Clean Room Design Book Rev10
Clean Room Design Book Rev10
INDEX
PROLOGUE (P.4)
I .- INTRODUCTION (P18)
II .- INTERNATIONAL STANDARDS FOR CLEAN ROOMS (P.47)
III .- THE DESIGN OF CLEAN ROOMS FOR THE MICROELECTRONICS
INDUSTRY (P.62)
IV .- THE DESIGN OF CLEAN ROOMS FOR THE PHARMACEUTICAL INDUSTRY
(P.79)
V .- PHARMACEUTICAL INDUSTRY VALIDATION AND QUALIFICATION (P.108)
VI .- CLEAM ROOM CRITICAL PATIENTS UNIT (UPC) (P.122)
VII .- GENERAL HISTORY OF INFECTIOUS AND IMMUNODEPRESSED
ISOLATES (P.136)
VIII .- FLUID MECHANICS CONCEPTS APPLIED TO CLEAN ROOM (P.149)
IX .- DEVELOPMENT OF P&ID INSTRUMENTATION DIAGRAMS IN CLEAN
ROOMS (P.179)
X .- CONTROL SEQUENCES FOR CLEAN ROOM HVAC SYSTEMS (P.201)
XI .- VAV AND CAV AIR SYSTEMS (P.230)
XII .- HOSPITAL HVAC DESIGN (P.238)
XIII .- CONDENSATION SYSTEMS FOR CLEAN ROOM HVAC SYSTEMS (P.288)
XIV . -ADVANCED AIR HANDLING UNIT SYSTEMS CONFIGURATIONS (P.348)
XV .- ANALYSIS OF CONTROL SYSTEMS FOR HANDLING UNITS IN TROPICAL
AREAS (P.387)
XVI .- UTAS CONFIGURATIONS FOR PHARMACEUTICAL APPLICATIONS (P.405)
XVII .- CONCLUSIONS (P.422)
CLEAN ROOM APPLICATION VIDEOS (P.432)
UMAS SELECTION SOFTWARE
Dedication
It is difficult to generate a special dedication, because many names come to mind, which were part
of my training, but starting with my grandmother Amanda for the love she gave me when I was little.
To my parents for the patience they had when I lived with them.
To my wife Andrea for the love and the wait of not being able to dedicate time to the family,
especially my two children, who sometimes do not understand what goes through their father's head.
But there are two people to whom I want to mention in a very special way, my dear mother-in-law,
who always gave me her support in the most difficult moments of life.
But there is a man who inserted me into this mysterious world of Air Conditioning, my friend and
first Boss, Mr. Rubén Cespedes, who I was lucky enough to work with twice. I always remember the
three months I was in training at his company and he taught me more than a teacher, more like a
father.
And finally, I hope it serves all those who are future generations, my dear grandson, Tomas Tapia
Sánchez, who knows that since he was born he has been my constant concern.
Celso Tapia
FOREWORD
In 1945 the need to test filters in gas masks against particles and biological
materials led to the development of counters for particles dispersed in the
environment. The final step, the development of the HEPA filter, took place at
SANDIA laboratories for the Atomic Energy Commission after World War II.
Nuclear particles that would have been fatal to personnel were isolated in
process areas with HEPA filters while allowing air to circulate through them.
Willis Whitfield pioneered the field of cleaning to perform clean work in
confined spaces. Finally the space age with its cleanliness requirements
promoted pollution control technology. In the 60s, documents such as FED STD
209a, NASA SP-5045, “Contamination Control Handbook”, NASA SP-4074,
“Clean Room Technology”, NASA SP-5045, “contamination control principles”
and “AF-TO-” were written. 00-25-203, “Contamination control of aerospace
facilities, US Air Force.” These documents contain principles that are still
relevant today. ISO/TC209 14644-1 is the international designation for
cleanroom cleanliness and incorporates the metric units used in other parts of the
world. Therefore, it is essential to have a certified air conditioning and
ventilation system that guarantees a safe environment for the patient, workers
and visitors.
Among the sites that require greater precision, calculation, evaluation and strict
control of environmental conditions within the HVAC sector is the
pharmaceutical industry. Extraction equipment, ducts, filters, diffusers, among
other systems, must be chosen carefully and based on the elements established
by the applicable regulations, so that the processes are optimal, the products are
of quality, and the personnel remains safe. .
The pharmaceutical industry is one of the sectors that requires the strictest air
controls in the indoor environment of production areas. The IPSE Regulations
establish the minimum requirements that must be met in the manufacturing
process of medicines marketed in the country, in addition to the specifications
that some products require, such as specific conditions of temperature, humidity
and air quality to be manufactured.
HVAC systems within the pharmaceutical industry are considered critical, as are
purified water and compressed air systems, because they are in direct contact
with the product. Each laboratory has defined methods to carry out the so-called
“good manufacturing practices” (GMP) throughout the production process,
which sometimes usually exceed the minimum requirements of the standard. In
this way, HVAC systems are not exempt from rigorous monitoring and
mandatory requirements when carrying out system validation.
Design
Deciding which HVAC system is correct when designing and installing depends
largely on how the production areas will be classified, which is done based on
the type of medication that you want to manufacture. Basically, there are two
groups of medications: sterile and non-sterile. For each group, the IPSE
standard, in its appendix A (normative), classifies production areas according to
the degree of asepsis necessary for their manufacturing.
Within the group of sterile medications, we can find, among others, all injectable
medications. In the group of non-sterile medications, there are, as
pharmaceutical forms, tablets, capsules, syrups, suspensions, emulsions,
ointments, creams, gels, among others.
The engineer in charge of designing the HVAC system within this industry must
carry out a preliminary investigation, focused on the type of medication that is to
be manufactured and the classification that corresponds to the area where
production is to be carried out, before beginning to develop calculations or
estimates; This will help select the equipment needed to integrate the system.
In itself, the correct design of the HVAC system is of utmost importance; first,
because it must comply with what is specified in current regulations; second,
because, when the equipment is finally installed, the system itself should not
generate cross contamination, and third, because within the air handling units
and within the ducts there should be no growth of fungi, yeast, bacteria or any
other type. of contamination that compromises the quality of the product or the
safety of personnel.
Cross contamination is one of the most important aspects to avoid in the
pharmaceutical industry. All manufacturing procedures, from receiving raw
materials to obtaining the final product, are designed to avoid cross
contamination; Even the architecture of the plant is designed to meet the same
objective.
Precision . Exact temperature, pressure and humidity ranges are vital to the
result.
One of the most common questions that arise when starting to design the critical
HVAC system for pharmaceutical production areas is determining whether or
not the air that is supplied to the areas can be returned. Logically, it is known
that by returning a certain amount of air, quite considerable energy savings are
achieved. Unfortunately, returns are not always allowed, although, if the same
product is manufactured within the areas and high volume dust is not produced,
it is possible to return it. However, if the products
In the case of ISO-8 class, they must have at least 95% efficiency filters and for
ISO-9 class they must have at least 85% efficiency filters.
The terminal filters mentioned in the standard for ISO classes 5, 6 and 7, in
addition to the efficiency already defined, must have an airtight cabinet, and the
accessories must be installed in a way that facilitates the integrity tests carried
out on the filters. filtered periodically by the validation department. It is
advisable that the filter have a gel seal on its perimeter to achieve airtightness
between the filter and the cabinet; This will provide an acceptable particle count.
The integrity tests carried out on the HEPA terminal filters, with 99.97 percent
efficiency, are done to guarantee that the filters are not broken or have
manufacturing defects. As particle counting in ISO-5 class is continuous during
the applied filling process for injectable medicines, it is of utmost importance to
ensure that the filters trap contaminating particles on their surface.
Within the components of the HVAC system, such as air handlers, air filters
must also be placed in stages; commonly there are three. An air handler that will
serve an ISO-Class 8 production area for non-sterile medications will have
pleated filters with 35 percent efficiency in the first stage; This is to prevent the
accumulation of dust inside the unit and to serve as a protector for the next
filtering stage. In the second filtering stage, filters with 65 to 70 percent
efficiency are usually placed as pre-filters, which will help protect the third
stage, which will finally give the 95 percent efficiency required by the standard.
Some laboratories sometimes require 99.97 percent efficient HEPA filters to be
installed in the third stage, instead of one of the
95 percent; this, in order to guarantee a particle count much lower than the
minimum specified by the standard; therefore, the 95 percent filter is placed in
the second stage. This is also allowed by the authorities.
During extractions, care must be taken to ensure that the air discharged into the
atmosphere does not contain medication residues. For this, the air must be
filtered with an efficiency similar to that of injection to avoid, as already
mentioned, the passage of contaminants into the environment.
It is necessary to remember that there is a very varied number of medications
that can be toxic, such as hormonal ones, which can cause considerable effects
on the human body if subjected to prolonged exposure. It is important to
mention that the extraction discharge ducts and dust collectors must be
constantly monitored through easily accessible sampling ports.
Filters should be changed according to a validated maintenance schedule. There
must be a standard operating procedure that defines how and when it should be
carried out. The standard requires that differential pressure gauges be installed in
all equipment that contains filters, whose reading must be recorded weekly to
prevent the filters from collapsing if they are too saturated. Dirty filters should
not be thrown away; They must be removed carefully, without shaking them, to
finally take them to confinement.
air changes
The calculation of the amount of air to be supplied must be carried out
respecting the air changes per hour specified in the standard.
INTRODUCTION
The clean room is a modern phenomenon. Although the roots of clean design and
management go back more than 100 years and are rooted in infection control in hospitals, the
need for a clean environment for industrial manufacturing is a requirement of modern society.
The use of clean rooms is diverse and shown in Table 1.1 is a selection of products that are
now being made clean rooms, or that require pollution control facilities. It can be seen that the
clean room requirement can be broadly divided into two. The first is that inanimate particles
are a problem and where their presence, even in submicron sizes, can prevent a product from
functioning or reduce its useful life. The second group requires the absence of particles
carrying microorganisms whose growth in the product (or in a hospitalized patient) could lead
to human infection. It can also be seen that many of the examples given are recent innovations
and this list will certainly be added to in the future, with there being a considerable increase in
demand for these types of rooms.
Table 1.1
Electronics Computers LCD screens, LED screens
Semiconductors Production of integrated circuits used in computer memory
and control
FIGURE 1 .1. Hospital room ventilation in the 1920s. A patient can inhale fresh air from
the funnel. The dirty air on the ground was extracted through another funnel.
Similar advances were being made in the engineering industries. The development of the first
clean rooms for industrial manufacturing largely began during World War II in the United
States and the United Kingdom primarily in an attempt to improve the quality and reliability
of instrumentation used in weapons, tanks and aircraft.
It was warned that the cleanliness of the production environment had to be improved or items
such as pump sights and precision bearings would malfunction. At that time clean rooms were
built that copied the design and practices of the operating room. Anyway, it was soon realized
that "bacteria-free" was not the same as "particle-free."
Therefore, great effort was made to ensure that materials and surfaces did not generate
particles, but it was not fully appreciated that the dispersion into the air of large quantities of
particles by machines and people had to be removed by large quantities of air. pure.
Table 1.2.a. Limit class according to US Federal Standard 209E for clean rooms
For example, a class 100,000 clean room limits the concentration of air particles equal to or
greater than 0.5 microns to 100,000 particles in a cubic foot of air, in the English system the
class indicates the number of particles per cubic foot.
where:
Cn =Maximum permitted number of particles per cubic meter equal to or greater than the
specified particle size, rounded to the nearest whole number.
N =It is the ISO class number, which must be a multiple of 0.1 and must be 9 or less.
D = is the particle size in micrometers.
Application Considerations
Hospitals. Clean rooms in hospitals are essential for controlling bacteria that can cause
infections in patients undergoing therapy or recovery. Hospital infections are among the top
ten causes of death in the United States. The minimum purity of the air entering the
operating room is 95%, with a particle filter of up to 0.3 microns. A filter suitable for a
surgery room costs around USD 250, and a surgery room requires a bank of filters, (33%
pre-filter and 66% or 95% filter).
Pharmaceutical industry.
The two most used standards concerning clean rooms for the pharmaceutical industry are
the European Union Guide to Good Manufacturing Practice (EU
Figure 2. Flow Lines in Clean Rooms (a) unidirectional and (b) non-unidirectional
3) Terminal Air Filters – High-efficiency filters used in clean rooms are installed at air
discharge points in the room. In air conditioning systems used in offices, etc. The filters will be
placed directly after the ventilation floor, but particles can be induced into the air supply ducts
or leave the duct surfaces and therefore pass into the room.
4) Room pressurization and passage grilles – To ensure that air does not pass from adjacent
dirtier areas into the clean room, the clean room is positively pressurized with respect to these
dirtier areas. This is done by extracting less air from the room than it is supplied, or by
extracting the supplied air in zones. To achieve the correct pressure and allow designed air
movement from the cleanest to the least clean rooms in a suite, vents or dampers are usually
seen at a low level on walls or doors.
Another indication of a clean room is the type of surface finish. The room will be built with
materials that do not generate particles and are easy to clean. Surfaces will be constructed in
such a way that they are accessible for cleaning and do not harbor dirt in crevices, for example.
openwork floors and recessed lighting.
Cleanliness in the air of a conventionally ventilated clean room depends on the quantity and
quality of the air supplied to the room and the efficiency of the mixing of the air.
Table 4 Speed and changes per hour for clean rooms, N=non-unidirectional. U=
unidirectional.
Table 5. Pressure differential between clean rooms in wc= Inches water column. Pa=
Pascals
Recovery time. Recovery time is inversely proportional to the air exchange rate. The recovery
time of a higher class (say from ISO 8 to ISO 7) can be estimated using the following formula:
When time t increases and the system reaches steady state the final concentration simply
becomes:
ISO Class 1 1
w- 1 ISO Class 2 2 0
M1
1 N-~
ISO Class 3 3 1 c 0.035
10 M2 TSO Class 4 4 2 d 0.35
100 JVi •2 5 4000 3 L. F 3.5
ISO Class5
Wq-g
YO'
1000 ISO Class 6 6 — 4 G, Il 35
Ws 4
'YO •
10000 Ws e
ISO Class 7 7 400 000 5 J. 350
100 000 w- ISO Class 8 8 4 000 000 6 K 3500
Mf
ISO Class 9 7 YO..
A comparison of the classes given in some of these various standards, as well as the ISO/CEN
(European Committee for Standardization) standard, is shown in Table 8.
Class Limits
(J.
Yo p.m 0.2 um 0.3um 0.5um 5um
Class name Volume units Volume units Volume units Volume units Volume units
YEA English (m' (1-) (m3) (m) (m)) (ft 3 ) (m') (ft 3 ) (m3 (ft 3 )
H
) )
Ml 350 9.91 75.7 2.14 30.9 0.875 10.0 0.283 — —
Ml. 5 1 I 240 35.0 265 7.50 106 3.00 35.3 LOO - -or —
M2 3 500 99.1 757 2J.4 309 8.75 100 2.83 — —
M2.5 10 12 400 350 2650 75.0 1 060 30.0 353 10.0 — —
M3 35000 991 7570 214 3090 87.5 1 000 28.3 — —
M3.5 100 — — 26 500 750 10 600 300 3 530 100 — —
M4 — — 75700 2 140 30900 875 10 000 283 — —
M4.5 1000 — — — — — — 35 300 1 000 247 7.00
M5 — — — — — — 100 000 2 830 618 17.5
M5.5 10000 — —— -— — — — 353000 10000 2 470 70.0
• PIC: GMP and Guidelines 1995 Valid in European countries outside the EU and Australia.
• FDAcGMP, 1987 Valid for the United States.
•EUGGMP 1997 Valid for the EU area.
Table 11, Comparison of the main pharmacy GMP guidelines regarding working conditions and
classes (classification given according to FS 209E).
(a) To achieve B air grades, the number of air changes must be related to the size of the room and the
equipment, personnel present in the room. The air system must be provided with appropriate filters
such as HEPA for grade A
(b) At rest it should be received in the state without anyone entering the room, after the 15-20 minute
'cleaning' period.
(c) Appropriate alert and action limits should be established for particulate and microbiology results.
If these limits are exceeded, operating procedures must prescribe corrective action.
The maximum concentration of microorganisms that should be found in the different grades of clean
rooms in the operational state is given in Table 13.
Table 13, The values of the EU GMP Guide (1997) for microbiological monitoring in the
operational state, for the manufacture of sterile products.
The EU GMP guide does not provide information on how to measure microorganisms. Test methods
will be found in the upcoming ISO biocontamination control standards and IEST RP 023.
Manufacturing operations in the EU GMP guide are divided into two categories: those where the
preparation is sealed in its final container and terminally sterilized, and those that must be prepared
aseptically at some or all stages. The guide suggests the following use of clean rooms:
Terminally sterilized products
Degree Operation examples
d
Preparation of solutions and components for subsequent filling
Remarks : The preparation of most products should be carried out at least in grade D environment,
when there is unusual risk, grade C environment should be used.
Remarks: After washing, the components should be handled at least in D grade environment.
Handling of sterile starting material should normally be done (see GGMP) in a Grade A environment
with a Grade B background. The preparation of solutions that must be sterile filtered during the
process, must be done in a grade C environment; unfiltered, the preparation of materials and products
must be carried out in grade A environment with a grade B background. Handling and filling of
aseptically prepared products should be done in a Grade A environment with a Grade B background.
Preparation and filling of sterile ointments, creams, suspensions and emulsions should be done in a
Grade A environment, with a Grade B background, when the product is exposed and not subsequently
filtered. Special conditions are specified in the GGMP when insulators or blow-fill seal, where
machines are used.
Biological risks, and the measures directed at them, are classified into four classes. Four laboratories
are used with risk levels from BL 1 to BL 4 (see Table 14).
Table 14, The four BL 1-BL 4 classes of biosafety laboratories.
BL 1 Standard normal laboratory , Ordinary biochemistry laboratories, school and university laboratories
BL 2 Special training and routines to prevent laboratory infections . Diagnostic laboratories, Appropriate waste
management, Health laboratories
BL 3 Special laboratory with negative pressure, Special security laboratories, Air locks for people and materials
Tuberculosis laboratories, Autoclave in the room, All work carried out in a security cabinet, Special decontamination of
waste
BL 4 Special laboratories with total separation between humans, high-risk laboratories and microorganisms in all
aspects, negative pressure, sterilization
• Productswatery
• Productsfreeze-dried
• Productspowdered
Aqueous Preparation Preparation of injectables in water (or as an emulsion) falls into two
main areas, i.e. aseptic production and terminal product sterilization production. If the
product is thermostable, it will normally be terminally sterilized.
Oral products
These products include bottles containing liquids, as well as tablets and capsules. Oral
products are not normally sterilized, but depend on the quality of the raw materials and, in
the case of aqueous liquids and creams, preservatives are frequently added to prevent the
development of any bacterial contamination in the container.
Most of these products are also produced in closed systems where the raw material enters at
one end and the finished product exits at the other end.
ENVIRONMENTAL CLEANING
The correct quality of cleaning of the internal environment is generally the difficult
requirement to achieve and is determined by:
• Staff
• Process equipment
• Surfaces
The most important contaminant in a pharmaceutical clean room is bacteria and
most, if not all of these, come from the people in the room. It is therefore useful to know the
number of people expected to work in the premises, as this will have a direct impact, taking
into account the amount of air required to dilute and eliminate airborne dispersion of
contamination from their bodies. . The effectiveness of your clean room clothing will have a
direct relationship to the contamination dispersed by people in the room and hence the
amount of air.
The type of clothing will also influence the cooling load, as the more effective the clothing is
in preventing dispersion, the less air is exchanged through the clothing, therefore the warmer
the staff will be and are likely to be. requires lower ambient temperatures.
Process equipment is a major source of particulate contamination.
Cost effective design.
Cleanroom surfaces can be sources of contamination due to surface dislodgement caused by
lack of cleanliness and durability.
Entry through faulty HEPA filter systems
Within one-way devices and room air supply terminals, a HEPA filter is widely used.
These filters are unlikely to have such high particle removal,
such as those commonly used in the most demanding parts of the microelectronics industry.
The reason for this is threefold, firstly, bacteria
• Egg crate or perforated plate type that provides a downward jet of air flow.
• Various types of vane or swirl diffusers that provide good ambient air induction.
Fig.23 Clean zone of vertical flow over autoclave discharge and vial filling machine.
General ambient environment controlled by a conventional turbulent airflow system
with low level return air. Curtains raised to show the equipment.
These two types of air supply devices give air movement of the type shown in Figures 24
and 25. The perforated box, or discharge type device will produce a jet stream of air beneath
it. This stream of air will carry pollution around its edges, but overall the air quality under
the diffuser will be good. The blade type of device is designed to entrain room air and mix it
with the incoming supply air; The air quality throughout the room will therefore be
reasonably constant. Therefore, it may appear that it is better to install dump-type air devices
and place critical operations under them. However, conditions outside this area should be
poorer and it is not unusual to find critical operations moving away from the designed
position. It is therefore the authors' belief that the
Fig 27, Specialized isolator for the processing and handling of potent drugs.
TERMINAL
FILTERS
PRESSURE
LOW LEVEL
EXTRACT
AIR LEAKAGE
PATHS
Fig. 31 Airflow through the suite: (a) doors closed; (b) open door between filling room
and equipment and component preparation room; (c) Open door between filling room
and changing area.
1 Good Manufacturing Practice, 2 Design Qualification, 3 Installation Qualification, 4 Operational Qualification, 5 Process Execution Qualification
EMA GMP Guide to Good Manufacturing Practices parts 1 and II GMP requirements for medicines and active ingredients:
validated processes, continuous stability controls , risk
management
Annex 11 Computerized systems
ICH ICH, QiA Stability Testing of New Drug Substances and Products Harmonized directives for the USA. USA, Japan and the
European Union
ICH, Q7A
Good Manufacturing Practice Guide for Active Pharmaceutical Ingredients
PS/INF11/2015 GUIDE TO GOOD MANUFACTURING PRACTICE FOR MEDICINAL PRODUCTS Identical to Annex 15 of the European GMP
ANNEX 15
1
1
1
US GMP (Current Good Manufacturing Practice (cGMP)) USA They are contained in the
Code of Federal Regulations (Code of Federal Regulations) 21 CFR part 210 (drugs) and 21
CFR part 211 (active ingredients), so they are legally binding on manufacturers and
importers. The GMPs are subject to an annual review (hence they are current).
Similarly, in Europe there are also two EU GMP Guides. Part I is aimed at drug
manufacturers and part 2 at active ingredient manufacturers.
Part I of the European Union Good Manufacturing Practice Guide comprises 9 chapters that
formulate the basic requirements for quality control in the development and manufacturing
process, as well as in relation to personnel, premises and equipment and quality controls.
Another fundamental requirement of the two GMP Guides is the continuous performance of
stability controls on the active ingredients and finished medicines. These stability checks
can be carried out in climatic chambers from the company BINDER GmbH.
"The basic GMP requirements are as follows: (i) all manufacturing processes are clearly
defined, systematically reviewed based on experience gained, and capable of consistently
producing medicines of the quality required [...] (ii) critical steps in manufacturing
processes and significant process changes are validated."
Validation
Validation serves as a quality control method and is an important component of GMP. The
definition according to the European Union can be found in the EU GMP Guidelines:
"Obtaining evidence, in accordance with Good Manufacturing Practice, that any procedure,
process, equipment, material, activity or system actually produces the intended result (see
also qualification)."Guide to Good Manufacturing Practice, Part I
The FDA previously defined validation as:
Above all grading activities is the grading plan. In this, unlike the validation plan, the
qualification measures to be carried out are described in detail. The responsible persons are
defined, as well as the tests to be carried out and, together with the risk assessment, the
acceptance criteria are included, that is, the parameters to be verified, the critical
characteristics for quality and the operational situations. On the part of the authorities and
the GMP, no regulations have been established that indicate the scope of the qualification.
Each of the stages of the qualification must be authorized before starting and will end with
the recapitulation, in writing, of the results of the qualification in the corresponding reports.
It is common to group the plan and the qualification report in the same document.
Qualification stages
In the Design Qualification (DQ) phase, the specifications and specifications are prepared.
The DQ is composed, in turn, of the User Requirement Specification (URS), the Functional
Design Specification (FDS) and the Design Specification (DS).
}D}Q in detail: The URS or user specification describes the requirements that the
equipment or installation must meet. The user specification has
The Factory Acceptance Test (FAT) is carried out by the manufacturer, who provides
documentary evidence that the equipment or system has been manufactured and operates
according to its specifications. Once the FAT has been successfully carried out, the
equipment or system is delivered to the customer by the manufacturer, thus receiving the
delivery release. After delivery
The installation qualification (IQ) is documentary proof that the equipment or system has
been delivered without damage, complete and in accordance with the previously specified
documentation. After carrying out a visual inspection, the equipment or, where applicable,
the system, will be installed in accordance with the manufacturer's instructions.
Users will be duly instructed on its handling. During installation qualification, the sensors
will be calibrated and adjusted, if this was not done successfully during the plant acceptance
test.
All activities carried out will be documented in a report, the release of which will be the
precondition to be met for the subsequent qualification of the operation.
As the last qualification activity, the Process Execution Qualification (PQ) is performed.
This represents documented proof that the equipment, in its state of load and under
operating conditions, is capable of achieving the expected results in a reproducible manner.
In the case of stability controls, the temperature distribution in different load states is of
great interest. Depending on the risk assessment, there may be another part of the process
execution qualification, known as "Worst Case" conditions. These operating conditions,
different from ideal conditions, can show to what extent product quality is affected.
Protective environment room (f), (n), (t) Positive 2 12 N/R No max 60 70-75/21-24
All room (e), (n\ (u) Negative 2 12 Forks No max 60 70-75/21-24
All isolation anteroom (t) (u) N/R N/R 10 Forks No N/R N/R
Labor/delivery/recovery. / postpartum (LDRP) (s) N/R 2 6 N/R N/R max 60 70-75/21-24
Labor/delivery/recovery (LDR) (s) N/R 2 6 N/R NR max 60 70-75/2 1-24
RADIOLOGY (v)
X-ray (diagnosis and treatment) N/R 2 6 NR N/R max 60 72-78/22-26
X-ray (surgery/critical care and catheterization) Positive 3 15 NR No max 60 70-75/21-24
Darkroom (g) Negative 2 10 Forks No N/R N/R
DIAGNOSTIC AND TREATMENT
Linen and trash chute room Negative N/R 10 Forks No N/R N/R
Bedpan room Negative N/R 10 Forks No N/R N/R
bathroom Negative N/R 10 Forks No N/R 72-78/22-26
Janitor's closet Negative N/R 10 Forks No N/R N/R
SUPPORT SPACE
• Single room
• Knowledge throughout the health group through appropriate signage (posters in the
room, record in the Medical History).
• The patient, family, and visitors should be instructed about the objectives of the
precautions we apply to the patient.
• Visits will be limited to the maximum, there should never be more than one family
member on each shift
• Depending on the type of precautions, the specific measures indicated in this
protocol reflected in the corresponding sections will be taken.
• If the patient has to go to another area of the hospital, a surgical mask will be placed
on them and the staff who will come into contact with the patient will be informed
of the rules (gown, gloves, hand washing, face masks...). according to the
specifications for each type of insulation.
Single room : mandatory for airborne diseases and reverse isolation. In cases of
transmission by contact or droplets, it is recommended (in these cases, if a single room is
not available, the distance between one patient and another must be at least one meter). In
cases of airborne transmission, the room should have a negative pressure system.
STANDARD PRECAUTIONS
Hand washing: should always be done after touching blood, body fluids and contaminated
material, whether or not you are wearing gloves. See hand washing protocol.
INDIVIDUAL
CONTACT (if possible) YEAH YEAH
SURGICAL SURGICAL
REVERSE INDIVIDUAL YEAH YEAH
MASK MASK
1. In cases of airborne transmission, the room should have a negative pressure system.
2. A particulate respirator will only be used in cases of airborne transmission. In other
cases (droplet isolation, reverse isolation or whenever necessary based on standard
precautions) use surgical masks.
AIR TRANSMISSION PRECAUTIONS
It is defined as the isolation that must be achieved when the dissemination of particles
smaller than five microns remain suspended in the air for long periods of time, and are thus
inhaled by a susceptible host.
Due to the risk it poses, it is required to use high-efficiency face masks (particulate
respirators).
Examples: Pulmonary Tuberculosis, Measles, Chickenpox.
Specifications:
• Isolated room with negative air pressure, closed door and open windows if no such
system exists.
• High efficiency face masks, particulate respirator. Discard it when leaving the room.
• The use of gloves, surgical mask and gown is recommended when having direct
contact with the patient. Discard mask and gloves before leaving the room. Remove
your robe before leaving the room.
• Hand washing is absolutely necessary before and after touching the patient.
• Patient transportation should be limited. Put on a surgical mask.
• Patient care team: when possible this will be dedicated to a single patient. If this is
not possible, clean and disinfect or sterilize it properly before using it on another
patient.
• Material for clinical use such as thermometers, sphygmomanometers, stethoscopes,
etc. It will be for the exclusive use of these patients, and if possible they will remain
inside the room.
REVERSE OR PROTECTIVE INSULATION
It tries to protect immunosuppressed patients from infections and febrile patients from
possible superinfections.
Specifications:
• Handwashing.
• Single room.
• Putting on a gown, cap, surgical mask and leggings before entering the room, for
anyone who comes into contact with the patient. The mask, leggings and hat will be
discarded before leaving the room. The robe will be left inside the room.
• Patient transportation should be limited, but if necessary, put a mask on and explain
to the patient the reason for this measure.
• Clean the stethoscope before and after use, and try to
individualize a tension sleeve.
• It should be applied to all patients with severe neutropenia (< 500
neutrophils) until this figure recovers and the clinical evolution is favorable.
NOTE: some infections require taking several types of precautions simultaneously. For
example: RAMS (contact and droplets), Adenovirus Pneumonia in children (contact and
Droplets), Chickenpox (airborne and contact).
6 .-If it is not occupied, the pressure ratio is maintained and the minimum is 6 ACH
7 .-Switching controls for reversible airflow (pressure ratio) will not be permitted.
1 .-12 ACH, 2 ACH outside air minimum, ACH for positive room supply airflow
7 .- When the ward has a previous room: the patient's room is positive to the previous
room, the previous room is positive to the corridor.
8 .-Monitoring device between the room and the corridor alarm when pressurization is not
maintained.
SA = INJECTION
RA = RETURN
EA = EXTRACTION
DV = EXFILTRATION/ INFILTRATION
P1 / DA + V1 ² /2 = P2 / DA + V2 ² /2 (Eq.2)
If we leave the equation based on pressure and consider that:
Q = flow rate = v1 A1 = v2 * A2, therefore:
V1 = Q/A1 (Eq.3)
V2 = Q/A2 (Eq.4)
P1/DA – P2 /DA = V2 ² /2 - V1 ² /2
(P1 – P2)/ DA = V2 ² /2 - V1 ² /2
( P1- P2 ) / DA = ( V2 ² --V1 ²)/ 2
DP = (V2 ² - V1 ²) * DA/ 2 (Eq.5)
If equation 3 and 4 are replaced in equation 5 we obtain:
It is important to note that the leak area is a very complex value to determine, but for
practical purposes ASHRAE recommends a range of the order of 0.045 m2 to 0.1 m2. The
other option that catalogs generally have, for clean room doors, include their estimated
leakage area.
To the extent that the leak area is less than 0.045 m2, the differential pressure inside the
clean rooms becomes very complicated to manage.
Diff (Pressure) = cte *Q² / (Af )² (Eq.7)
That is, to the extent that the leak area tends to zero, the pressure differential tends to
infinity, therefore the pressure differential is very difficult to control when the flow areas
are very small. Furthermore, if we look at equation 7, the leakage area is found to the square
power.
Sump Type:
This type of airlock is recommended for contaminated operations; in this case the air flow
will be towards the inside of the airlock, generating a depression in it.
We must bear in mind that a lock is a “passage” place, so when opening one of the doors the
pressure drop is inevitably zero, and this presupposes possible contamination, if the
openings are not made under the specific procedures. . On the other hand, as a result of this
abrupt drop in the differential, special attention must be paid to the direction of air flow in
the closed door, and it must be designed in such a way that there is no possibility of
reversing the design direction.
It is therefore essential to have knowledge of the pressure requirement from the beginning
of the project stage.
Below is a clean room, with multiple rooms and also the control system for several locks,
with their pressure differentials and interlocks.
The areas with their most important characteristics are the following:
Zone Description ISO classification RH
Classification Classification QTS KW VR Tlocal °C Te °C HUMIDITY HUMIDITY INJ FLOW FLOW R/H m3/h FLOW
GMPs FED STD 209 E m3 INT. % EXT.% QT m3/h DESIGN m3/h
On the other hand, the Bone cement Manufacturing area has a dust extraction of 800 m3/h and the Solvent area has a Type II Biosafety Booth, with
an extraction in the room of 400 m3/.
For calculation purposes, all doors have a creepage area of 0.045 m2, as shown in the following table.
Development a.- Obtain the injection flow rate required by each zone, based on what is needed per thermal load and per hour renewals,
resulting in the following:
Zone Description Classificatio Classificatio Classification VR HUMIDITY EXT. RH INJ FLOW FLOW R/H FLOW
nI n QTS KW Tlocal °C Te °C
FED STD 209 m3 INT. % HUMIDITY QT m3/h m3/h DESIGN m3/h
GMPs E % 60
1 SOLVENT 5 b CLASS 100 15 30 22 35 40 75 4.479 2250 4.479
2 LOCK 2 5 c CLASS 10,000 3 25 22 35 40 60 45 896 1125 1.125
3 PACKAGING 8 d CLASS 3 100 24 35 40 60 25 896 2500 2.500
4 BONE CEMENT 7 c 100,000
CLASS 10,000 4 45 20 35 40 60 45 1.194 2025 2.025
5 LOCK 1 7 c CLASS 10,000 2 25 20 35 40 60 45 597 1125 1.125
6 STORE 8 d CLASS 4 120 24 35 40 60 25 1.194 3000 3.000
7 LOCK 3 9 S/C 100,000 0,9 15 24 35 40 60 25 269 375 375
Note: In all UPC applications (critical patient unit, thermal loads are not required to be calculated, they are removed only for hourly renewals) The return flow is obtained by flow balance and in the case of non-critical areas it is approximately 80% of the
injection flow.
The calculation of injection per hourly renewal is widely used in hospital and pharmaceutical applications and its expression is very simple:
Vi = R/H * VR
VR = Room volume m3
Note 1: Remember that in the case of clean rooms, you should always choose the highest flow rate between the ones that are calculated by thermal load and by renovations.
Note 2: The flow rate due to thermal load in critical patient rooms, where 100% outside air is required, is always greater than that due to thermal load.
Note 3: In the case of laboratories, the flow rate due to thermal load is always higher, mainly due to the loads dissipated by the equipment.
b.- Obtain the leakage flows through each door, as indicated in the following table:
Zone Description Area Higher Pressure Differential Flow
Leakage pressure Pa minor Pa Da Leakage m3/h
P1 LOCK 1 / BONE CEMENT m20,045 15 10 5 304
P2 LOCK 1/WAREHOUSE 0,045 15 10 5 304
P3 PACKAGING/WAREHOUSE 0,045 15 10 5 304
P4 SOLVENT/LOCK 2 0,045 25 15 10 430
P5 LOCK 2/WAREHOUSE 0,045 15 10 5 304
P6 WAREHOUSE/LOCK 3 0,045 10 3 7 360
P7 LOCK 3/HALLWAY 0,045 3 0 3 236
c.- Carry out flow balances, taking into consideration that there must be a balance between the flow that enters and the flow that leaves:
Incoming flows; air injection, air infiltration
Outgoing flows; exfiltration, return, bath extraction, general extraction, equipment extraction, dust extraction and air return
d.- The UMAS must be selected according to the type of room classification, only room classifications C and D can be combined according to GMPs,
but zones A and Zone B must be with independent equipment.
In areas where there is dust extraction, such as in the case of tablet manufacturing, there can be no return.
The UMAS are separated by classifications below:
UMA-01
Zone Description ISO classification Classification Classification INJ FLOW FLOW EXFILTR. RETURN EXT. EXTRACC. EXTRACC.
GMPs FED STD 209 E M3/H INFILT. M3/H M3/H M3/H BATHROOM GENER. M3/H POWDER M3/H
M3/H
1 SOLVENT 5b CLASS 100 4.479 0 430 3.649 0 400 0
UMA-02
Zone Description ISO classification Classification Classification INJ FLOW FLOW EXFILTR. RETURN EXT. EXTRACC. EXTRACC.
GMPs FED STD 209 E M3/H INFILT. M3/H M3/H M3/H BATHROOM GENER. M3/H POWDER M3/H
M3/H
2 LOCK 2 5c CLASS 10,000 1.125 430 304 1.251 0 0 0
3 PACKAGING 8d CLASS 100,000 2.500 0 304 2.196 0 0 0
4 BONE CEMENT 7c CLASS 10,000 2.025 304 0 0 1.529 800
5 LOCK 1 7c CLASS 10,000 1.125 0 609 516 0 0 0
6 STORE 8d CLASS 100,000 3.000 913 360 3.553 0 0 0
7 LOCK 3 9 S/C S/C 375 360 236 499 0 0 0
10.150 2.007 1.813 8.015 0 1.529 800
e.- The type of UMA configuration must be selected, based on ASHRAE Regulations, a relationship is obtained between the injection flow
rate per hourly renewal and that obtained by Thermal Load.
R = Air flow rate per hour renewals / air flow rate per thermal load according to the , with this the configuration of
following schemes:
UMA 02
The data for each one must be obtained from the previous tables:
g.- The diagram of input and output signals, variables to control including access control is as follows:
h.- The P&D control diagrams of each of the UMAS are the following:
17
8
. . ■ Mechanical connection
Hydraulic signal
Instrument identification
Variable to
control 1- letter: Measured or modifying
variable
For
example;
TO. Analysis
E: Voltage
F: Flow
I: Current
J: Power
L Level
Q: Pressure
S: Speed, Frequency
T: Temperature
V- Vibration
These are the most common, although there are many others that appear in table 1.1.
The acronyms come from the English name of each of the instruments' functions.
Detail of each
loop element
2nd
and 3rd letters: Output, data presentation or modifier function.
For example,
A: Alarm
C: Controller E: Primary Sensor
H: High I : Indicator
L: Low P: Pressure
R: Recorder
S: Switch
T: Transmitter
V: Valve
7- Actuator
Designates a Temperature Controller with Indication capacity associated with control loop No. 60.
SWITH DIFFERENTIAL
PRESSURE
E 1 FLOW CONTROL
CONSTANT FLOW CONTROL
SPEED CONTROL
1. Operator accessible
1.1 Shared viewing
1.2 Shared viewing and control
1.3 Access to the communications network
1.4 Operator interface in the communications network
2. Auxiliary interface
2.1 panel mounted
2.2 manual station
Manual Diaphragm
Motor Solenoid
Example 5
With this information, although very summarized, of what a P&ID is, surely that graph or
diagram that we see so often in engineering projects and reminds us of a hieroglyph will no
longer seem so strange and intelligible to us.
Now we will surely know how to better interpret the information it offers us and know
better the instrumentation, design, functions and ultimately all the elements of the industrial
process that is represented to us.
Below, various examples of P&ID control are presented, aimed at clean room HVAC
systems, with the objective of analyzing based on what is explained in this chapter.
Based on the above: a.- You must identify the nomenclature of the plan
b.- The number of control loops and what each one controls
c.- Explain if the system is a ventilation or hydraulic P&ID diagram
d.- Indicate if the UMAS are recirculated air or 100% outside air.
Problem 7
Problem 7
Problem 7
Problem 7
Problem 7
Problem 7
Problem 7
Problem 7
AU Status Auto - Automatic Status Fll Pressure Transmitter 4 ind/heat - Pressure Transmitter with Indicator
BU Disarm, Breakdown
Break Down - PR Pressure Rupture - Vacuum Breaker
C.T. Conductivity Meter Transmitter - Conductivity transmitter P.T. Pressure Transmitter - Pressure Transmitter
IS Voltage Switch - Current Switch Ql Quantity Indicator - Quantity Indicator (Energy)
THAT Voltage Switch Alarm - Current Switch Alarm Q.T. Quantity Transmiter - Quantity (Energy) Transmitter
re riow Control - Flow Control R.A. Rupture Disc Alarm - Rupture Disc Alarm
FCAI Flow Control, Alarm & Indicator - Flow Indicator with Control RD Rupture Disc - Rupture Disc
FCV Flow Control Valve - 1 Gate Valve R.S. Rupture Disc Switch - Rupture Disc Sensor
F.D. Frequency Drive - Frequency Variator HE Speed Control - Speed Control
FlCV Fire Control Damper/ Valve - Fire Damper SC Al Speed Control, Alarm & Indicator - Speed Control Alarm with Indicator
h H^nd ■ Manual SW Start Order
H.C. Humidity Control - Humidity Control S.T. Status On-Off - Tin On-Off
H.T. Humidity Transmitter - Humidity Transmitter - Temperature Control
RC Temperature Control
HICA Humidity Transmitter, Control & Alarm - Humidity Transmitter Control and Alarm TCV Temperature Control Valve - 1 Gate Temperature Control Valve
Humidity & Temperature Transmitter - Temperature and Humidity Probe YOU Temperature Indicator - Thermometer
M Engine - Engine 1IC Temperature Indicator & Control - Thermometer with Control
M.N. Status Manual - Status Manual TICA Temperature Indicator, Control & Alarm - Thermometer with Control and Alarm
PC Pressure Control - Pressure Control YOU Temperature Transmitter ■ Temperature Transmitter
PDC Pressure Differential Control - Differential Pressure Control AND Position - Position
PDS Pressure Differential Switch - Differential Pressure Probe ALRE Position Alarm - Position Alarm
ADY
PDT Pressure Differential Transmitter - Pressure Transmitter Y.S. Position Sensor
Learning objectives
The sequence of operation is one of the most important design aspects of any HVAC system.
Without proper sequencing, the system could operate out of control or stop working altogether.
When approached methodically, the process can be broken down into smaller segments. We will
look at the steps required to successfully create an operating sequence using variable air volume
(VAV) for a single zone of an air handling unit serving a multi-cleanroom space. These same
steps can be applied to any team.
Before the designer can begin to actually create the sequence of operation, some information
must be gathered. That data collection and brainstorming process can be broken down into the
following main steps:
Figure 38: A schematic diagram shows the control components of the example air handling
unit (AHU). Courtesy of: JBA Consulting Engineers
Figure 38 shows the main components of the air handling unit (AHU) that we are considering for
our example. This unit has an air extractor, outside and supply air flow measurement stations,
mixing box, pre-filter, final filter, hot water coil, cold water coil and supply fan. The flow
diagram should also identify the air flow path and piping connections. It is not necessary to
include the air flow velocity and water flow rate data, as
Step 2: Classify the purpose of the team . One of the first questions to ask before proceeding is:
“What is the purpose of the system?” Often the purpose is to heat or cool to a temperature of
comfort for human occupants. Sometimes the purpose is to maintain acceptable temperatures for
a process (for example, a data center). Perhaps the system needs to maintain pressure
relationships for a particular space or group of spaces. The designer must also identify any other
equipment that is affected by the sequence. A makeup air unit, for example, must be interlocked
with the exhaust fan(s) that create the need for that makeup air unit. Keep in mind that a system
can have multiple purposes. An AHU may be designed to condition a space during normal
operation and also to function as a smoke control system during a fire.
Step 3: Identify the necessary inputs and outputs . It was noted earlier that the flowchart
should include entries for the controlled variables. Inputs are the readings that go into the building
management system (BMS). These include elements such as spatial sensors, air temperature
sensors, static or differential pressure sensors, etc. In developing this list of input devices, the
designer should consider which inputs are already available for use in the control system. Are any
of the required input devices included as part of the equipment or have they already been
specified for other purposes? At this time additional devices must be indicated and specified in
the construction documents. Outputs should also be considered at this time to prepare the
complete list of points. The outputs are the signals from the BMS system for the controlled
variable.
Step 4: Detail the system functions required by the regulations . Energy codes (such as
ASHRAE 90.1) are becoming stricter and increasingly demanding more efficient systems.
Identifying these requirements in advance helps ensure that the system will comply with
applicable energy savings regulations. Control requirements, isolation dampers, demand-
controlled ventilation, economizers, superheat limitations, dead zone, and supply air temperature
reset are examples of requirements in operating zone regulations that, where appropriate, should
be incorporated. to the sequence. It is important to recognize the requirements and exceptions for
your particular project location.
Other building, mechanical and fire code requirements should also be reviewed at this time. For
example, regulations may require that a unit be turned off if smoke is detected. Additional control
requirements may come into play if the equipment has a smoke control feature.
HVAC features and equipment required by regulations should be identified early in the design
process. This is one of the reasons why it makes sense to develop the sequence of controls early
in the design process. Doing so allows for a complete and exhaustive coordination initiative as the
design progresses.
Figure 39: This graph of an example building management system (BMS) shows several
points. The graphical outline presents a summary of the unit's status in a clean and simple
format. Courtesy of: ABS Systems Inc.
Table 18: A list of points is shown for the air handling unit example. All desired inputs and
outputs must be listed and classified. Courtesy of: JBA Consulting Engineers
Step 7: Identify setpoints . Setpoints are the values that the system attempts to maintain during
operation. Space temperature is a common example of a set point. The space sensor or thermostat
is the input device that measures the current temperature in the space. The control system
contrasts the actual state with the set point value. Setpoints are not limited to temperature. The
duct static pressure sensor that controls the fan speed will also have a set point. Similarly, a set
point must be identified for the carbon dioxide (CO2) sensor that serves as input to the demand-
controlled ventilation strategy.
The sequence of operation should concisely list these evaluations and how the system should
respond. Recommended descriptions for the last example may be similar to the following:
Figure 40: Air treatment units in redundant format connected to a common source and a
return duct. The sequence defines the positions of the control gates and the power-on
sequence of the units. Courtesy of: JBA Consulting Engineers
In cooling mode, the set point will be 75ºF ± 1ºF (adjustable). If the space temperature rises
above the cooling set point, the system will first modulate the cold water control valve from 0%
to 100% open according to proportional, integral and derivative (PID) control and flow. supply
fan air flow will be kept at the minimum position. The supply fan speed will be modulated from
minimum to 100% of design airflow if the control valve position is opened more than 70%
(adjustable). If the space temperature drops below the cooling set point, the system will modulate
the cold water control valve and close it according to the PID control. If the control valve opens
less than or equal to 50% (adjustable), the supply fan speed will reset to the minimum supply air
flow rate.
Supply Fan
On-off
StartStop
Status Aut
Statue Hand
VFD Control Panel
Return Fan
On-of
StartStop
Auto Status
Statue Hand
VFD Control Panel
Relief Fan
On-of
StarStop
Auto Status
Statue Hand
VFD Control Panel
Exhaust Fan
On-off
StartStop
Auto Status
Statue Hand
VFD Control Panel
On-of
StartStop
Auto Status
Statue Hand
Table 19: During the design stage, a matrix can be used to write the various modes of
operation. The designer can use this brainstorming exercise to help write the actual
control sequence.
Let us remember that the normal operating mode can also have several other modes associated
with it. In our example, we have economizer operation and recirculation operation. A matrix
like the snippet shown in Table 19 is an easy way to identify the parameters needed for
different modes of operation. Although this matrix will not always be included in the
construction documents, it provides the designer with a general summary that helps him or her
develop a written sequence of operation. The various analog and digital inputs and outputs
should, in some way, be clearly identified in the construction documents with the
corresponding control sequence that has been designed.
Step 9: Identify failure situations. At some point, system components will fail. Although
quality products help reduce the frequency of failures, they are inevitable. If the designer plans
for these failures in the sequence of operation, then they can reduce the resulting operational
impact when a failure occurs. Once again, we must be careful not to oversize. The strength
requirements for a typical office building will be substantially different than those for a data
center. Personal safety requirements must also be considered.
Failure considerations should focus on both the input devices and the controlled components
of the system. Failure of a static pressure sensor in the supply duct could result in improper
speed control of the supply fan variable frequency drive. If the value measured on this sensor
varies significantly from the expected value, a false measurement could have been received.
The operating sequence may specify that this reading be ignored if the value is percentage-
wise outside the expected value. Some input devices may also integrate a function into the
sensor to detect invalid readings.
Figure 41: Frequency converter is used in air extractors. The sequence jointly modulates the
speed of the fans to maintain a differential pressure within the space. Courtesy of: JBA
Consulting Engineers
Let's consider a low static pressure sensor reading. A sequence that identifies the failure of this
component can reset the power fan to some set speed that keeps the system running and
provides at least some capacity until the maintenance team can properly address the problem.
A system that does not anticipate that failure will continue to control the system using the
erroneous static pressure measurement. This system will likely increase the speed of the
supply fan until the system eventually shuts down due to high static pressure if a high static
pressure set point was considered in the original checklist. This typically requires a manual
reboot and the system will have a longer downtime than a system that does incorporate
failsafes. This is an important consideration for systems where environmental conditions are
critical or where safety could be compromised.
A power fan motor failure in a system with a single power fan has no true fail-safe position.
However, a system with multiple motors and supply fans could respond to this failure situation
without reducing the supply air flow. This is an excellent example of how the development of
an operating sequence can result in changes to the hardware components specified for the
system. The impact of feed fan motor failure may have been overlooked prior to this stage of
design.
Step 10: Review the sequence . At this point, the designer has completed the first step in
developing the operating sequence. A successful sequence is iterative and often requires
revisiting previous steps. It has been mentioned above that a designer might start writing the
actual functional responses of the system and realize that it does not have all the required input
and output devices. This may require an update to the initially developed flowchart. The
operating sequence development process may also identify features or options that were not
originally specified. Now is the time to adjust and fine-tune those specifications.
The best way to review the sequence of operation is to go through each of the actions and
responses. Decompose the system by identifying situations to which the sequence of operation
cannot adequately respond. Rewrite the sequence as necessary to address these scenarios. Ask
a colleague to review the sequence to make sure the purpose of the sequence is clear to
everyone.
Start up
Functional testing during commissioning helps ensure that the built project operates in
accordance with the design objective. Testing relies heavily on the designer's sequence of
operation. The equipment should not be expected to perform functions that were not required
by the sequence.
Discrepancies observed during the project start-up phase should be reviewed with the
designer. It may be necessary to update the operating sequence based on data collected during
functional testing. See the static pressure sensor example mentioned above. During start-up is
the appropriate time to verify whether fail-safe strategies are working as expected. The goal is
to keep the system running. The implementation of this feature should be tested by those
responsible for commissioning and the team should modify the setpoints as necessary to
achieve the desired results.
Commissioning is the last opportunity to evaluate the sequence before handing the project
over to the owner. The designer should participate in the commissioning process and review
the final commissioning report. The sequence may need to be modified based on observations
during the commissioning period. Changes this late in the project schedule could have major
implications for costs and planning. That said, the designer should not rely on the
commissioning process to compensate for a lack of adequate foresight during the design phase.
The building operator must have full knowledge of the sequence of operation. This ensures
that the facilities maintenance group operates the equipment consistent with the design
objectives by recognizing all the benefits of the implemented system. The building operator
can take control of the supply air temperature if there are complaints about the temperature of
a space. Said operator must understand the consequences that his taking control has on energy
efficiency. Identify the root causes of operational deficiencies and resolve problems at the
source.
Although the designer must consider operational needs during the design phase, those specific
details may not always be available. The sequence may need to be readjusted based on the
evolution of the building's operation over time. The sequence of operation should be
considered as a living document that is maintained continuously throughout the life of the
system. If this is done, knowledge can be transferred seamlessly within the operations group.
Understanding the control logic for existing equipment is important for designers working on
building renovations or tenant improvements within an existing space. Without this
knowledge, the new design could work against the base system rather than being coordinated
with it.
An update sequence also becomes a testbed for how the system should work. The sequence for
existing equipment can be modified to optimize energy efficiency and improve adaptation to
the evolved functional and operational requirements of buildings. Retrofitting and energy
audits are great ways to identify deficiencies in the control sequence of existing equipment.
Existing equipment without a well-defined operating sequence could be a good target for
energy optimization.
HVAC systems use a large amount of energy in commercial buildings. Developing a well-
thought-out operating sequence helps minimize the energy consumption of these systems.
Additionally, it allows the system to meet the criteria for which it was designed. The designer
must develop the sequence to a level of detail that is appropriate for the project at hand and
maximizes the success of that particular project.
to:
*
22
8
The supply air must be 18.52°F below ambient temperature, which is equivalent to 56.48°F.
Repeating the calculation for 12,000 BTU/h, the following result is achieved:
ΔT = Q ÷ (1.08 x CFM)
• Control loop 0507: 0508; 0509; 0510; 0511; 0512, differential pressure transmitter.
They control the differential pressure in the different rooms. For rooms 025;
026;027; 028; 029 and 030.
• Control loop 007, temperature control, has the control loops associated with the cold
water and hot water valves. Associated with the temperature transmitters in all
rooms.
Immunocompromised Rooms:
Each group of these rooms will be attended by an exclusive UMA for this purpose.
- These rooms must be overpressurized with respect to the hallway (minimum 10 Pa). The
control system will act on the duct air regulators to achieve this. Next to the room there will
be a visual panel that will provide a positive differential pressure reading between the room
and the hallway at all times. If the overpressure was lost, an alarm signal would be given.
1. Contact, both direct and indirect, is the most common mode of transmission in
healthcare, facilities, and other indoor environments.
HVAC systems have little impact on this mode of transmission.
2. Droplet transmission is characterized by the spread of microorganisms from an infected
person over short ranges (3–6 feet). The aerodynamics of this result in microbes contained
in fluids falling from the air quickly.
3. Airborne transmission involves the spread of microbes through droplet nuclei beyond
short ranges, such as through an HVAC system.
HVAC systems can affect the distribution patterns of airborne particles by dilution or
concentrations, moving them into or out of the breathing areas of susceptible people, or
accelerating or slowing the growth rate of airborne microbes. Improperly operated and
maintained HVAC systems can even become a reservoir for microorganisms.
Standard
ANSI / ASHRAE / ASHE Standard 170 - Ventilation of
health facilities (2017)
NFPA 101
GUIDELINES
Facility Guidelines Institute (FGI) Guidelines (2014) - for ventilation refers to ASHRAE Standard 170 - 2017
Guidelines for Environmental Infection Control in Health-Care Facilities", Recommendations of CDC (centers for Disease Control &
Prevention) and the Healthcare Infection Control Practices Advisory Committee ( HICPAC), 2014
• MONITORING DEVICE
It is necessary to use pressure differential in the corridor and connect its hoses between the room, lock and
corridor.
• All isolated rooms shall have a permanently installed device and/or mechanism, to constantly monitor
differential air pressure:
-Between the room (when occupied by patients with suspected infection or illness).
• The corridor or adjacent spaces of the room, whether or not there is an anteroom
• A local visual means shall be provided to always indicate that the differential is negative
• A minimum of 0.01” in.ac or 2.5 pa should be achieved.
Below is a table of the Ashrae 170, to see where the design data is obtained from.
ACH = (60*CFM)/VOLUME
CFM = (12*1000)760
= 200CFM
• These rooms are for patients who suffer from a weakened immune system and also have a contagious disease.
• The ventilation problems involved are the combination of room AII and PE
Positive Case
negative case
• surgical block
• obstetric block
• Intensive care units (ICU), pediatric and neonatal
• Special and isolation boxes
• Burn Units
• Sterilization rooms
• Preparation of cytostatic and sterile
• vascular radiology
• Endoscopy
• Microbiology Laboratory
Other important clean rooms:
Regarding what the ISO 14.644-1 Standard indicates, the following international table is available:
SUPPLIES
DIRTY
Operating rooms
White Zone
Pre-anesthesia /
ante-operative
medical work
room room
Gray zone
Patient access
Circuits for the configuration of: (a) double aisle and (b) single aisle
SURGICAL BLOCK
It is recommended that the number of operating rooms per surgical block is not excessive; eight,
operating rooms make it difficult to maintain discipline and air conditioning. more
The surgical block or surgical area must be independent from the general circulations of the hospital. The use of airlocks2
with interlocking automatic doors is recommended for access to the surgical block.
27
2
Ambulatory surgery.
c Class I ISO class 8 Ambulatory surgery operating room
Delivery rooms.
Type of Temperature
operating room
Minimum driven air flow Movements/hour (MH)
Humidity
Pressure Filters
18°C-26°C
A class Minimum 30 45- 55% humidity F5/F9/H14
2400 m-/hour
1200 mYhour (outside air)
+20Pa to +25Pa
Class B Minimum 20
229C-26°C
45- 55% humidity F5/F9/H13
Ventilation flow, hourly air movements, temperatures, pressure and filters indicated for operating rooms
Resolution
Press Pas Pressure Diff. Cte
Sector TYPE OF PAVILION volume e Iny flow. Variation
Time renewals ure Pressure Fu area m2 calculation Extraction flow Flow rate ratio
Da m3/h Flow m3/h
Da Da
PAVILION 1 organ transplant
Extraction m3,h
Extiltration ma/h
Pue rus outlet flow ma/h
Resolution
Sector TYPE OF PAVILION Volume m3 Diff. Pressure Cte Extraction
Pressure Variation
Hour renewals Pas Pressure Da Pa Iny flow. m3/h Fu area m2 calculation flow Flow rate %
Da Flow m3/h
PAVILION 1 Organ transplant 54 30 25 10 15 1620 0,046 355.407 596 1.024 63
PAVILION 2 Heart surgery 54 30 25 10 15 1620 0,046 355407 596 1.024 63
PAVILION 3 Conventional surgery 48 20 20 10 10 960 0,046 236.938 487 473 49
PAVILION 4 Conventional surgery 50 20 20 10 10 1.000 0,045 236938 487 513 51
PAVILION 5 Orthopedic surgery 54 30 25 10 15 1620 0,046 355.407 596 1.024 63
PAVILION 6 Ambulatory surgery 54 15 20 10 10 810 0,046 236938 48? 323 40
PAVILION 7 Ambulatory surgery 54 15 20 10 10 810 0,046 236938 487 323 40
PAVILION 8 Ambulatory surgery 54 15 20 10 10 810 0,046 236938 487 323 40
AISLE 120 20 10 3 7 2400 0,046 165.856 407 6.215
REMEMBER THAT
INJECTION FLOW + INFILTRATION FLOW = EXFILTRATION FLOW + EXTRACTION FLOW + RETURN FLOW
DOOR TYPE 1
VI 01 = Injection flow
VE1
MATERL
ESTER VE 01 = Extraction flow Ws 3,175 mm
door 01 exfiltration
AF = ( (2*H*3.175/1000}+ ( 1* A*3.175/1 000} r A*6.35/1000))
—= 1/4" = 6.35mm
—% DOOR TYPE 2
1/8" = 3.175mm
rTeTArsFRoot^DpT
T/s
Af = Leakage area = (0.045-0.13) 1/4“ s 6.35 mm
m2
AF = (| 3'H*3.175/1000) * ( 1* {AH A2)*3.175/1000) ♦ 1 *( A1+A2)* 6.35/1000) )
Dp = Pressure differential (pascals)
2 .- CLEAN HALLWAY
INJECTION FLOW 900m3/h
INTERNAL PRESSURE 12,5 pascals
VILLAGE HALL PRESSURE 0pascals
PRESSURE DIFERENCIAL 12,5 pascals
DOOR 02
AMOUNT 3
HEIGHT H 2m
WIDTH H 1,14 m
GUY SIMPLE VISAGRA
DOOR 03
AMOUNT 2
HEIGHT H 2m
WIDTH H 0,87 m
GUY SIMPLE VISAGRA
LEAK AREA 01 0,02 m2
LEAK AREA 02 0,02 m2
EXFILTRATION FLOW 01 (ve02) 673m3/h
EXFILTRATION FLOW 01 (ve03) 504m3/h
EXTRACTION FLOW 2.077 M3/H
3 .- RECOVERY ROOM
RECOVERY ROOM
4 .- STERILIZATION
CALCULATION OF LEAK FLOWS
Sterilization area
Door number Area of highest pressure at lowest pressure LEAK AREA Higher pressure Lower pressure Differential Flow Symbology
m2 Da Da Da leak m3/h
P1 CEYE/SLOCK 0,02098675 20 10 10 201 vex2/vinf2
P2 CEYE/SUB CEYE 0,02098675 20 15 5 142 vex1/vinf1
P3 LOCK / CORRIDOR 0,02098675 10 0 10 201 vex4/vinf4
P4 LOCK/ PREWASH 0,02098675 10 -2,5 12,5 224 vex3/vinf3
P5 HALLWAY/AUTOKEYS 0,02098675 0 -2,5 2,5 100 vinf 05
VI05 + v inf05 = VE 04
WASHING MACHINE
THERMO DISINFECTOR DELIVERY
MATERIAL
STERILE
LOCK BALANCE
vex 2 = vinf 02
5 .- IMMUNODEPRESSED ROOM
Door number Area of highest pressure at lowest pressure LEAK AREA Higher pressure Lower pressure Differential Flow Symbology
m2 Da Da Da leak m3/h
P1 isolated/bath 0,024 15 -1,5 16,5 299 v1
P2 isolated/sluice 0,020 15 10 5 134 v2
P3 lock/hallway 0,020 10 0 10 192 v3
P4 isolated room/hallway 0,025 15 0 15 297 v4
6 .- OPERATING ROOM 4
Door number Area of highest pressure at lowest pressure LEAK AREA Higher pressure Lower pressure Differential Flow Symbology
m2 Da Da Da leak m3/h
P1 Lock/corridor 0,021 14 0 14 237v1
P2 Operating room/airlock 0,058 25 14 11 581v2
P3 Operating room/white area 0,021 25 20 5 142v3
P4 White area/hallway 0,021 20 0 20 284v5
P5 Sub Ceye/ hallway 0,021 20 0 20 284v4
VI0
1
PAVILION
BALANCE
TRANSFER
VI01 = VEX01 + v3 +
QI CKD v2
GINEcdlFLUI
DO YOU VEX01 = VI01 - v2 -
| 14 dc •
COPY v3
—Ve4 VEX04 VEX LOCK BALANCE
25 pa 01
VI04 + v2 = VEX04 +
v1
VIO
2 VEX04 = VI04 + v2 -
20 pa
WHITE AREA
BALANCE
VI03 + v3 = VEX03 + v4
HANDWASHING VI0
SUB - CEYE VEX03 = VI03 + v3 -v4
3
REGA
ERIAL SUB CEYE
DRESSING BALANCE
TERIL 20 pa ROOM
VEX 20 pa
03 VI02 = VEX02 + v5
VEX0
2 WHITE AREA VEX02= VI02 - v5
Condensation
The fluid in the gaseous state is under high pressure, and passes through an exchanger called
a condenser. In this exchanger, the refrigerant fluid transfers the heat energy accumulated in
the evaporator and due to the effect of compression to the external medium (commonly
called a hot source). The effect of giving up that heat energy produces the condensation of
the fluid, taking it to a liquid state at high pressure. This heat transferred to the external
environment can in some cases be recovered to preheat water or air.
The refrigerant fluid is sub-cooled in order to ensure complete change from vapor to liquid.
Figure 4 Condenser diagram
provided by
the refrigerant
in H
condenser
This subcooling is usually between 4 and 7°C. Unlike overheating, it does not require
particular vigilance since it does not represent any type of threat to the components of the
refrigeration circuit.
The heat transfer fluid can be:
• Air
• Water (geothermal, towers)
Expansion:
The refrigerant fluid in a liquid state and high pressure is expanded in order to reduce that
pressure to low pressure. This decrease in pressure is essential to obtain a refrigerant fluid in
favorable conditions to capture the heat energy in the evaporator.
Pressurized
Axle
liquid and
Expansion Liquid Steam
bp
Enthalpy
Axis
Liquid
Evaporation:
The fluid in a liquid and vapor state is introduced into an exchanger (evaporator) where it
will be charged with heat energy from the fluid (water or air) that needs to be cooled (cold
source). This heating of the refrigerant causes its evaporation, going from the liquid state
with vapor to a low pressure gaseous state.
Overheating must be caused at the evaporator outlet in order to guarantee that the refrigerant
is completely in a gaseous state to protect the compressor from possible liquid shocks. This
superheat temperature is controlled to avoid possible negative influences on the
compression rate.
ENERGY EFFICIENCY
COP and EER
The COP is a unit of measurement that allows knowing the amount of electrical energy consumed by the system based on the heat produced
in the condenser.
The EER corresponding to the refrigeration energy efficiency indicates the same relationship, but with the cold produced in the evaporator.
Note: Remember that these coefficients refer to energy consumption kw h., not electrical power in kw
In the event that the energy exchange in the evaporator decreases, the pressure difference between HP and BP is reduced, causing lower
electrical consumption and restoring more cooling energy, which obviously increases the efficiency of the equipment.
Program Code heat rejection Code System Code Operation Code Duct Code CompressorCode
COR class air cooled Cold air in Cold air through water cooled
duct the floor water cooled
floor
TO >=3.2 >=3.0 >=4.5 >=4.45 >=4.5
b 3.0-3.2 2.8-3.0 3.9-4.05 4.15-4.45 4.25-4.5
c 2.8-3.0 2.6-2.8 3.75-3.9 3.85-4.15 4.0-4.25
d 2.6-2.8 2,4-26 3.6-3.75 3.55-3.85 375-4.0
AND 2.4-2.6 2.2-2.4 3.45-3.6 3.25-3.55 3.5-375
F 2.2-2.4 2.0-22 3.3-3.45 2.95-3.25 3.25-3.5
g <2.2 <2.0 <3.3 <2.95 <3.25
New regulations
The result obtained by both relationships fluctuates based on external conditions and thermal energy demand. Recently, manufacturers must
mention two new indicators, SCOP and SEER. The COP and EER are units of measurement that allow measuring the efficiency of
refrigeration machines for specific conditions of outdoor temperature and power load, which is why manufacturers favored technologies to
have high efficiencies for certain specific conditions. In light of this abuse, new SCOP and SEER ratios were developed that measure the
effectiveness of equipment for real-world conditions in a specific geographic area over a one-year period. This is because the equipment
operates partially since it is sized for maximum demand conditions. Therefore, the letter S that accompanies the new coefficients refers to
“seasonal”. There is no direct relationship between the previous coefficients and the new ones, these being parameters granted by the
manufacturers.
The COP reflects the energy performance of the cooling system (refer to section 1.3.1.3.1 to see how to evaluate it). If the installation has
measuring equipment such as pressure gauges, thermometers, etc., the COP of the system in operation can be measured and compared against
the theoretical COP. The theoretical COP is calculated from the nameplate data and the information available in the manufacturer's manual or
on the Internet.
Some standard COP values are listed in the following table.
COP min.
Kind of team
(kWwheat/kWelec)
Split: 2,8
< 1TR 3,0
> at 1 TR
1. Air-cooled systems: interior temperature of 27°C and 50% Relative Humidity (RH); outside temperature of 35°C in dry bulb and 24°C in
wet bulb.
2. Water-cooled systems: chilled water flow/return temperature of 6.7°C/12.2°C. Condenser inlet and outlet temperature 29.4°C/35°C.
These values only represent the COP of the compressor. To calculate the COP of the entire system, it will also be necessary to consider the
electrical consumption of the fans, pumps, and cooling towers. To illustrate this, consider an optimal COP of 4.8 in the 7°C/113°C regime.
This COP drops to 3.9 when the consumption of auxiliary equipment is considered. If we change the operating regime to 5°C/11°C, the COP
goes to 3.7 (lowers the evaporator by 2°C, therefore 6% performance).
ABROAD
AIR INTAKE
REFRI
ABROAD
■FRIGE RANTE
WATER TAKING
GLYCOLATED OF
AIR
FRIGE ÍANTE
TAKING OF
AIR
• The compressor
Inlet: low
pressure steam
Inlet: low Exit:
pressure steam compressed
steam
compressed
w
compressed
steam
Entrance;
* steam □
low pressure
Piston compressors
The piston compressor needs to be permanently lubricated. The lower part of the crankcase
forms an oil reserve. The pressure prevailing in the crankcase is the suction pressure. The
oil pump delivers a higher pressure (between 0.5 and 4 bar) than the pressure prevailing in
the crankcase.
The piston compressor is relatively sensitive to the arrival of liquid fluid, since the slightest
drop of liquid on the valves generates continuous and slow wear of the assembly. In the
event of a significant fluid entry, the destruction of the valves is immediate. For this reason,
these devices have anti-liquid shock protection (spring on the cylinder cover, capable of
lifting in case of liquid arrival).
The piston compressor is classified according to its construction into three types: sealed,
semi-sealed and open.
Semi-hermetic construction compressor
This type of equipment is enclosed in a casing equipped with an access cover to carry out
inspections. They are widely used in both commercial refrigeration and air conditioning and
are intended for
scroll compressor
The scroll compressor is made up of two spirals: the first is fixed, attached to the casing,
and the second is rotating. The spirals are 180° out of phase. The moving spiral is driven by
the motor and rotates inside the fixed spiral, forming a gas pocket. This orbital movement
produces a progressive reduction of the gas pocket until its total disappearance, thus
carrying out the compression cycle of the refrigerant.
By having much fewer moving parts than in piston compressors (60% less), there is less
friction, so this compressor is more efficient, low in noise, with little vibration.
This translates into a COP of around 4 on an annual average, while piston compressors have
a COP of approximately 2.5.
Its maximum power is 50 KW but several devices can be installed in parallel up to 300 kW.
To regulate your speed, there are three options:
screw compressor
Source: Bitzer
The volumetric efficiency of a screw compressor is high due to the absence of dead spaces,
as in piston compressors. This property ensures a high compression ratio. It must be well
lubricated to ensure tightness between the different moving parts, reduce noise and also to
cool the coolant. The compression ratio then reaches values of 20 without altering the
refrigerant.
The advantages of the screw compressor are its low wear and easy regulation. However, it is
still an expensive technology. Recently, the screw compressor has been used for power of
20 kW and above.
Centrifugal compressor or turbocharger
They are equipment capable of moving large quantities of air. The centrifugal compressor is
a dynamic type device, not positive displacement like most equipment used in refrigeration
machines. It consists of one or more driving wheels, mounted on an axle and contained
within a casing. The increase in pressure is achieved by conversion from kinetic energy.
Its operating principle is similar to fans or centrifugal pumps.
They do not have very high compression ratios. Its field of application is large air
conditioning installations.
In general, the piston (or reciprocating) compressor is used up to tens of kW. Up to
hundreds of kW, the screw compressor is used, also with positive displacement (or
volumetric), but from hundreds of kW onwards, the centrifugal compressor is used, and in
MW sizes the axial compressor is used.
When oil is not tolerated in the refrigerant gas, it is necessary to resort to the centrifugal
compressor, even in sizes that are the domain of the screw compressor (although oil-free
screw models exist). In cold production systems by compression of refrigerant gas, as in air
compressors, piston and screw compressors are used in smaller sizes. In large sizes,
centrifugal compressors are used, which are mainly used from 400 kW of shaft power.
water condensers
From a technological point of view, water condensers offer more diversity than air
condensers. The transmission coefficient K is higher and the cooling is guaranteed by water
whose specific heat is 4.18.
Bottle exchanger
This type of exchange has two purposes. The first is a liquid storage bottle and the second is
a condenser. It consists of a coil in which the cooling water circulates, the cooling fluid is
stored in the tank where it condenses upon contact with the water tube. The water heating
range is between 8 and 12°C.
Multi-tubular exchange
A large number of horizontal pipes are housed inside a tank and connected at their ends to
two collectors. The water circulates inside the pipes and the cooling fluid through the tank
where it condenses in contact with the water tubes. The advantage of this type of system lies
in the possibility of disassembling the elements, allowing better maintenance of the
assembly.
plate exchanger
air condensers
These exchangers allow superheated vapors from the compressor to change the state of the
refrigerant to liquid.
The superheated gases give up heat energy when they pass through the condenser in
exchange with the air, allowing the condensation of the refrigerant.
Air is an interesting condensation medium since it exists in large quantities. However, its
thermal transmission coefficient is very low, implying large exchange surfaces and air
flows.
The power of the condenser is equal to the sum of the cooling power (evaporator) and the
power of the compressor's electric motor.
Static capacitor
Sprayers or sprinklers
This is the water distribution system that distributes water homogeneously over the fill.
By pressure
This system is generally used in countercurrent towers, and uses nozzles that require a
certain water pressure (above 5 kg/cm²). Its regulation is complex compared to the gravity
system,
Water is sprayed through a series of nozzles located in the upper part of the tower. In order
to size the pump, the manufacturer specifies the water pressure that must be maintained in
these sprinklers.
The water is sprayed through nozzles and, in the same way as for the previous type of
tower, the manufacturer indicates the water pressure required at that point.
Open crossflow and forced draft tower
This tower has large diameter, low speed axial fans. Its transmission is by mail.
Crossflow and induced draft open tower scheme BAC cooling tower model S3000E
From now on we will use the term multipurpose in its "true" meaning to refer to a machine capable of carrying out a total
recovery in the summer season (not of provisional reversal of the cycle, to produce domestic hot water, with the consequent
inevitable losses of efficiency and comfort). It is therefore a so-called "4-tube" machine that must be hydraulically connected
to two different installations: the first will be the heating/air conditioning of the building; the second, the production of
domestic hot water. In general terms, versatility can characterize the air/water or water/water machine, both single-circuit
and double-circuit, monobloc or split version, with ON/OFF compressor or inverter (of the type with permanent magnet
motor, known as BrushLess-DC). .
Considering first, for simplicity, a single-circuit air/water machine, we can summarize the 5 different operating modes of a
"true" multipurpose machine, in the different seasons, as follows:
1. SUMMER SEASON: Production of cold water like a traditional chiller (evaporation by water "terminal use side" and
condensation by air "battery side").
2. SUMMER SEASON: Production of cold water with total recovery of condensation heat (total condensation by water, for
the production of DHW on specific plates).
3. WINTER SEASON: Production of hot water for heating, like a traditional heat pump (air evaporation "battery side" and
water condensation "terminal use side").
4. WINTER SEASON: DHW production momentarily interrupting the production of water for heating (DHW with priority). In
other words, air evaporation "battery side" and water condensation for the production of DHW on specific plates.
5. INTERMEDIATE SEASON: Production of DHW only (both in summer and winter) with battery evaporation.
Below is an image that shows the fundamental diagram of the refrigeration circuit of a multipurpose machine:
The refrigerant path in the different operating modes is regulated by the solenoid valves shown in the figure,
open or closed depending on the required function.
Winter setup
r MA AC AIL NE WANM A
S20c5) !
. cAiztacOdN
S20c5 1
="
LMTMMMENTD i CMIITACON
• SUMMER SEASON: condensation will be done by water in the "source side" exchanger.
• WINTER SEASON: for the production of water for heating, evaporation is carried out in the plate exchanger "source side",
and condensation in the "application side"; The same occurs in the production of domestic hot water, with the natural
displacement of the condensation from the plate exchanger from the installation side to the DHW side.
• INTERMEDIATE SEASON: Production of only DHW with evaporation always in the "source side" plate exchanger.
In water/water versions, the source side can be represented by gravitational water, as well as fluid from a geothermal probe
field, among others.
Finally, in the case of two-circuit machines, it is specified that it is possible for one circuit to work on the production of DHW and
another to continue condensation on the hot water of the heating installation. This solution is the one that offers the greatest
flexibility.
The possible modalities for a two-circuit machine are listed below.
As you can deduce, these are machines that can be used all year round. This is
possible thanks to the adoption of a fairly "flexible" refrigeration circuit
managed by a regulation system that requires particularly advanced hardware
and software.
As mentioned above, DHW production has priority: this means that, regardless
of the working mode on the installation side (heating or cooling), the machine
will be put into DHW mode as soon as it receives the demand signal from the
DHW cylinder probe or a similar thermostat.
First of all, it is remembered that multipurpose units (both ON/OFF and modulating) are NOT suitable for use as "fast" heaters,
and therefore a thermal accumulator will always (necessarily) be required for the production of AC5.
When we talk about the production of domestic hot water, we refer to the storage of thermal energy in a "technical" water
accumulator ; the water for sanitary use must be heated by a stainless steel coil located inside the accumulator; in this way it
avoids the storage of domestic water and it is not necessary to predispose the management of an anti-legionella cycle {for more
detailed information , consult the recommended hydraulic diagrams). This solution, which in our opinion is the most
appropriate, is illustrated in more detail in the section relating to the DHW tank.
Water accumulator
AC5 Accumulator technique
As a clarification, we remember that, if the designer opts for DHW storage, the accumulator must be suitable for the storage of
drinking water and have a coil (on which the multipurpose machine works) with a surface that makes heat exchange possible.
The system is suitable for the power of the machine , considering its working temperatures and the storage temperature of the
DHW in the accumulator. Please remember that the ACS must not come into contact with the hydraulic circuit of the
multipurpose units for any reason (a separation must always be provided).
In this case, in addition, a legionella cycle will have to be managed (the software of the multipurpose units is prepared for this
purpose) generally using an additional heater (e.g. e.g. an electrical resistance). It should be emphasized that this generally
implies a certain waste of energy, which could be avoided with the storage of technical water.
Regarding the control of legionella, we attach an extract from the ''Trento and Be Izano Guidelines for the prevention and
control of legionellosis; Official Bulletin n® 103 of 05.0S.20O0"
In the detailed diagram below, we briefly describe the main components of a multipurpose installation:
Smartphone Web
Multipurpose machine
As said before, it is the core of the multipurpose system. It is a machine with 4 connections and as such, it manages two
completely independent hydraulic circuits: on the one hand there is the production of hot/chilled water, for heating/cooling the
environments; on the other, the production of DHW.
In the machine definition phase, the configuration of the machine can be decided according to what is considered most
appropriate for integration with the installation (for example, the circulation pumps on the installation side and/or DHW side ,
they may be introduced into the machine or installed outside, but they will be managed in any way by the control logic through
contacts in the unit's electrical panel).
Thermal solar panels may be part of the system (connected to the DHW accumulator through a specific coil and then
hydraulically separated from the multipurpose machine) and also another high temperature source, which may feed the
accumulator through a special coil located in the part of above it.
To manage the priority in DHW production, the machine has a temperature probe that must be inserted into a well in the
accumulation tank.
This probe activates DHW production every time the tank temperature drops below a programmable limit value.
Alternatively, the voltage-free contact (connected to the electrical panel oven) can be used, coming from an external
thermostat.
LCP CCM
As mentioned before, the DHW accumulator is only responsible for storing energy in a quantity (and at a temperature) that
guarantees DHW production that covers the daily demand, at the required temperature.
Since there is no DHW storage but only energy storage (which is why we speak of "technical water") the accumulator must
necessarily have a stainless steel coil for instantaneous production.
The exchange surface of said coil must be able to guarantee the production of hot water at at least a minimum comfort
temperature (e.g. e.g. 40°C).
On the contrary, the hydraulic connections for connection to the multipurpose machine will be free of coils: the machine must
work with the full water content of the accumulator.
In this way, the water content of the accumulator itself is sufficient to guarantee the correct operation of the machine (heat
contribution to the DHW without unnecessary AT), also avoiding continuous on/off of the compressor thanks to the reduced
water content of the coil. its limited exchange capacity.
As can be seen in the attached figure, the coil for DHW production will always be the one with the largest surface area.
The solar panel and high temperature coils (optional) have a smaller surface area (due to the higher water
temperatures produced by these sources).
Stratification is essential to ensure not only obtaining the necessary amount of energy, but also (no less important) the
production of DHW at a sufficiently high temperature .
For this, it is necessary that the upper part of the tank is always maintained at a temperature (e.g. e.g. 50 X) higher than that of
produced water (e.g. e.g. 40 °C). In the lower part, however, since the extraction temperature of the water distribution network
is much lower ( e.g. 15 °C), the heat exchange is also sufficient if the temperature of the technical water corresponds to the
recovery of the multipurpose machine .
It is worth making some additional reflections on maximizing efficiency in the use of a coiled accumulator to combine solar
panels.
Surely, in the season of highest radiation, the energy demand for the DHW is largely covered by the operation of the
multipurpose machine in full recovery (as long as, of course, it is used for air conditioning of the environments).
Considering this, the presence of the thermal solar panel would no longer be essential during the hottest season . This does not
apply to the season in which climate control is not required , and therefore the advantage of total recovery is not taken
advantage of. In this period, the solar thermal panel can supply part of the energy for the DHW without (or almost without)
consumption of electrical energy .
This is possible as long as the temperature of the water inside the accumulator, in the zone at. where the solar panel coil is
located, is low enough to guarantee thermal exchange with the water produced by the panel (which no longer has the high
temperatures that can be reached in the season of greatest radiation).
In other words, it is advisable that the lower part of the tank, thanks to the stratification, be at a lower temperature than the
recovery temperature of the multipurpose machine , but above the water inlet temperature of the distribution network. In
practice , one should think of two superimposed zones , with the serpentine lower part and the recovery of the I ACS above the
solar serpentine .
The water from the network that enters the lower part is
heated anyway thanks to the energy provided by the solar
panel, before reaching the upper part of the coil, where the
exchange will be carried out with the technical water heated
by the multipurpose machine. .
In many cases, what is known as a DHW “preparator” is used: it is basically a tank with an external plate exchanger, which heats
the water from the network quickly. The circulation pump in the figure is activated by a flow switch when water enters the
network (after opening the tap), or periodically to maintain the external exchanger plates at the required temperature.
Note: there are applications in which the DHW side accumulator is actually used as a hot water accumulator (from full
recovery), for example to cover an air treatment unit. In this case the rules to be applied are the same as those taken into
account for the buffer tank on the installation side.
Another fundamental aspect is the insulation of the DHW tank : this must limit leaks as much as possible, but also allow the
useful temperature to be maintained for a sufficiently long time: In fact there can be a fairly long time interval between the
"recharging" phase of the tank. and obtaining energy for the ACS. The most common materials are expanded polyurethane with
a thickness of approximately 100 mm and =0.038 W/mK.
In general terms, it is a simple inertia accumulator, with the sole function of having a sufficient water content in the installation
to guarantee correct operation (what this means will be explained later).
In general, there are several installation solutions, some better than others. Specific:
II. Tank in series, in the impulsion (at the machine outlet, towards the use terminals) This solution is characterized by
guaranteeing the reduction of temperature variations towards the installation terminals. The disadvantage is that the working
flow rate of the machine is the same as that of the installation and, if, for example, the terminals have 2-way valves, the flow
imbalances that may arise must be taken into account. If diverter valves (known as 3-way valves) are adopted, the problem does
not arise.
III. Parallel tank (hydraulic decoupling with impulse pump towards the installation) It is the most refined solution, and allows
the working flow of the machine to be disassociated from that of the installation (which can even be set to zero, for example in
the case of start-ups). criticisms, zero thermal demands, etc.). The disadvantage is that installation and regulation are a little
more complex.
1. Reduction of temperature variations towards the terminals of the installation. Although the minimum water content of an
installation can be reduced through the use of sophisticated regulation algorithms, it must not be forgotten that terminals with
low inertia present lower performance with inlet water temperatures "in steps"
For more detailed information on the attenuation of variations, see the appendix "Installation-side accumulator inertia effects".
2. Maintenance of the supply temperature to the terminals in case of interruption of the heating/cooling phase for the priority
assigned to the DHW "call".
3. Reduction of the supply temperature to the terminals, in heating mode, during the defrost phase of the air/water machine,
during the winter season.
This effect can be mitigated by using "terminals" with high thermal inertia, but in other cases it represents a source of
inconvenience for the end user.
As mentioned before, it is possible that the accumulator represented in the diagram also performs the function of "hydraulic
separator" in such a way that the working flow rate of the machine and that of the distribution installation are completely
independent. In this case, it is necessary to pay close attention to the energy losses that are due to the mixing of the drive and
return fluids.
The colored arrows refer to operation in the heating phase (to the left of the tank is the machine that produces
hot water, and to the right is the distribution installation).
In the summer mode, the arrows are inverted: the introduction of the cold water produced is in the lower part of
the accumulator, and the extraction is towards the installation.
NOTE: for all installations with partialization of the use terminals (for example two-way valves in the batteries or
similar) in the different operating conditions, the water content of the installation may vary appreciably. This must
be taken into account when calculating the dimensions of the accumulators.
When we talk about the terminals of the facilities , we do so in the literal I sense, referring to the equipment in
charge of distributing heat in the environments (speaking specifically of the winter season).
It is necessary to make some reflections based on their characteristics ; If we simply consider two types of
terminals, fan coils and underfloor heating installations, we will notice some similarities and some distinctions,
1. The first reflection, common for terminals with high and low inertia, refers to the water temperatures. An
installation based on vapor compression machines will generally not be able to provide water at the same
temperature when external conditions vary. Specifically, operation in "heat pump" mode is affected by the
temperature of the outside air, both for the maximum thermal power and for the maximum temperature of the
water produced. It is therefore necessary, once the most critical conditions for the machine have been
established, evaluate what is the maximum thermal power actually available , the temperature of the discharge
water to the terminals, the integrated thermal power (excluding the defrost phases - as we will see later).
2. Naturally, the selected terminals must guarantee sufficient thermal input, depending on the demand of the
environment, with the temperature of the water actually produced by the machine. Practical problems often arise
because, in critical conditions, in addition to the reduction ( inevitable from the thermodynamic point of view) of
the thermal power of the machine , a decrease in the maximum temperature of the water produced can also be
obtained, with a consequent reduction in the exchange capacity of the terminals, and therefore with an
insufficient contribution to the environment. There are examples of implementations that work perfectly , which
include combinations of radiators and heat pumps, but without a doubt, the selection of the terminals itself must
be done paying close attention precisely to the water temperatures.
3. The speed of bringing the environment into operation must be considered depending on the required use. A
radiant system, in general terms, will not be suitable for applications that require rapid start-up; On the other
hand, a continuous use application can operate with temperatures that are a little more "convenient" from the
point of view of the energy efficiency of the heat engine. In the air conditioning phase, an "on demand" type of
use (as in the case of split and direct expansion systems) is not technically possible.
4. The defrosting phases of air/water machines (defrost) are considered from two points of view: it is necessary
that the integrated power (excluding what has been taken, for defrost, from the installation's water} allows it to
meet the demand and at the same time that the temperature of the water in the installation remains at a value
that allows the terminals to carry out a correct exchange. For high inertia terminals (such as underfloor heating)
their thermal capacity may be sufficient to guarantee the energy reserve necessary for defrost. For low inertia
terminals (for example fan coils) it is necessary to guarantee a sufficient water content (ta I and as described in
the corresponding chapter ).
The figure below illustrates a small installation diagram that represents a floor installation for "sensitive" cooling
(with dew point temperature control) and a fan coil that manages dehumidification, using water at 7' C that
produces the multipurpose machine.
2. To optimize system efficiency, it is NOT necessary for the multipurpose machine to continuously produce
water at a temperature of 7°C; You can also work at slightly higher temperatures (closer to those required by the
radiant part) by modifying the set point only in case of dehumidification demand, for example by an advanced
control, as also managed by the fan coil.
As shown in the figure, the delivery temperature to the radiant part must certainly avoid condensation phenomena
(that is, be higher than the temperature of the return point, which will be determined for example by the control of
the fan coil, through the measurement of relative humidity in the environment and dry bulb temperature).
The compressor of the refrigeration cycle of heat pumps guarantees high thermodynamic performance since it is of the scroll
type.
These compressors, in the versions with continuous variation of the rotation speed, are kept lubricated through a flow of oil,
guaranteed by a minimum pressure difference between the suction and discharge (and not by centrifugal force, as occurs
with fixed speed compressors).
If this pressure difference were to be lacking, the oil would stop passing, causing great risks of seizure in the mechanical
parts. A low pressure alarm in the delivery stops the machine at this moment, to avoid unpleasant consequences. A low
condensing pressure corresponds, for a fluid, to a low temperature and, in fact, if heat is removed too quickly from the
condensing fluid, a drop in its pressure occurs. Therefore, while the heat pump is in heating mode, if the water in the
accumulator is too cold (because the machine has been off for a long time or because it is the first time it is started in the
season or it is not have correctly calculated the dimensions of the accumulator), it will quickly extract the heat to the
condenser fluid. In machines with ON/OFF compressors (constant rotation speed), lubrication can be maintained, but in any
case, due to the drop in evaporation pressure, there is a significant reduction in evaporation pressure with the consequent
activation of useless defrost cycles and also, in any case, the activation of the low pressure switch.
Therefore it is necessary to artificially reduce the heat exchange in the condenser; There are two modalities:
- Use of a recirculation pump with an inverter: this will continuously reduce the flow rate that passes through the heat
pump condenser, reducing the heat exchange, and keeping the temperatures and pressures unchanged at the compressor
outlet. The pump inverter is driven directly by the unit's control processor, which is based on the pressure values recorded at
all times in the condenser.
We recommend this solution as it offers precise control and a reduction in the power consumed by the recirculation pump.
- Use of a three-way valve between the condenser and the accumulator, which allows, if it is open, to have a hot water
bypass (at the condenser outlet) that preheats the cold flow coming from the accumulator. In this case, the flow rate that
passes through the condenser remains constant (it is the temperature that changes) which allows obtaining an effect
analogous to that before in the refrigerant fluid. The three-way valve is managed by generating a signal from a temperature
probe at the condenser inlet, water side. This solution makes the pump operate at a constant speed.
In a horizontal design, air flows horizontally from a wall filled with filters through the side
of wall returns located on the opposite wall. In a vertical design, clean air is pushed
downward from HEPA/ULPA filters located on the ceiling; Air then typically carries
contaminants generated by people and processes into the clean room, and this contaminated
air is drawn into the perforated raised floor panels. The rule for selecting a horizontal or
vertical pattern is that vertically distributed processes require horizontal airflow and
horizontally distributed processes require vertical airflow.
For example, horizontal air is a flow that can be used in operations with strict cleaning
requirements; they occur near the filter wall and operations with lower cleaning
requirements occur further downstream from the filters. In some industries, such as the
pharmaceutical industry, perforated flooring is generally not feasible; Instead, solid
floors and low-level wall returns are most commonly used.
The main places of particle generation are generally not in the HEPA/ULPA filters (unless
there is a leak) but at the working and processing height where people, processes,
equipment, furniture, and particles are emitted. Therefore, the areas immediately below the
HEPA/ULPA filters offer the best air cleaning and the air becomes less clean at lower
elevations.
While personnel, workstations and equipment are inevitable obstacles to airline distortion,
flow lines for empty clean rooms must be designed and arranged with minimal flow
interruptions. Turbulent zones may have stagnation zones with no flow at all (stagnation),
reverse flow, or high velocity. When counter and currents produce stagnant areas, small
particles can clump there and
In this flow pattern, air can be supplied from HEPA filters located at various positions in the
ceiling and returned through low sidewall returns. Ceiling-mounted HEPA filters can be
distributed at equal or near-equal intervals throughout the cleanroom and grouped in critical
process areas. Using HEPA filters in the ceiling without diffusers provides a more direct
flow and therefore cleaner air below; however, cleaning the air away from the area under
the HEPA filters will be worse.
HEPA filters can also be placed in a remote location, such as on the discharge side of an air
handling unit (AHU) or recirculating fan unit (RFU), which provides the HEPA filter.
Air can be drawn directly into the clean room, or they can be placed within an extended
HEPA filter bank downstream and separate from the AHU or RFU with a lower face
velocity through the filters. In both cases, ceiling air diffusers can be used.
MIXED FLOW
As shown in Figure 14.3, mixed flow combines unidirectional and non-unidirectional
airflow in the same room; Separation enclosures such as one-way cabinets (clean benches),
isolators or minienvironments can be used to improve air cleanliness in more critical areas.
Protection of product from particle contamination Maintain personnel process Air cleaning by HEPA filtration:
by personnel or process downstream of the product. 1 .- Product
2 .- Process Area
3 .- Staff
Personal process protection associated with harmful Air cleaning by HEPA filtration:
contaminants 4.- Staff
5.- Process Area
Positioning of upstream 6.- Extraction process
personnel and providing
segregation to allow personnel to
have indirect contact with process
when necessary
Remove harmful contaminants from clean room to Thoroughly provide capture and Air cleaning by HEPA filtration:
protect room occupants eliminate air contaminated by 4.- Staff
particles, gases, chemicals. 5.- Process
Fumes, or microbes, and use of 6.- Extraction of the Enclosure
cleaning filters supplied to the
room.
AHU (Type2A)
n/a
9,8,7 AHU for
1 Simple meet the
requirements of Figure 14.4
AHU
ACH and of
refrigeration
7,6,5,4
2A Primary • AHU
RFU mainly for Figure 14.5
achieve
and with the flow rate of RFU greater equals
AHU secondary requirements of Flow rate of AHU
school cooling
• RFU for
comply with the
ACH requirement
(or speed
average) of the
room
(either
average speed)
of the room
Definitions
RFU: Recirculation fan unit: Recirculation fan unit
AHU: Air handling unit : air handling unit
: MU : Makeup Unit Tertiary handler
FFUs: Fan-Filter-Units :Fan Filter Unit
The design engineer can select a configuration with necessary modifications (such as dual return
paths) that can achieve indoor conditions. Air flows can be combined, diverted or sequentially
combined from both.
The following elements can be considered for the design of the system taking into account the
future commissioning:
• Critical parameters and operational values monitored and tracked.
• Total system power monitored
• Power monitoring of large equipment.
• Shut-off and isolation valves.
• Test ports and sensor locations
• Selected sensor locations for stable operation
Where :
v = Velocity m/s
Q = Flow m3/h
A = Area m2
For non-unidirectional airflows, it is more common to use the air change rate (ACR), often
expressed in air changes per hour (ach):
Where
N = Renewals hour (dimensionless)
Q = flow m3/h
V = Volume of the enclosure m3
Please note that not all unidirectional flow cleanrooms are arranged with 100% ceiling
coverage of HEPA filters, ULPA filters or FFU; some may only have 30% to 90% coverage
of the roof filter. In these cases, the actual air velocity at a process/operating height could be
much lower than the face velocity on HEPA/ULPA filters. From
N _ 60 Q _ 60 y^A _ 60- v I VJ HH
Where :
Q = flow rate, fpm(m3/h)
V = Clean room volume in ft3 (m3)
A = Clean room area ft2 (m2)
v = speed in fpm (m/min)
H = Height of the room ft (m)
N = ACR in the room, time changes
60 = One hour is 60 minutes
Cleanroom designers should be aware that using ACH values to compare two cleanrooms
with different heights is sometimes meaningless. For example, the aerospace industry
uses high-rise clean rooms for aircraft assembly, which could have room heights of 40
to 160 ft (12 to 50 m).
PRESSURE CONTROL IN CLEAN ROOMS
SUMMARY
Clean spaces use room pressurization or depressurization to create desired flow patterns
from less clean rooms to cleaner rooms and to minimize particulate, biological, gaseous,
and/or chemical contamination in the air. It is achieved by mechanically creating air
pressure differences between rooms to cause intentional air movement through the room
leak.
Traditionally, cleanroom pressurization control technologies have been based on intuitive
suggestions rather than well-established guidelines. A pressure differential of 0.05in. toilet
(12.5 Pa) has been used since it was adopted in US Federal Standard (FS) 209A, Cleaning
of Airborne Particles, Cleanrooms and Zone Cleaning (GSA 1966), and the "Clean Spaces"
chapter of the ASHRAE Handbook — HVACApplications (US). USA).
It was assumed that maintaining a closed-door cleanroom enclosure at 0.05 in. toilet (12.5
Pa) differential pressure meant that during door operation the desired flow patterns between
the two rooms would be maintained and that contamination caused by air flowing from the
less clean areas into the clean room would be minimized (even if the pressure differential
decreased significantly) (Sun et al. 3013a). However, using 0.05 in. toilet (12.5 Pa) for each
differential pressure step is believed to be oversimplified and may not be accurate enough
(Sun 2003), especially when a clean room is surrounded by an adjacent less clean area that
could be one, two, three or more, dirtier classes. Therefore, the recommendation is that
clean rooms be surrounded by areas of no more than one class less.
To study the performance of air lock quantitatively, one has to analyze the air flow leakage
through doors in closed and open conditions. The “power equation” is commonly used:
This equation is used to describe air leakage through irregular cracks, such as an air gap between
a door and its frame or through joints between floor and walls, walls and ceiling, ceiling tiles and
celling grids, and wall penetrations for ductwork, conduits and piping , etc.
Another single parameter to quantify the leakage opening is the effective leakage area (ELA). The
definition of ELA and its data tables for building components can be found in ASHRAE Handbook—
Fundamentals (ASHRAE 2017). Once a Q-APdata set is obtained. C and n can be calculated as
follows (Sun 2005):
m mhm
The characteristics of air flows through large designated openings, such as doors, are
somewhat different from those through small crevice openings. The sharp-edged orifice
flow equation is more suitable for describing larger openings (ASHRAE 2017):
Both the power equation and the orifice equation can be presented in a set of curves that
design engineers can easily use. Figure 14.10 illustrates the hole equation in a group of
curves. Among the three variables of leak air rate, differential pressure across the leak path,
and leak area, once two of them are known, the third variable can be identified.
Key relationships in air flow rates between the central AHU and room pressurization
variables can be found in Figure 8.20, where SA is supply air, RA is return air, EA is
exhaust air, FA is relief air and Q is leakage air.
Two mass balance equations can be simplified as volumetric balance equations when air
density is ignored:
The space pressurization index is an indicator of the relative pressurization level. It can be
used to adjust air gains or losses between zones, to organize the desired air flows within a
building.
If a room has multiple leak openings with adjacent rooms, the room pressurization ratio is:
Country-specific GMPs are presented globally, but most, if not all, are based on the US one
below.
• US Guidelines USA, enforced by the US Food and Drug Administration. USA (FDA):
• United States Codeof Federal Regulations, Chapter 1, Title 21, Parts 11,210,211,600–680
and 820 (GPO2016c)
• ISO 14644, Clean rooms and associated controlled environments (ISO2016)
• European guidelines, imposed by the European Medicines Agency (EMA):
• EU Guidelines on Good Manufacturing Practice: Medicinal Products for Human and
Veterinary Use, Volume 4 f EudraLex
The Rules Governing Medicinal Products in the European Union(EudraLex)(EC2010)
• Annex 1: Manufacture of style medicinal products products
• Annex 2: Manufacture of biological active substances and medicinal products for human
use
The type of enjoyment of the person who is at the level of the vein is a type of enjoyment.
Strong collaboration and harmonious coordination has been observed across the world.
GMP standard rules among other regulatory agencies of various countries, but it has been
shown that there is a lot of discussion.
The ISO 14644 series, however, points out the essential requirements of the company, that
is, different from the ISO14644-1 and 14644-2 standards. It is important for the community
Non-sterile products include pellets, capsules, liquids, topi-cals, and non-invasive medical
devices and supplies. Stated above, the objectives of pharmaceutical products and room
design and corrosion resistance are proposed.
Administrative
Administrative areas, conference rooms, locker rooms, cafeterias and other support
functions. The air conditioning system for these purposes has been designed to meet the
basic comfort requirements of employees.
Laboratory
The laboratory may require close monitoring to identify classified spaces, including
adjacent corridors and administrative spaces, depending on the function (for additional
discussion see Section 19.3.5).
Storage
The HVAC is designed so that minimum requirements for the materials being stored are
met.
The requirements for the state of service are therefore simulated manufacturing, for
example, the materials being processed are generally class 8 (grade C) equivalent
(ISO2015).
An inadequately designed installation, the transition point between the two, software and
manufacturing, and the cost of the installation, was performed and evaluated at a location
where the device was inspected.
Typically, a high value area will be used in a flow cabinet (DFB) designed to create a
mining environment atmosphere in the living room. Emergency actions have been used in
the lower part, within which a flow of light is shown in the background of the city.
In the design of new functions, processing equipment can be designed to protect first-level
protection for the product, by using material transfer systems of a pair of counters and other
types of control security elements.
Primary packaging
Once materials are processed into bulk products, they must be packaged. Once again, the
focus should be on protecting the product and the product contact surfaces (in this case, the
inside of the packaging materials), as the package now becomes an additional contact
surface. case of solid dosage forms, current designs for packaging lines, including the
limitation on a filling suite found with the same ISO Class 8.
Below we show a typical example of different types of UMAS.
Altitu
DAIKIN Specific volume (m'/kg) Absolute humidity
de •When Relative humidity (%) 100 90 80 70 (kg/kg)
Altitu passing 60
—0,05!
Point definition
de through
Point name [P3 Add Edit Delete
Dry bulb Data point (P1) Dry
0,051
temperature bulb temperature 35.0°
RH %[30,0< > Wet bulb C
Flow nffli 19800 ,< temperature Dew 28,2°
001!
-0 01
-0 00
Density (kg/m 1 )
Wet bulb temperature (°C)
Enthalpy (kcal/kg)
0,8 0w 0,9 0,9 O
80 20 40
OOI
The savings are achieved because the UMA is only used to cool the air or to overcome the sensible Thermal Load and the Fan only produces a
small 17.41°C to 17°C. Obtaining a saving of 74% compared to the initial configuration.
1. Psychrometric points
P1 P2 PP1 P3
Dry bulb temperature 35.0°C Dry bulb temperature 22.0°C Dry bulb temperature 25.1°C Dry bulb temperature 7.0°C
Wet bulb temperature 28.2°C Wet bulb temperature 13.9°C Wet bulb temperature 18.0°C Wet bulb temperature 5.5°C
Dew point 26.1°C Dew point 7.8°C Dew point 14.1°C Dew point 3.8°C
RH 60,0% RH 40,0% RH 50,4% RH 80,0%
Absolute humidity 0.0214kg/kg Absolute humidity 0.0066kg/kg Absolute humidity 0.0100kg/kg Absolute humidity 0.0050kg/kg
Enthalpy 21.5kcal/kg Enthalpy 9.3kcal/kg Enthalpy 12.1kcal/kg Enthalpy 4.7kcal/kg
Density 1,131kg/m s Density 1,191kg/m s Density 1,177kg/m 3 Density 1,256kg/m 3
specific volume 0.903m'/kg specific volume 0.845m'/kg Specific volume 0.858m 3 /kg Specific volume 0,800m 3 /kg
Pressure 101325,OPa Pressure 101325,OPa Pressure 101325,OPa Pressure 101325,OPa
Flow 1472m'/h Flow 4582m3/h Flow 6054m 3 /h Flow 6054m3/h
PP2 P4 PP3 P5
Dry bulb temperature 25.1°C Dry bulb temperature 23.0°C Dry bulb temperature 17.9°C Dry bulb temperature 12.0°C
Wet bulb temperature 13.6°C Wet bulb temperature 14.7°C Wet bulb temperature 12.0°C Wet bulb temperature 8.2°C
Dew point 3.8°C Dew point 8.7°C Dew point 7.3°C Dew point 4.5°C
RH 25,2% RH 40,0% RH 49,7% RH 60,0%
Absolute humidity 0.0050kg/kg Absolute humidity 0.0070kg/kg Absolute humidity 0.0063kg/kg Absolute humidity 0.0052kg/kg
Enthalpy 9.0kcal/kg Enthalpy 9.8kcal/kg Enthalpy 8.1kcal/kg Enthalpy 6.0kcal/kg
Density 1,180kg/m 3 Density 1,187kg/m 3 Density 1,208kg/m 3 Density 1,234kg/m 3
Specific volume 0.852m'/kg Specific volume 0.848m 3 /kg Specific volume 0.833m 3 /kg Specific volume 0.815m'/kg
Pressure 101325,OPa Pressure 101325,OPa Pressure 101325,OPa Pressure 101325,OPa
Flow 6054m'/h Flow 13746m 3 /h Flow 19800m 3 /h Flow 19800m 3 /h
PP4
Dry bulb temperature 17.9°C
Wet bulb temperature 10.9°C
Dew point 4.5°C
RH 41,0%
Absolute humidity 0.0052kg/kg
Enthalpy 7.5kcal/kg
Density 1,209kg/m'
Compared to spaces air conditioned for thermal comfort, clean rooms control other
variables in dry bulb temperature, relative humidity, and particle concentrations. It is
a difficult task to achieve those requirements with minimum energy consumption,
especially when different parameters interfere with each other. A significant amount
of energy would be wasted if the system is not properly designed and controlled.
Firstly, this document provides an overview and discussion of the essential elements
for the design and control of cleanroom air conditioning systems. Existing systems
and controls are classified into three typical options and their performances are based
on different conditions and loading conditions.
For a new design, the fully decoupled option is the preferred option for wetter areas.
The results of the analysis are applied in a modernization project for a
pharmaceutical factory located in Hong Kong, a humid subtropical city, which used
the "interactive option". This system is proposed to operate as a "partially decoupled
option" in this retrofit project requiring no modification to existing hardware. The
upgraded system option has been tested, providing reductions of 69.6% and 87.8%
in cooling and heating respectively.
Extensive comparison tests are performed on a dynamic Matlab/Simulink-based
platform.
DM
M2(S)
Theoretically, Option C reaches the limit of energy efficiency, because it completely decouples temperature and humidity control in the
system. It is recommended for new systems.
Although option B has the same performance with option C in the analyzed condition, its dehumidification capacity is limited to the amount
of fresh air flow.
Since the system configuration of Option B is almost the same as that of Option A, it is considered for modernization projects where the
system configuration of Option A is originally designed, according to the modernization project case reported in this document. Hereinafter,
the control method of option A is called the “reference method” and the control method of option B is called the “proposed method”.
• Classes C and D
Clean areas for less critical cases in the
production of sterile products.
I = equivalent to injection or supply of air,
generally obtained by hourly renewals or
by Thermal Load (m3/h)
E = Expulsion, encompasses general air
extraction, bathroom extraction, dust
extraction or air return (m3/h)
a.- Room 1
I1 = QF1 + E 1
E1 = I1 – QF1
b.- Lock 1
qf1 + I2 = qf2 + E2
E2 = I2 – ( qf1 – qf2)
c.- Room 2
qf2 + I3 = qf3 + E3
E3 = I3 – (qf2 – qf3)
E uma 01 = I1 – QF1
TYPICAL APPLICATIONS
Guy of ISO class Flow relationship between units Scheme type
HVAC configuration
Airflow amount
for
Room air
cleanliness
and total
cooling load
n/a
1 Simple AHU 9,8,7 AHU to meet
ACH and TO
refrigeration
requirements
TYPICAL APPLICATIONS
3 Primary RFU,
4,3,2 • The support
secondary AHU, and
tertiary unit ,1 AHU complies
support
requirements of Flow rate of RFU > 10
outside air, Flow rate of AHU “
pressurization or and
• AHU to meet
cooling
requirements
Figure A
Figure B
Figure C
Figure D
Step 5
Obtain the selections of the cooling equipment, both AHU, MU and RFU,
eit
he
r-
A design consideration for air includes temperature and humidity control. High
temperatures and humid environments can encourage microbial growth, where
microorganisms are deposited from the airstream onto surfaces. These parameters are
controlled through HVAC systems. Air conditioning systems normally have two preheating
batteries. The first battery recovers waste heat from the chillers, while the second
supplements this as needed, followed by an aerosol humidifier and finally a cooling battery.
Heating and cooling batteries are used for temperature control only.
Filtration
Filtration eliminates microorganisms. In clean rooms, this is achieved through HEPA filters,
which are designed to remove up to 99.997% of particles from the air. HEPA filters are
protected from blocking by pre-filters, which remove up to approximately 90% of particles
from the air. Therefore, if the air contains approximately 3 x 10 8 particles per m3, and there
is a prefilter and a HEPA filter, the prefilter removes a sufficient number of particles to
leave approximately 3 x 10 7 per m3 as a challenge for the HEPA filter . The terminal
HEPA filter will leave approximately 10 3 per m3 to enter the clean room. In the US
Figura 4: Illustration of air movement: UDAF (laminar flow) unit within a turbulent
flow clean room
Environmental monitoring
With critical air control parameters established within the clean room and physical
monitoring established to ensure the HVAC system is operating as designed, the
clean room should be subject to environmental monitoring to demonstrate whether
the room remains under control (ISO 14.644 -1). Monitoring consists of:
• Particle monitoring
• Viable monitoring
With particle monitoring, this is carried out using mobile optical particle counters or
particle counters linked to a facility monitoring system (FMS). Locations for
monitoring are selected by covering representative areas in the room or by orienting
monitoring towards the main activities within the room.
Rut : 10,544,078-2
0: cell: 9 41353221
0: [email protected]
Profile and Competencies
Mechanical Civil Engineer from the Pontifical Catholic University of Valparaiso, Professional Energy
Manager (PEM) USA, Master in Energy Efficiency of Buildings (Spain). Master in Environment and
Sustainable Management ( Spain), more than 24 years of experience in commercial and industrial facilities
systems. Of which around 15 years in Works, projects, consultancies, technical inspection in National
Hospitals and Clinics , in addition to having a strong orientation to Energy Efficiency Projects in air
conditioning, Clean Rooms, data Center, solar energy, health, electricity, currents weak, centralized control
and some residential photovoltaic projects.
Professional with great management of interpersonal relationships , ability to work as a team and form high-
performance teams , leadership, customer orientation, achievement orientation, great communication and
negotiation skills, proactivity, self-motivation and positive attitude.
Experience in Administration of large-scale Contracts , such as Solar Panel Plants, Hydroelectric Power
Plants in the past and now recently Ezequiel Gonzales Cortes Hospitals ( 52,000 m2), Curlcó Hospital Project
Phase ( 102,000 m2) and Gustavo Frike Hospital ( 92,000 m2), I have knowledge of ISO 9001, 14,001 and
50,001 quality standards.
In addition to managing the regulations specific to the specialties, such as UNE Standard, ASHRAE, ASME,
GMPs ( Good Manufacturing Practices ) , etc.
Public and private hospitals, and knowledge finished in Certifications of indoor air quality of surgical
pavilions , among which we can highlight the Mutual de Seguridad, Clínica de los Andes, Clínica and
Hospital de la Católica, Hospital de la Universidad de Chile, German Clinic of Santiago and Temuco, Naval
Hospital of Viña del Mar. Which has meant that I have to get certified in all the International Regulations of
the USA and Spain, both in Ashrae St 62.1, ISO Standard 14.644-1-2-3-4-5, UNE 1713 30-1, UNE 171530-2,
UNE 171,340, UNE 100012.
Including certifications in the US in fungi, bacteria, molds, VOCs , etc., in the field of energy efficiency I am
certified in 120 specialties ( Centralized Control, Pumps, Air Conditioning, boilers, etc.).
2014 PEM ( Project Manager Energy) United States Energy Institute , certification in HVAC Systems and
Schneiders data Center .