THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.

NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:
1. ALL FEEDER CABLES ARE CABLE TYPE PVCLA
EXCEPT AS INDICATED OTHERWISE
462-024-MCC-005 2. THIS DWG. MAY INCLUDE PROJECTS NOT YET EXISTING.
1200/5
FOR CONT. SEE 480V, 1200A, 3{, 3W, 60HZ, 42KAIC
3. ADDED SUMP PUMP MOTOR 462-GM-246A
DWG. BA-170183.002

RELIER NOTE-7 (TYP.)

FOR CONT. SEE LEFT BELOW


R 4. INSTALL NEW SIZE 2 COMBINATION STARTOR
R R R R R R R R R R R
UNIT WITH DRAWOUT, OPERATOR MECH. 100AF/50AT
MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP
BREAKER, WIRING AND TERMINAL BLOCK AT EMPTY
7A G 150A G 150A G 150A G 150A G 150A G 150A G 150A G 150A G 150A G 100A G 50A G CUBICLE 3RC.

A
NOTES FOR EWO-10S028:
A A A A A A A A A A A
PT
480-120V 1. EXISTING MCC#5 SHALL BE REPLACED WITH NEW
AS CPT
MCC AS SHOWN.

CPT CPT CPT CPT CPT CPT CPT CPT CPT CPT CPT
1 3 3 3 3 3 3 3 3 3 3 2 2. NEW MCC 462-024-MCC-005 SHALL BE
V VS A MANUFACTURED AS PER 16-SAMSS-503 AND IEC.

(0-600V) (0-1200A) SIM SIM SIM SIM SIM SIM SIM SIM SIM SIM SIM SIM 4. ALL EXISTING POWER AND CONTROL CABLES SHALL
C C C C C C C C C C C C BE TO RE-USED AND CONNECTED TO THE NEW
MOTOR CONTROL CENTER.

5. ALL EXISTING POWER AND CONTROL CABLES SHALL


BE SPLICED AS REQUIRED FOR THE NEW
INSTALLATION.
X-519 X-502 X-503 X-504 X-505 X-506 X-507 XX X-509 X-510 XX
6. THE MOTOR CONTROL CENTER VENDOR SHALL

PC-4697
PROVIDE THE MOST COMPACT AND SPACE SAVING

PC-4691
DESIGN.

7. NEW MOTOR CONTROL CENTER SHALL BE

3/C#1 + 4/C#12
INTELLIGENT TYPE.

7/C#10

3/C#2 + 4/C#12
8. NEW MOTOR CONTROL CENTER SHALL BE OF
WITHDRAWABLE TYPE UNITS.

9. NEW MOTOR CONTROL CENTER SWITCHING ASSEMBLIES


00

4/C#12 AWG
X-407 X-214 SHALL BE OF HORIZONTAL CONFIGURATION.

3/C#1 +
10. ALL OVERLOAD RELAYS WILL BE DIGITAL,
3/C#1 +
INTELLIGENT TYPE WITH COMMUNICATION CAPABILITIES.
4/C#12 AWG

11. CABLE BUS SHALL BE USED FOR INCOMING CABLE.

00

J.B J.B J.B J.B J.B J.B J.B J.B J.B J.B J.B J.B
SYMBOLS
TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

TO MARSHALLING
FOR STANDARD ELECTRICAL SYMBOLS SEE
PB PB PB PB PB PB PB PB PB PB PB PB STANDARD DRAWING AB-36766.
SS SS SS SS SS SS SS SS SS SS SS SS FOR SWITCHGEAR DEVICE FUNCTION NO.’S
0.5 50 50 50 50 50 50 50 50 50 40 20 SEE ELECTRICAL POWER MANUAL AES-P-116.02
CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET

CABINET
462-EM-201C-1

462-EM-202C-1

462-GM-246-A
462-EM-202A-4
462-EM-201B-5

462-EM-201C-3
462-EM-211-AA

462-EM-211-BB

462-EM-211-CC
462-EM-211-Y
462-GM-217-C

462-EM-211-Z
JB JUNCTION BOX CABLE BUS 00

SUMP PUMP
00 SIMOCODE PROV OR START-STOP
SIM PB
EQUIVALENT SS PUSH BUTTON

OPEN-CLOSE TAG NO. OF THE


PB X-201 CABLE TO
PUSH BUTTON
OC REMAIN AS IT IS
HAND-OFF-AUTO START/STOP
HOA PB
SELECTOR SWITCH PUSH BOTTON

CLOUDED PORTION INDICATE


SCOPE OF WORK UNDER EWO-16S028

480V, 1200A, 3{, 3W, 60HZ, 42KAIC

R R R R R R R MOTOR STARTER
MCP MCP 250AF MCP 150AF MCP MCP MCP MCP
FOR CONT. SEE RIGHT ABOVE

MCP
150A G 100A G 225AT 30A 100AT 150A G 150A G 7A G 100A G 100A G 00

INDICATING LAMP
A A A A A A A
00 R - RED (PUMP OFF)
G - GREEN (PUMP ON)
A - AMBER (PUMP TRIPPED)
CPT CPT CPT CPT CPT CPT CPT
4 3 3 3 1 3 3

REFERENCE DRAWINGS
SIM SIM SIM SIM SIM SIM SIM
ONE LINE DIAGRAM 13.8/2.4/0.48KV
NA-500346
C C C C C C C SYSTEM

ONE LINE DIAGRAM 2.4KV SWGR. BUS 1 NA-500544

ONE LINE DIAGRAM 480V MCC #1-3 NA-500490

00 ONE LINE DIAGRAM 480V MCC 004, 006-007 BA-974832


X-513 X-517 X-514 X-518 X-520
EQUIPMENT LAYOUT SUB #24 NA-648785

CABLE SCHED. MCC #1 & #2 SH. 2 & 3 NB-648836

DWG. CONTROL SHT. (EWO-57232) DD-312017-0


3/C#2/0 + 4/C#12

DWG. CONTROL SHT. (EWO-56781)


3/C#6 + 4/C#12
C-3

DD-121839-0
112.5KVA, 480-208/120V

DRAWING CONTROL J.O-37280 BD-226614


3/C#2/0 + 4/C#12

POWER, CONTROL, LIGHTING, & GROUNDING


BA-226694
TRANSFORMER #7

3/C#2 + 4/C#12

7/C#10 LAYOUT

BLOCK DIAGRAM SH-2 BA-226699

CABLE & CONDUIT SCH. SH.80-83 PLT-462 DD-873562

DRAWING CONTROL J.O. 10-00332 BD-142757

DRAWING CONTROL EWO-16S028 BD-974808


00
CABLE AND CONDUIT SCHEDULE BD-974831
C-6

REVISION VALIDATION
J.B J.B J.B
THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
TO MARSHALLING

TO MARSHALLING

TO MARSHALLING

PB OC
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

RIL
16S028-001
PB PB PB
GIL
SS SS DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
SS
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)
60 5 100 2
CABINET

CABINET

CABINET

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

OSL/SFA KHP/MAJ FAR


04/16/18 04/16/18 04/16/18
462-EM-204-E

462-GM-219A
462-GM-208E
462-MOV-006
MAIN DISTR.

REV.NO. DATE REVISION DESCRIPTION


PANEL ’C’

00 04/16/18 ISSUED FOR CONSTRUCTION


SPARE

SPARE

SPARE
SPARE

JOB ORDER/EWO NO.


F-201A

THIS REVISION IS NOT TO BE USED FOR


30 KW

16S028 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE

ONE LINE DIAGRAM E1L

480V 462-MCC-005 SUBSTATION #24


COMPRESSION & DEETH’ING PLANT ABQ

ABQAIQ SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

CONFIDENTIAL - downloaded by alhaah0y on 6/16/2022


462 P BA-974832 002 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05