 45 47 37 39 41 43 45 47 49 37 39 41 43 45 47
21#~24#: Empty
25#~26#: External N-phase input signal contacts.
Four-open four-closed auxiliary contact Five-open five-closed auxiliary contact Conventional products are empty. When an external transformer is
required to be attached for special order of users, they are external
36 38 40 44 46 48 50 36 38 40 44 46 48 50 52 54
transformer signal input contacts.
42 42
27#, 28#: Undervoltage release (Connected to the main circuit or connedted
to the output of the undervoltage delay module)
29#, 30#: Shunt release
31#, 32#: Closing coil
33#, 34#: Charging indication
34#, 35#: Charging motor
36#~56#: Auxiliary contact
Conventional products are four groups of adapters.
The three-open three-closed auxiliary contact, the four-open four-closed
37 39 41 43 45 47 49 51 37 39 41 43 45 47 49 51 53 55 auxiliary contact, the five-open five-closed auxiliary contact, and five
groups of adapters can be provided for the special order for users.
Note: 1. the full line section is connected, and the dot line should be
Six-open Six-closed auxiliary contact connected by customers.
Note: 2. when the voltages of the controller of the 2000-4000 frame
6 8 36 38 40 42 44 46 48 50 52 54
are AC 230V/AC 400V, the controller can be directly connected to
1#, 2#terminals. When the voltage is DC 220V/DC 110V, the controller
can be connected to 1#, 2# terminals after the power supply module
outputs DC 24V.
7 9 37 39 41 43 45 47 49 51 53 55
Installation and wiring Air Circuit Breaker P-054
2000-6300A frame
P/H type control unit
Integrated circuit
AC 220V
PSU-1
profibus DC 24V
24V
ST-DP + -
NC
GND
D+ D-
2 4 6 8 10 12 15 17 19 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT
N
FU
Processing SA
unit
AX AX
AX
Power supply of
a control loop
Q F X M
FU
1 3 5 7 9 11 13 14 16 18 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 55 XT
+ Green
-
Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release coil indication motor
release
Conventional products are four groups of adapters. The three-open three-closed auxiliary
contact, the four-open four-closed auxiliary contact, the five-open five-closed auxiliary
contact, and five groups of adapters can be provided for the special order for users.
37 39 41 43 45 47 49 51 37 39 41 43 45 47 49 51 53 55 ST-DP: DP protocol module. When the upper computer communication protocol
is Modbus-RTU, the ST-DP protocol module is not required. When the upper computer
communication protocol is Profibus-DP, the Modbus-RTU protocol module is
21#~24#: voltage display input signal contact required to be converted into Profibus-DP protocol by the ST-DP protocol module, extra
P/H type intelligent controller fee needed.
21#: N-phase voltage signal, 22#: A-phase voltage signal RU-1: relay module. The circuit breaker is used for breaking and making via remote
23#: B-phase voltage signal, 24#: C- phase voltage signal control, and is used for breaking and making signal energy amplification, extra fee needed.
25#~26#: External N-phase transformer or external earthing Note: 1. the full line section is connected, and the dot line should be connected by
current transformer input signal contacts. customers.
Conventional products are empty. When an external transformer Note: 2. when the voltages of the controller of the 2000-4000 frame are AC 230V/AC 400V,
is required for special order for users, they are external transformer the controller can be directly connected to 1#, 2#terminals.
signal input contacts. When the voltage is DC 220V/DC 110V, the controller can be connected to
27#, 28#: Undervoltage release (Connected to the main circuit or connedted to the output of 1#, 2# terminals after the power supply module outputs DC 24V.
the undervoltage delay module)
29#, 30#: Shunt release, 31#, 32#: Closing coil, 33#, 34#: Charging indication
34#, 35#: Charging motor, 36#~56#: Auxiliary contact
P-055 Air Circuit Breaker Installation and wiring
Position indication
55 57 58 60 61 63
Power supply
56 59 62
Operation requirements:
1. The chassis indication device can indicate the positions including "disconnected" ,"test" and "connected"which are completely or partially used
according to the requirements of order.
2. When the body of the draw-out type circuit breaker is pushed from the "disconnected" position to the "test" position, 55# and 56# terminals should be transferred
from connection into disconnection, and 56# and 57# terminals should be transferred from disconnection to connection.
3. When the body of the draw-out type circuit breaker is pushed from the "disconnected" position to the "test" position, 58# and 59# terminals should be transferred
from connection into disconnection, and 59# and 60# terminals should be transferred from disconnection to connection. There is sufficient safety distance
between the bus of the circuit breaker body and a bridge-type contact of the safety shutter, and tripping and switching operation can be carried out reliably.
4. When the body of the draw-out type circuit breaker is switched from the "test" position to the "connected" position, NXA16 type secondary circuit has no clearance.
The NXA20-63 type safety shutter swing continuously after sending out the ‘"cracking" sound, and the safety shutter jiggle handle rotates within 1.5 circles.
61# and 62# terminals are being transferred from connection to disconnection. 62# and 63# terminals are transferred from disconnection to connection.
The busbar of circuit breaker body is required to be reliably inserted into the bridge-type contact of the chassis base, and reliably bear the main circuit current
to operate.
5. When the body of the draw-out type circuit breaker is pushed from the "connected" position to the "test" position, 58# and 59# terminals should be transferred
from connection into disconnection, and 59# and 60# terminals should be transferred from disconnection to connection. There is sufficient safety distance
between the busbar of the circuit breaker body and a bridge-type contact of the chassis, and tripping and switching operation can be carried out reliably.
6. When the body of the draw-out type circuit breaker swings from the "test" position to the "disconnected" position, 55# and 56# terminals should be transferred from
connection to disconnection, and 56# and 57# terminals should be transferred from disconnection to connection, and at the same time, the circuit breaker
body still cannot be drawn out, and needs to swing toward the "disconnected" position until the handle cannot swing any more, and meanwhile, the circuit breaker
body can be drawn out. After the circuit breaker is pulled out, 55# and 56# terminals should be transferred from disconnection to connection,
and 56# and 57# terminals should be transferred from connection to disconnection.
7. In the position transfer operation process of the chassis, the operation can only be stopped when the indicator points to "disconnected", "test" and "conncected"
or the position indicator cannot display the position of the circuit breaker body in the chassis correctly.
8.The above terminal numbers are all position signal specific numbers (55#-63#), which are not compatible with secondary circuit terminal numbers.
Rated voltage (V) Rated heating current Ith(A) Rated operating current Ie(A) Rated control capacity
Ac400
Interphase barrier 5 0.75 300VA
Annex I: Configuration Air Circuit Breaker P-056
1600A frame 2000A frame 3200A frame 4000A frame 6300A frame
Standard configuration
Fixed type draw-out type Fixed type draw-out type Fixed type draw-out type Fixed type draw-out type Fixed type draw-out type
Optional accessories
1600A frame
Fixed type draw-out type
2000A frame
Fixed type draw-out type
3200A frame
Fixed type draw-out type
4000A frame
Fixed type draw-out type
6300A frame
Fixed type draw-out type
N
Standard undervoltage release ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Adjustable time-delay undervoltage unit
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Pushbutton lock
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
"Disconnected" position padlock
▪ ▪ ▪ ▪ ▪
Safety shutters padlock
▪ ▪ ▪ ▪ ▪
Body lock
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Position door interlock ▪ ▪ ▪ ▪ ▪
State door interlock ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 6CO
▪ ▪
ON/OFF indication contact 5NO + 5NC
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 3NO + 3NC
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 4NO+4NC
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 5CO
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
"Connected", "Disconnected" and "test"
position indication contact ▪ ▪ ▪ ▪ ▪
Mechanical interlock ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Source-changeover controller
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
External transformer (Neutral CT) ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Earth current transformer and
accessories thereof
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Interphase barrier ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Triple mechanical interlock
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
P-057 Air Circuit Breaker Annex Ⅱ: Selection table
closed electromagnet pulse (must select pulse type in the AC110V □ AC220/230/240V □ AC380/400/415V □
(default in motor operation)
automatic control system) □ DC110V □ DC220V □
Lock mechanism Pushbutton lock □ Safety shutters padlock □ Body lock □ One-lock one-key □ Two-locks one-key □
(Match) Three-locks two-keys □ "Disconnected" position padlock □ Door interlock (Body) □ Door interlock (chassis) □
Mechanical interlock
MI-3(2on+1off) □ MI-4(1on+2off) □ ILK2 □
(Match)
Source-changeover
1 "Normal" and 1 "Replacement" □ 2 "Incoming" and 1 "Busbar" □
controller (Match)
Annex Ⅲ: Earth fault protection Air Circuit Breaker P-058
Earth protection
There are two protected modes for metal single-phase earth fault, namely vector sum(T) and earth current(W).Type-T detects zero
sequence current and four-phase current vector(three-phase four-wire system) or three-phase current vector(three-phase three-wire
system) will be added to provide reference for earth protection. Type-W detects earthing cable current directly by special external
transformer. Type-W can protect both stages of breaker at the same time. Distance between the transformer and breaker should be
no more than 5m. Zone interlocking can be used in the condition of vector sum earth fault.
a.correlation setting parameters of earth protection
Note: The delay time of earth fault is divided into two stages, inverse time and definite time. When fault current is less than 1.0In or 1200A,the protection is inverse, the time
delay is calculated as follow:
t=(1.0In or1200A/I)²×Tg
In this equation: t---action time
Tg --- setting delay time
I---fault earth current
P-059 Air Circuit Breaker Annex Ⅲ: Earth fault protection
When fault current is more than 1.0In or 1200A, the protection is definite; the time delay is the setting delay time.
c. Schematic Diagram of detection
Type-T
L1 Transformer
L1
L2 CT
L2 L1
L3 L2
L3
N L3
PEN
PE
intelligent
intelligent controller
controller intelligent
controller
N
Neutral pole CT
3P 4P 3P+N
Type-W
L1
L2
L3
N
CTB-2
intelligent
4CT controller
PE or
PEN
Setting time(s) 0.06 0.08 0.17 0.25 0.33 0.42 0.5 0.58 0.67 0.75 0.83 Instantaneous
Multiple of Fault Current Maximum Breaking Time(s)
1 I∆n 0.36 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 0.04
2 I∆n 0.18 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 0.04
5 I∆n
0.072 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.04
10 I∆n
Annex Ⅲ: Earth fault protection Air Circuit Breaker P-060
L2 L2
L3 L3
R
intelligent
controller intelligent
controller
N
ZCT1:rectangular leakage transformer (NXA16&NXA20-3P) ZCT1:rectangular leakage transformer(NXA16-4P)
Note: For Frame nxa16(3P&4P) and NXA20(3P) products, busbar can go through ZCT1, however,
not for Frame NXA20 4P and FrameNXA32/NXA40/NXA63.
protection zone
NXA
P-061 Air Circuit Breaker Annex Ⅳ: Source-changeover controller
CD-1: A 2A type source-changeover system is used for the switch between power grids or between the power grid and generator.
When a normal power supply does not supply power normally, such as undervoltage, overvolgage, phase breaking, a spare power
supply is switched for supplying power. A mechanical interlock component is configured according to standard.
Disconnection: S1, S2 are stripped, and the system load is not powered
2A type of functions
Automatic (The system judges the operateion automatically, and the light
is on when pressing the left upper part)
S1: load is powered by switching to S1, the TIE buscouple is tripped, and
the light is on at the left upper part when pressing S1. N
1 S2: load is powered by switching to S2, the TIE buscouple is tripped, and
the light is on at the left upper part when pressing S2.
2 Switch
S1 & S2:Load is powered by S1 & S2, TIE buscouple is tripped; the light is
operation
on at the left upper part when pressing S1 & S2.
zone
S1&TIE: Load is powered by S1, TIE buscouple is tripped; the light is on at
the left upper part when pressing S1&TIE
Pressing anyone of buttons S1, S2 S1 & S2, S1&TIE, S2&TIE under the
automatic condition, the system becomes manual, and corresponding
operation is carried out when pressing corresponding buttons.
3A type functions
Note
Note Air Circuit Breaker P-064
Note