B974832002P00-480V 462-MCC-005
B974832002P00-480V 462-MCC-005
NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:
1. ALL FEEDER CABLES ARE CABLE TYPE PVCLA
EXCEPT AS INDICATED OTHERWISE
462-024-MCC-005 2. THIS DWG. MAY INCLUDE PROJECTS NOT YET EXISTING.
1200/5
FOR CONT. SEE 480V, 1200A, 3{, 3W, 60HZ, 42KAIC
3. ADDED SUMP PUMP MOTOR 462-GM-246A
DWG. BA-170183.002
A
NOTES FOR EWO-10S028:
A A A A A A A A A A A
PT
480-120V 1. EXISTING MCC#5 SHALL BE REPLACED WITH NEW
AS CPT
MCC AS SHOWN.
CPT CPT CPT CPT CPT CPT CPT CPT CPT CPT CPT
1 3 3 3 3 3 3 3 3 3 3 2 2. NEW MCC 462-024-MCC-005 SHALL BE
V VS A MANUFACTURED AS PER 16-SAMSS-503 AND IEC.
(0-600V) (0-1200A) SIM SIM SIM SIM SIM SIM SIM SIM SIM SIM SIM SIM 4. ALL EXISTING POWER AND CONTROL CABLES SHALL
C C C C C C C C C C C C BE TO RE-USED AND CONNECTED TO THE NEW
MOTOR CONTROL CENTER.
PC-4697
PROVIDE THE MOST COMPACT AND SPACE SAVING
PC-4691
DESIGN.
3/C#1 + 4/C#12
INTELLIGENT TYPE.
7/C#10
3/C#2 + 4/C#12
8. NEW MOTOR CONTROL CENTER SHALL BE OF
WITHDRAWABLE TYPE UNITS.
4/C#12 AWG
X-407 X-214 SHALL BE OF HORIZONTAL CONFIGURATION.
3/C#1 +
10. ALL OVERLOAD RELAYS WILL BE DIGITAL,
3/C#1 +
INTELLIGENT TYPE WITH COMMUNICATION CAPABILITIES.
4/C#12 AWG
00
J.B J.B J.B J.B J.B J.B J.B J.B J.B J.B J.B J.B
SYMBOLS
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
FOR STANDARD ELECTRICAL SYMBOLS SEE
PB PB PB PB PB PB PB PB PB PB PB PB STANDARD DRAWING AB-36766.
SS SS SS SS SS SS SS SS SS SS SS SS FOR SWITCHGEAR DEVICE FUNCTION NO.’S
0.5 50 50 50 50 50 50 50 50 50 40 20 SEE ELECTRICAL POWER MANUAL AES-P-116.02
CABINET
CABINET
CABINET
CABINET
CABINET
CABINET
CABINET
CABINET
CABINET
CABINET
CABINET
CABINET
462-EM-201C-1
462-EM-202C-1
462-GM-246-A
462-EM-202A-4
462-EM-201B-5
462-EM-201C-3
462-EM-211-AA
462-EM-211-BB
462-EM-211-CC
462-EM-211-Y
462-GM-217-C
462-EM-211-Z
JB JUNCTION BOX CABLE BUS 00
SUMP PUMP
00 SIMOCODE PROV OR START-STOP
SIM PB
EQUIVALENT SS PUSH BUTTON
R R R R R R R MOTOR STARTER
MCP MCP 250AF MCP 150AF MCP MCP MCP MCP
FOR CONT. SEE RIGHT ABOVE
MCP
150A G 100A G 225AT 30A 100AT 150A G 150A G 7A G 100A G 100A G 00
INDICATING LAMP
A A A A A A A
00 R - RED (PUMP OFF)
G - GREEN (PUMP ON)
A - AMBER (PUMP TRIPPED)
CPT CPT CPT CPT CPT CPT CPT
4 3 3 3 1 3 3
REFERENCE DRAWINGS
SIM SIM SIM SIM SIM SIM SIM
ONE LINE DIAGRAM 13.8/2.4/0.48KV
NA-500346
C C C C C C C SYSTEM
DD-121839-0
112.5KVA, 480-208/120V
3/C#2 + 4/C#12
7/C#10 LAYOUT
REVISION VALIDATION
J.B J.B J.B
THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
TO MARSHALLING
TO MARSHALLING
TO MARSHALLING
PB OC
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
RIL
16S028-001
PB PB PB
GIL
SS SS DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
SS
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)
60 5 100 2
CABINET
CABINET
CABINET
462-GM-219A
462-GM-208E
462-MOV-006
MAIN DISTR.
SPARE
SPARE
SPARE