0% found this document useful (0 votes)
128 views38 pages

Powerflex 750-Series Safe Torque Off Option Module: User Manual

Uploaded by

danschul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
128 views38 pages

Powerflex 750-Series Safe Torque Off Option Module: User Manual

Uploaded by

danschul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 38

PowerFlex 750-Series Safe

Torque Off Option Module


Catalog Number 20-750-S

User Manual Original Instructions


PowerFlex 750-Series Safe Torque Off Option Module User Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).

2 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Table of Contents

Preface
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Chapter 1
Safety Concept Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Important Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Safety Category 3 Performance Definition . . . . . . . . . . . . . . . . . . . 10
Stop Category Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Performance Level and Safety Integrity Level (SIL) 3 . . . . . . . . . 11
Proof Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PFD and PFH Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safe State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Safety Reaction Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Considerations for Safety Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Contact Information if Safety Option Failure Occurs . . . . . . . . . . . . 14

Chapter 2
Installation and Wiring Remove Power to the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Access the Control Pod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Set the Safety Enable Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Install the Safety Option Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wire the Safety Option Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Power Supply Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Verify Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Chapter 3
Safe Torque Off Option Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Operation Stop Category Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Appendix A
Specifications, Certifications, and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
CE Conformity Environmental Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Machinery Directive (2006/42/EC) . . . . . . . . . . . . . . . . . . . . . . . . 34
EMC Directive (2014/30/EU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 3


Table of Contents

Notes:

4 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Preface

This manual explains how the PowerFlex® 750-Series Safe Torque Off option
module can be used in Safety Integrity Level (SIL) 3, Performance Level [PLe],
or Category (cat.) 3 applications. It describes the safety requirements, including
PFD and PFH values and application verification information, and provides
information on installing, configuring, and troubleshooting the Safe Torque
Off option module.

Use this manual if you are responsible for designing, installing, configuring, or
troubleshooting safety applications that use the PowerFlex 750-Series Safe
Torque Off option module.

The 20-750-S Safe Torque Off option module applies to the following
PowerFlex 750-Series drives:
• PowerFlex 755TL low harmonic, non-regenerative drives
• PowerFlex 755TR regenerative drives
• PowerFlex 755TM drive systems with regenerative bus-supplies and
common-bus inverters
• PowerFlex 755 AC drives
• PowerFlex 753 AC drives

Throughout this manual, PowerFlex 755T drive products is used to refer to


PowerFlex 755TL drives, PowerFlex 755TR drives, and PowerFlex 755TM
drive systems.

We recommend that you have a basic understanding of the electrical circuitry


and familiarity with these products. You must also be trained and experienced
in the creation, operation, and maintenance of safety systems.

Summary of Changes This manual contains new and updated information as indicated in the
following table.

Topic Page
Updated Important statement in the Set the Safety Enable Jumper section to describe behavior if 18
jumper is not set correctly and list drives which do not have the jumper.
Added Environmental Pollution Degree Description (EN 61800-5-1) table to Appendix A. 32

Conventions In this manual, we list configuration parameters by number followed by the


name in brackets. For example, P24 [OverSpd Response].

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 5


Preface

Terminology This table defines abbreviations that are used in this manual.

Abbreviation Full Term Definition


1oo2 One out of Two Refers to the behavioral design of a dual-channel safety system.
cat. Category Classification of the safety-related parts of a control system in respect of their resistance to faults and
their subsequent behavior in the fault condition, and which is achieved by the structural arrangement
of the parts, fault detection, and/or by their reliability (source EN ISO 13849-1).
CL Claim Limit The maximum SIL rating that can be claimed for a Safety-Related Electrical Control System subsystem
in relation to architectural constraints and systematic safety integrity (source IEC 62061).
DCavg% Diagnostic Coverage Ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous
failures. (source IEC 61508).
EN European Norm The official European Standard.
ESD Emergency Shutdown Systems A system, usually independent of the main control system, that is designed to shut down an operating
system safely.
HFT Hardware Fault Tolerance The HFT equals n, where n+1 faults could cause the loss of the safety function. An HFT of 1 means that
2 faults are required before safety is lost.
HIM Human Interface Module A module used to configure a device.
IEC International Electrotechnical Commission The International Electrotechnical Commission (IEC) is the world’s leading organization that prepares
and publishes International Standards for all electrical, electronic, and related technologies.
IGBT Insulated Gate Bi-polar Transistors Typical power switch used to control main current.
ISO International Organization for Standardization The International Organization for Standardization is an international standard-setting body that is
composed of representatives from various national standards organizations.
MTTFD Mean Time to Failure The average length of time before a device has a dangerous failure.
PELV Protective Extra Low Voltage An electrical system where the voltage cannot exceed ELV under normal conditions, and under single-
fault conditions, except earth faults in other circuits. PELV is defined in IEC 61131-2.
PFD Probability of Dangerous Failure on Demand The average probability of a system to fail to perform its design function on demand.
PFH Average Frequency of a Dangerous Failure per Hour The average frequency of a system to have a dangerous failure occur per hour.
PL Performance Level EN ISO 13849-1 safety rating
SELV Safety Extra Low Voltage Circuit A secondary circuit that is designed and protected so that, under normal and single fault conditions, its
voltages do not exceed a safe value. SELV is defined in IEC 61010-2-201.
SIL Safety Integrity Level A measure of a products ability to lower the risk that a dangerous failure could occur.
STO Safe Torque Off The Safe Torque Off (STO) function is used to prevent unexpected motor rotation if there is an
emergency while the drive remains connected to the power supply. When STO is activated, the torque
power cannot reach the drive, thus stopping and preventing any motor shaft rotation.

6 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Preface

Additional Resources These documents contain additional information concerning related


Rockwell Automation products.
Resource Description

PowerFlex Safe Speed Monitor Safety Reference Manual, publication 750-RM001 Provides information on installing and configuring the safe speed monitor option module with
PowerFlex 750-Series drives.
System Design for Control of Electrical Noise Reference Manual, Information, examples, and techniques that are designed to minimize system failures caused by
publication GMC-RM001 electrical noise.
Safety Guidelines for the Application, Installation, and Maintenance of Solid Describes important differences between solid-state control and hardwired electromechanical
State Control, publication SGI-1.1 devices.
Enhanced PowerFlex 7-Class Human Interface Module (HIM) User Manual, Provides information for using the 20-HIM-A6 Human Interface Module to configure
publication 20HIM-UM001 PowerFlex 750-Series drives and the Safe Torque Off option module.
Online Help that provides a description of the different elements of the Connected Components
Connected Components Workbench Online Help Workbench™ software.
PowerFlex 750-Series Products with TotalFORCE® Control Technical Data, Provides detailed information on:
publication 750-TD100 • Drive and bus supply specifications
• Option specifications
• Fuse and circuit breaker ratings
PowerFlex 750-Series Products with TotalFORCE Control Installation Provides the basic steps to install PowerFlex 755TL drives, PowerFlex 755TR drives, and
Instructions, publication 750-IN100 PowerFlex 755TM bus supplies.
PowerFlex 755TM IP00 Open Type Kits Installation Instructions, Provides instructions to install IP00 Open Type kits in user-supplied enclosures.
publication 750-IN101
Provides detailed information on:
PowerFlex Drives with TotalFORCE Control Programming Manual, • I/O, control, and feedback options
publication 750-PM100 • Parameters and programming
• Faults, alarms, and troubleshooting
PowerFlex 755TM IP00 Open Type Kits Technical Data, publication 750-TD101 Provides detailed information on:
• Kit selection
• Kit ratings and specifications
• Option specifications
Provides detailed information on:
• Packaged drive specifications
PowerFlex 750-Series AC Drives Technical Data, publication 750-TD001
• Option specifications
• Fuse and circuit breaker ratings
Provides information on installing the Safe Torque Off option module in PowerFlex 750-Series
PowerFlex 750-Series AC Drive Installation Instructions, publication 750-IN001 drive.
PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001 Provides information on mounting, installing, and configuring PowerFlex 750-Series drives.
Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates, and other certification details

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 750-UM002J-EN-P- February 2021 7


Preface

Notes:

8 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 1

Safety Concept

This chapter describes the safety Performance Level concept and how the
PowerFlex® 750-Series Safe Torque Off option module meets the requirements
for SIL 3, or cat. 3, PLe applications.

Topic Page
Certification 9
Proof Tests 11
PFD and PFH Definitions 12
Safety Data 12
Safe State 13
Safety Reaction Time 13
Considerations for Safety Ratings 14
Contact Information if Safety Option Failure Occurs 14

Certification The PowerFlex 750-Series Safe Torque Off option module is certified for use in
safety applications up to and including SIL 3 according to EN/IEC 61800-5-2,
IEC 61508, and SIL CL3 according to EN 62061, Performance Level PLe, and
Category 3 according to EN ISO 13849-1. Safety requirements are based on
the standards current at the time of certification.

The TÜV Rheinland group has approved the PowerFlex 750-Series Safe
Torque Off option module for use in safety-related applications where the de-
energized state is considered to be the safe state. The examples in this manual
are based on achieving de-energization as the safe state for typical Machine
Safety and Emergency Shutdown (ESD) systems.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 9


Chapter 1

Important Safety Considerations

The system user is responsible for the following:


• Set-up, safety rating, and validation of any sensors or actuators
connected to the system
• Complete system-level risk assessment and reassess the system any time a
change is made
• Certification of the system to the desired safety Performance Level
• Project management and proof testing
• Program the application software and the safety option module
configurations in accordance with the information in this manual
• Access control to the system
• Analyze all configuration settings and choose the proper setting to
achieve the required safety rating

IMPORTANT When applying Safety, restrict access to qualified, authorized personnel


who are trained and experienced.

ATTENTION: When designing your system, consider how personnel exit the
machine if the door locks while they are in the machine. Additional
safeguarding devices may be required for your specific application.

Safety Category 3 Performance Definition

To achieve Safety Category 3, according to EN ISO 13849-1, design the safety-


related parts according to these guidelines:
• The safety-related parts of machine control systems and/or their
protective equipment, and their components, shall be designed,
constructed, selected, assembled, and combined in accordance with
relevant standards so that they can withstand expected conditions
• Basic safety principles shall be applied
• A single fault in any of its parts does not lead to a loss of safety function.
• The average diagnostic coverage of the safety-related parts of the control
system shall be medium
• The mean-time to dangerous failure of each of the redundant channels
shall be high
• Measures against common cause failure shall be applied

10 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 1

Stop Category Definitions

Conduct a risk assessment to determine the selection of a stop category for


each stop function.
• Stop Category 0 is achieved with immediate removal of power to the
actuator. This results in an uncontrolled coast-to-stop. Safe Torque Off
accomplishes a Stop Category 0 stop.
• Stop Category 1 is achieved with power available to the machine
actuators to achieve the stop. Power is removed from the actuators when
the stop is achieved.

IMPORTANT When designing the machine application, consider timing and distance for a
coast-to-stop (Stop Category 0 or Safe Torque Off). For more information
regarding stop categories and Safe Torque Off, refer to EN 60204-1 and
EN/IEC 61800-5-2, respectively.

Performance Level and Safety Integrity Level (SIL) 3

For safety-related control systems, Performance Level (PL), according to


EN ISO 13849-1, and SIL levels, according to IEC 61508 and EN 62061,
include a rating of the ability of the system to perform its safety functions. All
safety-related components of the control system must be included in both a
risk assessment and the determination of the achieved levels.

See the EN ISO 13849-1, IEC 61508, and EN 62061 standards for complete
information on requirements for PL and SIL determination.

Proof Tests The safety standards require that proof tests be performed on the equipment
that is used in the system. Proof tests are performed at user-defined intervals
and are dependent upon PFD and PFH values.

IMPORTANT Your specific application determines the time frame for the proof test
interval.
Verify operation of safety function after drive installation, modification, or
maintenance. See Verify Operation on page 22 for more information.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 11


Chapter 1

PFD and PFH Definitions Safety-related systems can be classified as operating in either a Low Demand
mode, or in a High Demand/Continuous mode.
• Low Demand mode: where the frequency of demands for operation that
are made on a safety-related system is no greater than one per year or no
greater than twice the proof test frequency.
• High Demand/Continuous mode: where the frequency of demands for
operation that are made on a safety-related system is greater than once
per year or greater than twice the proof test interval.

The SIL value for a low-demand safety-related system is directly related to


order-of-magnitude ranges of its average probability of failure to perform its
safety function satisfactorily on demand or, simply, average probability of a
dangerous failure on demand (PFD). The SIL value for a High Demand/
continuous mode safety-related system is directly related to the average
frequency of a dangerous failure occurring per hour (PFH).

Safety Data PFD and PFH calculations are based on the equations from Part 6 of
IEC 61508.

These tables provide data for a 20-year proof test interval and demonstrate the
worst-case effect of various configuration changes on the data.

IMPORTANT Determination of safety parameters is based on the assumptions that the


system operates in High-demand mode and that the safety function is
requested at least once every year.

Table 1 - PFD and PFH for PowerFlex 753 and PowerFlex 755 Drives
PowerFlex 753 and PowerFlex 755 Drives PowerFlex 755 Drives PowerFlex 755 Drives
Attribute PowerFlex 755 Drives Frame 8 Frame 9 Frame 10
Frames 1…7
PFDavg 3.29E-5 1.73E-4 2.65E-4 3.56E-4
PFH (1/hour) 3.75E-10 1.99E-9 3.04E-9 4.09E-9
SIL 3 3 3 3
PL e e e e
Category 3 3 3 3
MTTFDyears 143 171.9 104.4 75.5
DCavg% 99 (high) 97.4 (high) 97.5 (high) 97.5 (high)
HFT 1 (1oo2) 1 (1oo2) 1 (1oo2) 1 (1oo2)
Mission time 20 years 20 years 20 years 20 years

12 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 1

Table 2 - PFD and PFH for PowerFlex 755T Drive Products


Drive Frame Drive Frame Drive Frame Drive Frame Drive Frame Drive Frame Drive Frame Drive Frame Drive Frame
Attribute 5 and 6 7 and 8 9 10 11 12 13 14 15
PFDavg 3.70E-5 2.48E-4 2.74E-4 3.00E-4 3.26E-4 3.52E-4 3.77 E-4 4.29 E-4 4.81 E-4
PFH (1/hour) 4.22E-10 2.86E-9 3.15E-9 3.45E-9 3.75E-9 4.05E-9 4.34 E-9 4.94 E-9 5.54 E-9
SIL 3 3 3 3 3 3 3 3 3
PL e e e e e e e e e
Category 3 3 3 3 3 3 3 3 3
MTTFDyears 1055.5 (high) 186.7 (high) 142.7 (high) 115.5 (high) 97.0 (high) 83.7(high) 73.5 (high) 59.2 (high) 49.5 (high)
DCavg% 94.8 (high) 96.3 (high) 96.4 (high) 96.6 (high) 96.6 (high) 96.6 (high) 96.7 (high) 96.7 (high) 96.7 (high)
HFT 1 (1oo2) 1 (1oo2) 1 (1oo2) 1 (1oo2) 1 (1oo2) 1 (1oo2) 1 (1oo2) 1 (1oo2) 1 (1oo2)
Mission time 20 years 20 years 20 years 20 years 20 years 20 years 20 years 20 years 20 years

Safe State The safe state encompasses all operation that occurs outside of the other
monitoring and stopping behavior that is defined as part of the Safe Torque
Off option module.

If a Safe State fault is detected, the safety option module transitions to the safe
state. This includes faults that are related to the integrity of hardware or
firmware. The drive safe state is defined as preventing force-producing power
from being provided to the motor. For more information on the safe state, see
EN/IEC 61800-5-2.

IMPORTANT The drive is in the safe state if the safety function is installed and the drive
status is ‘Not Enabled’. Drive ‘Ready’ is NOT a safe state even if there is no
motion.

ATTENTION: In circumstances where external influences (for example,


falling of suspended loads) are present, additional measures (for example,
mechanical brakes) can be necessary to help prevent a hazard.

Safety Reaction Time The safety reaction time is the length of time from a safety-related event as
input to the system until the system is in the safe state.

The safety reaction time from an input signal condition that triggers a safe
stop, to the initiation of the configured Stop Type, is shown in Table 3.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 13


Chapter 1

Table 3 - Safety Reaction Time


Drive Family Value, Max
PowerFlex 753 drives 10 ms
Frames 1…7
PowerFlex 755 drives 10 ms
Frames 1…10
PowerFlex 755TL drives,
PowerFlex 755TR drives, and
10 ms
PowerFlex 755TM drive systems
Frames 7…15
PowerFlex 755TL drives
20 ms
Frames 5, 6

IMPORTANT An input signal condition that is present for less than the reaction time
cannot result in the safety function being performed. Repeated requests of
the safety function for less than the reaction time can result in a spurious
detection of a fault.

Figure 1 - Safety Reaction Timing Diagram


SE
SP

Safe Torque Off


Safety Reaction Time

Considerations for Safety The achievable safety rating of an application using the safety option module
installed in PowerFlex 750-Series drives is dependent upon many factors, drive
Ratings options, and the type of motor.

For applications that rely on the immediate removal of power to the actuator,
which results in an uncontrolled coast-to-stop, a safety rating up to and
including SIL 3, PLe, and Category 3 can be achieved.

Contact Information if Safety If you experience a failure with any safety-certified device, contact your local
Allen-Bradley distributor. With this contact, you can do the following:
Option Failure Occurs
• Return the device to Rockwell Automation so the failure is
appropriately logged for the catalog number that is affected and a record
is made of the failure.
• Request a failure analysis (if necessary) to determine the probable cause
of the failure.

14 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 2

Installation and Wiring

This chapter provides installation, jumper settings, and wiring for the
PowerFlex® 750-Series Safe Torque Off option module.

Topic Page
Remove Power to the System 16
Access the Control Pod 16
Set the Safety Enable Jumper 18
Install the Safety Option Module 19
Wire the Safety Option Module 20
Verify Operation 22

ATTENTION: The following information is merely a guide for proper


installation. Rockwell Automation cannot assume responsibility for the
compliance or the noncompliance to any code, national, local or otherwise
for the proper installation of this equipment. A hazard of personal injury
and/or equipment damage exists if codes are ignored during installation.

IMPORTANT Installation must be in accordance with the instructions in this user manual
and the installation instructions for your drive. Only qualified, authorized
personnel that are trained and experienced in safety can plan, implement,
and apply safety systems.

IMPORTANT During installation and maintenance, check your drive firmware release
notes for known anomalies and verify that there are no safety-related
anomalies.

The PowerFlex 750-Series Safe Torque Off option module is intended to be


part of the safety-related control system. Before installation, perform a risk
assessment that compares the PowerFlex 750-Series Safe Torque Off option
module specifications and all foreseeable operational and environmental
characteristics of the control system.

A safety analysis of the machine section that is controlled by the drive is


required to determine how often to test the safety function for proper
operation during the life of the machine.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 15


Chapter 2

Remove Power to the System Before performing any work on this drive, remove all power to the system.

ATTENTION:
• Electrical Shock Hazard. Verify that all sources of AC and DC power are de-
energized and locked out or tagged out in accordance with the requirements
of ANSI/NFPA 70E, Part II.
• To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged before performing any work on the drive. Measure
the DC bus voltage at the +DC and -DC terminals or test points. The voltage
must be zero.
For the location of the terminal block and test point sockets, see the manual for
your drive:
• PowerFlex 750-Series AC Drives Installation Instructions, publication
750-IN001.
• PowerFlex 750-Series Products with TotalFORCE Control Installation
Instructions, publication 750-IN100.
• PowerFlex 755TM IP00 Open Type Kits Installation Instructions, publication
750-IN101.
• In Safe Torque Off mode, hazardous voltages may still be present at the
motor. To avoid an electric shock hazard, disconnect power to the motor and
verify that the voltage is zero before performing any work on the motor.

Access the Control Pod The option module is installed in the drive control pod. Different drives have
different ways to access the control pod.

To access the control pod, follow these steps.


1. Open the door or remove cover.
2. Loosen the retention screw on the HIM cradle.

16 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 2

3. Lift the cradle until the latch engages.

Panel-mounted Drives

Drives in Cabinet Enclosures

See the installation instructions for your drive for more information.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 17


Chapter 2

Set the Safety Enable Jumper The PowerFlex 750-Series drives ship with the safety-enable (SAFETY)
jumper installed. The jumper, which is on the main control board, must be
removed when using the Safe Torque Off option module or a Safety Jumper In
fault (F213) occurs.

IMPORTANT A fault occurs on power up if the SAFETY Enable jumper is not set correctly.
PowerFlex 755 drives (frames 8…10) control boards do not have a SAFETY
jumper.

Figure 2 - PowerFlex 753 Drive Jumper Locations


SAFETY Enable
Hardware ENABLE (jumper in place)
(jumper removed)

PowerFlex 753 AC Drive

Figure 3 - PowerFlex 755 Drive Jumper Locations (Frames 1…7 only)


SAFETY Enable
(jumper removed)

PowerFlex 755 AC Drive

Hardware ENABLE (jumper in place)

PowerFlex 755 drives (frames 8, 9, and 10) do not have a safety enable jumper.

18 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 2

Figure 4 - PowerFlex 755T Drive Products Jumper Locations


SAFETY Enable
(jumper removed)

PowerFlex 755TL,
PowerFlex 755TR, and
PowerFlex 755TM Control Pod

Hardware ENABLE
(jumper in place)

Install the Safety Option To install the Safe Torque Off option module:
Module 1. Firmly press the module edge connector into the desired port.

IMPORTANT The Safe Torque Off option module can be installed in any drive port.
However, when used in an integrated motion application, the
module must be installed in port 6.

IMPORTANT Only one safety option module can be installed at a time. Installing
multiple or duplicate safety option modules is not supported.

2. Tighten the top and bottom retaining screws.


– Recommended torque = 0.45 N•m (4.0 lb•in)
– Recommended screwdriver = T15 Hexalobular

IMPORTANT Do not overtighten retaining screws.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 19


Chapter 2

PowerFlex 755 Frame 2 is shown

Wire the Safety Option Observe these wiring guidelines when installing the safety option module:
Module • Use copper wire with an insulation rating of 600V or greater is
recommended.
• Separate control wires from power wires by at least 0.3 m (1 ft).

Table 4 - Safety Option Module Terminal Block Specifications


Wire Size Range
Wire Type Strip Length
Maximum Minimum
20-750-S Safe Torque Off 0.8 mm2 0.3 mm2 Multi-conductor shielded 10 mm
Option Module (18 AWG) (28 AWG) cable (0.39 in.)

Table 5 - TB2 Terminal Designations


Terminal Name Description
SP+ +24 Volt Safety Power User-supplied power: 24 volt ±10%
SP+ SP-
SE+ SE- SP- Safety Power Common 45 mA typical
Sd Sd
SE+ +24 Volt Safety Enable User-supplied power: 24 volt ±10%
SE- Safety Enable Common 25 mA typical
Sd Shield Terminating point for wiring shields when an
TB2 EMC plate or conduit box is not installed.
Sd Shield

Safety Input Connection Example

Common SP-
+24V SP+
Dedicated Power Supply SE- Common
SE+ +24V
Sd Sd

20 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 2

Cabling

Safety input wiring must be protected against external damage by cable


ducting, conduit, armored cable, or other means.

Shielded cable is required. For proper shield termination, follow the


installation requirements that are related to EN 61800-3 and the EMC
Directive as described in these publications:
• PowerFlex 750-Series AC Drive Installation Instructions, publication
750-IN001
• PowerFlex 750-Series Products with TotalFORCE Control Installation
Instructions, publication 750-IN100

Power Supply Requirements

The external power supply must conform to the Directive 2014/35/EU


Low Voltage, by applying the requirements of EN61131-2 Programmable
Controllers, Part 2 - Equipment Requirements and Tests and one of the
following:
• EN60950 - SELV (Safety Extra Low Voltage)
• EN60204 - PELV (Protective Extra Low Voltage)
• IEC 60536 Safety Class III (SELV or PELV)
• UL 508 Limited Voltage Circuit
• 24V DC ±10% must be supplied by a power supply that complies with
IEC 60204 and IEC 61558-1.

For specific power supply recommendations, refer to your drive installation


instructions:
• PowerFlex 750-Series Products with TotalFORCE Control Installation
Instructions, publication 750-IN100.
• PowerFlex 750-Series AC Drives Installation Instructions, publication
750-IN001.

For planning information, see the guidelines in Industrial Automation Wiring


and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 21


Chapter 2

Verify Operation Test the safety function for proper operation after initial installation of the
safety option module. Retest the safety function at the intervals that are
determined by the safety analysis that is described on page 15.

Verify that both safety channels are functioning according to Table 6.

Table 6 - Channel Operation and Verification


Drive Not Drive Not Drive Not Drive Enabled
Safety Function Status Enabled Enabled Enabled (Ready)
Safety Channel Operation
Safety Option Module
Terminals SP+ & SP- No Power Applied Power Applied No Power Applied Power Applied
(safety power)
Safety Option Module
Terminals SE+ & SE- No Power Applied No Power Applied Power Applied Power Applied
(safety enable)

IMPORTANT If an external fault is present on the wiring or circuitry controlling the Safety
Enable or Safety Power inputs for a period of time, the safety option module
does not detect this condition. When the external fault condition is
removed, the safety option module allows an enable condition.
To achieve maximum safety rating, both safety inputs SP and SE must be
activated by appropriate dual-channel equipment. The repeated activation
of the safety function by only one input at a time can result in a spurious
detection of a fault.

TIP There is no safe-status output provided on the safety option module.

22 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 3

Safe Torque Off Option Module Operation

This chapter provides operation and Stop Category example wiring diagrams
for the PowerFlex® 750-Series Safe Torque Off option module.

Topic Page
Operation 23
Stop Category Wiring Examples 24

Operation The PowerFlex 750-Series Safe Torque Off option module (see Figure 5)
disables the drive’s output IGBTs by disconnecting power to the gate control
driver IC, or disabling the output of the gate-control driver IC. This helps
prevent the drive’s output power devices from switching in the pattern
necessary to generate AC power to the motor.

The safety option module can be used in combination with other safety devices
to satisfy the requirements of IEC 61508, EN/IEC 61800-5-2 SIL 3,
EN ISO 13849-1 PLe, and Category 3 for Safe Torque Off (STO).

IMPORTANT The safety option module is suitable for performing mechanical work on the
drive system or affected area of a machine only. It does not provide electrical
safety.
Do not use the safety option module as a control for starting and/or
stopping the drive.

IMPORTANT The safety option module does not eliminate dangerous voltages at the
drive output. Input power to the drive must be turned off and safety
procedures followed before performing any electrical work on the drive or
motor. See Remove Power to the System on page 16 for more information.

ATTENTION: In the event of the failure of two output IGBTs in the drive,
when the safety option module has controlled the drive outputs to the OFF
state, the drive can provide energy for up to 180° of rotation in a 2-pole
motor before torque production in the motor ceases.

Under normal operation, 24V DC is applied to both the Safety Power and
Safety Enable inputs of the safety option module. If the Safety Enable or Safety

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 23


Chapter 3

Power is de-energized, the outputs of the gate-control driver IC are disabled


and IGBT firing is disabled. On the PowerFlex 753/755, parameter 933 [Start
Inhibits] indicates that IGBTs are inhibited and the HIM indicates that the
drive is not enabled. On the PowerFlex 755T, this is indicated in parameter
10:351 [M Start Inhibits].

ATTENTION: By itself, the safety option module initiates a coast-to-stop


action. Additional protective measures must be applied when an application
requires a different stopping action.

Figure 5 - Drive Safe Torque Off Circuitry


AC Line Input
Power

PowerFlex 750-Series
AC Drives
+24V DC
Stop

Start
Start/Stop Common
24V DC Common
Jumpers:
ENABLE Installed
SAFETY Removed

Gate Control

Safety SP+
Power
SP–
Safety
Enable SE+
SE–
Sd
Sd

Motor

Stop Category Wiring The following diagrams illustrate Stop Category 0 and Stop Category 1 dual-
channel wiring examples for PowerFlex 750-Series drives with Guardmaster®
Examples safety relays. Examples include the following drive families:
• PowerFlex 753 and PowerFlex 755 Drives, Frames 1…10
• PowerFlex 755T Drive Products, Frames 5…15

24 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 3

Figure 6 - Stop Category 0


AC Line
Input Power
24V DC 0V DC COM

PowerFlex 750-Series
Drive
Guardmaster 24V DC
440R-D22R2
Dual-input Safety Relay STOP

A1 L12 START
Aux
(PAC) START/STOP COM
A2
DI L11
24V DC COM
S11 Y32 Reset
Jumpers:
S21 S34 ENABLE Installed
SAFETY Removed
LOGIC 0 Aux
1 (PAC)
2
8 3
7 4 Gate Control
6 5
Gray
S12 13
SensaGuard™ Pink SP+
Interlock Switch S22 14 SP–
S32 23 SE+
S42 24 SE–
Sd
Sd

Motor

Table 7 - Guardmaster DI Example Summary


Attribute Description
Circuit is shown with guard door closed and system ready for normal drive
Circuit status operation.
This is a dual-channel system with monitoring of the Safe Torque Off circuit and
drive. Opening the guard door switches the input circuits (S12 and S22) to the
Guardmaster monitoring safety relay. The output circuits (13, 14 and 23, 24) cause
Operating principle the safety option module and drive Enable circuit to trip and the motor coast-to-
stop. To restart the drive, the Guardmaster safety relay must first be reset followed
by a valid start command to the drive.
A single fault that is detected on the Guardmaster safety input circuits results in the
Fault detection lockout of the system at the next operation and does not cause loss of the safety
function.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 25


Chapter 3

Figure 7 - Stop Category 0


24V DC 0V DC COM

A1 A2 A3 A4 A5 A6

Micro800™
2080-IQ40B4 Plug-in I/O
B1 B2 B3 B4 B5 B6
Reset
Initiate Reset to AC Line
440C-CR30 Safety Relay via PAC Input Power

PowerFlex 750-Series
Drive
24V DC
Gray STOP
SensaGuard Pink START
Interlock Switch
START/STOP COM

1 2 3 4 5 6 7 8 9 10 11
24V DC COM
Jumpers:
PWR Guardmaster 440C-CR30 ENABLE Installed
RUN
FAULT Configurable SAFETY Removed
LOCK
COM
Safety Relay
DC+ COM
24V 0V 12 13 14 15 16 17 18 19 20 21
Gate Control

SP+
SP–
SE+
SE–
Sd
Sd

Motor

Table 8 - Guardmaster Configurable Relay Example Summary


Attribute Description
Circuit is shown with guard door closed and system ready for normal drive
Circuit status operation.
This is a dual-channel system with monitoring of the Safe Torque Off circuit and
drive. Monitoring is software configurable by using Connected Components
Workbench software. Opening the guard door switches the input circuits (1 and 2)
Operating principle to the Guardmaster monitoring safety relay. The output circuits (19, 20, and 21)
cause the drive Enable circuit to trip and the motor coast-to-stop. To restart the
drive, the Guardmaster safety relay must first be reset followed by a valid start
command to the drive.
When the hazard analysis for the overall machine determines the need for external
mechanical brakes or other stopping means, the external means shall be activated
Application Considerations after the removal of power for Stop Category 0.
If the safety option module sticks ON, the motor stops on command due to the
enable input. The system cannot be reset when this fault condition exists.

26 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 3

Figure 8 - Stop Category 1


24V DC 0V DC COM
A1 A2
Aux
Guardmaster
440R-D22R2 S11 DI Y32
(PAC) AC Line
Input Power
Dual-input Safety Relay
S21
LOGIC 0
1 Aux Aux PowerFlex 750-Series
2 Drive
(PAC) (PAC)
3 24V DC
8 Reset
7 4
6 5 STOP
S34
Gray START
S12 13
SensaGuard Pink START/STOP COM
Interlock Switch S22 14
24V DC COM
S32 23
Jumpers:
S42 24 ENABLE Installed
L11 SAFETY Removed

A1 L12 A2 Gate Control

Guardmaster
440R-EM4R2D
EMD SP+
B1 X32 SP–
Expansion Module Delayed 0
RANGE 1 SE+
9 2
3 SE–
8
7 6 5 4
Sd
TIME 1
2 Sd
10 3
9 4
8 7 6 5
37 17 Motor

38 18

47 27

48 L11 28

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 27


Chapter 3

Table 9 - Guardmaster DI and EMD Example Summary


Attribute Description
Circuit is shown with guard door closed and system ready for normal drive
Circuit status operation.
This is a dual-channel system with monitoring of the Safe Torque Off circuit and
drive. Opening the guard door switches the input circuits (S12, S22, and S32, S42)
to the Guardmaster monitoring safety relay. The output circuits (13, 14) issue a
Stop command to the drive and cause a controlled deceleration. After the
Operating principle programmed delay, the timed output circuits (17, 18 and 27, 28) cause the Safe
Torque Off option module and the drive Enable circuit to trip. If the motor is
rotating when the trip occurs, it will coast-to-stop. To restart the drive, the
Guardmaster safety relay must first be reset followed by a valid start command to
the drive.
A single fault that is detected on the Guardmaster safety input circuits results in the
lockout of the system at the next operation and does not cause loss of the safety
Fault detection function.
If the safety option module sticks ON, the motor stops on command due to the
enable input. The system cannot be reset when this fault condition exists.

Figure 9 - Stop Category 0


AC Line
Input Power
POINT Guard I/O™ Modules 0V DC COM
24V DC
Sinking Sourcing PowerFlex 750-Series
Gray Drive
I0 O0
SensaGuard Pink
Interlock Switch I1 O1
I2 O2
I3 COM
Safety Reset
COM
1734-IB8S 1734-OB8S Jumpers:
Fault Reset Digital Input Digital Output ENABLE Installed
SAFETY Removed
24V COM 24V COM

Gate Control

SP+
SP–
SE+
SE–
Sd
Sd

Motor

28 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Chapter 3

Table 10 - POINT Guard I/O Example Summary


Attribute Description
Circuit is shown with guard door closed and system ready for normal drive
Circuit status operation.
When a partial-access guard door is opened, the safety system initiates and
maintains a stop command to stop hazardous motion before a person can reach the
hazardous area. The safety system cannot be reset, and hazardous motion cannot
Operating principle be restarted while the guard door is open. Once the guard door is closed and the
stop command is reset, a valid start command is required before hazardous motion
can resume.
The GuardLogix® controller-logic monitors the system for valid status and faults.
When it receives a safety demand on its inputs or an invalid status or fault is
detected, the GuardLogix controller-logic deactivates its safety outputs and sends a
safety stop command.
Fault detection The PowerFlex drive monitors its internal safety circuits for valid status and faults.
When the GuardLogix controller de-energizes the drive Safe Torque Off (STO)
inputs, or an invalid state or fault is detected, the STO feature on the drive forces
the drive output power transistors to a disabled state. The hazardous motion that is
controlled by the drive coasts or ramps to a stop. This feature does not provide
electrical power isolation.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 29


Chapter 3

Notes:

30 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Appendix A

Specifications, Certifications, and CE


Conformity

This appendix provides general specifications for the PowerFlex 750-Series


Safe Torque Off option module.

Topic Page
Specifications 31
Certifications 33
CE Conformity 34

Specifications These specifications apply to the Safe Torque Off option module. For
additional specifications, refer to the following publications:
• PowerFlex 750-Series AC Drives Technical Data,
publication 750-TD001.
• PowerFlex 750-Series Products with TotalFORCE Control Technical
Data, publication 750-TD100.

Table 11 - General Specifications


Attribute Value
Standards when used with IEC 61800-5-2, EN 61800-5-1, EN 61800-3:, EN ISO 13849-1, EN 62061, EN
PowerFlex 750-Series 60204-1, IEC 61508 parts 1-7
SIL 3 according to EN 62061 / IEC 61508
Safety category when used with SIL CL 3 according to IEC 61800-5-2 / EN 62061 / IEC 61508
PowerFlex 750- Series
Cat. 4 and PL e according to EN ISO 13849-1
Standards when used with EN 61800-5-2, EN 61800-5-1, EN 61800-3, EN ISO 13849-1, EN 62061, EN
PowerFlex 750-Series with 60204-1, IEC 61508 parts 1-7
TotalFORCE Control

Safety category when used with SIL 3 according to EN 62061 / IEC 61508
PowerFlex 750-Series with SIL CL 3 according to EN 61800-5-2 / EN 62061 / IEC 61508
TotalFORCE Control Cat. 3 and PL e according to EN ISO 13849-1
Power supply (user I/O) 24V DC ±10%, 0.8…1.1 x rated voltage(2) PELV or SELV
Power consumption 4.4 W
Safety enable SE+, SE– 24V DC, 25 mA
Safety power SP+, SP– 24V DC, 45 mA
Input ON Voltage, min 24V DC ±10%, 21.6…26.4V DC
Input OFF Voltage, max 5V
Input OFF Current, max 2.5 mA @ 5V DC

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 31


Appendix A

Attribute Value
Conductor type Multi-conductor shielded cable
(1)
Conductor size 0.3…0.8 mm2 (28…18 AWG)
Strip length 10 mm (0.39 in.)
(1) See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) Safety outputs need additional fuse for reverse voltage protection of the control circuit. Install a 6 A slow-blow or 10 A fast-
acting fuse.

Environmental Specifications

The installation must comply with all environmental, pollution degree, and
drive enclosure rating specifications required for the operating environment.
Category Specification
Ambient temperature
Storage temperature
For detailed information on environmental, pollution degree, and drive
Shock enclosure rating specifications, see the technical data publication for your
Operating drive.
Packaged for shipment • PowerFlex 750-Series AC Drives Technical Data,
publication 750-TD001
Vibration • PowerFlex 750-Series Products with TotalFORCE Control Technical Data,
Operating publication 750-TD100
Packaged for shipment • PowerFlex 755TM IP00 Open Type Kits Technical Data,
publication 750-TD101
Sinusoidal loose load
Random secured
Surrounding environment

ATTENTION: Failure to maintain the specified ambient temperature can


result in a failure of the safety function.

IMPORTANT Products with a safety function installed must be protected against


conductive contamination by one of the following methods:
• Select a product with an enclosure type of at least IP54,
NEMA/UL Type 12
• Provide an environmentally controlled location for the product that does
not contain conductive contamination

Table 12 - Environmental Pollution Degree Description (EN 61800-5-1)


Surrounding Conductive Contamination Allowed by
Environment Pollution Acceptable Enclosures
Pollution Degree
Degree
Pollution degree 1 and 2 No possibility of conductive dust. All enclosures are acceptable.
Enclosure that meets or
Pollution degree 3 and 4 The possibility of conductive dust is allowed. exceeds IPS4, NEMA/UL Type 12
is required.

32 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Appendix A

Certifications See the Product Certifications website, rok.auto/certifications for Declarations


of Conformity, Certificates, and other certifications details.
Certification (1) Value
(2)
c-UL-us UL Listed, certified for US and Canada.
European Union 2014/30/EU EMC Directive, compliant with:
EN 61800-3; PowerFlex 750-Series AC Drive, Emissions, and Immunity
European Union 2006/42/EC Machinery Directive:
EN ISO 13849-1; Safety Function
CE
EN ISO 13849-2; Safety Function
EN 60204-1; Safety Function
EN 62061; Safety Function
EN 61800-5-2; Safety Function
Australian Radiocommunications Act, compliant with:
RCM
EN 61800-3; categories C2 and C3
Certified by TÜV Rheinland for Safety:
Up to SIL 3, according to EN 61800-5-2, and IEC 61508, and SIL CL3 according to
TÜV EN IEC 62061;
up to Performance Level PLe and Category 3, according to EN ISO 13849-1;
when used as described in this PowerFlex 750-Series Safe Torque Off User Manual,
publication 750-UM002.
(1) When product is marked, refer to rok.auto/certifications for Declarations of Conformity Certificates.
(2) Underwriters Laboratories Inc. has not evaluated the Safe Torque Off, or Safe Speed Monitor option modules for safety.

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 33


Appendix A

CE Conformity CE Declarations of Conformity are available online at: the Product


Certifications website, rok.auto/certifications.

The 20-750-S Safe Torque Off option module is in conformity with the
essential requirements of the 2006/42/EC Machinery Directive and the 2004/
108/EC EMC Directive when installed and maintained in accordance with
the instructions that are contained in this document. The following standards
have been applied to demonstrate conformity:

Machinery Directive (2006/42/EC)


• EN ISO 13849-1 Safety of machinery - safety-related parts of control
systems - Part 1: General principles for design
• EN 60204-1 Safety of machinery - Electrical equipment of machines -
Part 1: General requirements
• EN 62061 Safety of machinery - safety of safety-related electrical,
electronic, and programmable electronic control systems
• EN 61800-5-2 Adjustable speed electrical power drive systems -
Part 5-2: Safety requirement -
• IEC 61508 Part 1…7 safety of electrical/electronic/programmable
electronic safety-related systems

EMC Directive (2014/30/EU)


• EN 61800-3 - Adjustable speed electric power drive systems - Part 3:
EMC requirements and specific test methods

34 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


Index

A M
additional resources 7 Machinery Directive (2006/42/EC) 34
Australian Radiocommunications Act 33
P
C parameter
cat. 3 5 10 351 M Start Inhibits 24
CE 33 933 Start Inhibits 24
certification PFD
cat. 3 5 definition 6
CE 33 PFH
c-UL-us 33 definition 6
PLe 5 PL
RCM definition 6
RCM 33 PLe 5, 33
SIL CL3 5 probability of failure on demand 6
TÜV 33 probability of failure per hour 6
c-UL-us 33
proof test
20 year interval 12
D functional 11
interval 11
documentation
additional resources 7
R
RCM 33
E
electrical shock hazard 16
EMC Directive (2014/30/EU) 34 S
EN 61508-5-2 33 Safe State 13
encoder wire 20 safety enable 18
European Norm safety enable jumper 18
definition 6 Safety Integrity Level
SIL CL3 5
safety reaction time 13
F SIL CL3 5, 33
functional proof test 11

T
G TÜV 33
guidelines
wire 20
W
H wire
encoder 20
hardware enable jumper 18 wire guidelines 20
hazard
electrical shock 16

I
ISO 13849-1 33

J
jumper 18
hardware enable 18
safety enable 18

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 35


Index

Notes:

36 Rockwell Automation Publication 750-UM002J-EN-P - February 2021


PowerFlex 750-Series Safe Torque Off Option Module User Manual

Rockwell Automation Publication 750-UM002J-EN-P - February 2021 37


Rockwell Automation Support
Use these resources to access support information.

Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Allen-Bradley, Connected Components Workbench, GuardLogix, Guardmaster, Micro800, POINT Guard I/O, PowerFlex, Rockwell Automation, Rockwell Software, SensaGuard, and TotalFORCE are
trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

Publication 750-UM002J-EN-P - February 2021


Supersedes Publication 750-UM002I-EN-P - August 2019 Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like