Schneider Electric Circuit Breaker Protection Relay MVS
Schneider Electric Circuit Breaker Protection Relay MVS
User manual
07/2023
08 N
MVS
0H
2 50/6
60947-
IEC
Optional functions 66 The EasyPact MVS range of circuit breakers and switch-disconnectors oer current
ratings from 630 A to 4000 A.
E89775
Optional M2C contacts 66
Communication option 67
Technical appendix 69
System
System
Trip
Trip
ET6G
ET6G
alarm
alarm 50/60H
time
time tr 8 12 60947-2
long
long 16
IEC
(s) 4
(s)
Ir .8 .9.95 2
.7 20
1 24
Zone selective interlocking (ZSI) 71 .6
.5
.4 x In
1
.98
time
.5 at 6IrIr instantaneous
Ii
instantaneous
6
8 1012
short (s) 4 15
(s)
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
. 2 x In test
2.5 8 .1 2
0off
test
I t
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3 2
(s) .4 .
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I2t
I on
A fault
groundfault
ground
Digital display 72 Rating plate
Thermal memory 73
Calculating demand values 74
Identifying the electrical auxiliaries 75
Identication of the connection terminals 75
Electrical diagrams 77
Operation of electric auxiliaries 80 MVS08N
Rated insulation voltage
Discovering EasyPact MVS accessories 82
Indication contacts 82
Auxiliaries for remote operation 84
Device mechanical accessories 86
IT
Chassis mechanical accessories 88
Rated
Inspecting and testing before use 92 Ultimate
Initial tests 92
IEC 60947-2 / МЭК 60947-2 50/60Hz
What to do when the circuit breaker trips 93 ГОCT P 50030.2
N=50kA
EasyPact MVS circuit breakers are available in drawout and xed versions.
EasyPact MVS circuit breakers are available in drawout and xed versions. The drawout version is mounted on a chassis and the xed version is installed using
The drawout version is mounted on a chassis and the xed version is installed using xing brackets.
xing brackets.
E89777
E89777
System
System
Trip
Trip
ET6G
ET6G
N
MVS08
alarm
alarm 50/60H
time
time tr 8 12 60947-2
long
long 16
IEC
(s) 4
(s)
Ir .8 .9.95 2 20
1 24
.6.7 .98 instantaneous
instantaneous
.5 at 6IrIr
.5 1
.4 x In Ii 8 1012
time 6
short (s)
(s)
4 15
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
. 2 x In test
2.5 8 .1 2
0off
test
I t
2 10 on
on
1.5 Ir delay
x
setting tg
(s) . 4 .3 2
(s) .4 .
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I2t
I on
A fault
groundfault
ground
E89778
m
System
Syste
Trip
Trip
ET6G
ET6G
N
MVS08
alarm
alarm 2 50/60H
time
time tr 8 12 60947-
long
long 16
IEC
(s) 4
Ir .8 .9.95 (s)2
20
.7 uss
1 24
.6 .98 instantaneo
instantaneou
.5 at 6IrIr
.5 1
.4 x In Ii 8 1012
time 6
short (s)
(s)
4 15
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
x In test
8
.2 2 0off
2.5 .1 I t test
2 10 on
on
1.5 Ir delay
x
setting tg
(s) . 4 .3 2
(s) .4 .
E F .3 .1
Ig D G
C
.2 0off
off
H
B
on.1 I2t
I on
A fault
fault
ground
ground
Locking by keylocks
Locking by padlocks
Crank socket
**
Position release button
* During racking-in or racking-out operation of circuit breaker an automatic racking lock button
pops out at every distinct position - "Connected", "Test" and "Disconnected".
This lock indicates that exact position of the breaker is achieved and blocks operation of the crank.
Make sure that the position release button, is pushed-in before rotating the crank.
** Optional device- Not supplied as standard.
XF closing release
Opening pushbutton
Control unit*
Front
Side plate for
DB119318
Rating plate
Closing pushbutton
Locking by padlock, lead-seal cover
or screws for pushbuttons
Opening pushbutton
Control unit*
"Springs charged" and "Ready
Indicator for position of the to close" indicator
main contacts
Arc chute
Opening pushbutton
Trip unit*
Keylocking kit
Operation counter
Circuit breaker open Circuit breaker closed The charge status is indicated as follows. The springs in the circuit breaker operating mechanism must be charged to store
E89775
and discharged and discharged the energy required to close the main contacts. The springs may be charged
manually using the charging handle or the optional MCH gear motor.
E89851
E89852
E89851
I
ON
I ON
Push Push
System
System
Trip
Trip
ET6G
ET6G
E89789
E51290A
E89853
E89854
I ON
I
ON
Push Push
O OFF
O OFF
Push Push
E89855
I ON
Push
O OFF
Push
E51291A
E51216A
"ready to close".
The prerequisites are the following:
E89858
1. device open (OFF)
Device not "ready to close" 2. springs charged
3. no opening order present.
E51292A
If the circuit breaker is not "ready to close" when the order is given, stop the order
and start again when the circuit breaker is "ready to close".
E51216A
E89858
2. one MN undervoltage release (0.35 to 0.7 Un)
3. one MN undervoltage release (0.35 to 0.7 Un) with a delay unit (R or Rr).
When connected to a remote control panel, these releases can be used to open
the circuit breaker remotely.
E51293A
MX, MN Delay unit
E51294
E51296A
6
3 4 5
1 2
S
3 6
1
0.5
MN 1.5
3
UVR de MN
ateurfor UVR
V Retard
Remotely 100/13
0
Time
delay
AC/DC
1012
2 3
When connected to a remote control panel, the XF closing 1
WARNING XF
release (0.85 to 1.1 Un) can be used to close the circuit
breaker remotely.
E51294A
■ The device should only be installed and serviced by
professionals.
■ Avoid installation of XF release at MX position
E51293A
The purpose of the mechanical anti-pumping function is to ensure that a circuit Locally
breaker receiving simultaneous opening and closing orders does not open and If the circuit breaker is not equipped with the automatic reset option, reset it manually.
close indenitely.
If there is a continuous closing order, after opening the circuit breaker remains open
E89860
until the closing order is discontinued. A new closing order then closes the circuit
breaker. This function can be disabled by wiring the closing release in series with the
PF "ready to close" contact.
ET
RE S
Pushbutton locking using a padlock Locking the controls with one keylock
E89775
(shackle diameter 5 to 8 mm), a lead seal or screws. Locking
Open the circuit breaker. Turn the key, anti-clockwise. Remove the key.
Padlock Lead seal Screws
System
System
Trip
Trip
ET6G
ET6G
E51300B
E51301B
E51337A
E51217A
E51310A
E51311A
N
MVS08
alarm
alarm 50/60H
time
time tr 8 12 60947-2
long
long 16
IEC
(s) 4
Ir .8 .9.95 (s)2
20
.7 s
1 24
.6 .98 .5 at 6IrIr instantaneou
.5 instantaneous
1
.4 x In Ii 8 1012
time 6
short (s) 4 15
(s)
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
x In test
8
.2 2 0off
2.5 .1 I t test
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3 2
(s) .4 .
E F .3 .1
Ig D G
C
.2 0off
off
H 2
B
on.1 I t
I on
A fault
fault
ground
ground
Locking
Close the covers. Insert the padlock
shackle, lead seal
or screws. Check
The controls are inoperative.
E51302B
E51303B
O I
Push OFF Push ON
E51218A
Unlocking Unlocking
Remove the padlock, Lift the covers and swing The pushbuttons Insert the key. Turn the key, clockwise. The key cannot
lead seal or screws. them down. are no longer locked. be removed.
E51312A
E51313A
E51319A
E51303B
E51304B
E51305B
O I
Push OFF Push ON
DB119341
E51222A
Test
Test
E51453A
DB119342
E51219A
E51314A
Test
Test
b "test" position
2."test"position
E51454A
DB119343
E51220A
E51315A
Test
Test
10.9 mm
26 mm
b "disconnected" position
E51455A
DB119344
3."disconnected"position
Test
E51221A
E51316A
Test
32.2 mm
2 3
Push the circuit breaker into the chassis, taking care not to push on the control unit.
DB119350
DB119349
DB119718
Test
Test
E51223A
Test
1
2
3 4
Test
Test
Test
6 Test
STOP
The circuit breaker is in "disconnected" position.
Test
Test
2 3
E89788
2. when the circuit breaker is in "disconnected" position, the latch is raised and the
E89812
door is unlocked.
DB119354
System
System
Trip
Trip
ET6G
ET6G
N
MVS08
alarm
alarm 50/60H
60947-2
time
time tr 8 12 IEC
long
long (s) 4 16
Ir .8 .9.95 (s)2
20
.7
1 24
.6 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
time 6
short (s) 4 15
(s)
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
x In test
8
.2 2 0off
2.5 .1 I t test
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3 2
(s) .4 .
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I 2t
I on
A fault
groundfault
ground
Push the circuit breaker into the chassis, taking care not to push on the ET
Trip System.
E89813
System
System
Trip
Trip
ET6G
ET6G
N
MVS08
alarm
alarm 50/60H
time
time tr 8 12 60947-2
long
long IEC
(s) 4
(s) 16
Ir .8 .9.95 2
.7 20
System
System 1 24
Trip .6 .98 .5 at 6IrIr instantaneous
ET6G Trip .5 instantaneous
1
ET6G .4 x In Ii 8 1012
time 6
short (s) 4 15
(s)
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
. 2 x In test
2.5 8 .1 2
0off
test
I t
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3 2
(s) .4 .
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I2t
I on
A fault
groundfault
ground
N
MVS08
alarm
alarm 50/60H
time
time tr 8 12 60947-2
long
long IEC
(s) 4
(s) 16
Ir .8 .9.95 2
.7 20
1 24
.6 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
time 6
short (s) 4 15
(s)
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
. 2 x In test
2.5 8 .1 2
0off
test
I t
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3 2
(s) .4 .
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I 2t
I on
A fault
groundfault
ground
DB119355
Test
Test
E51230B
Test
1
2
3 4
Test
"connected" position. The device is in "test" position. rotation of crank. Push the release button
Failure to follow the instruction can result in to rotate the crank.
equipment damage.
Test
Test
6
Test
5
STOP
Test
If specied when ordering the chassis, this locking Disabling connection when the circuit breaker is in
function may be adapted to operate in all positions
E89815
"disconnected" position, using one to three
("connected", "test" and "disconnected"), instead of in
"disconnected" position alone. padlock (maximum shackle diameter 5 to 8 mm)
Locking
Circuit breaker in Pull out the tab.
"disconnected" position.
1 2
DB119358
DB119359
Test
System
System
Trip
Trip
ET6G
ET6G
N
MVS08
alarm
alarm 50/60H
time 8 12 60947-2
long
long
time tr IEC
(s) 4
(s) 16
Ir .8 .9.95 2 20
1 24
.6.7 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
time 6
short (s) 4 15
(s)
shorttime tsd .4 .4 .3
.2
Isd 4 5 3 off
off
3 .3 .1 2
6
. 2 x In test
2.5 8 .1 2
0off
test
I t
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3 2
(s) .4 .
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I2t
I on
A fault
groundfault
ground
Close the door. Put the EasyPact MVS in The door is locked.
DB119361
E89816
E89817
E89818
Unlocking.
Remove the padlock(s). Release the tab.
1 2
DB119362
DB119363
E89819
E89820
3
DB119364
System
System
Trip
Trip
ET6G
ET6G
N
MVS08
alarm
alarm 50/60H
60947-2
time
time tr 8 12 IEC
long
long (s) 4 16
Ir .8 .9.95 (s)2
20
.7
1 24
.6 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
time 6
short (s)
shorttime tsd .4 .4 .3 4 15
(s) .2
Isd 4 5 3 off
off
3 .3 .1 2
6
x In test
8
.2 2 0off
2.5 .1 I t test
2 10 on
on
1.5 Ir delay
x
setting tg
(s) . 4 .3 2
(s) .4 .
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I 2t
I on
A fault
groundfault
ground
DB119366
DB119365
"disconnected" position, using one padlock
(maximum shackle diameter 5 to 8 mm)
Test
Locking
Circuit breaker in Pull out the tab.
"disconnected" position.
E89821
E89822
33 44
DB119367
DB119368
Insert the shackle(max.diameter The crank cannot be inserted.
5 to 8 mm) of the padlock.
E89823
E89824
Unlocking
Insert the key(s). Turn the key(s). The crank can
be inserted.
1 2 3
Unlocking.
DB119370
DB119369
DB119371
Remove the padlock. Release the tab.
E89825
E89826
E51270A
DB118749
26 EasyPact MVS06-40 - 07/2023 EasyPact MVS06-40 - 07/2023 27
Using the EasyPact MVS Locking the circuit breaker in Using the EasyPact MVS Locking the circuit breaker
drawout chassis drawout chassis
disconnected position in all positions
MVS 08-40(N/H/T)
Padlocks and keylocks may be used together. Disabling connection when the circuit breaker is in For this operation, the circuit breaker Disabling use of the crank in all positions
must be removed from the chassis.
"disconnected" position, using one keylock It is possible to modify the padlock and keylock locking function. Instead of locking only
in "disconnected" position, it is possible to lock the circuit breaker in all positions.
Locking
Circuit breaker in Turn the key. Set the circuit breaker to Insert the crank.
"disconnected" position. "disconnected" position. Remove the
circuit breaker from the chassis.
E89829
Test
E51237A
Test
Test
Test
Remove the key. The crank cannot be inserted. Turn the catch to the right. The circuit breaker can now be locked in all positions.
E89830
E51240A
Unlocking
Insert the key. Turn the key. The crank can
be inserted.
E89832
E89833
E89827
Two type of keylocks are available
PROFALUX RONIS
E51269A
E51270A
E51338A
E51339A
DB119375
2
E51340A
DB119376
Four locking possibilities
Top and bottom shutters not locked. Top shutter locked,
Bottom shutter not locked.
E51341A
EasyPact MVS air circuit breakers are equipped with ET/ETA/ETV 2I Trip System: basic protection
E51389B
ET/ETA/ETV Trip System.
ET range of Trip Systems are designed to protect 2I
E51351A
CDB500035
E51352A
long time
long time
Ir tr alarm
alarm
.8 8
.7 (s) 4
.9 (s) 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir
[Ir
instantaneous
instantaneous
Ii
8 10
6
4 12
3 15
2 off
off
x In
test
test
Long time + Instantaneous
ETV5S
E51353A
CDB500030
E51354A
alarm
long time
long time
Ir tr alarm
alarm
.8 8
.7 (s) 4
.9 (s) 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir
Ir
short time instantaneous
short time instantaneous
Isd tsd Ii
4 5 (s) 8 10
3 (s) .4 .4 .3
6
Long time + Short time + 2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 2 2 off
off
on
on I t
0off
long time
long time
x Ir x In
Ir tr alarm
alarm
test .8 8
Instantaneous .7 (s) 4
.9 (s) 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir
Ir
short time instantaneous
short time instantaneous
Isd tsd Ii
4 5 (s) 8 10
3 (s) .4 .4 .3
6
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 2 2 off
off
on
on I t
0off
x Ir x In
setting delay test
test
tg
(s)
Ig
D E F (s) .4 .4 .3
C G .3 .2
B H .2 .1
A I on.1 2 0off
on I t off
ground fault
ground fault
E51394A
selective + ground-fault protection ET6G Trip System ETA6G Trip System ETV6G Trip System
E51393A
CDB500004
ET/ETA/ETV 2I ET/ETA/ETV 5S ET/ETA/ETV 6G
E51395A
long time
long time
Ir tr alarm
alarm
.8 8
.7 (s) 4
.9 (s) 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir
Ir
short time instantaneous
short time instantaneous
Isd tsd Ii
4 5 (s) 8 10
3 (s) .4 .4 .3
6
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 2 2 off
off
on
on I t
0off
x Ir x In
setting delay test
test
tg
(s)
Ig (s)
D E F .4 . 4 . 3
C G .3 .2
B H .2 .1
A I on.1 2 0off
on I t off
ground fault
ground fault
Ground-fault protection
E51358A
E51359A
1 10 Ir. Above 10 Ir, the time curve is constant.
1 circuit breakers for the zone selective interlocking function.
2
I t on 2
Short-time pick-up Isd and tripping delay tsd
2 I t on
2
ET/ETA/ETV Trip System 5S and 6G
I t off 2 pick-up Isd = Ir x … accuracy ± 10% 1.5 2 2.5 3 4 5 6 8 10
2 1 I t off
3 time delay (ms) setting I 2t Off 0 0.1 0.2 0.3 0.4
4 2 a t 1 0 Ir I2t On 0.1 0.2 0.3 0.4
3 5 I2t On or tsd (max resettable time) 20 80 14 0 2 30 35 0
I2t Off ts d ( m a x b r e a k t i m e ) 80 1 40 200 3 20 50 0
0 Ir Isd I 0 Ir Isd Ii I 0 Ig Instantaneous protection
1. current setting Ir (long 1. current setting Ir (long time) 1. pick-up Ig (ground fault) the instantaneous-protection function protects the distribution system
time) 2. tripping delay tr (long time) 2. tripping delay tg
2. tripping delay tr (long for 6 x Ir (ground fault) against solid short-circuits. Contrary to the short-time protection function,
time) for 6 x Ir 3. pick-up Isd (short time) the tripping delay for instantaneous protection is not adjustable.
3. pick-up Isd 4. tripping delay tsd (short The tripping order is sent to the circuit breaker as soon as current exceeds
(instantaneous) time) the set value, with a fixed time delay of 20 milliseconds.
5. pick-up Ii (instantaneous)
Instantaneous pick-up Isd
ET/ETA/ETV Trip System 2I
pick-up Isd = Ir x ... accuracy ± 10 % 1.5 2 2.5 3 4 5 6 8 10
Long-time protection time delay (ms)
The long-time protection function protects cables (phases and neutral) against
overloads.This function is based on true rms measurements. Instantaneous pick-up Ii
Thermal memory
The thermal memory continuously accounts for the amount of heat in the cables, ET/ETA/ETV Trip System 5S and 6G
both before and after tripping, whatever the value of the current (presence of an pick-up li = In (*) x … accuracy ± 10 % 2 3 4 6 8 10 12 15 OFF
overload or not).The thermal memory optimises the long-time protection function of time delay (ms)
the circuit breaker by taking into account the temperature rise in the cables.
The thermal memory assumes a cable cooling time of approximately 20 minutes.
Refer to page no.33 on selecting the type of
neutral protection. Protection of the fourth pole on four-pole circuit breakers
Long-time current setting Ir and standard tripping delay tr Protection of the neutral conductor depends on the distribution system.
There are three possibilities.
ET/ETA/ETV Trip System 2I, 5S and 6G 1. Neutral unprotected
current setting Ir = In (*) x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 2. Neutral protection at 0.5 In
tripping betweeen 1.05 and 1.20 Ir 3. Neutral protection at In
time setting Accuracy 0,5 1 2 4 8 12 16 20 24 Neutral protection for three-pole devices
time delay (s) tr at 1.5 x Ir 0 to - 30% 12.5 25 50 100 200 300 400 500 600 Neutral protection is not available on three-pole devices.
tr at 6 x Ir 0 to - 20% 0.7 (1) 1 2 4 8 12 16 20 24 Ground-fault protection on ET6G Trip System
tr at 7.2 x Ir 0 to - 20% 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 An ground fault in the protection conductors can provoke local temperature rise
(*) In: circuit breaker rating at the site of the fault or in the conductors.
(1) 0 to - 40% The purpose of the ground-fault protection function is to eliminate this type of fault.
Overload LED
(2) 0 to - 60% Type Description
long time long time long time
Ir .8 tr alarm Ir .8 tr 8
alarm alarm
8 .7
.7 .9 (s) 4 12 .9 (s) 4 12 (s) Residual 1. the function determines the zero-phase sequence
.6 .95 2 16 .6 .95 2 16
.5 .98 1 20 .5 .98 1 20 current, i.e. the vectorial sum of the phase and neutral
.4 1 .5 24 .4 1 .5 24
x In x In `Ir
6xIr `Ir currents
instantaneous short time instantaneous short time instantaneous
Isd Isd tsd Ii
4 4 (s) .4 .4 .3 6 8 10 (s) 2. it detects faults downstream of the circuit breaker.
3 5 3 5
2.5 6 2.5 6 .3 2 4 12
2 8 2 8 .2 .1 3 15
1.5 10 1.5 10 .1 0 2 off off
1. ground-fault and neutral protection are independent and can therefore be
x Ir x Ir on I2t off x In on off
setting setting delay test
combined.
(s) 2. ground-fault protection in 3P+N system is activated by installing a external
sensor(CT) in the neutral conductor and connecting to ET Trip System.
on off
ground fault
The auto-protection function (excessive temperature or Fault indications Measurement and display possibilities
short-circuit higher than circuit-breaker capacity) opens
Signals tripping due to an Signals tripping due b ETA measures instantaneous currents and stores the maximum values in maximeters.
the circuit breaker and turns on the Ap LED.
overrun of the long-time to an overrun of the b In addition to the values measured by ETA, ETV trip unit measures both current
current setting Ir. short-time pick-up Isd and voltage.
Caution.
If the circuit breaker remains closed and the Ap LED or the instantaneous
ETA and ETV measurements can be displayed on:
remains on, contact the Schneider after-sales pick-up Isd / Ii. b the digital screen of trip unit
support department. b a PC via the screen of the control unit
ETV6G Trip System ETV6G Trip System In addition, a bargraph on the front of the control unit continuously displays the
ET6G Trip System ET6G Trip System
Caution. currents measured on phases 1, 2 and 3 as a percentage of the long-time current
The battery maintains the fault indications. setting Ir.
If there are no indications, check the battery.
DB126369
1.125 x Ir
100 % 1 x Ir
0.8 x Ir
0.6 x Ir
Signals tripping due to an Signals tripping due to 40 % 0.4 x Ir
overrun of the ground fault the auto-protection, Ap
pick-up Ig function of the
Trip System
The following table indicates ETA and ETV measurement and display possibilities.
ETV6G Trip System ETV6G Trip System Measurements ETA ETV Displayed on...
ET6G Trip System ET6G Trip System
Trip
System
Trip
System Voltage unbalance Vunbal b b
ETA6G ETA6G
Instantaneous powers P, Q, S b b b
Power maximeters Pmax, Qmax, b b
Smax
100 % 100 %
Demand active power P b b b
40 % 40 % Demand apparent power S b b
Demand power maximeter (peak b b
menu menu
1 demand) Pmax
Instantaneous power factor PF b b b
2 Active energy Ep b b b
Reactive and apparent energy Eq, b b
Es
(1) The display of the Neutral current (IN) is available with ETV when the parameter "type of
network" has been set to 4 Wire 4CT (44). See page 50.
(2) Important: for 3-pole circuit breakers used on 4-wire systems (3ph + N), terminal VN on the
Triip system control unit must always be connected to the neutral. If this is not done, the phase-to
neutral voltage measurements can be erroneous.
Note: If no information is displayed on the screen, see: "Digital display" in the technical
appendix.
Measurement denitions ETV control units let you access information that can Trip history
be used to analyse or avoid circuit breaker tripping, The trip history displays the list of the last 10 trips.
thereby increasing the overall availability of your For each trip, the following indications are recorded and displayed:
installation. Available information includes the trip b the tripping cause: Ir, Isd, Ii, Ig or Auto-protection (Ap) trips
history and tripping pre-alarms.
Measurements Denition
List of trip causes:
Instantaneous current The rms value of the instantaneous time b overloads (Ir)
current. b short-circuits (Isd or Ii)
Neutral current Available with a 4-pole breaker b ground faults (Ig)
Current maximeter Maximum value of the instantaneous time b auto-protection (Ap).
current (refreshed every 500 ms) since Trip The trip history display is presented on page 60.
system installation or last reset.
Demand current (1) Mean of all instantaneous time current values Pre-alarms
over a given user-adjustable time interval (e.g. Denition
10 min). ETV control units can be set to deliver pre-alarms via their optional M2C contacts
Voltage The rms value of the voltage. (see page 66). These pre-alarms can be used to warn operators that the current
is approaching a trip threshold. In this way, remedial measures (e.g. load-
Average voltage Average of the 3 phase-to-phase voltages V12,
shedding, maintenance, etc.) can be taken before the circuit breaker trips,
V23 and V31:
avoiding unnecessary shutdowns.
V12 + V23 + V31
V avg =
3
Two types of pre-alarms are available, depending on the control unit.
Voltage unbalance Voltage unbalance on the most unbalanced bLong-time protection pre-alarm: all ETV control units can be set to deliver a
phase, displayed as a percentage of Vavg. pre-alarm via one of their two outputs when the current reaches 90 % of the
U long-time protection current setting Ir.
E max bGround-fault protection pre-alarm: ETV6.0G control units can also be set to
V avg deliver a pre-alarm via one of their two outputs when the current reaches 90 % of
the ground-fault protection pickup Ig. Both Ir and Ig pre-alarms can be
implemented if neither of the two outputs are required for other functions.
See page 62 for general information on output settings (M2C contacts) or page
0 V12 V23 V31
65 for an example of how to set an output to implement these or other functions.
ETV measures the maximum dierence
between the instantaneous time voltage of Operation
each phase and Vavg, and calculates the The Ir and Ig pre-alarms are delivered via the non-latching outputs (M2C
voltage unbalance: contacts) of ETV control units.
b Pickup (pre-alarm activation): when the current exceeds the pickup threshold
E max
V unbal = (equal to 90 % of the Ir current setting or Ig pickup), the output state changes
V avg from 0 to 1 after a time delay of 0.1 second.
Instantaneous power P: total active power b Dropout (pre-alarm deactivation): when the current falls below the dropout
Q: total reactive power threshold (equal to 85 % of the Ir current setting or Ig pickup), the output state
S: total apparent power returns to 0 after a non-adjustable time delay of 0.1 second and the pre-alarm is
P, Q and S are rms instantaneous values. automatically deactivated.
Power maximeter Maximum value of the instantaneous time
power (refreshed every 1 s) since Trip system
installation or last reset.
Measurements Pickup (pre-alarm Dropout (pre-alarm
Demand power (1) Mean of all instantaneous time power values
activation) deactivation)
over a given user-adjustable time interval (e.g.
10 min). Threshold Time delay Threshold Time delay
Instantaneous power PF = P / S Ir pre-alarm 90% of Ir 0.1 s 85% of Ir 0.1 s
factor PF
Ig pre-alarm 90% of Ig 0.1 s 85% of Ig 0.1 s
Total energy Ep: total active energy
Eq: total reactive energy
Es: total apparent energy
% of Ir or Ig
(1) For details on how demand is calculated, see "Calculating demand values" in the technical
appendix page 74.
Pickup threshold
90 %
Dropout threshold
85 %
0.1 s 0.1 s
Pre-alarm
Setting procedure for ET Trip System The rating of the circuit breaker in
this example is 2000 A.
Using the adjustment dials
E31366A
E31363A
E31364A
E31365A
System
System System Trip
Trip Trip ET5S
ET5S ET5S
1 2 3
In = 2000 A
A
2000
In =
E31368A
.6 .95
.5 .98 Ir = 0.7 x In = 1400 A
.4 1
x In Isd = 2 x Ir = 2800 A
Setting procedure for ETA/ETV Trip System instantaneous
Isd
4
1. Open the protective cover. 3 5
2.5 6
Isd
2 8
0 I 1.5 10
x Ir
E51410A
E51411A
System System
setting
ETA 6G Trip 6G Trip
ETA
Ir=
A
1 automatically displayed
2 on the digital screen in
absolute value with the
Set the tripping delay
relevant units.
b Current in amperes long time
(A and kA); Ir tr alarm tr = 1 second
t 8
(s) 4 12
b Tripping delays in
E31370A
2 16
seconds. 1 20
.5 24
3. If no information is displayed, see the "Digital 6xIr
tr
E51412A
display". (page 55) If no further action is taken, after
System a few seconds, the display returns to the main menu
Trip
ETA6G
40 %
menu
The rating of the circuit breaker in The rating of the circuit breaker
this example is 2000 A. in this example is 2000 A.
E51366A
E51366A
1 1
In = 2000 A In = 2000 A
A A
2000 2000
In = In =
E51373A
E51372A
t t 4 short time instantaneous
Ir Ir 3 5 6 8 10
Isd = 2 x Ir = 2800 A
E51373A
E51372A
2.5 6 4 12
2 8 3 15
1.5 10 2 off Isd Isd
x Ir x In
setting off Ii = 3 x In = 6000 A
Isd Isd Ii Ii off
test
0 0 I
Ii Ii B Ig = 640 A
t t
0 0 I
E51416A
E51415A
ground fault
Ig Ig
E51376A
E51375A
(s) .4 .4 .3
E51376A
E51375A
.3 .2 [Ir
tr tr I2t on I2t off tr tr
.2 .1 short time
.1 2
0 tsd = 0.2 s
on It off (s)
tsd tsd delay tsd tsd
I2t on I2t off
on off
0 0 I 0 0 I
test
t t (s)
E51419A
E51418A
tg = 0.2 s
on off
ground fault
tg tg
0 I 0 I
On four-pole circuit breakers,it is possible to select the type of neutral protection for The procedure for resetting the Resetting the fault indications
the fourth pole using the three-position dial on the circuit breaker: circuit breaker following a fault b determine why the circuit breaker tripped.
1. neutral unprotected (4P 3D); trip is presented in Page No.10. The fault indication is maintained until it is reset on the control unit.
2. neutral protection at 0.5 In (3D + N/2); v press the fault-trip reset button.
3. neutral protection at In (4P 4D).
ETV6G Trip System
The factory default setting is 3D+N/2.
E51383A
/2
3D+N
4P 4D
4P 3D
Caution!
With the 4P 3D setting, the current in the neutral must
not exceed the rated current of the circuit breaker.
+
E51444A
E51445A
E51404A
b maximeter current values for phases I1, I2, I3, neutral IN, the maximum ground-
fault current Ig on the ETA6G Trip System.
E51456B
System
Trip
ET6G
E51405A
E51406A
E51407A
E51408A
Max
Ir=
Press and hold a key. A A A
me
Press the "menu" button Press the "menu" button Press the "menu" button
to access the maximum to access the protection to return to the
current values measured settings and current measurements.
by the maximeter. tripping delays.
100 %
40 %
Current values may be read in the "Measurements" Display of current I1 Display of current I2 Display of current I3 Maximum current values can be reset using the Select the maximum Reset. Select another value
menu, which is also the main menu. "Maximeter" menu. current value to be to reset or return to
E51425A
E51426A
E51427A
reset (e.g. I2 max.). the main menu.
If no particular action is taken, the system displays the A A A If no particular action is taken, the system returns to
current value of the most heavily loaded phase. the main menu.
MAX MAX MAX
E51436A
E51437A
E51438A
A A A
E51407A
Max
E51409B
A
40 % 40 % 40 % 100 % 100 % 100 %
A
40 % 40 % 40 %
Press the "arrow" button Press the "arrow" button Press the "arrow" button 100 %
100 % to go on to current I2. to go on to current I3. to go on to current IN if
the neutral is protected.
40 % Press the "arrow" button Press and hold the Press the "arrow" button
40 % Display of current IN Display of current Ig The system returns to menu as many times as "arrow" button down for as many times as required
(ETA 6G) the display of current required to select I2 max. three to four seconds. to select another maximum
I1 The current value ashes value to reset or return to
during the reset, then the main menu.
changes to the present
value (the new maximum).
E51429A
E51428A
E51409B
A A A
40 % 40 % 40 %
Denitions
b ETV has two display modes: Tree Navigation and Quick View modes.
b All the screens of the ETV navigation trees are detailed on page 57.
Or
the ∆t value.
Current
A
ETV Current Quick View allows the operator to quickly view the The screens automatically scroll in a circular manner so that the operator can
6308
A
7727 most important electrical measurements (currents, view all the main electrical measurements one after another.
DB126450
voltages, active power, energy) without having to The current bargraph and overload LED remain visible at all times in Quick View
Current
Ph-Ph Ph-N
A touch the control unit keypad. mode.
4632 voltage for voltage for
3W systems 4W systems
V V
266
Energy
Quick View screen descriptions
MWh Quick View can be used to display the screens dened in:
__6 233
b the factory conguration
V V
Energy
MWh
V V
Screens dened in the actory conguration
285
ETV control units come with a factory Quick View conguration including the
Power following 9 screens, scrolled in the indicated order:
MW
3 - Current
Voltage A (ph 3/C)
A
V V
menu
ppp ppp
1 - Current
Power (ph 1/A)
A
MW MW
menu
4 - Voltage 4 - Voltage
ppp ppp 4W (V1N) 3W (V12)
V V
Active energy
MWh MWh
menu
ppp ppp
9 - Energy
Trip history MWh
5 - Voltage 5 - Voltage
menu
4W (V2N) 3W (V13)
ppp ppp V V
Measurement settings
ppp ppp
Min MW
menu
s
Software version
menu
DB126521
Instantaneous and demand current b make sure you are in manual control of the quick view mode, and if necessary,
Current
A A Current
press the button briey (< 1 s) to activate automatic scrolling and then
A
menu ppp ppp A
press the button briey (<1s) to activate the manual control of the quick view
Screen 1 mode
Screen 1 Current
Ph-Ph Ph-N
A
voltage for voltage for b when the screen to be removed appears, press and hold the button (> 4 s)
Max. of instantaneous current 3W systems 4W systems Display the screen
V V
to be deleted.
b when the message "OK dEL" is displayed, the screen has been removed.
Max A Max A Example: Removing the screen Current of phase 2/B
menu ppp ppp A A
Energy
MWh
A
A
302
3021
V V
Voltage Then press
A briey ( > 4 s) A
V V
31
3150
menu ppp ppp V
Energy
V
V V 700
until the message
Power Power
MW
MW
MWh MWh
MW MW
menu ppp ppp
V
is displayed. V
680
Active energy
V
V
69
690
Manual control of Quick View scrolling MW
MW
DB126473
no other action is taken. b access Tree Navigation mode by briey pressing the button (< 1 s)
b in this mode, display the screen you want to add using the menu and
It is then possible to manually scroll through each Quick View screen one after buttons, as described in "Tree Navigation" on page 56.
the other. b when the selected screen is displayed, press and hold the button (> 4 s)
Press briey Displays the next screen for 20 b when the message "OK Add" is displayed, the screen has been added to the
(< 1 s) s if no other action is taken. Quick View conguration. It will be placed in the last Quick View position.
DB126473
kVAr
is displayed.
b if you try to add a screen to an existing conguration that already has 10
screens, the message "QV full" will be displayed.
Tree Navigation
b The classical navigation trees presented in the "HMI introduction" on page 52 The gures below show all the screens of the 2 ETV navigation trees with all details
provide access to all the screens of ETV control units. concerning screen content and navigation between the various branches and screens of the
trees.
b The dierent screens are accessible using the menu and buttons and are
organised in branches corresponding to a given type of information. Display tree branches Screens
Default display A
The following branches are available, in the indicated order, depending on the
(instantaneous current of the most heavily
type of Trip System control unit:
loaded phase)
Branch (type of information) ETV
Display tree Instantaneous and demand currents I1 I2 I3 IN Ig (ETV6G)
Instantaneous current
A A A A A
Instantaneous and demand current b
Maximeters for instantaneous current b
Voltage b I1 I2 I3 IN
Power (total of 3 phases) b
A A A A
Active energy (total of 3 phases) b
Trip history (last 10) b
Protection setting display b
Setting tree Instantaneous current maximeters I1 I2 I3 IN Ig (ETV6G)
Communication settings b To reset current maximeters, see page 59.
Max A Max A Max A Max A A
Measurement settings b
menu
Output settings (with optional M2C contacts) b
Software version b
Voltages (3-wire systems) V12 V23 V31
Navigating with the keypad buttons V V V
menu
Press briefy
(< 1 s)
(symbol: a white hand) Voltages (4-wire systems) V1N V2N V3N V12 V23 V31
V V V V V V
Press and hold menu
(> 4 s)
(symbol: a grey hand)
Power P PF Q S Demand P
MW kVAr kVA MW
Active Power is displayed positively or
Screen information negatively according to the parameter menu
The positions of the downward arrows (one, two or three arrows) under the Power sign (see page 62).
information displayed on the screen indicate the phases concerned, as shown for
example in the screens below. Active energy Ep (MWh) Ep (MWh)
MWh MWh
Ep is displayed in MWh on 2 screens,
menu
MW
DB126475
A
DB126476
A
DB126477
V
DB126478
V
DB126479
see details on page 58.
To reset active energy, see page 27.
Trip history The trip history displays the list of the last ten trips.
(see details on page 60)
Protection settings display The protection settings displayed depend on the model of the ETV control unit.
(see details on page 61)
100 % 100 % 100 % 100 % 100 %
Setting tree branches Screens
6 A current in the 360 A current in phase 380 V phase-to-phase 220V phase-to-neutral 2.556 MW total active Communication settings k W
menu
neutral 1/A (arrow above 1/A). voltage between voltage between phase power of the 3 phases (see details on page 62)
(arrow above the N). phases 1/A and 2/B 2/B and neutral (arrows (arrows above the 3
(arrows above 1/A and above N and 2/B). phases).
2/B).
Measurement settings Min MW Min A
Default screen
If no particular action is taken, the system displays Example: Phase 1 is the most heavily loaded. Output settings (with optional M2C Ar
the instantaneous current of the most heavily contacts) menu
DB126492
loaded phase. (see details on page 62)
A
Ar
Software version
menu
100 %
DB127834
Example: display of Ep = 26.233 MWh (26233 kWh)
Select the maximum Reset Select another value of
current value to be current to reset or
MWh MWh
DB126496
DB126493
DB126494
DB126495
DB126504
DB126511
MWh MWh
menu menu menu
Press the "Arrow" button Press and hold the Press the "Arrow" button
as many times as "Arrow" button down for as many times as
100 % 100 %
required to access the I2 3 required to select
menu menu
max. screen. to 4 seconds. another maximum value
The old value changes to to reset or return to the
the present value (the main menu.
new maximum).
menu
DB127827
The total active energy (Ep) is calculated and displayed positively whatever
the value of the parameter Power sign. The Maximum totale active energy
displayed is 999 999 999 MWh. If the total active energy keeps increasing, the Select the active energy Reset Return to the main
value displayed is 999 999 999 MWh. screen menu
DB126504
DB127828
DB126485
MWh MWh A
Press the "Arrow" button Press and hold the Press the "Menu" button
as many times as "Arrow" button down to return to the main
required to access the for 3 to 4 seconds. menu.
total active energy The old value changes
screen (displaying the to the new value
whole number part of (starting at 0) when
the total active energy). releasing
the button.
Introduction
The trip history displays the list of the last 10 trips.
For each trip, the following indications are recorded and displayed: ETV2I ETV5S ETV6G
b the tripping cause: Ir, Isd, Ii, Ig or Auto-protection (Ap) trips
b the date and time of the trip (requires communication option in order to set Long-time current setting Ir Select the "Settings"
DB119483
menu. A
date and time).
The Ir value is
Example 1: Display for the rst (most recent) trip of the ve trips recorded in the
displayed rst.
trip history.
Ir: tripping cause.
: symbol indicating trip history display
DB126489
Long-time tripping delay tr Press the "arrow" button
1: trip number (1 being the most
to go on to the tr value.
recent)
5: total number of trips recorded. S
Example 2: Display for the ninth trip of the ten trips recorded in the trip history.
Short-time pick-up Isd Press the "arrow"
Ii: tripping cause.
button to go on to the A
: symbol indicating trip history display
DB126490
short-time Isd value.
9: trip number (1 being the most
recent)
10: total number of trips recorded.
or
Ig trip Ground-fault protection
Earth-leakage pick-up I∆n the I∆n value.
A
Δ
Ap trip Auto-protection
In this example, date is January third 2011 and time is 12 h 34 min and 56 s.
k 4.8
Number of kbits exchanged per second (kbauds on the
Baud rate XX.X 19.2 (kb) 9.6
Modbus network).
19.2 Simultaneously press and hold (four seconds) the "menu" and "arrow" buttons to
access the rst communication settings screen. The present value is displayed. A
Used for error checking based on the number of bits in the E (Even) closed padlock icon indicates that the setting is locked.
Parity E or n E
transmitted data group. n (None)
Unlocking and accessing the setting to be changed (fashing)
W
Type of Modbus connection: 4 menu
Modbus connection 4 or ULP 4
4-wire (4) or 2-wire + ULP (ULP) ULP
Measurement settings
Interval (window) Min MW
5 to 60
for demand power Period of time over which the demand power is calculated. XX 15 (minutes) (in 1 minute Press the "Quick View" button to open the padlock. The setting to be changed (or
calculation steps) the rst digit) will ash, indicating that it is ready to be modied.
Min A
Interval (window) 5 to 60
for demand current Period of time over which the demand current is calculated. XX 15 (minutes) (in 1 minute
calculation steps) Selecting the new setting
Type of network menu
b Setting 43 = 4-wire (3ph+N) and 3-pole CB (3 CTs) (3) 43
(3-wire or 4-wire)
b Setting 44 = 4-wire (3ph+N) and 4-pole CB (4 CTs) 44
and number of XX 43
or 3-pole CB (3 CTs) + external CT
circuit breaker poles
b Setting 33 = 3-wire (3ph) and 3-pole CB (3 CTs) (4) 33
(CTs).
By default, the ETV considers power owing into the circuit
+ Press the "Quick View" button to select the new setting.
Power sign breaker via the top terminals to loads connected to the bottom + or -- +
-- The possible settings are scrolled in a loop. Each press increments to the next
terminals as positive (top fed).
setting or choices in the loop.
Quick View display
Duration of display of each screen in Quick View mode 2 (s) s 1 to 9
duration
Conrming and locking the new setting
Output settings for ETV with optional M2C contacts
menu
Two outputs are available via the 2 optional M2C contacts:
Out 1
Output b Out 1 and Out 2.
Out 2
Setting possibilities are the same for both.
Not assigned
Various events can be assigned to each output: Press the "arrow" button to conrm the new setting. It stops ashing and a closed
b 3 trip events: Ir trip padlock is displayed.
v tripping caused by Ir Isd (includes
Event assigned to v tripping caused by Isd or Ii Ii) trip
the output v tripping caused by Ig (ETV6G) For a two-digit setting, this operation sets the rst digit and the second digit
Ig trip (6.0 E) ashes to indicate it is ready to be modied. Proceed as above to change it, then
b 2 pre-alarm events: Ar
v Ir pre-alarm Ir pre-alarm press the "menu" button to validate the new two-digit setting. It stops ashing,
Ar and a closed padlock is displayed.
v Ig pre-alarm (ETV6G) Ig pre-alarm
(6.0 E)
The output state (normally "0") can be controlled in three ways: menu
Forced to 1
b forced to 1 (for testing)
Output state b forced to 0 (for testing) Forced to 0
b changed from 0 to 1 (without latching) on occurrence of the Normal mode
assigned event (normal mode) (no latching)
(1) When the communication option is used, the communication parameters must be set. The communication module should be set up only when installed. Press the "arrow" button to go to the screen for the next parameter in the
Modifcation o a parameter on a system already in operation may lead to communication aults. (2) Note than all the deault screens include a closed padlock icon
communication settings branch.To go to the next branch (measurement settings),
. This means the value is protected. You must open the padlock to modiy the settings and close the padlock ater your modifcation in order to protect the
new value. The procedure is described on the next page. (3) Important: or 3-pole circuit breakers used on 4-wire systems (3ph + N), terminal VN on the Trip press the "menu" button.
system control unit must always be connected to the neutral. I this is not done, the phase-to-neutral voltage measurements can be erroneous. (4) Important: or
3-pole circuit breakers used on 3-wire systems (neutral not distributed), always set this value to 63 (see below) to avoid indications o a meaningless phase-to- Note: Within a given branch, the various parameters are organised in a loop. You must scroll
neutral voltage. through all the parameters o the branch using the "arrow" button to return to the same
parameter.To proceed to the next set-up branch (or exit the last branch), press the "menu"
button.
Example 1: Setting the Modbus address Example 2 : Setting Output 1 (for ETV with optional
M2C contacts)
The Modbus address is a two-digit number identifying the ETV in a Modbus
network. The state of output 1 can be associated with the occurrence of a given trip event.
Ar
k
menu
menu
DB127112
DB127029
Access the Output 1 setting Unlock and access the setting Modify the trip event assigned Conrm and lock the trip event
Access the existing Modbus Unlock and access the rst Modiy the rst digit Conrm the rst digit and screen to Output 1 setting
address digit (fashing) access the second digit
(fashing)
DB127113
DB127130
DB127131
DB127132
Ar
DB127030
DB127034
DB127035
DB127036
100 % 100 % 100 % 100 %
Simultaneously press the menu Press the button to open Press the button repeatedly Press the button to conrm
and the buttons for four the padlock. The existing until the desired trip event is and lock the new setting. The
menu
Simultaneously press the Press the button to open Press the button repeatedly Briey press the button to seconds to access the Modbus setting will ash, indicating it is displayed. You can scroll setting stops ashing and a
and the buttons for four the padlock and display the rst until the new value for the rst display the second digit. The address screen. Then press the ready to be modied through all possible events in a closed padlock is displayed.
menu
seconds to access the address digit (e.g. 4). It will ash, digit is displayed. You can scroll digit will stop ashing and the button to access the output loop (see list of possible events
setting screen. indicating it is ready to be through all possible values in a second digit will start ashing, setting screen. page 62).
The existing address is modied. loop (1). indicating it is ready to be The existing output setting is
displayed (default address 47 modied. displayed (default setting is
or XX). A closed padlock icon indicating that no trip event has
indicates that the value is been assigned to the output). A
locked. closed padlock icon indicates
that the setting is locked.
Modify the second digit Conrm and lock the new Display next setting screen Modify the output state control mode Conrm and lock the Output 1 Display next setting screen
state setting
setting (1)
DB127133
DB127134
DB404211
DB127109
DB127111
DB127110
k
Press the button repeatedly until the Press on the button to conrm Press the button again to go to
Press on the button Press the button again Briey press the button desired output state control mode is and lock the new setting. The the screen for the next parameter.
repeatedly until the new value to conrm and lock the new again to go on to the next displayed (see page 62). In normal mode, setting stops ashing and a closed
for the second digit is setting. The second digit stops parameter. the output goes from "0" to "1" (without padlock is displayed.
displayed. You can scroll ashing and a closed padlock latching) on occurrence of the assigned
through all possible values in a is displayed. event.
loop, as for the rst digit.
(1) The maximum address is 47. I you try to set a higher address, Trip System will set the
address to the maximum address o 47.
DB126379
The M2C contacts require an auxiliary power supply. The ETV control unit can be equipped with up to two M2C contacts (S1 and S2) The communication option uses a Modbus communication protocol to remotely
that can be used to activate: access the following information and functions available in the Trip Sytem control
b alarms to signal and identify tripping caused by long-time, short-time, unit:
474
484
b status indications
DB127801
instantaneous or ground-fault protection
b pre-alarms to warn of imminent tripping by ground-fault (ETV6G) or long-time b controls
protection. System
b measurements
5S Trip
ETV
b operating assistance.
It consists of an independent communication module installed behind the Trip
Contact operation Sytem control unit. This module receives and transmits information via the
The contacts can be set to change the state of ETV outputs Out1 and/or Out2
communication network. An infra-red link transmits data between the control unit
from 0 to 1 when certain events occur:
S1 S2 and the communication module.
b trip events, i.e. when the control unit is tripped by:
100 %
v long-time protection Ir
v short-time instantaneous protection Isd or Ii 40 %
Modbus communication
v ground-fault protection Ig (ETV6G only)
b pre-alarm events, i.e. when the current reaches 90 % of the following trip Modbus bus
menu
thresholds: The Modbus RS 485 (RTU protocol) system is an open bus on which
v long-time protection setting Ir communicating Modbus devices (EasyPact with Modbus EcoCOM are installed.
471
v ground-fault protection pickup Ig (ETV6G only). All types of PLCs and computers may be connected to the bus.
Wiring diagram or M2C contacts.
For details on how to assign dierent events to the contacts, see "Output settings"
Modbus communication parameters
For a EasyPact circuit breaker equipped with a Trip Sytem control unit, the
on page 62 or the example on page 65.
Modbus address, baud rate and parity are set using the keypad on the control
The communication option consists o an independent module unit.
Latching settings that fts behind the trip system control unit. The Modbus communication system is divided into four managers that secure
When the output state setting is in "Normal mode" (see page 62), the contacts are data exchange with the supervision system and the circuit-breaker actuators.
non-latching, i.e. the contact remains activated (state = 1) only as long as the The manager addresses are automatically derived from the circuit-breaker
event that caused the change of state remains present. address @xx entered via the Trip Sytem control unit (the default address is 47).
Two other output state settings are available (forced to 1 or 0) for testing needs
(see page 62). Modbus addresses
@xx Circuit-breaker manager (1 to 47)
Time delays @xx + 50 Chassis manager (51 to 97)
b Pickup: when the current exceeds the selected tripping or pre-alarm pickup @xx + 200 Measurement managers (201 to 247)
threshold, the output state changes from 0 to 1 after a xed time delay of 0.1
@xx + 100 Protection manager (101 to 147)
second.
b Dropout: when the circuit is opened by the circuit breaker or when the current
Number of devices
falls below the pre-alarm dropout threshold (see page 39), the output state
The maximum number of devices that may be connected to the Modbus bus
returns to 0 after a non-adjustable time delay of 0.1 second.
depends on the type of device (EasyPact with Modbus EcoCOM, the baud rate
Contact operating diagrams (19200 bauds is recommended), the volume of data exchanged and the desired
response time. The RS 485 physical layer oers up to 32 connection points on the
Contact operating diagram for long-time, short-time, instantaneous and ground- bus (1 master, 31 slaves).
fault protection trip alarms Each protection devices uses 1 or 2 connection points:
b a xed device requires only one connection point (communication module on
the device)
DB127847
Ir, Isd, Ii or Ig pickup tr, tsd or tg delay b A drawout or withdrawable device uses two connection points (communication
modules on the device and on the chassis).
The number of devices must never exceed 31 xed devices or 15 drawout/
withdrawable devices.
t
Bus length
Ir, Isd, Ii or Ig LED The maximum recommended length for the Modbus bus is 1200 m.
Fault-trip reset
DB413400
Pickup threshold
90 %
Dropout threshold
85 %
0.1 s 0.1 s
Pre-alarm
Data and functions available via the communication Long-time and instantaneous protection
option (ET/ETA/ETV 2I Trip System)
EasyPact circuit breakers equipped with Trip System control units and the
10 000
Communication option can be integrated in a Modbus communication
E60369A
5 000 Ir = 0.4…1 x In
environment. In this case the following information and functions are available
remotely. 2 000
ETV 1 000
Status indications 500
ON/OFF b 200
Spring charged CH b 100 tr = 0.5…24 s
Ready to close PF b
50
Fault-trip SDE b
Connected/disconnected/test position (via CE/CD/CT contacts of b 20
optional chassis communication module) 10
Measurements 5
Current t(s)
2
Instantaneous currents I1, I2, I3, IN, Ig, I∆N b Isd = 1.5…10 x Ir
1
Current maximeters: I1max, I2max, I3max, INmax, Igmax, I∆Nmax b
.5
Average current Iavg b
Current unbalance Iunbal b .2
Demand current .1
Demand currents I1, I2, I3, IN b .05
Demand current maximeters (peak demands) b .02
I1 max, I2 max, I3 max, IN max
.01
Voltage
.005
Phase-to-phase voltages V12, V23, V31 (3-wire and 4-wire b
systems) .002
Phase-to-neutral voltages V1N, V2N, V3N (4-wire systems) (1) b .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
Average voltage Vavg b
Voltage unbalance Vunbal b I / Ir
Power
Instantaneous power P, Q, S b
Demand power P, S b
Long-time, short-time and instantaneous
Demand power maximeters Pmax b protection (ET/ETA/ETV 5S Trip System)
Instantaneous power factor PF b
Energy
10 000
Total Energy Ep b 5 000 Ir = 0.4…1 x In
E60370B
E51397B
b A fault occurs at point A.
(ET/ETA/ETV 6G Trip System ) Downstream device no. 2 clears the fault and sends a signal to upstream device
10 000 no. 1, which maintains the short-time tripping delay tsd or the ground-fault tripping
Ir = 0.4…1 x In
E60370A
5 000 delay tg to which it is set.
b A fault occurs at point B.
2 000
Upstream device no. 1 detects the fault. In the absence of a signal from a
1 000 downstream device, the set time delay is not taken into account and the device
500 tr = 0.5…24 s
1 B trips according to the zero setting. If it is connected to a device further upstream, it
200
sends a signal to that device, which delays tripping according to its tsd or tg setting.
100
Note :
50 On device no. 1, the tsd and tg tripping delays must not be set to zero because this
20 would make discrimination impossible.
2
10 A
5
t(s) Isd = 1.5…10 x Ir Connections between control units
2 A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
1 2 upstream and downstream circuit breakers.
I t ON
.5 0.4 0.4 b ETA 5S, 6G
0.3 0.3 b ETV 5S, 6G
.2 0.2 0.2
0.1 2 0. 1
.1 I t OFF An interface is available for connection to previous generations of trip units.
0 0
.05
Ii = 2…15 x In . OFF (1)
.02
Caution.
.01 Wiring
If the protection function is not used on circuit breakers
.005 b maximum impedance: 2.7 Ω / 300 m
equipped for ZSI protection, a jumper must be installed
b capacity of connectors: 0.4 to 2.5 mm2
.002 to short terminals Z3, Z4 and Z5.
b wires: single or multicore
.001 If the jumper is not installed, the short-time and
b maximum length: 3000 metres
.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30 ground-fault tripping delays are set to zero, whatever
b limits to device interconnection:
x Ir x In the position of the adjustment dial. v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected to a
maximum of 10 inputs;
Terminals Z1 to Z5 correspond to the identical v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and to
Ground-fault protection indications on the circuit-breaker terminal blocks. an input ZSI - IN CR (Z4) or GF (Z5).
(ET/ETA/ETV 6G Trip System)
10 000
5 000
E71912A
E46266A
upstream 1 Z1
2 000 circuit-breaker Z2 tsd = 0.3
Ig = A…J x In (1)
1 000 1200 A max. Z3
Z4
500 Z5
200
point B
100
50
20
2 Z1
10 Z2
tsd = 0.2
5 Z3
t(s) Z4
I2t ON
2 Z5
1
point A
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
0.1 0.1
.1 I2t OFF
0 0 Z1 downstream Z1
.05 circuit-breaker
Z2 Z2
Z3 Z3
.02
Z4 Z4
.01 Z5 Z5
.005
.002
.001
.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300
I / In Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.
For information on connecting an external power b The display operates without an external power supply. Thermal memory
supply, see the electrical diagrams in the The digital display goes o if the current drops below 0.2 x In (In = rated current). The thermal memory is a means to simulate temperature rise and cooling caused
circuit-breaker catalogue. An optional 24 V DC external power supply may be used to maintain the display of by changes in the ow of current in the conductors.
currents even when the current drops below 0.2 x In.
These changes may be caused by:
b Display back-lighting is disabled in the following situations: 1. repetitive motor starting;
v current less than 1 x In on one phase; 2. loads uctuating near the protection settings;
v current less than 0.4 x In on two phases; 3. repeated circuit-breaker closing on a fault.
v current less than 0.2 x In on three phases. Control units without a thermal memory (contrary to bimetal strip thermal protection)
do not react to the above types of overloads because they do not last long enough to
b The maximeter does not operate for currents under 0.2 x In. cause tripping.
However, each overload produces a temperature rise and the cumulative eect can
b The display back-lighting and the maximeter may be maintained, whatever the lead to dangerous overheating.
current, by adding a 24 V DC external power supply. Even if an external power
supply is installed, the long-time, short-time, instantaneous and earth protection Trip System with a thermal memory record the temperature rise caused by each
functions will not use it. overload. Even very short overloads produce a temperature rise that is stored in the
memory. This information stored in the thermal memory reduces the tripping time.
PB101026-32A
ET/ETA/ETV Trip System and thermal memory
v 11 0/130, 200/240, 380/415 V AC (+10 % -15 %) All ET/ETA/ETV Trip System are equipped as standard with a thermal memory.
v 24/30, 48/60, 100/125 V DC (+20 % -20 %).
b Output voltage: 24 V DC ±5 %, 1 A. 1. for all protection functions, prior to tripping, the temperature-rise and cooling time
b Ripple < 1 %. constants are equal and depend on the tripping delay in question:
b Dielectric withstand : 3.5 kV rms between input/output, for 1 minute. a. if the tripping delay is short, the time constant is low;
b Overvoltage category: as per IEC 60947-1 cat. 4. b. if the tripping delay is long, the time constant is high.
External power supply.
2. for long-time protection, following tripping, the cooling curve is simulated by the
ET/ETA/ETV Trip System.
Closing of the circuit breaker prior to the end of the time constant (approximately 20
minutes) reduces the tripping time indicated in the tripping curves.
Following a trip, the short-time tsd tripping delay is reduced to the value of
the minimum setting for 20 seconds.
DB119377
b the demand values of phase and neutral currents,
824 814
b the demand value of the total active power.
The maximum (peak) demand current and power values are stored in the memory. 822 812
All demand values are updated once every minute. 821 811
Calculation method
Quadratic demand (thermal image)
The quadratic demand calculation model represents the conductor heat rise (thermal
image).
The heat rise created by the current I(t) over the time interval T is identical to that
created by a constant current Ith over the same interval. This current Ith represents Com UC1 UC2 UC3 M2C/UC4 SDE2/Res SDE1 MN MX1 XF PF MCH
the thermal efect o the current I(t) over the interval T. E5 E6 Z5 M1 M2 M3 F2 484/V3 184/K2 84 D2/C12 C2 A2 254 B2
Calculation of the demand value according to the thermal model must be always be E3 E4 Z3 Z4 T3 T4 VN 474/V2 182 82 C13 C3 A3 252 B3
performed on a sliding window. E1 E2 Z1 Z2 T1 T2 F1 471/V1 181/K1 81 D1/C11 C1 A1 251 B1
Note: The thermal demand value is similar to an rms value.
OF4 OF3 OF2 OF1
ETV control units use the quadratic model to calculate both demand current and 44 34 24 14
demand power. 42 32 22 12
41 31 21 11
Peak demand values
The ETV trip unit calculates:
b the maximum (peak) demand values of phase and neutral currents since the last
reset
b the maximum (peak) demand values of total active power since the last reset.
The peak demand values can be accessed and/or reset in the following ways:
b peak demand current: via the ETV control unit (see page 57) or the
Communication option (see page 68)
b peak demand power: via the Communication option (see page 68).
Fault
VN
V1
V2
V3
Stop
Close
Open
E89955
NCT
Indication contacts
Chassis contacts
Z5 84 D2 C2 A2 254 B2
E5 E6 Z5 M1 M2 M3 F2+ 484
CD3 Disconnected CE3 Connected CT3 Test
CD2 position CE2 position CT2 position
Z3 Z4 T3 T4 82 252 B3
CD1 contacts CE1 contacts CT1 contacts E3 E4 Z3 Z4 T3 T4 VN 474
Draw-out Air Circuit Breaker
Z1 Z2 T1 T2 81 D1 C1 A1 251 B1
E1 E2 Z1 Z2 T1 T2 F1 – 471
The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:
1. MVS06 to MVS 16: CT 400/1600; UV number: 33576
System
System
Trip
Trip
ET6G
ET6G
2. MVS08 to MVS 20: CT 400/2000; UV number: 34035
MVS08
N
3. MVS25 to MVS 40: CT 1000/4000; UV number: 34036
alarm
alarm 50/60H
time
time tr 8 12 60947-2
IEC
Ir
long
long
.7
(s) 4
.8 .9.95 (s)2
1
16
20
24
External sensor(CT)
.6 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
time 6
short
shorttime tsd .4 .4 .3
(s) 4 15
(s) .2
Isd 4 5 3 off
off
3 .3 .1 2
6
x In test
8
.2 2 0off
2.5 .1 I t test
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 . 3 2
(s) .4 .
E F .3 .1
Ig G
CD H
.2 0off
off
B
on.1 I 2t
I on
A fault
fault
ground
ground
MVS06-16(C) MVS08-40(N/H/T)
DB101409
open closed disconnected connected test
822
824
812
814
42
32
22
12
44
34
24
14
332
334
322
324
312
314
914
912
OF4 OF3 OF2 OF1 CT1
CD2 CD1 CE3 CE2 CE1
E60070A
E60076A
E60069A
E60068A
41
31
21
11
821
811
321
331
311
911
Indication contacts Contacts châssis
Indication contacts Chassis contacts
OF4 OF3 OF2 OF1 CD2 CD1 CE3 CE2 CE1 CT1
OF4 OF3 OF2 OF1 OF14 OF13 OF12 OF11 CD3 CD2 CD1 CE3 CE2 CE1 CT3 CT2 CT1
44 34 24 14 824 814 334 324 314 914
44 34 24 14 144 134 124 114 834 824 814 334 324 314 934 924 914
MCH
380V
Key:
CH Draw out device only
B1 Interconnected connections
Key:
(only one wire per connection point)
CN2 - 440/480 V Drawout device only
E60075A
XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard
Interconnected connections
(only one wire per connection point)
The ON/OFF indication contacts signal the status of Circuit breaker The ON/OFF indication contacts signal the status of
the device main contacts.
Circuit breaker
the device main contacts.
DB119378
completely closed completely open
E60363A
closed open main contacts
completely connected
completely disconnected
DB119379
separation of the main circuits
E60364A
test position separation of the auxiliary circuits separation of the main circuits
separation of the auxiliary circuits
completely disconnected test position completely connected
MVS06-16(C) MVS08-40(N/H/T)
E51331A
V AC 240 10A(rms) main contacts is a. 240/380 V: 10 A (rms)
380 6 A (rms) reached b. 480 V: 10 A (rms)
480 6 A (rms) 4. breaking capacity
690 3 A (rms) for DC power (DC12 as per
V DC 24/48 3A IEC60947-5-1):250 V:3A.
125 0.5 A
250 0.25 A Optional ON/OFF indication contacts(OF)
1. optional equipment, 1. OF contacts indicate 1. changeover contacts
one block of 4 OF the position of the main 2. rated current: 6 A
contacts per device contacts 3. breaking capacity 50/60 Hz
2. connection cables not 2. they trip when the for AC power (AC12 as per
E51332A
"Ready to close" contact (PF) included, see below: minimum isolation IEC60947-5-1):
b One optional PF b The contact indicates b Changeover contact one block of 4 OF distance between the a. 240/380 V: 6A (rms)
contact per device that the device may be b Breaking capacity at contacts:47887 main contacts is b . 480 V: 6 A (rms)
closed because all the cos ϕ = 0.3 (AC12 / DC12 3.connection cables: reached 4. breaking capacity
following are valid: as per IEC 60947-5-1) a. for xed device:47074 for DC power (DC12
v circuit breaker is open v standard, minimum b. for drawout IEC60947-5-1):250 V:3A.
v spring mechanism is current 10 mA / 24 V device:47849
charged V AC 240/380 5 A (rms)
v a maintained closing "Fault-trip" indication contact(SDE)
order is not present
1. standard equipment on 1. the contact provides a 1. changeover contacts
v a maintained opening
circuit breakers, one remote indication of 2. rated current: 5 A
order is not present.
SDE contact per device device opening due to 3. breaking capacity 50/60
2. not available for an electrical fault Hz for AC power (AC12
switch- disconnector as per IEC60947-5-1):
versions a. 240/380V:5A(rms)
b. 480 V: 5 A (rms)
4. breaking capacity
for DC power (DC12
as per IEC60947-5-1):
a. 48 V: 3 A
b. 125 V: 0.3 A
c. 250 V: 0.15 A.
MVS06-16(C) MVS08-40(N/H/T)
Gear motor (MCH) Gear motor (MCH)
E46790A
E51290A
b Optional accessory, b The gear motor b Operating threshold: 1. optional equipment, 1. the gear motor 1. charging time: 4
one MCH gear motor per automatically charges the 0.85 to 1.1 Un one MCH gear motor automatically charges seconds max.
device spring mechanism. b Consumption: per device and recharges the 2. consumption:
b Power supply: 180 VA or W 2. connection cables not spring mechanism a. 180 VA AC
v V AC 50/60 Hz: b Inrush current: included, see below: b. 180 W DC
-24/30V DC : 47888 3. in rush current: 2 to 3 In
- 100/130 V AC 2 to 3 In for 0.1 second -48/60V DC : 47889 for 0.1 second
- 200/240 V AC b Charging time: -100/130V DC: 47890 4. operating rate: maximum
- 380/415 V AC 3 seconds max. -200/250V DC: 47891 3 cycles per minute.
v V DC: b Operating rate: -100/130V AC: 47893
- 24/30 V DC maximum 3 cycles per -200/240V AC: 47894
-380/415V AC: 47896
- 48/60 V DC minute 3. connection cables:
- 100/125 V DC a. for xed device:4707
- 200/250 V DC b. for drawout device:47849
E51294A
E51294A
or 2 MX releases per instantaneously opens v XF: 0.85 to 1.1 Un MX per device. instantaneously opens 50ms ±10
device, 1 XF per device the circuit breaker when v MX: 0.7 to 1.1 Un breaker when energised the circuit breaker 2. operating threshold:
2. connections cables not when energised 0.7to1.1xUn
b The function (MX or energised b Consumption: included, see below. 2. the coil to be xed at 3. the supply can be
XF) is determined by b The XF release v pick-up: 200 VA or W - 24/30 V AC/DC: 33659 the dened location maintained
where the coil is installed instantaneously closes (80 ms) - 48/60 V AC/DC: 33660 only 4. consumption:
b Power supply: the circuit breaker when v hold: 4.5 VA or W - 100/130 V AC/DC: 33661 a. pick-up: 200VA/200W
v V AC 50/60 Hz: energised, if the device is b Circuit-breaker - 200/250 V AC/DC: 33662 b. hold: 4.5 VA/4.5W.
- 380/480 V AC/DC: 33664
- 24 V AC "ready to close". response time at Un: 3. connection cables:
- 48 V AC v XF: 55 ms ± 10 a. for xed device: 47074
- 100/130 VAC v MX: 50 ms ± 10. b. for drawout device:
- 200/250 V AC 47849
- 380/480 V AC
v V DC: Closing release(XF)
- 24/30 V DC 1.optional equipment, 1 1. the XF release 1. device response time:
E51294A
- 48/60 V DC XF per device. instantaneously closes 70ms+10/-15
- 100/130 V DC 2. connections cables not the circuit breaker 2. operating threshold:
included, see below. when energised, if 0.85 to 1.1xUn
- 200/250 V DC - 24/30 V AC/DC: 33659 the device is "ready to 3. the supply can be
- 48/60 V AC/DC: 33660 close". maintained
- 100/130 V AC/DC: 2. the coil to be xed at 4. consumption:
Instantaneous undervoltage releases (MN) MVS15511 the dened location a. pick-up:
E51294A
- 200/250 V AC/DC: only. 200VA/200W
b Optional accessory, b The MN release b Device response time: MVS15512 b. hold: 4.5 VA/4.5W.
1 MN per device instantaneously opens 90 ms ±5 - 380/480 V AC/DC:
b Power supply : the circuit breaker when b Operating threshold: MVS15513
v V AC 50/60 Hz: its supply voltage drops. v opening: 3. connection cables:
- 24 V AC 0.35 to 0.7 x Un a. for xed device:47074
b. for drawout device:
- 48 V AC v closing: 0.85 x Un 47849
- 100 / 130 V AC b Consumption:
- 200 / 250 V AC v pick-up (80 ms): Instantaneous undervoltage releases(MN)
- 380 / 480 V AC 200 VA
v V DC: v hold: 4.5 VA. 1. optional equipment, 1 1. the MN release 1. device response time:
MN per device instantaneously opens 90 ms±5
E51294A
E51296A
4 5
6 per device. release to eliminate b Operating threshold: 1. optional equipment, 1 1. the unit delays operation 1.device response time
2 3
1
b Delay-unit (must be circuit-breaker nuisance v opening: MN with delay unit per of the MN release to (adjustable type):
device. eliminate circuit-breaker 0.5s-0.9s-1.5s-3s
ordered in addition to the tripping during short 0.35 to 0.7 x Un 6 2. delay-unit (must be ordered nuisance tripping during 2. operating threshold:
3 4 5
S 1 2
E51296A
3 6
1
MN): voltage dips v closing: 0.85 x Un in addition to the MN): short voltage dips a. opening: 0.35 to 0.7 x Un
0.5
MN 1.5
3
UVR de MN v 48/60 V AC b The unit is wired in b Consumption: a. 48/60 V AC/DC 2. the unit is wired in series b. closing:0.85xUn
ateurfor UVR
0 V Retard
delay
100/13 Time
AC/DC
1012
50/60 Hz / DC series with the MN and v pick-up (80 ms): S
b. 100/130V AC/DC with the MN and must be 3. consumption:
3 6
1
0.5 c. 200/250V AC/DC installed outside the a. pick-up: 200VA/200W
2 3 v 100/130 V AC must be installed outside 200 VA MN 1.5
1 3
UVR de MN
ateurfor UVR d. 380/480V AC/DC circuit breaker b. hold: 4.5 VA/4.5W
0 V Retard
delay
50/60 Hz / DC the circuit breaker. v hold: 4.5 VA. 100/13 Time
AC/DC
1012
MVS06-16(C) MVS08-40(N/H/T)
E60499A
E46120A
b Optional accessory, b The CDP increases the standard equipment, one Escutcheon 1. the Escutcheon increases the
one CDP per device degree of protection to IP per device degree of protection to IP 40 and
v or xed device 40 and IK 07 (xed and a. for xed device:48601 IK 07 (xed and drawout
b. for drawout device:48603 devices).
v for drawout device. drawout devices).
Transparent cover(CP)
E46118A
Transparent cover (CCP) optional equipment, one Transparent 1. mounted with a Escutcheon, the
E60497A
cover per device equipped with a Transparent cover increases the
b Optional accessory, b Mounted with a CDP, Escutcheon (only for drawout degree of protection to IP 55 and
one CCP per device the CCP increases the devices:48604) IK 10 (only for drawout devices).
equipped with a CDP degree of protection to
IP 54 and IK 10 (xed and
drawout devices).
E46670
Blanking plate (OP) Escutcheon (only for drawout a cubicle not yet equipped with a
E60498A
devices:48605) device.
b Optional accessory, b Used with the
one OP per device escutcheon, this option
closes of the door
cut-out of a cubicle not
yet equipped with a Blankingplate
device. It may be used
with the escutcheon for
both xed and drawout
devices.
Transparent cover for pushbutton locking(VBP)
1. optional equipment, one locking 1. the transparent cover blocks
E46238A
cover per device:48536 access (together or separately)
to the push buttons used to open
and close the device
Transparent cover for pushbutton locking using a 2. locking requires a padlock, a
E60347A
lead seal or two screws.
padlock, lead seal or screws
b Optional accessory, b The transparent cover
one locking cover per blocks access (together
device or separately) to the
pushbuttons used to open
and close the device Device OFF position locking kit for keylocks(VSPO)
b Locking requires a
1. optional equipment, 1. the kit inhibits local or remote
padlock, a lead seal or 2. one locking kit per device. (key locks closing of the device.
two screws. not included. Common for Rois/
Profalux type keylocks)
3. part number: 64925
Device OFF position locking kit for keylocks
b Optional accessory: b The kit inhibits local or
one locking kit (without remote closing of the
keylock) per device device
b Locks not included: b Mounted on the
v for Profalux keylocks chassis and accessible
v for Ronis keylocks with the door closed, this
System
System
Trip
Trip
ET6G
system locks the circuit ET6G
v for Castell keylocks
v for Kirk keylocks. breaker in "disconnected" PROFALUX MVS08
N
.1 I t
2 10 on
on
delay
1.5 Ir
x
setting tg
(s) .4 .3 2
.
Note: Knock-out provision Ig D
E F
G
(s) .4
.3
.2
.1
0off
off
C H 2
B
on.1 I t
I on
A fault
fault
ground
ground
locking kit:
E51286A
b One keylock per
device, Ronis or Profalux RONIS Keylocks required for the device locking kit
type. 1. a. one key lock for locking kit. 2. a. two keylocks* with same prole.
b Adaptation kits alone b. part number: b. part number:
E51270A
Profalux
are available for Castell i). Profalux:42888 i). Profalux:42878
and Kirk keylocks. ii). Ronis:41940 ii). Ronis:41950
* one keylock mounted on the device
DB119180
+one keylock supplied separately for
interlocking another device.
E60011A
b Standard accessories, b The safety shutters b IP 20 for chassis b Optional accessory, b This device inhibits b It may be mounted on
E60030A
E60031A
provided on every automatically block the connections one door interlock per opening of the cubicle the left or right-hand side
chassis. access to the b IP 40 for the chassis door when the circuit of the chassis.
disconnecting contact disconnecting contact breaker is in "connected"
O OFF
push
"test" positions.
I specied when ordering the chassis, this locking Chassis breaker locking in "disconnected" position
function may be adapted to operate in all positions
b Optional accessory, b Mounted on the
E51498A
("connected", "test" and "disconnected"), instead of in
Racking interlock
one locking system per chassis and accessible b It is mounted on the
"disconnected" position alone. b Optional accessory, b This device prevents
device with the door closed, this right-hand side of the
one racking interlock per insertion of the racking
v for Profalux or Ronis system locks the chassis chassis.
chassis handle when the cubicle
keylocks in "disconnected" position
door is open.
v for Castell keylocks using one or two
v for Kirk keylocks. keylocks.
Mismatch protection
E59190A
b Optional accessory, b Mismatch protection
one mismatch protection ofers twenty diferent
device per chassis combinations that the
Ronis user may select to ensure
Keylocks required with the "disconnected" position that only a compatible
locking system circuit breaker is mounted
E51286A
E51273A
b One or two keylocks on a given chassis.
per locking system
v Ronis:
1 keylock
1 keylock + one identical Auxiliary terminal shield (CB)
E60345A
keylock
b Optional accessory, b The shield prevents
2 diferent key locks
one CB shield per chassis access to the terminal
Profalux v Profalux:
block of the electrical
1 keylock
auxiliaries.
1 keylock + one identical
DB119180
DB119191
keylock
2 diferent key locks.
b Adaptation kits alone
"Connected", "disconnected" and "test" position
E46095A
are available for Kirk and carriage switches (CE, CD, CT)
Castell keylocks.
b Optional accessories, b The carriage switches b Changeover contact
one to six carriage indicate the three b Breaking capacity at
switches positions: cos ϕ = 0.3 (AC12 / DC12
b Standard conguration, CE: connected position as per IEC 60947-5-1)
0 to 3 CE, 0 to 2 CD, CD: disconnected v standard, minimum
0 to 1 CT position (when the current 10 mA / 24 V
minimum isolation V AC 240 8 A (rms)
distance between the 380 8 A (rms)
main contacts and the
auxiliary contacts is
reached)
CT: test position.
E46652A
1. optional equipment, 1. this device inhibits 1. it may be mounted on carriage switches (CE, CD, CT)
one door interlock per opening of the cubicle the left or right-hand
chassis door when the circuit side of the chassis. 1. optional equipment, 1. the carriage switches 1. changeover contact
2. part number:47914 breaker is one to nine carriage indicate the three 2. rated current: 8 A
E46095A
in"connected" switches positions: 3. breaking capacity
or "test" position Standard conguration, CE: connected position 50/60 Hz for AC power
0 to 3 CE, 0 to 3 CD, CD: disconnected (AC12 as per
0 to 3 CT position (when the IEC60947-5-1):
2. part number minimum isolation 240 V: 8 A (rms)
(connection cables not distance between the 380 V/415 V: 8 A (rms)
included) main contacts and the 4. breaking capacity for
a. 1 carriage switch auxiliary contacts is DC power
33170 reached) (DC12 asper
CT: test position(in this IEC60947-5-1):
position, the power 125 V: 0.8 A.
circuits are
Circuit breaker locking in "disconnected" disconnected and the
auxialiary circuits are
E46561A
position(VSPD)
connected)
1. optional equipment, one 1. mounted on the chassis and
2. function dened based
locking kit per device for accessible with the door closed,this
on the location in
Profalux or Ronis system locks the circuit breaker in
chassis.
keylocks(not included) "disconnected" position using one
2. part number:48564 keylock
3. key locks to be ordered 2. the "disconnected" position locking
E51351A
Auxiliary terminal shield(CB)
separately. system may be modied to lock the
circuit breaker in all three positions. 1. optional equipment, 1. the shield prevents
one shield per chassis access to the terminal
2. part number: block of the electrical
3 pole:64942 auxiliaries.
4 pole:48596
Profalux Ronis Keylocks required with the "disconnected"
Top shutter closed
position locking system
E51334A
1. a. one lock for locking system 2. a. two keylocks with same prole.
E51287A
E51286A
b. part number: b. part number: Safety shutters(VO)
i). Profalux: 42888 i). Profalux: 42878
1. standard equipment 1. mounted on the 1. IP20.
ii). Ronis: 41940 ii). Ronis: 41950
2. set of shutters for top chassis, the safety
* one keylock mounted on the device
and bottom: shutters automatically
+one keylock supplied separately for
a. MVS08/MVS40 block access to the
interlocking another device.
Bottom shutter closed 3 poles disconnecting contact
4 poles cluster when the device
b. part number: is in the "disconnected"
3 poles: 48721 or "test" positions.
Operation counter(CDM) 4 poles: 48723
DB101115
1. optional equipment, per device
The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible with manual and electrical control functions.
This option is compulsory for all the source-changeover systems.
2. part number: : 48535
Shutter locking blocks
E46293A
DB101386
External sensor for earth-fault protection
the closed position.
The sensors, used with the 3P circuit breakers, are installed on the neutral
conductor for:
1. residual type earth-fault protection (with ET/ETA/ETV 6G Trip System)
The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:
E46428
These operations must be carried out in particular A general check of the circuit breaker takes only a few minutes and avoids any risk Note the fault
before using a EasyPact MVS device for the rst time. of mistakes due to errors or negligence. Faults are signalled locally and remotely by the indicators and auxiliary contacts
A general check must be carried out: installed on circuit breakers (depending on each conguration). See page 13 in
1. prior to initial use this manual.
2. following an extended period during which the circuit breaker is not used.
Operation
Check the mechanical operation of the circuit breakers:
1. opening of contacts
2. closing of contacts.
* Make sure that XF (closing coil) & MX (opening coil) are installed at the right locations.
Avoid installation of XF release at MX position. Failure to follow the instruction of
MN-MX-XF can not keep the circuit breaker at OFF position by remote control that
resulting equipment damage or risk of life.
Recommended program for devices used under normal Periodic inspections required Before undertaking any maintenance work, de-energise Arc chutes MVS 06-16 (C)
operating conditions: the installation and t locks or warnings in compliance
Interval Operations Procedure 1. remove the 2 xing screws:
Ambient temperature: -5° C / +60°C Normal atmosphere with all applicable safety standards.
each year 1. open and close the device see pages 12 and 13
locally and remotely,
successively using
E51280A
E51275AA
the various auxiliaries
2. test the operating see page 10
sequences
3. test ET/ETA/ETV Trip System see page 36
using the mini test kit
every two years 1. check the arc chutes see page 95
2. check the main contacts see page 95
3. check the see page 96
disconnecting-contact 2. check the arc chutes:
clusters chamber not cracked separators not corroded.
4. check the tightness of see the device
connections(50 N.m) installation manual If necessary, replace the arc chutes.
E51275AA
Support
MCH gear motor 1. user see page 11.
mechanical 1. user see Mechanical
interlocks interlocking manual.
connecting-rod 1. Schneider After Sales
springs Support
MX/MN/XF 1. user see pages 12, 13.
Part replacement must be programmed on the basis of the data below, listing the 2. check the arc chutes:
service life of the various parts in numbers of O/C cycles at the rated current. chamber not cracked separators not corroded.
* the service life of arc chutes & main contacts are at an operational voltage of 440V AC.
MVS06-16(C)
Rating Type MVS06 MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40
C layout no1 layout no1 layout no1 layout no1 layout no6
N layout no2 layout no2 layout no2 layout no2 layout no2 layout no3 layout no4 layout no5
H layout no2 layout no2 layout no2 layout no2 layout no2 layout no2 layout no4 layout no5
CA layout no1 layout no1 layout no1 layout no1 layout no6
Front
NA layout no2 layout no2 layout no2 layout no2 layout no2 layout no3 layout no4 layout no5 b 1 per 3- or 4- pole device.
HA layout no2 layout no2 layout no2 layout no2 layout no2 layout no2 layout no4 layout no5
E51325B
E51326B
Charging handle
b 1 per device.
E51327B
Crank
CDB500033
b 1 per device.
Disconnectiong-contact clusters
b number per circuit breaker, see table page 96.
MVS08-40(N/H/T)
Electrical accessories
The electrical accessories that may require replacement are the following: Problem Problem Problem
1. MCH gear motor
2. MX opening release circuit breaker cannot be closed locally or remotely 1. circuit breaker padlocked or keylocked in a. disable the locking function
3. XF closing release the "open" position
4. MN under voltage release.
2. circuit breaker interlocked mechanically a. check the position of the other circuit
See page 85 in the "Auxiliaries for remote operation" section for their characteristics in a source changeover system breaker in the changeover system
and part numbers. b. modify the situation to release the interlock
Arc chutes 3. circuit breaker not completely connected a. terminate racking in (connection) of the
E51335A
1. arc chute: MVS08-40 1. 3 or 4 chutes per circuit breaker circuit breaker
part number:MVS21807
4. the reset button signalling a fault trip has a. clear the fault
not been reset b. push the reset button on the front of the
circuit breaker
E46237A
1. cluster : 1. number per circuit order must be cancelled before the circuit
part number:33166 breaker, see table page 96. breaker can be closed
7. MN under voltage release not supplied a. there is an opening order. Determine the
with power origin of the order.
b. check the voltage and the supply
circuit (U > 0.85 Un). If the problem
persists,replace the release
8. XF closing release continuously supplied a. cut the supply of power to the XF closing
with power,but circuit breaker not "ready release, then send the closing order again
to close" (XF not wired in series with PF via the XF, but only if the circuit breaker is
contact) "ready to close"
E46109A
Front cover with knock-out provision for key
lock(standard) circuit breaker cannot be closed remotely but can be 1. closing order not executed by the XF a. check the voltage and the supply circuit
System
Trip System
ET6G
ET6G
Trip
closed locally using the closing pushbutton on breaker closing release (0.85-1.1Un). lf the problem persists,
1.front cover for 3-or 4 1.one per device.
replace the XF release
MVS08
N
poles devices.
alarm
alarm
long time
long time tr 8 12
(s) 4 16
Ir .8 .9.95 (s)
2 20
.6.7
.5
.4 x In
1
.98
1 24
.5 at 6 Ir
Ir instantaneous
instantaneous
50/60H
part number:
Ii 8 1012 IEC 60947-2
time 6
short
shorttime tsd .4 .3
(s)
(s) .4 4
Isd 4 5 .2 15
3 .3 3 off
off
6 .1
2
2.5 8 .2 x In
2 .1 2t 0off test
test
1.5
x Ir
setting
10 on
tg
on I
(s)
delay
. 4 .3
unexpected tripping without activation of the reset 1. MN undervoltage release supply voltage a. check the voltage and the supply circuit
(s) .4 .2
Ig E F
G
.3 .1
CD H .2 0off
off
B I
on.1 I2t
A on
fault
ground fault
ground
MVS21808
button signalling a fault trip too low (U> 0.85 Un)
2. load-shedding order sent to the MX a. check the overall load on the distribution
opening release by another device system
b. if necessary, modify the settings of
Charging handle devices in the installation
E46126A
3. unnecessary opening order from the MX a. determine the origin of the order
1. Manual operating 1. one handle per device. opening release
spring charging handle.
part number: 47940 unexpected tripping with activation of the reset button 1. overload a. determine and clear the causes of the
signalling a fault trip 2. earth fault fault
3. short-circuit detected by Trip unit b. check the condition of the circuit breaker
before putting it back into service
instantaneous opening after each attempt to close 1. thermal memory a. refer to page no.34-35
the circuit breaker with activation of the reset
button signalling a fault trip of this user manual.
2. transient over current when closing b. press the reset button
E51336A
a. modify the distribution system or the Trip
Crank unit settings.
1.crank per device. 1.one per device. b. check the condition of the circuit breaker
part number:47944 before putting it back into service
3. closing on a short-circuit c. press the reset button
a. clear the fault
b. check the condition of the circuit breaker
before putting it back into service
c. press the reset button
Ambient temperature
E51260B
Problem Probable causes Solutions
EasyPact MVS devices can operate under the following temperature
conditions:
circuit breaker cannot be opened remotely, but can 1. opening order not executed by the MX check the voltage and the supply circuit 1. the electrical and mechanical characteristics are stipulated for an ambient
be opened locally opening release (0.7-1.1Un). temperature of -5°C to +60°C
If the problem persists, replace the MX 2. circuit-breaker closing is guaranteed down to -35°C
release ET6G
ET6G
Trip
System
Trip
System
3. EasyPact MVS (without Trip System) can be stored in an ambient temperature of
N
MVS08
-40°C to +85°C
alarm
alarm 50/60H
time
time tr 8 12 60947-2
long
long IEC
(s) 4
(s) 16
Ir .8 .9.95 2 20
1 24
.6.7 .98 instantaneous
instantaneous
.5 at 6IrIr
.5 1
.4 x In Ii 8 1012
time 6
short (s) 4 15
shorttime tsd .4 .4 .3
(s) .2
Isd 4 5 3 off
off
3 .3 .1 2
6
. 2 x In test
2.5 8 .1 2
0off
test
I t
2 10 on
on
1.5 Ir delay
x
setting tg
(s) . 4 . 3 .2
(s) .4
E F
Ig G
.3 .1
CD
.2 0off
off
H
B
on.1 I2t
I on
A
2. opening order not executed by the MN drop in voltage insucient or residual voltage ground
fault
fault
ground
4. the Trip System can be stored in an ambient temperature of -25°C to +85°C.
undervoltage release (U<0.35Un) across the terminals of the
undervoltage release. lf the problem persists,
replace the MN release
circuit breaker can not be opened locally 1. operating mechanism malfunction or contact a Schneider service centre
welded contacts
circuit breaker can not be reset locally 1. insucient supply voltage for the MCH check the voltage and the supply circuit
gear motor (0.85 - 1.1 Un).
If the problem persists, replace the MCH Electromagnetic disturbances
release EasyPact MVS devices are protected against:
E51264B
1. overvoltages caused by devices that generate electromagnetic disturbances
nuisance tripping of the circuit breaker with 1. reset button not pushed-in completely push the reset button in completely 2. overvoltages caused by an atmospheric disturbances or by a distribution-system
activation of the reset button signalling a fault trip outage (e.g. failure of a lighting system)
3. devices emitting radio waves (radios, walkie-talkies, radar, etc.)
impossible to insert the crank in connected, test or 1. a padlock or keylock is present on the disable the locking function 4. electrostatic discharges produced by users.
disconnected position chassis or a door interlock is present Trip
System
System
ET6G Trip
ET6G
N
MVS08
EasyPact MVS devices have successfully passed the electromagnetic-compatibility
alarm
alarm 50/60H
time
time tr 8 12 60947-2
long
long IEC
(s) 4
(s) 16
Ir .8 .9.95 2 20
1 24
.6.7 .98 instantaneous
instantaneous
.5 at 6IrIr
.5 1
.4 x In Ii 8 1012
time 6
short (s) 4 15
shorttime tsd .4 .4 .3
(s) .2
Isd 4 5 3 off
off
3 .3 .1 2
6
. 2 x In test
2.5 8 .1 2
0off
test
I t
2 10 on
on
1.5 Ir delay
x
setting tg
(s) . 4 . 3 .2
(s) .4
impossible to turn the crank 1. the position release button has not been press the position release button Ig
CD
B
A
E F
I
G
H
fault
.3
.2
on.1 I2t
on
.1
0off
off
tests (EMC) dened by the following international standards:
groundfault
ground
circuit breaker cannot be removed from chassis 1. circuit breaker not in disconnected turn the crank until the circuit breaker is in The above tests guarantee that:
position disconnected position and the position 1. no nuisance tripping occurs
release button is popped-out. 2. tripping times are respected.
2. the rails are not completely out pull the rails all the way out
circuit breaker cannot be connected (racked in) 1. the safety shutters are locked remove the lock(s)
2. the disconnecting-contact clusters are reposition the clusters
incorrectly positioned
3. chassis locked in disconnected position disable the chassis locking function
4. the position release button has not been press the position release button
Cleaning
1. non-metallic parts:
pressed, preventing rotation of the crank
never use solvent, soap or any other cleaning product. Clean with a dry cloth only
5. the circuit breaker has not been insert the circuit breaker completely so that
2. metal parts:
suciently inserted in the chassis it is engaged in the racking mechanism
clean with a dry cloth whenever possible. If solvent, soap or any other cleaning
product must be used, make sure that it does not come into contact with non-
circuit breaker cannot be locked in disconnected 1. the circuit breaker is not in the right check the circuit breaker position by
metallic parts.
position position making sure the position release button is
popped-out.
2. the crank is still in the chassis remove the crank and store it
circuit breaker cannot be locked in connected, test 1. check that locking in any position is contact a Schneider service centre
or disconnected posttion enabled
2. the circuit breaker is not in the right check the circuit breaker position by
position making sure the position release button is
popped-out.
3. the crank is still in the chassis remove the crank and store it
the crank cannot be inserted to connect or 1. the rails are not completely in push the rails all the way in
disconnected the circuit breaker
the right-hand rail (chassis alone) or the circuit 1. the crank is still in the chassis remove the crank and store it
breaker cannot be drawn out
Schneider Electric Industries SAS As standards, specications and designs change from time to time, please ask for conrmation
35, rue Joseph Monier of the information given in this publication.
CS 30323
92506 Rueil Malmaison Cedex This document has been printed on ecological paper
France
Design: Schneider Electric
Photos: Schneider Electric
RCS Nanterre 954 503 439
Printed: MVS21734
Capital social 928 298 512 €
www.se.com
07-2023