Europe

Italy Spain
CHINT Italia Investment S.r.l. CHINT Electrics S.L.
Add: Via A. Pacino� 28, 30033 Noale (VE) Add: Calle José Echegaray, Num 8.Parque Empresarial Las Rozas
Tel: +39 041.446614 Edificio 3, Planta Baja, Oficina 7-8.C.P: 28232 Las Rozas (Madrid)
Fax +39 041.5845900 Tel: 0034 91 636 59 98
E-mail: [email protected] Fax: 0034 91 645 95 82
E-mail: [email protected]
Czech Republic
NOARK Electric Europe s.r.o. Russia
Add: Sezemická 2757/2, 193 00 Prague 9 ООО “Чинт Электрик”
Tel: +420 226 203 120
Юридический адрес: 109544, г. Москва, б-р Энтузиастов, д. 2, этаж 19,
Email: [email protected]
ком. 71; 72
Turkey Фактический адрес: РФ, 109544, г. Москва, б-р Энтузиастов, д. 2
Тел: +7 (495) 540-61-41
CHINT Turca Elektrik Sanayi VE Ticaret Anonim Sirke�
Тел: +7 (800) 222-61-41
Add: Zumrutevler Mahallesi Ural Sokak No. 22/18 NAS PLAZA B Block E-mail: [email protected]
KAT 1, Maltepe, Istanbul
Tel: +90216 621 00 55
Fax.:+90216 621 00 50
E-mail: [email protected]

North America La�n America


United States Brazil
NOARK Electric (USA) Inc CHINT Elétricos América do Sul Ltda
Add: 2188 Pomona Blvd., Pomona, CA 91768 Add: Av. Paulista, 1765 - Edi�cio Scarpa-Conj.22
Tel: 626-330-7007 Bela Vista –CEP 01311-200-São Paulo- SP
Fax: 626-330-8035 Tel: 0055-11-3266-7654
E-mail: [email protected] E-mail: chintla�[email protected]

Mexico
CHINT SOLAR MEXICO S DE RL DE CV
Peru
Add: Miguel Cervantes Saavedra 169 Piso 11 CHINT LATAM (PERU) S.A.C.
Col. Granada Del. Miguel Hidalgo
C.P. 11520 CDMX, México Add.: Camino Real 348 oficina 603, San Isidro, Lima
Tel: +52 1-55-8881-6127 Tel.: +51 1 763 4917
E-mail: [email protected] Email: [email protected]

West Asia & Africa Asia Pacific


U.A.E China
CHINT MIDDLE EAST AND AFRICA DMCC Zhejiang CHINT Electrics Co., Ltd.
Add: Unit No: 2101, Jumeirah business center 1, cluster G, Add (Shanghai):Bldg.2, No.3255 Sixian Road, Songjiang 201614 P.R.China
Jumeirah Lakes Towers, Dubai, UAE Tel: 0086-21-67777706
Tel: +97145571532 P.O BOX: 337555 Fax: 0086-21-67777777-88225

AIR CIRCUIT BREAKER


E-mail: [email protected] E-mail: asiapacifi[email protected]

India
Egypt CHINT India Energy Solu�on Private limited
CHINT Electrics (Egypt) Co., Ltd
Discovery Tower Plot No. A-17 Ground Floor Industrial Area NXA series air circuit breaker
Add: Building B16 - Smart village, Abu Rawash - Giza, Egypt Sector 62 Noida -201309
Tel: +20 1097173769 India Hotline: - 18002707977
P.O BOX : 00202 Company: - +91 1202975057
Email: [email protected] E-mail: marke�[email protected]

CHINT GLOBAL PTE. LTD.


Address: Building No.2, 3255 SiXian Road, Songjiang District, Shanghai, China
Postcode: 201614
Hotline

+86-4001177797
Tel: +86-21-6777 7777 Http://www.chintglobal.com
Fax: +86-21-6777 7777 E-mail: [email protected]

Printed by CHINT GROUP. No part of this brochure may be used or reproduced in any manner whatsoever without written permission. CHINT is the only CHINT GROUP ALL RIGHTS Reserved Recycle Paper Printed
publisher that can modify or change the content. Parts of the pictures used in the brochure are from the Internet. Pleases contact us in any case of copyright. 2020.07
ABOUT CHINT ONE CLOUD & TWO NETS STRATEGY

Business Model Innovation Solution Innovation

Solutions and Services for Customers Optimization for Manufacturing and Supply Chain

Intelligent Power Intelligent Product Factory Operation Intelligent


Energy Storage Automation Building Design and Service and Maintenance Manufacturing
System Solution Solution System Service System Solution

Intelligent Distributed Campus Process Industrial Smart


Photovoltaic System Microgrid Energy Efficiency Automation Automation Water
Solution Solution Solution Solution Solution Solution

Chint Energy Internet of Things Chint Industrial Internet of Things


( EIoT) ( IIoT )
CHINT A leading global provider of smart energy solutions
Chint Industrial Internet PaaS Platform
Founded in 1984, CHINT is a leading global provider of smart internal and external as the platform of intelligent technology
energy solutions. It is actively deploying“4+1” industrial and data application. Based on the Industrial Internet of Things
sectors including smart electrics, green energy, industrial (IIoT), CHINT built an intelligent manufacturing system and
control and automation, smart home and incubator, forming an realizes intelligent application in electrical industry. Relying on
integrated whole industry chain of “power generation, storage, the Energy Internet of Things (EIoT), CHINT built its smart
transmission, substation, distribution, sales and consumption”. energy system and develops the regional EIoT mode. Energy system optimization is an inevitable trend against the As a user-centric multi-energy complementary smart energy
And it boasts an extensive business network across over 140 background of resource shortage, environmental pollution and system, CHINT EIoT provides a package of energy solutions for
countries and regions as well as more than 30,000 employees Focusing on energy system of supply, storage, transmission, climate change – three challenges faced by global energy governments, industrial & commercial users and end users. Its
and an annual sales revenue of over USD 11.4 billion. CHINT has distribution and consumption, CHINT has core businesses of development. To keep in line with the trend, CHINT actively business includes Smart Energy Efficiency, Smart Power, Smart
been ranking among China’s Top 500 companies for 18 clean energy, energy distribution, big data and energy implements the business strategy of One Cloud & Two Nets, Home and Smart Clean Energy, etc.
consecutive years. Its subsidiary, CHINT Electrics is the first value-added services. Furthermore, CHINT pillar businesses continuously promotes the deep integration of big data, IoT, AI
company in China with low-voltage electrics as its main business include photovoltaic equipment, energy storage, power and manufacturing industry in stages to become a As a smart manufacturing system based on corporate digital
getting listed on the A-share market as one of the Top 50 Asian transmission & distribution, low-voltage apparatuses, platform-based enterprise, and leads the new direction of transformation, CHINT IIoT constitutes a flexible, high-efficiency
listed companies. intelligent terminals, software development and control industry development. and intelligent industrial system. Its business includes Intelligent
automation. With developing into a platform-based enterprise, Manufacturing, Intelligent Industry, Smart Water, Smart Heating,
To comply with the trend of integrated development of modern CHINT provides a package of energy solutions for public As a medium of smart technology and data applications, CHINT etc.
energy, intelligent manufacturing and digital technology, CHINT institutions, industrial & commercial users and end users, by Cloud connects corporate in-house manufacturing with
has adopted “One Cloud & Two Nets” as the business building a operation and management data, realizing digital applications
strategy. CHINT Cloud fulfills digital application and services in regional smart energy operation ecosphere. and services both internally and externally.
GLOBAL FOOTPRINT R&D, QUALITY, SALES, LOGISTICS

By providing reliable products and service for clients, CHINT puts forward the concept "Great Quality." Quality control and
upgrade is divided into four systems: scientific research, quality control, marketing service and logistics distribution. These methods
Moscow
Russia
and strategies make a comprehensive upgrade to product quality and services. Emphasis on "prevention first, continuous
Spain
Germany
Prague
Venice
improvement" is the basis of an effective quality inspection system. Leading the management process of "Great Quality" in the
North America
production process controls each link of production accurately and realizes the institutional operation of quality improvement.
Frankfurt
Madrid
Europe
US
Los Angeles
Jiuquan
Xianyang
Egypt
Algeria
Shanghai
"Great Quality" is not just a slogan, but a belief rooted in each employee's work. High-quality and accuracy are the basic requirement.
Dubai Hangzhou

Western Asia and Africa Wenzhou Mexico

Asia Pacific
Starting from a routine operation by each staff to implementing a high-quality of production and service, CHINT is
Thailand
Vietnam
your most reliable partner.
Malaysia

Singapore

Global R&D Center Latin America

Service Concept
International Marketing Territory
Peru
Brazil

Sincerely care for customers, quality creates value


Manufacturing Base
Sao Paulo

Logistics Center

Service Purpose
Innovative and progressive, satisfying the customers

GLOBAL CAPACITY LAYOUT


The industrial manufacturing bases are mainly located in Wenzhou, Hangzhou, Shanghai, Jiaxing and Xianyang. Additionally,
CHINIT has set up factories in Thailand, Egypt, Singapore, Vietnam, Malaysia, etc.

Integrated Vertical R&D Great Quality System One-stop Services 48-Hour Response

By gathering the global Ensuring flaw-free and CHINT's concept is that Providing end-to-end
industry elites to Provide safe trouble-free products, the it is not difficult to fulfill a high one-stop services for customers
Egypt Production Base Vietnam Production Base Malaysia Production Base Thailand Solar Power Singapore Complete Electric and stable energy-saving green multi-dimensional and -quality logistics distribution at with complaints, business
Production Base Equipment Production Base
and advanced electric products. multilevel control is one time, while it is difficult to consulting and technical support
conducted through stay as accurate and prompt as by solving problems immediately
procurement, inspection, the first-time. High-efficiency and including any possible prolems
At least 5% of revenue is
invested in research and quality control and and high-precision accuracy are in advance.
development
certification. our requirement.

Shanghai Production Base Hangzhou Production Base Wenzhou Production Base Jiaxing Production Base Xianyang Production Base
Air Circuit Breaker

NXA series air circuit breaker P-001

Overview P-003

Product selection P-005

Functions and features


Technical parameters P-009

Intelligent controller P-011

Protection feature P-015

Measurement precision of the intelligent controller P-017

Accessories P-019

Capacity derating and power loss P-023

Dimension of busbar P-026

Selective protection between NM8 and NXA P-027

Installation and wiring


Dimensions and installation P-029

Secondary circuit wiring P-051

Annex
Ⅰ Configuration P-056

Ⅱ Selection table P-057

Ⅲ Earth fault protection P-058

IV Source-changeover controller P-061


P-001 Air Circuit Breaker NXA series air circuit breaker

Structural features of the circuit breaker

Safety shutter
Arcing chamber

Shunt release
Undervoltage release
Auxiliary contact

Closed electromagnet

Intelligent controller

Operation mechanism
Energy-storage handle

Motor-driven energy-storage mechanism

Racking-handle

Breaking button
Making button

Front cover
NXA series air circuit breaker Air Circuit Breaker P-002

Circuit breaker description

3
16
4

15
5

6
N
7

10

14 11

13 12

1 Trademark 9 QR code

2 Secondary wiring terminal 10 Extraction draw plate (only applicable to draw-out type)

3 Breaking button 11 "Disconnected" position locking (only applicable to draw-out type)

4 Energy-storage handle 12 Racking-handle entry (only applicable to draw-out type)

5 Making button 13 Position indication (only applicable to draw-out type)

6 Nameplate 14 Racking-handle storage (only applicable to draw-out type)

7 Energy-storage/release indicator 15 Intelligent controller

8 Breaking/making indicator 16 Fault-breaking indicator reset button


P-003 Air Circuit Breaker Overview

Circuit breaker

● Frame size (A): 1600, 2000, 3200, 4000, 6300


● Breaking capacity: N,S,H
● Rated operational voltage Ue (VAC): 380/400/415, 440/525/690
● Number of poles: 3P, 4P
● Installation method: draw-out type, fixed type

Operation conditions and environment adaptability

● Operation temperature:
The electrical and mechanical characteristics are applicable to the ambient temperature
of -5℃-+40℃. NXA can also operate in the ambient temperature of -45℃-+70℃ (M type,
A type), -20℃-+70℃ (P type, H type, CD-1), the derating factor is seen in P23-24.
● Storage conditions: apply to -45℃~+70℃
● NXA can resist the following electromagnetic interference
— Overvoltage generated by electromagnetic interference
— Overvoltage caused by environment interference or a power distributing system
— Electrostatic discharge of radio waves (radio, intercom, radar and the like)
● NXA has successfully passed the test for electromagnetic compatibility specified according to
the following standards (EMC) IEC/EN 60947-2
Annex F
The test can guarantee no false tripping and no interference on tripping time
● Protection grade:
Front IP 20, other side IP 00

Connection

● Rear connection
Horizontal connection, vertical connection
● Optional accessories
Interphase barrier

Lock

● Padlocks of "Making" and "Breaking" push button


● Position padlock (for locking the circuit breaker at disconnected position)
● Chassis padlock
● Door interlock: the circuit breaker is arranged at the connected or test part so as to
prohibit to open the door

Indication contact

● Standard contact
Making and breaking indication contacts
Fault tripping indication contact
● Optional accessories
Position indication contact
Spring charged indication contact
Overview Air Circuit Breaker P-004

Drawowt type breaker

+ =

Drawer seat Body Drawout type breaker


N
Fixed type breaker

NXA16 NXA20~NXA40

Note:NXA63 fixed type is seen in P45

Accessories

Interphased partition Secondary wiring terminal-drawout type Secondary wiring terminal-fixed type

N pole CT Counter PSU-1


P-005 Air Circuit Breaker Product selection

NXA series air circuit breaker

Rated current
Frame size 400 630 800 1000 1250 1600 2000 2500 3200 3600 4000 5000 6300
Breaking capacity
N ▪ ▪ ▪ ▪ ▪ ▪
1600A S ▪ ▪ ▪ ▪ ▪ ▪
H ▪ ▪ ▪ ▪ ▪ ▪
N
▪ ▪ ▪ ▪ ▪ ▪
2000A S
▪ ▪ ▪ ▪ ▪ ▪
H
▪ ▪ ▪ ▪ ▪ ▪
N
▪ ▪ ▪ ▪
3200A S
▪ ▪ ▪ ▪
H
▪ ▪ ▪ ▪
N
▪ ▪ ▪
4000A S
▪ ▪ ▪
H
▪ ▪ ▪
6300A H
▪ ▪ ▪
Model definition and description

NXA 16 N 04 M D 3 AC230 M Other

Code of Code Code of Code of Code of Code of Code of Code of


Code of Code of breaking control circuit
of rated intelligent installation number operation special
Product frame size capacity voltage
current controller method of poles mode requirement

M: basic type No code: No code:


16:1600A N: basic 04-400A D: draw-out 3: AC 230:
motor no special
(04-16) type A
type 3 poles AC 230V
06-630A operation requirement
A: current type

N A B C

08-800A
20:2000A S: standard 10-1000A P: power type F: fixed 4: AC 400: M: manual Special
(06-20) type type 4 poles AC 400V operation requirements
12-1250A OA
code,
H: harmonic N A B C
16-1600A type such as: UVT
150
32:3200A H: advanced DC 110:
20-2000A
(16-32) type 100 DC 110V
25-2500A
0
32-3200A
40:4000A DC 220:
(32-40) 36-3600A DC 220V
40-4000A
50-5000A
63:6300A
(40-63) 63-6300A

1)
Note: Intelligent controller PT/HT type. The basic functions are the same with P/H type. T refers to the internal temperature measurement function.
2)
Manual operation does not contain motor-driven mechanism, closing electromagnet and shunt release. Motor operation contains all standard accessories of remote
operation.
3)
Auxiliary working voltage of the intelligent controller: corresponding power modules is required if DC220V or DC110V is selected.
4)
NXA16N10-AD3-AC230: frame size is 1600A, N type breaking capacity, rated current is 1000A, A type intelligent controller, draw-out type and 3 poles, control
voltage is AC 230V motor operation.
Product selection Air Circuit Breaker P-006

Model definition and description-intelligent controller

NXA 16 TU M 04 3 AC230

Code of Code of Intelligent Code of Code of Code of Code of auxiliary


product frame size controller intelligent controller rated current number of poles power supply

16:1600A (04-16) M: basic type 3: AC 230:


04-400A; 06-630A
3 poles AC 230V
A: current type 08-800A; 10-1000A
20:2000A (06-20)
12-1250A; 16-1600A 4:
P: power type AC 400:

32:3200A (16-32)
H: harmonic type
20-2000A; 25-2500A
32-3200A; 36-3600A
4 poles AC 400V
N
40-4000A; 50-5000A DC 110:
40:4000A (32-40) DC 110V
63-6300A

63:6300A (40-63) DC 220:


DC 220V

Model definition and description-accessories

NXA 16 CC 230VAC

Code of
Frame size Code of accessories Code of rated voltage
product

16:1600A CC: Closed electromagnet 230VAC: AC230V

20:2000A ST: Shunt tripper 400VAC: AC400V

32:3200A MO: Motor 110VDC: DC110V

40:4000A UVT: Undervoltage tripper 220VDC: DC220V

63:6300A ASUVT:Self-priming undervoltage tripper Rated voltage+delay time


(1s、3s、5s、7s)
20/40:2000A-4000A UVTD:UVT delay unit

20/32:2000A-3200A ASUVTD: ASUVT delay unit

20/63:2000A-6300A
P-007 Air Circuit Breaker Product selection

Model definition and description-accessories

NXA 16 OF C04

Code of
Frame size Code of accessories Specification of accessories
product

16:1600A C04: Four groups of contacts

20:2000A C05: Five groups of contacts

32:3200A C06: Six groups of contacts


OF: Auxiliary contact
40:4000A N3: Three normally open and three normally closed

63:6300A N4: Four normally open and four normally closed

20/40:2000A-4000A N5: Five normally open and five normally closed

20/32:2000A-3200A 1S1S: One lock and one key

20/63:2000A-6300A KL: Key lock 2S1S: Two locks and one key

3S2S: Three locks and two keys

FCDP: Fixed type door frame

DCDP: Draw-out type door frame

FD: Fixed type interphased partition

DD: Draw-out type interphased partition

CE-CD-CT: Position signal

ILK2: Mechanical interlocking


two interlocking steel cables

MI-3: Triple mechanical


interlock ( 2on+1off )

MI-4: Triple mechanical


interlock ( 1on+2off )
Note Air Circuit Breaker P-008

Note

N
P-009 Air Circuit Breaker Functions and features

Technical parameters
Features

Number of poles 3/4 6300A only 3P


Rated operational voltage Ue (V) AC 380/400/415 , AC 440/525/690
Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 12
Rated frequency (Hz) 50/60
Flashover distance (mm) 0
Applicable to isolation IEC/EN 60947-2 Applicable
Pollution grade IEC 60664-1 N:3

Frame size 1600A


Rated current (A) 400 630 800 1000 1250 1600
Rated current of the fourth pole (A) 400 630 800 1000 1250 1600
Type of the circuit breaker N S H
380/400/415V 50 42 50
Rated ultimate short circuit breaking capacity (kA rms) VAC 50/60Hz Icu
440/525/690V 30 36 36
380/400/415V 42 42 50
Rated service short circuit breaking capacity (kA rms) VAC 50/60Hz Ics
440/525/690V 30 36 36
Utilization category B
380/400/415V 42 42 42
Rated short-time withstand current (kA rms) VAC 50/60Hz Icw 1s
440/525/690V 30 36 36
380/400/415V 20 25 25
Icw 3s
440/525/690V - - -
380/400/415V 105 88.2 105
Closed capacity (kA peak) VAC 50/60Hz Icm
440/525/690V 63 75.6 75.6
Making current tripping protection function (MCR kA rms) 10 16 16
Breaking time (ms) 32
Closing time (ms) 70
Installation, connection and service life

Mechanical Without maintenance 15000


Service life C/O cycle
Electrical Without maintenance 8000
Connection Horizontal ▪

3P 254×243.5×318.5
Fixed type
Size (width × depth × height) 4P 324×243.5×318.5
3P 308×331.5×351
Draw-out type
4P 378×331.5×351
Functions and features Air Circuit Breaker P-010

2000A
630 800 1000 1250 1600 2000
3200A
1600 2000 2500 3200
4000A
3200 3600 4000
6300A
4000 5000 6000
N
630 800 1000 1250 1600 2000 1600 2000 2500 3200 3200 3600 4000 2000 2500 -
N S H N S H N S H H
80 65 80 80 80 100 80 85 100 120
50 55 55 65 70 70 65 75 75 85
50 65 65 80 80 85 80 85 85 120
50 55 55 65 70 70 65 75 75 85
B B B B
50 65 65 65 80 85 65 85 85 100
50 55 55 65 70 70 65 75 75 75
37 42 42 37 50 50 37 50 50 -
- - - - - - - - - -
176 143 176 176 176 220 176 187 220 264
105 121 121 143 154 154 143 165 165 187
16 16 16 26 26 26 26 26 26 26
32 32 32 32
70 70 70 70

15000 10000 10000 2000


8000 7000 3000 500
▪ ▪ ▪ ▪

374×344×400 439×373.5×400 550×337.5×400 897×435.5×399


469×344×400 554×373.5×400 700×337.5×400 897×435.5×399
403×430×438.5 463×499.5×438.5 569×416×438.5 923×500×435.5
498×430×438.5 578×499.5×438.5 719×416×438.5 923×500×435.5
P-011 Air Circuit Breaker Functions and features

Intelligent controller
M type intelligent controller (Basic type)

Protection
All the protective threshold and time delay are set by a dial switch
1

● Overload protection
— Ture RMS long-time-delay protection
2
— Thermal memory: heat accumulation before and after tripping

3 ● Short circuit protection


4 — Short-time delay (RMS) and instantaneous protection
12 — Optional four steps time-delay setting
5

13
6
● Earth fault protection
7 14 Optional four steps time-delay setting
8 15
● Neutral line overcurrent protection (4P)
16
The neutral protective threshold can be adjusted to 50%, 100% and OFF
17
9
18 ● Test function
10
Simulating 6Ir test current for test tripping
11

● Tripping record function

1. Display window: display the current ● Ampere meter


value, the setting parameter, the fault
current,the tripping time Measure the real and effective value (RMS) of
2. Ig indicator for earth fault indication current with the precision of 2% for 40% to 150% in setting
3. Ir indicator for overload long-time-
delay tripping
4. Isd indicator for short circuit short-
time-delay tripping
5. Ii indicator for short circuit tripping
6. Menu button for inquiring the dial
position and fault record
7. Rightward button: turn to the next
state when inquiring the dial
position
8. Return button: back to the previous
level or resetting
9. Overload long-time-delay current
setting
10. Short circuit short-time-delay current
setting
11. Earth fault current setting
12. Overload long-time-delay time
setting
13. Transparent cover lockhole
14. Short circuit short-time-delay time
setting
15. Neutral line protection setting
16. Earth fault time-delay setting
17. Test button for simulating 6IR
current
18. Short circuit instantaneous current
setting
Functions and features Air Circuit Breaker P-012

A type intelligent controller (Current type)

Protection
All the protective threshold and time delay are set by a dial switch
1

● Overload protection
2
— Ture RMS long-time-delay protection
— Thermal memory: heat accumulation before and after tripping

3 ● Short circuit protection


4 — Short-time delay (RMS) and instantaneous protection
5

6
12

13
— Optional four steps time-delay setting

● Earth fault protection


N
7 14 Optional four steps time-delay setting
8 15
● Neutral line overcurrent protection (4P)
16
The neutral protective threshold can be adjusted to 50%, 100% and OFF
17
9
18 ● Unbalanced current protection
10
Protecting phase failure or three phase unbalance
11

● Test function
1. Display window: display the current Simulating 6Ir test current for test tripping
value, the setting parameter, the
fault current, the tripping time
2. Ig indicator for earth fault ● Tripping record function
indication
3. Ir indicator for overload long- ● Ampere meter
time-delay tripping
Measure the real and effective value (RMS) of
4. Isd indicator for short circuit short-
time-delay tripping current with the precision of 2% for 40% to 150% in setting
5. Ii indicator for short circuit
tripping
6. Menu button for inquiring the dial
position and fault record
7. Rightward button: turn to the next
state when inquiring the dial
position
8. Return button: back to the previous
level or resetting
9. Overload long-time-delay current
setting
10. Short circuit short-time-delay
current setting
11. Earth fault current setting
12. Overload long-time-delay time
setting
13. Transparent cover lockhole
14. Short circuit short-time-delay time
setting
15. Neutral line protection setting
16. Earth fault time-delay setting
17. Test button for simulating 6IR
current
18. Short circuit instantaneous
current setting
P-013 Air Circuit Breaker Functions and features

P type intelligent controller (Power type)

Protection
Setting all protective threshold values and time-delay by button
The setting values can be displayed on LCD display window

1 ● Protection functions of all A type control units are included


● Earth current protection function (Optional)
2
External transformer are configured
3 ● Advanced protection function

4
— Unbalanced voltage protection
— Overvoltage and undervoltage protection
5
— Overfrequency and underfrequency protection
6 — Phase sequence protection
— Reverse power protection function
7
— Required value protection function
13
8 The required value of the real and effective value of each current is calculated within a measurement window.

14 When the required value is off limit, the protection action is carried out. The setting of a sliding time window
9
is in the menu of "setting of a measurement meter".
15
10 ·A-phase maximal required current value,
·B-phase maximal required current value,
11
·C-phase maximal required current value,
12 ·N-phase maximal required current value are respectively set for each circumstance of the required value
protection without being affected by the setting of the neutral line protection.

● Extended function
— Self-diagnosis by the intelligent controller
1. Ig indicator for earth fault
— Operation times/fault tripping/alarming/deflection recording function provides the
tripping
2. Ir indicator for overload long-
latest ten times of recording
time-delay tripping — Main contact abrasion display function for evaluating the contact abrasion degree
3. Isd indicator for short circuit short- according to mechanical life, electrical services and breaking capacities of different
time-delay tripping frames.
4. Ii indicator for short circuit — Internal clock function
tripping — A Mini-USB interface is connected with a PC to achieve the functions of protection
5. Running indicator flickering in
setting, fault record downloading, whole power quantity detection and parameter
normal running
reading of a circuit breaker.
6. LCD screen with three-color
backlight. Green stands for normal
— "test" push button
running, yellow stands for ● Electric energy meter
alarming and red stands for — Current measurement
tripping. — Voltage measurement
7. Setting button — Frequency measurement
8. Leftward button — Required value measurement
9. Upward button
— Power (active power, reactive power and apparent) measurement
10. Downward button
— Electric energy (active power, reactive power and apparent) measurement
11. Enter button
12. Rightward button
— Power factor measurement
13. Transparent cover lockhole ● LCD three-color backlight
14. Mini-USB interface Green stands for normal running, yellow stands for alarming and red stands for tripping.
15. Test button for tripping test
Functions and features Air Circuit Breaker P-014

H type intelligent controller (Harmonic wave type)


Protection
Setting all protective threshold values and time-delay by button

Besides the protective extended function of all P type control units,


H type control unit also comprises:
1
● Load monitoring function
2 ● Zone selective interlock (ZSI) (Optional)
3 ● Communication function
Modbus-RTU communication protocol
4
● Input/output function
5 — 2DI+2DO or 4DO

N
— DI signal: AC230V ( Standard configuration, and others can be selected);
6
DC110V
7 — DO needs to be configured with a power supply module (24VDC output) and
13 a relay module.
8

14
● Harmonic analysis function
9
— Measurement of the fundamental wave current, the fundamental wave line voltage,
15
10 the fundamental wave phase voltage, the fundamental wave power and each 3-31
odd harmonic wave current percentage (HRIh), the harmonic voltage percentage
11
(HRUh), the total harmonic wave current distortion rate (THDi, thdi) and the total
12 harmonic wave voltage distortion rate (THDu, thdu).
— The harmonic wave percentage(HR) refers to the ratio of root-mean-square value
of the Nth harmonic wave component contained in periodic alternative current quantity
to the root-mean-square value of the fundamental wave component, and is expressed
1. Ig indicator for earth fault
in percentage.
tripping
2. Ir indicator for overload long-
time-delay tripping
3. Isd indicator for short circuit short-
time-delay tripping
4. Ii indicator for short circuit
tripping
5. Running indicator flickering in
normal running
6. LCD screen with three-color
backlight. Green stands for normal
running, yellow stands for
alarming and red stands for
tripping.
7. Setting button
8. Leftward button
9. Upward button
10. Downward button
11. Enter button
12. Rightward button
13. Transparent cover lockhole
14. Mini-USB interface
15. Test button for tripping test
P-015 Air Circuit Breaker Functions and features

Protection features
The protection features of the intelligent controller comprise inverse time characteristic and constant time characteristic. When the fault current
exceeds the set value of the inverse time limit, the controller performs constant time protection.
The inverse time limit corresponds to the feature curve I2t.

Overload long-time-delay protection feature

Overload long-time-delay protection action threshold value


<1.05Ir : >2h, no action
≥1.3Ir : <1h, action

Ir current setting value range: 0.4In, 0.5 In, 0.6 In, 0.7 In, 0.8 In, 0.9 In, 1.0 In+OFF (M/A);0.4In~1.0In+OFF(P/H)
Inverse time limit action feature: I2t, wherein t=(6/N)2*tr

Setting Multiple of Current Action Time

1.5Ir 16 32 64 128 192 256 320 384

2Ir 9 18 36 72 108 144 180 216


6Ir 1 2 4 8 12 16 20 24

Note: N --- the multiple I/Ir obtained by dividing failure current by set current
t --- time delay action of the failure action
tr --- long-time-delay set value
Allowed error of the action time ±15%
Conventional factory tuning:Ir=1.0In
tr=2s@6Ir

Short circuit short-time-delay protection feature

Short circuit short-time-delay protection action threshold value


<0.85Isd: no action
>1.15Isd: action
Isd current set value range: 2Ir, 3Ir , 4Ir, 5Ir, 6Ir , 8Ir, 10Ir +OFF (max 50kA,M/A);2Ir~10Ir+OFF(max 50kA,P/H)

Current Action time Remark


2
Action feature I²t= (10Ir) tsd
Isd<I≤10Ir Inverse time limit P, H
Setting time s 0.1, 0.2, 0.3, 0.4

Setting time s 0.1, 0.2, 0.3, 0.4

I≥1.1Isd Constant time limit Minimum s 0.06, 0.16, 0.255, 0.34 M, A, P, H

Maximum s 0.14, 0.24, 0.345, 0.46


Return time 0.05, 0.14, 0.25, 0.33

Note: Isd---short-time-delay current set value


I--- failure current value
Ir— long-time-delay set value
t--- failure action time-delay time
tsd---short-time-delay inverse time limit set value
Permissible error of action time ±15%
Conventional factory tuning:Isd=8Ir(Ir<6250A)
Isd=50kA(Ir≥6250A)
tsd=0.4s
Functions and features Air Circuit Breaker P-016

Short circuit instantaneous protection features

Short circuit instantaneous protection action threshold value


<0.85Ii: no action
>1.15Ii: action
The current setting value of instantaneous action: 2In, 4In, 6In, 8In, 10In, 12In, 15In+OFF(NXA40 max50kA,NXA63 max63kA,M/A);
2In~15In+OFF(NXA40 max 50kA,NXA63 max63kA P/H)
Note: action time≤50ms
Conventional factory tuning:Ii=12In(In=400A~5000A)
Ii=63kA(In=6300A)

Earth fault protection action features

Earth fault protection action threshold value


<0.9Ig: no action
>1.1Ig: action
N
M/A

Current setting value A B C D E F G OFF


NXA16, 20 0.2In 0.3In 0.4In 0.5In 0.6In 0.8In In

NXA32, 40, 63 500A 640A 800A 960A 1040A 1120A 1200A


tg(s) Inverse time limit Action features
P/H ( Ig )²
NXA16、20: 0.2In~1.0In+OFF t= ×tg

NXA32、40、63: 500A~1200A+OFF
Setting time (s) 0.1 0.2 0.3 0.4
Minimum (s) 0.06 0.16 0.255 0.34
Constant time limit
Maximal (s) 0.14 0.24 0.345 0.46
Return time 0.05 0.14 0.25 0.33

Note: Ig --- earth fault protection setting value. Default setting:NXA16/20:Ig=0.5In


When In≥1250A,Ig max=1200A NXA32/40/63: Ig=800A
I --- failure current value
t --- failure action time-delay time
tg --- earthing inverse time limit set value
The permissible error of the inverse time limit action time: ±15%
Conventional factory tuning:OFF

Controller minimum display current

Frame In Minimum display value(A)

1600 400~1600 60
2000 630~2000 60
≥3200 ≥1600 120
P-017 Air Circuit Breaker Functions and features

Measurement precision of the intelligent controller


Current measurement

Measurement range Ia, Ib, Ic and IN are not less than 15In (rated current of the circuit breaker)
Below 0.1In: the measurement is inaccurate
0.1In-0.4In: the accuracy will be changed linearly from 5% to 2%
Measurement precision 0.4In-1.5In: the accuracy is 2%
>1.5In: the accuracy will be changed linearly from 2% to 15%
The measurement accuracy of the earthing current is 10%

Voltage measurement

Line voltage: 0V~600V


Measurement range
Phase voltage: 0V~300V
Measurement precision Error: ±1%

Frequency

Measurement range 40HZ~70HZ

Measurement precision Error: ± 0.1HZ

Power

Measurement mode The effective value mode


3P type: total active power, total reactive power and total apparent power
Measurement content
4P type: phase splitting active power, phase splitting reactive power, phase splitting apparent power, total active
power, total reactive power, total apparent power
Active power: -32768KW~ + 32767KW
Reactive power: -32768Kvar~ + 32767Kvar
Measurement power
Apparent power: 0KVA~65535KVA

Error: ±2.5%

Power factor
Measurement content phase splitting power factor,total power factor
Measurement range -1.00~+1.00

Electric energy

Input reactive electric energy (EQin), output reactive electric energy (Eqout)
Measurement content Input active electric energy (EPin), output active electric energy (Epout)
Total active electric energy (EPtotal), total reactive electric energy (EQtotal), total apparent electric energy (Estotal)

Active electric energy: -32768KWh~ + 32767KWh


Measurement range Reactive electric energy: -32768Kvarh~ + 32767Kvarh
Apparent electric energy: 0~65535KVAh
Measurement precision Error ±2.5%

Harmonic wave measurement


Current: Ia, Ib, Ic,IN
Fundamental wave measurement
Voltage: Uan,Ubn,Ucn

Total harmonic wave distortion THD: the total distortion rate of the harmonic wave relatively to the fundamental wave
THDu and thdu Thd: the total distortion rate of the harmonic wave relatively to the effective value
Amplitude wave spectrum of harmonic wave The controller can display FFT amplitude of odd harmonic wave from 3 to 31in percentage
Measurement precision of control unit ±2%
Tripping curves Air Circuit Breaker P-018

LSI curves

Ir=(0.4~1)In

1000

100

tr=(1~24)s

10
T(s)

Isd=(2~10)Ir(max50kA)
N
1

0.4
0.3
0.2
0.1 0.1

Ii=(2~15)In
(max50/63kA)

0.01
0.5 1 2 3 4 5 10 3 6 9 12 18 24 30
I(xIr) I(xIn)

Fig.1 Overcurrent protection curves

Earth fault protection curves

Ig=(0.2~1)In or
1000 500A~1200A

100

10
T(s)

0.4
0.3
0.2

0.1 0.1

0.01
0.1 1 10
I(xIn)

Fig.2 Asymmetrical earth fault protection curves


P-019 Air Circuit Breaker Functions and features

Accessories: locks
Pushbutton lock
The pushbutton lock is to lock the circuit breaker by a transperant conver blocks so as to
prevent the breaking button and the making button of the circuit breaker from misoperation
and guarantee the reliable running of the circuit breaker.

Body lock

● A key lock includes four types. The latter two are applied to 2 input and 1 connect
power distribution system:
— Random lock
— One lock and one key
— Two locks and one key
— Three locks and two keys
Note:When the user separately purchases the key lock for installation, the panel needs to
be opened with a hole opener, and the hole opener is provided by the user.
Hole diameter:NXA16:Φ21mm NXA20~63:Φ24mm

Safety shutters padlock


● The padlock is prepared by users.Diameter of the lock is no more than Φ5mm.
when a circuit breaker body is at the disconnected or test part,
the safety shutters automatically block access to the disconnecting contact cluster.

"Disconnected" position padlock

After the chassis and body are locked at "Disconnected" position by a padlock, the
racking-handle cannot be inserted into racking-handle entry, and then the position
of the body cannot be changed.

Door interlock
Circuit breaker state door interlock
A cabinet door is prohibited to be opened when the circuit breaker is closed.
The cabinet door is allowed to be opened when the circuit breaker is disconnected.
Circuit breaker position door interlock
The cabinet door is prohibited to be opened when the circuit breaker is at the connected
and test part. The cabinet door is allowed to be opened when the circuit breaker is at the
disconnected position.

Cable mechanical interlock

It can realize the interlock of two horizontal or vertical-installed,three poles or four


poles,drawout type or fixed type circuit breaker.

Circuit diagram Available running manner

1QF 2QF 3QF


0 0 0 1QF 2QF 3QF
0 0 1 0 0 0
0 1 1 0 0 1
1QF 2QF 3QF 1 0 0 1QF 2QF 3QF 0 1 0
1 1 0 1 0 0
1 0 1

Note:a. If need bend the cable,make sure radian is more than 120°.
b. Check and make sure enough lubricating oil of the cable.
c. The maximum distance between two interlock circuit breakers is1.5m.
Functions and features Air Circuit Breaker P-020

Accessories: indication contacts


ON/OFF indication contacts

Standard configuration 4CO 6CO(for AC of NXA16 only)


Breaking capacity Current (A) / Voltage (V) Current (A) / Voltage (V)
VAC(AC-15) 1.3/240, 0.75/415 1.3/240, 0.75/415
Utilization category
VDC(DC-13) 0.55/110, 0.27/220 0.55/110, 0.27/220

"Connected", "disconnected" and "test" position indication contact


Standard configuration 1CO/3
Breaking capacity Current (A) / Voltage (V)
VAC(AC-15) 1.3/240, 0.75/415
Utilization category
VDC(DC-13) 0.55/110, 0.27/220

Alarming contact
N
Standard configuration 1CO
Breaking capacity Current (A) / Voltage (V)
VAC(AC-15) 1.3/240, 0.75/415
Utilization category
VDC(DC-13) 0.55/110, 0.27/220

Spring charging indication contact


Standard configuration 1NO
Breaking capacity Current (A)/ Voltage (V)
VAC(AC-15) 1.3/240, 0.75/415
Utilization category
VDC(DC-13) 0.55/110, 0.27/220

1)
Note: CO refers to a switch contact, and a one-normally-open and one-normally-closed contact is matched with a
common terminal.
2)
NO refers to a normally open contact. NC refers to a normally closed contact.

Source-changeover systems

● Mechanical interlock
1 normal and 1 replacement
2 incoming and 1 busbar
● Source-changeover controller (with adaptor)
1 normal and 1 replacement: mechanical interlock+2A type controller
2 incoming and 1 busbar: mechanical interlock+3A type controller
P-021 Air Circuit Breaker Functions and features

●Motor-driven mechanism (MO) (Standard configuration)


When a circuit breaker is switched on, an motor operation mechanism stores energy
automatically, so that when the circuit breaker is tripped, the device can switch on instantly.
An energy-storage handle as spare when no auxiliary power supply is provided.

Characteristics
VAC 50/60HZ 220/230/240, 380/400/415
Power supply
VDC 110, 220
Operation threshold 0.85-1.1Us
Frame size: power loss (VA or W) 16: 75W; 20: 85W; 32: 110W; 40: 110W; 63: 150W
1600A frame MO 2000A~6300A frame MO Motor overcurrent ≤1min
Charging time ≤7s
Operation frequency ≤2times/min

●Voltage coils (CC &ST) (Standard configuration)


●Closing coil (CC)
After the energy storage of the motor is completed, the closed electromagnet can be
operated and controlled within a range of 10 meters to instantaneously release the
energy storage spring force of the operating mechanism to close the circuit breaker.
1600A frame CC&ST

AC110
Rated control power supply voltage Us(V)AC 220/230/240 AC 380/400/415 DC220 DC110
(not available for NXA16)

Operation Voltage(V) (0.85-1.1)Us

Close time (ms) ≤50

NXA16 pulse 56 56 250 250 -


Power
consumption intermittent 300 300 132 70 300
(VA/W) NXA20~63
pulse 880 1800 880 850 850

Notes:
2000A~6300A frame CC&ST
1. It must select pulse type in the automatic control system.
2. power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of
the pulse type cannot be more than 5 times/min, or the components are easily burnt.
3. Ensure that the product is in the energy storage state so that the closed electromagnet
may be energized;
4. If the product is not closed after a single power-on for 15s, must disconnect the power
on the closed electromagnet immediately.

●Shunt release (ST)


The power-on time cannot be greater than 2 seconds / time, and the power-on
frequency cannot be greater than 5 times / minute.
a. The shunt release should be used except for special products where the circuit breaker
must be directly disconnected manually;
b. The shunt release could operated within 10 meters to break the circuit breaker.

AC110
Rated control power supply voltage Us(V)AC 220/230/240 AC 380/400/415 DC220 DC110
(not available for NXA16)

Operation Voltage(V) (0.7-1.1)Us

Break time (ms) ≤28

NXA16 pulse 56 56 250 250 -


Power
consumption intermittent 300 300 132 70 300
(VA/W) NXA20~63
pulse 880 1800 880 850 850

Notes:
1. It must select pulse type in the automatic control system.
2. power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of
the pulse type cannot be more than 5 times/min, or the components are easily burnt;
3. If the circuit breaker is not break by a single power-on of 15 s, must disconnect the
power on the shunt release immediately.
Functions and features Air Circuit Breaker P-022

● Undervoltage release (UVT)


Under-voltage release (UVT) (Optional, The power must be turned on before the
circuit breaker is closed)
The under-voltage release has instantaneous operation and delayed operation:

Operation types of each frame under-voltage release

Self-priming Helped priming


Under-voltage instantaneous release Inm=1600A, 6300A Inm=2000A, 3200A, 4000A
1600A frame UVT 2000~4000A frame UVT
Under-voltage delay release Inm=1600A, 6300A Inm=2000A, 3200A, 4000A

Notes:
1. Inm=1600A under-voltage delay does not require an external delay controller.
The power-off operation is an instantaneous operation. There is no zero
voltage delay function;
2. Inm=6300A under-voltage delay does not require an external under-voltage delay
controller. There is a delay function for low voltage and power off;
N
6300A frame ASUVT 3. Inm=2000A~4000A under-voltage delay requires an external delay controller.
There is a delay operation when the power is off. There is a zero voltage delay function.

Delay time of under-voltage release Delay time (optional) Accuracy


Inm=1600A 1 s, 3 s, 5 s, 7 s (not adjustable) ±15%
Inm=2000A~4000A 1 s, 3 s, 5 s (not adjustable) 0~1s

Inm=6300A 0.3 s~7.5 s (adjustable) ±15%

The under-voltage will not operate when the voltage returns to 85% Ue and higher,, within 1/2 delay time.

2000~4000A frame UVTD


Note:
A self-priming under-voltage delay release may be provided for special orders
of NXA20~63. There is no external under-voltage delay controller, and the delay time
is 0.3s~7.5s, selectable and adjustable with an accuracy of ±15%.
When the under-voltage release is not powered, the circuit breaker cannot be closed
either electrically or manually.

Characteristics of under-voltage release

Rated control power supply voltage Ue(V) Ac110. AC220/230/240. AC380/400/415


Operating voltage (V) (0.35~0.7)Ue

Reliable closing voltage (V) (0.85~1.1)Ue

Reliable not-closing voltage (V) ≤0.35Ue

Power consumption (Inm=1600A/Inm=2000A~6300A) 20VA/48VA (W)


P-023 Air Circuit Breaker Functions and features

Capacity derating and power loss


Temperature capacity derating table of the fixed type circuit breaker
1600A frame
Ambient temperature 400A 630A 800A 1000A 1250A 1600A
Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - - - - - -
45° - - - - - - - - - - - -
50° - - - - - - - - - - 1550 1600
55° - - - - - - - - 1150 1200 1500 1550
60° - - 550 580 - - - - 1050 1100 1450 1500

2000A frame
Ambient temperature 630A 800A 1000A 1250A 1600A 2000A
Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - - - - - -
45° - - - - - - - - 1550 - 1900 -
50° - - - - - - - - 1500 1550 1850 1900
55° - - - - - - - - 1400 1450 1800 1800
60° - - - - - - - - 1300 1350 1700 1700

3200A frame

Ambient temperature 1600A 2000A 2500A 3200A


Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - -
45° - - - - - - - -
50° - - - - - - 3100 -
55° - - - - 2450 - 3000 3050
60° - - - - 2350 2400 2900 2950

4000A frame

Ambient temperature 3200A 3600A 4000A


Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - -
45° 3100 - - - 3800 3850
50° 3000 - - - 3600 3650
55° 3000 3050 3400 3450 3400 3450
60° 2900 2900 3200 3250 3200 3250

6300A frame

Ambient temperature 4000A 5000A 6300A


Connection mode Horizontal Horizontal Horizontal
40° - - -
45° - - -
50° - - 5600
55° - 4800 5400
60° - 4800 5200

Note: “-” refers to no capacity derating.


Functions and features Air Circuit Breaker P-024

Temperature capacity derating table of the draw-out type circuit breaker


1600A frame
Ambient temperature 400A 630A 800A 1000A 1250A 1600A
Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - - - - - -

45° - - - - - - - - - - 1550 -

50° - - - - - - - - 1150 1200 1500 1550


55° - - 550 580 - - - - 1050 1100 1450 1500
60° - - 500 530 - - 950 - 950 1000 1400 1450

2000A frame
Ambient temperature 630A 800A 1000A 1250A 1600A 2000A
N
Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - - - - - -

45° - - - - - - - - 1500 - 1850 1900


200°0壳架
50° - - - - - - - - 1400 1500 1750 1850
55° - - - - - - - - 1300 1400 1650 1750
60° 600 - - - - - 1200 - 1200 1300 1550 1650

3200A frame

Ambient temperature 1600A 2000A 2500A 3200A


Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - - - -

45° - - - - 2450 - 3100 -

50° - - - - 2400 2450 3000 3100


55° - - - - 2350 2400 2900 3000
60° - - - - 2300 2350 2800 2900

4000A frame

Ambient temperature 3200A 3600A 4000A


Connection mode Horizontal Vertical Horizontal Vertical Horizontal Vertical
40° - - - - - -

45° 3100 - - - 3800 3850


2000壳架
50° 3000 3100 - - 3600 3650
55° 2900 3000 3400 3450 3400 3450
60° 2800 2900 3200 3250 3200 3250

6300A frame

Ambient temperature 4000A 5000A 6300A


Connection mode Horizontal Horizontal Horizontal
40° - - -
45° - - -
50° - - 5600
55° - 4800 5400
60° - 4800 5200

Note: “-” refers to no capacity derating.


P-025 Air Circuit Breaker Functions and features

Altitude capacity derating factor

Altitude height (m) 2000 3000 4000 5000


Rated impulse withstand voltage (kV) Uimp 12 10 8.57 7.5
Average insulation grade (V) Ui 1000 833 714 625
Maximal operational voltage (V) 50/60HZ Ue 690 580 500 415
Average heat operational current(40)℃ 1.0 0.88 0.78 contact with factory

Power loss and input and output resistance


Power loss is the power loss of each pole measured at In, 50/60Hz. The input/output resistance is the DC resistance value of each pole
at the cold state.

Draw-out type Fixed type (W)


Frame size Rated current (A)
Power loss (W) Input/output resistance (μohm) Power loss (W) Input/output resistance (μohm)

400 30.5 63.6 15.6 32.4


630 75.7 63.6 38.6 32.4
800 99.1 51.6 54.1 28.2
1600A
1000 154.8 51.6 84.6 28.2
1250 241.9 51.6 132.2 28.2
1600 262.7 34.2 138.2 18.0
630 58.6 49.2 26.4 22.2
800 73.7 38.4 36.6 19.1
1000 115.2 38.4 57.2 19.1
2000A
1250 180 38.4 89.4 19.1
1600 294.9 38.4 146.5 19.1
2000 388.8 32.4 204.5 17.0
1600 127.2 16.6 60.1 7.8
2000 198.7 16.6 93.9 7.8
3200A
2500 310.5 16.6 146.7 7.8
3200 479.2 15.6 206.4 6.8
3200 435 14.1 239.6 7.8
4000A 3600 690.5 17.7 272.9 7.0
4000 852.5 17.7 337 7.0
4000 403.2 9.0 230.4 7.0
6300A 5000 630 9.0 360 7.0
6300 1000.2 8.8 571 6.4
Functions and features Air Circuit Breaker P-026

Dimension of busbar
Bolt configuration

Type of bolt Application Fastening busbar

16: M10 Fastening busbar (36~52)N·m


20~63: M12 Fastening busbar (61~94)N·m
16~63:M3 Fastening secondary connector (0.4~0.5)N.m

Hole size and installation twisting moment of busbar

DrillingΦ(mm) Diameter of bolt Fastening twisting moment

N
16:Φ11 M10 (36~52)N·m
20~63:Φ13 M12 (61~94)N·m

Connection busbar specification reference under different temperature

Maximum permissible temperature of busbar: 100℃


The material of busbar is bare copper

Ambient temperature(-45~40)°C Ambient temperature 50°C Ambient temperature 60°C


Rated
Frame 5mm thick busbar 10mm thick busbar 5mm thick busbar 10mm thick busbar 5mm thick busbar 10mm thick busbar
current
(A) Number Number Number Number Number Number
Specification Specification Specification Specification Specification Specification
of pieces of pieces of pieces of pieces of pieces of pieces
400 2 50*5 1 50*10 2 50*5 1 50*10 2 50*5 1 50*10
630 2 50*5 1 50*10 2 50*5 1 50*10 2 50*5 1 50*10
800 2 50*5 1 50*10 2 50*5 1 50*10 2 50*5 1 50*10
1600A
1000 3 50*5 2 50*10 3 50*5 2 50*10 3 50*5 2 50*10
1250 4 50*5 2 50*10 4 50*5 2 50*10 4 50*5 2 50*10
1600 4 50*5 2 50*10 4 50*5 2 50*10 4 50*5 2 50*10
630 2 50*5 1 50*10 2 50*5 1 50*10 2 60*5 1 60*10
800 2 50*5 1 50*10 2 50*5 1 50*10 2 60*5 1 60*10
1000 3 50*5 2 50*10 3 50*5 2 50*10 3 60*5 2 50*10
2000A
1250 3 60*5 2 50*10 3 60*5 2 50*10 3 60*5 2 50*10
1600 4 60*5 2 60*10 4 60*5 2 60*10 4 60*5 2 60*10
2000 6 60*5 3 60*10 6 60*5 3 60*10 6 60*5 3 60*10
1600 2 100*5 1 100*10 2 100*5 1 100*10 2 100*5 1 100*10
2000 4 100*5 2 100*10 4 100*5 2 100*10 4 100*5 2 100*10
3200A
2500 4 100*5 2 100*10 4 100*5 2 100*10 4 100*5 2 100*10
3200 8 100*5 4 100*10 8 100*5 4 100*10 8 100*5 4 100*10
3200 8 100*5 4 100*10 8 100*5 4 100*10 8 100*5 4 100*10
4000A 3600 7 120*5 3 120*12 7 120*5 3 120*12 7 120*5 3 120*12
4000 8 120*5 4 120*10 8 120*5 4 125*10 8 125*5 4 125*10
4000 12 100*5 6 100*10 12 100*5 6 100*10 14 100*5 7 100*10
6300A 5000 14 100*5 7 100*10 14 100*5 7 100*10 16 100*5 8 100*10
6300 16 100*5 8 100*10 16 100*5 8 100*10 18 100*5 9 100*10

Note:
a. When a copper bar selected by users is not matched with a wiring terminal of the circuit breaker, extended busbar is required to be designed
to transfer, and is designed by the users of their own. The cross section of the extended busbar cannot be less than the requirement in the table
above. The interval among the extended busbar is not less than the interval among wiring terminals of the circuit breaker.
b. After the busbar recommended in the table above is installed, the electric clearance between adjacent phases of the circuit breaker is not less
than 18mm.
c. Electrical elements are used for three-phase rectification and high-frequency inversion, such as a high-frequency induction heating furnace
(medium-frequency furnace steelmaking equipment), a solid high-frequency welding machine (such as an embedded arc electric welding
machine), vacuum heating smelting equipment (such as a monocrystalline silicon growth furnace), in load equipment by controlled silicon.
When a circuit breaker is selected, the influence on the circuit breaker by higher order harmonic component generated by controlled silicon is
required to be considered besides the influences by the environment temperature and altitude height. At the same time, capacity derating
is required, and the capacity coefficient (0.5-0.8) is recommended.
d. The electric clearance of fastening bolts of upper and lower busbar needs to be not less than 20mm after the installation of the busbar by users.
e. After the installation of the circuit breaker, the safety clearance among electrified bodies with different electric potential and between the
electrified bodies and the ground are not less than 18mm.
P-027 Air Circuit Breaker Functions and features

Selective protection between NM8 and NXA


Selective protection between NM8 and NXA Frame size rated current NXA16 NXA20

Rated current(A) 400 630 800 1000 1250 1600 630 800

Default setting
ratings of short 3.2 5.04 6.4 8 10 12.8 5.04 6.4
Upstream time-delay 8In(kA)
Downstream Setting ratings(kA) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

Delayed tripping
0.1,0.2,0.3,0.4
time (s)

Returnable time 0.05,0.14,0.25,0.33

Frame size Rated Instantaneous


rated current current(A) setting ratings(kA)

0.16 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8


16
0.19(Motor) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

0.2 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8


20
0.24(Motor) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

0.25 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8


25
0.30(Motor) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

0.32 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8


32
0.38(Motor) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

NM8-100 0.4 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8
40
NM8S-100 0.48(Motor) 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

0.5 0.8~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8


50
0.60(Motor) 0.828~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

0.63 0.869~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8


63
0.75(Motor) 1.035~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8

0.8 1.104~4 1.26~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.26~6.3 1.6~8


80
0.96(Motor) 1.325~4 1.324~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.324~6.3 1.6~8

1 1.380~4 1.380~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.380~6.3 1.6~8


100
1.20(Motor) 1.656~4 1.656~6.3 1.656~8 2~10 2.5~12.5 3.2~16 1.656~6.3 1.656~8

1 1.380~4 1.380~6.3 1.6~8 2~10 2.5~12.5 3.2~16 1.380~6.3 1.6~8


100
1.20(Motor) 1.656~4 1.656~6.3 1.656~8 2~10 2.5~12.5 3.2~16 1.656~6.3 1.656~8

1.25 1.725~4 1.725~6.3 1.725~8 2~10 2.5~12.5 3.2~16 1.725~6.3 1.725~8


125
1.5(Motor) 2.070~4 2.070~6.3 2.070~8 2.070~10 2.5~12.5 3.2~16 2.070~6.3 2.070~8

1.6 2.208~4 2.208~6.3 2.208~8 2.208~10 2.5~12.5 3.2~16 2.208~6.3 2.208~8


160
1.92(Motor) 2.650~4 2.649~6.3 2.649~8 2.649~10 2.649~12.5 3.2~16 2.649~6.3 2.649~8

NM8-250 1.8 2.484~4 2.484~6.3 2.484~8 2.484~10 2.500~12.5 3.2~16 2.484~6.3 2.484~8
180
NM8S-250 2.16(Motor) 2.981~4 2.980~6.3 2.980~8 2.980~10 2.980~12.5 3.2~16 2.980~6.3 2.980~8

2 2.760~4 2.760~6.3 2.760~8 2.760~10 2.760~12.5 3.2~16 2.760~6.3 2.760~8


200
2.4(Motor) 3.312~4 3.312~6.3 3.312~8 3.312~10 3.312~12.5 3.312 ~16 3.312~6.3 3.312~8

2.25 3.105~4 3.105~6.3 3.105~8 3.105~10 3.105~12.5 3.200~16 3.105~6.3 3.105~8


225
2.7(Motor) 3.726~4 3.726~6.3 3.726~8 3.726~10 3.726~12.5 3.720~16 3.726~6.3 3.726~8

2.5 3.450~4 3.450~6.3 3.450~8 3.450~10 3.450~12.5 3.450~16 3.450~6.3 3.450~8


250
3.0(Motor) / 4.140~6.3 4.140~8 4.140~10 4.140~12.5 4.140~16 4.140~6.3 4.140~8

2.5 3.450~4 3.450~6.3 3.450~8 3.450~10 3.450~12.5 3.450~16 3.450~6.3 3.450~8


250
3.0(Motor) / 4.140~6.3 4.140~8 4.140~10 4.140~12.5 4.140~16 4.140~6.3 4.140~8

3.15 / 4.347~6.3 4.347~8 4.347~10 4.347~12.5 4.347~16 4.347~6.3 4.347~8


315
3.78(Motor) / 5.216~6.3 5.216~8 5.216~10 5.216~12.5 5.216~16 5.216~6.3 5.216~8

NM8-630 3.5 / 4.830~6.3 4.830~8 4.830~10 4.830~12.5 4.830~16 4.830~6.3 4.830~8


350
NM8S-630 4.2(Motor) / 5.796~6.3 5.796~8 5.796~10 5.796~12.5 5.796~16 5.796~6.3 5.796~8

4 / 5.520~6.3 5.520~8 5.520~10 5.520~12.5 5.520~16 5.520~6.3 5.520~8


400
4.8(Motor) / / 6.624~8 6.624~10 6.624~12.5 6.624~16 / 6.624~8

5 / / 6.900~8 6.900~10 6.900~12.5 6.900~16 / 6.900~8


500
6.0(Motor) / / / 8.280~10 8.280~12.5 8.280~16 / /

6.3 / / / 8.694~10 8.694~12.5 8.694~16 / /


630
7.56(Motor) / / / / 10.43~12.5 10.43~16 / /

7 / / / 9.660~10 9.660~12.5 9.660~16 / /


700
8.4(Motor) / / / / 11.59~12.5 11.59~16 / /

NM8-1250 8 / / / / 11.04~12.5 11.04~16 / /


800
NM8S-1250 9.6(Motor) / / / / / 13.24~16 / /

10 / / / / / 13.80~16 / /
1000
12(Motor) / / / / / / / /

12.5 / / / / / / / /
1250
15.0(Motor) / / / / / / / /
Functions and features Air Circuit Breaker P-028

NXA20 NXA32 NXA40 NXA63

1000 1250 1600 2000 1600 2000 2500 3200 3200 3600 4000 4000 5000 6300

8 10 12.8 16 12.8 16 20 25.6 25.6 28.8 32 32 40 50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10

2~10

2~10
2.5~12.5

2.5~12.5

2.5~12.5
3.2~16

3.2~16

3.2~16
4~20

4~20

4~20
3.2~16

3.2~16

3.2~16
4~20

4~20

4~20
5~25

5~25

5~25
6.4~32

6.4~32

6.4~32
6.4~32

6.4~32

6.4~32
7.2~36

7.2~36

7.2~36
8~40

8~40

8~40
8~40

8~40

8~40
10~50

10~50

10~50
12.6~50

12.6~50

12.6~50
N
2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2.070~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2.208~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2.649~10 2.649~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2.484~10 2.5~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2.980~10 2.980~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

2.760~10 2.760~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

3.312~10 3.312~12.5 3.312~16 4~20 3.312~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

3.105~10 3.105~12.5 3.2~16 4~20 3.2~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

3.726~10 3.726~12.5 3.726~16 4~20 3.726~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

3.450~10 3.450~12.5 3.450~16 4~20 3.450~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

4.140~10 4.140~12.5 4.140~16 4.140~20 4.140~16 4.140~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

3.450~10 3.450~12.5 3.450~16 4~20 3.450~16 4~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

4.140~10 4.140~12.5 4.140~16 4.140~20 4.140~16 4.140~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

4.347~10 4.347~12.5 4.347~16 4.347~20 4.347~16 4.347~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

5.216~10 5.216~12.5 5.216~16 5.216~20 5.216~16 5.216~20 5.216~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

4.830~10 4.830~12.5 4.830~16 4.830~20 4.830~16 4.830~20 5~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

5.796~10 5.796~12.5 5.796~16 5.796~20 5.796~16 5.796~20 5.796~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

5.520~10 5.520~12.5 5.520~16 5.520~20 5.520~16 5.520~20 5.520~25 6.4~32 6.4~32 7.2~36 8~40 8~40 10~50 12.6~50

6.624~10 6.624~12.5 6.624~16 6.624~20 6.624~16 6.624~20 6.624~25 6.624~32 6.624~32 7.2~36 8~40 8~40 10~50 12.6~50

6.900~10 6.900~12.5 6.900~16 6.900~20 6.900~16 6.900~20 6.900~25 6.900~32 6.900~32 7.2~36 8~40 8~40 10~50 12.6~50

8.280~10 8.280~12.5 8.280~16 8.280~20 8.28~16 8.280~20 8.280~25 8.280~32 8.280~32 8.280~36 8.280~40 8.280~40 10~50 12.6~50

8.694~10 8.694~12.5 8.694~16 8.694~20 8.694~16 8.694~20 8.694~25 8.694~32 8.694~32 8.694~36 8.694~40 8.694~40 10~50 12.6~50

/ 10.43~12.5 10.43~16 10.43~20 10.43~16 10.43~20 10.43~25 10.43~32 10.43~32 10.43~36 10.43~40 10.43~40 10.43~50 12.6~50

9.660~10 9.660~12.5 9.660~16 9.660~20 9.660~16 9.660~20 9.660~25 9.660~32 9.660~32 9.660~36 9.660~40 9.660~40 10~50 12.6~50

/ 11.59~12.5 11.59~16 11.59~20 11.59~16 11.59~20 11.59~25 11.59~32 11.59~32 11.59~36 11.59~40 11.59~40 11.59~50 12.6~50

/ 11.04~12.5 11.04~16 11.04~20 11.04~16 11.04~20 11.04~25 11.04~32 11.04~32 11.04~36 11.04~40 11.04~40 11.04~50 12.6~50

/ / 13.24~16 13.24~20 13.24~16 13.24~20 13.24~25 13.24~32 13.24~32 13.24~36 13.24~40 13.24~40 13.24~50 13.24~50

/ / 13.80~16 13.80~20 13.80~16 13.80~20 13.80~25 13.80~32 13.80~32 13.80~36 13.80~40 13.80~40 13.80~50 13.8~50

/ / / 16.56~20 / 16.56~20 16.56~25 16.56~32 16.56~32 16.56~36 16.56~40 16.56~40 16.56~50 16.56~50

/ / / 17.25~20 / 17.25~20 17.25~25 17.25~32 17.25~32 17.25~36 17.25~40 17.25~40 17.25~50 17.25~50

/ / / / / / 20.70~25 20.70~32 20.70~32 20.70~36 20.70~40 20.70~40 20.70~50 20.70~50


P-029 Air Circuit Breaker Installation and wiring

Dimensions and installation


1600A fixed type

Front view Side view

Datum Y Inside of cabinet gate


105 105
B

N
137.5

RESET

A
318.5

Datum X

H
OFF ON

89
143.5
137.5

50.5
127 42 100 92.5
237(Three pole) 243.5
254(Three pole) F 87

307(Four pole)
324(Four pole)

Hole size

Hole size of the base Hole size of a panel


Datum Y
220 8×Φ4

F
10

4× 7 Datum Y
120
100

285

118.5
L
322

L1 Datum X

Schematic diagram of the overall size of the bottom surface


and the installation hole pitch

Installation plate
of the
circuit breaker

H L L1 Remark
5 237 254 In=400A~630A Fixed type, three pole 258
8 237 254 In=800A~1250A Fixed type, three pole
20 237 254 In=1600A Fixed type, three pole Hole size of the panel of the fixed type circuit breaker

5 307 324 In=400A~630A Fixed type, four pole


8 307 324 In=800A~1250A Fixed type, four pole
20 307 324 In=1600A Fixed type, four pole
Installation and wiring Air Circuit Breaker P-030

Horizontal connection

Side view Busbar size and busbar interval

A
Datum Y
45
N
8× 11

12.5
N pole 25

35.5
70 70 70

Datum Y
Datum Y

95 95 95 95 95

60 60 8×Ф13
6×Ф13
14
14

90

28
90

28

70 70 70 70 70

(Optional) (Optional)

Number of busbar

Number of pieces
"Rated current(A)" Three poles Four poles
A pole+C pole B pole A pole+B pole C pole+N pole
400~630 4 2 4 4
800~1250 4 2 4 4
1600 8 4 8 8
P-031 Air Circuit Breaker Installation and wiring

1600A draw-out type

Front view Side view

Datum Y Inside of cabinet gate


105 105

137.5
RESET

Datum X

H
351

OFF ON

89
137.5
176.5

83.5
连接
试验
分离

154 79.5 164 78


308(Three pole) 331.5(Connected position)
378(Four pole) 380.5(Disconnected position)
73
F

Hole size

Hole size of the base Hole size of a panel


Datum Y
220 10×Φ4
Datum Y
F
4× 8.5
118
164
224

Datum X
40

120

320

143.5
L
L1

Schematic diagram of the overall size of the


bottom surface and the installation hole pitch Installation plate
of the
118

circuit breaker

H L L1 Remark
5

5 287 308 In=400A~630A Three pole


8 287 308 In=800A~1250A Three pole 258

20 287 308 In=1600A Three pole


Ratio: 1:1.5 Hole size of a panel of the draw-out type circuit breaker
5 357 378 In=400A~630A Four pole

8 357 378 In=800A~1250A Four pole


20 357 378 In=1600A Four pole
Installation and wiring Air Circuit Breaker P-032

Horizontal connection

Side view Busbar size and interval

A Datum Y

N
45

26.5
12.5
8× 11 25
N pole

70 70 70

Datum Y Datum Y

95 95 95
95 95
60 8×Ф13
60 6×Ф13
14
14

28
81

28
81

70 70 70 70 70

Optional Optional

Number of busbar

Number of pieces
"Rated current(A)" Three poles Four poles
A pole+C pole B pole A pole+B pole C pole+N pole
400~630 4 2 4 4
800~1250 4 2 4 4
1600 8 4 8 8
P-033 Air Circuit Breaker Installation and wiring

2000A fixed type

Front view Side view

Datum Y Inside of cabinet gate

237
200
RESET

128.5
R
A

OFF ON
D
Datum X

H
112
128.5
150
163

55
292
F
192 (Threepole) 182 26.5
287(Fourpole) 42 219.5 82

67

Hole size

Hole size of the base Hole size of a panel

Datum Y
Datum Y
69.5
233

311
150

270

Datum X

4 × 12

302 Installation plate


171(Threepole) 171
of the
F
266(Fourpole) circuit breaker
28.5

4
Φ

Schematic diagram of the overall size of the


bottom surface and the installation hole pitch
172.5
345

Hole of the panel

H Remark
10 In=630A
15 In=800A~1600A
20 In=2000A
Installation and wiring Air Circuit Breaker P-034

Horizontal connection

Side view Busbar size and interval

A
Datum Y 60
N

17
N pole 8× 13
.
28

42
95 95 95

A
16×Φ13
N pole 30 60
14
60

30

N pole
115

40
95 95 95 86
17

horizontal connection Lengthen busbar


32×Φ13 28
60

95 95 95

L type vertical connection


P-035 Air Circuit Breaker Installation and wiring

2000A draw-out type

Front view Side view

Datum Y Inside of cabinet gate

45

239
200
RESET

128.5
A
OFF ON

Datum X
D

H112
128.5
150
199.5

Disconnected
position

92
292 379.5 31
430
201.5(Three pole) 201.5
296.5(Four pole) F 41

Hole size

Datum Y
Hole size of the base Hole size of a panel

Datum Y

11 17
33

11

156
175

303
273

Datum X
379

11
14
17

302
66

16

132.5(Three pole) 132.5 Installation


plate of the
47

227.5(Four pole) F circuit breaker


20

Schematic diagram of the overall size of the


Φ
×

172.5
11

bottom surface and the installation hole pitch Right outermost side
345 of the circuit breaker
201.5

Hole of the panel


H Remark
10 In=630A
15 In=800A~1600A

20 In=2000A
Installation and wiring Air Circuit Breaker P-036

Horizontal connection

Side view Busbar size and interval

A
N pole

13.5
N

30
60 Datum Y
28 8× 13

39.5
95 95 95

A
16×Φ13
N pole 30 60
14
60

30

N pole
115

40
95 95 95 92.5
17

horizontal connection Lengthen busbar 28


32×Φ13
60
95 95 95

L type vertical connection


P-037 Air Circuit Breaker Installation and wiring

3200A fixed type

Front view Side view

Inside of cabinet gate


Datum Y

237
200
RESET

A
128.5
R

H
OFF ON

Datum X

112
128.5

150

163

55
26.5
352
42 219.5 82
227(Three pole) 212
F 67
342(Four pole)

Hole size

Hole size of the base Hole of the panel

Datum Y Datum Y
69.5
233

311

Datum X
270
150

4× 12

362 Installation
panel of the
F circuit breaker
28.5

201(Three pole) 201


4
Φ

316(Four pole)
202.5

405
Schematic diagram of the overall size of the
bottom surface and the installation hole pitch Horizontal connection

H Remark
20 In=1600A~2500A
30 In=3200A
Installation and wiring Air Circuit Breaker P-038

Horizontal connection

Side view Busbar size and interval

A
16×Φ13
40 86

15
N极

72

40
115 115 115 96

Horizontal onnection (default configuration)

D
A
N pole
50 12×Φ13 Datum Y 86
17
39.5

N Pole 115 115 115


115

40

Horizontal short busbar


15

32×Φ13 40
86
115 115 115

L type vertical connection


P-039 Air Circuit Breaker Installation and wiring

3200A draw-out type(Default configuration)

Front view Side view

Datum Y Inside of cabinet gate


45

239
200
RESET

128.5
R

H0
OFF ON

Datum X

112
128.5

150

Disconnected
199.5

position

92
连接 退 进

试验

分离 抽出断路器前请拔出手柄

352 349 31
231.5(Three pole) 231.5
399.5
346.5(Four pole) F
41

3200A draw-out type(Horizontal short busbar)

Front view Side view

Datum Y Inside of cabinet gate


45

N
239
200

RESET

A
128.5

H1

R
H0

Datum X
OFF ON
112
128.5

150

Disconnected
199.5

position
92

连接 退 进

试验

分离 抽出断路器前请拔出手柄

352 349 31
231.5(Three pole) 231.5
399.5
346.5(Four pole) F
41
Installation and wiring Air Circuit Breaker P-040

Hole size

Hole size of the base Hole size of a panel

Datum Y
Datum Y 362
33

17
11

156
11
175

303
273
Datum X

379
N
11

3.5
14
17

66

20 47 16
Installation
162.5(Threepole) 162.5 panel of the
circuit breaker
F
277.5(Fourpole)

4
Φ
×
11
Schematic diagram of the overall size of the 405
bottom surface and the installation hole pitch

Hole of the panel

H0 H1 Remark
20 0 In=1600A~2500A
30 10+0.1
0 In=3200A

Horizontal connection

Busbar size and interval


Side view

N Pole A
16×Φ13
90 50 100
25
100

50

120 125 125 92.5

Horizontal connection(Default configuration)

N Pole
A
Datum Y
75
30

16×Φ13 100
25
14
39.5

N Pole
115

40
17

125 125 125 32×Φ13 40


100
Horizontal short busbar
120 125 125

L type vertical connection


P-041 Air Circuit Breaker Installation and wiring

4000A fixed type

Front view Side view

Inside of cabinet gate

Datum Y

237
200
RE SE T A

128.5
R

OF F ON
Datum X

H
100
128.5

150
163

67
282.5(Three pole) 26.5
267.5
42 213.5 82
432.5(Four pole)
F
67

Hole size

Hole size of the base Hole size of a panel

Datum Y Datum Y
378
8×Φ4

4× 12

Datum X
311
240
150

270
26.5

F
28.5

255.5(Three pole) 419 Installation panel


of the circuit breaker
282.5(Three pole) 267.5
405.5(Four pole) 255.5
432.5(Four pole)

Schematic diagram of the overall size of the Ratio 1:2 Hole size of the panel of the fixed type circuit breaker
bottom surface and the installation hole pitch

H Remark
16 In=3200A
20 In=3600A~4000A
Installation and wiring Air Circuit Breaker P-042

Horizontal connection

Side view Busbar size and interval

Datum Y
A
120

N
90
N pole 30 16× 11

17
39.5
150 150 150
P-043 Air Circuit Breaker Installation and wiring

4000A draw-out type

Front view Side view

Datum Y Inside of the cabinet gate

A
N 45

200
RESET

128.5

+0.1
R

10 0
438.5

OFF ON
Datum X

H
Disconnected

100±0.2
position
128.5

150

10+0.1
199.5

0
98.5
284.5(Three pole) 284.5 366 31
416
434.5(Four pole)
461

F
41

Hole size

Hole size of the base


Hole size of a panel

2×11×17 Datum Y
378
Datum Y
11×Φ4
11
33

156
303
273
175

Datum X
379
3.5

14
47 16
66

215 215 419 Installation panel


20

of the circuit breaker


365(Four pole) F

Schematic diagram of the overall size of the


bottom surface and the installation hole pitch
Ratio 1:1 Hole size of the panel of the draw-out type circuit breaker

H Remark
26 In=3200A
30 In=3600~4000A
Installation and wiring Air Circuit Breaker P-044

Horizontal connection

Side view Busbar size and interval

Datum Y
120
A 90
N pole 16× 11

37
N
30

14

28
150 150 150
P-045 Air Circuit Breaker Installation and wiring

6300A fixed type

Front view Side view

DatumY Inside of the cabinet gate

237
200
128.5
RESET

30
OFF ON
DatumX
释能

112
128.5

163
150

55
352
219.5 26.5
441
897 67

F 82

Hole size

Hole size of the base Hole size of panel

Datum Y
362

DatumY
69.5

Datum X
311
270
233

150

4×Φ12

F
860
28.5

8×Φ4 Installation panel of


the circuit breaker
405

Schematic diagram of the overall size of the bottom


surface and the installation hole pitch

Hole size of the panel of the fixed type circuit breaker


Installation and wiring Air Circuit Breaker P-046

Horizontal connection

Side view Busbar size and inter val

260 260
180 24×Φ15
260 DatumY
80

20

40
134
316.5 323.5

In=6300A

A
N
N pole 210 210
100 210 DatumY 155 28×Φ15
50 50 57.5 55

20

40
134
182.5 246.5 246.5

In=4000A~5000A(Four pole )

210 210
210 155 24×Φ15
DatumY
50 57.5 55
20

40
134

246.5 246.5

In=4000A~5000A(Three pole)
P-047 Air Circuit Breaker Installation and wiring

6300A draw-out type

Front view Side view

Inside of the cabinet gate


Datum Y

45
A

237
200
128.5

30
Datum X

112
128.5
Disconnected

150

199.5
position

92
31
454
41
923 500

Hole size

Hole size of the base Hole size of panel

Datum Y
362

2×12×17
156

Φ11
273

303
175

Datum X
Φ14
379
3.5
66

20 47 16

785
F

11×Φ4
Installation panel of
405 the circuit breaker

Hole size of the panel of the fixed type circuit breaker Hole size of the panel of the draw-out type circuit breaker
Installation and wiring Air Circuit Breaker P-048

Horizontal connection

Side view Busbar size and inter val

260 260
260 Datum Y 180 24×Φ15
80

20

40

100
113
316.5 323.5

In=6300A

A
N
N pole
100 210 210 210
28×Φ15
50 55 Datum Y

20
57.5

40
100
113
182.5 246.5 246.5

In=4000A~5000A (Four pole)

210 210 210


Datum Y 24×Φ15
55 57.5

20
40
100
113

246.5 246.5

In=4000A~5000A(Three pole)
P-049 Air Circuit Breaker Installation and wiring

External transformer (Neutral CT) (3P+N mode)


External transformer (Neutral CT) dimension

The installation overall dimension of an external N-phase transformer is as below when the controller is of 3P+N type.
The transformer is provided by the manufacturer. A connection copper bar and an installation support are manufactured by users.

35 4× 13
1 2

c
60

d
b
140
210
240

4 4- 10.5
1-Wiring panel 2-Busbar 3-Fixation panel 4-Transformer
30

3
Frame size a b c d
1600 45 20 40 88
a
170 2000 60 20 34 89
190
3200 80 20 35 110
4000 120 20 16 58
6300 80 20 35 110

4CT Type earth current transformer


Structural dimension of external earth current transformer (W type)

110 50

90 40

Color: White
29

S1 Lable S2 200
234.5

200

85
20

P1 4- 8.5

88 64
Installation and wiring Air Circuit Breaker P-050

CTB-2 Type earth current transformer


Structural dimension of external earth current transformer (W type)

25 50
100 2.75 22.2 7

7
14
23

23
55

16
72

52

7
32.25 35.5

4.8
17.35°

N
5

Undervoltage time delay controller Installation overall dimension of undervoltage time-delay controller
which is required to be plugged in the undervoltage time-delay tripper

98 15 37.5 10.5

2× 8.5
121.5

108
129

80

2× 4.5

84.5 30 81
P-051 Air Circuit Breaker Installation and wiring

Secondary circuit wiring


1600A frame
M/A type control unit

N A B C SB2 SB3

PE
-
2 4 6 8 10 12 14 16 18 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT

FU
SA
Processing
unit
AX Power supply of
a control loop

Q F X M
FU

1 3 5 7 9 11 13 15 17 19 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 57 XT
+ HL1 HL2 HL3 HL4

Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release release coil indication motor

AX auxiliary contact type


For user

Four groups of adapters (Default) Six groups of adapters

36 38 40 42 44 46 36 38 40 42 44 46 48 50 52

37 39 41 43 45 47 37 39 41 43 45 47 49 51 53

Q-Undervoltage release F-Shunt release X-Closing coil 25#~26#: External N-phase transformer input signal contacts. Conventional products are empty.
M-Charging motor SA-Limited XT-Wiring terminal When an external transformer is required to be attached for special order of users, they are external
AX-Auxiliary contact SB1-Emergency stop button transformer signal input contacts.
SB2-Tripping push button SB3-Closing push button HL1-Failure indication lamp 27#, 28#: Undervoltage release (Connected to the main circuit)
HL2-Charging indication lamp HL3-Tripping indication lamp 29#, 30#: Shunt release
HL4-Closing indication lamp FU-Fuse (6A) 31#, 32#: Closing coil
1#, 2#: Power supply of intelligent controller 33#, 34#: Charging indication
3#~5#: Tripping alarm contact (4-common point) 34#, 35#: Charging motor
6#, 9#: Auxiliary contact, normally open contact 36#~56#: Auxiliary contact
10#~11#: Empty Conventional products are four groups of adapters, and six groups of adapters can be provided(only for AC)
12#~19#: Empty for special order for users.
20#: PE line Note: The full line section is connected, and the dot line is connected
21#~24#: Empty by customers.
Installation and wiring Air Circuit Breaker P-052

1600A frame
P/H type control unit

Integrated circuit AC 220V

PSU-1
profibus DC 24V
24V
+ -
ST-DP NC
GND
D+D -

N
+ - DI0 DI1 DI2 DI3 DI4

Special shielded twisted pair DC 24V


Modbus-RTU RU-1
SB2 SB3
N A B C PE U NU AU BU C D01 D02 D03 D04
+ External
- Red transformer

2 4 6 8 10 12 15 17 19 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT

FU
Processing SA
unit AX Power supply of
a control loop

Q F X M
FU

1 3 5 7 9 11 13 14 16 18 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 55 XT
+ Green
-

Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release coil indication motor
release

AX auxiliary contact type


For user

H type intelligent controller with a programmable output contact


Four groups of adapters (Default) Six groups of adapters outputs in default: 12#, 13#: load 1 alarm, 12#, 14#: load 2 alarm,
12#,16#: tripping signal output, 12#, 18#: Closing signal output
36 38 40 42 44 46 36 38 40 42 44 46 48 50 52 P type intelligent controller with a programmable output contact
outputs in default: 12#, 13#: load 1 alarm, 12#, 14#: load C alarm,
12#, 16#: self-diagnosis alarm, 12#, 18#: failure tripping.
20#: PE line.
21#~24#: voltage display input signal contact
P/H type intelligent controller 21#:N-phase voltage signal
22#: A-phase voltage signal 23#:B-phase voltage signal,
24#: C- phase voltage signal
25#~26#: External N-phase transformer or external earth current
transformer input signal contacts. Conventional products are empty.
37 39 41 43 45 47 37 39 41 43 45 47 49 51 53
When an external transformer is required for special order for users,
they are external transformer signal input contacts.
27#, 28#: Undervoltage release (Connected to the main circuit)
29#, 30#: Shunt release
Q-Undervoltage release F-Shunt release 31#, 32#: Closing coil
X-Closing coil M-Charging motor 33#, 34#: Charging indication
SA-Limited switch XT-Wiring terminal AX-Auxiliary contact 34#, 35#: Charging motor
SB1-Emergency stop button SB2-Tripping push button 36#~56#: Auxiliary contact
SB3-Closing push button HL1-Failure indication lamp Conventional products are four groups of adapters, and six groups of
HL2-Charging indication lamp adapters can be provided for special order for users (only for AC).
HL3-Tripping indication lamp HL4-Closing indication lamp ST-DP: DP protocol module. When the upper computer
FU-Fuse (6A) PSU-1—power module communication protocol is Modbus-RTU, the ST-DP protocol module
1#, 2#: Power supply of intelligent controller is not required. When the upper computer communication protocol
3#~5#: Tripping alarm contact (4-common point) is Profibus-DP, the Modbus-RTU protocol module is required to be converted
6#~9#: Auxiliary contact, normally open contact into Profibus-DP protocol by the ST-DP protocol module, extra fee needed.
10#~11#: Defaulted communication output contact for a H type RU-1 :relay module. The circuit breaker is used for tripping and switching
intelligent controller. P type is empty via remote control, and is used for tripping and switching signal energy
12#~19#: Four groups of programmable output contacts amplification, extra fee needed.
12#:com, 18#:D01, 16#:D02, 14#D03, 13#D04 Note: The full line section is connected, and the dot line should be connected by customers.
P-053 Air Circuit Breaker Installation and wiring

2000-6300A frame
M/A type control unit

N A B C SB2 SB3

PE
-
2 4 6 8 10 12 14 16 18 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT

FU
Processing
SA
unit
AX AX
AX Power supply of
a control loop

Q F X M
FU

1 3 5 7 9 11 13 15 17 19 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 57 XT
+ HL1 HL2 HL3 HL4

Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release release coil indication motor

AX auxiliary contact type


For user

Four groups of adapters (Default) Five groups of adapters Three-open three-closed auxiliary contact Q-Undervoltage release F-Shunt release X-Closing coil
M-Charging motor SA-Limited switch XT-Wiring terminal
36 38 40 42 44 46 36 38 40 42 44 46 48 50 36 38 40 42 44 46 AX-Auxiliary contact SB1-Emergency stop button SB2-Tripping push button
SB3-Closing push button HL1-Failure indication lamp
HL2-Charging indication lamp HL3-Tripping indication lamp
HL4-Closing indication lamp FU-Fuse (6A)
1#, 2#: Power supply of intelligent controller
3#~5#: Tripping alarm contact (4-common point)
6#~9#: Auxiliary contact, normally open contact
10#~11#: Empty
12#~19#: Empty
20#: PE line
37 39 41 43 45 47 37 39 41 43 45 47 49 37 39 41 43 45 47
21#~24#: Empty
25#~26#: External N-phase input signal contacts.

Four-open four-closed auxiliary contact Five-open five-closed auxiliary contact Conventional products are empty. When an external transformer is
required to be attached for special order of users, they are external

36 38 40 44 46 48 50 36 38 40 44 46 48 50 52 54
transformer signal input contacts.
42 42
27#, 28#: Undervoltage release (Connected to the main circuit or connedted
to the output of the undervoltage delay module)
29#, 30#: Shunt release
31#, 32#: Closing coil
33#, 34#: Charging indication
34#, 35#: Charging motor
36#~56#: Auxiliary contact
Conventional products are four groups of adapters.
The three-open three-closed auxiliary contact, the four-open four-closed
37 39 41 43 45 47 49 51 37 39 41 43 45 47 49 51 53 55 auxiliary contact, the five-open five-closed auxiliary contact, and five
groups of adapters can be provided for the special order for users.
Note: 1. the full line section is connected, and the dot line should be
Six-open Six-closed auxiliary contact connected by customers.
Note: 2. when the voltages of the controller of the 2000-4000 frame
6 8 36 38 40 42 44 46 48 50 52 54
are AC 230V/AC 400V, the controller can be directly connected to
1#, 2#terminals. When the voltage is DC 220V/DC 110V, the controller
can be connected to 1#, 2# terminals after the power supply module
outputs DC 24V.

7 9 37 39 41 43 45 47 49 51 53 55
Installation and wiring Air Circuit Breaker P-054

2000-6300A frame
P/H type control unit

Integrated circuit
AC 220V
PSU-1
profibus DC 24V
24V
ST-DP + -
NC
GND
D+ D-

+ - DI0 DI1 DI2 DI3 DI4

Special shielded twisted pair DC 24V


Modbus-RTU
RU-1
SB2 SB3
N A B C PE U NU AU BU C D01 D02 D03 D04
+ External
- Red transformer

2 4 6 8 10 12 15 17 19 20 22 24 26 27 29 31 34 36 38 40 42 44 46 48 50 52 54 56 XT
N
FU
Processing SA
unit
AX AX
AX
Power supply of
a control loop

Q F X M
FU

1 3 5 7 9 11 13 14 16 18 21 23 25 28 30 32 33 35 37 39 41 43 45 47 49 51 53 55 XT
+ Green
-

Under-
Shunt closing Charging Charging
Main circuit Intelligent controller voltage Auxiliary switch
release coil indication motor
release

AX auxiliary contact type


For user

Five groups of adapters


Four groups of adapters (Default) Three-open three-closed auxiliary contact

Q-Undervoltage release F-Shunt release X-Closing coil


36 38 40 42 44 46 36 38 40 42 44 46 48 50 36 38 40 42 44 46
M-Charging motor SA-Limited switch XT-Wiring terminal
AX-Auxiliary contact SB1-Emergency stop button SB2-Tripping push button
SB3-Closing push button HL1-Failure indication lamp
HL2-Charging indication lamp HL3-Tripping indication lamp
HL4-Closing indication lamp FU-Fuse (6A) PSU-1—power module
1#, 2#: Power supply of intelligent controller
3#~5#: Tripping alarm contact (4-common point)
6#~9#: Auxiliary contact, normally open contact
10#~11#: Defaulted communication output contact for a H type intelligent controller.
37 39 41 43 45 47 37 39 41 43 45 47 49 37 39 41 43 45 47 P type is empty
12#~19#: Four groups of programmable output contacts
12#:com, 18 #:D01,16 #:D02,14 #D03,13 #D04
Four-open four-closed auxiliary contact Five-open five-closed auxiliary contact H type intelligent controller with a programmable output contact outputs in default:
12#, 13#: load 1 alarm, 12#, 14#: load 2 alarm, 12#,16#: tripping signal output,
36 38 40 42 44 46 48 50 36 38 40 42 44 46 48 50 52 54 12#, 18#: switching signal output.
P type intelligent controller with a programmable output contact outputs in default:
12#, 13#: load 1 alarm, 12#, 14#: load C alarm, 12#,16#: self-diagnosis alarm,
12#, 18#: failure tripping.
20#: PE line.

Conventional products are four groups of adapters. The three-open three-closed auxiliary
contact, the four-open four-closed auxiliary contact, the five-open five-closed auxiliary
contact, and five groups of adapters can be provided for the special order for users.
37 39 41 43 45 47 49 51 37 39 41 43 45 47 49 51 53 55 ST-DP: DP protocol module. When the upper computer communication protocol
is Modbus-RTU, the ST-DP protocol module is not required. When the upper computer
communication protocol is Profibus-DP, the Modbus-RTU protocol module is
21#~24#: voltage display input signal contact required to be converted into Profibus-DP protocol by the ST-DP protocol module, extra
P/H type intelligent controller fee needed.
21#: N-phase voltage signal, 22#: A-phase voltage signal RU-1: relay module. The circuit breaker is used for breaking and making via remote
23#: B-phase voltage signal, 24#: C- phase voltage signal control, and is used for breaking and making signal energy amplification, extra fee needed.
25#~26#: External N-phase transformer or external earthing Note: 1. the full line section is connected, and the dot line should be connected by
current transformer input signal contacts. customers.
Conventional products are empty. When an external transformer Note: 2. when the voltages of the controller of the 2000-4000 frame are AC 230V/AC 400V,
is required for special order for users, they are external transformer the controller can be directly connected to 1#, 2#terminals.
signal input contacts. When the voltage is DC 220V/DC 110V, the controller can be connected to
27#, 28#: Undervoltage release (Connected to the main circuit or connedted to the output of 1#, 2# terminals after the power supply module outputs DC 24V.
the undervoltage delay module)
29#, 30#: Shunt release, 31#, 32#: Closing coil, 33#, 34#: Charging indication
34#, 35#: Charging motor, 36#~56#: Auxiliary contact
P-055 Air Circuit Breaker Installation and wiring

Chassis position indicator device


Wiring diagram

Position indication

Disconnected Test Connected


indication indication indication

55 57 58 60 61 63

Power supply

56 59 62

Operation requirements:
1. The chassis indication device can indicate the positions including "disconnected" ,"test" and "connected"which are completely or partially used
according to the requirements of order.
2. When the body of the draw-out type circuit breaker is pushed from the "disconnected" position to the "test" position, 55# and 56# terminals should be transferred
from connection into disconnection, and 56# and 57# terminals should be transferred from disconnection to connection.
3. When the body of the draw-out type circuit breaker is pushed from the "disconnected" position to the "test" position, 58# and 59# terminals should be transferred
from connection into disconnection, and 59# and 60# terminals should be transferred from disconnection to connection. There is sufficient safety distance
between the bus of the circuit breaker body and a bridge-type contact of the safety shutter, and tripping and switching operation can be carried out reliably.
4. When the body of the draw-out type circuit breaker is switched from the "test" position to the "connected" position, NXA16 type secondary circuit has no clearance.
The NXA20-63 type safety shutter swing continuously after sending out the ‘"cracking" sound, and the safety shutter jiggle handle rotates within 1.5 circles.
61# and 62# terminals are being transferred from connection to disconnection. 62# and 63# terminals are transferred from disconnection to connection.
The busbar of circuit breaker body is required to be reliably inserted into the bridge-type contact of the chassis base, and reliably bear the main circuit current
to operate.
5. When the body of the draw-out type circuit breaker is pushed from the "connected" position to the "test" position, 58# and 59# terminals should be transferred
from connection into disconnection, and 59# and 60# terminals should be transferred from disconnection to connection. There is sufficient safety distance
between the busbar of the circuit breaker body and a bridge-type contact of the chassis, and tripping and switching operation can be carried out reliably.
6. When the body of the draw-out type circuit breaker swings from the "test" position to the "disconnected" position, 55# and 56# terminals should be transferred from
connection to disconnection, and 56# and 57# terminals should be transferred from disconnection to connection, and at the same time, the circuit breaker
body still cannot be drawn out, and needs to swing toward the "disconnected" position until the handle cannot swing any more, and meanwhile, the circuit breaker
body can be drawn out. After the circuit breaker is pulled out, 55# and 56# terminals should be transferred from disconnection to connection,
and 56# and 57# terminals should be transferred from connection to disconnection.
7. In the position transfer operation process of the chassis, the operation can only be stopped when the indicator points to "disconnected", "test" and "conncected"
or the position indicator cannot display the position of the circuit breaker body in the chassis correctly.
8.The above terminal numbers are all position signal specific numbers (55#-63#), which are not compatible with secondary circuit terminal numbers.

Position signal contact capacity

Rated voltage (V) Rated heating current Ith(A) Rated operating current Ie(A) Rated control capacity

Ac230 5 1.3 300VA

Ac400
Interphase barrier 5 0.75 300VA
Annex I: Configuration Air Circuit Breaker P-056

1600A frame 2000A frame 3200A frame 4000A frame 6300A frame
Standard configuration
Fixed type draw-out type Fixed type draw-out type Fixed type draw-out type Fixed type draw-out type Fixed type draw-out type

Circuit breaker body ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪


Chassis ▪ ▪ ▪ ▪ ▪
Intelligent controller ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Vertical and horizontal connection ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 4CO ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Failure tripping indication contact ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Motor operating mechanism ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Closing coil ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Shunt release ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Door frame ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪

Optional accessories
1600A frame
Fixed type draw-out type
2000A frame
Fixed type draw-out type
3200A frame
Fixed type draw-out type
4000A frame
Fixed type draw-out type
6300A frame
Fixed type draw-out type
N
Standard undervoltage release ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Adjustable time-delay undervoltage unit
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Pushbutton lock
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
"Disconnected" position padlock
▪ ▪ ▪ ▪ ▪
Safety shutters padlock
▪ ▪ ▪ ▪ ▪
Body lock
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Position door interlock ▪ ▪ ▪ ▪ ▪
State door interlock ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 6CO
▪ ▪
ON/OFF indication contact 5NO + 5NC
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 3NO + 3NC
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 4NO+4NC
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
ON/OFF indication contact 5CO
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
"Connected", "Disconnected" and "test"
position indication contact ▪ ▪ ▪ ▪ ▪
Mechanical interlock ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Source-changeover controller
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
External transformer (Neutral CT) ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Earth current transformer and
accessories thereof
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Interphase barrier ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Triple mechanical interlock
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
P-057 Air Circuit Breaker Annex Ⅱ: Selection table

Frame size 1600A 2000A 3200A 4000A 6300A


Circuit breaker N□ S□ H □ N□ S□ H□ N□ S□ H□ N□ S□ H□ H□
400A □ 630A □ 1600A □ 3200A □ 4000A □
630A □ 800A □ 2000A □ 3600A □ 5000A □
800A □ 1000A □ 2500A □ 4000A □ 6300A □
Rated current
1000A □ 1250A □ 3200A □
1250A □ 1600A □
1600A □ 2000A □
Number of poles 3 pole □ 4 pole □ (While In=6300A,no four poles)
Installation modes Horizontal draw-out □ Fixed and horizontal □

Intelligent controller M type □ A type □ P type □ H type □


AC110V □ AC220/230/240V □ AC 380/400/415V □ DC110V □ DC220V □
AC110V □ AC220/230/240V □ AC 380/400/415V □ Order V□

helped&instantaneous □ helped&delay (Inm≥2000A ,delay time:1s,3s,5s, non-adjustable). □


Under-voltage release
self-priming&instantaneous □ self-priming&delay (Inm≥2000A,delay time:0.3~7.5s, adjustable) □
(no DC)( Optional)
Note:NXA16 don't have helped type, delay time:1s,3s,5s,7s, non-adjustable. □

shunt release (default AC 110V □ AC220/230/240V □ AC380/400/415V □


Electric accessories Intermittent (only for Inm≥2000A,
(no AC110V for NXA16) in motor operation) DC110V □ DC220V □
by default in motor operation)□

closed electromagnet pulse (must select pulse type in the AC110V □ AC220/230/240V □ AC380/400/415V □
(default in motor operation)
automatic control system) □ DC110V □ DC220V □

Motor AC110V □ AC220/230/240V □ AC380/400/415V □ DC110V □ DC220V □

NXA16: C04□ C06□ (C06 only for AC)


Auxiliary contact
NXA20~63: N3□ N4□ N5□ C03□ C04□ C05□

Connection accessories Interphase barrise □

External transformer: Earth current transformer □ External transformer (Neutral CT) □


Controller accessories 1)
(Match) Note: Neutral CT is only applicable to 3P+N
2)
The earth current transformer should be selected when customers select earth current return type earthing protection.

Lock mechanism Pushbutton lock □ Safety shutters padlock □ Body lock □ One-lock one-key □ Two-locks one-key □
(Match) Three-locks two-keys □ "Disconnected" position padlock □ Door interlock (Body) □ Door interlock (chassis) □
Mechanical interlock
MI-3(2on+1off) □ MI-4(1on+2off) □ ILK2 □
(Match)

Source-changeover
1 "Normal" and 1 "Replacement" □ 2 "Incoming" and 1 "Busbar" □
controller (Match)
Annex Ⅲ: Earth fault protection Air Circuit Breaker P-058

Earth protection

There are two protected modes for metal single-phase earth fault, namely vector sum(T) and earth current(W).Type-T detects zero
sequence current and four-phase current vector(three-phase four-wire system) or three-phase current vector(three-phase three-wire
system) will be added to provide reference for earth protection. Type-W detects earthing cable current directly by special external
transformer. Type-W can protect both stages of breaker at the same time. Distance between the transformer and breaker should be
no more than 5m. Zone interlocking can be used in the condition of vector sum earth fault.
a.correlation setting parameters of earth protection

Parameter Names Setting range Setting step size Remarks


OFF+(0.2~1.0)×In (Frame NXA16/NXA20, Max= 1200A)
Set value of action current Ig 1A
OFF+(500A~1200A) (Frame NXA32/NXA40/NXA63)

delay time Tg (0.1~0.4)S 0.1s

1.At least one way of DO should be set


as “Zone Interlocking” or “earth Interlocking”
Signal unit options must be S2 or S3
When DI/DO is set as zone interlocking ,
it effects “Earth Zone Interlocking”
N
Zone interlocking of earth fault
and “Short Zone Interlocking”
(for T-type earth fault) (ZSI) 2.At least one way of DI should be set
When DI/DO is set as earth interlocking,
as “Zone Interlocking” or “earth Interlocking”
it only effects “earth Zone Interlocking”.
If the function isn’t set, it has no effect.

b. Operating characteristic of earth protection

Characteristic I/Ig Tripping time Permissible error


Non-operating characteristic <0.9 Non-operate
Operation characteristic >1.1 Operate
Time-delay operation ≥1.1 Note ±15% or inherent absolute error±40ms(choose the max value)

Note: The delay time of earth fault is divided into two stages, inverse time and definite time. When fault current is less than 1.0In or 1200A,the protection is inverse, the time
delay is calculated as follow:
t=(1.0In or1200A/I)²×Tg
In this equation: t---action time
Tg --- setting delay time
I---fault earth current
P-059 Air Circuit Breaker Annex Ⅲ: Earth fault protection

When fault current is more than 1.0In or 1200A, the protection is definite; the time delay is the setting delay time.
c. Schematic Diagram of detection
Type-T

L1 Transformer
L1
L2 CT
L2 L1
L3 L2
L3
N L3
PEN
PE
intelligent
intelligent controller
controller intelligent
controller
N
Neutral pole CT

3P 4P 3P+N

Type-W

L1
L2
L3
N
CTB-2

intelligent
4CT controller

PE or
PEN

4CT:external special transformer CTB-2:earth current transformer module

Leakage protection (E)


Leakage protection applies to leakage fault caused by insulation failure of equipment or human touching exposed electric conduction
position. Leakage tripping current I∆n is independent of breaker rated current. An extra rectangular transformer is needed for zero
sequence sampling method. This method is appropriate for small current protection because of its high accuracy and sensitivity.
a. correlation setting parameters of leakage protection

Parameter Names Setting range Setting step size


Set value of action current I∆n (0.5~30.0)A 0.1A
Delay time T∆n(S) Instantaneous,0.06,0.08,0.17,0.25,0.33,0.42,0.5,0.58,0.67,0.75,0.83
Operation mode Trip/Turn off

b .Operating characteristic of leakage protection

Characteristic I/I∆n Tripping time Permissible error


Non-operating characteristic <0.8 Non-operate
Operation characteristic >1.0 Operate
Time-delay operation ≥1.0 Shown in Table 18 ±10% (inherent absolute error±40ms)

Setting time(s) 0.06 0.08 0.17 0.25 0.33 0.42 0.5 0.58 0.67 0.75 0.83 Instantaneous
Multiple of Fault Current Maximum Breaking Time(s)
1 I∆n 0.36 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 0.04
2 I∆n 0.18 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 0.04
5 I∆n
0.072 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.04
10 I∆n
Annex Ⅲ: Earth fault protection Air Circuit Breaker P-060

c. Schematic Diagram of leakage protection

Transformer ZCT1 Transformer ZCT1


residualcurrenttransformer residualcurrenttransformer
CT CT
L1 L1

L2 L2

L3 L3

R
intelligent
controller intelligent
controller

N
ZCT1:rectangular leakage transformer (NXA16&NXA20-3P) ZCT1:rectangular leakage transformer(NXA16-4P)

Note: For Frame nxa16(3P&4P) and NXA20(3P) products, busbar can go through ZCT1, however,
not for Frame NXA20 4P and FrameNXA32/NXA40/NXA63.

Dual earth fault protection


NXA P/H type controller has a unique feature: the installation of two independent earth fault protection curves is permissible, so that two
kinds of configurations can be managed at the same time. The release can differentiate unlimited regional earth faults because of the
feature to command the NXA circuit breaker to trip and the limited regional earth fault to command the medium-voltage circuit breaker
to strip.

protection zone

NXA
P-061 Air Circuit Breaker Annex Ⅳ: Source-changeover controller

Functions of the controller


2A type display and operation

CD-1: A 2A type source-changeover system is used for the switch between power grids or between the power grid and generator.
When a normal power supply does not supply power normally, such as undervoltage, overvolgage, phase breaking, a spare power
supply is switched for supplying power. A mechanical interlock component is configured according to standard.

Automatic (The system judges the operateion automatically,


and the light is on when pressing the left upper part)

1 Manual (The mechanism is operated by a handle or with buttons


S1, S2 and OFF operation)
2
S1:load is powered by switching to S1, and the light is on when
Switch pressing S1 in the left upper part.
operation
zone S2: load is powered by switching to S2, and the light is on when
pressing S2 in the left upper part.

Disconnection: S1, S2 are stripped, and the system load is not powered

3 Pressing anyone of buttons S1, S2 and OFF under the automatic


condition, the system becomes manual, and corresponding operation
is carried out when pressing corresponding buttons.

2A type of functions

The controller has the following functions Truth table


1. Dual-circuit voltage detection display
S1-circuit power supply S2-circuit power supply
2. Overvoltage threshold value adjustment: 400V-480V
1 0
3. Undervoltage threshold value adjustment: 280V-360V 0 0
4. Adjustment of T1, T2, T3 and T4: 0.5-64S with the step size of 0.5S 0 1
5. Undervoltage and overvoltage fault indication
6. Power supply fault indication
7. State indication of the circuit breaker
8. Self-input and self-reset or self-input and self-reset selection
9. Manual or automatic selection
10. Comprehensive alarm for transfer failure (fault of the circuit breaker,
sending fault of control signals and unmet transfer conditions)
11. All primary adjustment states after resetting and before defaulting
12. Alarm contact
13. Unloading contact
14. Startup contact of a power generator
15. Standard configuration
16. Mechanical interlock
17. The controller has an overvoltage protection function,
and operates normally with long-term overvoltage: 130% Ue.
Annex Ⅳ: Source-changeover controller Air Circuit Breaker P-062

3A type display and operation


CD-1 A 3A source-changeover system is applicable to a power supplying system with two power supplies and one buscouple.
In the manual operation process, load cannot lead to power interruption, so that the safety running level and the power supplying
continuity for power distribution are enhanced. The 3A automatic power supply conversion system is applied to electric places.

Automatic (The system judges the operateion automatically, and the light
is on when pressing the left upper part)

Manual (The mechanism is operated by a handle or with buttons S1, S2,


S1 & S2, S1&TIE, S2&TIE and OFF operation)

S1: load is powered by switching to S1, the TIE buscouple is tripped, and
the light is on at the left upper part when pressing S1. N
1 S2: load is powered by switching to S2, the TIE buscouple is tripped, and
the light is on at the left upper part when pressing S2.
2 Switch
S1 & S2:Load is powered by S1 & S2, TIE buscouple is tripped; the light is
operation
on at the left upper part when pressing S1 & S2.
zone
S1&TIE: Load is powered by S1, TIE buscouple is tripped; the light is on at
the left upper part when pressing S1&TIE

S2&TIE: Load is powered by S2, TIE buscouple is tripped; the light is on at


the left upper part when pressing S2&TIE
3
Disconnection: S1,S2 and TIE are all stripped, and the system load is not powered.

Pressing anyone of buttons S1, S2 S1 & S2, S1&TIE, S2&TIE under the
automatic condition, the system becomes manual, and corresponding
operation is carried out when pressing corresponding buttons.

3A type functions

The controller has the following functions Truth table


1. Dual-circuit voltage detection display
S1-circuit power supply TIE buscouple S2-circuit power supply
2. Overvoltage threshold value adjustment: 400V-480V
1 0 1
3. Undervoltage threshold value adjustment: 280V-360V 1 1 0
4. Adjustment of T1, T2, T3 and T4: 0.5-64S with the step 0 1 1
size of 0.5S 1 0 0
5. Undervoltage and overvoltage fault indication 0 0 1
6. Power supply fault indication 0 0 0
7. State indication of the circuit breaker
8. Self-input and self-reset or self-input and self-reset selection
9. Manual or automatic selection
10. Comprehensive alarm for transfer failure (fault of the circuit breaker,
sending fault of control signals and unmet transfer conditions)
11. All primary adjustment states after resetting and before defaulting
12. Alarm contact
13. Unloading function
14. Standard configuration
15. Mechanical interlock
16. The controller has an overvoltage protection function,
and operates normally with long-term overvoltage: 130% Ue.
P-063 Air Circuit Breaker Note

Note
Note Air Circuit Breaker P-064